DESCRIPTION

TECHNICAL GUIDE

YORK Sunline 2000TM units are convertible single package high efficiency rooftops. All models have independent dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. All units include: · · Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards Two-stage cooling provided by dual independent refrigeration circuits with expansion valves, filter-driers, high and low pressure/loss of charge switches and freezestats Scroll compressors (25T model only) Two-stage heating provided by dual independent heat exchangers with aluminized steel tubes, redundant gas valves, spark ignition with induced draft logic Permanently lubricated motors Bottom or side air discharge configuration capability (field convertible) Belt Drive Blower Motor with high static drive option Manufactured under the quality standards of ISO9001 Simplicity® Control Board Zero-25% fixed air damper with hood Copper tube/aluminum fin coils Hinged filter access and tooless latched doors Rigging holes in base rails for lifting Single point power connection Complete factory package - tested, charged and wired CSA agency approvals on all units

SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS

DM 180, 240 & 300

15, 20 & 25 NOMINAL TONS

· ·

· · · · · · · · · · · ·

WARRANTY · · · One-year parts warranty A Five-year parts warranty on the compressors and electric heat elements Ten-year parts warranty on the gas-fired heat exchangers

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

262259-YTG-A-0706

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5 FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . 7 GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 31 LIST OF FIGURES Fig. # Pg. # Tbl. # LIST OF TABLES Pg. #

1 SOUND POWER RATING . . . . . . . . . . . . . . . . . . . . 8 2 CAPACITY RATINGS - (ARI 360) . . . . . . . . . . . . . . 8 3 GAS HEAT RATIINGS . . . . . . . . . . . . . . . . . . . . . . . 8 4 DM 180 COOLING CAPACITIES (15 TON) . . . . . . . 9 5 DM 240 COOLING CAPACITIES (20 TON) . . . . . . 10 6 DM 300 COOLING CAPACITIES (25 TON) . . . . . . 11 7 ALTITUDE CORRECTION FACTORS . . . . . . . . . . 12 8 SUPPLY AIR BLOWER PERFORMANCE (15 TON) COOLING ONLY 180 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 9 SUPPLY AIR BLOWER PERFORMANCE (20 TON) COOLING ONLY 240 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 10 SUPPLY AIR BLOWER PERFORMANCE (15 TON) GAS HEAT 180 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 11 SUPPLY AIR BLOWER PERFORMANCE (20 TON) GAS HEAT 240 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 12 SUPPLY AIR BLOWER PERFORMANCE (25 TON) GAS HEAT 300 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 13 BLOWER MOTOR AND DRIVE DATA . . . . . . . . . 19 14 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . 19 15 POWER EXHAUST PERFORMANCE . . . . . . . . . . 19 16 DM ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . 20 17 DM ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . 21 18 DM VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . 22 19 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 22 20 ELECTRIC HEAT CORRECTION FACTORS . . . . 23 21 UTILITIES ENTRY DATA . . . . . . . . . . . . . . . . . . . . 24 22 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . 26 23 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . 28

1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2 ALTITUDE/TEMPERATURE CONVERSION FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 3 DM FIELD WIRING DIAGRAM . . . . . . . . . . . . . . . . 23 4 UNIT DIMENSIONS & CLEARANCES 15, 20 & 25 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 5 REAR VIEW DIMENSIONS . . . . . . . . . . . . . . . . . . 25 6 UNIT DIMENSIONS DM180, 240 & 300 (RAINHOOD) . . . . . . . . . . . . . . . . . . . . . . . . . . 26 7 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . 27 8 TYPICAL UNIT APPLICATIONS . . . . . . . . . . . . . . . 27 9 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . 28 10 UNIT ROOF CURB DIMENSIONS . . . . . . . . . . . . . 29 11 ROOF CURB DUCT OPENINGS DIMENSION . . . 29 12 CUT AWAY OF ROOF CURB . . . . . . . . . . . . . . . . . 29 13 SIMPLICITY® CONTROL WIRING DIAGRAM . . . 30

2

Unitary Products Group

262259-YTG-A-0706

PRODUCT NOMENCLATURE

15-25 Ton Sunline 2000TM Model Number Nomenclature

D M 180 N24 A 2 A AA 1 0 1 2 4 A

Product Category D = A/C, Single Pkg., R-22 Product Style A = Style A

Product Identifier M = 8.5-9.0 EER A/C

Configuration Options (not required for all units) These four digits will not be assigned until a quote is requested, or an order placed. SS Drain Pan CPC Controller, DFS, APS Johnson Controller, DFS, APS Honeywell Controller, DFS, APS Novar Controller, DFS, APS Simplicity IntelliComfort Controller Simplicity IntelliComfort Controller w/ModLinc 2" Pleated filters

Nominal Cooling Capacity 180 = 15 Ton 240 = 20 Ton 300 = 25 Ton

Heat Type and Nominal Heat Capacity C00 = Cooling Only. No field installed electric heat Gas Heat Options N24 = 240 MBH Output Aluminized Steel N32 = 320 MBH Output Aluminized Steel S24 = 240 MBH Output Stainless Steel S32 = 320 MBH Output Stainless Steel Electric Heat Options E18 = 18 KW E36 = 36 KW E54 = 54 KW E72 = 72 KW

4" Pleated filters BAS Ready Unit with Belimo Economizer Double Wall Construction Heat Reclaim Coil Options (2 or 3 Row, 1-5/8" or 2-1/8" Stub Out) (WJ and WR models only) Any Combination of Additional Options that Don't Have an Option Code Pre-assigned

Product Generation 1 = First Generation 2 = Second Generation

Additional Options Standard Cabinet AA = None AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch RC = Coil Guard & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator & Condenser Coils Hinged Filter Door & Toolless Access Cabinet BA = Hinged Filter Door & Toolless Access Panels BB = Phase Monitor, Hinged Filter Door & Toolless Access Panels BC = Coil Guard, Hinged Filter Door & Toolless Access Panels BD = Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels BE = Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels BF = Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels BG = Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels BH = Phase Monitor, Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

Airflow A = Std. Drive B = Std. Drive/Single Input Econo. C = Std. Drive/Single Input Econo./Power Exhaust (Downflow Only) D = Std. Drive/Motorized Damper N = Hi Static Drive P = Hi Static Drive/Single Input Econo. Q = Hi Static Drive/Single Input Econo./Power Exhaust (Downflow Only) R = Hi Static Drive/Motorized Damper

Voltage 2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60

ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be located in digits 15-18.

Installation Options A = No Options Installed B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4 N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 & 5 Y = Options 4 & 5 Z = Options 3, 4 & 5 Options 1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet

Unitary Products Group

3

262259-YTG-A-0706

FEATURES

All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with factory installed power exhaust are suitable for bottom duct connections only. For bottom duct, you remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, you replace the supply and return air panels on the rear of the unit with a side duct flange accessory. All models are available with these "factory mounted" outdoor air damper options: · · · Single enthalpy economizer Single enthalpy economizer with power exhaust Motorized outdoor air damper

·

Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button. Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat. Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips. Nuisance Trip Protection and Strikes - To prevent nuisance trouble calls, the control board uses a "three times, you're out" philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor. On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.

·

·

·

·

A fixed outdoor air intake assembly will be shipped in the return air compartment of all units ordered without an economizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct. All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/or static pressure requirement. All compressors include scroll compressors and internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/ loss of charge switch to protect all system components. · Simplicity® Controls - Simplicity® control boards have standardized a number of features previously available only as options or by utilizing additional controls. · Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.

All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures. All models are CSA approved. · Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty. Gas Heat Operation - All gas heat units are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards. The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.

·

4

Unitary Products Group

262259-YTG-A-0706

ELECTRIC HEATER LOCATION (OPTIONAL ELECTRIC/ELECTRIC UNITS) HIGH EFFICIENCY COMPRESSORS WITH CRANKCASE HEATERS COPPER TUBE/ALUMINUM FIN CONDENSER COILS LOW VOLTAGE RELAY BOARD AND TERMINAL STRIP ELECTRICAL DISCONNECT MOUNTING LOCATION (Field installed) KNOCKOUT FOR SIDE CONTROL WIRING ENTRY 2" DISPOSABLE FILTERS KNOCKOUT FOR SIDE POWER WIRING ENTRY SIDE TERMINAL BLOCK (For Single Point Power Supply with Electric Heat) ELECTRIC\ELECTRIC UNITS BOTTOM POWER & CONTROL WIRING ENTRY KNOCKOUTS FOR SIDE GAS SUPPLY ENTRY HOLE FOR BOTTOM GAS SUPPLY ENTRY POWER VENTOR MOTOR WITH POST PURGE CYCLE

LONG LASTING POWDER PAINT FINISH ECONOMIZER HOOD

20 GAUGE ALUMINIZED STEEL TUBULAR HEAT EXCHANGERS

OUTDOOR AIR OPENING FOR SLIDE-IN/PLUG-IN INTERNAL ECONOMIZER(OPTION)

SIDE AND BOTTOM SUPPLY & RETURN AIR DUCT OPENINGS(SIDE X SIDE) 1" NPTI CONDENSATE DRAIN

BELT-DRIVE BLOWER MOTOR

FULL PERIMETER 14 GUAGE BASE RAILS WITH LIFTING HOLES

GAS/ELECTRIC UNIT SHOWN

FIGURE 1 - UNIT CUTAWAY

· Electric Heat Operation - All electric heat models (factory installed only) are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive current and temperature by fuses and two thermal limit switches. The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit. · BAS Controls - York's SunlineTM series units offer factory mounted BAS controls such as Simplicity® INTELLI-ComfortTM, Novar, Honeywell, Johnson, and CPC. · POWER EXHAUST - Our single economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation. The exhaust fan, motor and controls are installed and wired at the factory. The rain hood must be assembled and installed in the field. The power exhaust option can only be used on bottom duct configurations. · MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down. The rain hood is painted to match the basic unit and must be field assembled before installing. · PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes Technicoat 10-1" processes. Coating is applied by total immersion of the complete coil for maximum protection. ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures.

FACTORY-INSTALLED OPTIONS

· SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling. The rainhood is painted to match the basic unit and must be field-assembled before installing.

·

Unitary Products Group

5

262259-YTG-A-0706

·

FILTER OPTIONS - Standard units are shipped with 2" throw-away filters installed. 2" pleated and 4" pleated filters are offered as a factory installed option. CONVENIENCE OUTLET - This 110 volt outlet can be "powered" by the unit with a stepdown transformer or you may order the unit with a "non-powered" convenience outlet that can be wired in the field. DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only. BAS - Building Automation System Controls Simplicity® INTELLI-ComfortTM CONTROL - The York® Simplicity® INTELLI-ComfortTM control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Construction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-ComfortTM using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLIStartTM algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity® INTELLI-ComfortTM balances space temperature, ventilation air temperature, CO2 and humidity for ultimate comfort. Simplicity® INTELLI-ComfortTM with ModLINC CONTROL - The York® Simplicity® INTELLI-ComfortTM with ModLINC control is factory installed. It includes all the features of the INTELLI-ComfortTM control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol. Novar® BAS CONTROL - The Novar® ETC-3 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch. JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

·

·

CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch. HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch. SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.

·

·

·

·

Factory installed smoke detectors in the return air, may be subjected to freezing temperatures during "off" times due to out side air infiltration. these smoke detectors have an operational limit of 32°F to 131°F. smoke detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms. · COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit. STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly. STAINLESS STEEL DRAIN PAN- An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments. PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-ofphase condition. HIGH SPEED DRIVE - Includes a belt and blower pulley upgrade to enhance blower performance. DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory. HINGED FILTER DOOR/"TOOLESS" BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance. NOTE:Knobs are shipped separately within the unit to prevent shipping damage. These must be field installed for tool-less operation.

·

·

·

· ·

·

·

·

·

6

Unitary Products Group

262259-YTG-A-0706

FIELD-INSTALLED ACCESSORIES

· SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling. The rainhood is painted to match the basic unit and must be field-assembled before installing. · MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down. The rain hood is painted to match the basic unit and must be field assembled before installing. · ROOF CURBS - Fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly. They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports. · HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane. HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.

·

SIDE DUCT FLANGES - One-inch flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used individually for bottom supply/ horizontal return or horizontal supply/bottom return. They cannot be used on units with power exhaust. BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct. HIGH SPEED DRIVE - A smaller blower pulley and a shorter belt increase the speed of the supply air blower for applications with a higher CFM and/or static pressure requirements. ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy. BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work. FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes. WOOD SKID - Allows unit to be handled with 90" forks. CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits. COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit. PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-ofphase condition.

·

·

·

·

·

· ·

·

·

·

·

Unitary Products Group

7

262259-YTG-A-0706

TABLE 1: SOUND POWER RATING1

ESP CFM IWG 180 240 300 6,000 8,000 10,000 1.00 1.00 1.30 RPM 1,080 1,120 1160 BHP 4.60 6.65 12.5 63 99 102 108 125 99 102 108 BLOWER SOUND POWER (db 10-12 Watts) Octave Band Centerline Frequency (Hz) 250 89 92 98 500 82 85 91 1,000 84 87 93 2,000 77 80 86 4,000 72 75 81 8,000 67 70 76 SWL dB(A) 89 92 98 dB(A) @ 10Ft.2 56 59 65

UNIT SIZE

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings. 2. At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 360)1

MODEL COOLING ONLY DM180C/E00 DM240C/E00 DM300C/E00 COOLING WITH GAS HEAT DM180N/S DM240N/S DM300N/S DM180E18 DM180E36 DM180E54 DM180E72 DM240E18 DM240E36 DM240E54 DM240E72 DM300E18 DM300E36 DM300E54 DM300E72

176 232 290 8.5 8.5 8.5 9.0 8.05 8.3 176 234 290 8.7 8.6 8.5 9.2 8.05 8.7

TABLE 3: GAS HEAT RATIINGS

IPLV3 MODEL DM180N/S24 DM180N/S32 DM240N/S24 DM240N/S32 DM300N/S24 DM300N/S32 MBH INPUT

300 400 300 400 300 400

MBH

EER2

MBH OUTPUT

240 320 240 320 240 320

COOLING WITH ELECTRIC HEAT

176 176 174 174 234 234 232 232 290 290 287 284 8.7 8.6 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 9.2 9.1 8.7 8.7 8.05 8.05 8.05 8.05 8.6 8.6 8.2 8.2

NOTE: All gas units are two-stage heating. First stage is 50% of total. S.S.E. = Steady State Efficiency (80%) - output divided by input.

1. Certified in accordance with the Unitary Large Equipment certification program which is based on ARI Standard 340/360. 2. EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu's per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt). 3. IPLV = Integrated Part Load Value.

8

Unitary Products Group

262259-YTG-A-0706

TABLE 4: DM 180 COOLING CAPACITIES (15 TON)

TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL CFM WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 85°F TOTAL POWER CAP.1 INPUT2 MBH KW 227 202 187 187 220 199 181 181 213 195 176 176 207 187 170 170 200 179 165 165 17.5 16.8 16.2 16.1 17.3 16.7 16.1 16.0 17.2 16.5 16.0 15.9 17.0 16.3 15.8 15.7 16.8 16.1 15.6 15.5 SENSIBLE CAPACITY1, MBH ENTERING DRY BULB, °F 86 176 202 187 187 162 192 181 181 149 181 176 176 137 165 170 170 125 149 165 165 83 154 187 187 187 142 175 181 181 131 163 176 176 121 149 169 170 111 136 163 165 80 132 165 187 187 122 155 180 181 113 145 172 176 105 133 161 164 98 122 149 152 77 110 143 165 165 102 135 159 161 95 127 154 158 89 118 145 148 84 108 135 138 74 88 121 143 143 82 115 139 141 77 108 136 139 73 102 129 132 70 95 122 125 71 99 121 121 94 119 121 90 118 121 86 113 116 81 108 111 68 99 99 99 101 100 103 97 100 94 97 TOTAL CAP.1 MBH 213 189 175 175 208 186 170 170 202 184 166 166 196 176 161 161 189 168 156 156 POWER INPUT2 KW 18.4 17.7 17.0 17.0 18.3 17.6 16.9 16.9 18.1 17.4 16.8 16.7 17.9 17.2 16.6 16.5 17.6 17.0 16.3 16.3 86 169 189 175 175 157 183 170 170 144 177 166 166 132 161 161 161 119 144 156 156 95°F SENSIBLE CAPACITY1, MBH ENTERING DRY BULB, °F 83 147 180 175 175 136 169 170 170 126 159 166 166 116 145 160 161 106 130 154 156 80 125 158 175 175 116 149 170 170 108 141 165 166 100 129 153 154 92 117 141 141 77 102 136 153 153 96 129 150 150 90 123 147 148 84 113 137 138 78 103 127 128 74 80 114 131 131 76 109 130 130 72 104 129 130 68 97 121 122 65 90 113 114 71 92 109 109 89 110 110 86 111 111 81 105 106 76 100 100 68 87 87 90 90 93 93 89 90 86 87

7200

6750

6000

5250

4500

TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL CFM WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 105°F TOTAL POWER CAP.1 MBH 199 176 165 165 194 174 161 161 188 171 156 156 183 164 152 152 177 157 147 147 INPUT2 KW 19.3 18.5 17.9 17.9 19.1 18.3 17.7 17.8 19.0 18.2 17.6 17.6 18.8 18.0 17.4 17.4 18.5 17.8 17.2 17.2 86 164 176 165 165 152 172 161 161 139 168 156 156 127 153 152 152 115 139 147 147 SENSIBLE CAPACITY1, MBH ENTERING DRY BULB, °F 83 142 172 165 165 131 162 161 161 121 153 156 156 111 139 151 152 102 126 147 147 80 120 153 165 165 111 144 161 161 103 135 156 156 95 123 144 145 88 112 133 133 77 98 131 143 143 91 124 140 141 85 117 137 138 80 108 128 129 74 98 119 120 74 76 109 121 121 71 104 120 121 67 98 119 120 64 92 112 113 61 85 106 106 71 87 99 99 83 100 101 80 101 102 76 97 97 71 92 92 68 77 77 80 80 83 84 81 81 78 79 TOTAL CAP.1 MBH 185 164 155 155 180 161 151 151 174 158 146 146 170 152 143 143 165 147 139 139 POWER INPUT2 KW 20.2 19.3 18.7 18.8 20.0 19.1 18.6 18.7 19.8 18.9 18.4 18.5 19.6 18.8 18.2 18.3 19.4 18.6 18.0 18.1 86 159 164 155 155 147 161 151 151 134 158 146 146 123 146 143 143 111 135 139 139 115°F SENSIBLE CAPACITY1, MBH ENTERING DRY BULB, °F 83 137 164 155 155 127 155 151 151 116 147 146 146 107 134 142 143 97 121 139 139 80 115 148 155 155 106 138 151 151 98 129 146 146 91 118 136 136 84 107 125 125 77 93 125 133 134 86 118 131 131 80 111 128 128 75 102 120 120 70 94 111 112 74 71 103 111 112 66 98 111 111 61 92 110 110 59 86 104 104 56 80 98 98 71 81 89 90 78 90 91 74 92 92 70 88 88 66 84 85 68 67 68 70 71 73 74 72 72 70 71

7200

6750

6000

5250

4500

1. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance Table for the KW of the supply air blower motor. 2. These ratings include the condenser fan motors (Total 1.5 KW) and the compressor motors but not the supply air blower motor. NOTE: 1st stage of cooling capacity is 66% of total values shown above. Nominal Rating

Unitary Products Group

9

262259-YTG-A-0706

TABLE 5: DM 240 COOLING CAPACITIES (20 TON)

TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL CFM WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 85°F TOTAL POWER CAP.1 INPUT2 MBH KW 308 270 240 240 299 266 233 233 290 262 227 227 285 254 223 223 280 246 219 219 23.5 22.5 21.9 21.3 23.3 22.3 21.7 21.2 23.1 22.1 21.5 21.0 23.0 22.0 21.5 20.9 22.9 21.9 21.4 20.8 SENSIBLE CAPACITY1, MBH ENTERING DRY BULB, °F 86 243 270 240 240 224 258 233 233 205 246 227 227 189 224 223 223 172 203 219 219 83 213 254 240 240 197 238 233 233 181 222 227 227 167 203 218 220 154 185 209 214 80 183 225 240 240 170 211 231 233 157 198 221 227 146 182 206 211 135 166 190 195 77 153 195 210 210 143 184 204 207 133 174 197 203 125 161 185 190 117 148 172 177 74 123 165 180 180 116 158 177 180 109 150 173 179 104 140 163 169 98 129 153 158 71 135 150 150 131 150 153 127 150 155 119 142 148 111 135 140 68 120 120 123 126 126 131 121 126 116 121 TOTAL CAP.1 MBH 290 259 230 230 282 254 223 223 273 250 216 216 267 241 211 211 260 232 206 206 POWER INPUT2 KW 25.2 23.8 23.2 22.6 24.9 23.6 23.0 22.4 24.6 23.3 22.7 22.1 24.4 23.1 22.5 21.9 24.2 22.9 22.3 21.7 86 235 259 230 230 216 247 223 223 196 235 216 216 182 216 211 211 167 197 206 206 95°F SENSIBLE CAPACITY1, MBH ENTERING DRY BULB, °F 83 205 246 230 230 189 229 223 223 172 211 216 216 160 195 209 211 148 179 202 206 80 175 216 230 230 162 202 220 223 148 188 209 216 139 174 196 203 130 160 183 189 77 145 186 200 200 135 175 193 196 125 164 186 193 118 153 175 182 111 142 165 171 74 116 156 170 170 108 148 166 169 101 140 162 169 97 132 154 161 93 123 146 152 71 126 140 140 121 139 142 116 138 145 110 133 139 105 128 134 68 110 110 112 116 114 121 112 118 109 115

9400

9000

8000

7000

6000

TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL CFM WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 105°F TOTAL POWER CAP.1 MBH 269 241 218 218 263 237 213 213 256 234 208 208 249 226 202 202 243 217 197 197 INPUT2 KW 26.4 24.9 24.2 23.6 26.1 24.7 24.0 23.4 25.9 24.5 23.8 23.2 25.7 24.3 23.7 23.1 25.6 24.2 23.6 23.0 86 224 241 218 218 206 234 213 213 188 227 208 208 175 210 202 202 161 192 197 197 SENSIBLE CAPACITY1, MBH ENTERING DRY BULB, °F 83 194 234 218 218 179 219 213 213 164 204 208 208 153 189 201 202 143 174 195 197 80 164 206 218 218 152 193 210 213 140 180 201 208 132 168 189 195 124 155 177 183 77 134 176 189 189 126 166 183 186 117 156 177 184 111 147 168 174 106 137 159 165 74 104 146 159 159 99 139 156 159 93 133 153 160 90 125 147 153 87 118 140 146 71 116 129 129 112 129 132 109 129 136 104 126 132 100 122 128 68 99 99 102 106 106 112 104 111 103 109 TOTAL CAP.1 MBH 248 222 207 207 243 221 203 203 238 219 199 199 232 210 194 194 226 202 189 189 POWER INPUT2 KW 27.6 26.0 25.3 24.7 27.3 25.8 25.1 24.5 27.1 25.6 24.8 24.3 27.1 25.6 24.8 24.2 27.0 25.5 24.8 24.2 86 213 222 207 207 197 221 203 203 180 219 199 199 168 203 194 194 155 187 189 189 115°F SENSIBLE CAPACITY1, MBH ENTERING DRY BULB, °F 83 183 222 207 207 170 210 203 203 156 197 199 199 146 183 194 194 137 169 189 189 80 153 195 207 207 143 184 200 203 132 173 192 199 125 162 182 188 118 150 171 177 77 123 165 177 177 116 157 173 176 109 149 168 175 104 141 161 167 100 132 153 159 74 93 135 147 147 89 130 146 149 85 125 145 151 83 119 140 146 81 113 134 140 71 105 118 118 103 119 122 102 121 127 98 118 124 95 116 122 68 88 88 92 95 97 103 97 103 97 103

9400

9000

8000

7000

6000

1. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance Table for the KW of the supply air blower motor. 2. These ratings include the condenser fan motors (Total 2.3 KW) and the compressor motors but not the supply air blower motor.

Nominal Rating

10

Unitary Products Group

262259-YTG-A-0706

TABLE 6: DM 300 COOLING CAPACITIES (25 TON)

TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL CFM WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 85°F TOTAL POWER CAP.1 INPUT2 MBH KW 371 340 329 329 365 336 324 324 359 332 318 318 354 326 314 314 349 321 310 310 318 290 282 282 27.1 26.1 25.5 25.5 27.0 25.9 25.3 25.3 26.8 25.7 25.2 25.1 26.6 25.5 25.0 25.0 26.4 25.3 24.8 24.8 25.2 24.0 23.7 23.7 SENSIBLE CAPACITY1, MBH ENTERING DRY BULB, °F 86 277 335 329 329 260 317 324 324 244 298 318 318 229 280 314 314 215 262 310 310 186 226 277 281 83 240 299 329 329 226 283 324 324 213 268 318 318 201 252 306 308 190 237 293 297 167 206 258 262 80 203 262 329 329 193 249 313 315 182 237 296 301 173 224 282 286 165 212 268 272 148 187 240 243 77 167 226 293 292 159 216 279 281 151 206 265 270 145 196 254 258 140 187 243 247 129 168 221 224 74 130 189 256 256 125 182 245 247 120 175 235 239 117 168 226 230 115 162 218 222 110 149 201 205 71 152 219 219 148 212 214 144 204 208 141 198 203 137 193 197 130 192 186 68 116 183 183 114 178 180 113 173 177 113 170 175 112 168 172 111 163 167 TOTAL CAP.1 MBH 354 325 315 314 348 321 309 309 342 317 304 304 338 312 300 300 334 307 297 297 304 277 270 270 POWER INPUT2 KW 28.8 27.7 27.1 27.1 28.6 27.5 26.9 26.9 28.5 27.4 26.8 26.7 28.2 27.1 26.5 26.5 28.0 26.9 26.3 26.3 26.8 25.5 25.2 25.2 86 268 324 315 314 257 312 309 309 245 301 304 304 228 279 300 300 211 257 297 297 177 213 262 266 95°F SENSIBLE CAPACITY1, MBH ENTERING DRY BULB, °F 83 231 288 315 314 223 279 309 309 214 270 304 304 200 251 295 297 186 232 287 291 158 194 243 247 80 195 251 315 314 189 245 307 309 184 239 299 304 172 223 280 285 161 207 262 266 138 175 225 228 77 158 214 278 278 155 211 273 275 153 208 268 273 144 195 253 257 136 182 237 241 119 156 206 209 74 122 178 241 241 122 178 239 242 122 177 237 242 116 167 225 229 111 157 212 216 100 137 187 190 71 141 205 205 144 206 208 146 207 211 139 197 201 132 187 191 118 167 171 68 105 168 168 110 172 174 115 176 180 111 169 173 107 162 166 99 148 152

12000

11000

10000

9000

8000

6000

TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL CFM WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 105°F TOTAL POWER CAP.1 MBH 337 310 300 299 331 306 295 294 326 302 290 290 322 297 286 286 319 293 283 283 290 264 258 258 INPUT2 KW 30.7 29.5 28.8 28.8 30.5 29.3 28.5 28.5 30.2 29.0 28.3 28.2 30.0 28.8 28.1 28.1 29.8 28.6 28.0 28.0 28.3 26.9 26.6 26.6 86 264 309 300 299 254 302 295 294 244 294 290 290 228 276 286 286 212 259 283 283 180 224 258 258 SENSIBLE CAPACITY1, MBH ENTERING DRY BULB, °F 83 228 283 300 299 221 276 295 294 213 268 290 290 200 251 284 285 187 234 278 280 161 200 241 242 80 191 246 300 299 187 242 294 294 183 237 287 290 172 223 271 273 162 209 255 257 141 181 223 224 77 155 210 263 263 153 208 260 261 152 206 256 259 144 195 243 245 137 184 230 232 122 162 204 205 74 118 173 226 226 119 174 226 227 121 176 226 228 116 167 215 217 112 159 205 207 103 142 184 186 71 137 190 190 141 192 193 145 195 197 139 187 189 134 180 182 123 165 167 68 100 153 153 107 159 160 114 164 166 111 159 161 109 155 157 104 146 148 TOTAL CAP.1 MBH 320 294 285 285 315 291 280 280 310 287 276 275 306 283 272 272 303 278 269 269 276 251 245 245 POWER INPUT2 KW 32.6 31.3 30.5 30.5 32.3 31.0 30.3 30.3 32.1 30.8 30.0 29.9 31.8 30.5 29.8 29.7 31.6 30.3 29.6 29.6 30.0 28.5 28.2 28.2 86 261 294 285 285 252 291 280 280 243 287 276 275 228 274 272 272 213 260 269 269 183 222 245 245 115°F SENSIBLE CAPACITY1, MBH ENTERING DRY BULB, °F 83 224 278 285 285 218 273 280 280 212 267 276 275 200 251 272 272 188 235 269 269 164 203 239 240 80 188 242 285 285 185 239 280 280 181 236 276 275 172 223 262 261 163 210 248 248 145 194 220 221 77 151 205 248 248 151 205 246 246 151 205 245 244 144 195 234 234 138 185 223 223 125 165 201 202 74 114 169 212 211 117 171 213 213 120 174 214 214 116 167 206 206 113 160 198 198 106 146 182 182 71 132 175 175 138 179 179 143 183 183 139 178 178 135 173 173 127 163 163 68 95 138 138 104 145 145 112 152 152 111 150 150 110 148 148 108 144 144

12000

11000

10000

9000

8000

6000

1. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance Table for the KW of the supply air blower motor. 2. These ratings include the condenser fan motors (Total 2.3 KW) and the compressor motors but not the supply air blower motor.

Nominal Rating

Unitary Products Group

11

262259-YTG-A-0706

CFM, STATIC PRESSURE, AND POWER - ALTITUDE AND TEMPERATURE CORRECTIONS

The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level. The air flow rates listed in the standard blower performance tables are based on standard air at sea level. As the altitude or temperature increases, the density of air decreases. In

order to use the indoor blower tables for high altitude applications, certain corrections are necessary. A centrifugal fan is a "constant volume" device. This means that, if the rpm remains constant, the CFM delivered is the same regardless of the density of the air. However, since the air at high altitude is less dense, less static pressure will be generated and less power will be required than a similar application at sea level. Air density correction factors are shown in Table 7 and Figure 2.

TABLE 7: ALTITUDE CORRECTION FACTORS

AIR TEMP 40 50 60 70 80 90 100 0 1.060 1.039 1.019 1.000 0.982 0.964 0.946 1000 1.022 1.002 0.982 0.964 0.947 0.929 0.912 2000 0.986 0.966 0.948 0.930 0.913 0.897 0.880 3000 0.950 0.931 0.913 0.896 0.880 0.864 0.848 ALTITUDE (FEET) 4000 5000 0.916 0.882 0.898 0.864 0.880 0.848 0.864 0.832 0.848 0.817 0.833 0.802 0.817 0.787 6000 0.849 0.832 0.816 0.801 0.787 0.772 0.758 7000 0.818 0.802 0.787 0.772 0.758 0.744 0.730 8000 0.788 0.772 0.757 0.743 0.730 0.716 0.703 9000 0.758 0.743 0.729 0.715 0.702 0.689 0.676 10000 0.729 0.715 0.701 0.688 0.676 0.663 0.651

The examples below will assist in determining the airflow performance of the product at altitude. Example 1: What are the corrected CFM, static pressure, and BHP at an elevation of 5,000 ft. if the blower performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP? Solution: At an elevation of 5,000 ft the indoor blower will still deliver 6,000 CFM if the rpm is unchanged. However, Table 7 must be used to determine the static pressure and BHP. Since no temperature data is given, we will assume an air temperature of 70°F. Table 7 shows the correction factor to be 0.832. Corrected static pressure = 1.5 x 0.832 = 1.248 IWC Corrected BHP = 4.0 x 0.832 = 3.328 Example 2: A system, located at 5,000 feet of elevation, is to deliver 6,000 CFM at a static pressure of 1.5". Use the unit

blower tables to select the blower speed and the BHP requirement. Solution: As in the example above, no temperature information is given so 70°F is assumed. The 1.5" static pressure given is at an elevation of 5,000 ft. The first step is to convert this static pressure to equivalent sea level conditions. Sea level static pressure = 1.5 / .832 = 1.80" Enter the blower table at 6000 sCFM and static pressure of 1.8". The rpm listed will be the same rpm needed at 5,000 ft. Suppose that the corresponding BHP listed in the table is 3.2. This value must be corrected for elevation. BHP at 5,000 ft = 3.2 x .832 = 2.66

12

Unitary Products Group

262259-YTG-A-0706

Altitude/Temperature Conversion Factor

1.100

CORRECTION FACTOR

1.000

SEA LEVEL 1000 ft

0.900

2000 3000 4000

0.800

5000 6000 7000 8000 9000 10,000

0.700

0.600 40 50

TEMPERATURE (°F)

60

70

80

90

100

FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR

Unitary Products Group

13

262259-YTG-A-0706

TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - COOLING ONLY 180 MBH - BOTTOM DUCT CONNECTIONS

BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* 6.0** 5.5 4.5 3.5 3.0 2.0 1.0 6.0 5.5 4.5 3.5 3.0 2.0 1.0 6.0** 5.0 4.0 3.5 2.0 1.0 6.0 4.5 4.0 3.5 2.5 1.5 1.0 CFM 4500 ESP 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.2 1.3 1.5 1.6 1.7 1.9 2.1 1.0 1.1 1.2 1.3 1.5 1.6 1.3 1.5 1.6 1.7 1.9 2.1 2.2 BHP 2.4 2.5 2.6 2.9 3.0 3.1 3.2 2.9 3.0 3.2 3.4 3.5 3.7 3.9 2.4 2.6 2.9 3.0 3.2 3.3 2.9 3.2 3.4 3.5 3.7 3.9 4.0 KW 2.2 2.3 2.4 2.6 2.7 2.8 2.9 2.6 2.7 2.9 3.0 3.1 3.3 3.5 2.2 2.4 2.6 2.7 2.9 3.0 2.6 2.9 3.0 3.1 3.3 3.5 3.6 ESP 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.0 1.1 1.3 1.4 1.5 1.7 2.0 0.8 0.9 1.0 1.1 1.3 1.4 1.1 1.3 1.4 1.5 1.7 2.0 2.1 5250 BHP 3.0 3.1 3.4 3.6 3.7 3.8 3.9 3.6 3.7 3.9 4.0 4.2 4.5 4.7 3.1 3.3 3.6 3.7 3.9 4.0 3.7 3.9 4.0 4.2 4.5 4.7 4.8 KW 2.7 2.8 3.0 3.2 3.3 3.4 3.5 3.2 3.3 3.5 3.6 3.8 4.0 4.2 2.8 3.0 3.2 3.3 3.5 3.6 3.3 3.5 3.6 3.8 4.0 4.2 4.3 ESP 0.5 0.6 0.7 0.8 0.9 1.0 1.1 0.8 0.9 1.1 1.2 1.3 1.5 1.8 0.6 0.7 0.8 0.9 1.1 1.2 0.9 1.1 1.2 1.3 1.5 1.8 2.0 6000 BHP 3.2 3.5 3.7 4.0 4.1 4.2 4.5 4.0 4.1 4.5 4.7 4.9 5.1 5.5 3.5 3.7 4.0 4.1 4.5 4.7 4.1 4.5 4.7 4.9 5.1 5.5 5.7 KW 2.9 3.1 3.3 3.6 3.7 3.8 4.0 3.6 3.7 4.0 4.2 4.4 4.6 4.9 3.1 3.3 3.6 3.7 4.0 4.2 3.7 4.0 4.2 4.4 4.6 4.9 5.1 ESP 0.2 0.3 0.5 0.6 0.7 0.9 0.5 0.6 0.8 1.0 1.2 0.2 0.3 0.5 0.6 0.9 1.0 0.6 0.9 1.0 1.2 6750 BHP 4.1 4.4 4.7 4.8. 5.0 5.2 4.7 4.8 5.1 5.5 5.7 4.1 4.4 4.7 4.8 5.3 5.5 4.8 5.3 5.5 5.7 KW 3.7 3.9 4.2 4.3 4.5 4.7 4.2 4.3 4.6 4.9 5.1 3.7 3.9 4.2 4.3 4.7 4.9 4.3 4.7 4.9 5.1 ESP 0.2 0.4 0.5 0.6 0.7 0.4 0.5 0.7 0.2 0.4 0.5 0.7 0.5 0.7 7200 BHP 4.5 4.9 5.1 5.4 5.7 5.0 5.1 5.6 4.5 5.0 5.1 5.7 5.1 5.7 KW 4.0 4.4 4.6 4.8 5.1 4.4 4.6 5.0 4.0 4.4 4.6 5.1 4.6 5.1 -

208 VOLT AND STANDARD DRIVE 850 870 915 965 980 1010 1040 965 980 1025 1065 1095 1130 1170 870 915 965 980 1040 1065 980 1040 1065 1095 1130 1170 1190 NOTES:

208 VOLT AND HIGH SPEED DRIVE

230/460/575 VOLT AND STANDARD DRIVE

230/460/575 VOLT AND HIGH SPEED DRIVE

1. Blower performance includes fixed outdoor air, 2" T/A filters, a dry evaporator coil and no electric heat. 2. Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

14

Unitary Products Group

262259-YTG-A-0706

TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - COOLING ONLY 240 MBH - BOTTOM DUCT CONNECTIONS

BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* 6.0** 5.0 4.0 3.0 2.0 1.0 6.0 5.0 4.0 3.5 3.0 2.5 2.0 1.0 6.0** 5.0 4.0 3.5 2.5 1.5 1.0 6.0 5.0 4.0 3.5 3.0 2.0 1.5 1.0 CFM 6000 ESP 0.4 0.8 1.1 1.3 1.6 1.9 1.3 1.6 1.8 1.9 2.0 2.1 2.3 2.4 0.4 0.8 1.1 1.3 1.6 1.9 2.0 1.3 1.6 1.9 2.0 2.1 2.3 2.4 2.5 BHP 2.1 3.2 4.1 4.6 5.3 5.9 4.6 5.3 5.8 6.1 6.2 6.4 6.6 6.7 2.1 3.2 4.1 4.6 5.3 5.9 6.1 4.6 5.3 5.9 6.2 6.4 6.6 6.7 6.8 KW 1.8 2.7 3.4 3.9 4.5 5.0 3.9 4.5 4.9 5.1 5.2 5.4 5.5 5.6 1.8 2.7 3.4 3.9 4.5 5.0 5.1 3.9 4.5 5.0 5.2 5.4 5.5 5.6 5.7 ESP 0.1 0.5 0.9 1.1 1.4 1.7 1.1 1.4 1.7 1.8 1.9 2.0 2.1 2.2 0.1 0.5 0.9 1.1 1.4 1.7 1.8 1.1 1.4 1.7 1.9 2.0 2.1 2.2 2.3 7000 BHP 2.3 3.5 4.5 5.1 5.8 6.5 5.1 5.8 6.3 6.5 6.8 7.0 7.2 7.3 2.3 3.5 4.5 5.1 5.8 6.5 6.6 5.1 5.8 6.5 6.8 7.0 7.2 7.3 7.4 KW 2.0 2.9 3.8 4.3 4.9 5.5 4.3 4.9 5.3 5.5 5.7 5.9 6.0 6.1 2.0 2.9 3.8 4.3 4.9 5.5 5.6 4.3 4.9 5.5 5.7 5.9 6.0 6.1 6.2 ESP 0.2 0.6 0.8 1.2 1.5 0.8 1.2 1.5 1.6 1.7 1.8 1.9 2.1 0.2 0.6 0.8 1.2 1.5 1.6 0.8 1.2 1.5 1.7 1.8 1.9 2.1 2.2 8000 BHP 3.8 4.9 5.5 6.3 7.0 5.5 6.3 6.9 7.1 7.4 7.6 7.8 7.9 3.8 4.9 5.5 6.3 7.0 7.3 5.5 6.3 7.0 7.4 7.6 7.8 7.9 8.1 KW 3.2 4.1 4.6 5.3 5.9 4.6 5.3 5.8 6.0 6.2 6.4 6.6 6.7 3.2 4.1 4.6 5.3 5.9 6.1 4.6 5.3 5.9 6.2 6.4 6.6 6.7 6.8 ESP 0.1 0.4 0.7 1.0 0.4 0.7 1.0 1.1 1.2 1.3 1.5 0.1 0.4 0.7 1.0 1.1 0.4 0.7 1.0 1.2 1.3 1.5 9000 BHP 5.1 5.9 6.9 7.7 5.9 6.9 7.5 7.8 8.1 8.3 8.6 5.1 5.9 6.9 7.7 7.9 5.9 6.9 7.7 8.1 8.3 8.6 KW 4.3 5.0 5.8 6.5 5.0 5.8 6.3 6.6 6.8 7.0 7.2 4.3 5.0 5.8 6.5 6.7 5.0 5.8 6.5 6.8 7.0 7.2 ESP 0.2 0.6 0.2 0.5 0.6 0.7 0.2 0.6 0.7 0.2 0.6 0.7 9400 BHP 7.3 8.2 7.3 7.9 8.3 8.6 7.3 8.2 8.6 7.3 8.2 8.6 KW 6.1 6.9 6.1 6.7 7.0 7.3 6.1 6.9 7.3 6.1 6.9 7.3 -

208 VOLT AND STANDARD DRIVE 870 900 930 950 980 1015 950 980 1010 1020 1035 1050 1075 1100 870 900 930 950 980 1015 1025 950 980 1015 1035 1050 1080 1100 1120 NOTES:

208 VOLT AND HIGH SPEED DRIVE

230/460/575 VOLT AND STANDARD DRIVE

230/460/575 VOLT AND HIGH SPEED DRIVE

1. Blower performance includes fixed outdoor air, 2" T/A filters, a dry evaporator coil and no electric heat. 2. Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

Unitary Products Group

15

262259-YTG-A-0706

TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - GAS HEAT 180 MBH - BOTTOM DUCT CONNECTIONS

BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* 6.0** 5.5 4.5 3.5 3.0 2.0 1.0 6.0 5.5 4.5 3.5 2.0 1.0 6.0** 5.0 4.0 3.5 2.5 1.5 1.0 6.0 4.5 4.0 2.5 1.5 1.0 CFM 4500 ESP 0.9 1.0 1.1 1.2 1.3 1.4 1.6 1.2 1.3 1.4 1.6 1.9 2.1 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.3 1.6 1.7 1.9 2.1 2.2 BHP 2.4 2.5 2.6 2.7 2.9 3.0 3.2 2.7 2.9 3.1 3.4 3.6 3.9 2.5 2.6 2.7 2.9 3.0 3.1 3.4 2.9 3.2 3.4 3.6 3.9 4.0 KW 2.1 2.2 2.4 2.5 2.6 2.7 2.9 2.5 2.6 2.8 3.0 3.2 3.5 2.2 2.4 2.5 2.6 2.7 2.8 3.0 2.6 2.9 3.0 3.2 3.5 3.6 ESP 0.6 0.7 0.8 0.9 1.0 1.1 1.3 0.9 1.0 1.2 1.4 1.7 1.9 0.7 0.8 0.9 1.0 1.1 1.2 1.4 1.0 1.3 1.4 1.7 1.8 1.9 5250 BHP 2.9 3.0 3.1 3.2 3.4 3.6 3.8 3.2 3.4 3.6 3.9 4.4 4.7 3.0 3.1 3.2 3.4 3.6 3.7 3.9 3.4 3.8 3.9 4.4 4.7 4.8 KW 2.6 2.7 2.8 2.9 3.0 3.2 3.4 2.9 3.0 3.2 3.5 3.9 4.2 2.7 2.8 2.9 3.0 3.2 3.3 3.5 3.0 3.4 3.5 3.9 4.2 4.3 ESP 0.3 0.4 0.5 0.6 0.7 0.8 1.0 0.6 0.7 0.9 1.1 1.4 1.6 0.4 0.5 0.6 0.7 0.8 0.9 1.1 0.7 1.0 1.1 1.4 1.6 1.7 6000 BHP 3.4 3.5 3.6 3.7 3.8 4.0 4.4 3.7 3.8 4.1 4.5 5.0 5.5 3.5 3.6 3.7 3.8 4.0 4.2 4.5 3.8 4.4 4.5 5.0 5.5 5.6 KW 3.0 3.1 3.2 3.3 3.4 3.6 3.9 3.3 3.4 3.7 4.0 4.5 4.9 3.1 3.2 3.3 3.4 3.6 3.8 4.0 3.4 3.9 4.0 4.5 4.9 5.0 ESP 0.2 0.4 0.5 0.6 0.8 0.4 0.5 0.7 0.9 1.2 0.2 0.4 0.5 0.6 0.7 0.9 0.5 0.8 0.9 1.2 6750 BHP 4.1 4.4 4.5 4.7 5.0 4.4 4.5 4.8 5.1 5.8 4.1 4.4 4.5 4.7 4.9 5.1 4.5 5.0 5.1 5.8 KW 3.7 3.0 4.0 4.2 4.5 3.9 4.0 4.3 4.6 5.2 3.7 3.9 4.0 4.2 4.4 4.6 4.0 4.5 4.6 5.2 ESP 0.2 0.3 0.4 0.6 0.2 0.3 0.4 0.2 0.3 0.4 0.5 0.3 0.6 7200 BHP 5.0 5.1 5.4 5.6 5.0 5.1 5.5 5.0 5.1 5.4 5.7 5.1 5.6 KW 4.5 4.6 4.8 5.0 4.5 4.6 4.9 4.5 4.6 4.8 5.1 4.6 5.0 -

208 VOLT AND STANDARD DRIVE 850 870 915 965 980 1010 1040 965 980 1025 1065 1125 1170 870 915 965 980 1015 1050 1065 980 1045 1065 1125 1170 1190 NOTES:

208 VOLT AND HIGH SPEED DRIVE

230/460/575 VOLT AND STANDARD DRIVE

230/460/575 VOLT AND HIGH SPEED DRIVE

1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil. 2. Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

16

Unitary Products Group

262259-YTG-A-0706

TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - GAS HEAT 240 MBH - BOTTOM DUCT CONNECTIONS

BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* 6.0** 5.0 4.0 3.0 2.0 1.5 1.0 6.0 5.0 4.5 3.5 2.5 2.0 1.0 6.0** 5.0 4.0 3.5 2.5 2.0 1.5 1.0 6.0 5.0 4.5 4.0 3.5 3.0 2.5 1.5 1.0 CFM 6000 ESP 1.3 1.4 1.6 1.7 1.9 2.1 2.2 1.7 1.9 2.1 2.3 2.5 2.6 2.9 1.3 1.4 1.6 1.7 1.9 2.1 2.2 2.3 1.7 1.9 2.1 2.2 2.3 2.5 2.6 2.9 3.1 BHP 3.6 3.8 4.1 4.2 4.5 4.6 4.8 4.2 4.5 4.5 4.9 5.1 5.3 5.6 3.6 3.8 4.1 4.2 4.5 4.6 4.8 4.9 4.2 4.5 4.6 4.8 4.9 5.1 5.3 5.6 5.8 KW 3.0 3.2 3.4 3.6 3.8 3.9 4.0 3.6 3.8 3.9 4.1 4.3 4.4 4.7 3.0 3.2 3.4 3.6 3.8 3.9 4.0 4.1 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.7 4.9 ESP 0.7 0.9 1.1 1.3 1.5 1.6 1.7 1.3 1.5 1.6 1.8 2.0 2.1 2.3 0.7 0.9 1.1 1.3 1.5 1.6 1.7 1.8 1.3 1.5 1.6 1.7 1.8 2.0 2.1 2.3 2.5 7000 BHP 4.3 4.7 5.0 5.1 5.4 5.5 4.7 5.1 5.4 5.5 5.8 6.1 6.3 6.8 4.3 4.7 5.0 5.1 5.4 5.5 5.7 5.8 5.1 5.4 5.5 5.7 5.8 6.1 6.3 6.8 7.0 KW 3.7 4.0 4.2 4.3 4.5 4.7 4.8 4.3 4.5 4.7 4.9 5.1 5.3 5.7 3.7 4.0 4.2 4.3 4.5 4.7 4.8 4.9 4.3 4.5 4.7 4.8 4.9 5.1 5.3 4.7 5.9 ESP 0.2 0.4 0.6 0.8 1.0 1.1 1.2 0.8 1.0 1.1 1.3 1.4 1.5 1.8 0.2 0.4 0.6 0.8 1.0 1.1 1.2 1.3 0.8 1.0 1.1 1.2 1.3 1.4 1.5 1.8 1.9 8000 BHP 5.1 5.6 5.9 6.0 6.3 6.4 6.6 6.0 6.3 6.4 6.7 7.1 7.3 7.9 5.1 5.6 5.9 6.0 6.3 6.4 6.6 6.7 6.0 6.3 6.4 6.6 6.7 7.1 7.3 7.9 8.3 KW 4.3 4.7 5.0 5.1 5.3 5.4 5.6 5.1 5.3 5.4 5.7 6.0 6.2 6.6 4.3 4.7 5.0 5.1 5.3 5.4 5.6 5.7 5.1 5.3 5.4 5.6 5.7 6.0 6.2 6.6 6.9 ESP 0.1 0.2 0.4 0.5 0.7 0.2 0.4 0.5 0.7 0.9 1.0 0.1 0.2 0.4 0.5 0.6 0.7 0.2 0.4 0.5 0.6 0.7 0.9 1.0 9000 BHP 6.7 6.9 7.2 7.5 7.8 6.9 7.2 7.5 8.0 8.4 8.6 6.7 6.9 7.2 7.5 7.8 8.0 6.9 7.2 7.5 7.8 8.0 8.4 8.6 KW 5.7 5.8 6.1 6.3 6.6 5.8 6.1 6.3 6.7 7.0 7.2 5.7 5.8 6.1 6.3 6.6 6.7 5.8 6.1 6.3 6.6 6.7 7.0 7.2 ESP 0.1 0.2 0.1 0.2 0.1 0.2 0.1 0.2 9400 BHP 8.5 8.6 8.5 8.6 8.5 8.6 8.5 8.6 KW 7.1 7.3 7.1 7.3 7.1 7.3 7.1 7.3 -

208 VOLT AND STANDARD DRIVE 870 900 930 950 980 995 1015 950 980 995 1025 1050 1065 1100 870 900 930 950 965 995 1015 1025 950 980 995 1015 1025 1050 1065 1100 1120 NOTES:

208 VOLT AND HIGH SPEED DRIVE

230/460/575 VOLT AND STANDARD DRIVE

230/460/575 VOLT AND HIGH SPEED DRIVE

1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil. 2. Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

Unitary Products Group

17

262259-YTG-A-0706

TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT 300 MBH - BOTTOM DUCT CONNECTIONS

BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* 6.0 5.0 4.0 3.0 2.0 1.0 0.0 6.0 5.0 4.0 3.0 2.0 1.0 0.0 6.0* 5.0 4.0 3.0 2.0 1.0 0.0 6.0 5.0 4.0 3.0 2.0 1.0 0.0 CFM 7500 ESP 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.2 2.5 2.7 3.0 3.2 3.5 3.7 1.4 1.6 1.8 2.0 2.1 2.4 2.6 2.4 2.7 2.9 3.2 3.4 3.7 3.9 BHP 5.9 6.2 6.6 6.9 7.3 7.7 8.0 7.7 8.2 8.6 9.1 9.5 10.0 10.5 5.9 6.2 6.6 6.9 7.3 7.7 8.0 7.7 8.2 8.6 9.1 9.5 10.0 10.5 KW 4.9 5.1 5.4 5.7 6.0 6.3 6.6 6.3 6.7 7.0 7.4 7.8 8.2 8.6 4.9 5.1 5.4 5.7 6.0 6.3 6.6 6.3 6.7 7.0 7.4 7.8 8.2 8.6 ESP 5.0 0.7 0.9 1.1 1.3 1.6 1.8 1.6 1.9 2.1 2.4 2.7 3.0 3.2 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.1 2.3 2.6 2.9 3.1 3.4 3.7 8750 BHP 7.3 7.7 8.1 8.5 8.9 9.3 9.7 9.4 9.9 10.4 11.0 11.5 12.0 12.6 7.3 7.7 8.1 8.5 8.9 9.3 9.7 9.4 9.9 10.4 11.0 11.5 12.0 12.6 KW 6.0 6.3 6.7 7.0 7.3 7.6 8.0 7.7 8.1 8.5 9.0 9.4 9.9 10.3 6.0 6.3 6.7 7.0 7.3 7.6 8.0 7.7 8.1 8.5 9.0 9.4 9.9 10.3 ESP 0.2 0.4 0.6 0.8 1.0 0.9 1.2 1.4 1.7 2.0 2.3 2.6 0.5 0.7 0.9 1.1 1.3 1.6 1.8 1.6 1.9 2.2 2.5 2.7 3.0 3.3 10000 BHP 9.7 10.2 10.6 11.1 11.6 11.2 11.8 12.3 12.9 13.5 14.1 14.7 8.8 9.2 9.7 10.2 10.6 11.1 11.6 11.2 11.8 12.3 12.9 13.5 14.1 14.7 KW 8.0 8.3 8.7 9.1 9.5 9.2 9.7 10.1 10.6 11.1 11.6 12.1 7.2 7.6 8.0 8.3 8.7 9.1 9.5 9.2 9.7 10.1 10.6 11.1 11.6 12.1 ESP 0.2 0.3 0.6 0.9 1.2 1.5 1.8 0.1 0.3 0.6 0.8 1.0 1.3 1.1 1.4 1.7 2.0 2.2 2.6 2.9 11250 BHP 13.5 13.7 14.3 15.0 15.6 16.4 17.0 10.9 11.4 11.9 12.4 13.0 13.5 13.1 13.7 14.3 15.0 15.6 16.4 17.0 KW 11.0 11.2 11.7 12.3 12.8 13.4 13.9 8.9 9.4 9.8 10.2 10.6 11.0 10.7 11.2 11.7 12.3 12.8 13.4 13.9 ESP 0.2 0.4 0.7 0.5 0.8 1.1 1.4 12500 BHP 14.3 14.9 15.5 15.0 15.8 16.4 17.2 KW 11.7 12.2 12.7 12.3 12.9 13.5 14.1 -

208 VOLT AND STANDARD DRIVE 975 1005 1040 1070 1100 1135 1165 1140 1180 1215 1255 1290 1330 1365 975 1005 1040 1070 1100 1135 1165 1140 1180 1215 1255 1290 1330 1365 NOTES:

208 VOLT AND HIGH SPEED DRIVE

230/460/575 VOLT AND STANDARD DRIVE

230/460/575 VOLT AND HIGH SPEED DRIVE

1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil. 2. Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting.

18

Unitary Products Group

262259-YTG-A-0706

TABLE 13: BLOWER MOTOR AND DRIVE DATA

MODEL SIZE MOTOR1 BLOWER RANGE (RPM) HP FRAME EFF. (%) ADJUSTABLE MOTOR PULLEY DESIGNATION OUTSIDE DIA. (IN.) PITCH DIA. (IN.)

2

FIXED BLOWER PULLEY OUTSIDE PITCH DIA. DIA. (IN.) (IN.) 8.75 7.75 11.75 10.75 11.3 9.7 8.4 7.4 11.4 10.4 11.1 9.5

BELT (NOTCHED)

DRIVE

BORE DESIG(IN.) NATION BK90

PITCH BORE DESIGLENGTH QTY. (IN.) NATION (IN.) 1 1 1-3/16 1-3/16 BX81 BX68 BX83 BX81 82.8 69.8 84.8 82.8 86.0 84.0 1 1 1 1 1 1

Standard 850/1065 15 TON High Speed Access High Speed Access 965/1190 5 184 T 83 1VP56 5.35 4.3-5.3 1-1/8

BK80 BK120

Standard 870/1025 20 TON 950/1120 7.5 213 T 89 1VP68 6.75 5.5-6.5

2

1-3/8

BK110 1B5V110

Standard 975/1165 25 TON High 15 Speed 1140/1365 Access 254 T 91 1VP75X 7.5 6.2-7.4 1-5/8

1-7/16 5VX860 1-7/16 5VX840

1B5V94

1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream of any heating device. 2. Do NOT close this pulley below 1 turn open.

TABLE 14: STATIC RESISTANCES1

RESISTANCE, IWG DESCRIPTION 4500 WET INDOOR COIL 18 KW ELECTRIC HEAT OPTIONS 36 KW 54 KW 72 KW ECONOMIZER OPTION HORIZONTAL DUCT CONNECTIONS

2

CFM 15 TON 6000 0.1 0.1 0.2 0.3 0.4 0.1 0.2 7200 0.1 0.1 0.3 0.4 0.6 0.1 0.3 6000 0.1 0.1 0.1 0.2 0.2 0.1 0.2 0.1 0.1 0.1 0.2 0.2 0.1 0.1 20 TON 8000 0.1 0.1 0.2 0.3 0.4 0.1 0.3 9400 0.1 0.1 0.3 0.4 0.6 0.1 0.5 7500 0.11 0.31 0.38 0.62 0.68 0.06 0.36 25 TON 10000 0.11 0.56 0.68 1.10 1.21 0.11 0.32 12500 0.11 0.87 1.07 1.72 1.90 0.18 0.46

1. Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table (See Note 2 for exception.) 2. Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the ESP values on the respective unit's blower performance table.

TABLE 15: POWER EXHAUST PERFORMANCE

MOTOR SPEED HIGH2 MEDIUM LOW

1

STATIC RESISTANCE OF RETURN DUCTWORK, IWG 0.2 CFM

5250 4900 4400

0.3 kW

0.83 0.77 0.72

0.4 kW

0.85 0.79 0.74

0.5 kW

0.88 0.82 0.78

0.6 kW

0.93 0.85 -

CFM

4500 3900 3700

CFM

4200 3500 3000

CFM

3750 2900 -

CFM

3000 -

kW

0.99 -

1. Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection. 2. The factory setting.

Unitary Products Group

19

262259-YTG-A-0706

TABLE 16: DM ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET

COMPRESSORS MODEL (TONNAGE) VOLTAGE

RLA EACH LRA EACH

ID CONV OD FAN BLOWER OUTLET MOTORS MOTOR MODEL AMPS FLA EACH FLA

None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72

HEATER OPTION KW

0.0 13.5 27.0 40.6 54.1 0.0 18.0 36.0 54.0 72.0 0.0 18.0 36.0 54.0 72.0 0.0 18.0 36.0 54.0 72.0 0.0 13.5 27.0 40.6 54.1 0.0 18.0 36.0 54.0 72.0 0.0 18.0 36.0 54.0 72.0 0.0 18.0 36.0 54.0 72.0 0.0 13.5 27.0 40.6 54.1 0.0 18.0 36.0 54.0 72.0 0.0 18.0 36.0 54.0 72.0 0.0 18.0 36.0 54.0 72.0

STAGES

1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2

AMPS

37.5 75.1 112.6 150.1 43.3 86.6 129.9 173.2 21.7 43.3 65.0 86.6 17.3 34.6 52.0 69.3 37.5 75.1 112.6 150.1 43.3 86.6 129.9 173.2 21.7 43.3 65.0 86.6 17.3 34.6 52.0 69.3 37.5 75.1 112.6 150.1 43.3 86.6 129.9 173.2 21.7 43.3 65.0 86.6 17.3 34.6 52.0 69.3

MAX. MIN. FUSE/ CIRCUIT 1 AMPACITY BRKR SIZE (AMPS) (AMPS)

85.4 85.4 111.2 158.4 167.7 85.0 85.0 125.8 147.4 190.7 42.6 42.6 62.9 73.7 95.4 33.7 33.7 49.9 58.6 75.9 110.3 110.3 118.2 165.4 174.7 109.9 109.9 132.8 154.4 197.7 55.1 55.1 66.4 77.2 98.6 44.5 44.5 53.6 62.2 79.5 140.1 140.1 141.9 189.1 198.4 139.7 139.7 156.5 178.2 221.5 68.5 68.5 78.3 89.1 110.7 56.5 56.5 63.6 72.2 89.5 100 100 125 175 200 100 100 150 175 225 50 50 70 90 110 40 40 50 70 90 125 125 125 175 200 125 125 150 175 225 60 60 70 90 110 50 50 60 70 90 175 175 175 200 225 175 175 175 200 250 80 80 80 100 125 70 70 70 80 100

208

19.2

124

4.5

14.0

0.0

230 180 (15) 460

19.2

124

4.3

14.0

0.0

9.6

62

2.2

7.0

0.0

575

7.7

50

1.7

5.3

0.0

208

19.2

124

4.5

19.6

0.0

230 240 (20) 460

19.2

124

4.3

19.6

0.0

9.6

62

2.2

9.8

0.0

575

7.7

50

1.7

8.2

0.0

208

20.7

156

4.5

38.6

0.0

230 300 (25) 460

20.7

156

4.3

38.6

0.0

10.0

75

2.2

19.3

0.0

575

8.2

108

1.7

16.2

0.0

NOTE 1: HACR Type per NEC.

20

Unitary Products Group

262259-YTG-A-0706

TABLE 17: DM ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET

COMPRESSORS MODEL (TONNAGE) VOLTAGE

RLA EACH LRA EACH

ID CONV OD FAN BLOWER OUTLET MOTORS MOTOR MODEL AMPS FLA EACH FLA

None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72 None E18 E36 E54 E72

HEATER OPTION KW

0.0 13.5 27.0 40.6 54.1 0.0 18.0 36.0 54.0 72.0 0.0 18.0 36.0 54.0 72.0 0.0 18.0 36.0 54.0 72.0 0.0 13.5 27.0 40.6 54.1 0.0 18.0 36.0 54.0 72.0 0.0 18.0 36.0 54.0 72.0 0.0 18.0 36.0 54.0 72.0 0.0 13.5 27.0 40.6 54.1 0.0 18.0 36.0 54.0 72.0 0.0 18.0 36.0 54.0 72.0 0.0 18.0 36.0 54.0 72.0

STAGES

1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2

AMPS

37.5 75.1 112.6 150.1 43.3 86.6 129.9 173.2 21.7 43.3 65.0 86.6 17.3 34.6 52.0 69.3 37.5 75.1 112.6 150.1 43.3 86.6 129.9 173.2 21.7 43.3 65.0 86.6 17.3 34.6 52.0 69.3 37.5 75.1 112.6 150.1 43.3 86.6 129.9 173.2 21.7 43.3 65.0 86.6 17.3 34.6 52.0 69.3

MAX. MIN. FUSE/ CIRCUIT 1 AMPACITY BRKR SIZE (AMPS) (AMPS)

95.4 95.4 123.7 170.9 180.2 95.0 95.0 138.3 159.9 203.2 47.6 47.6 69.1 80.0 101.6 37.7 37.7 54.9 63.6 80.9 120.3 120.3 130.7 177.9 187.2 119.9 119.9 145.3 166.9 210.2 60.1 60.1 72.6 83.5 105.1 48.5 48.5 58.6 67.2 84.5 150.1 150.1 154.4 201.6 210.9 149.7 149.7 169.0 190.7 234.0 73.5 73.5 84.5 95.3 117.0 60.5 60.5 68.6 77.2 94.5 110 110 125 175 200 110 110 150 175 225 50 50 70 90 110 45 45 60 70 90 125 125 150 200 200 125 125 150 175 225 70 70 80 90 110 50 50 60 70 90 175 175 175 225 225 175 175 175 225 250 90 90 90 110 125 70 70 70 90 100

208

19.2

124

4.5

14.0

10.0

230 180 (15) 460

19.2

124

4.3

14.0

10.0

9.6

62

2.2

7.0

5.0

575

7.7

50

1.7

5.3

4.0

208

19.2

124

4.5

19.6

10.0

230 240 (20) 460

19.2

124

4.3

19.6

10.0

9.6

62

2.2

9.8

5.0

575

7.7

50

1.7

8.2

4.0

208

20.7

156

4.5

38.6

10.0

230 300 (25) 460

20.7

156

4.3

38.6

10.0

10.0

75

2.2

19.3

5.0

575

8.2

108

1.7

16.2

4.0

NOTE 1: HACR Type per NEC.

Unitary Products Group

21

262259-YTG-A-0706

TABLE 18: DM VOLTAGE LIMITATIONS1

VOLTAGE LIMITATIONS POWER SUPPLY VOLTAGE LIMITATIONS 208/230-3-60 460-3-60 575-3-60 VOLTAGE MIN.

187 414 518

MAX.

253 506 630

1. Utilization Range "A" in accordance with ARI Standard 110.

TABLE 19: PHYSICAL DATA

MODELS

EVAPORATOR BLOWER EVAPORATOR COIL CENTRIFUGAL BLOWER (Dia. x Wd.) FAN MOTOR HP ROWS DEEP FINS PER INCH FACE AREA (Sq. Ft.) PROPELLER DIA. (In.) (Each) FAN MOTOR HP (Each) NOM. CFM TOTAL (Each) ROWS DEEP FINS PER INCH FACE AREA (Sq. Ft.) 5 TON HERMETIC (RECIP.) 10 TON TANDEM (RECIP.) 12.5 TON TANDEM (SCROLL) QUANTITY PER UNIT (12" X 24" X 2" or 4") QUANTITY PER UNIT (16" X 20" X 2" or 4") QUANTITY PER UNIT (16" X 25" X 2" or 4") QUANTITY PER UNIT (18" X 24" X 2" or 4") TOTAL FACE AREA (Sq. Ft.) REFRIGERANT SYSTEM No.1 22 (Lb./Oz.) SYSTEM No. 2 COOLING ONLY BASIC UNIT N24 GAS / ELECTRIC N32 ECONOMIZER ECONOMIZER WITH POWER EXHAUST MOTORIZED DAMPER 18 KW 36 KW ELECTRIC HEATER 54 KW 72 KW ROOF CURB BAROMETRIC DAMPER ECONOMIZER / MOTORIZED DAMPER RAIN HOOD ECONOMIZER / POWER EXHAUST RAIN HOOD WOOD SKID OPTIONS ACCESSORIES

DM180

15x15 5.0 3 15.5

DM240

18x15 7.5 3 13.5 20 30 1 7,200 2 20 43.3 2 4 4 20 18/0 18/0 2100 2300 2340 160 245 150 25 30 35 40 185 45 55 90

DM300

18x15 15 4 25

CONDENSER FAN (Two Per Unit) CONDENSER COIL COMPRESSOR (Qty. Per Unit)

6,500 2 13 36 1 11 5 15 17/8 8/8 1900 2100 2140

7,200 3 15 43.3 2 12 24 20/8 23/8 2730 2930 2970

FILTERS

CHARGE

OPERATING WEIGHTS ( LBS.)

175

185

200

220

220

1. This compressor will be energized first.

22

Unitary Products Group

262259-YTG-A-0706

TABLE 20: ELECTRIC HEAT CORRECTION FACTORS

NOMINAL VOLTAGE 208 240 480 600 VOLTAGE

208 230 460 575

kW CAP. MULTIPLIER

1.00 0.92 0.92 0.92

CONTROL WIRING

COOLING ONLY (24 VOLT THERMOSTAT) THERMOSTAT1 TERMINALS UNIT TERMINAL RC BLOCK 1 TB2 RH R Y1 Y1 ADD Y2 Y2 JUMPER W1 W1 W2 3 G B LED1 LED2 ADD JUMPER COM A1 A2 T T TO REMOTE SENSOR 2THO4702224 IF USED 1Electronic programmable thermostat 2ET04700224 (includes subbase). 2Terminal block 1TB- located on relay board in 24-volt section of the unit control box. 3Second stage heating is not required on units with a single stage electric heater. 4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set-back position. NOTE: Fans switch must be in "ON" position for minimum ventilation during heater operation. W2 G B X

COOLING / HEATING (24 VOLT THERMOSTAT) THERMOSTAT1 UNIT TERMINAL TERMINALS BLOCK 1TB2

RH RC

ADD JUMPER

Y1 Y2 W1 W2 G

3

R Y1 Y2 W1 W2 G B X A1 A2 Y3

24 VOLT TRANSFORMER

NOT USED

4 4

24 VOLT A1 TRANSFORMER A2

24 Volt Thermostat 2TH04701024 or 2TH04701524 (with Subbase 2TB04700324). Terminal strip 1TB - located on relay board in 24-volt section of the unit control box. 3Second stage heating is not required on units with a single stage electric heater.

1 2

POWER WIRING

L1 LINE VOLTAGE TERMINAL L2 BLOCK 2TB L3 IN CONTROL BOX GROUND LUG Refer to the ELECTRICAL DATA tables to size the power wiring, the fuses and the disconnect switch.

FIGURE 3 - DM FIELD WIRING DIAGRAM

Unitary Products Group

23

262259-YTG-A-0706

BLOWER ACCESS BLOWER MOTOR ACCESS BLOWER COMPARTMENT ACCESS (Auxiliary) DOT PLUG (For pressure Drop Reading) ELECTRIC/ GAS HEAT ACCESS VENT AIR OUTLET HOODS COMBUSTION AIR INLET HOOD (C) GAS SUPPLY ENTRY

FIELD-SUPPLIED DISCONNECT SWITCH LOCATION

ECONOMIZER / MOTORIZED DAMPER, FIXED OUTDOOR INTAKE AIR AND POWER EXHAUST RAIN HOODS (See detail "Y") COMPRESSOR ACCESS COIL GUARD 48-5/8"(15 TON) 52-5/8" (20, 25 TON)

CONDENSER COILS 21" 5" 7-1/8" 6-3/8" ) 9-3/4" 5-7/8" 46-5/8" CONTROL BOX 35" ACCESS 11-1/2" BOTTOM SUPPLY AND RETURN AIR OPENINGS (See Note) RETURN AIR 33" SUPPLY AIR 2-3/4" 11-1/8" 21-1/2" All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. (B) POWER WIRING ENTRY 8-1/8" (A) CONTROL WIRING ENTRY 92" (A) CONTROL WIRING ENTRY (B) POWER WIRING ENTRY

N) ) TO TON 15 5 /4"( 20, 2 1 25- /4" ( 1 -1 136

FRONT VIEW

N) TO TON) 5 "(15 1/4 (20, 2 12- /4" -1 35

3-3/4"

UNIT BASE WITH RAILS Shown separately to illustrate Bottom Duct openings, Power and Gas Piping Connection locations

(D) GAS SUPPLY ENTRY

NOTE: For curb mounted units, refer to the curb hanger dimensions of the curb for the proper size of the supply and return air duct connections.

46-5/8" 9-1/4" 12-1/2" 9-3/4"

FIGURE 4 - UNIT DIMENSIONS & CLEARANCES 15, 20 & 25 TON TABLE 21: UTILITIES ENTRY DATA

HOLE A B C D OPENING SIZE (DIA.) 1-1/8" KO 3/4" NPS (Fem.) 3-5/8" KO 3" NPS (Fem.) 2-3/8" KO 1-11/16" Hole USED FOR Control Wiring Power Wiring Side Bottom Side Bottom

Gas Piping (Front)1 Gas Piping (Bottom)1,

2

1. One-inch gas piping NPT required. 2. Opening in the bottom of the unit can be located by the slice in the insulation. NOTE: All entry holes should be field sealed to prevent rain

water entry into the building.

24

Unitary Products Group

262259-YTG-A-0706

EVAPORATOR SECTION

40-3/8"

DOT PLUG (For pressure drop reading) FILTER ACCESS SUPPLY AIR RETURN AIR

COMPRESSOR ACCESS SUPPLY AIR ACCESS

OUTDOOR AIR 40-1/2" 18-5/8" 1" NPT FEMALE COND. DRAIN CONNECTION

OUTDOOR AIR COMPARTMENT ACCESS

Dimensions listed are for side duct flange openings; see Field Accessories for Side Duct Flange Kit.

27-3/4"

RETURN AIR ACCESS

5-1/8"

28-5/8" (15 TON) 39-5/8" (20, 25 TON)

REAR VIEW

FIGURE 5 -

REAR VIEW DIMENSIONS

NOTE:Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For bottom duct applications: 1. Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers. Remove and discard the bottom duct covers. Duct openings are closed with sheet metal covers except when the unit includes a power exhaust option. The covering consists of a heavy black paper composition. Replace the side supply and return air compartment panels. For side duct applications: 1. Replace the side panels on the supply and return air compartments with the side duct flange accessory kit panels. Connect ductwork to the flanges on those panels.

2.

2.

3.

Unitary Products Group

25

262259-YTG-A-0706

TABLE 22: MINIMUM CLEARANCES

LOCATION Front Rear Left Side (Filter Access) Right Side (Cond. Coil) Below Above Unit1 Unit2

CLEARANCE

36" 24" (Less Economizer) 49" (With Economizer) 24" (Less Economizer) 36" (With Economizer)3 36" 0" 72" With 36" Maximum Horizontal Overhang (For Condenser Air Discharge)

NOTE: ELEC / ELEC Models: Units and ductwork are approved for zero clearance to combustible material when equipped with electric heaters. GAS / ELEC Models: A 1" clearance must be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit. The products of combustion must not be allowed to accumulate within a confined space and recirculate. Locate unit so that the vent air outlet hood is at least: · Three (3) feet above any force air inlet located within 10 horizontal feet (excluding those integral to the unit). · Four (4) feet below, four horizontal feet from, or one foot above any door or gravity air inlet into the building. · Four (4) feet from electric and gas meters, regulators and relief equipment.

1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material. 2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet. 3. If economizer is factory installed, the unassembled rain hood must be removed from its ride along position in front of evaporator coil, or in the outdoor air compartment, prior to final installation.

SUPPLY AIR COMPARTMENT

POWER EXHAUST RAIN HOOD (on Return Air Compartment)

ECONOMIZER MOTORIZED DAMPER RAIN HOOD (on Outdoor Air Compartment)

ECONOMIZER / MOTORIZED DAMPER AND POWER EXHAUST RAIN HOODS

FIXED OUTDOOR AIR INTAKE HOOD (located on Return Air Compartment) 36-5/8" 1" CONDENSATE DRAIN (Must be trapped)

16-1/8"

5" 28-3/16" 92"

REAR VIEW DETAIL "Y" UNIT WITH RAIN HOODS

LH VIEW

FIGURE 6 -

UNIT DIMENSIONS DM180, 240 & 300 (RAINHOOD)

26

Unitary Products Group

262259-YTG-A-0706

FIGURE 7 - CENTER OF GRAVITY

FIGURE 8 - TYPICAL UNIT APPLICATIONS

Unitary Products Group

27

262259-YTG-A-0706

B

F

A F R O N T C

E D

A C B F R O N T

D

FIGURE 9 - FOUR AND SIX POINT LOADS TABLE 23: FOUR AND SIX POINT LOADS

Unit Size 180 Gas 240 Gas 300 Gas 180 Elec 240 Elec 300 Elec Total Shipping Weight 2300 2500 3130 2100 2300 2890 Total Shipping Weight 2300 2500 3130 2100 2300 2890 4 Point Loads (lbs) A 539 538 615 492 295 487 B 563 563 671 514 517 619 C 612 715 962 558 658 646 D 586 684 882 536 630 508

6 Point Loads (lbs) A 351 334 418 320 307 415 B 367 350 438 335 322 471 C 392 426 533 358 392 528 D 416 502 628 380 462 551 E 399 481 603 364 442 492 F 375 407 510 343 375 433

Unit Size 180 Gas 240 Gas 300 Gas 180 Elec 240 Elec 300 Elec

28

Unitary Products Group

262259-YTG-A-0706

SUPPLY AIR* BACK OF UNIT RETURN AIR* DUCT SUPPORT RAILS

MIN. ROOF OPENING: 39-7/8" WIDE X 61-7/8" Long OUTDOOR COIL END OF UNIT 4"

2" 4" 33-1/8"

2" 22-3/4"

35-7/8" 84" DUCT SIZES: Supply Air = 22-1/2" x 35-5/8" Return Air = 32-7/8" x 35-5/8"

14-1/4" (15 Ton) 25-1/4" (20, 25 Ton)

4"

115-5/16" (15 Ton) 126-1/4" (20, 25 Ton)

*Supply and Return Air (including duct support rails) as shown, are typical for bottom duct applications. For location of horizontal duct applications (on back of unit), refer to Unit Dimension details.

FRONT OF UNIT

FIGURE 10 -UNIT ROOF CURB DIMENSIONS

FIGURE 11 -ROOF CURB DUCT OPENINGS DIMENSION

1. 2. The 2" space between the ducts allows for "jumping" an existing roof joist. The 58-1/2" overall dimension of the ducts allows ductwork penetration between roof joists that are spaced on 72" centers.

FIGURE 12 -CUT AWAY OF ROOF CURB

NOTE: Ducts can be installed into the curb from the roof. All electrical and gas line connections can be made inside the curb.

Unitary Products Group

29

262259-YTG-A-0706

THERMOSTAT TERMINALS

CONTROL TERMINAL BLOCK

W1 W2 Y1 Y2 G R C

2 1

W1 W2 Y1 G OCC P P1 Y2 X R SD

5

Smoke Detector

4

R SD SD

Jumper

3

RC OCC X

C

6

C

24 VAC Class 2

TERMINALS ON A LIMITED NUMBER OF THERMOSTATS

1 2 3 4 5 6

Second stage heating not required on single stage heating units. Second stage cooling not required on single stage cooling units. Jumper is required if there is no Smoke Detector circuit. Jumper is required for any combination of R, RC, or RH. OCC is an output from the thermostat to indicate the Occupied condition. X is an input to the thermostat to display Error Status conditions.

FIGURE 13 - Simplicity® CONTROL WIRING DIAGRAM

30

Unitary Products Group

262259-YTG-A-0706

GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. York's Sunline 2000TM units are convertible single package units. All models have dual independent refrigerant circuits for efficient part load operation and maximum comfort control. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, replace the supply and return air panels on the rear of the unit with a side duct flange accessory. All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. Each unit shall have 2 condenser fan motors. A high speed drive accessory is available for applications with a higher CFM and/or static pressure requirement. All compressors include crankcase heat and internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch. The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with two compressor lockout circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures. All models are CSA approved. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements carry an additional 4-year warranty. Aluminized steel tubular heat exchangers carry an additional 9-year warranty.

ment. All unit wiring shall be both numbered and color coded. All units shall be manufactured in a facility certified to ISO 9001 standards and the cooling performance shall be rated in accordance with DOE and ARI test procedures. Units shall be CGA listed, classified to ANSIZ21.47 standards, UL 1995/ CAN/CSA No. 236-M90 conditions. UNIT CABINET Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 1000 hours salt spray test per ASTM-B117 standards. Indoor blower section shall be insulated with a minimum 1/2" thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the furnace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels shall be "large" size, easily removable for servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable 2" filters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 2" or 4" filters. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating air by-pass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 1" I.D. female and be a ridged mount connection. Unit shall incorporate a fixed outdoor air damper with an outdoor air intake opening covered with a bird screen and a rain hood painted to match the exterior of the unit. INDOOR (EVAPORATOR) FAN ASSEMBLY Fan shall be a belt drive assembly and include an adjustablepitch motor pulley. Job site selected (B.H.P.) brake horsepower shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. OUTDOOR (CONDENSER) FAN ASSEMBLY The outdoor fans shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically balanced for smooth operation. The 2 outdoor fan motors shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently. REFRIGERANT COMPONENTS Compressors: a. Shall be Scroll (25T only) compressors internally protected with internal high-pressure relief and over temperature protection.

DESCRIPTION

Units shall be factory-assembled, single packaged, DM***N Electric Cooling/Gas Heat, DM***C/E Electric Cooling/ Optional Electric Heat, designed for outdoor mounted installation. The 15, 20 and 25 ton units shall have minimum EER ratings of 8.5. They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/ return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to ship-

Unitary Products Group

31

262259-YTG-A-0706

b.

Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.

h. i.

Control board shall monitor each refrigerant safety switch independently. Control board shall retain last 5 fault codes in non volatile memory, which will not be lost in the event of a power loss.

Coils: a. Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option. Evaporator and Condenser coils shall be of the direct expansion, draw-thru, design.

GAS HEATING SECTION (DM***N MODELS) Shall be designed with induced draft combustion with post purge logic and energy saving direct spark ignition, redundant main gas valve. Ventor wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25° F. Burners shall be of the inshot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the following minimum protection: a. b. c. d. Primary and switches. auxiliary high-temperature limit

b.

Refrigerant Circuit and Refrigerant Safety Components shall include: a. b. c. Balance-port thermostatic expansion valve with independent circuit feed system. Filter drier/strainer to eliminate any moisture or foreign matter. Accessible service gage connections on both suction and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge. The refrigeration system shall provide at least 15° F of sub-cooling at design conditions. All models shall have two independent circuits.

Induced draft motor speed sensor. Flame roll out switch (automatic reset). Flame proving controls. Unit shall have two independent stages of capacity.

d. e.

UNIT CONTROLS a. Unit shall be complete with self-contained low-voltage control circuit protected by a resetable circuit breaker on the 24-volt transformer side. Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor. Loss-of-charge/Low-pressure switch. 1. 2. High-pressure switch. Freeze-protection thermostat, evaporator coil. If any of the above safety devices trip, a LED (light-emitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.

ELECTRIC HEATING (DM***C/E MODELS) Nickel chromium electric heating elements shall be provided as required by the application with 1 or 2 stage control, as required, from 13.5 KW to 72 KW capacities. The heating section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required). UNIT OPERATING CHARACTERISTICS Unit shall be capable of starting and running at 125° F outdoor temperature, exceeding maximum load criteria of ARI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 0° F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only). ELECTRICAL REQUIREMENTS All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring. STANDARD LIMITED WARRANTIES · · Compressor 5 Years Heat Exchanger 10 Years

b.

c.

d. e.

Unit shall incorporate "AUTO RESET" compressor over temperature, over current protection. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up. Unit control board shall have on-board diagnostics and fault code display. Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0 °F.

f. g.

32

Unitary Products Group

262259-YTG-A-0706

· ·

Electric Heat Element 5 Years Other Parts 1 Year

·

OPTIONAL OUTDOOR AIR (Shall be made available by either/or): · ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER - Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, springreturn damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and return air dampers that are interlocked and positioned by a 2-position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss. ROOF CURB - 14" high, full perimeter curb with wood nailer (shipped knocked-down). 100% BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit. PROPANE CONVERSION KIT - Contains new orifices and gas valve parts to convert from natural to L.P. gas. One per unit required.

HIGH ALTITUDE - NATURAL GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. HIGH ALTITUDE - PROPANE GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit. BURGLAR BARS - Designed to work with above roof curbs, depending on unit model. Fits duct openings of curb supply and return air openings. SIDE DUCT FLANGE - Supply and return air duct flanges for side duct applications. Do not use on units with power exhaust. HIGH SPEED DRIVE - Includes blower pulley and belt for higher CFM and/or static pressure requirements. WOOD SKID - Allows unit to be handled with 90" forks. ECONOMIZER/MOTORIZED DAMPER RAIN HOOD (DMN/E/C300 only) - Contains all hood panels and the hardware for assembling. ANTI-RECYCLE TIMER - Assures 5-minute off time between compressor cycles. COIL GUARD KIT - Guard for cooling coil. POWER EXHAUST OPTION - To work in conjunction with economizers. STAINLESS STEEL HEAT EXCHANGER STAINLESS STEEL DRAIN PAN TECHNICOAT PHENOLIC COATED CONDENSER AND EVAPORATOR COIL ELECTRONIC SINGLE ENTHALPY ECONOMIZER DIRTY FILTER SWITCH PHASE MONITOR COIL GUARD POWERED GFI CONVENIENCE OUTLET NON-POWERED GFI CONVENIENCE OUTLET BAS CONTROLS (Simplicity® INTELLI-ComfortTM CPC, JOHNSON, HONEYWELL, NOVAR) BAS READY ECONOMIZER (BELIMO ACTUATOR WITHOUT A CONTROLLER) HINGED FILTER DOOR ACCESS AND TOOLESS ACCESS PANELS HIGH SPEED DRIVE 2" THROW AWAY FILTERS 4" PLEATED FILTERS DISCONNECT SWITCH SUPPLY AIR SMOKE DETECTOR RETURN AIR SMOKE DETECTOR

·

·

·

· · ·

· · · · · · · · · · · · · · · · · · · · ·

OTHER FACTORY INSTALLED OPTIONS

·

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE · ·

·

Unitary Products Group

33

262259-YTG-A-0706

34

Unitary Products Group

262259-YTG-A-0706

Unitary Products Group

35

Subject to change without notice. Printed in U.S.A. Copyright © 2006 by Unitary Products. All rights reserved. Unitary Products Group 5005 York Drive

262259-YTG-A-0706 Supersedes: 246692/036-21476-002-E-0904 Norman OK 73069

Information

Y-TG, Gas/Elec Units and Single Package AC, Models: DM180, 240 & 300

36 pages

Find more like this

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

331700