Classification report

Airborne sound insulation of building elements Test report 163 29061/Z01/Z03e

This is a translation of the test report No. 163 29061/Z01/Z03 dated 01. December 2005

Client

AL 7 - MEIPA S.p.A. Via Poggio Renatico 1/3 40016 San Giorgio di Piano (BO) Italien

Basis EN ISO 140-1: 1997+A1: 2004 EN 20140-3: 1995+A1: 2004 EN ISO 717-1: 1996 Corresponds to the national version of DIN EN ISO 140-1, DIN EN ISO 140-3 and DIN EN ISO 717-1. Representation

Product System designation

Insulating glass unit with micro-louver system in cavity E.A.SY. Eclisse Aluminium System

Construction Exterior dimensions Gas filling of cavity Surface-related mass

4 mm Float / 24 mm SZR / 4 mm Float 1230 mm × 1480 mm (w × h) air 24 kg/m

2

Instructions for use The present test report serves to demonstrate the sound insulation of insulating glass. For germany is valid: - Rw is equivalent to Rw,P,Glas

Special features

none

Validity The data and results given relate solely to the tested and described test specimen. Testing for sound insulation does not allow any statement to be made on further characteristics of the present structure regarding performance and quality. Notes on publication

Weighted sound reduction index Rw Spectrum adaptation terms C and Ctr

Rw (C; Ctr) = 37 (-1; -5) dB

ift Rosenheim Centre for Acoustics 01. December 2005

The ift-Guidance Sheet "Hinweise zur Benutzung von ift-Prüfberichten" (Conditions and Guidance for the Use of ift Test Documents") applies. The cover sheet can be used as abstract. Contents The test report comprises a total of 9 pages:

i.V. Dr. Joachim Hessinger Head of Department ift Centre for Acoustics

p.p. Johann Baume Test engineer ift Centre for Acoustics

1 2 3 4

Object Procedure Test results Annotations

Data sheet (2 pages)

Classification report airborne sound insulation of building elements Page 2 of 9 Test report 163 29061/Z01/Z03e dated 01. December 2005 Client: AL 7 - MEIPA S.p.A., 40016 San Giorgio di Piano (BO)

1

1.1

Object

Description of test specimen

Insulating glass unit with micro-louver system in cavity AL 7 - MEIPA S.p.A. E.A.SY. Eclisse Aluminium System 22.02.2005 not specified 4 mm Float / 24 mm SZR / 4 mm Float 33.0 mm (at edge) 33.3 mm (centre of glazing) 1230 mm × 1480 mm (w × h) 1185 mm × 1430 mm (w × h) 44 kg 2 24 kg/m 19° C air 100 % (cavity with counterbalance valve) AL 7-MEIPA ­ Mi.Pr.A.Srl Aluminium 23.5 mm Two steps external: Polyurethane base, SIKAFLEX 219T, manufactured by Sika Italia S.p.a. internal: Polyethylene adhesive tape, manufactured by B.M.P. S.r.l. sun control device, adjustable slats AL 7 - MEIPA S.p.A. two-piece frame (vertical division) magnetic none

Product Manufacturer* Product designation* Date of manufacture* Product charge* Construction Total thickness External dimensions Visible size mass Surface-related mass temperature at pane surface Gas filling of cavity Spacer Manufacturer* Material* Total width Edge sealing*

louver system in cavity Manufacturer* Construction adjustment Special features

The description is based on inspection of the test specimen at ift. Article designations/ numbers as well as material specifications were given by the customer. (Additional data provided by the customer is marked with *).

Q:\LSW\Projekte\163_mig\29061-Meipa-AL7\16329061_Z01_Meipa-Al7e.doc

Classification report airborne sound insulation of building elements Page 3 of 9 Test report 163 29061/Z01/Z03e dated 01. December 2005 Client: AL 7 - MEIPA S.p.A., 40016 San Giorgio di Piano (BO)

1.2

Mounting into test rig Window test rig (,,Z-Wand"): Test rig without flanking transmission according to DIN EN ISO 140-1. The test opening is placed in an seperate concrete frame element with a 5 cm separation fugue, which is sealed in the test opening.

Test rig

Mounting of the test specimen By ift Rosenheim. Mounting position Test specimen mounted in the reveal of the test rig in ratio of 1/3 to 2/3 and fixed with glazing beads (timber, 25 mm × 25 mm) on both sides. The connection joints (reveal and glazing beads) are fully filled with plastic sealant type Perennator 2001 S grey.

Sealing to the test rig

Preparation of the test specimen The insulating glass unit was air-conditioned for 24 h in the test rig. 1.3 Representation of test specimen

The structural details were examined solely on the basis of the characteristics to be classified. The illustrations are based on unchanged documentation provided by the customer.

1 2 3 4 shutter air external 4 24 4 internal

Figure 1

Q:\LSW\Projekte\163_mig\29061-Meipa-AL7\16329061_Z01_Meipa-Al7e.doc

Schematic representation of sample

Figure 2

Schematic representation of sample

2

2.1

Procedure

Sampling The samples were selected by the customer 1 08. march 2005 by carrier commissioned by customer 17943/1

Selection Quantity Delivered Registration No.

Classification report airborne sound insulation of building elements Page 4 of 9 Test report 163 29061/Z01/Z03e dated 01. December 2005 Client: AL 7 - MEIPA S.p.A., 40016 San Giorgio di Piano (BO)

2.2

Process

Technical basics EN ISO 140-1: 1997+A1: 2004 Acoustics - Measurement of sound insulation in buildings and of building elements - Part 1: Requirements for laboratory test facilities with suppressed flanking transmission EN 20140-3: 1995+A1: 2004 Acoustics - Measurement of sound insulation in buildings and of building elements - Part 3: Laboratory measurements of airborne sound insulation of building elements EN ISO 717-1: 1996 Acoustics - Rating of sound insulation in buildings and of building elements - Part 1: Airborne sound insulation Corresponding to the national German standards DIN EN ISO 140-1: 2005-03, DIN EN ISO 140-3: 2005-05 and DIN EN ISO 717-1: 1997-01 Boundary conditions Deviations Test noise Reverberation time T As specified by the standard requirements There are no deviations from the test procedure and/or test conditions Pink Noise Measurement with rotating microphone. Arithmetic mean: 12 single measurements (2 loudspeaker positions each of 6 microphone positions)

Measurement equation sound level difference

A = 0.16

V [m²] T

Measurement with rotating microphones. Energetic mean: 2 single measurements (2 loudspeaker positions and 2 microphone curves)

S [dB] A

Measurement equation

R=L 1 -L 2 +10lg

Q:\LSW\Projekte\163_mig\29061-Meipa-AL7\16329061_Z01_Meipa-Al7e.doc

KEY A L1 L2 R T V S

Equivalent absorption area in m² Sound level of sending room in dB Sound level of receiving room in dB Sound reduction index in dB Reverberation time in s Volume of receiving room in m³ Test surface of specimen in m²

Classification report airborne sound insulation of building elements Page 5 of 9 Test report 163 29061/Z01/Z03e dated 01. December 2005 Client: AL 7 - MEIPA S.p.A., 40016 San Giorgio di Piano (BO)

2.3

Test equipment

Typ Nortronic 830 (Fa. Norsonic-Tippkemper) Type 1201 (Norsonic-Tippkemper) Type 1220 (Norsonic-Tippkemper) Type 1251 (Norsonic-Tippkemper) Dodecahedron (self-built) Type E120 (FG Elektronik)

Integrating sound meter Microphone preamplifiers Microphone units Calibrator loudspeakers Amplifier

Rotating microphone boom Self-built resp. Type 231-N-360 (Norsonic-Tippkemper)

2.4

Date

Testing

16. march 2005 Johann Baume

Testing personnel

Q:\LSW\Projekte\163_mig\29061-Meipa-AL7\16329061_Z01_Meipa-Al7e.doc

Classification report airborne sound insulation of building elements Page 6 of 9 Test report 163 29061/Z01/Z03e dated 01. December 2005 Client: AL 7 - MEIPA S.p.A., 40016 San Giorgio di Piano (BO)

3

Test results

The values of the measured airborne sound reduction index of the tested insulating glass unit were plotted and tabled in the enclosed data sheet related to frequency. For the frequency range of 100 Hz to 3150 Hz the weighted sound reduction index Rw and the spectrum adaptation terms C and Ctr are calculated according to DIN EN ISO 717-1 with the following results:

opening angle 0° (louvers closed) 90° (louvers open)

test result Rw (C; Ctr) = 37 (-1; -5) dB Rw (C; Ctr) = 38 (-2; -5) dB

data sheet Z01 Z03

As set out by DIN EN ISO 717-1, the following additional spectrum adaptation terms are obtained: opening angle 0° (louvers closed): C50-3150 = - dB; C100-5000 = -1 dB; C50-5000 = - dB; - dB; Ctr,50-3150 = - dB; Ctr,100-5000 = -5 dB; Ctr,50-5000 =

opening angle 90° (louvers open): C50-3150 = - dB; C100-5000 = -2 dB; C50-5000 = - dB; - dB; Ctr,50-3150 = - dB; Ctr,100-5000 = -5 dB; Ctr,50-5000 =

Q:\LSW\Projekte\163_mig\29061-Meipa-AL7\16329061_Z01_Meipa-Al7e.doc

Classification report airborne sound insulation of building elements Page 7 of 9 Test report 163 29061/Z01/Z03e dated 01. December 2005 Client: AL 7 - MEIPA S.p.A., 40016 San Giorgio di Piano (BO)

4

4.1

Annotations

Note on DIN 4109

Technical basics DIN 4109: 1989-11 Sound insulation in buildings; requirements and verifications DIN 4109 Beiblatt 1/A1: 2003-09 Sound insulation in buildings; construction examples and calculation methods; Amendment A1 For supply of evidence of sound insulation according to German standard DIN 4109 Beiblatt 1/A1, table 40 the weighted sound reduction index Rw corresponds to the test value Rw,P,Glas.

Rw,P,Glas = 37 dB

ift Rosenheim Centre for Acoustics 01. December 2005

Q:\LSW\Projekte\163_mig\29061-Meipa-AL7\16329061_Z01_Meipa-Al7e.doc

Sound reduction index according to DIN EN ISO 140-3

Laboratory measurement of sound insulation of building elements

Page 8 of 9 Classification report airborne sound insulation of building elements Test report 163 29061/Z01/Z03e dated 01. December 2005

Customer: AL 7 - MEIPA S.p.A., 40016 San Giorgio di Piano (BO) Client: AL 7 - MEIPA S.p.A., 40016 San Giorgio di Piano (BO) Product: Insulating glass unit with micro-louver system in cavity Designation: E.A.SY. Eclisse Aluminium System Data sheet: Z01

Design of test specimen Construction Dimensions Gas filling Mass Temperature Opening angle Test date Test opening 4 mm Float / 24 mm SZR / 4 mm Float Partition wall 1230 mm × 1480 mm Test noise 16. march 2005 1.25 m × 1.50 m = 1.88 m Concrete double partition Pink noise

2

air, 100 % (cavity with counterbalance Volumes of test rooms 3 valve) VS = 101 m 3 2 VE = 67.5 m 24 kg/m (surface-related) 19° (at pane surface) C 0° (louvres closed) Maximum sound reduction index Rw,max = 62 dB (related to test area) Installation conditions Test specimen fixed in the reveal of the test rig with glazing beads on both sides. Connecting joints are filled with plastic sealant. Climatic Conditions 21° 35% RH C;

Special features none

Q:\LSW\Projekte\163_mig\29061-Meipa-AL7\16329061_Z01_Meipa-Al7e.doc

f in Hz R in dB 50 63 80 100 25.1 125 21.2 160 20.0 200 24.3 250 29.8 315 27.1 400 28.3 500 35.1 630 37.8 800 43.1 1000 45.7 1250 49.9 1600 51.5 2000 52.0 2500 46.3 3150 35.0 4000 41.9 5000 46.7

Sound reduction index R in dB

shifted reference curve according to EN ISO 717-1 Test curve frequency range corresponds to reference curve

60

50

40

30

20

10

63

125

250

500

1000

2000

4000

Frequenz f in Hz

Rating according to EN ISO 717-1 (in third-octave bands): Rw (C; Ctr) = 37 (-1; -5) dB C50-3150 = - dB; C100-5000 = -1 dB; C50-5000 = Ctr,50-3150 = - dB; Ctr,100-5000 = -5 dB; Ctr,50-5000 = Test report No.: 163 29061/Z01/Z03e dated 01. December 2005

- dB; - dB;

ift Rosenheim ift Centre for Acoustics

i.V. Dr. Joachim Hessinger Head of Department

Sound reduction index according to DIN EN ISO 140-3

Laboratory measurement of sound insulation of building elements

Page 9 of 9 Classification report airborne sound insulation of building elements Test report 163 29061/Z01/Z03e dated 01. December 2005

Customer: AL 7 - MEIPA S.p.A., 40016 San Giorgio di Piano (BO) Client: AL 7 - MEIPA S.p.A., 40016 San Giorgio di Piano (BO) Product: Insulating glass unit with micro-louver system in cavity Designation: E.A.SY. Eclisse Aluminium System Data sheet: Z03

Design of test specimen Construction Dimensions Gas filling Mass Temperature Opening angle Test date Test opening 4 mm Float / 24 mm SZR / 4 mm Float Partition wall 1230 mm × 1480 mm Test noise 16. march 2005 1.25 m × 1.50 m = 1.88 m Concrete double partition Pink noise

2

air, 100 % (cavity with counterbalance Volumes of test rooms 3 valve) VS = 101 m 3 2 VE = 67.5 m 24 kg/m (surface-related) 19° (at pane surface) C 90° (louvres open) Maximum sound reduction index Rw,max = 62 dB (related to test area) Installation conditions Test specimen fixed in the reveal of the test rig with glazing beads on both sides.Connecting joints are filled with plastic sealant. Climatic Conditions 21° 35% RH C;

Special features none

Q:\LSW\Projekte\163_mig\29061-Meipa-AL7\16329061_Z01_Meipa-Al7e.doc

f in Hz R in dB 50 63 80 100 26.3 125 20.8 160 21.0 200 22.9 250 30.2 315 27.2 400 29.2 500 40.5 630 40.4 800 46.6 1000 48.9 1250 51.2 1600 52.2 2000 54.3 2500 49.9 3150 38.4 4000 45.9 5000 50.9

Sound reduction index R in dB

shifted reference curve according to EN ISO 717-1 Test curve frequency range corresponds to reference curve

60

50

40

30

20

10

63

125

250

500

1000

2000

4000

Frequenz f in Hz

Rating according to EN ISO 717-1 (in third-octave bands): Rw (C; Ctr) = 38 (-2; -5) dB C50-3150 = - dB; C100-5000 = -1 dB; C50-5000 = Ctr,50-3150 = - dB; Ctr,100-5000 = -5 dB; Ctr,50-5000 = Test report No.: 163 29061/Z01/Z03e dated 01. December 2005

- dB; - dB;

ift Rosenheim ift Centre for Acoustics

i.V. Dr. Joachim Hessinger Head of Department

Information

16329061_Z01_Meipa-Al7e

9 pages

Find more like this

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

686781


You might also be interested in

BETA
16329061_Z01_Meipa-Al7e