RS485 ­ JBUS/MODBUS®

Operating instructions

DIRIS A40/A41

F

GB

D

I

NL

E

P

OM C

ON

1

SOCOMEC GROUP SWITCHING PROTECTION & UPS

Systèmes de Coupure et de Protection Industrial Switching and Protection Systems

2

SOCOMEC - Réf. : CDR 27 038_gb

GB

Contents

PRELIMINARY OPERATIONS ________________________________________________4 GENERAL INFORMATION _______________________________________________4 INSTALLATION _____________________________________________________________5 CONNECTION _________________________________________________________5 PROGRAMMING ___________________________________________________________6 COMMUNICATION ADDRESS ___________________________________________7 COMMUNICATION SPEED ______________________________________________7 COMMUNICATION PARITY______________________________________________8 COMMUNICATION STOP BIT ___________________________________________8 COMMUNICATION _________________________________________________________9 THE STANDARD COMMUNICATIONS FRAME _____________________________9 LIST OF PARAMETERS TO BE DISPLAYED ______________________________10 Table of values with allocated current and voltage winf-ding ratios on 2 words____________10 Address available with the Monitoring or Control/Command option______________________11 Instant value display _______________________________________________________________12 Table of values without allocated current and voltage winding ratios on 1 word ___________13 Alarm event log ___________________________________________________________________16 Table of current and voltage harmonics ______________________________________________30 Option recognition table____________________________________________________________33 LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED ___________34 RESET TO ZERO: ENERGY METERS AND MAX. VALUES _________________43 SAVED COMMAND ___________________________________________________44 PULSE METERS VALUES ______________________________________________44 DATE AND HOUR SETTINGS___________________________________________45 LAST 10 ALARMS EVENT LOG _________________________________________45 LAST 10 VOLTAGE DIPS EVENT LOG / SAG _____________________________59 LAST 10 VOLTAGE SURGE EVENT LOG / SWELL ________________________64 MINIMUM AND MAXIMUM INSTANTANEOUS VALUES ____________________69 LAST 10 VOLTAGE CUT-OFFS EVENT LOG / SAG ________________________73 MEAN POWER EVENT LOG ____________________________________________75 MEAN VOLTAGE EVENT LOG __________________________________________75 MEAN FREQUENCY EVENT LOG _______________________________________75 TECHNICAL CHARACTERISTICS ___________________________________________76 GLOSSARY OF ABBREVIATIONS ___________________________________________76

SOCOMEC - Réf. : CDR 27 038_gb

3

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

PRELIMINARY OPERATIONS

For personnel and product safety please read the contents of these operating instructions carefully before connecting. Check the following points as soon as you receive the DIRIS A40/A41 package: · the packing is in good condition, · the product has not been damaged during transit,

· the product reference number conforms to your order, · the package contains the product and the operating instructions.

GENERAL INFORMATION

Functions

The optional IP Communication module must be connected to the DIRIS A40/A41 (réf. : 4825 0A40, 4825 0A41, 4825 1A40, 4525 1A41). It provides an RS485 serial link (2 or 3 wires) with JBUS/MODBUS® protocol for the use of DIRIS A40/A41 from a PC or PLC.

General points

For a standard configuration, an RS 485 link is used to connect up to 31 DIRIS or COUNTIS Ci with a PC or a PLC over a distance of 1200 metres, using JBUS/MODBUS© protocol.

1200 M

R = 120

N1

N2

Nn R = 120

DIRIS 109 E GB

Programmable controllers Other systems

1200 M

1200 M

R = 120

N1

0+- -+0 repetor RS485

Nn R = 120

DIRIS 110 E GB

Programmable controllers Other systems

Recommendations: You should use a shielded twisted pair (LIYCY type). In a disturbed environment or large network (in terms of length) we recommend the use of a shielded twisted pair (type LIYCY-CY). A repeater (1 channel) or an arrestor (4 channels) should be used if you intend to exceed the distance (1200 m) and/or maximum number (31) of DIRIS. Please contact us for more information.

NB : A 120 ohm resistance (found on the additional module) must be fixed at both ends of the link. Other solutions are available (modem, optical fibre, etc.). Please contact us.

4

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

INSTALLATION

CONNECTION

The module is fitted onto the back of the DIRIS A40/A41 in one of the 4 positions provided.

The DIRIS A40/A41 must be switched off

GB

Fix the module in one of the four positions.

DIRIS 342 A DIRIS 343 A

Follow indications when connecting the terminal. Switch on voltage supply.

O R= N 1 12 0

0V

-+

DIRIS 347 A

ON

1

SOCOMEC - Réf. : CDR 27 038_gb

5

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

PROGRAMMING

Previous menu

p.81

p.81

p.82

p.82

Following menu

6

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® PROGRAMMATION

COMMUNICATION ADDRESS > Example : COM ADR = 7

x3

x2

x1 confirm

COMMUNICATION SPEED > Example : BDS = 19200 bauds

x1

x1

x1 confirm

SOCOMEC - Réf. : CDR 27 038_gb

7

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

PROGRAMMATION

COMMUNICATION PARITY > Example : PAR = Even

x1

x 1 (Odd) x 2 (Even) x 3 (No)

x1 confirm

COMMUNICATION STOP BIT > Example : STOP = 2

x1

x 1 (2 bits) x 2 (1 bits)

x1 confirm

8

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

The JBUS/MODBUS® used by the DIRIS A40/A41 The mode of communication is the RTU (Remote involves a dialogue using a master-slave hierarchical Terminal Unit) using hexadecimal characters of at least 8 bits. structure. There are two possible dialogues: · the master communicates with a slave (DIRIS) and waits for its reply · the master communicates with all the slaves (DIRIS) without waiting for their reply.

THE STANDARD COMMUNICATIONS FRAME

The standard communications frame consists of:

Slave address Function code Address Data CRC 16

According to the JBUS/MODBUS® protocol, transmission time must be less than 3 silences, i.e. the emission time of 3 characters so that the message is processed by the DIRIS. To correctly use information, the following functions are important: 3 : to read n words (maximum 128). 6 : to write one word. 8 : to diagnose exchanges between the master and the slave via meters 1, 3, 4, 5 and 6. 16 : to write n words (maximum 128).

NB: When selecting slave address 0, a message is sent to all the instruments present on the network (only for functions 6 and 16). Comment : The response time (time out question/answer) is 250 ms maximum

SOCOMEC - Réf. : CDR 27 038_gb

9

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Table of values with allocated current and voltage winf-ding ratios on 2 words Decimal Hexa. Number Text address address of words 768 300 2 Phase 1 current 770 302 2 Phase 2 current 772 304 2 Phase 3 current 774 306 2 Neutral current 776 308 2 Phase to phase voltage U12 778 30A 2 Phase to phase voltage U23 780 30C 2 Phase to phase voltage U31 782 30E 2 Phase to neutral voltage phase 1 784 310 2 Phase to neutral voltage phase 2 786 312 2 Phase to neutral voltage phase 3 788 314 2 Frequency 790 316 2 active power +/792 318 2 reactive power +/794 31A 2 apparent power 796 31C 2 power factor -: leading and +: lagging 798 31E 2 Active power phase 1 +/800 320 2 Active power phase 2 +/802 322 2 Active power phase 3 +/804 324 2 Reactive power phase 1 +/806 326 2 Reactive power phase 2 +/808 328 2 Reactive power phase 3 +/810 32A 2 Apparent power phase 1 812 32C 2 Apparent power phase 2 814 32E 2 Apparent power phase 3 816 330 2 Power factor phase 1 -: leading and +: lagging 818 332 2 Power factor phase 2 -: leading and +: lagging 820 334 2 Power factor phase 3 -: leading and +: lagging 822 336 2 avg I1 824 338 2 avg I2 826 33A 2 avg I3 828 33C 2 avg active power + 830 33E 2 avg active power 832 340 2 avg reactive power + 834 342 2 avg reactive power 836 344 2 avg apparent power 838 346 2 max/avg I1 840 348 2 max/avg I2 842 34A 2 max/avg I3 844 34C 2 max/avg active power + 846 34E 2 max/avg active power 848 350 2 max/avg reactive power + 850 352 2 max/avg reactive power 852 354 2 max/avg apparent power 854 356 2 hour meter 856 358 2 Active energy + 858 35A 2 Reactive energy + 860 35C 2 Apparent energy 862 35E 2 Active energy 864 360 2 Reactive energy Unit mA mA mA mA V/100 V/100 V/100 V/100 V/100 V/100 Hz/100 kW/100 kvar/100 kVA/100 0.001 kW/100 kW/100 kW/100 kvar/100 kvar/100 kvar/100 kVA/100 kVA/100 kVA/100 0.001 0.001 0.001 mA mA mA kW/100 kW/100 kvar/100 kvar/100 kVA/100 mA mA mA kW/100 kW/100 kvar/100 kvar/100 kVA/100 1/100 h kWh kvarh kVAh kWh kvarh

10

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Address available with the Monitoring or Control/Command option Decimal Hexa. Number Text address address of words 866 362 2 Input pulse meter 1 868 364 2 Input pulse meter 2 870 366 2 Number of impulse meters 872 368 2 Current alarm : 0 : no alarm 1:I 2:U 3: P+ 4: Q+ 5: S 6: F 7 : PFL 8 : thd I 9 : thd U 10 : In 11 : HOUr 12 : V 13 : thd In 14 : thd V 15 : P16 : Q17 : PFC 874 36A 2 Current overrun : 0 : no alarm 1:I 2:U 3: P+ 4: Q+ 5: S 6: F 7 : PFL 8 : thd I 9 : thd U 10 : In 11 : HOUr 12 : V 13 : thd In 14 : thd V 15 : P16 : Q17 : PFC 876 36C 2 Number of inputs-outputs Low-order: number of inputs High-order: number of outputs 878 36E 2 Status of inputs-outputs 0 : status input 1 (0 = open, 1 = closed) bit 1 : status input 2 (0 = open, 1 = closed) bit 2 : status input 3 (0 = open, 1 = closed) bit 3 : status input 4 (0 = open, 1 = closed) bit 4 : status input 5 (0 = open, 1 = closed) bit 5 : status input 6 (0 = open, 1 = closed) bit 16 : status output 1 (0 = open, 1 = closed) bit 17 : status output 2 (0 = open, 1 = closed) bit 18 : status output 3 (0 = open, 1 = closed) bit 19 : status output 4 (0 = open, 1 = closed) bit 20 : status output 5 (0 = open, 1 = closed) bit 21 : status output 6 (0 = open, 1 = closed) Unit ­ ­ ­ ­

­

­

SOCOMEC - Réf. : CDR 27 038_gb

11

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Instant value display Decimal Hexa. address address 880 370 882 372 884 374 886 376 888 378 890 37A 892 37C 894 37E 896 380 898 382 900 384 902 386 904 388 906 38A 908 38C 910 38E 912 390 914 392 916 394 918 396 920 398 922 39A 924 39C Number of words 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Text System value for current System value for phase-to-phase voltage System value for phase-to-neutral voltage avg U12 avg U23 avg U31 avg V1 avg V2 avg V3 avg F max/avg U12 max/avg U23 max/avg U31 max/avg V1 max/avg V2 max/avg V3 max/avg F avg In max/avg In Mean positive active power between 2 signals Mean negative active power between 2 signals Mean positive reactive power between 2 signals Mean negative reactive power between 2 signals Unit mA V/100 V/100 V/100 V/100 V/100 V/100 V/100 V/100 Hz/100 V/100 V/100 V/100 V/100 V/100 V/100 Hz/100 mA mA 0.1 kW 0.1 kW 0.1 kvar 0.1 kvar

Zone size: 158 words (decimal) or 9E (hexadecimal). Example: To display all the values for DIRIS number 5 in one inquiry, the following frame should be sent: High-order address

03

Slave

05

Function

03

Low-order address

00

High-order word n°

00

Low-order word n°

9E

CRC 16

C5A7

12

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Table of values without allocated current and voltage winding ratios on 1 word Decimal address 1792 1793 1794 1795 1796 1797 1798 1799 1800 1801 1802 1803 1804 1805 1806 1807 1808 1809 1810 1811 1812 1813 1814 1815 1816 1817 1818 1819 1820 1821 1822 1823 1824 1825 1826 1827 1828 1829 1830 1831 1832 1833 1834 1835 Hexa. address 700 701 702 703 704 705 706 707 708 709 70A 70B 70C 70D 70E 70F 710 711 712 713 714 715 716 717 718 719 71A 71B 71C 71D 71E 71F 720 721 722 723 724 725 726 727 728 729 72A 72B Number of words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Text Phase 1 current Phase 2 current Phase 3 current Neutral current Phase to phase voltage U12 Phase to phase voltage U23 Phase to phase voltage U31 Phase to neutral voltage phase 1 Phase to neutral voltage phase 2 Phase to neutral voltage phase 3 Frequency active power +/ reactive power +/ apparent power +/ power factor L/C -: leading and +: lagging Active power phase 1 +/Active power phase 2 +/Active power phase 3 +/Reactive power phase 1 +/Reactive power phase 2 +/Reactive power phase 3 +/Apparent power phase 1 Apparent power phase 2 Apparent power phase 3 Power factor phase 1 L/C -: leading and +: lagging Power factor phase 2 L/C -: leading and +: lagging Power factor phase 3 L/C -: leading and +: lagging avg I1 avg I2 avg I3 avg active power + avg active power avg reactive power + avg reactive power avg apparent power max/avg I1 max/avg I2 max/avg I3 max/avg active power + max/avg active power max/avg reactive power + max/avg reactive power max/avg apparent power Active energy + < 10000 Unit mA mA mA mA V/10 V/10 V/10 V/10 V/10 V/10 Hz/100 W var kVA 0.001 W W W W var var VA VA VA 0.001 0.001 0.001 mA mA mA W W var var VA mA mA mA W W var var VA kWh

SOCOMEC - Réf. : CDR 27 038_gb

13

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Decimal address 1836 1837 1838 1839 1840 1841 1842 1843 1844 1845 1846 1847 1848 1849 1850 1851 1852 1853 1854 1855 1856 1857 1858 1859 1860 1861 1862 1863 1864 1865 1866 1867 1868 1869 1870 1871 1872 1873 1874 1875 1876 1877 1878 1879 1880 1881 1882 1883 Hexa. address 72C 72D 72E 72F 730 731 732 733 734 735 736 737 738 739 73A 73B 73C 73D 73E 73F 740 741 742 743 744 745 746 747 748 749 74A 74B 74C 74D 74E 74F 750 751 752 753 754 755 756 757 758 759 75A 75B Number of words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Text Active energy + > 10000 Reactive energy + < 10000 Reactive energy + > 10000 Apparent energy < 10000 Apparent energy > 10000 Active energy - < 10000 Active energy - >10000 Reactive energy - < 10000 Reactive energy - > 10000 Input pulse meter 1 < 10000 Input pulse meter 1 > 10000 Input pulse meter 2 < 10000 Input pulse meter 2 > 10000 Input pulse meter 3 < 10000 Input pulse meter 3 > 10000 Input pulse meter 4 < 10000 Input pulse meter 4 > 10000 Input pulse meter 5 < 10000 Input pulse meter 5 > 10000 Input pulse meter 6 < 10000 Input pulse meter 6 > 10000 Average value of currents Average value of phase to phase voltages Average value of phase to neutral voltages avg U12 avg U23 avg U31 avg V1 avg V2 avg V3 avg F max/avg U12 max/avg U23 max/avg U31 max/avg V1 max/avg V2 max/avg V3 max/avg F thd I1 thd I2 thd I3 thd In thd U12 thd U23 thd U31 thd V1 thd V2 thd V3 Unit kWh kvarh kvarh kVAh kVAh kWh kWh kvarh kvarh ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ mA V/10 V/10 V/10 V/10 V/10 V/10 V/10 V/10 Hz/100 V/10 V/10 V/10 V/10 V/10 V/10 Hz/100 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%

14

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Decimal address 1884 1885 1886 1887 1888 1889 1890 1891 Hexa. address 75C 75D 75E 75F 760 761 762 763 Number of words 1 1 1 1 1 1 1 1 Text Mean positive active power between 2 signals Mean negative active power between 2 signals Mean positive reactive power between 2 signals Mean negative reactive power between 2 signals Reserved Reserved Average values In In max Unit W W var var ­ ­ mA mA

Zone size: 100 words (decimal) or 64 (hexadecimal). Example : To read 177 645 kWh, the following message should be sent : Slave

05

Function

03

High-order address

07

Low-order address

2B

High-order word n°

00

Low-order word n°

02

CRC 16

B4F3

DIRIS A40/A41 reply:

Slave

05

Function

03

Number of bytes

04

Word 1 < 10000

IDDD 7645

Word 2 > 10000

11 17

CRC 16

6FD6

Example: To display all the values for DIRIS number 5 in one inquiry, the following frame should be sent:

Slave

05

Function

03

High-order address

07

Low-order address

00

High-order word n°

00

Low-order word n°

64

CRC 16

44D1

SOCOMEC - Réf. : CDR 27 038_gb

15

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log Decimal address 1280 Hexa. address 500 Number of words 1 Text Current alarm OUT 1 lower threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Current alarm OUT 1 lower threshold value Current alarm OUT 1 upper threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 Unit ­

1281 1283

501 503

2 1

­ ­

16

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address Hexa. address Number of words Text 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Current alarm OUT 1 upper threshold value Duration Alarm 1 OUT 1 ower threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Alarm 1 OUT 1ower threshold value Alarm 1 OUT 1 threshold value: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ Unit

1284 1286 1287

504 506 507

2 1 1

­ s. ­

1288 1290

508 50A

2 1

­ ­

SOCOMEC - Réf. : CDR 27 038_gb

17

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address Hexa. address Number of words Text 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Alarm 1 OUT 1 upper threshold value Duration Alarm 2 OUT 1 lower threshold 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Alarm 2 OUT 1 lower threshold value Unit

1291 1293 1294

50B 50D 50E

2 1 1

­ s. ­

1295

50F

2

­

18

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address 1297 Hexa. address 511 Number of words 1 Text Alarm 2 OUT 1 threshold value: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Alarm 2 OUT 1 upper threshold value Duration Alarm 3 OUT 1 lower threshold 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR Unit ­

1298 1300 1301

512 514 515

2 1 1

­ s. ­

SOCOMEC - Réf. : CDR 27 038_gb

19

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address Hexa. address Number of words Text 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Alarm 3 OUT 1ower threshold value Alarm 3 OUT 1 threshold value: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Alarm 3 OUT 1 upper threshold value Duration Current alarm OUT 2 lower threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ Unit

1302 1304

516 518

2 1

­ ­

1305 1307 1308

519 51B 51C

2 1 1

­ s. ­

20

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address Hexa. address Number of words Text 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Current alarm OUT 2 lower threshold value Current alarm OUT 2 upper threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Current alarm OUT 2 upper threshold value Unit

1309 1311

51D 51F

2 1

­ ­

1312

520

2

­

SOCOMEC - Réf. : CDR 27 038_gb

21

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address 1314 1315 Hexa. address 522 523 Number of words 1 1 Text Duration Alarm 1 OUT 2 lower threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Alarm 1 OUT 2 lower threshold value : Alarm 1 OUT 2 upper threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR Unit s. ­

1316 1318

524 526

2 1

­

22

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address Hexa. address Number of words Text 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Alarm 1 OUT Duration Alarm 2 OUT 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Alarm 2 OUT Alarm 2 OUT 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ Unit

1319 1321 1322

527 529 52A

2 1 1

2 upper threshold value 2 lower threshold:

­ s.

1323 1325

52B 52D

2 1

2 lower threshold value 2 upper threshold:

­ ­

SOCOMEC - Réf. : CDR 27 038_gb

23

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address Hexa. address Number of words Text 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Alarm 2 OUT 2 upper threshold value Duration Alarm 3 OUT 2 lower threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Unit

1326 1328 1329

52E 530 531

2 1 1

­ s

24

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address 1330 1332 Hexa. address 532 534 Number of words 2 1 Text Alarm 3 OUT 2 lower threshold value Alarm 3 OUT 2 upper threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Alarm 3 OUT 2 upper threshold value Duration Status inputs 1 and 2 plus 3, 4, 5, 6 Current alarm OUT 3 lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 Unit ­

1333 1335 1336 1337

535 537 538 539

2 1 1 1

­ s. ­

SOCOMEC - Réf. : CDR 27 038_gb

25

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address Hexa. address Number of words Text 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Current alarm Current alarm 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Current alarm Duration Current alarm 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 Unit

1338 1340

53A 53C

2 1

OUT 3 lower threshold value OUT 3 upper threshold:

­ ­ ­

1341 1343 1344

53D 53F 540

2 1 1

OUT 3 upper threshold value OUT 4 lower threshold :

­ s.

26

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address Hexa. address Number of words Text 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Current alarm OUT 4 lower threshold value Current alarm OUT 4 upper threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Current alarm OUT 4 upper threshold value Unit

1345 1347

541 543

2 1

­ ­ ­

1348

544

2

­

SOCOMEC - Réf. : CDR 27 038_gb

27

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address 1350 1351 Hexa. address 546 547 Number of words 1 1 Text Duration Current alarm OUT 5 lower threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Current alarm OUT 5 lower threshold value Current alarm OUT 5 upper threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 Unit s. ­

1352 1354

548 54A

2 1

­

28

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address Hexa. address Number of words Text 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Current alarm Duration Current alarm 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Current alarm Current alarm 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F Unit

1355 1357 1358

54B 54D 54E

2 1 1

OUT 5 upper threshold value OUT 6 lower threshold :

­ s. ­

1359 1361

54F 551

2 1

OUT 6 lower threshold value OUT 6 upper threshold:

­ ­

SOCOMEC - Réf. : CDR 27 038_gb

29

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Alarm event log (continued) Decimal address Hexa. address Number of words Text 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Current alarm OUT 6 upper threshold value Duration Unit

1362 1364

552 554

2 1

­ s.

Table of current and voltage harmonics Decimal address 2304 2305 2306 2307 2308 2309 2310 2311 2312 2313 2314 2315 2316 2317 2318 2319 2320 2321 2322 2323 2324 2325 2326 2327 2328 2329 2330 2331 2332 Hexa. address 900 901 902 903 904 905 906 907 908 909 90A 90B 90C 90D 90E 90F 910 911 912 913 914 915 916 917 918 919 91A 91B 91C Number of words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Text thd I1 thd I2 thd I3 thd In thd U12 thd U23 thd U31 thd V1 thd V2 thd V3 Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Unit 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%

I1 row 3 I2 row 3 I3 row 3 IN row 3 I1 row 5 I2 row 5 I3 row 5 IN row 5 I1 row 7 I2 row 7 I3 row 7 IN row 7 I1 row 9 I2 row 9 I3 row 9 IN row 9 I1 row 11 I2 row 11 I3 row 11

30

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Table of current and voltage harmonics (continued) Decimal address 2333 2334 2335 2336 2337 2338 2339 2340 2341 2342 2343 2344 2345 2346 2347 2348 2349 2350 2351 2352 2353 2354 2355 2356 2357 2358 2359 2360 2361 2362 2363 2364 2365 2366 2367 2368 2369 2370 2371 2372 2373 2374 2375 2376 2377 2378 2379 2380 2381 2382 2383 2384 2385 2386 2387 2388 Hexa. address 91D 91E 91F 920 921 922 923 924 925 926 927 928 929 92A 92B 92C 92D 92E 92F 930 931 932 933 934 935 936 937 938 939 93A 93B 93C 93D 93E 93F 940 941 942 943 944 945 946 947 948 949 94A 94B 94C 94D 94E 94F 950 951 952 953 954 Number of words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Text Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic IN row 11 I1 row 13 I2 row 13 I3 row 13 IN row 13 I1 row 15 I2 row 15 I3 row 15 IN row 15 U12 row 3 U23 row 3 U31 row 3 U12 row 5 U23 row 5 U31 row 5 U12 row 7 U23 row 7 U31 row 7 U12 row 9 U23 row 9 U31 row 9 U12 row 11 U23 row 11 U31 row 11 U12 row 13 U23 row 13 U31 row 13 U12 row 15 U23 row 15 U31 row 15 V1 row 3 V2 row 3 V3 row 3 V1 row 5 V2 row 5 V3 row 5 V1 row 7 V2 row 7 V3 row 7 V1 row 9 V2 row 9 V3 row 9 V1 row 11 V2 row 11 V3 row 11 V1 row 13 V2 row 13 V3 row 13 V1 row 15 V2 row 15 V3 row 15 I1 row 17 I2 row 17 I3 row 17 IN row 17 I1 row 19 Unit 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%

SOCOMEC - Réf. : CDR 27 038_gb

31

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Table of current and voltage harmonics Decimal Hexa. Number Text address address of words 2389 955 1 Harmonic I2 row 19 2390 956 1 Harmonic I3 row 19 2391 957 1 Harmonic IN row 19 2392 958 1 Harmonic I1 row 21 2393 959 1 Harmonic I2 row 21 2394 95A 1 Harmonic I3 row 21 2395 95B 1 Harmonic IN row 21 2396 95C 1 Harmonic I1 row 23 2397 95D 1 Harmonic I2 row 23 2398 95E 1 Harmonic I3 row 23 2399 95F 1 Harmonic IN row 23 2400 960 1 Harmonic I1 row 25 2401 961 1 Harmonic I2 row 25 2402 962 1 Harmonic I3 row 25 2403 963 1 Harmonic IN row 25 2404 964 1 Harmonic U12 row 17 2405 965 1 Harmonic U23 row 17 2406 966 1 Harmonic U31 row 17 2407 967 1 Harmonic U12 row 19 2408 968 1 Harmonic U23 row 19 2409 969 1 Harmonic U31 row 19 2410 96A 1 Harmonic U12 row 21 2411 96B 1 Harmonic U23 row 21 2412 96C 1 Harmonic U31 row 21 2413 96D 1 Harmonic U12 row 23 2414 96E 1 Harmonic U23 row 23 2415 96F 1 Harmonic U31 row 23 2416 970 1 Harmonic U12 row 25 2417 971 1 Harmonic U23 row 25 2418 972 1 Harmonic U31 row 25 2419 973 1 Harmonic V1 row 17 2420 974 1 Harmonic V2 row 17 2421 975 1 Harmonic V3 row 17 2422 976 1 Harmonic V1 row 19 2423 977 1 Harmonic V2 row 19 2424 978 1 Harmonic V3 row 19 2425 979 1 Harmonic V1 row 21 2426 97A 1 Harmonic V2 row 21 2427 97B 1 Harmonic V3 row 21 2428 97C 1 Harmonic V1 row 23 2429 97D 1 Harmonic V2 row 23 2430 97E 1 Harmonic V3 row 23 2431 97F 1 Harmonic V1 row 25 2432 980 1 Harmonic V2 row 25 2433 981 1 Harmonic V3 row 25 Size of this zone : 130 words (decimal) or 82 (hexadecimal) Unit 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%

32

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Option recognition table Decimal address 257 258 Hexa. address 101 102 Number of words 1 1 Text Unit ­ ­

Product code Slot option 1 0xFF : no option 0x00 : communication option 0x01 : metering option 0x03 : metering and harmonics option 0x20 : inputs/outputs option 0x30 : analog outputs option 0x40 : memory option 0x50 : Profibus option 0xF0 : presence of IN measure 259 103 1 Slot option 2 260 104 1 Slot option 3 261 105 1 Slot option 4 262 106 1 Version number 263 107 2 Serial number Size of this zone : 8 words (decimal) or 8 (hexadecimal)

­ ­ ­ ­ ­

SOCOMEC - Réf. : CDR 27 038_gb

33

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)

Decimal address 512 Hexa. address 200 Number of words 1 Text Network type: 0 : 1BL 1 : 2BL 2 : 3BL 3 : 3NBL 4 : 4BL 5 : 4NBL CT secondary : 1:1A 5:5A CT primary Voltage input on PT: 0 : No 1: Yes PT primary PT secondary: 60 : 60 V 100 : 100 V 110 : 110 V 115 : 115 V 120 : 120 V 173 : 173 V 190 : 190 V Synchronisation of I AVG/MAX: Time in seconds, possible values 2 : 2 seconds 10 : 10 seconds 300 : 5 minutes (5x60s) 480 : 8 minutes (8x60s) 600 : 10 minutes (10x60s) 900 : 15 minutes (15x60s) 1200 : 20 minutes (20x60s) 1800 : 30 minutes (30x60s) 3600 : 60 minutes (60x60s) Synchronisation of P/Q/S AVG/MAX: Time in seconds, possible values 10 : 10 seconds 300 : 5 minutes (5x60s) 480 : 8 minutes (8x60s) 600 : 10 minutes (10x60s) 900 : 15 minutes (15x60s) 1200 : 20 minutes (20x60s) 1800 : 30 minutes (30x60s) 3600 : 60 minutes (60x60s) OUT 1 allocation of the pulse output: 0 : kWh + 1 : kvarh + 2 : kVAh 3 : kWh 4 : kvarh OUT1 impulse value: 0 : 0.1 kWh/kvarh/kVAh 1 : 1 kWh/kvarh/kVAh 2 : 10 kWh/kvarh/kVAh Unit ­

513 514 515 516 518

201 202 203 204 206

1 1 1 2 1

A A ­ V V

519

207

1

s

520

208

1

s

521

209

1

­

522

20A

1

­

34

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)

Decimal address Hexa. address Number of words Text 3 : 100 kWh/kvarh/kVAh 4 : 1000 kWh/kvarh/kVAh 5 : 10000 kWh/kvarh/kVAh OUT 1 impulse duration: 1 : 100 ms 2 : 200 ms 3 : 300 ms 4 : 400 ms 5 : 500 ms 6 : 600 ms 7 : 700 ms 8 : 800 ms 9 : 900 ms OUT 2 allocation of the pulse output: 0 : kWh + 1 : kvarh + 2 : kVAh 3 : kWh 4 : kvarh OUT 2 impulse value: 0 : 0.1 kWh/kvarh/kVAh 1 : 1 kWh/kvarh/kVAh 2 : 10 kWh/kvarh/kVAh 3 : 100 kWh/kvarh/kVAh 4 : 1000 kWh/kvarh/kVAh 5 : 10000 kWh/kvarh/kVAh OUT 2 impulse duration : 1 : 100 ms 2 : 200 ms 3 : 300 ms 4 : 400 ms 5 : 500 ms 6 : 600 ms 7 : 700 ms 8 : 800 ms 9 : 900 ms Type of analog output OUT 1: 0 : 0/20 mA 1 : 4/20 mA 2 : 30 V Output allocation analog OUT 1: 0: I1 1 : I2 2 : I3 3 : In 4 : U12 5 : U23 6 : U31 7 : P 8 : Q 9 : S 10 : PFL 11 : V1 12 : V2 Unit

524

20C

1

­

525

20D

1

­

526

20E

1

­

527

20F

1

­

528

210

1

­

SOCOMEC - Réf. : CDR 27 038_gb

35

GB

523

20B

1

­

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)

Decimal address Hexa. address Number of words Text 13 : V3 14 : F 15 : PFC Value at 0 or 4 mA from analog output OUT 1 Unit at 0 or 4 mA from analog output OUT 1: 0:/ 1:k 2:M Value at 20 mA from analog output OUT 1 Unit at 20 mA from analog output OUT 1: 0:/ 1:k 2:M Type of analog output OUT 2 : 0 : 0/20 mA 1 : 4/20 mA 2 : 30 V Output allocation analog OUT 2: 0 : I1 1 : I2 2 : I3 3 : In 4 : U12 5 : U23 6 : U31 7 : P 8 : Q 9 : S 10 : PFL 11 : V1 12 : V2 13 : V3 14 : F 15 : PFC Value at 0 or 4 mA from analog output OUT 2 Unit at 0 or 4 mA from analog output OUT 2 : 0:/ 1:k 2:M Value at 20 mA from analog output OUT 2: Unit at 20 mA from analog output OUT 2: 0:/ 1:k 2:M Type of analog output OUT 3: 0 : 0/20 mA 1 : 4/20 mA 2 : 30 V Output allocation analog OUT 3: 0 : I1 1 : I2 2 : I3 3 : In 4 : U12 5 : U23 6 : U31 Unit

529 530

211 212

1 1

­ ­

531 532

213 214

1 1

­ ­

533

215

1

­

534

216

1

­

535 536

217 218

1 1

­ ­

537 538

219 21A

1 1

­ ­

539

21B

1

540

21C

1

­ ­

36

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)

Decimal address Hexa. address Number of words Text 7 : P 8 : Q 9 : S 10 : PFL 11 : V1 12 : V2 13 : V3 14 : F 15 : PFC Value at 0 or 4 mA from analog output OUT 3 Unit at 0 or 4 mA from analog output OUT 3: 0:/ 1:k 2:M Value at 20 mA from analog output OUT 3 Unit at 20 mA from analog output OUT 3: 0:/ 1:k 2:M Type of analog output OUT 4: 0 : 0/20 mA 1 : 4/20 mA 2 : 30 V Output allocation analog OUT 4: 0 : I1 1 : I2 2 : I3 3 : In 4 : U12 5 : U23 6 : U31 7 : P 8 : Q 9 : S 10 : PFL 11 : V1 12 : V2 13 : V3 14 : F 15 : PFC Value at 0 or 4 mA from analog output OUT 4 Unit at 0 or 4 mA from analog output OUT 4: 0:/ 1:k 2:M Value at 20 mA from analog output OUT 4 Unit at 20 mA from analog output OUT 4: 0:/ 1:k 2:M Allocation of OUT 1 relay: 0 : Cde 1:I 2:U 3 : P+ 4 : Q+ 5 : S Unit

541 542

21D 21E

1 1

­ ­

543 544

21F 220

1 1

­ ­

545

221

1

­

546

222

1

­

547 548

223 224

1 1

­ ­

549 550

225 226

1 1

­ ­

551

227

1

­

SOCOMEC - Réf. : CDR 27 038_gb

37

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)

Decimal address Hexa. address Number of words Text 6:F 7 : PFL 8 : thd 3I 9 : thd 3U 10 : IN 11 : HOUR 12 : V 13 : thd In 14 : thd 3V 15 : P16 : Q17 : PFC 18 : Cd-t Lower threshold OUT 1 Unit lower threshold OUT 1: 0:/ 1:k 2:M Threshold value OUT 1 Unit threshold value OUT : 0:/ 1:k 2:M Hysteresis 0 to 99 OUT 1 Specified time OUT 1 Relay status OUT 1: 0 : Open 1 : Closed Allocation of OUT 2 relay : 0 : Cde 1:I 2:U 3 : P+ 4 : Q+ 5 : S 6:F 7 : PFL 8 : thd 3I 9 : thd 3U 10 : IN 11 : HOUR 12 : V 13 : thd In 14 : thd 3V 15 : P16 : Q17 : PFC 18 : Cd-t Lower threshold OUT 2 Unit lower threshold OUT 2: 0:/ 1:k 2:M Threshold value OUT 2 Unit upper threshold OUT 2: 0: / 1:k 2:M Unit

552 553

228 229

1 1

­ ­

554 555

22A 22B

1 1

­ ­

556 557 558 559

22C 22D 22E 22F

1 1 1 1

% s. ­ ­

560 561

230 231

1 1

­ ­

562 563

232 233

1 1

­

­

38

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)

Decimal address 564 565 566 567 568 569 570 571 Hexa. address 234 235 236 237 238 239 23A 23B Number of words 1 1 1 1 1 1 1 1 Text Hysteresis 0 to 99 OUT 2 Specified time OUT 2 Relay status OUT 2 : 0 : Open 1 : Closed Relay status OUT 3 : 0 : Open 1 : Closed Relay status OUT 4 : 0 : Open 1 : Closed Relay status OUT 5 : 0 : Open 1 : Closed Relay status OUT 6 : 0 : Open 1 : Closed CT secondary neutral : 1: 1 A 5: 5 A CT primary neutral Synchronisation of U AVG/MAX : 10 : 10 seconds 300 : 5 minutes (5x60s) 480 : 8 minutes (8x60s) 600 : 10 minutes (10x60s) 900 : 15 minutes (15x60s) 1200 : 20 minutes (20x60s) 1800 : 30 minutes (30x60s) 3600 : 60 minutes (60x60s) Synchronisation of F AVG/MAX : 10 : 10 seconds 300 : 5 minutes (5x60s) 480 : 8 minutes (8x60s) 600 : 10 minutes (10x60s) 900 : 15 minutes (15x60s) 1200 : 20 minutes (20x60s) 1800 : 30 minutes (30x60s) 3600 : 60 minutes (60x60s) Mean power memory storage P+ : 0 : no 1 : yes Mean power memory storage P- : 0 : no 1 : yes Mean power memory storage Q+ : 0 : no 1 : yes Mean power memory storage Q- : 0 : no 1 : yes Mean power synchronisation signal : 0 : internal 1 : external Synchronisation period for P+, P-, Q+ et Q-: 300 : 5 minutes (5x60s) 480 : 8 minutes (8x60s) 600 : 10 minutes (10x60s) 900 : 15 minutes (15x60s) 1200 : 20 minutes (20x60s) 1800 : 30 minutes (30x60s) Unit % s. ­ ­ ­ ­ ­

572 573

23C 23D

1 1

A A s.

574

23E

1

s.

575

23F

1

576

240

1

577

241

1

578

242

1

579

243

1

580

244

1

s.

SOCOMEC - Réf. : CDR 27 038_gb

39

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)

Decimal address 581 Hexa. address 245 Number of words 1 Text Allocation of OUT 3 relay: 0 : Cde 1:I 2:U 3 : P+ 4 : Q+ 5 : S 6:F 7 : PFL 8 : thd 3I 9 : thd 3U 10 : IN 11 : HOUR 12 : V 13 : thd In 14 : thd 3V 15 : P16 : Q17 : PFC 18 : Cd-t Lower threshold OUT 3 Unit lower threshold OUT 3 : 0:/ 1:k 2:M Upper threshold OUT 3 Unit upper threshold OUT 3 : 0:/ 1:k 2:M Hysteresis 0 to 99 OUT 3 Specified time OUT 3 Relay status OUT 3 : 0 : Open 1 : Closed Allocation of OUT 4 relay: 0 : Cde 1:I 2:U 3 : P+ 4 : Q+ 5 : S 6:F 7 : PFL 8 : thd 3I 9 : thd 3U 10 : IN 11 : HOUR 12 : V 13 : thd In 14 : thd 3V 15 : P16 : Q17 : PFC 18 : Cd-t Unit

582 583

246 247

1 1

584 585

248 249

1 1

586 587 588 589

24A 24B 24C 24D

1 1 1 1

% s.

40

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)

Decimal address 590 591 Hexa. address 24E 24F Number of words 1 1 Text Lower threshold OUT 4 Unit lower threshold OUT 4 : 0:/ 1:k 2:M Upper threshold OUT 4 Unit upper threshold OUT 4 : 0:/ 1:k 2:M Hysteresis 0 to 99 OUT 4 Specified time OUT 4 Relay status OUT 4 : 0 : Open 1 : Closed Allocation of OUT 5 relay: 0 : Cde 1:I 2:U 3 : P+ 4 : Q+ 5 : S 6:F 7 : PFL 8 : thd 3I 9 : thd 3U 10 : IN 11 : HOUR 12 : V 13 : thd In 14 : thd 3V 15 : P16 : Q17 : PFC 18 : Cd-t Lower threshold OUT 5 Unit lower threshold OUT 5 : 0:/ 1:k 2:M Upper threshold OUT 5 Unit upper threshold OUT 5 : 0:/ 1:k 2:M Hysteresis 0 to 99 OUT 5 Specified time OUT 5 Relay status OUT 5 : 0 : Open 1 : Closed Allocation of OUT 6 relay: 0 : Cde 1:I 2:U Unit

592 593

250 251

1 1

594 595 596 597

252 253 254 255

1 1 1 1

% s.

598 599

256 257

1 1

600 601

258 259

1 1

602 603 604 605

25A 25B 25C 25D

1 1 1 1

% s.

SOCOMEC - Réf. : CDR 27 038_gb

41

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)

Decimal address Hexa. address Number of words Text 3 : P+ 4 : Q+ 5 : S 6:F 7 : PFL 8 : thd 3I 9 : thd 3U 10 : IN 11 : HOUR 12 : V 13 : thd In 14 : thd 3V 15 : P16 : Q17 : PFC 18 : Cd-t Lower threshold OUT 6 Unit lower threshold OUT 6 : 0:/ 1:k 2:M Upper threshold OUT 6 Unit upper threshold OUT 6 : 0:/ 1:k 2:M Hysteresis 0 to 99 OUT 6 Specified time OUT 6 Relay status OUT 6 : 0 : Open 1 : Closed Voltage dips detection threshold (SAG) Voltage dip detection threshold hysteresis (SAG) Voltage surge detection threshold hysteresis (SWELL) Voltage surge detection threshold hysteresis (SWELL) Unit

606 607

25E 25F

1 1

608 609

260 261

1 1

610 611 612 613 614 615 616

262 263 264 265 266 267 268

1 1 1 1 1 1 1

% s.

% % % %

Size of this zone: 105 words (decimals) or 69 (hexadecimals) Example: Configuration of a 4-wired unbalanced network (4 NBL) for DIRIS number 5. Slave

05

Function

06

High-order address

02

Low-order address

00

High-order word N°

00

Low-order word N°

05

CRC 16

49F5

DIRIS A40/A41 reply: Identical to message sent.

42

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

RESET TO ZERO: ENERGY METERS AND MAX. VALUES (FUNCTION 6)

Decimal address 1024 Hexa. address 400 Number of words 1 Text RAZ: Max3I : 0 x 0001 MaxP+ : 0 x 0002 MaxP-: 0 x 0004 MaxQ+ : 0 x 0008 MaxQ- : 0 x 0010 MaxS : 0 x 0020 Hour meter : 0 x 0040 kWh+ : 0 x 0080 kvarh+ : 0 x 0100 kVAh : 0 x 0200 kWh- : 0 x 0400 kvarh- : 0 x 0800 All parameters : 0 x 1000 MaxU : 0 x 2000 MaxV : 0 x 4000 MaxF : 0 x 8000 R.A.Z. : E1 : 0 x 0001 E2 : 0 x 0002 E3 : 0 x 0004 E4 : 0 x 0008 E5 : 0 x 0010 E6 : 0 x 0020 Min/Max I : 0 x 0040 Min/Max In : 0 x 0080 Min/Max U : 0 x 0100 Min/Max F : 0 x 0200 Min/Max PF : 0 x 0400 Min/Max P : 0 x 0800 Min/Max Q : 0 x 1000 Min/Max thd I : 0 x 2000 Min/Max thd In : 0 x 4000 Min/Max thd U : 0 x 8000 RAZ: Min/Max thd V : 0 x 0001 Min/Max V : 0 x 0002 Min/Max S : 0 x 0004 10 alarms event log : 0 x 0008 10 voltage dips event log : 0 x 0010 10 surges event log : 0 x 0020 10 cut-offs event log : 0 x 0040 Averaged out frequencies : 0 x 0080 Averaged out voltage values : 0 x 0100 Averaged out power values : 0 x 0200 Unit

1025

401

1

1026

402

1

SOCOMEC - Réf. : CDR 27 038_gb

43

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

RESET TO ZERO: ENERGY METERS AND MAX. VALUES (FUNCTION 6)

NB: To reset several parameters to zero, add the corresponding figure indicated in the "text" column. Example: reset Max P+ and kvarh + to zero: 2 + 100 = 102 (Hex) Example: To reset all values for DIRIS number 5 to zero, the following frame should be sent:

Slave

05

Function

06

High-order address

04

Low-order address

00

High-order word N°

10

Low-order word N°

00

CRC 16

84BE

DIRIS A40/A41 reply: identical to the message sent.

SAVED COMMAND (RESET)

The following command should be done to save programming parameters changes for DIRIS number 5. Slave

05

Function

06

High-order address

06

Low-order address

00

Values

0000

CRC 16

88C6

NB : The DIRIS A40/A41 responds with an identical frame.

PULSE METERS VALUES

Input meters Decimal Hexa. Number Text address address of words 2560 A00 2 Input E1, option ES 1 2562 A02 2 Input E2, option ES 1 2564 A04 2 Input E3, option ES 2 2566 A06 2 inputE4, option ES 2 2568 A08 2 Input E5, option ES 3 2570 A0A 2 Input E6, option ES 3 Size of this zone: 12 words (decimals) or C (hexadecimals) Unit

44

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

DATE AND HOUR SETTINGS (FUNCTION 3, 6 OR 16)

Input meters Decimal Hexa. Number address address of words 3072 C00 1 3073 C01 1 3074 C02 1 3075 C03 1 3076 C04 1 3077 C05 1 Zone size: 6 words (decimal) or 6 (hexadecimal). Text Day Month Year Hour Minute Second Unit

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-1 Decimal address 3088 3089 Hexa. address C10 C11 Number of words 1 1 Text Alarm output number (1 to 6) Lower threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Lower threshold value Lower threshold: 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 Unit

3090 3092

C12 C14

2 1

SOCOMEC - Réf. : CDR 27 038_gb

45

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-1 Decimal address Hexa. address Number of words Text 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Upper threshold value Duration Day Month Year Hour Minute Second Text Output number (1 to 6) Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 Unit

3093 3095 3096 3097 3098 3099 3100 3101 Alarm n-2 Decimal address 3102 3103

C15 C17 C18 C19 C1A C1B C1C C1D Hexa. address C1E C1F

2 1 1 1 1 1 1 1 Number of words 1 1

s

Unit

46

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-2 Decimal address Hexa. address Number of words Text 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Lower threshold value Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Upper threshold value Duration Day Month Year Hour Minute Second Unit

3104 3106

C20 C22

2 1

3107 3109 3110 3111 3112 3113 3114 3115

C23 C25 C26 C27 C28 C29 C2A C2B

2 1 1 1 1 1 1 1

s

SOCOMEC - Réf. : CDR 27 038_gb

47

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-3 Decimal address 3116 3117 Hexa. address C2C C2D Number of words 1 1 Text Output number (1 to 6) Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Lower threshold value Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR Unit

3118 3120

C2E C30

2 1

48

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-3 Decimal address Hexa. address Number of words Text 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Upper threshold value Duration Day Month Year Hour Minute Second Unit

3121 3123 3124 3125 3126 3127 3128 3129 Alarm n-4 Decimal address 3130 3131

C31 C33 C34 C35 C36 C37 C38 C39

2 1 1 1 1 1 1 1

s

Hexa. address C3A C3B

Number of words 1 1

Text Output number (1 to 6) Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC

Unit

SOCOMEC - Réf. : CDR 27 038_gb

49

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-4 Decimal address 3132 3134 Hexa. address C3C C3E Number of words 2 1 Text Lower threshold value Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Upper threshold value Duration Day Month Year Hour Minute Second Unit

3135 3137 3138 3139 3140 3141 3142 3143 Alarm n-5 Decimal address 3144 3145

C3F C41 C42 C43 C44 C45 C46 C47

2 1 1 1 1 1 1 1

s

Hexa. address C48 C49

Number of words 1 1

Text Output number (1 to 6) Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31

Unit

50

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-5 Decimal address Hexa. address Number of words Text 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Lower threshold value Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Unit

3146 3148

C4A C4C

2 1

SOCOMEC - Réf. : CDR 27 038_gb

51

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-5 Decimal address 3149 3151 3152 3153 3154 3155 3156 3157 Hexa. address C4D C4F C50 C51 C52 C53 C54 C55 Number of words 2 1 1 1 1 1 1 1 Text Upper threshold value Duration Day Month Year Hour Minute Second Unit

s s

Alarm n-6 Decimal address 3158 3159 Hexa. address C56 C57 Number of words 1 1 Text Output number (1 to 6) Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Lower threshold value Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 Unit

3160 3162

C58 C5A

2 1

52

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarme n-6 Decimal address Hexa. address Number of words Text 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Upper threshold value Duration Day Month Year Hour Minute Second Unit

3163 3165 3166 3167 3168 3169 3170 3171 Alarm n-7 Decimal address 3172 3173

C5B C5D C5E C5F C60 C61 C62 C63

2 1 1 1 1 1 1 1

s

Hexa. address C64 C65

Number of words 1 1

Text Output number (1 to 6) Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3

Unit

SOCOMEC - Réf. : CDR 27 038_gb

53

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-7 Decimal address Hexa. address Number of words Text 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Lower threshold value Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Upper threshold value Duration Day Month Year Hour Minute Second Unit

3174 3176

C66 C68

2 1

3177 3179 3180 3181 3182 3183 3184 3185

C69 C6B C6C C6D C6E C6F C70 C71

2 1 1 1 1 1 1 1

s

54

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-8 Decimal address 3186 3187 Hexa. address C72 C73 Number of words 1 1 Text Output number (1 to 6) Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Lower threshold value Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 Unit

3188 3190

C74 C76

2 1

SOCOMEC - Réf. : CDR 27 038_gb

55

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-8 Decimal address Hexa. address Number of words Text 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Upper threshold value Duration Day Month Year Hour Minute Second Unit

3191 3193 3194 3195 3196 3197 3198 3199 Alarm n-9 Decimal address 3200 3201

C77 C79 C7A C7B C7C C7D C7E C7F

2 1 1 1 1 1 1 1

s

Hexa. address C80 C81

Number of words 1 1

Text Output number (1 to 6) Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC

Unit

56

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-9 Decimal address 3202 3204 Hexa. address C82 C84 Number of words 2 1 Text Lower threshold value Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Upper threshold value Duration Day Month Year Hour Minute Second Unit

3205 3207 3208 3209 3210 3211 3212 3213

C85 C87 C88 C89 C8A C8B C8C C8D

2 1 1 1 1 1 1 1

s

SOCOMEC - Réf. : CDR 27 038_gb

57

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-10 Decimal address 3214 3215 Hexa. address C8E C8F Number of words 1 1 Text Output number (1 to 6) Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR 22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC Lower threshold value Lower threshold : 0 : no alarm 1 : I1 2 : I2 3 : I3 4 : In 5 : U12 6 : U23 7 : U31 8 : P+ 9 : Q+ 10 : S 11 : F 12 : PFL 15 : thd I1 16 : thd I2 17 : thd I3 18 : thd U12 19 : thd U23 20 : thd U31 21 : HOUR Unit

3216 3218

C90 C92

2 1

58

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LAST 10 ALARMS EVENT LOG (FUNCTION 3)

Alarm n-10 Decimal address Hexa. address Number of words Text Unit

22 : V1 23 : V2 24 : V3 25 : thd In 26 : thd V1 27 : thd V2 28 : thd V3 29 : P30 : Q31 : PFC 3219 C93 2 Upper threshold value 3221 C95 1 Duration 3222 C96 1 Day 3223 C97 1 Month 3224 C98 1 Year 3225 C99 1 Hour 3226 C9A 1 Minute 3227 C9B 1 Second Zone size: 140 words (decimal) or 8C (hexadecimal).

s

LAST 10 VOLTAGE DIPS EVENT LOG / SAG (FUNCTION 3)

Voltage dip n-1 Decimal address 3328 Hexa. address D00 Number of words 1 Text Query! : phase-to-phase residual value : 0 : no 5: U12 6: U23 7: U31 Value Query! : phase-to-neutral residual value : 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second Unit

3329 3331

D01 D03

2 1

3332 3334 3336 3337 3338 3339 3340 3341

D04 D06 D08 D09 D0A D0B D0C D0D

2 2 1 1 1 1 1 1

ms

SOCOMEC - Réf. : CDR 27 038_gb

59

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LAST 10 VOLTAGE DIPS EVENT LOG / SAG (FUNCTION 3)

Voltage dip n-2 Decimal address 3342 Hexa. address D0E Number of words 1 Text Query! : phase-to-phase residual value : 0 : no 5: U12 6: U23 7: U31 Value Query! : phase-to-neutral residual value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second Unit

3343 3345

D0F D11

2 1

3346 3348 3350 3351 3352 3353 3354 3355

D12 D14 D16 D17 D18 D19 D1A D1B

2 2 1 1 1 1 1 1

ms

Voltage dip n-3 Decimal address 3356

Hexa. address D1C

Number of words 1

Text Query! : phase-to-phase residual value : 0 : no 5: U12 6: U23 7: U31 Value Query! : phase-to-neutral residual value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second

Unit

3357 3359

D1D D1F

2 1

3360 3362 3364 3365 3366 3367 3368 3369

D20 D22 D24 D25 D26 D27 D28 D29

2 2 1 1 1 1 1 1

ms

60

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LAST 10 VOLTAGE DIPS EVENT LOG / SAG (FUNCTION 3)

Voltage dip n-4 Decimal address 3370 Hexa. address D2A Number of words 1 Text Query! : phase-to-phase residual value : 0 : no 5: U12 6: U23 7: U31 Value Query! : phase-to-neutral residual value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second Unit

3371 3373

D2B D2D

2 1

3374 3376 3378 3379 3380 3381 3382 3383

D2E D30 D32 D33 D34 D35 D36 D37

2 2 1 1 1 1 1 1

ms

Voltage dip n-5 Decimal address 3384

Hexa. address D38

Number of words 1

Text Query! : phase-to-phase residual value: 0 : no 5: U12 6: U23 7: U31 Value Query! : phase-to-neutral residual value: 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second

Unit

3385 3387

D39 D3B

2 1

3388 3390 3392 3393 3394 3395 3396 3397

D3C D3E D40 D41 D42 D43 D44 D45

2 2 1 1 1 1 1 1

ms

SOCOMEC - Réf. : CDR 27 038_gb

61

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LAST 10 VOLTAGE DIPS EVENT LOG / SAG (FUNCTION 3)

Voltage dip n-6 Decimal address 3398 Hexa. address D46 Number of words 1 Text Query! : phase-to-phase residual value : 0 : no 5: U12 6: U23 7: U31 Value Query! : phase-to-neutral residual value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second Unit

3399 3401

D47 D49

2 1

3402 3404 3406 3407 3408 3409 3410 3411

D4A D4C D4E D4F D50 D51 D52 D53

2 2 1 1 1 1 1 1

ms

Voltage dip n-7 Decimal address 3412

Hexa. address D54

Number of words 1

Text Query! : phase-to-phase residual value : 0 : no 5: U12 6: U23 7: U31 Value Query! : phase-to-neutral residual value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second

Unit

3413 3415

D55 D57

2 1

3416 3418 3420 3421 3422 3423 3424 3425

D58 D5A D5C D5D D5E D5F D60 D61

2 2 1 1 1 1 1 1

ms

62

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LAST 10 VOLTAGE DIPS EVENT LOG / SAG (FUNCTION 3)

Voltage dip n-8 Decimal address 3426 Hexa. address D62 Number of words 1 Text Query! : phase-to-phase residual value : 0 : no 5: U12 6: U23 7: U31 Value Query! : phase-to-neutral residual value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second Unit

3427 3429

D63 D65

2 1

3430 3432 3434 3435 3436 3437 3438 3439

D66 D68 D6A D6B D6C D6D D6E D6F

2 2 1 1 1 1 1 1

ms

Voltage dip n-9 Decimal address 3440

Hexa. address D70

Number of words 1

Text Query! : phase-to-phase residual value : 0 : no 5: U12 6: U23 7: U31 Value Query! : phase-to-neutral residual value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second

Unit

3441 3443

D71 D73

2 1

3444 3446 3448 3449 3450 3451 3452 3453

D74 D76 D78 D79 D7A D7B D7C D7D

2 2 1 1 1 1 1 1

ms

SOCOMEC - Réf. : CDR 27 038_gb

63

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LAST 10 VOLTAGE DIPS EVENT LOG / SAG (FUNCTION 3)

Voltage dip n-10 Decimal address 3454 Hexa. address D7E Number of words 1 Text Query! : phase-to-phase residual value : 0 : no 5: U12 6: U23 7: U31 Value Query! : phase-to-neutral residual value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second Unit

3455 3457

D7F D81

2 1

3458 3460 3462 3463 3464 3465 3466 3467

D82 D84 D86 D87 D88 D89 D8A D8B

2 2 1 1 1 1 1 1

ms

Zone size: 140 words (decimal) or 8C (hexadecimal).

LAST 10 VOLTAGE SURGE EVENT LOG / SWELL (FUNCTION 3)

Voltage surge n-1 Decimal address 3584 Hexa. address E00 Number of words 1 Text Unit

3585 3587

E01 E03

2 1

3588 3590 3592 3593 3594 3595 3596 3597

E04 E06 E08 E09 E0A E0B E0C E0D

2 2 1 1 1 1 1 1

Query! : maximum phase-to-phase value : 0 : no 5: U12 6: U23 7: U31 Value Query! : maximum phase-to-neutral value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration ms Day Month Year Hour Minute Second

64

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LAST 10 VOLTAGE SURGE EVENT LOG / SWELL (FUNCTION 3)

Voltage surge n-2 Decimal address 3598 Hexa. address E0E Number of words 1 Text Query! : maximum phase-to-phase value : 0 : no 5: U12 6: U23 7: U31 Value Query! : maximum phase-to-neutral value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second Unit

3599 3601

E0F E11

2 1

3602 3604 3606 3607 3608 3609 3610 3611

E12 E14 E16 E17 E18 E19 E1A E1B

2 2 1 1 1 1 1 1

ms

Voltage surge n-3 Decimal Hexa. address address 3612 E1C

Number of words 1

Text Query! : maximum phase-to-phase value : 0 : no 5: U12 6: U23 7: U31 Value Query! : maximum phase-to-neutral value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second

Unit

3613 3615

E1D E1F

2 1

3616 3618 3620 3621 3622 3623 3624 3625

E20 E22 E24 E25 E26 E27 E28 E29

2 2 1 1 1 1 1 1

ms

SOCOMEC - Réf. : CDR 27 038_gb

65

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LAST 10 VOLTAGE SURGE EVENT LOG / SWELL (FUNCTION 3)

Voltage surge n-4 Decimal address 3626 Hexa. address E2A Number of words 1 Text Query! : maximum phase-to-phase value : 0 : no 5: U12 6: U23 7: U31 Value Query! : maximum phase-to-neutral value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second Unit

3627 3629

E2B E2D

2 1

3630 3632 3634 3635 3636 3637 3638 3639

E2E E30 E32 E33 E34 E35 E36 E37

2 2 1 1 1 1 1 1

ms

Voltage surge n-5 Decimal Hexa. address address 3640 E38

Number of words 1

Text

Unit

3641 3643

E39 E3B

2 1

3644 3646 3648 3649 3650 3651 3652 3653

E3C E3E E40 E41 E42 E43 E44 E45

2 2 1 1 1 1 1 1

Query! : maximum phase-to-phase value : 0 : no 5: U12 6: U23 7: U31 Value Query! : maximum phase-to-neutral value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration ms Day Month Year Hour Minute Second

66

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LAST 10 VOLTAGE SURGE EVENT LOG / SWELL (FUNCTION 3)

Voltage surge n-6 Decimal address 3654 Hexa. address E46 Number of words 1 Text Query! : maximum phase-to-phase value : 0 : no 5: U12 6: U23 7: U31 Value Query! : maximum phase-to-neutral value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second Unit

3655 3657

E47 E49

2 1

3658 3660 3662 3663 3664 3665 3666 3667

E4A E4C E4E E4F E50 E51 E52 E53

2 2 1 1 1 1 1 1

ms

Voltage surge n-7 Decimal Hexa. address address 3668 E54

Number of words 1

Text Query! : maximum phase-to-phase value : 0 : no 5: U12 6: U23 7: U31 Value Query! : maximum phase-to-neutral value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second

Unit

3669 3671

E55 E57

2 1

3672 3674 3676 3677 3678 3679 3680 3681

E58 E5A E5C E5D E5E E5F E60 E61

2 2 1 1 1 1 1 1

ms

SOCOMEC - Réf. : CDR 27 038_gb

67

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LAST 10 VOLTAGE SURGE EVENT LOG / SWELL (FUNCTION 3)

Voltage surge n-8 Decimal address 3682 Hexa. address E62 Number of words 1 Text Query! : maximum phase-to-phase value : 0 : no 5: U12 6: U23 7: U31 Value Query! : maximum phase-to-neutral value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second Unit

3683 3685

E63 E65

2 1

3686 3688 3690 3691 3692 3693 3694 3695

E66 E68 E6A E6B E6C E6D E6E E6F

2 2 1 1 1 1 1 1

ms

Voltage surge n-9 Decimal Hexa. address address 3696 E70

Number of words 1

Text Query! : maximum phase-to-phase value : 0 : no 5: U12 6: U23 7: U31 Value Query! : maximum phase-to-neutral value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration Day Month Year Hour Minute Second

Unit

3697 3699

E71 E73

2 1

3700 3702 3704 3705 3706 3707 3708 3709

E74 E76 E78 E79 E7A E7B E7C E7D

2 2 1 1 1 1 1 1

ms

68

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

LAST 10 VOLTAGE SURGE EVENT LOG / SWELL (FUNCTION 3)

Voltage surge n-10 Decimal address 3710 Hexa. address E7E Number of words 1 Text Unit

3711 3713

E7F E81

2 1

3714 3716 3718 3719 3720 3721 3722 3723

E82 E84 E86 E87 E88 E89 E8A E8B

2 2 1 1 1 1 1 1

Query! : maximum phase-to-phase value : 0 : no 5: U12 6: U23 7: U31 Value Query! : maximum phase-to-neutral value : 0 : no 22 : V1 23 : V2 24 : V3 Value Duration ms Day Month Year Hour Minute Second

Zone size: 140 words (decimal) or 8C (hexadecimal).

MINIMUM AND MAXIMUM INSTANTANEOUS VALUES (FUNCTION 3)

Decimal address 3840 3842 3843 3844 3845 3846 3847 3848 3850 3851 3852 3853 3854 3855 3856 3858 3859 3860 3861 3862 3863 3864 3866 3867 3868 3869 3870 3871 3872 Hexa. address F00 F02 F03 F04 F05 F06 F07 F08 F0A F0B F0C F0D F0E F0F F10 F12 F13 F14 F15 F16 F17 F18 F1A F1B F1C F1D F1E F1F F20 Number of words 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 Text 3I minimum Day Month Year Hour Minute Second 3I maximum Day Month Year Hour Minute Second IN minimum Day Month Year Hour Minute Second IN maximum Day Month Year Hour Minute Second 3U minimum Unit mA

mA

mA

mA

mV

SOCOMEC - Réf. : CDR 27 038_gb

69

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

MINIMUM AND MAXIMUM INSTANTANEOUS VALUES (FUNCTION 3)

Decimal address 3874 3875 3876 3877 3878 3879 3880 3882 3883 3884 3885 3886 3887 3888 3890 3891 3892 3893 3894 3895 3896 3898 3899 3900 3901 3902 3903 3904 3906 3907 3908 3909 3910 3911 3912 3914 3915 3916 3917 3918 3919 3920 3922 3923 3924 3925 3926 3927 3928 3930 3931 3932 3933 3934 3935 3936 Hexa. address F22 F23 F24 F25 F26 F27 F28 F2A F2B F2C F2D F2E F2F F30 F32 F33 F34 F35 F36 F37 F38 F3A F3B F3C F3D F3E F3F F40 F42 F43 F44 F45 F46 F47 F48 F4A F4B F4C F4D F4E F4F F50 F52 F53 F54 F55 F56 F57 F58 F5A F5B F5C F5D F5E F5F F60 Number of words 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 Text Day Month Year Hour Minute Second 3U maximum Day Month Year Hour Minute Second 3V minimum Day Month Year Hour Minute Second 3V maximum Day Month Year Hour Minute Second F minimum Day Month Year Hour Minute Second F maximum Day Month Year Hour Minute Second PF minimum Day Month Year Hour Minute Second PF maximum Day Month Year Hour Minute Second P + minimum Unit

0.01 V

0.01 V

0.01 V

Hz / 100

Hz / 100

1 / 1000

1 / 1000

kW / 1000

70

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

MINIMUM AND MAXIMUM INSTANTANEOUS VALUES (FUNCTION 3)

Decimal address 3938 3939 3940 3941 3942 3943 3944 3946 3947 3948 3949 3950 3951 3952 3954 3955 3956 3957 3958 3959 3960 3962 3963 3964 3965 3966 3967 3968 3970 3971 3972 3973 3974 3975 3976 3978 3979 3980 3981 3982 3983 3984 3986 3987 3988 3989 3990 3991 3992 3994 3995 3996 3997 3998 3999 4000 Hexa. address F62 F63 F64 F65 F66 F67 F68 F6A F6B F6C F6D F6E F6F F70 F72 F73 F74 F75 F76 F77 F78 F7A F7B F7C F7D F7E F7F F80 F82 F83 F84 F85 F86 F87 F88 F8A F8B F8C F8D F8E F8F F90 F92 F93 F94 F95 F96 F97 F98 F9A F9B F9C F9D F9E F9F FA0 Number of words 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 Text Day Month Year Hour Minute Second P + maximum Day Month Year Hour Minute Second P - minimum Day Month Year Hour Minute Second P - maximum Day Month Year Hour Minute Second Q + minimum Day Month Year Hour Minute Second Q + maximum Day Month Year Hour Minute Second Q - minimum Day Month Year Hour Minute Second Q - maximum Day Month Year Hour Minute Second S minimum Unit

kW / 100

kW / 100

kvar / 100

kvar / 100

kvar / 100

kvar / 100

kvar / 100

kvar / 100

SOCOMEC - Réf. : CDR 27 038_gb

71

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

MINIMUM AND MAXIMUM INSTANTANEOUS VALUES (FUNCTION 3)

Decimal address 4002 4003 4004 4005 4006 4007 4008 4010 4011 4012 4013 4014 4015 4016 4018 4019 4020 4021 4022 4023 4024 4026 4027 4028 4029 4030 4031 4032 4034 4035 4036 4037 4038 4039 4040 4042 4043 4044 4045 4046 4047 4048 4050 4051 4052 4053 4054 4055 4056 4058 4059 4060 4061 4062 4063 4064 Hexa. address FA2 FA3 FA4 FA5 FA6 FA7 FA8 FAA FAB FAC FAD FAE FAF FB0 FB2 FB3 FB4 FB5 FB6 FB7 FB8 FBA FBB FBC FBD FBE FBF FC0 FC2 FC3 FC4 FC5 FC6 FC7 FC8 FCA FCB FCC FCD FCE FCF FD0 FD2 FD3 FD4 FD5 FD6 FD7 FD8 FDA FDB FDC FDD FDE FDF FE0 Number of words 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 Text Day Month Year Hour Minute Second S maximum Day Month Year Hour Minute Second THD 3I minimum Day Month Year Hour Minute Second THD 3I maximum Day Month Year Hour Minute Second THD IN minimum Day Month Year Hour Minute Second THD IN maximum Day Month Year Hour Minute Second THD 3U minimum Day Month Year Hour Minute Second THD 3U maximum Day Month Year Hour Minute Second THD 3V minimum Unit

kvar / 100

0.10 %

0.10 %

0.10 %

0.10 %

0.10 %

0.10 %

0.10 %

72

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

MINIMUM AND MAXIMUM INSTANTANEOUS VALUES (FUNCTION 3)

Decimal Hexa. Number Text address address of words 4066 FE2 1 Day 4067 FE3 1 Month 4068 FE4 1 Year 4069 FE5 1 Hour 4070 FE6 1 Minute 4071 FE7 1 Second 4072 FE8 2 THD 3V maximum 4074 FEA 1 Day 4075 FEB 1 Month 4076 FEC 1 Year 4077 FED 1 Hour 4078 FEE 1 Minute 4079 FEF 1 Second Zone size: 240 words (decimal) or FO (hexadecimal). Unit

0.10 %

LAST 10 VOLTAGE CUT-OFFS EVENT LOG / SAG (FUNCTION 3)

Outage n-1 Decimal address 4096 4097 4098 4099 4100 4101 Outage n-2 Decimal address 4102 4103 4104 4105 4106 4107 Outage n-3 Decimal address 4108 4109 4110 4111 4112 4113 Outage n-5 Decimal address 4114 4115 4116 4117 4118 4119 Hexa. address 1000 1001 1002 1003 1004 1005 Hexa. address 1006 1007 1008 1009 100A 100B Hexa. address 100C 100D 100E 100F 1010 1011 Hexa. address 1012 1013 1014 1015 1016 1017 Number of words 1 1 1 1 1 1 Number of words 1 1 1 1 1 1 Number of words 1 1 1 1 1 1 Number of words 1 1 1 1 1 1 Text Day Month Year Hour Minute Second Text Day Month Year Hour Minute Second Text Day Month Year Hour Minute Second Text Day Month Year Hour Minute Second

73

Unit

Unit

Unit

Unit

SOCOMEC - Réf. : CDR 27 038_gb

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

COMMUNICATION

LAST 10 VOLTAGE CUT-OFFS EVENT LOG / SAG (FUNCTION 3)

Outage n-5 Decimal address 4120 4121 4122 4123 4124 4125 Outage n-6 Decimal address 4126 4127 4128 4129 4130 4131 Outage n-7 Decimal address 4132 4133 4134 4135 4136 4137 Outage n-8 Decimal address 4138 4139 4140 4141 4142 4143 Outage n-9 Decimal address 4144 4145 4146 4147 4148 4149 Outage n-10 Decimal address 4150 4151 4152 4153 4154 4155 Hexa. address 1018 1019 101A 101B 101C 101D Hexa. address 101E 101F 1020 1021 1022 1023 Hexa. address 1024 1025 1026 1027 1028 1029 Hexa. address 102A 102B 102C 102D 102E 102F Hexa. address 1030 1031 1032 1033 1034 1035 Hexa. address 1036 1037 1038 1039 103A 103B Number of words 1 1 1 1 1 1 Number of words 1 1 1 1 1 1 Number of words 1 1 1 1 1 1 Number of words 1 1 1 1 1 1 Number of words 1 1 1 1 1 1 Number of words 1 1 1 1 1 1 Text Day Month Year Hour Minute Second Text Day Month Year Hour Minute Second Text Day Month Year Hour Minute Second Text Day Month Year Hour Minute Second Text Day Month Year Hour Minute Second Text Day Month Year Hour Minute Second Unit Unit Unit Unit Unit Unit

Zone size: 60 words (decimal) or 3C (hexadecimal).

74

SOCOMEC - Réf. : CDR 27 038_gb

DIRIS A40/A41 - RS485 - JBUS/MODBUS® COMMUNICATION

MEAN POWER EVENT LOG (FUNCTION 3)

Values not modified by current and voltage transformation ratios Decimal address 12288 12289 12290 12293 16793 21293 25793 30293 Hexa. address 3000 3001 3002 3004 4198 532C 64C0 7655 Number of words 1 1 3 4500 4500 4500 4500 Zone end Text Mean active power pointer P+/PMean reactive power pointer Q+/QDate/Hour pointers updating Zone P.1 saving mean active power values P+ / PZone P.2 saving mean active power values P+ / PZone Q.1 saving mean reactive power values Q+ / QZone Q.2 saving mean reactive power values Q+ / QUnit

W/10 W/10 W/10 W/10

Zone size: 18005 words (decimal) or 4655 (hexadecimal).

MEAN VOLTAGE EVENT LOG (FUNCTION 3)

Values not modified by voltage transformation ratio Decimal address 32768 32769 32772 33647 Hexa. address 8000 8001 8003 836E Number of words 1 2 875 Zone end Text Voltage pointer Date/Hour pointer updating 3U, 3V voltage values Unit

V/10

Zone size: 879 words (decimal) or 36F (hexadecimal).

MEAN FREQUENCY EVENT LOG (FUNCTION 3)

Decimal address 36864 36865 36868 45568 Hexa. address 9000 9001 9003 B1FF Number of words 1 2 8700 Zone end Text Frequency pointer Date/Hour pointer updating Frequency values Unit

Hz/100

Zone size: 8704 words (decimal) or 220 (hexadecimal).

SOCOMEC - Réf. : CDR 27 038_gb

75

GB

DIRIS A40/A41 - RS485 - JBUS/MODBUS®

TECHNICAL CHARACTERISTICS

COMMUNICATION

RS485 Protocole Speed Galvanic insulation 2 or 3 wires half duplex JBUS/MODBUS® protocol / RTU mode 2400 to 38400 Bauds 4 kV

CERTIFICATION

UL 61010-1 N° file : E25 7746

GLOSSARY OF ABBREVIATIONS

COM ADR BDS PAR NO Even Odd STOP 1 2 Communication Slave address Speed of communication in bauds Communication frame parity Without parity Even parity Odd parity Frame-stop beep 1 stop bit 2 stop bits

76

SOCOMEC - Réf. : CDR 27 038_gb

SOCOMEC - Réf. : CDR 27 038_gb

77

D

SOCOMEC - Ref.: CDR 27 038 gb - 01 / 07

DIRIS 345 A / QUAT NOT 3i

HEAD OFFICE

SOCOMEC GROUP SWITCHING PROTECTION & UPS S.A. capital 11 014 300 R.C. Strasbourg 548500 149 B 1, Rue de Westhouse - B.P. 10 - F-67235 Benfeld Cedex - FRANCE

I N T E R N AT I O N A L SALES DEPAR TMENT

SOCOMEC 1, rue de Westhouse - B.P. 10 F - 67235 Benfeld Cedex - FRANCE Tél. +33 (0)3 88 57 41 41 - Fax +33 (0)3 88 74 08 00 [email protected]

www.socomec.com

This document is not a contract. SOCOMEC reserves the right to modify features without prior notice in view of continued improvement.

Industrial Switching & Protection Systems

Information

cdr_27038_gb