Read RenewaireCatalog.pdf text version

Commercial Product Catalog

www.RenewAire.com · (800) 627-4499 · Fax: (608) 221-2824

4510 Helgesen Drive · Madison, Wisconsin 53718 USA

In CANADA www.MitsubishiElectric.ca · (905) 475-8989 · Fax: (905) 475-5231

advantages of heat and humidity transfer

Improves Indoor Air Quality

By providing simultaneous exhaust and fresh air supply, RenewAire reduces the concentration of harmful pollutants in indoor air - an absolute must in schools, offices and smoking environments.

Energy Recovery Ventilation: the proven

Meets Ventilation Codes for Air Exchange

Provides ample ventilation to meet ASHRAE 62 and the International Mechanical Code that now requires two to three more air exchanges than in the past.

Indoor Air Quality Problems Solved!

Controls Excess Moisture

Unlike conventional ventilation or basic heat exchangers, RenewAire moderates not only the temperature but the humidity content of incoming air, limiting humidity swings and associated biologic growths.

Ideal for Hot or Cold Environments

Catalog Page Reference

2 4 5 6 7 8 9 Residential Products BR70 BR130 EV130 EV200 EV300 HVI-Certified 34 Commercial Outdoor Units 36 EV450RT 38 HE1XRT 40 HE1XRTC 42 HE2XRT 44 HE2XRTC 46 HE3XRT 48 HE3XRTC 50 HE4XRT 52 HE4XRTC 54 HE6XRT 56 HE8XRT 58 Applied Products 60 CA-Series 62 PA-Series 64 Commercial Controls 66 ARI-Certified 67 Model Number Guide 68 Reference Info 69 Company History

Optimum Cold Weather Performance

Recaptures heat otherwise lost to exhaust air while controlling humidity extremes. This greatly reduces the demand on heating equipment lowering both initial costs and energy bills. Also protects heating coils from freeze damage.

Optimum Warm Weather Performance

Pre-cools and dehumidifies the fresh airstream by transfer of heat and humidity to the exhaust airstream. This greatly reduces air conditioning demand - lowering both initial costs and energy bills. On retrofits, the ventilation rate of exisitng A/C equipment can be as much as doubled.

10 Commercial Indoor Units 12 14 16 18 20 22 24 26 28 30 32 EV450IN HE1XINH HE1XINV HE2XINH HE2XINV HE3XINH HE3XINV HE4XINH HE4XINV HE6XIN HE8XIN

Energy Saved = Dollars Saved

RenewAire's all-weather performance can cut annual energy bills for heating, cooling and dehumidification of ventilation air by 50% or more.

W hy RenewAirE?

INSIDE

Fresh Air to Room

OUTSIDE

Stale Room Air

(exhausted to outside)

The Static-Plate Core is the Key!

Since the early 1980's, RenewAire has pioneered the use of the patented Lossnay* exchange core throughout the Americas. Listed below are some of the many reasons why this technology has become the ERV system preferred by leading HVAC professionals around the world.

Fixed Partition and Spacer Plates

(proprietary resin composite media)

Positive Airstream Separation

In the RenewAire core, fresh air never comes in contact with exhaust air passages. Hydroscopic resin plates separate the two airsteams so effectively that ARI certifies zero exhaust air transfer at normal, balanced operating conditions. As a result, RenewAire is perfect for controlled exhaust applications such as toilet areas, as well as for food service and health care occupancies.

Stale Room Air

Outside Air

No Condensate or Active Defrost

G4

Enhanced Humidity Transfer

RenewAire is proud to introduce the fourth generation Lossnay* energy recovery ventilation (ERV) core. · 30% more humidity transfer at ARI summer conditions · additional load reduction (over G3 core) HE1X = 0.2 ton @ 750 CFM EV450 = 0.1 ton @ 450 CFM

Direct water vapor transfer, driven by vapor pressure, eliminates condensation - and frosting - in virtually all applications and climate zones. No condensation allows for closer plate spacing, resulting in higher efficiencies and easier installations. It also means no need for the dampers or electrical defrost elements that reduce ventilation and rob energy efficiency in competing technologies.

Maintenance - Nothing Could Be Easier

The scheduled maintenance for RenewAire is so simple, it can be performed by any janitorial staff. No expensive service contracts are necessary because there is no wheel disassembly and washing, no seal or belt adjustments and no complex controls to calibrate. The result is the lowest maintenance cost of any ERV.

The Unbeatable RenewAire Warranty

An investment in RenewAire is protected by a 10-year core warranty (2 years on balance of the unit). This commitment twice as long as coverage on the best wheel products - speaks volumes about RenewAire's reliability, durability and consistent high performance.

RenewAire's remarkable performance is independently certified by:

Award-Winning Service and Support

RenewAire's team of professionals knows ERV. And our nationwide network of Sales Reps and quality Distributors are ready to serve you locally. When you call our support number, you'll talk to a knowledgeable factory expert - someone who knows not only our product line, but the best ways to integrate RenewAire with your preferred lines of heating and air conditioning equipment.

*Registered trademark of Mitsubishi Electric Corporation

Residential/Small Commercial Products

· Commercial quality, ducted equipment sized to meet required ventilation rates for homes and small commercial buildings. · Static-plate technology makes total energy savings practical for small-capacity systems. · May be mounted in any orientation. · Quiet, powerful blowers eliminate the need for air balancing in most applications. · Positive airsteam separation that is critical for smoking environments and bathroom exhaust. · No condensate pan or drain required. · Easiest maintenance of any ERV. · Performance certified by HVI. · Ten year core warranty.

Central Exhaust - Use EV Series

EA: Exhaust Air to outdoors OA: Outdoor Air intake RA: Room Air to be exhausted FA: Fresh Air to inside

NOTE: ERV Blower may be operated separately from Furnace Blower

General Exhaust - EV Series (or BR Series

mounted to furnace return air which requires furnace blower interconnect)

(See manual for additional installation methods.)

NOTE: ERV Blower may be operated separately from Furnace Blower

PTL Control

· primary control for EV70, EV130, EV200 & EV300 · runs unit an adjustable amount of time each hour · two wire, low voltage connection to ERV

PBL Control

· push button control turns on unit from bathrooms or other intermittent exhaust locations · 20 minute run-time with one touch · push 2x for 40 or 3x for 60 minutes · two wire, low voltage connection to PTL Control

FM Control

· alternate primary control for EV70, EV130, EV200 & EV300 · wires to EV unit and either thermostat or furnace control to turn on furnace blower · six wire, low voltage connection

2

(800) 627-4499 · Fax: (608) 221-2824

Residential Energy Recovery Ventilators: BR70, BR130, EV130, EV200 and EV300

Part I ­ General

A. Product Specification The unit shall be a packaged static plate energy recovery ventilator. RenewAire shall be the basis of design. B. Quality Assurance 1. The energy recovery ventilator shall be certified by the Home Ventilating Institute (HVI) under CSA 439. Both a heating and an air conditioning test must be run to demonstrate year round energy recovery. 2. Unit shall be Listed under UL 1812, Standard for Ducted Air to Air Heat Exchangers. 3. The energy recovery core shall meet NFPA 90A and 90B requirements for flame spread, not to exceed 25, and smoke generation, not to exceed 50, through an ongoing testing and verification program using UL Standard 723. 4. The RenewAire core shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of ten years from the date of purchase. Balance of Unit shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of two years from the date of purchase. C. Continuous Ventilation The unit shall accomplish energy recovery in both heating and cooling seasons and shall have the capacity to operate continuously without the need for bypass, recirculation, pre-heaters or other defrost cycles under normal operating conditions. D. Positive Airsteam Separation Exhaust and fresh airstreams shall at all times travel in separate passages and airstreams shall not mix. E. Laminar Flow Airflow through the energy recovery core shall be laminar, avoiding deposition of particulates on the interior of the exchange plate material.

Part III ­ Construction

1. The energy recovery core shall be of static plate, cross-flow construction, with no moving parts. 2. No condensate pan or drain shall be required. 3. The unit shall be supplied with an internal 24 VAC transformer and relay. 4. The unit shall have line cord for easy plug-in operation. 5. A latched and hinged door shall provide access to blowers, energy recovery core and filters. 6. Cabinet walls and doors shall be insulated with 1" FSK high-density board insulation, with additional ¼" foam insulation on access door for thermal and sound insulation. 7. The energy exchange element and blowers shall be protected by a polyester filter in both exhaust air and fresh airsteams.

Part II ­ Performance

A. Energy Transfer The energy recovery core shall be capable of transferring both sensible and latent energy between airsteams. Latent energy transfer shall be accomplished by direct water vapor transfer using molecular transport by hydroscopic resin. B. Passive Frost Control The energy recovery core shall perform without the occurrence of condensation or frosting under normal operating conditions (defined as outside temperatures above -10°F and inside relative humidity below 40%). Occasional extreme conditions shall not affect the usual function or performance of the energy recovery core.

3

www.RenewAire.com

BR70

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 40-70 CFM Number Motors: One, 0.08 hp V 120 HZ 60 Phase Single Input Watts 94 @ 69 CFM FLA 1.0

Control Voltage: 24 VAC Filters: Cleanable, spun polyester media. 7 1/2" x 10 1/2" x 1" Weight: 45 lbs (unit), 55 lbs (in carton) Shipping Dimensions: 21 1/2"W x 29"L x 13"H

G4 Performance

Airflow CFM

35 51 63 71 79 90

Options: Thru-the-Wall Kit Duct Collar Kit Total EFF% Winter/Summer*

75/60 71/56 68/53 66/50 64/48 61/45

ESP in H 20

0.50 0.40 0.30 0.25 0.20 0.10

Temp EFF%

84 80 77 75 73 70

* (See HVI certification report on page 9 for complete certified rating).

Dimensions

EA: OA: RA: FA: Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

TW: Thru Wall DH: Duct Hung

4

(800) 627-4499 · Fax: (608) 221-2824

BR130

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 50-140 CFM Unit may be mounted in any orientation Number Motors: One, 0.07 hp V 120 HZ 60 Phase Single Input Watts

121 @ 124 CFM

FLA 1.3

Control Voltage: Built in proportional runtime control and switched terminals for furnace / AC interconnect Filters: Cleanable, spun polyester media. 10 1/2" x 10 1/2" x 1" Weight: 55 lbs (unit), 65 lbs (in carton)

G4 Performance

Airflow CFM

52 69 94 113 124 132 141 148

Shipping Dimensions: 21 1/2"W x 32"L x 15 1/2"H Total EFF% Winter/Summer*

75/60 72/57 67/52 64/48 62/46 60/44 59/43 57/41

ESP in H20

0.70 0.60 0.50 0.40 0.35 0.30 0.20 0.10

Temp EFF%

83 80 76 73 71 70 68 67

Options: Thru-the-Wall Kit Duct Collar Kit

* (See HVI certification report on page 9 for complete certified rating).

Dimensions

EA: OA: RA: FA: Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

TW: Thru Wall DH: Duct Hung

5

www.RenewAire.com

EV130

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 50-140 CFM Unit may be mounted in any orientation Number Motors: One, 0.1 hp V 120 HZ 60 Phase Single Input Watts

121 @ 124 CFM

FLA 1.3

Control Voltage: 24 VAC Filters: Cleanable, spun polyester media. 10 1/2" x 10 1/2" x 1" Weight: 58 lbs (unit), 65 lbs (in carton) Shipping Dimensions: 21"W x 32"L x 17 1/2"H

G4 Performance

Airflow CFM

52 69 94 113 124 132 141 148

ESP in H20

0.70 0.60 0.50 0.40 0.35 0.30 0.20 0.10

Temp EFF%

83 80 76 73 71 70 68 67

Total EFF% Winter/Summer*

75/60 72/57 67/52 64/48 62/46 60/44 59/43 57/41

Options: PT - Percentage Timer Control PB - Push Button Point-of-Use Controls FM - Percentage Timer Control with Furnace Interlock DH24 - Dehumidistat Control Wall Caps

* (See HVI certification report on page 9 for complete certified rating).

Dimensions

EA: OA: RA: FA: Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

6

(800) 627-4499 · Fax: (608) 221-2824

EV200

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 100-200 CFM Number Motors: One, 0.1 hp V 120 HZ 60 Phase Single Input Watts

157 @ 181 CFM

FLA 1.5

Control Voltage: 24 VAC Filters: Cleanable, spun polyester media. 10 1/2" x 21 3/4" x 1" Weight: 80 lbs (unit), 88 lbs (in carton) Shipping Dimensions: 21 1/2"W x 32"L x 29"H

G4 Performance

Airflow CFM

122 149 168 176 181 186 192 200

ESP in H20

0.70 0.65 0.50 0.40 0.35 0.30 0.20 0.10

Temp EFF%

82 80 79 78 78 77 77 76

Total EFF% Winter/Summer*

74/59 72/56 70/55 69/54 69/53 68/53 68/52 67/52

Options: PT - Percentage Timer Control PB - Push Button Point-of-Use Controls FM - Percentage Timer Control with Furnace Interlock DH24 - Dehumidistat Control Wall Caps

* (See HVI certification report on page 9 for complete certified rating).

Dimensions

EA: OA: RA: FA: Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

7

www.RenewAire.com

EV300

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 150-300 CFM Number Motors: One, 0.2 hp V 120 HZ 60 Phase Single Input Watts

317 @ 295 CFM

FLA 3.3

Control Voltage: 24 VAC Filters: Cleanable, spun polyester media. 10 1/2" x 21 3/4" x 1" Weight: 88 lbs (unit), 95 lbs (in carton) Shipping Dimensions: 21 1/2"W x 32"L x 29"H

G4 Performance

Airflow CFM

93 163 202 253 279 295 315

ESP in H20

1.0 0.9 0.8 0.7 0.6 0.5 0.4

Temp EFF%

85 79 76 72 70 68 67

Total EFF% Winter/Summer*

76/62 70/55 67/51 62/47 60/44 59/43 57/41

Options: PT - Percentage Timer Control PB - Push Button Point-of-Use Controls FM - Percentage Timer Control with Furnace Interlock DH24 - Dehumidistat Control Wall Caps

* (See HVI certification report on page 9 for complete certified rating).

Dimensions

EA: OA: RA: FA: Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

8

(800) 627-4499 · Fax: (608) 221-2824

HVI-Tested/Certified Per CSA C439

Ext. Static Pressure Net Supply Airflow Ext. Static Pressure Net Supply Airflow

in. in. wg. (Pa n x 248.8) wg. (Pa = = n x 248.8)

Pa in. wg in. wg 0.1 25 0.1 0.2 50 0.2 75 0.3 0.3 100 0.4 100 0.4 125 Requirements Volts 120 Amps 1.0 0.5 17 35 Electrical

BR70 - Ventilation Performance BR70/EV70 - Ventilation Performance Gross Airflow Gross Airflow Supply Exhaust Supply Exhaust L/S CFM L/S CFM L/S CFM L/S CFM L/S L/S CFMCFM 41 86 4244 89 94 46 47 97 100 42 90 34 73 3539 75 82 39 41 84 87 37 79 28 59 2931 61 66 32 35 69 73 30 63 21 46 2225 47 53 25 29 53 62 24 51 17 37 22 46

09 0..9

0.8 0.7 0.6 0.5 0.4 0.3

0.8

0.7

0.6

0.5 0.4

0.3

0.2

Exhaust Air Transfer Ratio = 4% @ Amps 1.0 Electrical Requirements Volts 120 0.2 in. wg (50 PA) and 4% @ 0.4 in. wg (100 PA) in. wg (50 Energy Performance Exhaust Air Transfer Ratio = 4% @ 0.2BR70/EV70 -Pa)

Supply Temperature Supply C F Temperature C Heatin g F 0Heating 32 g 0 Coolin32 35 Cooling95 35 95 Net Airflow Net Airflow L/S CFM L/S CFM 32 69 34 74 30 64 33 70 S AverageBR70 -r Energy Performance Power S ensible Recovery Apparent Sensible Watts Efficiency % Effectiveness % Average Power Sensible Recovery Apparent Sensible Watts Efficiency % Effectiveness % 94 93 94 93 66 62 Net Moisture Transfer % Net Moisture Transfer % 53 50

0..2 01 0.1 0 0 0 0

25 50 75 100 125 150 175

25

(5 50 CFM 7L/s = n x 004719) 125 1 .

150

175

CFM (L/s = n x 0.4719)

77 Total Recove ry Efficiency % 78 42 Total Recovery Efficiency % 46

Ext. Static Pressure Pa 25 50 75 100 125 150 175

BR130/EV130 - Ventilation Performance Gross Airflow Net Supply Airflow Supply Exhaust in. wg L/S CFM L/S CFM L/S CFM 0.1 70 148 71 151 75 159 0.2 66 141 67 143 69 147 0.3 62 132 63 134 64 135 0.4 53 113 54 115 56 119 0.5 44 94 45 96 47 99 0.6 32 69 33 70 29 62 0.7 24 52 25 53 21 45

0.9 0.8

in. wg. (Pa = n x 248.8)

0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 0 25 50 75 100 125 150 175 CFM (L/s = n x 0.4719)

Electrical Requirements Volts 120 Amps 1.3 Exhaust Air Transfer Ratio = 2% @ 0.2 in. wg (50 PA) and 2% @ 0.4 in. wg (100 PA)

BR130/EV130 - Energy Performance Supply Temperature C F Heating 0 32 Cooling 35 95 Net Airflow L/S 58 59 CFM 124 126 Average Powerr Watts S ensible Recovery Apparent Sensible S Efficiency % Effectiveness % Net Moisture Transfer %

121 121

72

80 Total Recovery Efficiency % 46

55

Ext. Static Pressure Pa 25 50 75 100 125 150 175 in. wg 0.1 0.2 0.3 0.4 0.5 0.6 0.7

Net Supply Airflow

EV200 - Ventilation Performance Gross Airflow Supply Exhaust L/S CFM L/S CFM L/S CFM 97 207 100 213 109 232 90 192 93 199 104 221 88 186 90 192 101 216 83 176 85 181 96 204 79 168 81 173 88 187 70 149 72 154 76 162 57 122 59 126 68 145

0.9 0.8

in. wg. (Pa = n x 248.8)

0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 0 25 50 75 100 125 150 175 200 225 250

Electrical Requirements Volts 120 Amps 1.5 Exhaust Air Transfer Ratio = 3% @ 0.2 in. wg (50 PA) and 3% @ 0.4 in. wg (100 PA)

EV200 - Energy Performance Suppl y Temperature C F Heatin g 0 32 Coolin g 35 95 Net Airflow L/S 85 85 CFM 181 180 Average Powerr Watts S S ensible Recovery Apparent Sensible Efficiency % Effectiveness % Net Moisture Transfer %

CFM (L/s = n x 0.4719)

157 155

78

85 Total Recove ry Efficiency % 52

62

Ext. Static Pressure Pa 100 125 150 175 200 225 250 in. wg 0.4 0.5 0.6 0.7 0.8 0.9 1.0

Net Supply Airflow

EV300 - Ventilation Performance Gross Airflow Supply Exhaust L/S CFM L/S CFM L/S CFM 148 315 153 325 146 311 141 299 145 309 138 293 131 279 135 287 126 268 119 253 123 261 111 237 95 202 98 209 89 189 77 163 79 169 69 147 44 93 45 96 34 72

1.1 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 0 50 100 150 200 250 300 350 CFM (L/s = n x 0.4719)

Electrical Requirements Volts 120 Amps 3.3 Exhaust Air Transfer Ratio = 3% @ 0.4 in. wg (100 PA)

EV300 - Energy Performance Supply Temperatur e C F Heatin g 32 Coolin g 35 95 0 Net Airflow L/S 139 134 CFM 295 285 Average Powerr Watts Sensible Recovery Apparent Sensible S S Efficiency % Effectiveness % Net Moisture Transfer %

317 311

70

78 Total Recove ry Efficiency % 43

51

in. wg. (Pa = n x 248.8)

9

www.RenewAire.com

Commercial INDOOR Products

· Horizontal and vertical configuration. · Wide range of airflow and static capacities. · ARI certified performance data for efficiency and cross leakage. · UL tested flammability and smoke generation that meets NFPA 90A and 90B test standards for commercial applications. · Easy installation and service. · Ten year core warranty.

RenewAire means Trouble-Free ERV.

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

10

(800) 627-4499 · Fax: (608) 221-2824

Packaged Indoor Energy Recovery Ventilators: EV450IN, HE1XIN, HE2XIN, HE3XIN, HE4XIN, HE6XIN, HE8XIN

Part I - General

A. Product Specification The unit shall be a packaged static plate energy recovery ventilator. RenewAire shall be the basis of design. B. Quality Assurance 1. The energy recovery core shall be certified by ARI under its Standard 1060 for Energy Recovery Ventilators. Products not currently ARI Certified will not be accepted. 2. Unit shall be Listed under UL 1812, Standard for Ducted Air to Air Heat Exchangers. Due to ongoing product offerings and upgrades, some models and options are not included in UL Listing reports. Consult RenewAire for more information. 3. The energy recovery core shall meet NFPA 90A and 90B requirements for flame spread, not to exceed 25, and smoke generation, not to exceed 50, through an ongoing testing and verification program using UL Standard 723. 4. The RenewAire core shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of ten years from the date of purchase. Balance of Unit shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of two years from the date of purchase. B. Passive Frost Control The energy recovery core shall perform without the occurrence of condensation or frosting under normal operating conditions (defined as outside temperatures above -10°F and inside relative humidity below 40%). Occasional extreme conditions shall not affect the usual function or performance of the energy recovery core. C. Positive Airsteam Separation Exhaust and fresh airstreams shall at all times travel in separate passages, and airstreams shall not mix. The exhaust air transfer ratio (EATR) shall be ARI1060 certified as 0% at balanced pressure. D. Laminar Flow Airflow through the energy recovery core shall be laminar, avoiding deposition of particulates on the interior of the exchange plate material.

Part III ­ Product

A. Construction 1. The energy recovery core shall be of static plate, cross-flow construction, with no moving parts. 2. The unit shall be capable of operating in winter and summer conditions without generating condensate. No condensate pan or drain shall be required. 3. The unit cabinet shall be constructed of galvanized, 20-gauge steel, with lapped corners. 4. The unit shall have single-point power connection. 5. Flange components shall be provided suitable for connection of ductwork. 6. The exhaust and fresh airsteams shall both be protected by MERV 8 rated, 2 inch pleated, disposable filters positioned before the ERV core.

Part II ­ Performance

A. Energy Transfer The energy recovery core shall be capable of transferring both sensible and latent energy between airsteams. Latent energy transfer shall be accomplished through molecular transport by hydroscopic resin.

11

www.RenewAire.com

EV450IN

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 200-500 CFM ARI 1060 Certified Core: One L85 Airflow Rating Points (for ARI): 450 CFM and 338 CFM Motors: One, 0.6 hp (Single Phase) One, 0.5hp (Three Phase) Field Selectable Voltage V 115 208-230 277 HZ 60 60 60 60 60 Phase Single Single Single Three Three FLA 7.0 3.5 2.4 1.7-1.5 0.8

G4 Performance

Airflow CFM

225 338 380 450 540 575 600

208-230 Temp EFF%

81 77 76 73 70 69 68

ESP in H 20

1.25 1.00 0.90 0.65 0.25 0.00 -0.25

Watts 1P 3P

335 420 470 550 640 690 735 181 278 340 430 540 610 664

Total EFF% Winter/Summer*

73/61 69/56 68/54 65/50 62/46 61/45 60/43

460

Control Voltage: 24 VAC Filters: Two total, MERV 8, 2" pleated, 14" x 20" nominal size Weight: 141 lbs (unit), 160 lbs (in carton), up to 3 units on 50 lb pallet Shipping Dimensions: 37 1/2" W x 48" L x 17" H Options: 45EVHB - Hanging Bracket, Foot Kit 45EVDF - Rectangular 12" x 8" Flange Kit (2 in kit) 45EVT10 - 10" Round Transition Kit (2 in kit)

*At ARI 1060 standard conditions (See certified data on page 66 for core components.)

12

(800) 627-4499 · Fax: (608) 221-2824

EV450IN

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration EV450KIN...

Wall S (single) D (double) Phase 1 3 Voltage 1 (115) 4 (460) 5 (208-230) 6 (115/208-230) 7 (208-230/460) 9 (277) Contactor A (24 VAC) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) Other -- (none) W (white paint) C (custom paint) UL L (UL listed)

13

www.RenewAire.com

HE1XINH

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 250-925 CFM ARI 1060 Certified Core: One L125-00 Airflow Rating Points (for ARI): 750 CFM and 560 CFM Number Motors: Two, 0.75 hp Field Selectable Voltage (you must order phase) V 115 208-230 277 HZ 60 60 60 60 60 Phase Single Single Single Three Three FLA 8.6 4.3 2.4 2.1 1.1

Min. Cir. Amps Max. Fuse Size

19.4 9.7 5.4 4.7 2.5

25 15 15 15 15

G4 Performance

Airflow CFM

560 635 750 795 860 925 970

208-230 Temp EFF%

75 73 71 70 69 67 66

ESP in H 20

1.35 1.25 0.90 0.75 0.50 0.25 0.00

Watts 1P 3P

875 950 1,090 1,160 1,270 1,375 1,490 597 691 856 928 1,039 1,158 1,246

Total EFF% Winter/Summer*

67/53 66/51 63/48 62/47 61/46 59/44 58/43

460

Control Voltage: 24, 115, 230 VAC Filters: Two total, MERV 8, 2" pleated, 20" x 20" nominal size Weight: 211 lbs (unit), 250 lbs (shipping weight) Shipping Dimensions: 44" W x 56" L x 27" H Options: Controls (see pages 64 & 65) Wall caps

*At ARI 1060 standard conditions (See certified data on page 66 for core components.)

14

(800) 627-4499 · Fax: (608) 221-2824

HE1XINH

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE1XKINH...

Wall S (single) D (double) Phase 1 3 Voltage 1 (115) 4 (460) 5 (208-230) 6 (115/208-230) 7 (208-230/460) 9 (277) Other -- (none) W (white paint) C (custom paint) UL L (UL listed) N (not UL listed) FA Hp H (0.75) EA Hp H (0.75) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

15

www.RenewAire.com

HE1XINV

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 250-925 CFM ARI 1060 Certified Core: One L125-00 Airflow Rating Points (for ARI): 750 CFM and 560 CFM Number Motors: Two, 0.75 hp Field Selectable Voltage (you must order phase) V 115 208-230 277 HZ 60 60 60 60 60 Phase Single Single Single Three Three FLA 8.6 4.3 2.4 2.1 1.1

Min. Cir. Amps Max. Fuse Size

19.4 9.7 5.4 4.7 2.5

25 15 15 15 15

G4 Performance

Airflow CFM

560 635 750 795 860 925 970

208-230 Temp EFF%

75 73 71 70 69 67 66

ESP in H 20

1.35 1.25 0.90 0.75 0.50 0.25 0.00

Watts 1P 3P

875 950 1,090 1,160 1,270 1,375 1,490 597 691 856 928 1,039 1,158 1,246

Total EFF% Winter/Summer*

67/53 66/51 63/48 62/47 61/46 59/44 58/43

460

Control Voltage: 24, 115, 230 VAC Filters: Two total, MERV 8, 2" pleated, 20" x 20" nominal size Weight: 211 lbs (unit), 250 lbs (shipping weight) Shipping Dimensions: 44" W x 56" L x 27" H Options: Controls (see pages 64 & 65) Wall caps

*At ARI 1060 standard conditions (See certified data on page 66 for core components.)

16

(800) 627-4499 · Fax: (608) 221-2824

HE1XINV

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE1XKINV...

Wall S (single) D (double) Phase 1 3 Voltage 1 (115) 4 (460) 5 (208-230) 6 (115/208-230) 7 (208-230/460) 9 (277) Other -- (none) W (white paint) C (custom paint) UL L (UL listed) N (not UL listed) FA Hp H (0.75) EA Hp H (0.75) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

17

www.RenewAire.com

HE2XINH

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 500-2,000 CFM ARI 1060 Certified Core: Two L125-00 Airflow Rating Points (for ARI): 1,500 CFM and 1,120 CFM Number Motors: Direct Drive (DD) Four, Belt Drive (BD) Two Field Selectable Voltage (you must order phase) Drive HP DD 0.75 BD 1.5 Volts 115 208-230 208-230 460 208-230 460 HZ 60 60 60 60 60 60 Phase 1 1 3 3 3 3 FLA 8.6 4.3 5.6-5.0 2.8 7.0-6.6 3.5

Min. Cir. Amps Max. Fuse Size

36.6 18.3 12.6 6.3 15.8 7.9

45 20 20 15 20 15

G4 Performance

CFM

500 1,000 1,500 2,000

BD 2

Control Voltage: 24, 115, 230 Volt available Filters: Four total, MERV 8, 2" pleated, 20" x 20" nominal size

Effectiveness (%)

80

Sensible

Weight: 414 lbs (unit), 420 lbs (shipping weight)

Winter

Shipping Dimensions: 50" W x 62" L x 41" H

60

Total

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components.)

er To

tal

Airflow Performance

External Static Pressure (Inches Water Column)

Motor HP Blower RPM Nominal Turns Open CFM 0.75 (Four DD) 1.5 (Two BD) 2 (Two BD) N/A N/A 1,000 1,230 1,420 1,220 1,470 1,660 N/A N/A 4.5 2 0 4.5 2 0 0.0 BHP CFM 0.25 BHP CFM 0.5 BHP CFM 0.75 BHP CFM 1.0 BHP CFM 1.25 BHP CFM 930 1,125 1,475 1.5 BHP 0.9 1.1 1.7

1,950 CFM 2,240 Watts 1,378 1,694 1,956 1,681 2,025 0.5 0.9 1.4 0.9 1.6 -

1,830 CFM 2,155 Watts 1,175 1,550 1,850 1,530 1,925 0.5 0.9 1.4 0.9 1.5 -

1,670 CFM 2,020 Watts 900 1,335 1,680 1,315 1,750 2,000 0.4 0.8 1.2 0.7 1.4 2.0

1,400 CFM 1,795 Watts 635 1,125 1,475 1,100 1,575 1,900 0.4 0.7 1.2 0.7 1.3 1.9

1,150 CFM 1,490 Watts 1,000 1,300 975 1,375 1,750 0.7 1.1 0.6 1.2 1.8

700 CFM 1,190 Watts 500 1,200 1,275 1,570 0.6 1.1 1.2 1.7

18

(800) 627-4499 · Fax: (608) 221-2824

HE2XINH

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE2XKINH...

Wall S (single) D (double) Phase 1 3 Voltage 1 (115) 4 (460) 5 (208-230) 6 (115/208-230) 7 (208-230/460) 8 (575) 9 (277) Other -- (none) W (white paint) C (custom paint) UL L (UL listed) N (not UL listed) FA Hp J (1.5) K (2.0) Q (two 0.75) EA Hp J (1.5) K (2.0) Q (two 0.75) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

19

www.RenewAire.com

HE2XINV

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 500-2,000 CFM ARI 1060 Certified Core: Two L125-00 Airflow Rating Points (for ARI): 1,500 CFM and 1,120 CFM Number Motors: Direct Drive (DD) Four, Belt Drive (BD) Two Field Selectable Voltage (you must order phase) HP DD 0.75 Volts 115 208-230 208-230 460 208-230 460 HZ 60 60 60 60 60 60 Phase 1 1 3 3 3 3 FLA 8.6 4.3 5.6-5.0 2.8 7.0-6.6 3.5

Min. Cir. Amps Max. Fuse Size

36.6 18.3 12.6 6.3 15.8 7.9

45 20 20 15 20 15

G4 Performance

CFM

500 1,000 1,500 2,000

BD 1.5 BD 2

Control Voltage: 24, 115, 230 Volt available Filters: Four total, MERV 8, 2" pleated, 20" x 20" nominal size

Effectiveness (%)

80

Sensible

Weight: 399 lbs (unit), 420 lbs (shipping weight)

Winter

Shipping Dimensions: 48" W x 62" L x 55" H

60

Total

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components.)

er To

tal

Airflow Performance

External Static Pressure (Inches Water Column)

Motor HP Blower RPM Nominal Turns Open CFM 0.75 (Four DD) 1.5 (Two BD) 2 (Two BD) N/A N/A 1,000 1,230 1,420 1,220 1,470 1,660 N/A N/A 4.5 2 0 4.5 2 0 0.0 BHP CFM 0.25 BHP CFM 0.5 BHP CFM 0.75 BHP CFM 1.0 BHP CFM 1.25 BHP CFM 930 1,125 1,475 1.5 BHP 0.9 1.1 1.7

1,870 CFM 2,160 Watts 1,378 1,694 1,956 1,681 2,025 0.5 0.9 1.4 0.9 1.6 -

1,720 CFM 2,070 Watts 1,175 1,550 1,850 1,530 1,925 0.5 0.9 1.4 0.9 1.5 -

1,520 CFM 1,900 Watts 900 1,335 1,680 1,315 1,750 2,000 0.4 0.8 1.2 0.7 1.4 2.0

1,290 CFM 1,715 Watts 635 1,125 1,475 1,100 1,575 1,900 0.4 0.7 1.2 0.7 1.3 1.9

1,080 CFM 1,505 Watts 1,000 1,300 975 1,375 1,750 0.7 1.1 0.6 1.2 1.8

700 CFM 1,210 Watts 500 1,200 430 1,275 1,570 0.6 1.1 0.6 1.2 1.7

20

(800) 627-4499 · Fax: (608) 221-2824

HE2XINV

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE2XKINV...

Wall S (single) D (double) Phase 1 3 Voltage 1 (115) 4 (460) 5 (208-230) 6 (115/208-230) 7 (208-230/460) 8 (575) 9 (277) Other -- (none) W (white paint) C (custom paint) UL L (UL listed) N (not UL listed) FA Hp J (1.5) K (2.0) Q (two 0.75) EA Hp J (1.5) K (2.0) Q (two 0.75) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

21

www.RenewAire.com

HE3XINH

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 750-3,300 CFM ARI 1060 Certified Core: Three L125-00 Airflow Rating Points (for ARI): 2,250 CFM and 1,690 CFM Number Motors: Two HP 2 3 Volts 208-230 460 208-230 460 208-230 460 HZ 60 60 60 60 60 60 Phase 3 3 3 3 3 3 FLA 7.0-6.6 3.5 9.2-8.6 4.4

14.0-13.0 Min. Cir. Amps Max. Fuse Size

15.8 7.9 20.7 9.9 31.5 14.6

20 15 30 15 45 20

G4 Performance

CFM

1,500 2,000 2,500 3,000

5

6.5

Control Voltage: 24, 115, 230 Volt available Filters: Six total, MERV 8, 2" pleated, 20" x 20" nominal size Weight: 675 lbs (unit), 700 lbs (shipping weight)

Effectiveness (%)

80

Sensible

Shipping Dimensions: 72" W x 84" L x 46" H

Winter

60

Total

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components.)

er To

tal

Airflow Performance

External Static Pressure (Inches Water Column)

Motor HP Blower RPM Nominal Turns Open CFM 2 1,095 1,220 1,340 1,345 1,535 1,685 1,495 1,675 1,855 4 2 0 4.5 2 0 6.5 3.5 0 2,040 2,340 2,590 2,420 2,850 2,850 3,280 0.0 BHP 1.3 1.5 1.8 2.3 2.8 3.1 3.8 0.25 CFM 1,760 2,110 2,370 2,280 2,760 2,710 3,140 BHP 1.3 1.4 1.7 2.2 2.7 3.0 3.7 CFM 1,370 1,790 2,130 2,090 2,570 2.520 2,990 3,470 0.5 BHP 1.2 1.3 1.6 2.1 2.6 2.9 3.5 4.9 0.75 CFM 920 1,380 1,760 1,760 2,380 2,660 2,280 2,800 3,330 BHP 1.1 1.2 1.4 2.0 2.5 2.9 2.8 3.3 4.7 CFM 940 1,310 1,280 2,090 2,470 2,040 2,610 3,140 1.0 BHP 1.2 1.3 1.9 2.4 2.7 2.7 3.1 4.5 1.25 CFM 980 860 1,810 2,280 1,620 2,380 3,040 BHP 1.2 1.9 2.2 2.6 2.5 2.9 4.4 CFM 1,330 2,000 1,140 2,090 2,760 1.5 BHP 2.1 2.4 2.4 2.7 4.0

3

5

22

(800) 627-4499 · Fax: (608) 221-2824

HE3XINH

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE3XKINH...

Wall S (single) D (double) Phase 1 3 Voltage 4 (460) 5 (208-230) 7 (208-230/460) 8 (575) FA Hp K (2.0) L (3.0) M (5.0) EA Hp K (2.0) L (3.0) M (5.0) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

Other -- (none) W (white paint) C (custom paint)

UL L (UL listed) N (not UL listed)

23

www.RenewAire.com

HE3XINV

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 750-3,300 CFM ARI 1060 Certified Core: Three L125-00 Airflow Rating Points (for ARI): 2,250 CFM and 1,690 CFM Number Motors: Two HP 2 3 Volts 208-230 460 208-230 460 208-230 460 HZ 60 60 60 60 60 60 Phase 3 3 3 3 3 3 FLA 7.0-6.6 3.5 9.2-8.6 4.4

14.0-13.0 Min. Cir. Amps Max. Fuse Size

15.8 7.9 20.7 9.9 31.5 14.6

20 15 30 15 45 20

G4 Performance

CFM

1,500 2,000 2,500 3,000

5

6.5

Control Voltage: 24, 115, 230 Volt available Filters: Six total, MERV 8, 2" pleated, 20" x 20" nominal size Weight: 640 lbs (unit), 675 lbs (shipping weight)

Effectiveness (%)

80

Sensible

Shipping Dimensions: 45" W x 70" L x 70" H

Winter

60

Total

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components.)

er To

tal

Airflow Performance

External Static Pressure (Inches Water Column)

Motor HP Blower RPM Nominal Turns Open CFM 2 1,095 1,220 1,340 1,345 1,535 1,685 1,495 1,675 1,855 4 2 0 4.5 2 0 6.5 3.5 0 1,900 2,200 2,300 2,400 2,720 2,850 3,230 3.520 0.0 BHP 1.3 1.5 1.7 2.2 2.7 2.7 3.7 4.5 0.25 CFM 1,600 1,960 2,160 2,250 2,450 2,870 2,610 3,090 3,370 BHP 1.2 1.4 1.6 2.2 2.5 3.0 2.6 3.5 4.3 CFM 1,250 1,610 1,950 1,970 2,250 2,740 2.380 2,850 3,230 0.5 BHP 1.2 1.3 1.5 2.1 2.4 2.9 2.5 3.3 4.1 0.75 CFM 850 1,240 1,580 1,570 1,950 2,540 2,090 2,610 3,090 BHP 1.1 1.3 1.4 2.0 2.3 2.8 2.4 3.1 3.9 CFM 860 1,150 1,170 1,650 2,340 1,710 2,380 2,850 1.0 BHP 1.2 1.3 1.9 2.2 2.7 2.2 2.9 3.6 1.25 CFM 800 900 1,200 2,090 1,330 2,090 2,610 BHP 1.2 1.8 2.0 2.5 2.1 2.7 3.4 CFM 875 1,800 950 1,810 2,380 1.5 BHP 1.9 2.4 2.0 2.5 3.2

3

5

24

(800) 627-4499 · Fax: (608) 221-2824

HE3XINV

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE3XKINV...

Wall S (single) D (double) Phase 1 3 Voltage 4 (460) 5 (208-230) 7 (208-230/460) 8 (575) FA Hp K (2.0) L (3.0) M (5.0) EA Hp K (2.0) L (3.0) M (5.0) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

Other -- (none) W (white paint) C (custom paint)

UL L (UL listed) N (not UL listed)

25

www.RenewAire.com

HE4XINH

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 1,000-4,400 CFM ARI 1060 Certified Core: Four L125-00 Airflow Rating Points (for ARI): 3,000 CFM and 2,250 CFM Number Motors: Two HP 2 3 Volts 208-230 460 208-230 460 208-230 460 HZ 60 60 60 60 60 60 Phase 3 3 3 3 3 3 FLA 7.0-6.6 3.5 9.2-8.6 4.4

14.0-13.0 Min. Cir. Amps Max. Fuse Size

15.8 7.9 20.7 9.9 31.5 14.6

20 15 30 15 45 20

G4 Performance

CFM

1,000 2,000 3,000 4,000

5

6.5

Control Voltage: 24, 115, 230 Volt available Filters: Eight total, MERV 8, 2" pleated, 20" x 20" nominal size Weight: 846 lbs (unit), 900 lbs (shipping weight)

Effectiveness (%)

80

Sensible

Shipping Dimensions: 84" W x 92" L x 46" H

Winter Total

60

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components.)

er To

tal

Airflow Performance

External Static Pressure (Inches Water Column)

Motor HP Blower RPM Nominal Turns Open CFM 2 1,010 1,210 1,370 1,345 1,535 1,685 1,495 1,675 1,855 4.5 2 0 4.5 2 0 6 3 0 2,489 2,995 3,295 3,832 3,718 4,223 0.0 BHP 0.9 1.6 2.1 2.9 2.7 3.8 0.25 CFM 2,200 2,290 3,145 3,682 3,568 4,083 BHP 0.9 1.5 2.1 2.9 2.6 3.7 CFM 1,715 2,430 2,840 3,480 3,345 3,943 0.5 BHP 0.8 1.4 2.0 2.8 2.6 3.6 0.75 CFM 1,100 2,005 2,600 2,509 3,170 3,030 3,659 4,287 BHP 0.7 1.3 2.0 1.9 2.6 2.4 3.4 4.9 CFM 1,540 2,215 2,116 2,839 3,409 2,686 3,364 4,011 1.0 BHP 1.2 1.9 1.8 2.4 3.0 2.2 3.2 4.6 1.25 CFM 1,800 1,747 2,449 3,003 2,301 2,994 3,760 BHP 1.7 1.6 2.3 2.8 2.1 2.9 4.3 CFM 1,100 1,135 1,878 2,465 1,722 2,490 3,434 1.5 BHP 1.5 1.5 2.0 2.4 1.9 2.7 4.0

3

5

26

(800) 627-4499 · Fax: (608) 221-2824

HE4XINH

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE4XKINH...

Wall S (single) D (double) Phase 1 3 Voltage 4 (460) 5 (208-230) 7 (208-230/460) 8 (575) FA Hp K (2.0) L (3.0) M (5.0) EA Hp K (2.0) L (3.0) M (5.0) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

Other -- (none) W (white paint) C (custom paint)

UL L (UL listed) N (not UL listed)

27

www.RenewAire.com

HE4XINV

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 1,000-4,400 CFM ARI 1060 Certified Core: Four L125-00 Airflow Rating Points (for ARI): 3,000 CFM and 2,250 CFM Number Motors: Two HP 2 3 Volts 208-230 460 208-230 460 208-230 460 HZ 60 60 60 60 60 60 Phase 3 3 3 3 3 3 FLA 7.0-6.6 3.5 9.2-8.6 4.4

14.0-13.0 Min. Cir. Amps Max. Fuse Size

15.8 7.9 20.7 9.9 31.5 14.6

20 15 30 15 45 20

G4 Performance

CFM

1,000 2,000 3,000 4,000

5

6.5

Control Voltage: 24, 115, 230 Volt available Filters: Eight total, MERV 8, 2" pleated, 20" x 20" nominal size Weight: 815 lbs (unit), 875 lbs (shipping weight)

Sensible

Effectiveness (%)

80

Shipping Dimensions: 45" W x 90" L x 70" H

60

Winter

Total

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components.)

er To

tal

Airflow Performance

External Static Pressure (Inches Water Column)

Motor HP Blower RPM Nominal Turns Open CFM 2 1,010 1,210 1,370 1,345 1,535 1,685 1,495 1,675 1,855 4.5 2 0 4.5 2 0 6 3 0 2,300 2,800 3,068 3,042 3,452 3,348 3,896 0.0 BHP 0.9 1.5 2.2 2.0 2.7 2.7 3.9 0.25 CFM 1,810 2,350 2,754 2,705 3,226 3,114 3,688 BHP 0.8 1.4 2.0 1.9 2.6 2.6 3.7 CFM 1,300 1,950 2,430 2,341 2,955 2,820 3,466 4,229 0.5 BHP 0.7 1.3 1.9 1.8 2.5 2.4 3.6 4.9 0.75 CFM 1,500 2,082 1,983 2,696 3,148 2,549 3,232 3,979 BHP 1.3 1.8 1.7 2.3 2.9 2.3 3.4 4.6 CFM 1,050 1,725 1,611 2,422 2,884 2,268 2,972 3,700 1.0 BHP 1.2 1.7 1.6 2.2 2.8 2.2 3.2 4.3 1.25 CFM 1,342 1,211 2,093 2,595 1,917 2,694 3,430 BHP 1.6 1.5 2.0 2.6 2.1 3.0 4.0 CFM 1,722 2,269 1,523 2,392 3,178 1.5 BHP 1.9 2.4 1.9 2.8 3.8

3

5

28

(800) 627-4499 · Fax: (608) 221-2824

HE4XINV

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE4XKINV...

Wall S (single) D (double) Phase 1 3 Voltage 4 (460) 5 (208-230) 7 (208-230/460) 8 (575) FA Hp K (2.0) L (3.0) M (5.0) EA Hp K (2.0) L (3.0) M (5.0) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

Other -- (none) W (white paint) C (custom paint)

UL L (UL listed) N (not UL listed)

29

www.RenewAire.com

HE6XIN

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 1,500-6,500 CFM ARI 1060 Certified Core: Six L125-00 Airflow Rating Points (for ARI): 4,500 CFM and 3,375 CFM Number Motors: Two HP 5 7.5 Volts 208-230 460 208-230 460 HZ 60 60 60 60 Phase 3 3 3 3 FLA 14.2-13.0 6.5 20.9-19.2 9.6

Min. Cir. Amps Max. Fuse Size

32 14.6 47 21.6

50 20 70 30

G4 Performance

CFM

3,000 4,000 5,000 6,000

Control Voltage: 24, 115, 230 Volt available Filters: Twelve total, MERV 8, 2" pleated, 20" x 20" nominal size Weight: 2,340 lbs (unit), 2,640 lbs (shipping weight) Shipping Dimensions: 85" W x 114" L x 85" H

Effectiveness (%)

80

Sensible

60

Winter

Total

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components.)

er To

tal

Airflow Performance

External Static Pressure (Inches Water Column)

Motor HP Blower RPM Nominal Turns Open CFM 5 1,460 1,610 1,725 1,560 1,740 1,865 4.5 2 0 4.5 2 0 5,005 5,550 5,275 5,950 6,500 0.0 BHP 3.2 4.2 3.7 5.0 6.5 0.25 CFM 4,800 5,375 5,200 5,825 6,350 BHP 3.2 4.2 3.6 5.0 6.5 CFM 4,650 5,250 4,900 5,625 6,225 0.5 BHP 3.1 4.1 3.5 4.9 6.4 0.75 CFM 4,475 5,100 5,525 4,775 5,490 6,125 BHP 3.0 4.1 5.0 3.5 4.9 6.4 CFM 4,200 4,900 5,475 4,550 5,325 5,910 1.0 BHP 2.9 4.0 5.0 3.4 4.8 6.3 1.25 CFM 4,000 4,650 5,200 4,350 5,125 5,825 BHP 2.8 3.9 4.9 3.3 4.7 6.2 CFM 3,750 4,500 5,050 4,125 4,950 5,625 1.5 BHP 2.8 3.8 4.8 3.3 4.7 6.1

7.5

30

(800) 627-4499 · Fax: (608) 221-2824

HE6XIN

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE6XKIN...

Wall S (single) D (double) Phase 3 Voltage 4 (460) 5 (208-230) 8 (575) FA Hp M (5.0) N (7.5) EA Hp M (5.0) N (7.5) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

Other -- (none) W (white paint) C (custom paint)

31

www.RenewAire.com

HE8XIN

Indoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 2,000-8,000 CFM ARI 1060 Certified Core: Eight L125-00 Airflow Rating Points (for ARI): 6,000 CFM and 4,500 CFM Number Motors: Two HP 5 7.5 Volts 208-230 460 208-230 460 208-230 460 HZ 60 60 60 60 60 60 Phase 3 3 3 3 3 3 FLA 14.2-13.0 6.5 20.9-19.2 9.6 28.2-28.0 14

Min. Cir. Amps Max. Fuse Size

32 14.6 47 21.6 63.5 31.5

50 20 70 30 90 50

G4 Performance

CFM

2,000 4,000 6,000 8,000

10

Control Voltage: 24, 115, 230 Volt available Filters: Sixteen total, MERV 8, 2" pleated, 20" x 20" nominal size Weight: 2,525 lbs (unit), 2,825 lbs (shipping weight)

Effectiveness (%)

80

Sensible

Shipping Dimensions: 85" W x 114" L x 85" H

60

Winter

Total

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components.)

er To

tal

Airflow Performance

External Static Pressure (Inches Water Column)

Motor HP Blower RPM Nominal Turns Open CFM 5 1,460 1,610 1,725 1,560 1,740 1,865 1,810 2,020 2,105 4.5 2 0.5 4.5 2 0 4.5 2 1 5,575 6,200 6,550 6,000 6,700 7,000 7,850 0.0 BHP 3.2 4.3 5.0 3.9 5.3 6.1 8.5 0.25 CFM 5,425 6,010 6,380 5,850 6,575 6,875 7,745 BHP 3.2 4.3 5.0 3.9 5.3 6.1 8.5 CFM 5,200 5,875 6,210 5,650 6,400 6,750 7,625 7,950 0.5 BHP 3.2 4.2 5.0 3.8 5.3 6.1 8.5 9.6 0.75 CFM 5,000 5,700 6,100 5,475 6,300 6,800 6,600 7,450 7,800 BHP 3.2 4.2 5.0 3.8 5.3 7.5 6.0 8.4 9.6 CFM 4,775 5,500 5,880 5,275 6,125 6,675 6,425 7,350 7,725 1.0 BHP 3.1 4.2 4.9 3.8 5.3 7.5 6.0 8.4 9.6 1.25 CFM 4,550 5,325 5,730 5,100 5,950 6,500 6,275 7,200 7,600 BHP 3.0 4.1 4.8 3.7 5.2 7.5 6.0 8.3 9.5 CFM 4,270 5,125 5,510 4,875 5,750 6,375 6,100 7,050 7,450 1.5 BHP 2.9 4.1 4.8 3.7 5.2 7.4 5.9 8.3 9.5

7.5

10

32

(800) 627-4499 · Fax: (608) 221-2824

HE8XIN

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE8XKIN...

Wall S (single) D (double) Phase 3 Voltage 4 (460) 5 (208-230) 8 (575) FA Hp M (5.0) N (7.5) P (10.0) EA Hp M (5.0) N (7.5) P (10.0) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

Other -- (none) W (white paint) C (custom paint)

33

www.RenewAire.com

Commercial OutDOOR Products

· Many airflow orientation options (see page 68). · Weatherized cabinets with hoods for outdoor applications. · Wide range of airflow and static capacities. · Easy installation and service. · ARI certified performance data for efficiency and cross leakage. · UL tested flammability and smoke generation that meets NFPA 90A and 90B test standards for commercial applications. · Ten year core warranty.

RenewAire means Trouble-Free ERV.

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Contact RenewAire for other application schematics.

34

(800) 627-4499 · Fax: (608) 221-2824

Packaged Rooftop Energy Recovery Ventilators: EV450RT, HE1XRT, HE2XRT, HE3XRT, HE4XRT, HE6XRT & HE8XRT

Part I - General

A. Product Specification The unit shall be a packaged static plate energy recovery ventilator. RenewAire shall be the basis of design. B. Quality Assurance 1. The energy recovery core shall be certified by ARI under its Standard 1060 for Energy Recovery Ventilators. Products not currently ARI Certified will not be accepted. 2. Unit shall be Listed under UL 1812, Standard for Ducted Air to Air Heat Exchangers. Specific UL-1812 Listing Standards for outdoor units including rain testing, UV exposure testing, corrosion resistance and temperature extremes testing shall be required for these models. Due to ongoing product offerings and upgrades, some models and options are not included in UL Listing reports. Consult RenewAire for more information. 3. The energy recovery core shall meet NFPA 90A and 90B requirements for flame spread, not to exceed 25, and smoke generation, not to exceed 50, through an ongoing testing and verification program using UL Standard 723. 4. The RenewAire core shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of ten years from the date of purchase. Balance of Unit shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of two years from the date of purchase. D. Laminar Flow Airflow through the energy recovery core shall be laminar, avoiding deposition of particulates on the interior of the exchange plate material.

Part III ­ Product

A. Construction 1. The energy recovery core shall be of static plate, cross-flow construction, with no moving parts. 2. The unit shall be capable of operating in winter and summer conditions without generating condensate. No condensate pan or drain shall be required. 3. The unit cabinet shall be constructed of G90 galvanized, 20-gauge steel, with lapped corners. 4. The unit shall have single-point power connection. 5. The exhaust and fresh airsteams shall both be protected by MERV 8 rated, 2 inch pleated, disposable filters positioned before the ERV core. 6. Weatherhoods shall be screened to exclude birds and animals. Inlet weatherhood shall be sized to maintain inlet velocities below 500 fpm, and equipped with rain excluder baffles. B. Configuration 1. Unit shall be available from factory with vertical or horizontal return air and/or vertical or horizontal supply air duct connection openings. (Select from RTH, RTF, RTV or RTR configuration ­ see separate product specifications for duct opening details). 2. RTC (Rooftop Connect) units shall have return air and fresh air ducts configured to permit direct tie in to rooftop air handlers using factory offered transition piece. (See separate specification for transition piece availability). C. Options 1. Non-pitched roof curbs shall be available from the factory for use with all configurations of the rooftop series units. 2. Rooftop series units shall be available in double wall construction. 3. Transition pieces for RTC installation shall be available for major manufacturers packaged rooftop air conditioning units.

Part II ­ Performance

A. Energy Transfer The energy recovery core shall be capable of transferring both sensible and latent energy between airsteams. Latent energy transfer shall be accomplished through molecular transport by hydroscopic resin. B. Passive Frost Control The energy recovery core shall perform without the occurrence of condensation or frosting under normal operating conditions (defined as outside temperatures above -10°F and inside relative humidity below 40%). Occasional extreme conditions shall not affect the usual function or performance of the energy recovery core. C. Positive Airsteam Separation Exhaust and fresh airstreams shall at all times travel in separate passages, and airstreams shall not mix. The exhaust air transfer ratio (EATR) shall be ARI-1060 certified as 0% at balanced pressure.

35

www.RenewAire.com

EV450RT

Outdoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 240-550 CFM ARI 1060 Certified Core: One L85 Airflow Rating Points (for ARI): 450 CFM and 338 CFM Motors: One, 0.6 hp (Single Phase) One, 0.5 hp (Three Phase) Field Selectable Voltage V 115 208-230 277 HZ 60 60 60 60 60 Phase Single Single Single Three Three FLA 7.0 3.5 2.4 1.7-1.5 0.8

G4 Performance

Airflow CFM

240 338 380 450 500 550 600

208-230 Temp EFF%

81 77 76 73 71 69 68

ESP in H 20

1.00 0.85 0.75 0.50 0.25 0.00 -0.25

Watts 1P 3P

425 474 496 534 563 593 623 243 313 345 412 461 516 572

Total EFF% Winter/Summer*

73/60 69/56 68/54 65/50 63/48 62/46 60/43

460

Control Voltage: 24 VAC Filters: Two total, MERV 8, 2" pleated, 14" x 20" nominal size Weight: 185 lbs (unit), 235 lbs (shipping weight) Shipping Dimensions: 48" W x 90" L x 25" H (on pallet)

*At ARI 1060 standard conditions (See certified data on page 66 for core components.)

Dimensions

FA

RA

EA OA

PWR AND CONTROL WIRING DRILL HERE OR THRU BOTTOM

EBOX

TOP VIEW WITH DOOR OFF

FILTERS

37 1/2" 2 7/8" 3 1/8" 19 1/4" 4 3/4"

EA

LEFT VIEW 4 3/8" 33 7/8" 12 3/8" 3 1/8" 1

OA

RIGHT VIEW FRONT VIEW 47 7/8" 74 7/8"

FA

RA

36

(800) 627-4499 · Fax: (608) 221-2824

EV450RT

Application options

Standard Roof Curb Shown (available option). Curbs for sloped roofs or metal roofing are available on a custom basis from RenewAire or from local curb fabricators.

For horizontal connection of either the Fresh Air duct or the Return Air duct, stack the optional RTF/RTR Adapter on the Standard Roof Curb. Duct openings to be field cut into adapter. Opening location and size is flexible.

The RTH/RTC Adapter allows horizontal connection of both the Fresh Air and the Return Air ducts. It is also possible to connect the adapter directly to the return plenum of most Rooftop Units (openings must be cut into RTU). Duct openings to be field cut into adapter. Opening location and size is flexible.

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

37

www.RenewAire.com

HE1XRT

Outdoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 250-870 CFM ARI 1060 Certified Core: One L125-00 Airflow Rating Points (for ARI): 750 CFM and 560 CFM Number Motors: Two, 0.75 hp Field Selectable Voltage (you must order phase) V 115 208-230 277 HZ 60 60 60 60 60 Phase Single Single Single Three Three FLA 8.6 4.3 2.4 2.1 1.1

Min. Cir. Amps Max. Fuse Size

19.4 9.7 5.4 4.7 2.5

25 15 15 15 15

G4 Performance

Airflow CFM

250 560 650 730 750 820 950

208-230 Temp EFF%

82 75 73 72 71 69 67

ESP in H 20

1.75 1.45 1.25 1.00 0.90 0.50 0.00

Watts 1P 3P

1,080 1,220 1,300 1,385 1,400 1,475 1,630 685 955 1,060 1,155 1,175 1,255 1,430

Total EFF% Winter/Summer*

74/61 67/53 65/51 64/49 63/48 62/47 59/44

460

Control Voltage: 24, 115, 230 VAC Filters: Two total, MERV 8, 2" pleated, 20" x 20" nominal size Weight: 250 lbs (unit), 330 lbs (shipping weight) Shipping Dimensions: 31" W x 76" L x 45" H Options: Controls (see pages 64 & 65) Roof curb Alternate duct connections

*At ARI 1060 standard conditions (See certified data on page 66 for core components).

Base Type/Airflow Orientations

RTV

EA OA

EA

RTF

OA RA

FA

FA

RA

RTR

EA FA OA

EA FA

RTH

OA RA

RA

38

(800) 627-4499 · Fax: (608) 221-2824

HE1XRT

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

CURB1X

Model Configuration HE1XKRT...

Base Type V (vertical) H (horizontal) R (RA vertical) F (FA vertical) Wall S (single) D (double) Phase 1 3 Voltage 1 (115) 4 (460) 5 (208-230) 6 (115/208-230) 7 (208-230/460) 9 (277) Filter Monitor -- (none) F (filter monitor) Other -- (none) W (white paint) C (custom paint) UL L (UL listed) N (not UL listed) FA Hp H (0.75) EA Hp H (0.75) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40)

39

www.RenewAire.com

HE1XRTC

Outdoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 500-1,000 CFM ARI 1060 Certified Core: One L125-00 Airflow Rating Points (for ARI): 750 CFM and 560 CFM Number Motors: Two, 0.75 hp Field Selectable Voltage (you must order phase) V 115 208-230 277 HZ 60 60 60 60 60 Phase Single Single Single Three Three FLA 8.6 4.3 2.4 2.1 1.1

Min. Cir. Amps Max. Fuse Size

19.4 9.7 5.4 4.7 2.5

25 15 15 15 15

G4 Performance

CFM

300 500 700 900

208-230 460

Control Voltage: 24 VAC Filters: Two total, MERV 8, 2" pleated, 20" x 20" nominal size

Effectiveness (%)

80

Sensible

Weight: 300 lbs (unit), 375 lbs (shipping weight) Shipping Dimensions: 40" W x 87" L x 45" H

60

Winter

Summe

Total

r Total

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components).

Airflow Performance

Damper Position 100% Open 65% Open 55% Open 45% Open 35% Open 25% Open 15% Open Total Watts -0.5 1 Phase 1,295 1,285 1,275 1,265 1,265 1,265 1,260 3 Phase 1,155 1,140 1,130 1,120 1,110 1,100 1,085 EA 855 785 775 750 695 625 575 FA 1,035 980 965 920 860 780 585 EA 900 820 805 775 730 660 615

Static Pressure in Adjacent Air Handler (Inches Water Column)

-0.25 FA 985 945 920 875 820 750 630 EA 950 855 840 805 760 685 650 0.0 FA 940 900 875 935 775 715 665 EA 985 890 865 830 790 715 685 +0.25 FA 885 855 835 790 740 680 705 EA 1,045 935 900 860 820 750 730 +0.5 FA 835 810 790 750 700 650 745

40

(800) 627-4499 · Fax: (608) 221-2824

HE1XRTC

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE1XKRTC...

Wall S (single) D (double) Phase 1 3 Voltage 1 (115) 4 (460) 5 (208-230) 6 (115/208-230) 7 (208-230/460) 9 (277) Other -- (none) W (white paint) C (custom paint) UL L (UL listed) N (not UL listed) FA Hp H (0.75) EA Hp H (0.75) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

41

www.RenewAire.com

HE2XRT

Outdoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 500-2,000 CFM ARI 1060 Certified Core: Two L125-00 Airflow Rating Points (for ARI): 1,500 CFM and 1,120 CFM Number Motors: Direct Drive (DD) Four, Belt Drive (BD) Two Field Selectable Voltage (you must order phase) HP DD 0.75 Volts 115 208-230 208-230 460 208-230 460 HZ 60 60 60 60 60 60 Phase 1 1 3 3 3 3 FLA 8.6 4.3 5.6-5.0 2.8 7.0-6.6 3.5

Min. Cir. Amps Max. Fuse Size

36.6 18.3 12.6 6.3 15.8 7.9

45 20 20 15 20 15

G4 Performance

CFM

500 1,000 1,500 2,000

BD 1.5 BD 2

Control Voltage: 24, 115, 230 Volt available Filters: Four total, MERV 8, 2" pleated, 20" x 20" nominal size

Effectiveness (%)

80

Sensible

Weight: 488 lbs (unit), 525 lbs (shipping weight) Shipping Dimensions: 51" W x 76" L x 45" H

60

Winter

Total

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components).

er To

tal

Base Type/Airflow Orientations

RTV

EA OA

EA

RTF

OA RA

FA

FA

RA

RTR

EA FA OA

EA FA

RTH

OA RA

RA

Airflow Performance

Motor HP Blower RPM Nominal N/A N/A 1,000 1,230 1,420 1,220 1,470 1,660 Turns Open CFM 0.75 (Four DD) 1.5 (Two BD) 2 (Two BD) N/A N/A 4.5 2 0 4.5 2 0 0.0 BHP CFM 0.25 BHP CFM 0.5 BHP CFM 0.75 BHP

External Static Pressure (Inches Water Column)

1.0 CFM BHP CFM 1.25 BHP CFM 930 1,125 1,475 1.5 BHP 0.9 1.1 1.7

1,770 CFM 2,220 Watts 1,378 1,694 1,956 1,681 2,025 0.5 0.9 1.4 0.9 1.6 -

1,680 CFM 2,145 Watts 1,175 1,550 1,850 1,530 1,925 0.5 0.9 1.4 0.9 1.5 -

1,555 CFM 2,015 Watts 900 1,335 1,680 1,315 1,750 2,000 0.4 0.8 1.2 0.7 1.4 2.0

1,375 CFM 1,825 Watts 635 1,125 1,475 1,100 1,575 1,900 0.4 0.7 1.2 0.7 1.3 1.9

1,110 CFM 1,560 Watts 1,000 1,300 975 1,375 1,750 0.7 1.1 0.6 1.2 1.8

760 CFM 1,195 Watts 500 1,200 430 1,275 1,570 0.6 1.1 0.6 1.2 1.7

42

(800) 627-4499 · Fax: (608) 221-2824

HE2XRT

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

CURB2X

Model Configuration HE2XKRT...

Base Type V (vertical) H (horizontal) R (RA vertical) F (FA vertical) Wall S (single) D (double) Phase 1 3 Voltage 4 (460) 5 (208-230) 6 (115/208-230) 7 (208-230/460) 8 (575) 9 (277) Filter Monitor -- (none) F (filter monitor) Other -- (none) W (white paint) C (custom paint) UL L (UL listed) N (not UL listed) FA Hp J (1.5) K (2.0) Q (two 0.75) EA Hp J (1.5) K (2.0) Q (two 0.75) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40)

43

www.RenewAire.com

HE2XRTC

Outdoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 1,000-1,700 CFM ARI 1060 Certified Core: Two L125-00 Airflow Rating Points (for ARI): 1,500 CFM and 1,120 CFM Number Motors: Two, Belt Drive HP BD 2 BD 2 Volts 115 208-230 208-230 460 HZ 60 60 60 60 Phase 1 1 3 3 FLA 18.0 10.0-9.0 7.0-6.6 3.5

Min. Cir. Amps Max. Fuse Size

40.5 22.4 15.8 7.9

60 30 20 15

G4 Performance

CFM

500 1,000 1,500 2,000

Control Voltage: 24 Volt available Filters: Four total, MERV 8, 2" pleated, two 20" x 20" nominal size,

and two 14" x 20" nominal size

Weight: 538 lbs (unit), 575 lbs (shipping weight) Shipping Dimensions: 51" W x 76" L x 45" H

Effectiveness (%)

80

Sensible

60

Winter

Total

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components).

er To

tal

Airflow Performance

Static Pressure in Adjacent Air Handler (Inches Water Column)

Blower RPM Nominal 1,420 1,360 Exhaust Air 1,300 1,240 1,180 1,675 1,595 Fresh Air 1,515 1,435 1,355 Turns Open CFM 0 1 2 3 4 0 1 2 3 4 1,700 1,540 1,375 1,240 1,080 1,720 1,630 1,530 1,415 -0.5 BHP 1.8 1.7 1.5 1.4 1.3 2.0 1.9 1.8 1.6 CFM 1,850 1,720 1,600 1,440 1,300 1,620 1,520 1,430 1,310 -0.25 BHP 1.9 1.8 1.7 1.6 1.4 2.0 1.8 1.7 1.6 CFM 1,860 1,740 1,625 1,500 1,630 1,530 1,430 1,320 1,225 0.0 BHP 1.9 1.8 1.7 1.5 2.0 1.9 1.8 1.7 1.5 CFM 1,920 1,800 1,690 1,575 1,575 1,440 1,355 1,250 1,150 +0.25 BHP 2.0 1.8 1.7 1.6 2.0 1.8 1.7 1.6 1.5 CFM 1,980 1,860 1,740 1,640 1,465 1,355 1,230 1,135 1,035 +0.5 BHP 2.0 1.9 1.7 1.6 1.9 1.7 1.6 1.5 1.4

44

(800) 627-4499 · Fax: (608) 221-2824

HE2XRTC

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE2XKRTC...

Wall S (single) D (double) Phase 1 3 Voltage 4 (460) 5 (208-230) 6 (115/208-230) 7 (208-230/460) 8 (575) FA Hp K (2.0) EA Hp K (2.0) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

Other -- (none) W (white paint) C (custom paint)

UL L (UL listed) N (not UL listed)

45

www.RenewAire.com

HE3XRT

Outdoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 750-3,000 CFM ARI 1060 Certified Core: Three L125-00 Airflow Rating Points (for ARI): 2,250 CFM and 1,690 CFM Number Motors: Two HP 2 3 Volts 208-230 460 208-230 460 208-230 460 HZ 60 60 60 60 60 60 Phase 3 3 3 3 3 3 FLA 7.0-6.6 3.5 9.2-8.6 4.4

14.0-13.0 Min. Cir. Amps Max. Fuse Size

15.8 7.9 20.7 9.9 31.5 14.6

20 15 30 15 45 20

G4 Performance

CFM

1,500 2,000 2,500 3,000

5

6.5

Control Voltage: 24, 115, 230 Volt available Filters: Six total, MERV 8, 2" pleated, 20" x 20" nominal size Weight: 726 lbs (unit), 755 lbs (shipping weight)

Effectiveness (%)

80

Sensible

Shipping Dimensions: 72" W x 84" L x 49" H

Winter

60

Total

Base Type/Airflow Orientations

RTV

RTF

OA

EA OA RA

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components).

er To

tal

EA

FA

FA

RA

RTR

EA FA OA

EA FA

RTH

OA RA

RA

Airflow Performance

External Static Pressure (Inches Water Column)

Motor HP Blower RPM Nominal Turns Open CFM 2 1,095 1,220 1,340 1,345 1,535 1,685 1,495 1,675 1,855 4 2 0 4.5 2 0 6.5 3.5 0 2,040 2,340 2,590 2,420 2,850 2,850 3,280 0.0 BHP 1.3 1.5 1.8 2.3 2.8 3.1 3.8 0.25 CFM 1,760 2,110 2,370 2,280 2,760 2,710 3,140 BHP 1.3 1.4 1.7 2.2 2.7 3.0 3.7 CFM 1,370 1,790 2,130 2,090 2,570 2.520 2,990 3,470 0.5 BHP 1.2 1.3 1.6 2.1 2.6 2.9 3.5 4.9 0.75 CFM 920 1,380 1,760 1,760 2,380 2,660 2,280 2,800 3,330 BHP 1.1 1.2 1.4 2.0 2.5 2.9 2.8 3.3 4.7 CFM 940 1,310 1,280 2,090 2,470 2,040 2,610 3,140 1.0 BHP 1.2 1.3 1.9 2.4 2.7 2.7 3.1 4.5 1.25 CFM 980 860 1,810 2,280 1,620 2,380 3,040 BHP 1.2 1.9 2.2 2.6 2.5 2.9 4.4 CFM 1,330 2,000 1,140 2,090 2,760 1.5 BHP 2.1 2.4 2.4 2.7 4.0

3

5

46

(800) 627-4499 · Fax: (608) 221-2824

HE3XRT

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

CURB3X

Model Configuration HE3XKRT...

Base Type V (vertical) H (horizontal) R (RA vertical) F (FA vertical) Filter Monitor -- (none) F (filter monitor) Other -- (none) W (white paint) C (custom paint) Wall S (single) D (double) Phase 1 3 Voltage 4 (460) 5 (208-230) 7 (208-230/460) 8 (575) UL L (UL listed) N (not UL listed) FA Hp K (2.0) L (3.0) M (5.0) EA Hp K (2.0) L (3.0) M (5.0) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40)

47

www.RenewAire.com

HE3XRTC

Outdoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 1,700-2,500 CFM ARI 1060 Certified Core: Three L125-00 Airflow Rating Points (for ARI): 2,250 CFM and 1,690 CFM Number Motors: Two HP 3 Volts 208-230 460 HZ 60 60 Phase 3 3 FLA 9.2-8.6 4.4

Min. Cir. Amps Max. Fuse Size

20.7 9.9

30 15

Control Voltage: 24 Volt available Filters: Five total, MERV 8, 2" pleated, three 20" x 20" and two 16" x 25" nominal size

G4 Performance

CFM

1,500 2,000 2,500 3,000

Weight: 775 lbs (unit), 830 lbs (shipping weight) Shipping Dimensions: 72" W x 84" L x 50" H

Effectiveness (%)

80

Sensible

60

Winter

Total

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components).

er To

tal

Airflow Performance

Static Pressure in Adjacent Air Handler (Inches Water Column)

Blower RPM Nominal 1,520 1,465 Exhaust Air 1,405 1,345 1,285 1,800 1,740 Fresh Air 1,680 1,620 1,560 Turns Open CFM 0 1 2 3 4 0 1 2 3 4 2,130 2,000 1,915 1,725 2,565 2,480 2,375 2,290 2,200 -0.5 BHP 2.9 2.5 2.3 1.8 3.0 2.8 2.6 2.4 2.1 CFM 2,245 2,135 1,950 2,385 2,290 2,210 2,125 2,040 -0.25 BHP 2.8 2.6 2.1 2.9 2.7 2.5 2.4 2.1 CFM 2,455 2,345 2,180 2,225 2,150 2,070 1,990 1,910 0.0 BHP 3.0 2.7 2.3 2.8 2.6 2.4 2.3 2.0 CFM 2,475 2,345 2,065 1,975 1,910 1,825 1,725 +0.25 BHP 2.8 2.4 2.7 2.5 2.3 2.1 1.9 CFM 2,575 2,455 1,830 1,740 1,645 1,555 1,450 +0.5 BHP 2.9 2.5 2.4 2.2 2.0 1.8 1.5

48

(800) 627-4499 · Fax: (608) 221-2824

HE3XRTC

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE3XKRTC...

Wall S (single) D (double) Phase 3 Voltage 4 (460) 5 (208-230) 7 (208-230/460) 8 (575) FA Hp L (3.0) EA Hp L (3.0) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

Other -- (none) W (white paint) C (custom paint)

UL L (UL listed) N (not UL listed)

49

www.RenewAire.com

HE4XRT

Outdoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 1,000-4,400 CFM ARI 1060 Certified Core: Four L125-00 Airflow Rating Points (for ARI): 3,000 CFM and 2,250 CFM Number Motors: Two HP 2 3 Volts 208-230 460 208-230 460 208-230 460 HZ 60 60 60 60 60 60 Phase 3 3 3 3 3 3 FLA 7.0-6.6 3.5 9.2-8.6 4.4

14.0-13.0 Min. Cir. Amps Max. Fuse Size

15.8 7.9 20.7 9.9 31.5 14.6

20 15 30 15 45 20

G4 Performance

CFM

1,000 2,000 3,000 4,000

5

6.5

Control Voltage: 24, 115, 230 Volt available Filters: Eight total, MERV 8, 2" pleated, 20" x 20" nominal size Weight: 915 lbs (unit), 1,000 lbs (shipping weight)

Effectiveness (%)

80

Sensible

Shipping Dimensions: 84" W x 92" L x 49" H

60

Winter

Total

Base Type/Airflow Orientations

RTV

RTF

OA

EA OA RA

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components).

er To

tal

EA

FA

FA

RA

RTR

EA FA OA

EA FA

RTH

OA RA

RA

Airflow Performance

External Static Pressure (Inches Water Column)

Motor HP Blower RPM Nominal Turns Open CFM 2 1,010 1,210 1,370 1,345 1,535 1,685 1,495 1,675 1,855 4.5 2 0 4.5 2 0 6 3 0 2,489 2,995 3,295 3,832 3,718 4,223 0.0 BHP 0.9 1.6 2.1 2.9 2.7 3.8 0.25 CFM 2,200 2,290 3,145 3,682 3,568 4,083 BHP 0.9 1.5 2.1 2.9 2.6 3.7 CFM 1,715 2,430 2,840 3,480 3,345 3,943 0.5 BHP 0.8 1.4 2.0 2.8 2.6 3.6 0.75 CFM 1,100 2,005 2,600 2,509 3,170 3,030 3,659 4,287 BHP 0.7 1.3 2.0 1.9 2.6 2.4 3.4 4.9 CFM 1,540 2,215 2,116 2,839 3,409 2,686 3,364 4,011 1.0 BHP 1.2 1.9 1.8 2.4 3.0 2.2 3.2 4.6 1.25 CFM 1,800 1,747 2,449 3.003 2,301 2,994 3,760 BHP 1.7 1.6 2.3 2.8 2.1 2.9 4.3 CFM -1,100 1,135 1,878 2,465 1,722 2,490 3,434 1.5 BHP 1.5 1.5 2.0 2.4 1.9 2.7 4.0

3

5

50

(800) 627-4499 · Fax: (608) 221-2824

HE4XRT

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

CURB4X

Model Configuration HE4XKRT...

Base Type V (vertical) H (horizontal) R (RA vertical) F (FA vertical) Filter Monitor -- (none) F (filter monitor) Other -- (none) W (white paint) C (custom paint) Wall S (single) D (double) Phase 1 3 Voltage 4 (460) 5 (208-230) 7 (208-230/460) 8 (575) UL L (UL listed) N (not UL listed) FA Hp K (2.0) L (3.0) M (5.0) EA Hp K (2.0) L (3.0) M (5.0) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40)

51

www.RenewAire.com

HE4XRTC

Outdoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 2,500-3,700 CFM ARI 1060 Certified Core: Four L125-00 Airflow Rating Points (for ARI): 3,000 CFM and 2,250 CFM Number Motors: Two HP 5 Volts 208-230 460 HZ 60 60 Phase 3 3 FLA 14.0-13.0 6.5

Min. Cir. Amps Max. Fuse Size

31.5 14.6

45 20

Control Voltage: 24 Volt available Filters: Six total, MERV 8, 2" pleated, four 20" x 20", and two 16" x 25" nominal size

G4 Performance

CFM

1,000 2,000 3,000 4,000

Weight: 965 lbs (unit), 1,050 lbs (shipping weight) Shipping Dimensions: 84" W x 92" L x 50" H

Effectiveness (%)

80

Sensible

60

Winter

Total

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components).

er To

tal

Airflow Performance

Blower RPM Nominal

1,600 1,555 1,515 Exhaust Air 1,470 1,430 1,385 1,340 1,805 1,755 Fresh Air 1,705 1,655 1,605 1,555

Turns Open

CFM

Static Pressure in Adjacent Air Handler (Inches Water Column)

-0.5 BHP CFM -0.25 BHP CFM 0.0 BHP CFM +0.25 BHP CFM +0.5 BHP

0 1 2 3 4 5 6 1 2 3 4 5 6

3,700 3.575 3,415 3,235 3,085 2,980 2,880 3,710 3,600 3,510 3,400

3.6 3.5 3.2 2.9 2.7 2.5 2.3 5.0 4.8 4.3 3.9

4,000 3.900 3,740 3,600 3,455 3,280 3,135 3,585 3,470 3,335 3,220

3.8 3.6 3.5 3.2 3.0 2.7 2.5 4.9 4.6 4.1 3.8

4,250 4,220 4,135 4,000 3,820 3,640 3,475 3,410 3,310 3,210 3,110 3,010

4.3 3.9 3.8 3.6 3.2 2.9 2.7 4.9 4.5 4.2 3.7 3.4

4,325 4,275 4,215 4,140 3,985 3,840 3,190 3,130 3,030 2,920 2,810

4.3 4.2 4.0 3.6 3.2 2.9 4.6 4.2 3.8 3.4 3.2

4,380 4,340 4,300 4,260 4,170 4,080 3,210 3,110 3,010 2,910 2,800 2,710

4.6 4.5 4.3 3.8 3.4 3.0 4.9 4.3 3.9 3.6 3.2 3.0

52

(800) 627-4499 · Fax: (608) 221-2824

HE4XRTC

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration HE4XKRTC...

Wall S (single) D (double) Phase 3 Voltage 4 (460) 5 (208-230) 7 (208-230/460) 8 (575) FA Hp M (5.0) EA Hp M (5.0) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40) Filter Monitor -- (none) F (filter monitor)

Other -- (none) W (white paint) C (custom paint)

UL L (UL listed) N (not UL listed)

53

www.RenewAire.com

HE6XRT

Outdoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 1,500-6,500 CFM ARI 1060 Certified Core: Six L125-00 Airflow Rating Points (for ARI): 4,500 CFM and 3,375 CFM Number Motors: Two HP 5 7.5 Volts 208-230 460 208-230 460 HZ 60 60 60 60 Phase 3 3 3 3 FLA 14.2-13.0 6.5 20.9-19.2 9.6

Min. Cir. Amps Max. Fuse Size

32 14.6 47 21.6

50 20 70 30

G4 Performance

CFM

3,000 4,000 5,000 6,000

Control Voltage: 24, 115, 230 Volt available Filters: Twelve total, MERV 8, 2" pleated, 20" x 20" nominal size Weight: 2,410 lbs (unit), 2,710 lbs (shipping weight) Shipping Dimensions: 85" W x 114" L x 85" H

Effectiveness (%)

80

Sensible

Base Type/Airflow Orientations

RTV

EA OA

EA

60

Winter

RTF

OA RA

Total

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components).

er To

FA

FA

tal

RA

RTR

EA FA OA

EA FA

RTH

OA RA

RA

Airflow Performance

External Static Pressure (Inches Water Column)

Motor HP Blower RPM Nominal Turns Open CFM 5 1,460 1,610 1,725 1,560 1,740 1,865 4.5 2 0 4.5 2 0 5,005 5,550 5,275 5,950 6,500 0.0 BHP 3.2 4.2 3.7 5.0 6.5 0.25 CFM 4,800 5,375 5,200 5,825 6,350 BHP 3.2 4.2 3.6 5.0 6.5 CFM 4,650 5,250 4,900 5,625 6,225 0.5 BHP 3.1 4.1 3.5 4.9 6.4 0.75 CFM 4,475 5,100 5,525 4,775 5,490 6,125 BHP 3.0 4.1 5.0 3.5 4.9 6.4 CFM 4,200 4,900 5,475 4,550 5,325 5,910 1.0 BHP 2.9 4.0 5.0 3.4 4.8 6.3 1.25 CFM 4,000 4,650 5,200 4,350 5,125 5,825 BHP 2.8 3.9 4.9 3.3 4.7 6.2 CFM 3,750 4,500 5,050 4,125 4,950 5,625 1.5 BHP 2.8 3.8 4.8 3.3 4.7 6.1

7.5

54

(800) 627-4499 · Fax: (608) 221-2824

HE6XRT

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

CURB6X

Model Configuration HE6XKRT...

Base Type V (vertical) H (horizontal) R (RA vertical) F (FA vertical) Filter Monitor -- (none) F (filter monitor) Other -- (none) W (white paint) C (custom paint) Wall S (single) D (double) Phase 3 Voltage 4 (460) 5 (208-230) 8 (575) FA Hp M (5.0) N (7.5) EA Hp M (5.0) N (7.5) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40)

55

www.RenewAire.com

HE8XRT

Outdoor Unit Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 2,000-8,000 CFM ARI 1060 Certified Core: Eight L125-00 Airflow Rating Points (for ARI): 6,000 CFM and 4,500 CFM Number Motors: Two HP 5 7.5 Volts 208-230 460 208-230 460 208-230 460 HZ 60 60 60 60 60 60 Phase 3 3 3 3 3 3 FLA 14.2-13.0 6.5 20.9-19.2 9.6 28.2-28.0 14

Min. Cir. Amps Max. Fuse Size

32 14.6 47 21.6 63.5 31.5

50 20 70 30 90 50

G4 Performance

CFM

2,000 4,000 6,000 8,000

10

Control Voltage: 24, 115, 230 Volt available Filters: Sixteen total, MERV 8, 2" pleated, 20" x 20" nominal size Weight: 2,730 lbs (unit), 3,080 lbs (shipping weight)

Effectiveness (%)

80

Sensible Winter

Shipping Dimensions: 85" W x 114" L x 85" H

Total

60

Base Type/Airflow Orientations

RTV

RTF

OA

EA OA RA

Summ

40

*At ARI 1060 standard conditions (See certified data on page 66 for core components).

er To

tal

EA

FA

FA

RA

RTR

EA FA OA

EA FA

RTH

OA RA

RA

Airflow Performance

External Static Pressure (Inches Water Column)

Motor HP Blower RPM Nominal Turns Open CFM 5 1,460 1,610 1,725 1,560 1,740 1,865 1,810 2,020 2,105 4.5 2 0.5 4.5 2 0 4.5 2 1 5,575 6,200 6,550 6,000 6,700 7,000 7,850 0.0 BHP 3.2 4.3 5.0 3.9 5.3 6.1 8.5 0.25 CFM 5,425 6,010 6,380 5,850 6,575 6,875 7,745 BHP 3.2 4.3 5.0 3.9 5.3 6.1 8.5 CFM 5,200 5,875 6,210 5,650 6,400 6,750 7,625 7,950 0.5 BHP 3.2 4.2 5.0 3.8 5.3 6.1 8.5 9.6 0.75 CFM 5,000 5,700 6,100 5,475 6,300 6,800 6,600 7,450 7,800 BHP 3.2 4.2 5.0 3.8 5.3 7.5 6.0 8.4 9.6 CFM 4,775 5,500 5,880 5,275 6,125 6,675 6,425 7,350 7,725 1.0 BHP 3.1 4.2 4.9 3.8 5.3 7.5 6.0 8.4 9.6 1.25 CFM 4,550 5,325 5,730 5,100 5,950 6,500 6,275 7,200 7,600 BHP 3.0 4.1 4.8 3.7 5.2 7.5 6.0 8.3 9.5 CFM 4,270 5,125 5,510 4,875 5,750 6,375 6,100 7,050 7,450 1.5 BHP 2.9 4.1 4.8 3.7 5.2 7.4 5.9 8.3 9.5

7.5

10

56

(800) 627-4499 · Fax: (608) 221-2824

HE8XRT

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

CURB8X

Model Configuration HE8XKRT...

Base Type V (vertical) H (horizontal) R (RA vertical) F (FA vertical) Filter Monitor -- (none) F (filter monitor) Other -- (none) W (white paint) C (custom paint) Wall S (single) D (double) Phase 3 Voltage 4 (460) 5 (208-230) 8 (575) FA Hp M (5.0) N (7.5) P (10.0) EA Hp M (5.0) N (7.5) P (10.0) Contactor A (24 VAC) D (two 24 VAC) R (inverter ready) Disconnect -- (none) N (nonfused) F (fused) Transformer -- (none) T (TR40)

57

www.RenewAire.com

Applied Products

· Cost effective energy recovery for virtually any air handling system. · Field assembled into air handling systems or integrated in custom packaged air handlers. · Unlimited airflow capacity. · Flexible installation and easy servicing. · ARI certified performance data for efficiency and cross leakage. · UL tested flammability and smoke generation that meets NFPA 90A and 90B test standards for commercial applications. · Ten year core warranty.

RenewAire means Trouble-Free ERV.

Installation Example

Central Air Handler using CA4X and exhaust and make-up air blowers.

(CA-Series provide side service access and a "side-by-side" airflow arrangement.)

CA4X

Similar designs can use PA-Series arrays.

(PA-Series provide top service access and an "over-under" airflow arrangement.)

58

(800) 627-4499 · Fax: (608) 221-2824

CA & PA Series Applied Energy Recovery Ventilators: CA2X, CA3X, CA4X, PA6X, PA9X, PA8X & PA12X

Part I - General

A. Product Specification The unit shall be a packaged static plate energy recovery ventilator. RenewAire shall be the basis of design. B. Quality Assurance 1. The energy recovery core shall be certified by ARI under its Standard 1060 for Energy Recovery Ventilators. Products not currently ARI Certified will not be accepted. 2. Unit shall be Listed under UL 1812, Standard for Ducted Air to Air Heat Exchangers. Specific UL-1812 Listing Standards for outdoor units including rain testing, UV exposure testing, corrosion resistance and temperature extremes testing shall be required for these models. Due to ongoing product offerings and upgrades, some models and options are not included in UL Listing reports. Consult RenewAire for more information. 3. The energy recovery core shall meet NFPA 90A and 90B requirements for flame spread, not to exceed 25, and smoke generation, not to exceed 50, through an ongoing testing and verification program using UL Standard 723. 4. The RenewAire core shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of ten years from the date of purchase. Balance of Unit shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of two years from the date of purchase. C. Positive Airsteam Separation Exhaust and fresh airstreams shall at all times travel in separate passages, and airstreams shall not mix. The exhaust air transfer ratio (EATR) shall be ARI-1060 certified as 0% at balanced pressure. D. Laminar Flow Airflow through the energy recovery core shall be laminar, avoiding deposition of particulates on the interior of the exchange plate material.

Part III ­ Product

A. Construction 1. The energy recovery cores shall be of static plate, cross-flow construction, with no moving parts. 2. The unit shall be capable of operating in winter and summer conditions without generating condensate. No condensate pan or drain shall be required. 3. The unit cabinet shall be constructed of 20-gauge steel, with lapped edges. 4. All side, end and top panels shall be insulated with 1 inch FSK high density board insulation. PA bottom panels shall be insulated with ¼ inch sheet rubber insulation. 5. CA-Series - Cabinet construction to allow vertical stacking of the units up to three cabinets high for larger airflow applications. Hinged and latched access doors will be provided on each end of the unit, allowing filter service and maintenance. PA-Series - Latched access doors are provided on the top of each unit. 6. The energy recovery core shall be protected by MERV 8 rated 2" nominal pleated, disposable filters. B. Options The CA-Series units shall be available in double wall construction. CA and PA units are available pre-assembled on a structural steel base, allowing shipping as a complete assembly.

Part II ­ Performance

A. Energy Transfer The energy recovery core shall be capable of transferring both sensible and latent energy between airsteams. Latent energy transfer shall be accomplished through molecular transport by hydroscopic resin. B. Passive Frost Control The energy recovery core shall perform without the occurrence of condensation or frosting under normal operating conditions (defined as outside temperatures above -10°F and inside relative humidity below 40%). Occasional extreme conditions shall not affect the usual function or performance of the energy recovery core.

59

www.RenewAire.com

CA-Series

Indoor Unit - Up to 20,000 CFM in Stacked Arrays Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Insulated sheet metal cabinets with energy exchange cores and filters. Individual CA-Series units or stacks of units can be built into larger air handling systems. Blower not included and must be specified to meet job requirements. Description Typical Airflow Range CFM ARI 1060 Certified Core Airflow Rating Points (for ARI) Unit Weight Shipping Weight CA2X 500-2,200 CA3X 750-3,300 CA4X 1,0004,400

Two L125-00 Three L125-00 Four L125-00 1,500 and 1,120 CFM 225 lbs 275 lbs Four Total 2,250 and 1,690 CFM 325 lbs 375 lbs Six Total 3,000 and 2,250 CFM 400 lbs 475 lbs Eight Total

G4 Performance

CFM

Filters: MERV 8, 2" pleated 20" x 20" nominal size

Effectiveness (%)

500 80 60 40

1,000

1,500

2,000

Shipping Dimensions: CA2X - 40" W x 48" L x 41" H CA3X - 40" W x 67" L x 41" H CA4X - 40" W x 87" L x 41" H Insulation: One inch, high density, FSK faced, fiberglass

Sensible Winter Total Summe r Total

Options: Double wall construction

CA2X CFM CFM

Effectiveness (%)

Effectiveness (%)

1,250 80 60 40

1,750

2,250

2.750

1,000 80 60 40

2,000

3,000

4,000

Sensible Winter Tota l Summer To tal

Sensible Winter Total Summer To tal

CA3X

CA4X

*At ARI 1060 standard conditions (See certified data on page 66 for core components).

Airflow Performance

Internal Static Pressure (in. H2O)

2.0

2X

1.5

CA 3X

CA

1.0

CA3X

0.5 1,000 2,000 Airflow (CFM) 3,000 4,000

60

(800) 627-4499 · Fax: (608) 221-2824

CA

4X

CA-Series

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Note: Filters are provided for installation in any two of the locations shown, depending on which duct connections are selected for inlets. Filters are 2" x 20" x 20" pleated disposable.

Model Configuration CA_XKIN...

Wall S (single) D (double)

61

www.RenewAire.com

PA-Series

Indoor Unit - Unlimited Airflow in Multiple Arrays Specifications

Ventilation Type: Static Plate, Heat and Humidity Transfer Insulated sheet metal panels easily slide into receivers to enclose stacks of energy exchange cores using unique patented design, US Patent 5,660,228 Individual PA-Series units can be joined together to provide unlimited airflow capacities for larger air handling systems. Blower not included and must be specified to meet job requirements. Description Typical Airflow Range CFM ARI 1060 Certified Core Airflow Rating Points (for ARI) Unit Weight Shipping Weight PA6X 1,500-6,600 Six L125-00 4,500 and 3,375 CFM 565 lbs 650 lbs PA8X 2,000-8,800 PA9X 2,250-9,900 PA12X 3,000-13,200 Twelve L125-00 9,000 and 6,750 CFM 980 lbs 1,180 lbs

Eight L125-00 Nine L125-00 6,000 and 4,500 CFM 695 lbs 900 lbs 6,750 and 5,062 CFM 800 lbs 990 lbs

G4 Performance

CFM

3,000 4,000 5,000 6,000

Filters: MERV 8, 2" pleated, 20" x 20" nominal size PA6X - 12 Total PA9X - 18 Total PA8X - 16 Total PA12X - 24 Total Insulation: One inch, high density, FSK faced, fiberglass

CFM

3,500 5,000 6,500 8,000

Effectiveness (%)

Effectiveness (%)

80 60 40

80 60 40

Sensible

Winter Tota l

Sensible

Winter Tota l

PA6X

CFM

3,500 5,000 6,500

Summer To

tal

PA9X

CFM

5,000 7,000 9,000

Summer To

tal

8,000

11,000

Effectiveness (%)

Effectiveness (%)

80

80 60 40

Sensible

60 40

Winter Tota l

Sensible

Winter Tota l

PA8X

Summer To

tal

PA12X

*At ARI 1060 standard conditions (See certified data on page 66 for core components).

Summer To

tal

Airflow Performance

Internal Static Pressure (in. H2O)

2.0

PA 6

PA 8

PA 9

X

PA 12 X

9,000

1.5

X

1.0

CA3X

0.5

3,000 6,000 12,000

Airflow (CFM)

62

(800) 627-4499 · Fax: (608) 221-2824

X

PA-Series

Unit Dimensions

EA: OA: RA: FA:

Exhaust Air to outdoors Outdoor Air intake Room Air to be exhausted Fresh Air to inside

Model Configuration PA_XKIN...

Base Type -- (none) 9 (forklift base) Airflow Arrangement 1 (opposite-side entry, cross-flow) 2 (same-side entry, cross-flow) 3 (opposite-side entry, parallel-flow) 4 (same-side entry, parallel-flow) -- (default with pre-assembly option K) Wall S (single) D (double) Pre-Assembly K (knockdown) A (assembled)

63

www.RenewAire.com

Commercial Controls & Interconnection Options

These controls are intended to turn RenewAire commercial energy recovery ventilation systems on and off at appropriate times. Specification, installation and set-up is an easy process. RenewAire units should be ordered with the 24 volt contactor option for all controls. It is not necessary that RenewAire controls be used to operate RenewAire units. A wide range of controls or building automation systems may be used. Make sure units are ordered with compatible contactor control voltage. RenewAire residential units have their own line of compatible controls that are not intended to operate RenewAire commercial units.

TC7D

· · · · · ·

Digital Time Clock

up to 8 on/off cycles per day or 56 per week 24 VAC power requirement battery back-up wall mount or outdoor enclosure options wall mount fits any 4" x 4" electrical box optional RenewAire transformer relay package (TR40) may be used

TC7D-W Wall Mount

TC7D-E Control In NEMA 3R Enclosures

Motion (occupancy) Control

MC

MC-C Ceiling Mount

· · · · ·

passive infared sensor adjustable time-off delay to 30 minutes 24 VAC power requirement ceiling mount or directable wall mount covers up to 1500 sq. ft. floor space

ceiling mount - walking motion coverage up to 22 foot radius wall mount - various coverage patterns up to 90 linear feet of sensitivity

MC-W Wall Mount

· requires the use of RenewAire transformer relay package (TR40) (ordered separately)

CO2

· · · · · · ·

Carbon Dioxide Control

CO2-W Wall Mount

adjustable control from 600-2000 PPM digital display 24 VAC power requirement computer/BAS interface for information and control self calibrates during periods of low occupancy wall mount or add duct mount accessory requires the use of RenewAire transformer relay package (TR40) (ordered separately)

CO2-D Duct Mount

64

(800) 627-4499 · Fax: (608) 221-2824

DH24

· · · · ·

Dehumidistat Control

secondary control to time clock or other primary control mechanical switching of 24 VAC (or 120 VAC) adjustable from 0 - 100% relative humidity wall mount to single gang box Note: RenewAire ERVs are not to be used for applications where indoor relative humidity exceeds 50% RH for extended periods of time

DH24 Wall Mount

DS

· · · · ·

Disconnect Switch

fused or non-fused indoor or NEMA 3R exterior enclosures - I or E installation voltage must be specified 115, 208-230, 460 installed on unit and wired to unit contactor disconnects are configured as part of the model numbering for a unit (see page 67)

Transformer Relay Package

TR40

· · · · · · provides a 24 VAC, 40 VA class II power supply for unit control includes isolation relay with low voltage circuit breaker handles any RenewAire unit with one contactor installation voltage must be specified 115, 208-230, 460 installed in unit electric box TR40 is configured as part of the model numbering for a unit (see page 67)

IBC

Independent Blower Control

· adds a second contactor to allow independent control of exhaust fan and supply fan · may be used to provide economizer (no heat recovery operation) function · can provide relief fan or make-up air function to benefit building pressurization · IBC is configured as part of the model numbering guide for a unit (see page 67)

65

www.RenewAire.com

ARI-1060-2000

Certified Performance

Type

Test 1 Test 2 Test 3

ARI-1060 Certified Performance - Model Number L85-G4 Tilt Angl e Nominal Airflow Pressure Drop 100% - 450 SCFM 0.6 in. H2O Plate N/A 75% - 338 SCFM 0.5 in. H2O Leakage Ratings Thermal Effectiveness Ratings at 0" Pressure Differential Pressure Purge Angle Nominal Net Net Net Sensible Latent Total Differential EATR OACF or Setting Airflow Airflow Sensible Latent 450 Heating 450 73% 50% 65% 73% 50% -1 in. H2O 0.5% 1.00 N/A CFM Cooling CFM 73% 37% 50% 73% 37% 0 in. H2O 0.0% 1.02 N/A 338 Heating 338 77% 54% 69% 77% 54% 1 in. H2O 0.0% 1.05 N/A CFM Cooling CFM 77% 43% 56% 77% 43% ARI-1060 Certified Performance - Model Number L125-G4 Tilt Angl e Nominal Airflow Pressure Drop 100% - 750 SCFM 0.7 in. H2O Plate N/A 75% - 563 SCFM 0.5 in. H2O Leakage Ratings Thermal Effectiveness Ratings at 0" Pressure Differential Pressure Purge Angle Nominal Net Net Net Sensible Latent Total Differential EATR OACF or Setting Airflow Airflow Sensible Latent 750 Heating 750 71% 48% 63% 71% 48% -1 in. H2O 0.5% 1.00 N/A CFM Cooling CFM 71% 35% 48% 71% 35% 0 in. H2O 0.0% 1.02 N/A 563 Heating 563 75% 52% 67% 75% 52% N/A 1 in. H2O 0.0% 1.05 CFM Cooling CFM 75% 40% 53% 75% 40%

Type

Net Tota l 65% 50% 69% 56%

Test 1 Test 2 Test 3

Net Tota l 63% 48% 67% 53%

NOTE:

SCFM - Standard Cubic Feet per Minute EATR - Exhaust Air Transfer Ratio

OACF - Outdoor Air Correction Factor N/A - Not Applicable

Energy recovery component certified in accordance with ARI standard 1060-2000. Actual performance in packaged equipment may vary.

66

(800) 627-4499 · Fax: (608) 221-2824

Model Numbering Guide

Note: Not all options are available on every model. $=price adders

STANDARD FEATURES 6 CORE: "K" = G4 10 UNUSED IN HE MODEL 16-18 UNUSED IN THESE MODELS

MODEL NUMBER

1 2 3 4 5

K

6 7 8 9 1-5

10 11 12 13 14 15

- - 16 17 18 19 20 21 22 23 24 25

MODEL

"EV450", "HE-1X", "HE-2X" "HE-3X", "HE-4X", "HE-6X, "HE-8X" INDOOR/OUTDOOR 7-8 24 9

25

UL LISTING (SEE RESTRICTION 15):

UL: "L" = LISTED "N" = NON-LISTED "IN" = INDOOR, "RT" = ROOFTOP BASE TYPE (SEE RESTRICTION 1) "V", "H", "T" (INDOOR UNITS) "V", "H", "R", "F", "C" (ROOFTOP UNITS) "-" - DEFAULT IN EV450 MULTIPLE-CHOICE OR OPTIONAL FEATURES WALL TYPE: "S" = SINGLE, "D" = DOUBLE $ 11 PHASE: "1" = SINGLE-PHASE, "3" = THREE-PHASE 12 21 VOLTAGE: (SEE RESTRICTIONS 2, 3, 4 & 5) "1" = 115V, "4" = 460V, "5" = 208-230V, "6" = 115/208-230V, "7" = 208-230/460V, "8" = 575V, "9" = 277V 14 FA HORSEPOWER RESTRICTION 6 EA HORSEPOWER 15 13 OTHER OPTIONS: $

"-" = NONE, (STANDARD) "W" = WHITE PAINT, "C" = CUSTOM PAINT "X" = CUSTOM UNIT 23 22 OTHER OPTIONS (RESERVED) FILTER MONITOR (RESTRICTION 13) $

"-" = NONE, (STANDARD) "B" = FILTER MONITOR BOTH AIRSTREAMS 24V TRANSFORMER (RESTRICTIONS 11 & 12): $

"-" = NONE, (STANDARD) "T" = TR40 (TRANSFORMER WITH ISOLATION RELAY) 20 DISCONNECT (RESTRICTIONS 9 & 10): $

"H" = 0.75 HP EPACT DIRECT-DRIVE (HE-1X ONLY) "J" = 1.5HP EPACT (HE-2X ONLY) "K" = 2HP EPACT (HE-2X, HE-3X, HE-4X ONLY) "L" = 3HP EPACT (HE-3X, HE-4X ONLY) "M" = 5HP EPACT (HE-3X, HE-4X, HE-6X, HE-8X ONLY) "N" 7.5HP EPACT (HE-6X, HE-8X ONLY) "P" 10HP EPACT (HE-8X ONLY) $ "Q" = (2) 0.75HP EPACT DIRECT-DRIVE (HE-2X ONLY) "-" = DEFAULT IN EV450

"N" = NON-FUSED "F" = FUSED "-" = NONE, (STANDARD) 19 UNIT CONTROL (RESTRICTIONS 7 & 8)

"A" = (1) 24V CONTACTOR (STANDARD) "D" = (2) 24V CONTACTORS $ "R" = INVERTER READY (NO CONTACTOR)

HE MODELS

12-20 UNUSED IN PA, CA MODELS

STANDARD FEATURES

6

CORE: "K" = G4 7-8 "IN" = INDOOR

MODEL NUMBER

K I N

1 2 3 4 5 6 7 8 9 10 11

- - - - - - - - - - - 12 13 14 15 16 17 18 19 20 21 22 23 24 25

N

25 UL: "N" = NON-LISTED

1-2 MODEL: MULTIPLE-CHOICE OR OPTIONAL FEATURES "CA" = CABINET APPLIED "PA" = PANELIZED APPLIED QTY OF CORES: "nX" = (n) CORES n = 2, 3, 4 (CA MODELS) n = 6, 8, 9, 12 (PA MODELS) BASE TYPE (SEE DIAGRAM) (CA) "-" (NONE) (PA) "9" = FORKLIFT BASE 9 10 AIRFLOW ORIENTATION (UNUSED IN CA MODELS) 3-5 24 OPTION 4: PRE-ASSEMBLY "K" = KNOCKDOWN (PA MODELS) "A" = ASSEMBLED (PA MODELS) $ "-" = NOT APPLICABLE (CA MODELS) 23 OPTION 3 (RESERVED): "-" = NONE 22 OPTION 2 (RESERVED): "-" = NONE 21 OPTION 1 (RESERVED): "-" = NONE 11 WALL TYPE (UNUSED IN PA MODELS): "S" = SINGLE (CA MODELS ONLY) "D" = DOUBLE (CA MODELS ONLY) $

CA & PA MODELS

"1" = OPPOSITE-SIDE ENTRY, CROSS-FLOW "2" = SAME-SIDE ENTRY, CROSS FLOW "3" = OPPOSITE-SIDE ENTRY, PARALLEL-FLOW "4" = SAME-SIDE ENTRY, PARALLEL-FLOW "-" = DEFAULT IN CA MODELS AND IN PA MODELS WITH PRE-ASSEMBLY OPTION "K" (KNOCK-DOWN).

67

www.RenewAire.com

R eference I nformation

Unit Airflow Orientation

Indoor Options

H (Horizontal)

EA

Outdoor Options

RTV

OA

RTF

EA OA RA FA

RTH

RA

FA

EA FA OA RA

V (Vertical)

RTR

EA FA OA

RTEC

EA OA FA RA

RenewAire units are available in a wide range of orientations. Please refer to the diagrams above when choosing the correct unit for your application from the Model Numbering Guide.

RA

Ask for a

Technical Reference CD

NEW!

Ventilation Calculator in enhanced software package.

Trouble-Free ERV for over 25 years.

RenewAire Product & Ventilation Commitment

RenewAire ventilation products will give you cleaner air to breathe - letting you and your family feel better and healthier AND will do so in the most consistent, controlled, safe and energy-efficient manner possible.

Gree

n

Save Energy Reduce Pollution Material Efficient People Friendly

Ample Airflow Pressure Balanced Quiet Operation Energy Efficient Automatic Control

For over 25 years, RenewAire has been a pioneer in the use of plate exchangers that simultaneously tranfer heat and humidity between ventilation airstreams in extreme climates. From cool-dry (Point Barrow, Alaska) to hot-humid (Puerto Rico) climates, RenewAire exceeds customer expectations for effective, reliable ventilation solutions.

Ve n

il a

t

tio n

1980 1987 1998 2003 2005 2007

First HRV and ERV installations using a variety of plate and wheel technologies. ERV manufacturing begins using Mitsubishi "Lossnay" core. RenewAire model is the first listed by UL-1812 standard for ERV safety. HVI residential unit certification confirms superior heat and humidity transfer. Introduction of first roof-top connected unit (RTC). ARI-1060 commercial product certification of only ERV with 0% cross contamination. Over 100 school projects shipped in one year. G4 - 4th generation core introduced with enhanced humidity transfer. Introduction of BREEZE® easy to install residential unit. Energy Star Qualified with energy use in the lowest 20% of comparable buildings. New factory achieves LEED-Silver rating. 120,000th North American unit sold. 2007 sales result in 30,000 tons of CO2 emission reductions! Introduction of RD Series dedicated outdoor air system.

1983 1996 2001 2004 2006

2008

Full Line of Ventilation Products

Residential & Small Commercial

· 5 Models · 50 - 300 CFM · Built-In 24 V transformer/relay package

Commercial Products

· · · · 23 Models 250 - 7,950 CFM 1 or 3 phase multi-voltage 24 volt control

Applied Products

· CA-Series (cabinet) - 500 - 20,000 CFM · PA-Series (panelized) - 1,500 - Unlimited CFM · (Requires blowers & manifolds by others)

Dedicated Outdoor Air Systems

· · · · 4 Models 500 - 4400 CFM integrated VFD for each airstream coil options including DX, chilled water, hot water and combinations

Ventilation Exhaust Fans

· · · · 4 Models 50 - 150 CFM robust steel housing and duct collar themostefficientlineofexhaustfans available in North America

This piece was printed using earth-friendly soy ink on 100% post-consumer recycled paper. RenewAire ERVs are proudly manufactured in our LEED-Silver Certified facility using 100% wind generated electricity.

© RenewAire LLC, 2009 Part # LIT029

Information

72 pages

Find more like this

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

569101