Smart Motor Controllers -- SMC PLUS

Product Selection Open Type Controllers

Up to 480V AC

kW Current Rating (A) 24 35 54 97 135 180 240 360 500 650 720 850 1000 230V AC 50 Hz 5.5 10 15 25 37 51 75 110 150 200 220 257 315 400V AC 50 Hz 11 18.5 22 45 75 90 132 200 257 355 400 475 530 200V AC 60 Hz 1...5 1...10 1...15 5...30 5...40 5...60 5...75 5...125 5...150 5...200 5...250 10...300 10...350 HP 230V AC 60 Hz 1...7.5 1...10 1...20 5...30 5...50 5...60 5...75 5...150 5...200 5...250 5...300 10...350 10...400 460V AC 60 Hz 1...15 1...25 1...40 5...75 5...100 5...150 5...200 5...300 5...400 5...500 5...600 10...700 10...800 Cat. No. 150-A24NBD 150-A35NBD 150-A54NBD 150-A97NBD 150-A135NBD 150-A180NBD 150-A240NBD 150-A360NBD 150-A500NBD 150-A650NBD 150-A720NBD 150-A850NBD 150-A1000NBD

Bulletin 150

Price Adder Code a b c d e f g h i j k l m

Up to 600V AC

kW Current Rating (A) 24 35 54 97 135 180 240 360 500 650 720 850 1000 HP Cat. No. 150-A24NCD 150-A35NCD 150-A54NCD 150-A97NCD 150-A135NCD 150-A180NCD 150-A240NCD 150-A360NCD 150-A500NCD 150-A650NCD 150-A720NCD 150-A850NCD 150-A1000NCD

230V AC 50 400V AC 50 500V AC 50 200V AC 60 230V AC 60 460V AC 60 575V AC 60 Hz Hz Hz Hz Hz Hz Hz 5.5 10 15 25 37 51 75 110 150 200 220 257 315 11 18.5 22 45 75 90 132 200 257 355 400 475 530 15 22 37 63 90 132 160 250 355 475 500 600 710 1...5 1...10 1...15 5...30 5...40 5...60 5...75 5...125 5...150 5...200 5...250 10...300 10...350 1...7.5 1...10 1...20 5...30 5...50 5...60 5...75 5...150 5...200 5...250 5...300 10...350 10...400 1...15 1...25 1...40 5...75 5...100 5...150 5...200 5...300 5...400 5...500 5...600 10...700 10...800 1...20 1...30 1...50 5...75 5...125 5...150 5...250 5...350 5...500 5...600 5...700 10...800 10...1000

Price Adder Code a b c d e f g h i j k l m

The minimum rating is: 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97...720 A; 7.5 kW for devices rated 850 A and greater. HP ratings at motor terminal voltages for 208, 480 and 600 line volts, respectively. Controllers are shipped from the factory preset for soft start mode, 10 s acceleration, energy saver inactive, motor stall inactive, and control power 100...240V AC, 50/60 Hz.

Accessories -- Page 49 Options -- Page 50 Specifications -- Page 57 Approximate Dimensions -- Page 59

43

Bulletin 150

Smart Motor Controllers -- SMC PLUS

Product Selection, Continued IP30 (Type 1) Enclosed Non-Combination Controllers

SMC Easy Ship program Cat. Nos. are printed in blue. See page 39.

Bulletin 150 (Non-Combination Controller) -- The SMC PLUS Controller requires a separate 100...240V, 50/60 Hz single-phase control source. A thermal overload is not included. Terminals are provided for a separate thermal overload relay connection to the control circuit. Enclosures other than those listed are available. Consult Allen-Bradley Sales Office. Up to 480V AC

kW Current Rating (A) 24 35 54 97 135 180 240 360 500 650 720 850 1000 230V AC 50 Hz 5.5 10 15 25 37 51 75 110 150 200 220 257 315 400V AC 50 Hz 11 15 22 45 55 90 110 200 250 355 400 450 500 200V AC 60 Hz 1...5 1...10 1...15 5...30 5...40 5...60 5...75 5...125 5...150 5...200 5...250 10...300 10...350 HP 230V AC 60 Hz 1...7.5 1...10 1...20 5...30 5...50 5...60 5...75 5...150 5...200 5...250 5...300 10...350 10...400 460V AC 60 Hz 1...15 1...25 1...40 5...75 5...100 5...150 5...200 5...300 5...400 5...500 5...600 10...700 10...800 Cat. No. 150-A24JBD 150-A35JBD 150-A54JBD 150-A97BBD 150-A135BBD 150-A180BBD 150-A240BBD 150-A360BBD 150-A500BBD 150-A650BBD 150-A720BBD 150-A850BBD 150-A1000BBD Dimension Code Q Q Q R T T T U W X X X X

Price Adder Code a b c d e f g h i j k l m

Up to 600V AC

kW 230V AC 50 Hz 5.5 10 15 25 37 51 75 110 150 200 220 257 315 400V AC 50 Hz 11 18.5 22 45 75 90 132 200 257 355 400 475 530 500V AC 50 Hz 15 22 37 63 90 132 160 250 355 475 500 600 710 200V AC 60 Hz 1...5 1...10 1...15 5...30 5...40 5...60 5...75 5...125 5...150 5...200 5...250 10...300 10...350 HP 230V AC 60 Hz 1...7.5 1...10 1...20 5...30 5...50 5...60 5...75 5...150 5...200 5...250 5...300 10...350 10...400 460V AC 60 Hz 1...15 1...25 1...40 5...75 5...100 5...150 5...200 5...300 5...400 5...500 5...600 10...700 10...800 575V AC 60 Hz 1...20 1...30 1...50 5...75 5...125 5...150 5...250 5...350 5...500 5...600 5...700 10...800 10...1000 Cat. No. 150-A24JCD 150-A35JCD 150-A54JCD 150-A97BCD 150-A135BCD 150-A180BCD 150-A240BCD 150-A360BCD 150-A500BCD 150-A650BCD 150-A720BCD 150-A850BCD 150-A1000BCD Dimension Code Q Q Q R T T T U W X X X X

Current Rating (A) 24 35 54 97 135 180 240 360 500 650 720 850 1000

Price Adder Code a b c d e f g h i j k l m

The minimum rating is: 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97...720 A; 7.5 kW for devices rated 850 A and greater. HP ratings at motor terminal voltages for 208, 480 and 600 line volts, respectively. Controllers are shipped from the factory preset for soft start mode, 10 second acceleration, energy saver inactive, motor stall active, and control power 100...240V AC, 50/60 Hz.

Accessories -- Page 49 Options -- Page 50 Specifications -- Page 56 Approximate Dimensions -- Page 59

44

Smart Motor Controllers -- SMC PLUS

Product Selection, Continued IP65 (Type 4) Enclosed Non-Combination Controllers

Bulletin 150 (Non-Combination Controller) -- The SMC PLUS Controller requires a separate 100...240V, 50/60 Hz single-phase control source. A thermal overload is not included. Terminals are provided for a separate thermal overload relay connection to the control circuit. Enclosures other than those listed are available. Consult Allen-Bradley Sales Office. Up to 480V AC

kW 230V AC 50 Hz 5.5 10 15 25 37 51 75 110 150 200 220 257 315 400V AC 50 Hz 11 18.5 22 45 75 90 132 200 257 355 400 475 530 200V AC 60 Hz 1...5 1...10 1...15 5...30 5...40 5...60 5...75 5...125 5...150 5...200 5...250 10...300 10...350 HP 230V AC 60 Hz 1...7.5 1...10 1...20 5...30 5...50 5...60 5...75 5...150 5...200 5...250 5...300 10...350 10...400 460V AC 60 Hz 1...15 1...25 1...40 5...75 5...100 5...150 5...200 5...300 5...400 5...500 5...600 10...700 10...800 Cat. No. 150-A24FBD 150-A35FBD 150-A54FBD 150-A97FBD 150-A135FBD 150-A180FBD 150-A240FBD 150-A360FBD 150-A500FBD 150-A650FBD 150-A720FBD 150-A850FBD 150-A1000FBD Dimension Code Q Q Q S T T U V X Z1 Z1 Z1 Z1

Bulletin 150

Current Rating (A) 24 35 54 97 135 180 240 360 500 650 720 850 1000

Price Adder Code a b c d e f g h i j k l m

Up to 600V AC

kW 230V AC 50 Hz 5.5 10 15 25 37 51 75 110 150 200 220 257 315 400V AC 50 Hz 11 18.5 22 45 75 90 132 200 257 355 400 475 530 500V AC 50 Hz 15 22 37 63 90 132 160 250 355 475 500 600 710 200V AC 60 Hz 1...5 1...10 1...15 5...30 5...40 5...60 5...75 5...125 5...150 5...200 5...250 10...300 10...350 HP 230V AC 60 Hz 1...7.5 1...10 1...20 5...30 5...50 5...60 5...75 5...150 5...200 5...250 5...300 10...350 10...400 460V AC 60 Hz 1...15 1...25 1...40 5...75 5...100 5...150 5...200 5...300 5...400 5...500 5...600 10...700 10...800 575V AC 60 Hz 1...20 1...30 1...50 5...75 5...125 5...150 5...250 5...350 5...500 5...600 5...700 10...800 10...1000 Cat. No. 150-A24FCD 150-A35FCD 150-A54FCD 150-A97FCD 150-A135FCD 150-A180FCD 150-A240FCD 150-A360FCD 150-A500FCD 150-A650FCD 150-A720FCD 150-A850FCD 150-A1000FCD Dimension Code Q Q Q S T T V V X Z1 Z1 Z1 Z1

Current Rating (A) 24 35 54 97 135 180 240 360 500 650 720 850 1000

Price Adder Code a b c d e f g h i j k l m

The minimum rating is: 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97...720 A; 7.5 kW for devices rated 850 A and greater. HP ratings at motor terminal voltages for 208, 480 and 600 line volts, respectively. Controllers are shipped from the factory preset for soft start mode, 10 second acceleration, energy saver inactive, motor stall inactive, and control power 100...240V AC, 50/60 Hz. 97...1000 A Type 4 SMC PLUS Smart Motor Controllers include Bulletin 100 bypass contactors wired for 120V AC 50/60 Hz.

Accessories -- Page 49 Options -- Page 50 Specifications -- Page 56 Approximate Dimensions -- Page 59

45

Bulletin 150

Smart Motor Controllers -- SMC PLUS

Product Selection, Continued IP54 (Type 12) Enclosed Non-Combination Controllers

SMC Easy Ship program Cat. Nos. are printed in blue. See page 39.

Bulletin 150 (Non-Combination Controller) -- The SMC PLUS Controller requires a separate 100...240V, 50/60 Hz single-phase control source. A thermal overload is not included. Terminals are provided for a separate thermal overload relay connection to the control circuit. Enclosures other than those listed are available. Consult Allen-Bradley Sales Office. Up to 480V AC

kW Current Rating (A) 24 35 54 97 135 180 240 360 500 650 720 850 1000 230V AC 50 Hz 5.5 10 15 25 37 51 75 150 132 200 220 257 315 400V AC 50 Hz 11 18.5 22 45 75 90 132 200 257 355 400 475 530 200V AC 60 Hz 1...5 1...10 1...15 5...30 5...40 5...60 5...75 5...125 5...150 5...200 5...250 10...300 10...350 HP 230V AC 60 Hz 1...7.5 1...10 1...20 5...30 5...50 5...60 5...75 5...150 5...200 5...250 5...300 10...350 10...400 460V AC 60 Hz 1...15 1...25 1...40 5...75 5...100 5...150 5...200 5...300 5...400 5...500 5...600 10...700 10...800 Cat. No. 150-A24JBD 150-A35JBD 150-A54JBD 150-A97JBD 150-A135JBD 150-A180JBD 150-A240JBD 150-A360JBD 150-A500JBD 150-A650JBD 150-A720JBD 150-A850JBD 150-A1000JBD Dimension Code Q Q Q S T T U V X Z Z1 Z1 Z1

Price Adder Code a b c d e f g h i j k l m

Up to 600V AC

kW 230V AC 50 Hz 5.5 10 15 25 37 51 75 110 150 200 220 257 315 400V AC 50 Hz 11 18.5 22 45 75 90 132 200 257 355 400 475 530 500V AC 50 Hz 15 22 37 63 90 110 160 250 355 475 500 600 710 200V AC 60 Hz 1...5 1...10 1...15 5...30 5...40 5...60 5...75 5...125 5...150 5...200 5...250 10...300 10...350 HP 230V AC 60 Hz 1...7.5 1...10 1...20 5...30 5...50 5...60 5...75 5...150 5...200 5...250 5...300 10...350 10...400 460V AC 60 Hz 1...15 1...25 1...40 5...75 5...100 5...150 5...200 5...300 5...400 5...500 5...600 10...700 10...800 575V AC 60 Hz 1...20 1...30 1...50 5...75 5...125 5...150 5...250 5...350 5...500 5...600 5...700 10...800 10...1000 Cat. No. 150-A24JCD 150-A35JCD 150-A54JCD 150-A97JCD 150-A135JCD 150-A180JCD 150-A240JCD 150-A360JCD 150-A500JCD 150-A650JCD 150-A720JCD 150-A850JCD 150-A1000JCD Dimension Code Q Q Q S T T V V X Z Z1 Z1 Z1

Current Rating (A) 24 35 54 97 135 180 240 360 500 650 720 850 1000

Price Adder Code a b c d e f g h i j k l m

The minimum rating is: 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97...720 A; 7.5 kW for devices rated 850 A and greater. HP ratings at motor terminal voltages for 208, 480 and 600 line volts, respectively. Controllers are shipped from the factory preset for soft start mode, 10 second acceleration, energy saver inactive, motor stall inactive, and control power 100...240V AC, 50/60 Hz. 97...1000 A Type 12 SMC PLUS Smart Motor Controllers include Bulletin 100 Bypass Contactors wired for 120V AC 50/60 Hz.

Accessories -- Page 49 Options -- Page 50 Specifications -- Page 56 Approximate Dimensions -- Page 59

46

Smart Motor Controllers -- SMC PLUS

Product Selection, Continued Enclosed Combination Controllers

Bulletin 152H/153H (Combination Controller) -- Includes a 120V control transformer and a three-pole thermal overload relay less elements. Where isolating or bypass contactors are required, Bulletin 100 contactors are used (through 600 A). Enclosures other than those listed are available. Consult Allen-Bradley Sales Office.

IP54 (Type 12) Enclosed Combination Controller With Fusible Disconnect and Bypass Contactor Dimension Code Cat. No. 152H-WJB-42 152H-WJB-43 152H-WJB-44 152H-WJB-45 152H-WJB-46 152H-WJB-47 152H-WJB-48 152H-WJB-49 152H-WJB-50 152H-WJB-51 152H-WJB-52 152H-WJB-54 152H-WJB-56 152H-WJB-57 152H-WJB-58 152H-WJB-59 152H-WJB-60 152H-WJB-61 152H-WJB-62 152H-WJB-63 152H-WJB-65 152H-WJC-43 152H-WJC-44 152H-WJC-45 152H-WJC-46 152H-WJC-47 152H-WJC-48 152H-WJC-49 152H-WJC-50 152H-WJC-51 152H-WJC-52 152H-WJC-54 152H-WJC-56 152H-WJC-57 152H-WJC-58 152H-WJC-59 152H-WJC-60 152H-WJC-61 152H-WJC-62 152H-WJC-63 152H-WJC-65 152H-WJC-67

Bulletin 150

HP

Nominal Current (A)

Price Adder Code

IP30 (Type 1) Vented Enclosure With Fusible Disconnect Dimension Code Cat. No.

480V AC, 60 Hz 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 600 700 800 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 600 700 800 1000 24 30 35 40 54 70 82 97 125 156 180 240 302 360 410 477 525 575 675 800 915 24 28 35 40 54 65 80 115 125 170 200 240 310 360 385 450 500 600 700 800 1000 a b b c c d d d e f f g h h i i j j k l m a b b c c d d e e f g g h h i i i j k l m S T T T T U U U V W W W X2 X2 Y1 Y1 Z1 Z1 Z1 Z1 Z1 S T T T T U U V V W W X2 X2 Y1 Y1 Z1 Z1 Z1 Z1 Z1 Z1 152H-WAB-42 152H-WAB-43 152H-WAB-44 152H-WAB-45 152H-WAB-46 152H-WBB-47 152H-WBB-48 152H-WBB-49 152H-WBB-50 152H-WBB-51 152H-WBB-52 152H-WBB-54 152H-WBB-56 152H-WBB-57 152H-WBB-58 152H-WBB-59 152H-WBB-60 152H-WBB-61 152H-WBB-62 152H-WBB-63 152H-WBB-65 600V AC, 60 Hz 152H-WAC-43 152H-WAC-44 152H-WAC-45 152H-WAC-46 152H-WAC-47 152H-WBC-48 152H-WBC-49 152H-WBC-50 152H-WBC-51 152H-WBC-52 152H-WBC-54 152H-WBC-56 152H-WBC-57 152H-WBC-58 152H-WBC-59 152H-WBC-60 152H-WBC-61 152H-WBC-62 152H-WBC-63 152H-WBC-65 152H-WBC-67 S T T T T U U V V W W X2 X2 Y2 Y2 Z2 Z2 Z2 Z3 Z3 Z3 S T T T T U U U V W W W X2 X2 Y2 Y2 Z2 Z2 Z2 Z3 Z3

208V and 240V Controllers are available. Consult Allen-Bradley Sales Office. See page 56 for fuse clip size and type information. Accu-Stop Control is not available when a bypass contactor is used. Bypass contactors are used to bypass the SMC PLUS Controller when the motor has reached full speed. Includes internal circulating fan rather than enclosure ventilation. Includes internal circulating fan rather than bypass contactor.

Accessories -- Page 49 Options -- Page 50 Specifications -- Page 56 Approximate Dimensions -- Page 59

47

Bulletin 150

Smart Motor Controllers -- SMC PLUS

Product Selection, Continued Enclosed Combination Controllers

SMC Easy Ship program Cat. Nos. are printed in blue. See page 39.

Bulletin 152H/153H (Combination Controller) -- Includes a 120V control transformer and a three-pole thermal overload relay less elements. Where isolating or bypass contactors are required, Bulletin 100 contactors are used (through 600 A). Enclosures other than those listed are available. Consult Allen-Bradley Sales Office.

Price Adder Code a b b c c d d d e f f g h h i i j j k l m a b b c c d d e e f g g h h i i i j k l m IP30 (Type 1) Vented Enclosed Combination Controllers With Circuit Breaker Dimension Code S T T T T U U U V W W W X2 X2 Y1 Y1 Y2 Y2 Y2 Z Z S T T T T U U V V W W X2 X2 Y1 Y1 Y2 Y2 Y2 Z Z Z Cat. No. IP54 (Type 12) Enclosed Combination Controller With Circuit Breaker and Bypass Contactor Dimension Code S T T T T U U U V W W W X X Y1 Y1 Z Z Z Z Y3 S T T T T U U V V W W W X Y1 Y1 Z Z Z Z Y3 Y3 Cat. No. 153H-WJB-42 153H-WJB-43 153H-WJB-44 153H-WJB-45 153H-WJB-46 153H-WJB-47 153H-WJB-48 153H-WJB-49 153H-WJB-50 153H-WJB-51 153H-WJB-52 153H-WJB-54 153H-WJB-56 153H-WJB-57 153H-WJB-58 153H-WJB-59 153H-WJB-60 153H-WJB-61 153H-WJB-62 153H-WJB-63 153H-WJB-65 153H-WJC-43 153H-WJC-44 153H-WJC-45 153H-WJC-46 153H-WJC-47 153H-WJC-48 153H-WJC-49 153H-WJC-50 153H-WJC-51 153H-WJC-52 153H-WJC-54 153H-WJC-56 153H-WJC-57 153H-WJC-58 153H-WJC-59 153H-WJC-60 153H-WJC-61 153H-WJC-62 153H-WJC-63 153H-WJC-65 153H-WJC-67

HP 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 600 700 800 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 600 700 800 1000

Nominal Current 24 30 35 40 54 70 82 97 125 156 180 240 302 360 410 477 525 575 675 800 915 24 28 35 40 54 65 80 115 125 170 200 240 310 360 385 450 500 600 700 800 1000

480V AC, 60 Hz 153H-WAB-42 153H-WAB-43 153H-WAB-44 153H-WAB-45 153H-WAB-46 153H-WBB-47 153H-WBB-48 153H-WBB-49 153H-WBB-50 153H-WBB-51 153H-WBB-52 153H-WBB-54 153H-WBB-56 153H-WBB-57 153H-WBB-58 153H-WBB-59 153H-WBB-60 153H-WBB-61 153H-WBB-62 153H-WBB-63 153H-WBB-65 600V AC, 60 Hz 153H-WAC-43 153H-WAC-44 153H-WAC-45 153H-WAC-46 153H-WAC-47 153H-WBC-48 153H-WBC-49 153H-WBC-50 153H-WBC-51 153H-WBC-52 153H-WBC-54 153H-WBC-56 153H-WBC-57 153H-WBC-58 153H-WBC-59 153H-WBC-60 153H-WBC-61 153H-WBC-62 153H-WBC-63 153H-WBC-65 153H-WBC-67

208V and 240V Controllers are available. Consult Allen-Bradley Sales Office. See page 56 for circuit breaker size and rating plug size. Accu-Stop Control is not available when a bypass contactor is used. Bypass contactors are used to bypass the SMC PLUS Controller when the motor has reached full speed. Includes internal circulating fan rather than enclosure ventilation. Includes internal circulating fan rather than bypass contactor.

0

Accessories -- Page 49 Options -- Page 50 Specifications -- Page 56 Approximate Dimensions -- Page 59

48

Smart Motor Controllers -- SMC PLUS

Accessories Protective Modules (Field Modifications)

Nominal Current Rating (A) Field Modification Cat. No. 150-N84

Bulletin 150

Price Adder Code

Description 480V Protective Module

24...54

a...c 600V Protective Module 150-N86

480V Protective Module 97...360 d...h 600V Protective Module

150-N84L

150-N86L

Terminal Lug Kits (97...1000 A)

Total No. of Terminal Lugs Possible Each Side Line Side 3 6 6 9 6 Load Side 3 6 6 9 6

Nominal Current Rating (A) 97...135 180...360 500 650...720 850...1000

Conductor Range #6-4/0 AWG #6-4/0 AWG #4-500MCM AWG #4-500MCM AWG (2) 1/0-500MCM AWG

Pkg. Qty. 3 3 3 3 3

Cat. No. 199-LF1 199-LF1 199-LG1 199-LG1 199-LJ1

IEC Terminal Covers (Field Modification)

Description IEC line or load terminal covers for 97...135 A devices (includes line and load termination covers) IEC line and load terminal covers for 180...360 A devices (includes line and load termination covers) Field Modification Cat. No. 150-NT1

150-NT2

The same protective module mounts on the line or load side of the SMC PLUS. For applications requiring both line and load side protection, two protective modules must be ordered. Protective modules are standard on 500...1000 A units.

Product Selection -- Page 43

49

Bulletin 150 Options

Smart Motor Controllers -- SMC PLUS

SMC Easy Ship program descriptions are printed in blue. See page 39.

Price Adder Code a...m Cat. No. Modification A

Option Soft Stop

Description Provides a ramp down time of 2...60 seconds for applications which require an extended coast-to-rest. Provides smooth motor acceleration and deceleration, reducing surges caused by the starting and stopping of centrifugal pumps. Starting time is adjustable from 2...30 seconds, and stopping time is adjustable from 2...120 seconds. Provides a preset slow speed for positioning or alignment applications. Preset speeds can be selected at either 7% or 15% of rated motor speed, in the forward direction, 10% or 20% in the reverse direction. The direction of the motor is dip switch selectable. Slow speed current is adjustable from 50...450% of full load current.

Pump Control

a...m

B

Preset Slow Speed

a...m

C

SMB Smart Motor Braking

Provides a microcomputer based braking system which applies three-phase braking current to a standard squirrel-cage induction motor. The strength of the braking current is adjustable from 150...400% of full load motor current.

Accu-Stop

Provides precise stopping control for positioning or to minimize jogging to stop. A three-phase braking current is applied to the motor (adjustable from 150...400% of full load current) until it reaches a preset slow speed (either 7% or 15% of rated motor-speed). The motor is held at this speed until a stop command is given. Braking torque is then applied until the motor reaches zero speed. Slow speed current is adjustable from 50...450% of full load current.

Slow Speed with Braking

Provides forward slow speed for positioning and alignment, and braking control to stop.

a b c d e f g h i j k l m a b c d e f g h i j k l m a b c d e f g h i j k l m

D

E

F

Only one option may be added to the standard unit. Observe the thermal rating of the AC induction motor. Not intended to be used as an emergency stop. Refer to the applicable standards for emergency stop requirements. Add the designated letter to the end of the Cat. No. For example, to add the Pump Control Option: Cat. No 150-24NBD becomes Cat. No. 150-A24NBDB or Cat. No. 152B-WBB-56 becomes Cat. No. 152B-WBBB-56 for combination style. Accu-stop Control is not available when a bypass contactor is used. Kickstart is not available with this option. Product Selection -- Page 43

50

Smart Motor Controllers -- SMC PLUS

Options, Continued

Bulletin 150

SMC Easy Ship program descriptions are printed in blue. See page 39.

Option Description Start-Stop Push Button Start-Stop Push Button with H-O-A Selector Switch Soft Stop Push Button Pump Stop Push Button Slow Speed Push Button Brake Push Button Accu-Stop/Slow Speed Push Button Emergency Stop Fault Reset Hand-Off-Auto Selector Switch SMC-Off-Bypass Selector Switch Forward-Off-Reverse Selector Switch Transformer Pilot Light (Red Lens -- Easy Ship Program) Push-to-Test Pilot Light Control Circuit Transformer (fused primary and secondary) Additional 100 VA Control Circuit Transformer (fused primary and 24...54 A, 480V Line Side Protective Module 97...360 A, 480V Line Side Protective Module 24...54 A, 600V Line Side Protective Module 97...360 A, 600V Line Side Protective Module 24...54 A, 480V Load Side Protective Module 97...360 A, 480V Load Side Protective Module 24...54 A, 600V Load Side Protective Module 97...360 A, 600V Load Side Protective Module 24...54 A, 480V Both Line and Load Side Protective Modules 97...360 A, 480V Both Line and Load Side Protective Modules 24...54 A, 600V Both Line and Load Side Protective Modules 97...360 A, 600V Both Line and Load Side Protective Modules Three-pole thermal overload relay for 24...35 A units Three-pole thermal overload relay for 54 A units Three-pole thermal overload relay for 97...135 A units Three-pole thermal overload relay for 180...360 A units Three-pole thermal overload relay for 500 units Three-pole thermal overload relay for 650...850 A units Three-pole thermal overload relay for 1000 A units 24...54 A Overload Relay Reset 97...240 A Overload Relay Reset 360...1000 A Overload Relay Reset N.O. Overload Relay Auxiliary Contact N.C. Overload Relay Auxiliary Contact Price Adder Code Cat. No. Modification -1 -1F -1XA -1XB -1XC -1XD -1XE -1E -FR -3 -3B -3R -4_ -5_ -6P -6PX -8L4 -8L6 -8M4 -8M6 -8B4 -8B6

Push Buttons

a...m

Selector Switch Pilot Lights Control Circuit Transformer

a...m a...m a...m a...c d...h a...c d...h a...c d...h a...c d...h a...c d...h a...c d...h a...b c d...e f...h i j...l m a...c d...g h...m a...m a...d e...f g h i j k...l m

Protective Modules

Overload Relay

-OL

External Overload Relay Reset Overload Auxiliary Contact

-7 -9 -9A

Isolation Contactor

Isolation Contactor

Option push buttons are only available when the corresponding option module is selected. For example, Cat. No. 150-A24JBDA-1XA. Specify pilot light lens color. Options: Amber, Blue, Clear, Green, Red, and White. For example, -4R for a red lens. Line and Load Side Protective Modules are standard on 500...1000 A units. Three-pole thermal overload for Bulletin 150 enclosed controllers only. Overload is standard on Bulletins 152 and 153. Three-pole thermal overload does not include heater elements. External Overload Relay Reset is available with Bulletins 152, 153, and enclosed Bulletin 150 devices with overload option only. To order a non-combination or combination enclosed controller with an isolator contactor, add the letter "B" to the bulletin prefix. See pages 36-37. Bulletin 100 contactors are used through 600 A. Enclosure dimensions are subject to change. Consult factory for dimensions.

51

Bulletin 150

Smart Motor Controllers -- SMC PLUS

Options, Continued

Option

Description

Price Adder Code a...d e...f g h i j k...l m a...d e...f g h i j a...d e...f g h i j

Cat. No. Modification

Reversing Contactor

Reversing Contactor

NEMA Bypass Contactor

NEMA Isolation Contactor

Power Factor Correction Capacitors

NEMA Bypass for 24...97 A unit NEMA Bypass for 135...180 A unit NEMA Bypass for 240 A unit NEMA Bypass for 360 A unit NEMA Bypass for 500 A unit NEMA Bypass for 650 A unit NEMA Bypass for 24...97 A unit NEMA Bypass for 135...180 A unit NEMA Bypass for 240 A unit NEMA Bypass for 360 A unit NEMA Bypass for 500 A unit NEMA Bypass for 650 A unit 2 kVAR 2.5 kVAR 3 kVAR 4 kVAR 5 kVAR 6 kVAR 7 kVAR 7.5 kVAR 8 kVAR 9 kVAR 10 kVAR 11 kVAR 12.5 kVAR 14 kVAR 15 kVAR 16 kVAR 17.5 kVAR 18 kVAR 20 kVAR 22.5 kVAR 25 kVAR 27.5 kVAR 30 kVAR 32.5 kVAR 35 kVAR 37.5 kVAR 40 kVAR 42.5 kVAR 45 kVAR 47.5 kVAR 50 kVAR

-NB

-NI

-PFCC

To order a non-combination or combination enclosed controller with a reversing contactor, add an "R" to the bulletin prefix. See pages 41...42. Bulletin 104 contactors are used through 500 A @ 480V. Enclosure dimensions are subject to change. Consult factory for dimensions. 720, 850, 1000 A units currently use a NEMA Contactor. Power Factor Correction Capacitor to include Power Capacitors with 3-phase Class J Time-Delay Fusing and appropriately sized contactor. To order Power Factor Correction Capacitors indicate kVAR rating. For example: -PFCC30kVAR.

Product Selection -- Page 43 Accessories -- Page 49 Specifications -- Page 56 Approximate Dimensions -- Page 59

52

Smart Motor Controllers -- SMC PLUS

Options, Continued

Price Adder Code a...d e...f g h i j a b c d...e f g h i j...k l m a b...d e...g h i...j k...m a...m a...m a...m a...m a...h a...g h...m a...g h...m a...g h...m a...m a...m a...c d...f g h i j...k l...m Cat. No. Modification

Bulletin 150

Option

Description

Power Factor Correction Contactor

Power Factor Correction Capacitor Contactor

-PFCCC

SCR Fusing

Panel Board Type Ammeter

Panel Board Type Voltmeter Elapsed Time Meter Unwired Control Relays Control Relays

Auxiliary Contacts

Disconnect Auxiliary Circuit Breaker Disconnect Auxiliary

High Interrupting Circuit Breaker

Fast acting current limiting SCR fusing for 24 A unit Fast acting current limiting SCR fusing for 35 A unit Fast acting current limiting SCR fusing for 54 A unit Fast acting current limiting SCR fusing for 97...135 A units Fast acting current limiting SCR fusing for 180 A unit Fast acting current limiting SCR fusing for 240 A unit Fast acting current limiting SCR fusing for 360 A unit Fast acting current limiting SCR fusing for 500 A unit Fast acting current limiting SCR fusing for 650...720 A units Fast acting current limiting SCR fusing for 850 A unit Fast acting current limiting SCR fusing for 1000 A unit Single-phase panel board type ammeter for 24 A units Single-phase panel board type ammeter for 35...97 A units Single-phase panel board type ammeter for 135...240 A units Single-phase panel board type ammeter for 360 A units Single-phase panel board type ammeter for 500...650 A units Single-phase panel board type ammeter for 720...1000 A units Panel board type ammeter with switch for monitoring all three phases Single-phase panel board type voltmeter Panel board type voltmeter with switch for monitoring all three phases. Elapsed time meter Bulletin 700CF 4-pole relay ­ 2 N.O. and 2 N.C. Bulletin 700CF 4-pole relay ­ 3 N.O. and 1 N.C. Bulletin 700CF 4-pole relay ­ 4 N.O. On-Delay Off-Delay N.O. auxiliary contacts for 24...240 A units N.O. auxiliary contacts for 360...1000 A units N.C. auxiliary contacts for 24...240 A units N.C. auxiliary contacts for 360...1000 A units 1 N.O. ... 1 N.C. auxiliary contacts for 24...240 A units 1 N.O. ... 1 N.C. auxiliary contacts for 360...1000 A units N.O. disconnect auxiliary mounted on operating mechanism N.C. disconnect auxiliary mounted on operating mechanism Internal N.O. circuit breaker auxiliary Internal N.C. circuit breaker auxiliary High Interrupting Circuit Breaker for 24...54 A units High Interrupting Circuit Breaker for 97...180 A units High Interrupting Circuit Breaker for 240 A units High Interrupting Circuit Breaker for 360 A units High Interrupting Circuit Breaker for 500 A units High Interrupting Circuit Breaker for 650...720 A units High Interrupting Circuit Breaker for 850...1000 A units

-SCR

-85AA

-86AA -85AV -86AV -85T -89F22 -89F31 -89F40 -89FOD -89FOFD -90 -91 -901 -98 -99 -98X -99X

-HICB

Only the contactor will be provided. For motor horsepower above 500 consult factory for sizing and pricing. Instantaneous auxiliary contacts on Bulletin 700F relays are non-convertible. Available only with enclosed Bulletin 150, 152 and 153 devices with an isolation contactor or bypass contactor. Maximum of four (4) auxiliary contacts. Available only with Bulletin 152 and 153 devices. Maximum of two (2) disconnect auxiliaries. Available only with Bulletin 153 devices. Maximum of two (2) disconnect auxiliaries.

Product Selection -- Page 43

53

Bulletin 150

Smart Motor Controllers -- SMC PLUS

Options, Continued

Price Adder Code a...c d...e f...g h...i j...l m a...m a...m a...m a...m a...m a...m a...m a...i a...e f...g h...i j...k a...m a...m a...j k...l a...m a...m a...m a...m a...m a...m a...c d...e f...h i...m a...c d...e f...h i...m Cat. No. Modification

Option

Description Circuit Breaker Shunt Trip for 24...54 A units Circuit Breaker Shunt Trip for 97...135 A units Circuit Breaker Shunt Trip for 180...240 A units Circuit Breaker Shunt Trip for 360...500 A units Circuit Breaker Shunt Trip for 650...850 A units Circuit Breaker Shunt Trip for 1000 A units Additional load circuit breakers to be installed in panel. Customer is to stipulate size and quantity. Bulletin 813S Line Voltage Monitor Bulletin 817 Thermistor Protection Relay Bulletin 825 Smart Motor Manager and Bulletin 825 Converter Module Cutler-Hammer IQ1000 Protective Relay GE Multilin 269 Plus Protective Relay 4...20 mA output signal proportional to 1...100% motor FLC Bulletin 1409 Arcing Ground Fault Relay and Sensor for applications up to 400 HP Bulletin 1410 Motor Winding Heater for applications up to 600 HP Lightning Surge Protection Cabinet Strip Heater with Thermostat Service Entrance Label U.L. Label Panel Mounted Unwired Terminal Blocks 6 or 12 position Components mounted on enclosure mounting plate only Customer is to stipulate panel dimensions Customer is to stipulate paint color for enclosure Ship Board ­ MIL-S-901D Enclosure Type NEMA 3R Non-Combination

Shunt Trip

-754

Additional Load Circuit Breakers Line Voltage Monitor Thermistor Protection Relay Smart Motor Manager IQ1000 Protective Relay Multilin 269 Plus Transducer Output Ground Fault Protection

-ALCB -813S -817 -SMM -IQ1000 -269PLUS -TO -GFP

Motor Winding Heater Lightning Arrestor Strip Heater Service Entrance Label U.L. Label Unwired Terminal Blocks Panel Mount Specified Panel Dimensions Enclosure Color (Custom Paint) Enclosure Shock Mounts Enclosure Type NEMA 3R

-MWH -LA -SH -SEL -UL -TB6 -TB12 -PM -SPD -EC -SM

Enclosure Type NEMA 3R

Enclosure Type NEMA 3R Combination

Available only with Bulletin 153 devices. Requires an isolation contactor on the output of the SMC. Pricing to be determined upon request. To order a non-combination or combination enclosed controller with a NEMA 3R enclosure, add an "H" to the enclosure type prefix. Example: Cat. No. 152H-B240HBD-54. See pages 41...42. Enclosure dimensions are subject to change. Consult factory for dimensions. Enclosure price adder is to be added to NEMA 12 non-combination or combination price. Consult factory for pricing.

Product Selection -- Page 43 Accessories -- Page 49 Specifications -- Page 56 Approximate Dimensions -- Page 59

54

Smart Motor Controllers -- SMC PLUS

Options, Continued

Price Adder Code a...d e...f g...h i...m a...c d...e f...h i...m a...m a...m a...m Cat. No. Modification

Bulletin 150

Option Enclosure Type NEMA 4X Stainless Steel

Description

Enclosure Type NEMA 4X Stainless Steel Non-Combination

Enclosure Type NEMA 4X Stainless Steel Air Conditioning Wiring Diagrams Print Approval

Enclosure Type NEMA 4X Stainless Steel Combination AC Unit mounted on enclosure AutoCad Drawing of panel wiring Customer Requested Print Approval Drawings

-AC -WD -PA

To order a non-combination or combination enclosed controller with a NEMA 4X stainless steel enclosure, add an "S" to the enclosure type prefix. Example: Cat. No 152H-B240SBD-54. See pages 41...42. Enclosure dimensions are subject to change. Consult factory for dimensions. Enclosure price adder is to be added to the NEMA 12 non-combination or combination price. Pricing to be determined upon request. Order to be released to manufacturing upon return of signed approval drawing. Consult factory for pricing.

Product Selection -- Page 43 Accessories -- Page 49 Specifications -- Page 56 Approximate Dimensions -- Page 59

55

Information

13 pages

Find more like this

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

133104


You might also be interested in

BETA
pushbuttons
Microsoft Word - SCCR_WhitePaper.doc
ALTIVAR 16 AC Drive Catalog
britStand.set