Source-changeover systems for circuit breakers and switch-disconnectors 40 to 5000 A

Applications

To ensure a continuous supply of electrical power, certain installations are connected to two sources: c normal source N, c replacement source R used to supply the installation when the normal source is absent. The source-changeover system switches the load between these two sources. It can be automated to take into account the status of these sources before switching. Made up of two or three circuit breakers, Merlin Gerin sourcechangeover systems offer compact solutions optimising the essential functions: circuit protection, service continuity and energy management.

Guaranteeing continuous power for safety or production

c Commercial and service sector: v Operating rooms in hospitals, v safety systems for tall buildings, v computer rooms (banks, insurance companies, etc.), v lighting systems in shopping centres. c Industry: v continuous production lines, v engine rooms on ships, v critical auxiliaries in thermal power stations c Facilities: v port and railway installations, v runway lighting systems, v control systems on military sites.

Managing energy efficiently

c power supply management, c load shedding, c regulation.

2

Manual and automatic source-changeover systems

Manual source-changeover system

This is the most simple type of source-changeover system. It is controlled manually by an operator and consequently the time required to switch from the normal to the replacement source can vary. The manual sourcechangeover system is made up of two or three mechanically interlocked circuit breakers.

Automatic source-changeover system

This the system most often employed. No human intervention is required and switching form the normal to the replacement source takes place in less than 1 second. This changeover system is made up of: c 2 or 3 circuit breakers, c 1 mechanical and electrical interlocking system, c 1 controller either: v provided by the customer or contractor, v or supplied as an option (2 models available offering basic or extended source and load management functions).

Choice of automatic controller

BA controller, for a simple source-changeover system (automatic switching between the normal and replacement sources depending on their status). UA controller, for a source-changeover system integrating the following automatic functions: c automatic switching between sources, c control and management of engine generating sets, c load shedding for non-priority circuits, c switching to the replacement source if one of the phases of the normal source is absent. A communication option based on the Schneider internal bus is available for the UA controller.

UA controller

3

Functions and locations of source-changeover systems

Incoming feeders and main LV switchboards

G

or

Currents from 630A to 5000A

Power distribution

G

or

Currents from 250A to 1250A

Loads

G

or

Currents from 40A to 630A

4

Most frequent applications

Continuity of service for incoming feeders and LV switchboards

1 normal source 1 replacement source

G UN UR

Q1 Q2 Q3

Q1 0 1 0

Q2 0 0 1

2 normal sources 1 replacement source

TR1 TR2

Q1 0 1 0 0 1

Q2 0 0 1 0 0

Q3 0 0 0 1 1

Q1

Q2

2 sources with coupler on busbars

TR1 G Q1 Q2 Q3 TR2

Q1 0 1 0 0 1 1 0

Q2 0 0 1 0 0 1 1

Q3 0 0 0 1 1 0 1

Continuity of service for power distribution

Typical applications

Generator or permanent source

G

c continuous production processes c operating rooms c computer rooms (e.g. banks)

Q1 0 1 0

Q2 0 0 1

Q1

Q2

Continuity of service for specific applications

Typical applications

c large electrical installations (e.g. airports) c refrigeration units c special electricity tariffs c pumping stations c other

Generator or permanent source

G

Generator or permanent source

G

Q1 0 1 0

Q2 0 0 1

Q1

Q2

Q1

Q2

APPLICATION

5

Overview of solutions

Interlocking of two Compact circuit breakers via rotary handles

Interlocking of two Masterpact NT and NW circuit breakers using cables

Complete source-changeover assembly with two Interpact switch-disconnectors

Interlocking of two Compact NS circuit breakers on a mounting plate Interlocking of two Masterpact NT or NW circuit breakers using connecting rods Interlocking of three Masterpact NW circuit breakers using cables

6

Manual source-changeover systems Possibilities

All possibilities for the source-changeover system Type of devices INS40 to INS80 INS100 to INS160 INS250 (ratings 100 to 250) INV100 to INV250 (1) INS320 to INS630 INV320 to INV630 (1) NS100 to NS250 NS400 to NS630 mixed NS100 to NS630 (2) NS630b to NS1600 NT06 to NT16 NW08 to NW63 (1) visible break function (2) with rotary handle interlocking for NS400/630

Type of interlocking system complete assembly toggle keylock rotary handle on mounting plate

tripped

reset

c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c

c

cables / 2 side-by-side cables / 3 side-by-side cables / 2 stacked cables / 3 stacked connecting rods / 2 stacked

tripped

reset

Automatic source-changeover systems Mechanical interlocking systems

Possible combinations of Compact "Normal" and "Replacement" source devices

R

N

0 . OFF

R

0 . OFF

I . ON

N

R N

com

t1 (s)

IN LIN GER MERNS

compact m 50/60 UA automatis 200/240V Hz

N

UR

UN =

t4 (s)

O

t3 (s)

ANGE R DE RECH ANDE COMM EN CAS AREIL 250 D'APP LES REF: I AUSS POUR NS100-630 29270 POUR NS400 32520 er t break for circui t order emen N°: replac 250 REF also for NS100-630 29270 for NS400 32520

UN

R

ON

t2 (s)

R

N

ON OFF

R

1

UN =

OFF

ratings 12.5 ... 100 12.5 ... 160 12.5 ... 250 160 ... 400 250 ... 630

"Normal" N NS100 NS160 NS250 NS400 NS630

fault fault auto stop test

t5 (s) stop genera tor

N

manu

R

N

c c c c c c c c c c c c c c c c c c c c c c c c c

"Replacement" R NS100 NS160 NS250 NS400 NS630

Possible combinations of "Normal" and "Replacement" source devices (interlocking using connecting rods) ratings "Normal" N NS630b to NS1600 NS1600b to NS3200 NT06 to NT16 NW08 to NW40 NW40b to NW63 c "Replacement" R NS630b to NS1600 NS1600b to NS3200 NT06 to NT16 NW08 to NW40 NW40b to NW63

c c c c c c c c c

Compact NS630b to NS1600 devices cannot be combined with Masterpact NT (or NW) devices, however Masterpact NT and NW devices may be used together. Both devices must be either fixed or withdrawable to allow proper alignment of the mechanisms. Possible combinations of "Normal" and "Replacement" source devices (interlocking using cables) ratings "Normal" N NS630b to NS1600 NS1600b to NS3200 NT06 to NT16 NW08 to NW40 NW40b to NW63 c "Replacement" R NS630b to NS1600 NS1600b to NS3200 NT06 to NT16 NW08 to NW40 NW40b to NW63

c c c c c c c c c

Compact NS630b to NS1600 devices cannot be combined with Masterpact NT (or NW) devices, however any two Masterpact NT and NW devices may be used together, whatever their sizes or rating. Possible combinations of three devices ratings "Normal" N NS630b to NS1600 NS1600b to NS3200 NT06 to NT16 NW08 to NW40 NW40b to NW63 c c c c "Replacement" R NS630b to NS1600 NS1600b to NS3200 NT06 to NT16 NW08 to NW40 NW40b to NW63

Only Masterpact NW devices may be used when combining three devices.

7

Automatic source-changeover systems Functions and characteristics

Range

types of devices types of circuit breakers switch disconnector version mixing possibilities

Electrical characteristics

rating insulating voltage Ui (V AC) positive break indication number of poles (N and R breakers must have the same number of poles) electrical endurance (Normal-Replacement-Normal cycle) at 440 V, type N (for other voltages : see the product catalogue) ambient temperature

Masterpact automatic source-changeover system

Control characteristics

control voltage maximum consumption minimum switching time AC DC AC DC

Interlocking

mechanical on mounting plate (vertical or horizontal) by rods (stack-mounted devices) by cable (side-by-side or stack-mounted devices) by diagram (without IVE) with IVE unit auxiliary contacts used by circuit breaker

electrical

Protection and measurement

Compact automatic source-changeover system overload protection short-circuit protection earth-fault protection zone selective interlocking (ZSI) earth-leakage protection long time short time instantaneous

by Vigi module by control unit by add-on Vigirex relay

current measurements voltage, frequency, power measurements, etc.

Indication and control auxiliaries

available auxiliary indication contacts voltage releases voltage presence indicator voltage transformer ammeter module insulation monitoring module MX shunt MN undervoltage

Source-changeover controller

with permanent replacement source with standby generator set

Remote communication via bus

device status indications device remote control remote setting of 4-position switch indication and identification of protection status and alarms transmission of measurements

Installation and connection accessories

fixed front connected fixed rear connected withdrawable or plug-in

Installation and connection accessories

downstream coupling accessory bare-cable connectors terminal extensions terminal shields and inter-phase barriers locking front panel escutcheons

by padlock by keylock

8

Compact

NS100 to NS250 N/H/L NA all breakers NS100 to NS250 N/H/L/NA fixed or plug-in NS400 to NS630 N/H/L NA all breakers NS100 to NS630 N/H/L/NA fixed or plug-in NS630b to 1600 N/H/L NA all breakers NS630b to 1600 N/H/L/NA fixed or withdrawable NT06 to 16 N1/H1/H2/H3/L1 NA/HA/HF all mixing possibilities (fixed, withdrawable or fixed + withdrawable)

N1/H1/H2/H3/L1/NA/HA/HF

Masterpact

NW08 to 63 N1/H1/H2/H3/L1 NA/HA/HF all mixing possibilities (fixed,withdrawable or fixed + withdrawable)

N1/H1/H2/H3/L1/NA/HA/HF

15 to 250 A 750 c 3, 4 30 000 (NS100) 20 000 (NS160)

15 to 630 A 750 c 6 000 (NS400) 4 000 (NS630)

250 to 1600 A 750 c 5 000 (NS630b to NS1000) 4 000 (NS1250 to NS1600)

630 to 1600 A 1000 c 6 000 (NT06 to NT12) 3 000 (NNT16)

600 to 6300 A 1000 c 10 000 (NW08 to 16), 800(NW20), 5 000 (NW25 to 40), 1 500 (NW40 to NW63)

­25 °C to +70 °C (50 °C for 440 V - 60 Hz)

48 to 415 V - 50/60 Hz 440V - 60 Hz 24-250 V 500 VA 500 W 800 ms

500 VA 500 W 800 ms

180 VA 180 W 800 ms

180 VA 180 W 800 ms

180 VA 180 W 800 ms

c c c 1 OF + 1 SDE

c c c c c 1 OF + 1 SDE

c c c c 1 OF + 1 CE

c c c only with UA or BA 1 OF + 1 CE + 1 PF

c c only with UA or BA 1 OF + 1 CE + 1 PF

c c c c c c

c c c c c c c

c c c c c c c c

c c c c c c c c c

c c c c c c c c

OF + SD + (+ SDV) c c c c c c c BA controller c UA controller c c

2 OF + SD + (+ SDV) c c c c c c

2OF + SD c c

2OF + SD c c c c c c

2OF + SD c c c c c c

c c

c c c c c c c (vertical or horizontal) c (withdrawable on chassis)

c c c c c c c (vertical or horizontal) c (withdrawable on chassis)

c c c c c c c (vertical or horizontal) c (drawout)

c c (long rear connections) c (plug-in on base) c c c c c c

c c (long rear connections) c (plug-in on base) c c c c c c c

c c c c

c c c

c c c

9

Controller option selection for automatic source-changeover systems

Controller

compatible circuit breakers

4 - position switch

automatic operation forced operation on "Normal" source forced operation on "Replacement" source stop (both "Normal" and "Replacement" sources off)

Automatic operation

BA controller

monitoring of the "Normal" source and automatic changeover generator set startup generator set shutdown with adjustable delay load shedding and reconnection of non-priority circuits changeover to the "Replacement" source if one of the phases of the "Normal" phase is absent

Test

by opening the P25M circuit breaker supplying the controller by pressing the test button on the front of the controller

Indications

circuit breaker status indication on the front of the controller : on, off, fault trip automatic mode indicating contact

Other functions

UA controller

selection of type of "Normal" source (single-phase or three-phase) (1) voluntary transfer to "Replacement" source (e.g. energy management commands); during peak-tariff periods (energy management commands), forced operation on "Normal" if "Replacement" source not operational additional control contacts (for control by external signals) ; transfer to "Replacement" if contact is closed (e.g. frequency test for Ur) setting of maximum startup time of the "Replacement" source

Power supply

control voltages (2) 220 to 240 V 50/60 Hz 380 to 415 V 50/60 Hz - 440 V 60 Hz

Options

communication option

(1) e.g. 220 V single-phase or 220 V three-phase.

10

BA

UA

All Compact NS and Masterpact circuit breakers

c c c c c c c c c c c c c c c c c

c c

c c c c c

c

c

c c c c c

c c

(2) The controller is supplied by the ACP auxiliaries control unit. The voltage supplied to the controller must be the same as that of the ACP unit, the IVE unit and the motor mechanisms. If this voltage is the same as the source voltage, then the "Normal" and "Replacement" sources can be used to supply the ACP directly. If not, a BC type or equivalent isolation transformer must be used.

11

Schneider Electric Industries SA

5, rue Nadar 92506 Rueil-Malmaison Cedex France Tel : +33 (0)1 41 29 82 00 Fax : +33 (0)1 47 51 80 20

http://www.schneiderelectric.com

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication This document has been printed on ecological paper

Design: Schneider Electric Production: AMEG Printed:

ART81427

12/00

ABTED197063EN © 2000 Schneider Electric - All rights reserved.