PF4MNB DIRECT EXPANSION FAN COIL FOR R- 410A REFRIGERANT SIZES 019 THRU 061

Product Data

FEATURES/BENEFITS

AVAILABLE SIZES:

18,000 to 60,000 BTU unit, 1.5 to 5.0 ton unit

ELECTRICAL RANGE:

40-va, 208/230- transformer, 60 Hz, 1 Phase. -v

FAN MOTOR:

All unit designs incorporate integrated operational controls within the high efficiency X- electronic commutating motor (ECM). -13

CABINET:

The attractive, prepainted, galvanized steel casing offers rust protection for many years. All units have high-density insulation. These units are designed with a factory-supplied power plug. For easy cleaning, all units contain a factory-supplied, cleanable, framed filter.

COIL DESIGN:

The 019 through 031 sizes are slope coil units. The 037 through 061 sizes are "A" coil units. All models feature the components you need and expect, such as grooved copper tubing and lanced sine-wave aluminum fin. All units include fully-wettable coils, sweat-type refrigerant connections, and factory-washed coils for improved condensate control.

DRAIN PAN:

These units are designed with a high-impact thermoplastic condensate pan. All drain connections (primary and secondary) have been designed to ensure proper condensate drainage, limiting the amount of standing water.

CONTROLS:

Every unit comes fully equipped with cooling controls including 40- transformer and integrated fan control with time-va -delay relay (TDR). These units accommodate field-installed heater packages from 3- to 30-kW (fused, circuit breaker, or non-fused). All units include a factory-supplied power plug.

INSTALLATION:

Units are factory shipped for upflow or horizontal left discharge. Units can be field converted to horizontal right discharge. These units are field convertible to downflow with an accessory kit.

SERVICEABILITY:

A10097

All units are designed with a factory-installed bi-flow, hard-shutoff refrigerant specific TXV.

MODEL NUMBER NOMENCLATURE

PAYNE FAN COILS

1 P Product Type Fan Coil, Multipoise with R-410A Electrical N - 208/230v, 1 ph, 60 Hz Series B 2 F 3 4 4 M 5 N 6 B 7 0 8 1 9 9 10 0 11 0 12 0

Coil Coating

000 = No Heat T00 = Tin--- plate

Capacity

019 = 18,000 025 = 24,000 031 = 30,000 037 = 36,000 043 = 42,000 049 = 48,000 061 = 60,000

PF4MNB

ISO 9001:2000

Use of the AHRI Certified TM Mark indicates a manufacturer's participation in the program For verification of certification for individual products, go to www.ahridirectory.org.

REGISTERED

2

DIMENSIONS

UNIT PF4MNB019 PF4MNB025 PF4MNB031 PF4MNB037 PF4MNB043 PF4MNB049 PF4MNB061

NOTE: 1. SERIES DESIGNATION IS THE 14TH POSITION OF UNIT PRODUCT NUMBER 2. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED.

SERIES A A A A A A A

A 49 5/8" 49 5/8" 53 7/16" 49 5/8" 49 5/8" 53 7/16" 59 3/16"

B 17 5/8" 17 5/8" 21 1/8" 21 1/8" 21 1/8" 24 11/16" 24 11/16"

C 15 3/4" 15 3/4" 19 1/4" 19 1/4" 19 1/4" 22 3/4" 22 3/4"

D 15 5/8" 15 5/8" 19 1/8" 19 1/8" 19 1/8" 22 11/16" 22 11/16"

E 15 3/8" 15 3/8" 19 3/16" 15 11/16" 15 11/16" 19 1/2" 25 1/4"

F 23 1/8" 23 1/8" 26 15/16" 23 7/16" 23 7/16" 27 1/4" 32 15/16"

G 23 5/8" 23 5/8" 27 1/2" 23 1/8" 23 1/8" 26 15/16" 32 5/8" -

H

J 19" 19" -

COIL CONFIGURATION

SLOPE X X X -

"A" X X X X

SHIPPING WT (LBS) NON TIN-COATED 122 122 146 157 157 185 201

SHIPPING WT (LBS) TIN-COATED 122 122 146 157 157 185 201

28 5/16" 34 1/16"

NOTE: ALLOW 21" FROM FRONT FOR SERVICE

UNIT CONNECTION SIZES

SUCTION: 018 THRU 025 - 5/8" I.D. SWEAT 030 THRU 037 - 3/4" I.D. SWEAT 042 THRU 061 - 7/8" I.D. SWEAT LIQUID: 3/8" I.D. SWEAT CONDENSATE: 3/4" FPT

22 1/16" 10 3/16" 2 1/8" 1" 11" OUTLET AIR 7/8"

7/8", 1 3/32" 2" DIA. K.O.'S FOR HIGH VOLTAGE POWER WIRING 1 7/8"

ALTERNATE 7/8"DIA. K.O. FOR LOW VOLTAGE CONTROL WIRING

ALTERNATE 7/8",1 3/32",2"DIA. FOR HIGH VOLTAGE POWER WIRING OPPOSITE SIDE

K.O.'S

NOTE: MODULAR UNITS WILL HAVE A TWO-PIECE CABINET

7/8"DIA. K.O. FOR LOW VOLTAGE CONTROL WIRING

A

OPTIONAL FIELD CONVERTED RIGHT SIDE RETURN OPENING (SLOPE COIL UNITS ONLY) 1 1/2"

1 15/16"

1" 1 3/8"

TOP VIEW

1 3/16"

J

MAX 19"

H

15/16"

B C

DISCONNECT OR CIRCUIT BREAKER LOCATION BLOWER, CONTROL, & ELECTRIC HEATER ACCESS PANEL 1 3/4"

FOR MODULAR UNITS

1 1/4"

OPENING 19 13/16"

RIGHT SIDE VIEW

INLET AIR COIL ACCESS PANEL

2 1/2"

INLET AIR

2 5/8" 4 11/16" FITTING PANEL LIQUID LINE CONNECTION SUCTION LINE CONNECTION 3 1/16" LIQUID LINE CONNECTION

E

LIQUID LINE CONNECTION

10 7/16" 10 3/4" 6 3/16" 9 1/2" SUCTION LINE CONNECTION

5" OPENING 1"

FILTER ACCESS PANEL

D

INLET AIR

SLOPE COIL DETAILS

ACCESS PANEL CONFIG. FOR DOWNFLOW OR HORIZ. RIGHT APPLICATIONS AND DOWNFLOW APPLICATIONS

SHOWN WITH "A" COIL DETAILS CONNECTION LOCATIONS FOR UPFLOW OR HORIZ. APPLICATIONS

FRONT VIEW

CONNECTION LOCATIONS SHOWN FOR UPFLOW OR HORIZ. LEFT APPLICATIONS

SLOPE COILS "A" COILS

A10014

Fig. 1 - PF4MNB - English -

3

PF4MNB

3/4"

DIMENSIONS (cont.)

NOTES: 1. CONDENSATE PAN DRAIN CAPS NOT SHOWN FOR CLARITY. 2. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED. AIRFLOW 2 3/16" TYP. (2 PLACES)* AIRFLOW 7/16" TYP. (2 PLACES)*

SLOPE COIL

3 1/4"

F

1 1/4"

G

PRIMARY DRAIN SECONDARY DRAIN

1" TYP. (2 PLACES)*

SECONDARY DRAIN

PRIMARY DRAIN 2 7/8"

PF4MNB

1" TYP. (2 PLACES)*

7/16" TYP. (4 PLACES)* 1 1/4"

DOWNFLOW (FIELD CONVERTED)

PRIMARY DRAIN SECONDARY DRAIN 5/16" TYP.*

2 9/16"

2 3/16" TYP. (2 PLACES)*

3 1/4"

UPFLOW (AS SHIPPED)

PRIMARY DRAIN SECONDARY DRAIN

1 13/16" TYP.*

1 5/8"

1 1/4" 5/16" TYP.* 5/16" TYP.*

2 1/8" 1 13/16" TYP.

1 1/4"

1/2" TYP.*

F HORIZ. RIGHT (FIELD CONVERTED)

7/8" TYP.*

1/2" TYP.* 7/8" TYP.*

1 5/8" 2 7/8"

HORIZ. LEFT (AS SHIPPED)

5"

* HORIZONTAL MOUNT LOCATIONS - DIMPLES PROVIDED IN TOP PANEL, AND BACK OF CABINET. IN CABINET BOTTOM. HOLES PROVIDED

A-COIL

PRIMARY DRAIN SECONDARY DRAIN 1 13/16" TYP*

AIRFLOW

2 3/16" TYP. (2 PLACES)* 1/2" TYP* 1 1/2" 1 3/16" 7 7/8" 5/16" TYP*

AIRFLOW

7/16" TYP. (4 PLACES)

5 7/8"

F

4 3/4" 3 1/16"

G

7/8" TYP*

1" TYP. (2 PLACES) SECONDARY DRAIN PRIMARY DRAIN

SECONDARY DRAIN

HORIZ. LEFT (AS SHIPPED)

PRIMARY DRAIN

PRIMARY DRAIN

5/16" TYP.*

SECONDARY DRAIN

1" TYP. (2 PLACES)* 3" 1/8 1 1/2" 3 1/16" 5 7/8" 7 7/8" 1 13/16" TYP. 1 3/16" 1/2" TYP.* 7/8" TYP.* 2 3/16" TYP. (2 PLACES)* 4 3/4" 2 11/16"

7/16" TYP, (4 PLACES)*

DOWNFLOW (FIELD CONVERTED)

HORIZ. RIGHT (FIELD CONVERTED)

UPFLOW (AS SHIPPED)

A10015

Fig. 2 - PF4MNB - English -

4

DIMENSIONS (cont.)

UNIT SERIES

A 1260.5 1260.5 1357.3 1260.5 1260.5 1357.3 1503.4

B 447.7 447.7 536.6 536.6 536.6 627.1 627.1

C 400.0 400.0 489.0 489.0 489.0 577.8 577.8

D 396.9 396.9 485.8 485.8 485.8 576.3 576.3

E 390.5 390.5 487.4 398.5 398.5 495.3 641.4

F 587.4 587.4 684.2 595.3 595.3 692.2 836.6

G 600.1 600.1 698.5 587.4 587.4 684.2 828.7 -

H

J 482.6 482.6 -

COIL CONFIGURATION

SLOPE

"A"

SHIPPING WT (Kgs) NON TIN-COATED

SHIPPING WT (Kgs) TIN-COATED

PF4MNB019 PF4MNB025 PF4MNB031 PF4MNB037 PF4MNB043 PF4MNB049 PF4MNB061 NOTE:

A A A A A A A

X X X -

X X X X

55.3 55.3 66.2 71.2 71.2 84.1 91.2

55.3 55.3 66.2 71.2 71.2 84.1 91.2

719.2 865.2

1. SERIES DESIGNATION IS THE 14TH POSITION OF UNIT PRODUCT NUMBER 2. ALL DIMENSIONS ARE IN "MM" UNLESS NOTED.

NOTE: ALLOW 533.4 FROM FRONT FOR SERVICE

560.4

UNIT CONNECTION SIZES

SUCTION: 018 THRU 025 - 15.88 I.D. SWEAT 030 THRU 037 - 19.05 I.D. SWEAT 042 THRU 061 - 22.23 I.D. SWEAT LIQUID: 9.53 I.D. SWEAT CONDENSATE: 19.0 FPT 54.0

258.8 25.4

279.4 OUTLET AIR

22.2 19.0

ALTERNATE 22.23 DIA. K.O. FOR LOW VOLTAGE CONTROL WIRING

ALTERNATE 22.23, 27.78, 50.80 DIA. K.O.'S FOR HIGH VOLTAGE POWER WIRING OPPOSITE SIDE

NOTE: MODULAR UNITS WILL HAVE A TWO-PIECE CABINET

A

22.23, 27.78 50.80 DIA. K.O.'S FOR HIGH VOLTAGE POWER WIRING 47.6

OPTIONAL FIELD CONVERTED RIGHT SIDE RETURN OPENING (SLOPE COIL UNITS ONLY) 38.1

22.23 DIA. K.O. FOR LOW VOLTAGE CONTROL WIRING 30.2

J

MAX 482.6

H

49.2

25.4 34.9

FOR MODULAR UNITS

TOP VIEW

44.4

23.8

B C

DISCONNECT OR CIRCUIT BREAKER LOCATION BLOWER, CONTROL, & ELECTRIC HEATER ACCESS PANEL

31.8

OPENING 503.2

RIGHT SIDE VIEW

INLET AIR

63.5

COIL ACCESS PANEL

INLET AIR

66.7 119.1 FITTING PANEL LIQUID LINE CONNECTION SUCTION LINE CONNECTION 77.8 LIQUID LINE CONNECTION

E

LIQUID LINE CONNECTION

265.1 273.0 157.2 241.3 SUCTION LINE CONNECTION

127.0 OPENING 25.4

FILTER ACCESS PANEL

D

SLOPE COIL DETAILS

ACCESS PANEL CONFIG. FOR DOWNFLOW OR HORIZ. RIGHT APPLICATIONS AND DOWNFLOW APPLICATIONS

INLET AIR

SHOWN WITH "A" COIL DETAILS CONNECTION LOCATIONS FOR UPFLOW OR HORIZ. APPLICATIONS

FRONT VIEW

CONNECTION LOCATIONS SHOWN FOR UPFLOW OR HORIZ. LEFT APPLICATIONS

SLOPE COILS "A" COILS

A10016

Fig. 3 - PF4MNB - Metric -

5

PF4MNB

DIMENSIONS (cont.)

NOTES: 1. CONDENSATE PAN DRAIN CAPS NOT SHOWN FOR CLARITY. 2. ALL DIMENSIONS ARE IN "MM" UNLESS NOTED. AIRFLOW

SLOPE COIL

AIRFLOW 55.6 TYP. (2 PLACES)*

11.1 TYP. (2 PLACES)*

82.6

PRIMARY DRAIN

25.4 TYP. (2 PLACES)*

F

31.8

G

SECONDARY DRAIN

SECONDARY DRAIN

PRIMARY DRAIN

73.0

PF4MNB

25.4 TYP. (2 PLACES)*

11.1 TYP. (4 PLACES)*

31.8 55.6 TYP. (2 PLACES)* 82.6

65.1

DOWNFLOW (FIELD CONVERTED)

PRIMARY DRAIN SECONDARY DRAIN

UPFLOW (AS SHIPPED)

PRIMARY DRAIN 8.0 TYP.* SECONDARY DRAIN

46.0 TYP.*

31.8 41.3 8.0 TYP.* 12.7 TYP.*

46.0 TYP.*

54.0

31.8

F HORIZ. RIGHT (FIELD CONVERTED)

22.2 TYP.*

12.7 TYP.* 22.2 TYP.*

41.3 73.0

HORIZ. LEFT (AS SHIPPED)

127.0

A-COIL

* HORIZONTAL MOUNT LOCATIONS - DIMPLES PROVIDED IN TOP PANEL, AND BACK OF CABINET. IN CABINET BOTTOM. HOLES PROVIDED 3.45 DIA. HORIZONTAL HANGING HARDWARE TO BE FIELD SUPPLIED. PRIMARY DRAIN SECONDARY DRAIN 46.0 TYP*

AIRFLOW

55.6 TYP. (2 PLACES)* 12.7 TYP*

AIRFLOW

11.1 TYP. (4 PLACES)

38.1 30.2

149.2 200.0

F

120.6 77.8

G

22.2 TYP* SECONDARY DRAIN

8.0 TYP*

25.4 TYP. (2 PLACES) SECONDARY DRAIN PRIMARY DRAIN

HORIZ. LEFT (AS SHIPPED)

PRIMARY DRAIN 8.0 TYP.*

PRIMARY DRAIN

SECONDARY DRAIN

25.4 TYP. (2 PLACES)* 79.4 11.1 TYP, (4 PLACES)*

38.1 55.6 TYP. (2 PLACES)*

77.8 120.6

68.3

DOWNFLOW (FIELD CONVERTED)

46.0 TYP.

149.2 200.0

30.2

12.7 TYP.* 22.2 TYP.*

HORIZ. RIGHT (FIELD CONVERTED)

UPFLOW (AS SHIPPED)

A10017

Fig. 4 - PF4MNB - Metric -

6

PHYSICAL DATA

MODEL NO. PF4MNB019 PF4MNB025 PF4MNB031 PF4MNB037 PF4MNB043 PF4MNB049 PF4MNB061 FIELD INSTALLED HEAT(kW) 3, 5, 8, 10 3, 5, 8, 10, 15 5, 8, 10, 15, 20 5, 8, 9, 10, 15, 20 5 8, 9, 10, 15, 18, 20 5, 8, 9, 10, 15, 18, 20, 24, 30 5, 8, 9, 10, 15, 18, 20, 24, 30 NOMINAL COOLING CAPACITY(BTUH) 18,000 24,000 30,000 36,000 42,000 48,000 60,000 DIMENSIONS Height 49 5/8--- in 1261mm 49 5/8--- in 1261mm 53 7/16--- in 1357mm 49 5/8--- in 1260mm 49--- 5/8 1260 mm 53--- 7/16 1357 mm 59--- 3/16" 1503 mm Width 17 5/8--- in 447mm 17--- 5/8" 448 mm 21 1/8--- in 536mm 21--- 1/8" 537 mm 21--- 1/8" 537 mm 24 11/16--- in 627mm 24--- 11/16" 627 mm Depth 22--- 1/16" 560 mm 22--- 1/16" 560 mm 22--- 1/16" 560 mm 22--- 1/16" 560 mm 22--- 1/16" 560 mm 22--- 1/16" 560 mm 22--- 1/16" 560 mm SHIPPING WEIGHT 122 lb 55 kg 122 lb 55 kg 146 lb 66 kg 157 lb 71 kg 157 lb 71 kg 185 lb 84 kg 201 lb 91 kg

SPECIFICATIONS

MODEL PF4MNB 019 025 031 037 043 049 061 COIL R--- 410A Refrigerant TXV --- factory installed hard --- shutoff, bi--- flow type for heat pump application Metering Device TXV 2 ton 3 ton 4 ton Rows/Fins Per In. 3 / 14.5 Face Area (Sq. Ft.) 2.97 3.46 4.45 5.93 7.42 Configuration Slope A FAN CFM (Nominal) 600 800 1000 1200 1400 1600 2000 Motor Type (ECM) X--- 13 X--- 13 X--- 13 X--- 13 X--- 13 X--- 13 X--- 13 Motor Hp 1/3 1/3 1/2 1/2 1/2 3/4 3/4 FILTER 21--- 1/2--- in / 546 mm X 16--- 3/8--- in / 417 mm 19--- 7/8--- in / 505 mm 23--- 5/16--- in / 585 mm CABINET CONFIGURATION OPTIONS 1--- pc 1--- pc / Modular

7

PF4MNB

PERFORMANCE DATA

AIRFLOW PERFORMANCE (CFM)

MODEL & SIZE BLOWER SPEED Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 0.10 776 683 683 631 625 956 825 825 726 631 1189 1041 1041 924 779 1363 1237 1237 1095 1014 1519 1437 1437 1257 1237 1757 1664 1664 1459 1301 2030 1811 1811 1665 1462 0.20 745 644 644 563 524 920 795 795 695 563 1151 998 998 876 693 1332 1206 1206 1058 885 1490 1403 1403 1226 1206 1725 1626 1626 1420 1241 1995 1775 1775 1632 1418 0.30 696 589 589 500 457 891 757 757 635 500 1104 944 944 817 628 1294 1160 1160 1007 773 1454 1366 1366 1191 1160 1693 1593 1593 1379 1195 1961 1740 1740 1593 1371 0.40 660 548 548 443 417 851 722 722 598 443 1050 886 886 752 571 1253 1121 1121 951 673 1419 1333 1333 1141 1121 1653 1552 1552 1336 1150 1927 1703 1703 1556 1327 0.50 609 494 494 409 367 816 674 674 543 409 1003 837 837 704 526 1207 1070 1070 888 609 1379 1294 1294 1090 1070 1614 1517 1517 1298 1102 1888 1664 1664 1507 1278 0.60 572 461 461 361 319 780 634 634 509 361 959 772 772 660 476 1157 1013 1013 824 549 1332 1245 1245 1033 1013 1576 1477 1477 1259 1039 1842 1613 1613 1453 1228

PF4MNB019

PF4MNB025

PF4MNB

PF4MNB031

PF4MNB037

PF4MNB043

PF4MNB049

PF4MNB061

--- Airflow outside 450 cfm/ton. NOTES:

1. Airflow based upon dry coil at 230v with factory-approved filter and electric heater (2 element heater sizes 018 through 037, 3 element heater sizes 043 through 061). 2. Airflow at 208 volts is approximately the same as 230 volts because the X- motor is a constant torque motor. The torque doesn't drop -13 off at the speeds the motor operates. 3. To avoid potential for condensate blowing out of drain pan prior to making drain trap: Return static pressure must be less than 0.40 in wc. Horizontal applications of 043 - 061 sizes must have supply static greater than 0.20 in wc. 4. Airflow above 400 cfm/ton on 049-061 size could result in condensate blowing off coil or splashing out of drain pan.

8

PERFORMANCE DATA (cont.)

GROSS COOLING CAPACITIES (mbh)

PF4M SIZE INDOOR COIL AIR CFM EWB 72 / 22 67 / 19 525 62 / 17 72 / 22 67 / 19 600 62 / 17 72 / 22 67 / 19 675 62 / 17 72 / 22 67 / 19 700 62 / 17 72 / 22 67 / 19 800 62 / 17 72 / 22 67 / 19 900 62 / 17 72 / 22 67 / 19 875 62 / 17 72 / 22 67 / 19 1000 62 / 17 72 / 22 67 / 19 1125 62 / 17 72 / 22 67 / 19 1050 62 / 17 72 / 22 67 / 19 1200 62 / 17 72 / 22 67 / 19 1350 62 / 17 72 / 22 67 / 19 1225 62 / 17 72 / 22 67 / 19 1400 62 / 17 72 / 22 67 / 19 1575 62 / 17 72 / 22 67 / 19 1400 62 / 17 72 / 22 67 / 19 1600 62 / 17 72 / 22 67 / 19 1800 62 / 17 72 / 22 67 / 19 1600 62 / 17 72 / 22 67 / 19 1750 62 / 17 72 / 22 67 / 19 2000 62 / 17 TC 36 29 23 40 33 26 44 36 29 48 39 31 53 43 34 57 47 37 59 48 38 65 53 42 71 58 46 67 54 43 74 60 48 81 66 52 79 64 51 87 71 56 95 77 61 90 73 58 100 81 65 109 89 70 109 89 71 117 95 76 129 105 84 35 / 2 SHC 19 19 19 21 21 21 23 23 24 25 25 25 27 28 28 30 30 31 30 31 31 33 34 35 36 37 38 36 37 37 40 41 41 43 45 46 41 42 43 46 47 48 50 51 52 48 49 49 53 54 55 58 59 60 57 58 59 61 62 63 67 69 70 BF 0.00 0.01 0.02 0.00 0.02 0.02 0.00 0.02 0.03 0.00 0.03 0.03 0.00 0.04 0.04 0.00 0.05 0.05 0.00 0.03 0.04 0.00 0.04 0.05 0.00 0.05 0.06 0.00 0.03 0.03 0.00 0.04 0.04 0.00 0.05 0.05 0.00 0.04 0.04 0.00 0.05 0.06 0.00 0.06 0.07 0.00 0.03 0.03 0.00 0.04 0.04 0.00 0.05 0.05 0.00 0.02 0.03 0.00 0.03 0.03 0.00 0.04 0.04 SATURATED TEMPERATURE LEAVING EVAPORATOR (_F / °C) 40 / 4 45 / 7 50 / 10 TC SHC BF TC SHC BF TC SHC BF 33 17 0.00 28 15 0.00 24 13 0.00 26 17 0.01 22 15 0.02 17 13 0.02 20 17 0.02 16 15 0.02 12 12 0.07 36 19 0.00 32 17 0.00 27 14 0.01 29 19 0.02 24 17 0.02 19 14 0.02 22 19 0.02 17 17 0.03 13 13 0.08 40 21 0.00 35 18 0.00 29 16 0.02 32 21 0.03 26 18 0.03 21 16 0.03 24 21 0.03 19 19 0.04 15 15 0.10 43 22 0.00 37 19 0.00 31 17 0.02 34 22 0.03 28 20 0.03 22 17 0.03 26 23 0.03 20 20 0.04 16 16 0.10 47 24 0.00 41 21 0.01 35 18 0.03 37 25 0.04 31 22 0.04 25 19 0.04 29 25 0.04 23 22 0.05 18 18 0.12 51 27 0.00 45 23 0.03 38 20 0.04 41 27 0.05 34 24 0.05 27 21 0.05 31 28 0.05 25 24 0.06 20 20 0.14 53 27 0.00 46 24 0.01 38 20 0.02 42 28 0.03 35 24 0.04 27 21 0.04 32 28 0.04 25 24 0.04 20 20 0.11 58 30 0.00 51 26 0.02 42 23 0.04 46 31 0.04 38 27 0.05 30 23 0.05 35 31 0.05 28 27 0.06 22 22 0.13 63 33 0.00 55 29 0.03 46 25 0.05 50 33 0.05 42 29 0.06 33 25 0.06 38 34 0.06 30 30 0.07 24 24 0.15 60 32 0.00 52 28 0.00 44 24 0.02 47 33 0.03 40 29 0.03 31 25 0.03 36 33 0.03 29 29 0.04 22 22 0.10 66 36 0.00 58 31 0.01 48 27 0.03 52 36 0.04 44 32 0.04 35 27 0.04 40 37 0.04 32 32 0.05 25 25 0.12 72 39 0.00 63 34 0.03 53 30 0.04 57 40 0.05 48 35 0.05 38 30 0.05 44 41 0.05 35 36 0.06 28 28 0.14 71 37 0.00 62 33 0.02 52 28 0.03 56 38 0.04 47 33 0.04 37 29 0.04 43 38 0.04 34 34 0.05 27 27 0.12 78 41 0.00 68 36 0.03 57 31 0.04 62 42 0.05 52 37 0.05 41 32 0.05 47 43 0.06 38 38 0.06 30 30 0.14 85 45 0.00 74 39 0.04 62 34 0.05 67 46 0.06 56 40 0.06 44 35 0.07 51 47 0.07 41 41 0.08 33 33 0.17 81 43 0.00 71 38 0.00 59 32 0.02 64 44 0.03 54 38 0.03 42 33 0.03 49 44 0.03 39 39 0.04 30 30 0.10 89 48 0.00 78 42 0.01 65 36 0.03 71 48 0.04 59 43 0.04 47 36 0.04 54 49 0.04 43 43 0.05 34 34 0.12 97 52 0.00 85 46 0.03 71 39 0.04 77 53 0.05 65 47 0.05 51 40 0.05 59 54 0.05 47 48 0.06 37 37 0.14 98 51 0.00 86 45 0.00 73 39 0.01 78 52 0.02 66 46 0.02 52 39 0.03 60 52 0.03 48 46 0.03 37 37 0.09 105 55 0.00 92 48 0.01 78 41 0.02 84 56 0.03 70 49 0.03 56 42 0.03 64 56 0.03 51 50 0.04 40 40 0.10 116 60 0.00 102 53 0.02 86 46 0.03 92 62 0.04 78 54 0.04 62 47 0.04 71 63 0.04 57 55 0.05 45 45 0.12

LWB - Leaving Wet Bulb (_F / _C) MBH - 1000 Btuh -

019

025

031

037

043

049

061

TC 19 12 10 21 13 11 23 15 12 25 16 13 27 17 15 30 19 16 30 19 16 33 21 18 36 23 20 35 22 18 38 24 21 41 27 23 41 26 22 45 29 25 48 31 27 47 30 25 51 33 28 56 36 31 58 37 31 62 40 33 68 44 37

55 / 13 SHC 11 10 10 12 12 11 13 13 12 14 14 13 15 16 15 17 17 16 17 17 16 19 19 18 20 21 20 20 20 18 22 23 21 25 25 23 23 24 22 26 26 25 28 29 27 27 27 25 30 30 28 33 33 31 32 33 31 35 35 33 38 39 37

BF 0.01 0.02 0.24 0.02 0.03 0.25 0.02 0.03 0.26 0.03 0.04 0.26 0.04 0.05 0.28 0.05 0.06 0.29 0.03 0.04 0.27 0.04 0.05 0.29 0.05 0.07 0.30 0.03 0.04 0.26 0.04 0.05 0.28 0.05 0.06 0.29 0.04 0.05 0.28 0.05 0.06 0.29 0.06 0.07 0.31 0.03 0.04 0.26 0.04 0.05 0.28 0.05 0.06 0.29 0.02 0.03 0.24 0.02 0.03 0.25 0.03 0.05 0.27

See Notes following table. LEGEND CFM - Cubic Ft. per Minute SHC - Gross Sensible Capacity 1000 Btuh See NOTES on next page.

EWB - Entering Wet Bulb (_F / _C) BF - Bypass Factor -

TC - Gross Cooling Capacity 1000 Btuh -

9

PF4MNB

PERFORMANCE DATA (cont.)

NOTES:

PF4MNB

1. Contact manufacturer for cooling capacities at conditions other than shown in table. 2. Formulas: Leaving db = entering db -sensible heat cap. 1.09 x CFM Leaving wb = wb corresponding to enthalpy of air leaving coil (hlwb) -total capacity (Btuh) hlwb = hewb 4.5 x CFM where hewb = enthalpy of air entering coil. Direct interpolation is permissible. Do not extrapolate. 3. SHC is based on 80_F (27_C) db temperature of air entering coil. Below 80_F (27_C) db, subtract (Correction Factor x CFM) from SHC. Above 80_F (27_C) db, add (Correction Factor x CFM) to SHC. 4. Bypass Factor = 0 indicates no psychometric solution. Use bypass factor of next lower EWB for approximation.

SHC CORRECTION FACTOR

ENTERING AIR DRY-- BULB TEMPERATURE (_F) 79 BYPASS FACTOR 81 26 27 0.10 0.20 0.30 .098 0.87 0.76 78 82 25 28 1.96 1.74 1.53 77 83 25 28 2.94 2.62 2.29 76 84 24 29 Correction Factor 3.92 3.49 3.05 4.91 4.36 3.82 Use formula shown below 75 85 24 29 Under 75 Over 85 Under 75 Over 85

ENTERING AIR DRY-- BULB TEMPERATURE (_C)

Interpolation is permissible. Correction Factor = 1.09 x (1 --- BF) x (db --- 80)

MINIMUM CFM AND MOTOR SPEED SELECTION

FAN COIL SIZES 019 025 031 037 043 049 061 3 525 700 -- -- -- -- -- 5 525 700 875 1050 -- -- -- 8 525 700 875 970 1225 1400 1750 9 -- -- -- 970 1225 1400 1750 HEATER kW 10 15 600* -- 700 775* 875 875 970 920 1225 1225 1400 1400 1750 1750 18 -- -- -- -- 1225 1400 1750 20 -- -- 1060* 1040 1225 1400 1750 24 -- -- -- -- -- 1400 1750 30 -- -- -- -- -- 1400 1750

*Indicates medium speed (blue). All other motor speeds at low tap.

AIR DELIVERY PERFORMANCE CORRECTION COMPONENT PRESSURE DROP (in wc) AT INDICATED AIRFLOW (DRY-TO-WET COIL)

SIZE 019 025 031 037 043 049 061 500 0.034 0.016 --- ----- ----- ----- ----- --600 0.049 0.027 --- ----- ----- ----- ----- --700 0.063 0.038 --- ----- ----- ----- ----- --800 --- --0.049 0.049 --- ----- ----- ----- --900 --- --0.059 0.059 --- ----- ----- ----- --1000 --- ----- --0.070 0.055 --- ----- ----- --1100 --- ----- --0.080 0.064 --- ----- ----- --CFM 1200 1300 --- ----- ----- ----- ----- ----- --0.073 0.081 0.049 0.056 --- ----- ----- ----- --1400 --- ----- ----- ----- --0.063 0.038 --- --1500 --- ----- ----- ----- --0.070 0.043 --- --1600 --- ----- ----- ----- ----- --0.049 0.027 1700 --- ----- ----- ----- ----- --0.054 0.031 1800 --- ----- ----- ----- ----- --0.059 0.035 1900 --- ----- ----- ----- ----- ----- --0.039 2000 --- ----- ----- ----- ----- ----- --0.043

10

FACTORY-INSTALLED FILTER STATIC PRESSURE DROP (in wc)

UNIT SIZE PF4MNB 019, 025 031, 037, 043 049, 061 400 0.012 ----600 0.022 ----800 0.048 0.036 --1000 0.072 0.051 --CFM 1200 --0.07 --1400 --0.092 0.073 1600 --0.12 0.086 1800 ----0.105 2000 ----0.13

ELECTRIC HEATER STATIC PRESSURE DROP (in wc)

019 --- 031 HEATER ELEMENTS 0 1 2 3 4 kW 0 3, 5 8, 10 9, 15 20 EXTERNAL STATIC PRESSURE CORRECTION +.02 +.01 0 ­.02 ­.04 037--- 061 HEATER ELEMENTS 0 2 3 4 6 kW 0 8, 10 9, 15 20 18, 24, 30 EXTERNAL STATIC PRESSURE CORRECTION +.04 +.02 0 ­.02 ­.10

The airflow performance data was developed using fan coils with 10 ---kW electric heaters (2 elements) in the 018 through 037 size units and 15 ---kW heaters (3 elements) in the 042 through 060 size units. For fan coils with heaters of a different number of elements, the external available static at a given CFM from the curve may be corrected by adding or subtracting available external static pressure as indicated above.

ACCESSORY ELECTRIC HEATERS

HEATER PART NO. KFCEH0401N03 KFCEH0501N05 KFCEH0801N08 KFCEH0901N10 KFCEH3201F20 KFCEH1601315 KFCEH2001318 KFCEH3401F24 KFCEH3501F30 KFCEH2401C05 KFCEH2501C08 KFCEH2601C10 KFCEH3301C20 KFCEH2901N09 KFCEH3001F15 KFCEH3101C15

* { } **

kW @ 240V 3 5 8 10 20 15 18 24 30 5 8 10 20 9 15 15

VOLTS/ PH 230/1 230/1 230/1 230/1 230/1 230/3 230/3 230/3* 230/3* 230/1 230/1 230/1 230/1 230/1{ 230/1 230/1

STAGES (kW OPERATING) 3 5 8 10 5, 20 5, 15 6, 12, 18 8, 16, 24 10, 20, 30 5 8 10 5, 20 3, 9 5, 15 5, 15

INTERNAL CIRCUIT PROTECTION None None None None Fuse} None None Fuse Fuse Circuit Breaker Circuit Breaker Circuit Breaker Circuit Breaker None Fuse} Circuit Breaker

FAN COIL SIZE USED WITH 018­024 018­061 018­061 018­061 030­061 036­061 042­061 048--- 061 048--- 061 018­061 018­061 018­061 030­061 036­061 024­061 024­061

HEATING CAP .** @ 230V 9,400 15,700 25,100 31,400 62,800 47,100 56,500 78,300 94,100 15,700 25,100 31,400 62,800 28,200 47,100 47,100

Field convertible to 1 phase. Field convertible to 3 phase Single point wiring kit required for these heaters in Canada. Blower Motor heat not included.

11

PF4MNB

PERFORMANCE DATA (cont)

ESTIMATED SOUND POWER LEVEL (dBA)

UNIT SIZE 019 025 031 037 043 049 061

*

CONDITIONS Ext Static CFM Pressure 600 0.25 800 0.25 1000 0.25 1200 0.25 1400 0.25 1600 0.25 2000 0.25

OCTAVE BAND CENTER FREQUENCY* 63 64.7 66.0 67.0 67.8 68.4 69.0 70.0 125 60.7 62.0 63.0 63.8 64.4 65.0 66.0 250 56.7 58.0 59.0 59.8 60.4 61.0 62.0 500 53.7 55.0 56.0 56.8 57.4 58.0 59.0 1000 51.7 53.0 54.0 54.8 55.4 56.0 57.0 2000 49.7 51.0 52.0 52.8 53.4 54.0 55.0 4000 45.7 47.0 48.0 48.8 49.4 50.0 51.0

Estimated sound power levels have been derived using the method described in the 1987 ASHRAE HVAC Systems & Applications Handbook, Chapter 52, p.52.7

PF4MNB

FAN COIL ELECTRICAL DATA (UNITS WITHOUT ELECTRICAL HEAT)

MODEL NO. PF4MNB019(0,T)00 PF4MNB025(0,T)00 PF4MNB031(0,T)00 PF4MNB037(0,T)00 PF4MNB043(0,T)00 PF4MNB049(0,T)00 PF4MNB061(0,T)00

*

MTR HP 1/3 1/3 1/2 1/2 1/2 3/4 3/4

MTR FLA 2.8 2.8 4.1 4.1 4.1 6.0 6.0

VOLTS/PH/HZ 208/230/1/60 208/230/1/60 208/230/1/60 208/230/1/60 208/230/1/60 208/230/1/60 208/230/1/60

SINGLE CIRCUIT MAXIMUM OVERCURRENT MCA PROTECTION 3.5 15 3.5 15 5.1 15 5.1 15 5.1 15 7.5 15 7.5 15

BRANCH CIRCUIT MIN WIRE SIZE* AWG 14 14 14 14 14 14 14

Use copper wire only. Use 75_C only in this application. When using non ---metallic (NM) sheathed cable, wire size required should be based on that of 60_C conductors, instead of wire size shown in table above per NEC Article 336 ---26. FLA --- Full Load Amps NOTE: If branch circuit wire length exceeds 100 ft / 30.5 m, consult NEC 215 ---2 to determine maximum wire length. Use 2% voltage drop.

ELECTRIC HEATER INTERNAL PROTECTION

HEATER kW 3 5 8 10 15 20 24 30 9 15 18

*Circuit breakers are 2 pole.

PHASE 1 1 1 1 1 1 1/3 1/3 1/3 3 3

FUSE QTY/SIZE -- -- -- -- 2/30 -- 2/60 4/60 6/60 6/60 -- -- --

CKT BKR QTY/SIZE* -- 1/60 1/60 1/60 2/60 2/60 -- -- -- -- --

12

PF4MN

ACCESSORY ELECTRIC HEATER ELECTRICAL DATA

HEATER AMPS 208/230V Min Ampacity 208/230V** Single Circuit L1,L2 -- -- -- -- -- -- -- -- -- -- -- 53.8/58.5 53.8/58.5 -- -- 53.8/58.5 53.8/58.5 -- -- -- -- -- -- -- -- 4/4 1/1 3/3 0/00 45.3/50.0 -- 45.3/50.0 3/2 6/6 6/6 -- -- -- -- -- 6/6 -- -- 8/6 -- -- -- 8/8 8/8 -- -- -- -- 22.7/25.0 -- 6/6 10/10 22.7/25.0 4/4 6/6 10/10 -- 6/6 -- -- 10/10 8/8 -- 10/10 10/8 8/6 -- 8/8 6/6 8/8 6/6 -- 6/6 -- -- 10/10 -- 8/8 -- -- 10/10 -- -- -- 10/10 10/10 -- -- 10/10 10/10 -- -- -- -- -- 8/6 -- -- 10/10 -- -- 8/8 -- -- 10/10 -- -- -- -- -- -- 10/10 10/10 -- -- 10/10 10/10 -- -- -- -- -- 8/8 -- -- 10/10 -- -- -- 8/8 -- -- 10/10 -- -- -- 10/10 -- -- 10/10 -- -- 30/30 35/35 45/50 45/50 50/60 35/35 60/60 60/60 80/90 -- 50/60 60/70 100/110 -- 80/80 125/150 90/100 150/175 -- 8/8 -- -- 10/10 -- -- 35/35 -- 10/10 -- -- 10/10 -- -- 30/30 -- -- -- -- -- -- -- -- -- -- 60/60 60/60 -- -- 60/60 60/60 -- -- -- -- -- 12/12 -- -- 12/12 -- -- 20/20 -- L3,L4 L1,L2 L3,L4 L1,L2 L3,L4 L1,L2 15.9/17.3 26.0/28.4 31.2/33.5 26.0/28.4 31.2/33.5 44.7/48.5 44.7/48.5 49.5/53.5 32.0/34.5 53.8/58.5 53.8/58.5 76.3/83.4 -- 47.7/51.8 55.5/60.4 98.9/108.4 -- 71.2/77.8 116.9/127.9 86.8/95.0 144.8/158.5 Dual Circuit Single Circuit Single Circuit Single Circuit Dual Circuit Dual Circuit Dual Circuit L3,L4 -- -- -- -- -- -- -- -- -- -- -- 25/25 25/25 -- -- 50/50 50/50 -- -- -- -- Min Wire Size (AWG) 208/230V Min Gnd Wire Size 208/230V Max Fuse/Ckt Bkr Amps 208/230V Single Circuit 67/68 66/66 85/88 66/66 85/88 59/60 59/60 54/87 83/85 78/80 78/80 88/89 -- 56/90 76/77 85/109 -- 94/95 115/116 97/98 117/150 Dual Circuit L1,L2 -- -- -- -- -- -- -- -- -- -- -- 36.2/40.0 36.2/40.0 -- -- 36.2/40.0 36.2/40.0 -- -- -- -- -- -- -- -- 36.2/40.0 36.2/40.0 -- -- 18.1/20.0 18.1/20.0 -- -- -- -- -- -- -- -- -- -- -- L3,L4 BRANCH CIRCUIT Max Wire Length 208/230V (Ft) Dual Circuit L1,L2 -- -- -- -- -- -- -- -- -- -- -- 78/80 78/80 -- -- 78/80 78/80 -- -- -- -- L3,L4 -- -- -- -- -- -- -- -- -- -- -- 75/76 75/76 -- -- 59/59 59/59 -- -- -- -- P H A S E INTERNAL CIRCUIT PROTECTION Single Circuit 10.9/12.0 18.1/20.0 18.1/20.0 18.1/20.0 18.1/20.0 28.9/32.0 28.9/32.0 32.8/36.0 18.8/20.8 36.2/40.0 36.2/40.0 54.2/59.9 -- 31.3/34.6 37.6/41.5 72.3/79.9 -- 50.1/55.4 86.7/95.5 62.6/69.2 109.0/120.0 208v 2.3 3.8 3.8 3.8 3.8 6.0 6.0 6.8 6.8 7.5 7.5 11.3 11.3 11.3 13.5 15.0 15.0 18.0 18.0 22.5 22.5 1 Fuse 3 Fuse 1 Fuse 3 Fuse 1 Ckt Bkr 1 Fuse 3 None 3 None 1 Ckt Bkr 1 Fuse 1 Ckt Bkr 1 None 3 None 1 None 1 Ckt Bkr 1 None 1 Ckt Bkr 1 Ckt Bkr 1 None 1 None 1 None

HEATER PART NO.

KW

240v

KFCEH0401N03

3

KFCEH0501N051

5

KFCEH0501N052

5

KFCEH2401C051

5

KFCEH2401C052

5

KFCEH0801N08

8

KFCEH2501C08

8

KFCEH2901N09

9

KFCEH2901N09

9

KFCEH0901N10

10

KFCEH2601C10

10

KFCEH3001F15

15

KFCEH3101C15

15

KFCEH1601315

15

KFCEH2001318

18

13

PHASE 208V 18.0 22.5 1 36.2/40.0 36.2/40.0 36.2/40.0 1 28.9/32.0 28.9/32.0 28.9/32.0 44.7/48.5 53.8/58.5 L1,L2 L3,L4 L5,L6 L1,L2 HEATER AMPS 208/230V MIN AMPACITY 208/230V** L3,L4 36.2/40.0 45.3/50.0 L5,L6 36.2/40.0 45.3/50.0 L1,L2 8/8 6/6

KFCEH3201F20

20

KFCEH3301C20

20

24

KFCEH3401F24

24

KFCEH3501F30

30

30

FIELD MULTIPOINT WIRING OF 24-AND 30-KW SINGLE PHASE

MIN WIRE SIZE (AWG) 208/230V L3,L4 8/8 8/8 L5,L6 8/8 8/8 MIN GND WIRE SIZE 208/230V 10/10 10/10 MAX FUSE/CKT BKR AMPS 208/230V L1,L2 45/50 60/60 L3,L4 40/40 50/50 L5,L6 40/40 50/50 L1,L2 59/60 78/80 MAX WIRE LENGTH 208/230V (FT) L3,L4 73/73 59/59 L5,L6 73/73 59/59

HEATER PART NO.

KW

240V

KFCEH3401F24

24

KFCEH3501F30

30

{ } ** {{ }}

Field convertible to 1 phase, single or multiple supply circuit. Field convertible to 3 phase. Includes blower motor amps of largest fan coil used with heater. Copper wire must be used. If other than uncoated (non---plated), 75_C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the National Electric Code (ANSI/NFPA 70). Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.

NOTES: 1. For fan coil sizes 018 ---037. 2. For fan coil sizes 042 ---061. 3. Single circuit application of F15 and F20 heaters requires single ---point wiring kit accessory.

ACCESSORIES

1. 2. 3. 4. 5. 6. 7. 8. 9. ITEM Disconnect Kit Downflow Base Kit Downflow Conversion Kit Single--- Point Wiring Kit Filter Kit (12 Pack) Power Plug Kit (25 Pack) PVC Condensate Trap Kit (50 pack) Downflow/Horizontal Conversion Gasket Kit Horizontal Water Management Kit (25 pack) ACCESSORY PART NO.* KFADK0201DSC KFACB0201CFB KFACB0301CFB KFACB0401CFB KFADC0201SLP KFADC0401ACL KFASP0101SPK KFAFK0212MED KFAFK0312LRG KFAFK0412XXL KFAPP0125PLG KFAET0150ETK KFAHD0101SLP KFAHC0125AAA FAN COIL SIZE USED WITH Cooling controls and heaters 3--- through 10--- kW 019, 025 031, 037, 043 049, 061 Slope Coil Units--019, 025, 031 A--- Coil Units--037, 043, 049, 061 Only with 15--- and 20--- kW Fused Heaters 019, 025 031, 037, 043 049, 061 All All All All

PF4MNB

* Factory ---authorized and listed, field---installed.

Accessory Kits Description Suggested and Required Use.

1. Disconnect Kit The kit is used to disconnect electrical power to the fan coil so service or maintenance may be performed safely. SUGGESTED USE: Units for 3- through 10-kW electric resistance heaters and cooling controls. 2. Downflow Base Kit This kit is designed to provide a 1- (25 mm) minimum clearance between unit discharge plenum, ductwork, and combustible mater-in. ials. It also provides a gap-free seal with the floor. REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications. 3. Downflow Conversion Kit Fan coils are shipped from the factory for upflow or horizontal-left applications. Downflow conversion kits provide proper condensate water drainage and support for the coil when used in downflow applications. Separate kits are available for slope coils and A-coils. REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications. 4. Single Point Wiring Kit The single point wiring kit acts as a jumper between L1 and L3 lugs, and between the L2 and L4 lugs. This allows the installer to run 2 heavy-gauge, high voltage wires into the fan coil rather than 4 light-gauge, high voltage wires. SUGGESTED USE: Fan coils with 15- and 20-kW fused heaters only. 5. Filter Kit (12 pack) The kit consists of 12 fan coil framed filters. These filters collect large dust particles from the return air entering the fan coil and prevents them from collecting on the coil. This process helps to keep the coil clean, which increases heat transfer and in turn the efficiency of the system. SUGGESTED USE: To replace filters in fan coils. REQUIRED USE: All units unless a filter grille is used. 6. Power Plug Kit The kit consists of 25 wire harness assemblies. Each plug provides the high-voltage power connection to the fan coil in the absence of electric heat. REQUIRED USE: Units installed without electric heat. 7. Condensate Drain Trap Kit This kit consists of 50 PVC condensate traps. Each trap is pre-formed and ready for field installation. This deep trap helps the system make and hold proper condensate flow even during blower initiation. SUGGESTED USE: All fan coils. 8. Downflow/Horizontal Conversion Gasket Kit This kit provides the proper gasketing of units when applied in either a downflow or horizontal application. REQUIRED USE: Fan coils in either downflow or horizontal applications. 9. Horizontal Applications - Water Management Kit This kit provides proper installation of fan coils under conditions of high static pressure and high relative humidity. SUGGESTED USE: All fan coils.

E2010 Payne Heating & Cooling Systems D

7310 W. Morris St. D Indianapolis, IN 46231

Printed in U.S.A.

Edition Date: 01/10

Catalog No: SS---PF4---B---01

Replaces: NEW

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.