CONNECTION TO STRUCTURAL SUPPORTING MEMBERS TO BE THE SAME FOR VERTICAL, DIAGONAL & LONGITUDINAL 'L'S SEE SCHEDULE SHEET 17.

SYMM. ABOUT ADD STRUT CHANNEL OR ANGLE WHEN "L" GREATER THAN MAX. LENGTH PER SCHEDULE C L FOR STRUT CHANNEL SIZE & CONNECTION

STRUT CHANNEL BRACE (1-5/8") MAXIMUM LENGTH 6'

DISTANCE TO SUPPORTING MEMBER 6'-0" MAX. ADD STRUT CHANNEL OR ANGLE WHEN `L' GREATER THAN MAX.

AIRCRAFT CABLE BRACING. FOR CONNECTION, SEE

STRUT CHANNEL (1-5/8") FRAMING CHANNEL 1-5/8" "A" SEE DETAIL G "A"

2 MAX. 1

STRUCTURAL SUPPORTING MEMBERS

2'-8" MAX. TO

7'-0" MAX TO STRUCTURAL SUPPORTING MEMBER 1/2" CLEAR

VERTICAL `L' SEE SCHEDULE SHEET 17 HORIZONTAL `L' SEE SCHEDULE SHEET 17. MAX DIAGONAL `L' SEE SCHEDULE SHEET 17. DUCT SIZE 1 2

C OF BOLTS L C OF ANGLE L LONGITUDINAL `L' BRACE ONE EACH SIDE OF DUCT FOR SIZE SEE SCHEDULE SHEET 17. SHOWN DOTTED

EQ.

EQ.

DIAGONAL `<' BRACE. SEE SCHEDULE SHEET 17

HANGER ROD

1 2 MAX.

5" AT 96" DUCT.

(6'-0" MAX.) 6" (MAX.)

MAX. LENGTH 6'

SHEET METAL SCREW EQUALLY SPACED 18" O.C. MAXIMUM TYPICAL 4 SIDES

3/16" SELF TAPPING

3/16" SELFTAPPING SHEET

1/2" CLEAR MAX. 1"

METAL SCREWS EQUALLY SPACED 18" O.C. TYP. 4 SIDES

FOR BOLT SIZE SEE SCHEDULE SHEET 17 (TYP).

HORIZONTAL `<' SEE SCHEDULE SHEET 17 1 1

VERTICAL `<' SEE SCHEDULE SHEET 17

LONGITUDINAL `<' ONE EA. SIDE OF DUCT. FOR SIZE SEE SCHEDULE SHEET 17 (SHOWN DOTTED)

1

"L"

1

2 MAX

STRUT CHANNEL BRACE. FOR CONNECTION, SEE

HANGER ROD SIZE 6" 1 1

2 MAX

1"

1-

1/

TO SUPPORTING STRUCTURAL MEMBER

1-

1/

4"

INSTALL BENT FOR LONGITUDINAL BRACE AT THIS POINT

PIPE SIZE TO 2":1/8"x1-5/8" PIPE SIZE 2-1/2"-3":5/16"x1-5/8" PIPE SIZE 4"-8":1/4"x1-5/8"

TYPE 1 THRU 4 L P 3" X 1/4" (BENT) TYPE V, VI, VII > 4" X 3/8" (BENT)

4"

NUT AND BOLT LOCK WASHER. SEE SHEET 23

ADJUSTABLE SOLID OR SPLIT RING HANGER

The design, details and notes included herein are in compliance with Local Law 17/95 STANDARD NYC SEISMIC NOTE

EQ. DUCT SIZE

Ç BOLTS = Ç ANGLES DUCT

1"

SAME AS OPPOSITE SIDE

AS AN ALTERNATE, AIRCRAFT CABLE CAN BE USED. SEE SHEETS 22 & 44 PROVIDE CABLE BRACES ON BOTH SIDES OF DUCTS NOTES: 1. FOR SPACING OF BRACING REFER TO GENERAL NOTE 3, SHEET 1. 2. WHEN A COMBINATION OF DUCTS MUST B E CONNECTED TO VERTICAL OR HORIZONTAL `L'S. (ADD HORIZONTAL `L'S IF REQUIRED).

FOR BOLT SIZE SEE SCHEDULE SHEET 17.

TYPE 1 THRU 4 L P 3" X 1/4" (BENT) TYPE V, VI & VII > 4" X 3/8" (BENT)

"J" HANGER FELT PAD (FOR GLASS PIPE ONLY)

1. Seismic protection of all HVAC equipment, piping and ductwork shall be provided and shall comply with the applicable provisions of the New York City Building Code Reference Standard RS 9-6, latest revisions, and as revised below:

HORIZONTAL `<' SEE SCHEDULE SHEET 17.

INSULATION WHERE REQ'D

GALV. HOLDDOWN WIRE FOR GLASS PIPE ONLY.

Table 23-P

TRANSVERSE BRACE

A STRUT CHANNEL BRACING

B

CABLE BRACING N.T.S.

TYPICAL SIDE BRACING FOR RECTANGULAR DUCT DUCTS, RECTANGULAR-SIDE BRACING

1 2 MAX 1 FOR BOLT SIZE DIAGONAL ANGLE FRAMING CHANNEL 1-5/8" 2

TYPICAL CENTER BRACING FOR RECTANGULAR DUCTS 1 DUCTS, RECTANGULAR-CENTER BRACING

WOOD MEMBER 4x OR LARGER (FOR LAG SCREW) PIPE SIZE UP TO 2" FASTENER SEE ADJACENT TABLE AND DETAIL BELOW 2-1/2" TO 3" 4" & 5" 6" 8" ROD SIZE 5/16" 3/8" 1/2" 5/8" 3/4" LAG,SCREW SHANK DIAMETER 1/4"x3' 3/8"x3' 1/2"x3' 1/2"x3' 5/8"x4' MACHINE BOLT SIZE 1/4" 3/8" 1/2" 1/2" 5/8"

ALTERNATE PIPE BRACING DETAILS 2

FLAT HEAD STEEL DRIVE SCREW #16x2" #16x2" ------1 2 ADJUSTABLE HINGED CONNECTION 2 MAX FOR CONNECTION TYPES I & II 1-5/8" FRAMING CHANNEL 1

A 3

TRANSVERSE BRACE

B

a) adding after III.1

PIPES - BRACING, STRUT CHANNEL AND CABLE

CONC. SLAB EXPANSION ANCHOR BOLT

PIPES - BRACING, ATTACHMENT TO HANGER

EXPANSION ANCHOR BOLT EXPANSION ANCHOR BOLT

4

3. 4. 5. 6.

Sprinkler piping 2.00 Gas and high hazard piping 2.00 Other piping 0.67 HVAC ducts 0.67

(STUD BOLT

ADJUSTABLE HINGE

b) adding the following notes after note 4 at the bottom of the table:

CONNECTION

5" MIN.

1/4" STANDARD CLIP

EXPANSION ANCHOR BOLT

ANGLE.

SPLIT STEEL HANGER

5"

FRAMING CHANNEL STANDARD PIPE CLAMP 1-5/8" WIDE

STANDARD "U" HANGER. SEE ADJACENT SCHEDULE FOR ROD SIZE

THREADED ROD

ROD COULPING

12" DIA 1/2" EXPANSION ANCHOR BOLTS A

THREADED ROD

ONLY.

NOTE: NOT TO B E USED IN PRESTRESSED CONCRETE 1-5/8" FRAMMING CHANNEL

N

NOTE: NOT TO B E USED IN PRESTRESSED CONCRETE

O

5-3/8" 3-3/4"

ADJUSTABLE CONNECTIONS NOT FOR USE IN PRESTRESSED CONCRETE

CLINCH END OF NAIL NAIL SEE SHEET 13 FOR SIZE & QUANTITY

5. The design of seismic restraints for sprinkler piping in compliance with NFPA 13 using a design acceleration of 0.15 is acceptable in lieu of compliance with these provisions. 6. Seismic restraints are not required for any of the following conditions for other piping systems of HVAC ducts: 1. Piping or ducts suspended by individual hangers 12 inches or less in length from the top of the pipe or duct to the supporting structure. 2. Piping in boiler and mechanical rooms which has less than 1-1/4 inches inside diameter. 3. Piping in other areas which has less than 2-1/2 inches inside diameter. 4. Ducts which have a cross-sectional area less than 6 square feet.

2. Where equipment is resiliently mounted on springs or other types of vibration isolation supports, such supports shall have limits and stops to resist seismic deflection and forces.

L

LOW VELOCITY SHOT PIN (STUD BOLT) SEE SHEET 10 (FOR LOADS) LESS THAN 100#

FOR ALL SIZE PIPE UP TO 6" PIPE SIZE UP TO 1-1/2" 2" TO 5" 6" STEEL SIZE 1/8"x1-1/8" 1/4"x1-1/4" 3/8"x1-1/2" BOLT SIZE 3/8" 3/8" 1/2" TORQUE VALVE (FOOT POUNDS) 19 19 20 PIPE SIZE BOLT SIZE DIM A

.105" .105"

1-5/8" FRAMING CHANNEL

6"

SHEATHING 1/2" BOLT, NUT & WASHER STANDARD CUT WASHER WOOD MEMBER 2x OR LARGER MACHINE BOLT

8"

UP TO 1-1/2" 2"" TO 6"

1/2" 3/4"

1/8" 1/4"

1/2" NUT & SCREW

13

MACHINE BOLT SEE SHEET 12

/1

5" MIN.

5-

1/8" STANDARD CLIP ANGLE 5" MIN.

1

1/4" STANDARD CLIP ANGLE

EXPANSION ANCHOR BOLT,

ROD COUPLING

LONGITUDINAL BRACE

1-

C

TRANVERSE BRACE

D

7/

2

8"

4 BOLT DIA. MIN. 2" MIN. DIMENSION STANDARD "U" HANGER

1-1/4"

FOR VERTICAL HANGERS ONLY

3. Seismic protection devices shall resist the seismic forces determined under the New York City Building Code, as modified above, when applied in any direction without failure or permanent displacement of the protected system. 4. All seismic protection devices shall be the product of one manufacturer and shall have State of California Office of Statewide Health Planning and Development (OSHPD) preapproval "R" numbers certifying their maximum horizontal and vertical load ratings. The manufacturer of the seismic protection devices shall be a specialist in seismic mountings with at least five years experience on projects of a similar scope.

7/

1-1/4"

THREADED ROD HANGER ROD SIZE (FOR BRACES ONLY)

1-5/8" FRAMING CHANNEL

HANGER ROD SIZE

NOTE: INSTALL BRACES SHOWN ON THIS PAGE WITHIN 4" OF HANGER

ALTERNATE HINGED CONNECTION

K

DETAIL FOR BOLTED "U" HANGER CONNECTION

J STANDARD CLIP ANGLES M

NOT FOR USE IN PRESTRESSED CONCRETE NOTE: NOT TO B E USED IN PRESTRESSED CONCRETE

P R

PIPES-BRACING, ATTACHMENT

C B WOOD SCREWS TAPPED SIDE BEAM CONNECTOR A MINIMUM SIZE JOIST 2"x4" FLAT WASHER WOOD SCREW

5

CONNECTIONS, BOLTED "U"

6

CONNECTIONS, CONCRETE/WOOD

MAXIMUM TRAPEZE SPAN (SEE SCHEDULE SHEET 34)

7

CONNECTIONS, CONCRETE

8

5. The Contractor shall submit for approval seismic protection calculations prepared by a Professional Engineer licensed in the State of New York. The Professional Engineer shall sign and seal his calculations. Additionally, the Contractor shall submit for approval seismic protection device shop drawings, catalog cuts and location plans.

VERTICAL SUPPORT SAME AS OPPOSITE SIDE

MIN. SIZE JOIST 2"x4" ROD SIZE 3/8" 1/2" DIMENSION A 9/16" 3/4" B 1" 1-1/8" C 1/8" 3/8"

NOTE: HANGER ROD MAX LOAD 100# 180# A PIPE RUN "B" SCREWS SEE C L 1/4" STANDARD ANGLE CLIP T T EYE ROD SEE PROVIDE TRANSVERSE BRACE AT LAST VERTICAL SUPPORT

"TA" CAN BE USED AS LONGIUDINAL BRACE FOR PIPE RUN "B" & "TB" AS LONGITUDINAL BRACE FOR PIPE RUN "A" WHEN "d" IS WITHIN 24"

ADD VERTICAL ANGLE FROM SCHEDULE WHEN 'L' GREATER THAN MAXIMUM LENGTH PER SCHEDULE SHEET 34, OR STRUT CHANNEL

P 3"x1/4" L HOLD DOWN CLAMP (TYP)

FOR PIPE SIZE

T

1/4" 1/2"

C L

EYE ROD

T

PIPE RUN "A"

D

SCREW

LONGITUDINAL DIAGONAL 'L' BRACE ONE EACH END OF TRAPEZE. (SLOPE SAME AS TRANVERSE BRACE) PER SCHEDULE SHEET 34. AS AN ALTERNATE, STRUT CHANNEL PER SHEET 43 CAN BE USED (LONGITUDINAL DIAGONAL 'L' BRACE AT OPPOSITE END NOT SHOWN FOR CLARITY)

HOLDOWN CLAMP (TYPICAL)

FOR PIPE SIZE, SEE SHEET 34 NOTE 1.

SEE SCHEDULE ON SHEET 34 FOR RESPECTIVE END CONNECTIONS (TYP.)

1/2" HEX NUT

EQ. 9/32" HANGER ROD SEE BOLT TO ANGLE SEE SCHEDULE ON SHEET 3 4 'L' (6'-0" MAX)

1/2" STUD NUT WITH SPRING STRUT CHANNEL 12 GA. MIN.

TAPPED CONNECTOR

S

TA T T TB d NOTE THIS DETAIL APPLIES ONLY FOR COLD WATER PIPE AND GAS PIPE. d

3 1/4"

1fl" SQUARE x 1/8" É WASHER

EQ.

MINIMUM SIZE JOIST 2"x4" NAILS HANGER ROD SEE MINIMUM SIZE JOIST 2"x4" A

MAXIMUM SPACING FOR LONGITUDINAL BRACES

A

3/8" "T"-INDICATES TRANSVERSE BRACING "L"-INDITCATES LONGITUDINAL BRACING

7/8"

PLUMBER'S TAPE NOTES: 1. REFER TO `GENRAL NOTES' ON SHEETS 3 TROUGH 6 SPACING REQUIREMENT OF LATERAL BRACES 2. COORDINATE THE LOCATION OF LATERAL BRACES WITH MECHANICAL ENGINEER 1

2 MAX

STEEL NUT & BOLT(1/4"-20)

A

FOR TRAPEZE SECTION

TYPES III AND IV É 3"x1/4" (BENT) TYPES V AND V 1 É 4"x3/8" (BENT) DIAGONAL ANGLE OR STRUT CHANNEL

A

CONNECTION DETAIL FOR PIPES ON TRAPEZE

NOTE:

1. THIS DETAIL APPLIES ONLY FOR COLD WATER PIPE AND GAS PIPE.

BRACING SAME AS OPPOSITE SIDE

PLUMBERS TAPE

U

SECTION A-A

ANGLE CLIP

V

TYPICAL LOCATION OF LATERAL BRACING FOR PIPES

9

TYPICAL BRACING OF PIPES ON TRAPEZE

10

2. MAKE CERTAIN THAT PIPE IS CLAMPED TIGHLY BY HOLD DOWN CLAMP.

CONNECTIONS-WOOD

EXPANSION ANCHOR EQ. EQ. CONCRETE (LT. WT. OR HARDROCK)

PIPES-BRACING, LATERAL

STANDARD CUT WASHER MACHINE BOLT FOR SIZE WOOD SHEATHING

PIPES - BRACING, TRAPEZE

STEEL BEAM STEEL BEAM CLAMP "ELCEN" TYPE OR EQUAL NOTE!! BEAM CLAMP USED FOR VERTICAL ANGLE ONLY.

11

CONNECTIONS - PIPE TO TRAPEZE

12

2'-0" MIN. 8 NAILS AT 2-1/2"

d

WOOD MEMBER. USE 4x MIN. (SHOWN DOTTED) AT 3/4" BOLTS

NOTE: DIMENSIONS PROVIDED BY MANUFACTURER TO ACCOMODATE UNIT

ANGLES (LLH)

1/2" CLR. (MAX) É 4xÎ

4 DIAMETER MIN.

MACHINE BOLT.

1-1/2"x3" STRUCTURAL TUBING

NOTE FOR TYPE I AND II USE TYPE III CONNECTION

HEAVY GA. SHEET METAL "C" SECTION

1/4"

(TYP.)

1/2" (MIN) ROUND PIN CHAIN SHACKLE WITH 5/8"Ø PIN. HEAVY WIRE ROPE THIMBLES

"SIMPSON" A35 FRAMING ANCHOR (OR EQUAL) EACH END EACH SIDE.

EQ .

HOLES FOR BOLTS SHALL BE BORED 1/32" LARGER THAN THE NOMINAL BOLT DIA. 3-1/2"

A

CONNECTION TO STEEL BEAMS

GALVANIZED SHEET METAL FLASHING

VERTICAL, DIANGONAL OR LONGITUDINAL <'S

EQ .

12'-0" MAXIMUM

CLEVIS

U-BOLT CLIPS

BRACE PERPENDICULAR TO WOOD MEMBER

SCORE THREAD TO PREVENT NUT ROTATION

CONNECTIONS TO WOOD

BRACE PARALLEL TO WOOD MEMBER

1/2" DIA. BOLTS FOR CROSSBRACES

SPREADER CHANNEL SEE SCHEDULE SHEET 40

3"

<4x3-1/2"x5/16"x0'-5-1/2" TYP. EACH END 2-5/8" MACHINE BOLTS EA. LEG(OR EQUIVALENT WELDED CONN.)

HANGER ROD

CONC FILL

5/16" DIA. 7x7 AIRCRAFT CABLE. (USE 3/8" DIA. CABLE FOR TYPE VII). TENSION CABLE ONLY ENOUGH TO REMOVE SAG. 2 (MAX.)

1-1/2" sq. x 1/4" É WASHER AT 3/8" ROD EQ. 2-1/2" sq. x 1/4" É WASHER AT 1/2" ROD CONCRETE (LT. W T OR HARDROCK)

EQ.

SPANCRETE PLANK

ADDITIONAL ANGLE OR STRUT CHANNEL.

1

EQ. 1/8 1-1/2 VERTICAL AND DIAGONAL L'S. FOR SIZE & BOLTING ROD SIZE PER ANCHOR

EQ.

STEEL BEAM LONGITUDINAL < AS REQUIRED

CROSSBRACES ON EACH SIDE OF INTERIOR WINDOWS AND WELDED INTO AN "X" PATTERN HEAVY GA. SHEET METAL "Z" SECTION 3" DEFLECTIONS RSC SPRING SUPPORTS SEE DETAIL 5/8" DIA. BOLTS FOR BOLTING "C" SECTION INTO RSC SPRING SUPPORTS

18" CURB HEIGHT

(SHOWN DOTTED)

A

HANGER ROD CONNECTION TO CONCRETE TYPE III THRU VII

B

TYPICAL TOP CONNECTION FOR AIRCRAFT CABLE BRACING TYPE I THRU VII

TOP TUBE CONNECTION WITH 1/2" DIA. BOLTS

HANGER ROD

NOTE:

NOTES: RODS TO BE PLACED PRIOR TO CONC. FILL DRILL 1/16" LARGER HOLE THAN THE NOMINAL ROD DIA. THRU OPEN CELL.

VERTICAL ANGLE

B

14

CONNECTIONS TO SPREADERS USE WITH VERTICAL, DIAGONAL AND LONGITUDINAL L'S

10 APR 2006 3 FEB 2006

FOR CONSTRUCTION BANK REVIEW 100% BIDDING SUBMISSION ISSUED TO CONSULTANTS

THIS DETAIL CAN BE USED IN LIEU OF CAST-N-PLACE INSERTS .

CONNECTIONS TO SPANCRETE

ALTERNATE DETAIL FOR OMITTING ANGLE

CONNECTIONS - CONCRETE/CABLE

13

CONNECTIONS-WOOD/SPANCRETE

CONNECTION TO STRUCTURAL SUPPORTING MEMBER TO BE SAME FOR VERTICAL, DIAGONAL & LONGITUDINAL "L's".

CONNECTIONS-STEEL

1-5/8" FRAMING CHANNEL(12 GAUGE) 1-5/8"

15

SEISMIC ROOF CURB DETAIL

EXPANSION ANCHOR SEE SCHEDULE SHEET 40 CONCRETE (LT. WT. OR HARDROCK)

16

g CONCRETE (LT. WT. OR HARDROCK) CONCRETE FILL ON STEEL DECKING

20 SEP 2005 27 JUN 2005

TYPE I II g 1-3/8" 1-3/4"

LONGITUDINAL BRACE

ROD HANGER AND VERTICAL ANGLE, "ELCEN" WELDED BEAM ATTACHMENT OR EQUAL

THREADED STUD BOLT EXPANSION ANCHORS SHOWN HERE FOR EXAMPLE.

WASHER TO COVER WELD

3/16

TYP.

1 1/4" 1/2" CLR. (MAX.) TYP.

1-5/8"

ANGLES (LLH) SAME AS DETAILS "B" AND "C" ON SHEET 48 TYPES I THRU IV 2 1/2" STUD NUTS TYPE V, VI & VII 3-1/2" STUD NUTS

1" MIN.

MACHINE BOLT

EXPANSION ANCHOR

CUT WASHER HORIZONTAL LEG OF "L" PARALLEL TO DECKING RIBS

1/4" MIN. "L" (6'-0" MAX.) AIRCRAFT CABLE BRACING 1 2 MAX. Ç OF BOLTS = Ç OF ANGLE DIAGONAL ANGLE 1/8 1-24 ROD PER SCHEDULE SHEET 23

.709"-.719"

ANGLE (LLH). SEE SCHEDULE ON SHEET 40 FOR SIZE. BEND VETICAL LEG AS REQ'D FOR DIAGONAL BRACE

BOLT FOR SOLIDLY ATTACHING RTV TO TOP FLOATING RAIL TOP "FLOATING" RAIL CROSSBRACE

DATE

ISSUES / REVISIONS

Architect:

P 3x1/4 L

EDELMAN SULTAN KNOX WOOD/ARCHITECTS LLP

100 Lafayette Street, Suite 204, New York, NY 10013 tel: 212-431-4901 fax: 212-226-5958

Structural Engineer:

3"

ADD VERTICAL ANGLE FROM SCHEDULE WHEN "L" GREATER THAN MAXIMUM LENGTH

MATERIAL : 1 2 GAUGE (.105")STEEL "ELCEN" PIPE CLAMPHEAVY TYPE OR EQUAL

NOTES:

1. SEE SHEET 40 FOR SCHEDULE 2. THIS DETAIL IS NOT TO BE USED FOR VERTICAL HANGER. TIGHTEN ALL BOLTS WITH 50 FT. LB. TORQUE TESTING IS REQUIRED.

PLATE 3"x3/16" TYP.

STIFFENER CONNECTION FOR 7/8" ROD & SMALLER

2(MAX) 1 FOR PIPE SIZE BOLT TO ANGLE SEE SCHEDULE SHEET 23 ADD PIPE SLEEVE THAT HAS AN INSIDE DIAMETER 1/4"+/LARGER THAN OUTSIDE DIAMETER OF BOLT.

G

1-5/8" FRAMING CHANNEL SECTION

H

1/2" STUD NUTS WITH SPRING

A

A

TYPE I & II

EQUAL EQUAL

VERTICAL, DIAGONAL OR LONGITUDINAL ANGLE

1

4 -1/

"

1 1/4"

TYP.

"ELCEN" HANGER ROD CLIP OR EQUAL

3/8" "U" BOLT

HANGER ROD

ga. CONCRETE CAST-IN PLACE INSERT.

PLACE STANDARD CUT WASHER BETWEEN CONC. AND ANGLES

1-3/4"

BOLT SIZE: FOOT POUNDS:

1/4"-20 6

5/16"-18 11

3/8"-16 1/2"-13 19 50

3"

TORQUE VALUES FOR FRAMING CHANNEL BOLTS

STRUT CHANNEL SEE DETAIL "B" THIS SHEET FOR MINIMUM SECTION PROPERTIES

TYPE I & II ONLY

TYPE III IV V

g 3" 3-3/4" 4-1/2"

LOWER "STRUCTURAL" CROSSBRACE

ROBERT SILMAN ASSOCIATES ENGINEERS

88 University Place, New York, NY 10003 tel: 212-620-7970 fax: 212-620-8157

Mechanical Engineer:

ITEMS NOT NOTED SAME A S DETAIL A

A

CABLE BRACING FOR RECTANGULAR DUCTS

FOR PIPE SIZE

WHEN THERMAL INSULATED PIPING IS USED, DO NOT CONNECT BRACING OR HANGER DIRECTLY TO PIPE.

A

TYPICAL TOP CONNECTION FOR ALTERNATE DIAGONAL BRACE DETAIL

3/8" 7/8" 3/8"

CONCRETE (LT. WT. OR HARDROCK)

B

TYPE III,IV,V

g EQUAL EQUAL

ABRAHAM JOSELOW, P.E., P.C.

45 West 34th St., suite 1101 New York, NY 10001 tel: 212-736-2584 fax: 212-736-0241

RSC TO BE SECURELY ANCHORED TO ROOF STRUCTURE BY WELDING OR BOLTING

3/8" SQ. HEAD CUP POINT SET SCREW AT 2'-0" O.C. (MAX)

JAM NUT 1 1/2" SQ. X 1/8" > WASHER CLAMPING NUT WITH SERRATION STRUT CHANNEL 14 GAUGE (MIN) 1 5/8" 9/32" HANGER ROD (7/8"~ MAX.) SEE SCHEDULE SHEETS 23 OR 34 FOR SIZE (HANGER ROD CARRIES ALL VERTICAL LOAD) 1 5/8"

1 TYPICAL TRANSVERSE PIPE BRACING

N.T.S. NOTE:

1. LONGITUDINAL BRACINGS AT 80'-0" O.C. MAXIMUM UNLESS OTHERWISE NOTED. WHEN THE THERMAL EXPANSION OR CONTRACTION IS INVOLVED, PROVIDE LONGITUDINAL BRACINGS AT ANCHOR POINTS. THE LONGITUDINAL BRACES AND THE CONNECTIONS MUST BE CAPABLE OF RESISTING THE FORCE INDUCED BY EXPANSION AND CONTRACTION.

TYPICAL LONGITUDINAL PIPE BRACING

N.T.S.

NOTES:

1. LONGITUDINAL BRACINGS AT 80'-0" O.C. MAXIMUM UNLESS OTHERWISE NOTED. WHEN THERMAL EXPANSION OR CONTRACTION IS INVOLVED, PROVIDE LONGITUDINAL BRACINGS AT ANCHOR POINTS. THE LONGITUDINAL BRACES AND THE CONNECTIONS MUST B E CAPABLE OF RESISTING THE FORCE INDUCED BY THE EXPANSION AND CONTRACTION. 2. THIS BRACING DETAIL APPLIES ONLY FOR COLD WATER PIPE AND GAS PIPE WHERE MOVEMENT OF THE PIPE IS DUE TO TEMPERATURE DIFFERENTIAL IS NEGLIGIBLE. 3. IT IS THE RESPONSIBILITY OF THE USER OF THIS GUIDELINE TO ASCERTAIN THAT AN ADEQUATE BRACING AND THE ANCHORAGE DEVICE BE DESIGNED FOR PIPE WHENEVER THE MOVEMENT DUE TO THERMAL DIFFERENTIAL EXISTS. PROVIDE ONE ANCHOR POINT IN ONE PIPE RUN. ALLOW FOR LONGITUDINAL PIPE MOVEMENT AT THE OPPOSITE END OF THE ANCHOR POINT. 1/4"x1-5/8"x5-5/8" LONG STEEL PLATE

1-5/8" FRAMING CHANNEL (12 GAUGE)

MIRP RESIDENTIAL

1324-1337 INTERVALE AVE. THE BRONX, NEW YORK 10459 WHEDCO 50 East 168th Street Bronx, NY 10452

B

1"

TYPE III, IV, V

ITEMS NOT NOTED SAME A S DETAIL A 1-1/4"

PLACE STANDARD WASHWER BETWEEN CONC. AND ANGLES DOUBLE ANGLES

16 GA. MINIMUM BENT É WASHERS @ 24" O.C.

B STRUT CHANNEL WITH HANGER ROD ALTERNATE STIFFENER CONNECTION

CONNECTIONS TO CONCRETE

21

C

22

TYPE VI & VII CONNECTION TO CONCRETE

23

DUCT-BRACING, CABLE

17

PIPES - BRACING - TRANSVERSE

18

PIPES - BRACING - LONGITUDINAL

19

CHANNEL FRAMING

20

CONNECTIONS - DIAGONAL BRACE

CONNECTIONS - CONCRETE

SPRING SUPPORT DETAIL

24

TITLE:

M-9A

05012

SCALE: BY:

SEISMIC DETAILS

PROJECT NO. : SEAL:

NONE

CHECK:

YL

PJ

DATE:

27 JUN 2005

DWG. NO. :

Information

M-9A SEISMIC DETAILS v12

1 pages

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

698057


You might also be interested in

BETA
2011 Instruction 1120-S
Merit_Badge_Day_Flyer_rev.wps
2006 Instructions for Form 1120-S
2009 Instruction 1120-S
Microsoft Word - Carbozinc 11 HS PDS 11-06.doc