Read untitled text version

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

CONTENTS

Preface ................................................................................................................................1 Chapter 1 Product Introduction .......................................................................................2 Chapter 2 Technical Specifications .................................................................................3 2.1 Operating Voltage ......................................................................................................3 2.2 Standby Batteries .......................................................................................................3 2.3 Communication Loop Parameters .............................................................................3 2.4 Detection Loop Parameters .......................................................................................3 2.5 Output Loop Parameters............................................................................................4 2.6 Dimension ..................................................................................................................4 Chapter 3 Structure and Configuration ...........................................................................5 3.1 Appearance and Internal Structure ............................................................................5 3.1.1 Display and Operation Area ................................................................................6 3.1.2 Description of LEDs.............................................................................................7 3.1.3 Description of Keys .............................................................................................7 3.1.4 Zone Indication and Manual Intervention Panel (ZCP).......................................8 3.2 Configuration ..............................................................................................................9 3.2.1 Typical Configuration ...........................................................................................9 3.2.2 Optional Units ....................................................................................................10 3.3 Field Devices............................................................................................................ 11 3.3.1 A Series of Intelligent Fire Detectors ................................................................. 11 3.3.2 Modules ............................................................................................................. 11 3.3.3 Loop Isolator...................................................................................................... 11 3.3.4 Manual call points..............................................................................................12 3.3.5 Addressable sounder strobes............................................................................12 3.3.6 GST852RP Repeater Panel ..............................................................................12 3.4 Configuration (C&E Equation and Devices) Software .............................................12 Chapter 4 Mounting .........................................................................................................13 4.1 Configuration Inspection ..........................................................................................13 4.2 Mounting Cabinet .....................................................................................................13 4.3 Start-up Check .........................................................................................................14 4.4 Connections of Field Devices ..................................................................................15 4.4.1 Connection of Sounder Circuit Output ..............................................................16 4.4.2 Connection of F.P.E. Output ..............................................................................16 4.4.3 Connection of Fire Alarm Output.......................................................................17 4.4.4 Connection of Class A Loop ..............................................................................17 4.4.5 Connection of Communication Loop .................................................................18 4.5 Connection Inspection and Device Registration......................................................18 4.5.1 Connection Inspection.......................................................................................18 4.5.2 Registration of Devices .....................................................................................19 4.6 Definition of Devices ................................................................................................19 4.6.1 Installation .........................................................................................................19 Page I

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution 4.6.2 Toolbar of GST-DEF Software...........................................................................20 4.6.3 Operation Screens ............................................................................................23 4.6.4 Adding FACP .....................................................................................................24 4.6.5 Zone Definition ..................................................................................................24 4.6.6 Definition of Loop Devices ................................................................................26 4.6.7 Defining Repeater Panels .................................................................................28 4.6.8 Defining ZCP .....................................................................................................28 4.6.9 Defining Cause and Effect (C&E) Equation ......................................................30 4.7 Periphery Device Commission.................................................................................33 Chapter 5 Display and Disposal of System Information .............................................34 5.1 Normal Information...................................................................................................34 5.2 Fire Alarm .................................................................................................................34 5.2.1 Screen of Fire Alarm..........................................................................................34 5.2.2 Disposal of Fire Alarm Signal ............................................................................35 5.3 Fault Information ......................................................................................................36 5.3.1 Screen of Fault Information ...............................................................................36 5.3.2 Disposal of Fault Information ............................................................................37 5.4 Rules for Message Display ......................................................................................37 5.5 Rules for Sound Indication.......................................................................................37 Chapter 6 Description of System Operation.................................................................38 6.1 Keypad .....................................................................................................................38 6.1.1 Functions ...........................................................................................................38 6.1.2 Methods of Data Input .......................................................................................38 6.1.3 Unlocking and Locking the Keypad...................................................................38 6.2 User Operation Instruction .......................................................................................39 6.2.1 Changing time display .......................................................................................39 6.2.2 Browsing............................................................................................................39 6.2.3 Muting the panel ................................................................................................46 6.3 Instructions for System Operator .............................................................................46 6.3.1 Resetting the system.........................................................................................46 6.3.2 Disable and Enable ...........................................................................................46 6.3.3 Manual Operation ..............................................................................................47 6.3.4 Setting work mode of printer .............................................................................48 6.3.5 Checking all visual and audible indications.......................................................48 6.3.6 Gas Extinguishing Equipment ...........................................................................49 6.3.7 Security Mode Setting .......................................................................................49 6.4 Instructions for System Administrator ......................................................................50 6.4.1 Modifying System Time .....................................................................................50 6.4.2 Modifying Password ..........................................................................................50 6.4.3 Setting up Network Address of the Control Panel.............................................52 6.4.4 Setting up Beginning Zone Number of This FACP in Network .........................52 6.4.5 Setting up Display Mode of Network Messages ...............................................53 6.4.6 Initialization of System CPU ..............................................................................53 Page II

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution 6.4.7 Viewing Supervisory Data of Intelligent Devices...............................................53 Chapter 7 Troubleshooting.............................................................................................54 Chapter 8 Calculation of Battery Capacity....................................................................55 Appendix 1 Internal Connection Diagram.....................................................................56 Appendix 2 Device Type List ..........................................................................................57 Appendix 3 Operation Menu...........................................................................................59

Page III

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Preface

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual includes two parts: generic part and Fireman's Control Panel part. This is generic part. Please refer to relative part for description on Fireman's Control Panel. Please assign a specific person to keep this manual for occasional use during operation of the GST200 Intelligent Fire Alarm Control Panel.

Page 1

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Chapter 1 Product Introduction

GST200 Intelligent Fire Alarm Control Panel (FACP) is designed by EN 54 standard with qualities of simple installation, operation, and easy maintenance. It is used in fire alarm system with the following features: 1. 2. It controls at most 30 zones. Each zone has its own alarm and fault/disable LEDs and a label. Class A loop can have up to 235 addressable devices. It is compatible with a series of addressable GST products, which are intelligent sounder strobe (I-9403) complying with EN 54-3, photoelectric smoke detector (I-9102) complying with EN 54-7, intelligent manual call point (I-9202) complying with EN 54-11, intelligent reflective beam detector (I-9105R) complying with EN 54-12, input and output module (I-9300, I-9301) complying with GEI 1-084, and loop isolator (C-9503) complying with GEI 1-052. The LCD can display 8 lines in total and 18 characters each line, assisting the 15 LEDs to display important information. The memory does not lose data even if power supply is accidentally removed. It has manual keys for each zone, which can activate/silence the sounder strobes separately. Automatically prompting operation steps for every alarm device and for smoke exhaust and fire extinguisher by field programming. Sounder strobe interface provides 0.5A/24V output, compatible with GST conventional sounder strobe (C-9403) designed according to EN 54-3. RS232 interface enables communication with PC. RS485 interface enables networking.

3. 4. 5. 6. 7. 8. 9.

Page 2

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Chapter 2 Technical Specifications

2.1 Operating Voltage

Input Voltage: 230VAC Frequency: 50Hz/60Hz Input Current: 0.5A Fuse: 2A delay Recommended Wiring: 1.5mm2 or above shield cable, complying with local installation codes.

+10% -15%

/ 220VAC

+10% -15%

2.2 Standby Batteries

Maximum Charge Current: [email protected] float charge Type: Sealed lead acid batteries Maximum Charge Capacity: 24Ah Fuse: 8A Recommended Wiring: GST FireCable ® 2E/1.5 2 core and Earth 1.5mm2 CSA

2.3 Communication Loop Parameters

1 RS485 Communication Loop NETWORK (A, B): Communication bus, for connecting with up to 32 network control panels of different model. REPEATER (A, B): Communication bus for connecting with 10 repeater panels at most. Recommended Wiring: GST FireCable ® 2E/1.0 2 RS232 Communication Loop RS232 communication loop is connected with Graphic User Interface (GUI) system installed in PC through DB9 port. Recommended Wiring: Standard RS232 interface. The 2nd pin (for sending data), the 3rd pin (for receiving data), and the 5th pin (ground) are connected with PC through three-core shield cable (Note: Wire length should be less than 15m; shield layer and computer's enclosure should be connected to ground) 2 core and Earth 1mm2 CSA

2.4 Detection Loop Parameters

LOOP OUT (+, -): Polarized signal loop from the FACP, which can be connected with 235 addressable devices at most. LOOP IN (+, -): Polarized signal loop returning to the FACP. Output Voltage: 21V~27V pulse Page 3

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) Output Current: 0~300mA Recommended Wiring: GST FireCable ® 2E/1.0

The Intelligent Solution

2 core and Earth 1mm2 CSA

2.5 Output Loop Parameters

Recommend Wiring: GST FireCable ® 2E/1.0 1 FIRE ALARM OUTPUT (+, -) Output Voltage: 21VDC Output Current: 0~500mA Terminal Resistor: 4.7K 2 F.P.E OUTPUT (+, -) Output Voltage: 21VDC Output Current: 0~500mA Terminal Resistor: 4.7K 3 SOUNDER CIRCUIT OUTPUT (+, -) Output Voltage: 21VDC Output Current: 0~500mA Terminal Resistor: 4.7K 4 FAULT OUTPUT (NC, COM, NO) Contact Capacity: 24VDC @1.0A In fault state, NC and COM open, NO and COM close. 27VDC 27VDC 27VDC 2 core and Earth 1mm2 CSA

2.6 Dimension

400mm×560mm×182mm (L x W x H)

Page 4

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Chapter 3 Structure and Configuration

3.1 Appearance and Internal Structure

GST200 Intelligent Fire Alarm Control Panel is wall-mounted. Its appearance and internal structure are shown in Fig. 3-1 and 3-2. 1 2 6 5

3 7

4

Fig. 3-1 1 Clock display 2 LCD display 3 Printer panel 4 Optional units Fireman's Control Panel 5 LED indication 7 Zone indication and manual intervention panel (ZCP) 6 Keypad

Page 5

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Fig. 3-2 1 Display and operation area 2 Zone indication and manual intervention panel 3 Printer 4 Optional units (FCP) 5 Speaker 6 Power supply 7 Loop interface board 8 Filtering board (optional) 9 Loop module 10 PSU filter 11 Transformer 3.1.1 Display and Operation Area The display and operation area consists of clock display, LCD display, LED indication and keypad, which are shown in Fig. 3-3.

Fig. 3-3

Page 6

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) 3.1.2 Description of LEDs

The Intelligent Solution

FIRE: Red. It illuminates when the FACP detects an alarm condition of connected detectors. After fire alarm condition is removed, the fire status can be cleared by pressing ESC key, and this LED goes out simultaneously. COMMON FAULT: Yellow. It illuminates when the FACP detects fault of connected devices or itself. It goes out automatically when ESC is pressed after the fault condition is removed. DISABLED: Yellow. It illuminates when connected devices, F.P.E. output or SOUNDER CIRCUIT OUTPUT are disabled. MUTE: Yellow. It illuminates when the FACP is in mute state. AC FAULT: Yellow. It illuminates when 230VAC power is down or damaged. After the AC power resumes, it goes out automatically. SYSTEM FAULT: Yellow. It illuminates if the program encounters a dead halt. POWER HEALTHY: Green. It illuminates when main or standby power is normal. BATTERY FAULT: Yellow. It illuminates when standby power is in fault. After the fault is cleared, it will go out. F.P.E. FLT/DISABLE: Yellow. It flashes when F.P.E. output is in fault and illuminates steadily after the F.P.E. is disabled. SOUNDER FLT/DISABLE: Yellow. It flashes when the sounder circuit output (Sounder A) and the sounders on the loop are in fault and illuminates steadily after the sounder is disabled. PLANT CONTROL: Yellow. Action message indication. It illuminates when there are feedback signal inputs of fire-protective plant. DELAY MODE: Yellow, it illuminates when the output is set in delay mode. EXTINGUISHING SYSTEM RELEASE: Yellow. It illuminates when connected gas extinguishing equipment has been activated. EXTINGUISHING SYSTEM REQUEST: Yellow. It illuminates when the system is ready to start the gas extinguishing equipment but the FACP is in release-disabled or delayed state. EXTINGUISHING SYSTEM PERMIT: Yellow. It illuminates when extinguishing system is enabled. 3.1.3 Description of Keys SYSTEM: System set-up key PRINT: Printing mode setting SELF TEST: Pressing this key in normal state can test the visual and audible indication of the panel. Page 7

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) MODE: Setting up the gas extinguishing equipment START/STOP: Start/stop the loop devices.

The Intelligent Solution

ENABLE/DISABLE: Enabling/disabling addressable devices SEC: Setting up security mode RESET: Resetting the control panel BROWSE: Browsing the information of devices LOG: Viewing history record SCREEN: Setting up the screen contrast, message display mode and browsing cause and effect (C&E) equations. MUTE: Muting the FACP. VIEW FAULT: Displaying fault information LOCK: Locking the keypad when it is unlocked. SCROLL: Changing display contents when there are more than one piece of message. ESC: Canceling or quitting the operating menu. If it's pressed while the FACP is displaying messages, it will resume displaying messages of the highest level. VIEW DISABLE: Viewing disabled messages. ENTER: Confirming inputs to be valid. In normal monitoring state, pressing it can make the clock display change between month/day mode and hour/minute mode. VIEW PLANT Displaying action messages.

3.1.4 Zone Indication and Manual Intervention Panel (ZCP) Appearance of zone indication and manual intervention panel is shown in Fig. 3-4.

Fig. 3-4 Page 8

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution In this part, each unit consists of a key, two indicators and a label. The key is for start/stop control. Device labels can be stuck on the right side of the keys, and the user can put the corresponding names on them. Zone indication and manual intervention panel can complete the following functions through defining. 3.1.4.1 Zone Indication a) LEDs Fire: Red. It illuminates when a fire occurs in a zone. It goes out after the FACP is reset. Fault/Disable: Yellow. It flashes when there is any fault with the zone. If all devices in this zone are disabled, the LED illuminates steadily. It goes out after the trouble is cleared or the FACP is reset. b) The key of a zone is used to activate/silence sounder strobes in the zone.

3.1.4.2 Device Operations a) b) Command LED: Red. It illuminates when start command is given and goes out when stop command is given or the FACP resets. Key: Pressing it can start a device. If a device is started, pressing this key will stop it.

3.1.4.3 Operations of SILENCE Key: a) b) Command LED: It lights after the key pressed. If new alarm comes, the FACP is reset or SILENCE key is pressed again, the LED goes out. Key: Press the key in alarm state to silence all sounders, press again to resume them.

3.2 Configuration

3.2.1 Typical Configuration A typical FACP consists of main board, loop interface board, power supply, display area, and zone indication and manual intervention panel (ZCP). Main board Main board is the core of the FACP, which contains CPU and interfaces to other main parts and optional parts. Loop interface board It is signal interface board of the FACP, which has communication port, detecting port, fire alarm output port, fault output port etc. The loop interface board connects field devices and the FACP into a complete fire alarm system. Loop module The loop module provides an interface for Class A loop detection.

Page 9

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) Power supply

The Intelligent Solution

It provides power to the main board, loop interface board and printer. Its backup feature ensures that devices registered during commission are not lost in case of power fault. Display and operation part This part is used to indicate and display different status of the system, and enables relative operations through keypad (browsing, setting, printing and etc). Zone indication and manual intervention panel (ZCP) The ZCP can indicate fire alarm, fault/disable state of corresponding devices, and start and stop them accordingly. 3.2.2 Optional Units Fireman's Control Panel (FCP) Fireman's Control Panel is designed for controlling some important devices in the system like fire pump, smoke exhauster and blower. Fireman's Control Panel of the FACP can control at most 10 equipment by option. It can control at most 5 for equipment needing both start and stop. The panel can check short circuit and broken circuit with corresponding audio and visual indications, which can ensure the reliability of connection between the control panel itself and important devices as much as possible. Printer It is a built-in micro printer. With dot matrix printing it can print 96 kinds of ASCII code characters (capital or lower case of Latin letters, figures and symbols), 128 coded non-standard characters and chart symbol (some Chinese characters, Greek letters, block symbol etc.), and 16 code characters (6×7 dot) which can be defined by the user through program, and replace any code font by commanding, so as to print characters of different language. Communication card The FACP provides a multi-functional communication port, connecting with network cards to realize networking among GST series fire alarm control panels, to form urban fire alarm supervisory network through public telephone network and to fulfill graphic supervision by connecting with GUI system in the control center of buildings. The control panel watches network cards running in real time, that is, the cards can take effect as inserted. The FACP can provide two kinds of network cards: Local Network Card, Monitor & Control Card. Their structures are shown in Fig. 3-5.

Page 10

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Fig. 3-5 1 20P data cable connecting with main board. 2 Red LED, lit when receiving signals. 3 Green LED, lit when sending signals. 4 RS-485 network communication cable (A and B). 5 20P data cable connecting with main board. 6 Standard RS-232 interface connecting with GUI. Note: You need to purchase a RS-232 card for your first order of GST200. Only with this card, device definition and C&E equation can be downloaded from PC.

3.3 Field Devices

3.3.1 A Series of Intelligent Fire Detectors GST 200 can connect with a series of fire detectors, such as I-9102, I-9103, and I-9105R. The detectors mounted in the protected area transmit monitoring message to the control panel through ring detection loop. Every detector has its own address with which the control panel can supervise the information of alarm, fault, and normal status of the detectors. 3.3.2 Modules Used together with addressable input module I-9300 and addressable single I/O module I-9301. I-9300 module receives the signal of normally open switching signal, and transmits the information to the control panel (This type of FACP is able to activate the connected devices). I-9301 single I/O module connects with the devices controlled by the control panel, such as smoke exhauster, fan blower and fire valve. It can also receive the auto-feedback signal from these devices. 3.3.3 Loop Isolator Loop Isolator can disable the shorted part of loop from the whole system to ensure normal operation of other devices and to ascertain the location of the part in fault. After the fault is

Page 11

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution repaired, the loop isolator can automatically reset the isolated part and include it into the system. 3.3.4 Manual call points A series of manual call points (such as I-9202) can be connected with the loop of GST200. When fire is confirmed manually, press the glass on the MCP, alarm signal can be sent to the control panel. After receiving the alarm signal, the control panel will show the number and location of the MCP, and sound alarm. 3.3.5 Addressable sounder strobes Addressable sounder strobe is a kind of audible/ visual alarm device installed in field, which can be activated by fire alarm control panel in fire control center or by manual call point installed in field. A series of GST addressable sounder strobes (such as I-9403) can be connected to the loop of GST200. Being activated, it will generate strong audible/ visual alarm signal to warn people in field. 3.3.6 GST852RP Repeater Panel GST852RP Repeater Panel is designed with a microprocessor. When one or more detectors alarm fire, the repeater panel can display the address and information of the detectors and send out audible and optical signals. Through communication loops, it can be connected with fire alarm control panels, disposing and displaying the data transmitted from the control panels. When monitoring several floors or several zones with one fire alarm control panel, a repeater panel on each floor or in each zone can replace zonal fire alarm control panel.

3.4 Configuration (C&E Equation and Devices) Software

The software owns the functions of editing and downloading definition of device and C&E equation. Before the system starts operation, you need to define the device and C&E through configuration software via computer. Then download to the control panel.

Page 12

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Chapter 4 Mounting

Please follow the steps below to mount the GST200: 1 Check if you have received all items you ordered. 2 Mount the FACP. 3 Power up the FACP and carry out power-on inspection. 4 Connect field devices. 5 Inspect circuits and register devices. 6 Define the devices and download them to the control panel through the configuration software by PC according to engineering configuration. 7 Edit C&E equations and download them to the control panel through the configuration software by PC according to engineering configuration. 8 Commission and inspect field devices.

4.1 Configuration Inspection

Before installation, check the appearance of GST200 for the following items: Check Engineering Configuration Check the configuration according to packing list. The main items to be examined are: installation and operation manual, keys to the control panel, etc. Check Internal Configurations and Interconnection of the Control Panel All internal parts have been connected completely (including optional units) before the control panel leaves the factory. Therefore, mainly check the following items: zone indication and manual intervention panel and power supply. Check the connection among parts, including the connection between main board and power supply, switch board and loop interface board, zone indication and manual intervention panel with switch board, speaker and main board etc. Please refer to Appendix 1.

4.2 Mounting Cabinet

Dimension of the cabinet is shown in Fig. 4-1. Ambient Temperature: 0 Relative Humidity 95 +40 , non-condensing.

Page 13

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Fig. 4-1

4.3 Start-up Check

After installation, apply power to the FACP as shown in Fig. 4-2. Turn on the main and standby power supply in the cabinet and check if the control panel can self-test. The procedures are as follows. If the digital displays showing time illuminates one by one. If the LCD showing system messages such as fire alarm illuminates. If the LEDs showing the state of system illuminates one by one. If the LEDs showing the device state in ZCP illuminates in turn. If the speaker can give loud fire alarm sounds.

Power

AC Power

Switch

Fig. 4-2

Page 14

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

4.4 Connections of Field Devices

Caution: Do not connect power to your device until you have completed all input and output connections. Failure to do so may result in injury! GST200 connects with field devices by loop interface board. Terminals of loop interface board are shown in Fig. 4-3.

Fig. 4-3 CLASS CHANGE (XT3): Short it to make the sounders output. FAULT OUTPUT (XT8): The normally open contact is closed when fault condition occurs, and disconnected when the control panel repairs fault automatically. SOUNDER CIRCUIT OUTPUT (XT7): It outputs when there is fire alarm. It can be stopped by pressing "SILENCE" key on ZCP. Output can be disabled, and there is no output after disabled. The control panel will report fault when connected cable in short or open circuit. F.P.E. OUTPUT (XT6): It outputs when there is fire alarm. It can be disabled, and does not output when fire alarm occurs in disabled state. The control panel alarms fault when connected cable in short or open circuit. FIRE ALARM OUTPUT (XT5): It outputs when there is fire alarm and should give fault signals when connected circuit is shorted or opened. LOOP BUS (XT2, XT4) It can be connected with 235 coded points. With loop isolator in Class A loop, the detector protected by loop isolator is not missing when Page 15

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution there is short or open circuit. In this case, the control panel reports fault. RS-485 (XT11, XT12): To be connected with repeater panel and control panel. earthX8: This terminal is for checking earth fault when there is short circuit. F.P.E. OUTPUT, SOUNDER CIRCUIT OUTPUT and FIRE ALARM OUTPUT can provide three output modes: 24VDC active output , normally closed output and normally open output. You can set up the three modes through Pin X1 X7 according to Table 4-1. Table 4-1 Output F.P.E. Output Sounder Circuit Output Fire Alarm Output 24VDC Short 1 to 2 & 4 to 5 of X3. Short X7. Short 1 to 2 & 4 to 5 of X2. Short X6. Short 1 to 2 & 4 to 5 of X1. Short X5. Normally Closed Short 3 to 4 & 5 to of X3. Disconnect X7. Short 3 to 4 & 5 to 6 of X2. Disconnect X6. Short 3 to 4 & 5 to 6 of X1. Disconnect X5. Normally Open Short 2 to 3 & 5 to 6 of X3. Disconnect X7. Short 2 to 3 & 5 to 6 of X2. Disconnect X6. Short 2 to 3 & 5 to 6 of X1. Disconnect X5.

4.4.1 Connection of Sounder Circuit Output Connection of SOUNDER CIRCUIT OUTPUT is shown in Fig. 4-4.

SOUNDER CIRCUIT OUTPUT (XT7)

Diode Sounder

Diode Sounder

Terminal Resistor 4.7k

Fig. 4-4 Instruction: Remove the terminal resistor and keep it well. Connect the cable in correct polarity. Add a 4.7K resistor to the end of each circuit. NOTE: The sounder strobes are polarity sensitive. Note polarity in connection. The maximum current of the circuit depends on the number of sounder strobe. Do not overload. 4.4.2 Connection of F.P.E. Output F.P.E. output is shown in Fig. 4-5.

Page 16

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

FPE OUTPUT (XT6)

Diode FPE

Diode F.P.E.

Terminal Resistor 4.7k

Fig. 4-5 Instruction: Remove the terminal resistor and keep it well. Connect the cable in correct polarity. Add a 4.7K resistor to the end of each F.P.E output loop. NOTE: F.P.Es are polarity sensitive. Note polarity in connection. The maximum current of the circuit depends on the number of F.P.E. Do not overload. 4.4.3 Connection of Fire Alarm Output Fire alarm output is shown in Fig. 4-6.

Diode FIRE ALARM OUTPUT (XT5) Fire Monitoring Device Fig. 4-6 Instruction:

Diode Fire Monitoring Device

Terminal Resistor 4.7k

Remove the terminal resistor and keep it well. Connect the cable in correct polarity. Add a 4.7K resistor to the end of fire alarm output loop. NOTE: Fire supervisory devices are polarity sensitive. Note polarity in connection. The maximum current of the circuit depends on the number of fire supervisory device. Do not overload. 4.4.4 Connection of Class A Loop A Class A loop is shown in Fig. 4-7.

Page 17

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

LOOP OUT (XT4)

Loop Isolator

Addressable field devices

LOOP IN (XT2)

Loop Isolator

Addressable field devices

Fig. 4-7 Note: Every loop isolator can control up to 32 detectors. 4.4.5 Connection of Communication Loop

FACP

Network (XT11)

Up to 32 control panels

B

Repeater (XT12)

Up to 10 repeater panels

B

Fig. 4-8

4.5 Connection Inspection and Device Registration

4.5.1 Connection Inspection Check the circuit connected with the control panel. Insulation resistance measured at different circuits and ground should be more than 20M, the resistance in the detection loop should be more than 1k. The resistance among fire alarm output, sounder circuit output, F.P.E. output should be equal to terminal resistor.

Page 18

Repeater

A

Repeater Repeater Panel

FACP

A

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) 4.5.2 Registration of Devices

The Intelligent Solution

Pressing SYSTEM and inputting super password followed with ENTER system setting menu will appear. After re-started, the control panel will register the devices automatically. Please check if the number of devices, programming, and operation state in compliance with the project design and remove any problems.

4.6 Definition of Devices

Please define devices and C&E equation by configuration software (GST-DEF) via a PC, and download the definitions to the control panel. 4.6.1 Installation 4.6.1.1 Configuration Requirement Recommended Configuration: Pentium III 600 CPU or above, 256M memory or above, 1G or above hard disk available space. Operating System: Win98, Win2000, WinXP. 4.6.1.2 Software Installation The setup file of GST-DEF software is named Setup.exe. Double-clicking this file and following the installation wizard will install it into your PC. 4.6.1.3 Connection of PC with the FACP The software can work offline for defining in the office, only connecting to the panel for downloading the definition. The definition download needs a RS232 communication card. Connect the 232 card to the extend port of the FACP main board using ribbon cable (Fig. 4-11) and connect it with the PC using a 3-core shield cable with DB9F plugs at both ends. The 3-core shield cable is made as in Fig. 4-9. Maximum length of the cable is 15m. The connection is shown in Fig. 4-10.

Fig. 4-9

5 9

232 Card

Upload/download device definition and C&E equation Pin 2 Sending data Pin 3 Receiving data Pin 5 GND

4 8 3 7 2 6 1

Fig. 4-10 Page 19

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) 4.6.1.4 Registering the 232 communication card

The Intelligent Solution

After connecting the PC and the FACP, you need to register the 232 card from the FACP for proper download of the definition. Turning on the AC and battery switch of the FACP and entering system setting screen by pressing SYSTEM key and inputting Manager password, and then pressing the reset key SK1 on the main board (Fig. 4-11) will reboot the FACP and re-register all system devices including the 232 card. Completing the registration, you are ready to define the devices.

Fig. 4-11 Toolbar of GST-DEF Software The toolbar of the software is shown in Fig. 4-12. corresponding windows. Clicking the icons will enter

Fig. 4-12 Com Set is for setting the communication port. Its screen is as in Fig. 4-13.

Fig. 4-13

Page 20

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Com Test is for testing if the communication with the FACP is normal. The screen is in Fig. 4-14.

Fig. 4-14 In which, TestCount refers to the times of the testing. Successful means the number of successful communications. Failed is the number of failed testing. Timeout Factor is the communication timeout, programmable from 200ms to 2000ms. Log is a system reserved button not available for the users. Communication Detail lists the details of the communication messages. Database is used for database backup and recovery, whose operation screen is in Fig. 4-15.

Page 21

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Fig. 4-15 Backup Database: You can use this button to regularly backup the database in order to avoid loss of data. The backup data is saved by default into a folder named "backup" under the directory where the software is installed. Restore Database: Clicking this button can restore a database to the previously saved version. Rebooting the program is required to make the restored database valid. DevType is for adding device type. There are 67 types by default. The screen is shown in Fig. 4-16.

Fig. 4-16 Clicking "Browser...", the system pops up a dialogue box as in Fig. 4-17 for choosing the device type you want.

Page 22

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Fig. 4-17 Save: Pressing this button after adding or modifying a device type or icon will save the modification. Cancel: Pressing this button can cancel the current operation in case some urgent operation is needed while downloading or uploading large batch of device definitions. Exit system is used for exiting the software. Operation Screens System navigation tree provides a shortcut method for adding and deleting control panels, switching and setting among different panels (Fig. 4-18).

Fig. 4-18 Every node provides corresponding operations. At FACP level, the system displays the FACP type and number. Right-clicking the FACP, the following menu will pop up.

Page 23

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Fig. 4-19 The user can set communication port, test communication, export devices and equations, set FACP title, or delete this FACP. Under FACP Zone, the user can add or delete zones. Adding FACP Right-clicking FACP node, a menu for adding FACP will show. Clicking the option, a dialogue box as in Fig. 4-20 will show.

Fig. 4-20 FACP Name: You can key in descriptions to this FACP, or leave it blank. FACP Address: The address shall not be the same as other FACPs. FACP Type: The type of this FACP is named GST200EN. FACP Network: Ticking this option means the FACP is networked. Start Zone: This is the starting zone number of this FACP in network. Zone Definition 4.6.1.5 Use of Zone Definition By zone definition, you can define devices of a certain area (such as a large room) as one

Page 24

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution zone, and describe the features of the zone clearly through "Description". When the devices in the zone are in fire alarm, fault, action or disabled state, the FACP shows not only the abnormal messages, but also zonal messages and address of the device, so that the operators can find out the specific location and take effective measures. You will have to define zones before defining devices because a device must be in a zone. Clicking <FACP Zone> and choosing a FACP, the screen displays all zones of this FACP. Clicking the zone number you can view all devices of the zone as in Fig. 4-21.

Fig. 4-21 4.6.1.6 Adding Zones Clicking <New> a new zone will appear in the zone list. The GST200 can have at most 30 zones. You can briefly describe a zone in "Description" column using maximum 8 characters including letters, numbers and marks. Note: The defaulted zone background color is white, and font color is black. Different zones can be set with different colors, which make the zones distinct. 4.6.1.7 Deleting a Zone Choosing a zone (highlighted) and pressing the <Delete> button will delete this zone. 4.6.1.8 Downloading and Uploading Pressing <UploadAll> or <DownloadAll> will upload or download all zones. Choosing one or more zone and clicking <Upload> or <Download> will upload or download specific zone or zones. 4.6.1.9 Saving Zone Definitions Clicking <Save> will save all definitions. 4.6.1.10 Reloading Zones Pressing <Reload> will restore the zone definitions to the previously saved version. All modifications not saved will lose.

Page 25

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) Definition of Loop Devices 4.6.1.11 Use of Device Definition

The Intelligent Solution

The software can define device address, type, location description, zone and loop with which system operator can quickly locate the zone where fire alarm and fault condition occur. 4.6.1.12 Device Definition Clicking <Loop 001> under GST200EN in FACP Net column will enter the screen for defining loop devices Fig. 4-22 shows the screen after device definition. The GST200 panel has only one loop defaulted as "Loop 001".

Fig. 4-22 In the above screen, <Address> is the code of the device. <Device Number> is the 6-digit device number (zone number +code). There shall not be the same device numbers in a system (even in the network). <Loop> shows the loop number of the device. <Zone>: You can choose the zone number from the drop-down menu. <Device Type>: Choosing device type from the drop-down menu. Please choose compliant types. For type of modules is subject to the actual device they are connecting with. For example, the type of a module addressed 17 connecting with a fire door shall be 28-FireDoor. Please refer to Appendix 2 for the device type list. <Properties>: The output mode (level or pulse) can be chosen from the drop-down menu for sounders and output modules as in Fig. 4-23.

Page 26

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Fig. 4-23 Choosing "1-Level" means the device continuously output until it's manually stopped or the system is reset. Choosing "2-pulse" means the output is by pulse which is able to keep steady for 10 seconds (1 pulse). <Location>: You can describe the location here using maximum 32 characters including letters, numbers and marks. Note: The following addresses are reserved for the panel itself.

Fig. 4-24 238: Fault output, which is started when there is fault with the system. 239: Loop checking, which is started if the FACP cannot find the test voltage at the input terminal of Loop 001. 240: Sounder output, which is started when the FACP receives fire alarm. This output is used for connecting with conventional sounders. It can be silenced by the SILENCE key on the ZCP. 241: F.P.E. (Fire Protection Equipment) output, started when the FACP receives fire alarm signal. This output is used for connecting with fire protection equipment and cannot be silenced by the SILENCE key on the ZCP. 242: Fire alarm output which is started on receiving a fire alarm. This output is used for remote display of a fire alarm. It can be silenced by the SILENCE key on the ZCP. 4.6.1.13 Downloading and Uploading Device Definition Same as downloading and uploading zone definition, all or some specific loop device definitions can be uploaded and downloaded using corresponding toolbar buttons. 4.6.1.14 Device Checking Clicking the <Check> button, the system will check if the definition is correct. For example, there should not be duplicate device numbers, if so, the system will pop up an indication. You can then manually modify the 4th to 6th digit to make the number unique in the system.

Page 27

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) 4.6.1.15 Reloading Device Definitions

The Intelligent Solution

Clicking <Reload> will restore the device definitions to the previously saved version. All modifications not saved will lose. Defining Repeater Panels 4.6.1.16 Use of Repeater Panel Definition The software can define the location repeater panels. Therefore, in case of any fault with a repeater panel, the operators can find out its location and take measures in time. 4.6.1.17 Defining Repeater Panels Clicking <Repeaters> will enter the screen for defining repeater panels as in Fig. 4-25.

Fig. 4-25 GST200 can have at most 10 repeater panels. The description (Max. 8 characters) can be downloaded to the FACP. The FACP can display the description to the repeater panels in case of fault with it. This definition is not a necessary step. Even if the repeater(s) are not defined, The FACP will still work normally. Defining ZCP 4.6.1.18 Use of ZCP Definition By defining the ZCP, you can start corresponding field devices by keys on the panel, displaying LEDs. Each key/LED units can be defined for one of the following three purposes: Zone Indication, Start One Device or Silence. Silence: One of the units, usually put at the right bottom, can be defined as the silence key for all zonal sounders, which will re-sound on new fire alarms. Zone Indication: some units can be defined as the zonal indication for fire (red LED illuminates steadily), fault (yellow LED illuminates steadily) or disable (yellow LED flashes), while pressing the key will activate all sounders of the zones. Please note that by EN54 standard, "Zone Indication" key must be defined for each zone and one "Silence" key for the whole system. After definition of these Page 28

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution keys, if there are still some undefined keys, you can define them as "Start One Device" for starting field devices. Start One Device: This option will only be valid for associated output devices. Pressing the key will start a device, and the second press will stop it. This is an optional feature only. 4.6.1.19 Defining ZCP Clicking <ControlSwitch> will enter the screen for defining the ZCP as in Fig. 4-26.

Fig. 4-26 The above screen lists all 32 ZCP keys to be edited by the user: To Define a key as "SILENCE", you can click a cell under "Functions" and choose "Silence" from the drop-down list. To define a key as "Zone Indication", you can click a cell under "Zone to Display" and choose a zone from the drop-down list. The "Function" cell changes to "Zone Indication", and the background color will also change to what you defined for this Page 29

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution zone. To define a key as "Start One Device", you can click a cell under "Address of Device to Start" and choose the device address and description from the drop-down list. The "Function" cell changes to "Start One Device" and the background color will also change to what you defined for this zone. Editing "Description": Clicking a cell under "Description", you can key in or choose from the drop-down list(if available) the description to this key. But this message is only saved in the PC and cannot be downloaded to the FACP. 4.6.1.20 Uploading, Downloading and Saving ZCP Definitions After ZCP definition, you can upload or download single, multiple or all defined entries by dragging the mouse. Please remember to save your modifications during definition. 4.6.1.21 Reloading ZCP Definition Clicking the "Reload" button will restore the ZCP database to the previously saved version. Please note that all modifications after the "Save" operation will lose! Defining Cause and Effect (C&E) Equation 4.6.1.22 Use of C&E The FACP can define under what conditions fire alarm or suppression devices have to be started. So please define C&E equation after defining devices. Note: Please define C&E equation after completion of device definition. 4.6.1.23 Defining C&E Clicking <Equations> under navigation list will enter the screen for defining C&E as in Fig. 4-27.

: ??

Page 30

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Toolbar for C&E definition

Toolbar for uploading and uploading C&E

Fig. 4-27 Toolbar for C&E definition: <New Equ>: Adding C&E. <Insert Dev>: Adding devices into conditions or results. <Delete Dev>: Deleting devices from conditions or results. <Save Equ>: Temporarily saving the current equation. <Save as New>: Adding similar equations into temporary database. Toolbar for uploading and downloading C&E equations: <Upload>: Uploading equation to PC. <Upload All>: Uploading all equations from FACP to PC. <Download All>: Downloading all equations from the PC. The equations must be downloaded together. They cannot be downloaded one by one. <Delete>: Deleting a selected equation. <Save>: Saving all equations into database. Please save the equations after they are all defined. <Reload>: Restoring to the previously saved version. The number of devices in the conditions and results shall not exceed 10. If they exceed, please divide them into two equations. 4.6.1.24 Defining New Equations Clicking a cell under<Devices> of <Condition Devices> or <Effect Devices>, it will become editable. You can then manually input the device number. An easier way is double-clicking the cell and the list of the defined device will pop up. Choosing the Page 31

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution devices and double-clicking the cell again or clicking <OK>, the device will be in the cell (Fig. 4-28). If multiple devices are needed in the condition, you can click <Insert Dev> to add devices. Pressing <Relation> can set the relationship between devices, where + means "or" and "x" means "and". The operation for adding multiple devices to the effect side is the same as condition side. Delay time is editable to each device in the effect side. The unit for delay time is 10 seconds, and the maximum delay time is 10 minutes (600 seconds). For example, 6 means the delay time is 1 minute (6 10 60s).

Fig. 4-28 Clicking <Save Equ>, the newly defined equations will be added into the list at the bottom of the screen. You can then edit the next equation. 4.6.1.25 Fogging Devices You can also define devices of the same type using the "Fuzzy" option. Double clicking the cell under <Device>of <Condition Devices> or <Effect Devices>, the system will pop up the list of defined devices. Ticking the "Fuzzy Devices" option below the list will enable device fogging. By choosing the "Zone" and "Dev Type" options, you can quickly define C&E equations (Fig. 4-29).

Fig. 4-29 For example, <Zone>=01 & <Dev Type>=03 refer to any detector in Zone 1, and <Zone>=02, <Dev Type>= Any Type refer to any device in Zone 2.

Page 32

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution After choosing devices by fogging the zone and device type, you can go on to choose the number of devices. Please note that the relationship among all these devices is "and".

Fig. 4-30 For example, if <Device QTY>=2, then the condition is only met after any two of the selected devices alarm. 4.6.1.26 Rules for Display Specific devices (number starting with the letter "G") The 2nd and 3rd digits are for zone number. The 4th, 5th and 6th are for detector code. The 7th and 8th are for device type. For example, G0207503 refers to a photoelectric detector in Zone 2 whose code is 075. Fuzzy devices (number starting with the letter "S") The 2nd and 3rd digits are for zone number and "**" means any zone. The 4th, 5th and 6th digits are used for specifying the quantity of fuzzy devices which are displayed under <Device QTY>. The 7th and 8th digits are for device type, and "**" refers to devices of any type. For example, S0100203 refers to any two photoelectric detectors in Zone 1. Output devices can also be fogged 4.6.1.27 Editing Existing Equations Double-clicking the ID number of an equation from the list at the bottom of the screen in Fig. 4-29, you can edit it in the dialogue box popped up. then all compliant devices will be started.

Periphery Device Commission

System commission can be carried out after cables are connected, devices are defined and C&E equations are defined and downloaded and the final checking are done. The following steps are for your reference: 1. Fill and stick the ZCP labels corresponding to what have been defined. 2. Test all detector and check their locations. 3. Check device definition and modify improper parts. 4. Check and test C&E equation and modify improper parts.

Page 33

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Chapter 5 Display and Disposal of System Information

GST200 can be started after mounting according to Chapter 4. Turning on the external power switch, and main and standby power switch on the control panel, it starts power-on self-test and enters monitoring state. The system displays properly if it is in normal state, or the system displays improperly.

5.1 Normal Information

The normal display is shown in Fig. 5-1, which means the system is in working state. Then only POWER HEALTHY LED is lit.

GST CO., LTD SYSTEM ALL NORMAL

Working

Fig. 5-1

5.2 Fire Alarm

5.2.1 Screen of Fire Alarm FIRE LED is lit when there is fire alarm signal. Speaker of the control panel sounds (fire truck sound), and corresponding FIRE LED on the ZCP is also lit. (1) Fire alarm screen is shown like Fig 5-2 in zone display mode.

001 0f 002 ! FIRE! 10:18 Zone:003 floor3 Office3 Last! Fire! Zone: 003 Floor3 office3

Fig. 5-2 001 0f 002! FIRE! 10:18 // It means there are fire alarm signals in two zones and this is the first entry. Zone:003 floor3 description of the zone. Office3 // It means the number of zone with fire alarm and

// It is the description of the device with fire alarm signal.

Page 34

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Last! Fire! Zone: 003 // Zone number of the earliest fire alarm Floor3 office3 fire alarm. // Description information of the zone and device for the earliest

(2) Fire alarm screen for loop display mode is shown in Fig. 5-3.

001 0f 004! FIRE! 10:18 Zone:003 009Optical Office3 Last! Fire! Zone: 003 Floor3 office3

Fig. 5-3 001 0f 004! FIRE! 10:18 // It means there are four devices with fire alarm signals, this is the first entry. Zone: 003 009Optical // The number of zone with fire alarm and type and address of the device in fire alarm. Office3 // Description information of device in fire alarm // Number Zone where the earliest fire alarm occurs

Last! Fire! Zone: 003 Floor3 office3 alarm.

// Description of zone and device information of the earliest fire

Note: If this FACP is networked with other FACPs, then the displayed zone number here will be the defined device zone number + the starting zone number for this FACP (please refer to descriptions in Section 6.4.4). 5.2.2 Disposal of Fire Alarm Signal When fire alarm occurs, first find out the location according to the information shown on the control panel to verify whether the fire really happened. If it's a real fire, please take corresponding measures. Step 1: Evacuate the people in field. Step 2: Call the fire office. Step 3: Initiate extinguishers. If it is a false alarm, please take the following measures. Step 1: Press SILENCE to stop the sound. Step 2: Remove the factors that caused the false alarm. Step 3: Press RESET to make the control panel back to the normal state. If the device

Page 35

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution still gives false alarm, disable it and inform the installer or manufacturer for repair.

5.3 Fault Information

5.3.1 Screen of Fault Information When there are fault signals, different LEDs can be lit according to the type of fault. If it is mains fault, AC FAULT LED will be lit; if it is standby power fault, BATTERY FAULT LED will be lit; if it is system fault, SYSTEM FAULT LED will be lit; if it is field device fault, relative LED on the ZCP will flash. The speaker of the control panel gives alarm sound (ambulance sound). (1) Fault screen for zone display mode is shown in Fig. 5-4.

001 0f 002 FAULT10:18 Zone: 003-floor3 Office3

Fig. 5-4 001 0f 002 FAULT10:18 // It means there are fault signals in two zones, this is the first entry. Zone: 003-floor3 Office3 // The zone with fault and its description

// Description information of device with fault signals.

(2) Fault screen for loop display mode is shown in Fig. 5-5.

001 0f 004FAULT10:18 Zone: 003-011Optical

Fig. 5-5 001 0f 004 FAULT10:18 // It means there are four devices with fault signals, this is the first entry. Zone: 003-011Optical // Zone number where the fault exists and the type and address of the device with fault signals. Note: If this FACP is networked with other FACPs, then the displayed zone number here

Page 36

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution will be the defined device zone number + the starting zone number for this FACP (please refer to descriptions in Section 6.4.4). 5.3.2 Disposal of Fault Information There are two kinds of fault. One is system fault like mains and battery fault, and loop fault. The other is field device fault, like detector and module fault. If the system is battery powered, please charge the battery in time to avoid damaging it. If the battery has powered the system overtime, the control panel will shut down for protection. If it is system fault, please check and repair in time. If the panel needs to be shut down, please make detailed records. If it is field device fault, please repair it immediately. You can temporarily disable it if the fault cannot be cleared for some reason, and enable it again when it's repaired.

5.4 Rules for Message Display

If there are multiple messages in the system, they will be displayed in the following order: fire alarm, action, fault, start, disable. 1 2 3 The earliest fire alarm is displayed in priority. The latest action, fault, disabled message is displayed in priority. There are zone and loop display modes for fire alarm, fault, and disabled messages but start and action only has loop display mode. In any display mode, the system will return to displaying message of the highest priority if there is no operation within 20 seconds (15 30seconds).

5.5 Rules for Sound Indication

The FACP will sound to indicate fire alarm or fault messages. The FACP gives fire truck sound when fire alarm occurs. The FACP gives action sound when any device is activated. Module action: --slow "tick" sound. Gas extinguishing device action --police car sound. Delayed activation of devices by automatic C&E equation--quick "tick" sound. The FACP gives ambulance sound when fault occurs.

Page 37

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Chapter 6 Description of System Operation

6.1 Keypad

6.1.1 Functions Most of the keys have double functions. Lower mark is a character and upper mark is a command that is only activated in monitoring state. Most functional keys are controlled by password. The characters are only active after entering the menu. Pressing ESC will return to the previous level of the menu. 6.1.2 Methods of Data Input Pressing a character key all characters disappear, and the display shows the newly input one. The cursor will indicate the next input position (The cursor always indicates the position of the next to input, and returns to the first character after completion of a line). Pressing or can move the cursor to modify any character.

Pressing TAB, the highlight moves to the next position and returns to the first after the last position. Wherever the cursor is, Pressing ENTER key, all the input data will be saved. If there is no keypad operation for over 1 minute, the system will exit present state without saving the input data. 6.1.3 Unlocking and Locking the Keypad Unlocking the Keypad The control panel is locked by default when powered up. If some operations are needed, the LCD will display a screen requiring proper password. Inputting the correct password and pressing ENTER, you can continue to operate as the keypad is unlocked (Fig. 6-1).

GST CO., LTD Please Input Password ******** 8 digits

Fig. 6-1 Locking the Keypad Please lock the keypad after operations are finished or personnel on duty leave. Pressing LOCK, the screen will display "Press ENTER confirm" like in Fig. 6-2. Pressing ENTER, the keypad is locked. You will have to input password again to unlock the keypad for any new operation.

Page 38

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

GST CO., LTD

Press ENTER confirm

Fig. 6-2

6.2 User Operation Instruction

6.2.1 Changing time display The clock is usually displayed in hour and minute. In normal monitoring state, press ENTER, month and date are displayed. Press ENTER again or after a minute, hour and minute is displayed again. 6.2.2 Browsing 6.2.2.1 Turning pages You can view messages one by one by pressing " " and " ".

6.2.2.2 Browsing more than one piece of information The current information is highlighted when there are more than one message on the LCD. You can view its details by pressing ENTER or you can exit by pressing ESC. When the printer is set as "All History" mode, the present displayed message can be printed by pressing PRINT while browsing. 6.2.2.3 Setting LCD contrast and viewing C&E equation Pressing SCREEN, the system enters the screen for setting LCD contrast and display mode and browsing C&E equation, as shown in Fig. 6-3.

Display Mode

1 LCD Contrast 2 Browse Mode 3 Browsing C&E

Fig. 6-3 From the above screen, you can operate as follows: Inputting number 1, you can enter the screen for setting LCD contrast (Fig. 6-4).

Page 39

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) and are for increasing and decreasing LCD contrast.

The Intelligent Solution

GST CO.,LTD

*LCD Contrast* 90

Fig. 6-4 Input number 2, you can enter the screen for setting browse mode, as shown in Fig. 6-5. "1" is for zone mode, and "2" is for loop mode.

Browse Mode

1 Zone Mode 2 Loop Mode

Fig. 6-5 Input number 3, you can enter the screen for browsing C&E equation (Fig. 6-6). The highlighted message is the current message. You can scroll between different messages by pressing SCROLL. You can view further messages by pressing ENTER, or exit by pressing ESC. Browse C&E Sum: 003 C&E 001 C&E 002 C&E 003

ENTER

Browse C&E C&E 001 G0100103 G0100203+G0100203 G0100303 G0100103 G0100303 G0100103 G0100203 G0100303 G0100413 00 Fig. 6-6

The part before " " is the condition and that after it is the result.

Page 40

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) "×" means "and", and " " means "or". A condition is composed of the following items:

The Intelligent Solution

Device type Device address/Quantity of events defined in special condition Zone number of the device G: General conditions S: Special conditions General Condition: A device can be activated if its zone number, code and device type are correct. Special Condition: Both zone number and device type can be defined. If events with the same zone number and device type reach a defined number, this special condition comes into effect. Asterisk wildcard "*" represents any number used in special conditions. Event: It is the message generated by the FACP when there is fire alarm or action of device. A result is composed of the following items.

01 004 13 00 Delay time Device type Device address Zone number of the device 6.2.2.4 Browsing registered devices Pressing BROWSE can enter the screen for viewing registered devices, as shown in Fig. 6-7.

Browse 1. Active Equipment 2. COM Equipment 3. Access

Fig. 6-7 Input number 1, you can view loop devices. The display mode depends on what you have, loop mode or zone mode. a) Zone display mode is shown in Fig.6-8.

The present message is highlighted and can be chosen by pressing SCROLL. Press Page 41

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) ENTER for further messages and ESC for quitting.

The Intelligent Solution

Browse 03 Zone Zone:01 Zone:02 Zone:03

(012) Sum:004 Sum:004 Sum:004 Browse Zone: 01 Sum: 004 NO.001 Optical NO.002 Optical NO.003 Optical NO.004 Sounder

ENTER

ENTER

Browse Zone: 01 office1 NO.001 Optical Sensitivity: Nominal Office1

Fig. 6-8 Zone: 01 office1 // zone number, description of zone location. NO.001 Optical // address and type of the device. Sensitivity: Nominal // prosperity of the device. Office1// Description of device location. b) Loop display mode is shown in Fig. 6-9.

The present message is highlighted and can be chosen by pressing SCROLL. Press ENTER for further messages and ESC for quitting.

Page 42

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Browse Sum 012 NO.001 Optical NO.002 Optical NO.003 Optical NO.004 Sounder

ENTER Browse Zone 01 office1 NO.001 Optical Sensitivity Nominal Office1

Fig. 6-9 Zone: 01 office1 // zone number, description of zone location. NO.001 Optical // address and type of the device. Sensitivity: Nominal // device property. Office1 // Description of the device position Input number 2, you can view FACPs and repeater panels in network. Input number 3, you can view definitions to ZCP keys as in Fig. 6-10.

Browse Sum: 32 NO.01 Silence key NO.02 Zone 01 NO.03 004 Sounder

Fig. 6-10 Sum: 32 // The total number of keys on the ZCP. // Define key No. 1 as "Silence" key. // Define key No. 2 as zone 1.

NO.01 Silence key NO.02 Zone 01

NO.03 004 Sounder // Define key No. 3 as sounder whose start-up address is 004.

Page 43

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) 6.2.2.5 Browsing history log

The Intelligent Solution

Pressing LOG, the FACP enters the state of browsing history record. Using can browse every entry, the screen is shown in Fig. 6-11. History Record NO. 200 ! FIRE! TIME: 10:23 14/08 Zone: Name 121 Optical

and

, you

Fig. 6-11 NO. 200 ! FIRE! // The two hundredth history log // Fire alarm message

TIME: 10:23 14/08 // Date and time of the event Zone: Name 121 Optical // Zone number, zone name // Device address and type

6.2.2.6 Browsing fault messages You can view fault messages by pressing VIEW FAULT when the screen is displaying non-fault messages. The display varies by the type of fault messages. Please refer to Section 5.3. 6.2.2.7 Browsing disable messages You can view disable messages by pressing VIEW DISABLE when the screen is displaying non-disable messages. The screen of loop mode is shown in Fig. 6-12 and the screen for zone mode is shown in Fig. 6-13 and Fig. 6-14. 001 of 003 Disable 12:01 Zone 001 004Sounder Office1

Fig. 6-12 001 of 003 Disable 12:01 //There are three disabled devices in the system and this is the first.

Page 44

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Zone: 001 004Sounder //The zone number, address and device type of the disabled device. Office1 //Description message of the disabled device.

001 of 002 Disable 12:01 Zone 005 Z-005 029/029 Zone Fully Disabled

Fig. 6-13 001 of 002 Disable 12:01 // There are devices from 2 zones that are disabled, and this is the first zone. Zone 005 Z-005 zone. 029/029 // Zone number and description message of the disabled

// All 29 devices of the current zone are disabled.

Zone Fully Disabled // Current zone are completely disabled. 002 of 002 Disable 12:01 Zone 005 Z-005 016/029 Zone Part Disabled

Fig. 6-14 002 of 002 Disable 12:01 // There are devices from 2 zones that are disabled and this is the second zone. Zone: 006 zone. 016/030 zone. Z-006 // Zone number and description message of the disabled

//There are 16 disabled devices in all 30 devices of the current

Zone Part Disabled // The zone is partially disabled. 6.2.2.8 Browsing action messages You can view action messages by pressing VIEW PLANT when the screen is displaying non-action messages. The screen is shown in Fig. 6-15.

Page 45

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) 001 of 004 ACTION 12:15 Zone:001-004Sounder Office1

The Intelligent Solution

Fig. 6-15 001 of 004 ACTION 12:15 // There are 4 action messages in the system and this is the first, time 12:15. Zone:001-004Sounder device in action. Office1 //The zone number, device address and device of the

//Description message of the device in action.

Note: If this FACP is networked with other FACPs, then the displayed zone number here will be the defined device zone number + the starting zone number for this FACP (please refer to descriptions in Section 6.4.4). 6.2.3 Muting the panel Pressing MUTE can stop the sound; pressing MUTE again, the FACP is still in mute state. It will sound by priority when new event appears.

6.3 Instructions for System Operator

6.3.1 Resetting the system Pressing RESET can turn off all the control modules, local outputs and reset all the detectors, but will leave the disabled devices as they are. The LCD displays "RESET IN SYSTEM". LEDs will be turned off (Except for "POWER HEALTHY", "DELAY MODE", "EXTINGUISHING SYSTEM PERMIT" LEDs). "RESET" information will be written into running log. If there is still fire alarm, fault and action not acknowledged after pressing the RESET key, the FACP will remain relative sound indications. If all messages have been acknowledged by pressing RESET key, the system returns to normal display state. 6.3.2 Disable and Enable 6.3.2.1 Use of disable/enable The disabling/enabling of devices is mainly used when a trouble condition of a device cannot be removed in time. This device can then be temporarily disabled, and enabled after it's repaired. 6.3.2.2 Disabling/enabling a Device The DISABLED LED will illuminate when a device is disabled. The operation method is as follows:

Page 46

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) The Intelligent Solution Pressing ENABLE/DISABLE key will enter the screen in Fig. 6-16. ENABLE & DISABLE 1 Disable Devices 2 Enable Devices

Fig. 6-16 Inputting number 1 will enter the screen for disabling a device, as in Fig. 6-17.

Disable Z000C000T00 NoDefine

Fig. 6-17 In the above figure, entering the zone number, device number and device type will disable a device. You can input 3-digit number or asterisk after "Z" for zone number. You can input 3-digit number or asterisk after "C" for device code. You can input 2-digit number or asterisk after "T" for device type. Note: The asterisk * refers to number 0 9

Disabling Sounder circuit output: Entering zone number 000, device code 240 and device type 55 in turn will disable this output and light the SOUNDER FLT/DISABLE LED. Disabling F.P.E Output: Entering zone number 000, device code 241 and device type 55 will disable this output and light the F.P.E FLT/DISABLE LED. Inputting number 2 will enter the screen for enabling a device. You also need to input the zone number, device code and device type. The operation method is the same as disabling a device. 6.3.3 Manual Operation The FACP provides two method to start fire suppression devices quickly in case of a fire. 6.3.3.1 Operation through STAR/STOP Key Pressing START/STOP key can start/stop loop devices. The screen is as in Fig. 6-18. Page 47

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

*Start&Stop* 1 Start Devices 2 Stop Devices 3 View Start 4 View Delay

Fig. 6-18 Inputting number 1 will enter the screen for starting loop devices. Inputting the zone number, device code and device type in turn will start the device. Inputting number 2 will enter the screen for stopping loop devices. Inputting the zone number, device code and device type in turn will stop the device. Inputting number 3 will display the devices started. Inputting number 4 can view the delayed devices. PLANT CONTROL and corresponding action indicator on the ZCP will also be lit. 6.3.3.2 Operation through ZCP Pressing a defined key on the ZCP and entering required password will start the corresponding device. And the corresponding command LED illuminates. Pressing this key and entering the password again will stop it, and the command LED goes off. 6.3.4 Setting work mode of printer Press PRINT to enter print mode as shown in Fig. 6-19.

*Print Mode*

1 Disable 2 Only Fire 3 All History

Fig 6-19 Inputting "1" means print disabled. Inputting "2" means only printing fire alarm records Inputting "3" means you can print the current messages while browsing history records by pressing PRINT. 6.3.5 Checking all visual and audible indications In normal monitoring state, you can check all visual and audible indications of the control Page 48

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) panel by pressing SELF TEST. 6.3.6 Gas Extinguishing Equipment

The Intelligent Solution

Pressing MODE, you can set up gas extinguishing equipment. The screen is shown in Fig. 6-20.

*Extinguish*

1 Disable 2 Enable

Fig. 6-20 Inputting "1" means not to link gas extinguishing equipment by C&E automatically. Inputting "2" means to link gas extinguishing equipment by C&E automatically. 6.3.7 Security Mode Setting Pressing SEC, you can set up burglar mode. The screen is shown in Fig. 6-21.

*Burglar Mode*

1 Disable 2 Enable 3 Only Night

Fig. 6-21 If "1" is input, burglar mode is disabled. The system doesn't respond to the action of security modules. If "2" is input, burglar mode is enabled. The system responds to the action of security modules. If "3" is input, burglar mode is only effective during night. The screen shows a request for on and off time. Its window is shown in Fig. 6-22.

Page 49

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Burglar ON/OFF Time Please Input 00:00 ON 00:00 OFF

Fig. 6-22 If you input 19 at highlighted position, then press TAB, and input 30, the "ON" time of burglar mode is 19: 30. Pressing TAB, you can set up the "OFF" time. Input 07, press TAB, then input 30 again, the "OFF" time is 07: 30. Press ENTER to confirm, and the system exits to the screen in Fig. 6-21.

6.4 Instructions for System Administrator

Pressing SYSTEM can enter system setting screen. The screen is shown in Fig. 6-23.

*System Mode*

1 2 3 4 5 6 7 Time/Date Password Change Network Setup Zone Start Number Mute delay Mode Initialize System Equipment debug

Fig. 6-23 6.4.1 Modifying System Time Inputting "1" in the screen of Fig. 6-23, the system enters the Time/Date Setting as in Fig. 6-24. After inputting time at the highlighted position and pressing "TAB", then the next data is highlighted. Pressing "ENTER" will save the modification.

* Time/Date Setting* Please Input Day Month Year 04 01 05 Hour Minute Sec 11 39 55 Fig. 6-24 6.4.2 Modifying Password Inputting "2" in the screen of Fig. 6-23, the system enters the window of password Page 50

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) modification (Fig. 6-25). Now the passwords can be modified.

The Intelligent Solution

Password Setting

1. 2. Operator Password Manager Password

Fig. 6-25 Inputting "1" or "2" to choose the password to be modified, the system enters the window in Fig. 6-26.

Modify Password Input password

********

Fig. 6-25 After the password (8 digits from 0-9) is input, the LCD will display the screen in Fig. 6-27, requesting to re-enter the password.

Modify Password Confirm Password

********

Fig. 6-27 Inputting the new password again, if the two passwords are the same, it means the modification is successful and the LCD will display the window in Fig. 6-28.

Page 51

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

GST CO., LTD

Success

Fig. 6-28 6.4.3 Setting up Network Address of the Control Panel Inputting "3" in the screen in Fig. 6-23, the screen in Fig. 6-29 will display. Inputting the address of the control panel at the highlighted position and pressing ENTER, the address is set and the system exits the current screen.

* Net Local Address *

Please Input 01

Fig. 6-29 6.4.4 Setting up Beginning Zone Number of This FACP in Network Pressing "4" in the screen shown in Fig. 6-23, you can set the beginning zone number of the control panel. The screen is shown in Fig. 6-30. After inputting the number of zones in the network and pressing ENTER, the zone number will be set and the system exits the current screen. The settings here are used for the FACP to be connected into network with other FACPs. If the beginning zone number is set as 003, then the zone number for messages of fire, fault, disable and action will be the defined device zone number+003.

Net Zone Number

Please Input 001

Fig. 6-30

Page 52

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) 6.4.5 Setting up Display Mode of Network Messages

The Intelligent Solution

Pressing "3" in the screen shown in Fig. 6-23, you can set the display mode of network messages (Fig. 6-31). Inputting "1" means network messages are disabled, and "2" means they are enabled.

*Display Mode* 1 Disable 2 Enable

Fig. 6-31 6.4.6 Initialization of System CPU Inputting "6" in the screen shown in Fig. 6-23, you can initialize the system CPU. 6.4.7 Viewing Supervisory Data of Intelligent Devices Inputting "7" in the screen shown in Fig. 6-23 can enter the window in Fig. 6-32. Entering the device number and the command code can view the supervisory value of addressable devices.

GST CO.,LTD Device:000 Command:02

Fig. 6-32 Pressing different number keys represent different commands: "0" represents the command "Polling". If the displayed value is between 450 650, the device is in normal operation; if it's between 900 1200, the device is in alarm status, and if it's between 0 120, the device is in fault. "1" represents "registration" command, and 720 refers to normal condition. "2" represents the command for monitoring the commission status of beam detector. If the displayed value is between 680 750, the commission is completed. "15" means "Start" command, which can start corresponding devices. Other numbers are reserved for future expansion.

Page 53

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Chapter 7 Troubleshooting

No. 1 Problems No indication on the panel or abnormal indication Possible Cause a. AC input fuse blown b. Power is abnormal a. b. Solutions Replace fuse. Check and replace low-voltage switch power. Check the connection to display board. Check and connect AC wire. Replace AC fuse refer to the specification on the label Open the power box and check relative parts. Power up for more than eight hours with the AC power supply, if the fault still exists, replace the batteries.

c. Loose connection with switch board. c. a. No AC power b. AC fuse blown a. b. a. b.

2

Display "AC Fault" after power-up. Display "Bat Fault" after power-up.

3

Loose connection with a. battery. Battery discharged or damaged. b.

4 5

Unable to register Bus wrong or loose bus equipment connection

Check the bus

Unable to register Wrong or loose connection Check power supply to repeaters repeater panels of Communication cables and communication wires Cannot print a. b. c. Print mode is not set. a. Set the print mode. Check and connect the printer well. Replace the printer. Check and connect, then register again. Replace the circuit board of zone indication and manual intervention panel.

6

Loose connection with b. printer. Printer damaged c. Loose connection with a. ZCP. The circuit board of ZCP damaged. b.

7

No response after pressing keys on zone indication and manual intervention panel Equipment fault

a. b.

8

a. b.

Equipment disconnected. Equipment damaged.

a. Check connection b. Replace equipment Check the loop and repair. a. Check whether ground is properly connected. b. Contact our local distributor for maintenance.

9 10

Loop fault

Loop is shorted External interference. Corresponding parts are aging.

Clock or memory a. fault. b.

Page 54

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Chapter 8 Calculation of Battery Capacity

The equation for calculating the battery capacity of GST200 is as follows: Battery Capacity Ah =0.46 T 0.03 N+3.5

In which N is the number of detectors, and T is the time of operation in supervisory state.

Page 55

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Appendix 1 Internal Connection Diagram

1 Main Board 5 Speaker 9 Power Filter 13 Filter Board

2 Switch Board 6 Loop Board 10 ZCP Interface

3 LCD 7 Power Board 11Fireman's Control Pane

4 Printer 8 Transformer 12 Manual Lock

Page 56

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Appendix 2 Device Type List

Undefine ION R+F.Heat' Optical Fix Temp Gas Det Beam Det FlameDet CableDet Heat Det ION MCP VAModule Sounder FTModule HR MCP HR Pump SPKR Pmp PS.SW Extract Presuriz FreshAir Damper SM Vent AirInlet SolValve SM CURT RSD Clse FireDoor PS.DIFF Flow SW 00 01 02 03 04: 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 Undefined Ionization detector Rate of rise and temperature detector Photoelectrical detector Gas detector Infrared beam detector Ultraviolet flame detector Cable heat detector Analogue heat detector Combination detector Manual call point Voice alarm module Sounder strobe Fire telephone module Hydrant pump Hydrant pump Sprinkler pump Stabilized pressure pump Smoker exhauster Blower Fresh air Fire damp Smoke vent Air inlet Solenoid valve Roller shutter door middle point Shutter screen door close point Fire door Pressure switch Water flow indicator fixed smoke

Fixed temperature detector

Page 57

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part) Elevator AHU GENI Light.DB Power.DB WTR.CURT Gas Dump GasAbort Net Unit Repeater Module DryPower FoamPump FieldPSU EM Light EscapeLT GasActiv Security ZoneValv Cylinder DelugePM Undefine Stop Mod Silence SounderA SounderF Loop SW CRTFault Loop PSU.Bat PSU.AC Lock PART ZoneDir F.P.E 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65

The Intelligent Solution

Elevator Air handling unit Diesel generator Power for lightening Power distribution Solenoid valve for water curtain Gas start-up Gas stop Net unit Repeater panel Flash-locks valve Dry powder fire extinguisher Foam pump Power supply unit Emergency light Escape light Gas activation Security module Zone valve Cylinder Deluge pump Undefined Device stop Mute key Fire alarm sounder Fault sounder Loop switch CRT fault Loop Battery AC power Multi-wire lock Partial devices Zone direction Fire protection equipment

Page 58

GST200 Intelligent Fire Alarm Control Panel Installation and Operation Manual (Generic Part)

The Intelligent Solution

Appendix 3 Operation Menu

Menu BROWSE To look through equipment Active EQ Bus equipment COM EQ Communication equipment, including repeater panels and slave control panels Access ZCP LOG To view history record SCREEN To set screen menu LCD Contrast To set LCD contrast Browse Mode browsing Information Zone Mode Zone display mode Loop Mode Loop display mode Browsing C&E To view C&E equation PRINT To set printer menu [password required] Disable Printing disabled Only Fire Only printing fire information All History When viewing history records, you can print the information being viewed by pressing the "PRINT". MUTE You can silence the alarm sound by pressing "MUTE" VIEW FAULT Viewing fault information when in non-fault state. SELF TEST Audible-visible self-test key. In normal monitoring state, you can check all the audio-visible devices by pressing this key (password required). LOCK When keypad is in unlocked state, press this key to lock the keys. SCROLL When there is more than one piece of information, you can scroll the screen by pressing this key. ESC Pressing this key cancels output or exits menu. In information display state, you can return the system to the highest level. VIEW DISABLE In non-disable state, press this key to display the disabled information. MODE Setting gas extinguishing equipment (password required) Disable Do not automatically link gas-extinguishing system Enable Link gas extinguishing system automatically SYSTEM Setting system menu (password required) Time/Date Setting the system time Password Change Setting password Net Local Address Setting network address Zone Start Number Setting starting number of zones Display Mode Setting display mode of network info

Page 59

GST200 Intelligent Fire Alarm Control Panel The Intelligent Solution Installation and Operation Manual (Generic Part) Initialize System To initialize the system Equipment debug View supervisory data of intelligent devices ENTER Confirming the input is valid. In monitoring state, press this key to change time display between month/day and hour/minute modes. VIEW PLANT Press this key to display action information when in non-action mode. START\STOP [password required] Start EQ Starting bus equipment. An EQ code should be inputted when starting the EQ in loop mode. A zone number should be inputted when start all the EQ in zone mode. Stop EQ Stop bus EQ. In loop mode, input the device code to stop it. In zone mode, input the zone number to stop all devices of the zone. View Start In the state of non ­startup displayed, press the View Start key to display the startup information. ENABLE/DISABLE [password required] DISABLE Disabling the field device with fault ENABLE Enabling the field device repaired SEC Setting security mode [password required] Disable Burglar mode is invalid. The system doesn't respond to the action of security modules. Enable The burglar mode is enabled. The system responds to the action of security modules Only Night Burglar mode is only effective during night. The screen shows a request for on and off time. RESET Reset GST200 to normal monitoring state from fire alarm or fault state [password required].

Page 60

GST China

Gulf Security Technology Co., Ltd. No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 Tel: +86 (0) 335 8502528 Fax: +86 (0) 335 8508942 Email: [email protected] www.gst.com.cn

GST UK

Global System Technology PLC Lion Court, Staunton Harold Hall, Melbourne Road, Ashby de la Zouch, Leicestershire, England LE65 1RT Tel: +44 1283 225 478 Fax: +44 1283 220 690 Email: [email protected] www.gst.uk.com

GST Dubai

Global System Technology PLC PO Box 17998 Unit ZA04 JEBEL ALI Free Zone, Dubai, UAE Tel: +971 (0) 4 8833050 Fax: +971 (0) 4 8833053 Email: [email protected] www.gst.uk.com

Information

untitled

65 pages

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

708775


You might also be interested in

BETA
MP390 User's Guide
ADTUN40____OperEnglA1.PDF
CHAPTER 320 ELECTRIC POWER DISTRIBUTIONSYSTEMS
Cubase LE Getting Started