RAYCHEM - EPKT Terminations

Termination systems for polymeric and MIND paper insulated cables from 7.2kV up to 36kV

This worksheet enables you to arrive at a part number for an EPKT termination. Choose one figure from the left-hand column of each table.

Typical part number: EPKT 17C 3MO H3 B05 Voltage in kV 7 17 24 36 Size in mm² A B C D E F No. of Cores 1 3 Dielectric X M Location I O Length H1 H2 H3 H4 For single (1) core For three (3) core For 7.2kV For 12kV & 17kV For 24kV For 36kV 7.2kV 16 - 35 50 - 95 120 - 185 240 - 400 500 - 1000 -

Voltage (Umax) Cable size Number of cores Dielectric Location Length (3-core cables) Accessories

12kV & 17.5kV 16 - 25 35 - 70 95 - 185 240 - 400 500 - 800 1000

24kV 25 - 50 70 - 185 240 - 300 400 - 630 800 - 1000

36kV 50 - 95 120 - 185 240 - 500 630 - 1000

XLPE For MIND non-draining paper (not applicable for draining paper cables) Of the termination For INDOOR For OUTDOOR

For 450mm long For 650mm long (min for 17.5kV outdoor and 36kV indoor) For 800mm long (min for 24kV outdoor and 36kV outdoor) For 1200mm long

Note: The non tracking tubing (Red) can be supplied in one continuous length by adding the mod code "F" Example: EPKT 17C 3MO H4-F (3600mm Long).