Class I, Division 2

120 VAC (ITC)­ Note: PLTC and ITC used in cable tray systems must have a separation of at least 2 inches (5 cm) or a mechanical barrier from higher power circuits. Foundation Fieldbus cable (PLTC/ITC) FF cable (PLTC/ITC)

120 VAC (Limited to 5 Amps max.)

Terminator

FF cable (PLTC/ITC)

Liquidtight flexible conduit

Liquidtight flexible conduit

FF cable (PLTC/ITC) with messenger wire

FF general purpose cable

Nonincendive Field Wiring & Associated Apparatus

Class I, Division 1

Explosion Proof

Terminator inside Rigid metal conduit

Metal clad flexible conduit

120 VAC (ITC)

120 VAC (ITC)

FF cable (PLTC/ITC)

JM-3: Potted leads recommended to enable removal of VCT while bus energized Terminator Terminator FF I.S. (Intrinsically Safe) general purpose cable Redundant power supply connected through passsive drop connector

Discrete outputs Discrete inputs

4-20mA (in) PLTC/ITC with strut support 4-20mA (out) 24 VDC (PLTC/ITC) with strut support

Intrinsically Safe

PLTC/ITC with strut support

FF I.S. (Intrinsically Safe) general purpose cable Level Switches

Flow meter (4-wire) Temperature Probe Control Valve Rigid metal conduit On/Off Electric actuator Control valve

120/240 VAC

Protection concepts shown are for illustration purposes. Final acceptance of installation including wiring practices is subject to the authority having jurisdiction.

NEC 500 Wiring Guidelines

Nonincendive Field Wiring and Associated Apparatus Class I & II, Division 2

Conduit/Cabling: · General purpose cable Connections: · General purpose connectors · Quick connectors without limitation Field Instrument Components: · Drop connectors limit voltage and current into spur · Field instruments must be nonincendive field wiring apparatus rated with published parameters (Ci, Li, Vmax, I max) · Drop Connector and Field Instrument parameters must be coordinated as follows: Drop Connector Field Instrument Voc < Vmax Isc < Imax · Field instrument Ci and Li must be lower than values determined from ignition curves using 0.9 safety factor (Ci & Li for drop cable is negligible with length under 20m) Special Notes: · Intrinsically safe apparatus may also be used as nonincendive field wiring apparatus · Instrument wiring may be manipulated while energized

Consult StoneL's FieldLink Bus Networking Reference Guide for additional products and more information on models and options.

Explosion Proof System Class I & II, Division 1 & 2

Conduit/Cabling: · Rigid metal conduit or steel intermediate conduit · MI (Mineral Insulated, Metal Sheathed) or MC (Metal Clad) where flexibility required · Seal-Offs for all enclosures (except those with special ratings) Connections: · Fittings must be explosion proof approved Field Instruments: · Complete apparatus must be explosion proof rated Special Notes: · No seal-offs are required for StoneL JM & Quartz · Power must be removed before opening enclosures

JM (Junction Module) Series

Clear Cover ­ use for Class I & II, Div. 2 Aluminum Cover ­ use for Class I & II, Div. 1 and 2 · Functions include drop connectors, I/O modules, relay modules & more · Connections available with (3) or (4) 1/2" or 3/4" NPT. Specials available with compression fittings or quick connectors

FieldBlock Series

Use for Class I & II, Div. 2 · Functions include (4) drop connectors, I/O modules, relay modules & more · Connections available with (6) compression fittings, quick connectors or 1/2" NPT conduits. Specials may include from (4) to (10) connectors and different combinations

Other FieldLink Products

PS-1

FF Power Supply 459019 Class 2 approved for use with ITC/PLTC Class I Div. 2 wiring. Power supply may also be located in Class I Div. 2 areas. 24 VDC Power Supply 459016 Class 2 approved for use with ITC/PLTC Class I Div. 2 wiring. Power supply may also be located in Class I Div. 2 areas. FieldRack Enclosures Rated NEMA 4 & 4X for protecting nonincendive components from process environment in Class I Div. 2 areas FF Bus Cable - 463010 PLTC & ITC rated for use in Class I Div. 2 areas

JM-1

JMT0111C3 Passive Drop Connector* with clear cover

FB-1

FBS06009 Switched Protected Drop Connector* with compression fittings FBM94035 Input/Externally powered output module with compression fittings (special 8 fittings)

PS-2

JM-2

Tray Cabling System Class I & II, Division 2

Conduit/Cabling: · Power Limited Tray Cable (PLTC) rated or Instrument Tray Cable (ITC) rated cable used in cable tray · PLTC or ITC used as open wiring up to 15m (50 ft) protected by angles, struts or messenger wire and secured at intervals not exceeding 1.8m (6 ft) · PLTC or ITC used in liquidtight or MC flexible conduit Connections: · PLTC and ITC may be connected using compression fittings installed to avoid tensile stress at termination · Flexible cord and quick connectors suitable provided conditions are met as described for nonincendive equipment Field Instruments: · Must be nonincendive equipment rated Special Notes: · PLTC power supplies (Class 2 approved) limited to 100 watts with maximum of 60 VDC used to limit energy into the circuit · ITC power supplies limited to 5 amps and 150 volts rms

JMS0111C3 Switched Protected Drop Connector* with clear cover

FB-2

FR

JM-3

JMS0111E_ Switched Protected Drop Connector* with aluminum cover

JM-4

Intrinsically Safe (IS) Systems Class I & II, Division 1 & 2

Conduit/Cabling: · General purpose cable · Cable capacitance and inductance must be considered · Barriers (Associated Apparatus) limit voltage and current Connections: · General purpose connectors · Quick connectors without limitation Field Instrument Components: · Field instruments must be classified as simple (non-energy storing) or IS (IS Apparatus) · IS devices must be approved per FISCO or entity concept · Parameter matching using entity concept: IS Apparatus Associated Apparatus Lowest Vmax in segment > Voc Lowest Imax in segment > Isc Lowest Pmax in segment > Pt Ctotal (Field Devices+Cable) < Ca Ltotal (Field Devices+Cable) < La · Parameter matching using FISCO is same as entity concept except cable and device Li & Ci may be ignored (Must be within established FISCO values) Special Notes: · Instrument wiring may be manipulated while energized · Protected drop connectors are recommended since bus performance will be affected by short circuit on the spur

JMM933 _C3 I/O module with pneumatic valve and clear cover

PLTC/ITC

DCN

Passive Drop Connector 8 Amp max

* Drop connector provides over voltage and short circuit protection to spur and acts as barrier for nonincendive field wiring and related apparatus

Terminator - 461111 Fits into standard terminal strip spacing

Nonincendive Equipment Used in Explosion Proof & Tray Cabling Systems Class I & II, Division 2 Only

Seal-Offs not required Liquidtight conduit may be used where flexibility is required Field instruments must be nonincendive equipment rated Quick connectors may be used with the following provisions: 1. Power removed before plugging and unplugging 2. Current does not exceed 3 amps @ 120VAC 3. Cord is listed for hard usage with receptacle and plug of the locking and grounding type and does not exceed 900mm (3ft) 4. A label is attached to the receptacle warning against uplugging while energized Special Notes: · Enclosures may be opened while circuits are energized but wiring may not be manipulated until power is removed · · · ·

Consult StoneL's ValvePoint Catalog for additional products and more information on models and options.

Quartz Series VCTs*

Explosion proof aluminum platform with solid state dual module Aluminum Cover ­ use for Class I & II, Div. 1 and 2 Clear Cover ­ use for Class I & II, Div. 2

Eclipse Series VCTs*

Modular direct namur mount polycarbonate platform with integral proximity sensors

Onyx Series VCTs*

Polycarbonate enclosure with integral pneumatic valve and solid state sensors in dual module

ECG

ECG93 _ _ _ Wired with (2) microconnectors

ON

QZ-1

QZP93E _ _ Aluminum cover & (2) NPT conduits

ON93 _ _ _ _ _ _ Select brass or stainless steel pneumatic valve

ECN

ECN93_ _ _ Integral terminal strip & (2) NPT conduits

Prism Series

Polycarbonate enclosure with integral pneumatic valve and solid state sensors in dual module adaptable to fiaphragm and angle valves

Foundation Fieldbus Wiring Guidelines

Topology: Bus with spurs or tree; terminators required Number of Field Devices: 2 to 16 typical; theoretical maximum of 32 per segment Cabling: Shielded twisted pair Cable Length: 1900 meters (6,125 ft.) total of trunk length and spurs No. Devices Max. Spur Length 15 to 16 60 m (197 ft.) 13 to 14 90 m (295 ft.) 2 to 12 120m (394 ft.)

Legend

General Purpose Cable Intrinsically Safe general purpose cable PLTC/ITC in cable tray PLTC/ITC supported by messenger wire PLTC/ITC with strut support Rigid metal conduit or intermediate steel conduit Metal clad flexible conduit Liquidtight flexible conduit Seal fitting Quick mini connector Quick mini connector with clasp Quick micro connector (General Purpose Cable) Compression fitting

QZ-2

QZP93C _ _ Clear cover & (2) NPT conduits

Hawkeye Series

Solid state sensor ideal for point sensing.

HK

HK5_ _ _ _ _ Interface with FF I/O module. Available with 1/2" NPT or quick connectors

PM

PM93 _ _ _ _ _ _ _ Available with NPT, compression fittings or quick connectors

*VCTs: Valve Communication Terminals

StoneL Corporation Telephone 218-739-5774 www.stonel.com

PUB # FL-713-09/04

NEC 500 Standards

Information