Data Aire Series Chilled Water 7 through 50 ton

R

ISO 9001 Certified

Data Aire® ... the pioneer and builder of the most complete line of precision cooling equipment Data Aire's first precision cooling system was developed by data processing engineers who sought optimum environmental conditions for early computers. It was clear that "people comfort" air conditioning system were unable to meet the environmental requirements of computers and data processing equipment. Precision environmental control equipment with high sensible cooling ratios was a necessity. Problems with paper sticking , head crash, and static electricity were eliminated. Humidity fluctuation were controlled saving possible electrical and mechanical failures and more importantly ­ Downtime. Data Aire's innovative response to the challenge of eliminating problems within the computer room environment was the start of wide use precision cooling. As in the past, Data Aire is meeting today's challenge of not only the computer room but also the ever expanding telecommunications industry where precision cooling is vital to our everyday communications. Telecommunication equipment requires a controlled environment with clean and properly distributed air. As in the computer room, the environment must be precisely controlled ­ 24 hour a day, 365 days a year. Data Aire produces solutions. We have offered environmental control solutions to meet specific needs in the smallest of places and in areas of thousands of square feet. We are prepared to assist you, your in-house engineering department, consulting engineer, or construction department in defining the proper solutions and bringing them to a predefined outcome. Data Aire is committed to being the supplier of choice for environmental process cooling with flexibility, reliability, and expertise required to meet our customer's needs. To be successful, it is essential to be creative and use our resources to their fullest capabilities. The Data Aire goal is to benefit the employees, partners, and most of all ­ our customers with honesty and integrity. Data Aire Delivers!

DATA AIRE SERIES 7 to 50 TON CHILLED WATER UNITS

Product Description Performance/Electrical Data Dimensional Data Guide Specifications

Table of Contents

Design Features ...................................................................................................... 6 Control System ....................................................................................................... 7 Options .................................................................................................................. 10 Model Identification .............................................................................................. 12 Performance Data ................................................................................................. 13 Standard Airflow........................................................................... 14 Optional Airflow - Option 1 ........................................................ 22 Optional Airflow - Option 2 ........................................................ 30 Dimensional and Weight Data............................................................................... 38 Dimensional and Component Drawings ............................................................... 39

Guide Specifications ............................................................................................. 48

4

PRECISION COOLING

Data Aire Series chilled water units offer precision environmental control that brings a standard of reliable performance to meet today's market demands. Data Aire systems are designed for data centers, telecommunication sites, or anywhere process cooling is required. Chilled water units are available in 7 through 50 nominal tons with upflow or downflow air distribution. Each unit is factory run tested and put through a comprehensive quality control procedure.

HIGH PERFORMANCE/LOW COST

Engineered for performance and reliability, each Data Aire Series unit comes with Data Aire's commitment to excellence. This commitment began with Data Aire's first process cooling unit and has continued for more than 30 years of building the industry's finest control equipment.

DATA AIRE DELIVERS

Standard ship cycle is 30 days from date of order. With an optional premium "quick ship", units can be expedited to ship in little as one week. All units are built to your specific order and specification. Call your nearest Data Aire representative for more information.

COMFORT

Computer rooms and other environmentally controlled spaces require air which is clean and properly distributed, with precisely controlled temperature and humidity. Building or "people comfort" cooling systems are not designed to meet these demands. Data Aire Series chilled water units are designed to maintain temperature and humidity and properly distribute the required clean air in environmentally controlled areas.

DESIGN

Data Aire Series units feature a specially designed compact tubular steel frame which allows for minimum space requirement of air conditioning equipment in the controlled area. Although compact, all parts are easily accessible providing excellent serviceability. Units are finished with a furniture-grade insulated steel cabinet painted in your choice of color. The heart of the system is the Date Alarm Processor-II TM, a microprocessor based controller designed for precision environmental control. The DAP-IITM not only controls and monitors temperature, humidity, airflow, and cleanliness, it provides component runtimes, alarm history, and automatic self-test. All information is provided on a 2 row, 80 character, backlit liquid crystal display (LCD).

5

DESIGN FEATURES

CABINET and FRAME

Data Aire chilled water series units are constructed with heliarc welded tubular steel frame providing for maximum strength and ease of access. Side and front panels can be easily removed with quarter-turn fasteners allowing full access to all unit components. All panels include 1 inch thick, 11/ 2 pound density insulation for protection and sound attenuation.

REHEAT

Three stage electric reheat is standard. Low-watt density finned tubular sheathed coils provide ample capacity to maintain room conditions during dehumidification. Low-watt density coils eliminate ionization associated with open air electric resistance heating.

HUMIDIFICATION COIL SECTION

Designed for draw through application, the computer selected A-frame coil provides greater efficiency in the cooling and dehumidification process. Air is drawn through both slabs at velocities that provide effective surface exposure with minimum turbulence. The chilled water flow is controlled by a 3-way modulating mixing valve for accurate and economical temperature and dehumidification control. Bypass air is provided to prevent saturated air from being introduced into the controlled space. The coil sits in a stainless steel drain pan. Steam Generator Humidifier Units are furnished with an electric steam generator humidifier with "quick change" disposable cylinders and auto-flush cycle. The steam generator humidifier with its patented control system optimizes cylinder life by concentrating incoming water to a predetermined conductivity much higher than that of any entering water. The control system continuously monitors the conductivity in the cylinder through its electronics which allows water to be flushed as often as is necessary to maintain the level at this design conductivity. The high design conductivity results in a minimum flushing of heated water which saves energy. The humidifier is designed to allow all units at any voltage to produce full rated steam output at an optimum low water level.

FAN SECTION

The centrifugal, forward curved, double width, double inlet blower configuration is engineered for quiet reliable operation. The dual belt driven variable pitch drive section provides adjustable air flow capability to match the load requirements of the controlled space. The draw through design insures even air distribution across the coil and bypass, low internal cabinet pressure losses and static sealing of the filter section. Motors are mounted on an adjustable slide base and have internal overload protection.

FILTER SECTION

Units are provided with 4 inch deep, 30% efficient (based on ASHRAE Std. 52-76), pleated filters. The filter section is accessible from the top or side on downflow units and both sides on upflow units.

6

CONTROL SYSTEM

The microprocessor based Data Alarm Processor-II TM offers the definitive answer for precision environmental control. The DAP-IITM control system not only controls and monitors temperature, humidity, airflow, and cleanliness, it provides component runtimes, alarm history, and an automatic self-test of the microprocessor on system start-up. All messages are presented in a clear vernacular format and sequentially displayed on a 2 row, 80 character, backlit liquid crystal display (LCD). OPERATION - Highly reliable, flat, sealed switches with tactile feedback allow unit on/off operation, menu selection for programming, operational information, diagnostics, and historical data. Multilevel password prevents unauthorized access. Alarm conditions are enunciated by an audible alarm. The alarm silence switch will quiet the audible alarm but the display will continue to indicate the alarm condition until the problem is corrected.

STANDARD FEATURES Forward/Backward Menu Access Multilevel Password Access Stand Alone Panel All Settings from Face of Panel Factory Calibrated Temperature Sensor Factory Calibrated Humidity Sensor Database of Unit & Room Conditions All Programmed Settings Saved in EEPROM Battery Backup for Historical Data Automatic Self-Test Diagnostics

DIAGNOSTIC and SERVICE FEATURES Manual Diagnostics Program Alarms Displayed in Order of Occurrence Manual Override for: Blower, Cool, Heat 1, Humidification, Water Valve Adjustable Alarm Limit Four Programmable Optional Alarms Programmable Delays for Optional Alarms Programmable Remote Alarm Audio Alarm Tone Select Alarms Optionally Disabled

OPERATIONAL FEATURES Selectable Control Type Sequential Load Activation Temperature Anticipation Humidity Anticipation Dehumidification Mode Lockout Start Time Delay Automatic or Manual Restart Automatic Reheat Element Rotation Chilled Water Coil Flush Cycle

PROTECTIVE and SAFETY FEATURES Metal Shell Enclosure with Sealed Front Control Panel Isolation Transformer Opto-Coupler Signal Inputs Network Bypass Relays Protected 24 VAC Power Input Heavy Ground Planes & Power Foils Watch Dog Timer Fused RS-485 Network Lines Switching Power Supply

OPTIONAL FEATURES Humidifier Flush Cycle Analog Inputs RS-485 Network System Modulating Humidifier Control Two Additional Remote Alarms

7

CONTROL SYSTEM, continued

PROGRAMMABLE FUNCTIONS - The user friendly "Menu" switches permit step-by-step programming of the following selections: Temperature setpoint 65-85o F / 18.3-29.4o C High temperature alarm limit 70-90o F / 21.1-32.2o C Humidity setpoint 30-70% RH High humidity alarm limit 35-90% RH Mode and stage response time 1-5 minutes Reset equipment times Blower Reheat Strip 1, 2, 3 Humidifier Dehumidification Reset all to zero runtimes Automatic self-test acknowledge On/Off Dehumidification mode Dehumidification off System Start Delay 0-10 minutes in 5 second increments Message for optional alarm 1, 2, 3, 4 Custom message alarm: 25 space message* Fan motor overload: check motor amperage* Local alarm: see tag inside door* Standby pump on: check primary pump* UPS/alternate power on: check main power* Reheat inhibited Humidification inhibited Reheat and humidification inhibited Delay for optional alarm 1, 2, 3, 4 0-900 seconds/off Firestat temperature alarm limit Unit shutdown and alarm at 100-150o F Temperature scale Fahrenheit/Centigrade Remote alarm 1, 2, 3 selection* Custom message 1, 2, 3, 4* Dirty filter Discharge air sensor problem* Fan motor overload* Firestat High humidity High temperature Humidifier problem Humidifier sensor problem Local alarm 1, 2, 3, 4* Low humidity Low temperature Temperature deadband ± 1-5o F/C Low Temperature Alarm Limit 55-75o F/12.8-23.9o C Humidity deadband 1-15% RH Low humidity alarm limit 10-65% RH Audio alarm mode None/long/full/short beep Manual diagnostics Normal menu/diagnostic mode Humidity anticipation On/Off Low discharge temperature alarm limit* 45-60o F/7.2-15.6o C Power Failure or Restart Mode Automatic: no message Automatic: message, audio alarm, relay Manual: message, audio alarm, relay Person to contact on alarm Message not used Data processing manager Maintenance engineer Service company Custom message Define password 00-99 Humidifier autoflush timer* Autoflush timer not used 6 hours 12-96 hours in 12 hour increments Scheduled normal maintenance 1-1000 hours/off Control Logic Setpoint deviation/PID/smart logic Unit and network identification number 0-260 Calibrate temperature sensor + 9.9o F/C Calibrate humidity sensor + 30% RH Calibrate discharge sensor* 9.9o F/C Reheat stages None 1, 2, or 3 Hot water*

* Some programmable selections, displays, and alarms may require optional components or sensors. Contact your Data Aire representative for a detailed analysis of your requirements.

8

CONTROL SYSTEM, continued

PROGRAMMABLE FUNCTIONS, continued Low voltage Maintenance required Manual Override No Airflow No Water Flow* Power problem or restart Smoke detector* Standby pump on* Temperature sensor problem Water detection probe UPS/alternate power on Humidifier None Computer, non-modulating Computer, modulating Comfort, non-modulating Comfort, modulating Water valve mode None Chilled water cooling Humidification Inhibited Reheat inhibited

DISPLAYED CONDITIONS, DATA, and FUNCTIONS - The Data Alarm Processor-II displays and monitors the following conditions, data, and functions: Temperature setpoint Current temperature Current percent of capacity utilized Unit or network ID number Cooling Humidification Humidity setpoint Current humidity Current discharge air temperature* Zone number Reheat stages 1, 2, 3 Dehumidification

ALARMS - Alarm conditions are displayed and monitored on the microprocessor LCD along with an audible alarm. The alarm silence switch will quiet the audible alarm but the display will continue to indicate the alarm condition until it is corrected. The following alarms are displayed: High temperature warning High humidity warning Under floor water detection Dirty filter Manual override Low voltage warning Maintenance required Humidity sensor error Local alarm No water flow* Standby pump on* Low temperature warning Low humidity warning No air flow Humidifier failure Firestat tripped Power failure restart Temperature sensor error Discharge air sensor error* Fan motor overload* Smoke detected* Custom message*

HISTORICAL DATA - In order to facilitate maintenance and service, historical data can be recalled and displayed. The historical database is maintained by battery backup should power fail. The following data can be recalled and displayed: High temperature last 24 hours High humidity last 24 hours Average percent of capacity last hour Equipment runtimes Low temperature last 24 hours Low humidity last 24 hours Alarm history for last 10 alarms

* Some of the programmable selections, displays, or alarms may require additional components or sensors. Contact your Data Aire representative for a detailed analysis of your requirements.

9

Options

Data Aire Remote Telecommunications System 200TM The Data Aire Remote Telecommunications System 200 (DART-200) provides comprehensive monitoring and control of Data Aire units via a phone modem to a host PC station. The Data Aire units are interfaced with a communications module (DART-board) with integral phone modem. The DART-200 allows complete remote control, monitoring, and retrieval of all historical data of the Data Aire units through the unit mounted Data Alarm Processor-IITM. Upon an alarm at the unit, the DART-board can be programmed to automatically dial one or two pre-programmed numbers and transmit specific alarm information. All entry or configuration capabilities available at the Data Alarm Processor-II are accessible at the host station. The commands or requests for data from each unit are processed through the DART-board. A single DART-board will allow up to 32 Data Aire units to be connected and controlled. The DART-200 System is capable of monitoring and controlling up to 200 DART-boards.

System Features Automatic scrolling of current status Sensor database Password access Automatic status log prints Automatic scrolling of sensor readings Sequential display of alarms Multiple audio alarm modes Custom "Help" messages for alarms

Programmable Functions Temperature setpoint Temperature high limit Temperature low limit Temperature sensitivity (deadband) On/off/standby operation Unit ID number Password Humidity setpoint Humidity high limit Humidity low limit Humidity sensitivity (deadband) Unit rotation Zone number

Monitored Conditions Specific alarms from unit(s) Programmed local alarms from unit(s) Current temperature sensor readings All standard alarms from unit(s) Current operating mode Current humidity sensor readings

Historical Data Alarm history for last 10 alarms in order of occurrence and time since detected Current and average percent of capacity for last hour High and low temperature for last 24 hours High and low humidity for last 24 hours Equipment runtimes for: Evaporator motors, Reheat, Humidification, Dehumidification

* Some programmable selections, displays, and alarms may require optional components or sensors.

10

Options, continued

Remote Temperature and Humidity Sensors Temperature and humidity sensors may be ordered for remote wall mounting. Sensors are provided in a wall mount plastic case for remote sensing of temperature and humidity. 25 feet of shielded cable is provided for field wiring. Smoke Detector A unit mounted smoke detector will shut down the unit if smoke is sensed. The unit mounted microprocessor control will sound an alarm and display a "SMOKE DETECTED" message. The smoke detector is mounted in the return air stream and is provided with auxiliary contacts. Unit Mounted Disconnect A unit mounted nonautomatic disconnect switch is installed in the high voltage electrical section. The operating mechanism (handle) protrudes through the decorative exterior panel. The operating mechanism prevents access to the high voltage electrical components by not allowing entry until switched to the "OFF" position. Condensate Pump Condensate pumps may be ordered as factory installed or shipped loose for field installation. Condensate pumps are complete with sump, motor, and automatic control. The pumps are rated for 130 GPH at 20 foot maximum head or 40 GPH at 20 feet with check valve. Pumps shipped loose are available in 115, 230, or 460 volts. Floorstands Floorstands are adjustable ± 2 inches and may be ordered with factory installed turning vane or with seismic construction. High Efficiency Filters Standard filters are rated at 30% (per ASHRAE Std. 52-76). Higher efficiency filters are available (consult factory regarding efficiency and unit static pressure). Steam Generator Humidifier with Modulating Control Modulating control may be added to the steam generator humidifier. Modulating control will allow the humidifier to automatically adjust steam output to match changing room conditions. Self-regulating auto flush is included. Hot Water Reheat Where hot water is available, a water coil for reheat may be added. The coil is designed for 150 psi maximum water pressure and includes a 2-way valve (a 3-way is also available). Units with the hot water reheat do not include electric reheat. Supplemental reheat may be ordered. 2-Way Chilled Water Valve A 2-way chilled water valve is available to replace the standard 3-way valve where required. Upflow Plenum Upflow plenums are fully insulated and have front discharge air grille. Side grilles for both or one side are available. Plenums are 18" high and are painted to match the unit color.

11

Model Number Identification

MODEL NUMBER IDENTIFICATION DA C D - 15 3 4

DATA AIRE SERIES CHILLED WATER D - DOWNFLOW U - UPFLOW NOMINAL TONS VOLTAGE 2 - 208 or 230 4 - 460 5 - 575

3 - THREE PHASE

12

CHILLED WATER PERFORMANCE DATA

All capacity data is based on 45º F entering water temperature.

13

CHILLED WATER: Performance data at STANDARD airflow,

7 - 18 nominal tons

MODEL NUMBER CAPACITY* in Btu/hr - gross 80 ° F DB/67 ° F WB (50% RH) Total Sensible Flowrate in GPM Pressure drop in PSI 75 ° F DB/62.5 ° F WB (50% RH) Total Sensible Flowrate - GPM Pressure drop - PSI 75 ° F DB/61 ° F WB (45% RH) Total Sensible Flowrate - GPM Pressure drop - PSI 72 ° F DB/60 ° F WB (50% RH) Total Sensible Flow rate - GPM Pressure drop - PSI 72 ° F DB/ 58.6 ° F WB (45% RH) Total Sensible Flow rate - GPM Pressure drop - PSI

DACD/U-07 DACD/U-09 DACD/U-11 DACD/U-13 DACD/U-15 DACD/U-18

108,400 81,100 22 9.4

137,200 97,300 26 13.3

170,800 115,000 35 8.9

201,200 131,000 45 10.3

259,700 185,000 50 11.9

337,000 231,600 60 16.6

83,000 72,000 20 7.8

104,900 86,200 24 11.4

127,400 99,900 30 6.6

147,000 111,800 35 6.4

196,900 163,100 45 9.7

250,100 201,000 50 11.8

76,600 73,600 18 6.3

96,400 88,500 22 9.9

115,400 101,900 27 5.4

133,000 113,800 32 5.4

181,600 167,500 42 8.5

229,000 206,000 46 10.0

67,400 64,000 16 5.0

85,800 77,500 20 7.9

102,900 89,200 24 4.3

118,800 99,800 28 4.2

162,000 146,800 38 7.1

205,100 180,900 42 8.5

64,800 64,800 15 4.4

81,300 79,900 19 7.1

95,400 91,700 22 3.7

108,600 102,100 25 3.4

151,200 149,000 34 5.7

190,800 185,000 38 7.0

BLOWER SECTION BLOWER SECTION Airflow - CFM Standard motor - horsepower External static pressure - inches of W.G. Number of motors/fans 3,250 1.5 0.5 1/1 3,500 2 0.5 1/1 3,750 2 0.5 1/1 4,000 3 0.5 1/1 7,000 5 0.5 1/2 8,000 5 0.5 1/2

Maximum external static pressure (Standard motor) Maximum external static pressure (Next size motor) Next size motor - horsepower

Downflow Upflow Downflow Upflow

0.7 0.6 1.5 1.5 2

1.1 1.1 1.5 1.5 3

0.7 0.6 1.5 1.5 3

1.4 1.3 1.5 1.5 5

1.3 1.5 1.5 1.5 7.5

0.9 0.8 1.5 1.4 7.5

* Capacity data is based on 45º F entering water temperature.

14

CHILLED WATER: Performance data at STANDARD airflow, 22 - 50 nominal tons

MODEL NUMBER CAPACITY* in Btu/hr - gross 80 ° F DB/67 ° F WB (50% RH) Total Sensible Flow rate - GPM Pressure drop - PSI 75 ° F DB/62.5 ° F WB (50% RH) Total Sensible Flow rate - GPM Pressure drop - PSI 75 ° F DB/61 ° F WB (45% RH) Total Sensible Flow rate - GPM Pressure drop - PSI 72 ° F DB/60 ° F WB (50% RH) Total Sensible Flow rate - GPM Pressure drop - PSI 72 ° F DB/58.6 ° F WB (45% RH) Total Sensible Flow rate - GPM Pressure drop - PSI

DACD/U-22 DACD/U-26 DACD/U-30

DACD/U-40 DACD/U-45 DACD/U-50

412,100 276,300 72 25.7

450,400 299,300 92 21.3

553,300 368,000 100 25.6

649,000 451,600 125 21.2

771,500 524,000 140 27.2

881,600 589,800 150 32.3

305,700 239,000 60 18.4

337,200 260,000 80 16.4

417,800 321,400 90 21

476,900 390,400 100 14

564,300 450,500 110 17.6

647,900 507,400 120 21.7

278,500 244,300 55 15.6

305,800 265,100 73 13.9

379,800 328,100 83 18

441,300 402,300 95 12.7

521,000 464,200 105 16.2

591,300 519,400 110 18.5

250,000 214,800 50 13

274,800 233,300 66 11.5

342,200 289,100 76 15.3

392,800 352,000 85 10.2

459,900 404,000 90 12.1

529,500 456,100 100 15.5

230,700 220,000 45 10.7

251,900 238,800 59 9.4

314,500 296,400 69 12.9

364,900 357,900 75 8.1

431,600 416,700 85 10.8

495,400 471,300 95 14.1

BLOWER SECTION Airflow - CFM Standard motor - horsepower External static pressure - inches of W.G. Number of motors/fans 9,000 7.5 0.5 1/2 9,500 10 0.5 1/2 11,700 3 0.5 3/3 16,000 7.5 0.5 2/4 17,500 7.5 0.5 2/4 19,000 10 0.5 2/4

Maximum external static pressure (Standard motor) Maximum external static pressure (Next size motor) Next size motor - horsepower

Downflow Upflow Downflow Upflow

1.3 0.9 1.5 1.4 10

1.5 1.4 N/A N/A N/A

1.3 1.2 1.5 1.5 5

1.2 1.1 1.5 1.5 10

1.5 1.5 1.5 1.5 10

1.5 1.2 N/A N/A N/A

* Capacity data is based on 45º F entering water temperature.

15

CHILLED WATER: Performance data at STANDARD airflow,

7 - 18 nominal tons

MODEL NUMBER COIL DATA Face area - sq.ft. Rows of coils Face velocity - FPM

DACD/U-07 DACD/U-09 DACD/U-11 DACD/U-13 DACD/U-15 DACD/U-18

12.2 3 266

12.2 4 287

12.2 5 307

12.2 6 328

24.4 3 287

24.4 4 328

CONTROL VALVE Valve body Valve CV Valve size - inches

(Modulating control designed at 400 psi)

3-WAY 10 1

3-WAY 10 1

3-WAY 16 1-1/4

3-WAY 25 1-1/2

3-WAY 25 1-1/2

3-WAY 40 2

CONNECTION SIZES Supply - O.D. Copper Return - O.D. Copper Condensate drain Humidifier supply

(Inches)

1-1/8 1-1/8 3/4 1/4

1-1/8 1-1/8 3/4 1/4

1-5/8 1-5/8 3/4 1/4

1-5/8 1-5/8 3/4 1/4

1-5/8 1-5/8 3/4 1/4

2-1/8 2-1/8 3/4 1/4

REHEAT SECTION Type Capacity Electric 3-stage kW Btu/hr Steam Btu/hr Standard 15 51,225 Optional 91,000 62,000 Optional 55,000 39,600 5 Standard 15 51,225 Optional 94,000 65,000 Optional 56,000 41,300 5 Standard 15 51,225 Optional 96,000 68,000 Optional 61,300 44,200 6 Standard 15 51,225 Optional 99,000 71,000 Optional 63,000 45,600 6 Standard 22.5 76,835 Optional 195,000 134,000 Optional 121,500 87,200 8 Standard 22.5 76,835 Optional 208,000 47,000 Optional 128,600 93,400 8

Type Capacity

Downflow Upflow

Type Capacity

Hot water Btu/hr GPM

Downflow Upflow

HUMIDIFIER SECTION Type Capacity Steam generator kW lbs/hr *(adjustable) Standard 3.4 10 Standard 3.4 10 Standard 3.4 10 Standard 3.4 10 Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30*

16

CHILLED WATER: Performance data at STANDARD airflow,

22 - 50 nominal tons

MODEL NUMBER COIL DATA Face area in sq.ft. Rows of coil Face velocity in FPM

DACD/U-22 DACD/U-26 DACD/U-30 DACD/U-40 DACD/U-45 DACD/U-50

24.4 5 369

24.4 6 389

30.9 6 379

42.8 4 374

42.8 5 409

42.8 6 444

CONTROL VALVE Valve body Valve CV Valve size - inches

(Modulating control designed at 400 psi)

3-WAY 40 2

3-WAY 40 2

3-WAY 40 2

3-WAY 40 2

3-WAY 40 2

3-WAY 40 2

CONNECTION SIZES Supply - O.D. copper Return - O.D. copper Condensate drain Humidifier supply

(Inches)

2-1/8 2-1/8 3/4 1/4

2-1/8 2-1/8 3/4 1/4

2-1/8 2-1/8 3/4 1/4

2-5/8 2-5/8 3/4 1/4

2-5/8 2-5/8 3/4 1/4

2-5/8 2-5/8 3/4 1/4

REHEAT SECTION Type Capacity Electric 3-stage kW Btu/hr Steam Btu/hr Standard 22.5 76,835 Optional 217,000 159,000 Optional 135,000 99,000 8 Standard 22.5 76,835 Optional 222,000 164,000 Optional 137,900 101,800 8 Standard 22.5 76,835 Optional 276,000 202,000 Optional 164,600 122,800 10 Standard 30 102,360 Optional 278,000 207,000 Optional 178,700 130,800 10 Standard 30 102,360 Optional 286,000 216,000 Optional 185,200 136,600 10 Standard 30 102,360 Optional 298,000 223,000 Optional 191,400 142,100 10

Type Capacity

Downflow Upflow

Type Capacity

Hot water Btu/hr GPM

Downflow Upflow

HUMIDIFIER SECTION TYPE Steam generator CAPACITY kW lbs/hr *(adjustable) Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30*

17

CHILLED WATER: Performance data at STANDARD airflow,

7 - 18 nominal tons

MODEL NUMBER FILTER SECTION Quantity/size Downflow Upflow

DACD/U-07

DACD/U-09

DACD/U-11

DACD/U-13

DACD/U-15 DACD/U-18

(Pleated, 30% efficient, based on ASHRAE Std. 52-76)

4-16x20 2-20x25

4-16x20 2-20x25

4-16x20 2-20x25

4-16x20 2-20x25 2-16x25

2-16x20 4-16x25 2-20x25 2-16x25

2-16x20 4-16x25 2-20x25

ELECTRICAL SECTION

Electrical data based on STANDARD UNIT: electric reheat-YES, steam generator humidifier-YES, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

47/59/60 22/27/30 17/21/25

48/60/70 22/27/30 18/22/25

48/60/70 22/27/30 18/22/25

50/63/70 23/29/30 18/23/25

77/97/100 35/44/45 28/35/40

77/97/100 35/44/45 28/35/40

Electrical data based on: electric reheat - NO, steam generator humidifier - YES, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

22/28/30 7.1/8.8/15 5.4/6.8/15

22/28/30 7.3/9.1/15 5.9/7.4/15

22/28/30 7.3/9.1/15 5.9/7.4/15

25/31/35 8.0/11/15 6.7/8.4/15

43/54/60 19/24/25 16/19/20

43/54/60 19/24/25 16/19/20

Electrical data based on: electric reheat - YES, steam generator humidifier - NO, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

47/59/60 22/27/30 17/21/25

48/60/70 22/27/30 18/22/25

48/60/70 22/27/30 18/22/25

50/63/70 23/29/30 18/23/25

77/97/100 35/44/45 28/35/40

77/97/100 35/44/45 28/35/40

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

5.7/7.1/15 2.8/3.5/15 2.0/2.5/1

6.0/7.5/15 3.0/3.8/15 2.5/3.1/15

6.0/7.5/15 3.0/3.8/15 2.5/3.1/15

8.4/11/15 4.2/5.3/15 3.3/4.1/15

15/19/30 6.6/8.3/15 5.3/6.6/15

Electrical data based on: electric reheat - NO, steam generator humidifier - NO, and STANDARD MOTOR.

15/19/30 6.6/8.3/15 5.3/6.6/15

STANDARD MOTOR Motor horsepower Number of motors 208-230/3/60 460/3/60 575/3/60 FLA FLA FLA 1.5 1 4.8 2.8 2.0

2 1 6.0 3.0 2.5

2 1 6.0 3.0 2.5

3 1 8.4 4.2 3.3

5 1 14.8 6.6 5.3

5 1 14.8 6.6 5.3

FLA - Full load amps MCA - Minimum circuit ampacity (wire sizing amps) MFS - Maximum overcurrent protection device amp

18

CHILLED WATER: Performance data at STANDARD airflow,

22 - 50 nominal tons

MODEL NUMBER FILTER SECTION Quantity/size Downflow Upflow

DACD/U-22

DACD/U-26

DACD/U-30

DACD/U-40

DACD/U-45 DACD/U-50

(Pleated, 30% efficient based on ASHRAE Std. 52-76)

2-16x20 2-16x25 2-16x25 2-16x25

2-20x25 2-16x25 2-20x25 2-16x25

4-16x20 4-16x25 3-20x25 2-16x25

10-16x25

10-16x25

6-20x25

6-20x25

ELECTRICAL SECTION

Electrical data based on STANDARD UNIT: electric reheat-YES, steam generator humidifier-YES, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS 83/103/110 FLA/MCA/MFS FLA/MCA/MFS 38/48/50 31/39/40

93/116/125 42/53/60 33/41/45

88/105/110 123/149/150 123/149/150 143/172/225

41/49/50 33/39/40

58/70/80 47/57/60

58/70/80 47/57/60

Electrical data based on: electric reheat - NO, steam generator humidifier - YES, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

48/60/70 23/29/35 19/24/25

57/73/90 27/34/40 20/25/30

54/63/70 25/30/35 20/24/30

68/80/90 33/39/45 27/32/35

68/80/90 88/103/125 33/39/45 27/32/35

Electrical data based on: electric reheat - YES with and humidifier - NO, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS 83/103/110 FLA/MCA/MFS FLA/MCA/MFS 38/47/50 31/39/40

93/116/125 42/53/60 33/41/45

88/105/110 123/149/150 123/149/150 143/172/175

41/49/50 33/39/40

58/70/80 47/57/60

58/70/80 47/57/60

Electrical data based on: electric reheat - NO, humidifier - NO, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

20/25/45 10/13/20 8.6/11/15

30/38/60 14/18/30 10/13/20

25/27/35 13/14/15 10/11/15

40/45/60 20/23/30 17/19/25

40/45/60 20/23/30 17/19/25

STANDARD MOTOR Motor horsepower Number of motors 208-230/3/60 460/3/60 575/3/60 FLA FLA FLA 7.5 1 20.0 10.1 8.6

10 1 30.0 12.5 10.0

3 3 8.4 4.2 3.3

7.5 2 20.0 10.1 14.0

7.5 2 20.0 10.1 14.0

FLA - Full load amps MCA - Minimum circuit ampacity (wire sizing amps) MFS - Maximum overcurrent protection device amps

19

10-16x25

6-20x25

66/79/80 50/60/70

41/48/50 30/35/40

66/79/80 50/60/70

60/68/90 28/32/45 20/23/30

10 2 30.0 14.0 10.0

CHILLED WATER: Performance data at STANDARD airflow,

7 - 18 nominal tons

MODEL NUMBER

DACD/U-07 DACD/U-09 DACD/U-11 DACD/U-13 DACD/U-15 DACD/U-18

ELECTRICAL SECTION Electrical data based on standard unit: Electric Reheat - YES, steam generator Humidifier - YES, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

48/60/70 22/27/30 18/22/25

50/63/70 23/29/30 18/23/25

50/63/70 23/29/30 18/23/25

56/71/80 25/32/35 20/25/30

83/103/110 38/48/50 31/39/40

83/103/110 38/48/50 31/39/40

Electrical data based on: electric reheat - NO, steam generator humidifier - YES and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

22/28/30 7.3/9.1/15 5.9/7.4/15

25/31/35 8.7/11/15 6.7/8.4/15

25/31/35 8.7/11/15 6.7/8.4/15

31/39/40 11/14/15 8.9/11/15

48/60/70 23/29/35 19/24/25

48/60/70 23/29/35 19/24/25

Electrical data based on: electric reheat - YES, steam generator humidifier - NO and NEXT SIZE MOTOR.

460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS

22/27/30 18/22/25

23/29/30 18/23/25

23/29/30 18/23/25

25/32/35 20/25/30

38/48/50 31/39/40

208-230/3/60

FLA/MCA/MFS

48/60/70

50/63/70

50/63/70

56/71/80

83/103/110

83/103/110 38/48/50 31/39/40

Electrical data based on: electric reheat - NO, steam generator humidifier - NO and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

6.0/7.5/15 3.0/3.8/15 2.5/3.1/15

8.4/11/15 4.2/5.3/15 3.3/4.1/15

8.4/11/15 4.2/5.3/15 3.3/4.1/15

15/19/30 6.6/8.3/15 5.3/6.6/15

20/25/45 10/13/20 8.6/11/15

20/25/45 10/13/20 8.6/11/15

NEXT SIZE MOTOR

Motor horsepower Number of motors 208-230/3/60 460/3/60 575/3/60 FLA FLA FLA

2 1 6.0 3.0 2.5

3 1 8.4 4.2 3.3

3 1 8.4 4.2 3.3

5 1 14.8 6.6 5.3

7.5 1 14.8 6.6 5.3

7.5 1 20.0 10.1 8.6

FLA - Full load amps MCA - Minimum circuit ampacity (wire sizing amps) MFS - Maximum overcurrent protection device amps

20

CHILLED WATER: Performance data at STANDARD airflow,

22 - 50 nominal tons

MODEL NUMBER

DACD/U-22 DACD/U-26 DACD/U-30 DACD/U-40 DACD/U-45 DACD/U-50

ELECTRICAL SECTION Electrical data based on STANDARD UNIT: electric reheat-YES, steam generator humidifier-YES and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

93/116/125 42/53/60 33/41/45

N/A 107/126/150 143/172/175 143/172/175

N/A N/A N/A

N/A N/A

48/57/60 39/45/50

66/79/80 50/60/70

66/79/80 50/60/70

Electrical data based on: electric reheat - NO, steam generator humidifier - YES, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

58/73/80 27/84/40 20/25/30

N/A N/A N/A

73/84/80 33/37/40 26/80/35

88/103/125 41/48/50 30/35/40

88/103/125 41/48/50 30/35/40

N/A N/A N/A

Electrical data based on: electric reheat - YES, steam generator humidifier - NO, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

93/116/125 42/53/60 33/41/45

N/A 107/126/150 143/172/175 143/172/175

N/A N/A N/A

N/A N/A

48/57/60 39/45/50

66/79/80 50/60/70

66/79/80 50/60/70

Electrical data based on: electric reheat - NO, steam generator humidifier - NO, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

30/38/60 14/18/30 10/13/20

N/A N/A N/A

44/48/60 20/21/25 16/17/20

60/68/90 28/32/45 20/23/30

60/68/90 28/32/45 20/23/30

N/A N/A N/A

NEXT SIZE MOTOR

Motor horsepower Number of motors 208-230/3/60 460/3/60 575/3/60 FLA FLA FLA

10 1 30.0 14.0 10.0

N/A N/A N/A N/A N/A

5 3 14.8 6.6 5.3

10 2 30.0 14.0 10.0

10 2 30.0 14.0 10.0

N/A N/A N/A N/A N/A

FLA - Full load amps MCA - Minimum circuit ampacity (wire sizing amps) MFS - Maximum over current protection device ampacity

21

CHILLED WATER: Performance data at OPTIONAL airflow - Option 1,

7 - 18 nominal tons

MODEL NUMBER CAPACITY* in Btu/hr - gross 80 ° F DB/67 ° F WB (50% RH) Total Sensible Flow rate in GPM Pressure drop in PSI 75 ° F DB/62.5 ° F WB (50% RH) Total Sensible Flow rate in GPM Pressure drop in PSI 75 ° F DB/61 ° F WB (45% RH) Total Sensible Flow rate in GPM Pressure drop in PSI 72 ° F DB/60 ° F WB (50% RH) Total Sensible Flow rate in GPM Pressure drop in PSI 72 ° F DB/ 58.6 ° F WB (45% RH) Total Sensible Flow rate in GPM Pressure drop in PSI

DACD/U-07 DACD/U-09

DACD/U-11

DACD/U-13

DACD/U-15 DACD/U-18

115,200 89,000 22 9.4

146,200 106,500 26 13.3

183,100 125,700 35 8.9

216,700 143,200 45 10.3

276,700 202,100 50 11.9

347,900 241,500 60 16.6

88,900 79,200 20 7.8

112,500 94,800 24 11.4

136,800 109,600 30 6.6

158,100 122,500 35 6.4

210,800 178,700 45 9.7

258,500 210,000 50 11.8

82,700 80,700 18 6.3

104,000 97,500 22 9.9

124,600 112,200 27 5.4

143,600 125,100 32 5.4

195,700 183,700 42 8.5

237,400 215,400 46 10

72,300 70,000 16 5.0

92,200 85,200 20 7.9

110,600 98,000 24 4.3

127,700 109,400 28 4.2

173,900 160,700 38 7.1

212,200 189,000 42 8.5

70,100 70,100 15 4.4

88,100 87,400 19 7.1

103,400 100,700 22 3.7

117,500 112,100 25 3.4

163,500 162,400 34 5.7

198,000 193,100 38 7

BLOWER SECTION Airflow - CFM Standard motor - horsepower External static pressure - inches of W.G. Number of motors/fans 3,750 2 0.5 1/1 4,000 3 0.5 1/1 4,250 3 0.5 1/1 4,500 3 0.5 1/1 8,000 5 0.5 1/2 8,500 7.5 0.5 1 /2

Maximum external static pressure Downflow (Standard motor) Upflow Maximum external static pressure Downflow (Next size motor) Upflow Next size motor - horsepower

0.9 0.7 1.5 1.5 3

1.5 1.5 1.5 1.5 5

1.2 1.0 1.5 1.5 5

0.7 0.5 1.5 1.5 5

1.1 0.9 1.5 1.5 7.5

1.5 1.5 1.5 1.4 10

* Capacity data is based on 45º F entering water temperature.

22

CHILLED WATER: Performance data at OPTIONAL airflow - Option 1,

22 - 50 nominal tons

MODEL NUMBER CAPACITY* in Btu/hr - gross 80 ° F DB/67 ° F WB (50% RH) Total Sensible Flow rate in GPM Pressure drop in PSI 75 ° F DB/62.5 ° F WB (50% RH) Total Sensible Flow rate in GPM Pressure drop in PSI 75 ° F DB/61 ° F WB (45% RH) Total Sensible Flow rate in GPM Pressure drop in PSI 72 ° F DB/60 ° F WB (50% RH) Total Sensible Flow rate in GPM Pressure drop in PSI 72 ° F DB/58.6 ° F WB (45% RH) Total Sensible Flow rate in GPM Pressure drop in PSI

DACD/U-22 DACD/U-26 DACD/U-30 DACD/U-40 DACD/U-45 DACD/U-50

424,800 287,100 72 25.7

477,500 321,900 92 21.3

592,600 401,400 100 25.6

669,500 470,800 125 21.2

795,400 545,000 140 27.2

907,800 612,000 150 32.3

315,400 248,800 60 18.4

358,000 280,600 80 16.4

448,900 352,100 90 21.0

492,200 407,400 100 14.0

581,700 469,100 110 17.6

667,000 527,100 120 21.7

288,000 254,700 55 15.6

325,800 286,900 73 13.9

410,000 360,800 83 18.0

457,100 420,400 95 12.7

538,800 484,100 105 16.2

610,300 540,400 110 18.5

258,000 223,700 50 13.0

291,800 252,000 66 11.5

368,000 317,200 76 15.3

406,000 367,400 85 10.2

474,000 420,700 90 12.1

545,600 474,100 100 15.5

238,900 229,100 45 10.7

269,100 258,200 59 9.4

340,700 325,800 69 12.9

378,400 372,900 75 8.1

446,900 434,000 85 10.8

512,100 490,200 95 14.1

BLOWER SECTION Airflow in CFM Standard Motor Horsepower External static pressure - inches of W.G. Number of motors/fans 9,500 10 0.5 1/2 10,000 10 0.5 1/2 13,200 5 0.5 3/3 17,000 7.5 0.5 2/4 18,500 10 0.5 2/4 20,000 10 0.5 2/4

Maximum external static pressure Downflow 1.5 (Std. Motor) Upflow 1.5 Maximum external static pressure Downflow N/A (Next Size Motor) Upflow N/A Next size motor horsepower N/A

1.0 0.9 N/A N/A N/A

1.5 1.3 N/A N/A N/A

0.8 0.7 1.5 1.5 10

1.5 1.5 1.5 1.5 N/A

1.2 1.0 N/A N/A N/A

* Capacity data is based on 45º F entering water temperature.

23

CHILLED WATER: Performance data at OPTIONAL AIRFLOW - Option 1, 7 - 18 nominal tons

MODEL NUMBER COIL DATA Face area - sq.ft. Rows of coils Face velocity - fpm

DACD/U-07 DACD/U-09 DACD/U-11 DACD/U-13 DACD/U-15 DACD/U-18

12.2 3 307

12.2 4 328

12.2 5 348

12.2 6 369

24.4 3 328

24.4 4 348

CONTROL VALVE Valve Body Valve CV Valve size - inches

(Modulating Control designed at 400 psi)

3-WAY 10 1

3-WAY 10 1

3-WAY 16 1-1/4

3-WAY 25 1-1/2

3-WAY 25 1-1/2

3-WAY 40 2

CONNECTION SIZES Supply - O.D. Copper Return - O.D. Copper Condensate drain Humidifier supply

(Inches)

1-1/8 1-1/8 3/4 1/4

1-1/8 1-1/8 3/4 1/4

1-5/8 1-5/8 3/4 1/4

1-5/8 1-5/8 3/4 1/4

1-5/8 1-5/8 3/4 1/4

2-1/8 2-1/8 3/4 1/4

REHEAT SECTION Type Capacity Electric 3-stage kW Btu/hr Steam Btu/hr STD 15 51,225 Optional 96,000 68,000 Optional 58,300 42,700 5 STD 15 51,225 Optional 99,000 71,000 Optional 59,800 44,000 5 STD 15 51,225 Optional 101,000 74,000 Optional 64,700 47,000 6 STD 15 51,225 Optional 103,000 77,000 Optional 66,100 48,500 6 STD 22.5 76,835 Optional 208,000 147,000 Optional 128,600 93,400 8 STD 22.5 76,835 Optional 214,000 153,000 Optional 131,900 96,400 8

Type Capacity

Downflow Upflow

Type Capacity

Hot water Btu/hr GPM

Downflow Upflow

HUMIDIFIER SECTION Type Capacity Steam generator kW lbs/hr *(adjustable) Standard 3.4 10 Standard 3.4 10 Standard 3.4 10 Standard 3.4 10 Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30*

24

CHILLED WATER: Performance data at OPTIONAL AIRFLOW - Option 1,

22 - 50 nominal tons

MODEL NUMBER COIL DATA Face area - sq.ft. Rows of coil Face Velocity - fpm

DACD/U-22

DACD/U-26 DACD/U-30 DACD/U-40 DACD/U-45 DACD/U-50

24.4 5 389

24.4 6 410

30.9 6 427

42.8 4 397

42.8 5 432

42.8 6 467

CONTROL VALVE Valve body Valve CV Valve - inches

(Modulating Control designed at 400 psi)

3-WAY 40 2

3-WAY 40 2

3-WAY 40 2

3-WAY 40 2

3-WAY 40 2

3-WAY 40 2

CONNECTION SIZES Supply - O.D. Copper Return - O.D. Copper Condensate drain Humidifier supply

(Inches)

2-1/8 2-1/8 3/4 1/4

2-1/8 2-1/8 3/4 1/4

2-1/8 2-1/8 3/4 1/4

2-5/8 2-5/8 3/4 1/4

2-5/8 2-5/8 3/4 1/4

2-5/8 2-5/8 3/4 1/4

REHEAT SECTION Type Capacity Electric 3-stage kW Btu/hr Steam Btu/hr Standard 22.5 76,835 Optional 222,000 164,000 Optional 137,900 101,800 8 Standard 22.5 76,835 Optional 226,000 169,000 Optional 140,800 104,200 8 Standard 22.5 76,835 Optional 285,000 217,000 Optional 172,100 129,700 10 Standard 30 102,360 Optional 284,000 213,000 Optional 183,200 134,800 10 Standard 30 102,360 Optional 294,000 223,000 Optional 189,400 140,400 10 Standard 30 102,360 Optional 302,000 230,000 Optional 195,100 145,600 10

Type Capacity

Downflow Upflow

Type Capacity

Hot water Btu/hr GPM

Downflow Upflow

HUMIDIFIER SECTION Type Capacity Steam generator kW lbs/hr *(adjustable) Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30*

25

CHILLED WATER: Performance at OPTIONAL AIRFLOW - Option 1,

7 - 18 nominal

MODEL NUMBER FILTER SECTION Quantity/Size Downflow Upflow

DACD/U-07 DACD/U-09 DACD/U-11 DACD/U-13 DACD/U-15 DACD/U-18

(Pleated, 30% efficient, based on ASHRAE Std. 52-76)

4-16x20 2-20x25

4-16x20 2-20x25

4-16x20 2-20x25

4-16x20 2-20x25

2-16x20 4-16x25 2-20x25 2-16x25

2-16x20 4-16x25 2-20x25 2-16x25

ELECTRICAL SECTION

Electrical data based on STANDARD UNIT: electric reheat-YES, steam generator humidifier-YES, and STANDARD MOTOR.

460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS

22/27/30 18/22/25

23/29/30 18/23/25

23/29/30 18/23/25

23/29/30 18/23/25

35/44/45 28/35/40

208-230/3/60

FLA/MCA/MFS

48/60/70

50/63/70

50/63/70

50/63/70

77/97/100

Electrical data based on: electric reheat - NO, steam generator humidifier - YES, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS

22/28/30

25/31/35 8.5/11/15 6.7/8.4/15

25/31/35 8.5/11/15 6.7/8.4/15

25/31/35 8.5/11/15 6.7/8.4/15

43/54/60 19/24/25 16/19/20

FLA/MCA/MFS 7.3/9.1/15 FLA/MCA/MFS 5.9/7.4/15

Electrical data based on: electric reheat - YES, steam generator humidifier - NO, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

48/60/70 22/27/30 18/22/25

50/63/70 23/29/30 18/23/25

50/63/70 23/29/30 18/23/25

50/63/70 23/29/30 18/23/25

77/97/100 35/44/45 28/35/40

Electrical data based on: electric reheat - NO, steam generator humidifier - NO and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS

6/7.5/15 3/3.8/15

8.4/11/15 4.2/5.3/15 3.3/4.1/15

8.4/11/15 4.2/5.3/15 3.3/4.1/15

8.4/11/15 4.2/5.3/15 3.3/4.1/15

15/19/30 6.6/8.3/15 5.3/6.6/15

83/103/110 38/48/50 31/39/40

48/60/70 23/29/35 19/24/25

83/103/110 38/48/50 31/39/40

20/25/40 10/13/20 8.6/11/15

FLA/MCA/MFS 2.5/3.1/15

STANDARD MOTOR Motor horsepower Number of motors 208-230/3/60 460/3/60 575/3/60 FLA FLA FLA 2 1 6.0 3.0 2.5

3 1 8.4 4.2 3.3

3 1 8.4 4.2 3.3

3 1 8.4 4.2 3.3

5 1 14.8 6.6 5.3

7.5 1 20.0 10.1 8.6

FLA - Full load amps MCA - Minimum circuit ampacity (wire sizing amps) MFS - Maximum overcurrent protection device amp

26

CHILLED WATER: Performance data at OPTIONAL AIRFLOW - Option 1,

22 - 50 nominal tons

MODEL NUMBER FILTER SECTION Quantity/size Downflow Upflow

DACD/U-22 DACD/U-26 DACD/U-30 DACD/U-40 DACD/U-45 DACD/U-50

(Pleated, 30% efficient based on ASHRAE Std. 52-76)

2-16x20 2-16x25 2-16x25 2-16x25

2-20x25 2-16x25 2-20x25 2-16x25

4-16x20 4-16x25 3-20x25 2-16x25

10-16x25 6-20x25

10-16x25 6-20x25

ELECTRICAL SECTION

Electrical data based on STANDARD UNIT: electric reheat-YES, steam generator humidifier-YES, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS 93/116/125 FLA/MCA/MFS FLA/MCA/MFS 42/53/60 33/41/45

93/116/125 107/126/150 123/149/150 143/172/175 143/172/175

42/53/60 33/41/45

48/57/60 39/40/50

58/70/80 47/57/60

66/79/80 50/6070

Electrical data based on: electric reheat - NO, steam generator humidifier - YES, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

58/73/90 27/34/40 20/25/30

58/73/90 27/34/40 20/25/30

73/84/90 33/37/40 26/30/40

68/80/90 33/39/45 27/32/35

88/103/125 88/103/125

41/48/50 30/35/40

Electrical data based on: electric reheat - YES, steam generator humidifier - NO, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS 93/116/125 FLA/MCA/MFS FLA/MCA/MFS 42/53/60 33/41/45

93/116/125 107/126/150 123/149/150 143/172/175 143/172/175

42/53/60 33/41/45

48/57/60 39/40/50

56/70/80 47/57/60

66/79/80 50/60/70

Electrical data based on: electric reheat - NO, steam generator humidifier - NO, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

30/38/60 14/18/30 10/13/20

30/38/60 14/18/30 10/13/20

44/48/60 20/21/25 16/17/20

40/45/60 20/23/30 17/19/25

60/68/90 28/32/45 20/23/30

STANDARD MOTOR Motor horsepower Number of motors 208-230/3/60 460/3/60 575/3/60 FLA FLA FLA 10 1 30.0 14.0 10.0

10 1 30.0 14.0 10.0

5 3 14.8 6.6 5.3

7.5 2 20.0 10.1 8.6

10 2 30.0 14.0 10.0

FLA - Full load amps MCA - Minimum circuit ampacity (wire sizing amps) MFS - Maximum overcurrent protection device amps

27

10-16x25 6-20x25

66/79/80 50/6070

41/48/50 30/35/40

66/79/80 50/60/70

60/68/90 28/32/45 20/23/30

10 2 30.0 14.0 10.0

CHILLED WATER: Performance data at OPTIONAL AIRFLOW - Option 1,

7 - 18 nominal tons

MODEL NUMBER

DACD/U-07 DACD/U-09 DACD/U-11 DACD/U-13 DACD/U-15 DACD/U-18

ELECTRICAL SECTION Electric data based on: electric reheat - YES, steam generator humidifier - YES, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

50/63/70 23/29/30 18/23/25

56/71/80 25/32/35 20/25/30

56/71/80 25/32/35 20/25/30

56/71/80 25/32/35 20/25/30

83/103/110 38/48/50 31/39/40

93/116/125 42/53/60 33/41/45

Electrical data based on: electric reheat - NO, steam generator humidifier - YES, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

25/31/35 8.5/11/15 6.7/8.4/15

31/39/40 11/14/15 8.7/11/15

31/39/40 11/14/15 8.7/11/15

31/39/40 11/14/15 8.7/11/15

48/60/70 23/29/35 19/24/25

58/73/80 27/34/40 20/25/30

Electrical data based on: electric reheat - YES, steam generator humidifier - NO and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

50/63/70 23/29/30 18/23/25

56/71/80 25/32/35 20/25/30

56/71/80 25/32/35 20/25/30

56/71/80 25/32/35 20/25/30

83/103/110 38/48/50 31/39/40

93/116/125 42/53/60 33/41/45

Electrical data based on: electric reheat - NO, steam generator humidifier - NO, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

8.4/11/15 4.2/5.3/15 3.3/4.1/15

15/19/30 6.6/8.3/15 5.3/6.6/15

15/19/30 6.6/8.3/15 5.3/6.6/15

15/19/30 6.6/8.3/15 5.3/6.6/15

20/25/45 10/13/20 8.6/11/15

30/38/60 14/18/30 10/13/20

NEXT SIZE MOTOR Motor horsepower Number of motors 208-230/3/60 460/3/60 575/3/60 FLA FLA FLA 3 1 8.4 4.2 3.3

5 1 14.8 6.6 5.3

5 1 14.8 6.6 5.3

5 1 14.8 6.6 5.3

7.5 1 20.0 10.1 8.6

10 1 30.0 14.0 10.0

FLA - Full load amps MCA - Minimum circuit ampacity (wiring sizing amps) MFS - Maximum overcurrent protection device amps

28

CHILLED WATER: Performance data OPTIONAL AIRFLOW - Option 1,

22 - 50 nominal tons

MODEL NUMBER

DACD/U-22 DACD/U-26 DACD/U-30 DACD/U-40 DACD/U-45 DACD/U-50

ELECTRICAL SECTION Electrical data based on: electric reheat - YES, steam generator humidifier - YES, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS N/A N/A N/A N/A N/A N/A N/A 143/172/175

N/A N/A N/A

N/A N/A N/A

N/A N/A

66/79/80 50/60/70

Electrical data based on: electric reheat - NO, steam generator humidifier - YES, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

N/A N/A N/A

N/A N/A N/A

N/A N/A N/A

88/103/125 41/48/50 30/35/40

N/A N/A N/A

N/A N/A N/A

Electrical data based on: electric reheat - YES, steam generator humidifier - NO, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

N/A N/A N/A

N/A N/A N/A

N/A 143/172/175

N/A N/A N/A

N/A N/A N/A

N/A N/A

66/79/80 50/60/70

Electrical data based on: electric reheat - NO, steam generator humidifier - NO, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

N/A N/A N/A

N/A N/A N/A

N/A N/A N/A

60/68/90 28/32/45 20/23/30

N/A N/A N/A

N/A N/A N/A

NEXT SIZE MOTOR Motor horsepower Number of motors 208-230/3/60 460/3/60 575/3/60 FLA FLA FLA N/A N/A N/A N/A N/A

N/A N/A N/A N/A N/A

N/A N/A N/A N/A N/A

10 2 30.0 14.0 10.0

N/A N/A N/A N/A N/A

N/A N/A N/A N/A N/A

FLA - Full load amps MCA - Minimum circuit ampacity (wire sizing amps) MFS - Maximum overcurrent protection device amps

29

CHILLED WATER: Performance data at OPTIONAL AIRFLOW - Option 2,

7 - 18 nominal tons

MODEL NUMBER CAPACITY* in Btu/hr - gross 80 ° F DB/67 ° F WB (50% RH) Total Sensible Flow rate - GPM Pressure drop - PSI 75 ° F DB/62.5 ° F WB (50% RH) Total Sensible Flow rate - GPM Pressure drop - PSI 75 ° F DB/61 ° F WB (45% RH) Total Sensible Flow rate - GPM Pressure drop - PSI 72 ° F DB/60 ° F WB (50% RH) Total Sensible Flow rate - GPM Pressure drop - PSI 72 ° F DB/ 58.6 ° F WB (45% RH) Total Sensible Flow rate - GPM Pressure drop - PSI

DACD/U-07 DACD/U-09

DACD/U-11 DACD/U-13 DACD/U-15 DACD/U-18

121,200 96,400 22 9.4

154,100 115,300 26 13.3

199,100 140,800 35 8.9

243,000 165,800 45 10.3

291,700 218,200 50 11.9

368,000 260,600 60 16.6

94,100 85,900 20 7.8

119,200 102,900 24 11.4

149,400 123,400 30 6.6

177,400 142,300 35 6.4

289,300 193,400 45 9.7

274,000 227,200 50 11.8

88,200 87,100 18 6.3

110,900 105,800 22 9.9

137,000 126,600 27 5.4

162,500 146,200 32 5.4

208,500 198,700 42 8.5

253,000 233,400 46 10.0

76,800 75,400 16 5.0

98,000 92,300 20 7.9

120,900 110,200 24 4.3

143,400 127,300 28 4.2

184,700 173,600 38 7.1

225,400 204,400 42 8.5

74,700 74,700 15 4.4

94,300 94,200 19 7.1

114,100 112,900 22 3.7

133,500 130,400 25 3.4

174,700 174,300 34 5.7

211,600 208,300 38 7.0

BLOWER SECTION Airflow - CFM Standard motor - horsepower External static pressure - inches of W.G. Number of motors/fans 4,250 3 0.5 1/1 4,500 3 0.5 1/1 5,000 5 0.5 1/1 5,500 5 0.5 1/1 9,000 7.5 0.5 1/2 9,500 7.5 0.5 1/2

Maximum external static pressure (Standard motor) Maximum external static pressure (Next size motor) Next size motor - horsepower

Downflow Upflow Downflow Upflow

1.4 1.2 1.5 1.5 5

0.9 0.6 1.5 1.5 5

1.5 1.2 1.5 1.2 7.5

0.8 0.5 0.9 0.6 7.5

1.5 1.5 1.5 1.5 10

0.9 0.9 1.4 1.4 10

* Capacity data is based on 45º F entering water temperature

30

CHILLED WATER: Performance data at OPTIONAL AIRFLOW - Option 2,

22 - 50 nominal tons

MODEL NUMBER CAPACITY* in Btu/hr - gross 80 ° F DB/67 ° F WB (50% RH) Total Sensible Flow rate - GPM Pressure drop - PSI 75 ° F DB/62.5 ° F WB (50% RH) Total Sensible Flow rate - GPM Pressure drop - PSI 75 ° F DB/61° F WB (45% RH) Total Sensible Flow rate - GPM Pressure drop - PSI 72 ° F DB/60 ° F WB (50% RH) Total Sensible Flow rate - GPM Pressure drop - PSI 72 ° F DB/58.6 ° F WB (45% RH) Total Sensible Flow rate - GPM Pressure drop - PSI

DACD/U-22 DACD/U-26 DACD/U-30 DACD/U-40 DACD/U-45 DACD/U-50

437,000 297,800 72 25.7

495,000 337,100 92 21.3

634,400 439,300 100 25.6

688,800 489,500 125 21.2

828,900 575,500 140 27.2

932,700 633,600 150 32.3

324,700 258,400 60 18.4

371,600 294,500 80 16.4

482,400 387,200 90 21

506,900 424,000 100 14

606,500 496,200 110 17.6

685,500 546,400 120 21.7

297,200 264,900 55 15.6

339,100 301,700 73 13.9

443,300 398,100 83 18

472,200 437,900 95 12.7

564,100 513,000 105 16.2

628,600 561,000 110 18.5

265,800 232,400 50 13

303,000 264,400 66 11.5

396,200 349,200 76 15.3

418,600 382,300 85 10.2

494,700 445,000 90 12.1

561,000 491,600 100 15.5

246,700 238,000 45 10.7

280,600 271,200 59 9.4

369,600 358,700 69 12.9

391,300 387,200 75 8.1

468,700 458,600 85 10.8

528,300 508,500 95 14.1

BLOWER SECTION Airflow - CFM Standard motor - horsepower External static pressure - inches of W.G. Number of motors/fans 10,000 10 0.5 1/2 10,500 10 0.5 1/2 15,000 5 0.5 3/3 18,000 7.5 0.5 2/4 20,000 10 0.5 2/4 21,000 10 0.5 2/4

Maximum external static pressure (Standard motor) Maximum external static pressure (Next size motor) Next size motor - horsepower

Downflow Upflow

1.5 1.5

0.6 0.5 N/A N/A N/A

1.1 0.7 N/A N/A N/A

1.5 1.5 1.5 1.5 10

1.4 1.2 N/A N/A N/A

0.7 0.5 N/A N/A N/A

Downflow N/A Upflow N/A N/A

* Capacity data is based on 45º F entering water temperature

31

CHILLED WATER: Performance data at OPTIONAL AIRFLOW - Option 2,

7 - 18 nominal tons

MODEL NUMBER COIL DATA Face area - sq. ft. Rows of coil Face velocity - FPM

DACD/U-07 DACD/U-09

DACD/U-11 DACD/U-13 DACD/U-15 DACD/U-18

12.2 3 348

12.2 4 369

12.2 5 410

12.2 6 461

24.4 3 369

24.4 4 389

CONTROL VALVE Valve body Valve CV Valve size - inches

(Modulating Control designed at 400 psi)

3-WAY 10 1

3-WAY 10 1

3-WAY 16 1-1/4

3-WAY 25 1-1/2

3-WAY 25 1-1/2

3-WAY 40 2

CONNECTION SIZES Supply - O.D. Copper Return - O.D. Copper Condensate drain Humidifier supply

(Inches)

1-1/8 1-1/8 3/4 1/4

1-1/8 1-1/8 3/4 1/4

1-5/8 1-5/8 3/4 1/4

1-5/8 1-5/8 3/4 1/4

1-5/8 1-5/8 3/4 1/4

2-1/8 2-1/8 3/4 1/4

REHEAT SECTION Type Capacity Electric 3-Stage in kW in Btu/hr Steam in Btu/hr STD 15 51,225 Optional 101,000 74,000 Optional 61,300 45,200 5 STD 15 51,225 Optional 103,000 77,000 Optional 62,600 46,600 5 STD 15 51,225 Optional 107,000 80,000 Optional 69,000 50,900 6 STD 15 51,225 Optional 111,000 85,000 Optional 71,600 53,400 6 STD 22.5 76,835 Optional 217,000 159,000 Optional 135,000 99,000 8 STD 22.5 76,835 Optional 222,000 164,000 Optional 137,900 101,800 8

Type Capacity

Downflow Upflow

Type Capacity

Hot water in Btu/hr GPM

Downflow Upflow

HUMIDIFIER SECTION Type Capacity Steam generator kW lbs/hr *(adjustable) Standard 3.4 10 Standard 3.4 10 Standard 3.4 10 Standard 3.4 10 Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30*

32

CHILLED WATER: Performance data at OPTIONAL AIRFLOW - Option 2,

22 - 50 nominal tons

MODEL NUMBER COIL DATA Face area - sq. ft. Rows of coil Face velocity - FPM

DACD/U-22 DACD/U-26

DACD/U-30 DACD/U-40 DACD/U-45 DACD/U-50

24.4 5 410

24.4 6 485

30.9 6 427

42.8 4 421

42.8 5 467

42.8 6 491

CONTROL VALVE Valve body Valve CV Valve size - inches

(Modulating Control designed at 400 psi)

3-WAY 40 2

3-WAY 40 2

3-WAY 40 2

3-WAY 40 2

3-WAY 40 2

3-WAY 40 2

CONNECTION SIZES Supply - O.D. Copper Return - O.D. Copper Condensate drain Humidifier supply

(Inches)

2-1/8 2-1/8 3/4 1/4

2-1/8 2-1/8 3/4 1/4

2-1/8 2-1/8 3/4 1/4

2-5/8 2-5/8 3/4 1/4

2-5/8 2-5/8 3/4 1/4

2-5/8 2-5/8 3/4 1/4

REHEAT SECTION Type Capacity Electric 3-Stage kW Btu/hr Steam Btu/hr Standard 22.5 76,835 Optional 226,000 169,000 Optional 140,800 104,200 8 Standard 22.5 76,835 Optional 229,000 173,000 Optional 143,500 106,700 8 Standard 22.5 76,835 Optional 302,000 230,000 Optional 180,100 137,300 10 Standard 30 102,360 Optional 290,000 219,000 Optional 187,300 138,600 10 Standard 30 102,360 Optional 302,000 230,000 Optional 195,100 145,600 10 Standard 30 102,360 Optional 309,000 236,000 Optional 198,800 149,000 10

Type Capacity

Downflow Upflow

Type Capacity

Hot water in Btu/hr GPM

Downflow Upflow

HUMIDIFIER SECTION Type Capacity Steam generator kW lbs/hr *(adjustable) Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30* Standard 3.3-10.2 10-30*

33

CHILLED WATER: Performance data at OPTIONAL AIRFLOW - Option 2,

7 - 18 nominal tons

MODEL NUMBER FILTER SECTION Quantity/size Downflow Upflow

DACD/U-07 DACD/U-09

DACD/U-11 DACD/U-13 DACD/U-15 DACD/U-18

(Pleated, 30% efficient, based on ASHRAE Std. 52-76)

4-16x20 2-20x25

4-16x20 2-20x25

4-16x20 2-20x25

4-16x20 2-20x25

2-16x20 4-16x25 2-20x25 2-16x25

2-16x20 4-16x25 2-20x25 2-16x25

ELECTRICAL SECTION

Electrical data based on STANDARD UNIT: electric reheat-YES, steam generator humidifier-YES, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

50/63/70 23/29/30 18/23/25

50/63/70 23/29/30 18/23/25

56/71/80 25/32/35 20/25/30

56/71/80 25/32/35 20/25/30

56/74/180 38/48/50 31/39/40

83/103/110 38/48/50 31/39/40

Electrical data based on: electric reheat - NO, steam generator humidifier - YES, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

25/31/35 8.5/11/15 6.7/8.4/15

25/31/35 8.5/11/15 6.7/8.4/15

31/39/45 11/14/15 8.7/11/15

31/39/45 11/14/15 8.7/11/15

48/60/70 23/29/35 19/24/25

48/60/70 23/29/35 19/24/25

Electrical data based on: electric reheat - YES, steam generator humidifier - NO, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

50/63/70 23/29/30 18/23/25

50/63/70 23/29/30 18/23/25

56/71/80 25/32/35 20/25/30

56/71/80 25/32/35 20/25/30

83/103/110 38/48/50 31/39/40

83/103/110 38/48/50 31/39/40

Electrical data based on: electric reheat - NO, steam generator humidifier - NO, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

8.4/11/15 4.2/5.3/15 3.3/4.1/15

8.4/11/15 4.2/5.3/15 3.3/4.1/15

15/19/30 6.6/8.3/15 5.3/6.6/15

15/19/30 6.6/8.3/15 5.3/6.6/15

20/25/40 10/13/20 8.6/11/15

20/25/40 10/13/20 8.6/11/15

STANDARD MOTOR Motor horsepower Number of motors 208-230/3/60 460/3/60 575/3/60 FLA FLA FLA 3 1 8.4 4.2 3.3

3 1 8.4 4.2 3.3

5 1 14.8 6.6 5.3

5 1 14.8 6.6 5.3

7.5 1 20.0 10.1 8.6

7.5 1 20.0 10.1 8.6

FLA - Full load amps MCA - Minimum circuit ampacity (wire sizing amps) MFS - Maximum overcurrent protection device amps

34

CHILLED WATER: Performance data at OPTIONAL AIRFLOW - Option 2,

22 - 50 nominal tons

MODEL NUMBER FILTER SECTION Quantity/size Downflow Upflow

DACD/U-22 DACD/U-26

DACD/U-30 DACD/U-40 DACD/U-45 DACD/U-50

(Pleated, 30% efficient based on ASHRAE Std. 52-76)

2-16x20 2-16x25 2-16x25 2-16x25

2-20x25 2-16x25 2-20x25 2-16x25

4-16x20 4-16x25 3-20x25 2-16x25

10-16x25 6-20x25

10-16x25 6-20x25

ELECTRICAL SECTION

Electrical data based on STANDARD UNIT: electric reheat-YES, steam generator humidifier-YES, and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS 93/116/125 FLA/MCA/MFS FLA/MCA/MFS 42/53/60 33/41/45

93/116/125 107/126/150 123/149/150 143/172/175 143/172/175

42/53/60 33/41/45

48/57/60 39/45/50

58/70/80 47/57/60

66/79/80 50/60/70

Electrical data based on: electric reheat - NO, steam generator humidifier - YES and STANDARD MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

58/73/90 27/34/40 20/25/30

58/73/90 27/34/40 20/25/30

73/84/90 33/37/40 26/30/40

68/80/90 33/39/45 27/32/35

88/103/125 88/103/125 41/48/50 30/35/40

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS 93/116/125 FLA/MCA/MFS FLA/MCA/MFS 42/53/60 33/41/45

93/116/125 107/126/150 123/149/150 143/172/175 148/172/175

42/53/60 33/41/45

48/57/60 39/45/50

58/70/80 47/57/60

66/79/80 50/6070

Electrical data based on: electric reheat - YES, steam generator humidifier - NO and STANDARD MOTOR.

Electrical data based on: electric reheat - NO steam generator humidifier - NO and STANDARD MOTOR

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

30/38/60 14/18/30 10/13/20

30/38/60 14/18/30 10/13/20

44/48/60 20/21/25 16/17/20

40/45/60 20/23/30 17/19/25

60/68/90 28/32/45 20/23/30

STANDARD MOTOR Motor horsepower Number of motors 208-230/3/60 460/3/60 575/3/60 FLA FLA FLA 10 1 30.0 14.0 10.0

10 1 30.0 14.0 10.0

5 3 14.8 6.6 5.3

7.5 2 20.0 10.1 8.6

10 2 30.0 14.0 10.0

FLA - Full load amps MCA - Minimum circuit ampacity (sire sizing amps) MFS - Maximum overcurrent protection device amps

35

10-16x25 6-20x25

66/79/80 50/60/70

41/48/50 30/35/40

66/79/80 50/60/70

60/68/90 28/32/45 20/23/30

10 2 30.0 14.0 10.0

CHILLED WATER: Performance data at OPTIONAL AIRFLOW - Option 2,

7 - 18 nominal tons

MODEL NUMBER

DACD/U-07 DACD/U-09

DACD/U-11 DACD/U-13 DACD/U-15 DACD/U-18

ELECTRICAL SECTION Electrical data based on: electric reheat - YES, steam generator humidifier - YES, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

56/71/80 25/32/35 20/25/30

56/71/80 25/32/35 20/25/30

62/77/80 29/36/40 24/30/35

62/77/80 29/36/40 24/30/35

93/116/125 42/53/60 33/41/45

93/116/125 42/53/60 33/41/45

Electrical data based on: 208-230/3/60 460/3/60 575/3/60

electric reheat - NO, steam generator humidifier - YES and NEXT SIZE MOTOR.

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

31/39/45 11/14/15 8.7/11/15

31/39/45 11/14/15 8.7/11/15

36/45/50 14/18/25 12/15/20

36/45/50 14/18/25 12/15/20

58/78/80 27/34/40 20/25/30

58/78/80 27/34/40 20/25/30

Electrical data based on: electric reheat - YES steam generator humidifier - NO, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

56/71/80 25/32/35 20/25/30

56/71/80 25/32/35 20/25/30

62/77/80 25/32/35 24/30/35

62/77/80 25/32/35 24/30/35

93/116/125 42/53/60 33/41/45

93/116/125 42/53/60 33/41/45

Electrical data based on: electric reheat - NO, steam generator humidifier - NO and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

15/19/30 6.6/8.3/15 5.3/6.6/15

15/19/30 6.6/8.3/15 5.3/6.6/15

20/25/45 10/13/20 8.6/11/15

20/25/45 10/13/20 8.6/11/15

30/38/60 14/18/30 10/13/20

30/38/60 14/18/30 10/13/20

NEXT SIZE MOTOR Motor horsepower Number of motors 208-230/3/60 460/3/60 575/3/60 FLA FLA FLA 5 1 14.8 6.6 5.3

5 1 14.8 6.6 5.3

7.5 1 20.0 10.1 8.6

7.5 1 20.0 10.1 8.6

10 1 30.0 14.0 10.0

10 1 30.0 14.0 10.0

FLA - Full load amps MCA - Minimum circuit ampacity (wire sizing amps) MFS - Maximum overcurrent protection device amps

36

CHILLED WATER: Performance data at OPTIONAL AIRFLOW - Option 2,

22 - 50 nominal tons

MODEL NUMBER

DACD/U-22 DACD/U-26

DACD/U-30 DACD/U-40 DACD/U-45 DACD/U-50

ELECTRICAL SECTION Electrical data based on: electric reheat - YES, steam generator humidifier - YES, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS N/A N/A N/A N/A N/A N/A N/A 143/172/175

N/A N/A N/A

N/A N/A N/A

N/A N/A

66/79/80 50/60/70

Electrical data based on: electric reheat - NO, steam generator humidifier - YES, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

N/A N/A N/A

N/A N/A N/A

N/A N/A N/A

88/103/125 41/48/50 30/35/40

N/A N/A N/A

N/A N/A N/A

Electrical data based on: electric reheat - YES, steam generator humidifier - NO, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

N/A N/A N/A

N/A N/A N/A

N/A 143/172/175

N/A N/A N/A

N/A N/A N/A

N/A N/A

66/79/80 50/60/70

Electrical data based on: electric reheat - NO, steam generator humidifier - NO, and NEXT SIZE MOTOR.

208-230/3/60 460/3/60 575/3/60

FLA/MCA/MFS FLA/MCA/MFS FLA/MCA/MFS

N/A N/A N/A

N/A N/A N/A

N/A N/A N/A

60/68/90 28/32/45 20/23/30

N/A N/A N/A

N/A N/A N/A

NEXT SIZE MOTOR Motor horsepower Number of motors 208-230/3/60 460/3/60 575/3/60 FLA FLA FLA N/A N/A N/A N/A N/A

N/A N/A N/A N/A N/A

N/A N/A N/A N/A N/A

10 2 30.0 14.0 10.0

N/A N/A N/A N/A N/A

N/A N/A N/A N/A N/A

FLA - Full load amps MCA - Minimum circuit ampacity (wire sizing amps) MFS - Maximum overcurrent protection device amps

37

Weights and Dimensional Data

DOWNFLOW

Model DACD-07 DACD-09 DACD-11 DACD-13 DACD-15 DACD-18 DACD-22 DACD-26 DACD-30 DACD-40 DACD-45 DACD-50 Operating Weight 725 745 805 845 955 1,065 1,215 1,415 1,865 2,485 2,685 2,785 lbs lbs lbs lbs lbs lbs lbs lbs lbs lbs lbs lbs Shipping Weight 860 880 940 980 1,190 1,300 1,450 1,650 2,160 2,875 3,075 3,175 lbs lbs lbs lbs lbs lbs lbs lbs lbs lbs lbs lbs Length 43.00" 43.00" 43.00" 43.00" 74.50" 74.50" 74.50" 74.50" 93.25" 125.00" 125.00" 125.00" Width 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" Height 72.00" 72.00" 72.00" 72.00" 72.00" 72.00" 72.00" 72.00" 72.00" 72.00" 72.00" 72.00"

UPFLOW

Model DACU-07 DACU-09 DACU-11 DACU-13 DACU-15 DACU-18 DACU-22 DACU-26 DACU-30 DACU-40 DACU-45 DACU-50 Operating Weight 725 745 805 845 955 1,065 1,215 1,415 2,110 2,485 2,685 2,785 lbs lbs lbs lbs lbs lbs lbs lbs lbs lbs lbs lbs Shipping Weight 860 880 940 980 1,190 1,300 1,450 1,650 2,440 2,825 3,075 3,175 lbs lbs lbs lbs lbs lbs lbs lbs lbs lbs lbs lbs Length 43.00" 43.00" 43.00" 43.00" 74.50" 74.50" 74.50" 74.50" 106.00" 125.00" 125.00" 125.00" Width 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" 34.50" Height 72.00" 72.00" 72.00" 72.00" 72.00" 72.00" 72.00" 72.00" 72.00" 72.00" 72.00" 72.00"

38

CHILLED WATER DIMENSIONAL and COMPONENT DATA

39

DATA AIRE 7, 9, 11 and 13 ton, Downflow

40

DATA AIRE 7, 9, 11 and 13 ton, Upflow

41

DATA AIRE 15, 18, 22 and 26 ton, Downflow

42

DATA AIRE 15, 18, 22 and 26 ton, Upflow

43

DATA AIRE 30 ton, Downflow

44

DATA AIRE 30 ton, Upflow

45

DATA AIRE 40, 45 & 50 ton, Downflow

46

DATA AIRE 40, 45 & 50 ton, Upflow

47

Guide Specifications

DATA AIRE SERIES 7 to 50 TON CHILLED WATER UNITS

GENERAL The environmental control units shall be provided with a high sensible cooling system, factory assembled, piped, wired, and run tested prior to shipment and designed for the following air pattern: ___ Down Discharge ___ Top Discharge with Duct Connection ___ Top Discharge with Plenum The system shall be designed for draw through air arrangement to insure even air distribution to the entire face of the coil. Units shall be ETL or UL listed.

CABINET and FRAME The frame shall be constructed of 14 gauge welded tubular steel and coated with a heavy corrosion inhibiting finish for long life. All internal fans shall be of high grade steel and shall be coated and sealed for utmost protection against corrosion. The unit shall have complete front and side access by means of high quality furniture grade steel doors with heavy duty hinges. The doors shall be lined with one inch thick, 11/2 pound density fiber insulation. Each door shall be provided with sure close latches which shall be quickly removable for easy access and a polyurethane gasket to prevent air leakage. The doors shall be painted to match or contrast with other equipment in the space. Bypass air shall be provided around the cooling coil to prevent saturated air from being distributed to other equipment in the controlled space. The cooling coil shall sit in a stainless steel drain pan. The unit shall be painted _________________.

CHILLED WATER CIRCUIT The chilled water coil shall be in an "A" frame arrangement to allow maximum coil surface in a small cabinet. The large faced coil shall be constructed with 1/2" O.D. copper tube with 12 fins per inch of corrugated aluminum. Chilled water flow shall be controlled by a 3-way modulating valve for accurate and economical temperature control and dehumidification. Air bypass shall be provided to prevent saturated air from being introduced into the conditioned space. BLOWER SECTION The blower shall be a belt driven centrifugal type, double width, double inlet and shall be statically and dynamically balanced at the factory as a complete assembly to a maximum vibration level of two mils in any plane. The blower wheel shall be a maximum of 15 inches in diameter.. The blower wheel shall be supported on a heavy steel shaft having self-aligning ball bearings with a minimum life span of 100,000 hours. The blower wheel shall be driven by a motor on an adjustable slide base. The drive motor shall be 1750 rpm. The drive package shall be belt driven with two (2) belts and variable pitch sheave sized for 200% of the fan motor horsepower. The blower shall be located to draw air over the coil to insure even air distribution and maximum coil performance.

48

GUIDE SPECIFICATIONS, continued

FILTER CHAMBER The filter chamber shall be an integral part of the system, designed within the frame and cabinet. The filters shall be four inch (4") deep pleated design, rated not less than 30% efficient (based on ASHRAE Std. 52-76).

ELECTRIC REHEAT The reheat shall be of the finned enclosed, sheath type, fabricated of stainless steel core sheath with plated fins to withstand moist conditions. The reheat shall be installed on the air discharge side of the cooling coil and shall have three (3) stages. Each stage shall be ___ kW. The total kW shall be ___ to operate on a supply of ____ volts.

HUMIDIFIER Steam Generator Humidifier (7 through 13 ton units) - Provide the environmental control unit with a steam generator humidifier. The steam generating humidifier shall be of a self-contained disposable cylinder type with electronic controls. The capacity shall be 10 pounds per hour. Power consumption shall be 3.2 kW. The humidifier shall discharge pure steam with no material dust carry-over and have a self-regulating automatic flush cycle. Cylinders shall be disposable, not requiring cleaning or maintenance. The humidifier fill level, water conductivity, and flush rate shall automatically adapt, both in frequency and duration, to variations in the incoming water. (15 through 50 ton units) - Provide the environmental control unit with a steam generator humidifier. The steam generating humidifier shall be of the self-contained disposable type with electronic controls. The capacity shall be adjustable from 10 to 30 pounds per hour. Power consumption at 22 pounds shall not exceed 7.5 kW. The humidifier shall discharge pure steam with no material dust carry-over and have a self-regulating automatic flush cycle. Cylinders shall be disposable, not requiring cleaning or maintenance. The humidifier fill level, water conductivity, and flush rate shall automatically adapt, both in frequency and duration, to variations in the incoming water.

WATER SENSOR Units shall be provided with one (1) water sensor. The solid state water sensor shall be mounted under the unit to sense the presence of water. The sensor shall be connected to the microprocessor panel and activate an audible alarm. The water detector shall become an integral part of the microprocessor panel and shall display: "WATER DETECTED IN UNDER FLOOR AREA" message when the sensor is activated.

49

CONTROL SYSTEM

The environmental system shall be furnished with a microprocessor based Data Alarm Processor-II panel. The panel shall include unit switching functions and display normal functions, malfunctions, and service diagnostics on a 2 row, 80 character, backlit liquid crystal display (LCD) in a clear vernacular format. The panel shall allow recall and display of the high and low temperature for the last 24 hours, high and low humidity for the last 24 hours, current percent of capacity and average percent of capacity for the last hour of operation for cool 1, cool 2, reheat, humidification, and dehumidification, component runtimes for fan motor, reheat, humidification, and dehumidification. Programming shall have multilevel password access to prevent unauthorized access. Programming shall be accomplished entirely from the front of the unit without the need to access, set, or program switches inside the unit (front door of unit does not need to be opened). Programmable functions shall be entered on nonvolatile EEPROM to insure program retention should power fail. The historical data base shall be maintained by battery backup. Multiple messages shall be displayed by automatically scrolling from each message to the next. Alarm conditions, in addition to being displayed, shall enunciate an audible alarm. A summary alarm relay shall be available for remote alarms. Additional test or service terminal shall not be required for any functions. The control shall include temperature anticipation, moisture level humidity control and automatic flush cycles. An alarm condition shall continue to be displayed until the malfunction is corrected. Multiple alarms shall be displayed sequentially in order of occurrence and only those alarms which have not been acknowledged shall continue to sound an audible alarm. The Data Alarm Processor-II panel shall perform an automatic self-test on system start-up. A user accessible diagnostic program shall aid in system component trouble shooting by displaying on the unit LCD screen the name of the controlled item, output relay number, terminal plug and pin number for each controlled item. The following automatic control functions shall be included: Selectable control type Temperature anticipation Humidity anticipation Compressor short cycle Automatic or manual restart Auxiliary chilled water operation* Chilled water coil flush cycle* Start time delay Sequential load activation Dehumidification lockout Automatic reheat element rotation Energy saver (glycol operation)* Hot water coil flush cycle* Energy saver coil flush cycle*

The following conditions, data and normal functions shall be monitored and displayed: Temperature setpoint Current temperature Cooling Reheat Humidification The following switching and control functions shall be included: System On/Off switch Menu exit button Alarm silence button Manual override for: blower, cooling, heat 1, humidification Menu selection button Select button Program set button Humidity setpoint Current humidity Dehumidification Current percentage of capacity utilized Current discharge temperature*

50

CONTROL SYSTEM, continued

The following historical data shall be available: High temperature last 24 hours High humidity last 24 hours Alarm history (last ten alarms) Average percentage of capacity Low temperature last 24 hours Low humidity last 24 hours Equipment runtimes

The following alarm functions shall be monitored and displayed when they occur in addition to enunciating an audible alarm: High temperature warning High humidity warning Under floor water detected Dirty filter Manual override Low voltage warning Temperature sensor failure Maintenance required Custom message* Local alarm* Discharge air sensor failure* The following functions shall be programmable: Temperature setpoint (65-85o F, 18.3-29.4o C) Temperature deadband ( 1-5o F/C) High temperature alarm limit Low temperature alarm limit Mode and stage response time Audio alarm mode Define password Firestat temperature alarm limit Temperature scale Calibrate temperature sensor Water valve mode Message for optional alarm limit* Remote alarm 1, 2, 3 selection* Automatic self-test Dehumidification mode Calibrate discharge air sensor* Humidifier Humidity setpoint (30-70% RH) Humidity deadband (1-15% RH) High humidity alarm limit Low humidity alarm limit Reset equipment runtimes Manual diagnostics Humidifier auto flush timer Scheduled maintenance Control logic Calibrate humidity sensor Low discharge temperature alarm limit* Delay for optional alarms Person to contact on alarm Humidity anticipation Power problem or restart mode Reheat stages Low temperature warning Low humidity warning No air flow Humidifier failure Firestat tripped Power failure restart Humidity sensor failure Person to contact on alarm* No water flow* Smoke detected* Fan motor overload*

* Some of the programmable selections, displays, or alarms may require additional components or sensors.

51

Options

Data Aire Remote Telecommunications System 200TM Provide the Data Aire Remote Telecommunications System 200 (DART System 200) for comprehensive monitoring and control of the environmental control units via a phone modem to a host PC station.. The environmental control units shall be interfaced with a communications module (DART-Board) with integral phone modem. The DART System 200 shall allow complete remote control, monitoring, and retrieval of all historical data of the Data Aire units through the unit mounted Data Alarm Processor-IITM. Upon alarm at the unit, the DART-Board shall automatically dial one or two pre-programmed numbers and transmit specific alarm information. All entry or configuration capabilities available at the Data Alarm Processor-II shall be accessible at the host station. The commands or requests for data from each unit shall processed through the DART-Board. A single DART-Board shall allow up to 32 Data Aire units to be connected and controlled. The DART System 200 shall be capable of monitoring and controlling up to 200 DART-Boards. The following system features shall be provided: Automatic scrolling of current status Sensor database Password access Automatic status log prints The following programmable functions shall be provided: Temperature setpoint Temperature high limit Temperature low limit Temperature sensitivity (deadband) On/Off/Standby operation Unit identification number Password The following conditions shall be monitored: Specific alarms from unit(s) Programmed local alarms from unit(s) Current temperature sensor readings The following historical data shall be provided: Alarm history for last ten alarms in order of occurrence and time since detected Current and average percent of capacity for last hour Equipment runtimes for: evaporator fan motors, reheat, humidification, dehumidification All standard alarms from unit(s) Current operating mode Current humidity sensor readings Humidity setpoint Humidity high limit Humidity low limit Humidity sensitivity (deadband) Unit rotation Zone number Automatic scrolling of sensor readings Sequential display of alarms Multiple audio alarm modes Custom help messages for alarms

* Some programmable selections, displays, and alarms may require optional components or sensors.

52

Options, continued

Remote Temperature & Humidity Sensors Units shall be provided with remote temperature and humidity sensors. Sensors shall be provided in a plastic case for remote mounting. 25 feet of shielded cable shall be provided for field wiring.

Disconnect The environmental control unit shall include a nonautomatic disconnect switch mounted in the high voltage section of the electrical panel. The operating mechanism shall prevent access to the high voltage electrical components until switched to the "OFF" position. The operating mechanism shall protrude through the decorative door.

Smoke Detector The environmental control unit shall be provided with a smoke detector. The smoke detector shall be mounted with the sensing element in the return air stream. When the smoke detector is activated, it shall immediately shut down the unit.

Condensate Pump Units shall be provided with condensate pumps. Pumps shall be factory mounted/wired and shall include sump, motor, and automatic control. The pumps shall be rated for 130 GPH @ 20 foot maximum head (40 GPH @ 20 feet with check valve).

2-Way Chilled Water Valve Units shall be provided with a 2-way chilled water valve. The maximum water pressure shall be ___ psi.

High Efficiency Filters The environmental control unit shall include 60% efficient filters (based on ASHRAE Std. 52-76). The filters shall be four inch (4") deep pleated design.

Pre-Filters The environmental control unit shall have one inch (1") pre-filters in addition to the unit filters.

53

Options, continued

Upflow Plenum Units with top (upflow) discharge shall be provided with plenum. The plenum shall have a front discharge air grille and be fully insulated with one inch (1") thick, 11/2 pound density fiberglass insulation coated with neoprene. The plenum height shall be 18 inches and shall be painted to match the unit color.

Floorstand Units shall be provided with floorstands and vibration isolation pads. The floorstand shall be a completed welded base engineered to support the operating unit. The floorstand height shall be ___ inches and adjustable ±2 inches.

54

R

230 W. BlueRidge Avenue Orange, CA 92865 800-347-2473

www.dataaire.com e-mail: [email protected] A Member of the CS Group of Companies © 2003 Data Aire, Inc. Data Aire, Inc. reserves the right to make design changes for the purpose of product improvement, or to withdraw any design without notice.

DACW-0106

Information

CW_v08_2002

56 pages

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

152873


You might also be interested in

BETA
773 G-Series Loader Spec Sheet b-1718 Ver 08/01 LR SCREEN RESOLUTION ONLY
13357_Bradshaw_3p_c01.f.qxd
Reheat.PDF
Installation Manual, 20-2800 kW Industrial/Residential (TP-5700)
britStand.set