Read Microsoft Word - Offshore Cables Catalog IEC _NEK606_1_.doc text version

Offshore Cables Basic Program IEC / NEK TS 606

Index

NEK 606 Cable types .........................................................................................................................2 Halogen-free, mud resistant instrumentation cable RFOU(i) 250V, S1/S5 ........................................3 Halogen-free, mud resistant instrumentation cable RFOU(c) 250V, S2/S6 .......................................7 Halogen-free, mud resistant, fire resistant instrumentation cable BFOU(i) 250V, S3/S7 ..................11 Halogen-free, mud resistant, fire resistant instrumentation cable BFOU(c) 250V, S4/S8 .................16 Halogen-free, unarmoured mud resistant instrumentation cable RU(i) 250V, S11 ............................20 Halogen-free, unarmoured mud resistant instrumentation cable RU(c) 250V, S12 ...........................23 Halogen-free, fire resistant, unarmoured, mud resistant instrumentation cable BU(i) 250V, S13 .....26 Halogen-free, fire resistant, unarmoured, mud resistant instrumentation cable BU(c) 250V, S14 ....29 Halogen-free, mud resistant power cable RFOU 0,6/1kV, P1/P8 ......................................................32 Halogen-free, mud resistant power cable RFOU 0,6/1kV, P1/P8, double braided ............................40 Halogen-free, mud resistant power cable RFOU 0,6/1kV, P1/P8, large single core cables ..............42 Halogen-free, mud resistant HV power cable, RFOU 6/10(12)kV, P3/P10........................................44 Halogen-free, mud resistant HV power cable, RFOU 12/20(24)kV, P19/P21....................................48 Halogen-free, mud resistant, fire resistant power cable, BFOU 0,6/1kV, P5/P12..............................51 Halogen-free, mud resistant, fire resistant power cable, BFOU 0,6/1kV, P5/P12, double braided....58 Halogen-free, mud resistant, fire resistant power cable, BFOU 0,6/1kV, P5/P12, large single core cables .................................................................................................................................................61 Halogen-free, mud resistant insulated conductor UX 1000V, P15.....................................................63 Halogen-free, fire resistant, unarmoured, mud resistant power cable, BU 0,6/1kV, P17...................65 Halogen-free, unarmoured, mud resistant power cable, RU 0,6/1kV, P18 ........................................69 Approvals............................................................................................................................................74 Standards and tests............................................................................................................................75 Definition of terms...............................................................................................................................77 Mud resistance.......................................................................................................................77 Fire, flame, smoke and corrosion test methods .................................................................................78 Installation recommendations.............................................................................................................80 Electrical data .....................................................................................................................................81 Material properties ..............................................................................................................................90 SHF1 versus SHF2.............................................................................................................................92 Core colours for cables according to NEK 606 ..................................................................................93 Drum capacity in meters .....................................................................................................................94 Code designation for cables ...............................................................................................................95

www.drakaMOG.com

Subject to change without prior notice Page 1 of 96 2010-04-30

NEK 606 Cable types

List of all the cable types listed in NEK 606 : NEK 2004 Third Edition NEK TS 606 Code NEK TS 606 Description Draka Norsk Kabel's cable type Power cables LV and MV P1 P1 / P8 P2 P2 / P9 P3 P3/P10 P4 P4/P11 P5 P5/P12 P6 P6/P13 P7 P7/P14 P15 P16 P17 P18 P19 P19/P21 P20 P20/P22 P30 P31 P32 P33 P34 Instrumentation and telecommunication cables S1 S1/S5 S2 S2/S6 S3 S3/S7 S4 S4/S8 S9 S10 S11 S12 S13 S14 S15 S16 Optical Fibre Cable F1 F4 F5 F6 QFCI QFCI-HCF QFCB AICI QFCI QFCI-HCF QFCB AICI

RFOU / TFOU 0,6/1 kV RFOU / TFOU 3,6/6(7,2) kV RFOU / TFOU 6/10(12) kV RFOU / TFOU 8,7/15(17,5) kV BFOU 0,6/1 kV BFOU 3,6/6(7,2) kV BFOU 6/10(12) kV UX 0,6/1 kV IFLI 250V BU 0,6/1 kV RU 0,6/1 kV RFOU / TFOU 12/20(24) kV RFOU / TFOU 18/30(36) kV RFOU-HCF / TFOU-HCF 6/10(12) kV RFOU-HCF / TFOU-HCF 8,7/15(17,5) kV RFOU-HCF / TFOU-HCF 12/20(24) kV RFOU-HCF / TFOU-HCF 18/30(36) kV BFOU-HCF 0,6/1 kV

RFOU 0,6/1 kV RFOU 3,676(7,2) kV RFOU 6/10(12) kV RFOU 8,7/15(17,5) kV BFOU 0,6/1 kV UX 0,6/1 kV IFLI 250V BU 0,6/1 kV RU 0,6/1 kV RFOU 12/20(24) kV RFOU 18/30(36) kV RFOU-HCF 6/10(12) kV RFOU-HCF 8,7/15(17,5) kV RFOU-HCF 12/20(24) kV RFOU-HCF 18/30(36) kV BFOU-HCF 0,6/1 kV

RFOU(i) 250V RFOU(c) 250V BFOU(i) 250V BFOU(c) 250V IYXI(c) 60V IYOI(c) 60V RU(i) 250V RU(c) 250V BU(i) 250V BU(c) 250V BFOU-HCF(i) 250V BFOU-HCF(c) 250V

RFOU(i) 250V RFOU(c) 250V BFOU(i) 250V BFOU(c) 250V RU(i) 250V RU(c) 250V BU(i) 250V BU(c) 250V BFOU-HCF(i) 250V BFOU-HCF(c) 250V

Cable types P8 ­ P14, P21 ­ P22, S5 ­ S8 and F5 are to be mud resistant as per NEK TS 606

www.drakaMOG.com

Subject to change without prior notice Page 2 of 96 2010-04-30

Halogen-free, mud resistant instrumentation cable RFOU(i) 250V, S1/S5 Flame retardant halogen-free instrumentation cable. Mud resistant

RFOU(i) 150/250(300)V

EPR/EPR/TCWB/EVA

NEK TS 606 CodeS1/S5

Operating temperature Operating Voltage Standards applied Application Fixed installation for instrumentation, communication, Control and alarm systems in both EX- and safe areas. Meets the mud resistant requirements in NEK TS 606:2009. IEC 60092-376 (2003-05) IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 150/250(300)V

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Pair / Triple / Quad twisting Lay up / Shielding Inner covering Tape over inner covering Armour/screen Tape over armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour R Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 EP-rubber, IEC 60092-351 (EPR) Color coded cores twisted together. Pairs/Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair/triple is wrapped with polyester tape to prevent electrical contact with adjacent pairs/triples. Pairs/triples are identified by numbers printed directly on the insulated conductors. Individually shielded pairs/triples/quads are laid up in concentric layers and wrapped with a PETP tape. Flame retardant and halogen-free thermoset compound PET tape Tinned annealed copper wire braid PET tape Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) E.g. "meter" "year" DRAKA 01 RFOU(i) 250V S1/S5 4 PAIR 0,75 mm2 IEC 60092376 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel, Grey or Blue

F

O

U

www.drakaMOG.com

Subject to change without prior notice Page 3 of 96 2010-04-30

Core identification instrumentation cables

Pair - Black - Light Blue Triple - Black - Light Blue - Brown Quad - Black - Light Blue - Brown - Grey

Range and dimensions

Cross Number No of Conductor Insulation section of cores in Diameter, Thickness, core, elements element mm mm mm² 1 1 2 2 4 4 8 8 12 12 16 16 19 19 24 24 1 1 2 2 4 4 8 8 12 12 16 16 19 24 24 1 1 2 2 4 4 8 8 12 12 16 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 2 2 2 2 2 2 2 2 2 2 2 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 Thickness Inner covering, mm 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.4 1.4 1.9 1.9 1.9 1.9 2.1 2.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.4 1.4 2.1 2.1 2.1 2.5 2.5 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.4 1.4 1.9 Diameter inner covering, mm 7 ± 0.5 7 ± 0.5 10 ± 0.8 10 ± 0.8 11.5 ± 0.8 11.5 ± 0.8 15.5 ± 0.8 15.5 ± 0.8 18.5 ± 0.8 18.5 ± 0.8 21.5 ± 1 21.5 ± 1 22.5 ± 1 22.5 ± 1 26.5 ± 1 26.5 ± 1 Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.2 3.8 0.2 3.8 0.2 5.3 0.2 5.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 10.2 10.2 13.6 13.6 15.3 15.3 17.8 17.8 17.8 17.8 20.4 20.4 3.8 3.8 10.2 10.2 11.9 11.9 15.3 15.3 17.8 17.8 20.4 20.4 20.4 25.4 25.4 3.8 3.8 10.2 10.2 11.9 11.9 15.3 15.3 17.8 17.8 20.4 Thickness Outer Sheath, mm 1.1 1.1 1.2 1.2 1.3 1.3 1.5 1.5 1.6 1.6 1.7 1.7 1.7 1.7 1.9 1.9 1.1 1.1 1.3 1.3 1.4 1.4 1.6 1.6 1.7 1.7 1.8 1.8 1.8 2 2 1.1 1.1 1.3 1.3 1.4 1.4 1.6 1.6 1.8 1.8 1.9 Diameter outer sheath, mm 10 ± 0.8 10 ± 0.8 13 ± 0.8 13 ± 0.8 15 ± 0.8 15 ± 0.8 19.5 ± 0.8 19.5 ± 0.8 23 ± 1 23 ± 1 26 ± 1 26 ± 1 27 ± 1 27 ± 1 31.5 ± 1.5 31.5 ± 1.5 10.5 ± 0.8 10.5 ± 0.8 14.5 ± 0.8 14.5 ± 0.8 16.5 ± 0.8 16.5 ± 0.8 21.5 ± 1 21.5 ± 1 25.5 ± 1 25.5 ± 1 29.5 ± 1 29.5 ± 1 30 ± 1.5 36 ± 1.5 36 ± 1.5 11 ± 0.8 11 ± 0.8 15.5 ± 0.8 15.5 ± 0.8 18 ± 0.8 18 ± 0.8 23.5 ± 1 23.5 ± 1 28 ± 1 28 ± 1 31.5 ± Weight of Cable Approx. (Kg/Km) 185 185 275 275 430 430 690 690 940 940 1240 1240 1360 1360 1720 1720 200 200 380 380 520 520 830 830 1160 1160 1570 1570 1730 2270 2270 230 230 420 420 600 600 980 980 1380 1380 1830 Copper content Approx. (kg/km) 54 54 85 85 166 166 265 265 348 348 439 439 489 489 596 596 60 60 146 146 209 209 334 334 451 451 569 569 638 803 803 71 71 168 168 252 252 420 420 580 580 740

7.5 ± 0.5 0.2 7.5 ± 0.5 0.2 11 ± 0.8 11 ± 0.8 12.5 ± 0.8 12.5 ± 0.8 17 ± 0.8 17 ± 0.8 21 ± 1 21 ± 1 24.5 ± 1 24.5 ± 1 25.5 ± 1 30.5 ± 1.5 30.5 ± 1.5 8 ± 0.5 8 ± 0.5 12 ± 0.8 12 ± 0.8 14 ± 0.8 14 ± 0.8 19 ± 0.8 19 ± 0.8 23 ± 1 23 ± 1 26.5 ± 1 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.2 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3

www.drakaMOG.com

Subject to change without prior notice Page 4 of 96 2010-04-30

Cross Number No of Conductor Insulation section of cores in Diameter, Thickness, core, elements element mm mm mm²

Thickness Inner covering, mm

Diameter inner covering, mm

Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.3 0.3 0.3 0.4 0.4 0.4 0.4 20.4 22.9 22.9 36.2 36.2 40.7 40.7 4.5 4.5 11.9 13.6 13.6 17.8 17.8 20.4 20.4 22.9 22.9 40.7 40.7 4.5 11.9 13.6

Thickness Outer Sheath, mm

Diameter outer sheath, mm 1.5 31.5 ± 1.5 32.5 ± 1.5 32.5 ± 1.5 39 ± 1.5 39 ± 1.5 43 ± 2 43 ± 2 11.5 ± 0.8 11.5 ± 0.8 17.5 ± 0.8 20 ± 1 20 ± 1 26 ± 1 26 ± 1 31 ± 1.5 31 ± 1.5 36 ± 1.5 36 ± 1.5 44 ± 2 44 ± 2 12 ± 0.8 17.5 ± 0.8 20 ± 1

Weight of Cable Approx. (Kg/Km)

Copper content Approx. (kg/km)

16 19 19 24 24 32 32 1 1 2 4 4 8 8 12 12 16 16 24 24 1 2 4

2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 2 2 2

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2 2 2

0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7

1.9 1.9 1.9 2.3 2.3 2.4 2.4 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.4 1.4 2.3 2.3 2.5 2.5 1.1 1.1 1.1

26.5 ± 1 27.5 ± 1 27.5 ± 1 33 ± 1.5 33 ± 1.5 37 ± 1.5 37 ± 1.5

1.9 1.9 1.9 2.2 2.2 2.3 2.3 1.1 1.1 1.4 1.5 1.5 1.7 1.7 1.9 1.9 2 2 2.3 2.3 1.1 1.4 1.5

1830 2040 2040 2790 2790 3450 3450 260 260 510 740 740 1230 1230 1750 1750 2420 2420 3580 3580 280 530 770

740 866 866 1165 1165 1480 1480 93 93 213 325 325 558 558 776 776 992 992 1551 1551 99 225 350

8.5 ± 0.5 0.2 8.5 ± 0.5 0.2 13.5 ± 0.8 15.5 ± 0.8 15.5 ± 0.8 21.5 ± 1 21.5 ± 1 26 ± 1 26 ± 1 31 ± 1.5 31 ± 1.5 38 ± 1.5 38 ± 1.5 9 ± 0.5 13.5 ± 0.8 16 ± 0.8 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.2 0.3 0.3

Electrical values instrumentation cables

Type Shielded pair 0,75 mm² Shielded triple 0,75 mm² Shielded pair 1,5 mm² Shielded triple 1,5 mm² Shielded pair 2,5 mm² Shielded triple 2,5 mm² Capacitance, approx. (nF/km) 110 110 125 125 145 145 Inductance, approx, Resistance at 20°C, (mH/km) max. (Ohm/km) 0,67 26,3 0,67 26,3 0,63 12,9 0,63 12,9 0,59 8,02 0,59 8,02 L/R ratio, (microH/Ohm) 12,7 12,7 24,4 24,4 36,8 36,8

Ordering information

Part number 892000 892001 892006 892007 892018 892019 892030 892031 892036 892037 892042 892043 892045 892046 892048 892049 Description RFOU(I) 1PAIR 0.75mm² S1/S5 RFOU(I) 1PAIR 0.75mm² S1/S5 RFOU(I) 2PAIR 0.75mm² S1/S5 RFOU(I) 2PAIR 0.75mm² S1/S5 RFOU(I) 4PAIR 0.75mm² S1/S5 RFOU(I) 4PAIR 0.75mm² S1/S5 RFOU(I) 8PAIR 0.75mm² S1/S5 RFOU(I) 8PAIR 0.75mm² S1/S5 RFOU(I) 12PAIR 0.75mm² S1/S5 RFOU(I) 12PAIR 0.75mm² S1/S5 RFOU(I) 16PAIR 0.75mm² S1/S5 RFOU(I) 16PAIR 0.75mm² S1/S5 RFOU(I) 19PAIR 0.75mm² S1/S5 RFOU(I) 19PAIR 0.75mm² S1/S5 RFOU(I) 24PAIR 0.75mm² S1/S5 RFOU(I) 24PAIR 0.75mm² S1/S5 Sheath Colour GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE Stock item Yes Yes Yes Yes Yes EAN No. DNK 7021528920000 7021528920017 7021528920062 7021528920079 7021528920185 7021528920192 7021528920307 7021528920314 7021528920369 7021528920376 7021528920420 7021528920437 7021528920451 7021528920468 7021528920482 7021528920499 EL No. 1044620 1044619 1044621 1044622 1044623 1044624 1044628 1044629 1044630 1044631 1044633 1044632 1044634 1044635 1044636 1044637

www.drakaMOG.com

Subject to change without prior notice Page 5 of 96 2010-04-30

Part number 892060 892061 892066 892067 892078 892079 892090 892091 892096 892097 892102 892103 892106 892108 892109 892200 892201 892206 892207 892218 892219 892230 892231 892236 892237 892242 892243 892245 892246 892248 892249 892254 892255 892260 892261 892266 892278 892279 892290 892291 892296 892297 892302 892303 892308 892309 892400 892406 892418

Description RFOU(I) 1TRIP 0.75mm² S1/S5 RFOU(I) 1TRIP 0.75mm² S1/S5 RFOU(I) 2TRIP 0.75mm² S1/S5 RFOU(I) 2TRIP 0.75mm² S1/S5 RFOU(I) 4TRIP 0.75mm² S1/S5 RFOU(I) 4TRIP 0.75mm² S1/S5 RFOU(I) 8TRIP 0.75mm² S1/S5 RFOU(I) 8TRIP 0.75mm² S1/S5 RFOU(I) 12TRIP 0.75mm² S1/S5 RFOU(I) 12TRIP 0.75mm² S1/S5 RFOU(I) 16TRIP 0.75mm² S1/S5 RFOU(I) 16TRIP 0.75mm² S1/S5 RFOU(I) 19TRIP 0.75mm² S1/S5 RFOU(I) 24TRIP 0.75mm² S1/S5 RFOU(I) 24TRIP 0.75mm² S1/S5 RFOU(I) 1PAIR 1.5mm² S1/S5 RFOU(I) 1PAIR 1.5mm² S1/S5 RFOU(I) 2PAIR 1.5mm² S1/S5 RFOU(I) 2PAIR 1.5mm² S1/S5 RFOU(I) 4PAIR 1.5mm² S1/S5 RFOU(I) 4PAIR 1.5mm² S1/S5 RFOU(I) 8PAIR 1.5mm² S1/S5 RFOU(I) 8PAIR 1.5mm² S1/S5 RFOU(I) 12PAIR 1.5mm² S1/S5 RFOU(I) 12PAIR 1.5mm² S1/S5 RFOU(I) 16PAIR 1.5mm² S1/S5 RFOU(I) 16PAIR 1.5mm² S1/S5 RFOU(I) 19PAIR 1.5mm² S1/S5 RFOU(I) 19PAIR 1.5mm² S1/S5 RFOU(I) 24PAIR 1.5mm² S1/S5 RFOU(I) 24PAIR 1.5mm² S1/S5 RFOU(I) 32PAIR 1.5mm² S1/S5 RFOU(I) 32PAIR 1.5mm² S1/S5 RFOU(I) 1TRIP 1.5mm² S1/S5 RFOU(I) 1TRIP 1.5mm² S1/S5 RFOU(I) 2TRIP 1.5mm² S1/S5 RFOU(I) 4TRIP 1.5mm² S1/S5 RFOU(I) 4TRIP 1.5mm² S1/S5 RFOU(I) 8TRIP 1.5mm² S1/S5 RFOU(I) 8TRIP 1.5mm² S1/S5 RFOU(I) 12TRIP 1.5mm² S1/S5 RFOU(I) 12TRIP 1.5mm² S1/S5 RFOU(I) 16TRIP 1.5mm² S1/S5 RFOU(I) 16TRIP 1.5mm² S1/S5 RFOU(I) 24TRIP 1.5mm² S1/S5 RFOU(I) 24TRIP 1.5mm² S1/S5 RFOU(I) 1PAIR 2.5mm² S1/S5 RFOU(I) 2PAIR 2.5mm² S1/S5 RFOU(I) 4PAIR 2.5mm² S1/S5

Sheath Colour GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY GREY GREY

Stock item Yes Yes Yes Yes -

EAN No. DNK 7021528920604 7021528920611 7021528920666 7021528920673 7021528920789 7021528920796 7021528920901 7021528920918 7021528920963 7021528920970 7021528921021 7021528921038 7021528921069 7021528921083 7021528921090 7021528922004 7021528922011 7021528922066 7021528922073 7021528922189 7021528922196 7021528922301 7021528922318 7021528922363 7021528922370 7021528922424 7021528922431 7021528922455 7021528922462 7021528922486 7021528922493 7021528922547 7021528922554 7021528922608 7021528922615 7021528922660 7021528922783 7021528922790 7021528922905 7021528922912 7021528922967 7021528922974 7021528923025 7021528923032 7021528923087 7021528923094 7021528924008 7021528924060 7021528924183

EL No. 1044690 1044689 1044691 1044692 1044693 1044694 1044697 1044698 1044699 1044700 1044701 1044702 1044707 1044708 1044460 1044459 1044661 1044662 1044663 1044664 1044668 1044669 1044670 1044671 1044673 1044672 1044674 1044675 1044678 1044679 1044560 1044559 1044762 1044764 1044765 1044768 1044769 1044770 1044771 1044773 1044772 1044779 1044780 -

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 6 of 96 2010-04-30

Halogen-free, mud resistant instrumentation cable RFOU(c) 250V, S2/S6 Flame retardant halogen-free instrumentation cable. Mud resistant

RFOU(c) 150/250(300)V

EPR/EPR/TCWB/EVA

NEK TS 606 CodeS2/S6

Operating temperature Operating Voltage Standards applied Application Fixed installation for instrumentation, communication, Control and alarm systems in both EX- and safe areas. Meets the mud resistant requirements in NEK TS 606:2009. IEC 60092-376 (2003-05) IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 150/250(300)V

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Pair / Triple / Quad twisting Inner covering Tape over inner covering Armour/screen Tape over armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour F R Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 EP-rubber, IEC 60092-351 (EPR) Color coded cores twisted together and wrapped with polyester tape. Pairs/Triples are laid up collectively and screened by copper backed polyester tape with tinned copper drain wire. Pairs/triples are identified by numbers printed directly on the insulated conductors. Flame retardant and halogen-free thermoset compound PET tape Tinned annealed copper wire braid PET tape Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) E.g. "meter" "year" DRAKA 01 RFOU(c) 250V S2/S6 8 PAIR 0,75 mm2 IEC 60092-376 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel, Grey or Blue

O

U

www.drakaMOG.com

Subject to change without prior notice Page 7 of 96 2010-04-30

Core identification instrumentation cables

Pair - Black - Light Blue Triple - Black - Light Blue - Brown Quad - Black - Light Blue - Brown - Grey

Range and dimensions

Cross Number No of Conductor Insulation section of cores in Diameter, Thickness, core, elements element mm mm mm² 2 2 4 4 8 8 12 12 16 16 19 24 24 2 2 4 4 8 8 12 12 16 24 24 2 2 4 4 8 8 10 10 12 12 16 16 19 24 32 32 2 4 8 12 12 16 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 Thickness Inner covering, mm 1.1 1.1 1.1 1.1 1.1 1.1 1.4 1.4 1.9 1.9 1.9 2.1 2.1 1.1 1.1 1.1 1.1 1.1 1.1 1.4 1.4 2.1 2.5 2.5 1.1 1.1 1.1 1.1 1.1 1.1 1.2 1.2 1.4 1.4 1.9 1.9 1.9 2.3 2.4 2.4 1.1 1.1 1.1 1.4 1.4 2.1 Diameter inner covering, mm 10 ± 0.8 10 ± 0.8 11.5 ± 0.8 11.5 ± 0.8 15 ± 0.8 15 ± 0.8 18 ± 0.8 18 ± 0.8 20.5 ± 1 20.5 ± 1 21.5 ± 1 25 ± 1 25 ± 1 11 ± 0.8 11 ± 0.8 12.5 ± 0.8 12.5 ± 0.8 17 ± 0.8 17 ± 0.8 20 ± 1 20 ± 1 23 ± 1 28.5 ± 1 28.5 ± 1 12 ± 0.8 12 ± 0.8 14 ± 0.8 14 ± 0.8 18.5 ± 0.8 18.5 ± 0.8 21 ± 1 21 ± 1 22 ± 1 22 ± 1 25 ± 1 25 ± 1 26.5 ± 1 31 ± 1.5 34 ± 1.5 34 ± 1.5 13 ± 0.8 15.5 ± 0.8 21 ± 1 24.5 ± 1 24.5 ± 1 28 ± 1 Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.2 5.3 0.2 5.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.3 0.3 0.3 0.3 0.3 0.3 8.5 8.5 11.9 11.9 15.3 15.3 15.3 15.3 17.8 20.4 20.4 8.5 8.5 10.2 10.2 13.6 13.6 15.3 15.3 17.8 22.9 22.9 10.2 10.2 11.9 11.9 15.3 15.3 17.8 17.8 17.8 17.8 20.4 20.4 20.4 25.4 36.2 36.2 10.2 11.9 17.8 20.4 20.4 22.9 Thickness Outer Sheath, mm 1.2 1.2 1.3 1.3 1.4 1.4 1.5 1.5 1.6 1.6 1.7 1.8 1.8 1.3 1.3 1.3 1.3 1.5 1.5 1.6 1.6 1.7 2 2 1.3 1.3 1.4 1.4 1.6 1.6 1.7 1.7 1.7 1.7 1.8 1.8 1.9 2.1 2.2 2.2 1.4 1.4 1.7 1.8 1.8 1.9 Diameter outer sheath, mm 13 ± 0.8 13 ± 0.8 15 ± 0.8 15 ± 0.8 19 ± 0.8 19 ± 0.8 22 ± 1 22 ± 1 24.5 ± 1 24.5 ± 1 26 ± 1 29.5 ± 1 29.5 ± 1 14.5 ± 0.8 14.5 ± 0.8 16.5 ± 0.8 16.5 ± 0.8 21 ± 1 21 ± 1 24.5 ± 1 24.5 ± 1 27.5 ± 1 33.5 ± 1.5 33.5 ± 1.5 15.5 ± 0.8 15.5 ± 0.8 18 ± 0.8 18 ± 0.8 23 ± 1 23 ± 1 25.5 ± 1 25.5 ± 1 26.5 ± 1 26.5 ± 1 29.5 ± 1 29.5 ± 1 31 ± 1.5 36.5 ± 1.5 40 ± 2 40 ± 2 17 ± 0.8 19.5 ± 0.8 25.5 ± 1 29.5 ± 1 29.5 ± 1 33 ± 1.5 Weight of Cable Approx. (Kg/Km) 270 270 390 390 600 600 820 820 1040 1040 1170 1450 1450 350 350 470 470 740 740 1010 1010 1350 1950 1950 410 410 560 560 890 890 1070 1070 1210 1210 1580 1580 1750 2270 2890 2890 480 670 1130 1570 1570 2090 Copper content Approx. (kg/km) 81 81 138 139 223 223 307 307 358 358 422 510 510 126 126 181 181 291 291 385 385 488 692 692 162 162 234 234 379 379 459 459 515 515 651 651 735 924 1252 1252 190 291 517 710 710 903

www.drakaMOG.com

Subject to change without prior notice Page 8 of 96 2010-04-30

Cross Number No of Conductor Insulation section of cores in Diameter, Thickness, core, elements element mm mm mm² 16 24 24 2 4 4 12 3 3 3 2 2 2 2 1.5 1.5 1.5 2.5 2.5 2.5 2.5 1.6 1.6 1.6 2 2 2 2 0.7 0.7 0.7 0.7 0.7 0.7 0.7

Thickness Inner covering, mm 2.1 2.5 2.5 1.1 1.1 1.1 2.1

Diameter inner covering, mm 28 ± 1 35 ± 1.5 35 ± 1.5 13.5 ± 0.8 16 ± 0.8 16 ± 0.8 27 ± 1

Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.3 22.9 0.4 36.2 0.4 36.2 0.3 0.3 0.3 0.3 10.2 11.9 11.9 20.4

Thickness Outer Sheath, mm 1.9 2.2 2.2 1.4 1.4 1.4 1.8

Diameter outer sheath, mm 33 ± 1.5 41 ± 2 41 ± 2 17.5 ± 0.8 19.5 ± 0.8 19.5 ± 0.8 31.5 ± 1.5

Weight of Cable Approx. (Kg/Km) 2090 3120 3120 490 680 680 1740

Copper content Approx. (kg/km) 903 1369 1369 200 309 309 759

Electrical values instrumentation cables

Capacitance, approx. (nF/km) Unshielded pair 0,75 mm² 100 Unshielded triple 0,75 mm² 100 Unshielded pair 1,5 mm² 110 Unshielded triple 1,5 mm² 110 Unshielded pair 2,5 mm² 125 Unshielded triple 2,5 mm² 125 Type Inductance, approx, (mH/km) 0,67 0,67 0,63 0,63 0,59 0,59 Resistance at 20°C, max. (Ohm/km) 26,3 26,3 12,9 12,9 8,02 8,02 L/R ratio, (microH/Ohm) 12,7 12,7 24,4 24,4 36,8 36,8

Ordering information

Part number 892606 892607 892618 892619 892630 892631 892636 892637 892642 892643 892645 892648 892649 892666 892667 892678 892679 892690 892691 892696 892697 892702 892708 892709 892806 892807 892818 892819 892830 892831 892834 892835 892836 892837 892842 892843 Description RFOU(C) 2PAIR 0.75mm² S2/S6 RFOU(C) 2PAIR 0.75mm² S2/S6 RFOU(C) 4PAIR 0.75mm² S2/S6 RFOU(C) 4PAIR 0.75mm² S2/S6 RFOU(C) 8PAIR 0.75mm² S2/S6 RFOU(C) 8PAIR 0.75mm² S2/S6 RFOU(C) 12PAIR 0.75mm² S2/S6 RFOU(C) 12PAIR 0.75mm² S2/S6 RFOU(C) 16PAIR 0.75mm² S2/S6 RFOU(C) 16PAIR 0.75mm² S2/S6 RFOU(C) 19PAIR 0.75mm² S2/S6 RFOU(C) 24PAIR 0.75mm² S2/S6 RFOU(C) 24PAIR 0.75mm² S2/S6 RFOU(C) 2TRIP 0.75mm² S2/S6 RFOU(C) 2TRIP 0.75mm² S2/S6 RFOU(C) 4TRIP 0.75mm² S2/S6 RFOU(C) 4TRIP 0.75mm² S2/S6 RFOU(C) 8TRIP 0.75mm² S2/S6 RFOU(C) 8TRIP 0.75mm² S2/S6 RFOU(C) 12TRIP 0.75mm² S2/S6 RFOU(C) 12TRIP 0.75mm² S2/S6 RFOU(C) 16TRIP 0.75mm² S2/S6 RFOU(C) 24TRIP 0.75mm² S2/S6 RFOU(C) 24TRIP 0.75mm² S2/S6 RFOU(C) 2PAIR 1.5mm² S2/S6 RFOU(C) 2PAIR 1.5mm² S2/S6 RFOU(C) 4PAIR 1.5mm² S2/S6 RFOU(C) 4PAIR 1.5mm² S2/S6 RFOU(C) 8PAIR 1.5mm² S2/S6 RFOU(C) 8PAIR 1.5mm² S2/S6 RFOU(C) 10PAIR 1.5mm² S2/S6 RFOU(C) 10PAIR 1.5mm² S2/S6 RFOU(C) 12PAIR 1.5mm² S2/S6 RFOU(C) 12PAIR 1.5mm² S2/S6 RFOU(C) 16PAIR 1.5mm² S2/S6 RFOU(C) 16PAIR 1.5mm² S2/S6 Sheath Colour GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE Stock item Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes EAN No. DNK 7021528926064 7021528926071 7021528926187 7021528926194 7021528926309 7021528926316 7021528926361 7021528926378 7021528926422 7021528926439 7021528926453 7021528926484 7021528926491 7021528926668 7021528926675 7021528926781 7021528926798 7021528926903 7021528926910 7021528926965 7021528926972 7021528927023 7021528927085 7021528927092 7021528928068 7021528928075 7021528928181 7021528928198 7021528928303 7021528928310 7021528928341 7021528928358 7021528928365 7021528928372 7021528928426 7021528928433 EL No. 1044421 1044422 1044423 1044424 1044428 1044429 1044430 1044431 1044433 1044432 1044434 1044438 1044437 1044490 1044491 1044492 1044493 1044496 1044497 1044499 1044500 1044501 1044507 1044508 1044461 1044462 1044463 1044464 1044468 1044469 1044470 1044472 1044473

www.drakaMOG.com

Subject to change without prior notice Page 9 of 96 2010-04-30

Part number 892845 892848 892854 892855 892866 892878 892891 892896 892897 892902 892903 892908 892909 893006 893018 893019 893036

Description RFOU(C) 19PAIR 1.5mm² S2/S6 RFOU(C) 24PAIR 1.5mm² S2/S6 RFOU(C) 32PAIR 1.5mm² S2/S6 RFOU(C) 32PAIR 1.5mm² S2/S6 RFOU(C) 2TRIP 1.5mm² S2/S6 RFOU(C) 4TRIP 1.5mm² S2/S6 RFOU(C) 8TRIP 1.5mm² S2/S6 RFOU(C) 12TRIP 1.5mm² S2/S6 RFOU(C) 12TRIP 1.5mm² S2/S6 RFOU(C) 16TRIP 1.5mm² S2/S6 RFOU(C) 16TRIP 1.5mm² S2/S6 RFOU(C) 24TRIP 1.5mm² S2/S6 RFOU(C) 24TRIP 1.5mm² S2/S6 RFOU(C) 2PAIR 2.5mm² S2/S6 RFOU(C) 4PAIR 2.5mm² S2/S6 RFOU(C) 4PAIR 2.5mm² S2/S6 RFOU(C) 12PAIR 2.5mm² S2/S6

Sheath Colour GREY GREY GREY BLUE GREY GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY GREY BLUE GREY

Stock item Yes -

EAN No. DNK 7021528928457 7021528928488 7021528928549 7021528928556 7021528928662 7021528928785 7021528928914 7021528928969 7021528928976 7021528929027 7021528929034 7021528929089 7021528929096 7021528930061 7021528930184 7021528930191 7021528930368

EL No. 1044474 1044478 1044561 1044563 1044568 1044569 1044570 1044571 1044572 1044577 1044578 -

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 10 of 96 2010-04-30

Halogen-free, mud resistant, fire resistant instrumentation cable BFOU(i) 250V, S3/S7 Fire resistant, flame retardant halogen-free instrumentation cable. Mud resistant

BFOU(i) 150/250(300)V

MGT/EPR/EPR/TCWB/EVA

NEK TS 606 CodeS3/S7

Operating temperature Operating Voltage Standards applied Application Fixed installation for instrumentation, communication, control and alarm systems in both EX- and safe areas, emergency and critical systems where requirement for fire resistance exists. Meets the mud resistant requirements in NEK TS 606:2009. IEC 60092-376 (2003-05) IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60331-1, -2, -21 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 150/250(300)V

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Fire Resistant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Pair / Triple / Quad twisting Lay up / Shielding Inner covering Tape over inner covering Armour/screen Tape over armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour B Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 Mica-tape + EP-rubber, IEC 60092-351 (EPR) Color coded cores twisted together. Pairs/Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair/triple is wrapped with polyester tape to prevent electrical contact with adjacent pairs/triples. Pairs/triples are identified by numbered tape or by numbers printed directly on the insulated conductors. Individually shielded pairs/triples/quads are laid up in concentric layers and wrapped with a PETP tape. Flame retardant and halogen-free thermoplastic compound PET tape Tinned annealed copper wire braid PET tape Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) Eg. "meter" "year" DRAKA 01 BFOU(i) 250V S3/S7 16 PAIR 0,75 mm2 FLEX FLAME IEC 60092-376 IEC 60331-21 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel Grey or Blue

F

O

U

www.drakaMOG.com

Subject to change without prior notice Page 11 of 96 2010-04-30

Core identification instrumentation cables

Pair - Black - Light Blue Triple - Black - Light Blue - Brown Quad - Black - Light Blue - Brown - Grey

Range and dimensions

Cross Number No of Conductor Insulation section of cores in Diameter, Thickness, core, elements element mm mm mm² 1 1 1 1 2 2 4 4 8 8 12 12 16 16 19 19 24 24 1 1 2 2 4 4 8 8 12 12 16 19 24 24 1 1 2 2 4 4 8 8 12 2 2 2 4 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 2 2 2 2 2 2 2 2 2 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 Thickness Inner covering, mm 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.4 1.4 1.9 1.9 1.9 1.9 2.3 2.3 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.4 1.4 2.1 2.3 2.5 2.5 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.4 Diameter inner covering, mm Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 3.8 3.8 3.8 4.5 10.2 10.2 11.9 11.9 15.3 15.3 17.8 17.8 20.4 20.4 20.4 20.4 31.7 31.7 4.5 4.5 10.2 10.2 11.9 11.9 17.8 17.8 20.4 20.4 22.9 22.9 36.2 36.2 4.5 4.5 11.9 11.9 13.6 13.6 17.8 17.8 20.4 Thickness Outer Sheath, mm 1.1 1.1 1.1 1.2 1.3 1.3 1.4 1.4 1.6 1.6 1.7 1.7 1.8 1.8 1.9 1.9 2.1 2.1 1.1 1.1 1.4 1.4 1.4 1.4 1.7 1.7 1.8 1.8 1.9 2 2.2 2.2 1.1 1.1 1.4 1.4 1.5 1.5 1.7 1.7 1.9 Diameter outer sheath, mm 10.5 ± 0.8 10.5 ± 0.8 10.5 ± 0.8 12 ± 0.8 14.5 ± 0.8 14.5 ± 0.8 16.5 ± 0.8 16.5 ± 0.8 21.5 ± 1 21.5 ± 1 25 ± 1 25 ± 1 28.5 ± 1 28.5 ± 1 29.5 ± 1 29.5 ± 1 35.5 ± 1.5 35.5 ± 1.5 11 ± 0.8 11 ± 0.8 15.5 ± 0.8 15.5 ± 0.8 17.5 ± 0.8 17.5 ± 0.8 23 ± 1 23 ± 1 27.5 ± 1 27.5 ± 1 31.5 ± 1.5 33 ± 1.5 39 ± 1.5 39 ± 1.5 12 ± 0.8 12 ± 0.8 17 ± 0.8 17 ± 0.8 19.5 ± 0.8 19.5 ± 0.8 25.5 ± 1 25.5 ± 1 30.5 ± 1.5 Weight of Cable Approx. (Kg/Km) 200 200 200 250 360 360 490 490 780 780 1060 1060 1400 1400 1550 1550 2100 2100 220 220 410 410 570 570 960 960 1310 1310 1770 2000 2630 2630 255 255 480 480 670 670 1100 1100 1540 Copper content Approx. (kg/km) 54 55 54 74 133 133 183 183 283 283 373 373 465 465 514 514 708 708 68 68 146 146 209 209 359 359 477 477 594 663 909 909 79 79 184 184 269 269 446 446 606

7.5 ± 0.5 0.2 7.5 ± 0.5 0.2 7.5 ± 0.5 0.2 8.5 ± 0.5 0.2 11 ± 0.8 11 ± 0.8 12.5 ± 0.8 12.5 ± 0.8 17 ± 0.8 17 ± 0.8 20.5 ± 1 20.5 ± 1 24 ± 1 24 ± 1 25 ± 1 25 ± 1 30 ± 1.5 30 ± 1.5 8 ± 0.5 8 ± 0.5 12 ± 0.8 12 ± 0.8 14 ± 0.8 14 ± 0.8 18.5 ± 0.8 18.5 ± 0.8 22.5 ± 1 22.5 ± 1 26.5 ± 1 28 ± 1 33 ± 1.5 33 ± 1.5 9 ± 0.5 9 ± 0.5 13 ± 0.8 13 ± 0.8 15.5 ± 0.8 15.5 ± 0.8 21 ± 1 21 ± 1 25.5 ± 1 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.2 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.2 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.3

www.drakaMOG.com

Subject to change without prior notice Page 12 of 96 2010-04-30

Cross Number No of Conductor Insulation section of cores in Diameter, Thickness, core, elements element mm mm mm² 12 16 16 19 24 24 1 1 2 2 4 4 8 8 12 12 16 16 24 24 1 1 2 4 8 16 1 8 12 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 2 2 2 2 2 2 3 3 3 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2 2 2 2 2 2 2 2 2 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7

Thickness Inner covering, mm 1.4 2.1 2.1 2.1 2.3 2.3 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.6 1.6 2.3 2.3 2.7 2.7 1.1 1.1 1.1 1.1 1.1 2.3 1.1 1.3 2.6

Diameter inner covering, mm 25.5 ± 1 30 ± 1.5 30 ± 1.5 31 ± 1.5 36.5 ± 1.5 36.5 ± 1.5

Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.3 0.3 0.3 0.4 0.4 0.4 20.4 22.9 22.9 36.2 40.7 40.7 4.5 4.5 11.9 11.9 15.3 15.3 20.4 20.4 22.9 22.9 36.2 36.2 45.2 45.2 4.5 4.5 11.9 15.3 20.4 36.2 5.3 22.9 36.2

Thickness Outer Sheath, mm 1.9 2 2 2.1 2.3 2.3 1.2 1.2 1.5 1.5 1.6 1.6 1.8 1.8 2 2 2.2 2.2 2.5 2.5 1.2 1.2 1.5 1.6 1.8 2.2 1.2 2 2.2

Diameter outer sheath, mm 30.5 ± 1.5 35 ± 1.5 35 ± 1.5 36.5 ± 1.5 43 ± 2 43 ± 2 12.5 ± 0.8 12.5 ± 0.8 18.5 ± 0.8 18.5 ± 0.8 21 ± 1 21 ± 1 27 ± 1 27 ± 1 33.5 ± 1.5 33.5 ± 1.5 39 ± 1.5 39 ± 1.5 47.5 ± 2 47.5 ± 2 13 ± 0.8 13 ± 0.8 18.5 ± 0.8 21.5 ± 1 28 ± 1 39.5 ± 1.5 13.5 ± 0.8 30.5 ± 1.5 39.5 ± 1.5

Weight of Cable Approx. (Kg/Km) 1540 2080 2080 2460 3100 3100 290 290 560 560 830 830 1390 1390 1990 1990 2820 2820 4050 4050 300 300 560 830 1390 2820 350 1820 2940

Copper content Approx. (kg/km) 606 766 766 998 1211 1211 93 93 213 213 342 342 584 584 802 802 1123 1123 1596 1596 99 99 225 367 633 1221 129 844 1284

9.5 ± 0.5 0.2 9.5 ± 0.5 0.2 14.5 ± 0.8 14.5 ± 0.8 17 ± 0.8 17 ± 0.8 22.5 ± 1 22.5 ± 1 28.5 ± 1 28.5 ± 1 33 ± 1.5 33 ± 1.5 41 ± 2 41 ± 2 9.5 ± 0.5 9.5 ± 0.5 14.5 ± 0.8 17 ± 0.8 23.5 ± 1 33.5 ± 1.5 10.5 ± 0.8 25.5 ± 1 33.5 ± 1.5 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.4 0.2 0.2 0.3 0.3 0.3 0.4 0.2 0.3 0.4

www.drakaMOG.com

Subject to change without prior notice Page 13 of 96 2010-04-30

Electrical values instrumentation cables

Type Shielded pair 0,75 mm² Shielded triple 0,75 mm² Shielded pair 1,5 mm² Shielded triple 1,5 mm² Shielded pair 2,5 mm² Shielded triple 2,5 mm² Capacitance, approx. (nF/km) 110 110 125 125 145 145 Inductance, approx, (mH/km) 0,67 0,67 0,63 0,63 0,59 0,59 Resistance at 20°C, max. (Ohm/km) 26,3 26,3 12,9 12,9 8,02 8,02 L/R ratio, (microH/Ohm) 12,7 12,7 24,4 24,4 36,8 36,8

Ordering information

Part number 893200 89320083 893201 893203 893206 893207 893218 893219 893230 893231 893236 893237 893242 893243 893245 893246 893248 893249 893260 893261 893266 893267 893278 893279 893290 893291 893296 893297 893302 893305 893308 893309 893400 893401 893406 893407 893418 893419 893430 893431 893436 893437 893442 893443 893445 893448 893449 893460 893461 893466 893467 Description BFOU(I) 1PAIR 0.75mm² S3/S7 BFOU(I) 1PAIR 0.75mm² S3/S7 BFOU(I) 1PAIR 0.75mm² S3/S7 BFOU(I) 1QUAD 0.75mm² S3/S7 BFOU(I) 2PAIR 0.75mm² S3/S7 BFOU(I) 2PAIR 0.75mm² S3/S7 BFOU(I) 4PAIR 0.75mm² S3/S7 BFOU(I) 4PAIR 0.75mm² S3/S7 BFOU(I) 8PAIR 0.75mm² S3/S7 BFOU(I) 8PAIR 0.75mm² S3/S7 BFOU(I) 12PAIR 0.75mm² S3/S7 BFOU(I) 12PAIR 0.75mm² S3/S7 BFOU(I) 16PAIR 0.75mm² S3/S7 BFOU(I) 16PAIR 0.75mm² S3/S7 BFOU(I) 19PAIR 0.75mm² S3/S7 BFOU(I) 19PAIR 0.75mm² S3/S7 BFOU(I) 24PAIR 0.75mm² S3/S7 BFOU(I) 24PAIR 0.75mm² S3/S7 BFOU(I) 1TRIP 0.75mm² S3/S7 BFOU(I) 1TRIP 0.75mm² S3/S7 BFOU(I) 2TRIP 0.75mm² S3/S7 BFOU(I) 2TRIP 0.75mm² S3/S7 BFOU(I) 4TRIP 0.75mm² S3/S7 BFOU(I) 4TRIP 0.75mm² S3/S7 BFOU(I) 8TRIP 0.75mm² S3/S7 BFOU(I) 8TRIP 0.75mm² S3/S7 BFOU(I) 12TRIP 0.75mm² S3/S7 BFOU(I) 12TRIP 0.75mm² S3/S7 BFOU(I) 16TRIP 0.75mm² S3/S7 BFOU(I) 19TRIP 0.75mm² S3/S7 BFOU(I) 24TRIP 0.75mm² S3/S7 BFOU(I) 24TRIP 0.75mm² S3/S7 BFOU(I) 1PAIR 1.5mm² S3/S7 BFOU(I) 1PAIR 1.5mm² S3/S7 BFOU(I) 2PAIR 1.5mm² S3/S7 BFOU(I) 2PAIR 1.5mm² S3/S7 BFOU(I) 4PAIR 1.5mm² S3/S7 BFOU(I) 4PAIR 1.5mm² S3/S7 BFOU(I) 8PAIR 1.5mm² S3/S7 BFOU(I) 8PAIR 1.5mm² S3/S7 BFOU(I) 12PAIR 1.5mm² S3/S7 BFOU(I) 12PAIR 1.5mm² S3/S7 BFOU(I) 16PAIR 1.5mm² S3/S7 BFOU(I) 16PAIR 1.5mm² S3/S7 BFOU(I) 19PAIR 1.5mm² S3/S7 BFOU(I) 24PAIR 1.5mm² S3/S7 BFOU(I) 24PAIR 1.5mm² S3/S7 BFOU(I) 1TRIP 1.5mm² S3/S7 BFOU(I) 1TRIP 1.5mm² S3/S7 BFOU(I) 2TRIP 1.5mm² S3/S7 BFOU(I) 2TRIP 1.5mm² S3/S7 Sheath Colour GREY GREY BLUE GREY GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY GREY GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY GREY BLUE GREY BLUE GREY BLUE Stock item Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes EAN No. DNK 7021528932003 7021528932003 7021528932010 7021528932034 7021528932065 7021528932072 7021528932188 7021528932195 7021528932300 7021528932317 7021528932362 7021528932379 7021528932423 7021528932430 7021528932454 7021528932461 7021528932485 7021528932492 7021528932607 7021528932614 7021528932669 7021528932676 7021528932782 7021528932799 7021528932904 7021528932911 7021528932966 7021528932973 7021528933024 7021528933055 7021528933086 7021528933093 7021528934007 7021528934014 7021528934069 7021528934076 7021528934182 7021528934199 7021528934304 7021528934311 7021528934366 7021528934373 7021528934427 7021528934434 7021528934458 7021528934489 7021528934496 7021528934601 7021528934618 7021528934663 7021528934670 EL No. 1043820 1043820SDC 1043819 1044020 1044019 1044021 1044022 1044028 1044029 1044030 1044031 1044033 1044034 1044036 1044037 1043920 1043919 1044121 1044122 1044123 1044124 1044128 1044129 1044130 1044131 1044132 1044138 1044139 1043860 1043859 1044060 1044061 1044063 1044064 1044068 1044069 1044070 1044071 1044073 1044074 1044076 1044170 1044169 1044171 -

www.drakaMOG.com

Subject to change without prior notice Page 14 of 96 2010-04-30

Part number 893478 893479 893490 893491 893496 893497 893502 893503 893508 893509 893600 893601 893606 893618 893630 893642 893660 893690 893696

Description BFOU(I) 4TRIP 1.5mm² S3/S7 BFOU(I) 4TRIP 1.5mm² S3/S7 BFOU(I) 8TRIP 1.5mm² S3/S7 BFOU(I) 8TRIP 1.5mm² S3/S7 BFOU(I) 12TRIP 1.5mm² S3/S7 BFOU(I) 12TRIP 1.5mm² S3/S7 BFOU(I) 16TRIP 1.5mm² S3/S7 BFOU(I) 16TRIP 1.5mm² S3/S7 BFOU(I) 24TRIP 1.5mm² S3/S7 BFOU(I) 24TRIP 1.5mm² S3/S7 BFOU(I) 1PAIR 2.5mm² S3/S7 BFOU(I) 1PAIR 2.5mm² S3/S7 BFOU(I) 2PAIR 2.5mm² S3/S7 BFOU(I) 4PAIR 2.5mm² S3/S7 BFOU(I) 8PAIR 2.5mm² S3/S7 BFOU(I) 16PAIR 2.5mm² S3/S7 BFOU(I) 1TRIP 2.5mm² S3/S7 BFOU(I) 8TRIP 2.5mm² S3/S7 BFOU(I) 12TRIP 2.5mm² S3/S7

Sheath Colour GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY GREY GREY GREY GREY GREY GREY

Stock item Yes -

EAN No. DNK 7021528934786 7021528934793 7021528934908 7021528934915 7021528934960 7021528934977 7021528935028 7021528935035 7021528935080 7021528935097 7021528936001 7021528936018 7021528936063 7021528936186 7021528936308 7021528936421 7021528936605 7021528936902 7021528936964

EL No. 1044173 1044174 1044177 1044178 1044179 1044180 1044181 1044182 1044193 1044194 1044140 -

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 15 of 96 2010-04-30

Halogen-free, mud resistant, fire resistant instrumentation cable BFOU(c) 250V, S4/S8 Fire resistant, flame retardant halogen-free instrumentation cable. Mud resistant

BFOU(c) 150/250(300)V

MGT/EPR/EPR/TCWB/EVA

NEK TS 606 CodeS4/S8

Operating temperature Operating Voltage Standards applied Application Fixed installation for instrumentation, communication, control and alarm systems in both EX- and safe areas, emergency and critical systems where requirement for fire resistance exists. Meets the mud resistant requirements in NEK TS 606:2009. IEC 60092-376 (2003-05) IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60331-1, -2, -21 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 150/250(300)V

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Fire Resistant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Pair / Triple / Quad twisting Inner covering Tape over inner covering Armour/screen Tape over armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour F B Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 Mica-tape + EP-rubber, IEC 60092-351 (EPR) Color coded cores twisted together and wrapped with polyester tape. Pairs/Triples are laid up collectively and screened by copper backed polyester tape with tinned copper drain wire.Pairs/triples are identified by numbered tape or by numbers printed directly on the insulated conductors. Flame retardant and halogen-free thermoplastic compound PET tape Tinned annealed copper wire braid PET tape Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) Eg. "meter" "year" DRAKA 01 BFOU(c) 250V S4/S8 4 PAIR 0,75 mm2 FLEX FLAME IEC 60092-376 IEC 60331-21 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel Grey or Blue

O

U

www.drakaMOG.com

Subject to change without prior notice Page 16 of 96 2010-04-30

Core identification instrumentation cables

Pair - Black - Light Blue Triple - Black - Light Blue - Brown Quad - Black - Light Blue - Brown - Grey

Range and dimensions

Cross Number No of Conductor Insulation section of cores in Diameter, Thickness, core, elements element mm mm mm² 2 2 4 4 8 8 12 12 16 16 19 24 24 2 2 4 4 8 8 12 12 16 16 24 2 2 4 4 8 8 12 12 16 16 24 24 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 2 2 2 2 2 2 2 2 2 2 2 2 3 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 Thickness Inner covering, mm 1.1 1.1 1.1 1.1 1.1 1.1 1.4 1.4 1.9 1.9 1.9 2.3 2.3 1.1 1.1 1.1 1.1 1.1 1.1 1.4 1.4 2.1 2.1 2.5 1.1 1.1 1.1 1.1 1.1 1.1 1.4 1.4 1.9 1.9 2.3 2.3 1.1 Diameter inner covering, mm 10.5 ± 0.8 10.5 ± 0.8 12.5 ± 0.8 12.5 ± 0.8 16.5 ± 0.8 16.5 ± 0.8 19.5 ± 0.8 19.5 ± 0.8 22 ± 1 22 ± 1 23 ± 1 27.5 ± 1 27.5 ± 1 12 ± 0.8 12 ± 0.8 14 ± 0.8 14 ± 0.8 18.5 ± 0.8 18.5 ± 0.8 22 ± 1 22 ± 1 25.5 ± 1 25.5 ± 1 31.5 ± 1.5 13 ± 0.8 13 ± 0.8 15 ± 0.8 15 ± 0.8 20 ± 1 20 ± 1 24 ± 1 24 ± 1 27 ± 1 27 ± 1 33.5 ± 1.5 33.5 ± 1.5 14.5 ± Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.3 8.5 8.5 10.2 10.2 13.6 13.6 17.8 17.8 17.8 17.8 20.4 22.9 22.9 10.2 10.2 11.9 11.9 15.3 15.3 17.8 17.8 20.4 20.4 36.2 10.2 10.2 11.9 11.9 17.8 17.8 20.4 20.4 22.9 22.9 36.2 36.2 11.9 Thickness Outer Sheath, mm 1.3 1.3 1.4 1.4 1.5 1.5 1.6 1.6 1.7 1.7 1.8 2 2 1.3 1.3 1.4 1.4 1.6 1.6 1.8 1.8 1.9 1.9 2.1 1.4 1.4 1.4 1.4 1.7 1.7 1.8 1.8 1.9 1.9 2.2 2.2 1.4 Diameter outer sheath, mm 14.5 ± 0.8 14.5 ± 0.8 16 ± 0.8 16 ± 0.8 20.5 ± 1 20.5 ± 1 24 ± 1 24 ± 1 26.5 ± 1 26.5 ± 1 28 ± 1 32.5 ± 1.5 32.5 ± 1.5 15.5 ± 0.8 15.5 ± 0.8 18 ± 0.8 18 ± 0.8 23 ± 1 23 ± 1 27 ± 1 27 ± 1 30.5 ± 1.5 30.5 ± 1.5 37 ± 1.5 16.5 ± 0.8 16.5 ± 0.8 19 ± 0.8 19 ± 0.8 24.5 ± 1 24.5 ± 1 28.5 ± 1 28.5 ± 1 31.5 ± 1.5 31.5 ± 1.5 39.5 ± 1.5 39.5 ± 1.5 18.5 ± Weight of Cable Approx. (Kg/Km) 340 340 450 450 680 680 930 930 1180 1180 1330 1700 1700 400 400 540 540 870 870 1180 1180 1580 1580 2350 450 450 600 600 1000 1000 1360 1360 1760 1760 2640 2640 540 Copper content Approx. (kg/km) 113 113 155 155 240 240 332 332 383 383 447 536 536 143 143 198 198 308 308 410 410 513 513 822 162 162 234 234 404 404 540 540 677 677 1030 1030 207

www.drakaMOG.com

Subject to change without prior notice Page 17 of 96 2010-04-30

Cross Number No of Conductor Insulation section of cores in Diameter, Thickness, core, elements element mm mm mm²

Thickness Inner covering, mm

Diameter inner covering, mm 0.8 14.5 ± 0.8 17 ± 0.8 17 ± 0.8 22.5 ± 1 22.5 ± 1 27 ± 1 31.5 ± 1.5 31.5 ± 1.5 38.5 ± 1.5 14 ± 0.8 16.5 ± 0.8 22 ± 1 30.5 ± 1.5 37.5 ± 1.5 18.5 ± 0.8 25 ± 1 35 ± 1.5

Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.3 0.3 0.3 0.4 0.4 0.3 0.3 0.4 11.9 13.6 13.6 17.8 17.8 22.9 36.2 36.2 40.7 11.9 13.6 17.8 31.7 40.7 15.3 20.4 36.2

Thickness Outer Sheath, mm

Diameter outer sheath, mm 0.8 18.5 ± 0.8 21 ± 1 21 ± 1 27 ± 1 27 ± 1 32 ± 1.5 37 ± 1.5 37 ± 1.5 45 ± 2 18 ± 0.8 20.5 ± 1 27 ± 1 36 ± 1.5 44 ± 2 23 ± 1 30 ± 1.5 41.5 ± 2

Weight of Cable Approx. (Kg/Km)

Copper content Approx. (kg/km)

2 4 4 8 8 12 16 16 24 2 4 8 16 24 4 8 16

3 3 3 3 3 3 3 3 3 2 2 2 2 2 3 3 3

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2 2 2 2 2 2 2 2

0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7

1.1 1.1 1.1 1.1 1.1 1.4 2.3 2.3 2.7 1.1 1.1 1.1 2.3 2.7 1.1 1.1 2.6

1.4 1.5 1.5 1.8 1.8 1.9 2.1 2.1 2.4 1.4 1.5 1.8 2.1 2.4 1.6 1.9 2.3

540 760 760 1280 1280 1770 2560 2560 3610 530 740 1230 2410 3480 940 1620 3280

207 307 307 517 517 736 1034 1034 1421 217 325 551 1053 1509 435 762 1471

Electrical values instrumentation cables

Capacitance, approx. (nF/km) Unshielded pair 0,75 mm² 100 Unshielded triple 0,75 mm² 100 Unshielded pair 1,5 mm² 110 Unshielded triple 1,5 mm² 110 Unshielded pair 2,5 mm² 125 Unshielded triple 2,5 mm² 125 Type Inductance, approx, (mH/km) 0,67 0,67 0,63 0,63 0,59 0,59 Resistance at 20°C, max. (Ohm/km) 26,3 26,3 12,9 12,9 8,02 8,02 L/R ratio, (microH/Ohm) 12,7 12,7 24,4 24,4 36,8 36,8

Ordering information

Part number 893806 893807 893818 893819 893830 893831 893836 893837 893842 893843 893845 893848 893849 893866 893867 893878 893879 893890 893891 893896 893897 893902 893903 Description BFOU(C) 2PAIR 0.75mm² S4/S8 BFOU(C) 2PAIR 0.75mm² S4/S8 BFOU(C) 4PAIR 0.75mm² S4/S8 BFOU(C) 4PAIR 0.75mm² S4/S8 BFOU(C) 8PAIR 0.75mm² S4/S8 BFOU(C) 8PAIR 0.75mm² S4/S8 BFOU(C) 12PAIR 0.75mm² S4/S8 BFOU(C) 12PAIR 0.75mm² S4/S8 BFOU(C) 16PAIR 0.75mm² S4/S8 BFOU(C) 16PAIR 0.75mm² S4/S8 BFOU(C) 19PAIR 0.75mm² S4/S8 BFOU(C) 24PAIR 0.75mm² S4/S8 BFOU(C) 24PAIR 0.75mm² S4/S8 BFOU(C) 2TRIP 0.75mm² S4/S8 BFOU(C) 2TRIP 0.75mm² S4/S8 BFOU(C) 4TRIP 0.75mm² S4/S8 BFOU(C) 4TRIP 0.75mm² S4/S8 BFOU(C) 8TRIP 0.75mm² S4/S8 BFOU(C) 8TRIP 0.75mm² S4/S8 BFOU(C) 12TRIP 0.75mm² S4/S8 BFOU(C) 12TRIP 0.75mm² S4/S8 BFOU(C) 16TRIP 0.75mm² S4/S8 BFOU(C) 16TRIP 0.75mm² S4/S8 Sheath Colour GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE Stock item Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes EAN No. DNK 7021528938067 7021528938074 7021528938180 7021528938197 7021528938302 7021528938319 7021528938364 7021528938371 7021528938425 7021528938432 7021528938456 7021528938487 7021528938494 7021528938661 7021528938678 7021528938784 7021528938791 7021528938906 7021528938913 7021528938968 7021528938975 7021528939026 7021528939033 EL No. 1043821 1043822 1043823 1043824 1043828 1043829 1043830 1043831 1043833 1043834 1043836 1043837 1043921 1043922 1043924 1043925 1043928 1043929 1043930 1043931 1043933 1043934

www.drakaMOG.com

Subject to change without prior notice Page 18 of 96 2010-04-30

Part number 893908 894006 894007 894018 894019 894030 894031 894036 894037 894042 894043 894048 894049 894066 894067 894078 894079 894090 894091 894096 894102 894103 894108 894206 894218 894230 894242 894248 894278 894290 894302

Description BFOU(C) 24TRIP 0.75mm² S4/S8 BFOU(C) 2PAIR 1.5mm² S4/S8 BFOU(C) 2PAIR 1.5mm² S4/S8 BFOU(C) 4PAIR 1.5mm² S4/S8 BFOU(C) 4PAIR 1.5mm² S4/S8 BFOU(C) 8PAIR 1.5mm² S4/S8 BFOU(C) 8PAIR 1.5mm² S4/S8 BFOU(C) 12PAIR 1.5mm² S4/S8 BFOU(C) 12PAIR 1.5mm² S4/S8 BFOU(C) 16PAIR 1.5mm² S4/S8 BFOU(C) 16PAIR 1.5mm² S4/S8 BFOU(C) 24PAIR 1.5mm² S4/S8 BFOU(C) 24PAIR 1.5mm² S4/S8 BFOU(C) 2TRIP 1.5mm² S4/S8 BFOU(C) 2TRIP 1.5mm² S4/S8 BFOU(C) 4TRIP 1.5mm² S4/S8 BFOU(C) 4TRIP 1.5mm² S4/S8 BFOU(C) 8TRIP 1.5mm² S4/S8 BFOU(C) 8TRIP 1.5mm² S4/S8 BFOU(C) 12TRIP 1.5mm² S4/S8 BFOU(C) 16TRIP 1.5mm² S4/S8 BFOU(C) 16TRIP 1.5mm² S4/S8 BFOU(C) 24TRIP 1.5mm² S4/S8 BFOU(C) 2PAIR 2.5mm² S4/S8 BFOU(C) 4PAIR 2.5mm² S4/S8 BFOU(C) 8PAIR 2.5mm² S4/S8 BFOU(C) 16PAIR 2.5mm² S4/S8 BFOU(C) 24PAIR 2.5mm² S4/S8 BFOU(C) 4TRIP 2.5mm² S4/S8 BFOU(C) 8TRIP 2.5mm² S4/S8 BFOU(C) 16TRIP 2.5mm² S4/S8

Sheath Colour GREY GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY GREY BLUE GREY GREY GREY GREY GREY GREY GREY GREY GREY

Stock item Yes Yes Yes Yes Yes Yes Yes Yes Yes -

EAN No. DNK 7021528939088 7021528940060 7021528940077 7021528940183 7021528940190 7021528940305 7021528940312 7021528940367 7021528940374 7021528940428 7021528940435 7021528940480 7021528940497 7021528940664 7021528940671 7021528940787 7021528940794 7021528940909 7021528940916 7021528940961 7021528941029 7021528941036 7021528941081 7021528942064 7021528942187 7021528942309 7021528942422 7021528942484 7021528942781 7021528942903 7021528943023

EL No. 1043936 1043862 1043861 1043863 1043864 1043868 1043869 1043870 1043871 1043873 1043874 1043876 1043877 1043971 1043972 1043973 1043974 1043977 1043978 1043979 1043981 1043982 1043987 -

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 19 of 96 2010-04-30

Halogen-free, unarmoured mud resistant instrumentation cable RU(i) 250V, S11 Flame retardant halogen-free instrumentation cable. Mud resistant

RU(i) 150/250(300)V

EPR/EVA

NEK TS 606 CodeS11

Operating temperature Operating Voltage Standards applied Application Fixed installation for instrumentation, communication, Control and alarm systems in both EX- (Zone 2) and safe areas. Meets the mud resistant requirements in NEK TS 606:2009. IEC 60092-376 (2003-05) IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 150/250(300)V

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Pair / Triple / Quad twisting Lay up / Shielding Inner covering Armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour U R Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 EP-rubber, IEC 60092-351 (EPR) Color coded cores twisted together. Pairs/Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair/triple is wrapped with polyester tape to prevent electrical contact with adjacent pairs/triples. Pairs/triples are identified by numbers printed directly on the insulated conductors. Individually shielded pairs/triples/quads are laid up in concentric layers and wrapped with a PETP tape. No inner covering. (Additional tapes may be applied) No armour. Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) E.g. "meter" "year" DRAKA 01 RU(i) 250V S11 2 pair 0,75 mm2 IEC 60092-376 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel, Grey or Blue

www.drakaMOG.com

Subject to change without prior notice Page 20 of 96 2010-04-30

Core identification instrumentation cables

Pair - Black - Light Blue Triple - Black - Light Blue - Brown Quad - Black - Light Blue - Brown - Grey

Range and dimensions

No of Number of cores in elements element 1 1 2 2 4 8 12 16 24 1 2 4 8 12 16 24 1 1 2 2 4 8 12 16 24 1 2 4 8 16 24 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 Cross Conductor section Diameter, core, mm² mm 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 Insulation Thickness, mm 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 Weight of Thickness Diameter Cable Outer Sheath, outer sheath, Approx. mm mm (Kg/Km) 1 6.5 ± 0.5 85 1 6.5 ± 0.5 85 1.1 10 ± 0.8 140 1.1 10 ± 0.8 140 1.2 11.5 ± 0.8 235 1.3 15.5 ± 0.8 420 1.5 19 ± 0.8 610 1.5 21 ± 1 760 1.7 25.5 ± 1 1120 1 7 ± 0.5 95 1.2 11 ± 0.8 180 1.2 13 ± 0.8 290 1.4 18 ± 0.8 540 1.6 21.5 ± 1 790 1.6 23.5 ± 1 990 1.9 29.5 ± 1 1480 1 8 ± 0.5 120 1 8 ± 0.5 120 1.2 12 ± 0.8 220 1.2 12 ± 0.8 220 1.3 14.5 ± 0.8 370 1.5 20 ± 1 690 1.6 23.5 ± 1 970 1.7 26.5 ± 1 1260 2 32.5 ± 1.5 1880 1 8.5 ± 0.5 140 1.3 14 ± 0.8 285 1.3 16 ± 0.8 470 1.6 22.5 ± 1 900 1.9 30 ± 1.5 1700 2.2 37 ± 1.5 2530 Copper content Approx. (kg/km) 17 17 34 34 67 133 199 265 397 23 47 93 185 277 369 553 34 34 68 68 136 271 406 541 811 48 96 192 384 768 1152

Electrical values instrumentation cables

Type Shielded pair 0,75 mm² Shielded triple 0,75 mm² Shielded pair 1,5 mm² Shielded triple 1,5 mm² Shielded pair 2,5 mm² Shielded triple 2,5 mm² Capacitance, approx. (nF/km) 110 110 125 125 145 145 Inductance, approx, (mH/km) 0,67 0,67 0,63 0,63 0,59 0,59 Resistance at 20°C, max. (Ohm/km) 26,3 26,3 12,9 12,9 8,02 8,02 L/R ratio, (microH/Ohm) 12,7 12,7 24,4 24,4 36,8 36,8

www.drakaMOG.com

Subject to change without prior notice Page 21 of 96 2010-04-30

Ordering information

Part number 895000 895001 895006 895007 895018 895030 895036 895042 895048 895060 895066 895078 895090 895096 895102 895108 895200 895201 895206 895207 895218 895230 895236 895242 895248 895260 895266 895278 895290 895302 895308 Description RU(I) 250V 1PAIR 0.75mm² S11 RU(I) 250V 1PAIR 0.75mm² S11 RU(I) 250V 2PAIR 0.75mm² S11 RU(I) 250V 2PAIR 0.75mm² S11 RU(I) 250V 4PAIR 0.75mm² S11 RU(I) 250V 8PAIR 0.75mm² S11 RU(I) 250V 12PAIR 0.75mm² S11 RU(I) 250V 16PAIR 0.75mm² S11 RU(I) 250V 24PAIR 0.75mm² S11 RU(I) 250V 1TRIP 0.75mm² S11 RU(I) 250V 2TRIP 0.75mm² S11 RU(I) 250V 4TRIP 0.75mm² S11 RU(I) 250V 8TRIP 0.75mm² S11 RU(I) 250V 12TRIP 0.75mm² S11 RU(I) 250V 16TRIP 0.75mm² S11 RU(I) 250V 24TRIP 0.75mm² S11 RU(I) 250V 1PAIR 1.5mm² S11 RU(I) 250V 1PAIR 1.5mm² S11 RU(I) 250V 2PAIR 1.5mm² S11 RU(I) 250V 2PAIR 1.5mm² S11 RU(I) 250V 4PAIR 1.5mm² S11 RU(I) 250V 8PAIR 1.5mm² S11 RU(I) 250V 12PAIR 1.5mm² S11 RU(I) 250V 16PAIR 1.5mm² S11 RU(I) 250V 24PAIR 1.5mm² S11 RU(I) 250V 1TRIP 1.5mm² S11 RU(I) 250V 2TRIP 1.5mm² S11 RU(I) 250V 4TRIP 1.5mm² S11 RU(I) 250V 8TRIP 1.5mm² S11 RU(I) 250V 16TRIP 1.5mm² S11 RU(I) 250V 24TRIP 1.5mm² S11 Sheath Colour GREY BLUE GREY BLUE GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY BLUE GREY BLUE GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY Stock item EAN No. DNK 7021528950007 7021528950014 7021528950069 7021528950076 7021528950182 7021528950304 7021528950366 7021528950427 7021528950489 7021528950601 7021528950663 7021528950786 7021528950908 7021528950960 7021528951028 7021528951080 7021528952001 7021528952018 7021528952063 7021528952070 7021528952186 7021528952308 7021528952360 7021528952421 7021528952483 7021528952605 7021528952667 7021528952780 7021528952902 7021528953022 7021528953084 EL No. 1062100 1062101 1062106 1062107 1062118 1062130 1062136 1062142 1062148 1062160 1062166 1062178 1062190 1062194 1062196 1062198 1062200 1062201 1062206 1062207 1062218 1062230 1062236 1062242 1062248 1062260 1062266 1062278 1062290 1062296 1062298

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 22 of 96 2010-04-30

Halogen-free, unarmoured mud resistant instrumentation cable RU(c) 250V, S12 Flame retardant halogen-free instrumentation cable. Mud resistant

RU(c) 150/250(300)V

EPR/EVA

NEK TS 606 CodeS12

Operating temperature Operating Voltage Standards applied IEC 60092-376 (2003-05) IEC 60228 class 2 Fixed installation for instrumentation, communication, IEC 60092-351 Control and alarm systems in both EX- (Zone 2) and safe IEC 60092-359 areas. Meets the mud resistant requirements in NEK TS IEC 60332-1 606:2009. IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 Application

: 90°C : 150/250(300)V

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Pair / Triple / Quad twisting Inner covering Armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour U R Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 EP-rubber, IEC 60092-351 (EPR) Color coded cores twisted together and wrapped with polyester tape. Pairs/Triples are laid up collectively and screened by copper backed polyester tape with tinned copper drain wire. Pairs/triples are identified by numbers printed directly on the insulated conductors. No inner covering. (Additional tapes may be applied) No armour. Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) E.g. "meter" "year" DRAKA 01 RU(c) 250V S12 2 pair 0,75 mm2 IEC 60092-376 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel, Grey or Blue

www.drakaMOG.com

Subject to change without prior notice Page 23 of 96 2010-04-30

Core identification instrumentation cables

Pair - Black - Light Blue Triple - Black - Light Blue - Brown Quad - Black - Light Blue - Brown - Grey

Range and dimensions

No of Number of cores in elements element 2 4 4 8 12 16 19 24 2 4 4 8 16 24 2 4 8 12 12 16 24 2 4 8 12 16 24 2 2 2 2 2 2 2 2 3 3 3 3 3 3 2 2 2 2 2 2 2 3 3 3 3 3 3 Cross Conductor section Diameter, core, mm² mm 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 Insulation Thickness, mm 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 Weight of Thickness Diameter Cable Outer Sheath, outer sheath, Approx. mm mm (Kg/Km) 1.1 10 ± 0.8 135 1.1 11.5 ± 0.8 195 1.1 11.5 ± 0.8 195 1.3 15.5 ± 0.8 380 1.4 18 ± 0.8 510 1.5 19.5 ± 0.8 640 1.5 20.5 ± 1 730 1.7 24 ± 1 920 1.1 11 ± 0.8 170 1.2 13 ± 0.8 265 1.2 13 ± 0.8 265 1.4 17.5 ± 0.8 490 1.6 22 ± 1 870 1.8 27 ± 1 1260 1.2 12 ± 0.8 210 1.2 14 ± 0.8 320 1.4 19.5 ± 0.8 610 1.6 22.5 ± 1 850 1.6 22.5 ± 1 850 1.7 24.5 ± 1 1090 1.9 30 ± 1.5 1550 1.2 13.5 ± 0.8 265 1.3 16 ± 0.8 430 1.5 21.5 ± 1 820 1.7 25.5 ± 1 1170 1.8 27.5 ± 1 1500 2.1 34 ± 1.5 2210 Copper content Approx. (kg/km) 30 55 55 106 158 209 247 311 43 81 81 158 313 467 62 118 229 340 340 452 674 90 174 342 510 679 1015

Electrical values instrumentation cables

Capacitance, approx. (nF/km) Unshielded pair 0,75 mm² 100 Unshielded triple 0,75 mm² 100 Unshielded pair 1,5 mm² 110 Unshielded triple 1,5 mm² 110 Unshielded pair 2,5 mm² 125 Unshielded triple 2,5 mm² 125 Type Inductance, approx, (mH/km) 0,67 0,67 0,63 0,63 0,59 0,59 Resistance at 20°C, max. (Ohm/km) 26,3 26,3 12,9 12,9 8,02 8,02 L/R ratio, (microH/Ohm) 12,7 12,7 24,4 24,4 36,8 36,8

Ordering information

Part number 895606 895618 895619 895630 895636 895642 895645 895648 895666 895678 895679 895690 Description RU(C) 250V 2PAIR 0.75mm² S12 RU(C) 250V 4PAIR 0.75mm² S12 RU(C) 250V 4PAIR 0.75mm² S12 RU(C) 250V 8PAIR 0.75mm² S12 RU(C) 250V 12PAIR 0.75mm² S12 RU(C) 250V 16PAIR 0.75mm² S12 RU(C) 250V 19PAIR 0.75mm² S12 RU(C) 250V 24PAIR 0.75mm² S12 RU(C) 250V 2TRIP 0.75mm² S12 RU(C) 250V 4TRIP 0.75mm² S12 RU(C) 250V 4TRIP 0.75mm² S12 RU(C) 250V 8TRIP 0.75mm² S12 Sheath Colour GREY GREY BLUE GREY GREY GREY GREY GREY GREY GREY BLUE GREY Stock item EAN No. DNK 7021528956061 7021528956184 7021528956191 7021528956306 7021528956368 7021528956429 7021528956450 7021528956481 7021528956665 7021528956788 7021528956795 7021528956900 EL No. 1062506 1062518 1062530 1062536 1062542 1062545 1062548 1062566 1062578 1062590

www.drakaMOG.com

Subject to change without prior notice Page 24 of 96 2010-04-30

Part number 895702 895708 895806 895818 895830 895836 895837 895842 895848 895866 895878 895890 895896 895902 895908

Description RU(C) 250V 16TRIP 0.75mm² S12 RU(C) 250V 24TRIP 0.75mm² S12 RU(C) 250V 2PAIR 1.5mm² S12 RU(C) 250V 4PAIR 1.5mm² S12 RU(C) 250V 8PAIR 1.5mm² S12 RU(C) 250V 12PAIR 1.5mm² S12 RU(C) 250V 12PAIR 1.5mm² S12 RU(C) 250V 16PAIR 1.5mm² S12 RU(C) 250V 24PAIR 1.5mm² S12 RU(C) 250V 2TRIP 1.5mm² S12 RU(C) 250V 4TRIP 1.5mm² S12 RU(C) 250V 8TRIP 1.5mm² S12 RU(C) 250V 12TRIP 1.5mm² S12 RU(C) 250V 16TRIP 1.5mm² S12 RU(C) 250V 24TRIP 1.5mm² S12

Sheath Colour GREY GREY GREY GREY GREY GREY BLUE GREY GREY GREY GREY GREY GREY GREY GREY

Stock item -

EAN No. DNK 7021528957020 7021528957082 7021528958065 7021528958188 7021528958300 7021528958362 7021528958379 7021528958423 7021528958485 7021528958669 7021528958782 7021528958904 7021528958966 7021528959024 7021528959086

EL No. 1062603 1062608 1062706 1062718 1062730 1062736 1062737 1062742 1062748 1062766 1062778 1062790 1062794 1062796 1062798

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 25 of 96 2010-04-30

Halogen-free, fire resistant, unarmoured, mud resistant instrumentation cable BU(i) 250V, S13 Fire resistant, flame retardant halogenfree instrumentation cable. Mud resistant

BU(i) 150/250(300)V

MGT/EPR/EVA

NEK TS 606 CodeS13

Operating temperature Operating Voltage Standards applied Application Fixed installation for instrumentation, communication, control and alarm systems in both EX-(Zone 2) and safe areas, emergency and critical systems where requirement for fire resistance exists. Meets the mud resistant requirements in NEK TS 606:2009. IEC 60092-376 (2003-05) IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60331-21 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 150/250(300)V

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Fire Resistant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Pair / Triple / Quad twisting Lay up / Shielding Inner covering Armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour U B Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 Mica-tape + EP-rubber, IEC 60092-351 (EPR) Color coded cores twisted together. Pairs/Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair/triple is wrapped with polyester tape to prevent electrical contact with adjacent pairs/triples. Pairs/triples are identified by numbered tape or by numbers printed directly on the insulated conductors. Individually shielded pairs/triples/quads are laid up in concentric layers and wrapped with a PETP tape. No inner covering. (Additional tapes may be applied) No armour. Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) "meter" "year" DRAKA 01 BU(i) 250V S13 8 PAIR 0,75 mm2 FLEX - FLAME IEC 60092-376 IEC 60331-21 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel, Grey or Blue

www.drakaMOG.com

Subject to change without prior notice Page 26 of 96 2010-04-30

Core identification instrumentation cables

Pair - Black - Light Blue Triple - Black - Light Blue - Brown Quad - Black - Light Blue - Brown - Grey

Range and dimensions

No of Number of cores in elements element 1 1 2 2 4 8 12 16 24 1 2 4 8 12 16 24 1 1 2 2 4 4 8 8 12 12 16 24 24 1 1 2 4 8 12 16 24 1 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 2 Cross Conductor section Diameter, core, mm² mm 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2 Insulation Thickness, mm 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 Weight of Thickness Diameter Cable Outer Sheath, outer sheath, Approx. mm mm (Kg/Km) 1 7.5 ± 0.5 95 1 7.5 ± 0.5 95 1.2 11 ± 0.8 165 1.2 11 ± 0.8 165 1.2 13 ± 0.8 260 1.4 17.5 ± 0.8 490 1.6 21 ± 1 700 1.7 23.5 ± 1 900 1.9 29 ± 1 1300 1 7.5 ± 0.5 105 1.2 12 ± 0.8 200 1.3 14 ± 0.8 340 1.5 19.5 ± 0.8 640 1.7 23.5 ± 1 900 1.8 26 ± 1 1170 2.1 32.5 ± 1.5 1720 1 8.5 ± 0.5 130 1 8.5 ± 0.5 130 1.3 13.5 ± 0.8 250 1.3 13.5 ± 0.8 250 1.4 16 ± 0.8 420 1.4 16 ± 0.8 420 1.6 22 ± 1 770 1.6 22 ± 1 770 1.7 26 ± 1 1100 1.7 26 ± 1 1100 1.9 29.5 ± 1 1460 2.2 36.5 ± 1.5 2140 2.2 36.5 ± 1.5 2140 1.1 9.5 ± 0.5 165 1.1 9.5 ± 0.5 165 1.3 14.5 ± 0.8 320 1.4 17.5 ± 0.8 540 1.7 23.5 ± 1 1030 1.9 29 ± 1 1480 2 32.5 ± 1.5 1920 2.4 40.5 ± 2 2880 1.1 9.5 ± 0.5 170 Copper content Approx. (kg/km) 17 17 34 34 67 133 199 265 397 23 47 93 185 277 369 554 34 34 68 68 136 136 271 271 406 406 551 812 812 48 48 98 195 384 577 779 1168 55

Electrical values instrumentation cables

Type Shielded pair 0,75 mm² Shielded triple 0,75 mm² Shielded pair 1,5 mm² Shielded triple 1,5 mm² Shielded pair 2,5 mm² Shielded triple 2,5 mm² Capacitance, approx. (nF/km) 110 110 125 125 145 145 Inductance, approx, (mH/km) 0,67 0,67 0,63 0,63 0,59 0,59 Resistance at 20°C, max. (Ohm/km) 26,3 26,3 12,9 12,9 8,02 8,02 L/R ratio, (microH/Ohm) 12,7 12,7 24,4 24,4 36,8 36,8

www.drakaMOG.com

Subject to change without prior notice Page 27 of 96 2010-04-30

Ordering information

Part number 896200 896201 896206 896207 896218 896230 896236 896242 896248 896260 896266 896278 896290 896296 896302 896308 896400 896401 896406 896407 896418 896419 896430 896431 896436 896437 896442 896448 896449 896460 896461 896466 896478 896490 896496 896502 896508 896600 Description BU(I) 250V 1PAIR 0.75mm² S13 BU(I) 250V 1PAIR 0.75mm² S13 BU(I) 250V 2PAIR 0.75mm² S13 BU(I) 250V 2PAIR 0.75mm² S13 BU(I) 250V 4PAIR 0.75mm² S13 BU(I) 250V 8PAIR 0.75mm² S13 BU(I) 250V 12PAIR 0.75mm² S13 BU(I) 250V 16PAIR 0.75mm² S13 BU(I) 250V 24PAIR 0.75mm² S13 BU(I) 250V 1TRIP 0.75mm² S13 BU(I) 250V 2TRIP 0.75mm² S13 BU(I) 250V 4TRIP 0.75mm² S13 BU(I) 250V 8TRIP 0.75mm² S13 BU(I) 250V 12TRIP 0.75mm² S13 BU(I) 250V 16TRIP 0.75mm² S13 BU(I) 250V 24TRIP 0.75mm² S13 BU(I) 250V 1PAIR 1.5mm² S13 BU(I) 250V 1PAIR 1.5mm² S13 BU(I) 250V 2PAIR 1.5mm² S13 BU(I) 250V 2PAIR 1.5mm² S13 BU(I) 250V 4PAIR 1.5mm² S13 BU(I) 250V 4PAIR 1.5mm² S13 BU(I) 250V 8PAIR 1.5mm² S13 BU(I) 250V 8PAIR 1.5mm² S13 BU(I) 250V 12PAIR 1.5mm² S13 BU(I) 250V 12PAIR 1.5mm² S13 BU(I) 250V 16PAIR 1.5mm² S13 BU(I) 250V 24PAIR 1.5mm² S13 BU(I) 250V 24PAIR 1.5mm² S13 BU(I) 250V 1TRIP 1.5mm² S13 BU(I) 250V 1TRIP 1.5mm² S13 BU(I) 250V 2TRIP 1.5mm² S13 BU(I) 250V 4TRIP 1.5mm² S13 BU(I) 250V 8TRIP 1.5mm² S13 BU(I) 250V 12TRIP 1.5mm² S13 BU(I) 250V 16TRIP 1.5mm² S13 BU(I) 250V 24TRIP 1.5mm² S13 BU(I) 250V 1PAIR 2.5mm² S13 Sheath Colour GREY BLUE GREY BLUE GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY BLUE GREY GREY BLUE GREY BLUE GREY GREY GREY GREY GREY GREY GREY Stock item EAN No. DNK 7021528962000 7021528962017 7021528962062 7021528962079 7021528962185 7021528962307 7021528962369 7021528962420 7021528962482 7021528962604 7021528962666 7021528962789 7021528962901 7021528962963 7021528963021 7021528963083 7021528964004 7021528964011 7021528964066 7021528964073 7021528964189 7021528964196 7021528964301 7021528964318 7021528964363 7021528964370 7021528964424 7021528964486 7021528964493 7021528964608 7021528964615 7021528964660 7021528964783 7021528964905 7021528964967 7021528965025 7021528965087 7021528966008 EL No. 1063500 1063501 1063506 1063507 1063518 1063530 1063536 1063542 1063548 1063560 1063566 1063578 1063590 1063596 1063602 1063608 1063700 1063701 1063706 1063707 1063718 1063730 1063736 1063737 1063742 1063748 1063760 1063761 1063766 1063778 1063790 1063796 1063802 1063808 1063900

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 28 of 96 2010-04-30

Halogen-free, fire resistant, unarmoured, mud resistant instrumentation cable BU(c) 250V, S14 Fire resistant, flame retardant halogenfree instrumentation cable. Mud resistant

BU(c) 150/250(300)V

MGT/EPR/EVA

NEK TS 606 CodeS14

Operating temperature Operating Voltage Standards applied Application Fixed installation for instrumentation, communication, control and alarm systems in both EX-(Zone 2) and safe areas, emergency and critical systems where requirement for fire resistance exists. Meets the mud resistant requirements in NEK TS 606:2009. IEC 60092-376 (2003-05) IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60331-21 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 150/250(300)V

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Fire Resistant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Pair / Triple / Quad twisting Inner covering Armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour U B Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 Mica-tape + EP-rubber, IEC 60092-351 (EPR) Color coded cores twisted together and wrapped with polyester tape. Pairs/Triples are laid up collectively and screened by copper backed polyester tape with tinned copper drain wire.Pairs/triples are identified by numbered tape or by numbers printed directly on the insulated conductors. No inner covering. (Additional tapes may be applied) No armour. Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) "meter" "year" DRAKA 01 BU(c) 250V S14 8 PAIR 0,75 mm2 FLEX - FLAME IEC 60092-376 IEC 60331-21 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel, Grey or Blue

www.drakaMOG.com

Subject to change without prior notice Page 29 of 96 2010-04-30

Core identification instrumentation cables

Pair - Black - Light Blue Triple - Black - Light Blue - Brown Quad - Black - Light Blue - Brown - Grey

Range and dimensions

No of Number of cores in elements element 2 4 8 12 12 16 19 24 2 4 8 12 16 24 2 4 8 12 16 24 2 4 8 12 16 24 2 2 2 2 2 2 2 2 3 3 3 3 3 3 2 2 2 2 2 2 3 3 3 3 3 3 Cross Conductor section Diameter, core, mm² mm 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 Insulation Thickness, mm 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 Weight of Thickness Diameter Cable Outer Sheath, outer sheath, Approx. mm mm (Kg/Km) 1.1 10.5 ± 0.8 150 1.2 12.5 ± 0.8 230 1.4 17 ± 0.8 420 1.5 19.5 ± 0.8 570 1.5 19.5 ± 0.8 570 1.6 21.5 ± 1 720 1.7 23 ± 1 830 1.8 26.5 ± 1 1040 1.2 12 ± 0.8 200 1.3 14.5 ± 0.8 320 1.5 19.5 ± 0.8 580 1.6 22.5 ± 1 790 1.7 24.5 ± 1 1000 2 30.5 ± 1.5 1460 1.2 13 ± 0.8 230 1.3 15.5 ± 0.8 360 1.5 21 ± 1 660 1.7 24.5 ± 1 940 1.8 26.5 ± 1 1200 2.1 33 ± 1.5 1770 1.3 15 ± 0.8 310 1.4 17.5 ± 0.8 500 1.6 23.5 ± 1 930 1.8 28 ± 1 1310 1.9 30.5 ± 1.5 1680 2.2 37.5 ± 1.5 2480 Copper content Approx. (kg/km) 30 55 107 158 158 209 247 311 43 81 158 236 313 468 62 118 229 342 452 676 91 175 343 512 680 1016

Electrical values instrumentation cables

Capacitance, approx. (nF/km) Unshielded pair 0,75 mm² 100 Unshielded triple 0,75 mm² 100 Unshielded pair 1,5 mm² 110 Unshielded triple 1,5 mm² 110 Unshielded pair 2,5 mm² 125 Unshielded triple 2,5 mm² 125 Type Inductance, approx, (mH/km) 0,67 0,67 0,63 0,63 0,59 0,59 Resistance at 20°C, max. (Ohm/km) 26,3 26,3 12,9 12,9 8,02 8,02 L/R ratio, (microH/Ohm) 12,7 12,7 24,4 24,4 36,8 36,8

Ordering information

Part number 896806 896818 896830 896836 896837 896842 896845 896848 896866 896878 896890 896896 Description BU(C) 250V 2PAIR 0.75mm² S14 BU(C) 250V 4PAIR 0.75mm² S14 BU(C) 250V 8PAIR 0.75mm² S14 BU(C) 250V 12PAIR 0.75mm² S14 BU(C) 250V 12PAIR 0.75mm² S14 BU(C) 250V 16PAIR 0.75mm² S14 BU(C) 250V 19PAIR 0.75mm² S14 BU(C) 250V 24PAIR 0.75mm² S14 BU(C) 250V 2TRIP 0.75mm² S14 BU(C) 250V 4TRIP 0.75mm² S14 BU(C) 250V 8TRIP 0.75mm² S14 BU(C) 250V 12TRIP 0.75mm² S14 Sheath Colour GREY GREY GREY GREY BLUE GREY GREY GREY GREY GREY GREY GREY Stock item EAN No. DNK 7021528968064 7021528968187 7021528968309 7021528968361 7021528968378 7021528968422 7021528968453 7021528968484 7021528968668 7021528968781 7021528968903 7021528968965 EL No. 1064106 1064118 1064130 1064136 1064142 1064145 1064148 1064166 1064178 1064190 1064196

www.drakaMOG.com

Subject to change without prior notice Page 30 of 96 2010-04-30

Part number 896902 896908 897006 897018 897030 897036 897042 897048 897066 897078 897090 897096 897102 897108

Description BU(C) 250V 16TRIP 0.75mm² S14 BU(C) 250V 24TRIP 0.75mm² S14 BU(C) 250V 2PAIR 1.5mm² S14 BU(C) 250V 4PAIR 1.5mm² S14 BU(C) 250V 8PAIR 1.5mm² S14 BU(C) 250V 12PAIR 1.5mm² S14 BU(C) 250V 16PAIR 1.5mm² S14 BU(C) 250V 24PAIR 1.5mm² S14 BU(C) 250V 2TRIP 1.5mm² S14 BU(C) 250V 4TRIP 1.5mm² S14 BU(C) 250V 8TRIP 1.5mm² S14 BU(C) 250V 12TRIP 1.5mm² S14 BU(C) 250V 16TRIP 1.5mm² S14 BU(C) 250V 24TRIP 1.5mm² S14

Sheath Colour GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY GREY

Stock item -

EAN No. DNK 7021528969023 7021528969085 7021528970067 7021528970180 7021528970302 7021528970364 7021528970425 7021528970487 7021528970661 7021528970784 7021528970906 7021528970968 7021528971026 7021528971088

EL No. 1064203 1064208 1064306 1064318 1064330 1064336 1064342 1064348 1064366 1064378 1064390 1064396 1064402 1064408

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 31 of 96 2010-04-30

Halogen-free, mud resistant power cable RFOU 0,6/1kV, P1/P8 Flame retardant halogen-free power cable. Mud resistant

RFOU 0,6/1(1,2)kV

EPR/EPR/TCWB/EVA

NEK TS 606 CodeP1/P8

Operating temperature Operating Voltage Standards applied Application Fixed installation for power,control and lighting in both EX- and safe areas, general purposes. For installation in areas exposed to MUD and drilling/cleaning fluids. Meets the MUD resistance requirement in NEK TS 606:2009. IEC 60092-353 IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 0,6/1(1,2)kV

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Lay up / Shielding Inner covering Tape over inner covering Armour/screen Tape over armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour R F Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 EP-rubber, IEC 60092-351 (EPR) Cores laid up in concentric layers Flame retardant and halogen-free thermoset compound PET tape Tinned annealed copper wire braid PET tape Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) E.g. "meter" "year" DRAKA 01 RFOU 0,6/1KV P1/P8 3 x 35/16 mm2 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel, Black

O

U

www.drakaMOG.com

Subject to change without prior notice Page 32 of 96 2010-04-30

Core identification power cables

Single core - Black Two cores - Blue - Brown Three cores - Brown - Black - Grey Four cores - Blue - Brown - Black - Grey Five cores - Blue - Brown - Black - Grey - Black Seven cores and above - White with black numbers Two cores + earth (3G) - Yellow/green - Blue - Brown Three cores + earth (4G) - Yellow/green - Brown - Black - Grey Four cores + earth (5G) - Yellow/green - Blue - Brown - Black - Grey G / X in cable description - G = One of the cores are yellow/green - X = no yellow/green core Core identification - to HD308S2 - and IEC 60446:2007-05

Range and dimensions

Electrical Cross Number Cross section of section core, elements braid, mm² mm² 1 16 2.5 1 1 1 1 1 1 1 1 1 1 2 3G 4G 3 4 5 7 12 19 27 37 5G 7G 2 3G 3 4G 5G 4 5 7 25 35 50 70 95 120 150 185 240 300 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 4 6 6 10 10 10 10 10 16 16 4 4 6 6 6 10 10 10 16 4 6 6 6 6 Thickness Conductor Insulation Inner Diameter, Thickness, covering, mm mm mm 5.15 6.45 7.65 9.0 10.85 12.60 14.20 15.90 17.70 20.15 22.60 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.1 1.1 1.1 1.1 1.1 1.1 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.2 1.2 1.2 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 9.5 ± 0.5 0.2 4.5 11.5 ± 0.2 5.3 0.8 12.5 ± 0.3 10.2 0.8 14.5 ± 0.3 10.2 0.8 16.5 ± 0.3 12.7 0.8 18.5 ± 0.3 12.7 0.8 20.5 ± 1 0.3 15.3 22.5 ± 1 0.3 15.3 24.5 ± 1 0.3 17.8 Diameter inner covering, mm 27.5 ± 1 30.5 ± 1.5 0.3 0.3 20.4 20.4 5.3 5.3 8.5 5.3 8.5 10.2 10.2 13.6 15.3 17.8 20.4 10.2 10.2 5.3 8.5 8.5 10.2 10.2 10.2 10.2 11.9 Thickness Outer Sheath, mm 1.2 1.2 1.3 1.4 1.4 1.5 1.6 1.6 1.7 1.8 1.9 1.2 1.2 1.3 1.2 1.3 1.3 1.3 1.5 1.6 1.8 1.9 1.3 1.3 1.2 1.3 1.3 1.3 1.4 1.3 1.4 1.4 Diameter outer sheath, mm 13 ± 0.8 14.5 ± 0.8 16 ± 0.8 18.5 ± 0.8 20.5 ± 1 23 ± 1 25 ± 1 27 ± 1 29.5 ± 1 32.5 ± 1.5 35.5 ± 1.5 12.5 ± 0.8 13.5 ± 0.8 14.5 ± 0.8 13.5 ± 0.8 14.5 ± 0.8 15.5 ± 0.8 16 ± 0.8 20 ± 1 23 ± 1 27 ± 1 30 ± 1.5 15.5 ± 0.8 16 ± 0.8 13.5 ± 0.8 14.5 ± 0.8 14.5 ± 0.8 16 ± 0.8 17 ± 0.8 16 ± 0.8 17 ± 0.8 17.5 ± 0.8 Weight of Cable Approx. (Kg/Km) 360 490 650 840 1110 1400 1720 2060 2480 3130 3840 270 295 380 295 380 440 480 720 990 1310 1670 440 480 320 390 390 460 530 460 530 610 Copper content Approx. (kg/km) 190 283 413 534 757 973 1231 1507 1838 2365 2959 80 94 139 94 139 170 198 301 415 550 716 170 197 98 152 152 192 215 192 215 278

9.5 ± 0.5 0.2 10 ± 0.8 11 ± 0.8 10 ± 0.8 11 ± 0.8 12 ± 0.8 12 ± 0.8 16 ± 0.8 19 ± 0.8 22.5 ± 1 25 ± 1 12 ± 0.8 12 ± 0.8 10.5 ± 0.8 11 ± 0.8 11 ± 0.8 12 ± 0.8 13 ± 0.8 12 ± 0.8 13 ± 0.8 13.5 ± 0.8 0.2 0.3 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.3

www.drakaMOG.com

Subject to change without prior notice Page 33 of 96 2010-04-30

Electrical Cross Number Cross section of section core, elements braid, mm² mm² 12 2.5 10 19 2.5 10 27 2.5 16 37 2.5 16 4G 7G 2 3 4 5 3G 5G 2 3 4 4G 3G 5G 2 3 4 3G 5G 4G 2 3 4 4G 5G 3G 2 3 4 4G 3G 5G 2 3 4 4G 5G 2 3 4 4G 4 2.5 4 4 4 4 4 4 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16 16 16 25 25 25 25 25 25 35 35 35 35 35 50 50 50 50 6 6 6 6 6 6 6 10 10 10 16 16 16 16 16 16 16 16 16 25 25 25 -

Thickness Conductor Insulation Inner Diameter, Thickness, covering, mm mm mm 2.0 2.0 2.0 2.0 2.55 2.0 2.55 2.55 2.55 2.55 2.55 2.55 3.15 3.15 3.15 3.15 3.15 3.15 4.05 4.05 4.05 4.05 4.05 4.05 5.15 5.15 5.15 5.15 5.15 5.15 6.45 6.45 6.45 6.45 6.45 6.45 7.65 7.65 7.65 7.65 7.65 9.0 9.0 9.0 9.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.4 1.4 1.4 1.4 1.2 1.2 1.2 1.4 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.2 1.1 1.1 1.1 1.2 1.2 1.2 1.1 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.4 1.4

Diameter inner covering, mm 18 ± 0.8 21 ± 1 25 ± 1 28.5 ± 1 13.5 ± 0.8 13.5 ± 0.8 11.5 ± 0.8 12 ± 0.8 13.5 ± 0.8 14.5 ± 0.8 12 ± 0.8 14.5 ± 0.8 12.5 ± 0.8 13.5 ± 0.8 15 ± 0.8 15 ± 0.8 13.5 ± 0.8 16.5 ± 0.8 14.5 ± 0.8 15.5 ± 0.8 17 ± 0.8 15.5 ± 0.8 19 ± 0.8 17 ± 0.8 16.5 ± 0.8 17.5 ± 0.8 20 ± 1 20 ± 1 22 ± 1 17.5 ± 0.8 20.5 ± 1 22 ± 1 24 ± 1 24 ± 1 22 ± 1 26.5 ± 1 23 ± 1 24.5 ± 1 27 ± 1 27 ± 1 30 ± 1.5 26.5 ± 1 28.5 ± 1 32 ± 1.5 32 ± 1.5

Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.3 15.3 0.3 17.8 0.3 20.4 0.3 22.9 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.3 0.3 0.3 0.4 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.3 10.2 11.9 8.5 10.2 10.2 11.9 10.2 11.9 10.2 10.2 11.9 11.9 10.2 11.9 11.9 11.9 13.6 11.9 15.3 13.6 18.1 18.1 22.6 15.3 15.3 13.6 22.6 20.4 20.4 17.8 15.3 20.4 20.4 20.4 20.4 20.4 22.9 31.7 31.7 31.7 22.9

Thickness Outer Sheath, mm 1.6 1.7 1.9 2 1.4 1.4 1.3 1.3 1.4 1.4 1.3 1.4 1.3 1.4 1.4 1.4 1.4 1.5 1.4 1.4 1.5 1.4 1.5 1.5 1.5 1.5 1.6 1.6 1.6 1.5 1.6 1.6 1.7 1.7 1.6 1.8 1.7 1.7 1.8 1.8 1.9 1.8 1.9 2 2

Diameter outer sheath, mm 22 ± 1 25.5 ± 1 30 ± 1.5 34 ± 1.5 17 ± 0.8 17.5 ± 0.8 15 ± 0.8 16 ± 0.8 17 ± 0.8 18.5 ± 0.8 16 ± 0.8 18.5 ± 0.8 16.5 ± 0.8 17.5 ± 0.8 18.5 ± 0.8 18.5 ± 0.8 17.5 ± 0.8 20.5 ± 1 18.5 ± 0.8 19.5 ± 0.8 21 ± 1 19.5 ± 0.8 23 ± 1 21 ± 1 21 ± 1 22.5 ± 1 24.5 ± 1 24 ± 1 26 ± 1 22 ± 1 25.5 ± 1 26 ± 1 28.5 ± 1 28.5 ± 1 26 ± 1 31.5 ± 1.5 27.5 ± 1 29 ± 1 31.5 ± 1.5 31.5 ± 1.5 35 ± 1.5 31.5 ± 1.5 34 ± 1.5 37.5 ± 1.5 37 ± 1.5

Weight of Cable Approx. (Kg/Km) 930 1280 1720 2240 560 610 410 480 560 660 480 660 500 590 700 700 590 820 670 780 950 780 1140 950 950 1120 1400 1310 1540 1060 1340 1560 1910 1890 1510 2260 1600 1940 2380 2380 2870 2190 2680 3320 3230

Copper content Approx. (kg/km) 425 611 819 1074 247 277 157 210 247 300 210 300 209 264 335 335 264 390 300 391 496 388 603 496 481 626 806 734 881 571 685 894 1125 1100 844 1356 828 1142 1456 1456 1795 1181 1617 2052 1966

www.drakaMOG.com

Subject to change without prior notice Page 34 of 96 2010-04-30

Electrical Cross Number Cross section of section core, elements braid, mm² mm² 5G 50 2 3 4 4G 5G 5 2 3 4 4G 5G 2 3 4 4G 4G 4G 5 4 70 70 70 70 70 70 95 95 95 95 120 120 120 120 120 150 185 16 240 35 35 35 35 50 50 50 60 60 60 16 120

Thickness Conductor Insulation Inner Diameter, Thickness, covering, mm mm mm 9.0 10.85 10.85 10.85 10.85 10.85 10.85 12.60 12.60 12.60 12.60 14.20 14.20 14.20 14.20 14.20 15.90 17.7 5.15 19.1 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.8 2.0 1.0 2.2 1.4 1.2 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.6 1.4 1.4 1.6 1.6 1.6 1.8 1.2 2.0

Diameter inner covering, mm 35 ± 1.5 30.5 ± 1.5 33 ± 1.5 36.5 ± 1.5 36.5 ± 1.5 40.5 ± 2 40.5 ± 2 35 ± 1.5 37.5 ± 1.5 41.5 ± 2 41.5 ± 2 51 ± 2.5 38 ± 1.5 41 ± 2 46 ± 2 46 ± 2 51 ± 2.5 56.5 ± 2.5 22 ± 1 62 ± 2.5

Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.4 36.2 0.6 0.5 0.5 0.4 0.4 0.4 0.6 0.5 0.5 0.4 0.5 0.6 0.6 0.6 0.4 0.5 0.5 0.3 0.6 50.9 49.5 49.5 36.2 36.2 45.2 61.1 56.5 63.6 40.7 49.5 71.3 71.3 71.3 45.2 49.5 56.5 20.4 127.2

Thickness Outer Sheath, mm 2.1 1.9 2 2.2 2.2 2.3 2.3 2.1 2.2 2.4 2.4 2.7 2.2 2.3 2.5 2.5 2.7 2.9 1.6 3.0

Diameter outer sheath, mm 41 ± 2 36.5 ± 1.5 39 ± 1.5 43 ± 2 42.5 ± 2 46.5 ± 2 46.5 ± 2 41.5 ± 2 43.5 ± 2 48.5 ± 2 48 ± 2 58.5 ± 2.5 45 ± 2 48 ± 2 53.5 ± 2.5 52.5 ± 2.5 58.5 ± 2.5 64.5 ± 3 26 ± 1 72 ± 3.5

Weight of Cable Approx. (Kg/Km) 4030 3040 3730 4600 4470 5360 5440 3960 4830 6020 5790 8610 4810 5950 7440 7110 8790 10700 1590 14800

Copper content Approx. (kg/km) 2531 1782 2385 3018 2888 3528 3610 2317 3126 4020 3796 5909 2891 3975 5100 4781 5931 7241 930 8777

Ordering information

Part number 800000 800001 800002 800003 800004 800005 800006 800007 800008 800009 800010 800015 800016 800017 800018 800019 800020 800021 800022 800023 800024 800025 800026 800028 800029 800030 800032 800033 800034 800035 800036 Description RFOU 0.6/1kV 1X 16/2.5 P1/P8 RFOU 0.6/1kV 1X 25/4mm² P1/P8 RFOU 0.6/1kV 1X 35/6mm² P1/P8 RFOU 0.6/1kV 1X 50/6mm² P1/P8 RFOU 0.6/1kV 1X 70/10mm² P1/P8 RFOU 0.6/1kV 1X 95/10mm² P1/P8 RFOU 0.6/1kV 1X 120/10 P1/P8 RFOU 0.6/1kV 1X 150/10 P1/P8 RFOU 0.6/1kV 1X 185/10 P1/P8 RFOU 0.6/1kV 1X 240/16 P1/P8 RFOU 0.6/1kV 1X 300/16 P1/P8 RFOU 0.6/1kV 2X 1.5/4mm² P1/P8 RFOU 0.6/1kV 3G 1.5mm² P1/P8 RFOU 0.6/1kV 4G 1.5mm² P1/P8 RFOU 0.6/1kV 3X 1.5/4mm² P1/P8 RFOU 0.6/1kV 4X 1.5/6mm² P1/P8 RFOU 0.6/1kV 5X 1.5/6mm² P1/P8 RFOU 0.6/1kV 7X 1.5/6mm² P1/P8 RFOU 0.6/1kV 12X 1.5/10 P1/P8 RFOU 0.6/1kV 19X 1.5/10 P1/P8 RFOU 0.6/1kV 27X 1.5/10 P1/P8 RFOU 0.6/1kV 37X 1.5/16 P1/P8 RFOU 0.6/1kV 5G 1.5mm² P1/P8 RFOU 0.6/1kV 7G 1.5mm² P1/P8 RFOU 0.6/1kV 2X 2.5/4mm² P1/P8 RFOU 0.6/1kV 3G 2.5mm² P1/P8 RFOU 0.6/1kV 3X 2.5/6mm² P1/P8 RFOU 0.6/1kV 4G 2.5mm² P1/P8 RFOU 0.6/1kV 5G 2.5mm² P1/P8 RFOU 0.6/1kV 4X 2.5/6mm² P1/P8 RFOU 0.6/1kV 5X 2.5/6mm² P1/P8 Sheath Colour BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK Stock item Yes Yes Yes Yes Yes Yes Yes Yes Yes EAN No. DNK 7021528000009 7021528000016 7021528000023 7021528000030 7021528000047 7021528000054 7021528000061 7021528000078 7021528000085 7021528000092 7021528000108 7021528000153 7021528000160 7021528000177 7021528000184 7021528000191 7021528000207 7021528000214 7021528000221 7021528000238 7021528000245 7021528000252 7021528000269 7021528000283 7021528000290 7021528000306 7021528000320 7021528000337 7021528000344 7021528000351 7021528000368 EL No. 1044206 1044207 1044208 1044210 1044211 1044213 1044214 1044215 1044220 1044240 1044260 1044305 1044307 1044312 1044319 1044327 1044337 1044221 1044241 1044261 1044355

www.drakaMOG.com

Subject to change without prior notice Page 35 of 96 2010-04-30

Part number 800037 800038 800039 800040 800041 800043 800044 800045 800046 800047 800048 800049 800050 800051 800052 800053 800054 800055 800056 800057 800058 800059 800060 800061 800062 800063 800064 800065 800066 800067 800068 800069 800070 800071 800072 800073 800074 800075 800076 800077 800078 800079 800081 800082 800083 800084 800085 800087 800088 800089 800090 800091 800092 800094 800095 800096 800097 800099 800100 800101 800105 800106 800108 800110

Description RFOU 0.6/1kV 7X 2.5/6mm² P1/P8 RFOU 0.6/1kV 12X 2.5/10 P1/P8 RFOU 0.6/1kV 19X 2.5/10 P1/P8 RFOU 0.6/1kV 27X 2.5/16 P1/P8 RFOU 0.6/1kV 37X 2.5/16 P1/P8 RFOU 0.6/1kV 4G 4mm² P1/P8 RFOU 0.6/1kV 7G 2.5mm² P1/P8 RFOU 0.6/1kV 2X 4/6mm² P1/P8 RFOU 0.6/1kV 3X 4/6mm² P1/P8 RFOU 0.6/1kV 4X 4/6mm² P1/P8 RFOU 0.6/1kV 5X 4/6mm² P1/P8 RFOU 0.6/1kV 3G 4mm² P1/P8 RFOU 0.6/1kV 5G 4mm² P1/P8 RFOU 0.6/1kV 2X 6/6mm² P1/P8 RFOU 0.6/1kV 3X 6/6mm² P1/P8 RFOU 0.6/1kV 4X 6/6mm² P1/P8 RFOU 0.6/1kV 4G 6mm² P1/P8 RFOU 0.6/1kV 3G 6mm² P1/P8 RFOU 0.6/1kV 5G 6mm² P1/P8 RFOU 0.6/1kV 2X 10/10mm² P1/P8 RFOU 0.6/1kV 3X 10/10mm² P1/P8 RFOU 0.6/1kV 4X 10/10mm² P1/P8 RFOU 0.6/1kV 3G 10mm² P1/P8 RFOU 0.6/1kV 5G 10mm² P1/P8 RFOU 0.6/1kV 4G 10mm² P1/P8 RFOU 0.6/1kV 2X 16/16mm² P1/P8 RFOU 0.6/1kV 3X 16/16mm² P1/P8 RFOU 0.6/1kV 4X 16/16mm² P1/P8 RFOU 0.6/1kV 4G 16mm² P1/P8 RFOU 0.6/1kV 5G 16mm² P1/P8 RFOU 0.6/1kV 3G 16mm² P1/P8 RFOU 0.6/1kV 2X 25/16mm² P1/P8 RFOU 0.6/1kV 3X 25/16mm² P1/P8 RFOU 0.6/1kV 4X 25/16mm² P1/P8 RFOU 0.6/1kV 4G 25mm² P1/P8 RFOU 0.6/1kV 3G 25mm² P1/P8 RFOU 0.6/1kV 5G 25mm² P1/P8 RFOU 0.6/1kV 2X 35/16mm² P1/P8 RFOU 0.6/1kV 3X 35/16mm² P1/P8 RFOU 0.6/1kV 4X 35/16mm² P1/P8 RFOU 0.6/1kV 4G 35mm² P1/P8 RFOU 0.6/1kV 5G 35mm² P1/P8 RFOU 0.6/1kV 2X 50/25mm² P1/P8 RFOU 0.6/1kV 3X 50/25mm² P1/P8 RFOU 0.6/1kV 4X 50/25mm² P1/P8 RFOU 0.6/1kV 4G 50mm² P1/P8 RFOU 0.6/1kV 5G 50mm² P1/P8 RFOU 0.6/1kV 2X 70/35mm² P1/P8 RFOU 0.6/1kV 3X 70/35mm² P1/P8 RFOU 0.6/1kV 4X 70/35mm² P1/P8 RFOU 0.6/1kV 4G 70mm² P1/P8 RFOU 0.6/1kV 5G 70mm² P1/P8 RFOU 0.6/1kV 5X 70/35mm² P1/P8 RFOU 0.6/1kV 2X 95/50mm² P1/P8 RFOU 0.6/1kV 3X 95/50mm² P1/P8 RFOU 0.6/1kV 4X 95/50mm² P1/P8 RFOU 0.6/1kV 4G 95mm² P1/P8 RFOU 0.6/1kV 5G 120mm² P1/P8 RFOU 0.6/1kV 2X 120/60 P1/P8 RFOU 0.6/1kV 3X 120/60 P1/P8 RFOU 0.6/1kV 4X 120/60 P1/P8 RFOU 0.6/1kV 4G 120mm² P1/P8 RFOU 0.6/1kV 4G 150mm² P1/P8 RFOU 0.6/1kV 4G 185mm² P1/P8

Sheath Colour BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK

Stock item Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes -

EAN No. DNK 7021528000375 7021528000382 7021528000399 7021528000405 7021528000412 7021528000436 7021528000443 7021528000450 7021528000467 7021528000474 7021528000481 7021528000498 7021528000504 7021528000511 7021528000528 7021528000535 7021528000542 7021528000559 7021528000566 7021528000573 7021528000580 7021528000597 7021528000603 7021528000610 7021528000627 7021528000634 7021528000641 7021528000658 7021528000665 7021528000672 7021528000689 7021528000696 7021528000702 7021528000719 7021528000726 7021528000733 7021528000740 7021528000757 7021528000764 7021528000771 7021528000788 7021528000795 7021528000818 7021528000825 7021528000832 7021528000849 7021528000856 7021528000870 7021528000887 7021528000894 7021528000900 7021528000917 7021528000924 7021528000948 7021528000955 7021528000962 7021528000979 7021528000993 7021528001006 7021528001013 7021528001051 7021528001068 7021528001082 7021528001105

EL No. 1044357 1044362 1044369 1044377 1044387 1044222 1044242 1044262 1044223 1044243 1044263 1044224 1044244 1044264 1044225 1044245 1044265 1044226 1044246 1044266 1044247 1044267 1044248 1044268 1044249 1044269 1044250 1044270 1044251 -

www.drakaMOG.com

Subject to change without prior notice Page 36 of 96 2010-04-30

Part number Description 800116 RFOU 0.6/1kV 5X 16/16mm² P1/P8 803906 RFOU 0.6/1kV 4X 240/120 P1/P8

Sheath Colour BLACK BLACK

Stock item -

EAN No. DNK 7021528001167 7021528039061

EL No. -

Electrical values power cables

Number of elements Cross Electrical Conductor Max. section Cross type 2 conductor core, section resistance at mm² braid, mm² 20°C, Ohm/km 16 2.5 STCC 1.16 25 4 STCC 0.734 35 6 STCC 0.529 50 6 STCC 0.391 70 10 STCC 0.27 95 10 STCC 0.195 120 10 STCC 0.154 150 10 STCC 0.126 185 10 STCC 0.1 240 16 STCC 0.0762 300 16 STCC 0.0607 1.5 4 STCC 12.2 1.5 STCC 12.2 1.5 STCC 12.2 1.5 4 STCC 12.2 1.5 6 STCC 12.2 1.5 6 STCC 12.2 1.5 6 STCC 12.2 1.5 10 STCC 12.2 1.5 10 STCC 12.2 1.5 10 STCC 12.2 1.5 16 STCC 12.2 1.5 STCC 12.2 1.5 STCC 12.2 2.5 4 STCC 7.56 2.5 STCC 7.56 2.5 6 STCC 7.56 2.5 STCC 7.56 2.5 STCC 7.56 2.5 6 STCC 7.56 2.5 6 STCC 7.56 2.5 6 STCC 7.56 2.5 10 STCC 7.56 2.5 10 STCC 7.56 2.5 16 STCC 7.56 2.5 16 STCC 7.56 4 STCC 4.7 2.5 STCC 7.56 4 6 STCC 4.7 4 6 STCC 4.7 4 6 STCC 4.7 4 6 STCC 4.7 4 STCC 4.7 4 STCC 4.7 6 6 STCC 3.11 6 6 STCC 3.11 6 6 STCC 3.11 6 STCC 3.11 6 STCC 3.11 6 STCC 3.11 10 10 STCC 1.84 10 10 STCC 1.84 10 10 STCC 1.84 10 STCC 1.84 10 STCC 1.84 Max. conductor resistance at 90°C, Ohm/km 1.48 0.936 0.675 0.499 0.344 0.249 0.196 0.161 0.128 0.0972 0.0774 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 9.64 9.64 9.64 9.64 9.64 9.64 9.64 9.64 9.64 9.64 9.64 9.64 5.99 9.64 5.99 5.99 5.99 5.99 5.99 5.99 3.97 3.97 3.97 3.97 3.97 3.97 2.35 2.35 2.35 2.35 2.35 Reactance at 50Hz, Ohm/km Reactance at 60Hz, Ohm/km Current rating IEC 60092-352 Table B.4, Ampere 96 127 157 196 242 293 339 389 444 522 601 20 20 16 16 16 13.5 12 10 8.5 7.5 7 16 12.5 26 26 21 21 21 21 17.5 15.5 13 11 10 9 28 16.5 34 28 28 23.5 34 28 44 36 36 36 44 36 61 50 50 61 50 Short circuit rating 1 second, Ampere 2240 3500 4900 7000 9800 13300 16800 21000 25900 33600 42000 210 210 210 210 210 210 210 210 210 210 210 210 210 350 350 350 350 350 350 350 350 350 350 350 350 560 350 560 560 560 560 560 560 840 840 840 840 840 840 1400 1400 1400 1400 1400

1 1 1 1 1 1 1 1 1 1 1 2 3G 4G 3 4 5 7 12 19 27 37 5G 7G 2 3G 3 4G 5G 4 5 7 12 19 27 37 4G 7G 2 3 4 5 3G 5G 2 3 4 4G 3G 5G 2 3 4 3G 5G

0.116 0.110 0.106 0.104 0.099 0.097 0.094 0.092 0.091 0.089 0.087 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.103 0.103 0.103 0.103 0.103 0.103 0.103 0.103 0.103 0.103 0.103 0.103 0.096 0.103 0.096 0.096 0.096 0.096 0.096 0.096 0.090 0.090 0.090 0.090 0.090 0.090 0.084 0.084 0.084 0.084 0.084

0.140 0.132 0.128 0.125 0.119 0.116 0.113 0.111 0.109 0.107 0.105 0.132 0.132 0.132 0.132 0.132 0.132 0.132 0.132 0.132 0.132 0.132 0.132 0.132 0.123 0.123 0.123 0.123 0.123 0.123 0.123 0.123 0.123 0.123 0.123 0.123 0.115 0.123 0.115 0.115 0.115 0.115 0.115 0.115 0.108 0.108 0.108 0.108 0.108 0.108 0.101 0.101 0.101 0.101 0.101

www.drakaMOG.com

Subject to change without prior notice Page 37 of 96 2010-04-30

Number of elements

4G 2 3 4 4G 5G 3G 2 3 4 4G 3G 5G 2 3 4 4G 5G 2 3 4 4G 5G 2 3 4 4G 5G 5 2 3 4 4G 5G 2 3 4 4G 4G 4G 5 4

Cross Electrical Conductor Max. section Cross type 2 conductor core, section resistance at mm² braid, mm² 20°C, Ohm/km 10 STCC 1.84 16 16 STCC 1.16 16 16 STCC 1.16 16 16 STCC 1.16 16 STCC 1.16 16 STCC 1.16 16 STCC 1.16 25 16 STCC 0.734 25 16 STCC 0.734 25 16 STCC 0.734 25 STCC 0.734 25 STCC 0.734 25 STCC 0.734 35 16 STCC 0.529 35 16 STCC 0.529 35 16 STCC 0.529 35 STCC 0.529 35 STCC 0.529 50 25 STCC 0.391 50 25 STCC 0.391 50 25 STCC 0.391 50 STCC 0.391 50 STCC 0.391 70 35 STCC 0.27 70 35 STCC 0.27 70 35 STCC 0.27 70 STCC 0.27 70 STCC 0.27 70 35 STCC 0.27 95 50 STCC 0.195 95 50 STCC 0.195 95 50 STCC 0.195 95 STCC 0.195 120 STCC 0.154 120 60 STCC 0.154 120 60 STCC 0.154 120 60 STCC 0.154 120 STCC 0.154 150 STCC 0.126 185 STCC 0.1 16 16 STCC 1.16 240 120 STCC 0.0762

Max. conductor resistance at 90°C, Ohm/km 2.35 1.48 1.48 1.48 1.48 1.48 1.48 0.936 0.936 0.936 0.936 0.936 0.936 0.675 0.675 0.675 0.675 0.675 0.499 0.499 0.499 0.499 0.499 0.344 0.344 0.344 0.344 0.344 0.344 0.249 0.249 0.249 0.249 0.196 0.196 0.196 0.196 0.196 0.161 0.128 1.48 0.0972

Reactance at 50Hz, Ohm/km

Reactance at 60Hz, Ohm/km

0.084 0.080 0.080 0.080 0.080 0.080 0.080 0.079 0.079 0.079 0.079 0.079 0.079 0.076 0.076 0.076 0.076 0.076 0.076 0.076 0.076 0.076 0.076 0.074 0.074 0.074 0.074 0.074 0.074 0.073 0.073 0.073 0.073 0.072 0.072 0.072 0.072 0.072 0.072 0.072 0.080 0.080

0.101 0.096 0.096 0.096 0.096 0.096 0.096 0.095 0.095 0.095 0.095 0.095 0.095 0.092 0.092 0.092 0.092 0.092 0.092 0.092 0.092 0.092 0.092 0.088 0.088 0.088 0.088 0.088 0.088 0.088 0.088 0.088 0.088 0.086 0.086 0.086 0.086 0.086 0.087 0.086 0.096 0.095

Current rating IEC 60092-352 Table B.4, Ampere 50 80 67 67 67 67 80 108 89 89 89 108 89 133 110 110 110 110 167 137 137 137 137 206 169 169 169 169 141.5 249 205 205 205 237 288 237 237 237 272 311 56 365

Short circuit rating 1 second, Ampere 1400 2240 2240 2240 2240 2240 2240 3500 3500 3500 3500 3500 3500 4900 4900 4900 4900 4900 7000 7000 7000 7000 7000 9800 9800 9800 9800 9800 9800 13300 13300 13300 13300 16800 16800 16800 16800 16800 21000 25900 2240 33600

www.drakaMOG.com

Subject to change without prior notice Page 38 of 96 2010-04-30

Ambient temperature correction factors

Ambient Temp °C Rating factor 35 1.10 40 1.05 45 1.00 50 0.94 55 0.88 60 0.82 65 0.74 70 0.67 75 0.58 80 0.47

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 39 of 96 2010-04-30

Halogen-free, mud resistant power cable RFOU 0,6/1kV, P1/P8, double braided Flame retardant halogen-free power cable. Mud resistant. Double braided.

RFOU 0,6/1(1,2)kV

EPR/EPR/TCWB/EVA

NEK TS 606 CodeP1/P8

Operating temperature Operating Voltage Standards applied Application Fixed installation for power,control and lighting in both EX- and safe areas, general purposes. For installation in areas exposed to MUD and drilling/cleaning fluids. Meets the MUD resistance requirement in NEK TS 606:2009. IEC 60092-353 IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 0,6/1(1,2)kV

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Lay up / Shielding Inner covering Tape over inner covering Armour/screen Tape over armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour R F Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 EP-rubber, IEC 60092-351 (EPR) Cores laid up in concentric layers Flame retardant and halogen-free thermoset compound PET tape + rubberized Polyamide tape Two layers of tinned copper wire braid (double braid) PET tape + rubberized Polyamide tape Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) E.g. "meter" "year" DRAKA 01 RFOU 0,6/1kV P1/P8 3 x 185/95 mm2 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel, Black

O

U

www.drakaMOG.com

Subject to change without prior notice Page 40 of 96 2010-04-30

Core identification power cables

Single core - Black Two cores - Blue - Brown Three cores - Brown - Black - Grey Four cores - Blue - Brown - Black - Grey Five cores - Blue - Brown - Black - Grey - Black Seven cores and above - White with black numbers Two cores + earth (3G) - Yellow/green - Blue - Brown Three cores + earth (4G) - Yellow/green - Brown - Black - Grey Four cores + earth (5G) - Yellow/green - Blue - Brown - Black - Grey G / X in cable description - G = One of the cores are yellow/green - X = no yellow/green core Core identification - to HD308S2 - and IEC 60446:2007-05

Range and dimensions

Electrical Cross Thickness Number Cross Conductor Insulation section Inner of section Diameter, Thickness, core, covering, elements mm mm braid, mm² mm mm² 3 3 4 4 3 185 150 150 185 240 95 70 70 95 120 17.70 15.9 15.9 17.7 20.15 2.0 1.8 1.8 2.0 2.2 1.6 1.6 2 2 1.8 Diameter inner covering, mm 50.5 ± 2.5 46 ± 2 51.5 ± 2.5 57 ± 2.5 57.5 ± 2.5 Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.5 0.4 0.4 0.5 0.6 127.2 90.5 90.5 113.1 142.5 Thickness Outer Sheath, mm 2.7 2.6 2.8 3 3 Diameter outer sheath, mm 59.5 ± 2.5 54 ± 2.5 60.5 ± 3 67 ± 3 68 ± 3 Weight of Cable Approx. (Kg/Km) 9230 7460 9400 11430 11800 Copper content Approx. (kg/km) 6283 4971 6373 7837 8046

Ordering information

Part number 800093 800102 800109 800111 800112 Description RFOU 0.6/1kV 3X 185/95 P1/P8 RFOU 0.6/1kV 3X 150/70 P1/P8 RFOU 0.6/1kV 4X 150/70 P1/P8 RFOU 0.6/1kV 4X 185/95 P1/P8 RFOU 0.6/1kV 3X 240/120 P1/P8 Sheath Colour BLACK BLACK BLACK BLACK BLACK Stock item EAN No. DNK 7021528000931 7021528001020 7021528001099 7021528001112 7021528001129 EL No. 1044252 -

Electrical values power cables

Number of elements Cross Electrical Conductor Max. section Cross type 2 conductor core, section resistance at mm² braid, mm² 20°C, Ohm/km 185 95 STCC 0.1 150 70 STCC 0.126 150 70 STCC 0.126 185 95 STCC 0.1 240 120 STCC 0.0762 Max. conductor resistance at 90°C, Ohm/km 0.128 0.161 0.161 0.161 0.0972 Reactance at 50Hz, Ohm/km Reactance at 60Hz, Ohm/km Current rating IEC 60092-352 Table B.4, Ampere 311 272 272 311 365 Short circuit rating 1 second, Ampere 25900 21000 21000 25900 33600

3 3 4 4 3

0.072 0.072 0.072 0.072 0.072

0.086 0.087 0.087 0.086 0.086

Ambient temperature correction factors

Ambient Temp °C Rating factor 35 1.10 40 1.05 45 1.00 50 0.94 55 0.88 60 0.82 65 0.74 70 0.67 75 0.58 80 0.47

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 41 of 96 2010-04-30

Halogen-free, mud resistant power cable RFOU 0,6/1kV, P1/P8, large single core cables Flame retardant halogen-free power cable. Mud resistant. Single core cable.

RFOU 0,6/1(1,2)kV

EPR/EPR/TCWB/EVA

NEK TS 606 CodeP1/P8

Operating temperature Operating Voltage Standards applied Application Fixed installation for power,control and lighting in both EX- and safe areas, general purposes. For installation in areas exposed to MUD and drilling/cleaning fluids. Meets the MUD resistance requirement in NEK TS 606:2009. IEC 60092-353/60502-1 IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 0,6/1(1,2)kV

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Lay up / Shielding Inner covering Tape over inner covering Armour/screen Tape over armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour R F Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 EP-rubber, IEC 60092-351 (EPR) Cores laid up in concentric layers Flame retardant and halogen-free thermoset compound PET tape Tinned annealed copper wire braid PET tape Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) E.g. "meter" "year" DRAKA 01 RFOU 0,6/1KV P1/P8 1 x 500/25 mm2 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel, Black

O

U

www.drakaMOG.com

Subject to change without prior notice Page 42 of 96 2010-04-30

Core identification power cables

Single core - Black Two cores - Blue - Brown Three cores - Brown - Black - Grey Four cores - Blue - Brown - Black - Grey Five cores - Blue - Brown - Black - Grey - Black Seven cores and above - White with black numbers Two cores + earth (3G) - Yellow/green - Blue - Brown Three cores + earth (4G) - Yellow/green - Brown - Black - Grey Four cores + earth (5G) - Yellow/green - Blue - Brown - Black - Grey G / X in cable description - G = One of the cores are yellow/green - X = no yellow/green core Core identification - to HD308S2 - and IEC 60446:2007-05

Range and dimensions

Electrical Cross Thickness Number Cross Conductor Insulation section Inner of section Diameter, Thickness, core, covering, elements mm mm braid, mm² mm mm² 1 1 1 400 500 630 25 25 25 26.00 29.0 32.80 2.4 2.4 2.4 1.4 1.4 1.4 Diameter inner covering, mm 34.5 ± 1.5 38 ± 1.5 41.5 ± 2 Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.4 0.4 0.4 31.7 36.2 40.7 Thickness Outer Sheath, mm 2.1 2.2 2.3 Diameter outer sheath, mm 40.5 ± 2 44 ± 2 48 ± 2 Weight of Cable Approx. (Kg/Km) 5070 6220 7650 Copper content Approx. (kg/km) 3970 4923 6195

Ordering information

Part number 800011 800012 800013 Description RFOU 0.6/1kV 1X 400/25 P1/P8 RFOU 0.6/1kV 1X 500/25 P1/P8 RFOU 0.6/1kV 1X 630/25 P1/P8 Sheath Colour BLACK BLACK BLACK Stock item EAN No. DNK 7021528000115 7021528000122 7021528000139 EL No. -

Electrical values power cables

Number of elements Cross Electrical Conductor Max. Max. Reactance section Cross type 2 conductor conductor at 50Hz, core, section resistance at resistance at Ohm/km mm² braid, mm² 20°C, 90°C, Ohm/km Ohm/km 400 500 630 25 25 25 STCC STCC STCC 0.0475 0.0369 0.0286 0.0606 0.0471 0.0365 0.087 0.085 0.083 Reactance at 60Hz, Ohm/km Current Short rating IEC circuit 60092-352 rating 1 Table B.4, second, Ampere Ampere 690 dc / 56000 670 ac 780 dc / 70000 720 ac 890 dc / 88200 780 ac

1 1 1

0.104 0.103 0.100

Ambient temperature correction factors

Ambient Temp °C Rating factor 35 1.10 40 1.05 45 1.00 50 0.94 55 0.88 60 0.82 65 0.74 70 0.67 75 0.58 80 0.47

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 43 of 96 2010-04-30

Halogen-free, mud resistant HV power cable, RFOU 6/10(12)kV, P3/P10 Flame retardant halogen-free medium voltage (MV) cable. Mud resistant

RFOU 6/10(12) kV

EPR/EPR/TCWB/EVA

NEK TS 606 CodeP3/P10

Operating temperature Operating Voltage Standards applied Application Fixed installation for medium voltage (MV) power in both EXand safe areas, general purposes. For installation in areas exposed to MUD and drilling/cleaning fluids. Meets the MUD resistance requirement in NEK TS 606:2009 IEC 60092-354 IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 6/10(12) kV

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Conductor screen semiconductive Insulation Insulation screen semicoductive Lay up / Shielding Inner covering Tape over inner covering Armour/screen Tape over armour/screen Outer sheath F O U Tinned stranded and compressed copper (STCC), IEC 60228 class 2 Semiconductive layer (EP-rubber) R EP-rubber, IEC 60092-351 (EPR) Semiconductive layer (EP-rubber) Cores are laid up together. Cores are identified by Brown, Black or Grey threads under and over the metallic screen on each conductor. Flame retardant and halogen-free thermoset compound PET tape Tinned annealed copper wire braid PET tape Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359)

Marking text Manufacturing unit Outer sheath colour

E.g. "meter" "year" DRAKA 04 RFOU 6/10(12)KV P3/P10 3 x 95/50 mm2 IEC 60332-3-22 DRAKA 04 = Draka Industrial Cable, Germany Red

www.drakaMOG.com

Subject to change without prior notice Page 44 of 96 2010-04-30

Range and dimensions

Electrical Cross Thickness Number Cross Conductor Insulation section Inner of Diameter, Thickness, section core, covering, elements braid, mm mm mm² mm mm² 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 16 25 35 50 70 95 120 150 185 240 300 400 500 630 16 25 35 50 70 95 120 150 185 240 300 11 11 11 11 16 16 20 19 18 21 29 35 40 40 32 31 35 31 35 50 60 75 45 53 55 5.2 6.5 7.4 8.8 10.3 12.1 13.6 15.1 16.8 19.1 21.5 24.5 27.5 32.3 5.2 6.5 7.4 8.8 10.3 12.1 13.6 15.1 16.8 19.1 21.5 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 1.0 1.0 1.0 1.0 1.0 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.4 1.4 1.4 1.4 1.4 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 Diameter inner covering, mm Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 12.7 12.7 12.7 12.7 17.8 20.4 22.9 20.4 20.4 22.9 30.5 40.7 49.8 49.8 36.2 31 35 31 40.7 54.3 70.7 86.5 56.5 63.6 70.7 Thickness Outer Sheath, mm 1.6 1.7 1.7 1.9 1.9 2.0 2.0 2.0 2.1 2.1 2.2 2.3 2.5 2.7 2.4 2.4 2.5 2.8 2.8 2.8 3 3.2 3.3 3.5 3.7 Diameter outer sheath, mm 24.0 ± 1,5 25.0 ± 1,5 Weight of Cable Approx. (Kg/Km) 900 1100 Copper content Approx. (kg/km) 420 516 611 780 971 1251 1506 1793 2138 2702 3395 4536 5782 7016 1145 1465 1573 2124 2880 3975 4650 5634 6511 8609 10725

18.5 ±1.0 0.3 20,0 ±1.0 0.3 21.0 ± 1.5 22.0 ± 1.0 0.3 0.3

26.0± 1.5 1200 28.0 ± 1.5 30.0 ± 2.0 32.0 ± 2.0 34.0 ± 2.0 35.0 ± 2.0 36.5 ± 2.0 1450 1700 2100 2350 2600 3100

23.5 ±1.5 0.3 25.5 ±1.5 0.3 27.5 ± 1.5 0.3

28.5 ±1.5 0.3 30.5 ±1.5 0.3 33.0 ± 1.5 35 ±1.5 36 ±1.5 41.5 ± 2.0 46.5 ± 2.0 39.0 ± 1.5 42.0 ± 1.5 43.5 ± 2.0 47.0 ± 2.0 50.0 ± 2.0 54.0 ± 2.0 57.5 ± 2.0 60 ± 2 64.5 ± 2.5 69.5 ± 2.5 74.5 ± 3.0 0.3 0.3 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.5 0.6 0.5 0.5 0.5

39.0± 2.0 3800 41.5 ± 2.5 45.5 ± 2.5 49.5 ± 2.5 54.5 ± 3.0 46.0 ± 2.5 49.5 ± 2.5 4600 5900 7350 8750 3300 3800

51.5± 3.0 4300 55 ± 3 58.5 ± 3 5000 6000

62.5± 3.0 7500 66.5 ± 3.0 70.5 ± 3 74.0 ± 3.5 8350 9800 11300

79.5± 3.5 13300 85.0± 4.0 16300

Ordering information

Part number 804000 804001 804002 804003 804004 804005 804006 804007 804008 804009 804010 804011 Description RFOU 6/10KV 1X 16/11mm² P3/P10 RFOU 6/10KV 1X 25/11mm² P3/P10 RFOU 6/10KV 1X 35/11mm² P3/P10 RFOU 6/10KV 1X 50/11mm² P3/P10 RFOU 6/10KV 1X 70/16mm² P3/P10 RFOU 6/10KV 1X 95/16mm² P3/P10 RFOU 6/10KV 1X 120/20mm² P3/P10 RFOU 6/10KV 1X 150/19mm² P3/P10 RFOU 6/10KV 1X185/18mm² P3/P10 RFOU 6/10KV 1X 240/21mm² P3/P10 RFOU 6/10KV 1X 300/29mm² P3/P10 RFOU 6/10KV 1X 400/35mm² P3/P10 Sheath Colour RED RED RED RED RED RED RED RED RED RED RED RED Stock item EAN No. DNK 7021528040005 7021528040012 7021528040029 7021528040036 7021528040043 7021528040050 7021528040067 7021528040074 7021528040081 7021528040098 7021528040104 7021528040111 EL No. 1061020 1061021 1061000 1061001 1061002 1061003 1061004 1061005 1061006 1061007 1061008 1061022

www.drakaMOG.com

Subject to change without prior notice Page 45 of 96 2010-04-30

Part number 804012 804013 804020 804021 804022 804023 804024 804025 804026 804027 804028 804029 804030

Description RFOU 6/10KV 1X 500/40mm² P3/P10 RFOU 6/10KV 1X 630/40mm² P3/P10 RFOU 6/10KV 3X 16/32mm² P3/P10 RFOU 6/10KV 3X 25/31mm² P3/P10 RFOU 6/10KV 3X 35/35mm² P3/P10 RFOU 6/10KV 3X 50/31mm² P3/P10 RFOU 6/10KV 3X 70/35mm² P3/P10 RFOU 6/10KV 3X 95/50mm² P3/P10 RFOU 6/10KV 3X 120/60mm² P3/P10 RFOU 6/10KV 3X 150/75mm² P3/P10 RFOU 6/10KV 3X 185/45mm² P3/P10 RFOU 6/10KV 3X 240/53mm² P3/P10 RFOU 6/10KV 3X 300/55mm² P3/P10

Sheath Colour RED RED RED RED RED RED RED RED RED RED RED RED RED

Stock item -

EAN No. DNK 7021528040128 7021528040135 7021528040203 7021528040210 7021528040227 7021528040234 7021528040241 7021528040258 7021528040265 7021528040272 7021528040289 7021528040296 7021528040302

EL No. 1061023 1061024 1061009 1061010 1061011 1061012 1061013 1061014 1061015 1061016 1061017 1061018 1061019

Electrical values power cables

Number Cross Electrical Conductor Max. of section Cross type 2 conductor elements core, section resistance mm² braid, at 20°C, mm² Ohm/km Max. Reactance Reactance Capacitans conductor at 50Hz, at 60Hz, per phase, resistance Ohm/km Ohm/km nF/km at 90°C, Ohm/km Current rating IEC 60092352 Table B.4, Ampere 96 127 157 196 242 293 339 389 444 522 601 690 dc / 670 ac 780 dc / 720 ac 890 dc / 780 ac 67 89 110 137 169 205 237 272 311 365 421 Short circuit rating 1 second, Ampere

1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3

16 25 35 50 70 95 120 150 185 240 300 400 500 630 16 25 35 50 70 95 120 150 185 240 300

11 11 11 11 16 16 20 19 18 21 29 35 40 40 32 31 35 31 35 50 60 75 45 53 55

STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC

1.16 0.734 0.529 0.391 0.270 0.195 0.154 0.126 0.100 0.0762 0.0607 0.0475 0.0369 0.0286 1.16 0.734 0.529 0.391 0.270 0.195 0.154 0.126 0.100 0.0762 0.0607

1.48 0.936 0.675 0.499 0.344 0.249 0.196 0.161 0.128 0.0972 0.0774 0.0606 0.0471 0.0365 1.48 0.936 0.675 0.499 0.344 0.249 0.196 0.161 0.128 0.0972 0.0774

0.154 0.144 0.138 0.132 0.125 0.119 0.116 0.111 0.108 0.104 0.104 0.090 0.097 0.092 0.119 0.119 0.114 0.108 0.103 0.098 0.095 0.092 0.092 0.087 0.084

0.185 0.173 0.166 0.158 0.150 0.142 0.139 0.133 0.130 0.125 0.124 0.118 0.117 0.110 0.143 0.143 0.137 0.130 0.124 0.118 0.114 0.111 0.111 0.104 0.101

220 250 270 300 340 380 410 450 480 540 590 660 720 840 220 250 270 300 340 380 410 450 480 540 590

2240 3500 4900 7000 9800 13300 16800 21000 25900 33600 42000 56000 70000 88200 2240 3500 4900 7000 9800 13300 16800 21000 25900 33600 42000

Ambient temperature correction factors

Ambient Temp °C Rating factor 35 1.10 40 1.05 45 1.00 50 0.94 55 0.88 60 0.82 65 0.74 70 0.67 75 0.58 80 0.47

Installation recommendations

Minimum Bending Radius during Installation 15 x D Minimum Bending Radius Fixed Installed 9xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 46 of 96 2010-04-30

www.drakaMOG.com

Subject to change without prior notice Page 47 of 96 2010-04-30

Halogen-free, mud resistant HV power cable, RFOU 12/20(24)kV, P19/P21 Flame retardant halogen-free medium voltage (MV) cable. Mud resistant

RFOU 12/20(24) kV

EPR/EPR/TCWB/EVA

NEK TS 606 CodeP19/P21

Operating temperature Operating Voltage Standards applied Application IEC 60092-354 IEC 60228 class 2 Fixed installation for medium voltage (MV) power in both EX- IEC 60092-351 and safe areas, general purposes. For installation in areas IEC 60092-359 exposed to MUD and drilling/cleaning fluids. Meets the MUD IEC 60332-1 resistance requirement in NEK TS 606:2009 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 12/20(24) kV

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Conductor screen semiconductive Insulation Insulation screen semicoductive Lay up / Shielding Inner covering Tape over inner covering Armour/screen Tape over armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour F Tinned stranded and compressed copper (STCC), IEC 60228 class 2 Semiconductive layer (EP-rubber) R EP-rubber, IEC 60092-351 (EPR) Semiconductive layer (EP-rubber) Cores are laid up together. Cores are identified by Brown, Black or Grey threads under and over the metallic screen on each conductor. Flame retardant and halogen-free thermoset compound PET tape Tinned annealed copper wire braid PET tape Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) E.g. "meter" "year" DRAKA 04 RFOU 12/20(24)KV P19/P21 3 x 95/50 mm2 IEC 60332-3-22 DRAKA 04 = Draka Industrial Cable, Germany Red

O

U

www.drakaMOG.com

Subject to change without prior notice Page 48 of 96 2010-04-30

Range and dimensions

Electrical Cross Number Cross section of section core, elements braid, mm² mm² 1 16 13 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 25 35 50 70 95 120 150 185 240 300 16 25 35 50 70 95 120 150 185 240 13 13 15 13 17 15 15 18 23 28 31 35 35 35 35 50 60 75 45 55 Thickness Conductor Insulation Inner Diameter, Thickness, covering, mm mm mm 5.2 6.5 7.4 8.8 10.3 12.1 13.6 15.1 16.8 19.1 21.5 5.2 6.5 7.4 8.8 10.3 12.1 13.6 15.1 16.8 19.1 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 1.0 1.0 1.2 1.2 1.2 1.2 1.3 1.3 1.4 1.4 1.4 1.4 1.4 1.4 1.8 1.8 2.0 2.0 2.0 2.0 2.2 Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 22.5 ±1.0 0.3 15.3 Diameter inner covering, mm 24 ±1.0 25 ±1.5 26.5 ±1.5 28 ± 1.5 30 ±1.5 31.5 ±1.5 33 ±1.5 35 ±1.5 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 15.3 15.3 17.8 15.3 20.4 17.8 17.8 20.4 25.4 30.5 36.2 40.7 40.7 40.7 40.7 56.5 70.7 91.9 56.5 70.7 Thickness Outer Sheath, mm 1.6 1.7 1.8 2.0 2.1 2.1 2.1 2.2 2.2 2.4 2.6 2.6 2.7 2.8 3.0 3.1 3.3 3.4 3.5 3.7 3.9 Diameter outer sheath, mm 28 ± 1.5 29.5 ± 1.5 31 ± 2 32.5 ± 2 34 ± 2.0 36 ± 2 38 ± 2 40 ± 2.5 41.5 ± 2.5 45.0 ± 2.5 47.0 ± 3.0 55.5 ± 3.0 58.5 ± 3.0 61 ± 3.0 65.5 ± 3.5 68.5 ± 3.5 73.5 ± 4.0 77 ± 4.0 80.0 ± 4.5 85.0 ± 4.5 90.0 ± 4.5 Weight of Cable Approx. (Kg/Km) 1200 1300 1450 1700 2000 2400 2650 3000 3500 4350 5200 9300 4950 5500 6500 7500 9300 10250 11700 12950 15900 Copper content Approx. (kg/km) 495 561 671 811 1001 1210 1491 1835 2201 2915 3640 4112 1558 1885 2276 2979 4112 4761 5822 6615 8797

37.5 ±1.5 0.3 41.0 ±2.0 0.3 48 ± 2.0 51 ± 2.0 53 ± 2.0 57.0 ± 2.0 60 ± 2.5 64.5 ± 3.0 67.5 ± 3.0 71.0 ± 3.0 75.0 ± 3.5 79.5 ± 3.5 0.4 0.4 0.4 0.4 0.4 0.5 0.5 0.5 0.5 0.5

Ordering information

Part number 804100 804101 804102 804103 804104 804105 804106 804107 804108 804109 804110 804120 804121 804122 804123 804124 804125 804126 804127 804128 804129 Description RFOU 12/20KV 1X 16/13mm² P19/P21 RFOU 12/20KV 1X 25/13mm² P19/P21 RFOU 12/20KV 1X 35/13mm² P19/P21 RFOU 12/20KV 1X 50/15mm² P19/P21 RFOU 12/20KV 1X 70/13mm² P19/P21 RFOU 12/20KV 1X 95/17mm² P19/P21 RFOU 12/20KV 1X120/15mm² P19/P21 RFOU 12/20KV 1X150/15mm² P19/P21 RFOU 12/20KV 1X185/18mm² P19/P21 RFOU 12/20KV 1X240/23mm² P19/P21 RFOU 12/20KV 1X300/28mm² P19/P21 RFOU 12/20KV 3X 16/31mm² P19/P21 RFOU 12/20KV 3X 25/35mm² P19/P21 RFOU 12/20KV 3X 35/35mm² P19/P21 RFOU 12/20KV 3X 50/35mm² P19/P21 RFOU 12/20KV 3X 70/35mm² P19/P21 RFOU 12/20KV 3X 95/50mm² P19/P21 RFOU 12/20KV 3X120/60mm² P19/P21 RFOU 12/20KV 3X150/75mm² P19/P21 RFOU 12/20kV 3X 185/45mm² P19/P21 RFOU 12/20KV 3X240/55mm² P19/P21 Sheath Colour RED RED RED RED RED RED RED RED RED RED RED RED RED RED RED RED RED RED RED RED RED Stock item EAN No. DNK 7021528041002 7021528041019 7021528041026 7021528041033 7021528041040 7021528041057 7021528041064 7021528041071 7021528041088 7021528041095 7021528041101 7021528041200 7021528041217 7021528041224 7021528041231 7021528041248 7021528041255 7021528041262 7021528041279 7021528041286 7021528041293 EL No. 1061035 1061038 -

www.drakaMOG.com

Subject to change without prior notice Page 49 of 96 2010-04-30

Electrical values power cables

Number Cross Electrical Conductor Max. of section Cross type 2 conductor elements core, section resistance mm² braid, at 20°C, mm² Ohm/km Max. Reactance Reactance Capacitans conductor at 50Hz, at 60Hz, per phase, resistance Ohm/km Ohm/km nF/km at 90°C, Ohm/km Current rating IEC 60092352 Table B.4, Ampere 96 127 157 196 242 293 339 389 444 522 601 67 89 110 137 169 205 237 272 311 365 Short circuit rating 1 second, Ampere

1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3

16 25 35 50 70 95 120 150 185 240 300 16 25 35 50 70 95 120 150 185 240

13 13 13 15 13 17 15 15 18 23 28 31 35 35 35 35 50 60 75 45 55

STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC STCC

1.16 0.734 0.529 0.391 0.270 0.195 0.154 0.126 0.100 0.0762 0.0607 1.16 0.734 0.529 0.391 0.270 0.195 0.154 0.126 0.100 0.0762

1.479 0.936 0.675 0.499 0.344 0.249 0.196 0.161 0.128 0.0972 0.0774 1.48 0.936 0.675 0.499 0.344 0.249 0.196 0.161 0.128 0.0972

0.164 0.154 0.149 0.140 0.133 0.127 0.124 0.119 0.116 0.112 0.108 0.143 0.133 0.128 0.121 0.115 0.109 0.105 0.102 0.099 0.095

0.197 0.185 0.178 0.169 0.160 0.152 0.149 0.142 0.139 0.134 0.130 0.172 0.160 0.153 0.145 0.135 0.131 0.126 0.122 0.118 0.114

170 190 200 220 250 270 300 320 340 380 410 170 190 200 220 250 270 300 320 340 380

2240 3500 4900 7000 9800 13300 16800 21000 25900 33600 42000 2240 3500 4900 7000 9800 13300 16800 21000 25900 33600

Ambient temperature correction factors

Ambient Temp °C Rating factor 35 1.10 40 1.05 45 1.00 50 0.94 55 0.88 60 0.82 65 0.74 70 0.67 75 0.58 80 0.47

Installation recommendations

Minimum Bending Radius during Installation 15 x D Minimum Bending Radius Fixed Installed 9xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 50 of 96 2010-04-30

Halogen-free, mud resistant, fire resistant power cable, BFOU 0,6/1kV, P5/P12 Fire resistant, flame retardant halogenfree power cable. Mud resistant

BFOU 0,6/1(1,2)kV

MGT/EPR/EPR/TCWB/EVA

NEK TS 606 CodeP5/P12

Operating temperature Operating Voltage Standards applied Application IEC 60092-353 IEC 60228 class 2 Fixed installation for power, control and lighting in both EXIEC 60092-351 and safe areas, emergency and critical systems where IEC 60092-359 requirement for fire resistance exists. For installation in IEC 60332-1 areas exposed to MUD and drilling/cleaning fluids. Meets the IEC 60332-3-22 MUD resistance requirement in NEK TS 606:2009. IEC 60331-1, -2, -21 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 0,6/1(1,2)kV

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Fire Resistant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Lay up / Shielding Inner covering Tape over inner covering Armour/screen Tape over armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour B F Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 Mica-tape + EP-rubber, IEC 60092-351 (EPR) Cores laid up in concentric layers Flame retardant and halogen-free thermoplastic compound PET tape Tinned annealed copper wire braid PET tape Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) E.g. "meter" "year" DRAKA 01 BFOU 0,6/1kV P5/P12 3 x 25/16 mm2 FLEX FLAME IEC 60331-21 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel Black

O

U

www.drakaMOG.com

Subject to change without prior notice Page 51 of 96 2010-04-30

Core identification power cables

Single core - Black Two cores - Blue - Brown Three cores - Brown - Black - Grey Four cores - Blue - Brown - Black - Grey Five cores - Blue - Brown - Black - Grey - Black Seven cores and above - White with black numbers Two cores + earth (3G) - Yellow/green - Blue - Brown Three cores + earth (4G) - Yellow/green - Brown - Black - Grey Four cores + earth (5G) - Yellow/green - Blue - Brown - Black - Grey G / X in cable description - G = One of the cores are yellow/green - X = no yellow/green core Core identification - to HD308S2 - and IEC 60446:2007-05

Range and dimensions

Electrical Cross Number Cross section of section core, elements braid, mm² mm² 1 16 4 1 1 1 1 1 1 1 1 1 2 3G 4G 3 4 5 7 12 19 27 37 5G 32 7G 2 3G 3 4G 4 8G 7 25 50 70 95 120 150 185 240 300 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 6 10 10 10 10 10 10 16 16 4 6 6 6 6 10 10 16 16 16 6 6 6 6 Thickness Conductor Insulation Inner Diameter, Thickness, covering, mm mm mm 5.15 6.45 9.0 10.85 12.60 14.20 15.90 17.70 20.15 22.60 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.0 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.1 1.1 1.1 1.1 1.1 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.2 1.2 1.2 1.4 1.1 1.4 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 Diameter inner covering, mm 10 ± 0.8 11.5 ± 0.8 15 ± 0.8 16.5 ± 0.8 18.5 ± 0.8 20.5 ± 1 23 ± 1 25 ± 1 28 ± 1 30.5 ± 1.5 10 ± 0.8 10.5 ± 0.8 11.5 ± 0.8 10.5 ± 0.8 11.5 ± 0.8 13 ± 0.8 13 ± 0.8 17 ± 0.8 20.5 ± 1 24 ± 1 27.5 ± 1 13 ± 0.8 26.5 ± 1 14 ± 0.8 11 ± 0.8 11.5 ± 0.8 11.5 ± 0.8 12.5 ± 0.8 12.5 ± 0.8 19.5 ± 0.8 14 ± 0.8 Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.2 5.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 8.5 12.7 12.7 15.3 15.3 17.8 17.8 20.4 22.9 5.3 8.5 10.2 8.5 10.2 10.2 11.9 15.3 17.8 20.4 22.9 10.2 22.9 11.9 8.5 10.2 10.2 10.2 10.2 15.3 11.9 Thickness Outer Sheath, mm 1.2 1.3 1.4 1.4 1.5 1.6 1.7 1.7 1.8 1.9 1.2 1.3 1.3 1.3 1.3 1.4 1.4 1.6 1.7 1.9 2 1.4 2 1.4 1.3 1.3 1.3 1.3 1.3 1.5 1.4 Diameter outer sheath, mm 13 ± 0.8 15.5 ± 0.8 18.5 ± 0.8 20.5 ± 1 23 ± 1 25 ± 1 27.5 ± 1 29.5 ± 1 33 ± 1.5 36 ± 1.5 13 ± 0.8 14.5 ± 0.8 15.5 ± 0.8 14.5 ± 0.8 15.5 ± 0.8 16.5 ± 0.8 17 ± 0.8 21.5 ± 1 25 ± 1 29 ± 1 32.5 ± 1.5 16.5 ± 0.8 31.5 ± 1.5 18 ± 0.8 14.5 ± 0.8 15 ± 0.8 15 ± 0.8 16.5 ± 0.8 16.5 ± 0.8 23.5 ± 1 18 ± 0.8 Weight of Cable Approx. (Kg/Km) 370 530 880 1120 1430 1740 2130 2510 3160 3890 285 360 420 360 420 480 540 810 1100 1450 1880 480 1740 630 370 420 420 480 480 790 630 Copper content Approx. (kg/km) 198 314 559 756 996 1231 1535 1838 2365 2984 80 125 156 125 156 170 215 318 440 577 741 170 671 277 129 169 169 192 192 333 277

www.drakaMOG.com

Subject to change without prior notice Page 52 of 96 2010-04-30

Electrical Cross Number Cross section of section core, elements braid, mm² mm² 12 2.5 10 19 2.5 16 27 2.5 16 37 5G 4G 5G 2 3 4 3G 2 3 4 3G 4G 5G 2 3 4 3G 4G 5G 2 3 4 3G 5G 4G 2 3 4 4 4G 5G 3G 2 3 4 3G 4G 5G 2 3 4 5G 4G 2 3 4 4G 2.5 2.5 4 4 4 4 4 4 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16 16 16 25 25 25 25 25 25 25 35 35 35 35 35 35 50 50 50 50 50 70 70 70 70 25 6 6 6 6 6 6 10 10 10 16 16 16 16 16 16 16 16 16 25 25 25 35 35 35 -

Thickness Conductor Insulation Inner Diameter, Thickness, covering, mm mm mm 2.0 2.0 2.0 2.0 2.0 2.55 2.55 2.55 2.55 2.55 2.55 3.15 3.15 3.15 3.15 3.15 3.15 4.05 4.05 4.05 4.05 4.05 4.05 5.15 5.15 5.15 5.15 5.15 5.15 6.45 6.45 6.45 6.45 6.45 6.45 6.45 7.65 7.65 7.65 7.65 7.65 7.65 9.0 9.0 9.0 9.0 9.0 10.85 10.85 10.85 10.85 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.2 1.2 1.4 1.4 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.2 1.1 1.1 1.2 1.1 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.4 1.4 1.2 1.4 1.4 1.4 1.6 1.4 1.4 1.4

Diameter inner covering, mm 19 ± 0.8 22.5 ± 1 27 ± 1 30.5 ± 1.5 14 ± 0.8 14 ± 0.8 15.5 ± 0.8 12 ± 0.8 13 ± 0.8 14 ± 0.8 13 ± 0.8 13 ± 0.8 14 ± 0.8 15.5 ± 0.8 14 ± 0.8 15.5 ± 0.8 17 ± 0.8 15 ± 0.8 16 ± 0.8 18 ± 0.8 16 ± 0.8 18 ± 0.8 20 ± 1 17.5 ± 0.8 18.5 ± 0.8 20.5 ± 1 18.5 ± 0.8 23 ± 1 20.5 ± 1 21 ± 1 22.5 ± 1 25 ± 1 25 ± 1 27.5 ± 1 22.5 ± 1 23.5 ± 1 25 ± 1 28 ± 1 25 ± 1 28 ± 1 31 ± 1.5 27.5 ± 1 29 ± 1 32.5 ± 1.5 36 ± 1.5 32.5 ± 1.5 31.5 ± 1.5 33.5 ± 1.5 37 ± 1.5 37 ± 1.5

Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.3 17.8 0.3 20.4 0.3 22.9 0.4 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.5 0.4 0.4 0.3 0.3 0.3 0.4 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.4 0.3 0.6 0.5 0.4 0.4 36.2 11.9 11.9 11.9 10.2 10.2 11.9 10.2 10.2 11.9 11.9 11.9 11.9 13.6 11.9 11.9 13.6 11.9 13.6 15.3 21.2 22.6 22.6 15.3 17.8 15.3 22.6 20.4 20.4 17.8 20.4 17.8 20.4 20.4 20.4 17.8 20.4 22.9 31.7 31.7 31.7 36.2 22.9 50.9 49.5 45.2 36.2

Thickness Outer Sheath, mm 1.6 1.8 2 2.2 1.4 1.4 1.4 1.3 1.3 1.4 1.3 1.4 1.4 1.4 1.4 1.4 1.5 1.4 1.5 1.5 1.5 1.5 1.6 1.5 1.5 1.6 1.5 1.7 1.6 1.6 1.7 1.8 1.8 1.8 1.7 1.7 1.8 1.9 1.8 1.9 2 1.8 1.9 2 2.2 2 2 2 2.2 2.2

Diameter outer sheath, mm 23 ± 1 27 ± 1 32 ± 1.5 36.5 ± 1.5 18 ± 0.8 18 ± 0.8 19.5 ± 0.8 15.5 ± 0.8 16.5 ± 0.8 18 ± 0.8 16.5 ± 0.8 17 ± 0.8 18 ± 0.8 19.5 ± 0.8 18 ± 0.8 19.5 ± 0.8 21.5 ± 1 19 ± 0.8 20 ± 1 22 ± 1 20 ± 1 22 ± 1 24 ± 1 22 ± 1 23 ± 1 25.5 ± 1 22.5 ± 1 27.5 ± 1 25 ± 1 26 ± 1 27 ± 1 29.5 ± 1 29.5 ± 1 32 ± 1.5 27 ± 1 28 ± 1 30 ± 1.5 33 ± 1.5 30 ± 1.5 33 ± 1.5 36.5 ± 1.5 32.5 ± 1.5 34.5 ± 1.5 38 ± 1.5 42 ± 2 38 ± 1.5 38 ± 1.5 39 ± 1.5 43 ± 2 43 ± 2

Weight of Cable Approx. (Kg/Km) 990 1370 1860 2510 570 610 700 450 510 610 510 530 620 720 620 720 880 680 800 960 800 960 1170 990 1170 1420 1090 1610 1330 1370 1600 1960 1960 1930 2290 1580 1640 2010 2470 1980 2470 3010 2270 2730 3380 4120 3290 3190 3770 4610 4520

Copper content Approx. (kg/km) 450 636 844 1204 231 263 300 173 210 263 210 209 281 335 281 335 406 299 390 496 388 496 603 501 660 806 588 905 734 685 894 1125 1125 1100 1356 869 828 1142 1456 1117 1456 1795 1181 1617 2052 2531 1968 1783 2386 2977 2888

www.drakaMOG.com

Subject to change without prior notice Page 53 of 96 2010-04-30

Electrical Cross Number Cross section of section core, elements braid, mm² mm² 5G 70 3 95 50 4 95 50 4G 95 5G 95 3 120 60 4 4G 4G 4G 4G 4 3 5 120 120 150 150 185 240 185 16 60 70 95 16

Thickness Conductor Insulation Inner Diameter, Thickness, covering, mm mm mm 10.85 12.60 12.60 12.60 12.60 14.20 14.20 14.20 15.90 17.70 16.8 5.15 1.4 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.8 1.8 2.0 2.2 2.0 1.0 1.4 1.4 1.6 1.6 1.6 1.4 1.6 1.6 1.6 1.8 2.0 1.2

Diameter inner covering, mm 41 ± 2 38 ± 1.5 42.5 ± 2 42.5 ± 2 47 ± 2 41.5 ± 2 46.5 ± 2 46.5 ± 2 52 ± 2.5 57.5 ± 2.5 50.5 ± 2 23 ± 1

Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.4 40.7 0.6 61.1 0.5 63.6 0.4 40.7 0.4 45.2 0.6 71.3 0.6 0.4 0.5 0.5 0.6 0.3 71.3 45.2 49.5 56.5 112 20.4

Thickness Outer Sheath, mm 2.3 2.2 2.4 2.4 2.6 2.4 2.5 2.5 2.7 2.9 3.0 1.7

Diameter outer sheath, mm 47 ± 2 44.5 ± 2 49.5 ± 2 49 ± 2 54 ± 2.5 48.5 ± 2 53.5 ± 2.5 53 ± 2.5 59.5 ± 2.5 65.5 ± 3 60 ± 3 27.5 ± 1

Weight of Cable Approx. (Kg/Km) 5450 4940 6140 5900 7140 6030 7470 7180 8910 8800 10830 15300 9200 1640

Copper content Approx. (kg/km) 3566 3169 4022 3794 4688 3976 5060 4781 5943 5801 7251 9901 6610 930

Ordering information

Part number 800200 800201 800203 800204 800205 800206 800207 800208 800209 800210 800215 800216 800217 800218 800219 800220 800221 800222 800223 800224 800225 800226 800227 800228 800229 800230 800232 800233 800235 800236 800237 800238 800239 800240 800241 800242 800243 800244 800245 800246 800247 800250 Description BFOU 0.6/1kV 1X 16/4mm² P5/P12 BFOU 0.6/1kV 1X 25/6mm² P5/P12 BFOU 0.6/1kV 1X 50/10 P5/P12 BFOU 0.6/1kV 1X 70/10 P5/P12 BFOU 0.6/1kV 1X 95/10 P5/P12 BFOU 0.6/1kV 1X 120/10 P5/P12 BFOU 0.6/1kV 1X 150/10 P5/P12 BFOU 0.6/1kV 1X 185/10 P5/P12 BFOU 0.6/1kV 1X 240/16 P5/P12 BFOU 0.6/1kV 1X 300/16 P5/P12 BFOU 0.6/1kV 2X 1.5/4 P5/P12 BFOU 0.6/1kV 3G 1.5mm² P5/P12 BFOU 0.6/1kV 4G 1.5mm² P5/P12 BFOU 0.6/1kV 3X 1.5/6 P5/P12 BFOU 0.6/1kV 4X 1.5/6 P5/P12 BFOU 0.6/1kV 5X 1.5/6 P5/P12 BFOU 0.6/1kV 7X 1.5/6 P5/P12 BFOU 0.6/1kV 12X 1.5/10 P5/P12 BFOU 0.6/1kV 19X 1.5/10 P5/P12 BFOU 0.6/1kV 27X 1.5/16 P5/P12 BFOU 0.6/1kV 37X 1.5/16 P5/P12 BFOU 0.6/1kV 5G 1.5mm² P5/P12 BFOU 0.6/1kV 32X 1.5/16 P5/P12 BFOU 0.6/1kV 7G 2.5mm² P5/P12 BFOU 0.6/1kV 2X 2.5/6 P5/P12 BFOU 0.6/1kV 3G 2.5mm² P5/P12 BFOU 0.6/1kV 3X 2.5/6 P5/P12 BFOU 0.6/1kV 4G 2.5mm² P5/P12 BFOU 0.6/1kV 4X 2.5/6 P5/P12 BFOU 0.6/1kV 8G 2.5mm² P5/P12 BFOU 0.6/1kV 7X 2.5/6 P5/P12 BFOU 0.6/1kV 12X 2.5/10 P5/P12 BFOU 0.6/1kV 19X 2.5/16 P5/P12 BFOU 0.6/1kV 27X 2.5/16 P5/P12 BFOU 0.6/1kV 37X 2.5/25 P5/P12 BFOU 0.6/1kV 5G 2.5mm² P5/P12 BFOU 0.6/1kV 4G 4mm² P5/P12 BFOU 0.6/1kV 5G 4mm² P5/P12 BFOU 0.6/1kV 2X 4/6mm² P5/P12 BFOU 0.6/1kV 3X 4/6mm² P5/P12 BFOU 0.6/1kV 4X 4/6mm² P5/P12 BFOU 0.6/1kV 3G 4mm² P5/P12 Sheath Colour BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK Stock item Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes EAN No. DNK 7021528002003 7021528002010 7021528002034 7021528002041 7021528002058 7021528002065 7021528002072 7021528002089 7021528002096 7021528002102 7021528002157 7021528002164 7021528002171 7021528002188 7021528002195 7021528002201 7021528002218 7021528002225 7021528002232 7021528002249 7021528002256 7021528002263 7021528002270 7021528002287 7021528002294 7021528002300 7021528002324 7021528002331 7021528002355 7021528002362 7021528002379 7021528002386 7021528002393 7021528002409 7021528002416 7021528002423 7021528002430 7021528002447 7021528002454 7021528002461 7021528002478 7021528002508 EL No. 1043605 1043608 1043609 1043610 1043611 1043612 1043613 1043615 1043620 1043619 1043640 1043660 1043705 1043707 1043712 1043719 1043727 1043737 1043621 1043639 1043641 1043659 1043661 1043757 1043762 1043769 1043777 1043787 1043755 1043622 1043642 1043662 -

www.drakaMOG.com

Subject to change without prior notice Page 54 of 96 2010-04-30

Part number 800251 800252 800253 800254 800255 800256 800257 800258 800259 800260 800261 800262 800263 800264 800265 800266 800267 800268 800269 800270 800271 80027183 800272 800273 800274 800275 800276 800277 800278 800279 800280 800281 800282 800283 800284 800285 800287 800288 800289 800290 800291 800295 800296 800297 800298 800301 800304 800306 800307 800308 800310 800312 800313 800316

Description BFOU 0.6/1kV 2X 6/6mm² P5/P12 BFOU 0.6/1kV 3X 6/6mm² P5/P12 BFOU 0.6/1kV 4X 6/6mm² P5/P12 BFOU 0.6/1kV 3G 6mm² P5/P12 BFOU 0.6/1kV 4G 6mm² P5/P12 BFOU 0.6/1kV 5G 6mm² P5/P12 BFOU 0.6/1kV 2X 10/10 P5/P12 BFOU 0.6/1kV 3X 10/10 P5/P12 BFOU 0.6/1kV 4X 10/10 P5/P12 BFOU 0.6/1kV 3G 10mm² P5/P12 BFOU 0.6/1kV 4G 10mm² P5/P12 BFOU 0.6/1kV 5G 10mm² P5/P12 BFOU 0.6/1kV 2X 16/16 P5/P12 BFOU 0.6/1kV 3X 16/16 P5/P12 BFOU 0.6/1kV 4X 16/16 P5/P12 BFOU 0.6/1kV 3G 16mm² P5/P12 BFOU 0.6/1kV 5G 16mm² P5/P12 BFOU 0.6/1kV 4G 16mm² P5/P12 BFOU 0.6/1kV 2X 25/16 P5/P12 BFOU 0.6/1kV 3X 25/16 P5/P12 BFOU 0.6/1kV 4X 25/16 P5/P12 BFOU 0.6/1kV 4X 25mm² P5/P12 BFOU 0.6/1kV 4G 25mm² P5/P12 BFOU 0.6/1kV 5G 25mm² P5/P12 BFOU 0.6/1kV 3G 25mm² P5/P12 BFOU 0.6/1kV 2X 35/16 P5/P12 BFOU 0.6/1kV 3X 35/16 P5/P12 BFOU 0.6/1kV 4X 35/16 P5/P12 BFOU 0.6/1kV 3G 35mm² P5/P12 BFOU 0.6/1kV 4G 35mm² P5/P12 BFOU 0.6/1kV 5G 35mm² P5/P12 BFOU 0.6/1kV 2X 50/25 P5/P12 BFOU 0.6/1kV 3X 50/25 P5/P12 BFOU 0.6/1kV 4X 50/25 P5/P12 BFOU 0.6/1kV 5G 50mm² P5/P12 BFOU 0.6/1kV 4G 50mm² P5/P12 BFOU 0.6/1kV 2X 70/35 P5/P12 BFOU 0.6/1kV 3X 70/35 P5/P12 BFOU 0.6/1kV 4X 70/35 P5/P12 BFOU 0.6/1kV 4G 70mm² P5/P12 BFOU 0.6/1kV 5G 70mm² P5/P12 BFOU 0.6/1kV 3X 95/50 P5/P12 BFOU 0.6/1kV 4X 95/50 P5/P12 BFOU 0.6/1kV 4G 95mm² P5/P12 BFOU 0.6/1kV 5G 95mm² P5/P12 BFOU 0.6/1kV 3X 120/60 P5/P12 BFOU 0.6/1kV 4X 120/60 P5/P12 BFOU 0.6/1kV 4G 120mm² P5/P12 BFOU 0.6/1kV 4G 150mm² P5/P12 BFOU 0.6/1kV 4G 150mm² P5/P12 BFOU 0.6/1kV 4G 185mm² P5/P12 BFOU 0.6/1kV 4X 240/70 P5/P12 BFOU 0.6/1kV 3X 185/95 P5/P12 BFOU 0.6/1kV 5X 16/16 P5/P12

Sheath Colour BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK

Stock item Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes -

EAN No. DNK 7021528002515 7021528002522 7021528002539 7021528002546 7021528002553 7021528002560 7021528002577 7021528002584 7021528002591 7021528002607 7021528002614 7021528002621 7021528002638 7021528002645 7021528002652 7021528002669 7021528002676 7021528002683 7021528002690 7021528002706 7021528002713 702152800271833 7021528002720 7021528002737 7021528002744 7021528002751 7021528002768 7021528002775 7021528002782 7021528002799 7021528002805 7021528002812 7021528002829 7021528002836 7021528002843 7021528002850 7021528002874 7021528002881 7021528002898 7021528002904 7021528002911 7021528002959 7021528002966 7021528002973 7021528002980 7021528003017 7021528003048 7021528003062 7021528003079 7021528003086 7021528003109 7021528003123 7021528003130 7021528003161

EL No. 1043623 1043643 1043663 1043624 1043644 1043664 1043625 1043645 1043665 1043626 1043646 1043666 1043666SDC 1043627 1043647 1043667 1043648 1043668 1043629 1043649 1043669 1043650 1043670 1043651 -

Electrical values power cables

Number of elements Cross Electrical Conductor Max. section Cross type 2 conductor core, section resistance at mm² braid, mm² 20°C, Ohm/km 16 4 STCC 1.16 25 6 STCC 0.734 50 10 STCC 0.391 Max. conductor resistance at 90°C, Ohm/km 1.48 0.936 0.499 Reactance at 50Hz, Ohm/km Reactance at 60Hz, Ohm/km Current Short rating IEC circuit 60092-352 rating 1 Table B.4, second, Ampere Ampere 96 2240 127 3500 196 7000

1 1 1

0.118 0.114 0.105

0.142 0.136 0.126

www.drakaMOG.com

Subject to change without prior notice Page 55 of 96 2010-04-30

Number of elements

1 1 1 1 1 1 1 2 3G 4G 3 4 5 7 12 19 27 37 5G 32 7G 2 3G 3 4G 4 8G 7 12 19 27 37 5G 4G 5G 2 3 4 3G 2 3 4 3G 4G 5G 2 3 4 3G 4G 5G 2 3 4 3G 5G 4G 2 3 4

Cross Electrical Conductor Max. section Cross type 2 conductor core, section resistance at mm² braid, mm² 20°C, Ohm/km 70 10 STCC 0.27 95 10 STCC 0.195 120 10 STCC 0.154 150 10 STCC 0.126 185 10 STCC 0.1 240 16 STCC 0.0762 300 16 STCC 0.0607 1.5 4 STCC 12.2 1.5 STCC 12.2 1.5 STCC 12.2 1.5 6 STCC 12.2 1.5 6 STCC 12.2 1.5 6 STCC 12.2 1.5 6 STCC 12.2 1.5 10 STCC 12.2 1.5 10 STCC 12.2 1.5 16 STCC 12.2 1.5 16 STCC 12.2 1.5 STCC 12.2 1.5 16 STCC 12.2 2.5 STCC 7.56 2.5 6 STCC 7.56 2.5 STCC 7.56 2.5 6 STCC 7.56 2.5 STCC 7.56 2.5 6 STCC 7.56 2.5 STCC 7.56 2.5 6 STCC 7.56 2.5 10 STCC 7.56 2.5 16 STCC 7.56 2.5 16 STCC 7.56 2.5 25 STCC 7.56 2.5 STCC 7.56 4 STCC 4.7 4 STCC 4.7 4 6 STCC 4.7 4 6 STCC 4.7 4 6 STCC 4.7 4 STCC 4.7 6 6 STCC 3.11 6 6 STCC 3.11 6 6 STCC 3.11 6 STCC 3.11 6 STCC 3.11 6 STCC 3.11 10 10 STCC 1.84 10 10 STCC 1.84 10 10 STCC 1.84 10 STCC 1.84 10 STCC 1.84 10 STCC 1.84 16 16 STCC 1.16 16 16 STCC 1.16 16 16 STCC 1.16 16 STCC 1.16 16 STCC 1.16 16 STCC 1.16 25 16 STCC 0.734 25 16 STCC 0.734 25 16 STCC 0.734

Max. conductor resistance at 90°C, Ohm/km 0.344 0.249 0.196 0.161 0.128 0.0972 0.0774 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 9.64 9.64 9.64 9.64 9.64 9.64 9.64 9.64 9.64 9.64 9.64 9.64 9.64 5.99 5.99 5.99 5.99 5.99 5.99 3.97 3.97 3.97 3.97 3.97 3.97 2.35 2.35 2.35 2.35 2.35 2.35 1.48 1.48 1.48 1.48 1.48 1.48 0.936 0.936 0.936

Reactance at 50Hz, Ohm/km

Reactance at 60Hz, Ohm/km

0.1 0.097 0.095 0.094 0.092 0.09 0.088 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.107 0.107 0.107 0.107 0.107 0.107 0.107 0.107 0.107 0.107 0.107 0.107 0.107 0.1 0.1 0.100 0.100 0.1 0.1 0.094 0.094 0.094 0.094 0.094 0.094 0.088 0.088 0.088 0.088 0.088 0.088 0.082 0.082 0.082 0.082 0.082 0.082 0.081 0.081 0.081

0.12 0.116 0.114 0.112 0.11 0.108 0.106 0.138 0.138 0.138 0.138 0.138 0.138 0.138 0.138 0.138 0.138 0.138 0.138 0.138 0.129 0.129 0.129 0.129 0.129 0.129 0.129 0.129 0.129 0.129 0.129 0.129 0.129 0.120 0.120 0.120 0.120 0.120 0.120 0.112 0.112 0.112 0.112 0.112 0.112 0.105 0.105 0.105 0.105 0.105 0.105 0.099 0.099 0.099 0.099 0.099 0.099 0.098 0.098 0.098

Current rating IEC 60092-352 Table B.4, Ampere 242 293 339 389 444 522 601 20 20 16 16 16 13.5 12 10 8.5 7.5 7 16 7 16.5 26 26 21 21 21 15.5 15.5 13 11 10 9 21 28 28 34 28 28 34 44 36 36 44 36 36 61 50 50 61 50 50 80 67 67 80 67 67 108 89 89

Short circuit rating 1 second, Ampere 9800 13300 16800 21000 25900 33600 42000 210 210 210 210 210 210 210 210 210 210 210 210 210 350 350 350 350 350 350 350 350 350 350 350 350 350 560 560 560 560 560 560 840 840 840 840 840 840 1400 1400 1400 1400 1400 1400 2240 2240 2240 2240 2240 2240 3500 3500 3500

www.drakaMOG.com

Subject to change without prior notice Page 56 of 96 2010-04-30

Number of elements

4 4G 5G 3G 2 3 4 3G 4G 5G 2 3 4 5G 4G 2 3 4 4G 5G 3 4 4G 5G 3 4 4G 4G 4G 4G 4 3 5

Cross Electrical Conductor Max. section Cross type 2 conductor core, section resistance at mm² braid, mm² 20°C, Ohm/km 25 STCC 0.734 25 STCC 0.734 25 STCC 0.734 25 STCC 0.734 35 16 STCC 0.529 35 16 STCC 0.529 35 16 STCC 0.529 35 STCC 0.529 35 STCC 0.529 35 STCC 0.529 50 25 STCC 0.391 50 25 STCC 0.391 50 25 STCC 0.391 50 STCC 0.391 50 STCC 0.391 70 35 STCC 0.27 70 35 STCC 0.27 70 35 STCC 0.27 70 STCC 0.27 70 STCC 0.27 95 50 STCC 0.195 95 50 STCC 0.195 95 STCC 0.195 95 STCC 0.195 120 60 STCC 0.154 120 60 STCC 0.154 120 STCC 0.154 150 STCC 0.126 150 STCC 0.126 185 STCC 0.1 240 70 STCC 0.0762 185 95 STCC 0.1 16 16 STCC 1.16

Max. conductor resistance at 90°C, Ohm/km 0.936 0.936 0.936 0.936 0.675 0.675 0.675 0.675 0.675 0.675 0.499 0.499 0.499 0.499 0.499 0.344 0.344 0.344 0.344 0.344 0.249 0.249 0.249 0.249 0.196 0.196 0.196 0.161 0.161 0.128 0.0972 0.128 1.48

Reactance at 50Hz, Ohm/km

Reactance at 60Hz, Ohm/km

0.081 0.081 0.081 0.078 0.078 0.078 0.078 0.078 0.078 0.078 0.078 0.078 0.078 0.078 0.075 0.077 0.077 0.075 0.075 0.075 0.075 0.075 0.075 0.073 0.073 0.073 0.073 0.073 0.074 0.082

0.098 0.098 0.098 0.094 0.094 0.094 0.094 0.094 0.094 0.094 0.093 0.093 0.093 0.093 0.092 0.092 0.092 0.092 0.092 0.090 0.090 0.090 0.090 0.088 0.088 0.088 0.088 0.088 0.089 0.099

Current rating IEC 60092-352 Table B.4, Ampere 89 89 89 108 133 110 110 133 110 110 167 137 137 137 137 206 169 169 169 169 205 205 205 205 237 237 237 272 272 311 365 311 56

Short circuit rating 1 second, Ampere 3500 3500 3500 3500 4900 4900 4900 4900 4900 4900 4900 7000 7000 7000 7000 9800 9800 9800 9800 9800 13300 13300 13300 13300 16800 16800 16800 21000 21000 25900 33600 25900 2240

Ambient temperature correction factors

Ambient Temp °C Rating factor 35 1.10 40 1.05 45 1.00 50 0.94 55 0.88 60 0.82 65 0.74 70 0.67 75 0.58 80 0.47

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 57 of 96 2010-04-30

Halogen-free, mud resistant, fire resistant power cable, BFOU 0,6/1kV, P5/P12, double braided Fire resistant, flame retardant halogen-free power cable. Mud resistant. Double braided.

BFOU 0,6/1(1,2)kV

MGT/EPR/EPR/TCWB/EVA

NEK TS 606 CodeP5/P12

Operating temperature Operating Voltage Standards applied Application Fixed installation for power, control and lighting in both EX- and safe areas, emergency and critical systems where requirement for fire resistance exists. For installation in areas exposed to MUD and drilling/cleaning fluids. Meets the MUD resistance requirement in NEK TS 606:2009. IEC 60092-353 IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60331-1, -2, -21 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 0,6/1(1,2)kV

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Fire Resistant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Lay up / Shielding Inner covering Tape over inner covering Armour/screen Tape over armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour B F Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 Mica-tape + EP-rubber, IEC 60092-351 (EPR) Cores laid up in concentric layers Flame retardant and halogen-free thermoplastic compound PET tape + rubberized Polyamide tape Two layers of tinned copper wire braid (double braid) PET tape + rubberized Polyamide tape Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) E.g. "meter" "year" DRAKA 01 BFOU 0,6/1kV P5/P12 3 x 25/16 mm2 FLEX FLAME IEC 60331-21 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel Black

O

U

www.drakaMOG.com

Subject to change without prior notice Page 58 of 96 2010-04-30

Core identification power cables

Single core - Black Two cores - Blue - Brown Three cores - Brown - Black - Grey Four cores - Blue - Brown - Black - Grey Five cores - Blue - Brown - Black - Grey - Black Seven cores and above - White with black numbers Two cores + earth (3G) - Yellow/green - Blue - Brown Three cores + earth (4G) - Yellow/green - Brown - Black - Grey Four cores + earth (5G) - Yellow/green - Blue - Brown - Black - Grey G / X in cable description - G = One of the cores are yellow/green - X = no yellow/green core Core identification - to HD308S2 - and IEC 60446:2007-05

Range and dimensions

Electrical Cross Thickness Number Cross Conductor Insulation section Inner of section Diameter, Thickness, core, covering, elements mm mm braid, mm² mm mm² 3 4 3 2 4 3 150 150 240 150 185 185 70 70 120 70 95 95 15.90 15.90 19.1 18.1 17.7 17.70 1.8 1.8 2.2 1.8 2.0 2.0 1.4 1.6 2.0 1.8 1.8 1.6 Diameter inner covering, mm 46.5 ± 2 52 ± 2.5 Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.4 0.5 81.4 99 138.5 86 54.3 127.2 Thickness Outer Sheath, mm 2.6 2.8 3.0 2.5 2.9 2.8 Diameter outer sheath, mm 54.5 ± 2.5 61 ± 3 65.0 ± 3.0 52 ± 2.5 68±3 61 ± 3 Weight of Cable Approx. (Kg/Km) 7470 9490 11900 5350 11660 9380 Copper content Approx. (kg/km) 4945 6451 8043 3577 7750 6297

56.0 ±2.0 0.7 44 ± 2 57.5 ± 2.5 51.5 ± 2.5 0.4 0.4 0.5

Ordering information

Part number 800302 800309 800314 800317 800391 800392 Description BFOU 0.6/1kV 3X 150/70 P5/P12 BFOU 0.6/1kV 4X 150/70 P5/P12 BFOU 0.6/1kV 3X 240/120 P5/P12 BFOU 0.6/1kV 2X 150/70mm² BFOU 0.6/1kV 4X 185/95 P5/P12 BFOU 0.6/1kV 3X 185/95 P5/P12 Sheath Colour BLACK BLACK BLACK BLACK BLACK BLACK Stock item Yes EAN No. DNK 7021528003024 7021528003093 7021528003147 7021528003178 7021528003918 7021528003925 EL No. 1043652 -

Electrical values power cables

Number of elements Cross Electrical Conductor Max. section Cross type conductor core, section resistance at mm² braid, mm² 20°C, Ohm/km 150 70 KGTFR 0.126 150 70 KGTFR 0.126 240 120 KGTFR 0.0762 150 70 KGTFR 0.126 185 95 KGTFR 0.1 185 95 KGTFR 0.1 Max. conductor resistance at 90°C, Ohm/km 0.161 0.161 0.0972 0.161 0.128 0.128 Reactance at 50Hz, Ohm/km Reactance at 60Hz, Ohm/km Current rating IEC 60092-352 Table B.4, Ampere 272 272 365 331 311 311 Short circuit rating 1 second, Ampere 21000 21000 33600 21000 25900 25900

3 4 3 2 4 3

0.073 0.073 0.074 0.072 0.073 0.073

0.088 0.088 0.089 0.088 0.088 0.088

Ambient temperature correction factors

Ambient Temp °C Rating factor 35 1.10 40 1.05 45 1.00 50 0.94 55 0.88 60 0.82 65 0.74 70 0.67 75 0.58 80 0.47

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 59 of 96 2010-04-30

www.drakaMOG.com

Subject to change without prior notice Page 60 of 96 2010-04-30

Halogen-free, mud resistant, fire resistant power cable, BFOU 0,6/1kV, P5/P12, large single core cables Fire resistant, flame retardant halogenfree power cable. Mud resistant. Single core cable.

BFOU 0,6/1(1,2)kV

MGT/EPR/EPR/TCWB/EVA

NEK TS 606 CodeP5/P12

Operating temperature Operating Voltage Standards applied Application IEC 60092-353/60502-1 IEC 60228 class 2 Fixed installation for power, control and lighting in both EXIEC 60092-351 and safe areas, emergency and critical systems where IEC 60092-359 requirement for fire resistance exists. For installation in IEC 60332-1 areas exposed to MUD and drilling/cleaning fluids. Meets the IEC 60332-3-22 MUD resistance requirement in NEK TS 606:2009. IEC 60331-1, -2, -21 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 0,6/1(1,2)kV

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Fire Resistant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Lay up / Shielding Inner covering Tape over inner covering Armour/screen Tape over armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour B F Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 Mica-tape + EP-rubber, IEC 60092-351 (EPR) Cores laid up in concentric layers Flame retardant and halogen-free thermoplastic compound PET tape Tinned annealed copper wire braid PET tape Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) E.g. "meter" "year" DRAKA 01 BFOU 0,6/1kV P5/P12 3 x 25/16 mm2 FLEX FLAME IEC 60331-21 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel Black

O

U

www.drakaMOG.com

Subject to change without prior notice Page 61 of 96 2010-04-30

Core identification power cables

Single core - Black Two cores - Blue - Brown Three cores - Brown - Black - Grey Four cores - Blue - Brown - Black - Grey Five cores - Blue - Brown - Black - Grey - Black Seven cores and above - White with black numbers Two cores + earth (3G) - Yellow/green - Blue - Brown Three cores + earth (4G) - Yellow/green - Brown - Black - Grey Four cores + earth (5G) - Yellow/green - Blue - Brown - Black - Grey G / X in cable description - G = One of the cores are yellow/green - X = no yellow/green core Core identification - to HD308S2 - and IEC 60446:2007-05

Range and dimensions

Electrical Cross Number Cross section of section core, elements braid, mm² mm² 1 400 25 1 630 25 Thickness Conductor Insulation Inner Diameter, Thickness, covering, mm mm mm 26.00 32.80 2.4 2.8 1.4 1.4 Diameter inner covering, mm 35 ± 1.5 42 ± 2 Mechanical Diameter crossBraid section of Wire, the braid, mm mm² 0.4 31.7 0.4 40.7 Thickness Outer Sheath, mm 2.1 2.3 Diameter outer sheath, mm 41 ± 2 48.5 ± 2 Weight of Cable Approx. (Kg/Km) 5130 7700 Copper content Approx. (kg/km) 3974 6205

Ordering information

Part number 800211 800213 Description BFOU 0.6/1kV 1X 400/25 P5/P12 BFOU 0.6/1kV 1X 630/25 P5/P12 Sheath Colour BLACK BLACK Stock item EAN No. DNK 7021528002119 7021528002133 EL No. -

Electrical values power cables

Number of elements Cross Electrical Conductor Max. Max. Reactance section Cross type 2 conductor conductor at 50Hz, core, section resistance at resistance at Ohm/km mm² braid, mm² 20°C, 90°C, Ohm/km Ohm/km 400 630 25 25 STCC STCC 0.0475 0.0286 0.0606 0.0606 0.088 0.084 Reactance at 60Hz, Ohm/km Current Short rating IEC circuit 60092-352 rating 1 Table B.4, second, Ampere Ampere 690 dc / 56000 670 ac 890 dc / 88200 780 ac

1 1

0.105 0.101

Ambient temperature correction factors

Ambient Temp °C Rating factor 35 1.10 40 1.05 45 1.00 50 0.94 55 0.88 60 0.82 65 0.74 70 0.67 75 0.58 80 0.47

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 62 of 96 2010-04-30

Halogen-free, mud resistant insulated conductor UX 1000V, P15

1

2

3

Flame retardant conductors

UX 1000V

Halogen-free, NEK 606 Type: P15 Maximum operating Conductor temperature Operating voltage : 90°C : 1000V

Application Insulated conductor for earthing and bonding services. Mud resistant in accordance with NEK TS 606:2009.

Standards applied IEC:60092-353 & NEK TS 606:2009 IEC:60332-3-22 IEC:60754-1,2 IEC:61034-1,2

- Design guidelines - Flame retardance - Halogen-free properties - Smoke density

CONSTRUCTION

CODE LETTER Conductor Insulation Unsheathed Marking U X E.g; "meter" "year" DRAKA NORSK KABEL UX 1000V P15 1x 95 mm² IEC 332-3-22 Yellow/green Tinned, stranded copper. (1) PETP-tape. (2) Flame retardant halogen-free thermoset compound, HF90 (IEC 60092-351). (3)

Colour

www.drakaMOG.com

Subject to change without prior notice Page 63 of 96 2010-04-30

RANGE AND DIMENSIONS: UX 1000V Insulated conductor, P15

Conductor area (mm²) Conductor diameter approx. (mm) 3,15 4,05 5,15 6,4 7,65 9,00 10,85 12,60 14,20 15,90 17,70 20,15 22,60 32,80 Insulation thickness (mm) 1,0 1,0 1,0 1,2 1,2 1,4 1,4 1,6 1,6 1,8 2,0 2,2 2,4 2,8 Diameter over insulation (mm) 5,5±0,8 6,5±0,8 7,5±0,8 9,5±0,8 10,5±1,0 12,5±1,0 14,5±1,0 16,5±1,0 18,0±1,0 20,0±1,5 22,0±1,5 25,0±1,5 28,0±1,5 38,5±2,0 Weight of conductor approx. (kg/km) 80 120 180 280 370 520 730 970 1220 1520 1890 2450 3090 6350 Copper content approx. (kg/km)

6 10 16 25 35 50 70 95 120 150 185 240 300 630

54 87 143 224 310 430 620 840 1080 1342 1670 2183 2762 5800

Installation recommendations:

In accordance with IEC 60092-352 Minimum bending radius During installation Fixed installed 25N x total cross section of conductors 8 x cable diameter 6 x cable diameter - 20 °C Maximum pulling tension Minium installation temperature

Ordering information:

Conductor area (mm²) DRAKA NORSK KABEL Part number Yellow/green 800800 800801 800802 800803 800804 800805 800806 800807 800808 800809 800810 800811 800812 800815 El-number (Norway only)

6 10 16 25 35 50 70 95 120 150 185 240 300 630

1045541 1045542 1045543 1045553 1045563 1045573 1045583 1045593 1045603 1045604

www.drakaMOG.com

Subject to change without prior notice Page 64 of 96 2010-04-30

Halogen-free, fire resistant, unarmoured, mud resistant power cable, BU 0,6/1kV, P17 Fire resistant, flame retardant halogen-free power cable. Mud resistant

BU 0,6/1(1,2)kV

MGT/EPR/EVA

NEK TS 606 CodeP17

Operating temperature Operating Voltage Standards applied Application Fixed installation for power, control and lighting in safe areas, emergency and critical systems where requirement for fire resistance exists. For installation in areas exposed to MUD and drilling/cleaning fluids. Meets the MUD resistance requirement in NEK TS 606:2009. These cables are double-insulated and Single core cables are used as battery cables. IEC 60092-353 IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60331-21 IEC 60754-1,2 IEC 61034-1,2

: 90°C : 0,6/1(1,2)kV

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Fire Resistant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Lay up / Shielding Inner covering Armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour B Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 Mica-tape + EP-rubber, IEC 60092-351 (EPR) Cores laid up in concentric layers No inner covering. (Additional tapes may be applied) No armour. Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) E.g. "meter" "year" DRAKA 01 BU 0,6/1kV P17 1 x 70 mm2 IEC 60331-21 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel, Black

U

www.drakaMOG.com

Subject to change without prior notice Page 65 of 96 2010-04-30

Core identification power cables

Single core - Black Two cores - Blue - Brown Three cores - Brown - Black - Grey Four cores - Blue - Brown - Black - Grey Five cores - Blue - Brown - Black - Grey - Black Seven cores and above - White with black numbers Two cores + earth (3G) - Yellow/green - Blue - Brown Three cores + earth (4G) - Yellow/green - Brown - Black - Grey Four cores + earth (5G) - Yellow/green - Blue - Brown - Black - Grey G / X in cable description - G = One of the cores are yellow/green - X = no yellow/green core Core identification - to HD308S2 - and IEC 60446:2007-05

Range and dimensions

Number of elements 1 1 1 1 1 1 1 1 1 2 3G 3 7 19 2 3G 3 4G 5G 7 12 19 3 3G 2 3 5G 2 3 3 3 3G 3 3 3 Cross section core, mm² 25 35 50 70 95 120 150 185 10 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 4 4 6 6 6 10 10 16 25 25 35 50 150 Thickness Conductor Insulation Outer Sheath, Diameter, mm Thickness, mm mm 6.45 7.65 9.0 10.85 12.60 14.20 15.90 17.70 4.05 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.55 2.55 3.15 3.15 3.15 4.05 4.05 5.15 6.45 6.45 7.65 9.0 15.9 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.2 1.2 1.2 1.4 1.8 1.1 1.2 1.2 1.3 1.4 1.4 1.5 1.6 1 1.1 1.1 1.1 1.2 1.5 1.1 1.2 1.2 1.2 1.3 1.3 1.4 1.6 1.2 1.2 1.2 1.2 1.4 1.3 1.4 1.4 1.5 1.5 1.7 1.9 2.3 Diameter outer sheath, mm 11.5 ± 0.8 13 ± 0.8 15 ± 0.8 17 ± 0.8 19.5 ± 0.8 21 ± 1 23.5 ± 1 26 ± 1 8.5 ± 0.5 10 ± 0.8 10.5 ± 0.8 10.5 ± 0.8 14 ± 0.8 22.5 ± 1 11 ± 0.8 11.5 ± 0.8 11.5 ± 0.8 13 ± 0.8 14.5 ± 0.8 15.5 ± 0.8 21 ± 1 25 ± 1 13 ± 0.8 13 ± 0.8 13.5 ± 0.8 14.5 ± 0.8 18 ± 0.8 15.5 ± 0.8 16.5 ± 0.8 19 ± 0.8 22.5 ± 1 23 ± 1 26 ± 1 30 ± 1.5 48 ± 2 Copper Weight of Cable content Approx. Approx. (Kg/Km) (kg/km) 350 231 460 314 620 434 850 632 1120 847 1390 1075 1730 1357 2110 1664 160 91 150 28 175 42 175 42 320 98 760 266 185 46 220 69 220 69 265 92 340 115 410 161 650 276 990 436 295 110 295 110 310 109 380 164 600 273 440 182 550 271 790 438 1160 688 1190 694 1550 927 2120 1293 5910 4020

www.drakaMOG.com

Subject to change without prior notice Page 66 of 96 2010-04-30

Ordering information

Part number 801201 801202 801203 801204 801205 801206 801207 801208 801214 801215 801216 801218 801225 801228 801233 801234 801236 801237 801240 801244 801245 801246 801253 801254 801259 801261 801263 801266 801267 801273 801279 801280 801286 801292 801298 Description BU 0.6/1kV 1X 25mm² P17 BU 0.6/1kV 1X 35mm² P17 BU 0.6/1kV 1X 50mm² P17 BU 0.6/1kV 1X 70mm² P17 BU 0.6/1kV 1X 95mm² P17 BU 0.6/1kV 1X 120mm² P17 BU 0.6/1kV 1X 150mm² P17 BU 0.6/1kV 1X 185mm² P17 BU 0.6/1kV 1X 10mm² P17 BU 0.6/1kV 2X 1.5mm² P17 BU 0.6/1kV 3G 1.5mm² P17 BU 0.6/1kV 3X 1.5mm² P17 BU 0.6/1kV 7X 1.5mm² P17 BU 0.6/1kV 19X 1.5mm² P17 BU 0.6/1kV 2X 2.5mm² P17 BU 0.6/1kV 3G 2.5mm² P17 BU 0.6/1kV 3X 2.5mm² P17 BU 0.6/1kV 4G 2.5mm² P17 BU 0.6/1kV 5G 2.5mm² P17 BU 0.6/1kV 7X 2.5mm² P17 BU 0.6/1kV 12X 2.5mm² P17 BU 0.6/1kV 19X 2.5mm² P17 BU 0,6/1KV 3X 4 MM2 P17 BU 0.6/1kV 3G 4mm² P17 BU 0,6/1KV 2X 6 MM2 P17 BU 0.6/1kV 3X 6mm² P17 BU 0.6/1kV 5G 6mm² P17 BU 0.6/1kV 2X 10mm² P17 BU 0,6/1KV 3X 10 MM2 P17 BU 0.6/1kV 3X 16mm² P17 BU 0,6/1KV 3X 25 mm² P17 BU 0.6/1kV 3G 25mm² P17 BU 0,6/1KV 3X 35 mm² P17 BU 0,6/1KV 3X 50 mm² P17 BU 0,6/1KV 3X 150 mm² P17 Sheath Colour BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK Stock item Yes EAN No. DNK 7021528012019 7021528012026 7021528012033 7021528012040 7021528012057 7021528012064 7021528012071 7021528012088 7021528012149 7021528012156 7021528012163 7021528012187 7021528012255 7021528012286 7021528012330 7021528012347 7021528012361 7021528012378 7021528012408 7021528012446 7021528012453 7021528012460 7021528012538 7021528012545 7021528012590 7021528012613 7021528012637 7021528012668 7021528012675 7021528012736 7021528012798 7021528012804 7021528012866 7021528012927 7021528012989 EL No. 1061201 1061203 1061205 1061207 -

Electrical values power cables

Number of elements Cross section core, mm² 25 35 50 70 95 120 150 185 10 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 Max. conductor resistance at 20°C, Ohm/km 0.734 0.529 0.391 0.27 0.195 0.154 0.126 0.1 1.84 12.2 12.2 12.2 12.2 12.2 7.56 7.56 7.56 7.56 7.56 7.56 Max. conductor resistance at 90°C, Ohm/km 0.936 0.675 0.499 0.344 0.249 0.196 0.161 0.128 2.35 15.6 15.6 15.6 15.6 15.6 9.64 9.64 9.64 9.64 9.64 9.64 Reactance at 50Hz, Ohm/km 0.097 0.093 0.091 0.087 0.085 0.084 0.083 0.083 0.108 0.115 0.115 0.115 0.115 0.115 0.107 0.107 0.107 0.107 0.107 0.107 Reactance at 60Hz, Ohm/km 0.117 0.111 0.109 0.105 0.102 0.100 0.100 0.100 0.130 0.138 0.138 0.138 0.138 0.138 0.129 0.129 0.129 0.129 0.129 0.129 Current rating IEC 60092-352 Table B.4, Ampere 127 157 196 242 293 339 389 444 72 20 20 16 12 8.5 26 26 21 21 21 15.5 Short circuit rating 1 second, Ampere 3500 4900 7000 9800 13300 16800 21000 25900 1400 210 210 210 210 210 350 350 350 350 350 350

1 1 1 1 1 1 1 1 1 2 3G 3 7 19 2 3G 3 4G 5G 7

www.drakaMOG.com

Subject to change without prior notice Page 67 of 96 2010-04-30

Number of elements

Cross section core, mm² 2.5 2.5 4 4 6 6 6 10 10 16 25 25 35 50 150

Max. conductor resistance at 20°C, Ohm/km 7.56 7.56 4.7 4.7 3.11 3.11 3.11 1.84 1.84 1.16 0.734 0.734 0.529 0.391 0.126

Max. conductor resistance at 90°C, Ohm/km 15.6 15.6 5.99 9.64 3.97 3.97 3.97 3.97 2.35 1.48 0.936 0.936 0.675 0.499 0.161

Reactance at 50Hz, Ohm/km 0.115 0.115 0.100 0.107 0.094 0.094 0.094 0.094 0.088 0.082 0.079 0.082 0.078 0.078 0.073

Reactance at 60Hz, Ohm/km 0.138 0.138 0.120 0.129 0.112 0.112 0.112 0.112 0.105 0.099 0.095 0.099 0.094 0.093 0.088

12 19 3 3G 2 3 5G 2 3 3 3 3G 3 3 3

Current rating IEC 60092-352 Table B.4, Ampere 13 11 28 34 44 36 36 61 50 67 89 108 110 137 272

Short circuit rating 1 second, Ampere 350 350 560 560 840 840 840 1400 1400 2240 3500 3500 4900 7000 21000

Ambient temperature correction factors

Ambient Temp °C Rating factor 35 1.10 40 1.05 45 1.00 50 0.94 55 0.88 60 0.82 65 0.74 70 0.67 75 0.58 80 0.47

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 68 of 96 2010-04-30

Halogen-free, unarmoured, mud resistant power cable, RU 0,6/1kV, P18 Flame retardant halogen-free power cable. Mud resistant

RU 0,6/1(1,2)kV

EPR/EVA

NEK TS 606 CodeP18

Operating temperature Operating Voltage Standards applied Application IEC 60092-353 Fixed installation for power,control and lighting in both EX- and safe IEC 60228 class 2 areas, general purposes. For installation in areas exposed to MUD IEC 60092-351 IEC 60092-359 and drilling/cleaning fluids. Meets the OIL & MUD resistance IEC 60332-1 requirement in NEK TS 606:2009. These cables are doubleIEC 60332-3-22 insulated and Single core cables are used as battery cables. IEC 60754-1,2 IEC 61034-1,2

: 90°C : 0,6/1(1,2)kV

- Design - Conductor - Insulation - Sheath - Flame Retardant - Flame Retardant - Halogen Free - Low Smoke

Construction

Code Letter Conductor Insulation Lay up / Shielding Inner covering Armour/screen Outer sheath Marking text Manufacturing unit Outer sheath colour R Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 EP-rubber, IEC 60092-351 (EPR) Cores laid up in concentric layers No inner covering. (Additional tapes may be applied) No armour. Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359) E.g. "meter" "year" DRAKA 01 RU 0,6/1KV P18 3 x 2,5 mm2 IEC 60332-3-22 DRAKA 01 = Draka Norsk Kabel, Black

U

www.drakaMOG.com

Subject to change without prior notice Page 69 of 96 2010-04-30

Core identification power cables

Single core - Black Two cores - Blue - Brown Three cores - Brown - Black - Grey Four cores - Blue - Brown - Black - Grey Five cores - Blue - Brown - Black - Grey - Black Seven cores and above - White with black numbers Two cores + earth (3G) - Yellow/green - Blue - Brown Three cores + earth (4G) - Yellow/green - Brown - Black - Grey Four cores + earth (5G) - Yellow/green - Blue - Brown - Black - Grey G / X in cable description - G = One of the cores are yellow/green - X = no yellow/green core Core identification - to HD308S2 - and IEC 60446:2007-05

Range and dimensions

Number of elements 1 1 1 1 1 1 1 1 1 2 3G 3 4G 4 7G 5 7 12 19 24 2 3G 3 4G 4 5G 5 7 2 3G 3 4G 4 5G 2 3G 3 4 5G 4G 2 3 4G 5G 3 4 Cross Conductor section core, Diameter, mm mm² 25 6.45 50 9.0 70 10.9 95 12.60 120 14.20 150 15.90 185 17.70 240 20.15 300 22.60 1.5 1.6 1.5 1.6 1.5 1.6 1.5 1.6 1.5 1.6 1.5 1.6 1.5 1.6 1.5 1.6 1.5 1.6 1.5 1.6 1.5 1.6 2.5 2.0 2.5 2.0 2.5 2.0 2.5 2.0 2.5 2.0 2.5 2.0 2.5 2.0 2.5 2.0 4 2.55 4 2.55 4 2.55 4 2.55 4 2.55 4 2.55 6 3.15 6 3.15 6 3.15 6 3.15 6 3.15 6 3.15 10 4.05 10 4.05 10 4.05 10 4.05 16 5.15 16 5.15 Thickness Insulation Outer Sheath, Thickness, mm mm 1.2 1.1 1.4 1.2 1.4 1.3 1.6 1.4 1.6 1.4 1.8 1.5 2.0 1.6 2.2 1.7 2.4 1.8 1.0 1.1 1.0 1.1 1.0 1.1 1.0 1.1 1.0 1.1 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.4 1.0 1.5 1.0 1.6 1.0 1.1 1.0 1.1 1.0 1.1 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.3 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.3 1.0 1.2 1.0 1.2 1.0 1.2 1.0 1.3 1.0 1.3 1.0 1.3 1.0 1.2 1.0 1.3 1.0 1.3 1.0 1.4 1.0 1.4 1.0 1.4 Weight of Cable Diameter outer Approx. sheath, mm (Kg/Km) 11.5 ± 0.8 340 14.5 ± 0.8 610 16.5 ± 0.8 820 19 ± 0.8 1110 20.5 ± 1 1370 23 ± 1 1710 25.5 ± 1 2090 28.5 ± 1 2680 31.5 ± 1.5 3370 9.5 ± 0.5 135 10 ± 0.8 160 10 ± 0.8 160 11 ± 0.8 190 11 ± 0.8 190 13.5 ± 0.8 290 12 ± 0.8 240 13.5 ± 0.8 290 18 ± 0.8 470 21 ± 1 700 25 ± 1 890 10.5 ± 0.8 170 11 ± 0.8 205 11 ± 0.8 205 12 ± 0.8 255 12 ± 0.8 250 13.5 ± 0.8 320 13.5 ± 0.8 320 14.5 ± 0.8 390 11.5 ± 0.8 225 12 ± 0.8 275 12 ± 0.8 275 13.5 ± 0.8 340 13.5 ± 0.8 340 15 ± 0.8 410 12.5 ± 0.8 290 13.5 ± 0.8 360 13.5 ± 0.8 360 15 ± 0.8 450 16.5 ± 0.8 550 15 ± 0.8 450 14.5 ± 0.8 410 15.5 ± 0.8 530 17.5 ± 0.8 660 19 ± 0.8 820 18.5 ± 0.8 780 20 ± 1 950 Copper content Approx. (kg/km) 231 434 620 847 1082 1357 1664 2165 2757 28 42 42 56 56 98 70 98 168 266 333 46 69 69 92 92 115 115 160 74 110 110 147 147 183 109 164 164 219 273 219 181 272 363 453 438 579

www.drakaMOG.com

Subject to change without prior notice Page 70 of 96 2010-04-30

Number of elements 3G 4G 5G 3 4 4G 2 3 4G 5G 3 5G 3 5G

Cross Conductor section core, Diameter, mm mm² 16 5.15 16 5.15 16 5.15 25 6.45 25 6.45 25 6.45 35 7.65 35 7.65 35 7.65 35 7.65 50 9.0 50 9.0 70 10.85 70 10.85

Thickness Insulation Outer Sheath, Thickness, mm mm 1.0 1.4 1.0 1.4 1.0 1.5 1.2 1.5 1.2 1.6 1.2 1.6 1.2 1.5 1.2 1.6 1.2 1.7 1.2 1.8 1.4 1.7 1.4 2 1.4 1.9 1.4 2.1

Weight of Cable Diameter outer Approx. sheath, mm (Kg/Km) 18.5 ± 0.8 780 20 ± 1 980 22.5 ± 1 1200 22.5 ± 1 1170 24.5 ± 1 1420 25 ± 1 1500 23 ± 1 1150 25 ± 1 1520 28 ± 1 1950 31 ± 1.5 2370 29.5 ± 1 2090 36.5 ± 1.5 3310 34 ± 1.5 2900 42 ± 2 4550

Copper content Approx. (kg/km) 438 584 730 694 916 925 618 943 1257 1571 1306 2177 1900 3167

Ordering information

Part number 831701 831703 831704 831705 831706 831707 831708 831709 831710 831715 831716 831718 831719 831721 831723 831724 831725 831726 831728 831729 831733 831734 831736 831737 831739 831740 831741 831743 831751 831752 831753 831754 831755 831756 831759 831760 831761 831762 831763 831764 831766 831767 831769 831770 831773 Description RU 0.6/1kV 1X 25mm² P18 RU 0.6/1kV 1X 50mm² P18 RU 0,6/1KV 1X 70 MM2 P18 RU 0.6/1kV 1X 95mm² P18 RU 0.6/1kV 1X 120mm² P18 RU 0.6/1kV 1X 150mm² P18 RU 0.6/1kV 1X 185mm² P18 RU 0.6/1kV 1X 240mm² P18 RU 0.6/1kV 1X 300mm² P18 RU 0.6/1kV 2X 1.5mm² P18 RU 0.6/1kV 3G 1.5mm² P18 RU 0.6/1kV 3X 1.5mm² P18 RU 0.6/1kV 4G 1.5mm² P18 RU 0.6/1kV 4X 1.5mm² P18 RU 0.6/1kV 7G 1.5mm² P18 RU 0.6/1kV 5X 1.5mm² P18 RU 0.6/1kV 7X 1.5mm² P18 RU 0.6/1kV 12X 1.5mm² P18 RU 0.6/1kV 19X 1.5mm² P18 RU 0,6/1KV 24X 1,5 MM2 P18 RU 0.6/1kV 2X 2.5mm² P18 RU 0.6/1kV 3G 2.5mm² P18 RU 0.6/1kV 3X 2.5mm² P18 RU 0.6/1kV 4G 2.5mm² P18 RU 0,6/1KV 4X 2,5 MM2 P18 RU 0.6/1kV 5G 2.5mm² P18 RU 0.6/1kV 5X 2.5mm² P18 RU 0,6/1KV 7X 2,5 MM2 P18 RU 0,6/1KV 2X 4 MM2 P18 RU 0.6/1kV 3G 4mm² P18 RU 0.6/1kV 3X 4mm² P18 RU 0.6/1kV 4G 4mm² P18 RU 0,6/1KV 4X 4 MM2 P18 RU 0,6/1KV 5G 4mm² P18 RU 0,6/1KV 2X 6 MM2 P18 RU 0.6/1kV 3G 6mm² P18 RU 0.6/1kV 3X 6mm² P18 RU 0.6/1kV 4X 6mm² P18 RU 0.6/1kV 5G 6mm² P18 RU 0.6/1kV 4G 6mm² P18 RU 0,6/1KV 2X 10 MM2 P18 RU 0.6/1kV 3X 10mm² P18 RU 0.6/1kV 4G 10mm² P18 RU 0.6/1kV 5G 10mm² P18 RU 0.6/1kV 3X 16mm² P18 Sheath Colour BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK Stock item EAN No. DNK 7021528317015 7021528317039 7021528317046 7021528317053 7021528317060 7021528317077 7021528317084 7021528317091 7021528317107 7021528317152 7021528317169 7021528317183 7021528317190 7021528317213 7021528317237 7021528317244 7021528317251 7021528317268 7021528317282 7021528317299 7021528317336 7021528317343 7021528317367 7021528317374 7021528317398 7021528317404 7021528317411 7021528317435 7021528317510 7021528317527 7021528317534 7021528317541 7021528317558 7021528317565 7021528317596 7021528317602 7021528317619 7021528317626 7021528317633 7021528317640 7021528317664 7021528317671 7021528317695 7021528317701 7021528317732 EL No. 1061403 1061407 1061434 1061437 1061461 -

www.drakaMOG.com

Subject to change without prior notice Page 71 of 96 2010-04-30

Part number 831774 831775 831776 831777 831780 831781 831782 831785 831786 831788 831789 831792 831796 831798 831799

Description RU 0,6/1KV 4X 16 MM2 P18 RU 0.6/1kV 3G 16mm² P18 RU 0.6/1kV 4G 16mm² P18 RU 0.6/1kV 5G 16mm² P18 RU 0.6/1kV 3X 25mm² P18 RU 0,6/1KV 4X 25 MM2 P18 RU 0.6/1kV 4G 25mm² P18 RU 0,6/1KV 2X 35 MM2 P18 RU 0.6/1kV 3X 35mm² P18 RU 0.6/1kV 4G 35mm² P18 RU 0.6/1kV 5G 35mm² P18 RU 0.6/1kV 3X 50mm² P18 RU 0.6/1kV 5G 50mm² P18 RU 0.6/1kV 3X 70mm² P18 RU 0.6/1kV 5G 70mm² P18

Sheath Colour BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK

Stock item -

EAN No. DNK 7021528317749 7021528317756 7021528317763 7021528317770 7021528317800 7021528317817 7021528317824 7021528317855 7021528317862 7021528317886 7021528317893 7021528317923 7021528317961 7021528317985 7021528317992

EL No. -

Electrical values power cables

Number of elements Cross section core, mm² 25 50 70 95 120 150 185 240 300 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 4 4 4 4 4 4 6 6 6 6 6 6 10 10 10 Max. conductor resistance at 20°C, Ohm/km 0.734 0.391 0.27 0.195 0.154 0.126 0.1 0.0762 0.0607 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 7.56 7.56 7.56 7.56 7.56 7.56 7.56 7.56 4.7 4.7 4.7 4.7 4.7 4.7 3.11 3.11 3.11 3.11 3.11 3.11 1.84 1.84 1.84 Max. conductor resistance at 90°C, Ohm/km 0.499 0.499 0.344 0.249 0.196 0.161 0.128 0.0972 0.0774 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6 9.64 9.64 9.64 9.64 9.64 9.64 9.64 9.64 5.99 5.99 5.99 5.99 5.99 5.99 3.97 3.97 3.97 3.97 3.97 3.97 2.35 2.35 2.35 Reactance at Reactance at 50Hz, 60Hz, Ohm/km Ohm/km 0.089 0.089 0.099 0.084 0.082 0.082 0.081 0.080 0.080 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.102 0.103 0.103 0.103 0.103 0.103 0.103 0.103 0.096 0.096 0.096 0.096 0.096 0.096 0.090 0.090 0.090 0.090 0.090 0.090 0.084 0.084 0.084 0.107 0.107 0.120 0.101 0.099 0.098 0.098 0.096 0.096 0.132 0.132 0.132 0.132 0.132 0.132 0.132 0.132 0.132 0.132 0.132 0.123 0.123 0.123 0.123 0.123 0.123 0.123 0.123 0.115 0.115 0.115 0.115 0.115 0.115 0.108 0.108 0.108 0.108 0.108 0.108 0.101 0.101 0.101 Current rating IEC 60092-352 Table B.4, Ampere 127 196 242 293 339 389 444 522 601 20 20 16 16 16 12.5 13.5 12 10 8.5 8 26 26 21 21 21 21 17.5 15.5 34 34 28 28 28 28 44 44 36 36 36 36 61 50 50 Short circuit rating 1 second, Ampere 3500 7000 9800 13300 16800 21000 25900 33600 42000 210 210 210 210 210 210 210 210 210 210 210 350 350 350 350 350 350 350 350 560 560 560 560 560 560 840 840 840 840 840 840 1400 1400 1400

1 1 1 1 1 1 1 1 1 2 3G 3 4G 4 7G 5 7 12 19 24 2 3G 3 4G 4 5G 5 7 2 3G 3 4G 4 5G 2 3G 3 4 5G 4G 2 3 4G

www.drakaMOG.com

Subject to change without prior notice Page 72 of 96 2010-04-30

Number of elements

Cross section core, mm² 10 16 16 16 16 16 25 25 25 35 35 35 35 50 50 70 70

Max. conductor resistance at 20°C, Ohm/km 1.84 1.16 1.16 1.16 1.16 1.16 0.734 0.734 0.734 0.529 0.529 0.529 0.529 0.391 0.391 0.27 0.27

Max. conductor resistance at 90°C, Ohm/km 2.35 1.48 1.48 1.48 1.48 1.48 0.936 0.936 0.936 0.675 0.675 0.675 0.675 0.499 0.499 0.344 0.344

Reactance at Reactance at 50Hz, 60Hz, Ohm/km Ohm/km 0.084 0.080 0.080 0.080 0.080 0.103 0.079 0.079 0.079 0.076 0.076 0.076 0.076 0.076 0.076 0.075 0.076 0.101 0.096 0.096 0.096 0.096 0.123 0.095 0.095 0.095 0.092 0.092 0.092 0.092 0.092 0.092 0.091 0.092

5G 3 4 3G 4G 5G 3 4 4G 2 3 4G 5G 3 5G 3 5G

Current rating IEC 60092-352 Table B.4, Ampere 50 67 67 80 67 67 89 89 89 133 110 110 110 137 137 169 169

Short circuit rating 1 second, Ampere 1400 2240 2240 2240 2240 2240 3500 3500 3500 4900 4900 4900 4900 7000 7000 9800 9800

Ambient temperature correction factors

Ambient Temp °C Rating factor 35 1.10 40 1.05 45 1.00 50 0.94 55 0.88 60 0.82 65 0.74 70 0.67 75 0.58 80 0.47

Installation recommendations

Minimum Bending Radius during Installation 8xD Minimum Bending Radius Fixed Installed 6xD Maximum Tensile Load During Installation 50 N /mm² Minimum Installation Temperature -20°C

www.drakaMOG.com

Subject to change without prior notice Page 73 of 96 2010-04-30

Approvals

Our cables carry these major approvals:

DET NORSKE VERITAS

AMERICAN BUREAU OF SHIPPING

LLOYDS REGISTER OF SHIPPING

RINA

BUREAU VERITAS

RUSSIAN MARITIME REGISTER OF SHIPPING

RFOU 250 V (c) (i) RU 250V (c) (i) RFOU 0,6/1 kV RFOU 6/10 kV RFOU 12/20 kV RU 0,6/1 kV BFOU 250 V (c) (i) BU 250V (i) (c) BFOU 0,6/1 kV BU 0,6/1kV BFCU 250V (c) (i) BFCU 0,6/1kV RFCU 250V (c) (i) RFCU 0,6/1kV

*) *) *) *)

All cables are designed in accordance with IEC 60092-350, IEC 60092-353, IEC 60092-354 and IEC 60092-376 except those marked with *) . They are designed in accordance with BS 6883

www.drakaMOG.com

Subject to change without prior notice Page 74 of 96 2010-04-30

Standards and tests

Standards IEC 60092-350 Designation Title Electrical installations in ships Part 350: General construction and test methods of power, control and instrumentation cables for shipboard and offshore applications Electrical installations in ships Part 351: Insulating materials for shipboard and offshore units, power, control, instrumentation, telecommunication and data cables Electrical installations in ships Part 352: Choice and installation of electrical cables Electrical installations in ships ­ Part 353: Single and multicore non-radial field power cables with extruded solid insulation for rated voltage 1 kV and 3 kV. Electrical installations in ships ­ Part 354: Single -and three-core power cables with extruded solid insulation for rated voltages 6 kV (Um = 7,2kV) up to 30 kV (Um = 36 kV) Electrical installations in ships ­ Part 359: Sheathing materials for shipboard power and telecommunication cables. Electrical installations in ships ­ Part 376: Cables for control and instrumentation circuits 150/250 V (300 V) Conductors of insulated cables. Test method for fire with shock at a temperature of at least 830°C for cables of rated voltage up to and including 0,6/1,0 kV and with an overall diameter exceeding 20 mm Test method for fire with shock at a temperature of at least 830°C for cables of rated voltage up to and including 0,6/1,0 kV and with an overall diameter not exceeding 20 mm Test method for fire with shock at a temperature of at least 830°C for cables of rated voltage up to and including 0,6/1,0 kV tested in a metal enclosure Test for electric cables under fire conditions ­ Circuit integrity ­ Part 11 Apparatus ­ Fire alone at a flame temperature of at least 750°C Test for electric cables under fire conditions ­ Circuit integrity ­ Part 21 Procedures and requirements ­ Cables of rated voltage up to and including 0,6/1kV Test for electric cables under fire conditions ­ Circuit integrity ­ Part 25 Procedures and requirements ­ Optical fibre cables Test on electric and optical fibre cables under fire conditions. Part 1-1 Test for vertical flame propagation for a single insulated wire or cable - Apparatus Test on electric and optical fibre cables under fire conditions. Part 1-2 Test for vertical flame propagation for a single insulated wire or cable ­ Procedure for 1 kW pre-mixed flame

IEC 60092-351

IEC 60092-352

IEC 60092-353

IEC 60092-354

IEC 60092-359

IEC 60092-376

IEC 60228 IEC 60331-1

IEC 60331-2

IEC 60331-3

IEC 60331-11

IEC 60331-21

IEC 60331-25

IEC 60332-1-1

IEC 60332-1-2

www.drakaMOG.com

Subject to change without prior notice Page 75 of 96 2010-04-30

Standards

Designation Title

IEC 60332-1-3

Test on electric and optical fibre cables under fire conditions. Part 1-3 Test for vertical flame propagation for a single insulated wire or cable ­ Procedure for determination of flaming droplets/particles Test on electric and optical fibre cables under fire conditions. Part 2-1 Test for vertical flame propagation for a single small insulated wire or cable - Apparatus Test on electric and optical fibre cables under fire conditions. Part 2-2 Test for vertical flame propagation for a single small insulated wire or cable ­ Procedure for diffusion flame Tests on electric and optical fibre cables under fire conditions. Part 3-10: test for vertical flame spread of vertically-mounted bunched wires or cables ­ Apparatus Tests on electric cables under fire conditions. Part 3-21 Test for vertical flame spread of vertically-mounted bunched wires or cables ­ Category A F/R Tests on electric and optical fibre cables under fire conditions. Part 3-22: Test for vertical flame spread of vertically-mounted bunched wires or cables ­ Category A Tests on electric and optical fibre cables under fire conditions. Part 3-23: Test for vertical flame spread of vertically-mounted bunched wires or cables ­ Category B Tests on electric and optical fibre cables under fire conditions. Part 3-24: Test for vertical flame spread of vertically-mounted bunched wires or cables ­ Category C Tests on electric and optical fibre cables under fire conditions. Part 3-25: Test for vertical flame spread of vertically-mounted bunched wires or cables ­ Category D Basic and safety principles for man-machine interface, marking and identification ­ Identification of conductors by colours or alphanumerics Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) ­ Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV) Test on gases evolved during combustion of electrical cables. Part 1: Determination of the amount of halogen acid gas. Test on gases evolved during combustion of electrical cables. Part 2: Determination of degree of acidity of gases evolved during the combustion of materials taken from electric cables by measuring pH and conductivity. Common test methods for insulating and sheathing materials of electric cables.

IEC 60332-2-1

IEC 60332-2-2

IEC 60332-3-10

IEC 60332-3-21

IEC 60332-3-22

IEC 60332-3-23

IEC 60332-3-24

IEC 60332-3-25

IEC 60446

IEC 60501-1

IEC 60754-1

IEC 60754-2

IEC 60811

www.drakaMOG.com

Subject to change without prior notice Page 76 of 96 2010-04-30

Definition of terms

Flame retardance The cables shall withstand the test specified in IEC 60332-3-22. Single, earth and bonding wires shall withstand the test specified in IEC 60332-1. Fire resistance Fire resistant cables shall be tested in accordance with IEC 60331-1, 60331-2 and 60331-21. Content of halogen To demonstrate that the cables are halogen-free they shall be tested to IEC 60754-1, maximum content of halogen = 5 mg/g. Smoke Emission During a cable fire the smoke emission is recommended to have a minimum value of 60% when tested in accordance with IEC 61034-2

Oil resistance For cables with thermoplastic sheath material there are no requirements for oil resistance properties. All thermoset sheathed cables shall be suitable for an oil production installation. The oil resistance properties shall be demonstrated by a test according to IEC 60092-359 SHF-2 with the cable immersed in IRM oil no. 902 at 100°C for 24 hours.

Mud resistance In accordance with NEK 606 the mud resistant cables shall have a sheath (SHF Mud) that complies with the requirements in IEC 60092-359 for SHF2 and the below specified. Mud resistant cables shall be designed with sheathing compounds suitable for installation and operation in contact with MUD unless otherwise specified. The MUD resistance test requirements for sheathing compounds SHF Mud are as follows: Tensile strength variation 30% 25% 25% Elongation at break variation 30% 25% 25% Volume swell variation 30% 20% 20% Weight increase variation 30% 15% 15%

Test fluid Mineral oil type IRM 903 Calcium Bromide Brine (Waterbased) Carbo Sea (Oil based)

Temperature 100°C 70°C 70°C

Duration 7d 56 d 56 d

www.drakaMOG.com

Subject to change without prior notice Page 77 of 96 2010-04-30

Fire, flame, smoke and corrosion test methods

Cables' integrity during a fire

Fire resistance During a fire it is vital that emergency circuits should continue to function. This could be communication circuits, emergency lights, alarms and fire pumps, etc. On oil rigs and platforms and other confined areas this could be a matter of life and death. Cables that will function in a fire ensuring circuit integrity BFOU / BFCU / BU cables These cable types have Mica Glass Tape applied around the conductors which then is insualed with heatresistant EP-rubber and have an outer sheathing of a halogen-free thermoset material. Test method IEC 60331-21 750°C, 90 minutes. As an option we offer cables to 1000°C for 3 hours with an upgraded IEC 60331 test.

Flame propagation

Flame retardant cables must be self-extinguishing when the source of flames dies out. Flame retardant cables with built-in self-extinguishing properties These cables have sheathing and bedding with hydrated flame retardants that provide resistance to ignition and flame spread. Test methods IEC 60332 - 1 IEC 60332 ­ 3 ­ 22 (Cat.A), -23 (Cat.B) and ­ 24 (Cat.C). IEC 60332 - 3 Category Part 22 (Cat.A) Part 23 (Cat.B) Part 24 (Cat.C) Amount of combustible material in litres per metre of cable ladder 7 3,5 1,5 Burning time Minutes 40 40 20

Smoke risk to personnel

Smoke evolution is of major significance in situations where escape routes are limited in the event of fire. Cables having exceptionally low smoke emission All offshore topside cables and fire resistant cables listed in this catalogue, have sheathing and insulation based on halogen-free materials. To minimise the risk of smoke and toxic gases, each component from conductor tapes to outer sheath has been taken into consideration.

www.drakaMOG.com

Subject to change without prior notice Page 78 of 96 2010-04-30

Test method

3 m Cube Test for the measurement of smoke density. IEC 61034 - 2

Damage to expensive equipment

Corrosion Halogen-free cables will not cause corrosion to metals. When halogen - containing cables burn, the gases generated in combustion of the sheathing and insulation may cause corrosion. The secondary effects after a fire are often many times larger than the damages caused by the fire itself.

Test method

IEC 60754 - 1 IEC 60754 - 2

www.drakaMOG.com

Subject to change without prior notice Page 79 of 96 2010-04-30

Installation recommendations

The following installation recommendations are in accordance with IEC regulations and practice. Different regulations may apply in other countries.

Minimum cable bending radius. Cables for rated voltages up to 0,6/1 kV, in accordance with IEC 60092-352. Outer diameter of cable Minimum bending radius when fixed installed Unbraided cables Braided cables 4D 6D 6D 6D Minimum bending radius during installation

D < 25mm D > 25mm

8D 8D

Medium voltage cables up to and including 12/20(24) kV: Minimum bending radius during installation: Minimum bending radius when fixed installed: 15D 9D

Installation temperature. Minimum recommended installation temperature for cables of rated voltage up to 20 kV, such as:

RFOU ­ BFOU ­ RU ­ BU

-20°C

Pulling tension. The cable pulling tension during installation can be estimated by means of the following formula: p= or p= 25 N × total cross section of conductors in the unarmoured cable 50 N × total cross section of conductors in the armoured cable

Additional tension will be supplied from the braid and the insulation and sheathing compound.

www.drakaMOG.com

Subject to change without prior notice Page 80 of 96 2010-04-30

Electrical data

Conductor Resistance

Resistance formula:

L

R=p

A

R = resistance in ohm per phase

Ohm · mm

2

p = specific resistance

m

A = conductor area mm², L = conductor length, m Resistance as a function of temperature: R = R0 (1 + (t-20 °C)) R = Resistance at t=20°C, t = conductor temperature °C, = 0,00393 for copper

Conductor resistance tinned annealed copper 250V.

In accordance with IEC 60092-376. Nominal No. of wires conductor and diameter area of wires mm² 0,5 0,75 1 1,5 2,5 mm 7x 0,30 7x 0,36 7x 0,43 7x 0,525 7x 0,67 Approx. diam. Max. resistance pr km 20°C ohm 41,6 26,3 19,3 12,9 8,02 90°C ohm 53,0 33,5 24,6 16,4 10,2

mmØ 0,9 1,1 1,3 1,6 2,0

Conductor resistance tinned annealed copper 0,6/1kV, 1,8/3(3,6)kV.

In accordance with IEC 60228, class 2. Tinned stranded annealed copper conductors for single core and multicore cables 0,6/1kV and 1,8/3kV Nominal conductor area mm² 0,5 0,75 1 1,5 2,5 4 No. of wires and diameter of wires mm 7x 0,30 7x 0,37 7x 0,43 7x 0,53 7x 0,67 7x 0,85 Approx. diam. Max. resistance pr km 20°C ohm 36,7 24,8 18,2 12,2 7,56 4,70 90°C ohm 46,8 31,6 23,2 15,6 9,64 5,99

mmØ 0,9 1,1 1,3 1,6 2,0 2,6

www.drakaMOG.com

Subject to change without prior notice Page 81 of 96 2010-04-30

Nominal conductor area mm² 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630

No. of wires and diameter of wires mm 7x 1,05 7x 1,35 7x 1,71 7 x 2,13 19x 1,53 19x 1,80 19x 2,17 37x 1,80 37x 2,03 37x 2,27 37x 2,52 61x 2,24 61x 2,52 91x 2,36 91x 2,64 127x 2,52

Approx. diam.

Max. resistance pr km 20°C ohm 3,11 1,84 1,16 0,734 0,529 0,391 0,270 0,195 0,154 0,126 0,100 0,0762 0,0607 0,04475 0,0369 0,0286 90°C ohm 3,97 2,35 1,48 0,936 0,675 0,499 0,344 0,249 0,196 0,161 0,128 0,0972 0,0774 0,0596 0,0463 0,0359

mmØ 3,2 4,1 5,2 6,6 7,7 9,1 10,9 12,6 14,2 15,9 17,7 20,2 22,6 26,0 29,0 32,8

Conductor resistance, tinned annealed copper conductor 3,6/6(7,2)kV, 6/10(12)kV, 8,7/15(17,5)kV, 12/20(24)kV and 18/30(36)kV.

In accordance with IEC 60228, class 2. Compressed tinned stranded annealed copper conductors for single core and multicore cables 3,6/6kV, 6/10kV, 8,7/15kV, 12/20(24)kV and 18/30(36)kV. Nominal conductor area mm² 16 25 35 50 70 95 120 150 185 240 300 No. of wires and diameter of wires *) mm 7x 1,71 7 x 2,14 19x 1,53 19x 1,80 19x 2,17 37x 1,80 37x 2,03 37x 2,27 37x 2,52 61x 2,24 61x 2,52 Approx. diam. Max. resistance pr km 20°C ohm 1,16 0,734 0,529 0,391 0,270 0,195 0,154 0,126 0,100 0,0762 0,0607 90°C ohm 1,48 0,936 0,675 0,499 0,344 0,249 0,196 0,161 0,128 0,0972 0,0774

mmØ 5,2 6,5 7,4 8,8 10,3 12,1 13,6 15,1 16,8 19,1 21,5

*) Diameter of wires before compressing

www.drakaMOG.com

Subject to change without prior notice Page 82 of 96 2010-04-30

Wire gauge conversion table

US Standard cross-section to square millimetres

U.S. Standard

20 AWG 18 16 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 MCM 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1250 1500 1750 2000

Equivalent cross-section mm²

0.519 0.823 1.31 2.08 3.31 5.26 8.37 13.30 21.15 33.62 42.41 53.49 67.23 85.01 107.2 126.7 152.0 177.3 202.7 228.0 253.4 278.7 304.0 329.4 354.7 380.0 405.4 430.7 456.0 481.4 506.7 633.4 760.0 886.7 1013.4

Nearest available cross-section mm²

0.5 ­ 0.75 1.0 1.5 2.5 4 6 10 16 25 35 50 50 - 70 70 95 120 120 - 150 150 185 185 185-240 240 240 ­ 300 300 300 300 ­ 400 400 400 400 400 400 400 ­ 630 630 800 800 ­ 1000 1000

www.drakaMOG.com

Subject to change without prior notice Page 83 of 96 2010-04-30

Current ratings for 250V and 0,6/1kV cables in fixed installations.

Current carrying capacities in continuous service at maximum rated temperature of 90°C. In accordance with IEC 60092-352 (2005) Annex B, Table B.4. Ambient temperature 45°C Conductor area mm² 1 1,5 2,5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 1-core Amp 18 23 30 40 52 72 96 127 157 196 242 293 339 389 444 522 601 690 dc / 670 ac 780 dc / 720 ac 890 dc / 780 ac 2-core Amp 15 20 26 34 44 61 82 108 133 167 206 249 288 331 377 444 511 587 dc / 570 ac 663 dc / 612 ac 757 dc / 663 ac 3-4 core Amp 13 16 21 28 36 50 67 89 110 137 169 205 237 273 311 366 420 483 dc / 469 ac 546 dc / 504 ac 623 dc / 546 dc

For cables with more than 4 cores, the current ratings are given by the following formula:

I1 I= 3 N I1 = current rating for single core N = number of cores No. of cores 5 7 12 19 24 37 1,5 mm² Amp 13 12 10 9 8 7 2,5 mm² Amp 18 16 13 11 10 9

www.drakaMOG.com

Subject to change without prior notice Page 84 of 96 2010-04-30

Current rating for 1,8/3(3,6)kV, 3,6/6(7,2)kV, 6/10(12)kV, 8,7/15(17,5)kV, 12/20(24)kV and 18/30(36)kV cables in fixed installations.

Current carrying capacities in continuous service at maximum rated temperature of 90°C. In accordance with IEC 60092-352 (2005) Annex B, Table B.4. Conductor area mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630 1-core Amp 96 127 157 196 242 293 339 389 444 522 601 690 dc / 670 ac 780 dc / 720 ac 890 dc / 780 ac 2-core Amp 82 108 133 167 206 249 288 331 377 444 511 3-4 core Amp 67 89 110 137 169 205 237 273 311 366 420 -

The tabled current ratings must be adjusted for ambient air temperatures other than 45°C. Appropriate rating factors are: Ambient air temp. °C Rating factors 35 40 45 50 55 60 65 70 75 80

1,10 1,05 1,00 0,94 0,88 0,82 0,74 0,67 0,58 0,47

www.drakaMOG.com

Subject to change without prior notice Page 85 of 96 2010-04-30

Short circuit ratings

The following short circuit currents are for cables normally operating at a maximum conductor temperature of 90°C. The theoretical temperature that arises in the conductor during a short circuit, which is used as a basis of the calculation, is 250°C. EPR and XLPE insulation are capable of withstanding short term temperatures up to 250°C.The short circuit currents for copper conductors given in the table are values for one second, for other durations the current may be calculated from the following formula: I It = t It = short ciricut current for t sec. (Amp), l = short circuit current for one sec. (Amp), t = short circuit duration (sec.) The duration of the short circuit based on these assumptions should be between 0,2 sec. and 5 sec. Conductor area mm² Current 1 second amperes Conductor area mm² 70 95 120 150 185 240 300 400 500 630 Current 1 second amperes

1,0 1,5 2,5 4 6 10 16 25 35 50

140 210 350 560 840 1400 2240 3500 4900 7000

9800 13300 16800 21000 25900 33600 42000 56000 70000 88200

Reactance

The reactance of a cable operating in an AC system depends on many factors, including, in particular, the axial spacing between conductors and the proximity and magnetic properties of adjacent steelwork. The former is known for multicore cable, but may vary for single core cables depending upon the spacing between them and their disposition when installed. Reactance of cables in certain disposition when installed. Reactance of cables in certain dispositions remote from steelwork are calculable and are shown. The tabulated values are for cables with circular conductors. The value for a sector-shaped conductor should be taken as 90% of the calculated value. Induction for 2-, 3- and 4- conductor cables is given by the formula: 2a L = 0,2 * ( In ( ) + 0,25 ) * 10-6 d L = Induction in H/m and phase, a = Axial space between conductors in mm. d = conductor diameter in mm. Reactance for 2-, 3- and 4-conductor cables is given by the formula: X=2**f*L*I

www.drakaMOG.com

Subject to change without prior notice Page 86 of 96 2010-04-30

X = Reactance in ohm pr. Phase, f = frequency in Hz, L = Induction in H/m and phase I = Conductor length in meter.

Reactance Values for Cables

Power and control cables. RFOU 0,6/1 kV Cross2-, 3- and 4 cores section ohm/km mm² 1,5 2,5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 60 Hz 0,132 0,123 0,115 0,108 0,101 0,096 0,095 0,092 0,092 0,091 0,088 0,086 0,087 0,086 0,086 0,086 50 Hz 0,110 0,103 0,096 0,090 0,084 0,080 0,079 0,076 0,076 0,075 0,073 0,072 0,072 0,072 0,072 0,071

1- core* ohm/km 60 Hz 50 Hz

0,139 0,134 0,127 0,123 0,120 0,116 0,113 0,110 0,109 0,109 0,105

0,116 0,112 0,106 0,103 0,100 0,097 0,094 0,092 0,091 0,090 0,087

*) Reactance for 1-conductor cables given at Three- foil formation

Power and control cables, BFOU 0,6/1 kV. Cross- section 2-, 3- and 4 core ohm/km mm² 60 Hz 50 Hz 1,5 0,138 0,115 2,5 0,129 0,107 4 0,120 0,100 6 0,112 0,094 10 0,105 0,088 16 0,099 0,082 25 0,098 0,081 35 0,094 0,078 50 0,093 0,078 70 0,090 0,075 95 0,090 0,075 120 0,088 0,073 150 0,088 0,073 185 0,088 0,073 240 0,087 0,072 300 0,086 0,072

1- core* ohm/km 60 Hz 50 Hz

0,144 0,135 0,129 0,125 0,121 0,117 0,112 0,112 0,109 0,109 0,108

0,120 0,112 0,107 0,104 0,101 0,098 0,094 0,094 0,091 0,091 0,090

*) Reactance for 1-conductor cables given at Three- foil formation

www.drakaMOG.com

Subject to change without prior notice Page 87 of 96 2010-04-30

Medium Voltage Power cables. RFOU 6/10 kV Cross3 core 1- core* section ohm/km ohm/km mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630 50 Hz 60 Hz 0.119 0.119 0.114 0.108 0.103 0.098 0.095 0.092 0.092 0.087 0.084 0.143 0.143 0.137 0.130 0.124 0.118 0.114 0.111 0.111 0.104 0.101 50 Hz 60 Hz 0.154 0.144 0.138 0.132 0.125 0.119 0.116 0.111 0.108 0.104 0.104 0.090 0.097 0.092 0.185 0.173 0.166 0.158 0.150 0.142 0.139 0.133 0.130 0.125 0.124 0.118 0.117 0.110

*) Reactance for 1-conductor cables given at Three- foil formation

Medium Voltage Power cables. RFOU 12/20(24)kV. Cross3 core 1-core* section ohm/km ohm/km mm² 35 50 70 95 120 150 185 240 300 50 Hz 60 Hz 0.128 0.121 0.115 0.109 0.105 0.102 0.099 0.095 0.153 0.145 0.135 0.131 0.126 0.122 0.118 0.114 50 Hz 60 Hz 0.149 0.140 0.133 0.127 0.124 0.119 0.116 0.112 0.108 0.178 0.169 0.160 0.152 0.149 0.142 0.139 0.134 0.130

*) Reactance for 1-conductor cables given at Three- foil formation

Impedance

Induction for 2-, 3- and 4- conductor cables is given by the formula: Z = ( R2 + X2 ) Z = Impedansce in ohm pr. phase, X = Reactance in ohm pr. phase. R = Resistance at operating temprature in ohm pr. phase.

www.drakaMOG.com

Subject to change without prior notice Page 88 of 96 2010-04-30

Electrical characteristics for instrumentation and telecommunication cables such as 250 V cables: RFOU and BFOU according to IEC 60092-376

Cables with collective screen Capacitance, approx. Type (nF/km) Unshielded pair 0,75 mm² 100 Unshielded triple 0,75 mm² 100 Unshielded pair 1,5 mm² 110 Unshielded triple 1,5 mm² 110 Unshielded pair 2,5 mm² 125 Unshielded triple 2,5 mm² 125

Inductance, approx, (mH/km) 0,67 0,67 0,63 0,63 0,59 0,59

Resistance at 20°C, max. (Ohm/km) 26,3 26,3 12,9 12,9 8,02 8,02

L/R ratio, (microH/Ohm) 12,7 12,7 24,4 24,4 36,8 36,8

Cables with individually screened pair/triples Capacitance, approx. Type (nF/km) Shielded pair 0,75 mm² 110 Shielded triple 0,75 mm² 110 Shielded pair 1,5 mm² 125 Shielded triple 1,5 mm² 125 Shielded pair 2,5 mm² 145 Shielded triple 2,5 mm² 145

Inductance, approx, (mH/km) 0,67 0,67 0,63 0,63 0,59 0,59

Resistance at 20°C, max. (Ohm/km) 26,3 26,3 12,9 12,9 8,02 8,02

L/R ratio, (microH/Ohm) 12,7 12,7 24,4 24,4 36,8 36,8

www.drakaMOG.com

Subject to change without prior notice Page 89 of 96 2010-04-30

Material properties

Polymeric materials used in cables for ships and offshore topside installations For 30 years Draka Norsk Kabel has been facing the same challenge : The increasing severe performance criteria demands from our ship and offshore customers. Elastomers are the major part of our cable construction. The insulation, bedding and sheathing have been developed through intensive research and development to meet the offshore and ship industry's specific and stringent requirements. This information is not intended to give you details of the elastomers in use. For correct selection and application of materials our technical representatives will be pleased to provide you with more complete information.

EP - rubber (EPDM) EPDM is a hydrocarbon rubber that combines electrical performance suitable for fire resistant offshore cables with mechanical toughness and resistance to ozone, UV light and heat. It's wet electrical properties are unique. Applications : Wire insulation Bedding compounds

Flame retardant halogen-free termoset compound (EVA) EVA, ethylene vinyl acetate, is a multi-functional elastomer, which resists the combined deteriorating influences of heat, oil and weather. (In accordance with IEC 60092-359 type SHF2). For offshore applications, EVA can be compounded to produce high quality cable sheathing with low smoke and flame propagation, and with no emission of halogenous acids. Applications : Cable sheathing on offshore oil platforms, ships, hotels and in rooms with expensive equipment, which must not be subjected to corrosion damage. Low smoke , Flame retardant , Halogen-free and Thermoplastic compounds , HFFR. When PVC is not acceptable due to the problems chlorine (halogen) containing materials present in the event of a fire HFFR must be used. (In accordance with IEC 60092-359 type SHF1). Our HFFR materials will not propagate a fire along a cable run, drip or give off black smoke. No acid gases will be released during a fire that can corrode and damage expensive equipment. Applications: Cable sheating for Rooms with IT equipment high - rise buldings (hotels) hospitals Telephone exchanges subway systems, airports and many others. XLPE ­ Crosslinked Polyethylene

www.drakaMOG.com

Subject to change without prior notice Page 90 of 96 2010-04-30

Polyethylene is the most used plastic material. By introducing chemical bonding between the chains in PE we get XLPE, a thermoset type of PE. In cable insulation it is used for the excellent insulation properties , very good mechanical strength , low density and good thermal stability. Applications : Wire insulations

Physical and chemical properties of Draka's sheathing compounds for use in offshore topside and shipboard cables

Enhanced oil resistant EVA (SHF2) 3-4 5 4 3 3-4 3-4* NITRILE/PVC PVC HFFR (SHF1) 2-3 4-3 4 3 0 0

Mechanical properties Weathering (O2 -O3 ) Heat resistance Low temperature Hydrocarbons general Hydrocarbons high aromatic (MUD) Sea-water Fire resistant Oxygen Index Smoke generation Halogens

4 4 3 3 4 4

4 5 2-3 2 2 1

3 4 4(35) 5 No

4 3 3(28) 2 CI

4 4 4(32) 1 CI

3 4 4(35) 5 No

5 - Excellent, 4 - Very good, 3 - Good, 2 - Medium, 1 - Poor, 0 - Not recommended

* Drilling MUD is not one chemical, but a mix of different chemicals and each producer have their own composition. The sheathing material could be resistant to the aromatics in the MUD, but be affected by uther chemicals like corrosion inhibitors. Each MUD must therefore be tested for compatibility with the cable sheathing. The test method for this MUD test is descriebed in NEK TS 606: 2009 Fourth edition.

www.drakaMOG.com

Subject to change without prior notice Page 91 of 96 2010-04-30

SHF1 versus SHF2

The table below addresses only some main characteristics differences. For complete information see IEC60092-359 SHF1 Halogen-free Thermoplastic SHF2 Halogen-free Elastomeric or thermosetting material

Type of material

Some main characteristics Mechanical characteristics after immersion in hot oil (IEC 60811-2-1, clause 10)* * If oil resistance is required for a halogen-free compound, SHF 2 compound is recommended. No requirements 100 °C for 24 hours: · ±40% maximum variation in tensile strength: · ±40% maximum variation in elongation at break 200 °C, 15 min time under load with 20 (N/mm²) mechanical stress: · 175% Maximum elongation under load · 25% Maximum permanent elongation after cooling No requirements

Hot set test (IEC 60811-2-1, clause 9)

No requirements

Pressure test at high temperature IEC 60811-3-1, subclause 8.2)

80 °C, 4-6 min under load depending on cable diameter: · 50% Maximum permissible deformation 150 °C) 1h duration:

Heat shock test (IEC 60811-3-1, subclause 9.2) Ozone resistance test IEC 60811-2-1, clause 8 (Alternative test method may be used in some countries for legal reasons)

No requirements

No requirements

25 ± 2°C for 24 h: · Max 0,025 to 0,030 % ozone concentration (in volume)

www.drakaMOG.com

Subject to change without prior notice Page 92 of 96 2010-04-30

Core colours for cables according to NEK 606

Please look at the actual page for each cable type. Instrumentation and communications cable for fixed installation (conductor size from 0,75 mm² and above) such as RFOU, BFOU, RU and BU 250V. Pair: Black -- Light blue Triple: Black -- Light blue - Brown Pairs and triples are identified by numbered tape with printed black numbers or by numbers printed directly on the insulated conductors. Power and control cables for fixed installation, such as RFOU, BFOU, RU and BU 0,6/1kV One core: Two cores: Two cores + earth Three cores: Three cores + earth Four cores: Four cores + earth Five cores Above 5-cores : Black Blue ­ Brown Blue ­ Brown ­ Yellow/green Brown - Black ­ Grey Brown - Black ­ Grey ­ Yellow/green Blue - Brown - Black­ Grey Blue - Brown - Black­ Grey ­ Yellow/green Blue - Brown - Black­ Grey - Black

Black numbers on white base.

Colours are in accordance with IEC 60446 and Cenelec HD 308S2

Medium Voltage cables for fixed installation, RFOU 1-core : Off-white insulation + black semi-conductive layer. 3-cores : Off-white insulation + black semi-conductive layer identified by White-Black-Red threads under and over the metallic screen on each individual core. Separate earth conductor (if any): Yellow/green

www.drakaMOG.com

Subject to change without prior notice Page 93 of 96 2010-04-30

Drum capacity in meters

Free space mm. Drum No:

Overall cable diam.mm

10 12 14 360 250 185 720 500 370 850 565 425 1470 1020 770 1440 1105 1520 R5 R6 R6T R8 R9 R10 R10A R11 R12 R14 R14A R16 R16A R18 R20 R22 R24 R26

Free 30 30 30 30 30 30 30 40 50 60 60 60 60 70 70 80 90 100 space mm Drum No: Overall cable diam.mm

10 12 14

16 18 20 22 24

280

550 450 375

825 620 510 420 340

1160 920 745 615 515 570 460 380 320

1335 1010 850 700 580 1510 1100 885 830 1565 1925 1075 1065 880 740 1645 1380 870

16 18 20 22 24

26 28 30 32 34

440 380 330

270 235 205 180 160

470 440 345 330

685 555 525 410 395

905 745 705 560 545

630 540 470 415 370

1175 985 930 755 735

740 635 555 490 430

1485 1255 1045 980 825 1685 1375 1300 1105 1565 1350

26 28 30 32 34

36 38 40 42 44

140 130 115

370 285

420 405 390 300 285

330 295 265 240 220

580 560 445 430 410

385 345 310 285 260

765 630 605 485 460

1035 860 830 640 620

1265 1070 1035 820 790 1570 1355 1255 1065 2060 1870 1700

36 38 40 42 44

46 48 50 52 54

200 185 170 160 145

390 315 300 285 285

235 215 200 185 170

440 445 340 320 320

595 595 460 440 420

760 635 605 580 550

1025 895 855 820 665

1560 1430 1320 1220 1130

46 48 50 52 54

56 58 60 62 64

135 125 120

160 150 140 130 120

300 300 215 215

420 420 400 310 290

445 425 425 400 405

670 635 640 500 500

1050 980 915 860 805

56 58 60 62 64

66 68 70 72 74

115 110 100

290 275 275 255 260

380 295 275 275 275

475 475 445 360 360

755 715 675 635 600

66 68 70 72 74

76 78

255 255

335 335

570 540

76 78

www.drakaMOG.com

Subject to change without prior notice Page 94 of 96 2010-04-30

Code designation for cables

A cable code of 2 - 4 letters is used to descriebe the construction. Additional abbrevation for instrumentation cables: Collective screen = (c) Individual pair or triple screen = (i) The interpretation ( per letter) can be read from the table below:

1st. letter: Insulation A B C Fibre, tight cladded Fire resistant tape + insulation (Halogen-free) Polychloroprene (Neoprene) PCP, or chlorinated polyethylene CPE D Impregnated paper Drip free E Polyethylene - PE Polypropylene - PP F G H I K L M N O P Q R S T U V PE or PP + filling compound Polyamid - PA Chlorosulphonated polyethylene - CSP Thermoplastic compound (Halogen-free) Paper Air + plastics (Coaxial cable) Expanded PE or PP + filling compound Impregnated paper Impregnated paper, oilfilled cable Polyvinylchloride - PVC Fibre in loose tube Ethylenepropylene rubber EPR Silicone rubber Cross-linked polyethylene XLPE Halogen-free thermoset compound EMA or EVA Fibre, slotted core V U S T P Q R Ethylenepropylene rubber EPR Bedding or taping + concentric conductor PE + aluminium wire + steel tape Halogen-free thermoset compound EMA or EVA Aluminium screen V Double wire armour (two layers) V U U T S Polyvinylchloride - PVC P Q R N O Polyurethane Lead + Plastics N O Steel (laminated to outer jacket) Copper wire braid (Tinned or bare) Phosphorbronze wire braid Steel wires + counter steel tape (optional) Steel wires (round) + filling compound Concentric conductor (Screen) T Cross-linked polyethylene XLPE Halogen-free thermoset compound EMA or EVA Other halogen-free thermoset materials S R Ethylenepropylene rubber - EPR Silicone rubber Q P Polyvinylchloride - PVC O N Polyurethane M K L I G H Chlorosulphonated polyethylene - CSP Thermoplastic compound (Halogen-free) Lead Aluminium laminate + plastics sheath Polyester M K L Steel wire, plastics or rubber coated Aluminium (laminated to outer jacket) M Polyester L K I F E Polyethylene - PE Polypropylene - PP Bedding or taping (Halogen-free) G H Steel tape + steel wires Steel tapes, 4 off I G H PE + PA Chlorosulphonated polyethylene - CSP Thermoplastic compound (Halogen-free) Lead F E D C A B 2nd. letter Bedding / inner sheath Aluminium (optional with corrosion protection) Corrogated aluminium (o.w.c.p.) Polychloroprene (Neoprene) PCP, or chlorinated polyethylene CPE Aluminium + Plastics D Oil filled cable reinforcement (Longitudinal / Transverse) Oil filled cable reinforcement (Transverse only) Flat steel wire armour F Semi-conducting PE E Polyethylene - PE Polypropylene - PP D C Galvanized steel wire braid C B Steel tapes, 2 off B Hydrocarbon resistant sehath Polychloroprene (Neoprene) PCP, or chlorinated polyethylene CPE A 3rd. letter Armouring / screen Strength member yarn A 4th. letter Outer sheath Yarn + bitumen

www.drakaMOG.com

Subject to change without prior notice Page 95 of 96 2010-04-30

1st. letter: Insulation W X Y Z Flour plastics PTFE / FEP Other materials No insulation W X Y Z

2nd. letter Bedding / inner sheath Other materials No bedding or equivalent Screen Flour plastics W X Y Z

3rd. letter Armouring / screen Catenary wire No armour W X Y Z

4th. letter Outer sheath Other materials No sheath

Flour plastics

www.drakaMOG.com

Subject to change without prior notice Page 96 of 96 2010-04-30

Information