AIR HANDLERS

AIR HANDLERS

RHLA- High Efficiency featuring R-22 Refrigerant RHLL- High Efficiency featuring Earth-Friendly R-410A Refrigerant

earth friendly refrigerant

AIR HANDLERS

RHSA- Standard Efficiency featuring R-22 Refrigerant RHSL- Standard Efficiency featuring Earth-Friendly R-410A Refrigerant Features

I

earth friendly refrigerant

RHLA/RHLL feature GE's new X-13 motor which provides enhanced SEER performance with most Rheem outdoor units. I 11/2 ton [5.3 kW] through 5 ton [17.6 kW] models are between 421/2 to 551/2 inches [1080 to 1410 mm] tall and 22 inches [559 mm] deep. I Versatile 4-way convertible design for upflow, downflow, horizontal left and horizontal right applications. I Factory-installed high efficiency indoor coil. I All models meet or exceed 330 to 400 CFM [156 to 189 L/s] per ton at .3 inches [.7 kPa] of external static pressure. I Enhanced airflow up to .7" external static pressure. I Sturdy construction with 1.0 inch [.24 kPa] of reinforced foil faced jacket insulation for excellent thermal and sound insulation. I Field-installed auxiliary electric heater kits provide exact heat for indoor comfort. Kits include circuit breakers which meet UL and cUL requirements for service disconnect.

Engineering Features

RHLA/RHLL/RHSA/RHSL- Series

I

The most compact unit design available, all standard heat air handler models only 421/2 to 551/2 inches [1079 to 1409 mm] high. I Attractive pre-painted cabinet exterior. I Rugged wall steel cabinet construction, designed for added strength and versatility. I 1.0" foil faced insulation mechanically retained in blower compartment for excellent thermal and sound performance. I Four leg blower motor mount. I Blower housing with controls, motor and blower. Slide out design for service and maintenance convenience. I Traditional open wire element design for heat applications. I Field convertible for vertical downflow, horizontal left hand or right hand air supply. I 3 combustible floor base accessories fit all model sizes when required for downflow installations on combustible floors. I Indoor coil design provides low air side pressure drop, high performance and extremely compact size.

[ ] Designates Metric Conversions

I

Expansion valve on indoor coil provides for operation with air conditioning or heat pump using the same coil. I Coils are constructed of aluminum fins bonded to internally grooved copper tubing. I Molded polymer corrosion resistant condensate drain pan is provided on all indoor coils. I Supply duct flanges provided as standard on air handler cabinet. I Provisions for field electrical, connections available from either side or top of the air handler cabinet. I Connection point for high voltage wiring is inside the air handler cabinet. Low voltage connection is made on the outside of the air handler cabinet. I Concentric knockouts are provided for power connection to cabinet. Installer may pull desired hole size up to 2 inches [51 mm] for 11/2 inch [38 mm] conduit. I Front refrigerant and drain connections.

GENERAL TERMS OF LIMITED WARRANTY

Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty. Indoor Coil leaks caused by factory defects .................................................Five (5) Years Electric Heating Element ............................Five (5) Years Any Other Part ............................................Five (5) Years

For Complete Details of the Limited Warranty, Including Applicable Terms and Conditions, See Your Local Installer or Contact the Manufacturer for a Copy.

2

Rheem Manufacturing Company

Model Identification

R H L A -- HM 24 17 J A

Design Variation A = 1st Design Voltage A = 115/1/60 J = 208/240/1/60 Cabinet Size 17 = 17.5" [431.8 mm] (600-1200 CFM) 21 = 21" [533.4 mm] (1400-1600 CFM) 24 = 24.5" [609.6 mm] (1600-1800 CFM) Capacity 24 = 18,000/24,000 BTU/H [5.27/7.03 kW] 36 = 30,000/36,000 BTU/H [6.79/10.55 kW] 48 = 42,000/48,000 BTU/H [12.31/14.06 kW] 60 = 60,000 BTU/H [17.58 kW] HM = A/C or HP Multi-Position (Vertical Upflow/Horizontal Left is the factory configuration) Refrigerant A = R-22 L = R-410A L = High Efficiency (X-13 Motor) Classification H = Air Handler Rheem

Available Models at A Voltage

RHSA(L)-HM1817AA RHSA(L)-HM2417AA RHSA(L)-HM3017AA RHSA(L)-HM3617AA RHSA(L)-HM4221AA RHSA(L)-HM4821AA RHLA(L)-HM2417AA RHLA(L)-HM3617AA RHLA(L)-HM4821AA RHLA(L)-HM4824AA RHLA(L)-HM6024AA

Available Models at J Voltage

RHSA(L)-HM1817JA RHSA(L)-HM2417JA RHSA(L)-HM3017JA RHSA(L)-HM3617JA RHSA(L)-HM3621JA RHSA(L)-HM4221JA RHSA(L)-HM4821JA RHSA(L)-HM4824JA RHSA(L)-HM6024JA* RHLA(L)-HM2417JA RHLA(L)-HM3617JA RHLA(L)-HM4821JA RHLA(L)-HM4824JA RHLA(L)-HM6024JA

Available Models at D Voltage

RHSA(L)-HM3617DA RHSA(L)-HM3621DA RHSA(L)-HM4221DA RHSA(L)-HM4821DA RHSA(L)-HM4824DA RHSA(L)-HM6024DA

R

H

S

A

-- HM 18 17

J

A

Design Variation A = 1st Design Voltage A = 115/1/60 D = 480V-3-60 J = 208/240/1/60 Cabinet Size 17 = 17.5" [431.8 mm] (600-1200 CFM) 21 = 21" [533.4 mm] (1200-1600 CFM) 24 = 24.5" [609.6 mm] (1600-1800 CFM) Capacity 18 = 18,000 BTU/H [5.27 kW] 24 = 24,000 BTU/H [7.03 kW] 30 = 30,000 BTU/H [8.79 kW] 36 = 36,000 BTU/H [10.55 kW] 42 = 42,000 BTU/H [12.31 kW] 48 = 48,000 BTU/H [14.06 kW] 60 = 60,000 BTU/H [17.58 kW]

*RHSA(L)-HM6024JA is ARI rated for three phase application only. · Supply circuit protective devices may be fuses or "HACR" type circuit breakers. · Largest motor load is included in single circuit and multiple circuit. · If non-standard fuse size is specified, use the next larger fuse size. · J Voltage (230V) single-phase air handler is designed to be used with single or three phase 230 volt power. In the case of connecting 3-phase power to the air handler terminal block, bring only two leads to the terminal block. Cap, insulate and fully secure the third lead. · The air handlers are shipped from the factory with the proper indoor coil installed, and cannot be ordered without a coil. · The air handlers do not have an internal filter rack. An external filter rack or other means of filtration is required.

HM = A/C or HP, Multi-Position (Vertical Upflow/Horizontal Left is the factory configuration) Refrigerant A = R-22 L = R-410A S = Standard Model (PSC Motor) Classification H = Air Handler Rheem [ ] Designates Metric Conversions

Rheem Manufacturing Company

3

Unit Dimensions

ELECTRICAL CONNECTIONS MAY EXIT TOP OR EITHER SIDE HIGH VOLTAGE CONNECTION 7/8 [22.2 mm], 13/32 [27.8 mm], 131/32 [50 mm] DIA. KNOCKOUTS.

SUPPLY AIR

NOTE: 24 CLEARANCE REQUIRED IN FRONT OF UNIT FOR FILTER AND COIL MAINTENANCE.

W A

105/16 [262 mm]

LOW VOLTAGE CONNECTION 5/8 [15.9 mm] AND 7/8 [22.2 mm] KNOCKOUT

Return Air Opening Dimensions

Model Cabinet Size 17 21 24 Return Air Opening Width (Inches) 157/8 193/8 227/8 Return Air Opening Depth/Length (Inches) 193/4 193/4 193/4

H

AUXILIARY DRAIN CONNECTION 3/4 [19.1 mm] FEMALE PIPE THREAD (NPT) HORIZONTAL APPLICATION ONLY

3/4

PRIMARY DRAIN CONNECTION [19.1 mm] FEMALE PIPE THREAD (NPT)

AUXILIARY DRAIN CONNECTION 3/4 [19.1 mm] FEMALE PIPE THREAD (NPT) UPFLOW/DOWNFLOW APPLICATION ONLY

LIQUID LINE CONNECTION COPPER (SWEAT) VAPOR LINE CONNECTION COPPER (SWEAT)

191/2 [495 mm] RETURN AIR OPENING 2111/16 [551 mm]

UPFLOW UNIT SHOWN: UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW, HORIZONTAL RIGHT OR LEFT AIR SUPPLY.

HORIZONTAL ADAPTER KIT

515/16 [151 mm]

41/8 1 [105 mm] 3 /16 [76 mm] 13/16 [48 mm] 11/8 [29 mm] 11/16 [27 mm] 13/8 [35 mm] 213/16 [71 mm]

VAPOR LINE CONNECTION AUXILIARY HORIZONTAL DRAIN CONNECTION

51/4 [133 mm] 53/8 [136 mm]

PRIMARY DRAIN CONNECTION AUXILIARY UPFLOW/DOWNFLOW DRAIN CONNECTION

LIQUID LINE CONNECTION

VERTICAL DRAIN PAN

[ ] Designates Metric Conversions ( ) Designates Unit with Double Coil Cabinet

Unit Dimensions & Weights

Model Size 1817/2417 3017/3617 3621 4221/4821 4824 6024 Unit Width "W" In. [mm] 171/2 [445] 171/2 [445] 211/2 [533] 211/2 [533] 241/2 [622] 241/2 [622] Unit Height "H" In. [mm] 421/2 [1080] 421/2 [1080] 421/2 [1080] 501/2 [1282] 551/2 [1410] 551/2 [1410] Supply Duct "A" In. [mm] 161/2 [406] 161/2 [406] 191/2 [495] 191/2 [495] 231/2 [584] 231/2 [584] Air Flow CFM (Nom.) [L/s] Lo Hi 600 [283] 800 [378] 1000 [472] 1200 [566] 1200 [566] -- 1400 [661] 1600 [755] 1600 [755] -- -- 1800 [850] Unit Weight/Shipping Weight (Lbs.) [kg] Unit With Coil (Max. KW) 82/96 [37/44] 92/106 [37/48] 97/112 [44/51] 150/166 [68/75] 162/180 [73/81] 181/198 [82/90]

4

Rheem Manufacturing Company

Airflow Directions

UPFLOW DOWNFLOW

HORIZONTAL LEFT HAND AIRFLOW

HORIZONTAL RIGHT HAND AIRFLOW

Rheem Manufacturing Company

5

Airflow Performance

Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size, voltage and number of electric heaters to be used. Make sure external static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric heat operation. For optimum blower performance, operate the unit in the .3 [8 mm] to .7 inches [18 mm] W.C. external static range. Units with coils should be applied with a minimum of .1 inch [3 mm] W.C. external static range.

Airflow Operating Limits

Model Cabinet Size Cooling BTUH x 1,000 Cooling Tons Nominal Heat Pump or Air Conditioning Maximum Heat/Cool CFM [L/s] (37.5 CFM [18 L/s]/1,000 BTUH) (450 CFM [212 L/s]/Ton Nominal) Heat Pump or Air Conditioning Nominal Heat/Cool CFM [L/s] (33.3 CFM [16 L/s]/1,000 BTUH) (400 CFM [189 L/s]/Ton Nominal) Heat Pump or Air Conditioning Minimum Heat/Cool CFM [L/s] (30.0 CFM [14 L/s]/1,255 BTUH) (360 CFM [170 L/s]/Ton Nominal) Maximum kW Electric Heating & Minimum Electric Heat CFM [L/s] Maximum Electric Heat Rise °F [°C] -018 1.5 675 [319] 17 -024 2 900 [425] -030 2.5 1125 [531] 17 -036 3 1350 [637] -042 3.5 1575 [743] 21 -048 4 1800 [850] -048 4 1800 [850] 24 -060 5 1930 [911]

600 [283]

800 [378]

1000 [472]

1200 [566]

1400 [661]

1600 [755]

1600 [755]

1800 [850]

540 [255] 10 500 [236] 85 [29]

720 [340] 10 650 [307] 85 [29]

900 [425] 15 865 [408] 85 [29]

1080 [510] 15 1015 [400] 85 [29]

1260 [595] 20 1200 [566] 85 [29]

1440 [680] 20 1400 [600] 85 [29]

1440 [680] 20 1400 [600] 85 [29]

1620 [765] 25 1730 [821] 85 [29]

[ ] Designates Metric Conversions

6

Rheem Manufacturing Company

240V Airflow Performance Data--RHSA/RHSL (PSC Motor)

Model No. Motor Speed from Factory Manufacturer Recommended Air-Flow Range (Min/Max) CFM Blower Size/ Motor HP [W] # of Speed PSC CFM [L/s] Air Delivery/RPM/Watts--240 Volts Motor Speed 0.1 [.02]

CFM Low -1817 No Heater Low 240V 517/711 CFM [244/336 L/s] 10x6 1/5 HP [149] 2 Speed High RPM Watts CFM RPM Watts CFM Low -1817 with 13 kW Heater Low 240V 467/661 CFM [230/312 L/s] 10x6 1/5 HP [149] 2 Speed High RPM Watts CFM RPM Watts CFM Low -2417 No Heater Low 240V 647/888 CFM [305/419 L/s] 10x6 1/5 HP [149] 2 Speed High RPM Watts CFM RPM Watts CFM Low -2417 with 13 kW Heater Low 240V 617/638 CFM [291/395 L/s] 10x6 1/5 HP [149] 2 Speed High RPM Watts CFM RPM Watts CFM Low -3017 No Heater Low 240V 864/1004 CFM [408/474 L/s] 10x8 1/4 HP [186] 2 Speed High RPM Watts CFM RPM Watts CFM Low -3017 with 18 kW Heater Low 240V 814/904 CFM [384/427 L/s] 10x8 1/4 HP [186] 2 Speed High RPM Watts CFM RPM Watts CFM Low -3617/-3621 No Heater Low 240V 1104/1248 CFM [521/589 L/s] 11x8 1/3 HP [249] 2 Speed High RPM Watts CFM RPM Watts 668 [315] 541 180 -- -- -- 638 [301] 571 171 -- -- -- 817 [386] 616 239 -- -- -- 787 [371] 646 230 -- -- -- 1022 [482] 700 344 -- -- -- 972 [459] 750 324 -- -- -- 1229 [580] 788 466 -- -- --

External Static Pressure--Inches W.C. [kPa] 0.2 [.05]

637 [301] 596 171 -- -- -- 607 [286] 626 162 -- -- -- 779 [368] 667 230 -- -- -- 749 [353] 697 221 -- -- -- 987 [466] 754 313 -- -- -- 937 [442] 804 293 -- -- -- 1201 [567] 833 462 -- -- --

0.3 [.07]

595 [281] 657 166 -- -- -- 565 [267] 687 157 -- -- -- 757 [357] 715 221 -- -- -- 727 [343] 745 212 -- -- -- 940 [444] 794 302 -- -- -- 890 [420] 844 282 -- -- -- 1170 [552] 872 427 -- -- --

0.4 [.10]

560 [264] 706 161 -- -- -- 530 [250] 736 152 -- -- -- 693 [327] 770 206 -- -- -- 663 [313] 800 197 -- -- -- 903 [426] 833 294 -- -- -- 853 [403] 883 274 -- -- -- 1141 [538] 909 406 -- -- --

0.5 [.12]

517 [244] 761 155 711 [336] 812 243 487 [230] 791 146 661 [312] 837 232 647 [305] 808 196 888 [419] 875 331 617 [291] 838 187 838 [395] 900 320 864 [408] 870 288 1004 [474] 924 364 814 [384] 920 268 904 [427] 949 334 1104 [521] 951 395 1248 [589] 1008 488

0.6 [.15]

-- -- -- 662 [312] 853 227 -- -- -- 612 [289] 878 216 -- -- -- 828 [391] 908 313 -- -- -- 778 [367] 933 302 -- -- -- 951 [449] 953 352 -- -- -- 851 [402] 978 322 -- -- -- 1194 [563] 1028 475

0.7 [.17]

-- -- -- 614 [290] 890 210 -- -- -- 564 [266] 915 199 -- -- -- 774 [365] 958 301 -- -- -- 724 [342] 983 290 -- -- -- 883 [417] 975 344 -- -- -- 783 [370] 1000 314 -- -- -- 1133 [535] 1042 454

Notes: · The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. · The following formula can be used to calculation the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater ­ (Airflow without heater ­ Airflow with maximum heater) x (N kW/maximum heater kW)

[ ] Designates Metric Conversions

Rheem Manufacturing Company

7

240V Airflow Performance Data--RHSA/RHSL (PSC Motor) (con't.)

Model No. Motor Speed from Factory Manufacturer Recommended Air-Flow Range (Min/Max) CFM Blower Size/ Motor HP [W] # of Speed PSC CFM [L/s] Air Delivery/RPM/Watts--240 Volts Motor Speed 0.1 [.02]

CFM Low -3617/3621 with 18 kW Heater Low 240V 1054/1148 CFM [497/542 L/s] 10x8 1/3 HP [249] 2 Speed High RPM Watts CFM RPM Watts CFM Low -4221 No Heater Low 240V 1241/1537 CFM [586/725 L/s] 10x10 1/2 HP [373] 2 Speed High RPM Watts CFM RPM Watts CFM Low -4221 with 20 kW Heater Low 240V 1225/1500 CFM [553/678 L/s] 10x10 1/2 HP [373] 2 Speed High RPM Watts CFM RPM Watts CFM Low -4821/-4824 No Heater Low 240V 1572/1824 CFM [742/861 L/s] 10x10 3/4 HP [559] 2 Speed High RPM Watts CFM RPM Watts CFM Low -4821/-4824 with 25 kW Heater Low 240V 1225/1500 CFM [709/814 L/s] 10x10 3/4 HP [559] 2 Speed High RPM Watts CFM RPM Watts CFM Low -6024 No Heater Low 240V 1766/1965 CFM [833/927 L/s] 11x11 3/4 HP [559] 2 Speed High RPM Watts CFM RPM Watts CFM Low -6024 with 30 kW Heater Low 240V 1225/1500 CFM [709/814 L/s] 11x11 3/4 HP [559] 2 Speed High RPM Watts CFM RPM Watts 1179 [556] 838 446 -- -- -- 1526 [720] 834 560 -- -- -- 1456 [687] 886 542 -- -- -- 1741 [822] 878 785 -- -- -- 1671 [789] 945 715 -- -- -- 1944 [917] 764 779 -- -- -- 1844 [870] 839 745 -- -- --

External Static Pressure--Inches W.C. [kPa] 0.2 [.05]

1151 [543] 883 442 -- -- -- 1474 [696] 870 549 -- -- -- 1404 [663] 906 524 -- -- -- 1719 [811] 920 757 -- -- -- 1649 [778] 965 685 -- -- -- 1912 [902] 803 763 -- -- -- 1812 [855] 865 729 -- -- --

0.3 [.07]

1120 [529] 922 407 -- -- -- 1427 [673] 902 535 -- -- -- 1357 [640] 925 505 -- -- -- 1667 [787] 950 707 -- -- -- 1597 [754] 995 650 -- -- -- 1860 [878] 838 747 -- -- -- 1760 [831] 890 713 -- -- --

0.4 [.10]

1091 [515] 959 386 -- -- -- 1307 [617] 948 476 -- -- -- 1237 [584] 959 468 -- -- -- 1628 [768] 981 667 -- -- -- 1558 [735] 1025 630 -- -- -- 1813 [856] 865 729 -- -- -- 1713 [808] 913 696 -- -- --

0.5 [.12]

1054 [497] 1001 375 1148 [542] 1033 458 1241 [586] 968 462 1537 [725] 1072 860 1171 [553] 992 431 1437 [678] 1080 840 1572 [742] 1007 641 1824 [861] 1102 871 1502 [709] 1050 610 1724 [814] 1116 810 1766 [833] 889 708 1965 [927] 943 828 1666 [786] 935 678 1865 [880] 987 788

0.6 [.15]

-- -- -- 1094 [516] 1053 445 -- -- -- 1418 [669] 1077 835 -- -- -- 1318 [622] 1090 800 -- -- -- 1767 [834] 1112 830 -- -- -- 1667 [787] 1119 780 -- -- -- 1908 [900] 967 799 -- -- -- 1808 [853] 1001 766

0.7 [.17]

-- -- -- 1033 [487] 1067 424 -- -- -- 1334 [630] 1085 820 -- -- -- 1234 [582] 1105 785 -- -- -- 1653 [780] 1121 770 -- -- -- 1553 [733] 1130 730 -- -- -- 1854 [875] 977 795 -- -- -- 1754 [828] 1014 744

Notes: · The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. · The following formula can be used to calculation the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater ­ (Airflow without heater ­ Airflow with maximum heater) x (N kW/maximum heater kW)

[ ] Designates Metric Conversions

8

Rheem Manufacturing Company

115/208/480V Airflow Performance Data--RHSA/RHSL (PSC Motor)

Model No. Motor Speed from Factory Manufacturer Recommended Air-Flow Range (Min/Max) CFM Blower Size/ Motor HP [W] # of Speed PSC CFM [L/s] Air Delivery/RPM/Watts--115/208/480 Volts Motor Speed 0.1 [.02]

CFM Low -1817 No Heater Low 240V 523/705 CFM [247/333 L/s] 10x6 1/5 HP [149] 2 Speed High RPM Watts CFM RPM Watts CFM Low -1817 with 13 kW Heater Low 240V 493/655 CFM [233/309 L/s] 10x6 1/5 HP [149] 2 Speed High RPM Watts CFM RPM Watts CFM Low -2417 No Heater Low 240V 682/897 CFM [322/423 L/s] 10x6 1/5 HP [149] 2 Speed High RPM Watts CFM RPM Watts CFM Low -2417 with 13 kW Heater Low 240V 652/847CFM [308/400 L/s] 10x6 1/5 HP [149] 2 Speed High RPM Watts CFM RPM Watts CFM Low -3017 No Heater Low 240V 883/1015 CFM [417/479 L/s] 10x8 1/4 HP [186] 2 Speed High RPM Watts CFM RPM Watts CFM Low -3017 with 18 kW Heater Low 240V 833/915 CFM [393/432 L/s] 10x8 1/4 HP [186] 2 Speed High RPM Watts CFM RPM Watts CFM Low -3617/-3621 No Heater Low 240V 1062/1194 CFM [501/563 L/s] 10x8 1/3 HP [249] 2 Speed High RPM Watts CFM RPM Watts 681 [321] 541 193 -- -- -- 651 [307] 571 184 -- -- -- 875 [413] 648 259 -- -- -- 845 [399] 678 250 -- -- -- 1038 [490] 721 325 -- -- -- 988 [466] 771 305 -- -- -- 1201 [567] 833 462 -- -- --

External Static Pressure--Inches W.C. [kPa] 0.2 [.05]

636 [300] 601 181 -- -- -- 606 [286] 631 172 -- -- -- 806 [380] 700 255 -- -- -- 776 [366] 730 246 -- -- -- 1010 [477] 771 314 -- -- -- 960 [453] 821 294 -- -- -- 1170 [552] 872 427 -- -- --

0.3 [.07]

606 [286] 670 173 -- -- -- 576 [272] 700 164 -- -- -- 787 [371] 745 243 -- -- -- 757 [357] 775 234 -- -- -- 976 [461] 799 303 -- -- -- 926 [437] 849 283 -- -- -- 1141 [538] 909 406 -- -- --

0.4 [.10]

567 [268] 714 164 -- -- -- 537 [253] 744 155 -- -- -- 739 [349] 794 234 -- -- -- 709 [335] 824 225 -- -- -- 925 [437] 848 290 -- -- -- 875 [413] 898 270 -- -- -- 1104 [521] 951 396 -- -- --

0.5 [.12]

523 [247] 768 157 705 [333] 815 239 493 [233] 798 148 655 [309] 840 228 682 [322] 827 227 897 [423] 906 332 652 [308] 857 218 847 [400] 931 321 883 [417] 880 286 1015 [479] 928 356 833 [393] 930 266 915 [432] 953 326 1062 [501] 965 385 1194 [563] 1024 475

0.6 [.15]

-- -- -- 650 [307] 861 227 -- -- -- 600 [283] 886 216 -- -- -- 851 [402] 925 318 -- -- -- 801 [378] 950 307 -- -- -- 963 [454] 955 341 -- -- -- 863 [407] 980 311 -- -- -- 1134 [535] 1042 454

0.7 [.17]

-- -- -- 599 [283] 989 204 -- -- -- 549 [259] 1014 193 -- -- -- 765 [361] 955 306 -- -- -- 715 [337] 980 295 -- -- -- 890 [420] 974 329 -- -- -- 790 [373] 999 299 -- -- -- 1078 [509] 1060 417

Notes: · The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. · The following formula can be used to calculation the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater ­ (Airflow without heater ­ Airflow with maximum heater) x (N kW/maximum heater kW)

[ ] Designates Metric Conversions

Rheem Manufacturing Company

9

115/208/480V Airflow Performance Data--RHSA/RHSL (PSC Motor)

Model No. Motor Speed from Factory Manufacturer Recommended Air-Flow Range (Min/Max) CFM Blower Size/ Motor HP [W] # of Speed PSC CFM [L/s] Air Delivery/RPM/Watts--115/208/480V Volts Motor Speed 0.1 [.02]

CFM Low -3617/3621 with 18 kW Heater Low 240V 1012/1094 CFM [478/516 L/s] 10x8 1/3 HP [249] 2 Speed High RPM Watts CFM RPM Watts CFM Low -4221 No Heater Low 240V 1211/1514 CFM [571/714 L/s] 10x10 1/2 HP [373] 2 Speed High RPM Watts CFM RPM Watts CFM Low -4221 with 20 kW Heater Low 240V 1225/1500 CFM [538/667 L/s] 10x10 1/2 HP [373] 2 Speed High RPM Watts CFM RPM Watts CFM Low -4821/-4824 No Heater Low 240V 1542/1787 CFM [728/843 L/s] 10x10 3/4 HP [559] 2 Speed High RPM Watts CFM RPM Watts CFM Low -4821/-4824 with 25 kW Heater Low 240V 1225/1500 CFM [695/796 L/s] 10x10 3/4 HP [559] 2 Speed High RPM Watts CFM RPM Watts CFM Low -6024 No Heater Low 240V 1710/1967 CFM [807/928 L/s] 11x11 3/4 HP [559] 2 Speed High RPM Watts CFM RPM Watts CFM Low -6024 with 30 kW Heater Low 240V 1225/1500 CFM [695/796 L/s] 11x11 3/4 HP [559] 2 Speed High RPM Watts CFM RPM Watts 1151 [543] 883 442 -- -- -- 1493 [705] 822 540 -- -- -- 1423 [672] 870 514 -- -- -- 1711 [807] 863 765 -- -- -- 1641 [774] 930 700 -- -- -- 1866 [881] 764 778 -- -- -- 1796 [848] 828 735 -- -- --

External Static Pressure--Inches W.C. [kPa] 0.2 [.05]

1120 [529] 922 407 -- -- -- 1449 [684] 858 519 -- -- -- 1379 [651] 882 508 -- -- -- 1689 [797] 905 737 -- -- -- 1619 [764] 950 660 -- -- -- 1833 [865] 803 756 -- -- -- 1763 [832] 860 718 -- -- --

0.3 [.07]

1091 [515] 959 386 -- -- -- 1363 [643] 885 506 -- -- -- 1293 [610] 925 490 -- -- -- 1637 [773] 935 687 -- -- -- 1567 [739] 985 630 -- -- -- 1806 [852] 824 733 -- -- -- 1736 [819] 878 705 -- -- --

0.4 [.10]

1054 [497] 1001 376 -- -- -- 1287 [607] 931 484 -- -- -- 1217 [574] 957 461 -- -- -- 1598 [754] 966 647 -- -- -- 1528 [721] 1015 600 -- -- -- 1772 [836] 856 715 -- -- -- 1702 [803] 890 695 -- -- --

0.5 [.12]

1012 [478] 1015 365 1094 [516] 1049 445 1211 [571] 958 459 1514 [714] 1061 710 1141 [538] 992 431 1414 [667] 1067 700 1542 [728] 992 621 1787 [843] 1089 695 1472 [695] 1041 580 1687 [796] 1095 670 1710 [807] 886 701 1967 [928] 948 850 1640 [774] 1001 678 1867 [881] 989 818

0.6 [.15]

-- -- 1034 [488] 1067 424 -- -- -- 1411 [666] 1069 702 -- -- -- 1311 [619] 1080 678 -- -- -- 1679 [792] 1098 665 -- -- -- 1579 [745] 1107 635 -- -- -- 1916 [904] 959 827 -- -- -- 1816 [857] 1005 795

0.7 [.17]

-- -- 978 [462] 1085 387 -- -- -- 1315 [621] 1078 677 -- -- -- 1215 [573] 1094 665 -- -- -- 1575 [743] 1110 630 -- -- -- 1475 [696] 1120 615 -- -- -- 1863 [879] 991 816 -- -- -- 1763 [832] 1020 780

Notes: · The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. · The following formula can be used to calculation the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater ­ (Airflow without heater ­ Airflow with maximum heater) x (N kW/maximum heater kW)

[ ] Designates Metric Conversions

10

Rheem Manufacturing Company

115V/208V/240V Airflow Performance Data--RHLA/RHLL (X-13 Motor)

Model No. Tonnage Application Motor Speed From Factory Manufacturer Blower Size/ Recommended Motor Motor Air-Flow Range HP [W] Speed (Min/Max) CFM # of Speed

CFM 2 -2417 No Heater 1.5 Ton 4 509/681 CFM [240/321 L/s] 10x6 1/3 HP [249] 5 Speed 3 RPM Watts CFM RPM Watts CFM 2 -2417 with 13 kW Heater 1.5 Ton 4 490/666 CFM [231/314 L/s] 10x6 1/3 HP [249] 5 Speed 3 RPM Watts CFM RPM Watts CFM 4 -2417 No Heater 2 Ton 4 730/651 CFM [345/307 L/s] 10x6 1/3 HP [249] 5 Speed 5 RPM Watts CFM RPM Watts CFM 4 -2417 with 13 kW Heater 2 Ton 4 711/626CFM [336/295 L/s] 10x6 1/3 HP [249] 5 Speed 5 RPM Watts CFM RPM Watts 2 -3617 No Heater 2.5 Ton 4 935/1084 CFM [441/512 L/s] 10x8 1/2 HP [373] 5 Speed 3 RPM Watts CFM RPM Watts 2 -3617 with 18 kW Heater 2.5 Ton 4 910/1059 CFM [429/500 L/s] 10x8 1/2 HP [373] 5 Speed 3 RPM Watts CFM RPM Watts 4 -3617 No Heater 3 Ton 4 1130/1275 CFM [533/602 L/s] 10x8 1/2 HP [373] 5 Speed 5 RPM Watts CFM RPM Watts 4 -3617 with 18 kW Heater 3 Ton 4 1105/1250 CFM [521/590 L/s] 10x8 1/2 HP [373] 5 Speed 5 RPM Watts CFM RPM Watts

X-13 CFM [L/s] Air Delivery/RPM/Watts--115/208/240 Volts External Static Pressure--Inches W.C. [kPa] 0.1 [.02]

689 [325] 671 153 -- -- -- 670 [316] 699 162 -- -- -- 875 [413] 775 237 -- -- -- 856 [404] 803 246 -- -- -- 671 153 -- -- -- 711 164 -- -- -- 775 237 -- -- -- 815 248 -- -- --

0.2 [.05]

644 [304] 725 168 -- -- -- 625 [295] 753 177 -- -- -- 839 [396] 816 249 -- -- -- 820 [387] 844 258 -- -- -- 725 168 -- -- -- 765 179 -- -- -- 816 249 -- -- -- 856 260 -- -- --

0.3 [.07]

602 [284] 764 174 -- -- -- 583 [275] 792 183 -- -- -- 804 [379] 846 259 -- -- -- 785 [370] 874 268 -- -- -- 764 174 -- -- -- 804 185 -- -- -- 846 259 -- -- -- 886 270 -- -- --

0.4 [.10]

563 [266] 809 180 -- -- -- 544 [257] 837 189 -- -- -- 762 [360] 882 268 -- -- -- 743 [351] 910 277 -- -- -- 809 180 -- -- -- 952 [449] 849 191 -- -- -- 882 268 -- -- -- 922 279 -- -- --

0.5 [.12]

509 [240] 852 188 681 [321] 896 249 490 [231] 880 197 666 [314] 916 257 730 [345] 926 277 651 [307] 963 338 711 [336] 954 286 626 [295] 983 346 935 [441] 852 188 896 249 910 [429] 892 199 936 260 926 277 963 338 966 288 1003 349

0.6 [.15]

-- -- -- 644 [304] 936 257 -- -- -- 629 [297] 956 265 -- -- -- 614 [290] 999 348 -- -- -- 589 [278] 1019 356 -- -- -- 936 257 -- -- -- 976 268 -- -- -- 999 348 -- -- -- 1039 359

0.7 [.17]

-- -- -- 603 [285] 971 261 -- -- -- 588 [277] 991 269 -- -- -- 573 [270] 1029 363 -- -- -- 548 [259] 1049 371 -- -- -- 971 261 -- -- -- 1011 272 -- -- -- 1029 363 -- -- -- 1069 374

CFM 1093 [516] 1050 [496] 1017 [480] 977 [461]

1084 [512] 1040 [491] 1001 [472]

CFM 1068 [504] 1025 [484] 992 [468]

1059 [500] 1015 [479] 976 [461]

CFM 1270 [599] 1237 [584] 1199 [566] 1165 [550] 1130 [533]

1275 [602] 1244 [587] 1211 [571]

CFM 1245 [588] 1212 [572] 1174 [554] 1140 [538] 1105 [521]

1250 [590] 1219 [575] 1186 [560]

Notes: · The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. · The following formula can be used to calculation the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater ­ (Airflow without heater ­ Airflow with maximum heater) x (N kW/maximum heater kW)

[ ] Designates Metric Conversions

Rheem Manufacturing Company

11

115/208/240V Airflow Performance Data--RHLA/RHLL (X-13 Motor) (con't.)

Model No. Tonnage Application Motor Speed From Factory Manufacturer Blower Size/ Recommended Motor Motor Air-Flow Range HP [W] Speed (Min/Max) CFM # of Speed

4 -4821 No Heater 3.5 Ton 4 1337/1447 CFM [631/683 L/s] 10x10 3/4 HP [559] 5 Speed 5 RPM Watts CFM RPM Watts 2 -4821 with 20 kW Heater 3.5 Ton 4 1297/1333 CFM [612/629 L/s] 10x10 3/4 HP [559] 5 Speed 3 RPM Watts CFM RPM Watts Low -4821 No Heater 4 Ton 4 1535/1654 CFM [724/781 L/s] 10x10 3/4 HP [559] 5 Speed High RPM Watts CFM RPM Watts Low -4821 with 25 kW Heater 4 Ton 4 1495/1614 CFM [706/762 L/s] 10x10 3/4 HP [559] 2 Speed High RPM Watts CFM RPM Watts Low -4824 No Heater 4 Ton 4 1545/1732 CFM [729/817 L/s] 11x11 3/4 HP [559] 5 Speed High RPM Watts CFM RPM Watts Low -4824 with 25 kW Heater 4 Ton Low 240V 1505/1692 CFM [710/798 L/s] 11x11 3/4 HP [559] 5 Speed High RPM Watts CFM RPM Watts Low -6024 No Heater 5 Ton Low 240V 1739/1905 CFM [821/899 L/s] 11x11 3/4 HP [559] 5 Speed High RPM Watts CFM RPM Watts Low -6024 with 30 kW Heater 5 Ton Low 240V 1699/1865 CFM [802/880 L/s] 11x11 3/4 HP [559] 5 Speed High RPM Watts CFM RPM Watts

PSC CFM [L/s] Air Delivery/RPM/Watts--115/208/240 Volts External Static Pressure--Inches W.C. [kPa] 0.1 [.02]

781 257 -- -- -- 831 277 -- -- -- 853 351 -- -- -- 894 389 -- -- -- 660 297 -- -- -- 680 305 -- -- -- 712 389 -- -- -- 750 410 -- -- --

0.2 [.05]

825 271 -- -- -- 875 295 -- -- -- 893 387 -- -- -- 932 400 -- -- -- 698 311 -- -- -- 736 330 -- -- -- 749 409 -- -- -- 790 420 -- -- --

0.3 [.07]

867 303 -- -- -- 919 313 -- -- -- 934 401 -- -- -- 970 410 -- -- -- 734 326 -- -- -- 760 341 -- -- -- 787 419 -- -- -- 810 430 -- -- --

0.4 [.10]

905 307 -- -- -- 954 319 -- -- -- 968 406 -- -- -- 1020 430 -- -- -- 762 340 -- -- -- 790 350 -- -- -- 815 432 -- -- -- 850 455 -- -- --

0.5 [.12]

949 315 987 394 989 325 1011 350 1015 422 1036 500 1052 450 1085 514 795 353 840 448 820 361 865 460 856 459 894 565 880 479 920 565

0.6 [.15]

-- -- -- 1034 406 -- -- -- 1046 364 -- -- -- 1078 513 -- -- -- 1090 520 -- -- -- 872 467 -- -- -- 890 470 -- -- -- 924 570 -- -- -- 945 587

0.7 [.17]

-- -- -- 1065 405 -- -- -- 1080 377 -- -- -- 1095 523 -- -- -- 1105 530 -- -- -- 899 480 -- -- -- 1014 481 -- -- -- 950 592 -- -- -- 970 610

CFM 1473 [695] 1442 [681] 1401 [661] 1373 [648] 1337 [631]

1447 [683] 1433 [676] 1402 [662]

CFM 1433 [676] 1402 [662] 1361 [642] 1333 [629] 1297 [612]

1333 [629] 1300 [613] 1267 [598]

CFM 1665 [786] 1631 [770] 1601 [756] 1572 [742] 1535 [724]

1654 [781] 1624 [766] 1563 [738]

CFM 1625 [767] 1591 [751] 1561 [737] 1532 [723] 1495 [706]

1614 [762] 1584 [748] 1523 [719]

CFM 1748 [825] 1669 [788] 1639 [773] 1599 [755] 1545 [729]

1732 [817] 1683 [794] 1630 [769]

CFM 1708 [806] 1629 [769] 1599 [755] 1559 [736] 1505 [710]

1692 [798] 1643 [775] 1590 [750]

CFM 1902 [898] 1862 [879] 1809 [854] 1781 [840] 1739 [821]

1905 [899] 1866 [881] 1832 [865]

CFM 1862 [879] 1822 [860] 1769 [835] 1741 [822] 1699 [802]

1865 [880] 1826 [862] 1792 [846]

Notes: · The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. · The following formula can be used to calculation the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater ­ (Airflow without heater ­ Airflow with maximum heater) x (N kW/maximum heater kW)

[ ] Designates Metric Conversions

12

Rheem Manufacturing Company

RHSA/RHSL Electrical Data ­ Blower Motor Only ­ No Electric Heat

Cooling Capacity Tons 11/2 2 21/2 3 31/2 4 11/2 2 21/2 3 31/2 4 5 3 31/2 4 5 Voltage Application Phase* Hertz HP [W] 1/5 [149] 1/5 [149] 1/4 [186] 1/3 [249] 1/2 [373] 3/4 [559] 1/5 [149] 1/5 [149] 1/4 [186] 1/3 [249] 1/2 [373] 3/4 [559] 3/4 [559] 1/3 [249] 1/3 [249] 3/4 [559] 3/4 [559] RPM 1075 1075 1075 1075 1075 1075 1075 1075 1075 1075 1075 1075 1075 1075 1075 1075 1075 Speeds 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Circuit Amps. 2.3 3.8 4.7 6.1 7.9 8.4 1.7 1.7 2.5 2.5 5.2 5.2 5.2 1.4 2.1 2.2 2.2 Minimum Circuit Ampacity 3.0 5.0 6.0 8.0 10.0 11.0 3.0 3.0 4.0 4.0 7.0 7.0 7.0 2.0 3.0 3.0 3.0 Maximum Circuit Protector 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

115

1

60

208/240

1&3

60

208/240 480 480

3 3 3

60 60 60

* Blower motors are all single phase motors.

RHLA/RHLL Electrical Data ­ Blower Motor Only ­ No Electric Heat

Cooling Capacity Tons 11/2 & 2 21/2 & 3 31/2 & 4 5 11/2 & 2 21/2 & 3 31/2 & 4 5 Voltage Application Phase* Hertz HP [W] 1/3 [249] 1/2 [373] 3/4 [559] 3/4 [559] 1/3 [249] 1/2 [373] 3/4 [559] 3/4 [559] RPM 300-1100 300-1100 300-1100 300-1100 300-1100 300-1100 300-1100 300-1100 Speeds 4 4 4 4 4 4 4 4 Circuit Amps. 1.6 2.7 3.8 4.6 4.8 6.8 8.4 8.4 Minimum Circuit Ampacity 2.0 4.0 5.0 6.0 6.0 9.0 11.0 11.0 Maximum Circuit Protector 15 15 15 15 15 15 15 15

208/240

1&3

60

115

1

60

* Blower motors are all single phase motors.

[ ] Designates Metric Conversions

Rheem Manufacturing Company

13

RHSA/RHSL Electrical Data ­ with Electric Heat

Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all auxiliary heating requirements.

Nominal Cooling Capacity Tons/ Cabinet Size Rheem Model No. RXBH-17A03J RXBH-17A05J RXBH-17A07J RXBH-17A10J RXBH-17A13J RXBH-17A13J RXBH-17A07C RXBH-17A10C RXBH-17A13C RXBH-17A03J RXBH-17A05J RXBH-17A07J RXBH-17A10J RXBH-17A13J RXBH-17A13J RXBH-17A15J RXBH-17A15J 2 1/2 & 3/ 17 RXBH-17A18J RXBH-17A18J RXBH-17A07C RXBH-17A10C RXBH-17A13C RXBH-17A15C RXBH-17A18C RXBH-17A07D RXBH-17A10D RXBH-17A15D RXBH-17A18D RXBH-24A05J RXBH-24A07J RXBH-24A10J RXBH-24A15J RXBH-24A15J RXBH-24A18J 3/ 21 RXBH-24A18J RXBH-24A07C RXBH-24A10C RXBH-24A15C RXBH-24A18C RXBH-24A07D RXBH-24A10D RXBH-24A15D RXBH-24A18D Heater kW 208/240V. 2.25/3.0 3.6/4.8 5.4/7.2 7.2/9.6 9.4/12.5 3.1/4.2 6.3/8.3 5.4/7.2 7.2/9.6 9.4/12.5 2.25/3.0 3.6/4.8 5.4/7.2 7.2/9.6 9.4/12.5 3.1/4.2 6.3/8.3 10.8/14.4 3.6/4.8 7.2/9.6 12.8/17.0 4.3/5.7 8.5/11.3 5.4/7.2 7.2/9.6 9.4/12.5 10.8/14.4 12.8/17.0 7.2 9.6 14.4 17 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 3.6/4.8 7.2/9.6 12.8/17.0 6.4/8.5 6.4/8.5 5.4/7.2 7.2/9.6 10.8/14.4 12.8/17.0 7.2 9.6 14.4 17 PH/Hz 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 No. Elements kW Per 1 - 3.0 1 - 4.8 2 - 3.6 2 - 4.8 3-4.17 1-4.17 2-4.17 3 - 2.4 3 - 3.2 3 - 4.17 1 - 3.0 1 - 4.8 2 - 3.6 2 - 4.8 3-4.17 1-4.17 2-4.17 3-4.8 1 - 4.8 2 - 4.8 3-5.68 1-5.68 2 - 5.68 3 - 2.4 3 - 3.2 3 - 4.17 3 - 4.8 3-5.68 2-3.6 3 - 3.2 3 - 4.8 3 - 5.68 1 - 4.8 2 - 3.6 2 - 4.8 3-4.8 1 - 4.8 2 - 4.8 4-4.26 2 - 4.26 2 - 4.26 3 - 2.4 3 - 3.2 3 - 4.8 3-5.68 2-3.6 3 - 3.2 3 - 4.8 3 - 5.68 Circuit SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE Circuit Amps. 10.8/12.5 17.3/20.0 26.0/30.0 34.6/40.0 45.1/52.1 15.0/17.4 30.1/34.7 15.0/17.3 20.0/23.1 26.1/30.1 10.8/12.5 17.3/20.0 26.0/30.0 34.6/40.0 45.1/52.1 15.0/17.4 30.1/34.7 51.9/60.0 17.3/20.0 34.6/40.0 61.6/70.8 20.5/23.6 41.1/47.2 15.0/17.3 20.0/23.1 26.1/30.1 30.0/34.6 35.5/41.0 8.7 11.6 17.3 20.4 17.3/20.0 26.0/30.0 34.6/40.0 51.9/60.0 17.3/20.0 34.6/40.0 61.6/70.8 30.8/35.4 30.8/35.4 15.0/17.3 20.0/23.1 30.0/34.6 35.5/41.0 8.7 11.6 17.3 20.4 Motor Ampacity 1.7 1.7 1.7 1.7 1.7 1.7 0 1.7 1.7 1.7 2.5 2.5 2.5 2.5 2.5 2.5 0 2.5 2.5 0 2.5 2.5 0 2.5 2.5 2.5 2.5 2.5 1.4 1.4 1.4 1.4 2.5 2.5 2.5 2.5 2.5 0 2.5 2.5 0 2.5 2.5 2.5 2.5 1.4 1.4 1.4 1.4 Minimum Circuit Ampacity 16/18 24/28 35/40 46/53 59/68 21/24 38/44 21/24 28/31 35/40 17/19 25/29 36/41 47/54 60/69 22/25 38/44 68/79 25/29 44/50 81/92 29/33 52/59 22/25 29/32 36/41 41/47 48/55 13 17 24 28 25/29 36/41 47/54 68/79 25/29 44/50 81/92 42/48 39/45 22/25 29/32 41/47 48/55 13 17 24 28 Maximum Circuit Protection 20/20 25/30 35/40 50/60 60/70 25/25 40/45 25/25 30/35 35/40 20/20 25/30 40/45 50/60 60/70 25/25 40/45 70/80 25/30 45/50 90/100 30/35 60/60 25/25 30/35 40/45 45/50 50/60 15 20 25 30 25/30 40/45 50/60 70/80 25/30 45/50 90/100 45/50 40/45 25/25 30/35 45/50 50/60 15 20 25 30

1 1/2 & 2/ 17

· Supply circuit protective devices may be fused or "HACR" type circuit breakers. · If non-standard fuse size is specified, use next size larger standard fuse size. · If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details. · Largest motor load is included in single circuit or circuit 1 of multiple circuit. · Heater loads are balanced on 3 PH. models with 3 or 6 heaters only. · Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)

· No electrical heating elements are permitted to be used with A voltage (115V) air handler. · J voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3 phase power to air handler terminal block without the heater, bring only two leads to terminal block. Cap, insulate and fully secure the third lead. · Do not use 480 volts electrical heaters on 230 volts air handlers. · Do not use 230 volts electrical heaters on 480 volts air handlers.

14

Rheem Manufacturing Company

RHSA/RHSL Electrical Data ­ with Electric Heat (con't.)

Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all auxiliary heating requirements.

Nominal Cooling Capacity Tons/ Cabinet Size Model No. RXBH-24A05J RXBH-24A07J RXBH-24A10J RXBH-24A15J RXBH-24A15J RXBH-24A18J RXBH-24A18J RXBH-24A20J RXBH-24A20J RXBH-24A25J RXBH-24A25J (4-ton only) RXBH-24A07C RXBH-24A10C RXBH-24A15C RXBH-24A18C RXBH-24A20C RXBH-24A20C RXBH-24A25C RXBH-24A25C (4-ton only) RXBH-24A07D RXBH-24A10D RXBH-24A15D RXBH-24A18D RXBH-24A20D RXBH-24A25D (4-ton only) RXBH-24A07C RXBH-24A10C RXBH-24A15C RXBH-24A18C RXBH-24A20C RXBH-24A20C RXBH-24A25C 5/ 24 RXBH-24A25C RXBH-24A30C RXBH-24A30C RXBH-24A07D RXBH-24A10D RXBH-24A15D RXBH-24A18D RXBH-24A20D RXBH-24A25D RXBH-24A30D Heater kW 208/240V. 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 3.6/4.8 7.2/9.6 12.8/17 6.4/8.5 6.4/8.5 14.4/19.2 7.2/9.6 7.2/9.6 18.0/24.0 6.0/8.0 6.0/8.0 6.0/8.0 5.4/7.2 7.2/9.6 10.8/14.4 12.8/17.0 14.4/19.2 7.2/9.6 7.2/9.6 18.0/24.0 9.0/12.0 9.0/12.0 7.2 9.6 14.4 17 19.2 24.0 5.4/7.2 7.2/9.6 10.8/14.4 12.8/17.0 14.4/19.2 7.2/9.6 7.2/9.6 18.0/24.0 9.0/12.0 9.0/12.0 21.6/28.8 10.8/14.4 10.8/14.4 7.2 9.6 14.4 17 19.2 24.0 28.8 PH/Hz 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 No. Elements kW Per 1 - 4.8 2 - 3.6 2 - 4.8 3-4.8 1 - 4.8 2 - 4.8 4-4.26 2 - 4.26 2 - 4.26 4-4.8 2 - 4.8 2 - 4.8 6-4.0 2 - 4.0 2 - 4.0 2 - 4.0 3 - 2.4 3 - 3.2 3 - 4.8 3-2.84 3-3.2 3 - 3.2 3 - 3.2 6-4.0 3 - 4.0 3 - 4.0 2-3.6 3 - 3.2 3 - 4.8 3 - 5.68 6 - 3.2 6 - 4.0 3 - 2.4 3 - 3.2 3 - 4.8 3-2.84 3-3.2 3 - 3.2 3 - 3.2 6-4.0 3 - 4.0 3 - 4.0 6-4.8 3 - 4.8 3 - 4.8 2-3.6 3 - 3.2 3 - 4.8 3 - 5.68 6 - 3.2 6 - 4.0 6 - 4.8 Circuit SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 MULTIPLE CKT 3 SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE Circuit Amps. 17.3/20.0 26.0/30.0 34.6/40.0 51.9/60.0 17.3/20.0 34.6/40.0 61.6/70.8 30.8/35.4 30.8/35.4 69.2/80 34.6/40.0 34.6/40.0 86.4/99.9 28.8/33.3 28.8/33.3 28.8/33.3 15.0/17.3 20.0/23.1 30.0/34.6 35.6/41.0 40.0/46.2 20.0/23.1 20.0/23.1 50.0/57.8 25.0/28.9 25.0/28.9 8.7 11.6 17.3 20.4 23.2 28.8 15.0/17.3 20.0/23.1 30.0/34.6 35.6/41.0 40.0/46.2 20.0/23.1 20.0/23.1 50.0/57.8 25.0/28.9 25.0/28.9 60.0/69.4 30.0/34.7 30.0/34.7 8.7 11.6 17.3 20.4 23.2 28.8 34.6 Motor Ampacity 4.0 4.0 4.0 4.0 4.0 0.0 4.0 4.0 0.0 4.0 4.0 0.0 4.0 4.0 0.0 0.0 4.0 4.0 4.0 4.0 4.0 4.0 0.0 4.0 4.0 0.0 2.2 2.2 2.2 2.2 2.2 2.2 4.4 4.4 4.4 4.4 4.4 4.4 0 4.4 4.4 0 4.4 4.4 0 2.2 2.2 2.2 2.2 2.2 2.2 2.2 Minimum Circuit Ampacity 27/30 38/43 49/55 70/80 27/30 44/50 82/94 44/50 39/45 92/105 49/55 44/50 113/130 42/47 36/42 36/42 24/27 30/34 43/49 50/57 55/63 30/34 25/29 68/78 37/42 32/37 14 18 25 29 32 39 25/28 31/35 43/49 50/57 56/64 31/35 25/29 68/78 37/42 32/37 81/93 43/49 38/44 14 18 25 29 32 39 46 Maximum Circuit Protection 30/30 40/45 50/60 70/80 30/30 45/50 90/100 45/50 40/45 100/110 50/60 45/50 125/150 45/50 40/45 40/45 25/30 30/35 45/50 50/60 60/70 30/35 25/30 70/80 40/45 35/40 15 20 25 30 35 40 25/30 35/35 45/50 50/60 60/70 35/35 25/30 70/80 40/45 35/40 90/100 45/50 40/45 15 20 25 30 35 40 50

3 1/2 & 4/ 21 and 4/ 24

· Supply circuit protective devices may be fused or "HACR" type circuit breakers. · If non-standard fuse size is specified, use next size larger standard fuse size. · If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details. · Largest motor load is included in single circuit or circuit 1 of multiple circuit. · Heater loads are balanced on 3 PH. models with 3 or 6 heaters only. · Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)

· No electrical heating elements are permitted to be used with A voltage (115V) air handler. · J voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3 phase power to air handler terminal block without the heater, bring only two leads to terminal block. Cap, insulate and fully secure the third lead. · Do not use 480 volts electrical heaters on 230 volts air handlers. · Do not use 230 volts electrical heaters on 480 volts air handlers.

Rheem Manufacturing Company

15

RHLA/RHLL Electrical Data ­ with Electric Heat

Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all auxiliary heating requirements.

Nominal Cooling Capacity Tons/ Cabinet Size Rheem Model No. RXBH-17A03J RXBH-17A05J RXBH-17A07J RXBH-17A10J RXBH-17A13J RXBH-17A13J RXBH-17A07C RXBH-17A10C RXBH-17A13C RXBH-17A03J RXBH-17A05J RXBH-17A07J RXBH-17A10J RXBH-17A13J RXBH-17A13J RXBH-17A15J 21/2 & 3/ 17 RXBH-17A15J RXBH-17A18J RXBH-17A18J RXBH-17A07C RXBH-17A10C RXBH-17A13C RXBH-17A15C RXBH-17A18C RXBH-24A05J RXBH-24A07J RXBH-24A10J RXBH-24A15J RXBH-24A15J RXBH-24A18J RXBH-24A18J RXBH-24A20J RXBH-24A20J 31/2 & 4/ 21 RXBH-24A25J RXBH-24A25J (4-ton only) RXBH-24A07C RXBH-24A10C RXBH-24A15C RXBH-24A18C RXBH-24A20C RXBH-24A20C RXBH-24A25C RXBH-24A25C (4-ton only) Heater KW 208/240V 2.25/3.0 3.6/4.8 5.4/7.2 7.2/9.6 9.4/12.5 3.1/4.2 6.3/8.3 5.4/7.2 7.2/9.6 9.4/12.5 2.25/3.0 3.6/4.8 5.4/7.2 7.2/9.6 9.4/12.5 3.1/4.2 6.3/8.3 10.8/14.4 3.6/4.8 7.2/9.6 12.8/17.0 4.3/5.7 8.5/11.3 5.4/7.2 7.2/9.6 9.4/12.5 10.8/14.4 12.8/17.0 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 3.6/4.8 7.2/9.6 12.8/17 6.4/8.5 6.4/8.5 14.4/19.2 7.2/9.6 7.2/9.6 18.0/24.0 6.0/8.0 6.0/8.0 6.0/8.0 5.4/7.2 7.2/9.6 10.8/14.4 12.8/17.0 14.4/19.2 7.2/9.6 7.2/9.6 18.0/24.0 9.0/12.0 9.0/12.0 PH/HZ 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 3/60 3/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 No. Elements KW Per 1 - 3.0 1 - 4.8 2 - 3.6 2 - 4.8 3-4.17 1-4.17 2-4.17 3 - 2.4 3 - 3.2 3 - 4.17 1 - 3.0 1 - 4.8 2 - 3.6 2 - 4.8 3-4.17 1-4.17 2-4.17 3-4.8 1 - 4.8 2 - 4.8 3-5.68 1-5.68 2 - 5.68 3 - 2.4 3 - 3.2 3 - 4.17 3 - 4.8 3-5.68 1 - 4.8 2 - 3.6 2 - 4.8 3-4.8 1 - 4.8 2 - 4.8 4-4.26 2 - 4.26 2 - 4.26 4-4.8 2 - 4.8 2 - 4.8 6-4.0 2 - 4.0 2 - 4.0 2 - 4.0 3 - 2.4 3 - 3.2 3 - 4.8 3-2.84 3-3.2 3 - 3.2 3 - 3.2 6-4.0 3 - 4.0 3 - 4.0 Type Supply Circuit Single Circuit Multiple Circuit SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 MULTIPLE CKT 3 SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 Circuit Amps. 10.8/12.5 17.3/20.0 26.0/30.0 34.6/40.0 45.1/52.1 15.0/17.4 30.1/34.7 15.0/17.3 20.0/23.1 26.1/30.1 10.8/12.5 17.3/20.0 26.0/30.0 34.6/40.0 45.1/52.1 15.0/17.4 30.1/34.7 51.9/60.0 17.3/20.0 34.6/40.0 61.6/70.8 20.5/23.6 41.1/47.2 15.0/17.3 20.0/23.1 26.1/30.1 30.0/34.6 35.5/41.0 17.3/20.0 26.0/30.0 34.6/40.0 51.9/60.0 17.3/20.0 34.6/40.0 61.6/70.8 30.8/35.4 30.8/35.4 69.2/80 34.6/40.0 34.6/40.0 86.4/99.9 28.8/33.3 28.8/33.3 28.8/33.3 15.0/17.3 20.0/23.1 30.0/34.6 35.6/41.0 40.0/46.2 20.0/23.1 20.0/23.1 50.0/57.8 25.0/28.9 25.0/28.9 Motor Ampacity 1.6 1.6 1.6 1.6 1.6 1.6 0 1.6 1.6 1.6 2.7 2.7 2.7 2.7 2.7 2.7 0 2.7 2.7 0 2.7 2.7 0 2.7 2.7 2.7 2.7 2.7 3.8 3.8 3.8 3.8 3.8 0.0 3.8 3.8 0.0 3.8 3.8 0.0 3.8 3.8 0.0 0.0 3.8 3.8 3.8 3.8 3.8 3.8 0.0 3.8 3.8 0.0 Minimum Circuit Ampacity 16/18 24/27 35/40 46/52 59/68 21/24 38/44 21/24 27/31 35/40 17/19 25/29 36/41 47/54 60/69 23/26 38/44 69/79 25/29 44/50 81/92 29/33 52/59 23/25 29/33 36/41 41/47 48/55 27/30 38/43 48/55 70/80 27/30 44/50 82/94 44/49 39/45 92/105 48/55 44/50 113/130 41/47 36/42 36/42 24/27 30/34 43/48 50/56 55/63 30/34 25/29 68/77 36/41 32/37 Maximum Circuit Protection 20/20 25/30 35/40 50/60 60/70 25/25 40/45 25/25 30/35 35/40 20/20 25/30 40/45 50/60 60/70 25/30 40/45 70/80 25/30 45/50 90/100 30/35 60/60 25/25 30/35 40/45 45/50 50/60 30/30 40/45 50/60 70/80 30/30 45/50 90/100 45/50 40/45 100/110 50/60 45/50 125/150 45/50 40/45 40/45 25/30 30/35 45/50 50/60 60/70 30/35 25/30 70/80 40/45 35/40

11/2 & 2/ 17

· Supply circuit protective devices may be fused or "HACR" type circuit breakers. · If non-standard fuse size is specified, use next size larger standard fuse size. · If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details. · Largest motor load is included in single circuit or circuit 1 of multiple circuit. · Heater loads are balanced on 3 PH. models with 3 or 6 heaters only. · Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)

· No electrical heating elements are permitted to be used with A voltage (115V) air handler. · J voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3 phase power to air handler terminal block without the heater, bring only two leads to terminal block. Cap, insulate and fully secure the third lead. · Do not use 480 volts electrical heaters on 230 volts air handlers. · Do not use 230 volts electrical heaters on 480 volts air handlers.

16

Rheem Manufacturing Company

RHLA/RHLL Electrical Data ­ with Electric Heat (con't.)

Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all auxiliary heating requirements.

Nominal Cooling Capacity Tons/ Cabinet Size Rheem Model No. RXBH-24A07J RXBH-24A10J RXBH-24A15J RXBH-24A15J RXBH-24A18J RXBH-24A18J RXBH-24A20J RXBH-24A20J RXBH-24A25J RXBH-24A25J 4 & 5/ 24 RXBH-24A30J RXBH-24A30J (5-ton only) RXBH-24A07C RXBH-24A10C RXBH-24A15C RXBH-24A18C RXBH-24A20C RXBH-24A20C RXBH-24A25C RXBH-24A25C RXBH-24A30C RXBH-24A30C (5-ton only) Heater KW 208/240V 5.4/7.2 7.2/9.6 10.8/14.4 3.6/4.8 7.2/9.6 12.8/17 6.4/8.5 6.4/8.5 14.4/19.2 7.2/9.6 7.2/9.6 18.0/24.0 6.0/8.0 6.0/8.0 6.0/8.0 21.6/28.8 7.2/9.6 7.2/9.6 7.2/9.6 5.4/7.2 7.2/9.6 10.8/14.4 12.8/17.0 14.4/19.2 7.2/9.6 7.2/9.6 18.0/24.0 9.0/12.0 9.0/12.0 21.6/28.8 10.8/14.4 10.8/14.4 PH/HZ 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 No. Elements KW Per 2 - 3.6 2 - 4.8 3-4.8 1 - 4.8 2 - 4.8 4-4.26 2 - 4.26 2 - 4.26 4-4.8 2 - 4.8 2 - 4.8 6-4.0 2 - 4.0 2 - 4.0 2 - 4.0 6-4.8 2 - 4.8 2 - 4.8 2 - 4.8 3 - 2.4 3 - 3.2 3 - 4.8 3-2.84 3-3.2 3 - 3.2 3 - 3.2 6-4.0 3 - 4.0 3 - 4.0 6-4.8 3 - 4.8 3 - 4.8 Type Supply Circuit Single Circuit Multiple Circuit SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 MULTIPLE CKT 3 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 MULTIPLE CKT 3 SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 Circuit Amps. 26.0/30.0 34.6/40.0 51.9/60.0 17.3/20.0 34.6/40.0 61.6/70.8 30.8/35.4 30.8/35.4 69.2/80 34.6/40.0 34.6/40.0 86.4/99.9 28.8/33.3 28.8/33.3 28.8/33.3 103.8/120. 34.6/40.0 34.6/40.0 34.6/40.0 15.0/17.3 20.0/23.1 30.0/34.6 35.6/41.0 40.0/46.2 20.0/23.1 20.0/23.1 50.0/57.8 25.0/28.9 25.0/28.9 60.0/69.4 30.0/34.7 30.0/34.7 Motor Ampacity 4.6 4.6 4.6 4.6 0 4.6 4.6 0 4.6 4.6 0 4.6 4.6 0 0 4.6 4.6 0 0 4.6 4.6 4.6 4.6 4.6 4.6 0 4.6 4.6 0 4.6 4.6 0 Minimum Circuit Ampacity 39/44 49/56 71/81 28/31 44/50 83/95 45/50 39/45 93/106 49/56 44/50 114/131 42/48 36/42 36/42 136/156 49/56 44/50 44/50 25/28 31/35 44/49 51/57 56/64 31/35 25/29 69/78 37/42 32/37 81/93 44/50 38/44 Maximum Circuit Protection 40/45 50/60 80/90 30/35 45/50 90/100 45/50 40/45 100/110 50/60 45/50 125/150 45/50 40/45 40/45 150/175 50/60 45/50 45/50 25/30 35/35 45/50 60/60 60/70 35/35 25/30 70/80 40/45 35/40 90/100 45/50 40/45

· Supply circuit protective devices may be fused or "HACR" type circuit breakers. · If non-standard fuse size is specified, use next size larger standard fuse size. · If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details. · Largest motor load is included in single circuit or circuit 1 of multiple circuit. · Heater loads are balanced on 3 PH. models with 3 or 6 heaters only. · Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)

· No electrical heating elements are permitted to be used with A voltage (115V) air handler. · J voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3 phase power to air handler terminal block without the heater, bring only two leads to terminal block. Cap, insulate and fully secure the third lead. · Do not use 480 volts electrical heaters on 230 volts air handlers. · Do not use 230 volts electrical heaters on 480 volts air handlers.

Rheem Manufacturing Company

17

Electrical Wiring:

Power Wiring · Field wiring must comply with the National Electrical Code (C.E.C. in Canada) and any applicable local ordinance. · Supply wiring must be 75°C minimum copper conductors only. · See electrical data for product Ampacity rating and Circuit Protector requirement. Grounding · This product must be sufficiently grounded in accordance with National Electrical Code (C.E.C. in Canada) and any applicable local ordinance. · A grounding lug is provided.

Accessories-Kits--Parts

· Combustible Floor Base RXHBModel Cabinet Size 17 21 24 Combustible Floor Base Model Number RXHB-17 RXHB-21 RXHB-24

· Auxiliary Electric Heater Kits RXBHHeater Kits include circuit breakers which meet UL and cUL requirements for service disconnect. See the Electric Heat Electrical Data in this specification sheet for specific Heater Kit Model numbers. · Horizontal Adapter Kit RXHHThis horizontal adapter kit is used to convert Upflow/Downflow only models to horizontal flow. See the following table to order proper horizontal adapter kit.

Coil Model 2414 2417 3617/3621 4821/4824 8024 Horizontal Adapter Kit Model Number (Single Qty.) RXHH-A01 RXHH-A02 RXHH-A03 RXHH-A04 RXHH-A05 Horizontal Adapter Kit Model Number (10-Pack Qty.) RXHH-A01 x 10 RXHH-A02 x 10 RXHH-A03 x 10 RXHH-A04 x 10 RXHH-A05 x 10

· Jumper Bar Kit 3 Ckt. to 1 Ckt. RXBJ-A31 is used to convert single phase multiple three circuit units to a single supply circuit. Kit includes cover and screw for line side terminals. · Jumper Bar Kit 2 Ckt. to 1 Ckt. RXBJ-A21 is used to convert single phase multiple two circuit units to a single supply circuit. Kit includes cover and screw for line side terminals. · Note: No jumper bar kit is available to convert three phase multiple two circuit units to a single supply circuit. · Auxiliary Horizontal Overflow Pan Accessory RXBMNominal Cooling Capacity-Tons 11/2 - 3 31/2 - 5 Auxiliary Horizontal Overflow Pan Accessory Model Number RXBM-AC48 RXBM-AC61

· External Filter Base RXHFModel Cabinet Size 17 21 24 Filter Size In. [mm] 16 x 20 [406 x 508] 20 x 20 [508 x 508] 25 x 20 [635 x 508] Part Number* RXHF-17 RXHF-21 RXHF-24 A 15.70 19.20 22.70 B 17.5 21.0 25.5

· External Filter Rack RXHF-B17, B21, B24

Model Cabinet Size 17 21 24 Filter Size In. [mm] 16 x 20 [406 x 508] 20 x 20 [508 x 508] 25 x 20 [635 x 508] Part Number* RXHF-B17 RXHF-B21 RXHF-B24 A 16.90 20.40 25.00 B 20.77 20.77 21.04

*Accommodates 1" or 2" filter [ ] Designates Metric Conversions

*Accommodates 1" filter

RXHF-B

11/2 [38 mm]

RXHF-

B B

A A

18

Rheem Manufacturing Company

NOTES

Rheem Manufacturing Company

19

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.

RHEEM AIR CONDITIONING DIVISION

5600 Old Greenwood Road, Fort Smith, Arkansas 72908

"In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice."

PRINTED IN U.S.A. 3-07 DC FORM NO. H11-524 REV. 3

Supersedes Form N o . H 11 - 5 2 4 R e v. 2

Information

H11-524 Rev. 3 Rheem RHSA, RHSL, RHLA, RHLL Air Handler Specification Sheets

20 pages

Find more like this

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

255166


You might also be interested in

BETA
RT-PRC001-EN 07/04
20536913
SECTION 00000 - COVER
PT-DW730 Series - PT-DW730US/DX800US