Read Fire Protection - Chapter 1 text version

2007 APPROVAL GUIDE

CHAPTER 1

AUTOMATIC SPRINKLER SYSTEMS

Automatic sprinkler protection is recommended for industrial and other buildings having combustible construction or combustible occupancies. There are many FM Approved types of automatic sprinklers. Typical examples include: upright, pendent, flush, recessed, concealed, sidewall, dry-pendent and dry-upright, Early Suppression Fast Response (ESFR), Quick Response (QR), extended coverage, corrosion resistant, large drop, rack storage and decorative coated. A sprinkler operates automatically when the heat-actuated element is heated to, or above, its thermal rating. Selection of the proper temperature rating for automatic sprinklers is important. The proper rating provides a factor of safety designed to prevent premature operation. The rating should be selected from the following table:

TEMPERATURE RATINGS OF SPRINKLERS

Rating Ordinary Intermediate High Extra High Very Extra High Ultra High Max Temperature at Sprinkler Level 100°F (38°C) 150°F (66°C) 225°F (107°C) 300°F (149°C) 365°F (185°C) 465°F (241°C) Rated Temperature of Sprinkler 135° through 170°F (57° through 77°C) 175° through 225°F (79° through 107°C) 250° through 300°F (121° through 149°C) 325° through 375°F (163° through 191°C) 400° through 475°F (204° through 246°C) 500° through 650°F (260° through 343°C) Frame Color Unpainted* White Blue Red Green Orange

*Frame arms of 135°F (57°C) sprinklers of some manufacturers are painted black.

Sprinklers of ``very extra high'' and ``ultra high'' ratings are primarily used for internal protection of chambers such as ovens and dryers having working temperatures above 300°F (149°C). When the sprinklers are normally heated to the working temperature of the oven or dryer, under accidental fire conditions they will operate fast enough for safe protection. However, when the sprinklers are initially at the same temperature as a cold oven or dryer, operation may be so severely retarded that the oven or dryer is virtually without internal sprinkler protection. Specially coated or plated sprinklers are available for use where corrosion resistance is desired and decorative coated sprinklers are available for areas where improved appearance is desired. For corrosion resistance, wax is satisfactory except in extreme atmospheres. Wax has too low a melting point for high-degree heads, whereas a bituminous coating affords some protection. A lead coating protects against certain mild corrosive atmospheres. Wax-over-lead provides good sprinkler protection. Corrosion resistant sprinklers such as those manufactured from stainless steel or other corrosion resistant materials currently afford the best available protection. Common decorative finishes are bright brass, chrome, paint, or polyester coating. These finishes are for decorative purposes only and are not FM Approved for corrosion resistance. Only sprinklers supplied by the listed manufacturers are FM Approved. Any change in the device after it leaves the manufacturer voids the Approval. Coated, plated and painted sprinklers rated above 165°F (74°C) have the standard temperature color code either on the frame arms or on the compression screws, except in the case of bulb type decorative coated sprinklers in which the bulb fluid color indicates the temperature rating per the following table:

Temperature Rating °F (°C) 135° (57°) 155° (68°) 175° (79°) 200° (93°) 250°, 286° (121°, 141°) 325°, 360° (162°, 182°) 400°­650° (204°­343°) Bulb Color Code Orange Red Yellow Green Blue Mauve Black

When selecting a specific type of sprinkler, refer to the FM Global Property Loss Prevention Data Sheets to ensure that the sprinkler selected is capable of providing adequate fire protection for the intended occupancy. In addition, working plans of proposed layouts, showing all details with respect to location of sprinklers and piping, description

1-2

September 2007 -- Approval Guide Automatic Sprinkler Systems

of the occupancy and details of construction, should be sent to your insurance company for review before the materials are fabricated. The plans will be accepted or changes will be recommended to assure that the work will be done according to the best practice and to avoid the possibility of later requests for changes. Unless otherwise noted, automatic sprinkler system components, which are subjected to system water pressure, have a rated working pressure of 175 psi (1205 kPa). In this section, FM Approved sprinklers are listed in a tabular format. Because this format limits the space in which the information can be provided, the following conventions are used: The sprinkler nominal discharge coefficient (K-factor) is expressed in US customary units of gal/min/(psi)½. Sprinkler response categories are abbreviated as follows:

SR QR FR Quick Response Suppression Mode Fast Response Standard Response

Heat responsive elements are identified as either Fusible or, in the case of bulb type elements, with the nominal bulb diameter in millimeters (e.g., 2.5 mm, 3 mm, etc.) Nominal thread sizes are expressed using American National Standard Taper Pipe Threads (NPT). Sprinklers intended for sale outside the United States shall have threads which are in compliance with other national or international standards as permitted at the sole discretion of FM Approvals. Sprinkler finishes are identified as follows:

Finish Brass Chrome Black Plated Bright Brass Lead Wax Wax Over Lead Polyester Painted Unfinished, Plain Brass or Bronze Chrome Plated Black Plated Bright Brass Plated Lead Coated (for extra corrosion protection in some atmospheres) Wax Coated (for extra corrosion protection in some atmospheres) Wax Over Lead Coated (for extra corrosion protection in some atmospheres) Polyester Coated (any color) Painted (any color) Description

Sprinkler nominal temperature ratings are expressed in degrees Fahrenheit (°F) followed by the equivalent in degrees Celsius (°C). Company names are abbreviated in the individual listings.

Company Anber Globe Angus CPF GW Globe Grinnell Kidde Nanjing Minimax Paradise Reliable Rolland Senju Spraying Sys Tyco Tyco Mfg Ltd Victaulic Viking Viking SA Manufacturer's Name and Address Anber Globe SA, Av de Las Flores 13, Parque Ind El Molino, 28970 Humanes de Madrid, Madrid Spain Angus Fire Sprinklers, Thame Park Rd, Oxfordshire 0X9 3RT, United Kingdom CPF Industriale SpA, Via E Fermi, 98-25064 Gussago Brescia, Italy GW Sprinkler A/S, Kastanievej 15 DK-5620 Glamsbjerg Denmark Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658 Grinnell Corp, 3 Tyco Park, Exeter NH 03833 Kidde Fire Fighting, 2 Executive Way, Ranson WV 25438 Nanjing Fire Protection Technology Co Ltd, 12 Shiyang Rd, Baxia District, Nanjing, China Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840 Bad Oldesloe, Germany Paradise Industry Co, Ltd, 65-2 Chooneui-Dong, Woonmi-Ku, Bucheon-City, Kyunggi-Do Korea (420-120) Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313 Rolland Arroseurs Sprinklers, Ste Rolland/Usine, 73410 Mognard, France Senju Sprinkler Co Ltd, 23 Senju-Hashido-Cho Adachi-Ku Tokyo Japan 120 Spraying Systems Co, North Ave at Schmale Rd, Box 7900, Wheaton IL 60189 Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446 Tyco Fire Products Manufacturing Ltd, Stockport Trading Estate, Yew St Stockport, Cheshire SK4 2JW, United Kingdom Victaulic Company, Box 31, Easton PA 18044 The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058 Viking SA, Zone Industrielle Haneboesch, L-4562, Differdange/Niedercorn, Luxembourg

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-3

Control Mode Sprinklers Open Sprinklers, Control Mode (Specific Application) Window and Cornice

Window and cornice sprinklers are open sprinklers designed to protect windows and combustible cornices against outside exposing fires. Window and cornice sprinklers have no automatic operating element and are available in various nominal orifice sizes. Their operation depends usually on the opening of a control valve by hand, although they are sometimes automatically controlled with a thermostatically operated deluge valve.

Open Sprinklers, Control Mode (Specific Application) Window and Cornice (Class 2014)

Company Grinnell Grinnell Grinnell Reliable Reliable Reliable Reliable Reliable Reliable Reliable Reliable Spraying Sys Spraying Sys Spraying Sys Spraying Sys Viking Viking Viking Viking Model Issue A Issue A Issue A R0413 R0414 R0415 R0418 R0416 R0411 R0428 R0426 FM-1/2K60 FM-1/2K80 FM-3/4K120 FM-3/4K210 VK790 VK791 VK792 VK793 Orifice Size

1/4 5/16 3/8 1/4 5/16 3/8 1/2 5/8 3/4 1/2 5/8

NPT

1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 3/ 4 3/ 4 1/ 2 3/ 4 1/ 2 1/ 2 3/ 4 3/ 4 1/ 2 1/ 2 1/ 2 1/ 2

Type Window Sprinkler Window Sprinkler Window Sprinkler Window Sprinkler Window Sprinkler Window Sprinkler Window Sprinkler Window Sprinkler Window Sprinkler Cornice Sprinkler Cornice Sprinkler Window Sprinkler Window Sprinkler Window Sprinkler Window Sprinkler Window Sprinkler Window Sprinkler Window Sprinkler Window Sprinkler

in. in. in. in. in. in. in. in. in. in. in. in. in. in. in. in. in. in. in.

17/64 5/16 3/8 1/2 1/4 5/16 3/8 7/16

K2.8 Standard Spray Sprinklers

Control mode standard spray sprinklers have deflectors specially designed to discharge water in all directions below the plane of the deflector. Thus, the spray pattern is roughly that of a half sphere filled with water spray. Little or no water is discharged upward to wet the ceiling. Upright control mode sprinklers are not intended for use in the pendent position; FM Approved pendent control mode sprinklers are required. Control mode automatic sprinklers with a nominal discharge coefficient of 2.8 gal/min/(psi)½ have cross sectional dimensions of the water passageway less than 3/8 in. and may require the use of individual or system strainers per the appropriate FM Global Property Loss Prevention Data Sheets.

FM Approvals

1-4

September 2007 -- Approval Guide Automatic Sprinkler Systems

K2.8 Upright (Class 2002)

Company Kidde Reliable Reliable Reliable Tyco Tyco Mfg Ltd Victaulic Victaulic Viking Viking Viking SA Model AS2702 R1021 R1021 R1721 TY1151 TY1151 V2701 V2701 VK001 VK005 VK001 K 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 Type Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Response SR SR SR SR SR SR SR SR SR SR SR Element 5 mm Fusible Fusible 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm Fusible 5 mm NPT (in.)

1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2

Finishes Brass, Chrome, Wax, Lead, Wax Over Lead Brass, Chrome, Black Plated, Bright Brass, Lead Wax, Wax Over Lead Brass, Chrome, Black Plated, Bright Brass Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester, Lead Wax, Wax Over Lead Brass, Chrome, Wax Brass Brass, Chrome, Wax

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 165°, 212°F (57°, 74°, 100°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 155°, 200°F (68°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 165°, 220°F (74°, 104°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

K2.8 Upright, Quick Response (Class 2020)

Company Tyco Victaulic Viking Model TY1131 V2702 VK325 K 2.8 2.8 2.8 Type Upright Upright Upright Response QR QR QR Element 3 mm 3 mm 3 mm NPT (in.)

1/ 2 1/ 2 1/ 2

Finishes Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester, Lead Brass, Chrome

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

K2.8 Pendent (Class 2002)

Company Kidde Reliable Reliable Tyco Tyco Mfg Ltd Model AS2701 R1011 R1011 TY1251 TY1251 K 2.8 2.8 2.8 2.8 2.8 Type Pendent Pendent Pendent Pendent Pendent Response SR SR SR SR SR Element 5 mm Fusible Fusible 5 mm 5 mm NPT (in.)

1/ 2 1/ 2 1/ 2 1/ 2 1/ 2

Finishes Brass, Chrome, Wax, Lead, Wax Over Lead Brass, Chrome, Black Plated, Bright Brass, Lead Wax, Wax Over Lead Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 165°, 212°F (57°, 74°, 100°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-5

Company Viking Viking Viking SA

Model VK003 VK007 VK003

K 2.8 2.8 2.8

Type Pendent Pendent Pendent

Response SR SR SR

Element 5 mm Fusible 5 mm

NPT (in.)

1/ 2 1/ 2 1/ 2

Finishes Brass, Chrome, Wax Brass Brass, Chrome, Wax

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 165°, 220°F (74°, 104°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

K2.8 Pendent, Quick Response (Class 2020)

Company Tyco Viking Model TY1231 VK329 K 2.8 2.8 Type Pendent Pendent Response QR QR Element 3 mm 3 mm NPT (in.)

1/ 2 1/ 2

Finishes Brass, Chrome, Bright Brass, Polyester Brass, Chrome

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93° 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

K2.8 Flush, Recessed and Concealed (Pendent)

Pendent flush, recessed and concealed sprinklers are intended for use with a concealed piping system. Flush types are constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution. Recessed types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed types incorporate a cover plate which is heat activated and can be manually removed to prevent over-painting of the cover plate. All of these sprinkler types are intended for use where attractive appearance under a ceiling is desired, in such occupancies as offices, hotel lobbies, dining rooms, clubs and similar properties. FM Approved flush, recessed and concealed sprinklers are limited to a maximum temperature rating of 225°F (107°C) and to protection of hazard occupancies described in the FM Global Property Loss Prevention Data Sheets. Quick response flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.

K2.8 Flush, Recessed and Concealed (Class 2015)

Company Reliable Reliable Reliable Reliable Viking Viking Viking Model R2211 R2212 R5411 R5412 VK003 VK003 VK461 K 2.8 2.8 2.8 2.8 2.8 2.8 2.8 Type Concealed Pendent Adj. Concealed Pendent Concealed Pendent Adj. Concealed Pendent Recessed Pendent Recessed Pendent Concealed Pendent Response SR SR SR SR SR SR SR Element Fusible Fusible Fusible Fusible 5 mm 5 mm 3 mm NPT (in.)

1/2 1/2 1/2 1/2 1/2 1/2 1/2

Finishes Brass Brass Brass Brass Brass, Chrome Brass, Chrome Brass 165°F (74°C) 165°F (74°C) 165°F (74°C) 165°F (74°C)

Temp Ratings, °F (°C)

135°, 155°, 175°, 200°, 212°F (57°, 68°, 79°, 93°, 100°C) with E-1 Recessed Escutcheon 135°, 155°, 175°, 200°, 212°F (57°, 68°, 79°, 93°, 100°C) with E-2 Threaded Recessed Escutcheon 155°, 175°, 200°F (68°, 79°, 93°C)

K5.6 Standard Spray Sprinklers

Control mode standard spray sprinklers have deflectors specially designed to discharge water in all directions below the plane of the deflector. Thus, the spray pattern is roughly that of a half sphere filled with water spray. Little or no water is discharged upward to wet the ceiling. Upright control mode sprinklers are not intended for use in the pendent position. FM Approved pendent control mode sprinklers are required. Control mode automatic sprinklers with a nominal discharge coefficient of 5.6 gal/min/(psi)½ are similar to control mode sprinklers with a nominal discharge coefficient of 2.8 gal/min/(psi)½, except that they discharge 100% more water at the same discharge pressure.

FM Approvals

1-6

September 2007 -- Approval Guide Automatic Sprinkler Systems

K5.6 Upright (Class 2016)

Company Anber Globe Angus CPF GW Globe Globe Kidde Kidde Nanjing Paradise Reliable Reliable Reliable Rolland Senju Tyco Tyco Tyco Tyco Tyco Tyco Tyco Mfg Ltd Tyco Mfg Ltd Victaulic Victaulic Model GN5661 S SKR 15 S GL5661 GL5661 AS5602 AS5602 NX003 PI210 R1025 R1025 R1725 N SS6512 TY3104 TY3104 TY3111 TY3111 TY3151 TY3151 TY3104 TY3151 V2703 V2703 K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 Type Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Response SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR Element 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm Fusible Fusible 5 mm 5 mm Fusible 5 mm 5 mm Fusible Fusible 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm NPT (in.)

1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome Brass, Chrome, Polyester Brass, Chrome, Polyester Wax, Lead, Wax Over Lead Brass, Bright Brass, Chrome, Lead Wax, Wax Over Lead Brass, Chrome Chrome Brass, Chrome, Black Plated, Bright Brass Wax, Lead, Wax Over Lead Brass, Chrome, Black Plated, Bright Brass Brass, Chrome Brass Brass, Chrome, Bright Brass, Polyester Wax Brass, Chrome Wax, Lead Brass, Chrome, Bright Brass, Polyester Wax Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester, Lead Wax, Lead, Wax Over Lead

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286° (57°, 68°, 79°, 93°, 141° ) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 155°, 200°F (68°, 93°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 155°, 175°, 200°F (68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57° , 68°, 79°, 93°C) 155°, 200°F (68°, 93°C) 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 162°, 205°, 282°F (72°, 96°, 139°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C) 135°, 155°, 200°F (57°, 68°, 93°C) 165°, 212°, 280°F (74°, 100°, 138°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 155°, 200°F (68°, 93°C)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-7

Company Viking Viking Viking Viking SA

Model VK100 VK108 VK145 VK100

K 5.6 5.6 5.6 5.6

Type Upright Upright Upright Upright

Response SR SR SR SR

Element 5 mm Fusible 5 mm 5 mm

NPT (in.)

1/ 2 1/ 2 1/ 2 1/ 2

Finishes Brass, Chrome, Wax, Polyester Brass, Polyester Brass, Chrome, Wax, Polyester Brass, Chrome, Wax

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 212°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 100°, 141°, 182°, 260°C) 165°, 220°, 286°F (74°, 104°, 141°C) 135°, 155°, 175°, 200°, 212°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 100°, 141°, 182°, 260°C) 135°, 155°, 175°, 200°, 212°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 100°, 141°, 182°, 260°C)

K5.6 Upright, Quick Response (Class 2020)

Company Anber Globe Angus CPF GW Globe Kidde Nanjing Paradise Reliable Rolland Tyco Tyco Tyco Tyco Mfg Ltd Tyco Mfg Ltd Victaulic Victaulic Viking Viking Viking Model GN5615 S SKR 15 S GL5615 AS5652 NX004 PI211 R3625 N TY3105 TY3121 TY3131 TY3105 TY3131 V2704 V2704 VK300 VK301 VK345 K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 Type Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Response QR QR QR QR QR QR QR QR QR QR QR QR QR QR QR QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm Fusible 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm Fusible 3 mm NPT (in.)

1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Bright Plated Brass, Chrome Chrome Brass, Chrome, Bright Brass Brass, Chrome Brass, Chrome, Bright Brass, Polyester Brass, Chrome Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester, Lead Wax, Lead, Wax Over Lead Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°F (57°,68°,79°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°F (57°, 68°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 165°, 212°F, (74°, 100°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 155°, 200°F (68°, 93°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 165°, 205°F, (74°, 96°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

FM Approvals

1-8

September 2007 -- Approval Guide Automatic Sprinkler Systems

K5.6 Pendent (Class 2017)

Company Anber Globe Angus CPF GW Globe Globe Kidde Kidde Paradise Reliable Reliable Reliable Reliable Reliable Rolland Senju Tyco Tyco Tyco Tyco Tyco Tyco Tyco Mfg Ltd Tyco Mfg Ltd Victaulic Model GN5651 S SKR 15 S GL5651 GL5651 AS5601 AS5601 PI220 R1015 R1015 R1015 R1715 RA1314 N SS6511 TY3204 TY3204 TY3211 TY3211 TY3251 TY3251 TY3204 TY3251 V2707 K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 Type Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Response SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR Element 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm Fusible Fusible Fusible 5 mm 5 mm 5 mm Fusible 5 mm 5 mm Fusible Fusible 5 mm 5 mm 5 mm 5 mm 5 mm NPT (in.)

1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2

Finishes Brass, Chrome Brass, Chrome, Polyester Brass, Chrome Brass, Chrome, Polyester Brass, Chrome, Polyester Wax, Lead, Wax Over Lead Brass, Bright Brass, Chrome, Lead Wax, Wax Over Lead Chrome Brass, Chrome, Black Plated, Bright Brass Lead Wax, Wax Over Lead Brass, Chrome, Black Plated, Bright Brass Brass, Bright Brass, Chrome, Black Plated, Polyester Brass, Chrome Brass Brass, Chrome, Bright Brass, Polyester Wax Brass, Chrome Wax, Lead Brass, Chrome, Bright Brass, Polyester Wax Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester, Lead

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286° (57°, 68°, 79°, 93°, 141°) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 155°, 200°F (68°, 93°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 155°, 175°, 200°F (68°, 79°, 93°C) 155°, 200°F (68°, 93°C) 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C) 165°, 212°, 286°F (74°, 100°, 141°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 162°, 205°, 282°F (72°, 96°, 139°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C) 135°, 155°, 200°F (57°, 68°, 93°C) 165°, 212°, 280°F (74°, 100°, 138°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-9

Company Victaulic Viking Viking Viking SA

Model V2707 VK102 VK110 VK102

K 5.6 5.6 5.6 5.6

Type Pendent Pendent Pendent Pendent

Response SR SR SR SR

Element 5 mm 5 mm Fusible 5 mm

NPT (in.)

1/ 2 1/ 2 1/ 2 1/ 2

Finishes Wax, Wax Over Lead Brass, Chrome, Polyester, Wax Brass, Polyester Brass, Chrome, Polyester, Wax

Temp Ratings, °F (°C) 155°, 200°F (68°, 93°C) 135°, 155°, 175°, 200°, 212°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 100°, 141°, 182°, 260°C) 165°, 220°, 286°F (74°, 104°, 141°C) 135°, 155°, 175°, 200°, 212°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 100°, 141°, 182°, 260°C)

K5.6 Pendent, Quick Response (Class 2020)

Company Anber Globe Angus CPF GW Globe Kidde Paradise Paradise Reliable Reliable Rolland Tyco Tyco Tyco Tyco Tyco Mfg Ltd Tyco Mfg Ltd Victaulic Victaulic Viking Viking Model GN5601 S SKR 15 S GL5601 AS5651 PI221 PI222 R3615 RA1414 N TY3201 TY3205 TY3221 TY3231 TY3205 TY3231 V2708 V2708 VK302 VK303 K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 Type Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Response QR QR QR QR QR QR QR QR QR QR QR QR QR QR QR QR QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm Fusible 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm Fusible NPT (in.)

1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2 1/ 2

Finishes Brass, Chrome Brass, Chrome, Polyester Brass, Chrome Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Bright Brass Chrome Chrome Brass, Chrome, Bright Brass Brass, Bright Brass, Chrome, Black Plated, Polyester Brass, Chrome Chrome Brass, Chrome, Bright Brass, Polyester Brass Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester, Lead Wax, Wax Over Lead Brass, Chrome, Polyester Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°F (57°, 68°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 155°F (68°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 165°, 205°F (74°, 96°C)

FM Approvals

1-10

September 2007 -- Approval Guide Automatic Sprinkler Systems

Company Viking SA

Model VK302

K 5.6

Type Pendent

Response QR

Element 3 mm

NPT (in.)

1/ 2

Finishes Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F, (57°, 68°, 79°, 93°, 141°C)

K5.6 Standard Sidewall

Sidewall automatic sprinklers are equipped with a special deflector which discharges most of the water in a forward direction. They are special purpose sprinklers originally developed for locations such as executive offices, hotel lobbies and dining rooms, where the installation of standard sprinklers with the usual ceiling spacing and pipe location may be objectionable because of appearance. Installed near the junction of the ceiling and wall, they are satisfactory for light hazards and where ceiling protection is not an important factor. They are also installed for special applications where their directional properties are desirable. Approval is limited to control mode sprinklers with a nominal discharge coefficient of 5.6. gal/min/(psi)½ only, in nominal temperature ratings of 300°F (149°C) or lower. Vertical sidewall sprinklers are FM Approved for use in both the upright and pendent positions, except where noted otherwise.

K5.6 Sidewall (Class 2012)

Company Angus GW Globe Globe Kidde Reliable Reliable Reliable Reliable Reliable Reliable Reliable Reliable Reliable Tyco Tyco Tyco Model S S GL5670 GL5675 AS5632 R1235 R1235 R1285 R1285 R1285 R1735 R1735 R1785 R1785 TY3304 TY3304 TY3311 K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 Type Vertical Sidewall Vertical Sidewall Horizontal Sidewall Vertical Sidewall Horizontal Sidewall Horizontal Sidewall Horizontal Sidewall Vertical Sidewall Vertical Sidewall Vertical Sidewall Horizontal Sidewall Horizontal Sidewall Vertical Sidewall Vertical Sidewall Horizontal Sidewall Horizontal Sidewall Horizontal Sidewall Response SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR Element 5 mm 5 mm 5 mm 5 mm 5 mm Fusible Fusible Fusible Fusible Fusible 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm Fusible NPT (in.)

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

Brass, Bright Brass, Chrome, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) Wax, Lead, Wax Over Lead Brass, Chrome, Black Plated, Bright Brass, Lead Wax, Wax Over Lead Lead Wax, Wax Over Lead Brass, Chrome, Black Plated, Bright Brass, Lead Brass, Chrome, Black Plated, Bright Brass Lead, Wax, Wax Over Lead Lead, Wax, Wax Over Lead Brass, Chrome, Black Plated, Bright Brass Brass, Chrome, Polyester Wax Brass, Chrome 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C) 165°, 212°F (74°, 100°C) 165°, 212°, 286°F (74°, 100°, 141°C) 165°, 212°F (74°, 100°C) 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°C) 135°, 155°, 200°F (57°, 68°, 93°C) 165°, 212°, 280°F (74°, 100°, 138°C)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-11

Company Tyco Tyco Tyco Tyco Tyco Mfg Ltd Tyco Mfg Ltd Victaulic Victaulic Viking Viking Viking Viking Viking SA Viking SA

Model TY3351 TY3351 TY3451 TY3451 TY3304 TY3451 V2709 V2709 VK104 VK106 VK112 VK114 VK104 VK106

K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6

Type Horizontal Sidewall Horizontal Sidewall Vertical Sidewall Vertical Sidewall Horizontal Sidewall Vertical Sidewall Horizontal Sidewall Horizontal Sidewall Horizontal Sidewall Vertical Sidewall Horizontal Sidewall Vertical Sidewall Horizontal Sidewall Vertical Sidewall

Response SR SR SR SR SR SR SR SR SR SR SR SR SR SR

Element 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm Fusible Fusible 5 mm 5 mm

NPT (in.)

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Finishes Brass, Chrome, Polyester Wax

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F, 360°F (57°, 68°, 79°, 93°, 141°, 182°C ) 135°, 155°, 200°F (57°, 68°, 93°C)

Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, Polyester 141°, 182°C) Wax Brass, Chrome, Polyester 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°C)

Brass, Chrome, Bright Brass, 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C) Polyester Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) Polyester, Lead Wax, Wax Over Lead Brass, Chrome Brass, Chrome Brass Brass, Chrome Brass, Chrome Brass, Chrome 155°, 200°F (68°, 93°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 165°, 220°, 286°F (74°, 104°, 141°C) 165°, 220°, 286°F (74°, 104°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

K5.6 Sidewall, Quick Response (Class 2020)

Company Angus GW Globe Globe Kidde Reliable Reliable Tyco Tyco Tyco Tyco Model S S GL5626 GL5632 AS5633 R3635 R3685 TY3305 TY3321 TY3331 TY3431 K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 Type Vertical Sidewall Vertical Sidewall Horizontal Sidewall Vertical Sidewall Horizontal Sidewall Horizontal Sidewall Vertical Sidewall Horizontal Sidewall Horizontal Sidewall Horizontal Sidewall Vertical Sidewall Response QR QR QR QR QR QR QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm Fusible 3 mm 3 mm NPT (in.)

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Bright Brass Brass, Chrome, Bright Brass Brass, Chrome, Bright Brass

Temp Ratings, °F (°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°F (57°, 68°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°C) Polyester Brass, Chrome 165°, 212°F (74°, 100°C)

Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) Polyester Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) Polyester

FM Approvals

1-12

September 2007 -- Approval Guide Automatic Sprinkler Systems

Company Tyco Mfg Ltd Tyco Mfg Ltd Tyco Mfg Ltd Victaulic Viking Viking Viking Viking SA Viking SA

Model TY3305 TY3331 TY3431 V2710 VK304 VK305 VK306 VK304 VK306

K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6

Type Horizontal Sidewall Horizontal Sidewall Vertical Sidewall Horizontal Sidewall Horizontal Sidewall Horizontal Sidewall Vertical Sidewall Horizontal Sidewall Vertical Sidewall

Response QR QR QR QR QR QR QR QR QR

Element 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm

NPT (in.)

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Finishes

Temp Ratings, °F (°C)

Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°C) Polyester Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) Polyester Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) Polyester Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) Polyester, Lead Brass, Chrome Brass Brass, Chrome Brass, Chrome Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

K5.6 Corrosion Resistant (Stainless Steel)

The sprinklers listed below are primarily manufactured from a stainless steel alloy. These sprinklers afford improved corrosion protection, but should be selected for compatibility with the intended environment.

K5.6 Stainless Steel, Upright (Class 2042)

Company Angus GW Viking Model S S VK130 K 5.6 5.6 5.6 Type Upright Upright Upright Response SR SR SR Element 5 mm 5 mm 5 mm NPT (in.)

1/2 1/2 1/2

Finishes AISI 316 (UNS S31254) Stainless Steel Alloy AISI 316 (UNS S31254) Stainless Steel Alloy 316L (UNS-NO8367) Stainless Steel Alloy

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C)

K5.6 Stainless Steel, Upright Quick Response (Class 2020)

Company Angus GW Model S S K 5.6 5.6 Type Upright Upright Response QR QR Element 3 mm 3 mm NPT (in.)

1/2 1/2

Finishes AISI 316 (UNS S31254) Stainless Steel Alloy AISI 316 (UNS S31254) Stainless Steel Alloy

Temp Ratings, °F (°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°F (57°, 68°, 79°C)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-13

K5.6 Stainless Steel, Pendent (Class 2042)

Company Angus GW Viking Model S S VK132 K 5.6 5.6 5.6 Type Pendent Pendent Pendent Response SR SR SR Element 5 mm 5 mm 5 mm NPT (in.)

1/2 1/2 1/2

Finishes AISI 316 (UNS S31254) Stainless Steel Alloy AISI 316 (UNS S31254) Stainless Steel Alloy 316L (UNS-NO8367) Stainless Steel Alloy

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C)

K5.6 Stainless Steel, Pendent, Quick Response (Class 2020)

Company Angus GW Model S S K 5.6 5.6 Type Pendent Pendent Response QR QR Element 3 mm 3 mm NPT (in.)

1/2 1/2

Finishes AISI 316 (UNS S31254) Stainless Steel Alloy AISI 316 (UNS S31254) Stainless Steel Alloy

Temp Ratings, °F (°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°F (57°, 68°, 79°C)

K5.6 Flush, Recessed and Concealed (Pendent or Sidewall)

Pendent flush, recessed and concealed sprinklers are intended for use with a concealed piping system. Flush types are constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution. Recessed types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed types incorporate a cover plate which is heat activated and can be manually removed to prevent over-painting of the cover plate. All of these sprinkler types are intended for use where attractive appearance under a ceiling is desired, in such occupancies as offices, hotel lobbies, dining rooms, clubs and similar properties. Sidewall flush, recessed and concealed sprinklers are similar to pendent flush recessed and concealed sprinklers except that they are designed to be installed in a wall near the junction of the ceiling and wall. They are equipped with a special deflector which discharges most of the water in a forward direction. FM Approved flush, recessed and concealed sprinklers are limited to a maximum temperature rating of 225°F (107°C) and to protection of hazard occupancies described in the FM Global Property Loss Prevention Data Sheets. Quick response flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.

K5.6 Flush, Recessed and Concealed (Class 2015)

Company Angus GW Globe Globe Kidde Reliable Reliable Model S S GL5651 GL5654 AS5601 R1015 R1118 K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 Type Recessed Pendent Recessed Pendent Recessed Pendent Concealed Pendent Recessed Pendent Recessed Pendent Adj. Recessed Pendent Response SR SR SR SR SR SR SR Element 5 mm 5 mm 5 mm 5 mm 5 mm Fusible Fusible NPT (in.)

1/2 1/2 1/2 1/2 1/2 1/2 1/2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome Brass Brass, Chrome, Bright Brass Brass Brass 155°F (68°C) 155°F (68°C)

Temp Ratings, °F (°C)

135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 165°, 212°F (57°, 74°, 100°C) 135°, 165°, 212°F (57°, 74°, 100°C)

FM Approvals

1-14

September 2007 -- Approval Guide Automatic Sprinkler Systems

Company Reliable Reliable Reliable Reliable Reliable Reliable Senju Tyco Tyco Tyco Tyco Tyco Tyco Tyco Mfg Ltd Tyco Mfg Ltd Victaulic Victaulic Viking Viking Viking Viking Viking Viking SA

Model R1715 R2215 R2218 R5415 R5418 RA1314 SS2531 TY3204 TY3211 TY3251 TY3504 TY3505 TY3551 TY3204 TY3251 V2707 V3802 VK102 VK102 VK302 VK400 VK404 VK102

K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6

Type Recessed Pendent Concealed Pendent Adj. Concealed Pendent Concealed Pendent Adj. Concealed Pendent Recessed Pendent Flush Pendent Recessed Pendent Recessed Pendent Recessed Pendent Adj. Concealed Pendent Adj. Concealed Pendent Adj. Concealed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Concealed Pendent Recessed Pendent Concealed Pendent Concealed Pendent Flush Pendent Concealed Pendent Recessed Pendent

Response SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR

Element 5 mm Fusible Fusible Fusible Fusible 5 mm Fusible 5 mm Fusible 5 mm 5 mm 3 mm 5 mm 5 mm 5 mm 5 mm 3 mm 5 mm 5 mm 3 mm Fusible Fusible 5 mm

NPT (in.)

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Finishes Brass, Chrome, Black Plated, Bright Brass Brass Brass Brass Brass Brass, Bright Brass, Chrome, Black Plated, Polyester Chrome, Painted Brass, Chrome, Bright Brass Brass, Chrome Brass, Chrome, Bright Brass Brass Brass Brass Brass, Chrome, Bright Brass Brass, Chrome, Bright Brass Brass, Chrome, Bright Brass, Polyester Brass Brass, Chrome, Polyester Brass Brass Brass, Chrome, Polyester Brass Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 165°F (74°C) 165°F (74°C) 165°F (74°C) 165°F (74°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 162°F , 205°F (72°, 96°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) * 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) * 155°, 200°F (68°, 93°C) 155°, 200°F (68°, 93°C) 155°, 200°F (68°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) * 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) * 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 155°, 175°, 200°F (68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) with Viking E-1 or E-2 Recessed Escutcheon 155°, 175°, 200°F (68°, 79°, 93°C) with Viking E-1 or E-2 Recessed Escutcheon 155°, 175°, 200°F (68°, 79°, 93°C) with Viking E-1 or E-2 Recessed Escutcheon 165°, 220°F (74°, 104°C) 165°F (74°C) 135, 155, 175, 200, (57, 68, 79, 93) with Viking E-1, or E-2 Recessed Escutcheon

*This sprinkler is FM Approved with a die cast frame only.

K5.6 Flush, Recessed and Concealed, Quick Response (Class 2020)

Company Angus GW Globe Reliable Reliable Model S S GL5601 R3615 RA1414 K 5.6 5.6 5.6 5.6 5.6 Type Recessed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Response QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm 3 mm NPT (in.)

1/2 1/2 1/2 1/2 1/2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Bright Brass Brass, Bright Brass, Chrome, Black Plated, Polyester 155°F (68°C) 155°F (68°C)

Temp Ratings, °F (°C)

135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-15

Company Tyco Tyco Tyco Mfg Ltd Tyco Victaulic Viking Viking Viking SA

Model TY3205 TY3231 TY3205 TY3231 V2708 VK302 VK402 VK302

K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6

Type Recessed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Flush Pendent Recessed Pendent

Response QR QR QR QR QR QR QR QR

Element 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm Fusible 3 mm

NPT (in.)

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Finishes Brass, Chrome, Bright Brass Brass, Chrome, Bright Brass Brass, Chrome, Bright Brass Brass, Chrome, Bright Brass Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) with Viking E-1 or E-2 Recessed Escutcheon 165°F (74°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

K5.6 Sidewall Flush, Recessed and Concealed (Class 2015)

Company Tyco Tyco Tyco Mfg Ltd Tyco Mfg Ltd Victaulic Model TY3304 TY3351 TY3304 TY3351 V2709 K 5.6 5.6 5.6 5.6 5.6 Type Recessed Horizontal Sidewall Recessed Horizontal Sidewall Recessed Horizontal Sidewall Recessed Horizontal Sidewall Recessed Horizontal Sidewall Response SR SR SR SR SR Element 5 mm 5 mm 5 mm 5 mm 5 mm NPT (in.)

1/2 1/2 1/2 1/2 1/2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Bright Brass, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

K5.6 Sidewall Flush, Recessed and Concealed, Quick Response (Class 2020)

Company Tyco Tyco Tyco Mfg Ltd Tyco Mfg Ltd Victaulic Model TY3305 TY3331 TY3305 TY3331 V2710 K 5.6 5.6 5.6 5.6 5.6 Type Recessed Horizontal Sidewall Recessed Horizontal Sidewall Recessed Horizontal Sidewall Recessed Horizontal Sidewall Recessed Horizontal Sidewall Response QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm 3 mm NPT (in.)

1/2 1/2 1/2 1/2 1/2

Finishes Brass, Chrome, Bright Polyester Brass, Chrome, Bright Polyester Brass, Chrome, Bright Polyester Brass, Chrome, Bright Polyester Brass, Chrome, Bright Polyester, Lead

Temp Ratings, °F (°C) Brass, Brass, Brass, Brass, Brass, 135°, 155°, 175°, 200 °F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200 °F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

K5.6 Dry

Control mode dry automatic sprinklers are similar to other control mode sprinklers except that the sprinkler body is permanently secured to an extension nipple which includes a valve at the inlet end to prevent water from entering the nipple until the sprinkler operates. The sprinkler is threaded into a pipe fitting above the ceiling or enclosure at the valve end, thus replacing a drop nipple. The purpose of these devices is (1) to eliminate possible freezing due to the collection of condensation in the drop nipple (2) to eliminate the need to remove standard pendent sprinklers installed in a dry-pipe system in order to drain the system after flooding, and (3) to provide protection for unheated areas such as store windows or food freezers using a wet system in which the sprinkler pipes are located in a heated area. Unless otherwise noted, FM Approved dry sprinklers are limited to a maximum nominal length of 48 in. (1.2 m).

FM Approvals

1-16

September 2007 -- Approval Guide Automatic Sprinkler Systems

K5.6 Dry Upright (Class 2013)

Company Globe Tyco Viking Victaulic Model GL5683* TY3155 VK160 V3601 K 5.6 5.6 5.6 5.6 Type Dry Upright Dry Upright Dry Upright Dry Upright Response SR SR SR SR Element 5 mm 5 mm 5 mm 5 mm NPT (in.) 1 1 1 1 Finishes Brass, Chrome, Polyester Brass, Chrome Brass Brass, NICOTEF Coated Temp Ratings, °F (°C) 155°, 200°, 286°F (68°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°, 360°F (56°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)

* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Dry Upright Quick Response (Class 2020)

Company Globe Tyco Victaulic Model GL5639* TY3135 V3602 K 5.6 5.6 5.6 Type Dry Upright Dry Upright Dry Upright Response QR QR QR Element 3 mm 3 mm 3 mm NPT (in.) 1 1 1 Finishes Brass, Chrome, Polyester Brass, Chrome Brass, NICOTEF Coated Temp Ratings, °F (°C) 155°, 200°, 286°F (68°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)

* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Dry Pendent (Class 2013)

Company Globe Reliable Tyco Victaulic Viking Viking Model GL5679* R5314 TY3255 V3605 VK150 VK154 K 5.6 5.6 5.6 5.6 5.6 5.6 Type Dry Pendent Dry Pendent Dry Pendent Dry Pendent Dry Pendent Dry Adj. Pendent Response SR SR SR SR SR SR Element 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm NPT (in.) 1 1 1 1 1 1 Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome Brass, NICOTEF Coated Brass, Chrome Brass, Chrome Temp Ratings, °F (°C) 155°, 200°, 286°F (68°, 93°, 141°C) 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°, 360°F (56°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Dry Pendent, Quick Response (Class 2020)

Company Globe Reliable Tyco Model GL5635* R5714 TY3235 K 5.6 5.6 5.6 Type Dry Pendent Dry Pendent Dry Pendent Response QR QR QR Element 3 mm 3 mm 3 mm NPT (in.) 1 1 1 Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome Temp Ratings, °F (°C) 155°, 200°, 286°F (68°, 93°, 141°C) 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-17

Company Victaulic

Model V3606

K 5.6

Type Dry Pendent

Response QR

Element 3 mm

NPT (in.) 1

Finishes Brass, NICOTEF Coated

Temp Ratings, °F (°C) 155°, 286°F (68°, 141°C)

* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Dry Sidewall (Class 2013)

Company Globe Reliable Tyco Victaulic Viking Viking Model GL5685* R5334 TY3355 V3609 VK152 VK156 K 5.6 5.6 5.6 5.6 5.6 5.6 Type Dry Horizontal Sidewall Dry Horizontal Sidewall Dry Horizontal Sidewall Dry Horizontal Sidewall Dry Horizontal Sidewall Dry Adj. Horizontal Sidewall Response SR SR SR SR SR SR Element 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm NPT (in.) 1 1 1 1 1 1 Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome Brass, NICOTEF Coated Brass, Chrome, Bright Brass Brass, Chrome, Bright Brass Temp Ratings, °F (°C) 155°, 200°, 286°F (68°, 93°, 141°C) 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (56°, 68°, 79°, 93°, 141°C) 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Dry Sidewall, Quick Response (Class 2020)

Company Globe Reliable Tyco Victaulic Model GL5641* R5734 TY3335 V3610 K 5.6 5.6 5.6 5.6 Type Dry Horizontal Sidewall Dry Horizontal Sidewall Dry Horizontal Sidewall Dry Horizontal Sidewall Response QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm NPT (in.) 1 1 1 1 Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome Brass, NICOTEF Coated Temp Ratings, °F (°C) 155°, 200°, 286°F (68°, 93°, 141°C) 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)

* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Dry, Flush, Recessed and Concealed (Pendent or Sidewall)

Dry pendent flush, recessed and concealed sprinklers are dry sprinklers intended for use with a concealed piping system. Flush types are constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution. Recessed types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed types incorporate a cover plate which is heat activated and can be manually removed to prevent over-painting of the cover plate. All of these sprinkler types are intended for use where attractive appearance under a ceiling is desired, in such occupancies as offices, hotel lobbies, dining rooms, clubs and similar properties. Dry sidewall flush, recessed and concealed sprinklers are similar to dry pendent flush recessed and concealed sprinklers except that they are designed to be installed in a wall near the junction of the ceiling and wall. They are equipped with a special deflector which discharges most of the water in a forward direction. FM Approved flush, recessed and concealed sprinklers are limited to a maximum temperature rating of 225°F (107°C) and to protection of hazard occupancies described in the FM Global Property Loss Prevention Data Sheets. Quick response flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.

FM Approvals

1-18

September 2007 -- Approval Guide Automatic Sprinkler Systems

K5.6 Dry Flush, Recessed and Concealed (Class 2015)

Company Globe Globe Reliable Reliable Reliable Reliable Reliable Reliable Tyco Victaulic Victaulic Viking Viking Model GL5679* GL5685* R5314 R5314 R5334 R5714 R5714 R5734 TY3255 V3605 V3609 VK158 VK162 K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 Type Dry Recessed Pendent Dry Recessed Horizontal Sidewall Dry Concealed Pendent Dry Recessed Pendent Dry Recessed Horizontal Sidewall Dry Concealed Pendent Dry Recessed Pendent Dry Recessed Horizontal Sidewall Dry Recessed Pendent Dry Recessed Pendent Dry Recessed Horizontal Sidewall Dry Recessed Pendent Dry Recessed Horizontal Sidewall Response SR SR SR SR SR SR SR SR SR SR SR SR SR Element 5 mm 5 mm 5 mm 5 mm 5 mm 3 mm 3 mm 3 mm 5 mm 5 mm 5 mm 5 mm 5 mm NPT (in.) 1 1 1 1 1 1 1 1 1 1 1 1 1 Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome Brass, NICOTEF Coated Brass, NICOTEF Coated Brass, Chrome Brass, Chrome, Bright Brass Temp Ratings, °F (°C) 155°, 200°F (68°, 93°C) 155°, 200°F (68°, 93°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 175°, 200°F (56°, 68°, 79°, 93°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Dry Flush, Recessed and Concealed, Quick Response (Class 2020)

Company Globe Globe Tyco Victaulic Victaulic Model GL5635* GL5641* TY3235 V3606 V3610 K 5.6 5.6 5.6 5.6 5.6 Type Dry Recessed Pendent Dry Recessed Horizontal Sidewall Dry Recessed Pendent Dry Recessed Pendent Dry Recessed Horizontal Sidewall Response QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm 3 mm NPT (in.) 1 1 1 1 1 Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome Brass, NICOTEF Coated Brass, NICOTEF Coated Temp Ratings, °F (°C) 155°, 200°F (68°, 93°C) 155°, 200°F (68°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 200°F (57°, 68°, 93°C) 135°, 155°, 200°F (57°, 68°, 93°C)

* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Rack Storage

Rack storage sprinklers (also called intermediate level sprinklers) provide in-rack protection for rack storage arrays. These sprinklers are similar to the basic sprinkler types from which they are derived except that they are equipped with a disc mounted above the thermal-sensitive element which protects it from delayed operation as a result of water discharge from nearby sprinklers at higher elevations. Rack storage sprinklers are available with nominal discharge coefficients of 5.6 gal/min/(psi)½ and 8.0 gal/min/(psi)½ and in both upright and pendent configurations. When using quick response rack storage sprinklers, standard response sprinklers will continue to be required at the ceiling level in accordance with the FM Global Property Loss Prevention Data Sheets. Reference should be made to the FM Global Property Loss Prevention Data Sheets with regard to selection of type and temperature rating for a given installation.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-19

K5.6 Rack Storage, Upright (Class 2005)

Company Globe Kidde Reliable Tyco Tyco Victaulic Viking Viking Model GL5663 AS5604 R1425 TY3113 TY3153 V2721 VK550 VK552 K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 Type Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Response SR SR SR SR SR SR SR SR Element 5 mm 5 mm Fusible Fusible 5 mm 5 mm 5 mm Fusible NPT (in.)

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Finishes Brass Brass Brass Brass Brass Brass Brass Brass

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C) 165°, 212°, 280°F (74°, 100°, 138°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 165°, 220°, 286°F (74°, 104°, 141°C)

K5.6 Rack Storage, Upright, Quick Response (Class 2020)

Company Globe Reliable Tyco Tyco Victaulic Viking Viking SA

Model GL5617 R7095 TY3123 TY3133 V2722 VK556 VK556

K 5.6 5.6 5.6 5.6 5.6 5.6 5.6

Type Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright

Response QR QR QR QR QR QR QR

Element 3 mm 3 mm Fusible 3 mm 3 mm 3 mm 3 mm

NPT (in.)

1/2 1/2 1/2 1/2 1/2 1/2 1/2

Finishes Brass Brass Brass Brass Brass Brass Brass

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

K5.6 Rack Storage, Pendent (Class 2005)

Company Angus GW Globe

Model S S GL5672

K 5.6 5.6 5.6

Type Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent

Response SR SR SR

Element 5 mm 5 mm 5 mm

NPT (in.)

1/2 1/2 1/2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C)

FM Approvals

1-20

September 2007 -- Approval Guide Automatic Sprinkler Systems

Company Kidde Reliable Reliable Tyco Tyco Victaulic Viking Viking

Model AS5601 R1015 R7025 TY3204 TY3251 V2723 VK102 VK110

K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6

Type Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent

Response SR SR SR SR SR SR SR SR

Element 5 mm Fusible 5 mm 5 mm 5 mm 5 mm 5 mm Fusible

NPT (in.)

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Finishes Brass Brass Brass

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C )

Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, Polyester 93°, 141°, 182°, 260°C) Brass, Chrome, Bright Brass, 135°, 155°,175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, Polyester 93°, 141°, 182°, 260°C) Brass Brass Brass 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 165°, 220°, 286°F (74°, 104°, 141°C)

K5.6 Rack Storage, Pendent, Quick Response (Class 2020)

Company Angus GW Globe Reliable Tyco Tyco Tyco Victaulic Viking Viking SA Model S S GL5612 R3615 TY3205 TY3221 TY3231 V2724 VK302 VK302 K 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 Type Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Response QR QR QR QR QR QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm 3 mm Fusible 3 mm 3 mm 3 mm 3 mm NPT (in.)

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass Brass

Temp Ratings, °F (°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) Polyester Brass 165°, 212°F, (74°, 100°C)

Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) Polyester Brass Brass Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

K5.6 Extended Coverage Light Hazard (ECLH) (Pendent or Sidewall)

Control mode, Extended Coverage-Light Hazard (ECLH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of 15 ft by 15 ft (4.6 m by 4.6 m) for upright and pendent standard sprinklers and 14 ft by 14 ft (4.3 m by 4.3 m) for vertical and horizontal sidewall sprinklers. Upright and pendent ECLH sprinklers, regardless of nominal discharge coefficient, have a maximum spacing (width by length) of 20 ft by 20 ft (6.1 m by 6.1 m). Horizontal sidewall ECLH sprinklers with a nominal discharge coefficient of 5.6 gal/min/(psi)½ have a maximum spacing (width by length) of 16 ft by 20 ft (4.9 m by 6.1 m). Horizontal sidewall ECLH sprinklers with a nominal discharge coefficient of 8.0 gal/min/(psi)½ have a maximum spacing (width by length) of 16 ft by 24 ft (4.9 m by 7.3 m). The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. FM Approved ECLH sprinklers are limited to a maximum temperature rating of 175°F (79°C).

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-21

Extended Coverage Light Hazard (ECLH) K5.6 Pendent (Class 2022)

Company Viking Viking SA Model VK600 VK600 K 5.6 5.6 Type Pendent Pendent Response SR SR Element 3 mm 3 mm NPT (in.)

1/2 1/2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester 175°F (79°C) 175°F (79°C)

Temp Ratings, °F (°C)

Extended Coverage Light Hazard (ECLH) K5.6 Pendent, Quick Response (Class 2020)

Company Tyco Viking Viking SA Model TY3232 VK600 VK600 K 5.6 5.6 5.6 Type Pendent Pendent Pendent Response QR QR QR Element 3 mm 3 mm 3 mm NPT (in.)

1/2 1/2 1/2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester 155°F (68°C)

Temp Ratings, °F (°C)

135°, 155°F (57°, 68°C) 135°, 155°F (57°, 68°C)

Extended Coverage Light Hazard (ECLH) K5.6 Sidewall (Class 2022)

Company Tyco Tyco Mfg Ltd Model TY3332 TY3332 K 5.6 5.6 Type Horizontal Sidewall Horizontal Sidewall Response SR SR Element 3 mm 3 mm NPT (in.)

1/2 1/2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester 175°F (79°C) 175°F (79°C)

Temp Ratings, °F (°C)

Extended Coverage Light Hazard (ECLH) K5.6 Sidewall, Quick Response (Class 2020)

Company Reliable Tyco Tyco Tyco Tyco Mfg Ltd Model R4865 TY3302 TY3322 TY3332 TY3332 K 5.6 5.6 5.6 5.6 5.6 Type Horizontal Sidewall Horizontal Sidewall Horizontal Sidewall Horizontal Sidewall Horizontal Sidewall Response QR QR QR QR QR Element 3 mm 3 mm Fusible 3 mm 3 mm NPT (in.)

1/2 1/2 1/2 1/2 1/2

Finishes

Temp Ratings, °F (°C)

Brass, Chrome, Bright Brass, 135°, 155°, 175°F (57°, 68°, 79°C) Black Plated, Polyester Brass, Chrome, Bright Brass, 155°F (68°C) Polyester Brass, Chrome Brass, Chrome, Polyester Brass, Chrome, Polyester 165°F (74°C) 135°, 155°F (57°, 68°C) 135°, 155°F (57°, 68°C)

K5.6 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Pendent or Sidewall)

Control mode, Extended Coverage-Light Hazard (ECLH) flush, recessed and concealed sprinklers are ECLH sprinklers intended for use with a concealed piping system. Flush pendent types are constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution. Recessed pendent types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed pendent types incorporate a cover plate which is heat activated and can be manually removed to prevent over-painting of the cover plate. Sidewall flush, recessed and concealed sprinklers are similar to pendent flush recessed and concealed sprinklers except that they are designed to be installed in a wall near the junction of the ceiling and wall. They are equipped with a special deflector which discharges most of the water in a forward direction. All of these sprinkler types are intended for use in light hazard occupancies where attractive apearance under a ceiling is desired.

FM Approvals

1-22

September 2007 -- Approval Guide Automatic Sprinkler Systems

The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. Quick response ECLH flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.

Extended Coverage Light Hazard (ECLH) Flush, Recessed and Concealed (Class 2022)

Company Tyco Tyco Mfg Ltd Viking Model TY3332 TY3332 VK600 K 5.6 5.6 5.6 Type Recessed Horizontal Sidewall Recessed Horizontal Sidewall Recessed Pendent Response SR SR SR Element 3 mm 3 mm 3 mm NPT (in.)

1/ 2 1/ 2 1/ 2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester 175°F (79°C) 175°F (79°C) 175°F (79°C)

Temp Ratings, °F (°C)

Extended Coverage Light Hazard (ECLH) Flush, Recessed and Concealed, Quick Response (Class 2020)

Company Reliable Tyco Tyco Tyco Tyco Mfg Ltd Viking Model R4865 TY3232 TY3302 TY3332 TY3332 VK600 K 5.6 5.6 5.6 5.6 5.6 5.6 Type Recessed Horizontal Sidewall Recessed Pendent Recessed Horizontal Sidewall Recessed Horizontal Sidewall Recessed Horizontal Sidewall Recessed Pendent Response QR QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm NPT (in.)

1/ 2

Finishes Brass, Chrome, Bright Brass, Black Plated, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester 135°F (57°C) 155°F (68°C) 155°F (68°C)

Temp Ratings, °F (°C)

1/ 2 1/ 2 1/ 2 1/ 2 1/ 2

135°, 155°F (57°, 68°C) 135°, 155°F (57°, 68°C) 135°, 155°F (57°, 68°C)

K5.6 Wax Coated High Temperature

There are instances where high temperature sprinklers, rated 250-300°F (121-149°C), are installed for purposes other than expected ambient temperatures above 225°F (107°C) and where the environment is corrosive. The sprinklers listed below have been coated with a wax normally intended for intermediate temperature sprinklers, 175-225°F (79-107°C) These sprinklers are not recommended for installation in areas where the ambient temperature may exceed 150°F (66°C).

K5.6 Wax Coated, High Temperature, Upright (Class 2043)

Company Reliable Reliable Tyco Tyco Victaulic Model R1025 R1725 TY3104 TY3151 V2703 K 5.6 5.6 5.6 5.6 5.6 Type Upright Upright Upright Upright Upright Response SR SR SR SR SR Element Fusible 5 mm 5 mm 5 mm 5 mm NPT (in.)

1/2 1/2 1/2 1/2 1/2

Finishes Wax Wax Wax Wax Wax, Wax Over Lead 286°F (141°C) 286°F (141°C) 286°F (141°C) 286°F (141°C) 286°F (141°C)

Temp Ratings, °F (°C)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-23

K5.6 Wax Coated, High Temperature, Pendent (Class 2043)

Company Reliable Reliable Tyco Tyco Victaulic Model R1015 R1715 TY3204 TY3251 V2707 K 5.6 5.6 5.6 5.6 5.6 Type Pendent Pendent Pendent Pendent Pendent Response SR SR SR SR SR Element Fusible 5 mm 5 mm 5 mm 5 mm NPT (in.)

1/2 1/2 1/2 1/2 1/2

Finishes Wax Wax Wax Wax Wax, Wax Over Lead 286°F (141°C) 286°F (141°C) 286°F (141°C) 286°F (141°C) 286°F (141°C)

Temp Ratings, °F (°C)

Wax Coated, High Temperature, Sidewall (Class 2043)

Company Tyco Tyco Victaulic Model TY3351 TY3451 V2709 K 5.6 5.6 5.6 Type Horizontal Sidewall Vertical Sidewall Horizontal Sidewall Response SR SR SR Element 5 mm 5 mm 5 mm NPT (in.)

1/2 1/2 1/2

Finishes Brass Brass Wax, Wax Over Lead 286°F (141°C) 286°F (141°C) 286°F (141°C)

Temp Ratings, °F (°C)

K5.6 High Temperature Oven

Automatic sprinklers listed in this category are for use in high temperature ovens only. These sprinklers are not to be used in other occupancies.

K5.6 High Temperature Oven, Upright (Class 2016)

Company Grinnell Model G1036 K 5.6 Type Upright Response SR Element 11 mm NPT (in.)

1/2

Finishes Brass

Temp Ratings, °F (°C) 400°, 500°, 650°F (204°, 260°, 343°C)

K5.6 High Temperature Oven, Pendent (Class 2017)

Company Grinnell Model G1040 K 5.6 Type Pendent Response SR Element 11 mm NPT (in.)

1/2

Finishes Brass

Temp Ratings, °F (°C) 400°, 500°, 650°F (204°, 260°, 343°C)

K8.0 Standard Spray Sprinklers

Control mode standard spray sprinklers have deflectors specially designed to discharge water in all directions below the plane of the deflector. Thus, the spray pattern is roughly that of a half sphere filled with water spray. Little or no water is discharged upward to wet the ceiling. Upright control mode sprinklers are not intended for use in the pendent position FM Approved pendent control mode sprinklers are required. Control mode automatic sprinklers with a nominal discharge coefficient of 8.0 gal/min/(psi)½ are similar to control mode sprinklers with a nominal discharge coefficient of 5.6 gal/min/(psi)½ except that they discharge 40% more water at the same discharge pressure. The greater capacity is useful in some situations where very high density is required. Special size piping systems are needed.

FM Approvals

1-24

September 2007 -- Approval Guide Automatic Sprinkler Systems

K8.0 Upright (Class 2001)

Company Anber Globe Angus GW Globe Globe Kidde Kidde Kidde Kidde Reliable Reliable Reliable Reliable Reliable Rolland Tyco Tyco Tyco Tyco Tyco Tyco Tyco Tyco Mfg Ltd Tyco Mfg Ltd Victaulic Model GN8164 S S GL8164 GL8164 AS8002 AS8002 AS8004 AS8004 R1026 R1027 R1027 R1027 R1722 N TY4111 TY4111 TY4151 TY4151 TY4811 TY4811 TY4851 TY4151 TY4851 V3401 K 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Type Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Response SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR Element 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm Fusible Fusible Fusible Fusible 5 mm 5 mm Fusible Fusible 5 mm 5 mm Fusible Fusible 5 mm 5 mm 5 mm 5 mm

1/ 2 1/ 2 1/ 2

NPT (in.)

3/ 4

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester, Brass, Chrome, Polyester Wax, Lead, Wax Over Lead Brass, Chrome, Lead Wax, Wax Over Lead Brass, Chrome, Lead Wax, Wax Over Lead Brass, Chrome, Black Plated, Bright Brass Brass, Chrome, Black Plated, Bright Brass Lead Wax, Wax Over Lead Brass, Chrome, Black Plated, Polyester Brass, Chrome Brass, Chrome Wax, Lead Brass, Chrome, Bright Brass, Polyester Wax Brass, Chrome Wax, Lead Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 155°, 200°F (68°, 93°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 155°, 175°, 200°F (68°, 79°, 93°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 155°, 175°, 200°F (68°, 79°, 93°C) 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C) 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C) 165°, 212°, 286°F (74°, 100°, 141°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 165°, 212°, 280°, 360°F (74°, 100°, 138°, 182°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C) 135°, 155°, 200°F (57°, 68°, 93°C) 165°, 212°, 280°F (74°, 100°, 138°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C)

and 3/4 and 3/4

3/ 4 3/ 4 1/ 2 1/ 2 3/ 4 3/ 4 1/ 2 3/ 4 3/ 4 3/ 4 3/ 4

and 3/4

3/ 4 3/ 4 3/ 4 3/ 4 1/ 2 1/ 2 1/ 2 3/ 4 1/ 2 3/ 4

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-25

Company Victaulic Viking Viking Viking Viking SA Viking SA

Model V3401 VK200 VK200 VK204 VK200 VK200

K 8.0 8.0 8.0 8.0 8.0 8.0

Type Upright Upright Upright Upright Upright Upright

Response SR SR SR SR SR SR

Element 5 mm 5 mm 5 mm Fusible 5 mm 5 mm

NPT (in.)

3/ 4 1/ 2 1/ 2

Finishes Wax, Lead, Wax Over Lead Brass, Chrome, Polyester Wax Brass, Polyester Brass, Chrome Wax

Temp Ratings, °F (°C) 155°, 200°F (68°, 93°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 165°, 220°, 286°F (74°, 104°, 141°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

and 3/4 and 3/4

3/ 4

1/ 2 1/ 2

and 3/4 and 3/4

K8.0 Upright, Quick Response (Class 2020)

Company Anber Globe Angus GW Globe Globe Kidde Kidde Reliable Rolland Tyco Tyco Tyco Mfg Ltd Victaulic Viking Model GN8118 S S GL8115 GL8118 AS8052 AS8054 R3622 N TY4121 TY4131 TY4131 V3402 VK350 K 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Type Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Upright Response QR QR QR QR QR QR QR QR QR QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm Fusible 3 mm 3 mm 3 mm 3 mm

1/ 2 1/ 2 1/ 2

NPT (in.)

3/ 4

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Bright Brass Brass, Chrome, Bright Brass Brass, Chrome, Bright Brass, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°F (57°, 68°C) 135°, 155°F (57°, 68°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

and 3/4 and 3/4

1/ 2 3/ 4 1/ 2 3/ 4 3/ 4

and

3/ 4 3/ 4 3/ 4 3/ 4 3/ 4

3/4

Brass, Chrome Brass, Chrome Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester, Lead Brass, Chrome, Polyester

K8.0 Dry Upright (Class 2013)

Company Victaulic Model V3603* K 8.0 Type Dry Upright Response SR Element 5 mm NPT (in.) 1 Finishes Brass, NICOTEF Coated Temp Ratings, °F (°C) 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)

*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).

FM Approvals

1-26

September 2007 -- Approval Guide Automatic Sprinkler Systems

K8.0 Dry Upright Quick Response (Class 2020)

Company Victaulic Model V3604* K 8.0 Type Dry Upright Response QR Element 3 mm NPT (in.) 1 Finishes Brass, NICOTEF Coated Temp Ratings, °F (°C) 155°, 286°F (68°, 141°C)

*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).

K8.0 Dry Pendent (Class 2013)

Company Victaulic Model V3607* K 8.0 Type Dry Pendent Response SR Element 5 mm NPT (in.) 1 Finishes Brass, NICOTEF Coated Temp Ratings, °F (°C) 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)

*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).

K8.0 Dry Pendent, Quick Response (Class 2020)

Company Victaulic Model V3608* K 8.0 Type Dry Pendent Response QR Element 3 mm NPT (in.) 1 Finishes Brass, NICOTEF Coated Temp Ratings, °F (°C) 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)

*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).

K8.0 Pendent (Class 2001)

Company Anber Globe Angus GW Globe Globe Globe Kidde Kidde Kidde Kidde Reliable Model GN8156 S S GL8151 GL8156 GL8156 AS8001 AS8001 AS8003 AS8003 R1016 K 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Type Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Response SR SR SR SR SR SR SR SR SR SR SR Element 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm Fusible

1/ 2 1/ 2

NPT (in.)

3/ 4

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Wax, Lead, Wax Over Lead Brass, Chrome, Lead Wax, Wax Over Lead Brass, Chrome, Lead Wax, Wax Over Lead Brass, Chrome, Black Plated, Bright Brass

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 155°, 200°F (68°, 93°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 155°, 175°, 200°F (57°, 68°, 79°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 155°, 175°, 200°F (57°, 68°, 79°C) 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C)

and 3/4 and 3/4

1/ 2 3/ 4 3/ 4 1/ 2 1/ 2 3/ 4 3/ 4 1/ 2

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-27

Company Reliable Reliable Reliable Reliable Rolland Tyco Tyco Tyco Tyco Tyco Tyco Tyco Tyco Mfg Ltd Tyco Mfg Ltd Victaulic Victaulic Viking Viking Viking Viking SA Viking SA

Model R1017 R1017 R1017 R1712 N TY4211 TY4211 TY4251 TY4251 TY4911 TY4911 TY4951 TY4251 TY4951 V3405 V3405 VK202 VK202 VK206 VK202 VK202

K 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0

Type Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent

Response SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR SR

Element Fusible Fusible Fusible 5 mm 5 mm Fusible Fusible 5 mm 5 mm Fusible Fusible 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm Fusible 5 mm 5 mm

NPT (in.)

3/ 4 3/ 4 3/ 4 3/ 4 1/ 2

Finishes Brass, Chrome, Black Plated, Bright Brass Lead Wax, Wax Over Lead Brass, Chrome, Black Plated Brass, Chrome Brass, Chrome Wax, Lead Brass, Chrome, Bright Brass, Polyester Wax Brass, Chrome Wax, Lead Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester, Lead Wax, Wax Over Lead Brass, Chrome Wax Brass Brass, Chrome Wax

Temp Ratings, °F (°C) 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C) 165°, 212°, 286°F (74°, 100°, 141°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 165°, 212°, 280°F (74°, 100°, 138°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C) 135°, 155°, 200°F (57°, 68°, 93°C) 165°, 212°, 280°, 360°F (74°, 100°, 138°, 182°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 155°, 200°F (68°, 93°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 165°, 220°, 286°F (74°, 104°, 141°C) 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

and 3/4

3/ 4 3/ 4 3/ 4 3/ 4 1/ 2 1/ 2 1/ 2 3/ 4 1/ 2 3/ 4 3/ 4

1/ 2 1/ 2

and 3/4 and 3/4

3/ 4

1/ 2 1/ 2

and 3/4 and 3/4

K8.0 Pendent, Quick Response (Class 2020)

Company Anber Globe Angus Model GN8106 S K 8.0 8 Type Pendent Pendent Response QR QR Element 3 mm 3 mm

1/ 2

NPT (in.)

3/ 4

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°F (57°, 68°, 79°C)

and 3/4

FM Approvals

1-28

September 2007 -- Approval Guide Automatic Sprinkler Systems

Company GW Globe Globe Kidde Kidde Reliable Rolland Tyco Tyco Tyco Mfg Ltd Victaulic Viking

Model S GL8101 GL8106 AS8051 AS8053 R3612 N TY4221 TY4231 TY4231 V3406 VK352

K 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0

Type Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent Pendent

Response QR QR QR QR QR QR QR QR QR QR QR QR

Element 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm Fusible 3 mm 3 mm 3 mm 3 mm

NPT (in.)

1/ 2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Bright Brass Brass, Chrome, Bright Brass Brass, Chrome, Bright Brass Brass, Chrome Brass, Chrome Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Bright Brass, Polyester, Lead Brass, Chrome

Temp Ratings, °F (°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°F (57°, 68°C) 135°, 155°F (57°, 68°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

and 3/4

1/ 2 3/ 4 1/ 2 3/ 4 3/ 4

1/ 2

and 3/4

3/ 4 3/ 4 3/ 4 3/ 4 3/ 4

K8.0 Corrosion Resistant (Stainless Steel)

The sprinklers listed below are primarily manufactured from a stainless steel alloy. These sprinklers afford improved corrosion protection, but should be selected for compatibility with the intended environment. Corrosion resistant automatic sprinklers with a nominal discharge coefficient of 8.0 gal/min/(psi)½ are similar to corrosion resistant sprinklers with a nominal discharge coefficient of 5.6 gal/min/(psi)½ except that they discharge 40% more water at the same discharge pressure. The greater capacity is useful in some situations where very high density is required. Special size piping systems are needed.

K8.0 Stainless Steel, Upright (Class 2042)

Company Angus GW Model S S K 8.0 8.0 Type Upright Upright Response SR SR Element 5 mm 5 mm NPT (in.)

1/ 2 1/ 2

Finishes AISI 316 (UNS S31254) Stainless Steel Alloy AISI 316 (UNS S31254) Stainless Steel Alloy

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C)

and

3/4

and 3/4

K8.0 Stainless Steel, Upright, Quick Response (Class 2020)

Company Angus GW Model S S K 8.0 8.0 Type Upright Upright Response QR QR Element 3 mm 3 mm NPT (in.)

1/ 2 1/ 2

Finishes AISI 316 (UNS S31254) Stainless Steel Alloy AISI 316 (UNS S31254) Stainless Steel Alloy

Temp Ratings, °F (°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°F (57°, 68°, 79°C)

and

3/4

and 3/4

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-29

K8.0 Stainless Steel, Pendent (Class 2042)

Company Angus GW Model S S K 8.0 8.0 Type Pendent Pendent Response SR SR Element 5 mm 5 mm NPT (in.)

1/ 2 1/ 2

Finishes AISI 316 (UNS S31254) Stainless Steel Alloy AISI 316 (UNS S31254) Stainless Steel Alloy

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C)

and

3/4

and 3/4

K8.0 Stainless Steel, Pendent Quick Response (Class 2020)

Company Angus GW Model S S K 8.0 8.0 Type Pendent Pendent Response QR QR Element 3 mm 3 mm NPT (in.)

1/ 2 1/ 2

Finishes AISI 316 (UNS S31254) Stainless Steel Alloy AISI 316 (UNS S31254) Stainless Steel Alloy

Temp Ratings, °F (°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°F (57°, 68°, 79°C)

and 3/4 and 3/4

K8.0 Flush, Recessed and Concealed (Pendent)

Pendent flush, recessed and concealed sprinklers with a nominal discharge coefficient of 8.0 gal/min/(psi)½ are similar to those with a nominal discharge coefficient of 5.6 gal/min/(psi)½ except that they discharge 40% more water at the same discharge pressure. These sprinklers are intended for use with a concealed piping system. Flush types are constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution. Recessed types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed types incorporate a cover plate which is heat activated and can be manually removed to prevent over-painting of the cover plate. All of these sprinkler types are intended for use where attractive appearance under a ceiling is desired, in such occupancies as offices, hotel lobbies, dining rooms, clubs and similar properties. FM Approved flush, recessed and concealed sprinklers are limited to a maximum temperature rating of 225°F (107°C) and to protection of hazard occupancies described in the FM Global Property Loss Prevention Data Sheets. Quick response flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.

K8.0 Flush, Recessed and Concealed (Class 2015)

Company Globe Globe Reliable Tyco Tyco Victaulic Viking Model GL8151 GL8156 R1712 TY4251 TY4951 V3405 VK202 K 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Type Recessed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Response SR SR SR SR SR SR SR Element 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm 5 mm

1/ 2

NPT (in.)

1/2 3/4 3/4 3/4 1/2 3/4

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Black Plated, Bright Brass Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) Polyester Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) Polyester Brass, Chrome 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

and 3/4

FM Approvals

1-30

September 2007 -- Approval Guide Automatic Sprinkler Systems

Company Viking Viking

Model VK202 VK352

K 8.0 8.0

Type Concealed Pendent Concealed Pendent

Response SR SR

Element 5 mm 3 mm

NPT (in.)

3/4 3/4

Finishes Brass Brass

Temp Ratings, °F (°C) 155°, 175°, 200°F (68°, 79°, 93°C) 155°, 175°, 200°F (68°, 79°, 93°C)

K8.0 Dry, Flush, Recessed and Concealed (Pendent or Sidewall) K8.0 Dry Flush, Recessed and Concealed (Class 2015)

Company Victaulic Model V3607* K 8.0 Type Dry Recessed Pendent Response SR Element 5 mm NPT (in.) 1 Finishes Brass, NICOTEF Coated Temp Ratings, °F (°C) 135°, 155°, 200°F (57°, 68°, 93°C)

*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).

K8.0 Flush, Recessed and Concealed, Quick Response (Class 2020)

Company Globe Globe Reliable Tyco Tyco Mfg Ltd Viking Viking SA Model GL8101 GL8106 R3612 TY4231 TY4231 VK352 VK352 K 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Type Recessed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Recessed Pendent Response QR QR QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm NPT (in.)

1/2 3/4 3/4 3/4 3/4

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Bright Brass

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

in. in. in.

Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) Polyester Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) Polyester Brass, Chrome Brass, Chrome 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)

3/4 3/4

K8.0 Dry Flush, Recessed and Concealed, Quick Response (Class 2020)

Company Victaulic Model V3608* K 8.0 Type Dry Recessed Pendent Response QR Element 3 mm NPT (in.) 1 Finishes Brass, NICOTEF Coated Temp Ratings, °F (°C) 135°, 155°, 200°F (57°, 68°, 93°C)

*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).

K8.0 Rack Storage

Rack storage sprinklers (also called intermediate level sprinklers) provide in-rack protection for rack storage arrays. These sprinklers are similar to the basic sprinkler types from which they are derived except that they are equipped with a disc mounted above the thermal-sensitive element which protects it from delayed operation as a result of water discharge from nearby sprinklers at higher elevations. Rack storage sprinklers are available with nominal discharge coefficients of 5.6 gal/min/(psi)½ and 8.0 gal/min/(psi)½ and in both upright and pendent configurations. When using quick response rack storage sprinklers, standard response sprinklers will continue to be required at the ceiling level in accordance with the FM Global Property Loss Prevention Data Sheets. Reference should be made to the FM Global Property Loss Prevention Data Sheets with regard to selection of type and temperature rating for a given installation.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-31

K8.0 Rack Storage, Upright (Class 2005)

Company Globe Globe Kidde Reliable Reliable Tyco Tyco Victaulic Viking Viking Model GL8163 GL8166 AS8006 R1427 R7022 TY4113 TY4153 V3417 VK560 VK562 K 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Type Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Response SR SR SR SR SR SR QR SR SR SR Element 5 mm 5 mm 5 mm Fusible 5 mm Fusible 5 mm 5 mm 5 mm Fusible NPT (in.)

1/2 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

Finishes Brass Brass Brass Brass Brass Brass Brass Brass Brass Brass

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 165°, 212°, 280°F (74°, 100°, 138°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 165°, 220°, 286°F (74°, 104°, 141°C)

K8.0 Rack Storage, Upright, Quick Response (Class 2020)

Company Globe Globe Kidde Kidde Reliable Tyco Tyco Victaulic Viking Viking SA Model GL8117 GL8120 AS8052 AS8056 R7092 TY4123 TY4133 V3418 VK566 VK566 K 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Type Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Rack Storage Upright Response QR QR QR QR QR QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm 3 mm Fusible 3 mm 3 mm 3 mm 3 mm NPT (in.)

1/2 3/4 1/2 3/4 3/4 3/4 3/4 3/4 3/4 3/4

Finishes Brass Brass Brass Brass Brass Brass Brass Brass Brass Brass

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°F (57°, 68°C) 135°, 155°F (57°, 68°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

FM Approvals

1-32

September 2007 -- Approval Guide Automatic Sprinkler Systems

K8.0 Rack Storage, Pendent (Class 2005)

Company Angus GW Globe Globe Grinnell Kidde Reliable Reliable Tyco Victaulic Viking Viking Model S S GL8158 GL8172 G3152 AS8003 R1017 R1712 TY4251 V3419 VK202 VK206 K 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Type Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Response SR SR SR SR SR SR SR SR SR SR SR SR Element 5 mm 5 mm 5 mm 5 mm Fusible 5 mm Fusible 5 mm 5 mm 5 mm 5 mm Fusible NPT (in.)

1/ 2 1/ 2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass Brass Brass Brass Brass Brass Brass, Chrome, Polyester Brass Brass Brass

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 165°, 212°, 280°F (74°, 100°, 138°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°,175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°, 182°, 260°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C) 165°, 220°, 286°F (74°, 104°, 141°C)

and 3/4 and 3/4

3/4 1/2 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

K8.0 Rack Storage, Pendent, Quick Response (Class 2020)

Company Angus GW Globe Globe Kidde Reliable Tyco Tyco Victaulic Viking Viking SA Model S S GL8112 GL8108 AS8053 R3612 TY4221 TY4231 V3420 VK352 VK352 K 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Type Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Rack Storage Pendent Response QR QR QR QR QR QR QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm Fusible 3 mm 3 mm 3 mm 3 mm NPT (in.)

1/ 2 1/ 2

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass Brass Brass Brass Brass Brass, Chrome, Polyester Brass Brass Brass

Temp Ratings, °F (°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°F (57°, 68°, 79°C) 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C) 135°, 155°F (57°, 68°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

and 3/4 and 3/4

1/2 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-33

K8.0 Wax Coated, High Temperature

There are instances where high temperature sprinklers, rated 250-300°F (121-149°C), are installed for purposes other than expected ambient temperatures above 225°F (107°C) and where the environment is corrosive. The sprinklers listed below have been coated with a wax normally intended for intermediate temperature sprinklers, 175-225°F (79-107°C) These sprinklers are not recommended for installation in areas where the ambient temperature may exceed 150°F (66°C).

K8.0 Upright, Wax Coated, High Temperature (Class 2043)

Company Reliable Tyco Tyco Victaulic Model R1026 TY4111 TY4151 V3401 K 8.0 8.0 8.0 8.0 Type Upright Upright Upright Upright Response SR SR SR SR Element Fusible Fusible 5 mm 5 mm NPT (in.)

1/ 2 3/ 4 3/ 4 3/ 4

Finishes Wax Wax Wax Wax, Wax Over Lead 286°F (141°C) 280°F (138°C) 286°F (141°C) 286°F (141°C)

Temp Ratings, °F (°C)

K8.0 Pendent, Wax Coated, High Temperature (Class 2043)

Company Reliable Reliable Tyco Tyco Tyco Victaulic Model R1016 R1017 TY4211 TY4251 TY4951 V3405 K 8.0 8.0 8.0 8.0 8.0 8 Type Pendent Pendent Pendent Pendent Pendent Pendent Response SR SR SR SR SR SR Element Fusible Fusible Fusible 5 mm 5 mm 5 mm NPT (in.)

1/ 2 3/ 4 3/ 4 3/ 4 1/ 2 3/ 4

Finishes Wax Wax Wax Wax Wax Wax, Wax Over Lead 286°F (141°C) 286°F (141°C) 280°F (138°C) 286°F (141°C) 286°F (141°C) 286°F (141°C)

Temp Ratings, °F (°C)

K8.0 High Temperature Oven

Automatic sprinklers listed in this category are for use in high temperature ovens only. These sprinklers are not to be used in other occupancies.

K8.0 High Temperature Oven (Class 2001)

Company Grinnell Grinnell Model G1136 G1140 K 8.0 8.0 Type Upright Pendent Response SR SR Element 11 mm 11 mm NPT (in.)

3/ 4 3/ 4

Finishes Brass Brass

Temp Ratings, °F (°C) 400°, 500°F (204°, 260°C) 400°, 500°F (204°, 260°C)

K8.0 Extended Coverage Light Hazard (ECLH)

Control mode, Extended Coverage-Light Hazard (ECLH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of 15 ft by 15 ft (4.6 m by 4.6 m) for upright and pendent standard sprinklers and 14 ft by 14 ft (4.3 m by 4.3 m) for vertical and horizontal sidewall sprinklers. Upright and pendent ECLH sprinklers, regardless of nominal discharge coefficient, have a maximum spacing (width by length) of 20 ft by 20 ft (6.1 m by 6.1 m). Horizontal sidewall ECLH sprinklers with a nominal discharge

FM Approvals

1-34

September 2007 -- Approval Guide Automatic Sprinkler Systems

coefficient of 5.6 gal/min/(psi)½ have a maximum spacing (width by length) of 16 ft by 20 ft (4.9 m by 6.1 m). Horizontal sidewall ECLH sprinklers with a nominal discharge coefficient of 8.0 gal/min/(psi)½ have a maximum spacing (width by length) of 16 ft by 24 ft (4.9 m by 7.3 m). The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. FM Approved ECLH sprinklers are limited to a maximum temperature rating of 175°F (79°C).

K8.0 Extended Coverage Light Hazard (ECLH), Pendent (Class 2022)

Company Viking Viking SA Model VK602 VK602 K 8.0 8.0 Type Pendent Pendent Response SR SR Element 3 mm 3 mm NPT (in.)

3/4 3/4

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester 175°F (79°C) 175°F (79°C)

Temp Ratings, °F (°C)

K8.0 Extended Coverage Light Hazard (ECLH), Pendent, Quick Response (Class 2020)

Company Reliable Tyco Viking Viking SA Model R4842 TY4232 VK602 VK602 K 8.0 8.0 8.0 8.0 Type Pendent Pendent Pendent Pendent Response QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm NPT (in.)

3/4 3/4 3/4 3/4

Finishes Brass, Chrome, Polyester Coated

Temp Ratings, °F (°C) 135°, 155°F (57°, 68°C)

Brass, Chrome, Bright Brass, 135°, 155°F (57°, 68°C) Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester 135°, 155°F (57°, 68°C) 135°, 155°F (57°, 68°C)

K8.0 Extended Coverage Light Hazard (ECLH), Sidewall (Class 2022)

Company Tyco Tyco Mfg Ltd Victaulic Model TY4332 TY4332 V3415 K 8.0 8.0 8.0 Type Horizontal Sidewall Horizontal Sidewall Horizontal Sidewall Response SR SR SR Element 3 mm 3 mm 5 mm NPT (in.)

3/4 3/4 3/4

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester 175°F (79°C) 175°F (79°C) 135°F (57°C)

Temp Ratings, °F (°C)

K8.0 Extended Coverage Light Hazard (ECLH), Sidewall, Quick Response (Class 2020)

Company Reliable Tyco Tyco Model R4862 TY4322 TY4332 K 8.0 8.0 8.0 Type Horizontal Sidewall Horizontal Sidewall Horizontal Sidewall Response QR QR QR Element 3 mm Fusible 3 mm NPT (in.)

3/4 3/4 3/4

Finishes

Temp Ratings, °F (°C)

Brass, Chrome, Bright Brass, 135°, 155, °175°F (57°, 68°, 79°C) Black Plated, Polyester Brass, Chrome Brass, Chrome, Polyester 165°F (74°C) 135°, 155°F (57°, 68°C)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-35

Company Tyco Mfg Ltd Victaulic Viking Viking

Model TY4332 V3416 VK606 VK630

K 8.0 8.0 8.0 8.0

Type Horizontal Sidewall Horizontal Sidewall Horizontal Sidewall Horizontal Sidewall

Response QR QR QR QR

Element 3 mm 3 mm 3 mm 3mm

NPT (in.)

3/4 3/4 3/4 3/4

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°F (57°, 68°C) 135°, 155°F (57°, 68°C) 135°, 155°F (57°, 68°C) 135°, 155°, 175° F (57°, 68°, 79°C)

K8.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Pendent or Sidewall)

Control mode, Extended Coverage-Light Hazard (ECLH) flush, recessed and concealed sprinklers are ECLH sprinklers intended for use with a concealed piping system. Flush pendent types are constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution. Recessed pendent types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed pendent types incorporate a cover plate which is heat activated and can be manually removed to prevent over-painting of the cover plate. Sidewall flush, recessed and concealed sprinklers are similar to pendent flush recessed and concealed sprinklers except that they are designed to be installed in a wall near the junction of the ceiling and wall. They are equipped with a special deflector which discharges most of the water in a forward direction. All of these sprinkler types are intended for use in light hazard occupancies where attractive appearance under a ceiling is desired. The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. Quick response ECLH flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.

K8.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Class 2022)

Company Tyco Tyco Mfg Ltd Victaulic Viking Viking Model TY4332 TY4332 V3416 VK602 VK606 K 8.0 8.0 8.0 8.0 8.0 Type Recessed Horizontal Sidewall Recessed Horizontal Sidewall Recessed Horizontal Sidewall Recessed Pendent Recessed Horizontal Sidewall Response SR SR SR SR SR Element 3 mm 3 mm 3 mm 3 mm 3 mm NPT (in.)

3/4 3/4 3/4 3/4 3/4

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester

Temp Ratings, °F (°C) 175°F (79°C) 175°F (79°C) 155°F (68°C) 175°F (79°C) 175°F (79°C) with Viking E-1 or E-2 recessed escutcheon

K8.0 Extended Coverage Light Hazard (ECLH), Flush Recessed and Concealed, Quick Response (Class 2020)

Company Reliable Reliable Tyco Tyco Tyco Mfg Ltd Model R4842 R4862 TY4232 TY4332 TY4332 K 8.0 8.0 8.0 8.0 8.0 Type Recessed Pendent Recessed Horizontal Sidewall Recessed Pendent Recessed Horizontal Sidewall Recessed Horizontal Sidewall Response QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm 3 mm NPT (in.)

3/4 3/4 3/4 3/4 3/4

Finishes

Temp Ratings, °F (°C)

Brass, Chrome, Bright Brass, 135°, 155°F (57°, 68°C) Black Plated, Polyester Brass, Chrome, Bright Brass, 135°, 155°F (57°, 68°C) Black Plated, Polyester Brass, Chrome, Bright Brass, 135°F (57°C) Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester 135°, 155°F (57°, 68°C) 135°, 155°F (57°, 68°C)

FM Approvals

1-36

September 2007 -- Approval Guide Automatic Sprinkler Systems

Company Victaulic Viking Viking Viking

Model V3416 VK602 VK606 VK630

K 8.0 8.0 8.0 8.0

Type Recessed Horizontal Sidewall Recessed Pendent Recessed Horizontal Sidewall Recessed Horizontal Sidewall

Response QR QR QR QR

Element 3 mm 3 mm 3 mm 3mm

NPT (in.)

3/4 3/4 3/4 3/4

Finishes Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°F (57°C) 135°, 155°F (57°, 68°C) 135°, 155°F (57°, 68°C) with Viking E-1 or E-2 recessed escutcheon 135°, 155°, 175° F (57°, 68°, 79°C)

K11.2 Control Mode (Specific Application)

Control mode specific application (CMSA) automatic sprinklers with a nominal discharge coefficient of 11.2 gal/min/[psi]1/2 are generally utilized for storage type occupancies. Install these sprinklers in accordance with FM Global Property Loss Prevention Data Sheet 2-7, Installation Rules for Sprinkler Systems Using Control Mode Specific Application (CMSA) Ceiling Sprinklers for Storage Applications, and base their design on the occupancy-specific FM Global Property Loss Prevention Data Sheet.

K11.2 Control Mode (Specific Application) Upright (Class 2007)

Company Viking Model VK540 K 11.2 Type Upright Response SR Element 5 mm NPT (in.)

3/4

Finishes Brass

Temp Ratings, °F (°C) 155°, 200°, 286°F (68°, 93°, 141°C)

K11.2 Control Mode (Density/Area)

Control mode automatic sprinklers with a nominal discharge coefficient of 11.2 gal/min/(psi)½ are similar to control mode sprinklers with a nominal discharge coefficient of 8.0 gal/min/(psi)½ except that they discharge approximately 40% more water at the same discharge pressure. They are not control mode (specific application) sprinklers (i.e., they are not to be utilized in ``large drop'' sprinkler applications.) These are standard spray sprinklers intended for use in automatic sprinkler fire protection systems designed using the ``Density/Area'' method. Control mode sprinklers with a nominal discharge coefficient of 11.2 gal/min/(psi)½ offer the advantage of higher design densities at lower water supply pressures, which may allow adequate sprinkler protection to be achieved without the need for additional fire pumps. See the appropriate occupancy/hazard specific data sheet to determine the sprinkler's acceptable minimum and maximum operating parameters such as sprinkler spacing, operating pressure, etc. The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers.

K11.2 Upright (Class 2009)

Company Reliable Tyco Tyco Tyco Tyco Model R2921 TY5151 TY5151 TY5851 TY5851 K 11.2 11.2 11.2 11.2 11.2 Type Upright Upright Upright Upright Upright Response SR SR SR SR SR Element Fusible 5 mm 5 mm 5 mm 5 mm NPT (in.)

1/2

Finishes Brass, Chrome Brass, Chrome, Lead Wax, Wax Over Lead Brass, Chrome, Lead Wax, Wax Over Lead

Temp Ratings, °F (°C) 165°, 212°, 286°F (74°, 100°, 141°C) 155°, 200°, 286°F (68°, 93°, 141°C) 155°, 200°F (68°, 93°C) 155°, 200°, 286°F (68°, 93°, 141°C) 155°, 200°F (68°, 93°C)

and

3/4 3/4 1/2 1/2

3/ 4

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-37

Company Tyco Tyco Tyco Tyco Victaulic Victaulic Viking

Model TY5811 TY5811 TY5111 TY5111 V3403 V3403 VK530

K 11.2 11.2 11.2 11.2 11.2 11.2 11.2

Type Upright Upright Upright Upright Upright Upright Upright

Response SR SR SR SR SR SR SR

Element Fusible Fusible Fusible Fusible 5 mm 5 mm 5 mm

NPT (in.)

1/2 1/2 3/4 3/4 3/4 3/4 3/4

Finishes Brass, Chrome, Lead Wax, Wax Over Lead Brass, Chrome, Lead Wax, Wax Over Lead Brass, Chrome, Polyester, Lead Wax, Wax Over Lead Brass, Chrome

Temp Ratings, °F (°C) 165°, 212°, 286°F (74°, 100°, 141°C) 165°, 212°F (74°, 100°C) 165°, 212°, 286°F (74°, 100°, 141°C) 165°, 212°F (74°, 100°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 155°, 200°F (68°, 93°C) 155°, 175°, 200°, 286°F (68°, 79°, 93°, 141°C)

K11.2 Upright, Quick Response (Class 2020)

Company Tyco Victaulic Model TY5131 V3404 K 11.2 11.2 Type Upright Upright Response QR QR Element 3 mm 3 mm NPT (in.)

3/4 3/4

Finishes Brass, Chrome Brass, Chrome, Polyester, Lead

Temp Ratings, °F (°C) 155°, 200°, 286°F (68°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

K11.2 Pendent (Class 2009)

Company Tyco Tyco Tyco Victaulic Victaulic Model TY5211 TY5251 TY5251 V3407 V3407 K 11.2 11.2 11.2 11.2 11.2 Type Pendent Pendent Pendent Pendent Pendent Response SR SR SR SR SR Element Fusible 5 mm 5 mm 5 mm 5 mm NPT (in.)

3/4 3/4 3/4 3/4 3/4

Finishes Brass, Chrome Brass, Chrome, Lead Wax, Wax Over Lead Brass, Lead Wax, Wax Over Lead

Temp Ratings, °F (°C) 165°, 212°, 286°F (74°, 100°, 141°C) 155°, 200°, 286°F (68°, 93°, 141°C) 155°, 200°F (68°, 93°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 155°, 200°F (68°, 93°C)

K11.2 Pendent, Quick Response (Class 2020)

Company Tyco Victaulic Victaulic Model TY5231 V3408 V3408 K 11.2 11.2 11.2 Type Pendent Pendent Pendent Response QR QR QR Element 3 mm 3 mm 3 mm NPT (in.)

3/4 3/4 3/4

Finishes Brass, Chrome Brass, Lead Brass, Chrome, Polyester, Lead

Temp Ratings, °F (°C) 155°, 200°, 286°F (68°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

FM Approvals

1-38

September 2007 -- Approval Guide Automatic Sprinkler Systems

K11.2 Extended Coverage Ordinary Hazard (ECOH)

Control mode, Extended Coverage Ordinary Hazard (ECOH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of 15 ft × 15 ft (4.6 m × 4.6 m) for upright and pendent standard coverage sprinklers. ECOH sprinklers with a nominal discharge coefficient of 11.2 gal/min/(psi) have a maximum spacing of 16 ft × 16 ft (4.9 m × 4.9 m) and a minimum spacing of 10 ft × 10 ft (3.0 m × 3.0 m). ECOH sprinklers are equipped with a quick response heat responsive element. However, they are FM Approved as standard response sprinklers due the delay caused by the extended maximum spacing between adjacent sprinklers. The FM Global Property Loss Prevention Data Sheets should be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers. Sprinklers not installed to these guidelines will not provide adequate property protection in the event of a fire.

11.2 ECOH Upright (Class 2022)

Company Viking Model VK532 K 11.2 Type Upright Response SR Element 3 mm NPT (in.)

3/4

Finishes Brass, Chrome, Polyester

Temp Ratings, °F (°C) 155°, 175°, 200°, 286°F (68°, 79°, 93°, 141°C)

11.2 ECOH Pendent (Class 2022)

Company Tyco Model TY5237 K 11.2 Type Pendent Response SR Element 3 mm NPT (in.)

3/4

Finishes Brass, Chrome, Polyester, Lead

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

K11.2 Extended Coverage Light Hazard (ECLH)

K11.2 Extended Coverage Light Hazard (ECLH) Pendent (Class 2022)

Control mode, Extended Coverage-Light Hazard (ECLH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of 15 ft by 15 ft (4.6 m by 4.6 m) for upright and pendent standard sprinklers and 14 ft by 14 ft (4.3 m by 4.3 m) for vertical and horizontal sidewall sprinklers. Upright and pendent ECLH sprinklers, regardless of nominal discharge coefficient, have a maximum spacing (width by length) of 20 ft by 20 ft (6.1 m by 6.1 m). The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. FM Approved ECLH sprinklers are limited to a maximum temperature rating of 175°F (79°C).

Company Victaulic Model V3411 K 11.2 Type Pendent Response SR Element 5 mm NPT (in.)

3/4

Finishes Brass, Chrome, Bright Brass, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°F (57°, 68°, 79°C)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-39

K11.2 Extended Coverage Light Hazard (ECLH) Pendent, Quick Response (Class 2020)

Company Tyco Victaulic Viking Model TY5237 V3412 VK608 K 11.2 11.2 11.2 Type Pendent Pendent Pendent Response QR QR QR Element 3 mm 3 mm 3 mm NPT (in.)

3/4 3/4 3/4

Finishes Brass, Chrome, Polyester, Lead Brass, Chrome, Bright Brass, Polyester Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°F (57°, 68°C) 135°, 155°F. (57°, 68°C) 135°, 155°, 175°F (57°, 68°, 79°C)

K11.2 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Pendent)

Control mode, Extended Coverage-Light Hazard (ECLH) flush, recessed and concealed sprinklers are ECLH sprinklers intended for use with a concealed piping system. Flush pendent types are constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution. Recessed pendent types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed pendent types incorporate a cover plate which is heat activated and can be manually removed to prevent over-painting of the cover plate. All of these sprinkler types are intended for use in light hazard occupancies where attractive appearance under a ceiling is desired. The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. Quick response ECLH flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.

K11.2 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed Types (Class 2022)

Company Victaulic Model V3411 K 11.2 Type Recessed Pendent Response SR Element 5 mm NPT (in.)

3/ 4

Finishes Brass, Chrome, Bright Brass, Polyester

Temp Ratings, °F (°C) 135°, 155°F (57°, 68°C)

K11.2 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed Types, Quick Response (Class 2020)

Company Tyco Victaulic Viking Model TY5237 V3412 VK608 K 11.2 11.2 11.2 Type Recessed Pendent Recessed Pendent Recessed Pendent Response QR QR QR Element 3 mm 3 mm 3 mm NPT (in.)

3/ 4 3/ 4 3/ 4

Finishes Brass, Chrome, Polyester, Lead Brass, Chrome, Polyester Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°F (57°, 68°C) 135°F (57°C) 135°, 155°F (57°, 68°C)

FM Approvals

1-40

September 2007 -- Approval Guide Automatic Sprinkler Systems

K11.2 Wax Coated, High Temperature

There are instances where high temperature sprinklers, rated 250-300°F (121-149°C), are installed for purposes other than expected ambient temperatures above 225°F (107°C) and where the environment is corrosive. The sprinklers listed below have been coated with a wax normally intended for intermediate temperature sprinklers, 175-225°F (79-107°C) These sprinklers are not recommended for installation in areas where the ambient temperature may exceed 150°F (66°C).

Wax Coated, High Temperature, Upright (Class 2043)

Company Tyco Tyco Victaulic Model TY5811 TY5111 V3403 K 11.2 11.2 11.2 Type Upright Upright Upright Response SR SR SR Element Fusible Fusible 5 mm NPT (in.)

1/ 2 3/ 4 3/ 4

Finishes Wax, Wax Over Lead Wax, Wax Over Lead Wax, Wax Over Lead 286°F (141°C) 286°F (141°C) 286°F (141°C)

Temp Ratings, °F (°C)

K11.2 Wax Coated, High Temperature, Pendent (Class 2043)

Company Victaulic Model V3407 K 11.2 Type Pendent Response SR Element 5 mm NPT (in.)

3/ 4

Finishes Wax, Wax Over Lead 286°F (141°C)

Temp Ratings, °F (°C)

K14.0 Control Mode (Density/Area)

Control mode automatic sprinklers with a nominal discharge coefficient of 14.0 gal/min/(psi)½ are similar to control mode sprinklers with a nominal discharge coefficient of 11.2 gal/min/(psi)½ except that they discharge approximately 25% more water at the same discharge pressure. These are standard spray sprinklers intended for use in automatic sprinkler fire protection systems designed using the ``Density/Area'' method. Control mode automatic sprinklers with a nominal discharge coefficient of 14.0 gal/min/(psi)½ offer the advantage of higher design densities at lower water supply pressures, which may allow adequate sprinkler protection to be achieved without the need for additional fire pumps. The FM Global Property Loss Prevention Data Sheets should be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers.

K14.0 Pendent (Class 2023)

Company Reliable Model R4613 K 14.0 Type Pendent Response SR Element Fusible NPT (in.)

3/4

Finishes Brass

Temp Ratings, °F (°C) 165°, 212°, 286°F (74°, 100°, 141°C)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-41

K14.0 Extended Coverage Ordinary Hazard (ECOH)

Control mode, Extended Coverage Ordinary Hazard (ECOH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of 15 ft × 15 ft (4.6 m × 4.6 m) for upright and pendent standard coverage sprinklers. ECOH sprinklers with a nominal discharge coefficient of 14.0 gal/min/(psi)½ have a maximum spacing of 20 ft × 20 ft (6.1 × m × 6.1 m) and a minimum spacing of 10 ft × 10 ft (3.0 m × 3.0 m). ECOH sprinklers are equipped with a quick response heat responsive element. However, they are FM Approved as standard response sprinklers due the delay caused by the extended maximum spacing between adjacent sprinklers. The FM Global Property Loss Prevention Data Sheets should be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers. Sprinklers not installed to these guidelines will not provide adequate property protection in the event of a fire.

14 ECOH Upright (Class 2022)

Company Tyco Model TY6137 K 14.0 Type Upright Response SR Element 3 mm NPT (in.)

3/ 4

Finishes Brass, Chrome, Polyester, Lead

Temp Ratings, °F (°C) 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

14 ECOH Pendent (Class 2022)

Company Tyco Mfg Ltd Viking Model TY6237 VK572 K 14.0 14.0 Type Pendent Pendent Response SR SR Element 3 mm 3 mm NPT (in.)

3/ 4 3/ 4

Finishes Brass, Chrome, Polyester, Lead Brass

Temp Ratings, °F (°C) 135° , 155° , 175° , 200° , 286°F (57°, 68°, 79°, 93°, 141°C) 155°, 175°, 200°, 286°F (68°, 79°, 93°, 141°C)

K14.0 Extended Coverage Light Hazard (ECLH)

Control mode, Extended Coverage-Light Hazard (ECLH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of 15 ft by 15 ft (4.6 m by 4.6 m) for upright and pendent standard sprinklers and 14 ft by 14 ft (4.3 m by 4.3 m) for vertical and horizontal sidewall sprinklers. Upright and pendent ECLH sprinklers, regardless of nominal discharge coefficient, have a maximum spacing (width by length) of 20 ft by 20 ft (6.1 m by 6.1 m). The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. FM Approved ECLH sprinklers are limited to a maximum temperature rating of 175°F (79°C).

K14.0 Extended Coverage Light Hazard (ECLH), Pendent (Class 2023)

Company Victaulic Model V3413 K 14.0 Type Pendent Response SR Element 5 mm NPT (in.)

3/ 4

Finishes Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°, 175°F (57°, 68°, 79°C)

K14.0 Extended Coverage Light Hazard (ECLH), Pendent, Quick Response (Class 2020)

Company Tyco Mfg Ltd Victaulic Model TY6237 V3414 K 14.0 14.0 Type Pendent Pendent Response QR QR Element 3 mm 3 mm NPT (in.)

3/ 4 3/ 4

Finishes Brass, Chrome, Polyester, Lead Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°F, (57°, 68°C) 135°, 155°F (57°, 68°C)

FM Approvals

1-42

September 2007 -- Approval Guide Automatic Sprinkler Systems

K14.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Pendent)

Control mode, Extended Coverage-Light Hazard (ECLH) flush, recessed and concealed sprinklers are ECLH sprinklers intended for use with a concealed piping system. Flush pendent types are constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution. Recessed pendent types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed pendent types incorporate a cover plate which is heat activated and can be manually removed to prevent over-painting of the cover plate. All of these sprinkler types are intended for use in light hazard occupancies where attractive appearance under a ceiling is desired.

K14.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Class 2015)

Company Victaulic Model V3413 K 14.0 Type Recessed Pendent Response SR Element 5 mm NPT (in.)

3/ 4

Finishes Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°F (57°, 68°C)

K14.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed, Quick Response (Class 2020)

Company Tyco Mfg Ltd Victaulic Model TY6237 V3414 K 14.0 14.0 Type Recessed Pendent Recessed Pendent Response QR QR Element 3 mm 3 mm NPT (in.)

3/ 4 3/ 4

Finishes Brass, Chrome, Polyester, Lead Brass, Chrome, Polyester

Temp Ratings, °F (°C) 135°, 155°F, (57°, 68°C) 135°F (57°C)

K14.0 Extended Coverage Metal Building

Control mode, extended coverage metal building sidewall sprinklers are designed to protect metal buildings by discharging water perpendicular to the beams. These sprinklers are equipped with a quick response heat responsive element. However, they are FM Approved as standard response sprinklers due the delay caused by the extended maximum spacing between adjacent sprinklers. They are intended to protect certain light and ordinary hazard occupancies where a ``Density/Area'' design is permitted in the FM Global Loss Prevention Data Sheets. Care must be exercised to utilize these sprinklers only in applications for which they have been shown to be effective, as various restrictions apply. The FM Global Property Loss Prevention Data Sheets should be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers.

K14.0 Extended Coverage Metal Building Horizontal Sidewall (Class 2033)

Company Reliable Model R6932 K 14.0 Type Horizontal Sidewall Response SR Element Fusible NPT (in.)

3/4

Finishes Brass

Temp Ratings, °F (°C) 165°, 212°F (74°, 100°C)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-43

K16.8 Control Mode (Density/Area)

Control mode automatic sprinklers with a nominal discharge coefficient of 16.8 gal/min/(psi)½ are similar to control mode sprinklers with a nominal discharge coefficient of 11.2 gal/min/(psi)½ except that they discharge approximately 50% more water at the same discharge pressure. These are standard spray sprinklers intended for use in automatic sprinkler fire protection systems designed using the ``Density/Area'' method. These sprinklers are expected to 1) prewet combustibles surrounding the actual fire area to limit fire size, 2) cool the roof area directly over the fire to prevent structural failure, and 3) cool the roof area remote from the actual fire area so that too many sprinklers do not open and overtax the water supply. Control mode automatic sprinklers with a nominal discharge coefficient of 16.8 gal/min/(psi)½ offer the advantage of higher design densities at lower water supply pressures, which may allow adequate sprinkler protection to be achieved without the need for additional fire pumps. Care must be exercised to utilize these sprinklers only in applications for which they have been shown to be effective, as various restrictions apply. The FM Global Property Loss Prevention Data Sheets should be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers.

K16.8 Upright (Class 2024)

Company Viking Model VK580 K 16.8 Type Upright Response SR Element 5 mm NPT (in.)

3/4

Finishes Brass

Temp Ratings, °F (°C) 155°, 175°, 200°, 286°F (68°, 79°, 93°, 141°C)

K16.8 Control Mode (Specific Application)

Control mode (specific application) automatic sprinklers with a nominal discharge coefficient of 16.8 gal/min/(psi)½ are designed to 1) prewet combustibles surrounding the actual fire area to limit fire size, 2) cool the roof area directly over the fire to prevent structural failure, and 3) cool the roof area remote from the actual fire area so that too many sprinklers do not open and overtax the water supply. These sprinklers differ from control mode (density/area) sprinklers in that a fire protection system utilizing control mode (specific application) sprinklers is designed based on a given number of sprinklers operating at a specified minimum water supply pressure. Control mode (specific application) automatic sprinklers with a nominal discharge coefficient of 16.8 gal/min/(psi)½ offer the advantage of higher design densities at lower water supply pressures, which may allow adequate sprinkler protection to be achieved without the need for additional fire pumps. Care must be exercised to only utilize these sprinklers in applications for which they have been shown to be effective. The FM Global Property Loss Prevention Data Sheets should be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers.

K16.8 Control Mode (Specific Application) Upright (Class 2007)

Company Tyco Model TY7103 K 16.8 Type Upright Response SR Element 5 mm NPT (in.)

3/4

Finishes Brass 286°F (141°C)

Temp Ratings, °F (°C)

FM Approvals

1-44

September 2007 -- Approval Guide Automatic Sprinkler Systems

K25.2 Control Mode, Extended Coverage

Control mode, Extended Coverage sprinklers are designed to be installed at spacing and coverage areas up to 14 ft × 14 ft (4.3 m × 4.3 m) and a minimum spacing of 10 ft × 10 ft (3.0 m × 3.0 m). These sprinklers are for use in occupancies where a ``Density/Area'' design is permitted in the FM Global Loss Prevention Data Sheets. The FM Global Property Loss Prevention Data Sheets should be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers. Sprinklers not installed to these guidelines may not provide adequate property protection in the event of a fire.

K25.2 Extended Coverage Upright (Class 2022)

Company Tyco Model TY9128 K 25.2 Type Upright Response SR Element Fusible NPT (in.) 1 Brass Finishes Temp Ratings, °F (°C) 165°, 214°F (74°, 101°C)

Control Mode (Specific Application), Cooling Tower

Automatic control mode sprinklers for cooling towers are special purpose heads developed for the protection of fill areas of crossflow water cooling towers.

Automatic Sprinklers, Control Mode (Specific Application), Cooling Tower (Class 2019)

Company Grinnell Grinnell Kidde Model Issue C, Type I Issue C, Type II 38E Nominal 7/16, 1/2 in. orifice dia. Orifice Size Type Cooling Tower Nozzle Cooling Tower Nozzle Cooling Tower Nozzle Notes For use in towers with diffusion decks. For use in towers without diffusion decks.

Residential Mode Sprinklers

Residential sprinklers are fast response sprinklers that have been specifically investigated for their ability to enhance the survivability of occupants in the room of fire origin. They are intended to prevent flashover in the room of origin, thus improving the chance for occupants to escape or be evacuated. These sprinklers are FM Approved for use in the protection of dwelling units only. FM Approved sprinklers have been tested for effective performance as life safety devices at the minimum single sprinkler flow rates and maximum coverage areas listed in the Residential Sprinkler Minimum Flow Requirements Table below. These flow rates and coverage areas correspond to a discharge density equal to or greater than the minimum allowable discharge density of 0.05 gal/min/ft2 (2.04 mm/min), in accordance with NFPA 13R and 13D. FM Approved residential sprinklers have been determined to perform effectively as property protection devices when installed in accordance with the coverage area and density limitations specified in FM Global Property Loss Prevention Data Sheet 3-26. Residential sprinklers shall be installed in strict accordance with the FM Global Property Loss Prevention Data Sheets.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-45

Automatic Sprinklers, Residential Mode (Class 2030)

Company Tyco Tyco Tyco Tyco Viking Model TY4234 TY4234 TY4334 TY4334 VK420 K 6.9 6.9 5.8 5.8 3.8 Type Pendent Recessed Pendent HSW Recessed HSW Flush Pendent Response QR QR QR QR QR Element 3 mm 3 mm 3 mm 3 mm Fusible NPT (in.)

3/4 3/4 1/2 1/2 1/2

Finishes Brass, Chrome, Polyester Brass, Chrome, Brass, Chrome, Painted Brass, Chrome, Painted Brass, Chrome, Painted Polyester White White White

Temp Ratings, °F (°C) 155°, 175°F (68°, 79°C) 155°, 175°F (68°, 79°C) 155°, 175°F (68°, 79°C) 155°, 175°F (68°, 79°C) 165°F (74°C)

Residential Sprinkler Minimum Flow Requirements

Company Tyco Model TY4234 Max Coverage Area, ft × ft (m × m) 20 × 20 (6.1 × 6.1) 18 × 18 (5.5 × 5.5) 16 × 16 (4.9 × 4.9) Viking VK420 14 × 14 (4.3 × 4.3) 12 × 12 (3.7 × 3.7) 12 × 12 (3.7 × 3.7) 14 × 14 (4.3 × 4.3) Tyco TY4334 16 × 16 (4.9 × 4.9) 16 × 18 (4.9 × 5.5) 16 × 20 (4.9 × 6.1) 18 × 18 (5.5 × 5.5) Min Flow Rate, gal/min (L/min) 23 (87.1) 20 (75.7) 26 (98.4) 20 (75.7) 14 (53.0) 22 (83.3) 22 (83.3) 24 (90.8) 28 (106) 32 (121) 33 (125)

Suppression Mode Sprinklers K14.0 Suppression Mode [ESFR]

Suppression mode (formerly called Early Suppression-Fast Response or ``ESFR'') sprinklers with a nominal discharge coefficient of 14.0 gal/min/(psi)½ are designed to be used against severe fire challenges in occupancies where fire suppression is possible. They are not intended for use in occupancies where fires cannot be suppressed with water (e.g., low flash point flammable liquids, oxidizing chemicals, etc.). The expression ``suppression'' relates to sprinkler system performance whereby the first few sprinklers to operate provide sufficient water to the fire to reduce it promptly to an acceptable level, if not extinguish it. The effectiveness of suppression mode sprinklers depends on the combination of fast response and the quality and efficiency of the sprinkler discharge. Intermediate temperature-rated suppression mode sprinklers with a nominal discharge coefficient of 14.0 gal/min/(psi)½ are limited for use near localized heat sources. Consult the FM Global Property Loss Prevention Data Sheets concerning suppression mode sprinklers prior to designing and installing automatic fire protection systems utilizing this type of sprinkler. The FM Global Property Loss Prevention Data Sheets shall be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers.

FM Approvals

1-46

September 2007 -- Approval Guide Automatic Sprinkler Systems

K14.0 ESFR Upright (Class 2008)

Company Viking Model VK520 K 14.0 Type Upright Response FR Element Fusible NPT (in.)

3/4

Finishes Brass

Temp Ratings, °F (°C) 165°, 205°F (74°, 96°C)

K14.0 ESFR Pendent (Class 2008)

Company Kidde Reliable Reliable Tyco Viking Model AS1451 R5012 RA0512 TY6226 VK500 K 14.0 14.0 14.0 14.0 14.0 Type Pendent Pendent Pendent Pendent Pendent Response FR FR FR FR FR Element 2.5 mm 2.5 mm Fusible Fusible Fusible NPT (in.)

3/4 3/4 3/4 3/4 3/4

Finishes Brass Brass Brass Brass Brass

Temp Ratings, °F (°C) 155°, 200°F (68°, 93°C) 155°, 200°F (68°, 93°C) 165°, 212°F (74°, 100°C) 165°, 214°F (74°, 101°C) 165°, 205°F (74°, 96°C)

K16.8 Suppression Mode [ESFR]

Suppression mode (formerly called Early Suppression-Fast Response or ``ESFR'') automatic sprinklers with a nominal discharge coefficient of 16.8 gal/min/(psi)½ are similar to suppression mode sprinklers with nominal discharge coefficients of 14.0 gal/min/(psi)½ in that they are designed to be used against severe fire challenges in occupancies where fire suppression is possible. They are not intended for use in occupancies where fires cannot be suppressed with water (e.g., low flash point flammable liquids, oxidizing chemicals, etc.). This sprinkler offers the advantage of adequate hydraulic design at lower water supply pressures, which may allow adequate sprinkler protection to be achieved without the need for additional fire pumps. Consult the FM Global Property Loss Prevention Data Sheets concerning suppression mode sprinklers prior to designing and installing automatic fire protection systems utilizing this type of sprinkler. The FM Global Property Loss Prevention Data Sheets shall be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers.

K16.8 ESFR Upright (Class 2027)

Company Tyco Model TY7126 K 16.8 Type Upright Response FR Element Fusible NPT (in.)

3/4

Finishes Brass

Temp Ratings, °F (°C) 165°, 214°F (74°, 101°C)

K16.8 ESFR Pendent (Class 2027)

Company Tyco Mfg Ltd Viking Model TY7226 VK503 K 16.8 16.8 Type Pendent Pendent Response FR FR Element Fusible Fusible NPT (in.)

3/4 3/4

Finishes Brass Brass

Temp Ratings, °F (°C) 165°, 214°F (74°, 101°C) 165°, 205°F, (74°, 96°C)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-47

K22.4 Suppression Mode [ESFR]

Suppression mode (formerly called Early Suppression-Fast Response or ``ESFR'') automatic sprinklers with a nominal discharge coefficient of 22.4 gal/min/(psi)½ are similar to suppression mode sprinklers with nominal discharge coefficients of 14.0 and 16.8 gal/min/(psi)½ in that they are designed to be used against severe fire challenges. They are not, however, direct replacements for suppression mode pendent sprinklers with nominal discharge coefficients of 14.0 and 16.8 gal/min/(psi)½ in all applications. They are intended for use in certain occupancies where fire suppression is possible and are not suitable for use in occupancies where fires cannot be suppressed by water. This sprinkler offers the advantage of adequate hydraulic design at lower water supply pressures, which may allow adequate sprinkler protection to be achieved without the need for additional fire pumps. The range of applications for which this sprinkler can be used is smaller than that of suppression mode pendent sprinklers with nominal discharge coefficients of 14.0 and 16.8 gal/min/(psi)½. Care must be exercised to only utilize these sprinklers in applications for which they have been shown to be effective. Consult the FM Global Property Loss Prevention Data Sheets concerning suppression mode sprinklers prior to designing and installing automatic fire protection systems utilizing this type of sprinkler. The FM Global Property Loss Prevention Data Sheets shall be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers.

K22.4 ESFR Pendent (Class 2028)

Company Reliable Reliable Model R6611 RA1011 K 22.4 22.4 Type Pendent Pendent Response FR FR Element 2.5 mm Fusible NPT (in.) 1 1 Finishes Brass Brass Temp Ratings, °F (°C) 155°, 200°F (68°, 93°C) 212°F (100°C)

K25.2 Suppression Mode [ESFR]

Suppression mode (formerly called Early Suppression-Fast Response or ``ESFR'') automatic sprinklers with a nominal discharge coefficient of 25.2 gal/min/(psi)½ are similar to suppression mode sprinklers with nominal discharge coefficients of 14.0 and 16.8 gal/min/(psi)½ in that they are designed to be used against severe fire challenges. They are not, however, direct replacements for suppression mode pendent sprinklers with nominal discharge coefficients of 14.0 and 16.8 gal/min/(psi)½ in all applications. They are intended for use in certain occupancies where fire suppression is possible and are not suitable for use in occupancies where fires cannot be suppressed by water. This sprinkler offers the advantage of adequate hydraulic design at lower water supply pressures, which may allow adequate sprinkler protection to be achieved without the need for additional fire pumps. The range of applications for which this sprinkler can be used is smaller than that of suppression mode pendent sprinklers with nominal discharge coefficients of 14.0 and 16.8 gal/min/(psi)½. Care must be exercised to only utilize these sprinklers in applications for which they have been shown to be effective. Consult the FM Global Property Loss Prevention Data Sheets concerning suppression mode sprinklers prior to designing and installing automatic fire protection systems utilizing this type of sprinkler. The FM Global Property Loss Prevention Data Sheets shall be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers.

K25.2 ESFR Pendent (Class 2026)

Company Tyco Viking Model TY9226 VK510 K 25.2 25.2 Type Pendent Pendent Response FR FR Element Fusible Fusible NPT (in.) 1 1 Finishes Brass Brass Temp Ratings, °F (°C) 165°, 214°F (74°, 101°C) 165°, 205°F (74°, 96°C)

FM Approvals

1-48

September 2007 -- Approval Guide Automatic Sprinkler Systems

Sprinkler Guards/Shields

Sprinkler guards are designed to protect automatic sprinklers from mechanical damage in the event of a minor impact. They can be used on upright or pendent automatic sprinklers. Specific guards listed below for use with Early Suppression Fast Response (ESFR) automatic sprinklers are only intended for use under conveyors, mezzanines or other similar obstructions and are specifically not for use at ceiling level. Sprinkler shields are mounted directly to the sprinkler casting or may accompany the sprinkler guard to protect the thermal sensitive element from retarded operation due to water discharge from nearby sprinklers at higher elevations.

Sprinkler Guards/Shields (Class 2091)

Company Angus Angus GW GW Globe Globe Reliable Reliable Reliable Reliable Tyco Tyco Tyco Tyco Victaulic Victaulic Victaulic Victaulic Viking Viking Viking Viking Viking Viking Model Angus Angus GW GW JGS JG C-1 C-2 C-3 C-5 G1 G2 G1/S1 G4 V27 V27 V34 V34 A-1 B-1 C-1 D-1 D-1/E-1 D-1/F-1 Type Guard Guard Guard Guard Guard/Shield Guard Guard Guard Guard/Shield Guard/Shield Guard Guard Guard/Shield Guard Guard Guard/Shield Guard Guard/Shield Guard Guard/Shield Guard/Shield Guard Guard/Shield Guard/Shield Sprinklers FM Approved with Model S, 3 mm, K5.6 and 8.0 (1/2 in. and 3/4 in. NPT) Model S, 5 mm, K5.6 and 8.0 (1/2 in. and 3/4 in. NPT) Model S, 3 mm, K5.6 and 8.0 (1/2 in. and 3/4 in. NPT) Model S, 5 mm, K5.6 and K8.0 (1/2 in. and 3/4 in. NPT) GL5615, GL5661, GL8118, GL8164 GL5601, GL5615, GL5661, GL5651, GL8106, GL8118, GL8156, GL8164 R1011, R1015, R1016, R1017, R1021, R1025, R1026, R1027, R1235, R1285, R1712, R1715, R1721, R1725, R1735, R1785, R3612, R3615, R3622, R3625, R3635, R3685 R5314, R5714 R1025, R1027, R1725, R3622, R3625 R1015, R1017, R1715, R3615 TY3104, TY3151, TY3204, TY3251, TY4151, TY4251, TY4851, TY4951 TY5111, TY5131, TY5151, TY5211, TY5231, TY5251, TY5811, TY5851 TY3104, TY3151, TY4151 TY3104, TY3105 TY3131, TY3151, TY3204, TY3205, TY3231, TY3251, TY3304, TY3332, TY3351 V2703, V2704, V2707, V2708 V2703, V2704 V3401, V3402, V3403, V3404, V3405, V3406, V3407, V3408 V3401, V3402, V3403, V3404 VK001, VK003, VK005, VK007, VK100, VK102, VK108, VK130, VK132, VK200, VK202, VK204, VK206, VK300, VK350, VK352 VK005, VK108, VK204, VK300, VK350 VK007, VK206, VK302, VK352 VK001, VK003, VK005, VK007, VK100, VK102, VK108, VK130, VK132, VK200, VK202, VK204, VK206, VK300, VK350, VK352 VK001, VK005, VK100, VK108, VK130, VK200, VK204, VK300, VK350 VK003, VK007, VK102, VK132, VK202, VK206, VK352 Upright automatic sprinklers Fusible upright and pendent automatic sprinklers Upright automatic sprinklers Pendent automatic sprinklers Upright automatic sprinklers Sprinkler Types Upright and pendent automatic sprinklers Upright and pendent automatic sprinklers Upright and pendent automatic sprinklers Upright and pendent automatic sprinklers Upright automatic sprinklers Upright and pendent automatic sprinklers

Pendent automatic sprinklers Upright automatic sprinklers Pendent automatic sprinklers

Upright automatic sprinklers Pendent automatic sprinklers

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-49

Company Viking SA Viking SA

Model B-1 C-1

Type Guard/Shield Guard/Shield

Sprinklers FM Approved with VK005, VK108, VK204, VK300, VK350 VK007, VK206, VK302, VK352

Sprinkler Types Upright automatic sprinklers Pendent automatic sprinklers

FM Approvals

1-50

September 2007 -- Approval Guide Automatic Sprinkler Systems

SIGHT DRAINS

Sight drains may be used in sprinkler systems where the drain discharge outlet is not readily visible. When they are used, the discharge should conform to FM Global Property Loss Prevention Data Sheets and any local health or water department regulations. They are not to be used upstream of a valve or fitting which can trap pressure between the sight drain and the drain line. Unless otherwise noted in the listing, these sight drains have 175 psi (1205 kPa) rated working pressure.

Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154

1, 11/4, 11/2, 2 in. NPS 250 psi (1725 kPa) rated working pressure.

Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446

Grinnell or TFP Fig. SF1. 1, 2 in. NPS.

TELESCOPING SPRINKLER ASSEMBLIES FOR USE IN ANECHOIC CHAMBERS

Telescoping sprinkler assemblies are used to extend automatic or open sprinklers below the tips of the anechoic material in anechoic chambers. The assemblies are to be installed according to manufacturer's directives and in compliance with FM Global Property Loss Prevention Data Sheet 1-53.

Sprinkler Innovations LLC, 5 Perry Way, Newburyport MA 01950

Model NPT in. Assembly length ft (m) Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SI-1.0 SI-1.5 SI-2.0 SI-2.5 SI-3.0 SI-3.5 SI-4.0 SI-4.5 SI-5.0 SI-5.5 SI-6.0

3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4

1 (0.3) 1.5 (0.46) 2 (0.61) 2.5 (0.76) 3 (0.91) 3.5 (1.1) 4 (1.2) 4.5 (1.4) 5 (1.5) 5.5 (1.7) 6 (1.8)

8.6 (2.6) 9.4 (2.8) 10.2 (3.1) 11.0 (3.3) 11.8 (3.6) 12.0 (3.7) 12.2 (3.7) 12.4 (3.8) 12.6 (3.8) 12.8 (3.8) 12.9 (3.9)

Approval is limited to the vertical down position and with two cables attached to the springs. Approval is limited to the horizontal position and with one cable attached to the spring. The maximum rated working pressure is 175 psi (1205 kPa). These models were tested with a automatic sprinkler with a Nominal Discharge Coefficient of 8.0 gal/min/(psi)½. The minimum water pressure required to move the piston to the fully extended position is 25 psi (170 kPa). The following automatic sprinklers are FM Approved for use in the models listed above:

SIN Nominal K-Factor Bulb Type Sprinkler Manufacturer

GL8164 VK350

Model

8.0 8.0

NPT in.

Job G5, 5 mm Job F3, 3 mm

Assembly length ft (m)

Globe Fire Sprinkler Corporation The Viking Corporation

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SI-1.0 SI-1.5 SI-2.0 SI-2.5 SI-3.0 SI-3.5 SI-4.0

3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4

1 (0.3) 1.5 (0.46) 2 (0.61) 2.5 (0.76) 3 (0.91) 3.5 (1.1) 4 (1.2)

9.2 (2.8) 10.1 (3.1) 11.1 (3.4) 12.1 (3.7) 13.1 (3.9) 13.2 (4.0) 13.4 (4.1)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-51

Model

NPT in.

Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SI-4.5 SI-5.0 SI-5.5 SI-6.0

3/ 4 3/ 4 3/ 4 3/ 4

4.5 (1.4) 5 (1.5) 5.5 (1.7) 6 (1.8)

13.6 (4.1) 13.8 (4.2) 13.9 (4.2) 14.1 (4.3)

Approval is limited to the vertical down position and with two cables attached to the springs. Approval is limited to the horizontal position and with one cable attached to the spring. The maximum rated working pressure is 175 psi (1205 kPa). These models were tested with an automatic sprinkler with a Nominal Discharge Coefficient of 11.2 gal/min/(psi)½. The minimum water pressure required to move the piston to the fully extended position is 25 psi (170 kPa). The following automatic sprinklers are FM Approved for use in the models listed above:

SIN Nominal K-Factor Bulb Type Sprinkler Manufacturer

VK530

11.2

Job G5, 5 mm

The Viking Corporation

Model

NPT in.

Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SI-B-1.0 SI-B-1.5 SI-B-2.0 SI-B-2.5 SI-B-3.0 SI-B-3.5 SI-B-4.0 SI-B-4.5 SI-B-5.0 SI-B-5.5 SI-B-6.0

3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4

1 (0.3) 1.5 (0.5) 2 (0.6) 2.5 (0.8) 3 (0.9) 3.5 (1.1) 4 (1.2) 4.5 (1.4) 5 (1.5) 5.5 (1.7) 6 (1.8)

3.7 (1.1) 3.7 (1.1) 3.7 (1.1) 3.7 (1.1) 3.7 (1.1) 4.15 (1.3) 4.6 (1.4) 5.05 (1.5) 5.5 (1.7) 5.95 (1.8) 6.4 (1.9)

Approval is limited to the vertical down position only and with two cables attached to the springs. The maximum rated working pressure is 175 psi (1205 kPa). These models were tested with an automatic sprinkler with a Nominal Discharge Coefficient of 8.0 gal/min/(psi)½. The minimum water pressure required to move the piston to the fully extended position is 25 psi (170 kPa). The following automatic sprinklers are FM Approved for use in the models listed above:

SIN Nominal K-Factor Bulb Type Sprinkler Manufacturer

GL8164 VK350

Model

8.0 8.0

NPT in.

Job G5, 5 mm Job F3, 3 mm

Assembly length ft (m)

Globe Fire Sprinkler Corporation The Viking Corporation

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SI-B-1.0 SI-B-1.5 SI-B-2.0 SI-B-2.5 SI-B-3.0 SI-B-3.5 SI-B-4.0 SI-B-4.5 SI-B-5.0 SI-B-5.5 SI-B-6.0

3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4 3/ 4

1 (0.3) 1.5 (0.5) 2 (0.6) 2.5 (0.8) 3 (0.9) 3.5 (1.1) 4 (1.2) 4.5 (1.4) 5 (1.5) 5.5 (1.7) 6 (1.8)

3.3 (1.0) 3.6 (1.1) 3.8 (1.2) 4.1 (1.3) 4.3 (1.4) 4.9 (1.5) 5.4 (1.6) 6.0 (1.8) 6.5 (2.0) 7.1 (2.2) 7.6 (2.3)

FM Approvals

1-52

September 2007 -- Approval Guide Automatic Sprinkler Systems

Approval is limited to the vertical down position only and with two cables attached to the springs. The maximum rated working pressure is 175 psi (1205 kPa). These models were tested with an automatic sprinkler with a Nominal Discharge Coefficient of 11.2 gal/min/(psi)½. The minimum water pressure required to move the piston to the fully extended position is 25 psi (170 kPa). The following automatic sprinklers are FM Approved for use in the models listed above:

SIN Nominal K-Factor Bulb Type Sprinkler Manufacturer

VK530

11.2

Job G5, 5 mm

The Viking Corporation

FLEXIBLE SPRINKLER HOSE WITH FITTINGS FOR CLEANROOM CEILINGS

Flexible sprinkler hose with threaded end fittings are for use in cleanroom ceilings. The flexible hoses are to be installed according to the manufacturer's directives. Unless indicated, the hoses have a rated working pressure of 175 psi (1205 kPa).

AA Precision Metal Ltd, No. 23 Ta Pu, Wu Chuan Village, Ta Yuan Hsiang, Tao-Yuan Hsien, Taiwan ROC

Model NPT in. Hose Assembly length ft (m) Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

AA001-13 AA001-13 AA001-13 AA001-13

1/ 2 1/ 2 1/ 2 1/ 2

2 (0.61) 4 (1.22) 6 (1.83) 7 (2.13)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by AA Precision Metal Ltd.

CLEANPAK International Inc, 11241 SE Hwy 212, Clackamas OR 97015

Model NPT in. Hose Assembly length ft (m) Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

Clean-Flex Model Welded Clean-Flex Model Welded Clean-Flex Model Welded Clean-Flex Model Welded

1/ 2 1/ 2 1/ 2 1/ 2

2 (0.6) 3 (0.9) 4 (1.2) 6 (1.8)

11.7 (3.5) 16.9 (5.1) 21.8 (6.6) 28.9 (8.8)

Clean-Flex Model Welded. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanrooms. Approval is limited for use in cleanroom ceilings manufactured by CLEANPAK International Inc. When properly installed, the collar on the outlet pipe butts up against hold-down bracket on upper surface of ceiling and the sprinkler head frame extends below the ceiling.

Model NPT in. Hose Assembly length ft (m) Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

WF-WCO-N-50-C304L WF-WCO-N-50-C316L WF-WCO-A-50-C304L WF-WCO-A-50-C316L

1/ 2 1/ 2 1/ 2 1/ 2

4 (1.2) 4 (1.2) 4 (1.2) 4 (1.2) 6 (1.8) 6 (1.8) 6 (1.8) 6 (1.8)

15.4 (4.7) 15.4 (4.7) 15.4 (4.7) 15.4 (4.7) 21.4 (6.5) 21.4 (6.5) 21.4 (6.5) 21.4 (6.5)

WF-WCO-N-72-C304L WF-WCO-N-72-C316L WF-WCO-A-72-C304L WF-WCO-A-72-C316L

1/ 2 1/ 2 1/ 2 1/ 2

Cleanpak Model WF WCO: 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanrooms. The WCO Series is constructed of extruded seamless vacuum-formed white tube of open-pitch convoluted PTFE, protected by stainless steel braid. Available with and without armor covering. Approval is limited for use in cleanroom ceilings manufactured by CLEANPAK International Inc. WF = Weld Free N = No Armor covering A = Armor covering 50 = Live length in inches between collars. 72 = Live length in inches between collars. C304L/C316L = Stainless Steel alloy for the couplers on the ends of the hose.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-53

Flexible sprinkler hose with threaded end fittings are for use in commercial suspended ceilings. The flexible hoses are to be installed according to the manufacturer's directives. Unless indicated, the hoses have a rated working pressure of 175 psi (1205 kPa).

Dektronic Enterprise Co Ltd, 8F, No. 155, Sec. 1, Jung Shan Road, Yung He City, Taipei, Hsien Taiwan ROC 83113

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

DK-FLH1001-UIS DK-FLH1002-UIS DK-FLH1003-UIS

4.2 (1.3) 6.1 (1.8) 7.1 (2.1)

11.5 (3.5) 53.9 (16.4) 63.5 (19.3)

1/ 2

1/ 2

1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by United Information Systems Co., Ltd. (``T'' Grid Model TG001 and Cross Joint Model CJ001).

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

DK-FLH1001-CTC

4.2 (1.3)

11.5 (3.5)

1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Cherng-Gang Technology Construct Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

DK-FLH1001-F

4.2 (1.3)

11.5 (3.5)

1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Fuji Electric Co., Ltd.

Easyflex Inc, 15011 Parkway Loop, Unit G, Tustin CA 92780-6522

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

EFSPC-01A EFSPC-02A EFSPC-03A EFSPC-04A EFSPC-05A

2.5 (750) 3.9 (1200) 5.6 (1700) 7.2 (2200) 8.5 (2600)

1.6 (0.5) 9.5 (2.9) 13.6 (4.1) 19.2 (5.9) 25.4 (7.7)

1/ 2

1/ 2

1/ 2

1/ 2

1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanrooms. Approval is limited for use in cleanrooms manufactured by Shin Sung Engineering Co., Ltd.

FlexHead Industries Inc, 56 Lowland St, Holliston MA 01746

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRCS0036

3 (0.9)

15.1 (4.6)

Model CRCS0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling Model CG6200 manufactured by Channel Systems Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRCS0072

6 (1.8)

27.5 (8.4)

Model CRCS0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling Model CG6200 manufactured by Channel Systems Inc.

FM Approvals

1-54

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model

NPT in.

1/ 2

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRC 0036

3 (0.9)

15.1 (4.6)

Model CRC 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Clestra Cleanrooms Inc., now owned and manufactured by Gordon Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRC 0072

6 (1.8)

27.5 (8.4)

Model CRC 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Clestra Cleanrooms Inc., now owned and manufactured by Gordon Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRCAPL-0036

3 (0.9)

15.1 (4.6)

Model CRAPL-0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling grid manufactured by Kikukawa.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRCAPL-0072

6 (1.8)

27.5 (8.5)

Model CRAPL-0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling grid manufactured by Kikukawa.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRCS0036

3 (0.9)

15.1 (4.6)

Model CRCS0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling Model CG6200 manufactured by Channel Systems Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRCS0072

6 (1.8)

27.5 (8.4)

Model CRCS0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling Model CG6200 manufactured by Channel Systems Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRD 0036

3 (0.9)

15.1 (4.6)

Model CRD 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Daw Technologies, Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRD 0072

6 (1.8)

28.4 (8.4)

Model CRD 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Daw Technologies, Inc.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-55

Model

NPT in.

1/ 2

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRD 1036

3 (0.9)

15.1 (4.6)

Model CRD 1036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Daw Technologies, Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRSBB 0036

3 (0.9)

15.1 (4.6)

Model CRFH-0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling grid Model No. UG-1, UG-1 Gel, UG-Lite and UG-Lite-Gel manufactured by F. H. Chase Inc..

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRSBB 0072

6 (1.8)

27.5 (8.4)

Model CRFH 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling grid Model No. UG-1, UG-1 Gel, UG-Lite and UG-Lite-Gel manufactured by F. H. Chase Inc..

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRD 1072

6 (1.8)

27.5 (8.4)

Model CRD 1072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Daw Technologies, Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRGDS0036

3 (0.9)

15.1 (4.6)

Model CRGDS0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling Model DS/20 manufactured by Gordon Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRGDS0072

6 (1.8)

27.5 (8.4)

Model CRGDS0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling Model DS/20 manufactured by Gordon Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRF20036

3 (0.9)

15.1 (4.6)

Model CRF20036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling Model F2000D manufactured by Facilities Incorporated.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRF20072

6 (1.8)

27.5 (8.4)

Model CRF20072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling Model F2000D manufactured by Facilities Incorporated.

FM Approvals

1-56

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model

NPT in.

1/ 2

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRF40036

3 (0.9)

15.1 (4.6)

Model CRF40036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling Model F4000D manufactured by Facilities Incorporated.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRF40072

6 (1.8)

27.5 (8.4)

Model CRF40072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling Model F4000D manufactured by Facilities Incorporated.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRG 0036

3 (0.9)

15.1 (4.6)

Model CRG 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Gordon Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRG 0072

6 (1.8)

27.5 (8.4)

Model CRG 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Gordon Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRGV0036

3 (0.9)

15.1 (4.6)

Model CRGV0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Galvani SRL.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRGV0072

6 (1.8)

27.5 (8.4)

Model CRGV0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Galvani SRL.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRH 0036

3 (0.9)

15.1 (4.6)

Model CRH 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRH 0072

6 (1.8)

28.4 (8.4)

Model CRH 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-57

Model

NPT in.

1/ 2

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRS 0036

3 (0.9)

15.1 (4.6)

Model CRS 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRS 0040

3.3 (1.0)

15.3 (4.7)

Model CRS 0040. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRS 0060

5 (1.52)

24 (7.3)

Model CRS 0060. 1 in. nominal dia. flexible sprinkler metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRS 0072

6 (1.8)

27.5 (8.4)

Model CRS 0072. 1 in. nominal dia. flexible sprinkler metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRSBB 0036

3 (0.9)

15.1 (4.6)

Model CRSBB-0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling grid Model No. 2035 manufactured by SBB Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRSBB 0072

6 (1.8)

27.5 (8.4)

Model CRSBB 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling grid Model No. 2035 manufactured by SBB Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRW 0036

3 (0.9)

15.1 (4.6)

Model CRW 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by M+W Zander (formerly Meissner & Wurst).

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRW 0072

6 (1.8)

28.4 (8.4)

Model CRW 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by M+W Zander (formerly Meissner & Wurst).

FM Approvals

1-58

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model

NPT in.

1/ 2

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRYCF 0036

3 (0.9)

15.1 (4.6)

Model CRYCF 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Yung Cheng Feng.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRYCF 0072

6 (1.8)

27.5 (8.4)

Model CRYCF 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Yung Cheng Feng.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRH0036-PTFE

3 (0.9)

10.4 (3.4)

Model CRH0036-PTFE. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. This hose assembly utilizes a stainless steel braid over a nominal 1 in. I.D. PTFE (polytetrafluoroethylene) convoluted hose. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRH0072-PTFE

6 (1.8)

15.1 (4.6)

Model CRH0072-PTFE. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. This hose assembly utilizes a stainless steel braid over a nominal 1 in. I.D. PTFE (polytetrafluoroethylene) convoluted hose. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRH0036-PTFE-A

3 (0.9)

10.4 (3.4)

Model CRH0036-PTFE-A. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. This hose assembly has an armor protective covering over a stainless steel braid over a nominal 1 in. I.D. PTFE (polytetrafluoroethylene) convoluted hose. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRH0072-PTFE-A

6 (1.8)

15.1 (4.6)

Model CRH0072-PTFE-A. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. This hose assembly has an armor protective covering over a stainless steel braid over a nominal 1 in. I.D. PTFE (polytetrafluoroethylene) convoluted hose. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRW0036-PTFE-A

3 (0.9)

10.4 (3.4)

Model CRW0036-PTFE-A. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. This hose assembly has an armor protective covering over a stainless steel braid over a nominal 1 in. I.D. PTFE (polytetrafluoroethylene) convoluted hose. Approval is limited for use in cleanroom ceiling grid manufactured by M&W.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRW0072-PTFE-A

6 (1.8)

15.1 (4.6)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-59

Model CRW0072-PTFE-A. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. This hose assembly has an armor protective covering over a stainless steel braid over a nominal 1 in. I.D. PTFE (polytetrafluoroethylene) convoluted hose. Approval is limited for use in cleanroom ceiling grid manufactured by M&W.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRGLRP-0036

3 (0.9)

15.1 (4.6)

Model CRGLRP-0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling grid P/N LRPSCSTROUGH manufactured by Gordon.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRGLRP-0072

6 (1.8)

27.5 (8.5)

Model CRGLRP-0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceiling grid P/N LRPSCSTROUGH manufactured by Gordon.

HUNTAIR, 11555 SW Myslony St, Tualatin OR 97062

Model GRA0141 DROP NIPPLE ASSEMBLY 1 in. nominal dia flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Available in 6 ft lengths. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

GRA0141

6 (1.8)

23.5 (7.2)

Model GRA0141 DROP NIPPLE ASSEMBLY. 1 in. nominal dia flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.

Kofulso Co Ltd, 377-8 Gumgok, Seogu, Incheon, South Korea

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

KFB-SPC-01A KFB-SPC-02A KFB-SPC-03A KFB-SPC-04A KFB-SPC-05A

2.5 (750) 3.9 (1200) 5.6 (1700) 7.2 (2200) 8.5 (2600)

1.6 (0.5) 9.5 (2.9) 13.6 (4.1) 19.2 (5.9) 25.4 (7.7)

1/ 2

1/ 2

1/ 2

1/ 2

1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanrooms. Approval is limited for use in cleanrooms manufactured by Shin Sung Engineering Co., Ltd.

Panew Company Limited, 8F-5, No. 2 Jianba Road, Chung Ho, Taipei Hsien, Taiwan ROC

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9700 P-9700 P-9700 P-9700

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9700 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by AA Precision Metal Ltd.

FM Approvals

1-60

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model

NPT in.

1/ 2

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9710 P-9710 P-9710 P-9710

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9710 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Topline Engineering Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9720 P-9720 P-9720 P-9720

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9720 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Fuji Electric Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9730 P-9730 P-9730 P-9730

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9730 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Yung Cheng Feng Engineering Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9740 P-9740 P-9740 P-9740

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9740 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by United Information Systems Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9750 P-9750 P-9750 P-9750

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-61

Model P-9750 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Topwell Engineering Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9760 P-9760 P-9760 P-9760

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9760 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by M+W Zander Facility Engineering GmbH.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9770 P-9770 P-9770 P-9770

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9770 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Tenryo Technology and Engineering Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9790 P-9790 P-9790 P-9790

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9790 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Tien Hann Engineering Co., Ltd.

Paradise Industry Co Ltd, 65-2 Chooneui-Dong, Woonmi-Ku, Bucheon-City Kyunggi-Do, Korea (420-120)

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SFT-1000 SFT-1000 SFT-1500 SFT-1500-1 SFT-1500-1 SFT-D SFT-D SFT-E SFT-E

4.5 (1.4) 6.1 (1.8) 7.2 (2.2) 4.5 (1.4) 6.1 (1.8) 3.3 (1.0) 8.5 (2.6) 3.3 (1.0) 8.5 (2.6)

14.4 (4.4) 16.7 (5.1) 23.3 (7.1) 14.4 (4.4) 16.7 (5.1) 13.1 (4.2) 28.2 (8.6) 13.7 (4.2) 36.8 (11.2)

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

FM Approvals

1-62

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model

NPT in.

1/ 2

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SFT-F SFT-F SFT-L SFT-L SFT-M SFT-M

3.3 (1.0) 8.5 (2.6) 3.3 (1.0) 8.5 (2.6) 3.3 (1.0) 8.5 (2.6)

13.7 (4.2) 36.8 (11.2) 13.7 (4.2) 31.1 (9.5) 13.7 (4.2) 36.8 (11.2)

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

Models: SFT-1000 and SFT-1500-1. 1 in. nominal dia. flexible metal sprinkler hose with fittings for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is in the range of 4.5 ft (1400 mm) through 6.1 ft (1800 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering Co., Ltd. and Songhwa Engineering. Model SFT-1500. 1 in. nominal dia. flexible metal sprinkler hose with fittings for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering Co., Ltd. and Songhwa Engineering. Models: SFT-D, SFT-E, SFT-F, SFT-L and SFT-M. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is in the range of 3.3 ft (1000 mm) through 8.5 ft (2600 mm). Approval is limited for use in cleanroom ceilings manufactured by Hankook E&C, LG Engineering and Construct Corp., Shin Sung Engineering Co., Ltd. and Songhwa Engineering.

Seung Jin Industry Co Ltd, 612, 5 Bar Shi-Wha Industrial Complex, 685-11 Sunggog-Dong, Ansan-Si Kyunggi-Do, 429-450 Korea

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CRXXYY ­ ZZZZ CRXXYY ­ ZZZZ CRXXYY ­ ZZZZ CRXXYY ­ ZZZZ

2.6 (0.8) 8.5 (2.6) 3.3 (1.0) 8.2 (2.5)

8.3 (2.6) 31.8 (9.7) 7.6 (2.3) 31.4 (9.6)

1/ 2

3/ 4

3/ 4

CR: Cleanroom

XX: 12 for 1/2 in. reducer and 34 for 3/4 in. reducer. YY: Length of Hose assembly. (08 is a 0.8 m (2.6 ft) long hose assembly and 26 is a 2.6 m (8.5 ft) long hose assembly. 08 through 26 for 1/2 in. reducer, and 10 through 25 for 3/4 in. reducer. ZZZZ: Year and month manufactured.

Approval of this 1 in. nominal dia. flexible metal hose is limited for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in a cleanroom ceiling Model S-139 manufactured by Shin Sung Engineering Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SJ-CR-01 SJ-CR-01

3.3 (1.0) 3.3 (1.0)

9.9 (3.0) 9.4 (2.9)

3/ 4

Model SJ-CR-01. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval of 3.3 ft (1.0 m). Approval is limited for use in cleanroom ceiling Model S-139 manufactured by Shinsung Engineering Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SJ-CR-02 SJ-CR-02

6 (1.8) 6 (1.8)

19.3 (5.9) 19.0 (5.8)

3/ 4

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-63

Model SJ-CR-02. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval of 6 ft (1.8 m). Approval is limited for use in cleanroom ceiling Model S-139 manufactured by Shinsung Engineering Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SJ-CR-03 SJ-CR-03

8.3 (2.5 ) 8.3 (2.5)

26 (7.9) 31.6 (9.6)

3/ 4

Model SJ-CR-03. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval of 8.3 ft (2.5 m). Approval is limited for use in cleanroom ceiling Model S-139 manufactured by Shinsung Engineering Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SJ-CR-08 SJ-CR-25

2.6 (0.8) 8.2 (2.5)

10.9 (3.3) 35.3 (10.8)

1/ 2

Model SJ-CR-08 through SJ-CR-25. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in a cleanroom ceiling Model S-139 manufactured by Shin Sung Engineering Co., Ltd. Approval of these models is in the range as stated above. 08 to 25 is the range of length, 0.8 m to 2.5 m (2.6 ft to 8.2 ft).

Shanghai Genius Technical Corp Ltd, No. 7166 Zhong Chun Road, Qibao Town, Minhang District, Shanghai, P.R. China 201101

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9700 P-9700 P-9700 P-9700

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9700. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by AA Precision Metal Ltd.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9710 P-9710 P-9710 P-9710

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9710. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Topline Engineering Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9720 P-9720 P-9720 P-9720

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9720. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Fuji Electric Co., Ltd.

FM Approvals

1-64

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model

NPT in.

1/ 2

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9730 P-9730 P-9730 P-9730

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9730. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Yung Cheng Feng Engineering Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9740 P-9740 P-9740 P-9740

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9740. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by United Information Systems Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9750 P-9750 P-9750 P-9750

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9750. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Topwell Engineering Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9760 P-9760 P-9760 P-9760

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9760. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by M+W Zander Facility Engineering GmbH.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9770 P-9770 P-9770 P-9770

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-65

Model P-9770. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Tenryo Technology and Engineering Co., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9790 P-9790 P-9790 P-9790

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9790. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by Tien Hann Engineering Co., Ltd.

Super Flex Enterprises Co Ltd, No. 16, Lane 561, Sec 2, Kouji Rd, Taoyuan City, Taoyuan, Taiwan ROC

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SP-L SP-L SP-L SP-L SP-L SP-L SP-L SP-L SP-L SP-L SP-L SP-L SP-L

1.9 (0.60) 2.1 (0.64) 2.6 (0.80) 3.1 (0.96) 3.3 (1.0) 3.5 (1.0) 3.8 (1.2) 3.9 (1.2) 4.4 (1.3) 5.2 (1.6) 6.9 (2.1) 7.8 (2.4) 8.4 (2.6)

12.5 (3.8) 12.7 (3.9) 13.1 (4.0) 15.8 (4.8) 16.4 (5.0) 17.4 (5.3) 19.0 (5.8) 19.7 (6.0) 21.9 (6.7) 28.8 (8.8) 17.8 (5.4) 18.2 (5.5) 18.5 (5.6)

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

Model SP-L. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in the following cleanroom ceilings: · · · · · · · · · · · · · AA Precision Metal Ltd. ACC Tech Materials Co., Ltd. Fuji Electric Systems L&K Engineering Co., Ltd Long Long Clean Room Technology Co., Ltd. M+W Zander North Enging Corp.-Howell Tenryo Technology & Engineering Co., Ltd. Topline System Engineering Co., Ltd. Tien Hann Engineering Co., Ltd. Topwell Engineering Co., Ltd. United Information Systems Co., Ltd. Yung Cheng Feng Engineering Co., Ltd

NPT in.

1/ 2

Model

Hose Assembly Length ft (m)

Equivalent length of 1 in. Schedule 40 pipe ft (m)

SP-L-1

1.9 (0.60)

12.5 (3.8)

FM Approvals

1-66

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model

NPT in.

1/ 2

Hose Assembly Length ft (m)

Equivalent length of 1 in. Schedule 40 pipe ft (m)

SP-L-1 SP-L-1 SP-L-1 SP-L-1 SP-L-1 SP-L-1 SP-L-1 SP-L-1 SP-L-1 SP-L-1 SP-L-1 SP-L-1

2.1 (0.64) 2.6 (0.80) 3.1 (0.96) 3.3 (1.0) 3.5 (1.0) 3.8 (1.2) 3.9 (1.2) 4.4 (1.3) 5.2 (1.6) 6.9 (2.1) 7.8 (2.4) 8.4 (2.6)

12.7 (3.9) 13.1 (4.0) 15.8 (4.8) 16.4 (5.0) 17.4 (5.3) 19.0 (5.8) 19.7 (6.0) 21.9 (6.7) 28.8 (8.8) 17.8 (5.4) 18.2 (5.5) 18.5 (5.6)

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

Model SP-L-1. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited for use in the following cleanroom ceilings: · · · · · · · · · · · · · AA Precision Metal Ltd. ACC Tech Materials Co., Ltd. Fuji Electric Systems L&K Engineering Co., Ltd Long Long Clean Room Technology Co., Ltd. M+W Zander North Enging Corp.-Howell Tenryo Technology & Engineering Co., Ltd. Topline System Engineering Co., Ltd. Tien Hann Engineering Co., Ltd. Topwell Engineering Co., Ltd. United Information Systems Co., Ltd. Yung Cheng Feng Engineering Co., Ltd

US Hose Corporation, 815 Forestwood Drive, Romeoville IL 60446

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SF56016TFWC000

5 (1.5)

22.4 (6.8)

Model SF56016TFWC000. 1 in. nominal dia. flexible sprinkler hose for connection to automatic sprinklers in cleanrooms. This hose assembly has an armor protective covering over a stainless steel braid over a nominal 1 in. I.D. (polytetrafluoroethylene) PTFE convoluted hose. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SF56016TFWC001

6 (1.8)

29.9 (9.1)

Model SF56016TFWC001. 1 in. nominal dia. flexible sprinkler hose for connection to automatic sprinklers in cleanrooms. This hose assembly has an armor protective covering over a stainless steel braid over a nominal 1 in. I.D. (polytetrafluoroethylene) PTFE convoluted hose. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-67

Uniteq BV, Peelterbaan 8, 6002 NK Weert, The Netherlands

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

T1S025

3.3 (1.0)

14.2 (4.2)

Model T1S025. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. This hose assembly has a stainless steel braid over a nominal 1 in. I.D. (polytetrafluoroethylene) PTFE hose. Approval is limited for use in cleanroom ceilings manufactured by M+W Zander Type 55/70-T/E Profile.

Witzenmann GmbH, Postfach 1280, D-75112 Pforzheim, Germany

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

HYDRA HYDRA

3.3 (1.0) 7.7 (2.0)

7.7 (2.3) 16.0 (4.8)

1/ 2

HYDRA Hose. 1 in. (25 mm) nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is in the range of 3.3 ft to 7.7 ft (1000 mm to 2000 mm). Approval is limited for use in cleanroom ceilings manufactured by the following companies:

Company M & W Zander Facility Eng. GmbH M & W Zander Facility Eng. GmbH Daldrop & Dr. Ing Huber GmbH + Co. Grid Style M & W Profile Type Grid 55/60-FL/E M & W Profile Type Grid 55/70-T/E 40N

Yong Won E.N.C. Ltd, 116-1 Sedgu-Ri, Kwangjeuk-Myun, Yangju-Gun Keungki-Do, Korea

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

YB25-I YB25-I

3.5 (1.07) 8.4 (2.57)

9.3 (2.8) 18.4 (5.6)

1/ 2

Model YB25-I. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering Co. Ltd. The Model YB25-I is a one piece style. The reducer and nipple are welded to the flexible hose.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

YB25-II YB25-II

3.5 (1.07) 8.4 (2.57)

9.3 (2.8) 18.4 (5.6)

1/ 2

Model YB25-II. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering Co. Ltd. The Model YB25-II is a three piece style. The reducer and nipple are connected to the flexible hose using as a nut.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

YB25-III YB25-III

3.5 (1.07) 8.4 (2.57)

9.3 (2.8) 18.4 (5.6)

1/ 2

Model YB25-III. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering Co. Ltd. The Model YB25-III is a two piece style. The reducer is welded to the flexible hose and nipple is connected to the flexible hose using a nut.

FM Approvals

1-68

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model

NPT in.

1/ 2

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

YB28-IA YB28-IA

3.5 (1.07) 8.4 (2.57)

9.3 (2.8) 18.4 (5.6)

1/ 2

Model YB28-lA. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering Co. Ltd. The Model YB28-IA is a one piece style. The reducer and nipple are welded to the flexible hose.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

YB28-I YB28-I

3.5 (1.07) 8.4 (2.57)

9.3 (2.8) 18.4 (5.6)

1/ 2

Model YB28-l. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering Co. Ltd. The Model YB28-I is a one piece style. The reducer and nipple are welded to the flexible hose.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

YB28-II YB28-II

3.5 (1.07) 8.4 (2.57)

9.3 (2.8) 18.4 (5.6)

1/ 2

Model YB28-II. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering Co. Ltd. The Model YB28-II is a three piece style. The reducer and nipple are connected to the flexible hose using as a nut.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

YB28-III YB28-III

3.5 (1.07) 8.4 (2.57)

9.3 (2.8) 18.4 (5.6)

1/ 2

Model YB28-III. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering Co. Ltd. The Model YB28-III is a two piece style. The reducer is welded to the flexible hose and nipple is connected to the flexible hose using a nut.

FLEXIBLE SPRINKLER HOSE WITH FITTINGS FOR DUCTS

Flexible sprinkler hose with threaded end fittings are for use in ducts. The flexible hoses are to be installed according to the manufacturer's directives. All of the models listed below are 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in ducts. Approval is limited for use in ducts only. Unless indicated, the hoses have a rated working pressure of 175 psi (1205 kPa).

Dektronic Enterprise Co Ltd, 8F, No. 155, Sec. 1, Jung Shan Road, Yung He City, Taipei, Hsien Taiwan ROC 83113

NPT in.

1/ 2

Model

Hose Assembly length ft (mm)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

IL001 IL001 IL001

1.9 (0.6) 3.9 (1.2) 6.6 (2.0)

5.9 (1.8) 11.5 (3.5) 20.1 (6.1)

1/ 2

1/ 2

The 1 in. nominal diameter flexible sprinkler hose Model IL001 is Approved for providing a connection to automatic sprinkler protection to the interior of Fiberglass Reinforced Plastic (FRP) ducts and is not FM Approved for use in other applications. Approval is limited to using GS27 resin as the bonding agent between the bottom mounting block and the FRP duct.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-69

Model

NPT in.

1/ 2

Hose Assembly length ft (mm)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

IL001 IL001 IL001

1.9 (0.6) 3.9 (1.2) 6.6 (2.0)

5.9 (1.8) 11.5 (3.5) 20.1 (6.1)

1/ 2

1/ 2

The 1 in. nominal diameter flexible sprinkler hose Model IL001 is Approved for providing a connection to automatic sprinkler protection to the interior of steel ducts and is not FM Approved for use in other applications. Approval is limited to using GS27 resin as the bonding agent between the bottom mounting block and the steel duct.

NPT in.

1/ 2

Model

Hose Assembly length ft (mm)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

IL001 IL001 IL001

1.9 (0.6) 3.9 (1.2) 6.6 (2.0)

5.9 (1.8) 11.5 (3.5) 20.1 (6.1)

1/ 2

1/ 2

The 1 in. nominal diameter flexible sprinkler hose Model IL001 is Approved for providing a connection to automatic sprinkler protection to the interior of polypropylene plastic ducts and is not FM Approved for use in other applications. Approval is limited to using GS27 resin as the bonding agent between the bottom mounting block and the polypropylene plastic duct.

Easyflex Inc, 15011 Parkway Loop, Unit G, Tustin CA 92780-6522

NPT in.

1/ 2

Model

Hose Assembly length ft (mm)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

EFDC-01A EFDC-02A EFDC-03A EFDC-04A EFDC-05A

2.5 (750) 3.9 (1200) 5.6 (1700) 7.2 (2200) 8.5 (2600)

8.7 (2.6) 16.7 (5.1) 22.5 (6.9) 28.3 (8.6) 34.5 (10.5)

1/ 2

1/ 2

1/ 2

1/ 2

1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in ducts. Approval is limited for use in circular flange metal ducts.

EFDS-01A EFDS-02A EFDS-03A EFDS-04A EFDS-05A

1/ 2

2.5 (750) 3.9 (1200) 5.6 (1700) 7.2 (2200) 8.5 (2600)

8.7 (2.6) 16.7 (5.1) 22.5 (6.9) 28.3 (8.6) 34.5 (10.5)

1/ 2

1/ 2

1/ 2

1/ 2

1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in ducts. Approval is limited for use in square flange metal ducts.

FlexHead Industries Inc, 56 Lowland St, Holliston MA 01746

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

1024 1036

2 (0.6) 3 (.9)

11 (3.6) 19 (5.8)

1/ 2

FM Approvals

1-70

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model

NPT in.

1/ 2

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

1048

4 (1.2)

21 (6.4)

Approval of the Model 1000 series is limited to use in providing sprinkler protection to the interior of Fiberglass Reinforced Plastic (FRP) ducts and is not FM Approved for use in ducts of other materials or for other applications. Approval is limited to using Derakane 510 resin as the bonding agent between the bottom mounting block and the FRP duct.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

1124 1136 1148

2 (0.6) 3 (0.6) 4 (1.2)

11 (3.6) 19 (5.8) 21 (6.4)

1/ 2

1/ 2

Approval of the Model 1100 series is limited to use in providing sprinkler protection to the interior of metal ducts and is not FM Approved for use in ducts of other materials or for other applications.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

1224 1236 1248

2.5 (0.7) 3.5 (1.1) 4.5 (1.4)

11 (3.6) 19 (5.8) 21 (6.4)

1/ 2

1/ 2

Approval of the Model 1200 series is limited to use in providing sprinkler protection to the interior of polypropylene plastic ducts and is not FM Approved for use in ducts of other materials or for other applications.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

1324 1336 1348

2.5 (0.7) 3.5 (1.1) 4.5 (1.4)

11 (3.6) 19 (5.8) 21 (6.4)

1/ 2

1/ 2

Approval of the Model 1300 series is limited to use in providing sprinkler protection to the interior of polyvinyl chloride (PVC) plastic ducts and is not FM Approved for use in ducts of other materials or for other applications.

Kofulso Co Ltd, 377-8 Gumgok, Seogu, Incheon, South Korea

NPT in.

1/ 2

Model

Hose Assembly length ft (mm)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

KFB-SPDC-01A KFB-SPDC-02A KFB-SPDC-03A KFB-SPDC-04A KFB-SPDC-05A

2.5 (750) 3.9 (1200) 5.6 (1700) 7.2 (2200) 8.5 (2600)

8.7 (2.6) 16.7 (5.1) 22.5 (6.9) 28.3 (8.6) 34.5 (10.5)

1/ 2

1/ 2

1/ 2

1/ 2

1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in ducts. Approval is limited for use in circular flange metal ducts.

KFB-SPDS-01A

1/ 2

2.5 (750)

8.7 (2.6)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-71

Model

NPT in.

1/ 2

Hose Assembly length ft (mm)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

KFB-SPDS-02A KFB-SPDS-03A KFB-SPDS-04A KFB-SPDS-05A

3.9 (1200) 5.6 (1700) 7.2 (2200) 8.5 (2600)

16.7 (5.1) 22.5 (6.9) 28.3 (8.6) 34.5 (10.5)

1/ 2

1/ 2

1/ 2

1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in ducts. Approval is limited for use in square flange metal ducts.

Panew Company Limited, 8F-5, No. 2 Jianba Road, Chung Ho, Taipei Hsien, Taiwan ROC

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9900 P-9900 P-9900 P-9900

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9900 Approval is limited to use in providing sprinkler protection to the interior of Fiberglass Reinforced Plastic (FRP) ducts, Polypropylene plastic ducts and metal ducts and is not FM Approved for use in ducts of other materials or for other applications.

Paradise Industry Co Ltd, 65-2 Chooneui-Dong, Woonmi-Ku, Bucheon-City Kyunggi-Do, Korea (420-120)

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SFT-N SFT-N SFT-O SFT-O

3.3 (1.0 ) 8.5 (2.6 ) 3.3 (1.0 ) 8.5 (2.6 )

13.7 (4.2 ) 18.5 (5.6 ) 13.7 (4.2 ) 18.5 (5.6 )

1/ 2

1/ 2

1/ 2

1 in. nominal dia. flexible sprinkler hose with fittings for providing a connection to automatic sprinklers in ducts. Approval is in the range of 3.3 ft (1000 mm) to 8.5 ft (2600 mm).

Seung Jin Industry Co Ltd, 612, 5 Bar Shi-Wha Industrial Complex, 685-11 Sunggog-Dong, Ansan-Si Kyunggi-Do, 429-450 Korea

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

DUXX-YYYY DUXX-YYYY DUXX-YYYY DUXX-YYYY

2.6 (0.8) 8.5 (2.6) 2.6 (0.8) 8.5 (2.6)

8.3 (2.6) 31.8 (9.7) 7.6 (2.3) 31.4 (9.6)

1/ 2

3/ 4

3/ 4

DU: Duct XX: Product length. 08 through 26 (08 is a 0.8 m (2.6 ft) long hose assembly and 26 is a 2.6 m (8.5 ft) long hose assembly. YYYY: Year and month manufactured.

Approval of these 1 in. nominal dia. flexible metal sprinkler hose model is limited to use in providing sprinkler protection to the interior of Fiberglass Reinforced Plastic (FRP) ducts and is not Approved for use in ducts of other materials or for other applications.

FM Approvals

1-72

September 2007 -- Approval Guide Automatic Sprinkler Systems

Shanghai Genius Technical Corp Ltd, No. 7166 Zhong Chun Road, Qibao Town, Minhang District, Shanghai, P.R. China 201101

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9900 P-9900 P-9900 P-9900

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

5.5 (1.7) 7.8 (2.4) 11.1 (3.4) 12.6 (3.7)

1/ 2

1/ 2

1/ 2

Model P-9900. Approval is limited to use in providing sprinkler protection to the interior of Fiberglass Reinforced Plastic (FRP) ducts, Polypropylene plastic ducts and metal ducts and is not FM Approved for use in ducts of other materials or for other applications.

Yong Won E.N.C. Ltd, 116-1 Sedgu-Ri, Kwangjeuk-Myun, Yangju-Gun Keungki-Do, Korea

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

YB28-D-B YB28-D-B YB28-D-B YB28-D-B YB28-D-F YB28-D-F YB28-D-F YB28-D-F

3.5 (1.07) 8.4 (2.57) 3.5 (1.07) 8.4 (2.57) 3.5 (1.07) 8.4 (2.57) 3.5 (1.07) 8.4 (2.57)

5.5 (1.6) 15.2 (4.6) 5.7 (1.7) 17.0 (5.2) 5.5 (1.6) 15.2 (4.6) 5.7 (1.7) 17.0 (5.2)

1/ 2

3/ 4

3/ 4

1/ 2

1/ 2

3/ 4

3/ 4

Model YB28-D-BP 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in ducts. Available in a range from (3.5 to 8.4 feet) 1075 mm to 2575 mm. Approval is limited to interior sprinkler protection of Polypropylene Plastic ducts of 10 to 60 in. (25.4 to 152.4 cm) diameter and is not Approved for use in ducts of other materials or for other applications. The Model YB28-D-BP is a one piece hose with nuts on each end. A threaded nipple is connected to the nut at the inlet of the hose. Approval is limited to interior sprinkler protection of Fiberglass Reinforced Plastic (FRP) ducts of 10 to 60 in. (25.4 to 152.4 cm) diameter and is not Approved for use in ducts of other materials or for other applications. Approval is limited to using FRP bond made by Korea Chemical Company as the bonding agent between the bottom mounting block and the FRP duct.

FLEXIBLE SPRINKLER HOSE WITH FITTINGS FOR COMMERCIAL SUSPENDED CEILINGS

Flexible sprinkler hose with threaded end fittings are for use in commercial suspended ceilings. The flexible hoses are to be installed according to the manufacturer's directives. Unless indicated, the hoses have a rated working pressure of 175 psi (1205 kPa).

AF-USA LLC, 503 Industrial Drive, Bensenville IL 60106

NPT in.

1/ 2

Model

Hose Assembly length ft (mm)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

AFBW24H AFBW31H AFBW36H AFBW48H

2 (0.6) 2.6 (0.78) 3 (0.91) 4 (1.2)

18.9 (5.7) 26.5 (8.1) 31.9 (9.7) 44.3 (13.5)

1/ 2

1/ 2

1/ 2

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-73

Model

NPT in.

1/ 2

Hose Assembly length ft (mm)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

AFBW60H AFBW72H AFBW84H

5 (1.5) 6 (1.8) 7 (2.1)

55.5 (16.9) 61.5 (18.7) 59.9 (18.3)

1/ 2

1/ 2

AFB24H AFB31H AFB36H AFB48H AFB60H AFB72H AFB84H

1/ 2

2 (0.6) 2.6 (0.78) 3 (0.91) 4 (1.2) 5 (1.5) 6 (1.8) 7 (2.1)

18.9 (5.7) 26.5 (8.1) 31.9 (9.7) 44.3 (13.5) 55.5 (16.9) 61.5 (18.7) 59.9 (18.3)

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

AFBW24T AFBW31T AFBW36T AFBW48T AFBW60T AFBW72T AFBW84T

3/ 4

2 (0.6) 2.6 (0.78) 3 (0.91) 4 (1.2) 5 (1.5) 6 (1.8) 7 (2.1)

18.2 (5.5) 26.0 (7.9) 31.6 (9.6) 40.3 (12.3) 54.1 (16.5) 60.1 (18.3) 59.5 (18.1)

3/ 4

3/ 4

3/ 4

3/ 4

3/ 4

3/ 4

AFB24T AFB31T AFB36T AFB48T AFB60T AFB72T AFB84T

3/ 4

2 (0.6) 2.6 (0.78) 3 (0.91) 4 (1.2) 5 (1.5) 6 (1.8) 7 (2.1)

18.2 (5.5) 26.0 (7.9) 31.6 (9.6) 40.3 (12.3) 54.1 (16.5) 60.1 (18.3) 59.5 (18.1)

3/ 4

3/ 4

3/ 4

3/ 4

3/ 4

3/ 4

1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is limited for use in commercial suspended ceilings with a bracket system manufactured by AF-USA LLC. The code of information for these model designations is as follows:

Marking Description

AF B W

Manufacturer's initials Braid Welded: These model hoses have a weld on the outlet end, securing the outlet reducer to the hose. A slip nut connects the flexible hose to the inlet nipple.

FM Approvals

1-74

September 2007 -- Approval Guide Automatic Sprinkler Systems

Marking

Description

Flexible Hose Lengths: 24 31 36 48 60 72 84 H T 24 in. 31 in. 36 in. 48 in. 60 in. 72 in. 84 in.

1/ 2 3/ 4

in. NPT outlet in. NPT outlet

Dong-A Flexible Metal Tubes Co Ltd, 5th Floor, Yuchang B/D, #108-6, Yangjae Dong, Seocho-Gu, Seoul, Korea (137-130)

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

DA-SPB-01A-NPT DA-SPB-02A-NPT DA-SPB-03A-NPT DA-SPB-04A-NPT DA-SPB-05A-NPT

2.5 (0.78) 4 (1.2) 5 (1.5) 6.2 (1.8) 8.3 (2.5)

14.6 (4.5) 28.0 (8.5) 50.2 (15.3) 53.5 (16.3) 67.1 (20.4)

1/ 2

1/ 2

1/ 2

1/ 2

DA-SPNB-01A-NPT DA-SPNB-02A-NPT DA-SPNB-03A-NPT DA-SPNB-04A-NPT DA-SPNB-05A-NPT

1/ 2

2.5 (0.78) 4 (1.2) 5 (1.5) 6.2 (1.8) 8.3 (2.5)

14.6 (4.5) 28.0 (8.5) 50.2 (15.3) 53.5 (16.3) 67.1 (20.4)

1/ 2

1/ 2

1/ 2

1/ 2

DA-SPWB-01A-NPT DA-SPWB-02A-NPT DA-SPWB-03A-NPT DA-SPWB-04A-NPT DA-SPWB-05A-NPT

1/ 2

2.5 (0.78) 4 (1.2) 5 (1.5) 6.2 (1.8) 8.3 (2.5)

14.6 (4.5) 28.0 (8.5) 50.2 (15.3) 53.5 (16.3) 67.1 (20.4)

1/ 2

1/ 2

1/ 2

1/ 2

DA-SPB-01B-NPT DA-SPB-02B-NPT DA-SPB-03B-NPT DA-SPB-04B-NPT DA-SPB-05B-NPT

3/ 4

2.5 (0.78) 4 (1.2) 5 (1.5) 6.2 (1.8) 8.3 (2.5)

20.7 (6.3) 32.1 (9.8) 48.4 (14.7) 56.6 (17.2) 77.1 (23.5)

3/ 4

3/ 4

3/ 4

3/ 4

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-75

Model

NPT in.

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

DA-SPNB-01B-NPT DA-SPNB-02B-NPT DA-SPNB-03B-NPT DA-SPNB-04B-NPT DA-SPNB-05B-NPT

3/ 4

2.5 (0.78) 4 (1.2) 5 (1.5) 6.2 (1.8) 8.3 (2.5)

20.7 (6.3) 32.1 (9.8) 48.4 (14.7) 56.6 (17.2) 77.1 (23.5)

3/ 4

3/ 4

3/ 4

3/ 4

DA-SPWB-01B-NPT DA-SPWB-02B-NPT DA-SPWB-03B-NPT DA-SPWB-04B-NPT DA-SPWB-05B-NPT

3/ 4

2.5 (0.78) 4 (1.2) 5 (1.5) 6.2 (1.8) 8.3 (2.5)

20.7 (6.3) 32.1 (9.8) 48.4 (14.7) 56.6 (17.2) 77.1 (23.5)

3/ 4

3/ 4

3/ 4

3/ 4

1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is limited for use in commercial suspended ceilings. Approval is limited for use in commercial suspended ceilings with a bracket system manufactured by Dong-A Flexible Metal Tubes Co., Ltd. The code of information for these model designations is as follows:

Marking Description

DA SPB SPNB SPWB 01 02 03 04 05 A B

Manufacturer's initials The hose is threaded to a nipple on the inlet end and threaded to a reducer at the outlet. The hose is threaded to a nipple on the inlet end and the reducer is brazed to the flexible hose at the outlet The hose is brazed to a nipple on the inlet end and brazed to a reducer at the outlet Flexible Hose Lengths: 01 = 780 mm 02 = 1,220 mm 03 = 1,540 mm 04 = 1,880 mm 05 = 2,500 mm

1/2 3/4

in. NPT in. NPT

Easyflex Inc, 15011 Parkway Loop, Unit G, Tustin CA 92780-6522

NPT in.

1/ 2

Model

Hose Assembly length ft (mm)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

EFB231 EFB248 EFB260 EFB285 EFB2102

2.5 (750) 3.9 (1200) 5.6 (1700) 7.2 (2200) 8.5 (2600)

8.7 (2.6) 16.7 (5.1) 22.5 (6.9) 28.3 (8.6) 34.5 (10.5)

1/ 2

1/ 2

1/ 2

1/ 2

EFB331

3/ 4

2.5 (750)

7.2 (2.2)

FM Approvals

1-76

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model

NPT in.

3/ 4

Hose Assembly length ft (mm)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

EFB348 EFB360 EFB385 EFB3102

3.9 (1200) 5.6 (1700) 7.2 (2200) 8.5 (2600)

12.7 (3.9) 18.8 (5.7) 22.9 (6.9) 33.4 (10.2)

3/ 4

3/ 4

3/ 4

1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is limited for use in commercial suspended ceilings with a bracket system manufactured by Easyflex Inc.

FlexHead Industries Inc, 56 Lowland St, Holliston MA 01746

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

2024 2036 2048 2060 2072

2 (0.6) 3 (0.9) 4 (1.2) 5 (1.5) 6 (1.8)

3.5 (1.1) 4.8 (1.5) 6.8 (2.1) 8.5 (2.6) 8.9 (2.7)

1/ 2

1/ 2

1/ 2

1/ 2

This is a standard flexible hose with a pressure rating of 175 psi (1205 kPa). Approval on these models of flexible metal sprinkler hose is limited for use in commercial suspended ceilings (T-Bar Grid) and Sheetrock suspended ceilings, with a ceiling bracket system manufactured by FlexHead Industries Inc. The FlexHead brackets are identified as follows: Part Numbers: · SP-24-BKT (1) · SP-24-BKT (2) · MP-24-BKT · MP-24-BKT-2 · SP-06TZ-BKT · AD-16-BKT-2 · AD-24-BKT-2 · UH-2

SP = Single Port MP = Multiport TZ = Tech Zone AD = Adjustable UH = Universal Hub (1) = 1 Piece (2) = 2 Piece 06 = Length in inches of bracket 16 = Length in inches of bracket 24 = Length in inches of bracket BKT = Bracket

The FlexHead Clamp Model UH-2 with a maximum 2 ft (610 mm) 3/8 in. nominal size threaded rod is for attachment to support these hose models. The Model UH-2 FlexHead clamp is manufactured by FlexHead Industries Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

2024H 2036H 2048H 2060H 2072H

2 (0.6) 3 (0.9) 4 (1.2) 5 (1.5) 6 (1.8)

11 (3.6) 19 (5.8) 21 (6.4) 24 (7.3) 27.5 (8.4)

1/ 2

1/ 2

1/ 2

1/ 2

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-77

The ``H'' indicates a high pressure of 300 psi (2070 kPa). Approval of this flexible metal sprinkler hose is limited for use in commercial suspended ceilings, (T-Bar Grid) and Sheetrock suspended ceilings with a ceiling bracket system manufactured by FlexHead Industries Inc. The FlexHead brackets are identified as follows: Part Numbers: · SP-24-BKT (1) · SP-24-BKT (2) · MP-24-BKT · MP-24-BKT-2 · SP-06TZ-BKT · AD-16-BKT-2 · AD-24-BKT-2 · UH-2

SP = Single Port MP = Multiport TZ = Tech Zone AD = Adjustable UH = Universal Hub (1) = 1 Piece (2) = 2 Piece 06 = Length in inches of bracket 16 = Length in inches of bracket 24 = Length in inches of bracket BKT = Bracket

The FlexHead Clamp Model UH-2 with a maximum 2 ft (610 mm) 3/8 in. nominal size threaded rod is for attachment to support these hose models. The Model UH-2 FlexHead clamp is manufactured by FlexHead Industries Inc.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

2024M 2036M 2048M 2060M 2072M

2 (0.6) 3 (0.9) 4 (1.2) 5 (1.5) 6 (1.8)

2.9 (0.9) 4.4 (1.3) 6.7 (2.0) 10.4 (3.4) 11.4 (3.5)

1/ 2

1/ 2

1/ 2

1/ 2

The ``M'' indicates a mechanical flare type connection with a pressure rating of 300 psi (2070 kPa). Approval of this flexible metal sprinkler hose is limited for use in commercial suspended ceilings, with a ceiling bracket system manufactured by FlexHead Industries Inc. The FlexHead brackets are identified as follows: Part Numbers: · SP-24-BKT (1) · SP-24-BKT (2) · MP-24-BKT · MP-24-BKT-2 · SP-06TZ-BKT · AD-16-BKT-2 · AD-24-BKT-2 · UH-2

SP = Single Port MP = Multiport TZ = Tech Zone AD = Adjustable UH = Universal Hub (1) = 1 Piece (2) = 2 Piece 06 = Length in inches of bracket 16 = Length in inches of bracket 24 = Length in inches of bracket BKT = Bracket

The FlexHead Clamp Model UH-2 with a maximum 2 ft (610 mm) 3/8 in. nominal size threaded rod is for attachment to support these hose models. The Model UH-2 FlexHead clamp is manufactured by FlexHead Industries Inc.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

2024E 2036E 2048E 2060E 2072E

2 (0.6) 3 (0.9) 4 (1.2) 5 (1.5) 6 (1.8)

5.5 (1.7) 6.8 (2.1) 8.8 (2.7) 10.5 (3.2) 10.9 (3.3)

1/ 2

1/ 2

1/ 2

1/ 2

The ``E'' indicates an elbow welded on the end of the hose. Approval of these models of flexible metal sprinkler hose incorporate a stainless steel elbow welded on the outlet end of the hose and are limited for use in commercial suspended ceilings (T-Bar Grid) and Sheetrock suspended ceilings, with a ceiling bracket system manufactured by FlexHead Industries Inc. The FlexHead brackets are identified as follows:

FM Approvals

1-78

September 2007 -- Approval Guide Automatic Sprinkler Systems

Part Numbers: · SP-24-BKT (1) · SP-24-BKT (2) · MP-24-BKT · MP-24-BKT-2 · SP-06TZ-BKT · AD-16-BKT-2 · AD-24-BKT-2 · UH-2

SP = Single Port MP = Multiport TZ = Tech Zone AD = Adjustable UH = Universal Hub (1) = 1 Piece (2) = 2 Piece 06 = Length in inches of bracket 16 = Length in inches of bracket 24 = Length in inches of bracket BKT = Bracket

The FlexHead Clamp Model UH-2 with a maximum 2 ft (610 mm) 3/8 in. nominal size threaded rod is for attachment to support these hose models. The Model UH-2 FlexHead clamp is manufactured by FlexHead Industries Inc.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

2024E-LP 2036E-LP 2048E-LP 2060E-LP 2072E-LP

2 (0.6) 3 (0.9) 4 (1.2) 5 (1.5) 6 (1.8)

5.5 (1.7) 6.8 (2.1) 8.8 (2.7) 10.5 (3.2) 10.9 (3.3)

1/ 2

1/ 2

1/ 2

1/ 2

2024E-LP 75 2036E-LP 75 2048E-LP 75 2060E-LP 75 2072E-LP 75

3/ 4

2 (0.6) 3 (0.9) 4 (1.2) 5 (1.5) 6 (1.8)

7.8 (2.4) 8.1 (2.5) 17.9 (5.4) 19.9 (6.1) 24.3 (7.4)

3/ 4

3/ 4

3/ 4

3/ 4

The ``E-LP'' indicates a ``low profile'' elbow unit welded on the end of the hose. Approval of these models of flexible metal sprinkler hose incorporates a stainless steel elbow welded on the outlet end of the hose and with unistrut channel and pipe clamp is limited to securing these models to the building structure. These models are for use in commercial suspended ceilings (T-Bar Grid) and Sheetrock suspended ceilings with very limited room between floors.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

2036-E-PTFE

3 (0.9)

10.4 (3.4)

Model 2036-E-PTFE. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings (T-Bar Grid) and Sheetrock suspended ceilings. This assembly utilizes a stainless steel braid over a nominal 1 in. I.D. PTFE (polytetrafluoroethylene) convoluted hose. The ``E'' indicates an elbow attached on the end of the hose. This hose model is for use with the Model UH-2 (Universal Hub) FlexHead clamp with a maximum 2 ft (610 mm) 3/8 in. nominal size threaded rod.

NPT in.

3/ 4

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

2024 75 2036 75 2048 75 2060 75 2072 75

2 (0.6) 3 (0.9) 4 (1.2) 5 (1.5) 6 (1.8)

7.8 (2.4) 8.1 (2.5) 17.9 (5.4) 19.9 (6.1) 24.3 (7.4)

3/ 4

3/ 4

3/ 4

3/ 4

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-79

This is a standard hose with a pressure rating of 175 psi (1205 kPa). The ``75'' indicates a 3/4 inch NPT outlet. Approval on these models of flexible metal sprinkler hose is limited for use in commercial suspended ceilings (T-Bar Grid) and Sheetrock suspended ceilings, with a ceiling bracket system manufactured by FlexHead Industries Inc. The FlexHead brackets are identified as follows: Part Numbers: · SP-24-BKT (1) · SP-24-BKT (2) · MP-24-BKT · MP-24-BKT-2 · SP-06TZ-BKT · AD-16-BKT-2 · AD-24-BKT-2 · UH-2

SP = Single Port MP = Multiport TZ = Tech Zone AD = Adjustable UH = Universal Hub (1) = 1 Piece (2) = 2 Piece 06 = Length in inches of bracket 16 = Length in inches of bracket 24 = Length in inches of bracket BKT = Bracket

The FlexHead Clamp Model UH-2 with a maximum 2 ft (610 mm) 3/8 in. nominal size threaded rod is for attachment to support these hose models. The Model UH-2 FlexHead clamp is manufactured by FlexHead Industries Inc.

Kofulso Co Ltd, 377-8 Gumgok, Seogu, Incheon, South Korea

NPT in.

1/ 2

Model

Hose Assembly length, ft (mm)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

KFB224 KFB231 KFB236 KFB248 KFB260 KFB267 KFB272 KFB287 KFB2102

2.0 (610) 2.6 (790) 3.0 (915) 4.0 (1220) 5.0 (1525) 5.6 (1700) 6.0 (1830) 7.2 (2200) 8.5 (2600) 2.0 (610) 2.6 (790) 3.0 (915) 4.0 (1220) 5.0 (1525) 5.6 (1700) 6.0 (1830) 7.2 (2200) 8.5 (2600)

6.8 (2.1) 8.7 (2.6) 11.5 (3.5) 16.7 (5.1) 20.6 (6.3) 22.5 (6.9) 24.0 (7.3) 28.3 (8.6) 34.5 (10.5) 4.7 (1.4) 7.2 (2.2) 10.6 (3.2) 12.7 (3.9) 17.0 (5.2) 18.8 (5.7) 19.8 (6.0) 22.9 (6.9) 33.4 (10.2)

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

KFB324 KFB331 KFB336 KFB348 KFB360 KFB367 KFB372 KFB387 KFB3102

3/ 4

3/ 4

3/ 4

3/ 4

3/ 4

3/ 4

3/ 4

3/ 4

3/ 4

1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is limited for use in commercial suspended ceilings with the following bracket systems manufactured by Kofulso Co., Ltd. · · · · · · · ``GSB'' with ``SSB''. ``TBS'' with ``SSB''. ``TBS'' with ``SBB''. ``TBL'' with ``SSB''. ``TBL'' with ``SBB''. Stock Bar and clamp assembly in a T-Bar ceiling grid. SHB System and a GSB Bracket assembly in a T-Bar ceiling grid.

FM Approvals

1-80

September 2007 -- Approval Guide Automatic Sprinkler Systems

The description of the bracket systems are as follows: GSB: Grid Snap Bracket - Length of ``GSB'': 24 in. (610 mm) SSB: Snap Clamp Center Bracket SBB: Bolt Clamp Center Bracket TBS: T-Bar Bracket Short TBL: T-Bar Bracket Long Length of Stock Bar: 25 in. (635 mm) SHB: Center Bracket Hook Clamp

NPT in.

1/ 2

Model

Hose Assembly length, ft (mm)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

KFBL224 KFBL231 KFBL236 KFBL248 KFBL260 KFBL267 KFBL272 KFBL287 KFBL2102

2.0 (610) 2.6 (790) 3.0 (915) 4.0 (1220) 5.0 (1525) 5.6 (1700) 6.0 (1830) 7.2 (2200) 8.5 (2600)

18.0 (5.5) 20.6 (6.3) 22.3 (6.8) 26.7 (8.1) 20.6 (6.3) 32.9 (10.0) 26.3 (8.0) 33.6 (10.2) 41.0 (12.5)

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

KFBL324 KFBL331 KFBL336 KFBL348 KFBL360 KFBL367 KFBL372 KFBL387 KFBL3102

3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

2.0 (610) 2.6 (790) 3.0 (915) 4.0 (1220) 5.0 (1525) 5.6 (1700) 6.0 (1830) 7.2 (2200) 8.5 (2600)

16.2 (4.9) 19.4 (5.9) 21.6 (6.6) 27.1 (8.3) 22.5 (6.8) 33.8 (10.3) 26.1 (7.9) 33.3 (10.1) 41.7 (12.7)

· · · · · · ·

``GSB'' with ``SSB''. ``TBS'' with ``SSB''. ``TBS'' with ``SBB''. ``TBL'' with ``SSB''. ``TBL'' with ``SBB''. Stock Bar and clamp assembly in a T-Bar ceiling grid. SHB System and a GSB Bracket assembly in a T-Bar ceiling grid.

The description of the bracket systems are as follows: GSB: Grid Snap Bracket ­ Length of ``GSB'': 24 in. (610 mm) SSB: Snap Clamp Center Bracket SBB: Bolt Clamp Center Bracket TBS: T-Bar Bracket Short TBL: T-Bar Bracket Long Length of Stock Bar: 25 in. (635 mm) SHB: Center Bracket Hook Clamp

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-81

The code of information for these model designations is the following:

Model Description

KFBL224

KF: Kofulso (Manufacturer's initials) B: Braided hose L: Elbow 2: 1/2 in. NPT 24: Flexible Hose Length in inches

KFB3102

KF: Kofulso (Manufacturer's initials) B: Braided hose 3: 3/4 in. NPT 102: Flexible hose length in inches

Model

NPT in.

1/ 2

Hose Assembly length, ft (mm)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

KFB-SP-01A KFB-SP-02A KFB-SP-03A KFB-SP-04A KFB-SP-05A

2.5 (750) 3.9 (1200) 5.6 (1700) 7.2 (2200) 8.5 (2600)

8.7 (2.6) 16.7 (5.1) 22.5 (6.9) 28.3 (8.6) 34.5 (10.5)

1/ 2

1/ 2

1/ 2

1/ 2

KFB-SP-01AB KFB-SP-02AB KFB-SP-03AB KFB-SP-04AB KFB-SP-05AB

3/ 4

2.5 (750) 3.9 (1200) 5.6 (1700) 7.2 (2200) 8.5 (2600)

7.2 (2.2) 12.7 (3.9) 18.8 (5.7) 22.9 (6.9) 33.4 (10.2)

3/ 4

3/ 4

3/ 4

3/ 4

Model

Description

KFB-SP-01A or KFB-SP-01AB

KF: Kofulso (Manufacturer's initials)

B: Braided hose SP: Flexible 01 in. = 02 in. = 03 in. = 04 in. = 05 in. = Hose Lengths: 2.5 ft (750 mm) 3.9 ft (1200 mm) 5.6 ft (1700 mm) 7.2 ft (2200 mm) 8.5 ft (2600 mm)

A: 1/2 in. NPT AB: 3/4 in. NPT

Panew Company Limited, 8F-5, No. 2 Jianba Road, Chung Ho, Taipei Hsien, Taiwan ROC

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9100 P-9100 P-9100

2 (0.61) 4 (1.22) 6 (1.83)

10.4 (3.2) 14.5 (4.4) 18.6 (5.7)

1/ 2

1/ 2

FM Approvals

1-82

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model

NPT in.

1/ 2

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9100

7 (2.13)

20.4 (6.2)

Model P-9100. 1 in. nominal dia. Two piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings. The sprinkler adapter is threaded to the flexible hose. Approval is limited for use in commercial suspended ceilings with a ceiling sprinkler system manufactured by Panew Company Limited.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalentdc Length of 1 in. Schedule 40 Pipe, ft (m)

P-9120 P-9120 P-9120 P-9120

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

6.5 (1.9) 15.9 (4.8) 23.1 (7.1) 26.2 (8.0)

1/ 2

1/ 2

1/ 2

Model P-9120. 1 in. nominal dia. One piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings. The sprinkler adapter and nipple is welded to the flexible hose. Approval is limited for use in commercial suspended ceilings with a ceiling sprinkler system manufactured by Panew Company Limited.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9200 P-9200 P-9200 P-9200

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

6.5 (1.9) 15.9 (4.8) 23.1 (7.1) 26.2 (8.0)

1/ 2

1/ 2

1/ 2

Model P-9200. 1 in. nominal dia. One piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings. The sprinkler adapter and nipple is welded to the flexible hose. Approval is limited for use in commercial suspended ceilings with a ceiling sprinkler system manufactured by Panew Company Limited.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9210 P-9210 P-9210 P-9210

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

6.5 (1.9) 15.9 (4.8) 23.1 (7.1) 26.2 (8.0)

1/ 2

1/ 2

1/ 2

Model P-9210. 1 in. nominal dia. One piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings. The sprinkler adapter and coupling/threaded fitting is welded to the flexible hose. Approval is limited for use in commercial suspended ceilings with a ceiling sprinkler system manufactured by Panew Company Limited.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9211 P-9211 P-9211 P-9211

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

6.5 (1.9) 15.9 (4.8) 23.1 (7.1) 26.2 (8.0)

1/ 2

1/ 2

1/ 2

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-83

Model P-9211. 1 in. nominal dia. One piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings. The sprinkler adapter and coupling/threaded fitting is welded to the flexible hose. Approval is limited for use in commercial suspended ceilings with a ceiling sprinkler system manufactured by Panew Company Limited.

Paradise Industry Co Ltd, 65-2 Chooneui-Dong, Woonmi-Ku, Bucheon-City Kyunggi-Do, Korea (420-120)

Model SFT-A. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is in the range of 3.3 ft (1000 mm) to 8.4 ft (2550 mm), and is limited for use in commercial suspended ceilings. Model SFT-C. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is in the range of 3.3 ft (1000 mm) to 8.1 ft (2470 mm), and is limited for use in commercial suspended ceilings.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SFT-A SFT-A SFT-C SFT-C

3.3 (1.0) 8.4 (2.55) 3.3 (1.0) 8.1 (2.47)

6.1 (1.8) 14.9 (4.5) 5.9 (1.8) 14.6 (4.5)

1/ 2

1/ 2

1/ 2

Approval is limited for use in commercial suspended ceilings, with a ceiling bracket system manufactured by Paradise Industry Co., Ltd.

Rapidrop Limited, Rutland Business Park, Newark Road, Peterborough PE1 5WA, United Kingdom

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

Rapidrop® -SPB-01A-NPT Rapidrop® -SPB-02A-NPT Rapidrop® -SPB-03A-NPT Rapidrop® -SPB-04A-NPT Rapidrop® -SPB-05A-NPT

2.5 (0.7) 4 (1.2) 5 (1.5) 6.2 (1.8) 8.3 (2.5)

14.6 (4.5) 28.0 (8.5) 50.2 (15.3) 53.5 (16.3) 67.1 (20.4)

1/ 2

1/ 2

1/ 2

1/ 2

Rapidrop® -SPNB-01A-NPT Rapidrop® -SPNB-02A-NPT Rapidrop® -SPNB-03A-NPT Rapidrop® -SPNB-04A-NPT Rapidrop® -SPNB-05A-NPT

1/ 2

2.5 (0.7) 4 (1.2) 5 (1.5) 6.2 (1.8) 8.3 (2.5)

14.6 (4.5) 28.0 (8.5) 50.2 (15.3) 53.5 (16.3) 67.1 (20.4)

1/ 2

1/ 2

1/ 2

1/ 2

Rapidrop® -SPWB-01A-NPT Rapidrop® -SPWB-02A-NPT Rapidrop® -SPWB-03A-NPT Rapidrop® -SPWB-04A-NPT Rapidrop® -SPWB-05A-NPT

1/ 2

2.5 (0.7) 4 (1.2) 5 (1.5) 6.2 (1.8) 8.3 (2.5)

14.6 (4.5) 28.0 (8.5) 50.2 (15.3) 53.5 (16.3) 67.1 (20.4)

1/ 2

1/ 2

1/ 2

1/ 2

Rapidrop® -SPB-01B-NPT Rapidrop® -SPB-02B-NPT Rapidrop® -SPB-03B-NPT

3/ 4

2.5 (0.7) 4 (1.2) 5 (1.5)

20.7 (6.3) 32.1 (9.8) 48.4 (14.7)

3/ 4

3/ 4

FM Approvals

1-84

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model

NPT in.

3/ 4

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

Rapidrop® -SPB-04B-NPT Rapidrop® -SPB-05B-NPT

6.2 (1.8) 8.3 (2.5)

56.6 (17.2) 77.1 (23.5)

3/ 4

Rapidrop® -SPNB-01B-NPT Rapidrop® -SPNB-02B-NPT Rapidrop® -SPNB-03B-NPT Rapidrop® -SPNB-04B-NPT Rapidrop® -SPNB-05B-NPT

3/ 4

2.5 (0.7) 4 (1.2) 5 (1.5) 6.2 (1.8) 8.3 (2.5)

20.7 (6.3) 32.1 (9.8) 48.4 (14.7) 56.6 (17.2) 77.1 (23.5)

3/ 4

3/ 4

3/ 4

3/ 4

Rapidrop® -SPWB-01B-NPT Rapidrop® -SPWB-02B-NPT Rapidrop® -SPWB-03B-NPT Rapidrop® -SPWB-04B-NPT Rapidrop® -SPWB-05B-NPT

3/ 4

2.5 (0.7) 4 (1.2) 5 (1.5) 6.2 (1.8) 8.3 (2.5)

20.7 (6.3) 32.1 (9.8) 48.4 (14.7) 56.6 (17.2) 77.1 (23.5)

3/ 4

3/ 4

3/ 4

3/ 4

1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is limited for use in commercial suspended ceilings. Approval is limited for use in commercial suspended ceilings with a bracket system manufactured by Rapidrop Limited. The code of information for these model designations is as follows: Marking Rapidrop® SPB SPNB SPWB 01 02 03 04 05 A B Description Company Name & Trademark The hose is threaded to a nipple on the inlet end and threaded to a reducer at the outlet. The hose is threaded to a nipple on the inlet end and the reducer is brazed to the flexible hose at the outlet The hose is brazed to a nipple on the inlet end and brazed to a reducer at the outlet Flexible Hose Lengths: 01 = 780 mm 02 = 1,220 mm 03 = 1,540 mm 04 = 1,880 mm 05 = 2,500 mm

1/ 2 3/ 4

in. NPT in. NPT

Seung Jin Industry Co Ltd, 612, 5 Bar Shi-Wha Industrial Complex, 685-11 Sunggog-Dong, Ansan-Si Kyunggi-Do, 429-450 Korea

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CCBUXX-YYYY CCBUXX-YYYY CCBUXX-YYYY CCBUXX-YYYY CCXX-YYYY CCXX-YYYY

2.6 (0.8) 8.5 (2.6) 2.6 (0.8) 8.5 (2.6) 2.6 (0.8) 8.5 (2.6)

8.3 (2.6) 31.8 (9.7) 7.6 (2.3) 31.4 (9.6) 8.3 (2.6) 31.8 (9.7)

1/ 2

3/ 4

3/ 4

1/ 2

1/ 2

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-85

Model

NPT in.

3/ 4

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

CCXX-YYYY CCXX-YYYY

2.6 (0.8) 8.5 (2.6)

7.6 (2.3) 31.4 (9.6)

3/ 4

CC: Commercial Ceiling BU: Bushing Type XX: Product length. 08 through 26 (08 is a 0.8 m (2.6 ft) long hose assembly and 26 is a 2.6 m (8.5 ft) long hose assembly. YYYY: Year and month manufactured.

Approval of these 1 in. nominal dia. flexible metal sprinkler hose models is limited to use in providing sprinkler protection to commercial suspended ceilings. Approval is limited for use in commercial suspended ceilings with a ceiling sprinkler system manufactured by Seung Jin Industry Co., Ltd.

Shanghai Genius Technical Corp Ltd, No. 7166 Zhong Chun Road, Qibao Town, Minhang District, Shanghai, P.R. China 201101

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9100 P-9100 P-9100 P-9100

2 (0.61) 4 (1.22) 6 (1.83) 7 (2.13)

10.4 (3.2) 14.5 (4.4) 18.6 (5.7) 20.4 (6.2)

1/ 2

1/ 2

1/ 2

Model P-9100. 1 in. nominal dia. two piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings. The sprinkler adapter is threaded to the flexible hose. Approval is limited for use in commercial suspended ceilings with a ceiling sprinkler system manufactured by Shanghai Genius Technical Corp., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9120 P-9120 P-9120 P-9120

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

6.5 (1.9) 15.9 (4.8) 23.1 (7.1) 26.2 (8.0)

1/ 2

1/ 2

1/ 2

Model P-9120. 1 in. nominal dia. one piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings. The sprinkler adapter and nipple is welded to the flexible hose. Approval is limited for use in commercial suspended ceilings with a ceiling sprinkler system manufactured by Shanghai Genius Technical Corp., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9200 P-9200 P-9200 P-9200

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

6.5 (1.9) 15.9 (4.8) 23.1 (7.1) 26.2 (8.0)

1/ 2

1/ 2

1/ 2

Model P-9200. 1 in. nominal dia. one piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings. The sprinkler adapter and nipple is welded to the flexible hose. Approval is limited for use in commercial suspended ceilings with a ceiling sprinkler system manufactured by Shanghai Genius Technical Corp., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9210

2 (0.6)

6.5 (1.9)

FM Approvals

1-86

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model

NPT in.

1/ 2

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9210 P-9210 P-9210

4 (1.2) 6 (1.8) 7 (2.1)

15.9 (4.8) 23.1 (7.1) 26.2 (8.0)

1/ 2

1/ 2

Model P-9210. 1 in. nominal dia. one piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings. The sprinkler adapter and coupling/threaded fitting is welded to the flexible hose. Approval is limited for use in commercial suspended ceilings with a ceiling sprinkler system manufactured by Shanghai Genius Technical Corp., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

P-9211 P-9211 P-9211 P-9211

2 (0.6) 4 (1.2) 6 (1.8) 7 (2.1)

6.5 (1.9) 15.9 (4.8) 23.1 (7.1) 26.2 (8.0)

1/ 2

1/ 2

1/ 2

Model P-9211. 1 in. nominal dia. one piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings. The sprinkler adapter and coupling/threaded fitting is welded to the flexible hose. Approval is limited for use in commercial suspended ceilings with a ceiling sprinkler system manufactured by Shanghai Genius Technical Corp., Ltd.

Super Flex Enterprises Co Ltd, No. 16, Lane 561, Sec. 2, Kouji Rd., Taoyuan City, Taoyuan, Taiwan, R.O.C.

NPT in.

1/ 2

Model

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

SP-A SP-A SP-A SP-A SP-A

1.9 (0.6) 2.9 (0.9) 3.9 (1.2) 4.9 (1.5) 5.9 (1.8)

4.4 (1.4) 5.9 (1.9) 8.2 (2.6) 10.1 (3.2) 12.1 (3.7)

1/ 2

1/ 2

1/ 2

1/ 2

The model SP-A has a pressure rating of 230 psi (1585 kPa). 1 in. nominal diameter flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is limited for use in commercial suspended ceilings with a bracket system manufactured by Super Flex Enterprises Co., Ltd.

Virotec Rohrtechnik GmbH & Co KG, Meininger Weg 8, D-36132 Eiterfeld Germany

Model Designation NPT in.

1/ 2

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

VX-W-27-21-R-10 VX-W-27-21-NPT-10 VX-W-27-21-R-15 VX-W-27-21-NPT-15 VX-W-27-21-R-20 VX-W-27-21-NPT-20 VX-W-27-21-R-25 VX-W-27-21-NPT-25 VX-W-34-21-R-10 VX-W-34-21-NPT-10 VX-W-34-21-R-15 VX-W-34-21-NPT-15 VX-W-34-21-R-20 VX-W-34-21-NPT-20

3.3 (1.0) 4.9 (1.5) 6.6 (2.0) 8.2 (2.5) 3.3 (1.0) 4.9 (1.5) 6.6 (2.0)

6.8 (2.1) 9.0 (2.7) 10.0 (3.0) 15.2 (4.6) 6.8 (2.1) 9.0 (2.7) 10.0 (3.0)

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-87

Model Designation

NPT in.

1/ 2

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

VX-W-34-21-R-25 VX-W-34-21-NPT-25 VX-W-34-27-R-10 VX-W-34-27-NPT-10 VX-W-34-27-R-15 VX-W-34-27-NPT-15 VX-W-34-27-R-20 VX-W-34-27-NPT-20 VX-W-34-27-R-25 VX-W-34-27-NPT-25 VX-SW-27-21-R-10 VX-SW-27-21-NPT-10 VX-SW-27-21-R-15 VX-SW-27-21-NPT-15 VX-SW-27-21-R-20 VX-SW-27-21-NPT-20 VX-SW-27-21-R-25 VX-SW-27-21-NPT-25 VX-SW-27-21-90-R-10 VX-SW-27-21-90-NPT-10 VX-SW-27-21-90-R-15 VX-SW-27-21-90-NPT-15 VX-SW-27-21-90-R-20 VX-SW-27-21-90-NPT-20 VX-SW-27-21-90-R-25 VX-SW-27-21-90-NPT-25 VX-SW-27-27-R-10 VX-SW-27-27-NPT-10 VX-SW-27-27-R-15 VX-SW-27-27-NPT-15 VX-SW-27-27-R-20 VX-SW-27-27-NPT-20 VX-SW-27-27-R-25 VX-SW-27-27-NPT-25 VX-SW-27-27i-R-10 VX-SW-27-27i-NPT-10 VX-SW-27-27i-R-15 VX-SW-27-27i-NPT-15 VX-SW-27-27i-R-20 VX-SW-27-27i-NPT-20 VX-SW-27-27i-R-25 VX-SW-27-27i-NPT-25 VX-SW-34-21-R-10 VX-SW-34-21-NPT-10 VX-SW-34-21-R-15 VX-SW-34-21-NPT-15 VX-SW-34-21-R-20 VX-SW-34-21-NPT-20 VX-SW-34-21-R-25 VX-SW-34-21-NPT-25 VX-SW-34-21-90-R-10 VX-SW-34-21-90-NPT-10 VX-SW-34-21-90-R-15 VX-SW-34-21-90-NPT-15 VX-SW-34-21-90-R-20 VX-SW-34-21-90-NPT-20 VX-SW-34-21-90-R-25 VX-SW-34-21-90-NPT-25 VX-SW-34-27-R-10 VX-SW-34-27-NPT-10 VX-SW-34-27-R-15 VX-SW-34-27-NPT-15 VX-SW-34-27-R-20 VX-SW-34-27-NPT-20

8.2 (2.5) 3.3 (1.0) 4.9 (1.5) 6.6 (2.0) 8.2 (2.5) 3.3 (1.0) 4.9 (1.5) 6.6 (2.0) 8.2 (2.5) 3.3 (1.0) 4.9 (1.5) 6.6 (2.0) 8.2 (2.5) 3.3 (1.0) 4.9 (1.5) 6.6 (2.0) 8.2 (2.5) 3.3 (1.0) 4.9 (1.5) 6.6 (2.0) 8.2 (2.5) 3.3 (1.0) 4.9 (1.5) 6.6 (2.0) 8.2 (2.5) 3.3 (1.0) 4.9 (1.5) 6.6 (2.0) 8.2 (2.5) 3.3 (1.0) 4.9 (1.5) 6.6 (2.0)

15.2 (4.6) 8.2 (2.5) 11.9 (3.6) 13.6 (4.1) 19.0 (5.8) 6.8 (2.1) 9.0 (2.7) 10.0 (3.0) 15.2 (4.6) 6.8 (2.1) 9.0 (2.7) 10.0 (3.0) 17.8 (5.4) 8.2 (2.5) 11.9 (3.6) 13.6 (4.1) 19.0 (5.8) 8.2 (2.5) 11.9 (3.6) 13.6 (4.1) 19.0 (5.8) 6.8 (2.1) 9.0 (2.7) 10.0 (3.0) 15.2 (4.6) 6.8 (2.1) 9.0 (2.7) 10.0 (3.0) 17.8 (5.4) 8.2 (2.5) 11.9 (3.6) 13.6 (4.1)

3/ 4

3/ 4

3/ 4

3/ 4

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

3/ 4

3/ 4

3/ 4

FM Approvals

1-88

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model Designation

NPT in.

3/ 4

Hose Assembly length, ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

VX-SW-34-27-R-25 VX-SW-34-27-NPT-25 VX-SW-34-27-90-R-10 VX-SW-34-27-90-NPT-10 VX-SW-34-27-90-R-15 VX-SW-34-27-90-NPT-15 VX-SW-34-27-90-R-20 VX-SW-34-27-90-NPT-20 VX-SW-34-27-90-R-25 VX-SW-34-27-90-NPT-25 VX-SW-34-34-R-10 VX-SW-34-34-NPT-10 VX-SW-34-34-R-15 VX-SW-34-34-NPT-15 VX-SW-34-34-R-20 VX-SW-34-34-NPT-20 VX-SW-34-34-R-25 VX-SW-34-34-NPT-25 VX-SW-34-34i-R-10 VX-SW-34-34i-NPT-10 VX-SW-34-34i-R-15 VX-SW-34-34i-NPT-15 VX-SW-34-34i-R-20 VX-SW-34-34i-NPT-20 VX-SW-34-34i-R-25 VX-SW-34-34i-NPT-25

8.2 (2.5) 3.3 (1.0) 4.9 (1.5) 6.6 (2.0) 8.2 (2.5) 3.3 (1.0) 4.9 (1.5) 6.6 (2.0) 8.2 (2.5) 3.3 (1.0) 4.9 (1.5) 6.6 (2.0) 8.2 (2.5)

19.0 (5.8) 8.2 (2.5) 11.9 (3.6) 13.6 (4.1) 17.3 (5.3) 6.8 (2.1) 9.0 (2.7) 10.0 (3.0) 15.2 (4.6) 6.8 (2.1) 9.0 (2.7) 10.0 (3.0) 15.2 (4.6)

3/ 4

3/ 4

3/ 4

3/ 4

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1/ 2

1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is limited for use in commercial suspended ceilings with a bracket system manufactured by Virotec Rohrtechnik GmbH & Co. KG.

Yong Won E.N.C. Ltd, 116-1 Seogu-Ri, Kwangjeuk-Myun, Yangju-Gun Keungki-Do, Korea

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

YB25 YB25 YB28 YB28 YB28 YB28

2.2 (0.7) 8.2 (2.5) 2.2 (0.7) 8.4 (2.6) 2.2 (0.7) 8.4 (2.6)

18.6 (5.7) 91.5 (27.8) 5.5 (1.6) 15.2 (4.6) 5.7 (1.6) 17.0 (5.2)

1/ 2

1/ 2

1/ 2

3/ 4

3/ 4

Model YB25 and YB28. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial ceilings. Available in a range from 2.2 to 8.4 ft (700 mm to 2600 mm). Approval is limited for use in commercial suspended ceilings with a ceiling bracket system manufactured by Yong Won E.N.C., Ltd. These models are available as a two piece style and three piece style. The two piece style, the reducer is welded to the flexible hose and the nipple is connected to the flexible hose using a nut. The three piece style, the reducer and nipple is threaded to the flexible hose.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

YB28 A Type YB28 A Type YB28 A Type YB28 A Type

3.5 (1.07) 8.4 (2.57) 3.5 (1.07) 8.4 (2.57)

5.5 (1.6) 15.2 (4.6) 5.7 (1.7) 17.0 (5.2)

1/ 2

3/ 4

3/ 4

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-89

Model: YB28 A Type. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial ceilings. Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). This model is a one piece style as the reducer and nipple are welded to the flexible hose. Approval is limited for use in a wood tile ceiling. The tile size is 11.5 × 11.5 × 1 in. (292 × 292 × 25 mm) with a ceiling bracket system manufactured by Yong Won E.N.C., Ltd.

NPT in.

1/ 2

Model

Hose Assembly length ft (m)

Equivalent Length of 1 in. Schedule 40 Pipe, ft (m)

YB28 B Type YB28 B Type YB28 B Type YB28 B Type

3.5 (1.07) 8.4 (2.57) 3.5 (1.07) 8.4 (2.57)

5.5 (1.6) 15.2 (4.6) 5.7 (1.7) 17.0 (5.2)

1/ 2

3/ 4

3/ 4

Model: YB28 B Type. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial ceilings. Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). This model is a one piece style as the reducer and nipple are welded to the flexible hose. Approval is limited for use in a S.G.P Ceiling (metal panel). The tile size is 11.75 × 11.75 × 15/8 in. (300 × 300 × 41.3 mm), with a ceiling bracket system manufactured by Yong Won E.N.C., Ltd.

ADJUSTABLE SPRINKLER FITTINGS

Adjustable fittings are designed for use on wet-pipe pendent-sprinkler drop-pipes. They allow the sprinkler contractor, after the suspended ceiling has been installed, to adjust the drop to the desired length without cutting the pipe.

Allied Piping Products Inc, 500 Ternes Drive, Monroe MI 48162

Product Designation Min Length, in. (mm) Max Length, in. (mm)

100 125* 300*

*Models 125 and 300 have a 300 psi (2070 kPa) rated working pressure.

57/8 (149) 421/64 (110) 537/64 (142)

83/4 (222) 513/16 (148) 825/64 (213)

Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446

Product Designation Min Length, in. (mm) Max Length, in. (mm)

Short Alpha* Long Alpha*

*Fittings have a 250 psi (1725 kPa) rated working pressure.

41/4 (108) 51/2 (140)

6 (152) 83/8 (213)

Merit Manufacturing, Division of Anvil International Inc, 110 Corporate Dr, Suite 10, Portsmouth NH 03801

Product Designation

1/ 2

Min Length, in. (mm)

Max Length, in. (mm)

in. NPT Outlet* 41/8 (105) 6 1/ 8 (156) 3 1/ 2 (89) 4 1/ 2 (114) 5 1/ 2 (140) 7 7/ 8 (200) 51/8 (131) 91/8 (232) 41/2 (114) 61/2 (165) 81/2 (216) 107/8 (276)

M1.150 M3.150 F1.150 F2.150 F3.150 ME3.150

3/ 4

in. NPT Outlet* 8.0 (203) 31/4 (83) 11.0 (280) 41/4 (108)

M3.175 F1.175

FM Approvals

1-90

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Min Length, in. (mm)

Max Length, in. (mm)

F3.175 F3.175R

*These fittings have a 300 psi (2070 kPa) rated working pressure.

51/4 (133) 7.35 (187)

81/4 (210) 10.35 (263)

Virotec Rohrtechnik GmbH & Co KG, Meininger Weg 8, D-36132B 36132 Eiterfield, Germany

Product Designation Min Length, in. (mm) Max Length, in. (mm)

VL0.5* VL1.0* VLS0.5 VLS1.0

All fittings have a plain end inlet (branch) and must be threaded in the field.

15.8 (400) 34.7 (880) 15.8 (400) 34.7 (880)

20.5 (520) 39.4 (1000) 19.7 (500) 38.6 (980)

*These fittings are available with either a 3/8, 1/2 or 3/4 in. female NPT outlet sprinkler connection. These fittings are available with either a 3/8 or 1/2 in. female NPT outlet sprinkler connection. Product Designation Min Length, in. (mm) Max Length, in. (mm)

VS 0.1 VS 0.2 VS 0.3* VS 0.4* VS 0.5* VS 1.0*

All fittings have a 360 psi (2482 kPa) rated working pressure. All fittings have a female 1/2 in. NPT outlet sprinkler connection.

3.9 (99) 5.5 (140) 8.6 (218) 11.8 (300) 16.5 (419) 39.0 (991)

6.3 (160) 9.5 (241) 12.6 (320) 15.8 (401) 20.5 (521) 43.0 (1092)

These fittings have a male 1 in. NPT inlet (branch) connection. These fittings have a plain end inlet (branch) and must be threaded in the field. *Minimum length listed is based upon adjustment by screwing of the adjusting tube only. A 6.3 in. (160 mm) minimum length can be obtained on these fittings by cutting the inlet end and tapping a male 1 in. NPT. The VS 0.1 and VS 0.2 cannot be shortened.

FIXED SPRINKLER FITTINGS

Merit Manufacturing, Division of Anvil International Inc, 110 Corporate Dr, Suite 10, Portsmouth NH 03801

Product Designation

1/ 2 3/ 4

Fixed Lengths in in.

Adjustment

in. NPT Outlet* MLX.3-.150 in. NPT Outlet* MLX.3-.175

8, 12, 18, 24, 30, 36 8, 12, 18, 24, 30, 36

3 in. 3 in.

1/ 2

in. NPT Outlet* LN-.150 3/4 in. NPT Outlet* LN-.175

*These fittings have a 300 psi (2070 kPa) rated working pressure.

6, 12, 18, 24, 30, 36 6, 12, 18, 24, 30, 36

These fittings are available with an optional escutcheon plate which can be positioned anywhere on the lower three inches of the fitting, to fit up to a clearance hole in the suspended ceiling. The escutcheon plate is not designed for use with a specific sprinkler, and is not to be fitted to any sprinkler body.

Texas Manufacturing Co, Box 115, Whitesboro TX 76273

Product Designation Fixed Lengths in inches

Model 80 1/2 in. NPT Outlet

4 through 36 inch lengths, in 2 inch increments

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-91

Product Designation

Fixed Lengths in inches

Model 81 3/4 in. NPT Outlet

4 through 36 inch lengths, in 2 inch increments

Model 82 1/2 or 3/4 in. NPT both ends

4 through 36 inch lengths, in 2 inch increments

These fittings have a 300 psi (2070 kPa) rated working pressure.

SPARE SPRINKLER CABINETS

The number of sprinklers carried for replacement should be governed by size of system, time needed to get sprinklers from supplier and number of sprinklers likely to be opened by extraordinary conditions, such as flash fire. Ordinarily, under average conditions, the number of emergency sprinklers should be: 6 for systems not over 300 sprinklers; 12 for systems of 300-1000 sprinklers; 24 for systems above 1000 sprinklers. There should be spare heads of the various temperature ratings used and a wrench for each make of sprinkler.

Globe Pipe Hanger Products Inc, 14601 Industrial Pkwy, Cleveland OH 44135

Cabinet for six automatic sprinklers and sprinkler wrench.

TRIM WATER PRESSURE RELIEF VALVES (FIXED)

A trim water pressure relief valve is a small valve designed to relieve pressure build-up in a sprinkler system or in valve trim. It is open to a drain line. Unless otherwise specified, rated working pressure is 175 psi (1205 kPa) and factory set pressure is 175 psi (1205 kPa).

AGF Mfg Inc, 100 Quaker Lane, Malvern PA 19355

Product Designation Nominal Pipe Size, in. NPT

1/ 2

Pressure Rating psi (kPa)

Remarks

Model M7000 Model M7200

175 (1205) 175 (1205)

­ ­

3/ 4

TRIM WATER PRESSURE RELIEF VALVES (ADJUSTABLE)

An adjustable set pressure trim water pressure relief valve is a small valve designed to relieve pressure build-up in a sprinkler system or in valve trim. It is open to a drain line. Unless otherwise specified, rated working pressure is 175 psi (1205 kPa). The range of pressure setting is shown below.

Cla-Val Canada Corp, 4687 Christie Dr, Beamsville, Ontario L0R 1B4, Canada

Product Designation Nominal Pipe Size Inches, NPT

1/2, 3/4

Pressure Rating psi (kPa)

Remarks

Catalog Number 55L

Remarks:

300 (2070)

a, b, c

a. Valve supplied with Female NPT inlet and outlet connection. b. Adjustable relief pressure settings from 0 to 75, 20 to 200, or 100 to 300 psi (0 to 515, 140 to 1380, or 690 to 2070 kPa). c. Not suitable for discharging the full rated pump capacity.

Cla-Val Co, Box 1325, Newport Beach CA 92659

Product Designation Nominal Pipe Size Inches, NPT

1/2, 3/4

Pressure Rating psi (kPa)

Remarks

Catalog Number 55L

300 (2070)

a, b, c

FM Approvals

1-92

September 2007 -- Approval Guide Automatic Sprinkler Systems

Remarks: a. Valve supplied with Female NPT inlet and outlet connection. b. Adjustable relief pressure settings from 0 to 75, 20 to 200, or 100 to 300 psi (0 to 515, 140 to 1380, or 690 to 2070 kPa). c. Not suitable for discharging the full rated pump capacity.

Edwards Pentair Water, 800 Airport Rd, N Aurora IL 60542

Product Designation Nominal Pipe Size Inches, NPT Pressure Rating psi (kPa) Remarks

Model 20

Remarks:

¾, 1, 1-1/2, 2, 2-1/2

300 (2070)

a, b, c

a. Valve supplied with Female NPT inlet and outlet connection. b. Relief pressure settings of 175, 250, or 300 psi (1205, 1725, or 2070 kPa). c. Not suitable for discharging the full rated pump capacity.

Kunkle Valve, Div of Tyco Valves and Control, 1221 Katherine Street NW, Cullman AL 35055

Product Designation Nominal Pipe Size Inches, NPT

3/ 4

Pressure Rating psi (kPa)

Remarks

Model 918BDD Model 918BDE

Remarks:

300 (2070) 300 (2070)

a, b, c a, b, c

1

a. Valve supplied with Male NPT inlet connection and Female NPT outlet connection. b. Adjustable relief pressure settings from 60 to 125, 126 to 175, or 176 to 250 psi (415 to 860, 870 to 1205, or 1215 to 1725 kPa). c. Not suitable for discharging the full rated pump capacity.

Wilkins Operation, Zurn Industries Inc, 1747 Commerce Way, Paso Robles CA 93446

Product Designation Nominal Pipe Size Inches, NPT

1/2, 3/4

Pressure Rating psi (kPa)

Remarks

Model P4000

Remarks:

300 (2070)

a, b, c

a. Valve supplied with Female NPT inlet and outlet connection. b. Adjustable relief pressure settings from 0 to 75, 20 to 200, or 100 to 300 psi (0 to 515, 140 to 1380, or 690 to 2070 kPa). c. Not suitable for discharging the full rated pump capacity.

SPRINKLER SYSTEM ALARM TESTERS

Each separate sprinkler system must be equipped with a separate waterflow alarm. In a high rise building, the system for each floor must be separately alarmed. Where pressure reducing valves are used, a dual alarm and drain piping arrangement is required. The alarm testers listed below combine test and drain valves, a waterflow sight glass, and a calibrated flow orifice in a single assembly to simplify the piping required for such arrangements.

AGF Mfg Inc, 100 Quaker Lane, Malvern PA 19355

Model 1000 TESTanDRAIN. 1, 11/4, 11/2, 2 in. NPT or 1, 11/4, 11/2, 2 in. BSP. Female threaded connections. 2.8, 5.6, 8.0, 11.0 nominal K-factor. 300 psi (2070 kPa) rated working pressure. For 11/4, 11/2, 2 in. NPT size only, 14.0, 16.8, 22.4, and 25.2 nominal K-factor. 300 psi (2070 kPa) rated working pressure. 1, 11/4, NPT sizes have either a 1/2 or 3/4 in. NPT tapped and plugged outlet in the tailpiece. 11/2 and 2 in. NPT sizes have either a 1/2, 3/4, or 1 in. NPT tapped and plugged outlet in the tailpiece. Model 1011 TESTanDRAIN 1, 11/4,11/2, 2 in. NPT or 1, 11/4, 11/2, 2 in. BSP Female threaded connections. 2.8, 5.6, 8.0, 11.0 nominal K-factor. 300 psi (2070 kPa) rated working pressure. For 11/4, 11/2, 2 in. size only, 14.0, 16.8, 22.4, and 25.2 nominal K-factor. 300 psi (2070 kPa) rated working pressure. 1, 11/4 NPT sizes have either a 1/2 or 3/4 in. NPT tapped and plugged outlet in the tailpiece 11/2, 2 in. NPT size have either a 1/2, 3/4, or 1 in. NPT tapped and plugged outlet in the tailpiece. Model 1200 RemoteTEST style TESTanDRAIN valve with solenoid valve. 1, 11/4,11/2, 2 in. NPT female threaded connections. 2.8, 5.6, and 8.0 nominal K-factor. 300 psi (2070 kPa) rated working pressure. For 11/2 and 2 in. NPT size only, 11.0 nominal K-factor. Solenoid valve rated at 24 V dc only. Model 1500 TESTanDRAIN. 2 in. FNPT or BSP end connections. Ductile Iron Body. 2.8, 5.6, 8.0, 11.0, 14.0, 16.8, 22.4, and 25.2 nominal K-factor. 300 psi (2070 kPa) rated working pressure. Model 1511 TESTanDRAIN. 2 in. FNPT or BSP end connections. Ductile Iron Body. 2.8, 5.6, 8.0, 11.0, 14.0, 16.8, 22.4, and 25.2 nominal K-factor. 300 psi (2070 kPa) rated working pressure. Model 2000 TESTanDRAIN 1 in. NPT female threaded connections. 2.8, 5.6, 8.0, and 11.0 nominal K-factor. 11/4 in. NPT female threaded connections. 2.8, 5.6, 8.0, 11.0, and 14.0 nominal K-factor. 300 psi (2070 kPa) rated working pressure. Model 2500 TESTanDRAIN 1 in. NPT female threaded connections. 2.8, 5.6, 8.0, and 11.0 nominal K-factor. 11/4 in. NPT female threaded connections. 2.8, 5.6, 8.0, 11.0, and 14.0 nominal K-factor. 2 in. FNPT or cut grooved end connections. 2.8, 5.6, 8.0, 11.0, 14.0, 16.8, 22.4, and 25.2 nominal K-factor. 300 psi (2070 kPa) rated working pressure. Model 2511 TESTanDRAIN 1 in. NPT female threaded connections. 2.8, 5.6, 8.0, and 11.0 nominal K-factor. 11/4 in. NPT female threaded connections. 2.8, 5.6, 8.0, 11.0, and 14.0 nominal K-factor. 2 in. FNPT or cut grooved end connections. 2.8, 5.6, 8.0, 11.0, 14.0, 16.8, 22.4, and 25.2 nominal K-factor. 300 psi (2070 kPa) rated working pressure.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-93

GJ Innovations Inc, 1328 Josephine Court, Sebring FL 33875

``Sure-Test.'' 1, 11/4 in. NPT. Female threaded connections. 5.6 nominal K-factor. 175 psi (1205 kPa) rated working pressure.

A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d'Opaglio, Italy

Model A61. 1 and 11/4 NPT female threaded connections. 5.6 nominal K-factor. 175 psi (1205 kPa) rated working pressure.

Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Grinnell or Gem Model F-350. 11/4 in. NPS female threaded connections. 5.6 nominal K-factor. 175 psi (1205 kPa) rated working pressure.

National Fire Fighting Mfg, FZCO, Box 17014, Jebel Ali Free Zone, Dubai, UAE

Model A61. 1 and 11/4 in. NPT female threaded connections. 1/2 in. nominal orifice. 175 psi (1205 kPa) rated working pressure.

Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY, United Kingdom

Model A61. 1 and 11/4 NPT female threaded connections. 1/2 in. nominal orifice. 175 psi (1205 kPa) rated working pressure.

Tyco Fire Products, 3 Tyco Park, Exeter NH 03833

Grinnell or TFP F-350. 1-1/4 in. NPS female threaded connections. 5.6 nominal K-factor. 175psi (1206 kPa) rated working pressure.

Victaulic Company, Box 31, Easton PA 18044

Style 718 TestMaster. 11/4 in. NPT female threaded connections. 2.8, 5.6 and 8.0 nominal K-factor. 300 psi (2070 kPa) rated working pressure on Schedule 10 and 40 pipe. Style 719 TestMaster. 11/4 in. FIT connections for plain-end pipe. 2.8, 5.6 and 8.0 nominal K-factor. 175 psi (1205 kPa) rated working pressure on Allied Tube ``Dyna-Flow'' non-threadable Lightwall pipe, Schedule 10 and 40 pipe. Style 720 TestMaster II. Sizes 1, 11/4, 11/2 and 2 in. NPT female threads, sizes 11/4, 11/2 and 2 in. NPS grooved ends. 1/2 in. and 17/32 in. nominal orifice inserts. 5.6 and 8.0 nominal K-factor. Rated working pressure is 300 psi (2070 kPa). Style 720P TestMaster II. Sizes 1, 11/4, 11/2, and 2 in. NPT female threads. Equipped with a pressure relief valve set for 175 psi (1205 kPa) cracking pressure.

Victaulic-Europe, Neerhonderd 37, Industriepark Kwatrecht, B-9230 Wetteren, Belgium

Style 718 TestMaster. 11/4 in. NPT female threaded connections. 2.8, 5.6 and 8.0 nominal K-factor. 300 psi (2070 kPa) rated working pressure on Schedule 10 and 40 pipe. Style 719 TestMaster. 11/4 in. FIT connections for plain-end pipe. 2.8, 5.6 and 8.0 nominal K-factor. 175 psi (1205 kPa) rated working pressure on Allied Tube ``Dyna-Flow'' non-threadable Lightwall pipe, Schedule 10 and 40 pipe.

RISER MANIFOLD ASSEMBLIES

These devices are intended to replace a field fabricated assembly of components, which normally include a shutoff valve, an orifice made from an open sprinkler head, a sight glass, a water collection wastecone, a vane-type waterflow indicator and interconnecting pipe and fittings. They are usually mounted aboveground and indoors where the water supply enters a building.

AGF Mfg Inc, 100 Quaker Lane, Malvern PA 19355

Model 9000 Floor Control Valve 2 in. FNPT or 21/2 in. cut grooved end connections. Ductile Iron body. 2.8, 5.6, 8.0, 11.0, and 14.0 nominal K-factor. 300 psi (2070 kPa) rated working pressure. 24 Volt dc vane indicator. Manual gear operator with handwheel. Valves are Approved for above ground, indoor use only. The gearbox is available with two supervisory switches.

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Model CR commercial risers are intended for commercial applications in 11/2 through 8 in. nominal sizes. 300 psi (2070 kPa) rating.

Nominal Pipe Size, in. Description

11/2 and 2 2-8

Female by Female Threaded Ends Grooved Inlet and Outlet Ends

Reliable Riser ­ Residential, 175 psi (1205 kPa)

Nominal Pipe Size, in. Description

11/2 2

Female by Female Threaded Ends Female by Female Threaded Ends

Reliable Riser ­ Residential, 175 psi (1205 kPa)

Nominal Pipe Size, in. Description

11/2 2

Female by Female Metric Threaded Ends Female by Female Metric Threaded Ends

Model FCV floor control valves are intended for commercial applications in 11/2 through 8 in. nominal sizes. 300 psi (2070 kPa).

Nominal Pipe Size, in. Description

11/2 and 2 2-8

Female by Female Threaded Ends Grooved Inlet and Outlet Ends

FM Approvals

1-94

September 2007 -- Approval Guide Automatic Sprinkler Systems

Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446

Model 513 is intended for commercial applications in 11/2 through 6 in. nominal sizes.

Nominal Pipe Size, in. Description

11/2 1 1/ 2 2-6

Male Threaded Inlet and Female Threaded Outlet Male Threaded Inlet and Male Threaded Outlet Grooved Inlet and Outlet

Model 513D is intended for residential applications in 1 through 2 in. sizes.

1 1 1/ 2 1 1/ 2 2 2 Female by Female Threaded Ends Male by Female Threaded Ends Male by Male Threaded Ends Grooved Ends Male Thread by Grooved Ends

Model 513R is intended for residential applications in 11/2 through 2 in. sizes.

11/2 1 1/ 2 2 2 Male by Female Threaded Ends Male by Male Threaded Ends Grooved ends Male thread by grooved ends

Victaulic Company, Box 31, Easton PA 18044

Style 747P Riser Manifold assembly in sizes 2, 3, 4, and 6 in. NPS. 175 psi (1208 kPa) rated working pressure. Manifold has standard rolled-grooved inlet and outlet. Equipped with the Style 720P TestMaster II, with female NPT threaded end connections, with a pressure relief valve set for 175 psi (1208 kPa) cracking pressure. Style 747 Riser Manifold assembly in sizes 2, 21/2, 3, 4, and 6 in. NPS. 300 psi (2070 kPa) rated working pressure. Manifold has standard rolled-grooved inlet and outlet. Equipped with the Style 720 TestMaster II Alarm Tester with grooved ends, a vane type flow indicator, and a pressure gage and gage valve.

BRANCH LINE TESTERS

Line testers are installed on sprinkler system branch lines between the last sprinkler and its fitting. Opening a side outlet allows water to flow through the tester. This simplifies and reduces the cost of testing and flushing system branch lines.

AGF Mfg Inc, 100 Quaker Lane, Malvern PA 19355

Branch Line Tester. Model 3011. 1 in. female pipe thread end connections. 300 psi (2070 kPa) rated pressure. Available with 3/8, 1/2 and 17/32 nominal sizes orifice. Available with lever handle or tee handle.

A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d'Opaglio, Italy

Line Tester. Model A59. 1 in. female pipe thread.

WATERFLOW ALARM VALVES

Waterflow alarm valves (alarm check valves) are installed in either vertical or horizontal positions in wetpipe sprinkler systems to sound a fire alarm gong when a flow of water from the system equals or exceeds that of a single sprinkler. They are designed for use with hydraulic or electric gongs or both. There are two designs, the differential type and the pilot valve type. The differential type has a rubber-faced clapper with an annular groove in the seat; the pilot valve type has a metal-faced clapper with a pilot valve attached to the clapper arm. A retard chamber, which minimizes false alarms due to surges and fluctuations in water supply pressure, may be supplied with the alarm valve. If a retard chamber is supplied, only the listed chamber for a specific manufacturer and valve model shall be used. Alarm valves are FM Approved with specific trim, and no substitutes or omissions in part or in full are allowed. Alarms are tested by flowing water through the system test pipe. Pilot valves may be field-adjusted to assure alarm reliability. Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.

Anber Globe SA, Av de Las Flores 13, Parque Ind El Molino, 28970 Humanes de Madrid, Madrid Spain

Model No. Product Type Nominal Pipe Size, in. Rated Working Pressure, psi (kPa) Remarks

H-1 H-2 H-3

Flange Inlet × Flange Outlet Grooved Inlet × Grooved Outlet Flange Inlet × Groove Outlet

3, 4, 6 3, 4 3, 4, 6

175 (1205) 175 (1205) 175 (1205)

a, b, c b, c a, b, c

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-95

Remarks: a. Available in ANSI and ISO flange patterns. b. FM Approved for horizontal and vertical installations in 3 in. NPS only. c. FM Approved for use with Model H retard chamber.

Model E. 21/2 in. and 65 mm. Model E-1 retard chamber. All valves available with flanged connections. Standard size valves painted black or gray. Metric size valves painted blue. Model E. 21/2 in. and 65 mm. Model E-1 retard chamber and E3 trim package. All valves available with flanged connections. Standard size valves painted black or gray. Metric size valves painted red (when supplied with ISO threads in valve trim). NOTE: The placement of a test and drain valve (E3 trim option) in lieu of the 2'' (50 mm) drain valve does not replace the need for an inspector's test connection at the most remote location of the sprinkler system. The test and drain valve shall not be used in lieu of the inspector's test connection for the testing of the entire wet piping system. The test and drain valve shall only be used to exercise the clapper and check the mechanical alarm (water motor gong).

Angus Fire Sprinklers, Thame Park Rd, Oxfordshire OX9 3RT United Kingdom

End Connections Inlet x Outlet Nominal Valve Size, NPS Max Rated Working Pressure, psi (kPa)

Product Description

Remarks

Model C-1 Model C-1 Model C-1 Model C-1 Model C-1 Model C1-H

Remarks:

Flange x Flange Flange x Grooved Grooved x Grooved Flange x Flange Flange x Grooved Flange x Flange

4 in. (100 mm) 4 in. (100 mm) 4 in. (100 mm) 6, 8 in. (150, 200 mm) 6 in. (150 mm) 4 in. (100 mm)

290 (2000) 290 (2000) 290 (2000) 175 (1205) 175 (1205) 290 (2000)

a, b a, b a, b a, b a, b a, c

a. No retard chamber supplied. b. Limited to installation in vertical risers at locations having constant water supply pressures. c. Limited to horizontal installation at locations having constant water supply pressures.

Calanbau Brandschutzanlagen GmbH, Wenderter Strasse 12, D-31157 Sarstedt, Germany

Model NMX 80, 100, 150, 200 mm. Available with flanged inlet and outlet connections or flanged inlet and cut-grooved outlet connections. With Model NAV retard chamber.

GW Sprinkler A/S, Kastanievej 15, DK-5620 Glamsbjerg, Denmark

Product Description End Connections Inlet × Outlet Nominal Valve Size, NPS Max Rated Working Pressure, psi (kPa)

Remarks

Model E Model C-1 Model C-1 Model C-1 Model C-1 Model C-1 Model C1-H

Remarks: a. b. c. d.

Flange × Flange Flange × Flange Flange × Grooved Grooved × Grooved Flange × Flange Flange × Grooved Flange × Flange

3, 4, 6, 8 in. (80, 100, 150, 200 mm) 4 in. (100 mm) 4 in. (100 mm) 4 in. (100 mm) 6, 8 in. (150, 200 mm) 6 in. (150 mm) 3, 4 in. (80, 100 mm)

175 (1205) 290 (2000) 290 (2000) 290 (2000) 175 (1205) 175 (1205) 290 (2000)

a b, c b, c b, c b, c b, c b, d

FM Approved for use with Model E-1 retard chamber. No retard chamber supplied. Limited to installation in vertical risers at locations having constant water supply pressures. Limited to horizontal installation at locations having constant water supply pressures.

Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658

Models B, G-2. 4, 6, 8 in. NPS. Model J-1. 4, 6 in. Model J-2. 4, 6 in. Cut grooved inlet and outlet. Model H-1. 4, 6 in. Flanged inlet and outlet connections. Model H-1. 8 in. Flanged inlet and outlet connections. Vertical installation only. Model H-2. 4 in. Cut-grooved inlet and outlet connections.

FM Approvals

1-96

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model H-3. 4, 6 in. Flanged inlet to cut-grooved outlet. Model H-3. 8 in. Flanged inlet and outlet connections. Vertical installation only. Model H. 8 in. Flanged inlet and outlet connections. With ``Automatic'' Model B retard chamber. Limited to installation in vertical risers only. Models H-1, H-2, H-3, J-1, J-2. With Model B or H retard chamber. Models J-1 and J-2 limited to installation in vertical risers only. Model G. 3, 8 in. With Model E retard chamber. Limited to installation in vertical risers only.

Jomos Brandschutz AG, Sagmattstrasse 5, CH-4710 Balsthal, Switzerland

Model NMX 80, 100, 150, 200 mm. Available with flanged inlet and outlet connections or flanged inlet and cut-grooved outlet connections. With or without retard chamber. Available with or without DirectAlarm trimming (alarm testing without drawing water from sprinkler system pipework). NOTE: The placement of a test and drain valve in the valve trim does not eliminate the need for an inspector's test connection at the most remote location of the sprinkler system.

Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840 Bad Oldesloe, Germany

Product Designation Description Nominal Pipe Size, in. (mm) Max Working Pressure, psi (kPa) Remarks

Model NMX

a. Resilient seat. b. With Model NAV retard chamber.

Flanged by Flanged or Flanged by Grooved

3, 4, 6, 8 (80, 100, 150, 200)

175 (1205)

a, b

Paradise Industry Co Ltd, Plant 65-2 Chooneui-Dong, Woonmi-Ku, Bucheon City, Kyunggi-Do, Korea (420-120)

Model FAVB Water Flow Alarm Valves in sizes 100 and 150 mm NPS. Flanged inlet and outlet connections, ANSI or Korean Standard with others available. Suitable for vertical installation. Supplied with retard chamber.

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Model E. 21/2, 3, 4, 6, 8 in.; 65, 100, 150, 200 mm. Model E-1 retard chamber. All valves available with flanged connections. 3, 4, 6, 8 in. sizes also available with grooved outlets. Standard size valves painted black or gray. Metric size valves painted blue. Model E. 21/2, 3, 4, 6, 8 in., and 65, 100, 150, 200 mm. Model E-1 retard chamber and E3 trim package. All valves available with flanged connections. 3, 4, 6, 8 in. sizes also available with grooved outlets. Standard size valves painted black or gray. Metric size valves painted red (when supplied with ISO threads in valve trim). NOTE: The placement of a test and drain valve (E3 Trim option) in lieu of the 2'' (50mm) drain valve does not replace the need for an inspector's test connection at the most remote location of the sprinkler system. The test and drain valve shall not be used in lieu of the inspector's test connection for the testing of the entire wet piping system. The test and drain valve shall only be used to exercise the clapper and check the mechanical alarm (water motor gong). Model E3. 4, 6, and 8 in., and 100, 165, 200 mm Model E-1 retard chamber, and E3 trim package. Valves are available with cut grooved inlet and outlet end connections, with a 300 psi (2070 kPa) maximum pressure rating. Standard size valves are painted black or red (when supplied with ISO threads in valve trim). Valves are considered FM Approved for horizontal and vertical installations. NOTE: The placement of a test and drain valve (E3 Trim option) in lieu of the 2'' (50 mm) drain valve does not replace the need for an inspector's test connection at the most remote location of the sprinkler system. The test and drain valve shall not be used in lieu of the inspector's test connection for the testing of the entire wet piping system. The test and drain valve shall only be used to exercise the clapper and check the mechanical alarm (water motor gong).

Rolland Arroseurs Sprinklers, Ste Rolland/Usine, 73410 Mognard, France

Model B. 3, 4, 6, 8 in. With Model E retard chamber. Limited to installations in vertical risers only. Flanged inlet and outlet connections. Model D. 3, 4, 6, 8 in. With Model E retard chamber. Limited to installations in vertical risers only. Flanged inlet to cut-grooved outlet. Astra Model E. 4, 6 in. with Model E retard chamber. Limited to installations with vertical risers only. Cut grooved inlet and outlet connections.

Shanghai Jindun Fire-Fighting Security Service Co Ltd, 65# Henqiao Road Fanrong Industrial Area Zhoupu, Pudong, Shanghai, 201318, Peoples' Republic of China

Model Number Product Type Nominal Pipe Size, Inch Rated Working Pressure, psi (kPa) Remarks

ZSFZ

Remarks:

Flange Inlet × Flange Outlet

4, 6, 8

232 (1600)

a, b

a. Available in ISO flange patterns only. b. Approved for use with Model ZSFZ retard chamber.

Tecnicas e Ingenieria de Proteccion SA (TIPSA), Apartado de Correos 293, 08720 Vilafranca del Penedes, Barcelona Spain

Model Number End Connections Inlet × Outlet Nominal Valve Size, NPS Rated Working Pressure, psi (kPa) Remarks

P3 P4

Remarks:

Flange × Flange DN 80 Flange × Flange DN 100

80 (3) 100 (4)

12.5 (181) 12.5 (181)

a, b, c a, b, c

a. Available in ISO flange patterns. b. FM Approved vertical installations. c. FM Approved for use with Model T retard chamber.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-97

Total Walther GmbH, Feuerschutz und Sicherheit, Waltherstrasse 51, 51069 Koln, Germany ¨

Model NV 100/3. 100 mm. Model NV 150/3. 150 mm. Model NV 200/3. 200 mm. The above are limited to installation at locations having constant water supply pressures. Model NV 200. 8 in. NPS.

Tyco Fire Products, 451 N Cannon Ave, Lansdale PA 19446

End Connections Inlet x Outlet Nominal Valve Size, NPS in. (mm) Max Rated Working Pressure, psi (kPa)

Product Description

Remarks

AV-1 AV-1 AV-1 AV-1 AV-1 AV-1 AV-1 AV-1 AV-1 AV-1 AV-1 AV-1

Remarks:

Flange x Flange Flange x Flange Flange x Groove Flange x Groove Groove x Groove Groove x Groove Flange x Flange Flange x Flange Flange x Groove Flange x Groove Groove x Groove Groove x Groove

4, 6, 8 in. 4, 6 in. 165 mm 4, 6, 8 in. 76.1 mm, 165 mm 4, 6 in. 165 mm 4, 6 in. 76.1 mm, 165 mm 4, 6 in. 165 mm 4, 6, 8 in. 4, 6, 8 in. 165 mm 21/2, 4, 6, 8 in. 76.1 mm, 165 mm 4, 6, 8 in. 165 mm 21/2, 4, 6, 8 in. 76.1 mm, 165 mm 4, 6, 8 in. 165 mm 21/2, 21/2,

175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070)

a, b, c d, e a, b, c d, e a, c d a, b, c a, d, e a, b, c a, d, e a, c a, d

a. FM Approved for use with Model RC-1 retard chamber. b. Available with Rp2 drain and ANSI, ISO, AS, or JIS flanges. Valves with Rp2 drain limited to vertical risers. Alarm test trim (Grinnell PSN 52-201-2-2002) must be according to installation requirements. c. 175 psi (1205 kPa) rated valves are supplied with grey iron bodies and covers. 300 psi (2070 kPa) rated valves are supplied with ductile iron bodies and covers. d. Approved for use with European trim for European installations. NOTE: The placement of a test and drain valve in lieu of the 2 inch (50 mm) NPS drain valve does not replace the need for an inspector's test connection at the most remote location of the sprinkler system. The test and drain valve shall not be used in lieu of the inspector's test connection for testing of the entire wet piping system. The test and drain valve shall only be used to exercise the clapper and check the mechanical alarm (water motor gong). e. Approved when supplied with ANSI, ISO, AS, or JIS flanges.

Tyco Fire Products Manufacturing Ltd, Stockport Trading Estate Yew St, Stockport Cheshire SK4 2JW, United Kingdom

Product Designation Description Nominal Pipe Size, in. (mm) Max Working Pressure, psi (kPa) Remarks

Model LW

Alarm Check Valve, Flanged Ends

3 (80)

175 (1205)

a, b

a. Resilient seat. b. Limited to installation at locations having constant water supply pressures.

Venus Fire Protection Ltd, 4105 Portland Blvd, Sherbrooke, Quebec J1L 1X9, Canada

Product Designation Description Nominal Pipe Size, in. (mm) Max Working Pressure, psi (kPa) Remarks

Model B Model D Model E

Alarm Check Valve, Flanged by Flanged Alarm Check Valve, Flanged by Grooved Alarm Check Valve, Grooved by Grooved

3, 4, 6, 8 4, 6, 8 4, 6

175 (1205) 175 (1205) 175 (1205)

a, b, c a, b, c a, b, c

a. Resilient seat. b. With Model E retard chamber. c. Limited to installations with vertical risers only.

FM Approvals

1-98

September 2007 -- Approval Guide Automatic Sprinkler Systems

Victaulic Company, Box 31, Easton PA 18044

Product Designation Description Nominal Pipe Size, in. (mm) Max Working Pressure, psi (kPa) Remarks

Series 751 FireLock Series 751 FireLock Series 751 FireLock Series 751 FireLock Series 759 FireLock

Alarm Check Valve, Grooved Ends Alarm Check Valve, Flanged by Grooved Alarm Check Valve, Grooved Ends Alarm Check Valve, Flanged by Grooved Alarm Check Valve, Grooved Ends

11/2,

2, 3, 4, 6 76.1, 165.1 mm 4, 6 8 8

21/2,

300 (2065) 300 (2065) 225 (1550) 225 (1550) 175 (1205)

a, b, c a, b, c a, b, c a, b, c a, b, c

3, 4, 6, 8 76.1, 165.1, 216.3 mm

a. Resilient seat. b. Available with Series 752 retard chamber. c. Suitable for vertical or horizontal installation.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

Product Designation Description Nominal Pipe Size, in. (mm) Max Working Pressure, psi (kPa) Remarks

Model J-1 Model J-1 Model J-1

a. Resilient seat. b. With Model C-1 retard chamber.

Alarm Check Valve, Flanged Ends Alarm Check Valve, Grooved Ends Alarm Check Valve, Flanged by Grooved

3, 4, 6, 8 (76, 80, 100, 150) 3, 4, 6, 8 (76, 80, 100, 150) 3, 4, 6, 8 (76, 80, 100, 150)

250 (1725) 250 (1725) 250 (1725)

a, b a, b a, b

WATERFLOW DETECTORS, VANE TYPE

Waterflow detectors installed in sprinkler systems provide an electrical alarm when a flow of water from the system equals or exceeds that of a single sprinkler. They can be used with either open or closed signaling circuits. They may consist of a flexible vane which projects into the waterway or a pressure-sensing device. For the flexible vane type, water movement deflects the vane, and the motion is transmitted to an alarm-actuating switch after a predetermined time delay. The time delay is accomplished by the use of an instantly recycling retard. Unless otherwise noted in the listing, the flexible vane type is to be used with pipe having an inside diameter which corresponds to Schedule 40 pipe for sizes up to and including 6 in. (152 mm) or Schedule 30 pipe for sizes 8 and 10 in. (203 and 254 mm). Waterflow detectors should not be specified for those systems where the time duration of a pressure fluctuation is greater than the retard time. Instantly recycling retards will not transmit an electrical alarm until the time duration of the pressure fluctuation or waterflow past the vane of the flow detector has exceeded the predetermined time setting of 30-60 seconds. Unless otherwise noted in the listing, these detectors have 175 psi (1205 kPa) rated working pressure.

ADT Security Services Inc, One Town Center Rd, Boca Raton FL 33486

Model B6145. Model 6156 (explosionproof). 21/2 through 8 in. NPS. 1 A at 110 V ac, 1 A at 12 V dc, 110 V dc. Used with any FM Approved recycling retard and/or transmitter. No. D6123. 21/2 through 8 in. NPS. Pneumatic retard and transmitter. No. E6127. 21/2 through 8 in. NPS. Pneumatic retard not instantly recycling. Used with FM Approved Type C2130-001 transmitter. Waterflow Detector. Model 6155. Obtains input signal from a pressure transducer connected by a high pressure hose into the sprinkler system. Power requirements are 11-15 V dc; output contacts are DPDT alarm contacts for connections to transmitter and local annunciation. Contacts rated for 1 A at 115 V ac, 2 A at 24 V dc.

Fire-Lite Alarms Inc, One Fire-Lite Place, Northford CT 06472

Model WFVR. 2 through 8 in. NPS. Pneumatic retard. Contacts rated for 7 A at 125 V ac. Model WFD. 2 through 8 in. NPS. 250 psi (1725 kPa) rated working pressure. Two snap switches and pneumatic retard. Contacts rated for 7 A at 125 V ac, 0.25 A at 24 V dc. Model WFD-SP. 2 through 8 in. NPS. 250 psi (1725 kPa) rated working pressure. One snap switch and pneumatic retard. Contacts rated for 7 A at 125 V ac, 0.25 A at 24 V dc. Models WFD-10, WFD-SP-10. 2 through 5 in. NPS, for use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in. (3 mm); 8 in. NPS, for use with pipe having a wall thickness of 0.188 in. (5 mm). 250 psi (1725 kPa) rated working pressure. Model WFD-10 has two snap switches and pneumatic retard; Model WFD-SP-10 has one snap switch and pneumatic retard. Contacts rated for 7 A at 125 V ac, 0.25 A at 24 V dc. A Model T tamper switch kit (P/N 546-6000) is available as optional equipment for field installation on Models WFD, WFD-SP, WFD-10, WFDSP-10 devices. Models WFD-H, WFD-H-10. 2 through 8 in. 250 psi (1725 kPa) rated working pressure. Two snap switches and pneumatic retard. Contacts rated for 5A at 125 V ac, 0.25 A at 24 V dc. Model WFD-H-10. 2 through 5 in. NPS, for use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in. (3.4 mm); 8 in. NPS, for use with pipe having a wall thickness of 0.188 in. (4.8 mm).

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-99

Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658

Model WFG. 2 through 8 in. NPS. Pneumatic retard and two snap switches. 250 psi (1725 kPa) rated working pressure. Contacts rated for 7 A at 125 V ac, 0.25 A at 24 V dc. A Model T tamper switch kit (P/N 546-6000) is available as optional equipment for field installation on the Model WFG device.

Potter Electric Signal & Manufacturing Ltd, 55 Glencameron Rd, Thornhill, Ontario L3T 1P2, Canada

Model VSR-D. 2 through 10 in. NPS. Furnished with two snap switches and pneumatic retard. Model VSR-T. 2 through 5 in. NPS, for use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in. (3 mm); 8 in. NPS, for use with pipe having a wall thickness of 0.188 in. (5 mm). 250 psi (1725 kPa) rated working pressure. A tamper switch kit (P/N 5420220) is available as optional equipment for field installation on the Models VSR-D, VSR-T devices. Model VSR-E. 2 through 6 in. NPS. Furnished with two snap switches and pneumatic retard. 450 psi (3105 kPa) rated working pressure. Model VSR-F. 2 through 8 in. NPS. Furnished with two snap switches and pneumatic retard. 450 psi (3105 kPa) rated working pressure. Models VS-F, VSR-F. 2 through 5 in. NPS, for use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in. (3 mm); 8 in. NPS (203 mm), for use with pipe having a wall thickness of 0.188 in. (5 mm), or Schedule 40 pipe.

Potter Electric Signal Company, 2081 Craig Road, Saint Louis MO 63146

Model VSR. 2 through 8 in. NPS. Furnished with two snap switches and pneumatic retard. 450 psi (3100 kPa) rated working pressure. Model VSR-TSK. 2 through 6 in. NPS. Furnished with two snap switches and pneumatic retard, and a tamper switch to indicate that the cover was removed. 450 psi (3100 kPa) rated working pressure. Model VSR-F. 2 through 8 in. NPS. Furnished with two snap switches and pneumatic retard. 450 psi (3105 kPa) rated working pressure. Models VS-F, VSR-F. 2 through 5 in. NPS, for use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in. (3 mm); 8 in. NPS (203 mm), for use with pipe having a wall thickness of 0.188 in. (5 mm), or Schedule 40 pipe. Model VSR-FE-2. 2 through 5 in. NPS, for use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in. (3 mm); 8 in. NPS, for use with pipe having a wall thickness of 0.188 in. (5 mm). All sizes also for use in Schedule 40 pipe. 450 psi (3105 kPa) rated working pressure. Furnished with electronic retard. Model VSR-FEX. 2 through 8 in. NPS. For simultaneous usage as explosionproof for Class I, Division 1, Groups C and D; dust-ignitionproof for Class II/III, Division 1, Groups E, F and G hazardous (classified) locations indoors and outdoors (NEMA Type 4); 2 through 5 in. NPS, for use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in. (3 mm); 8 in. NPS, for use with pipe having a wall thickness of 0.188 in. (5 mm). All sizes also for use in Schedule 40 pipe. 450 psi (3105 kPa) rated working pressure. Furnished with pneumatic retard.

System Sensor, Div of Honeywell, 3825 Ohio Ave, Saint Charles IL 60174

Accuflow Model AFDXX, 2 through 8 in. NPS as indicated in table below. 2 through 5 in. NPS have a 450 psi (3105 kPa) rated working pressure. 6 and 8 in. NPS have a 400 psi (2760 kPa) rated working pressure. Two switches and a solid state retard. Contacts rated for 0.6 A, at 125 V ac, 2.0 A, 30 V dc.

Model No.* Nominal Pipe Size, mm

AFD20* AFD25# AFD30-2# AFD35# AFD40# AFD50# AFD60# AFD80§

All models suitable for use in schedule 40 steel sprinkler pipe. *Also for use with Schedule 5 steel sprinkler pipe. #Also for use with Lightwall steel sprinkler pipe. Also for use with Schedule 10 steel sprinkler pipe. Also for use with pipe having a wall thickness of 0.134 in. (3 mm). § Also for use with pipe having a wall thickness of 0.188 in. (5 mm).

2 21/2 3 31/2 4 5 6 8

AFDXXA: Models AFD20A, 25A, 30-2A, 35A, 40A, 50A, 60A, and 80A for Canadian distribution have a factory installed tamper switch rated for 5 A at 125/250 V ac, 3 A at 30 V dc. AFDXXE: Accuflow Model AFDXXE, 2 through 8 in. NPS as indicated in table below. 2 through 4 in. NPS have a 450 psi (3105 kPa) rated working pressure. 6 and 8 in. NPS have a 400 psi (2760 kPa) rated working pressure. Two switches and a solid state retard. Contacts rated for 0.6 A, at 125 V ac, 2.0 A, 30 Vdc.

Model No.* Nominal Pipe Size, mm

AFD20E AFD25E AFD30-2E AFD40E AFD60E AFD80E

*All models suitable for use with BS 1387 medium and heavy pipe, DIN 2448 and 2458 pipe.

2 (60) 21/2 (76) 3 (89) 4 (114) 6 (165) 8 (219)

Model 546-9000. Cover tamper switch available for Models AFD20 (E), 25 (E), 30 (E), 35, 40 (E), 50, 60 (E) and 80 (E) rated for 5 A at 125/250 V ac, 3 A at 30 V dc.

FM Approvals

1-100

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model WFD-XX 2 through 8 in. NPS as indicated in Table below. 2 through 4 in. NPS have a 450 psi (3105 kPa) rated working pressure. 6 and 8 in. NPS have a 400 psi (2760 kPa) rated working pressure. Two snap switches and pneumatic retard. 2 through 6 in. NPS sizes rated for Schedules 10 and 40. 8 in. NPS size rated for 0.188 in wall, Schedules 10 and 30 pipe.

Model No.* Nominal Pipe Size, mm

WFD20E WFD25E WFD30E WFD30E-2E WFD40E WFD60E WFD80E

60 76 89 89 114 165 219

*Suitable for use in BS 1387 medium and heavy pipe, DIN 2448 and 2458 pipe. 2 through 4 in. NPS have a 450 psi (3105 kPa) rated working pressure. 6 and 8 in. NPS have a 400 psi (2760 kPa) rated working pressure. Two snap switches and pneumatic retard. Model No. Nominal Pipe Size, in.

WFD20 WFD25 WFD30 WFD30-2 WFD35 WFD40 WFD50 WFD60 WFD80

2 21/2 3 3 31/2 4 5 6 8

Model WFD-10. 2 through 5 in. NPS, for use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in. (3 mm); 8 in. NPS, for use with pipe having a wall thickness of 0.188 in. (5 mm). 450 psi (3105 kPa) rated working pressure. 2 through 5 in. NPS have a 450 psi (3105 kPa) rated working pressure. 6 and 8 in. NPS have a 400 psi (2760 kPa) rated working pressure. Model WFD-10 has two snap switches and pneumatic retard. Contacts rated for 7 A at 125 V ac, 0.25 A at 24 V dc.

Model No.* Nominal Pipe Size, in.

WFD20 WFD25 WFD30 WFD30-2 WFD35 WFD40 WFD50 WFD60 WFD80§

2 21/2 3 3 31/2 4 5 6 8

Model WFDXX-EXP 2 through 8 in. NPS as indicated in table below. These models are suitable for use in hazardous locations: Class I, Groups B, C, D Division 1, Class II, Groups E, F, G, Division 1, and Class III, Division 1 NEMA 4 enclosure. 2 through 5 in. NPS have a 450 psi (3105 kPa) rated working pressure. 6 and 8 in. NPS have a 400 psi (2760 kPa) rated working pressure. Two snap switches and pneumatic retard. Contacts rated for 10 A, at 125/250 V ac, 2.5 A, 24 V dc.

Model No.* Nominal Pipe Size, in.

WFD20-EXP WFD25-EXP WFD30-EXP WFD30-2EXP WFD35-EXP WFD40-EXP WFD50-EXP WFD60-EXP WFD80-EXP§

2 21/2 3 3 31/2 4 5 6 8

*All models suitable for use in Schedule 40 pipe. Two snap switches and pneumatic retard. Two snap switches and pneumatic retard. Also for use with Schedule 10 pipe. Also for use with pipe having a wall thickness of 0.134 in. (3 mm). §Also for use with pipe having a wall thickness of 0.188 in. (5 mm).

Models WFD20A, 25A, 30A, 40A, 50A, 60A, 80A for Canadian distribution have factory installed cover tamper switch rated for 5 A at 125/250 V ac, 2.5 A at 24 V dc. Model 546-7000. Cover tamper switch available for Models WFD20, 25, 30, 35, 40, 50, 60, 80 rated for 5 A at 125/250 V ac, 2.5 A at 24 V dc.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

Model VSR-D. 2 through 10 in. NPS. Furnished with two snap switches and pneumatic retard.

TESTERS FOR VANE TYPE WATERFLOW DETECTORS

When energized, tester supplies circulating water around a vane type waterflow detector, causing vane motion to be transmitted to an alarm-actuating switch after the predetermined time delay has occurred. Suitable for use with FM Approved vane detectors in 2 through 8 in. nominal sizes. No sprinkler system water has to be sent to a drain with this system.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-101

Unless otherwise specified, these testers have 175 psi (1205 kPa) rated working pressure.

National Fire Fighting Mfg, FZCO, Box 17014, Jebel Ali Free Zone, Dubai, UAE

``Zonecheck'' Vane Type Waterflow Indicator Test Devices. Available in sizes 2 through 6 in. NPS. Can be original installation, or a retrofit, to run piping around indicator. All sizes available in Schedule 10 and 40 piping configurations. Either 120 V ac or 230 V ac power required.

Project Fire Products Ltd, Pasturefields Lane, Industrial Estate, Hixon, Staffordshire ST18 0PH, United Kingdom

``Zonecheck'' Vane Type Waterflow Indicator Test Devices. Available in sizes 1 through 6 in. NPS. Can be original installation, or a retrofit, to run piping around indicator. All sizes available in Schedule 10, 40, BS 1387 Medium and Heavy piping configurations. Either 120 V ac or 230 V ac power required.

Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY, United Kingdom

``Zonecheck'' Vane Type Waterflow Indicator Test Devices. Available in sizes 2 through 6 in. NPS. Can be original installation, or a retrofit, to run piping around indicator. All sizes available in Schedule 10 and 40 piping configurations. Either 120 V ac or 230 V ac power required.

DRY PIPE VALVES

In buildings where it is impractical to keep temperatures above freezing, automatic sprinkler systems can be equipped with an FM Approved dry pipe valve. The sprinkler piping contains air under pressure, instead of water. When a sprinkler operates, air escapes, the dry pipe valve trips, and water is admitted automatically to the system Dry pipe systems should be installed in accordance with FM Global Loss Prevention Data Sheet 2-8N, Installation of Sprinkler Systems. Additionally, if their use is intended for refrigerated storage, FM Global Loss Prevention Data Sheet 8-29 should be referred to. System calculations regarding required system air capacity should be performed if only one air pressure maintenance device is contemplated for several sprinkler systems. Dry pipe valves are designed so that a moderate amount of air pressure will hold back a much greater water pressure. In the differential type, the air pressure holds the water clapper closed either by means of a difference in areas on which the water and air pressures act, or by a combination of this principal with a lever action. In the mechanical type, a clapper on the water seat is held closed by a system of levers which are controlled by a relatively small air clapper. A suitable alarm is connected to the dry pipe valve so that a warning is given when the valve operates. This may be a mechanical alarm that operates by a hydraulic motor, or a hydraulic pressure switch that closes an electric circuit to operate a bell, horn, or remote signaling system. Unless otherwise noted in the listing, these dry pipe valves have 175 psi (1205 kPa) rated working pressure.

Anber Globe SA, Av de Las Flores 13, Parque Ind El Molino, 28970 Humanes de Madrid, Madrid Spain

Model A. 21/2 in. NPS. 90° angle. Threaded or cut groove inlet and outlet connections. Model D. 4, 6 in. NPS; 100, 150 mm NPS. Standard size valves painted black or gray. Metric size valves painted blue. Flanged inlet. Flanged or grooved outlet. Model LDX Dry Pipe Valve System, 4 and 6 in. NPS. Model LDX dry pipe valves have a flanged inlet and grooved outlet. Model LDX check valves have grooved inlet and outlet connections. Model DDX-LP Dry Pipe Valve System consists of Model DDX Deluge Valves in sizes 4 in. and 6 in. NPS (100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. The Model DDX-LP Dry Pipe Valves have an external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. The Model DDX Deluge Valves have grooved inlet and grooved outlet end connections. The DDX-LP system is designed for systems with water supply pressures from 20 psi (138 kPa) to 250 psi (1724 kPa), and corresponding sprinkler system air pressures, nominally, of 12 psi (83 kPa) to 24 psi (165 kPa). A loss of system air pressure, such as when a sprinkler activates, opens the pneumatic actuator which opens the DDX valve, sending water to the sprinklers and sounding alarms. The system utilizes a Model LP (low pressure) pilot line actuator, a Model LP low pressure pneumatic actuator, a Model B Manual Pull Station, and a System Sensor EPS10-1 pressure alarm switch. A Model B1 accelerator is an available option for use with this system. In the event that water builds up inside the deluge valve due to condensate from the air supply system or water from a valve trip, a drain valve is provided to drain the valve body and riser. The rated working pressure of the Model DDX-LP Dry Pipe Valve System is 250 psi (1724 kPa).

Angus Fire Sprinklers, Thame Park Rd, Oxfordshire OX9 3RT, United Kingdom

Model D. 100, 150 mm NPS. Metric size valves painted blue.

Calanbau Brandschutzanlagen GmbH, Wenderter Strasse 12, D-31157 Sarstedt, Germany

Model TMX 80, 100, 150 mm.

Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446

Model Model Model Model Model D, AF. 2, 21/2, 3 in. E. 6 in. Flanged inlet and cut-grooved outlet connections. H, AF. 4, 6 in. K, AG. 4, 6 in. Flanged inlet and cut-grooved outlet connections. C. 3, 4, 6 in. NPS. Available with flange/flange and flange/groove end connections.

Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620

``Automatic'' Model 39. 4, 6 in. NPS. Flange/flange connection. ``Automatic'' Model 39A. 6 in. NPS. Flange/flange connection. ``Automatic'' Model GTO. 4, 6 in. NPS. Flange/groove connection.

GW Sprinkler A/S, Kastanievej 15, DK-5620 Glamsbjerg, Denmark

Model D. 100, 150 mm NPS. Valves painted red.

FM Approvals

1-102

September 2007 -- Approval Guide Automatic Sprinkler Systems

Globe Fire Sprinkler Corp, 4077 Air Park Dr Standish MI 48658

Model D. 3 in. NPS. Model F-2. 4, 6 in. NPS. Used with Model C quick-opening device. Model F-3. 4, 6 in. NPS. Flanged. Used with Model C accelerator or with Model C accelerator and Model C antiflooding device. Model G-3. 4, 6 in. NPS with cut groove at top. Used with Model C accelerator or with Model C accelerator and Model C antiflooding device.

Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Grinnell Grinnell Grinnell Grinnell or or or or Gem Gem Gem Gem Model A-2. 2 in. NPS. Model F302. 4, 6 in. NPS. Model F3021. 4, 6 in. NPS. Model F3061. 2, 3, 4, 6 in. NPS.

Jomos Brandschutz AG, Sagmattstrasse 5, CH-4710 Balsthal, Switzerland

Model TMX. 80, 100, 150 mm. Available with flange x flange or flange x groove end connections.

Magisco Valves Ltd, 53 Limes Rd, Tettenhall, Wolverhampton WV6 8RD, United Kingdom

MAG Model M799DG-04E. 3, 4, 6, 8 in. NPS. 300 psi rated working pressure. Available with wafer or flanged inlet and outlet connections.

Mil Ltd, 17 Moshe Beker St, Box 15200, Rishon Lezion 75051, Israel

Product Designation End Connection Nominal Pipe Size, in. (mm) Max Working Pressure, psi (kPa) Remarks

INBAL Model 799-DG04-E

Wafer Flanged Inlet and Outlet

3, 4, 6, 8 (80, 100, 150, 200)

175 (2070)

­

Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840, Bad Oldesloe, Germany

Product Designation End Connections Nominal Pipe Size, in. (mm) Max Working Pressure, psi (kPa) Remarks

Model TMX

Flanged × Flanged Flanged × Grooved Grooved × Grooved

3, 4, 6 (80, 100, 150)

175 (1205)

­

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Model A. 21/2 in. NPS. 90° angle. Threaded or cut groove inlet and outlet connections. Model D. 4, 6 in. NPS; 100, 150 mm NPS. Standard size valves painted black or gray. Metric size valves painted blue. Flanged inlet. Flanged or grooved outlet. Model LDX low pressure Dry Pipe Valve System, 4 and 6 in. NPS, 100 and 150 mm NPS. Model LDX dry pipe valves have a flanged inlet and grooved outlet. Model LDX low pressure check valves have grooved inlet and outlet connections. The Model LDX Dry Pipe Valves are available with the optional Model B-1 Accelerator. Model DDX-LP Dry Pipe Valve System consists of Model DDX Deluge Valves in sizes 4 in. and 6 in. NPS (100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. The Model DDX-LP Dry Pipe Valves have an external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. The Model DDX Deluge Valves have grooved inlet and grooved outlet end connections. The DDX-LP system is designed for systems with water supply pressures from 20 psi (138 kPa) to 250 psi (1724 kPa), and corresponding sprinkler system air pressures, nominally, of 12 psi (83 kPa) to 24 psi (165 kPa). A loss of system air pressure, such as when a sprinkler activates, opens the pneumatic actuator which opens the DDX valve, sending water to the sprinklers and sounding alarms. The system utilizes the Reliable Model LP (low pressure) pilot line actuator, the Reliable Model LP low pressure pneumatic actuator, the Reliable Model B Manual Pull Station, and a System Sensor EPS10-1 pressure alarm switch. The Reliable Model B1 accelerator is an available option for use with this system. In the event that water builds up inside the deluge valve due to condensate from the air supply system or water from a valve trip, a drain valve is provided to drain the valve body and riser. The rated working pressure of the Model LP Dry Pipe Valve System is 250 psi (1724 kPa).

Rolland Arroseurs Sprinklers, Ste Rolland/Usine, 73410 Mognard, France

Model A. 3, 4, 6 in. NPS. Flange/flange connection. Model B. 4, 6 in. NPS. Flange/groove connection. Model E. 4 in. NPS. Groove/Groove connection.

SES Enser Engineering, Via Carolina Romani 8/10, 20091 Bresso (MI), Italy

FARES Model F799DG-04E. 3, 4, 6, 8 in. NPS. 300 psi rated working pressure. Available with wafer or flanged inlet and outlet connections.

Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154

Model A. 2*, 3, 4, 6 in. NPS. Available with flange/flange and flange/groove end connections. Model A-1. 4, 6 in. NPS. Flange/Groove end connections.

*Also available with groove/groove end connections.

Tyco Fire Products, 451 N Cannon Ave, Lansdale PA 19446

Model DPV-1. 4, 6 in. NPS. Rated working pressure 250 psi (1725 kPa). Available with flange × flange, grooved x grooved and flange × grooved end connections. Model DPV-1. 21/2 and 3 in. NPS. Rated working pressure 250 psi (1725 kPa). Available with flange × grooved end connections.

Venus Fire Protection Ltd, 4105 Portland Blvd, Sherbrooke, Quebec J1L 1X9, Canada

Astra Model A. 3, 4, 6 in. NPS. Flange/flange connection. Astra Model B. 4, 6 in. NPS. Flange/groove connection. Astra Model E. 4 in. NPS. Groove/groove connection.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-103

Victaulic Company, Box 31, Easton PA 18044

Series 756 Firelock Dry Pipe Valves, sizes 11/2, 2, 21/2, 3, 4, 6, and 8 in. NPS, grooved inlet and grooved outlet or flanged inlet and grooved outlet in sizes 4, 6, and 8 in. NPS, vertical or horizontal orientation; sizes 76.1 and 165.1 mm NPS, grooved inlet and outlet. Consists of the Series 756 FireLock dry pipe valve, Style 753-A dry actuator, Series 749 Auto Drain (pressure operated relief valve), Series 748 Ball Check Valve, and Series 729 Ball Drip Valve. Optional Series 757 or 757-P air maintenance device; It may include an optional accelerator, the Series 746. 300 psi (2069 kPa) rated working pressure, except for the 8 in. valves, which have a rated working pressure of 225 psi (1551 kPa). Series 756-LPA Firelock Dry Pipe Valves, sizes 11/2, 2, 21/2, 3, 4, 6, and 8 in. NPS, grooved inlet and grooved outlet or flanged inlet and grooved outlet in sizes 4, 6, and 8 in. NPS, vertical or horizontal orientation; sizes 76.1 and 165.1 mm NPS, grooved inlet and outlet, vertical or horizontal orientation. Consists of Series 756 FireLock dry pipe valve, Series 776 low pressure actuator for low pressure, nominally 10 psi, supervised system pressure; Series 749 Auto Drain (pressure operated relief valve), Series 748 Ball Check Valve, Series 729 Ball Drip Valve. It may include an optional accelerator, the Series 746, and/or the Series 757 air maintenance device. 300 psi (2069 kPa) rated working pressure, except for the 8 in. valves, which have a rated working pressure of 225 psi (1551 kPa). The Series 757-P Air Maintenance Trim Assembly is an option used to control the system air pressure on dry pipe valves. All dry pipe valves offer the Series 75-W Water Column Drain Kit as an option, which automatically drains water from the sprinkler systems and subsequently reseals to maintain air pressure in the system piping. All dry pipe valves discussed above offer the Series 75-B supplemental alarm valve as an option recommended for systems where continuous flow to the alarm port, which supplies flow to the water motor alarm, must be positively maintained. Series 768 Firelock NXT Dry Valve in sizes 11/2, 2, 21/2, 3, 4, 6 and 8 in. NPS, grooved inlet and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following: · · · · · · · · · Series 776 Low Pressure Pneumatic Actuator with Auto Vent pressure operated system air pressure relief valve Series 749 Auto Drain pressure operated piston charge line water relief valve Series 729 alarm line Drip Check Valve Series 748 anti-flood Ball Check Valve Series 768 alarm line 3-Way Ball Valve for alarm/test/off Series 768 Air Manifold Assembly with integral restrictor/screen/anti-flood ball check valve Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections System Main Drain Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.

Optional system components include: · · · · · · · · Regulated Air Maintenance Trim Assemblies Series 757 or 757-P (with pressure switch) Air Maintenance Devices Series 746-LPA Accelerator System Sensor EPS10-2 alarm line pressure switch System Sensor EPS40-2 system air pressure supervisory switch Series 760 Water Motor Alarm Series 755 Manual Pull Station Series 705W water supply butterfly shutoff valve

All Dry Pipe Valves are available factory assembled in the Victaulic Series 745 Fire-Pac enclosure, a cabinet containing all system components and accessories, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

Model F-1. 3, 4, 6 in. flange/flange, groove/groove, and flange/groove end connections. Dry Pipe Valves are available factory assembled in the Viking Total Pac2 enclosure, in sizes 3 through 6 in. NPS. The Total Pac2 enclosure and assembled valves comprise an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm connections, and the electrical connections for the alarm devices and optional air compressor. Model F-2, 3, 4, 6 in. groove/groove end connections. Dry Pipe valves are available factory assembled in the Viking Total [email protected] enclosure, in sizes 3 through 6 in. NPS. The Total Pac2 enclosure and assembled valves comprise an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm connections, and the electrical connections for the alarm devices and optional air compressor.

ACCELERATORS with Built-In Antiflooding Device

These combine the operating characteristics of an accelerator and antiflooding device in a single mechanical unit. When installed on a dry pipe valve, they cause the valve to trip more quickly and also to exclude foreign particles from entering the accelerator mechanism. Because both the accelerator and antiflooding feature are combined in a single unit, no separate antiflooding device is required. Unless otherwise noted in the listing, these accelerators have 175 psi (1205 kPa) rated working pressure.

Angus Fire Sprinklers, Thame Park Rd, Oxfordshire OX9 3RT, United Kingdom

Model B1. For use with Angus Model D dry pipe valve.

Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446

Model B. For use with Central Models AF, AG, 3, 4, 6 in. or Grinnell or Gem Models F302, F3021, 4, 6 in. or Star Model A, 2, 3, 4, 6 in. NPS dry pipe valves, 4, 6 in. or Grinnell Duomatic dry systems (refrigerated area sprinkler systems). Model B Accelerator. For use with Central Sprinkler Company 3, 4, 6 in. NPS Model AF and 4, 6 in. NPS Model AG Dry Pipe Valves.

GW Sprinkler A/S, Kastanievej 15, DK-5620 Glamsbjerg, Denmark

Model B. For use with GW Sprinkler A/S Model D, 100, 150 mm dry pipe valve. Valves painted red.

FM Approvals

1-104

September 2007 -- Approval Guide Automatic Sprinkler Systems

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Models B, B1. For use with Reliable Model D or Star Model A dry pipe valve. The Model B-1 Accelerator is an optional component for use with the Reliable Model LDX Dry Pipe Valve System.

Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154

Model S430. For use with Grinnell or Gem Models F302, F3021, 4, 6 in. or Star Model A, 2, 3, 4, 6 in. NPS dry pipe valves, 4, 6 in. Duomatic dry systems (Refrigerated Area Sprinkler Systems).

Tyco Fire Products, 451 N Cannon Ave, Lansdale PA 19446

Tyco Fire Products Accelerator. Model ACC-1. For use with Tyco Model DPV-1, 21/2, 3, 4, 6 in., Grinnell or Gem Models F302, F3021, 4, 6 in., Star Model A, 2, 3, 4, 6 in. and Model A-1, 4, 6 in., Central Models AF and AG, 3, 4, 6 in. NPS dry pipe valves, 4, 6 in. Duomatic dry systems (refrigerated area sprinkler systems).

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

Model D-1. For use with Viking Models E-1, E-2, F-1 dry pipe valves. Model D-2. For use with Viking Models E-1, E-2, F-1 dry pipe valves.

ACCELERATORS AND EXHAUSTERS

An accelerator or exhauster, attached to a dry pipe valve, causes the valve to trip quickly upon sprinkler operation. These devices operate when loss of system air pressure exceeds a predetermined rate. Unless otherwise noted in the listing, these accelerators and exhausters have 175 psi (1205 kPa) rated working pressure.

Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446

Model A Accelerator, Model A Antiflooding Device Assembly. For use with Models H, K, AF, AG; 4, 6 in. NPS dry pipe valves.

Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620

``Automatic'' Model 1 Accelerator. For use with ``Automatic'' Model 39 dry pipe valve.

Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658

Accelerator. Model C.

Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Standard Model A Accelerator. For use with Star Model G or Hodgman Model C dry pipe valve.

Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840 Bad Oldesloe, Germany

Model SE2 Accelerator. For use with Model TMX dry pipe valves.

Potter Electric Signal Company, 2081 Craig Road, Saint Louis MO 63146

Model QRS Electronic Accelerator System. Consists of a Potter Model QRS Quick Release Pressure Switch, Potter Model PFC-100RC Fire Alarm Releasing Panel, Skinner Model 73218BN4UNLVNOC111C2 solenoid valve and associated trim for use on the following dry pipe valves:

Manufacturer Model No. Size, in.

Tyco Fire Products GEM Central Central Star Star

DPV-1 F302/F3021 AF AF/AG A A-1

21/2,

3, 4 and 6 4 and 6 3 4 and 6 4 and 6 4 and 6

Note 1: The Model QRS Accelerator with Model PFC-100RC Panel is configured such that one accelerator and one control panel is utilized for one dry pipe valve.

Model QRS Electronic Accelerator System. Consists of a Potter Model QRS Quick Release Pressure Switch, Potter Model PFC-4410-RC Fire Alarm Releasing Panel, Skinner Model 73218BN4UNLVNOC111C2 solenoid valve and associated trim for use on the following dry pipe valves (Note 2) and a preaction valve (Note 3): Dry Pipe Valves

Manufacturer Model No. Size, in.

Tyco Fire Products GEM Central Central Star Star

DPV-1 F302/F3021 AF AF/AG A A-1

21/2,

3, 4 and 6 4 and 6 3 4 and 6 4 and 6 4 and 6

Note 2: The Model PFC-4410-RC Panel, standard program #14, is configured such that one control panel can be utilized for up to four dry pipe valves with four Model QRS Accelerators.

Double-Interlock Preaction Valve, Electric/Pneumatic-Electric with cross-zoned control panel

Manufacturer Model No. Size, in.

Tyco Fire Products

DV-5

11/2 thru 8

Note 3: The Model PFC-4410-RC Panel, standard program #13, is configured such that one control panel is utilized for one preaction valve with one Model QRS Accelerator.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-105

Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154

Star Exhauster. Model BB.

Victaulic Company, Box 31, Easton PA 18044

Series 746 Accelerator, 300 psi (2070 kPa) rated pressure. For use with Series 756 Firelock Dry Pipe Valves and Series 758 Firelock Actuated Valves.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

Viking Supervised Rate-of-Rise Releasing System. Used to accelerate a dry valve. Model E-1 Accelerator, Model B-1 Antiflooding Device Assembly. For use with Model F-1 and E-2 dry pipe valves.

ANTIFLOODING DEVICES for Accelerators

When a dry pipe valve operates, water flows to the accelerator. Foreign particles may be carried with the water to the accelerator. An antiflooding device is installed in the line between the valve and accelerator to prevent foreign material from entering the accelerator where it is likely to cause malfunction. Unless otherwise noted in the listing, these devices have 175 psi (1205 kPa) rated working pressure.

Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Standard Model A.

PRESSURE MAINTENANCE DEVICES, Dry Pipe Systems

These pressure maintenance devices automatically maintain a predetermined air or nitrogen pressure in dry pipe sprinkler systems. Some devices may be used with a noncontinuous air supply which is capable of initially filling the system. Other systems require a continuous air or nitrogen supply. Unless noted otherwise in the listing, these air maintenance devices have a pressure rating of 175 psi (1205 kPa).

Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446

Models D, D-1, DU, DU-1. Model C.

Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620

``Automatic'' Models A, A-1.

General Air Products Inc, 604 Jeffers Circle, Exton PA 19341

Models AMD-1, AMD-1 ALT, AMD-2, AMD-2 ALT, AMD-3.

Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658

Models H-1, H-2, H-3.

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Models A-2, B-1, B-2.

Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154

Models A, B.

Tyco Fire Products, 451 N Cannon Ave, Lansdale PA 19446

Tyco Model AMD-1. 200 psi (1380 kPa) working pressure. Air maintenance. Tyco Model AMD-2. Air maintenance. Tyco Model AMD-3. Nitrogen maintenance.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

Air Maintenance Device. Model D-2. Air Compressor. Model D-1, E-1, 50 and 60 cycle.

AIR PRESSURE MAINTENANCE DEVICES, Special Sprinkler Systems

These devices are designed for use with fire protection equipment which requires supervisory air pressure of approximately 1.5 psi (10 kPa).

Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Grinnell or Gem Supervisory Air Panel. Model F112.

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Air Compressor Panel. Reliable Model B. Automatic Air Pressure Maintenance Device. Reliable Model C.

FM Approvals

1-106

September 2007 -- Approval Guide Automatic Sprinkler Systems

AIR DRYING UNITS

These devices are intended for use in a dry pipe or a refrigerated area spinkler system application. Each unit, in conjunction with an FM Approved air maintenance device, provides air with reduced humidity to lower the possibility of ice formation in a single dry pipe system.

General Air Products Inc, 604 Jeffers Circle, Exton PA 19341

Dry Air Pac Air Drying Units. Models DAP500, DAP1000 and DAP2000. Units are provided with an FM Approved air maintenance device.

DELUGE SPRINKLER SYSTEMS

Deluge sprinkler systems have open sprinklers or open spray nozzles and are used where it is desirable to discharge water through all of the system's sprinklers or nozzles simultaneously. Prior to discharge there is no water in the sprinkler piping. The water supply is held back by a control valve which is operated manually or automatically by the actuation of a fire detection system. The fire detection system is required to be one of the following types: wet pilot sprinkler line, dry pilot sprinkler line, hydraulic rate-of-rise, pneumatic rate-of-rise or electric. FM Approved combinations of control valves and fire detection system(s) are listed under AUTOMATIC WATER CONTROL VALVES. Automatic sprinklers are used on wet or dry pilot sprinkler lines. The dry pilot sprinkler line may also require a dry pilot actuator depending upon the type of automatic water control valve. When required, only the compatible dry pilot actuator listed for a specific valve under AUTOMATIC WATER CONTROL VALVES shall be used in FM Approved systems. Electrically operated deluge sprinkler systems are FM Approved on a component basis. Only the major, compatible components listed for a specific valve under AUTOMATIC WATER CONTROL VALVES shall be used in an FM Approved system. FM Global installation acceptance may stipulate that only heat-actuated fire detection devices be used. Acceptance criteria by other jurisdictional authorities may vary. Deluge sprinkler systems identified in the listing by an asterisk (*) have either hydraulic or pneumatic rate-of-rise fire detection and are FM Approved as complete systems. Only the listed components for a specific manufacturer shall be used in an FM Approved system.

Anber Globe SA, Av de Las Flores 13, Parque Ind El Molino, 28970 Humanes de Madrid, Madrid Spain

Deluge Sprinkler System consist of Model A, 21/2 in. NPS and Models B and BX in sizes 4 and 6 in. and 100 and 150 mm NPS deluge valves. Model BX deluge valves have an external reset feature. Systems are Approved for hydraulic, pneumatic or electric releasing means. Model DDX Deluge Sprinkler System consists of Model DDX Deluge Valves in sizes 4 inch and 6 inch NPS (100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. Systems are Approved for hydraulic (wet pilot line), pneumatic (dry pilot line), or electric (solenoid valve) releasing means. Model DDX valves have grooved inlet and grooved outlet end connections. In the event that water builds up inside the deluge valve due to condensate from the air supply system or water from a valve trip, a drain valve is provided to drain the valve body and riser. The Wet Pilot Trim set is connected to the push rod chamber outlet and provides the 2 inch main drain, the alarm test, the water supply pressure gage, and the push rod chamber supply connections. A wet pilot line, which extends up to the open deluge sprinkler grid, contains a closed sprinklers or other fixed temperature releases. When the closed sprinkler is activated and opened by a fire, the pilot line pressure is released which opens the DDX valve, sending water to the sprinklers and sounding alarms. TheWet Pilot Trim set is used when the Model F1-FTR fixed temperature release is used in the wet pilot line, and/or when the Model A or B emergency stations/manual pull boxes can be used for releasing. The rated working pressure of the Wet Pilot Deluge System is 250 psi (1724 kPa). The Dry Pilot Trim set is used when a fixed temperature release is used in the dry pilot line. A dry pilot line, which extends up to the open deluge sprinkler grid, contains closed sprinklers or other fixed temperature releases. When a closed sprinkler is activated and opened by a fire, the pilot line pressure is released which opens the pneumatic actuator, which opens the DDX valve, sending water to the sprinklers and sounding alarms. The Model LP (low pressure) pilot line actuator is used in the dry pilot line and is designed for systems with water supply pressures from 20 psi (138 kPa) to 250 psi (1724 kPa), and corresponding dry pilot line pneumatic pressures, nominally, of 12 psi (83 kPa) to 24 psi (165 kPa). The system uses the Model A or B emergency stations/manual pull boxes which can be used for manual releasing. The rated working pressure of the Dry Pilot Deluge System is 250 psi (1724 kPa). The Electric Actuation Trim set is connected to the push rod chamber outlet and provides the 2 inch main drain, the alarm test, the water supply pressure gage, and the push rod chamber supply connections. The Model A or B emergency stations/manual pull boxes can be used for manual releasing. This system's Notifier RP 1001 Fire Alarm/Releasing Control Panel is utilized for the electric release and alarm functions. Only when there is an electrical signal to the releasing control panel from a fire detector, such as when a fixed temperature heat detector is activated, does the solenoid valve open which opens the DDX valve, sending water to the sprinklers. Only FM Approved fixed temperature heat devices shall be used in the release system and in the sprinkler piping. The control panel has an appropriately sized battery, Notifier Model PS 12120, to provide 90 hours of backup emergency power. The system utilizes the normally closed solenoid valve, P/N 6871020020. The rated working pressure of the Electric Actuation Deluge System is 250 psi (1724 kPa)

Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446

Deluge Sprinkler System. Consists of Model A, 4 and 6 in., or Model DL water control valve, 2 in. Deluge Sprinkler System. Consists of Model B, 3, 4 and 6 in. NPS water control valve Central Hidromatic Deluge Sprinkler System. Consists of Model B-1, 3, 4, 6 in. NPS water control valve. Model G-1 water control valves have an external reset feature. Systems are FM Approved for hydraulic, pnuematic or electric release trim. Rated working pressure is 250 psi (2070 kPa).

Cla-Val Company, Box 1325, Newport Beach CA 92659

Deluge Sprinkler System consists of Model 834 automatic water control valve and Model H&A 150-200-BNHA pilot valve. Sizes 4, 6, 8, 10 in. NPS. 250 psi (1725 kPa) rated working pressure.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-107

Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620

``Automatic'' Suprotex Deluge System*. Consists of Model C automatic water control valve, sizes 21/2, 6 in.; 1/8 in. circuit tubing with the following Heat Actuated Devices (HADs): 87-100A, 87-150, 87-180, 87-190, 87-530A, 87-540A, 87-560, 87-570; No. 90-100 compensating vent; Nos. 81-100A, 83-100A releases; Nos. 81-600A, 83-600 secondary releases (only acceptable when rate-of-rise circuits are a secondary means of system activation); Model 70-200 break glass station; manual pull handle; Model 64-100G manual pull station; No. 148-200C air pump panel; No. 2403C2H low pressure regulator; No. 79-340A air dryer; No. 39-713 drum drip or No. 79-943C reservoir; No. 1621 high pressure regulator; No. 148-250 restriction orifice; No. 79-840B air line mercury check; No. 121 mercury check; No. S76-650 weight switch; Model 94-160 low pressure actuator; emergency release (quick opening valve); Model 123-100 hydropneumatic control. ``Automatic'' Deluge Sprinkler System. Consists of Model D, F water control valves, 21/2, 4, 6 in. or Model E water control valve, 6 in., which must be equipped with Viking Model C-1 pressure-operated relief valve.

Flamex Inc, 4365 Federal Drive, Greensboro NC 027410

Deluge Sprinkler Systems. Consists of Model FSX deluge valves with either Electric, Dry Pilot Line, or Wet Pilot Line releasing means. The valves are available in flange by flange end connections, DIN sizes of 50, 80, 100, and 150 mm NPS. The electric solenoid is an impulse type solenoid valve, part no. 84 0131. The dry pilot line actuator is a diaphragm valve, part no. 20 9353-E. With electrical releasing, the control panel FMZ 4100 GAB 32, with 90 hours of 24 Vdc battery backup is used. The Models FSX deluge valves have a rated working pressure of 232 psi (16 bar).

GW Sprinkler A/S, Kastanievej 15, DK-5620 Glamsbjerg, Denmark

Deluge Sprinkler System. Consists of Model B water control valve, 100, 150 mm NPS.

Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658

Consists of Model F Water Control Valve. 21/2, 4, 6 in. Consists of Model D1.5, 11/2 in. NPS, and Model D2, 2 in. NPS, Water Control Valves.

Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Grinnell or Gem Multitrol Deluge System*. Consists of Model C automatic water control valve, sizes 21/2, 6 in.; 1/8 in. circuit tubing with the following Heat Actuated Devices (HADs): 87-100A, -150, -180, -190, -530A, -540A, -560, -570; No. 90-100 compensating vent; Nos. 81-100A, 83-100A releases; Nos. 81-600A, 83-600 secondary releases (only acceptable when rate-of-rise circuits are a secondary means of system activation); Model 70-200 break glass station; manual pull handle; Model 64-100G manual pull station; No. 148-200C air pump panel; No. 2403C2H low pressure regulator; No. 79-340A air dryer; No. 39-713 drum drip or No. 79-943C reservoir; No. 1621 high pressure regulator; No. 148-250 restriction orifice; No. 79-840B air line mercury check; No. 121 mercury check; No. S76-650 weight switch; Model 94-160 low pressure actuator; emergency release (quick opening valve); Model 123-100 hydropneumatic control. Grinnell or Gem Deluge Sprinkler System. Consists of Model A-4 multimatic water control valve, 4, 6 in.; Model F430 thermal control valve, 1, 11/2 in. NPS; Model B flooding valve, 2 in. NPS. Grinnell or Gem Selfcon System. A self-contained limited water supply system intended primarily for isolated hazards using open nozzles. Each installation needs individual review. Grinnell or Gem Electrospray Deluge Sprinkler System. Consists of Model A-4 deluge valve, 4, 6 in. or Model B flooding valve, 2 in. Wormald Deluge Sprinkler System. Consists of Wormald Model A1 water control valve, 100, 150 mm (4, 6 in.). Grinnell or Gem Model F445. 21/2 in. angle valve. Grinnell or Gem Model F446. 21/2 in. angle valve. 250 psi (1725 kPa).

Jomos Brandschutz AG, Sagmattstrasse 5, CH-4710 Balsthal, Switzerland

Deluge Sprinkler Systems. Consists of Model FSX deluge valves with either Electric, Dry Pilot Line, or Wet Pilot Line releasing means. The valves are available in Flange by Flange end connections, DIN sizes of 50, 80, 100, and 150 mm NPS. The electric solenoid is an impulse type solenoid valve, Minimax part no. 84 0131. The dry pilot line actuator is a diaphragm valve, Minimax part no. 20 9353-E. With electrical releasing, the Minimax control panel FMZ 4100 GAB 32, with 90 hours of 24 Vdc battery backup is used. The Models FSX deluge valves have a rated working pressure of 232 psi (16 bar).

Magisco Valves Ltd, 53 Limes Rd, Tettenhall, Wolverhampton WV6 8RD, United Kingdom

MAG Model M799DG-04A (wet pilot), MAG Model M799DG-04B (dry pilot), MAG Model M799DG-04C (electric). Consists of 3, 4, 6, 8 in. NPS MAG Model M799DG-04 automatic water control valve. MAG Models M799DG-04A and M799DG-04B have a rated working pressure of 300 psi (2070 kPa).

Mil Ltd, 17 Moshe Beker St, Box 15200, Rishon Lezion 75051, Israel

INBAL Model 799-DG-01-HMP (wet pilot) and INBAL Model 799-DG-01-PMP (dry pilot). Consists of 3, 4, 6, 8 in. NPS INBAL Model 799-DG-01 water control valve. 6 in. NPS rated working pressure of 300 psi (2070 kPa). INBAL Model 799-DG04-A (wet pilot), INBAL Model 799-DG04-B (dry pilot), INBAL Model 799-DG04-C (electric). Consists of 3, 4, 6, 8 in. NPS INBAL Model 799-DG04 automatic water control valve. INBAL Models 799-DG04-A and 799-DG04-B have a rated working pressure of 300 psi (2070 kPa).

Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840 Bad Oldesloe, Germany

Deluge Sprinkler Systems. Consists of Model FSX deluge valves with either Electric, Dry Pilot Line, or Wet Pilot Line releasing means. The valves are available in Flange by Flange end connections, DIN sizes of 50, 80, 100, and 150 mm NPS. The electric solenoid is an impulse type solenoid valve, Minimax P/N 84 0131. The dry pilot line actuator is a diaphragm valve, Minimax P/N 20 9353-E. With electrical releasing, the Minimax control panel FMZ 4100 GAB 32, with 90 hours of 24 Vdc battery backup is used. The Models FSX deluge valves have a rated working pressure of 232 psi (16 bar).

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Deluge Sprinkler System consists of Model A, 21/2 in. NPS and Models B and BX in sizes 4 and 6 in. and 100 and 150 mm NPS deluge valves. Model BX deluge valves have an external reset feature. Systems are FM Approved for hydraulic, pneumatic or electric releasing means. Model DDX Deluge Sprinkler System. Consists of Model DDX Deluge Valves in sizes 4 inch and 6 inch NPS (100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. Systems are Approved for hydraulic (wet pilot line), pneumatic (dry pilot line), or electric (solenoid valve) releasing means. Model DDX valves have grooved inlet and grooved outlet end connections. In the event that water builds up inside the deluge valve due to condensate from the air supply system or water from a valve trip, a drain valve is provided to drain the valve body and riser. The Wet Pilot Trim. Set is connected to the push rod chamber outlet and provides the 2 inch main drain, the alarm test, the water supply pressure gage, and the push rod chamber supply connections. A wet pilot line, which extends up to the open deluge sprinkler grid, contains a closed sprinklers or other fixed temperature releases. When the closed sprinkler is activated and opened by a fire, the pilot line pressure

FM Approvals

1-108

September 2007 -- Approval Guide Automatic Sprinkler Systems

is released which opens the DDX valve, sending water to the sprinklers and sounding alarms. The Wet Pilot Trim set is used when the Reliable Model F1-FTR fixed temperature release is used in the wet pilot line, and/or when the Reliable Model A or B emergency stations/manual pull boxes can be used for releasing. The rated working pressure of the Wet Pilot Deluge System is 250 psi (1724 kPa). The Dry Pilot Trim. Set is used when a fixed temperature release is used in the dry pilot line. A dry pilot line, which extends up to the open deluge sprinkler grid, contains closed sprinklers or other fixed temperature releases. When a closed sprinkler is activated and opened by a fire, the pilot line pressure is released which opens the pneumatic actuator, which opens the DDX valve, sending water to the sprinklers and sounding alarms. The Reliable Model LP (low pressure) pilot line actuator is used in the dry pilot line and is designed for systems with water supply pressures from 20 psi (138 kPa) to 250 psi (1724 kPa), and corresponding dry pilot line pneumatic pressures, nominally, of 12 psi (83 kPa) to 24 psi (165 kPa). The system uses the Reliable Model A or B emergency stations/manual pull boxes which can be used for manual releasing. The rated working pressure of the Dry Pilot Deluge System is 250 psi (1724 kPa). The Electric Actuation Trim. Set is connected to the push rod chamber outlet and provides the 2 inch main drain, the alarm test, the water supply pressure gage, and the push rod chamber supply connections. The Reliable Model A or B emergency stations/manual pull boxes can be used for manual releasing. This system's Notifier RP 1001 Fire Alarm/Releasing Control Panel is utilized for the electric release and alarm functions. Only when there is an electrical signal to the releasing control panel from a fire detector, such as when a fixed temperature heat detector is activated, does the solenoid valve open which opens the DDX valve, sending water to the sprinklers. Only FM Approved fixed temperature heat devices shall be used in the release system and in the sprinkler piping. The control panel has an appropriately sized battery, Notifier Model PS 12120, to provide 90 hours of backup emergency power. The system utilizes the normally closed solenoid valve, Reliable P/N 6871020020. The rated working pressure of the Electric Actuation Deluge System is 250 psi (1724 kPa).

SES Enser Engineering, Via Carolina Romani 8/10, 20091 Bresso (MI), Italy

FARES Model F799DG-04A (wet pilot), FARES Model F799DG-04B (dry pilot), FARES Model F799DG-04C (electric). Consists of 3, 4, 6, 8 in. NPS FARES Model 799-DG04 automatic water control valve. FARES Models F799DG-04A and F799DG-04B have a rated working pressure of 300 psi (2070 kPa).

Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154

Star Deluge Sprinkler System. Consists of Model D water control valve, 3, 6 in. NPS. With 24 V dc operating coils. Star Hidromatic Deluge Sprinkler System. Consists of Model G, 3, 4, 6 in. NPS water control valve. Star Hidromatic Deluge Sprinkler System. Consists of Model G-1, 3, 4, 6 in. NPS water control valve. Model G-1 water control valves have an external reset feature. Systems are FM Approved for hydraulic, pnuematic or electric release trim. Rated working pressure is 250 psi (2070 kPa). Star Deluge Sprinkler System. Consists of Model F430 thermal control valve, 1, 11/2 in. NPS; Model B flooding valve, 2 in. NPS. Star Deluge Sprinkler System. Consists of Model B flooding valve, 2 in. NPS.

Total Walther GmbH, Feuerschutz und Sicherheit, Waltherstrasse 51, 51069 Koln, Germany ¨

Deluge Sprinkler System. Consists of Model EKFV water control valve. DN 200 mm. A spool piece containing a 2 in. (51 mm) drain valve is attached to the inlet flange of each valve.

Tyco Fire Products, 451 N Cannon Ave, Lansdale PA 19446

Model DV-1 water control valve. 4, 6 in. NPS. Model DV-3. 21/2 in. angle valve. Model DV-3HP. 21/2 in. angle valve. 250 psi (1725 kPa). Tyco Fire Products Deluge Sprinkler System. Consists of Model DV-5 water control valve in sizes 11/2, 2, 3, 4, 6 and 8 in. NPS (40, 50, 80, 100, 150 and 200 mm DN). Systems are FM Approved for hydraulic, pneumatic or electric release trim in both U.S. and European styles. Rated working pressure is 250 psi (1725 kPa). The pressure rating of electrically operated deluge sprinkler systems will be determined by the solenoid valve used. Systems using a Skinner Model No. 73218BN4UNLVN0C111C2 solenoid valve will be rated at 175 psi (1205 kPa). Systems using a Skinner Model No. 73212BN4TNLVN0C322C2 solenoid valve will be rated at 250 psi (1725 kPa). Model DV-5 water control valves are available with the following end connections:

Valve Size, inch (mm) End Connections

11/2, 2 (40, 50) 11/2, 2, 3, 4, 6, 8 (40, 50, 80, 100, 150, 200) 3, 4, 6, 8 (80, 100, 150, 200) 3, 4, 6, 8 (80, 100, 150, 200)

Threaded Grooved Flanged Flanged x Grooved

The Deluge Sprinkler Systems, with the DV-5 water control valve, is available factory assembled vertically inside the Model DV-5 Red-E Cabinet in sizes 11/2, 2, 3, 4, and 6 in. NPS. The Red-E cabinet and assembled system components comprise an integrated fire protection system which is assembled and tested at the factory. The cabinet contains: the system shutoff valve, Model DV-5 deluge valve, 24 Vdc battery backup, and an electrical control/release panel which is pre wired to the switches for the alarm, supervisory, and trouble functions. Installation requires the connection to the water inlet and outlet, main drain, electrical power supply, and the alarm and detection circuits. When dry pilot release is utilized, a built-in air compressor and air maintenance device provides controlled pilot line air pressure.

Tyco Fire Products, 3 Tyco Park, Exeter NH 03833

Tyco Deluge Sprinkler System. Consists of Model DV-2 flooding valve, 2 in. NPS. Tyco Electrospray Deluge Sprinkler System. Consists of Model DV-2 flooding valve, 2 in.

Victaulic Company, Box 31, Easton PA 18044

Series 758 FireLock Automatic Water Control Valves. Includes the Series 753-A pneumatic actuator for a dry pilot sprinkler line. Series 758-LPA FireLock Automatic Water Control Valves. Includes the Series 776 low pressure pneumatic actuator for a low pressure dry pilot sprinkler line, nominally 10 psi. Series 758 and Series 758-LPA available in sizes 11/2, 2, 21/2, 3, 4, 6, and 8 in. NPS, grooved inlet and outlet or flanged inlet and grooved outlet in 4, 6, and 8 in. NPS, vertical or horizontal orientation; sizes 76.1 and 165.1 mm NPS, grooved inlet and outlet, vertical or horizontal orientation. Both the Series 758 and 758-LPA include the Series 749 Auto Drain (pressure operated relief valve); the Series 755 manual pull station; the Series 748 Ball Check; the Series 729 Ball Drip; the optional Series 757 or Series 757-P air maintenance devices for a dry pilot sprinkler line. Rated working pressure is 300 psi (2069 kPa) except: for electric activation it is 175 psi (1207 kPa) with the ASCO Model No. 8210G207 solenoid valve; 300 psi (2069 kPa) with the Victaulic Series 753-E solenoid valve, except the 8 in. valves, which have a rated working pressure of 225 psi (1551 kPa). Series 769 Firelock NXT Deluge Valves with Dry Pilot Line Pneumatic Release. Sizes 11/2, 2, 21/2, 3, 4, 6 and 8 in. NPS. Grooved inlet and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following: · Series 776 Low Pressure Pneumatic Actuator with Auto Vent pressure operated system air pressure relief valve · Series 749 Auto Drain pressure operated piston charge line water relief valve; Series 729 alarm line Drip Check Valve

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-109

· · · · ·

Series 768 alarm line 3-Way Ball Valve for alarm/test/of Series 768 dry pilot line Air Manifold Assembly with integral restrictor/screen/anti-flood ball check valve Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections System Main Drain Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.

Optional system components include: · · · · · · · Regulated pilot line Air Maintenance Trim Assemblies Series 757 or 757-P (with pressure switch) Air Maintenance Devices System Sensor EPS10-2 alarm line pressure switch System Sensor EPS40-2 pilot line system air pressure supervisory switch Series 755 Manual Pull Station Series 760 Water Motor Alarm Series 705W water supply butterfly shutoff valve.

Series 769 Firelock NXT Deluge Valves with Wet Pilot Line Hydraulic Release. Sizes 11/2, 2, 21/2, 3, 4, 6 and 8 in. NPS. Grooved inlet and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following: · · · · · · Series 749 Auto Drain pressure operated piston charge line water relief valve Series 729 alarm line Drip Check Valve Series 768 alarm line 3-Way Ball Valve for alarm/test/off Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections System Main Drain Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.

Optional system components include: · · · · System Sensor EPS10-2 alarm line pressure switch Series 755 Manual Pull Station Series 760 Water Motor Alarm Series 705W water supply butterfly shutoff valve.

Series 769 Firelock NXT Deluge Valve with Electric Release. Sizes 11/2, 2, 21/2, 3, 4, 6 and 8 in. NPS. Grooved inlet and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following: · · · · · · · Series 753-E normally closed solenoid valve Series 749 Auto Drain pressure operated piston charge line water relief valve Series 729 alarm line Drip Check Valve Series 768 alarm line 3-Way Ball Valve for alarm/test/off Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections System Main Drain Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.

Optional system components include: · · · · System Sensor EPS10-2 alarm line pressure switch Series 755 Manual Pull Station Series 760 Water Motor Alarm Series 705W water supply butterfly shutoff valve.

The 11/2, 2, 21/2, 3, 4, and 6 in. NPS Deluge Sprinkler Systems are available factory assembled in the Victaulic Series 745 Fire-Pac enclosure, a cabinet containing all system components and accessories, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply. The Series 745 Fire-Pacs may be connected to Notifier AFP-200 Programmable Analog Fire control with software no. AFP2R2.42 or System Sensor PDRP-1001 fire control with operating system firmware revision level A. The AFP-200 control contains FMM-1 Module with a signaling line circuit which can be configured to meet Styles 4, 6 or 7 wiring performance as described in NFPA72. The addressable panels utilize model XP-10M module which may be configured at the factory to monitor the Fire-Pac cabinet and valve station. Optional LED Interface Module 4XTM and Relay Module RTM-8 provide outputs for auxiliary applications.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

Viking Deluge Sprinkler System*. Consists of Model E-1 or E-2 water control valve 2, 3**, 4** or 6 in. NPS, or Model F-1 or F-2 in-line globe water control valves 11/2, 2, 21/2, 3, 4, 6 or 8 in. NPS, or Model E-3 or E-4 water control valve 11/2 in. NPS; Model C-1 or C-2 emergency release; Model H-1 or R-1 pneumatic actuator; Model C-1 or C-2 thermostatic rate-of-rise release; Model C-1 pressure-operated relief valve (PORV); Model 07756, 07758, 09470 or 09471 pressure switch. Available with Speed Control Assembly trim option. Available with Easy Trim option utilizing Model A-1 or A-2 pressure shut-off valve (PSOV). Previous system ratings were dependent on the solenoid valve used. See table of related components shown under Automatic Water Control Valves. Model F-1 and F-2, in-line globe water control valves, 8 in. NPS, are available with grooved by grooved end connections or flanged by flanged end connections. Model F-1 or F-2 in-line globe water control valves, 3, 4, and 6 in. NPS, are available with grooved by grooved, flanged by flanged end, or flanged inlet by grooved outlet connections. Model F-1 or F-2 in-line globe water control valves, 11/2, 2 and 21/2 in. NPS, are available with grooved by grooved, or screwed end connections. Deluge Sprinkler Systems are available factory assembled in the Viking Total Pac enclosure, in sizes 11/2 through 6 in. NPS with electric, pneumatic (dry pilot), and hydraulic (wet pilot) releases. The Total Pac enclosure and assembled valve systems comprise an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply.

**Available with ISO flanges (P/N 10 and P/N 16).

Deluge Sprinkler Systems, which utilize the angle type main water control valves, are available factory assembled in the Viking Total Pac2 enclosure, a second generation enclosure which replaces the Total Pac. The Total Pac2 is available in several configurations: 1) the system

FM Approvals

1-110

September 2007 -- Approval Guide Automatic Sprinkler Systems

fully enclosed on legs with an access door and a built in electrical control panel (when electric activation required); 2) the valve system fully enclosed on legs with an access door and a remote control panel; 3) the valve system assembled to a skid and used with a remote control panel. All Deluge Sprinkler Systems are available with the TrimPac package in both conventional and Easy Trim configurations.

PREACTION SPRINKLER SYSTEMS

Preaction systems are equipped with automatic sprinklers and are used where it is important to prevent the accidental discharge of water. These systems may also be used where an alarm is desired in advance of sprinkler operation or where it is desired to minimize the water delivery delay inherent in a standard dry-pipe system. For this reason, the following factors must be carefully assessed: detector spacing and sensitivity, sprinkler piping arrangement and ceiling construction. Supervisory air pressure is maintained in the sprinkler piping of a preaction sprinkler system. A trouble alarm sounds if the supervisory air pressure is not maintained; however, such a condition will not cause the automatic water control valve to operate. Generally, a single check valve is installed downstream of the automatic water control valve to contain the supervisory air pressure. Except for the addition of a single check valve and the use of automatic sprinklers, components of preaction sprinkler systems are identical or similar to those of deluge sprinkler systems. The water supply is held back by a water control valve which is operated manually or automatically by the actuation of a fire detection system. The fire detection system is required to be one of the following types: hydraulic rate-of-rise, pneumatic rate-of-rise or electric. FM Approved combinations of control valves and fire detection system(s) are listed under AUTOMATIC WATER CONTROL VALVES. Electrically operated preaction sprinkler systems are FM Approved on a component basis. Only the major, compatible components listed for a specific valve under AUTOMATIC WATER CONTROL VALVES shall be used in designing an FM Approved system. FM Global installation acceptance may stipulate that only heat-actuated fire detection devices be used. Acceptance criteria by other jurisdictional authorities may vary. Preaction sprinkler systems identified in the listing by an asterisk (*) have either hydraulic or pneumatic rate-of-rise fire detection and are FM Approved as complete systems. Only the listed components for a specific manufacturer shall be used in an FM Approved system.

Anber Globe SA, Av de Las Flores 13, Parque Ind El Molino, 28970 Humanes de Madrid, Madrid Spain

Preaction Sprinkler System consists of Model A 21/2 in. NPS and Models B and BX 4 or 6 in. NPS water control valves and Approved rubber faced check valve. Model BX water control valves have an external reset feature. Systems are Approved for hydraulic, pneumatic or electric releasing means. Preaction Sprinkler Systems utilizing electric releasing means are available factory assembled in the PrePak enclosure and the Model BX PrePak Preaction System, utilizing a size 4 or 6 in. Model BX deluge valve. The PrePak enclosure and assembled valve systems comprise an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply. Preaction Sprinkler System, a Supertrol Single Interlock Preaction, consists of Model DDX Deluge Valves in sizes 4 in. and 6 in. (100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. Model DDX valves have grooved inlet and grooved outlet end connections. The system utilizes low pressure, nominally 2 psi (13.8 kPa), sprinkler system supervisory air pressure to activate alarms, with electric activation for a valve trip. A loss of system air pressure, such as when a sprinkler activates, will not open the Model DDX valve but causes the low pressure alarm to sound. Only when there is also an electrical signal to the releasing control panel from a fire detector, such as when a fixed temperature heat detector is activated, does the solenoid valve open which opens the DDX valve, sending water to the sprinklers. The Model A or B emergency stations/manual pull boxes can be used for manual releasing. This system's Notifier RP 1001 Fire Alarm/Releasing Control Panel is utilized for the electric release and alarm functions. The release solenoid valve is P/N 6871020020. Only FM Approved fixed temperature heat devices shall be used in the release system and in the sprinkler piping. The control panel has an appropriately sized battery, Notifier Model PS 12120, to provide 90 hours of backup emergency power. The rated working pressure of the Supertrol Single Interlock Preaction System is 250 psi (1724 kPa).

Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446

Central Preaction Sprinkler System. Consists of Model B, 4 in. NPS water control valve and FM Approved rubber-faced check valve.

Cla-Val Company, Box 1325, Newport Beach CA 92659

Preaction Sprinkler System consists of Model 834 automatic water control valve, Model H&A 150-200-BNHA pilot valve and Skinner Model 71395SN2ENJ1NOH111C2 solenoid valve. Sizes 4, 6, 8,10 in. NPS. 250 psi (1725 kPa) rated working pressure.

Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620

``Automatic'' Suprotex Preaction Sprinkler System*. Consists of Model C, 21/2, 6 in. water control valve; FM Approved rubber-faced check valve; 1/8 in. circuit tubing with the following Heat Actuated Devices (HADs): 87-500B, 87-550, 87-580, 87-590, 87-530A, 87-540A, 87-560, 87-570; No. 90-100 compensating vent; Nos. 81-100A, 83-100A releases; Nos. 81-600A, 83-600 secondary releases (only acceptable when rate-of-rise circuits are a secondary means of system activation); Model 70-200 break glass station; manual pull handle; Model 64-100G manual pull station; No. 148-100C air pump panel; No. 2403C2H low pressure regulator; No. 79-904B or 79-904C low pressure alarm switch; No. 79-340A air dryer; No. 39-713 drum drip or No. 79-943C reservoir; No. 1621 high pressure regulator; No. 148-250 restriction orifice; No. 79-840B air line mercury check; No. 121 mercury check; No. S76-650 weight switch; Model 94-160 low pressure actuator; emergency release (quick opening valve); Model 123-100 hydropneumatic control. ``Automatic'' Preaction Sprinkler System. Consists of Model D, F water control valves, 21/2, 4, 6 in. with FM Approved rubber-faced check valve or Model E water control valve, 6 in. equipped with Viking Model C-1 pressure-operated relief valve and FM Approved rubber-faced check valve.

Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658

Consists of Model F Water Control Valve. 21/2, 4, 6 in. with FM Approved water-faced check valve. Consists of Model D1.5, 11/2 in. NPS, and Model D2, 2 in. NPS, Water Control Valves.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-111

Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Grinnell or Gem Multitrol Preaction Sprinkler System*. Consists of Model C, 21/2, 6 in. water control valve; FM Approved rubber-faced check valve; 1/8 in. circuit tubing with the following Heat Actuated Devices (HADs): 87-500B, -550, -580, -590, -530A, -540A, -560, -570; No. 90-100 compensating vent; Nos. 81-100A, 83-100A releases; Nos. 81-600A, 83-600 secondary releases (only acceptable when rate-of-rise circuits are a secondary means of system activation); Model 70-200 break glass station; manual pull handle; Model 64-100G manual pull station; No. 148-100C air pump panel; No. 2403C2H low pressure regulator; No. 79-904B or -904C low pressure alarm switch; No. 79-340A air dryer; No. 39-713 drum drip or No. 79-943C reservoir; No. 1621 high pressure regulator; No. 148-250 restriction orifice; No. 79-840B air line mercury check; No. 121 mercury check; No. S76-650 weight switch; Model 94-160 low pressure actuator; emergency release (quick opening valve); Model 123-100 hydropneumatic control. Grinnell or Gem Electrospray Preaction Sprinkler System. Consists of Model A-4, 4, 6 in. water control valve or Model B, 2 in. flooding valve and FM Approved rubber-faced check valve. Grinnell or Gem Model F445. 21/2 in. angle valve and FM Approved rubber-faced check valve.

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Preaction Sprinkler System consists of Model A, 21/2 in. NPS and Models B and BX 4 or 6 in. NPS water control valves and FM Approved rubber-faced check valve. Model BX, in sizes 4 and 6 in., as well as 100 and 150 mm NPS, water control valves have an external reset feature. Systems are FM Approved for hydraulic, pneumatic or electric releasing means. Preaction Sprinkler Systems utilizing electric releasing means are available factory assembled in the Reliable PrePak enclosure, both the Model A PrePak Preaction System, size 21/2 in., and the Model BX PrePak Preaction System, utilizing a size 4 or 6 in. Model BX deluge valve. The PrePak enclosure and assembled valve systems comprise an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply. Preaction Sprinkler Systems. A Supertrol Single Interlock Preaction, consists of Model DDX Deluge Valves in sizes 4 in. and 6 in. (100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. Model DDX valves have grooved inlet and grooved outlet end connections. The system utilizes low pressure, nominally 2 psi (13.8 kPa), sprinkler system supervisory air pressure to activate alarms, with electric activation for a valve trip. A loss of system air pressure, such as when a sprinkler activates, will not open the Model DDX valve but causes the low pressure alarm to sound. Only when there is also an electrical signal to the releasing control panel from a fire detector, such as when a fixed temperature heat detector is activated, does the solenoid valve open which opens the DDX valve, sending water to the sprinklers. The Reliable Model A or B emergency stations/manual pull boxes can be used for manual releasing. This system's Notifier RP 1001 Fire Alarm/Releasing Control Panel is utilized for the electric release and alarm functions. The release solenoid valve is the Reliable P/N 6871020020. Only FM Approved fixed temperature heat devices shall be used in the release system and in the sprinkler piping. The control panel has an appropriately sized battery, Notifier Model PS 12120, to provide 90 hours of backup emergency power. The rated working pressure of the Supertrol Single Interlock Preaction System is 250 psi (1724 kPa).

Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154

Star Preaction Sprinkler System. Consists of Model G Hidromatic, 4 in. NPS water control valve and FM Approved rubber-faced check valve. Star Preaction Sprinkler System. Consists of Model B, 2 in. flooding valve and FM Approved rubber-faced check valve.

Tyco Fire Products, 451 N Cannon Ave, Lansdale PA 19446

Model DV-1. 4, 6 in. NPS water control valve and FM Approved rubber-faced check valve. Model DV-3. 21/2 in. angle valve and FM Approved rubber-faced check valve. Tyco Fire Products Preaction Sprinkler System. Consists of Model DV-5 water control valve in sizes 11/2, 2, 3, 4 and 6 in. NPS (40, 50, 80, 100, 150 and 200 DN) with an Approved rubber faced check valve. Systems are FM Approved with trim in both U.S. and European styles. Rated working pressure is 250 psi (1725 kPa). Model DV-5 water control valves are available with the following end connections:

Valve Size, inch (mm) End Connections

11/2, 2 (40, 50) 11/2, 2, 3, 4, 6, 8 (40, 50, 80, 100, 150, 200) 3, 4, 6, 8 (80, 100, 150, 200) 3, 4, 6, 8 (80, 100, 150, 200)

Threaded Grooved Flanged Flanged × Grooved

The Preaction Systems, with the DV-5 water control valve, are available factory assembled vertically inside the Model DV-5 Red-E Cabinet in sizes 11/2, 2, 3, 4, and 6 in. NPS. The Red-E cabinet and assembled system components comprise an integrated fire protection system which is assembled and tested at the factory. The cabinet contains: the system shutoff valve, Model DV-5 deluge valve, 24 Vdc battery backup, and an electrical control/release panel for the solenoid valve release. The control panel is prewired to the switches for the alarm, supervisory, and trouble functions. Installation requires the connection to the water inlet inlet and outlet, main drain, electrical power supply, and the alarm and detection circuits. A built-in air compressor and air maintenance device provides controlled system air pressure.

Tyco Fire Products, 3 Tyco Park, Exeter NH 03833

Tyco Electrospray Preaction Sprinkler System. Consists of Model DV-2, 2 in. flooding valve and FM Approved rubber-faced check valve.

Victaulic Company, Box 31, Easton PA 18044

Series 758-LPA FireLock Automatic Water Control Valve, electric release, available in sizes 11/2, 2, 21/2, 3, 4, 6, and 8 in. NPS, grooved inlet and grooved outlet, and flanged inlet and grooved outlet in sizes 4, 6, and 8 in. NPS, vertical or horizontal orientation; sizes 76.1 and 165.1 mm NPS, grooved inlet and grooved outlet, vertical or horizontal orientation. The 758-LPA includes the Series 776 pneumatic actuator for low pressure, nominally 10 psi, supervised system pressure. Series 749 Auto Drain (pressure operated relief valve); the Series 755 manual pull station; the Series 748 Ball Check; the Series 729 Ball Drip; the optional Series 757 or Series 757-P air maintenance devices for a dry pilot sprinkler line. Rated working pressure is 300 psi (2069 kPa) except: for electric activation it is 175 psi (1207 kPa) with the ASCO Model No. 8210G207 solenoid valve; 300 psi (2069 kPa) with the Victaulic Series 753-E solenoid valve, except the 8 in. valves, which have a rated working pressure of 225 psi (1551 kPa). The Series 75-D Water Column Drain Kit is an option, which automatically drains water from the sprinkler system and subsequently reseals to maintain air pressure in the system piping. Series 769 Firelock NXT Single-Interlocked Valve with Electric Release. Sizes 11/2, 2, 21/2, 3, 4, 6 and 8 in. NPS. The system rated working pressure is 300 psi (2070 kPa). Grooved inlet and grooved outlet, installed vertically. Major trim components consist of the following: · Series 753-E normally closed solenoid valve · Series 749 Auto Drain pressure operated piston charge line water relief valve

FM Approvals

1-112

September 2007 -- Approval Guide Automatic Sprinkler Systems

· · · · · ·

Series 748 anti-flood Ball Check Valve Series 729 alarm line Drip Check Valve Series 768 alarm line 3-Way Ball Valve for alarm/test/off Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections System Main Drain Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.

Optional system components include: · · · · · System Sensor EPS10-2 alarm line pressure switch System Sensor EPS40-2 system air pressure supervisory switch Series 755 Manual Pull Station Series 760 Water Motor Alarm Series 705W water supply butterfly shutoff valve.

All preaction sprinkler systems discussed above offer the Series 75-B supplemental alarm valve as an option recommended for systems where continuous flow to the alarm port, which supplies flow to the water motor alarm, must be positively maintained. Some Preaction Sprinkler Systems are available factory assembled in the Victaulic Series 745 Fire-Pac enclosure, a cabinet containing all system components and accessories, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply. The Series 745 Fire-Pacs may be connected to Notifier AFP-200 Programmable Analog Fire control with software no. AFP2R2.42 or System Sensor PDRP-1001 fire control with operating system firmware revision level A. The AFP-200 control contains FMM-1 Module with a signaling line circuit which can be configured to meet Styles 4, 6 or 7 wiring performance as described in NFPA72. The addressable panels utilize model XP-10M module which may be configured at the factory to monitor the Fire-Pac cabinet and valve station. Optional LED Interface Module 4XTM and Relay Module RTM-8 provide outputs for auxiliary applications.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

Viking Preaction Sprinkler System. Consists of Model E-1 or E-2 water control valve, 2, 3, 4, 6 in. NPS, or in-line globe Model F-1 or F-2 water control valves,11/2, 2, 21/2, 3, 4, 6 or 8 in. NPS, or Model E-3 or E-4 water control valve 11/2 in. NPS; Model C-1 or C-2 emergency release; Model H-1 or R-1 pneumatic actuator; Model C-1 or C-2 thermostatic rate-of-rise release; Model C-1 pressure-operated relief valve (PORV); Model 07756, 07758, 09470 or 09471 pressure switch; Model 07757, 07821, 07759, 07822, 09472 or 09473 air supervisory switch; FM Approved rubber-faced check valve. Available with Speed Control Assembly trim option. Available with Easy Trim option utilizing Model A-1 or A-2 pressure shut-off valve (PSOV). Available with TrimPac trim package in both conventional and Easy Trim configurations. Previous system ratings were dependent on the solenoid valve used. See table of related components shown under Automatic Water Control Valves. Model F-1 and F-2, in-line globe water control valves, 8 in. NPS, are available with grooved by grooved end connections or flanged by flanged end connections. Model F-1 or F-2 in-line globe water control valves, 3, 4, and 6 in. NPS, are available with grooved by grooved, flanged by flanged end, or flanged inlet by grooved outlet connections. Model F-1 or F-2 in-line globe water control valves, 11/2, 2 and 21/2 in. NPS, are available with grooved by grooved, or screwed end connections. Preaction Sprinkler Systems are available factory assembled in the Viking Total Pac enclosure, in sizes 11/2 through 6 in. NPS with electric release. The Total Pac enclosure and assembled valve systems comprise an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply. Sprinkler System. Sure Fire Fail/Safe supervised dry system using a deluge valve controlled by a electric release system and pneumatic system pressure. Consists of angle type water control valves Model E-1 or E-2, in sizes 2, 3, 4, and 6 in. NPS, or Model E-3 or E-4 in size 1/2 in. NPS; or in-line Model F-1 or F-2 globe type water control valve in sizes 11/2, 2, 21/2, 3, 4, 6, and 8 in. NPS; strainer; restricted orifice 1 with 0.063 in. (1.6 mm) dia. orifice; Model B-1 Release control Panel, equipped with an appropriately sized battery to provide 90 hours of emergency power, equipped capable of cross zoned operation with FM Approved compatible pressure switch and heat actuated device; FM Approved solenoid valves include the normally open Viking Model 11595, the normally closed Viking Model 11591, the normally open explosion proof Viking Model 11596, the normally closed explosion proof Viking Model 11592; or N.C. Solenoid Valve, Viking P/N 11591 and N.O. Solenoid Valve, Viking P/N 13215 for 250 psi (1725 kPa) rated working pressure. Pneumatic actuators Model H-1 or R-1; Model C-1 or C-2 emergency releases; dual SPDT Model 09473 air supervisory switch; Model 09470 or Model 09471 pressure switch; dehydrator P/N 01285A; Model D-2 air pressure maintenance device; available with Easy Trim option, utilizing a Model A-1 or A-2 pressure shut-off valve (PSOV); trim available in galvanized, brass or stainless steel piping; FM Approved rubber-faced system check valve. Available with TrimPac trim package in Easy Trim configuration. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping. Model F-1 and F-2 valves are capable of vertical installation. Same valve end connections as noted above. Rated working pressure 250 psi (1725 kPa); piping above the riser check valve contains supervisory air pressure at 30-50 psi (205-345 kPa) to monitor system integrity. If the system piping is damaged, the low air pressure alarm is activated and the normally open solenoid valve is activated closed but the main water control valve does not trip and no water flows into the sprinkler system until the heat detection device is actuated. This causes the normally closed solenoid valve to open which activates the control valve and water flow is supplied to the sprinkler system. Also when heat detector is activated by fire, the main control valve operates supplying water to the sprinkler system. In loss of power condition, the system operates from system supervisory air and the pneumatic actuator. Preaction Sprinkler Systems, which utilize the angle type main water control valves, are available factory assembled in the Viking Total Pac2 enclosure, a second generation enclosure which replaces the Total Pac. The Total Pac2 is available in several configurations: 1) the system fully enclosed on legs with an access door and a built in electrical control panel (when electric activation required); 2) the valve system fully enclosed on legs with an access door and a remote control panel; 3) the valve system assembled to a skid and used with a remote control panel.

REFRIGERATED AREA SPRINKLER SYSTEMS

A refrigerated area sprinkler system affords fire protection in refrigerated rooms or buildings and includes special safeguards against accidental filling with water and subsequent freezing of the system. A fire detection system must actuate and one or more automatic sprinklers in the piping must operate before water will enter the sprinkler system. An alarm sounds if the detection system only is actuated while pneumatic pressure is maintained in the sprinkler piping. An alarm also sounds if the pneumatic pressure in the sprinkler piping is not properly maintained. In either case, water does not enter the system piping. These systems should be installed in accordance with FM Global Loss Prevention Data Sheet 8-29, ``Refrigerated Storage''. System calculations regarding required system air capacity should be performed if only one air maintenance device is contemplaed for several sprinkler systems.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-113

Refrigerated area sprinkler systems which are operated pneumatically/hydraulically are FM Approved as complete systems. Only the listed components for a given system may be used in combination. Fire detection systems which are operated electrically are FM Approved on a component basis. Only compatible components may be used in combination.

Anber Globe SA, Av de Las Flores 13, Parque Ind El Molino, 28970 Humanes de Madrid, Madrid Spain

Type A Supertrol Refrigerated Area System. Double interlocked supervised refrigerated area sprinkler system, controlled by an electric release system and pneumatic system pressure. Consists of a Model B or BX deluge valve (4, 6 in. NPS), compatible solenoid valve, Model A dry pilot actuator, Model B1 or A2, air pressure maintenance device, Model A hydraulic manual pull box, or Model B manual emergency station, United Electric switch Models J54-8300 and J54-8295 or system sensor EPS10 and EPS40 series pressure alarm switches, Approved rubber faced check valve and an Approved compatible automatic release control panel with appropriately sized battery to provide 90 hours emergency power. Only Approved fixed temperature heat sensitive devices shall be used in the release system and in the sprinkler piping. Type D Supertrol Refrigerated Area System. Double interlocked supervised refrigerated area sprinkler system, controlled by an electric release system and pneumatic system pressure. Consists of a Model B or BX deluge valve (4, 6 in. NPS) or Model A deluge valve (21/2 in. NPS), compatible solenoid valve, Model B1, or A2, air pressure maintenance device, Model A hydraulic manual pull box, or Model B manual emergency station, United Electric switch Models J54-8300 and J54-8295 or system sensor EPS10 and EPS40 series pressure alarm switches, Approved rubber faced check valve and an Approved compatible automatic release control panel capable of cross-zone operation with appropriately sized battery to provide 90 hours emergency power. Only Approved fixed temperature heat sensitive devices shall be used in the release system and in the sprinkler piping. Type D Supertrol Refrigerated Area Sprinkler Systems are available factory assembled in the PrePak enclosure and the Model BX PrePak Refrigerated Area Sprinkler System, utilizing a size 4 or 6 in. Model BX deluge valve. The PrePak enclosure and assembled valve systems comprise an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply. Supertrol Type D Double Interlock Preaction System, pneumatic-electric/electric, consists of Model DDX Deluge Valves in sizes 4 in. and 6 in. (100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. Model DDX valves have grooved inlet and grooved outlet end connections. The system utilizes low pressure, nominally 10 psi (69 kPa), sprinkler system supervisory air pressure and a cross-zoned releasing control panel such that two electrical signals must energize two control panel initiating circuits before water flows through the valve. A loss of system air pressure, such as when a sprinkler activates, activates the EPS10-2 pressure switch and provides one signal to the control panel. An electrical signal from a fire detector, such as when a fixed temperature heat detector is activated, provides the other signal to the control panel. The two signals open the solenoid valve, P/N 6871020020, and results in flow out the sprinklers. The Model A or B emergency stations/manual pull boxes can be used for manual releasing. The Model B1 accelerator is an available option for use with this system. In the event that water builds up inside the deluge valve due to condensate from the air supply system or water from a valve trip, a drain valve is provided to drain the valve body and riser. This system's Notifier RP 1001 Fire Alarm/Releasing Control Panel, adjusted for cross-zoned operation, is utilized for the electric release and alarm functions. Only FM Approved fixed temperature heat devices shall be used in the release system and in the sprinkler piping. The control panel has an appropriately sized battery, Notifier Model PS 12120, to provide 90 hours of backup emergency power. The rated working pressure of the Supertrol Type D Double Interlock Preaction System is 250 psi (1724 kPa). Supertrol Type F Double Interlock Preaction System, pneumatic/electric, consists of Model DDX Deluge Valves in sizes 4 in. and 6 in. (100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. Model DDX valves have grooved inlet and grooved outlet end connections. The Type F system is designed for systems with water supply pressures from 20 psi (138 kPa) to 250 psi (1724 kPa), and corresponding sprinkler system pneumatic pressures, nominally, of 12 psi (83 kPa) to 24 psi (165 kPa). A loss of system air pressure, such as when a sprinkler activates, opens the Model LP (low pressure) pilot line actuator causing the low pressure alarm to sound, but the DDX valve remains closed. The system utilizes the System Sensor EPS10-2 pressure alarm switch. Only when there is also an electrical signal to the releasing control panel from a fire detector, such as when a fixed temperature heat detector is activated, does the solenoid valve, P/N 6871020020, open which opens the DDX valve, sending water to the sprinklers. The Model A or B emergency stations/manual pull boxes can be used for manual releasing. The Model B1 accelerator is an available option for use with this system. In the event that water builds up inside the deluge valve due to condensate from the air supply system or water from a valve trip, a drain valve is provided to drain the valve body and riser. This system's Notifier RP 1001 Fire Alarm/ Releasing Control Panel is utilized for the electric release and alarm functions. Only FM Approved fixed temperature heat devices shall be used in the release system and in the sprinkler piping. The control panel has an appropriately sized battery, Notifier Model PS 12120, to provide 90 hours of backup emergency power. The rated working pressure of the Supertrol Type F Double Interlock Preaction System is 250 psi (1724 kPa).

Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446

Model A Refrigerated Area System. Double interlocked, supervised refrigerated area sprinkler system controlled by an FM Approved control panel cross-zoned with compatible FM Approved pressure switch and heat actuated devices. Consists of automatic water control valve Model A, 4, 6 in. NPS, Skinner Model 73218BN4UNLVN0C111C2, 24 V dc solenoid valve, Potter Model PS10-2A pressure switch, shotgun Model 90 check valve, Central Model D-1 or D-U1 air maintenance device, and an FM Approved release control panel compatible with solenoid valve capable of cross-zoned operation with appropriately sized battery to provide 90 hours of emergency power. Only FM Approved fixed temperature heat sensitive devices shall be used in the release system and in the sprinkler piping. Sprinkler System. Double interlocked, uses a deluge valve controlled by an electronic release system and pneumatic system pressure. Consists of automatic water control valve Model C, 3, 4, 6 in. NPS with 3/32 in. diaphragm chamber orifice, Skinner LV2LBX25 or 73218BN4UNLVNOC111C2 solenoid valve, Star Model AA-R actuator, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours of emergency power; United Electric Control Co Models J54-8300 and J54-8295 pressure alarm switches; Tyco Model MC-1 manual control station. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping. Sprinkler System. Double interlocked, uses a deluge valve controlled by an electric release system and pneumatic system pressure. Consists of automatic water control valve Model C-1, 3, 4, 6 in. NPS with 3/32 in. diaphragm chamber orifice, Skinner 73212BN4TNLVNOC322C2 solenoid valves, Tyco Model DP-1 dry pilot actuator, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours of emergency power; United Electric Control Co Models J54-8300 and J54-8295 pressure alarm switches; Tyco Model MC-1 manual control station. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping.

Cla-Val Company, Box 1325, Newport Beach CA 92659

Sprinkler System. Double interlocked, uses a deluge valve controlled by an electric release system and pneumatic system pressure. Consists of automatic water control valve Model 834 in sizes 4, 6, 8,10 in. NPS, Model H&A 150-200-BNHA pilot valve, Skinner Model 71395SN2ENJ1NOH111C2 three-way solenoid valve, compatible Approved automatic release control panel with appropriately sized battery to provide 90 hours of emergency power, Approved pressure alarm switch. Only Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping.

FM Approvals

1-114

September 2007 -- Approval Guide Automatic Sprinkler Systems

Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Grinnell or Gem Duomatic Dry System. Double interlocked, uses a deluge valve controlled by an electric release system and pneumatic system pressure. Consists of automatic water control valve Model A-4, 4, 6 in. NPS; Tyco Model DP-1 dry pilot actuator; Tyco Model MC-1 manual control station; Potter Model PS10-1, pressure alarm switch; Potter Model PS40-1 low air pressure alarm switch; 1/2 in. NPS Skinner Models LV2LBX25 or 73218BN4UNLVNOC111C2 or ASCO Models R8210A107 or 8210G207, 24 V dc solenoid valve; compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours emergency power; FM Approved rubber faced check valve. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping. Grinnell or Gem Double Interlocked System. Uses an automatic water control valve controlled by an electric release system and pneumatic system pressure. Consists of Tyco Model DV-1 valve in 4 and 6 in. NPS, Tyco Model DP-1 dry pilot actuator, 1/2 in. NPS Skinner Models LV2LBX25 or 73218BN4UNLVNOC111C2, 24 V dc solenoid, or 1/2 in. NPS ASCO Models 8210G207, T8210A107, R8210A107, or 8210A107, 24 V dc solenoid valve, F520 check valve, Tyco Model MC-1 manual control station, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours emergency power. An FM Approved Tyco Fire Products Model ACC-1 accelerator trimmed to act as an exhauster may be used as an option. Grinnell or Gem Double Interlocked System. Uses an automatic water control valve controlled by an electric release system and pneumatic system pressure. Consists of Tyco Model DV-1 valve in 4 and 6 in. NPS, Potter Model PS10-2A Pressure Alarm Switch, 1/2 in. NPS Skinner Models LV2LBX25 or 73218BN4UNLVNOC111C2, 24 V dc solenoid, or 1/2 in. NPS ASCO Models 8210G207, T8210A107, R8210A107, or 8210A107, 24 V dc solenoid valve, F520 check valve, Tyco Model MC-1 manual control station, compatible FM Approved automatic release control panel capable of cross-zone operation, with appropriately sized battery to provide 90 hours emergency power. An FM Approved Tyco Fire Products Model ACC-1 accelerator trimmed to act as an exhauster may be used as an option. Grinnell or Gem Double Interlocked System. Uses an automatic water control valve controlled by an electric release system and pneumatic system pressure. Consists of F445 valve in 21/2 in. NPS, Potter Model PS10-2A Pressure Alarm Switch, 1/2 in. NPS Skinner Models LV2LBX25 or 73218BN4UNLVNOC111C2, 24 V dc solenoid, or 1/2 in. NPS ASCO Models 8210G207, T8210A107, R8210A107, or 8210A107, 24 V dc solenoid valve, F52 check valve, Tyco Model MC-1 manual control station, compatible FM Approved automatic release control panel capable of cross-zone operation, with appropriately sized battery to provide 90 hours emergency power, and Viking PORV valve. Grinnell or Gem Double Interlocked System. Uses an automatic water control valve controlled by an electric release system and pneumatic system pressure. Consists of F445 valve in 21/2 in. NPS, Tyco Model DP-1 dry pilot actuator, 1/2 in. NPS Skinner Models LV2LBX25 or 73218BN4UNLVNOC111C2, 24 V dc solenoid, or 1/2 in. NPS ASCO Models 8210G207, T8210A107, R8210A107, or 8210A107, 24 V dc solenoid valve, F52 check valve, Tyco Model MC-1 manual control station, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours emergency power, and Viking PORV valve.

Magisco Valves Ltd, 53 Limes Rd, Tettenhall, Wolverhampton WV6 8RD, United Kingdom

Sprinkler System. Double interlocked, uses a deluge valve controlled by an electric release system and pneumatic system pressure. Consists of 3, 4, 6, 8 in. NPS MAG Model M799DG-04K automatic water control valve, Model 284-08 3-way pilot, Model 377 pneumatic actuator, Model 379 air reset unit, Model 375 flow release pilot, Skinner Model 73218BN4UNLVN0C111C2 or ASCO Model 8210G207, 24 V dc solenoid valve, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours of emergency power. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping.

Mil Ltd, 17 Moshe Beker St, Box 15200, Rishon Lezion 75051, Israel

Sprinkler System. Double interlocked, uses a deluge valve controlled by an electric release system and pneumatic system pressure. Consists of 3, 4, 6, 8 in. NPS INBAL Model 799-DG04-K automatic water control valve, Model 284-08 3-way pilot, Model 377 pneumatic actuator, Model 379 air reset unit, Model 375 flow release pilot, Skinner Model 73218BN4UNLVN0C111C2 or ASCO Model 8210G207, 24 V dc solenoid valve, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours of emergency power. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping.

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Type A Supertrol Refrigerated Area System. Double interlocked supervised refrigerated area sprinkler system, controlled by an electric release system and pneumatic system pressure. Consists of a Reliable Model B or BX, in sizes 4 and 6 in., as well as 100 and 150 mm NPS, water control valve, compatible solenoid valve, Reliable Model A dry pilot actuator, Reliable Model B1, or A2, air pressure maintenance device, Reliable Model A hydraulic manual pull box, or Model B manual emergency station, United Electric switch Models J54-8300 and J54-8295 or system sensor EPS10 and EPS40 series pressure alarm switches, FM Approved rubber faced check valve and an FM Approved compatible automatic release control panel with appropriately sized battery to provide 90 hours emergency power. Only FM Approved fixed temperature heat sensitive devices shall be used in the release system and in the sprinkler piping. Type D Supertrol Refrigerated Area System. Double interlocked supervised refrigerated area sprinkler system, controlled by an electric release system and pneumatic system pressure. Consists of a Reliable Model B or BX, in sizes 4 and 6 in., as well as 100 and 150 mm NPS, or Reliable Model A deluge valve (21/2 in. NPS), compatible solenoid valve, Reliable Model B1, or A2, air pressure maintenance device, Reliable Model A hydraulic manual pull box, or Model B manual emergency station, United Electric switch Models J54-8300 and J54-8295 or system sensor EPS10 and EPS40 series pressure alarm switches, FM Approved rubber faced check valve and an FM Approved compatible automatic release control panel capable of cross-zone operation with appropriately sized battery to provide 90 hours emergency power. Only FM Approved fixed temperature heat sensitive devices shall be used in the release system and in the sprinkler piping. Type D Supertrol Refrigerated Area Sprinkler Systems are available factory assembled in the Reliable PrePak enclosure, both the Model A PrePak Refrigerated Area Sprinkler System, size 21/2 in., and the Model BX PrePak Refrigerated Area Sprinkler System, utilizing a Model BX deluge valve, in sizes 4 and 6 in., as well as 100 and 150 mm NPS. The PrePak enclosure and assembled valve systems comprise an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply. Type F Supertrol Refrigerated Area System. Double interlocked supervised refrigerated area sprinkler system, controlled by an electric solenoid valve release in series with a pneumatic pressure release pneumatic actuator. Consists of a Reliable Model B or BX Deluge valve, a Model G Right-Check riser valve, both in sizes of 4 or 6 in. NPS, as well as in sizes 100 and 150 mm NPS. Model B or BX Deluge valves have ANSI flanged inlets and grooved outlets. Model G Right-Check riser valves have grooved inlets and outlets. Also utilized are: a Reliable Model LDX pneumatic actuator, Reliable Models B-2 or A-2 air pressure maintenance devices, a Reliable Model B manual emergency pull station, a System Sensor EPS 10-1 pressure switch, or a United Electric J54-A-8300, forlow air pressure supervision, and a System Sensor EPS 10-2, or a United Electric J54-A-8295, for water flow indication. The Reliable Model B1 accelerator is an available option for use with this system. This system's Notifier RP 1001 Fire Alarm/Releasing Control Panel is utilized for the electric release and alarm functions. Only FM Approved fixed temperature heat devices shall be used in the release system and in the sprinkler piping. The control panel has a appropriately sized battery, Notifier Model PS 12120, to provide 90 hours emergency power. Compatible 24Vdc energized NC solenoid valves are listed in the ``Automatic Water Control Valve'' section of this Guide. System rated working pressure is 175 psi. The Type F Supertrol Refrigerated Area Sprinkler Systems are available factory assembled in the the PrePak enclosure. The PrePak enclosure integrates the complete fire protection system in a cabinet which is assembled and tested at the factory, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply. Supertrol Type D Double Interlock Preaction System. Pneumatic-electric/electric, consists of Model DDX Deluge Valves in sizes 4 in. and 6 in. (100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-115

clapper. Model DDX valves have grooved inlet and grooved outlet end connections. The system utilizes low pressure, nominally 10 psi (69 kPa), sprinkler system supervisory air pressure and a cross-zoned releasing control panel such that two electrical signals must energize two control panel initiating circuits before water flows through the valve. A loss of system air pressure, such as when a sprinkler activates, activates the EPS10-2 pressure switch and provides one signal to the control panel. An electrical signal from a fire detector, such as when a fixed temperature heat detector is activated, provides the other signal to the control panel. The two signals open the solenoid valve, Reliable P/N 6871020020, and results in flow out the sprinklers. The Reliable Model A or B emergency stations/manual pull boxes can be used for manual releasing. The Reliable Model B1 accelerator is an available option for use with this system. In the event that water builds up inside the deluge valve due to condensate from the air supply system or water from a valve trip, a drain valve is provided to drain the valve body and riser. This system's Notifier RP 1001 Fire Alarm/Releasing Control Panel, adjusted for cross-zoned operation, is utilized for the electric release and alarm functions. Only FM Approved fixed temperature heat devices shall be used in the release system and in the sprinkler piping. The control panel has an appropriately sized battery, Notifier Model PS 12120, to provide 90 hours of backup emergency power. The rated working pressure of the Supertrol Type D Double Interlock Preaction System is 250 psi (1724 kPa). Supertrol Type F Double Interlock Preaction System, pneumatic/electric. Consists of Model DDX Deluge Valves in sizes 4 in. and 6 in. (100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. Model DDX valves have grooved inlet and grooved outlet end connections. The Type F system is designed for systems with water supply pressures from 20 psi (138 kPa) to 250 psi (1724 kPa), and corresponding sprinkler system pneumatic pressures, nominally, of 12 psi (83 kPa) to 24 psi (165 kPa). A loss of system air pressure, such as when a sprinkler activates, opens the Reliable Model LP (low pressure) pilot line actuator causing the low pressure alarm to sound, but the DDX valve remains closed. The system utilizes the System Sensor EPS10-2 pressure alarm switch. Only when there is also an electrical signal to the releasing control panel from a fire detector, such as when a fixed temperature heat detector is activated, does the solenoid valve, Reliable P/N 6871020020, open which opens the DDX valve, sending water to the sprinklers. The Reliable Model A or B emergency stations/manual pull boxes can be used for manual releasing. The Reliable Model B1 accelerator is an available option for use with this system. In the event that water builds up inside the deluge valve due to condensate from the air supply system or water from a valve trip, a drain valve is provided to drain the valve body and riser. This system's Notifier RP 1001 Fire Alarm/Releasing Control Panel is utilized for the electric release and alarm functions. Only FM Approved fixed temperature heat devices shall be used in the release system and in the sprinkler piping. The control panel has an appropriately sized battery, Notifier Model PS 12120, to provide 90 hours of backup emergency power. The rated working pressure of the Supertrol Type F Double Interlock Preaction System is 250 psi (1724 kPa).

SES Enser Engineering, Via Carolina Romani 8/10, 20091 Bresso (MI), Italy

Sprinkler System. Double interlocked, uses a deluge valve controlled by an electric release system and pneumatic system pressure. Consists of 3, 4, 6, 8 in. NPS FARES Model F799-DG04K automatic water control valve, Model 284-08 3-way pilot, Model 377 pneumatic actuator, Model 379 air reset unit, Model 375 flow release pilot, Skinner Model 73218BN4UNLVN0C111C2 or ASCO Model 8210G207, 24 V dc solenoid valve, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours of emergency power. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping.

Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154

Sprinkler System. Double interlocked, uses a deluge valve controlled by an electric release system and pneumatic system pressure. Consists of automatic water control valve Model A, 3, 4, 6 in. NPS with 3/32 in. diaphragm chamber orifice, Skinner LV2LBX25 or 73218BN4UNLVNOC111C2 solenoid valves, Star Model AA-R or Tyco Model DP-1 dry pilot actuator, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours of emergency power; United Electric Control Co Models J54-8300 and J54-8295 pressure alarm switches; Star Model A manual control station. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping. Sprinkler System. Double interlocked, uses a deluge valve controlled by an electric release system and pneumatic system pressure. Consists of automatic water control valve Model A-1, 3, 4, 6 in. NPS with 3/32 in. diaphragm chamber orifice, Skinner 73212BN4TNLVNOC322C2 solenoid valves, Tyco Model DP-1 dry pilot actuator, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours of emergency power; United Electric Control Co Models J54-8300 and J54-8295 pressure alarm switches; Tyco Model MC-1 manual control station. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping.

Tyco Fire Products, 451 N Cannon Ave, Lansdale PA 19446

Tyco Fire Products Double Interlocked System. Uses an automatic water control valve controlled by an electric release system and pneumatic system pressure. Consists of Model DV-1 valve in 4 and 6 in. NPS, Model DP-1 dry pilot actuator, 1/2 in. NPS Skinner Models LV2LBX25 or 73218BN4UNLVNOC111C2, 24 V dc solenoid, or 1/2 in. NPS ASCO Models 8210G207, T8210A107, R8210A107, or 8210A107, 24 V dc solenoid valve, Grinnell or GEM Model F520 check valve, Model MC-1 manual control station, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours emergency power. A Tyco Fire Products Model ACC-1 accelerator trimmed to act as an exhauster may be used as an option. Tyco Fire Products Double Interlocked System. Uses an automatic water control valve controlled by an electric release system and pneumatic system pressure. Consists of Model DV-3 valve in 21/2 in. NPS, Potter Model PS10- 2A Pressure Alarm Switch, 1/2 in. NPS Skinner Models LV2LBX25 or 73218BN4UNLVNOC111C2, 24 V dc solenoid, or 1/2 in. NPS ASCO Models 8210G207, T8210A107, R8210A107, or 8210A107, 24 V dc solenoid valve, Grinnell or GEM Model F52 check valve, Model MC-1 manual control station, compatible FM Approved automatic release control panel capable of cross-zone operation, with appropriately sized battery to provide 90 hours emergency power, and Viking PORV valve. Tyco Fire Products Double Interlocked System. Uses an automatic water control valve controlled by an electric release system and pneumatic system pressure. Consists of Model DV-3 valve in 21/2 in. NPS, Model DP-1 dry pilot actuator, 1/2 in. NPS Skinner Models LV2LBX25 or 73218BN4UNLVNOC111C2, 24 V dc solenoid, or 1/2 in. NPS ASCO Models 8210G207, T8210A107, R8210A107, or 8210A107, 24 V dc solenoid valve, Grinnell or GEM Model F52 check valve, Model MC-1 manual control station, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours emergency power, and Viking PORV valve. Tyco Fire Products Refrigerated Area Sprinkler System. Double interlocked, supervised refrigerated area system controlled by an electric release system and pneumatic system pressure. Consists of Model DV-5 water control valve in sizes 11/2, 2, 3, 4 and 6 in. NPS, Potter Model PS40-2A low air pressure alarm switch, Potter Model PS10-2A waterflow pressure alarm switch, Tyco Model DP-1 dry pilot actuator, Tyco Model FSV-1 pressure operated relief valve, Tyco Model MC-1 manual control station, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours of emergency power. The pressure rating of electrically operated deluge sprinkler systems will be determined by the solenoid valve used. Systems using a Skinner Model No. 73218BN4UNLVN0C111C2 solenoid valve will be rated at 175 psi (1205 kPa). Systems using a Skinner Model No. 73212BN4TNLVN0C322C2 solenoid valve will be rated at 250 psi (1725 kPa). Only FM Approved fixed temperature heat sensitive devices shall be used in the release system and in the sprinkler piping Tyco Fire Products Refrigerated Area Sprinkler System. Double interlocked, supervised refrigerated area system controlled by an electric release system and electrically monitored pneumatic system pressure. Consists of Model DV-5 water control valve in sizes 11/2, 2, 3, 4 and 6 in. NPS, Potter Model PS10-2A low air pressure alarm switch, Model PS10-2A waterflow pressure alarm switch, Tyco Model ASV-1 automatic shut-off valve, Tyco Model MC-1 manual control station, compatible FM Approved automatic release control panel capable of cross-zone operation, with appropriately sized battery to provide 90 hours of emergency power. The pressure rating of electrically operated deluge sprinkler systems will be determined by the solenoid valve used. Systems using a Skinner Model No. 73218BN4UNLVN0C111C2

FM Approvals

1-116

September 2007 -- Approval Guide Automatic Sprinkler Systems

solenoid valve will be rated at 175 psi (1205 kPa). Systems using a Skinner Model No. 73212BN4TNLVN0C322C2 solenoid valve will be rated at 250 psi (1725 kPa). Only FM Approved fixed temperature heat sensitive devices shall be used in the release system and in the sprinkler piping. Refrigerated Area Sprinkler Systems, with the DV-5 water control valve, are available factory assembled vertically inside the Model DV-5 Red-E Cabinet in sizes 11/2, 2, 3, 4, and 6 in. NPS. The Red-E cabinet and assembled system components comprise an integrated fire protection system which is assembled and tested at the factory. The cabinet contains: the system shutoff valve, Model DV-5 deluge valve, 24 Vdc battery backup, and an electrical control/release panel for the solenoid valve release. The control panel is prewired to the switches for the alarm, supervisory, and trouble functions. Installation requires the connection to the water inlet inlet and outlet, main drain, electrical power supply, and the alarm and detection circuits. A built-in air compressor and air maintenance device provides controlled system air pressure.

Victaulic Company, Box 31, Easton PA 18044

Double-interlocked, uses a Series 758-DPA FireLock Automatic Water Control Valve controlled by pneumatic dry pilot line pressure and pneumatic system pressure. Sizes 11/2, 2, 21/2, 3, 4, 6, and 8 in. NPS, grooved inlet and grooved outlet, and flanged inlet and grooved outlet in sizes 4, 6, and 8 in. NPS, vertical or horizontal orientation; sizes 76.1 and 165.1 mm NPS, grooved inlet and outlet, vertical or horizontal orientation. Includes the Series 798 pneumatic/pneumatic actuator for low pressure, nominally 10 psi, supervised system pressure, a single component containing both pneumatic releases; Series 749 Auto Drain (pressure operated relief valve); Series 755 manual pull station; optional Series 757 or 757-P air maintenance devices. Rated working pressure is 300 psi (2069 kPa), except for the 8 in. valves, which have a rated working pressure of 225 psi (1551 kPa). Double-interlocked Series 758 FireLock Automatic Water Control Valve, pneumatic/electric release, electric/electric release, and pneumatic/electric/electric releases. Sizes 11/2, 2, 21/2, 3, 4, 6, and 8 in. NPS, grooved inlet and outlet, and flanged inlet and grooved outlet in sizes 4, 6, and 8 in. NPS, vertical or horizontal orientation; sizes 76.1 and 165.1 mm NPS, grooved inlet and outlet, vertical or horizontal orientation. Compatible FM Approved automatic release control panel capable of cross-zone operation with appropriately sized battery to provide 90 hours of emergency power and FM Approved pressure alarm switch. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping. Series 749 Auto Drain (pressure operated relief valve); Series 755 manual pull station; optional Series 757 or 757-P air maintenance devices; rated working pressure for electric activation is 175 psi (1207 kPa) with the ASCO Model No. 8210G207 solenoid valve; 300 psi (2069 kPa) with the Victaulic Series 753-E solenoid valve, except the 8 in. valves, which have a rated working pressure of 225 psi (1551 kPa). Series 769 Firelock NXT Double-Interlocked Valve with Electric-Pneumatic/Electric Release for Cross-Zoned Control Panel. Sizes 11/2, 2, 21/2, 3, 4, 6 and 8 in. NPS. Grooved inlet and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following: · · · · · · · · · Series 753-E normally closed solenoid valve System Sensor EPS40-2 system air pressure supervisory switch Series 749 Auto Drain pressure operated piston charge line water relief valve Series 748 anti-flood Ball Check Valve Series 729 alarm line Drip Check Valve Series 768 alarm line 3-Way Ball Valve for alarm/test/off Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections System Main Drain Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.

Optional system components include: · · · · System Sensor EPS10-2 alarm line pressure switch Series 755 Manual Pull Station Series 760 Water Motor Alarm Series 705W water supply butterfly shutoff valve

Series 769 Firelock NXT Double-Interlocked Valve with Electric/Pneumatic Release. Sizes 21/2, 3, 4, 6 and 8 in. NPS. Grooved inlet and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following: · · · · · · · · · · Series 776 Low Pressure Pneumatic Actuator with Auto Vent pressure operated system air pressure relief valve Series 753-E normally closed solenoid valve Series 749 Auto Drain pressure operated piston charge line water relief valve Series 729 alarm line Drip Check Valve Series 748 anti-flood Ball Check Valve Series 768 alarm line 3-Way Ball Valve for alarm/test/off Series 768 Air Manifold Assembly with integral restrictor/screen/anti-flood ball check valve Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections System Main Drain Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.

Optional system components include: · · · · · · · · Regulated Air Maintenance Trim Assemblies Series 757 or 757-P with pressure switch Series 746-LPA Accelerator System Sensor EPS10-2 alarm line pressure switch System Sensor EPS40-2 system air pressure supervisory switch Series 755 Manual Pull Station Series 760 Water Motor Alarm Series 705W water supply butterfly shutoff valve.

Series 769 Firelock NXT Double-Interlocked Valve with Electric/Pneumatic Release Sizes 11/2, 2, 21/2, 3, 4, 6, and 8 in. NPS. Grooved inlet and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following: · Series 767 Electric/Pneumatic Actuator; an Auto Vent pressure operated system air pressure relief valve · Series 749 Auto Drain pressure operated piston charge line water relief valve

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-117

· · · · · · ·

Series 729 alarm line Drip Check Valve Series 748 anti-flood Ball Check Valve Series 768 alarm line 3-Way Ball Valve for alarm/test/off Series 768 Air Manifold Assembly with integral restrictor/screen/anti-flood ball check valve Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections System Main Drain Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.

Optional system components include: · · · · · · · · Regulated Air Maintenance Trim Assemblies Series 757 or 757-P with pressure switch Series 746-LPA Accelerator System Sensor EPS10-2 alarm line pressure switch System Sensor EPS40-2 system air pressure supervisory switch Series 755 Manual Pull Station Series 760 Water Motor Alarm Series 705W water supply butterfly shutoff valve.

Series 769 Firelock NXT Double-Interlocked Valve with Pneumatic/Pneumatic Release. Sizes 11/2, 2, 21/2, 3, 4, 6, and 8 in. NPS. Grooved inlet and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of: the following: · · · · · · · · · Series 798 Pneumatic/Pneumatic Actuator with Auto Vent pressure operated system air pressure relief valve Series 749 Auto Drain pressure operated piston charge line water relief valve Series 729 alarm line Drip Check Valve Series 748 anti-flood Ball Check Valve Series 768 alarm line 3-Way Ball Valve for alarm/test/off Two Series 768 Air Manifold Assemblies with integral restrictor/screen/anti-flood ball check valve Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections System Main Drain Valve, size 2 in. with three 1/2 in. NPT outlets for gage and drain connections Series 752 piston charge line Strainer/Check Valve/Restrictor assembly

Optional system components include: · · · · · · · · Regulated Air Maintenance Trim Assemblies Series 757 or 757-P with pressure switch Two Series 746-LPA Accelerators System Sensor EPS10-2 alarm line pressure switch System Sensor EPS40-2 system air pressure supervisory switch Series 755 Manual Pull Station Series 760 Water Motor Alarm Series 705W water supply butterfly shutoff valve.

All refrigerated area sprinkler systems discussed above offer the Series 757-P Air Maintenance Trim Assembly as an option. It is used to control the system air pressure on all refrigerated area sprinkler systems, by controlling small air compressors which do not have pressure control switches. All refrigerated area sprinkler systems discussed above offer the Series 75-W Water Column Drain Kit as an option, which automatically drains water from the sprinkler systems and subsequently reseals to maintain air pressure in the system piping. All refrigerated area sprinkler systems discussed above offer the Series 75-B supplemental alarm valve as an option recommended for systems where continuous flow to the alarm port, which supplies flow to the water motor alarm, must be positively maintained. All the 11/2, 2, 21/2, 3, 4, and 6 in. NPS Refrigerated Area Sprinkler Systems discussed above are available factory assembled in the Victaulic Series 745 Fire-Pac enclosure, a cabinet containing all system components and accessories, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply. The Series 745 Fire-Pacs may be connected to Notifier AFP-200 Programmable Analog Fire control with software no. AFP2R2.42 or System Sensor PDRP-1001 fire control with operating system firmware revision level A. The AFP-200 control contains FMM-1 Module with a signaling line circuit which can be configured to meet Styles 4, 6 or 7 wiring performance as described in NFPA72. The addressable panels utilize model XP-10M module which may be configured at the factory to monitor the Fire-Pac cabinet and valve station. Optional LED Interface Module 4XTM and Relay Module RTM-8 provide outputs for auxiliary applications.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

Sprinkler System. Double interlocked, supervised, dry system using a deluge valve controlled by a pneumatic release system and pneumatic system pressure. Consists of water control valve Model E-1 or E-2, 2, 3, 4, 6 in. NPS or Model E-3 or E-4 in size 11/2 in. NPS or Model F-1 or F-2 in-line globe water control valves 11/2, 2, 21/2, 3, 4, 6 and 8 in. NPS; strainer; restricted orifice with 0.063 in. (1.6 mm) dia. orifice; Model C-1 or C-2 emergency release; Model 07757, 07821, 07759 or 07822 air supervisory switch; Model 07756 or 07758 pressure switch; Model C pressure-operated relief valve (PORV); two Model H-1 pneumatic actuators; dehydrator P/N 01285A; Model D-2 air pressure maintenance device; available with Speed Control Assembly trim option; FM Approved rubber-faced check valve. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping. Model E-3 and E-4, 11/2 in. NPS and Model E-1 and E-2, 2 in. NPS available with screwed connections only. Model E-1 or E-2, 3, 4, 6 in. NPS available with flanged end connections or flanged inlet and cut-grooved outlet connections. Model F-1 and F-2, in-line globe water control valves, 8 in. NPS, are available with grooved by grooved end connections or flanged by flanged end connections. Model F-1 or F-2 in-line globe water control valves, 3, 4, and 6 in. NPS, are available with grooved by grooved, flanged by flanged end, or flanged inlet by grooved outlet connections. Model F-1 or F-2 in-line globe water control valves, 11/2, 2 and 21/2 in. NPS, are available with grooved by grooved, or screwed end connections. Rated working pressure is 250 psi (1725 kPa). Previous system ratings are dependent on the solenoid valve used. See table of related components shown under Automatic Water Control Valves. Sprinkler System. Double interlocked, supervised, dry system using a deluge valve controlled by an electric release system and pneumatic system pressure. Consists of water control valve Model E-1 or E-2, 2, 3, 4, 6 in. NPS or Model E-3 or E-4 in size 11/2 in. NPS or Model F-1 or F-2 in-line globe water control valves 11/2, 2, 21/2, 3, 4, 6 and 8 in. NPS; strainer; restricted orifice with 0.063 in. (1.6 mm) dia. orifice; Model C-1 emergency release; Model 07757, 07821, 07759 or 07822 air supervisory switch; Model 07756, 07758, 09470 or 09471 pressure switch;

FM Approvals

1-118

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model H-1 or R-1 pneumatic actuator; Model C pressure-operated relief valve (PORV); dehydrator P/N 01285A; Model D-2 air pressure maintenance device; compatible FM Approved solenoid valve and automatic release panel equipped with appropriately sized battery to provide required 90 hours of emergency power; available with Speed Control Assembly trim option; FM Approved rubber-faced check valve. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping. Model E-3 and E-4, 11/2 in. NPS and Model E-1 and E-2, 2 in. NPS available with screwed connections only. Model E-1 or E-2, 3, 4, 6 in. NPS available with flanged inlet and outlet or flanged inlet and cut-grooved outlet connections. Model F-1 and F-2, in-line globe water control valves, 8 in. NPS, are available with grooved by grooved end connections or flanged by flanged end connections. Model F-1 or F-2 in-line globe water control valves, 3, 4, and 6 in. NPS, are available with grooved by grooved, flanged by flanged end, or flanged inlet by grooved outlet connections. Model F-1 or F-2 in-line globe water control valves, 11/2, 2 and 21/2 in. NPS, are available with grooved by grooved, or screwed end connections. Rated working pressure is 250 psi (1725 kPa). Previous system ratings are dependent on the solenoid valve used. See table of related components shown under Automatic Water Control Valves. Sprinkler System. Double interlocked, Electric Pneu-Lectric, supervised dry system using a deluge valve controlled by electric release system and pneumatic system pressure. Consists of water control valve Model E-1 or E-2 in size 2, 3, 4 or 6 in. NPS or Model E-3 or E-4 in size 11/2 in. NPS or Model F-1 or F-2 in-line globe water control valves 11/2, 2, 21/2, 3, 4, 6 or 8 in. NPS; priming line including strainer, 0.063 in. (1.6 mm) dia. orifice and spring loaded check valve; Model C-1 or C-2 emergency release; for 10 psi (69 kPa) supervisory air system use Model 09471 dual SPDT pressure switches; for 30 psi (207 kPa) supervisory air system use Model 09473 dual SPDT pressure switches; Model C-1 pressure-operated relief valve (PORV) including conventional deluge trim; dehydrator P/N 01285A; Model D-2 air pressure maintenance; compatible FM Approved solenoid valve and automatic release control panel, equipped capable of cross zoned operation with FM Approved compatible pressure switch and heat actuated device and appropriately sized battery to provide required 90 hours of emergency power; available with Speed Control Assembly trim option; available with Easy Trim option utilizing Model A-1 or A-2 pressure shut-off valve (PSOV); FM Approved rubber-faced check valve. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and sprinkler piping. Model E-3 and E-4, 11/2 in. NPS and Model E-1 and E-2, 2 in. NPS available with screwed connections only. Model E-1 or E-2, 3, 4, 6 in. NPS available with flanged end connections or flanged inlet and cut-groove outlet connections. Model F-1 and F-2, 3, 4, 6, 8 in. NPS available with grooved end connections or flanged end connections or flanged inlet and grooved outlet end connections. Model F-1 or F-2 in-line globe water control valves, 11/2, 2 and 21/2, in. NPS, are available with grooved by grooved, or screwed end connections. Rated working pressure is 250psi (1725 kPa). The rated working pressure of the Electric/Pnue-Electric refrigerated area sprinkler system is dependent on the solenoid valve used. See table of related components shown under Automatic Water Control Valves. Refrigerated Area Sprinkler Systems are available factory assembled in the Viking Total Pac enclosure with in sizes 11/2 through 6 in. NPS, with electric/pneumatic, pneumatic/pneumatic, and electric-pneumatic/electric releases. The Total Pac enclosure and assembled valve systems comprise an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply. Sprinkler System. Sure Fire Fail/Safe double interlocked, supervised dry system using a deluge valve controlled by a electric release system and pneumatic system pressure. Consists of angle type water control valves Model E-1 or E-2, in sizes 2, 3, 4, and 6 in. NPS, or Model E-3 or E-4 in size 11/2 in. NPS; or in-line Model F-1 or F-2 in-line globe type water control valves in sizes 11/2, 2, 21/2, 3, 4, 6 and 8 in. NPS; strainer; restricted orifice with 0.063 in. (1.6 mm) dia. orifice; Model B-1 release control panel, with an appropriately sized battery to provide 90 hours of emergency power, equipped capable of cross zoned operation with FM Approved compatible pressure switch and heat actuated device; FM Approved solenoid valves include the normally open Viking Model 11595, the normally closed Viking Model 11591, the normally open explosion proof Viking Model 11596, the normally closed explosion proof Viking Model 11592; or N.C. Solenoid Valve, Viking P/N 11591 and N.O. Solenoid Valve, Viking P/N 13215 for 250 psi (1725 kPa) rated working pressure. Pneumatic actuators Model H-1 or R-1; Model C-1 or C-2 emergency releases; dual SPDT Model 09473 and single SPDT Model 09472 air supervisory switch; Model 09470, 09471 pressure switch; dehydrator P/N 01285A; Model D-2 air pressure maintenance device; available with Easy Trim option, utilizing a Model A-1 or A-2 pressure shut-off valve (PSOV); trim available in galvanized, brass or stainless steel piping; FM Approved rubber-faced System check valve. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping. Model F-1 and F-2 valves are capable of vertical installation. Same valve end connections as noted above. Rated working pressure 250 psi (1725 kPa). Piping above the riser check valve contains supervisory air pressure at 30-50 psi (205-345 kPa) to monitor system integrity. If the system piping is damaged, the low air pressure alarm is activated and the normally open solenoid valve is activated closed, but the main water control valve does not trip, and no water flows into the sprinkler system until the heat detection device is actuated. This causes the normally closed solenoid valve to open which activates the control valve and water flow is supplied to the sprinkler system. Also the low air supervisory switch and the heat detection device must activate before the system control valve will open and supply water to the sprinkler system. In loss of power condition, the system operates from system supervised air and the pneumatic actuator. Refrigerated Area Sprinkler Systems, which utilize the angle type main water control valves, are available factory assembled in the Viking Total Pac2 enclosure, a second generation enclosure which replaces the Total Pac. The Total Pac2 is available in several configurations: 1) the system fully enclosed on legs with an access door and a built in electrical control panel (when electric activation required); 2) the valve system fully enclosed on legs with an access door and a remote control panel; 3) the valve system assembled to a skid and used with a remote control panel. All Refrigerated Area Sprinkler Systems are available with TrimPac trim package.

Tyco Fire Products, 451 N Cannon Ave, Lansdale PA 19446

Tyco Fire Products Double Interlocked System. Uses an automatic water control valve controlled by an electric release system and pneumatic system pressure. Consists of Model DV-1 valve in 4 and 6 in. NPS, Model DP-1 dry pilot actuator, 1/2 in. NPS Skinner Models LV2LBX25 or 73218BN4UNLVNOC111C2, 24 V dc solenoid, or 1/2 in. NPS ASCO Models 8210G207, T8210A107, R8210A107, or 8210A107, 24 V dc solenoid valve, Grinnell or GEM Model F520 check valve, Model MC-1 manual control station, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours emergency power. A Tyco Fire Products Model ACC-1 accelerator trimmed to act as an exhauster may be used as an option.

ON-OFF MULTICYCLE SPRINKLER SYSTEMS

Multicycle sprinkler systems are FM Approved automatic sprinklers and hydraulic controls capable of repeated on-off cycles appropriate to the possible redevelopment of fire in the protected area. The cycling occurs as the result of fire detector operation which, acting as an electrical interlock, causes the main water control valve to open and close. Fire detector actuation precedes sprinkler operation so water is discharged as from a conventional water system. Should the fire rekindle after its initial control, water again flows from the opened sprinklers. Manual control valve operation, in the event of detector impairment, is a required system capability. Sprinkler replacement after a fire does not cause impairment of protection. Plans for converting existing wet or dry sprinkler systems to multicycle should be reviewed by your insurance company before actual installation.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-119

A very important feature of the multicycle sprinkler system is its effect toward the reduction of the closed-valve, catastrophic fire. With the multicycle system, the manual sprinkler control valve would not have to be closed except in the very infrequent case of major maintenance involving a certain small section of the overall system. Unless otherwise noted in the listing, this system has 175 psi (1205 kPa) rated working pressure.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

Firecycle II System. Consists of the Model H-1, H-2, H-3 or H-4 main water control valve in size 11/2 in. NPS or the Model H-1 or H-2 main water control valve, in sizes 2, 3, 4 or 6 in. NPS or the Model J-1 and J-2 main water control valve in size 4, 6, 8 in. NPS and accessories; FM Approved check valve (Viking Models D-2 or equivalent having rubber-faced clapper); Model D-1 control panel and series circuit of P/N 04625-B, 140°F (60°C); 04626-B, 160°F (71°C); 04627-B, 190°F (88°C); 04628-B, 225°F (107°C) heat-actuated fire detectors connected by Firecycle aluminum clad fire alarm cable; Model C-1 valve trim box; Model C-1 emergency release (optional); Model A-1 battery charger/ power supply P/N 03982C or P/N 04362C; available with Speed Control Assembly trim option; FM Approved waterflow alarm. Model H-1 or H-2, 3, 4, 6 in. NPS water control valve available with flanged inlet and outlet or flanged inlet and cut-grooved outlet connections. Model H-1, H-2, H-3 and H-4, size 11/2 NPS and Model H-1 and H-2, size 2 in. NPS water control valve available with screwed connections only. Model J-1 and J-2 main water control valve in size 4, 6, 8 in. NPS available with grooved end connections. Firecycle II Sprinkler Systems rated at 175 psi (1205 kPa). The electric equipment controls the mechanical operations necessary to start automatically and stop water flow from those standard sprinklers opened by fire. The temperature rating of the detector should be lower than the rating of its adjacent sprinklers. Power failure and fire alarm are signaled automatically. System is powered by line voltage and maintains charge in 24 V emergency battery supply (90 hr standby capability). Piping above riser check valve normally contains supervisory air pressure at 10-15 psi (70-105 kPa). Detectors are spaced according to ceiling construction and possible obstruction conditions, but should not exceed 40 ft (12 m) for P/N 04625-B or 25 ft (8 m) for P/N's 04626-B, 04627-B and 04628-B; their location should be within 18 in. (457 mm) laterally of a sprinkler deflector except in low hazard occupancies. Sprinkler discharge continues for a timed interval (5 min. normally) after all normally closed contact detectors have been restored; this interval should be extended to 15 min. where persistent localized fire is anticipated. The manufacturer's instructions and appropriate sprinkler installation rules should be followed in Firecycle installation, testing and maintenance. The Firecycle III Model E-1 Control Panel automatically starts and stops waterflow to the sprinkler system in response to the on-off cycling of the heat responsive detectors. Piping above the riser check valve contains supervisory air pressure at 25-30 psi to monitor system integrity. If the system piping is damaged, the low air pressure alarm is activated, but the main water control valve does not trip and no water flows from the sprinkler system. Firecycle III System. Consists of Model H-1 or H-3, 11/2, 2, 3, 4 or 6 in. NPS main water control valve or Model J-1 or J-2, 11/2, 2, 21/2, 3, 4, 6, 8 in. NPS main water control valve and accessories; FM Approved check valve (Viking Model E-1 or equivalent having rubber-faced clapper); Firecycle III Control Panel E-1, Viking P/N 10751 and 10752; Firecycle III Model B heat-actuated fire detectors for 140°F (60°C), P/N 04625-B; 160°F (71°C), 04626-B; 190°F (88°C), P/N 04627-B; 225°F (107°C), P/N 04628-B; Firecycle aluminum clad detector cable, P/N 04632-A; Model C-1 emergency release; 90-hour, 17 A-H battery back-up power supply capable of being recharged in 48 hours, P/N A-09867; N.C. Solenoid Valve, Viking P/N A-08408 and N.O. Solenoid Valve, Viking P/N A-08407 for 175 psi (1205 kPa) rated working pressure. N.C. Solenoid Valve, Viking P/N 11591 and N.O. Solenoid Valve, Viking P/N 11595 for 250 psi (1725 kPa); or N.C. Solenoid Valve, Viking P/N 11591 and N.O. Solenoid Valve, Viking P/N 13215 for 250 psi (1725 kPa) rated working pressure. FM Approved 30 psi Supervisory Pressure Switch; FM Approved 5 psi Pressure Alarm Switch; Pneumatic Actuator, Viking Model H-1; Pressure Operated Relief Valve (P.O.R.V.), Viking Model C-1; Automatic Drip Check Valve, Viking Model D-1. Available with TrimPac trim package. A restricted and regulated air supply is recommended by the manufacturer. An equivalent FM Approved air pressure maintenance device may be used. Model J-1 and J-2, in-line globe water control valves, 8 in. NPS, are available with grooved by grooved end connections or flanged by flanged end connections. Model J-1 or J-2 in-line globe water control valves, 3, 4, and 6 in. NPS, are available with grooved by grooved, flanged by flanged end, or flanged inlet by grooved outlet connections. Model J-1 or J-2 in-line globe water control valves, 11/2, 2 and 21/2 in. NPS, are available with grooved by grooved, or screwed end connections. The Firecycle III Model E-1 Control Panel automatically starts and stops waterflow to the sprinkler system in response to the on-off cycling of the heat responsive detectors. Piping above the riser check valve contains supervisory air pressure at 25-30 psi to monitor system intergrity. If the system piping is damaged, the low air pressure alarm is activated, but the main water control valve does not trip and no water flows from the sprinkler system. The temperature rating of the detector should be lower than the rating of its adjacent sprinklers. Power failure and fire alarm are signaled automatically. System is powered by line voltage (110/220/240 V ac) and operates (cycles) normally with the 24 V emergency battery back-up system (90 hr standby capability). Detectors are spaced according to ceiling construction and possible obstruction conditions, but should not exceed 40 ft (12 m) for P/N 04625-B or 25 ft (8 m) for P/N 04626-B, 04627-B and 04628-B; their location should be within 18 in. (457 mm) laterally of a sprinkler deflector except in low hazard occupancies. Sprinkler discharge continues for a timed interval (5 min. normally) after all normally closed contact detectors have been restored; this interval should be extended to 15 min. where persistent localized fire is anticipated. The manufacturer's instructions and appropriate sprinkler installation rules should be followed in Firecycle III installation, testing and maintenance. FireCycle III and FireCycle III-OH Sprinkler Systems are available factory assembled in the Viking Total Pac enclosure in sizes 11/2 through 6 in. NPS, when utilizing the angle type main water control valves, Models H-3 and H-1, in both single-interlock preaction and cycling wet pipe configurations. The Total Pac enclosure and assembled valve systems comprise an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply. Firecycle III-OH System. Single Interlock Preaction System. Consists of Model H-3 main water control valve, size 11/2 NPS, or Model H-1 main water control valve, sizes 2, 3, 4 or 6 in. NPS, or Models F-1 or F-2 main water control valves, sizes 4 and 6 in., or Models J-1 or J-2 main water control valves, sizes 11/2, 2, 21/2, 4, 6, and 8 in. NPS; Viking Model F-1 riser check valve, sizes 3, 4, 6, and 8 in., or Model L-1 riser check valve, sizes 11/2 and 2 in. having a rubber-faced clapper); Firecycle III Control Panel E-1, Viking P/N 10751 and 10752; Firecycle III-OH heat detectors are self-restoring, normally closed, heat-actuated switches. There are two types: Viking Model C surface mount and Viking Model C flush mount. The surface mount is attached directly to a ceiling or to a ceiling mounted standard octagonal electrical box, and the detector wire in conduit is exposed below the ceiling. The flush mount detector is attached to a standard octagonal electrical box recessed in the ceiling, and the detector wire is concealed above the ceiling. The detector wire is Viking P/N 09954, NEC FPL rated wire, 16 gage, 2 conductor, 2 hour rated (in conduit or equal), or Viking P/N 11988, NEC FPL rated wire, 18 gage, 2 conductor, 2 hour rated (in conduit or equal), or Viking P/N 04236A, aluminum clad wire installed behind proper rated construction. Model C normally closed heat-actuated flush mounted fire detectors for Ordinary Hazard applications: 140°F (60°C), P/N 11723; 160°F (71°C), P/N 11724; 190°F (88°C), P/N 11725; 225°F (107°C), P/N 11726; Model C normally closed heat-actuated surface mounted fire detectors for Ordinary Hazard applications: 140°F (60°C), P/N 11727; 160°F (71°C), P/N 11728; 190°F (88°C), P/N 11729; 225°F (107°C), P/N 11730. Model C-1 emergency release; 90-hour, 18 A-H battery back-up power supply capable of being recharged in 48 hours, P/N A-09867. For 250 psi rated working pressure, N.C. solenoid valve, Viking P/N 11591 and N.O. solenoid valve, Viking P/N 11596; or N.C. Solenoid Valve, Viking P/N 11591 and N.O. Solenoid Valve, Viking P/N 13215 for 250 psi (1725 kPa) rated working pressure; 30-50 psi adjustable supervisory pressure Switch; 5 psi Pressure Alarm Switch; Pneumatic Actuator, Viking Model H-1; Pressure Operated Relief Valve (P.O.R.V.), Viking Model C-1; Automatic Drip Check Valve, Viking Model D-1. Available with TrimPac trim package. A restricted and regulated air supply is recommended by the manufacturer. The Firecycle III-OH On-Off Preaction Sprinkler System piping has supervisory system air pressure

FM Approvals

1-120

September 2007 -- Approval Guide Automatic Sprinkler Systems

(minimum 30 psi, for 20 psi water supply pressure, up to 50 psi, for 250 psi water supply pressure) to monitor system integrity. If the system piping is damaged or a sprinkler activates, the low air pressure alarm is activated, but the main water control valve does not trip and no water flows to the sprinkler system. When the heat detection system has been activated, the main water control valve opens and water will flow out any open sprinklers. The Firecycle III Model E-1 Control Panel automatically starts and stops water flow to the sprinkler system in response to the on-off cycling of the heat responsive detectors. The heat detectors open when the detectors are exposed to the heat of the fire and close when the detector cools below its set point. Sprinkler discharge continues for a timed ``soak''interval (5 min normally) after all normally closed contact detectors have closed. This interval should be extended to15 minutes where persistent localized fire is anticipated. The on-off cycling of the heat responsive contacts controls the system solenoid valves which in turn control the opening and closing of the main water control valve. The temperature rating of the detectors should be lower than the rating of its adjacent sprinklers. Power failure and fire alarms are signaled automatically. System is powered by line voltage (110/220/240 VAC) and operates (cycles) normally with the 24 VDC emergency battery back-up system (90 hr standby capability). Detectors are spaced according to ceiling construction and possible obstruction conditions, but should not exceed 40 ft (12 m) for P/N 11727 or 25 ft (8 m) for P/N 11728, 11729 and 11730; their location should be in accordance with NFPA 72E. The manufacturer's instructions and appropriate sprinkler installation rules should be followed in Firecycle III-OH installation, testing and maintenance. The FireCycle III System-OH is rated for 250 psi (1725 kpa) operating pressure. Firecycle III-OH Cycling Wet Pipe System. Consists of: Model H-3 main water control valve, size 11/2 NPS, or Model H-1 main water control valve, sizes 2, 3, 4 or 6 in. NPS, or Models J-1 or J-2, 11/2, 2, 21/2, 3, 4, 6 and 8 in. NPS main water control valve and accessories; Water Flow Switch and system Drain Valve down stream of control valve. Firecycle III Control Panel E-1, Viking P/N 10751 and 10752; Firecycle III-OH heat detectors are self-restoring, normally closed, heat-actuated switches. There are two types: Viking Model C surface mount and Viking Model C flush mount. The surface mount is attached directly to a ceiling or to a ceiling mounted standard octagonal electrical box, and the detector wire in conduit is exposed below the ceiling. The flush mount detector is attached to a standard octagonal electrical box recessed in the ceiling, and the detector wire is concealed above the ceiling. The detector wire is Viking P/N 09954, NEC FPL rated wire, 16 gage, 2 conductor, 2 hour rated (in conduit or equal), or Viking P/N 11988, NEC FPL rated wire, 18 gage, 2 conductor, 2 hour rated (in conduit or equal), or Viking P/N 04236A, aluminum clad wire installed behind proper rated construction.; Model C normally closed heat-actuated flush mounted fire detectors for Ordinary Hazard applications: 140°F (60°C), P/N 11723; 160°F (71°C), P/N 11724; 190°F (88°C), P/N 11725; 225°F (107°C), P/N 11726; Model C normally closed heat-actuated surface mounted fire detectors for Ordinary Hazard applications: 140°F (60°C), P/N 11727; 160°F (71°C), P/N 11728; 190°F (88°C), P/N 11729; 225°F (107°C), P/N 11730; Model C-1 emergency release; 90- hour,18 A-H battery back-up power supply capable of being recharged in 48 hours, P/N A-09867. For 250 psi rated working pressure, N.C. solenoid valve, Viking P/N 11591 and N.O. solenoid valve, Viking P/N 11596; or N.C. Solenoid Valve, Viking P/N 11591 and N.O. Solenoid Valve, Viking P/N 13215 for 250 psi (1725 kPa) rated working pressure. The Firecycle III-OH Cycling Wet System in the normal set condition has the main water control valve in the open position, the sprinkler piping is filled with water, and water will flow from any activated sprinklers. The Firecycle III Model E-1 Control Panel automatically starts and stops water flow to the sprinkler system in response to the on-off cycling of the heat responsive detectors. The heat detectors open when the detectors are exposed to the heat of the fire and close when the detector cools below its set point. Sprinkler discharge continues for a timed ``soak''interval (5 min normally) after all normally closed contact detectors have closed. This interval should be extended to 15 minutes where persistent localized fire is anticipated. The on-off cycling of the heat responsive contacts controls the system solenoid valves which in turn control the opening and closing of the main water control valve. The temperature rating of the detectors should be lower than the rating of its adjacent sprinklers. Power failure and fire alarms are signaled automatically. System is powered by line voltage 110/220/240 V ac) and operates (cycles) normally with the 24 VDC emergency battery back-up system (90 hr standby capability). Detectors are spaced according to ceiling construction and possible obstruction conditions, but should not exceed 40 ft (12 m) for P/N 11727 or 25 ft (8 m) for P/N 11728, 11729 and 11730; their location should be in accordance with NFPA 72E. The manufacturer's instructions and appropriate sprinkler installation rules should be followed in Firecycle III-OH installation, testing and maintenance. The FireCycle III System-OH is rated for 250 psi (1725 kpa) operating pressure. Multicycle On-Off Sprinkler Systems, which utilize the angle type main water control valves, are available factory assembled in the Viking Total Pac2 enclosure, a second generation enclosure which replaces the Total Pac. The Total Pac2 is available in several configurations: 1) the system fully enclosed on legs with an access door and a built in electrical control panel (when electric activation required); 2) the valve system fully enclosed on legs with an access door and a remote control panel; 3) the valve system assembled to a skid and used with a remote control panel. Available with TrimPac trim package.

AUTOMATIC RELEASES FOR PREACTION AND DELUGE SPRINKLER SYSTEMS

The function of these releases is to open water valves automatically via FM Approved fire detection devices. Release control panels FM Approved for deluge and preaction sprinkler systems are compatible with the specified solenoid-operated valves, have standby power supplies capable of providing the required 90-hour system operation should primary power fail, and fire detection circuitry capable of operation during open circuit fault condition.

ADT Security Services Inc, One Town Center Rd, Boca Raton FL 33486

Unimode II. Programmable fire alarm panel using firmware revision level 6. The min configuration consists of either a CAB-A2, -B2, -C2, -D2, -A3, -B3, -C3 or -D3 enclosure, CPU-5000 central processing unit, MPS-24, -24A or -24B power supply, and an initiating module IZM-4 or -8. CPU-5000 provides two indicating circuits; one alarm and one trouble relay output, reverse polarity circuit, and a local energy municipal tie for auxiliary protective signaling. Indicating appliance circuits supply 18-30 V dc; therefore, the FM Approved devices used must be capable of operating throughout the entire voltage range. Unimode II requires TCM-2 or -4 time control modules with operating system firmware revision level 2. Modules are programmable for either cross zone or dual zone operation. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby battery packs (24 V dc, 12 and 25 AH) provide 90 hour standby operation. See LOCAL PROTECTIVE SIGNALING listing for other FM Approved modules. Unimode 4-16. Programmable fire alarm panel using firmware revision level 3. The min configuration consists of a CAB-500 enclosure, CPU-500 central processing unit, MPS-24BPCA power supply, 4000TA transformer, and an initiating module IZ-4 or -8. CPU-500 provides two indicating circuits; one alarm and one trouble relay output, reverse polarity circuit, and a local energy municipal tie for auxiliary protective signaling. Requires TC-2 or -4 time control modules with operating system firmware revision level 2. Modules are programmable for either cross zone or dual zone operation. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby battery packs (24 V dc, 12 and 25 AH) provide 90 hour standby operation. See LOCAL PROTECTIVE SIGNALING listing for other FM Approved modules. ADT Unimode-300 or Unimode-400 Fire Alarm Control Panel. Programmable control. Basic system consists of a combination of ADTCPU-300 or ADT-CPU-400 module and MPS-400 power supply. 120/240 V ac primary system provides four notification appliance circuit/ releasing circuit outputs from the MPS-400 rated at 24 V dc 2.5 A. Release circuit requires REL 2.2K end-of-line device for supervision. Total MPS-400 power output is 6 A in alarm. Standby battery (24 V dc up to 55 AH) provides 90 hour standby operation. (See control panel description under LOCAL PROTECTIVE SIGNALING.)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-121

Unimode-640 Fire Alarm Control Panel. Basic system consists of the ADT-CPU-640 module with internal power supply. 120 V ac primary system provides four notification appliance circuit/releasing circuit outputs rated at 24 V dc 2.5 A plus two 24 V dc 1.25 A (total) auxiliary outputs. Total power output is 6 A in alarm, 3A in standby. Release circuit requires REL 2.2K end-of-line device for supervision. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (TM-4) provides a local energy municipal tie for auxiliary protective signaling. Standby battery (24 V dc up to 60 AH) provides 90 hour standby operation. See control panel description under LOCAL PROTECTIVE SIGNALING.

Alison Control Inc, 35 Daniel Rd, Fairfield NJ 07004

Model A888-MXXX Detection System. (Each X is a numeral; each system configuration has a different suffix designation.) An ``H'' suffix is used to differentiate between plug-in boards having the HI-GJ2K-4730-109L relays and those which do not. The system consists of the following: P/N 108800 reporting switchboard; P/N 108800-2 reporting switchboard; P/N 108801 solenoid control board used with compatible combinations of solenoid and deluge water valves as listed under AUTOMATIC WATER CONTROL VALVES; P/N 108804 or P/N 108817 detection boards; P/N 108806 internal relay board; P/N 108807 external relay board; P/N 108809 alarm board; P/N 108810 audible alarm board; P/N 108811 rate-of-rise detection board (not recommended for use in refrigerated areas) used with 9090 Series thermistor cable; sensor cable terminators 9090E-50M1, 9090K-50M1, 9090E-51A, 9090K-51A and 9090H-51A; junction boxes 2003K-SSM1, 2003E-SSM1, 2002K-SSM1, and 2002E-SSM1; optional P/N 108812 T-to-I and P/N 108816 hot spot locator boards used with 9090 Series thermistor cables; P/N 108813 battery charger module and P/N 108818 terminator diode board; P/N 108819 latching indicator board. The releasing device circuit is FM Approved for use in the manual reset mode only; automatic reset is not FM Approved for use with sprinkler systems. The releasing device circuit is rated at 8 A max. Primary power is 120 V ac or 90-140 V dc. Battery standby capacity is provided with P/N 883184, 883209, 883214 or 883157 battery pack for 90 hours of emergency operation. Up to 192 AH of battery capacity is provided with two P/N 883157 packs in parallel. Operating temperature range is -40° to 140°F (-40° to 60°C).

Ansul Incorporated, One Stanton St, Marinette WI 54143

Fire Alarm Control. Autopulse IQ-301 Analog Fire Panel. Programmable control uses firmware revision level 2. Contains a signaling line circuit with cross-zone capability and four indicating appliance/release circuits. For deluge and preaction sprinkler system release, compatible solenoid valves are ASCO Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby battery packs (24 V dc, 7 to 12 AH) provide 90 hours standby operation. AUTOPULSE IQ-396X Fire Alarm Control Panel. Programmable control. Basic system consists of a combination of CPU-400 module and MPS-400 power supply. 120/240 V ac primary system provides four notification appliance circuit/releasing circuit outputs from the MPS-400 rated at 24 V dc 2.5 A. Release circuit requires REL 2.2K end-of-line device for supervision. Total MPS-400 power output is 6 A in alarm. Standby battery (24 V dc up to 55 AH) provides 90 hour standby operation. (See control panel description under LOCAL PROTECTIVE SIGNALING.) Autopulse 442D with operating system Firmware Revision Level A. Including LED Interface Module (4XLM); Zone Relay Module (4XZM); Remote Annunciator (RZA-4X). Panel provides four input circuits: one detector; one manual release/detector; one waterflow; one supervisory and four output circuits; one alarm/waterflow bell; one waterflow/supervisory bell; one release; one supervisory bell/release. In addition, one regulated and one unregulated 24 V auxiliary power output; one alarm and one trouble relay output are provided. Combined load for all external devices not to exceed 2.25 A. Field programmable using dip switches for either cross zone or dual zone. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models T8210A107, R8210A107, 8210A107 and Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (4XTM) provides a local energy municipal tie for auxiliary protective signaling. In the event of primary power failure, battery packs (24 V dc, 12, 15 AH) are suitable for 90 hours of standby operation. Autopulse IQ-636X(E)Fire Alarm Control Panel. Basic system consists of the IQ636-CPU(E)module with internal power supply. 120 V ac primary system provides four notification appliance circuit/releasing circuit outputs rated at 24 V dc 2.5 A plus two 24 V dc 1.25 A (total) auxiliary outputs. Total power output is 6 A in alarm, 3A in standby. Release circuit requires REL 2.2K end-of-line device for supervision. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (TM-4) provides a local energy municipal tie for auxiliary protective signaling. Standby battery (24 V dc up to 60 AH) provides 90 hour standby operation. See control panel description under LOCAL PROTECTIVE SIGNALING. Series Autopulse Z-10 control with Rev. 1.01 software. Panel Model 430525 (red enclosure) is provided with 4 initiating device circuits (IDC), which must be connected to TEPG-US Model 430531 Class A Adapter Module to configure for (Class A) Style D wiring. Two release circuits are provided for sprinkler release. Each releasing appliance circuit must connect to a TEPG-US Model 430687 coil supervision module which in turn is connected to a compatible 24 V dc actuator or solenoid. For Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. Optional TEPG-US Models 430548 and 430550 External Battery Chargers provide the Autopulse Z-10 charging capability for a standby battery bank up to 50 AH in capacity to supply the required 90 hours of standby power. (See Control Panel Description under LOCAL PROTECTIVE SIGNALING.) Series Autopulse Z-28 Addressable Control System. Analog control panel with Software Revision Level 3.03 using programmed Notification Appliance Circuits N3 or N4 on the Autopulse Z-28 SFI/O card. Each releasing appliance circuit must connect to a TEPG-US Model 430687 coil supervision module which in turn is connected to a compatible 24 V dc actuation device. Optional TEPG-US Model 430657 or 431193 Suppression Release Peripheral connects to the SLCNet circuit and to a notification appliance circuit from either the Autopulse Z-28 fire alarm control panel, or from the Autopulse Z-28 EXT Notification Appliance Circuit Extender. This peripheral monitors the output releasing appliance circuit wiring for opens and shorts. Each releasing appliance circuit must connect to a TEPG-US Model 430687 coil supervision module which in turn is connected to a compatible 24 V dc solenoid or actuation device. For FM Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. SLCNet signaling line circuits must be configured for Class A, Style 6 wiring for this application. 24 Vdc batteries rated 25-50 AH are available to provide 90 hours of emergency operation. For battery requirements exceeding 25 AH, the TEPG-US Models 430548 or 430550 External Battery Charger must be used. (See Control Panel Description under LOCAL PROTECTIVE SIGNALING.)

Buckeye Fire Equipment Co, 110 Kings Road, King Mountain NC 28086

Shield-SZ DipSwitch Programmable Fire Alarm Control Panel using Version 1.00 firmware; P/N SZ-120-2R (110 V ac) and SZ-240-2R (240 V ac). The system may include SZ120-0c (110 V ac) or SZ250-0c (208 or 240 V ac) enclosures with transformer, SZ200-17 (17 AH) battery assembly, SZ101 controller, SZ400 Class A Input Module, and SZ440 Relay module. In the sprinkler mode, the SZ101 Controller Card provides two initiating device circuits (capable of cross-zone, sequential alarm or single detector release) for fire detection, one waterlow circuit; one supervisory circuit, all of which are Class B Style A. Initiating device circuits must be converted to Class A Style D with Class A input module SZ400 for sprinkler release. In addition, the controller provides three notification circuits (all Class B, Style Y); one alarm relay (non-programmable); one trouble relay (non-programmable), and one solenoid releasing circuit for activation of compatible 24 V solenoid valves. For FM Approved combinations of solenoid and deluge water valves refer to AUTOMATIC WATER CONTROL VALVES.

CHEMETRON Fire Systems, 4801 Southwick Dr, 3rd Floor, Matteson IL 60443

Micro 1001 with operating system Firmware Revision Level A. Including a zone relay module. Panel provides four input circuits: one detector; one manual release/detector; one waterflow; one supervisory and four output circuits; one alarm/waterflow bell; one waterflow/

FM Approvals

1-122

September 2007 -- Approval Guide Automatic Sprinkler Systems

supervisory bell; one release; one supervisory bell/release. In addition, one regulated and one unregulated 24 V auxiliary power output; one alarm and one trouble relay output are provided. Combined load for all external devices not to exceed 2.25 A. Field programmable using dip switches for either cross zone or dual zone. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models T8210A107, R8210A107, 8210A107 and Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. In the event of primary power failure, battery packs (24 V dc, 12, 15 AH) are suitable for 90 hours of standby power. Fire Alarm Control. Micro-200I Analog Fire Panel. Programmable control (see listing under LOCAL PROTECTIVE SIGNALING). Contains a signaling line circuit with cross-zone capability and four indicating appliance/release circuits. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby battery packs (24 V dc, 7 to 12 AH) provide 90 hours standby operation. MICRO-640I Fire Alarm Control Panel. Basic system consists of the MICRO-640-CPU module with internal power supply. 120 V ac primary system provides four notification appliance circuit/releasing circuit outputs rated at 24 V dc 2.5 A plus two 24 V dc 1.25 A (total) auxiliary outputs. Total power output is 6 A in alarm, 3A in standby. Release circuit requires REL 2.2K end-of-line device for supervision. Release circuit can be provided via FCM-1 module and/or XP5-C and XP5-M Transponders. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (TM-4) provides a local energy municipal tie for auxiliary protective signaling. Standby battery (24 V dc up to 60 AH) provides 90 hour standby operation. See control panel description under LOCAL PROTECTIVE SIGNALING.

Detector Electronics Corp, 6901 W 110th St, Minneapolis MN 55438

FDRS Programmable System. The FDRS control contains a max of four R7404B7001 or R7494B5001 Controllers, an R6006 Relay Output Module, an R1425 Detonator Module, and a W2400 Ground Fault Monitor Module for communication with a FM Approved fire alarm control in temperatures of -40° to +75°C (-40° to 167°F). For the controllers, as the major circuits are not capable of operation during open circuit fault conditions, the input circuit supervision requirements are met by using two detectors on different circuits to provide redundant monitoring of the same area. Controller firmware is the following: R7404B7001 (002267-025/Rev. E); R7494B5001 (002267-032/Rev. C). The R6006 Relay Output Module receives inputs from solid state switching devices and provides load relay switching in response to the input signals for communication to the FM Approved fire alarm control. The firmware for the R6006 variations is the following: 002267-003/Rev. G (R6006A2001 and R6006C1008) and 002267-004/Rev. E (R6006B3004 and R6006D4009). The R1425 Detonator Module accepts an initiating device circuit input and provides high speed response for actuating a max of two solenoids, one on each of two releasing circuits, for automatic release of water or extinguishing systems. Honeywell solenoid valve Model 73218BN4UNLVNOC111C2 is FM Approved for use with deluge applications. The Model W2400 Ground Fault Monitor Module provides ground fault monitoring integrity for the system. Field devices include X3301, X2200, X5200, and X9800 Pulse Output version Flame Detectors (see further details in listings under Fire Detection, Flame Actuated). The FDRS system is provided with 24 V dc power derived from a 120 V ac, 60 Hz input power supply/battery charger, Models EQ2110PS, EQ2130PS, EQ2175PS, with BFD battery fault detector, which provides battery back-up supervision and is connected, via dry contacts, to a FM Approved fire alarm control in temperatures of 0° to +50°C. For automatic release of extinguishing systems, the FDRS is connected to an FM Approved local protective control. For automatic release of preaction and deluge sprinkler systems, the FDRS is connected to an FM Approved control for automatic release of preaction and deluge sprinkler systems. Batteries (maximum AH rating dependent on power supply used) provide the necessary 90 hours standby capacity. For those occupancies having a 24 V dc primary supply plus a secondary (standby) supply with the 24 or 90 hour capacity (refineries, power plants, gas processing distribution networks, etc.), the power supply/battery charger may not be required. Eagle Quantum System. The releasing circuit for the EQ2500ARM agent release module or for the FENWALNET 2000 release module (74-200001-001) will actuate the following compatible 24 V dc solenoid valves: ASCO Models T8210A107, R8210A107, 8210A107 and 8210G207; and Skinner Models LV2LBX25, 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2 and 71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. (See also description under AUTOMATIC RELEASES FOR EXTINGUISHING SYSTEMS AND OTHER FIRE PROTECTION EQUIPMENT.) Eagle Quantum Premier System. Releasing circuit operation provided by EQ3700 Direct Current Input/Output (DCIO) Module, EQ3730 Enhanced Discrete Input/Output (EDIO) Module, EQ3740 Intelligent Protection Module (IPM), and EQ25xxARM Agent Release Module. EQ300X Series Controller has Class A signaling line circuit, (referred to as local operating network [LON]). EQ3730EDIO can be configured for Class A initiating device circuits. Use of EQ22xxIDC Initiating Device Circuit and EQ3700 DCIO, EQ3730EDIO and EQ3740 IPM Modules' Class B initiating device circuits requires the initiating device circuits from these modules to be no longer than 20 ft (6 m) and be installed in conduit. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models T8210A107, R8210A107, 8210A107, 8210G207, HV2648571, HV2648581, Skinner Models 73218BN4UNLVNOC111C2, 73212BN4TN00N0C111C2, 73212BN4TNLVNOC322C2, and 71395SN2ENJ1NOH111C2, Viking Model No. HV-274-060-001. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. Power supplies EQ2110PS, EQ2130PS and EQ2175PS use batteries of maximum capacities of 100, 300, and 750 AH, respectively, to provide 90 hours of emergency power. (See also description under AUTOMATIC RELEASES FOR EXTINGUISHING SYSTEMS AND OTHER FIRE PROTECTION EQUIPMENT.)

Fike Corp, 704 S 10th St, Blue Springs MO 64013

INTELLA-SCAN II. Models 10-201-E1, -E2, -E4 programmable fire alarm control panel with enhanced control unit (10-2111) using Version 1.3 firmware. Two Class A initiating circuits are provided on the input/input module (10-1777A or 10-2096), one Class A initiating circuit is provided on the input/output module (10-1778A or 10-2097). Analog communications module (10-2101) provides Class A initiating circuit for connection of up to 127 addressable initiating devices. The Class A initiating circuits are capable of cross-zone operation. Addressable solenoid output module (55-007) provides a supervised 24 V dc output rated at one amp; the solenoid output activation time should be set for no less than one min. Compatible solenoid valves are ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. See LOCAL PROTECTIVE SIGNALING listing for min configuration requirements and optional module designations. In the event of primary power failure, four 33 AH, 12 V batteries (connected in parallel for 66 AH, 24 V dc) (10-048) provide 90 hours of emergency power. Equipment suitable for use at temperatures of 32° to 122°F (0° to 50°C), unless otherwise indicated. SHP Programmable Fire Alarm Control P/N 10-063 with V1.00 firmware. Controller Part Number designation as follows:P/N 10-2452-2 for preaction sprinkler release mode only, or P/N 10-2452-1 for clean agent and/or preaction sprinkler release mode. Five initiating device circuits (IDCs) are located on the controller board of the SHP. Inputs 1 and 2 are capable of cross-zone, sequential alarm, or single detector release. The initiating device circuits must be converted to (Class A) Style D wiring performance with the connection of Class A input module, P/N 10-2450. Two 12 V dc, up to 40 AH batteries wired in series provide the required 90 hours of secondary power. For FM Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. [See further description under LOCAL PROTECTIVE SIGNALING]. Cheetah Addressable Control System with Software Revision Level 5.30 using solenoid module P/N 55-022 and release module P/N 10-1832. For FM Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. 24 V dc batteries rated 7-65 AH are available to provide 90 hours of emergency operation. (See description under LOCAL PROTECTIVE SIGNALING.) CyberCat 254 and 1016 Fire Alarm Control Systems (P/N 10-064 & 10-066). Programmable addressable systems consisting of P/N 10-2525 and P/N 10-2472 CyberCat Controllers with V1.30 firmware for the 254 and 1016 models, respectively, within P/N 10-2483(R/B) enclosure, and power supply with transformers P/N 02-10881 (120 Vac) or P/N 02-10882 (240 Vac). Controller connects with P/N 55-042 or

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-123

55-047 Supervised Control Module (SCM) to provide peer-to-peer digital communication protocol between the conventional notification appliance circuits and the CyberCat signaling line circuit. In addition, the SCM operates solenoids rated up to 2 Amps @ 24 V dc. Controller is also compatible with P/N 55-052 and P/N 55-053 Releasing Control Modules (RCM). The RCM supervises solenoid of a sprinkler water control valve and is connected to the controller SLC loop. For Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. 24 V dc batteries rated 18-75 AH are available to provide 90 hours of emergency operation. [See further description under LOCAL PROTECTIVE SIGNALING]. Cheetah Xi Fire Alarm Control System (P/N 10-068). Programmable addressable system consisting of P/N 10-2542 Cheetah Xi Controller with V1.30, within P/N 10-2541(R/G) enclosure, and power supply with transformers P/N 02-10881 (120 Vac) or P/N 02-10882 (240 Vac). Controller connects with p/ns 55-042 or 55-047 Supervised Control Module (SCM) to provide peer-to-peer digital communication protocol between the conventional notification appliance circuits and the CyberCat signaling line circuit. In addition, the SCM operates solenoids rated up to 2 Amps @ 24 V dc. In addition, Release Control Module p/ns 55-042 or 55-047 operates solenoids rated up to 2 Amps @24 V dc. For Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. 24 V dc batteries rated 18-75 AH are available to provide 90 hours of emergency operation. [See further description under LOCAL PROTECTIVE SIGNALING]. Cheetah Xi 50 and Cyber Cat 50 Fire Alarm Control units are programmable addressable systems consisting of [P/N 10-2622, P/N 10-2620], respectively Controller with V3.00, within P/N 10-2623(R/G) and 10-2621 (R/B) enclosure, and power supply with transformers P/N 02-10881. Controller connects with p/ns 55-042 or 55-047 Supervised Control Module (SCM) to provide peer-to-peer digital communication protocol between the conventional notification appliance circuits and the signaling line circuit. In addition, the SCM operates solenoids rated up to 2 Amps @24V dc. In addition, Release Control Module [p/ns 55-042 or 55-047] operates solenoids rated up to 2 Amps @24 V dc. For Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. 24 V dc batteries rated 18-75 AH are available to provide 90 hours of emergency operation. [See further description under LOCAL PROTECTIVE SIGNALING]. Rhino programmable control includes (DCM) detection and control module P/N 10-2141 (110 V ac) or -2144 (220 V ac) which are capable of cross-zone detection. Compatible with ASCO Models 8210A107, R8210A107, T8210A107 and Skinner Model LV2LBX25 and 73218BN4UNLVNOC111C2 solenoid valves. For FM Approved combinations of solenoid water control valves, refer to AUTOMATIC WATER CONTROL VALVES. 24 V dc batteries rated 17-33 AH are available to provide 90 hours of emergency operation. (See also LOCAL PROTECTIVE SIGNALING.) Shark Fire Alarm Control. Analog Addressable Control P/N 10-056-1 with firmware level 2.00. The Detector Board (P/N 10-2323) provides one signaling line circuit (SLC) which meets NFPA Style 4, 6, or 7 wiring performance. Two notification appliance circuits (Class A or B) Style Y, or Z are provided. Each NAC is rated for 1.5 Amps output and can control one solenoid each. Solenoid Series Impedance device P/N 10-2360 must be used when connecting a solenoid to the NAC circuit. Optional Addressable NAC Module P/N 55-038 (which requires a separate 24 V dc power to operate) provides a 2 A, 30 V dc output for a solenoid valve. The output circuit is supervised using a 47K ohm end of line resistor. 24 V dc batteries rated 7-65 AH are available to provide 24 hours of emergency operation. For FM Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. [For specific details on this system see LOCAL PROTECTIVE SIGNALING].

Fire Control Instruments Inc, 16 Southwest Park, Westwood MA 02090

Models FC-72DL, -DL2. Power supply operates on 120 V ac, 2.0 A, delivering 24 V dc at 4.0 A to battery charger and Class A detection circuit(s). For Model FC-72DL2, Class A initiating circuits are capable of cross-zone operation. FC-72DL provides one initiating device circuit; FC-72DL2 provides two, one of which can be used for N.O. contact supervisory devices. A typical configuration would include BMFC-6 basic control card, PS-6 power supply, 1 or 2 ZDM zone module(s), and BCM-6 bell card. Supervised releasing circuit for Skinner solenoid valve Model LV2LBX25 or ASCO solenoid valve Models WPX8223A3E, T8210A107, R8210A107, 8210A107 or the Star Model D deluge valve solenoid. Optional RDF releasing device interface module for Skinner solenoid valve Model LV2LBX25 or ASCO solenoid valve Models T8210A107, R8210A107 or 8210A107. The FC-72DL, -72DL2 are equipped with battery to provide 90 hours of emergency power. Model FC-72 with RDF releasing module for use with Skinner solenoid valve Model LV2LBX25. Must be equipped with 4.5, 6.0, 12.0, 15 or 31 AH batteries to provide 90 hours of standby power. The system may include any module (see also LOCAL PROTECTIVE SIGNALING) except TDS-438 time delay switch. The detection and signaling circuits must be wired in the Class A configuration. The Class A initiating circuits are capable of cross-zone operation. Model FC-72 for use with Skinner solenoid valve Model LV2LBX25 or ASCO solenoid valves Models T8210A107, R8210A107 and 8210A107. Must be equipped with batteries (4-31 AH) to provide 90 hours of emergency power. The system may include any module (see also LOCAL PROTECTIVE SIGNALING) except TDS-438 time delay switch. The detection and signaling circuits must be wired in the Class A configuration. The Class A initiating circuits are capable of cross-zone operation. FC-ID Addressable Programmable Fire Alarm System with Model RZST-2 remote zone signaling transponder and up to 5 RZB remote zone boards (each providing an addressable initiating circuit and a set of programmable alarm or trouble dry contacts) or RSB remote signal boards (each providing one releasing or indicating circuit or programmable set of dry contacts). The RZST-2 includes internal PS-6 24 V dc 4 A power supply. RSM remote signaling module provides the same functions as RSB but must receive power for release circuit from RZST-2 PS-6 power supply. Other functional modules can be selected as dictated by the needs of a particular installation (see listing for the FC-ID system under LOCAL PROTECTIVE SIGNALING). Compatible solenoid valves are ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries for the FC-ID control from 6 to 31 AH and for the RZST-2 from 6 to 15 AH provide 90 hours emergency power. FCI 7100 Series Release. Uses FCP 7100 field configuration program, Ver. 5.05 (capable of cross-zone operation). Class A initiating circuits are provided by the CAOM Class A module. Includes either MCOM or AOM-2S module programmed for preaction/deluge sprinkler applications, interfacing the either of the following solenoid valves: Skinner Models LV2LBX25, 73218BN4UNLVNOC111C2, and 71395SN2ENJ1NOH111C2 and ASCO Model 8210G207. Requires DRBC-1 power supply unit equipped with 110 AH batteries to provide 90 hours of emergency operation. See description under LOCAL PROTECTIVE SIGNALING. FCI 7200 Micro Fire Alarm Control. Uses FCP 7200 field configuration program, Version 4.1 (capable of cross-zone operation). Class A initiating circuits are provided on the analog (ALU-M) module. Compatible with ASCO Models 8210A107, T8210A107 and R8210A107 solenoid valves. 24 V dc standby batteries rated 6 to 31 AH are available to provide 90 hours of emergency operation. (See description under LOCAL PROTECTIVE SIGNALING.) FCI 7200 Series Release. Uses FCP 7200 field configuration program, Ver. 6.2 (capable of cross-zone operation). Class A initiating circuits are provided by the ALU Class A module. Includes either SCU or AOM-2S module programmed for preaction/deluge sprinkler applications, interfacing the either of the following solenoid valves: Skinner Models LV2LBX25, 73218BN4UNLVNOC111C2, and 71395SN2ENJ1NOH111C2 and ASCO Model 8210G207. Requires batteries to provide 90 hours of emergency operation. See description under LOCAL PROTECTIVE SIGNALING. E3 Series Release. Class A initiating circuits are provided by the ILI-MB-E3 main board. Output circuit of the main board or via AOM-2S, AOM-2SF module for preaction/deluge sprinkler applications. PM-9 power supply unit equipped with 55 AH batteries to provide 90 hours of emergency operation. See description under LOCAL PROTECTIVE SIGNALING.

Fire-Lite Alarms Inc, One Fire-Lite Place, Northford CT 06472

Sensiscan 2000 programmable fire alarm panel using firmware revision level 3. The min configuration consists of either a CAB-A2F, -B2F, -A3F or -B3F enclosure, CPU-2000 central processing unit, MPS-24F or -24BF power supply, and an initiating module IZ-4F or -8F. CPU-2000 provides two indicating circuits, one alarm and one trouble relay output, reverse polarity circuit, and a local energy municipal tie for auxiliary protective signaling. Requires TC-2F or -4F time control modules with operating system firmware revision level 2. Modules are programmable

FM Approvals

1-124

September 2007 -- Approval Guide Automatic Sprinkler Systems

for either cross zone or dual zone operation. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25, and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby battery packs (24 V dc, 12 and 15 AH) provide 90 hours of standby operation. See LOCAL PROTECTIVE SIGNALING listing for other FM Approved modules.

GE Security Inc, 8985 Town Center Pkwy, Bradenton FL 34202 Mirtone, 8985 Town Center Pkwy, Bradenton FL 34202

Automatic Release. EST2 Fire Panel (see listing under LOCAL PROTECTIVE SIGNALING). Programmable control. Release circuits are via SIGA-REL releasing module. Used with model RELA-EOL polarized end of line resistor. For deluge and preaction sprinkler system release, compatible solenoid valves include Skinner solenoid valve Model LV2LBX25; ASCO solenoid valves Model T821A107, R821A107, 821A107 and 8210G207; Skinner solenoid valves Model 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, and 71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries are available in 24 AH capacity to provide the required 90 hours of standby operation. Automatic Release. EST3 Fire Panel (see listing under LOCAL PROTECTIVE SIGNALING). Programmable control. Release circuits are via SIGA-REL releasing module. Used with model RELA-EOL polarized end of line resistor. For deluge and preaction sprinkler system release, compatible solenoid valves include Skinner solenoid valve Model LV2LBX25; ASCO solenoid valves Model T821A107, R821A107, 821A107 and 8210G207; Skinner solenoid valves Model 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, and 71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries are available in 65 AH capacity to provide the required 90 hours of standby operation. Automatic Release. MIR-2 Fire Panel (see listing under LOCAL PROTECTIVE SIGNALING). Programmable control. Release circuits are via GSA-REL releasing module. Used with model RELA-EOL polarized end of line resistor. For deluge and preaction sprinkler system release, compatible solenoid valves include Skinner solenoid valve Model LV2LBX25; ASCO solenoid valves Model T821A107, R821A107, 821A107 and 8210G207; Skinner solenoid valves Model 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, and 71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries are available in 24 AH capacity to provide the required 90 hours of standby operation. Automatic Release. MIR-3 Fire Panel (see listing under LOCAL PROTECTIVE SIGNALING). Programmable control. Release circuits are via GSA-REL releasing module. Used with model RELA-EOL polarized end of line resistor. For deluge and preaction sprinkler system release, compatible solenoid valves include Skinner solenoid valve Model LV2LBX25; ASCO solenoid valves Model T821A107, R821A107, 821A107 and 8210G207; Skinner solenoid valves Model 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, and 71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries are available in 65 AH capacity to provide the required 90 hours of standby operation. Automatic Release. Quick Start (QSC, QS1, and QS4) Fire Alarm Control. (See listing under LOCAL PROTECTIVE SIGNALING). Programmable control. Release circuits are via SIGA-REL releasing module which may use SIGA-APS auxiliary power supply. Used with model RELA-EOL polarized end of line resistor. For deluge and preaction sprinkler system release, compatible solenoid valves include Skinner solenoid valve Model LV2LBX25; ASCO solenoid valves Model T821A107, R821A107, 821A107 and 8210G207; Skinner solenoid valves Model 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, and 71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries are available in 40 Ah capacity to provide the required 90 hours of standby operation. Quick Start (QSC, QS1, and QS4) Fire Alarm Control. Programmable control. Release circuits are via SIGA-REL releasing module which may use SIGA-APS auxiliary power supply. Used with model RELA-EOL polarized end of line resistor. Any one of the following manual releases, service disconnect switches, and abort stations must be used: model 276A-REL or 278A-REL manual release, RELA-SRV service disconnect, and RELA-ABT abort station. Standby batteries are available in up to 40 Ah capacity to provide the required 24 hours of standby operation. (See listing under LOCAL PROTECTIVE SIGNALING). Automatic Release. Quick Start (MIRQSC, MIRQS1, and MIRQS4) Fire Alarm Control. (See listing under LOCAL PROTECTIVE SIGNALING). Programmable control. Release circuits are via SIGA-REL releasing module which may use SIGA-APS auxiliary power supply. Used with model RELA-EOL polarized end of line resistor. For deluge and preaction sprinkler system release, compatible solenoid valves include Skinner solenoid valve Model LV2LBX25; ASCO solenoid valves Model T821A107, R821A107, 821A107 and 8210G207; Skinner solenoid valves Model 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, and 71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries are available in 40 Ah capacity to provide the required 90 hours of standby operation.

Gamewell Co, The, 12 Clintonville Rd, Northford CT 06472

IdentiFlex 610 analog/addressable fire alarm control with Version 7.2.1 firmware. The IF610 system consists of a CPU module, operators display, bus driver module, analog addressable interface module AAM-95, and a 6.0A power supply. The IdentiFlex-610 analog addressable interface modules AAM-95 monitor and control up to 126 analog/addressable devices per circuit for a total of 504 devices per module. The signaling line circuits (SLC) shall be wired for (Class A) Style 6 performance. The IdentiFlex-610 bus driver module has two Style Y or Z notification appliance circuits rated 2A each and four Form C relays rated 2A @ 30 V DC or 120 VAC @ 1 amps. The Addressable Releasing Solenoid Interface module RSI-95 is installed with the AAM-95 module to provide releasing solenoid control. Only one RSI-95 and solenoid may be connected together for each releasing circuit. Operating input voltage: 120 V ac @ 60Hz. Secondary Power: 24 V dc batteries rated 7-25 AH are available to provide 90 hours emergency operation. (See also LOCAL PROTECTIVE SIGNALING for detailed information.) IdentiFlex 632 and IdentiFlex 654/658 Conventional and Analog/Addressable Fire Alarm Control Systems with Firmware Version 7.0. The IdentiFlex 632/654/658 are analog/addressable and conventional microprocessor based fire alarm controls. The IdentiFlex 632/654/658 can monitor and control up to 2016 analog addressable input/output points. In addition, the IdentiFlex 632 can also accommodate up to 56 conventional input/output circuits. The IdentiFlex 654/658 can accommodate up to 128 conventional input/output points. The signaling line circuits (SLC) shall be wired for (Class A) Style 6 performance. The Addressable Releasing Solenoid Interface module RSI-95 is installed with the AAM-95 module to provide releasing solenoid control. Only one RSI-95 and solenoid may be connected together for each releasing circuit. The Conventional Input Modules (CIM-4 or CIM-8) provide monitoring capabilities of conventional detectors and contact type devices. Required module CIM-SDA Initiating (Class A) Adapter provides a (Class A) Style D wiring for input circuits. 24 V dc batteries rated 5-50 AH are available to provide 90 hours emergency operation. Optional Auxiliary Power Supply, APS-8 mounts into one module expansion slot providing two 4 amp outputs for notification appliances or auxiliary power. (See also AUTOMATIC RELEASES FOR PREACTION AND DELUGE SYSTEMS.) IdentiFlex 602 Series, models IF 602-126R, IF 602-126RXL, IF602-252R and IF602-252RXL programmable controls. The Addressable Releasing Solenoid Interface module RSI-95 is installed to provide releasing solenoid control. Only one RSI-95 and solenoid may be connected together for each releasing circuit. These panels are compatible with Solenoid groups [A], [B], [D], [E], [F], [G]. Standby battery (24 V dc, 26 AH) provides 90 hour standby operation. (See control panel description under LOCAL PROTECTIVE SIGNALING.)

Honeywell International Inc, 1500 W Dundee Rd, Arlington Heights IL 60004

Automatic Release. XLS-100 Fire Panel (see listing under LOCAL PROTECTIVE SIGNALING). Programmable control. Release circuits are via XLS-REL releasing module. Used with model RELA-EOL polarized end of line resistor. For deluge and preaction sprinkler system release, compatible solenoid valves include Skinner solenoid valve Model LV2LBX25; ASCO solenoid valves Model T821A107, R821A107, 821A107 and 8210G207; Skinner solenoid valves Model 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, and 71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries are available in 24 AH capacity to provide the required 90 hours of standby operation.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-125

Automatic Release. XLS-1000 Fire Panel (see listing under LOCAL PROTECTIVE SIGNALING). Programmable control. Release circuits are via XLS-REL releasing module. Used with model RELA-EOL polarized end of line resistor. For deluge and preaction sprinkler system release, compatible solenoid valves include Skinner solenoid valve Model LV2LBX25; ASCO solenoid valves Model T821A107, R821A107, 821A107 and 8210G207; Skinner solenoid valves Model 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, and 71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries are available in 65 AH capacity to provide the required 90 hours of standby operation. XLS140(E) Fire Alarm Control Panel. Basic system consists of the XLS140-CPU module with internal power supply. 120 V ac primary system provides four notification appliance circuit/releasing circuit outputs rated at 24 V dc 2.5 A plus two 24 V dc 1.25 A (total) auxiliary outputs. Total power output is 6 A in alarm, 3A in standby. Release circuit requires REL 2.2K end-of-line device for supervision. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (TM-4) provides a local energy municipal tie for auxiliary protective signaling. Standby battery (24 V dc up to 60 AH) provides 90 hour standby operation. See control panel description under LOCAL PROTECTIVE SIGNALING.

Johnson Controls Inc, 507 E Michigan St, Milwaukee WI 53202-5202

FC-2000 programmable fire alarm panel using firmware revision level 6. The min configuration consists of either a CAB-A2, -B2, -C2, -D2, -A3, -B3, -C3 or -D3 enclosure, CPU-2000 central processing unit, MPS-24, -24A or -24B power supply and an initiating module IZM-4 or -8. CPU-2000 provides two indicating circuits; one alarm and one trouble relay output, reverse polarity circuit and a local energy municipal tie for auxiliary protective signaling. Indicating appliance circuits supply 18-30 V dc; therefore, the FM Approved devices used must be capable of operating throughout the entire voltage range. FC-2000 requires TCM-2 or -4 time control modules with operating system firmware revision level 2. Modules are programmable for either cross zone or dual zone operation. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby battery packs (24 V dc, 12 and 25 AH) provide 90 hour standby operation. See LOCAL PROTECTIVE SIGNALING listing for other FM Approved modules. Fire Alarm Control. IFC-200 Analog Fire Panel. Programmable control uses firmware revision level 2. Contains a signaling line circuit with cross-zone capability and four indicating appliance/release circuits. For deluge and preaction sprinkler system release, compatible solenoid valves are ASCO Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby battery packs (24 V dc, 7 to 12 AH) provide 90 hours standby operation. IFC-400 Fire Alarm Control Panel. Programmable control. Basic system consists of a combination of CPU-400 module and MPS-400 power supply. 120/240 V ac primary system provides four notification appliance circuit/releasing circuit outputs from the MPS-400 rated at 24 V dc 2.5 A. Release circuit requires REL 2.2K end-of-line device for supervision. Total MPS-400 power output is 6 A in alarm. Standby battery (24 V dc up to 55 AH) provides 90 hour standby operation. (See control panel description under LOCAL PROTECTIVE SIGNALING.) IFC-640(E) Fire Alarm Control Panel. Basic system consists of the JCPU-640 module with internal power supply. 120 V ac primary system provides four notification appliance circuit/releasing circuit outputs rated at 24 V dc 2.5 A plus two 24 V dc 1.25 A (total) auxiliary outputs. Total power output is 6 A in alarm, 3A in standby. Release circuit requires REL 2.2K end-of-line device for supervision. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (TM-4) provides a local energy municipal tie for auxiliary protective signaling. Standby battery (24 V dc up to 60 AH) provides 90 hour standby operation. See control panel description under LOCAL PROTECTIVE SIGNALING. IFC1010 Fire Alarm Control Panel. (See listing under LOCAL PROTECTIVE SIGNALING.) Standby battery packs (24 V dc, 9.5 to 55 AH) provide 90 hour standby operation. IFC2020 Fire Alarm Control Panel. (See listing under LOCAL PROTECTIVE SIGNALING.) Standby battery packs (24 V dc, 9.5 to 55 AH) provide 90 hour standby operation. IFC-3030 Fire Alarm Control Panel. Basic system consists of a combination of JCPU-3030ND or JCPU-3030D, AMPS-24/-24E Power Supply, 120/240 VAC primary system is an addressable power supply and battery charger with two outputs rated at 24V dc, 1.0A, and 24V dc, 4.5A. It operates in FlashScan® or CLIP mode. Release circuit requires REL 2.2K end-of-line device for supervision. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (TM-4) provides a local energy municipal tie for auxiliary protective signaling. Standby battery (24 V dc up to 60 AH) provides 90 hour standby operation. (See control panel description under LOCAL PROTECTIVE SIGNALING). IFC-3030 Fire Alarm Control Panel. Basic system consists of a combination of JCPU-3030ND or JCPU-3030D, AMPS-24/-24E Power Supply, 120/240 VAC primary system is an addressable power supply and battery charger with two outputs rated at 24 V dc, 1.0 A, and 24 V dc, 4.5 A. It operates in FlashScan® or CLIP mode. Release circuit requires REL 2.2K end-of-line device for supervision. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (TM-4) provides a local energy municipal tie for auxiliary protective signaling. Standby battery (24 V dc up to 60 AH) provides 90 hour standby operation. (See control panel description under LOCAL PROTECTIVE SIGNALING).

Kidde-Fenwal Inc, 400 Main Street, Ashland MA 01721

GEMINI Control P/N 295031. Contains P/N 295005 common control module, P/N 295006 suppression module (capable of cross-zone operation), P/N 295009 detection (Class A) module and 4 A power supply. Standby batteries rated 60 AH provide for 90 hours of emergency operation. Gemini II Multi-Hazard Control System. Modular system consisting of a Main Control Panel (MCP) with Rev. BA operating software, Remote Hazard Unit (RHU) with Rev. BA operating software, Remote Display Unit (RDU) with Rev. BA operating software and Optional Relay Board (ORB). Both the MCP and the RHU are provided with two release circuits and a stop valve output are provided for agent release or sprinkler release which will actuate one 24 V dc control head P/N 48650001, 899175 or 890181. For Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. The modular system is provided with a standby battery bank up to 66 AH in capacity to supply the required 90 hours of standby power. (See Control Panel Description under LOCAL PROTECTIVE SIGNALING.) FemwalNET 2000 and FenwalNET 2000 LT programmable analog control panels are equipped with CCM (single loop P/N 74-200008-701) Rev. CCMF82.3SL. FenwalNET 2000ML is equipped with CCM (Multi loop P/N 76-100008-800) software Rev. CCMF82.3ML. All the controls are equipped with power supply module (P/N 74-200009-010) Rev. AA (configured for releasing service). Optional agent release module (P/N 74-200001-001) Rev. AD may be installed in the FenwalNET 2000 and FenwalNET 2000 ML. For Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. 24 V dc batteries rated 17-99 AH are available to provide 90 hours of emergency operation. (See description under LOCAL PROTECTIVE SIGNALING.) Fenwal 3220 Multi-Hazard Control System. Modular system consisting of a Main Control Panel (MCP) with Rev. BA operating software, Remote Hazard Unit (RHU) with Rev. BA operating software, Remote Display Unit (RDU) with Rev. BA operating software and Optional Relay Board (ORB). Both the MCP and the RHU are provided with two release circuits for agent release or sprinkler release which will actuate one 24 V dc control head P/N 48650001, 899175 or 890181. For Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. The modular system is provided with a standby battery bank up to 66 AH in capacity to supply the required 90 hours of standby power. (See Control Panel Description under LOCAL PROTECTIVE SIGNALING.)

FM Approvals

1-126

September 2007 -- Approval Guide Automatic Sprinkler Systems

PEGAsys and PEGAsys LV programmable analog control panels equipped with CCM (single loop P/N 76-100008-701) Rev. CCMP82.3SL. PEGAsys ML is equipped with CCM (multi-loop P/N 76-200008-800) software Rev. CCMP82.3ML. All the controls are equipped with power supply module (P/N 76-100009-010) Rev. AA (configured for releasing service). Optional agent release module (P/N 76-100001-001) Rev. AD may be installed in the PEGAsys and PEGAsys ML. For Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. 24 V dc batteries rated 17-99 AH are available to provide 90 hours of emergency operation. (See description under LOCAL PROTECTIVE SIGNALING.) FENWALNET 6000 programmable analog addressable fire alarm control system with operating software Rev. 1.2.1. The control has one (Class A) Style 6, 7 or (Class B), Style 4 Signaling Line Circuit (SLC) that communicates with up to 255 analog addressable devices. The control also has two (Class A), Style Z or (Class B), Style Y Notification Appliance Circuits (NACs) rated 1.5 A @ 24 V dc. In addition, there are two releasing circuits rated 2.4A (max) @ 24 V dc for explosive initiators or solenoid-operated control heads and valves. Two more configurable output circuits are located on the mother board. The output circuits are used for connection to solenoid-operated control heads and valves, rated 2.4 A (max) @ 24 V dc. 24 V dc batteries rated 7 - 70 AH are available to provide 90 hours of emergency operation. [See further description under LOCAL PROTECTIVE SIGNALING.] ARIES programmable analog addressable fire alarm control system with operating software Rev. 1.2.1. The control has one (Class A) Style 6, 7 or (Class B), Style 4 Signaling Line Circuit (SLC) that communicates with up to 255 analog addressable devices. The control also has two (Class A), Style Z or (Class B), Style Y Notification Appliance Circuits (NACs) rated 1.5 A @ 24 V dc. In addition, there are two releasing circuits rated 2.4A (max) @ 24 V dc for solenoid-operated control heads and valves. Two more configurable output circuits are located on the mother board. The output circuits are used for connection to solenoid-operated control heads and valves, rated 2.4 A (max) @ 24 V dc. 24 V dc batteries rated 7-70 AH are available to provide 90 hours of emergency operation. [See further description under LOCAL PROTECTIVE SIGNALING]. Model AEGIS conventional fire alarm-suppression control panel consists of Rev. 1.0.0 operating software. The control panel has one manual release circuit rated 24 V dc, 10 mA. One abort circuit rated 24 V dc, 10 mA. There are two (Class B) Style Y, supervised, releasing circuits rated 2.4A (max) @ 24 V dc. The panel is provided with the releasing circuits for agent release or sprinkler release which will actuate a 24 V dc control head. For Approved combination of solenoid and water control valves, refer to Automatic Water Control Valve listings that follow. The panel is provided with standby battery capacity up to 68 AH to supply the required 90 hours of standby. (See control panel description under LOCAL SERVICE.) Model 732 conventional fire alarm-suppression control panel consists of Rev. 1.0.0 operating software. The control panel has one manual release circuit rated 24 V dc, 10 mA. One abort circuit rated 24 V dc, 10 mA. There are two (Class B) Style Y, supervised, releasing circuits rated 2.4A (max) @ 24 V dc. The panel is provided with the releasing circuits for agent release or sprinkler release which will actuate a 24 V dc control head. For Approved combination of solenoid and water control valves, refer to Automatic Water Control Valve listings that follow. The panel is provided with standby battery capacity up to 68 AH to supply the required 90 hours of standby. (See control panel description under LOCAL SERVICE.)

King-Fisher Co, 2350 Foster Ave, Wheeling IL 60090

DACS I Detection, Actuation and Control System. Consists of Model KF-24-DS fire control (single zone) or KF-24-DS with optional Model KF-24-AN zone annunciator (up to 8 zones), integral 24 V dc power supply/battery charger. The Class A initiating circuits are capable of cross-zone operation. May be used with Kepco 110 V dc power supply Model RMD 24-B-110. Class A type initiating (detection) circuits for connection of FM Approved normally-open alarm contact heat detectors or manual stations. Supervised releasing circuits for use with 24 V dc Skinner Model LV2LBX-25 solenoid valve. DACS equipped with 5 to 50 AH batteries to provide up to 90 hours of emergency power. 80 AH batteries are available to provide more than the required 90 hours. DACS II Detection, Actuation and Control System. Consists of Model KFUCP control with Class A initiating circuits utilizing Models KF-TL-300, -400, -500, -540, -700, -900 line type (thermistor) heat detectors. The Class A initiating circuits are capable of cross-zone operation. May be used with Kepco 110 V dc power supply, Model RMD 24-B-110. The model number is the temperature (°F) at which a 50 ft (15 m) length of thermistor will have a resistance of 100 ohms. Supervised releasing circuits for use with Skinner Model LV2LBX-25, 24 V dc solenoid valve and the FM Approved Grinnell Model A-4 or Reliable Automatic Sprinkler Model B deluge valves. DACS II is equipped with 5 to 50 AH batteries to provide the required 90 hours of emergency power; 80 AH batteries are available to provide more than the required 90 hours. Fire Alarm Control Panel. Models KFRTI-20, -52. Provide up to 20 and 52 alarm zones respectively, through the selection of the following subassemblies: 66115 power supply board, 66150 CPU board (Software Ver. IRII-6), 66156 alarm control board, 66165 dual zone Class ``A'' input board, 66167 single zone Class ``A'' input with release, 66163 4-zone input board, 66099 main mother board, 66107 zone mother board; 66111 switch panel assembly. The Class A initiating circuits are capable of cross-zone operation. The single zone input with release is rated for 24 V dc, 1.3 A. For deluge and preaction sprinkler systems, compatible solenoid valves include ASCO Models R8210A107, T8210107, 8210A107 or Skinner Model LV2LX25. Refer to AUTOMATIC WATER CONTROL VALVES for FM Approved combinations of solenoid and deluge water valves. The total current available for release and signaling devices is limited to 2A. The following batteries are available to provide 24 or 90 hours of standby power: 17014 (5 AH), 17012 (12.5 AH), 17015 (25 AH).

Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840 Bad Oldesloe, Germany

Fire Alarm Control Panel FMZ 4100 GAB 32. Control uses software level 41EGB32X, P/N 902657. Control consists of the Line Card Rack (P/N 802599), which houses redundant CPU cards ZKR (P/N 895465), LED control card LEDAK (P/N 806271), Line cards LK and LKA (P/N 802551 and P/N 805424), Extinguishing Control card LO (P/N 837190), FTX Spark Test card (P/N 802540), SK Loop (MxLoop) card (P/N 902026), PC/printer interface card PC/DRUIF (P/N 832349), relay interface card IF2 (P/N 802538). The following cards connect directly to external modules and detectors: 8 relay card RK8 and RK8TQ (P/N 802587 and P/N 800843), line termination cards LAK8 and LAK8A (P/N 802563and P/N 806477), solenoid valve/monitored output cards MVA4F (P/N 853507), SAK2 loop (MxLoop) connection card (P/N 800255), spark test connection cards FTX-AK8 (P/N 806209). Logic power supply 5 V DC/2 A (P/N 837104), Logic power supply 15 V DC/2 A (P/N 837116), 24V/6amp power supply USVI-SE-210 (P/N 835193 )). Front panel FPTUL with 8x40 character LCD display (P/N 801215), LED panels F + S FPFUS (P/N 837189) and FPS for MxLoop devices indication only (P/N 851973), ground fault module MEM (P/N 800096). Control can provide up to 32/96/128 × 9V Class B detection input zones (maximum 32 detectors per one zone), the panel designations being FMZ 4100 GAB 32, FMZ 4100 GAB 96, and FMZ 4100 GAB 128 respectively. The latter use line termination cards LAK8 or LAK8A, 32/96/128 Zener groups for manual pull stations (open circuit) connections, 32/96/128 solenoid/notification appliances/monitored outputs via MVA4F cards. Compatible with the following initiating devices: DMX 3000, and 3003 manual stations, IMX 1001E ionization type smoke detector, rated IP 23, OMX 1001C, OMX 1111C photoelectric type smoke detectors, rated IP 23, WMX 1000 D60, WMX 1000 D90, WMX 1000 F60, rated IP 65 and WMX 1000 F90 (rated IP 65) heat detectors, FMX 3100, FMX3511, and UMX 3000 flame detectors, all rated IP 65 and FUX 3001(L1) spark detector, rated IP65. Series F60 and D60 heat detectors are combination of fixed temperature and rate-of-rise 140°F (60°C), while Series F90 and D90 heat detectors have triggering temperature ranging from 201°F (94°C) to 230°F (110°C). Spacing guide for D60 and D90 series heat detectors is 25 × 25 feet (7.6 × 7.6 m); while for F60 and F90 series it is 15 × 15 feet (4.6 × 4.6 m). Compatible with the following analog addressable devices via the MxLoop card: IMX50 ionization smoke detector, OMX50 photoelectric smoke detector, WMX50 D60 rate-of-rise heat detector: spacing guide for D60 series heat detectors is 30 × 30 feet (9.1m × 9.1 m); DMX50/50F manual stations, SMX50 short circuit loop isolator, SUX50/50H contact monitoring module. For electric activated Deluge Sprinkler Systems, compatible solenoid valves are Minimax type 1/2-24 V/DC-2/2-Impulse, Minimax P/N 84 0131. Standby batteries 24 V, 65 AH provide 90 hours of emergency battery backup supply.

Mircom Technologies Ltd, 25 Interchange Way, Vaughan, Ontario L4K 5W3, Canada

FR-320-D (or blank)-R(or W) programmable fire alarm releasing control panel. ICAC-306 Class A Converter Module is required to configure the 6 initiating device circuits (IDC) for Class A, Style D operation. Provides 2 Class B releasing circuits. For deluge and preaction sprinkler

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-127

system release, compatible solenoid valves include ASCO Models T8210A107, R8210A107, 8210A107. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Primary power 120 or 240 V ac. 24 V dc secondary supply consisting of batteries rated 10-26 AH provide required 90 hours of emergency operation. (See also description under AUTOMATIC RELEASES FOR EXTINGUISHING SYSTEMS AND OTHER FIRE PROTECTION EQUIPMENT.)

Notifier, 12 Clintonville Rd, Northford CT 06472-1653

RP-1001 with operating system firmware revision level A. Including LED Interface Module (4XLM); Zone Relay Module (4XZM); Remote Annunciator (RZA-4X). Panel provides four input circuits: one detector; one manual release/detector; one waterflow; one supervisory and four output circuits: one alarm/waterflow bell; one waterflow/supervisory bell; one release; one supervisory bell/release. In addition one regulated and one unregulated 24 V auxiliary power output; one alarm and one trouble relay output are provided. Combined load for all external devices not to exceed 2.25 A. Field programmable using dip switches for either cross zone or dual zone. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (4XTM) provides a local energy municipal tie for auxiliary protective signaling. In the event of primary power failure battery packs (24 V dc, 12, 15 AH) are suitable for 90 hours of standby operation. System 500 programmable fire alarm panel using firmware revision level 3. The min configuration consists of a CAB-500 enclosure, CPU-500 central processing unit, MPS-24BPCA power supply, 4000TA transformer, and an initiating module IZ-4 or IZ-8. CPU-500 provides two indicating circuits; one alarm and one trouble relay output, reverse polarity circuit and a local energy municipal tie for auxiliary protective signaling. Requires TC-2 or TC-4 time control modules with operating system firmware revision level 2. Modules are programmable for either cross zone or dual zone operation. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby battery packs (24 V dc, 12 and 25 AH) provide 90 hour standby operation. See LOCAL PROTECTIVE SIGNALING listing for other FM Approved modules. System 5000 Programmable fire alarm panel using firmware revision level 6. The min configuration consists of either a CAB-A2, -B2, -C2, -D2, -A3, -B3, -C3 or -D3 enclosure, CPU-5000 central processing unit, MPS-24, -24A or -24B power supply and an initiating module IZM-4 or -8. CPU-5000 provides two indicating circuits; one alarm and one trouble relay output, reverse polarity circuit and a local energy municipal tie for auxiliary protective signaling. Indicating appliance circuits supply 18-30 V dc; therefore, the FM Approved devices used must be capable of operating throughout the entire voltage range. System 5000 requires TCM-2 or -4 time control modules with operating system firmware revision level 2. Modules are programmable for either cross zone or dual zone operation. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby battery packs (24 V dc, 12 and 25 AH) provide 90 hour standby operation. See LOCAL PROTECTIVE SIGNALING listing for other FM Approved modules. Fire Alarm Control. AFP-200 Analog Fire Panel. Programmable control (see listing under LOCAL PROTECTIVE SIGNALING). Contains a signaling line circuit with cross-zone capability and four indicating appliance/release circuits. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25, and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby battery packs (24 V dc, 7 to 12 AH) provide 90 hours standby operation. Fire Alarm Control. AM2020 Fire Panel. (See listing under LOCAL PROTECTIVE SIGNALING.) Programmable control. Release circuit is via CMX-1 and LIB-200, LIB-200A or LIB-400 modules. Standby battery packs (24 V dc, 9.5 to 55 AH) provide 90 hours standby power. Fire Alarm Control. AFP1010 Fire Panel. (See LOCAL PROTECTIVE SIGNALING.) Programmable control. Release circuit is via CMX-1 and LIB-200, LIB-200A or LIB-400 modules. Contains up to two output circuits. Standby battery packs (24 V dc, 9.5 to 55 AH) provide 90 hours standby power. AFC-600 Fire Alarm Control Panel. Basic system consists of a combination of CPU-600 module and MPS-6 power supply. 120/240 V ac primary system provides four notification appliance circuit/releasing circuit outputs from the MPS-6 rated at 24 V dc 2.5 A. Release circuit requires REL 2.2K end-of-line device for supervision. Total MPS-6 power output is 6 A in alarm. Standby battery (24 V dc up to 60 AH) provides 90 hour standby operation. See control panel description under LOCAL PROTECTIVE SIGNALING. AFP-300 or AFP-400 Fire Alarm Control Panel. Programmable control. Basic system consists of a combination of CPU-300 or CPU-400 module and MPS-400 power supply. 120/240 V ac primary system provides four notification appliance circuit/releasing circuit outputs from the MPS-400 rated at 24 V dc 2.5 A. Release circuit requires REL 2.2K end-of-line device for supervision. Total MPS-400 power output is 6 A in alarm. Standby battery (24 V dc up to 55 AH) provides 90 hour standby operation. (See control panel description under LOCAL PROTECTIVE SIGNALING.) NFS-3030 Fire Alarm Control Panel. Basic system consists of a combination of CPU-3030ND or CPU-3030D, AMPS-24/-24E Power Supply, 120/240 VAC primary system is an addressable power supply and battery charger with two outputs rated at 24Vdc, 1.0A, and 24V dc 4.5A. It operates in FlashScan® or CLIP mode. Release circuit requires REL 2.2K end-of-line device for supervision. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (TM-4) provides a local energy municipal tie for auxiliary protective signaling. Standby battery (24 V dc up to 60 AH) provides 90 hour standby operation. (See control panel description under LOCAL PROTECTIVE SIGNALING). NFS-640(E) Fire Alarm Control Panel. Basic system consists of the CPU-640 module with internal power supply. 120 V ac primary system provides four notification appliance circuit/releasing circuit outputs rated at 24 V dc, 2.5 A plus two 24 V dc, 1.25 A (total) auxiliary outputs. Total power output is 6 A in alarm, 3A in standby. Release circuit requires REL 2.2K end-of-line device for supervision. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (TM-4) provides a local energy municipal tie for auxiliary protective signaling. Standby battery (24 V dc up to 60 AH) provides 90 hour standby operation. See control panel description under LOCAL PROTECTIVE SIGNALING. NFS2-3030 Fire Alarm Control Panel. Basic system consists of a combination of CPU2-3030ND or CPU2-3030D, AMPS-24/-24E Power Supply, 120/240 VAC primary system is an addressable power supply and battery charger with two outputs rated at 24Vdc, 1.0A, and 24 V dc 4.5A. It operates in FlashScan® or CLIP mode. Release circuit requires REL 2.2K end-of-line device for supervision. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (TM-4) provides a local energy municipal tie for auxiliary protective signaling. Standby battery (24 V dc up to 60 AH) provides 90 hour standby operation. (See control panel description under LOCAL PROTECTIVE SIGNALING).

Pem-All Fire Extinguisher Corp, Div Pem Systems Inc, 39A Myrtle St, Cranford NJ 07016

PEM-2001 with operating system firmware revision level A. Including LED Interface Module (4XLM); Zone Relay Module (4XZM); Remote Annunciator (RZA-4X). Panel provides four input circuits: one detector; one manual release/detector; one waterflow; one supervisory and four output circuits: one alarm/waterflow bell; one waterflow/supervisory bell; one release; one supervisory bell/release. In addition one regulated and one unregulated 24 V auxiliary power output; one alarm and one trouble relay output are provided. Combined load for all extenal devices not to exceed 2.25 A. Field programmable using dip switches for either cross zone or dual zone. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (4XTM) provides a local energy municipal tie for auxiliary protective signaling. In the event of primary power failure, battery packs (24 V dc, 12, 15 AH) are suitable for 90 hours of standby operation.

FM Approvals

1-128

September 2007 -- Approval Guide Automatic Sprinkler Systems

Potter Electric Signal Company, 2081 Craig Road, Saint Louis MO 63146

PFC Series 100R Fire Control Panel provides one Style D initiating circuit, one Style B non-latching supervisory device circuit, one voltage reversing Style Y indicating circuit rated 24 V dc, 500 mA, one voltage reversing releasing circuit rated 24 V dc, 1 A and one auxiliary power supply circuit rated 24 V dc, 15 mA. Compatible solenoid valves are ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries rated 8 AH provide 90 hours of emergency operation. (See also LOCAL PROTECTIVE SIGNALING.) PFC Series 2000RC Fire Control Panel. (See also LOCAL PROTECTIVE SIGNALING.) Uses Firmware Version 1.1 with release circuit discharge times selectable (2 min. or continuous). Contains two signal initiating device circuits (field programmable for Style B or D operation), two signal indicating circuits, one manual releasing circuit, and one polarized releasing device circuit (24 V dc, 1 A continuous, 3 A momentary). The Style B and D initiating circuits are capable of cross-zone operation. Combined load of all external devices including signaling devices not to exceed 3 A. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25 and solenoid actuator in Star Sprinkler Model D deluge valve solenoid (P/N 5550). For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. In the event of primary power failure, standby battery packs (24 V dc, 6.5, 8, 10, 12, or 15 AH) are available for 90 hours emergency power. Model PFC-100RC Programmable Fire Control Panel. Provides one Style D alarm signal initiating device circuit, one Style B non-latching supervisory signal initiating device circuit, one voltage reversing Style Y notification appliance circuit rated 24 V dc, 500 mA, one voltage reversing releasing circuit rated 24 V dc, 1 A and one auxiliary power supply circuit rated 24 V dc, 15 mA. Compatible solenoid valves are ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries rated 8 AH provide 90 hours of emergency operation. (See also LOCAL PROTECTIVE SIGNALING.) Model PFC-4410 and PFC-4410A Programmable Fire Control Panel, using software Rev. 3.5. Provides four Class B (Style B) alarm signal initiating device circuits, one Class B (Style B) supervisory signal initiating device circuit, four voltage reversing Class B (Style Y) programmable output circuits rated 24 V dc, 1 A, and one auxiliary power supply circuit rated 24 V dc, 50 mA with 12 AH standby batteries or 75 mA with 17 AH standby batteries. CA2Z Class A initiating device module required to convert two Class B initiating device circuits to Class A (Style D) operation. Up to two CA2Z modules may be used. Initiating device circuits are capable of cross-zone operation. Compatible solenoid valves are ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model 73218B4UNLVOC111C2. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries rated 12 and 17 AH provide 90 hours of emergency operation. (See also LOCAL PROTECTIVE SIGNALING.) Model PFC-4410-RC and PFC-4410A-RC Fire Alarm Controls, using software Rev. 4.14. Provides four Class B (Style B) alarm signal initiating device circuits, one Class B (Style B) supervisory signal initiating device circuit, four voltage reversing Class B (Style Y) output circuits rated 24 V dc, 1 A, and one auxiliary power supply circuit rated 24 V dc, 200 mA. CA2Z Class A initiating device module required to convert two Class B initiating device circuits to Class A (Style D) operation. Up to two CA2Z modules may be used. Initiating device circuits are capable of cross-zone operation. Compatible solenoid valves are ASCO Models R8210A107, T8210A107, 8210A107, Skinner Models 73218B4UNLVOC111C2 and 73212BN4TNLVNOC322C2, and Viking Model HV-274-060-001. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries rated 12 AH provide the required 90 hours of emergency operation. (See also LOCAL PROTECTIVE SIGNALING.)

Protectowire Co, 40 Grissom Road, Plymouth MA 02360

Control Panel. Series ACR-1600, -1600HD, -1600LTI. Consists of Module CP-1041-S or -M and up to 50 AH capacity batteries for 90 hour standby power, at least one ZM-2200 or -2201 Class A zone module, at least one SM-1000 or -1001 release module and other functional modules as dictated by the needs of a specific installation (see listing of other functional modules under LOCAL PROTECTIVE SIGNALING). The control may be configured to provide supervision for 50 detection zones and is capable of cross-zone operation. Detection circuit suitability for Classes I, II, III, Division 1, Groups A, B, C, D, E, F and G hazardous locations via Leeds and Northrup Barrier 316569. FS-2000 Series Modular Fire Control Panel. Release module (RS-91 or RM-91) compatible with Skinner LV2LBX25, and ASCO Model 8210A107 solenoids (with or without R or T suffix), RS-91D compatible with Star Model D deluge valve. Release circuit on module RS-1 compatible with all valve groups A through K inclusive. Must be used with the class A detector circuit on a standard zone card ZC-91A/M for preaction deluge operations. Suitable for use with FM Approved automatic fire detectors such as Protectowire heat sensitive cable. Detection circuits are capable of cross zone applications. 24 V dc batteries for 90 hours of standby power are available in 4.5-55 AH capacities. (See also LOCAL PROTECTIVE SIGNALING.) FireSystem-2600HD Series Modular Fire Control Panel. Release module (RM-2)compatible with Skinner LV2LBX25, and ASCO Model 210A107 solenoids (with or without R or T suffix), (fused appropriately), Star Model D deluge; ASCO 8210G207; Skinner 73218BN4UNLVNOC111C2; Skinner 73212BN4TNLVNOC322C2; Skinner 71395SN2ENJ1NOH111C2; and Viking HV-274-060-001; solenoid valves. Suitable for use with FM Approved automatic fire detectors such as Protectowire heat sensitive cable. Detection circuits are capable of cross zone applications 24 V dc batteries for 90 hours of standby power are available in 7.0-60 AH capacities. (See also LOCAL PROTECTIVE SIGNALING.) Model SRP4x4 Fire Alarm Control. Control provided with four initiating device circuits (IDC), which must be configured for Class A Style D wiring. Up to three release circuits are provided. Each releasing appliance circuit is connected to a compatible 24 V dc solenoid. For FM Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. Standby battery bank rated 24 V dc, 18 AH is required to provide 90 hours of standby power. (See control panel description under LOCAL PROTECTIVE SIGNALING.)

Pyrene Corp, 130 Esna Park Dr, Markham Ontario L3R 1E3 Canada

Fire Alarm and Extinguishment Control Panel Series 4000 configured with 40-3002 extinguishment module and other functional modules as dictated by the needs of the installation (see listing for the Series 4000 control under LOCAL PROTECTIVE SIGNALING for other functional modules). For deluge/preaction sprinkler system applications, the Series 4000 control must be configured to provide Class A (Style D) initiating circuits. Initiating circuits can be configured for cross-zone operation. Release device circuits are rated at 2 A. Compatible solenoid valves are ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries rated 16 AH are available to provide 90 hours emergency power.

Pyro-Chem Inc, One Stanton Street, Marinette WI 54143

Fire Alarm Control. PCR-400IP Analog Fire Panel. Programmable control (see listing under LOCAL PROTECTIVE SIGNALING). Contains a signaling line circuit with cross-zone capability and four indicating appliance/release circuits. Release circuit can be provided via FCM-1 module and/or XP5-C and XP5-M Transponders. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25, and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby battery packs (24 V dc, 7 to 12 AH) provide 90 hours standby operation. Series Triton RP control with Rev. 1.01 software. Panel Model 551450 (red enclosure) is provided with 4 initiating device circuits (IDC), which must be connected to TEPG-US Model 430531 Class A Adapter Module to configure for (Class A) Style D wiring. Two release circuits are provided for sprinkler release. Each releasing appliance circuit must connect to a TEPG-US Model 430687 coil supervision module which in turn is connected to a compatible 24 V dc actuator or solenoid. For FM Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. Optional TEPG-US Models 430548 and 430550 External Battery Chargers provide the Triton RP charging capability for a standby battery bank up to 50 AH in capacity to supply the required 90 hours of standby power. (See Control Panel Description under LOCAL PROTECTIVE SIGNALING.)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-129

Series Triton RPA Addressable Control System. Analog control panel with Software Revision Level 3.03 using programmed Notification Appliance Circuits N3 or N4 on the Triton RPA SFI/O card. Each releasing appliance circuit must connect to a TEPG-US Model 430687 coil supervision module which in turn is connected to a compatible 24 V dc actuation device. Optional TEPG-US Model 430657 or 431193 Suppression Release Peripheral connects to the SLCNet circuit and to a notification appliance circuit from either the Triton RPA fire alarm control panel, or from the Triton EXT Notification Appliance Circuit Extender. This peripheral monitors the output releasing appliance circuit wiring for opens and shorts. Each releasing appliance circuit must connect to a TEPG-US Model 430687 coil supervision module which in turn is connected to a compatible 24 V dc solenoid or actuation device. For FM Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. SLCNet signaling line circuits must be configured for Class A, Style 6 wiring for this application. 24 Vdc batteries rated 25-50 AH are available to provide 90 hours of emergency operation. For battery requirements exceeding 25 AH, the TEPG-US Models 430548 or 430550 External Battery Charger must be used. (See Control Panel Description under LOCAL PROTECTIVE SIGNALING.)

Secutron Inc, 25 Interchange Way, Vaughan, Ontario L4K 5W3, Canada

MR2320-D (or blank)-R programmable fire alarm releasing control panel. MR-2300-A Class A Converter Module is required to configure the 6 initiating device circuits (IDC) for Class A, Style D operation. Provides 2 Class B releasing circuits. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models T8210A107, R8210A107, 8210A107. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Primary power 120 or 240 V ac. 24 V dc secondary supply consisting of batteries rated 10 - 26 AH provide required 90 hours of emergency operation. (See also description under AUTOMATIC RELEASES FOR EXTINGUISHING SYSTEMS AND OTHER FIRE PROTECTION EQUIPMENT.) Control Panels (compatible for use with Automatic Water Control Valves) Control Panel Group [(New group number to be assigned)]. These panels are compatible with Solenoid Groups [B]. MR2320 Series programmable fire alarm releasing control panels.

Siemens Building Technologies Inc, Fire Safety, 8 Fernwood Rd, Florham Park NJ 07932

Automatic Release. ALS2 Fire Panel (see listing under LOCAL PROTECTIVE SIGNALING). Programmable control. Release circuits are via SIGA-REL-LG releasing module. Used with model RELA-EOL polarized end of line resistor. For deluge and preaction sprinkler system release, compatible solenoid valves include Skinner solenoid valve Model LV2LBX25; ASCO solenoid valves Model T821A107, R821A107, 821A107 and 8210G207; Skinner solenoid valves Model 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, and 71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries are available in 24 AH capacity to provide the required 90 hours of standby operation. Automatic Release. ALS3 Fire Panel (see listing under LOCAL PROTECTIVE SIGNALING). Programmable control. Release circuits are via SIGA-REL-LG releasing module. Used with model RELA-EOL polarized end of line resistor. For deluge and preaction sprinkler system release, compatible solenoid valves include Skinner solenoid valve Model LV2LBX25; ASCO solenoid valves Model T821A107, R821A107, 821A107 and 8210G207; Skinner solenoid valves Model 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, and 71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries are available in 65 AH capacity to provide the required 90 hours of standby operation. System 3 Universal Alarm Control. Contains two initiating device circuits for ``Class A'' operation. FM Approved configuration consists of CP-35 control panel, PS-35S power supply, BC-35 battery charger and the following modules: DC-35S filter/regulator, TC-30U battery transfer, RM-30U or RM-30RU release, ZN-31U dual contact zone. Compatible solenoid valves are ASCO Models T8210A107, R8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. In the event of primary power failure, two 12 V 55 AH GC12550 batteries provide 90 hours of emergency power. See LOCAL PROTECTIVE SIGNALING listing for other FM Approved modules. MPC-6000 Fire Alarm Control Unit. Modular System made up of various combinations of devices and programmable configurations. Enclosures are MPC6-ENC or MPC6-ENC-B with SFTK-6B or SFTK-6R trim kits. Minimum system configuration includes an MPC6-MB2 main terminal board which includes a regulated 24V power supply, MPC6-DB2 display board with firmware version 7.01, an X1 Addressable Device Circuit with a capacity for 252 Addresses, four independent Class B (Style Y) notification appliance circuits (NACs) which can be combined in pairs for Class A (Style Z) operation, a Serial Interface Circuit that will drive 16 remote LCD annunicators and up to 8 Serial Relay Units and Serial Annuicator Units, four Form C relay contacts each rated at 1A @ 28Vdc and an RJ-11 Programming Port and MPC-REL Releaseing Module with RPT-1 Releasing Power Transformer. 90 hours of secondary power provided by two 12Vdc (38Ah) batteries mounted in an external BE-1 battery box. An optional external BE-1 battery box is available to allow connection of batteries up to 38Ah. For FM Approved combinations of solenoid control valves, refer to Automatic Water Control Valve listings. [See complete MPC-6000 system description under LOCAL PROTECTIVE SIGNALING]. MXL Programmable Modular Fire Alarm System. Uses Version 10.06 operating system and field programming software CSG-M Version 10.03. Requires CSM-4 signal module (configured for releasing service) compatible with Skinner Model LV2LBX25 and ASCO Models 8210A107 (with R or T suffixes) and Alarm-Saf Model AS/PS5-BFS-24-UL power supply. 24 V dc standby batteries rated (15-55 AH) are available for MXL control and Alarm-Saf power supply (31 AH) to provide 90 hours of emergency operation. (See also LOCAL PROTECTIVE SIGNALING.) MXL-IQ Programmable Modular Fire Alarm System. Uses Version. 6.06 operating system and field programming software CSG-M Version 10.03. Requires CSM-4 signal module (configured for releasing service) compatible with Skinner Model LV2LBX25 and ASCO Models 8210A107 (with R or T suffixes) and Alarm-Saf Model AS/PS5-BFS-24-UL power supply. 24 V dc standby batteries rated (15-55 AH) are available for MXL-IQ control and Alarm-Saf power supply (31 AH) to provide 90 hours of emergency operation. (See also LOCAL PROTECTIVE SIGNALING.) FireFinder XLS Fire Alarm Control System. Modular System made up of various combinations of devices and programmable configurations. Any of the CAB1, CAB2 or CAB3 Cabinet Enclosures may be used with CAB-MP mounting plate, CAB-TK trim kit and card cages CC-2 or CC-5. Any combination system must house a PMI [Person-Machine Interface] considered the main processor with a firmware level at 3.04; a Zone Indicating Card [ZIC-4A] which is equipped with four programmable (Class B) Style Y, or (Class A) Style Z circuits. These output circuits are rated 4A each and must be configured as releasing circuits. A Device Loop Card [DLC] allows a basic system to connect up to 252 addressable analog devices. The DLC has one programmable (Class B) Style 4.0 or (Class A) Style 6 signaling line circuit. Only the (Class A) Style 6 signaling line circuit is permitted for this releasing application. Any combination of the following compatible devices may be connected to the DLC: Manual Pull Stations HMS/S & D, HMS-M, HMS-2S, and HMS-SA; Photoelectric and Thermal sensor HFP-11 with 3.0%/ft nominal obscuration sensitivity and 135F/57C temperature sensor, Thermal sensor HFPT-11 rated at 135F/57C thermal sensitivity suitable for a listed spacing of 20 x 20 feet (6.1 x 6.1 m) with any of the following bases: RL-HC, DB-HR, ADB-11, or ADBX-11; Addressable Switch Interface Module [HTRI-S, -D, -M, or ­R]; Loop Isolator Module [HLIM]; Two-wire Smoke Interface Module [HZM] which is compatible with Models DI-3/3H, DI-A3/A3H, DI-B3/B3H, DT-3P-135, DT-11, PB-1191, PE-3, and PE-11/11T detectors. The HZM must be converted to (Class A) Style D wiring performance for this releasing application. Each system must be provided with a PSC-12 power supply which provides 120/240 V ac primary and 24 V dc secondary power. The power supply is provided with four Form C relays each rated 4A @120 V ac. Two 12 V dc (15-100 AH) batteries connect to the PSC-12 to provide 90 hours of back up. Optional Power Supply Extender [PSX-12], may be connected to provide additional 24 V dc (12 A) power. For Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. [See further description under LOCAL PROTECTIVE SIGNALING]. FS-250 Fire Seeker Fire Alarm Control Unit. Modular System made up of various combinations of devices and programmable configurations. Enclosures are FS-250-ENCL-R or FS-250-ENCL with FS-SFT or FS-SFT-R trim kits. Minimum system configuration includes an FS-250-MB2 main terminal board which includes a regulated 24 V power supply, FS-250-DB2 display board with firmware version 7.01, an

FM Approvals

1-130

September 2007 -- Approval Guide Automatic Sprinkler Systems

FS-DLC device loop card with a P2 Addressable Device Circuit and capacity for 252 Addresses, four independent Class B (Style Y) notification appliance circuits (NACs) which can be combined in pairs for Class A (Style Z) operation, a Serial Interface Circuit that will drive 16 remote LCD annunciators and up to 8 Serial Relay Units and Serial Annunciator Units, four Form C relay contacts each rated at 1A @ 28 V dc and an RJ-11 Programming Port and FS-REL Releasing Module with FS-RPT Releasing Power Transformer. 90 hours of secondary power provided by two 12 V dc (38Ah) batteries mounted in an external CAB-BATT battery box. For Approved combinations of solenoid control valves, refer to Automatic Water Control Valve listings. [See complete FS-250 system description under LOCAL PROTECTIVE SIGNALING].

Siemens Switzerland Ltd, Building Technologies Group, Gubelstrasse 22, CH-6301 Zug Switzerland

ALGORex Fire Detection System. NOTE: This system may not comply with all requirements of NFPA 72-1999 which would be applicable to FM Approval if the equipment were to be marketed in North America. Programmable fire alarm panel (CSCI1145). 24 V dc panel operable on primary voltage rating of 240 V ac. (See CS1140 system description under LOCAL PROTECTIVE SIGNALING.) Preaction and deluge system control requires optional E3G060 I/O module release provides outputs rated at 24 V dc at 2 A max per output, 4 A total per module, alarm horn and illuminated warning panel outputs rated at 24 V dc at 2 A max per output for preaction-deluge releasing and E3M 071 (DS112V3 NLV 1.2) interactive detection line wired Class A Style 7 for alarm initiation. The E3G080 (CS1140/V7.1) provides two release outputs rated at 24 V dc at 2 A max, alarm horn and illuminated warning panel outputs rated at 24 V dc at 2 A max, five monitored detection lines for manual actuation, stop or blocking button (abort), signal contact ``loss of extinguishing agent'', signal contact ``extinguishing blocked'' and signal contact ``extinguishing actuated''. Additionally, there is a LON interface (Class B signaling line circuit) for connection to the B3Q440 operating unit ``extinguishing'' (Firmware B3Q440/27C256-LON/V1.01). The B3Q440 provides indications and controls for a single extinguishing system. It may be located in the CS1140 enclosure or remotely mounted in a separate enclosure. Indications are provided for alarm, extinguishing command, extinguishing activated, trouble, power on, automatic actuation of extinguishing blocked and manual actuation of extinguishing blocked. Controls provided, in addition to a key switch to inhibit their operation, are: automatic actuation of extinguishing blocked, manual actuation of extinguishing blocked, switch off alarm horn and switch off illuminated warning panel. The B3Q440 also requires a 24 V dc supply from the control unit. (See also LOCAL PROTECTIVE SIGNALING and Automatic Release of Extinguishing Systems)

Simplex Time Recorder Co, 50 Technology Dr, Westminster MA 01441-0001

Series 4004R control. Panel Models 4004-9301 (beige enclosure) and -9302 (red enclosure) are each provided with 4 initiating device circuits (IDC), which must be connected to 4004-9864 Class A Adapter Module to configure for (Class A) Style D wiring. Two release circuits are provided for sprinkler release. Each releasing appliance circuit must connect to a 2081-9046 coil supervision modules which in turn is connected to a compatible 24 and 12 V dc actuators or solenoid. For FM Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. Optional Models 4081-9301, -9302, -9303, and -9304 External Battery Chargers provide the 4004R charging capability for a standby battery bank up to 50 AH in capacity to supply the required 90 hours of standby power. [See Control Panel Description under LOCAL PROTECTIVE SIGNALING.] 4010 Addressable Control System. Analog control panel with Software Revision Level 3.01 using programmed Notification Appliance Circuits N3 or N4 on the 4010 SFI/O card. One releasing circuit will actuate one 24 V dc control head. Optional 4090-9005 and -9006 Suppression Release Peripheral connects to the notification appliance circuit (NAC 3 or 4) from the 4010 fire alarm control panel. This peripheral monitors the output releasing appliance circuit wiring for opens and shorts. Each releasing appliance circuit must connect to a 2081-9046 coil supervision module which in turn is connected to a compatible 24 V dc solenoid. For FM Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. IDNet signaling line circuits must be configured for Class A, Style 6 wiring for this application. 24 V dc batteries rated 25-50 AH are available to provide 90 hours of emergency operation. For battery requirements exceeding 25 AH, the 4081-9301 to -9304 external battery charger must be used. (See description under LOCAL PROTECTIVE SIGNALING.) Model 4020-8001 Fire Alarm Control. Configured with Models 2081-9046 coil supervision module, 565-317 agent discharge power supply regulator and other functional modules as dictated by the needs of the installation (see listing for the 4020-8001 under LOCAL PROTECTIVE SIGNALING for other functional modules). For deluge/preaction sprinkler system applications, the 4020 control must be programmed to provide Style D initiating circuits. Master controller can be programmed for cross-zone operation. Release device circuits are rated at 2 A. The 4020-8001 control must be loaded per field wiring diagram 841-941 for proper valve operation. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries from 6.2 to 50 AH are available to provide 90 hours emergency power. (See also LOCAL PROTECTIVE SIGNALING.) Model 4100 Control. Configured with Models 4100-4001 or -4321 signal modules, Model 4100-0129 limiter module, Model 2081-9046 coil supervision module, Models 4100-5014 Class A eight-zone monitor assemblies and other functional modules as dictated by the needs of the installation (see listing for the 4100 series control under LOCAL PROTECTIVE SIGNALING for other functional modules). Release device circuits are rated at 2 A. The 4100 control must be loaded per field wiring diagram 841-941 for proper valve operation. For FM Approved combinations of solenoid and deluge water valves refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries from 6.2 to 110 AH are available to provide 90 hours of emergency power. 4100U Addressable Control System. Programmable control panel with Software Revision Level 11.02.01. IDNet signaling line circuits must be configured for Class A, Style 6 wiring for this application. Models 4090-9005 and -9006 Suppression Release Peripherals with Software Rev. 1.01 connect to the notification appliance circuit from the 4100U fire alarm control panel. These peripherals monitor the output releasing appliance circuit wiring for opens and shorts. Each releasing appliance circuit must connect to a 2081-9046 coil supervision module which in turn is connected to a compatible 24 V dc solenoid. For FM Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. 24 V dc batteries rated up to 125 AH are available to provide 90 hours of emergency operation. (See description under LOCAL PROTECTIVE SIGNALING.) 4120 Network Control configured with Models 4120-4001, -4321 signal modules, 4120-0129 limiter module, 2081-9032 coil supervision module, Model 4120-5014 Class A eight zone monitor assembly and other functional modules as indicated by the needs of the installation (see listing for the 4120 Network System under LOCAL PROTECTIVE SIGNALING for other functional modules). For deluge/preaction sprinkler system applications, the 4120 network control must be programmed to provide Style D initiating circuits. Master controller can be programmed for cross-zone operation. Release device circuits are rated at 2 A. The 4120 control must be loaded per field wiring diagram 841-731 for proper valve operation. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries from 6.2 to 110 AH are available to provide 90 hours emergency power. (See also LOCAL PROTECTIVE SIGNALING.) The Autocall TFX series fire alarm control with configuration program software CONSYS (Ver. 12.0). The minimum system configuration consists of a minimum of one TFX series releasing control panel (TFX-500 or TFX-800) with either RPS-424 or PSM 800 power supply unit with 90 hours of battery standby (110 AH), OXA-502RM addressable relay module, 505SDA notification appliance module, analog ``Class'' zone which interfaces with appropriate initiating devices, solenoid disconnect switch and Skinner Models 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, 71395SN2ENJ1NOH111C2, LV2LBX25 or ASCO Models 8210A107, R8210A107, T810A107, 8210G207 and Star Model 5550 solenoids.

Spectronics Corp, 4645 Hartley, Lincoln NE 68504

Deluge/Preaction Sprinkler System Release. Model 640 or 641 control panel using 640/641-A2 output card or 641-COM A control card for operation of FM Approved releasing devices rated 3 A continuous/24 V dc. The 640/641-A2 card may be programmed to provide cross-zone actuation of releasing devices. Style D initiating circuits required for deluge/preaction sprinkler system release provided by 640/641-S1A, -S2A, -S2WA input cards. Refer to AUTOMATIC WATER CONTROL VALVES for compatible combinations of solenoid and deluge water control valves. Standby battery pack (20 AH/24 V dc) provides 90 hours of emergency power. (See also LOCAL PROTECTIVE SIGNALING.)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-131

System Sensor, Div of Honeywell, 3825 Ohio Ave, Saint Charles IL 60174

PDRP-1001 with operating system firmware revision level A. Including LED Interface Module (4XLM); Zone Relay Module (4XZM); Remote Annunciator (RZA-4X). Panel provides four input circuits: one detector; one manual release/detector; one waterflow; one supervisory and four output circuits: one alarm/waterflow bell; one waterflow/supervisory bell; one release; one supervisory bell/release. In addition one regulated and one unregulated 24 V auxiliary power output; one alarm and one trouble relay output are provided. Combined load for external devices not to exceed 2.25 A. Field programmable using dip switches for either cross zone or dual zone. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (4XTM) provides a local energy municipal tie for auxiliary protective signaling. In the event of primary power failure battery packs (24 V dc, 12, 15 AH) are suitable for 90 hours of standby operation.

TEPG-US, 91 Technology Dr, Westminster MA 01441

Series T310-9301, -9302, -9311, and -9312 Addressable Control System. Analog control panels with Software Revision Level 3.03 using programmed Notification Appliance Circuits N3 or N4 on the T310 SFI/O card. Each releasing appliance circuit must connect to a Model T301-0050 coil supervision module which in turn is connected to a compatible 24 V dc actuation device. Optional TEPG-US Model 430657 or 431193 Suppression Release Peripheral connects to the SLCNet circuit and to a notification appliance circuit from either the T310 fire alarm control panel, or from the T310-9201 or -9211 Notification Appliance Circuit Extender. This peripheral monitors the output releasing appliance circuit wiring for opens and shorts. Each releasing appliance circuit must connect to a Model T301-0050 coil supervision module which in turn is connected to a compatible 24 V dc solenoid or actuation device. For FM Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. SLCNet signaling line circuits must be configured for Class A, Style 6 wiring for this application. 24 Vdc batteries rated 25-50 AH are available to provide 90 hours of emergency operation. For battery requirements exceeding 25 AH, the TEPG-US Models T390-9101 or T390-9102 External Battery Charger must be used. (See Control Panel Description under LOCAL PROTECTIVE SIGNALING.)

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

PAR-3 Model B-1 (P/N 07907) with operating system Firmware Revision Level E. Includes LED Interface Module (4XLM), Zone Relay Module (4XZM), Remote Annunciator (RZA-4X). Panel provides four input circuits: one detector; one manual release/detector; one waterflow; and one supervisory, and four output circuits: one alarm/waterflow bell; one waterflow/supervisory bell; one release; and one supervisory bell/release. In addition, one regulated and one unregulated 24 V auxiliary power output, and one alarm and one trouble relay output are provided. Combined load for all external devices not to exceed 2.25 A. Field programmable using dip switches for either cross zone or dual zone. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107; Skinner Models LV2LBX25; and Viking Models 11591, 11592, 11601 and 11602 (explosion proof) normally closed (N.C.); solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (4XTM) provides a local energy municipal tie for auxiliary protective signaling. In the event of primary power failure, battery packs (24 V dc, 12, 15 AH) are provided for 90 hours standby operation. Firecycle III, Model E-1 with operating system firmware revision level A. Including LED Interface Module (4XLM; P/N 07910); Zone Relay Module (4XZM; P/N 07912); Remote Annunciator (RZA-4X; P/N 07911). Panel provides four input circuits: one detector; one manual release/detector; one waterflow; one supervisory and four output circuits: one alarm/waterflow bell; one waterflow/supervisory bell; one release; one supervisory bell/release. In addition one regulated and one unregulated 24 V auxiliary power output; one alarm and one trouble relay output are provided. Combined load for all external devices not to exceed 2.25 A. Field programmable using dip switches for either cross zone or dual zone. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107; Viking Models 11591, 11592, 11601 and 11602 (explosionproof) normally closed (N.C.), 11595, 11596 (explosionproof) normally open (N.O.); and Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (4XTM) provides a local energy municipal tie for auxiliary protective signaling. In the event of primary power failure battery packs (24 V dc, 12, 15 AH) are suitable for 90 hours of standby operation.

Viking Electronic Services LLC, 620 Allendale Rd, King of Prussia PA 19406

e-LAN and e-LAN Lite Fire Alarm Control Panels. Basic system consists of a 4 Amp power supply module (P/N VF8115-00), Control Unit Board (P/N VF1500-00) and Panel Annunciator Board (P/N VF1501-00). Release circuit requires a 2.7K end-of-line device for Squibb supervision (Not required for solenoid operation) and SRM solenoid release module (P/N VF6006-00). For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Standby battery (24 V dc, 60 AH) provides 90 hour standby operation. (See control panels descriptions under LOCAL PROTECTIVE SIGNALING).

FM Approvals

1-132

September 2007 -- Approval Guide Automatic Sprinkler Systems

AUTOMATIC WATER CONTROL VALVES (TABLE)

Deluge System Only Deluge or Preaction System Electric Solenoid Release Groups X [E] X [E] Control Panel Groups+ X [1] X [2] X [1] X [2] Detectors

Manufacturer Anber Globe Av de Las Flores 13, Parque Ind El Molino, 28970 Humanes de Madrid, Madrid Spain Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Water Valve Designation & Size *Model A in. NPS Models B, BX. 4, 6 in. NPS; 100, 150 mm NPS 2 1/ 2

Wet Pilot Sprinkler Line X X

Dry Pilot PneuSprinkler matic Hydraulic Line & Rate-of- Rate-ofActuator Rise# Rise# X [E] X [E]

Grinnell or Gem Model A-4. 4, 6 in. NPS

X

X [D-1]

X

X X X X

[A] [B] [D] [E]

X [1] X [2] X [2] X [1] X [2] X [1] X [2]

*Grinnell or Gem Model B. 2 in. NPS Grinnell or Gem Model C. 21/2, 6 in. NPS Grinnell or Gem Model F445. 21/2 in. NPS Angle Body Grinnell or Gem Model F446. 21/2 in. NPS Angle Body. 250 psi (1725 kPa) *Grinnell or Gem Thermal Control Valve Model F430. 1, 11/2 in. NPS. Wormald Model A1. 100, 150 mm (4, 6 in.) Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446 Model DL. 2 in. Model A. 4, 6 in. NPS Model B, 4 in. Model B, 3, 6 in. NPS Model C, 3, 6, in. NPS Model A-1. 3, 4, 6 in. NPS 250 psi (1725 kPa) Model G-1. 3, 4, 6 in. NPS 250 psi (1725 kPa) Cla-Val Company, Box 1325 Newport Beach CA 92659 Dixon Valve & Coupling Co, 2 Executive Way, Ranson WV 25438 Model 834 4, 6, 8, 10 in. NPS 250 psi (1725 kPa) RWP ``Automatic'' Model C. 21/2, 6 in. NPS ``Automatic'' Model 134-260. 2 in. NPS ``Automatic'' Models D, F. 21/2, 4, 6 in. ``Automatic'' Model E. 6 in. Flamex Inc, 4365 Federal Drive Greensboro NC 27410 GW Sprinkler A/S, Kastanievej 15, DK-5620 Glamsbjerg, Denmark Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658 Jomos Brandschutz AG, Sagmattstrasse 5, CH-710 Balsthal, Switzerland Magisco Valves Ltd, 53 Limes Rd, Tettenhall, Wolverhampton WV6 8RD United Kingdom Model FSX Deluge Valves 50, 80, 100, 150 mm Model B. 100, 150 mm NPS

X

X [D-1]

X [A] X [1] X [2] X [B] X [2] X [D] X [E] X [1] X [2] X

X

X [D-1]

X

X [D-1]

X

X [F]

X [4]

X

X X X X X X X X X

X [A]

X [A]

X [1] X [2]

X [DP-1] X [AA-R] X [AA-R] X [DP-1] X [DP-1] X

X [A] X [E} X [A] X [E] X [F] X [F] X[G]

X [1] X [2] X [2] X [1] X [2] X [4] X [4] X[1]X[2]

X X

X[] X [B-1, F-1] X [B-1, F-1]

X X X X X X [A] [B] [A] [B] X [1] X [2] X [2] X [1] X [2] X [2]

X

X

[Minimax 20 9353-E]

X[L]

X[11]

X [A]

Model F. 21/2, 4, 6 in. Model D2, 2 in. NPS Model FSX Deluge Valves. Sizes 50, 80, 100 and 150 mm

X X X

X [B-1, F-1] X

[Minimax 20 9353-E]

X [A] X [1] X [2] X [D] X [E] X [2] X [L] X [11]

MAG Model M799DG-04A, 3, 4, 6, 8 in. NPS. 300 psi (2070 kPa) rated working pressure. MAG Model M799DG-04B, 3, 4, 6, 8 in. NPS. 300 psi (2070 kPa) rated working pressure. MAG Model M799DG-04C, 3, 4, 6, 8 in. NPS. 300 psi (2070 kPa) rated working pressure.

X

X

X

X

X[D] X [E]

X[1] X[2]

X indicates FM Approved or compatible. #See DELUGE, PREACTION or REFRIGERATED AREA SPRINKLER SYSTEM listings.

DRY PILOT ACTUATOR -- Compatible models are shown in brackets in the table. Open brackets [ ] indicate none required.

FM Approvals

Any device listed under ELECTRICAL SIGNALING, unless listed for signaling or special application only.

X X X X

[A] [D] [E] [B]

X [1] X [2] X [1] X [2] X [1] X [2] X [2]

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-133

Deluge System Only

Deluge or Preaction System

Manufacturer Mil Ltd, 17 Moshe Beker St, Box 15200, Rishon Lezion 75051, Israel

*Model A. 21/2 in. NPS Models B, BX. 4, 6 in. NPS; 100, 150 mm NPS Model A. 3, 4, 6 in. NPS Model B. 2 in. NPS Model D. 3, 6 in. NPS Model G. 3, 4, 6 in. NPS Model A-1. 3, 4, 6 in. NPS 250 psi (1725 kPa) Model G-1. 3, 4, 6 in. NPS 250 psi (1725 kPa) Model EKFV. DN 200 mm (8 in.). A spool piece containing a 2 in. (51 mm) drain valve is attached to the inlet flange of each valve. Model DV-1. 4, 6 in. NPS

X X X X X X X

X [A] X [A] X [AA-R] [DP-1] X [DP-1] X [AA-R] [DP-1] X [DP-1] X [DP-1] X

X [E] X [D] X [E] X [D] X [A][E] X [A][D][E] X [B] X [C] X [A][E] X [F] X [F]

X [1] X [2] X [1] X [2] X [1] X [2] X [1] X [2] X [2] X [3] X [1] X [2] X [4] X [4]

Total Walther GmbH, Feuerschutz und Sicherheit, Waltherstrasse 51, 51069 Koln, Germany ¨ Tyco Fire Products, 451 N Cannon Ave, Lansdale PA 19446

X

X [DP-1]

Model DV-3. 21/2 in. NPS. Angle Body. Model DV-3HP. 21/2 in. NPS. Angle Body. 250 psi (1725 kPa) *Tyco Model DV- 2. 2 in. NPS

X

X [DP-1]

X X

X [DP-1] X [DP-1]

X

X [A] X [B] X [D] X [E] X [A] X [D] X [E] X [B] X [F] X X X X [A] [B] [D] [E]

X [1] X [2] X [2] X [1] X [2] X [1] X [2] X [1] X [2] X [1] X [2] X[1] X [2] X [2] X [4] X [1] X [2] X [2] X [1] X [2] X[4]

Victaulic Company, Box 31, Easton PA 18044

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

X X [DP-1] X[F] Model DV-5, 11/2, 2, 3, 4, 6, 8 in. NPS (40, 50, 80, 100, 150, 200 mm DN) 250 psi (1725 kPa). Tyco Fire Products systems are dual rated and are FM Approved only as a complete Deluge or Preaction System. (See appropriate listing.) System ratings are dependent on the solenoid valve used. Only major electrical components listed above may be interchanged. X X [753A] X [B] X [1] X [2] Series 758 FireLock 11/2, 2, 21/2, 3, X X [D] 4, 6 and 8 in. grv × grv; 175 psi [776LPA] (1205); X [I] 4, 6 and 8 in. available in flange inlet × grv outlet; 300 psi (2070 X X [I] X [I] X [2] kPa). [776LPA] Series 769 FireLock 11/2, 2, 21/2, 3, 4, 6 and 8 in. grv x grv; 300 psi (2070 kPa) X X X X X [F] X [4] X [8] *Model E-3, E-4. 11/2 in. NPT. X [J] X [K] X [1] X [2] *Model E-1, E-2. 2 in. NPT. **Model E-1, E-2. 3, 4, 6 in. NPS. Available with FxF and FxG. Model F-1, F-2: 11/2, 2, 21/2, 3, 4, 6, 8 in. NPS. Available with GxG, FxF and FxG and screwed ends (see system description) Above systems: 250 psi (1725 kPa) Viking systems are dual rated and are FM Approved only as a complete Deluge or Preaction System. (See appropriate listing.) Only major electrical components listed above may be interchanged. Solenoid Groups J and K used in Viking Sure-Fire Fail/Safe Systems.

X indicates FM Approved or compatible. #See DELUGE, PREACTION or REFRIGERATED AREA SPRINKLER SYSTEM listings.

DRY PILOT ACTUATOR -- Compatible models are shown in brackets in the table. Open brackets [ ] indicate none required.

FM Approvals

Any device listed under ELECTRICAL SIGNALING, unless listed for signaling or special application only.

Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23849 Bad Oldesloe, Germany Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313 Star Sprinkler Inc, 7071 S 13th, Suite 103, Oak Creek WI 53154

Water Valve Designation & Size INBAL Model 799-DG-01. 3, 4, 6, 8 in. NPS. 6 in. NPS. 300 psi (2070 kPa) rated working pressure. INBAL Model 799-DG-04-A, 3, 4, 6, 8 in. NPS. 300 psi (2070 kPa) rated working pressure. INBAL Model 799-DG-04-B, 3, 4, 6, 8 in. NPS. 300 psi (2070 kPa) rated working pressure. INBAL Model 799-DG-04-C, 3, 4, 6, 8 in. NPS. 300 psi (2070 kPa) rated working pressure. Model FSX Deluge Valves. Sizes 50, 80, 100 and 150 mm 232 (16 bar) RWP

PneuElectric Dry Pilot matic Control Wet Pilot Sprinkler Rate- Hydraulic Solenoid Release Panel DetecSprinkler Line & ofRate-of# # tors Groups Groups+ Line Actuator Rise Rise X X

X

X

X

X

X[D] X [E] X [1] X [2] X X [Minimax

20 9353-E]

X [L]

X [11]

1-134

September 2007 -- Approval Guide Automatic Sprinkler Systems

AUTOMATIC WATER CONTROL VALVES

The automatic-opening valves on the opposite page are FM Approved for controlling the flow of water to sprinklers, spray nozzles or mechanical foam-making equipment when supervised as required. Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure. Valves identified in the listing by a single asterisk (*) have screwed connections only; valves identified by a double asterisk (**) are available with flanged inlet and cut-grooved outlet connections; others have flanged inlet and outlet connections. See DELUGE SPRINKLER SYSTEMS or PREACTION SPRINKLER SYSTEMS listings for detailed information. Footnotes to the Table follow. SOLENOID RELEASE VALVES -- Compatible valve groups are shown in brackets in the table. Empty brackets [ ] indicate none required.

Solenoid Group [A]. Skinner solenoid valve Model LV2LBX25, 24 V dc, 11 WATTS, 458 mA, 1/2 in. NPS, 1/2 in. orifice. Solenoid Group [B]. These valves are interchangeable. ASCO solenoid valve Model T8210A107, 24 V dc, 16.8 WATTS, 700 mA, 1/2 in. NPS, 5/8 in. orifice. ASCO solenoid valve Model R8210A107, 24 V dc, 16.8 WATTS, 700 mA, 1/2 in. NPS, 5/8 in. orifice. ASCO solenoid valve Model 8210A107, 24 V dc, 16.8 WATTS, 700 mA, 1/2 in. NPS, 5/8 in. orifice. Solenoid Group [C]. Star Sprinkler Corp. Solenoid P/N 5550, 24 V dc, part of Model D deluge valve. Solenoid Group [D]. ASCO solenoid valve Model 8210G207, 24 V dc, 10.6 WATTS, 440 mA, 1/2 in. NPS, 1/2 in. orifice. Solenoid Group [E]. Skinner solenoid valve Model 73218BN4UNLVNOC111C2, 24 V dc, 10 WATTS, 420 mA, 1/2 in. NPS, 5/8 in. orifice. Skinner solenoid valve Model 73212BN4TN00N0C111C2, 24 V dc, 10 WATTS, 420 mA, 1/2 in. orifice, 5-300 psi rated working pressure. Solenoid Group [F]. Skinner solenoid valve Model 73212BN4TNLVNOC322C2, 24 V dc, 22 WATTS, 1/2 in. NPS, 0.92 A, 250 psi (1725 kPa), 1/2 in. orifice. Solenoid Group [G]. Skinner solenoid valve Model 71395SN2ENJ1NOH111C2, 24 V dc, 10 WATTS, 420 mA, 1/4 in. NPS, 1/16 in. orifice, 250 psi (1725 kPa) rated working pressure. Solenoid Group [I]. Victaulic Series 753-E solenoid valve, 24 V dc, 8.7 WATTS, 1/2 in. NPS, 364 mA, 300 psi (2069 kPa), 1/2 in. orifice. Solenoid Group [J]. Viking Model (2069 kPa), 4.1 Viking Model (2069 kPa), 4.1 No. 11591 and 11592 (explosion proof) normally closed (NC) solenoid valve, 24 V dc, 10 WATTS, 1/2 in. NPS, 300 psi Cv. No. 11595 and 11596 (explosion proof) normally open (NO) solenoid valve, 24 V dc, 10 WATTS, 1/2 in. NPS, 300 psi Cv.

Solenoid Group [K]. Viking Model No. 11601 and 11602 (explosion proof) normally closed (NC) solenoid valve, 24 V dc, 9 WATTS, 1/2 in. NPS, 250 psi (1725 kPa), 6.2 Cv. Viking Model No. 13215 normally open (NO) solenoid valve, 24 V dc, 9 WATTS, 1/2 in. NPS, 250 psi (1725 kPa), 4.1 Cv. Solenoid Group [L]: Minimax part no. 84 0131 impulse type solenoid valve. The valve shifts position (open or closed) when a voltage pulse is applied to the coil. After shifting position it remains there without electrical power being applied, even if the supply voltage is disconnected. Only when the polarity of the voltage is reversed will the valve shift to the other position. It is the electrical release for the Minimax Model FSX Deluge Valves. In these deulge systems, it is installed in the NC (normally closed) position upon initial set-up. Nominal voltage of 24 Vdc, operating voltage of 18-28 Vdc, 11 WATTS, 460 mA,1/2 in. NPS, 13 mm (1/2 in.) orifice dia.

+CONTROL PANELS. Details for panels are listed under AUTOMATIC RELEASES. Panels must have appropriately sized battery to provide required 90 hours of emergency power.

Control Panel Group [1]. These panels are only compatible with Solenoid Groups [A], [D], [E], [G], [I], [J] and [K]:

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-135

Fire Control Instruments Inc, 16 Southwest Park Westwood MA 02090

Model Model Model Model FC-72. FCI 7100 Series Control. FCI 7200 Series Control. E3 Series Control.

GE Security Inc, 8985 Town Center Pkwy, Bradenton FL 34202 Mirtone, 8985 Town Center Pkwy, Bradenton FL 34202

Model EST2 control panel. Model EST3 control panel. Models MIRQSC, MIRQS1 and MIRQS4 Quick Start Control panels.

Johnson Controls Inc, 507 E Michigan St, Milwaukee WI 53202-5202

IFC1010 Fire Alarm Control Panel IFC2020 Fire Alarm Control Panel.

Notifier, 12 Clintonville Rd, Northford CT 06472-1653

AM-2020 Fire Panel. AFP-1010 Fire Panel.

Protectowire Co, 40 Grissom Road, Plymouth MA 02360

Models ACR-1600, -1600HD Series Control. Control Panel Group [2]. These panels are compatible with Solenoid Groups [A], [B], [D], [E], [G], [I], [J] and [K]:

ADT Security Services Inc, One Town Center Rd, Boca Raton FL 33486

Unimode-640 Fire Alarm Control Panel.

Alison Control Inc, 35 Daniel Rd, Fairfield NJ 07004

Model A888-MXXX Detection System.

Ansul Incorporated, One Stanton St, Marinette WI 54143

Autopulse Autopulse Autopulse Autopulse IQ-301 Analog Fire Panel. IQ-396X Fire Alarm Control Panel. 442D Preaction/Deluge Control System. IQ-636X(E) Fire Alarm Control Panel.

Buckeye Fire Equipment Co, 110 Kings Road, King Mountain NC 28086

Shield-SZ Fire Alarm Control Panel.

CHEMETRON Fire Systems, 4801 Southwick Dr 3rd Floor Matteson IL 60443

Micro 1001 Preaction/Deluge Control System. Micro-200I Analog Fire Panel. MICRO-640I Fire Alarm Control Panel. MICRO-640I Fire Alarm Control Panel.

Detector Electronics Corp, 6901 W 110th St, Minneapolis MN 55438

Eagle Quantum System. (See description under AUTOMATIC RELEASES FOR EXTINGUISHING SYSTEMS and other fire protection equipment.)

Fike Corp, 704 S 10th St, Blue Springs MO 64013

INTELLA-SCAN II Models 10-201-E1, -E2, -E4. Rhino Programmable Control. SHP Pro Programmable Fire Alarm Control P/N 10-063 with V1.00 firmware. Cheetah Addressable Control System. CyberCat 1016 Fire Alarm Control System. P/N 10-2472 Controller with 1.04 firmware. CyberCat 254 Fire Alarm Control System. P/N 10-2525 Controller with 1.04 firmware. Cheetah Xi 50 Fire Alarm Control System. P/N 10-2622 Controller with 3.00 firmware. CyberCat 50 Fire Alarm Control System. P/N 10-2620 Controller with 3.00 firmware.

Fire Control Instruments Inc, 16 Southwest Park Westwood MA 02090

Model Model Model Model Model FC-72 DL Deluge System Control Panel. FC-ID Fire Alarm Control with RZST-2 transponder and RSM release module. FCI 7200 Series Control. FCI 7100 Series Control. E3 Series Control.

Fire-Lite Alarms Inc, One Fire-Lite Place Northford CT 06472

Sensiscan 2000.

GE Security Inc, 8985 Town Center Pkwy, Bradenton FL 34202 Mirtone, 8985 Town Center Pkwy, Bradenton FL 34202

Model EST2 control panel. Model EST3 control panel. Models QSC, QS1 and QS4 Quick Start Control panels. Model EST2 control panel. Model EST3 control panel. Models MIRQSC, MIRQS1 and MIRQS4 Quick Start Control panels.

FM Approvals

1-136

September 2007 -- Approval Guide Automatic Sprinkler Systems

Gamewell Co, The, 12 Clintonville Rd, Northford CT 06472

IdentiFlex 630 and 650 control panels. IdentiFlex 610 fire alarm control.

Johnson Controls Inc, 507 E Michigan St, Milwaukee WI 53202-5202

FC-2000 System. IFC-200 Analog Fire Panel. IFC-400 Fire Alarm Control Panel.

Kidde-Fenwal Inc, 400 Main Street, Ashland MA 01721

GEMINI P/N 295031. Gemini II Multi-Hazard Control System. FenwalNET 2000. FenwalNET 2000 LT Fire Alarm Control. FenwalNET 2000 ML control panel. Fenwal 3220 Multi-Hazard Control System. PEGAsys control panel. PEGAsys LV Fire Alarm Control. PEGAsys ML control panel. FENWALNET 6000 programmable analog addressable fire alarm control system with operating sofware Rev. 1.2.1. ARIES programmable analog addressable fire alarm control system with operating software Rev. 1.2.1. Model AEGIS conventional fire alarm-suppression control panel Model 732 conventional fire alarm-suppression control panel

King-Fisher Co, 2350 Foster Ave Wheeling IL 60090

DACS I and DACS II (Detection, Actuation and Control System), KFRTI-20, -52.

Notifier, 12 Clintonville Rd, Northford CT 06472-1653

AFC-600 Fire Alarm Control Panel. NFS-3030 Fire Alarm Control Panel. NFS-640(E) Fire Alarm Control Panel. AFP-200 Analog Fire Panel. AFP-200 release with CMX-2 module. AFP-300 or AFP-400 Fire Alarm Control Panel. AFP-300 or AFP-400 Fire Alarm Control Panels with CMX-2 module. AFP-1010 Fire Panel with CMX-2 module. AM-2020 Fire Panel with CMX-2 module. NFS2-3030 Fire Alarm Control Panel. RP-1001 Preaction/Deluge Control System. RP-1002 Preaction/Deluge Control System. System 500. System 5000.

Pem-All Fire Extinguisher Corp, Div Pem Systems Inc, 39A Myrtle St, Cranford NJ 07016

PEM-2001 Preaction/Deluge Control System.

Potter Electric Signal Company, 2081 Craig Road, Saint Louis MO 63146

PFC Series 100R, PFC 2000RC. Models PFC-100RC, PFC-4410, PFC-4410A.

Protectowire Co, 40 Grissom Road, PLymouth MA 02360

Models ACR-1600, -1600HD Series Control, FS 2000 Series Control. Model SRP 4×4.

Pyrene Corp, 130 Esna Park Dr Markham Ontario L3R 1E3 Canada

Fire Alarm Control Panel Series 4000.

Siemens Building Technologies Inc, Fire Safety, 8 Fernwood Rd, Florham Park NJ 07932

FireFinder XLS Fire Alarm Control System housing a PMI main processor with a firmware level at 3.04. MPC-6000 Fire Alarm Control Unit. MXL Programmable Modular Fire Alarm System. System 3 Universal Alarm Control. FS-250 Fire Seeker Fire Alarm Control Unit

Simplex Time Recorder Co, 50 Technology Drive, Westminster MA 01441-0001

Series 4004R Control. 4010 Fire Alarm Control (Firmware 3.01) with 4090-9005 Suppression Release Peripheral. 4020-8001 Fire Alarm Control. 4100 Microprocessor Based Monitoring and Control System. 4100U Fire Alarm Control (Firmware 11.02.01) with 4090-9005 or -9006 (Software 1.01) Suppression Release Peripheral. 4120 Network System.

Spectronics Corp, 4645 Hartley Lincoln NE 68504

Models 640 and 641.

System Sensor, Div of Honeywell, 3825 Ohio Ave Saint Charles IL 60174

PDRP-1001 Preaction/Deluge Control System.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

PAR-3 Model B-1 Preaction/Deluge Control System. Firecycle III, Model E-1.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-137

Control Panel Group [3]. These panels are compatible with Solenoid Group [C].

ADT Security Services Inc, One Town Center Rd, Boca Raton FL 33486

Unimode-640 Fire Alarm Control Panel.

Alison Control Inc, 35 Daniel Rd, Fairfield NJ 07004

A888-MXXX Plug-In Detection System.

Ansul Incorporated, One Stanton St, Marinette WI 54143

Autopulse Autopulse Autopulse Autopulse Autopulse IQ-301 Analog Fire Panel. IQ-396X Fire Alarm Control Panel. 442D Preaction/Deluge Control System. Z-10 Fire Alarm Control Panel [firmware 1.01] IQ-636X(E) Fire Alarm Control Panel.

CHEMETRON Fire Systems, 4801 Southwick Dr 3rd Floor Matteson IL 60443

Micro-200I Analog Fire Panel. MICRO-640I Fire Alarm Control Panel. MICRO-640I Fire Alarm Control Panel.

Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620

``Automatic'' Micro 1001 Preaction/Deluge Control System.

Fire Control Instruments Inc, 16 Southwest Park Westwood MA 02090

FC-72 DL Deluge System Control Panel.

Fire-Lite Alarms Inc, One Fire-Lite Place Northford CT 06472

Sensiscan 2000.

Johnson Controls Inc, 507 E Michigan St, Milwaukee WI 53202-5202

FC-2000 System. IFC-200 Analog Fire Panel. IFC-400 Fire Alarm Control Panel.

Kidde-Fenwal Inc, 400 Main Street, Ashland MA 01721

GEMINI P/N 295031.

Notifier, 12 Clintonville Rd, Northford CT 06472-1653

AFC-600 Fire Alarm Control Panel. NFS-3030 Fire Alarm Control Panel. NFS-640(E) Fire Alarm Control Panel. AFP-200 Analog Fire Panel. AFP-200 release with CMX-2 module. AFP-300 or AFP-400 Fire Alarm Control Panel. AFP-300 or AFP-400 Fire Alarm Control Panels with CMX-2 module. AFP-1010 Fire Panel with CMX-2 module. AM-2020 Fire Panel with CMX-2 module. NFS2-3030 Fire Alarm Control Panel. RP-1001 Preaction/Deluge Control System. RP-1002 Preaction/Deluge Control System. System 500. System 5000.

Pem-All Fire Extinguisher Corp, Div Pem Systems Inc, 39A Myrtle St, Cranford NJ 07016

PEM-2001 Preaction/Deluge Control System.

Potter Electric Signal Company, 2081 Craig Road, Saint Louis MO 63146

PFC 2000RC.

Protectowire Co, 40 Grissom Road, Plymouth MA 02360

Models ACR-1600, -1600 HD Series Control, FS 2000 Series Control.

Pyro-Chem Inc, One Stanton St, Marinette WI 54143

Triton RP Fire Alarm Control Panel [firmware 1.01]

Simplex Time Recorder Co, 50 Technology Drive, Westminster MA 01441-0001

Series 4004R Control.

System Sensor, Div of Honeywell, 3825 Ohio Ave Saint Charles IL 60174

PDRP-1001 Preaction/Deluge Control System.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

PAR-3 Model B-1 Preaction/Deluge Control System. Control Panel Group [4]. This panel is compatible with Solenoid Group [F].

ADT Security Services Inc, One Town Center Rd, Boca Raton FL 33486

Unimode-640 Fire Alarm Control Panel.

FM Approvals

1-138

September 2007 -- Approval Guide Automatic Sprinkler Systems

Ansul Incorporated, One Stanton St, Marinette WI 54143

Autopulse IQ-396X Fire Alarm Control Panel. Autopulse IQ-636X(E) Fire Alarm Control Panel.

Chemetron Fire Systems, 3rd Floor 4801 Southwick, Matteson IL 60443

MICRO-640I Fire Alarm Control Panel. MICRO-640I Fire Alarm Control Panel.

Detector Electronics Corp, 6901 West 110th St, Minneapolis MN 55438

Model FDRS Programmable System. Eagle Quantum System. (See description under AUTOMATIC RELEASES FOR EXTINGUISHING SYSTEMS and other fire protection equipment.)

Fike Corp, 704 S 10th Street, Blue Springs MO 64015

CyberCat 1016 Fire Alarm Control System. P/N 10-2472 Controller with 1.04 firmware. CyberCat 254 Fire Alarm Control System. P/N 10-2525 Controller with 1.04 firmware. Cheetah Xi 50 Fire Alarm Control System. P/N 10-2622 Controller with 3.00 firmware. CyberCat 50 Fire Alarm Control System. P/N 10-2620 Controller with 3.00 firmware.

Fire Control Instruments Inc, 16 Southwest Park Westwood MA 02090

Model FCI 7100 Series Control. Model FCI 7200 Series Control. Model E3 Series Control.

GE Security Inc, 8985 Town Center Pkwy, Bradenton FL 34202

Model EST2 control panel. Model EST3 control panel. Models QSC, QS1 and QS4 Quick Start Control panels. Model EST2 control panel. Model EST3 control panel. Models QSC, QS1 and QS4 Quick Start Control panels.

Johnson Controls Inc, 507 E Michigan St, Milwaukee WI 53202-5202

IFC-400 Fire Alarm Control Panel.

Potter Electric Signal Company, 2081 Craig Road, Saint Louis MO 63146

PFC 2000RC.

Notifier, 12 Clintonville Rd, Northford CT 06472-1653

AFC-600 Fire Alarm Control Panel. NFS-3030 Fire Alarm Control Panel. NFS-640(E) Fire Alarm Control Panel. AFP-200 release with CMX-2 module. AFP-300 or AFP-400 Fire Alarm Control Panel. AFP-300 or AFP-400 Fire Alarm Control Panels with CMX-2 module. AFP-1010 Fire Panel with CMX-2 module. AM-2020 Fire Panel with CMX-2 module. NFS2-3030 Fire Alarm Control Panel. RP-1001 Preaction/Deluge Control System. RP-1002 Preaction/Deluge Control System. System 500. System 5000.

Simplex Time Recorder Co, 50 Technology Drive, Westminster MA 01441-0001

Series 4004R Control. 4010 Fire Alarm Control (Firmware 3.01) with 4090-9005 Suppression Release Peripheral. 4100U Fire Alarm Control (Firmware 11.02.01) with 4090-9005 or -9006 (Software 1.01) Suppression Release Peripheral. Control Panel Group [5]. This system is only compatible with Solenoid Group [E].

Detector Electronics Corp, 6901 West 110th St, Minneapolis MN 55438

Model FDRS Programmable System.

Siemens Switzerland Ltd, Building Technologies Group, Gubelstrasse 22, CH-6301 Zug Switzerland

CS1140/1145 AlgoRex Fire Detection System. Control Panel Group [6]. These panels are only compatible with Solenoid Groups [A] and [B].

Simplex Time Recorder Co, 50 Technology Drive, Westminster MA 01441-0001

4010 Fire Alarm Control. Control Panel Group [7]. These panels are compatible with solenoid Groups [A], [B], [C], [D], [E], [F] and [G].

Protectowire Co, 40 Grissom Road, Plymouth MA 02360

Models ACR-1600, -1600 HD Series Control, FS 2000 Series Control. FireSystem, 2600 HD Series Modular Fire Control Panel. Release Module (RM-2).

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-139

Control Panel Group [8]. These panels are compatible with Solenoid Group [F] and [H].

Fike Corp, 704 S 10th St, Blue Springs MO 64013

SHP Pro Programmable Fire Alarm Control P/N 10-063 with V1.00 firmware. Shark Fire Alarm Control (P/N 10-056-1) with Rev. 2.00 Firmware.

Protectowire Co, 40 Grissom Road, Plymouth MA 02360

FireSystem, 2600 HD Series Modular Fire Control Panel. Release Module (RM-2). FS 2000 Series Control. Model SRP 4×4.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

PAR-3 Model B-1 Preaction/Deluge Control System.

Siemens Building Technologies Inc, Fire Safety, 8 Fernwood Rd, Florham Park NJ 07932

FireFinder XLS Fire Alarm Control System housing a PMI main processor with a firmware level at 3.04. MPC-6000 Fire Alarm Control Unit. FS-250 Fire Seeker Fire Alarm Control Unit Control Panel Group [9]. These panels are compatible with Solenoid Groups [A], [B], [D], [E], [F] and [G]:

Fike Corp, 704 S 10th St, Blue Springs MO 64013

Shark Fire Alarm Control (P/N 10-056-1) with Rev. 2.00 Firmware.

Gamewell Co, The, 12 Clintonville Road, Northford CT 06472

IdentiFlex 602 Series, models IF 602-126R, IF 602-126RXL, IF602-252R and IF602-252RXL programmable controls, with Version 8.0 firmware. IdentiFlex 610 analog / addressable fire alarm control with Version 7.2.1 firmware IdentiFlex 632 and IdentiFlex 654 / 658 Conventional and Analog / Addressable Fire Alarm Control Systems with Version 7.2.1 firmware.

Pyro-Chem Inc, One Stanton St, Marinette WI 54143

Triton RP Fire Alarm Control Panel [firmware 1.01] Triton RPA Fire Alarm Control (firmware 3.03) with TEPG-US Model 430657 Suppression Release Peripheral. Autopulse Z-10 Fire Alarm Control Panel [firmware 1.01] Autopulse Z-28 Fire Alarm Control (firmware 3.03) with TEPG-US Model 430657 Suppression Release Peripheral.

Simplex Time Recorder Co, 50 Technology Drive, Westminster MA 01441-0001

Autocall TFX-400 fire alarm control. Autocall TFX-500 fire alarm control. Autocall TFX-800 fire alarm control. Control Panel Group [10]. These panels are compatible with Solenoid Groups [B], [D], [E], [F] and [G]:

Detector Electronics Corp, 6901 W 110th St, Minneapolis MN 55438

Eagle Quantum Premier System. (See description under AUTOMATIC RELEASES FOR EXTINGUISHING SYSTEMS and other fire protection equipment.) Control Panel Group [11]. This electrical control panel is compatible with Solenoid Group [L]:

Minimax GmbH & Co KG, Box 1260 Industriestrasse 10-12, D-23840 Bad Oldsloe, Germany

Minimax FMZ 4100 GAB 32 Preaction Deluge Control System.

PRESSURE GAUGES

Gauges for sprinkler systems and fire pumps are designed for use with air or water. These gauges are usually of the Bourdon tube type. The moving parts are fabricated of appropriate corrosion-resistant materials. When installed on the air side of a dry pipe system, a retard type gauge may be used. This gauge is assembled with a tube appropriate to the unretarded pressure range of the gauge and is provided with a spring to resist the full scale load. The two common sizes are 41/2 and 31/2 in. diameter. These gauges can be calibrated with a hydraulic testing unit by adjusting the dial pointer to read correctly at known pressures. Accuracy requirements are that the gauge be correct within 2% over the center third of its scale and within 3% over the remaining two-thirds. Dial marking subdivisions correspond to the maximum accuracy of the gauge. For service on fire pumps where the suction may be taken under a lift, compound pressure vacuum gauges are available graduated in pressure units over both the pressure and vacuum scales, and are designed not to be injured by vacuum. To minimize possible damage and provide maximum accuracy, gauges should be selected with scales of about twice the maximum system pressure.

Ashcroft Inc, 250 E Main St, Stratford CT 06614

``Ashcroft'' Brand Type 35-W1005P-02L-XUL Pressure Gauge. 0-100 psi (0-690 kPa), 0-150 psi (0-1035 kPa), 0-250 psi (0-1725 kPa), 0-300 psi (0-2070 kPa), 0-600 psi (0-4135 kPa). 31/2 in. Retard Pressure Gauge. 0-80-250 psi (0-550-1725 kPa).

FM Approvals

1-140

September 2007 -- Approval Guide Automatic Sprinkler Systems

Brecco Corp, 4433 W Van Buren St, Suite #5, Phoenix AZ 85043-3925

Pressure Gauge. Model W-101, Air/Water; 0-300 psi (0-2070 kPa). 31/2 in. Retard Pressure Gauge. Model W-102, air; 0-80-250 psi (0-550-1725 kPa). 31/2 in.

Kujawska Fabryka Manometrow ``KFM'' S.A., uL. Legska 29/35, 87-800 Wloclawek, Poland

Model 111.10.100. Plastic or steel case with a 1/4 in. male NPT bottom connection, 4 in. (100 mm) size. Model 111.12.100. Steel case and a 1/4 in. male NPT rear connection, 4 in. (100 mm) size. Measuring Ranges:

Psi kPa

-15 to 0 -15 to 150 0 to 150 0 to 250 0 to 400 0 to 600

-1 to 0 -1 to 9 0 to 10 0 to 16 0 to 25 0 to 40

US Gauge, Div Ametek Inc, 900 Clymer Ave, Sellersville PA 18960

Air or Water Pressure Gauge. P-1590. 0-100, 0-300, 0-600 psi (0-690, 0-2070, 0-4135 kPa). R-1590. 0-80-250 psi (0-550-1725 kPa). 31/2, 41/2 in.

WIKA ALEXANDER WIEGAND GmbH & Co, Alexander-Wiegand-Straße, 63911 Klingenberg, Germany

Pressure Gauge. Model 111.10.100. Plastic or steel case, 31/2 in size (100 mm). Pressure Gauge. Model 111.12.100. Steel case only, 31/2 in size (100 mm). Measuring Ranges:

Psi kPa Bar

-15 to 0 -15 to 150 0 to 150 0 to 250 0 to 400 0 to 600

-100 to 0 -100 to 900 0 to 1000 0 to 1600 0 to 2500 0 to 4000

-1 to 0 -1 to 9 0 to 10 0 to 16 0 to 25 0 to 40

WIKA Instrument Corp, 1000 Wiegand Blvd, Lawrenceville GA 30243

Air or Water Pressure Gauge. Model 111.10SP.100. Plastic or steel with brass plated finish case. 0-600 psi (0-4140 kPa). 4 in. Retard Pressure Gauge. Model 111.10SP.100. 0-80-250 psi (0-550-1725 kPa). 4 in.

OUTSIDE SCREW AND YOKE GATE VALVES

Outside screw and yoke gate valves are recommended for service indoors and in pits outdoors. They are not recommended for throttling service. The stem indicates at a glance whether or not the valve is open. Smaller sizes, 3/4 through 2 in. NPS inclusive, are of bronze. Large sizes, 21/2 through 14 in. NPS inclusive, are of iron, bronze mounted. One manufacturer makes valves of bronze up through the 3 in. size. Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.

AVK International A/S, Tech Bizonvej 3, Skovby 8464 Galten, Denmark

Series 25 Resilient Seated Gate Valves. 21/2 through 8 in. NPS valves have a rated working Pressure of 250 psi (1725 kPa). 10 and 12 in. NPS valves have a rated working Pressure of 200 psi (1380 kPa). All available with or without Indicator Post Flange.

21/2, 2 1/ 2, 2 1/ 2, 2 1/ 2, 2 1/ 2, 2 1/ 2, 3, 3, 3, 3, 3, 3 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 8, 10, 12 8, 10, 12 8, 10, 12 8 8 Flanged Flanged by Mechanical Joint Standardized Mechanical Joint Flanged by Push-on Joint Push-on Joint Cut Grooved

Resilient seat. 4-8 in. sizes only available with AISI 304 stainless steel stem as an alternate material to bronze.

AVK Saudi Valves Manufacturing Co Ltd, Phase 4, Street No. LO 404, Jeddah, KSA 21443

Series 45 Resilient Seated Gate Valves. 21/2 through 12 in. NPS. Valves have a rated working Pressure of 250 psi (1725 kPa).

21/2, 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 4, 6, 8, 10, 12 4, 6, 8, 10, 12 DN65, DN80, DN100, DN150, DN200, DN250, and DN300 3, 4, 6, 8 3, 4, 6, 8 4, 6, 8, 10, 12 Flanged (ANSI Class 125) Standardized Mechanical Joint Flanged (ANSI Class 125) × Standardized Mechanical Joint Flanged (ANSI Class 125) × Tyton Tyton Flanged (ANSI Class 250) Metric, PN 10/16 Grooved End (AWWA C606) Grooved End (AWWA C606) by Flanged Tapping Flange (ANSI Class 125) × Standardized Mech. Joint

4-8 in. sizes only available with AISI 304 stainless steel stem as an alternate material to bronze.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-141

American AVK Co, 5286 East Home Ave, Fresno CA 93727

Series 25 Resilient Seated Gate Valves. 21/2 through 8 in. NPS valves have a rated working Pressure of 250 psi (1725 kPa). 10 and 12 in. NPS valves have a rated working Pressure of 200 psi (1380 kPa). All available with or without Indicator Post Flange.

21/2, 2 1/ 2, 2 1/ 2, 2 1/ 2, 2 1/ 2, 2 1/ 2, 3, 3, 3, 3, 3, 3 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 8, 10, 12 8, 10, 12 8, 10, 12 8 8 Flanged Flanged by Mechanical Joint Standardized Mechanical Joint Flanged by Push-on Joint Push-on Joint Cut Grooved

Series 45 Resilient Seated Gate Valves. 3 through 8 in. NPS valves have a rated working pressure of 250 psi (1725 kPa). 4, 6, and 8 in. NPS sizes only, available with AISI 304 Stainless Steel stems as an alternate material to bronze stems.

3, 4, 6, 8 3, 4, 6, 8 Grooved Ends Flanged by Grooved Ends

American Darling Valve, Div American Cast Iron Pipe Co (ACIPCO), Box 2727, Birmingham AL 35202

All Series 2500-1 . All Series 2500-1 valves have a 250 psi (1725 kPa) working pressure.

4, 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 8, 10, 10, 10, 10, 10, 10, 12 12 12 12 12 12 Flanged (ANSI Class 125, 150, 250) Standardized Mechanical Joint Flanged (ANSI Class 125) × Standardized Mechanical Joint Flanged (ANSI Class 125) × Tyton Tyton Tapping Flange (ANSI Class 125) × Standard Mechanical Joint

American Flow Control, Div American Cast Iron Pipe Co (ACIPCO), Box 2727, Birmingham AL 35202

Series 2500. Resilient Seated Gate Valves. 2 through 12 in. NPS valves have a rated working pressure of 250 psi (1725 kPa). 14 and 16 in. NPS valves have a rated working pressure of 200 psi (1380 kPa). Available with the following end connections:

2, 3, 2, 4, 4, 4, 4, 2, 2, 21/2, 14, 16 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12, 14, 16 6, 8, 10, 12, 14, 16 6, 8, 10, 12 6, 8, 10, 12 6, 8, 10, 12, 14, 16 21/2, 3, 14, 16 2 1/ 2, 3 Flanged (ANSI Class 125) Flanged (ANSI Class 125, 150, 250) Standardized Mechanical Joint Flanged (ANSI Class 125) × Standardized Mechanical Joint Flanged (ANSI Class 125) × Tyton Tyton Tapping Flange (ANSI Class 125) × Standard Mechanical Joint Push-on Threaded

Series 2500. Resilient Seated Gate Valves. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

4, 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 8, 10, 10, 10, 10, 10, 10, 12 12 12 12 12 12 Flanged (ANSI Class 125, 150, 250) Standardized Mechanical Joint Flanged (ANSI Class 125) x Standardized Mechanical Joint Flanged (ANSI Class 125) x Tyton Tyton Tapping Flange (ANSI Class 125) x Standard Mechanical Joint

Clow Canada, a Div of Canada Pipe, 254 Henry St, Brantford, Ontario N3T 5T7, Canada

Fig. 459. 1/2 through 2 in. NPS.

Clow Valve Co, Div McWane Inc, 902 S 2nd St, Oskaloosa IA 52577

Series F-6100. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

Model No. Size End Connections

F-6170 F-6172 F-6176 F-6180

21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8

Flanged Mechanical Joint Flanged x Mechanical Joint Push-on for PVC

Model 2638. Resilient Seated Gate Valves. Sizes 4 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

4, 4, 4, 4, 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 8, 8, 8 8, 10, 10, 10, 10, 10, 10, 10, 12 12 12 12 12 12 12 Flanged Flanged × Groove Flanged × Mechanical Joint Flanged × Tyton Grooved Mechanical Joint × Mechanical Joint Mechanical Joint × Tapping PVC Tyton

10, 12

Model 2639 Resilient Seated Gate Valves. Sizes 21/2 through 3 in. NPS. 250 psi (1725 kPa) rated working pressure. Sizes 4 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 2 1/ 2, 3 Flanged Flanged × Groove

FM Approvals

1-142

September 2007 -- Approval Guide Automatic Sprinkler Systems

3, 4, 6, 8, 10, 12 21/2, 3, 4 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 2 1/ 2, 3 4, 6, 8, 10, 12

Flanged × Mechanical Joint Grooved Mechanical Joint Mechanical Joint × Tapping PVC Threaded Tyton

Model 2640. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

2, 21/2, 3, 4, 6, 8, 10, 12 2 1/ 2, 3 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 21/2, 3, 4 2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 2, 21/2, 3, 4, 6, 8, 10, 12 2, 21/2, 3 4, 6, 8, 10, 12 Flanged Flanged × Groove Flanged × Mechanical Joint Flanged × Tyton Grooved Mechanical Joint × Mechanical Joint Mechanical Joint × Tapping PVC Threaded Tyton

Crane Valves, 1000 No. 12th Ave, Washington IA 52353

No. 459. 1/2 through 2 in. NPS. No. 467. 21/2 through 12 in. NPS. Flanged.

Ever Metal Industry Co Ltd, 853 Kwang Fu Rd, Pa Teh City, Tao Yuen Hsien, Taiwan ROC

Model 762U. Metal to Metal Seated Gate Valve. 2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

2, 3, 4, 6, 8, 10, 12 Flanged

Model 722U. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged

Model 722H. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged

Model 722G. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Grooved

Model 722GF. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Grooved × Flanged

Fivalco (Qingdao) Co Ltd, 11 Shuangyuan Road, Chengyang Qingdao, Shandong PRC 266111

Model GVOSY-1161-200PSI. Resilient Seated Gate Valves. Sizes 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI, BS10, BS4505, JIS B2212, JIS B2213)

Model GVOSY-1161-250PSI. Resilient Seated Gate Valves. Sizes 4, 6 and 8 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

4, 6, 8 Flanged × Flanged (ANSI)

Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Fig. 66. 1/2 through 2 in. NPS. Fig. 101F. 21/2 through 10 in. NPS. Flanged. Fig. 151RB. 21/2 through 8 in. NPS. Flanged.

Resilient seat.

Hammond Valve, 16550 West Stratton Drive, New Berlin WI 53151

Model IR114OUL. 21/2 through 8 in. NPS. Flanged.

Jenkins Valve, 1000 N. 12th Ave, Washington IA 52353

Model 825CJ. Metal to metal seated gate valve. 21/2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged

Kennedy Valve, Div McWane Inc, 1021 E Water St, Elmira NY 14901

Figure 66. Sizes 1/2 through 2 in. NPS. Available with the following end connections:

1/2, 3/4,

1, 11/4, 11/2, 2

Threaded

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-143

Figure 67. Sizes 21/2 through 6 in. NPS. Available with the following end connections:

21/2, 3, 4, 6 Threaded

Model Ken-Seal II. Resilient Seated Gate Valves. Sizes 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 2 1/ 2, 3 Flanged Threaded

Model KS-FW. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

2, 21/2, 3, 4, 6, 8, 10, 12 2, 21/2, 3 Flanged Threaded

Model KS-RW. Resilient Seated Gate Valves. Sizes 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

4, 6, 8, 10, 12 21/2, 3, 4, 6, 8 21/2, 3, 4, 6, 8 Flanged Flanged x Grooved Grooved

Lichfield Fire & Safety Equipment Co Ltd, 2nd Floor, Suite 4, Saturn Centre, Spring Rd, Ettingshall Rd, Wolverhampton WV4 WTX, United Kingdom

Model 762U. Metal to Metal Seated Gate Valve. 2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

2, 3, 4, 6, 8, 10, 12 Flanged

Model 722U. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged

Model 722H. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged

Model 722G. Resilient Seated Gate Valve. 3, 4 and 6 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

3, 4, 6 Grooved

Lien Hwa Iron Works Co Ltd, 112 Sec 2 Kuang Fu Rd, Sanchung Taipei Hsien 24113, Taiwan ROC

Fig. 101F. 21/2 through 10 in. NPS. Flanged. Fig. 151RB. 21/2 through 8 in. NPS. Flanged.

Resilient seat.

Linx Limited, 184 John Clarke Road, Middletown RI 02802

``United'' Model 5000. Resilient Seated Gate Valves. Sizes 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI, BS10, BS4505, JIS B2212, JIS B2213)

``United'' Model 5100. Resilient Seated Gate Valves. Sizes 4, 6 and 8 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

4, 6, 8 Flanged × Flanged (ANSI)

M&H Valve Co, Box 2088, Anniston AL 36202

Model 4068. Resilient Seated Gate Valves. Sizes 4 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

4, 6, 8, 10, 12 4, 6, 8, 10, 12 Flanged Mechanical Joint

Matco Products Inc, Rte 22 Box 27, Brewster NY 10509

Model 105U, 21/2, 3, 4, 6, 8, 10, 12 in. Flanged.

Resilient seat.

Milwaukee Valve Company Inc, 16550 West Stratton Drive, New Berlin WI 53151

Model 2885FP. Metal to Metal Seated Gate Valve. 21/2 through 8 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8 Flanged

FM Approvals

1-144

September 2007 -- Approval Guide Automatic Sprinkler Systems

Figure 118. Metal to Metal Seated Gate Valve. 1 through 2 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

1, 11/4, 11/2, 2 Threaded

Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel

Quikcoup Style 400. Resilient Seated Gate Valves. Sizes 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI, BS10, BS4505, JIS B2212, JIS B2213)

Quikcoup Style 425. Resilient Seated Gate Valves. Sizes 4, 6 and 8 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

4, 6, 8 Flanged × Flanged (ANSI)

Mueller Co, 500 W Eldorado St, Decatur IL 62525

Series 2073. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Available with the following end connections.

Figure No. Size End Connections

A-2073-5 A-2073-6 A-2073-8 A-2073-16 A-2073-20 A-2073-24 A-2073-26

3, 4, 6, 8, 10, 12, 14 2, 21/2, 3, 4, 6, 8, 10, 12, 14 2, 21/2, 3, 4, 6, 8 3, 4, 6, 8, 10, 12, 14 3, 4, 6, 8, 10, 12, 14 4, 6, 8, 10, 12, 14 3, 4, 6, 8, 10, 12, 14

Hub Flanged Threaded Flanged by Mechanical Joint Standardized Mechanical Joint Asbestos Cement Hub Flanged by Asbestos Cement Hub

Series 2079. Resilient Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Available with the following end connections.

Figure No. Size End Connections

A-2079-6 A-2079-16 A-2079-23 A-2079-24 A-2079-26 A-2079-53

4, 4, 4, 4, 4,

6, 8, 6, 8, 6, 8, 6, 8, 6, 8, 4, 6

10 10 10 10 10

Flanged Flanged by Mechanical Joint Mechanical Joint A/C Pipe Ends Flanged by A/C Pipe End Flanged by Grooved

Figure 2360*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

21/2, 3, 4, 6, 8 21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8 4, 6, 8 4, 6, 8, 10, 12 4, 6, 8, 10, 12 2 1/ 2, 3 Compression Ends Flanged Standardized Mechanical Joint Standardized Mechanical Joint by Flanged Standardized Mechanical Joint by Tapping Flange Mechanical Joint (Cut In/D150) Mechanical Joint by Standardized Mechanical Joint (Cut In/D150) Slip ­ On Slip ­ On by Flange Threaded

Figure 2361*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

4, 4, 4, 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 8, 8, 8 10, 10, 10, 10, 10, 10, 10, 12, 12, 12, 12 12, 12, 12 14**, 16** 14**, 16** 14**, 16** 14**, 16** 14**, 16** Flanged Standardized Mechanical Joint Standardized Mechanical Joint by Flanged Standardized Mechanical Joint by Tapping Flange Slip ­ On Slip ­ On by Flange AquaGrip restrained mechanical joint, NPS AquaGrip restrained mechanical joint, IPS

Figure 2362*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

3, 4, 6, 8, 10, 12 2 1/ 2, 3 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 21/2, Flanged Threaded Standardized Mechanical Joint Standardized Mechanical Joint by Flanged Standardized Mechanical Joint by Tapping Flange Slip ­ On Slip ­ On by Flange

Figure 2460. Resilient Seated Gate Valves. 250 psi (1724 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8 21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8 4, 6, 8, 10, 12 2 1/ 2, 3 Compression Ends Flanged Standardized Mechanical Joint Standardized Mechanical Joint by Tapping Flange Mechanical Joint (Cut In/D-150) Slip ­ On Threaded

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-145

Figure 2462. Resilient Seated Gate Valves. 250 psi (1724 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8 21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8 4, 6, 8, 10, 12 2 1/ 2, 3 Compression Ends Flanged Standardized Mechanical Joint Standardized Mechanical Joint by Tapping Flange Mechanical Joint (Cut In/D-150) Slip ­ On Threaded

*Bonnet with indicator post flange. **Rated Working Pressure 250 psi (1724 kPa).

AquaGrip end connections FM Approved for use with FM Approved PVC, HDPE and ductile iron pipe. 10 and 12 in. NPS AquaGrip end connections limited to 160 psi (1105 kPa) rated working pressure when used with HDPE pipe.

NIBCO Inc, 1516 Middlebury St, Elkhart IN 46515

Fig. T-104-0. 1/2 through 2 in. NPS. Screwed. With threads available to ANSI/ASME B1.20.1 and BS21 Pipe Thread Standards. Fig. F-697-0. 21/2 through 10 in. NPS. 300 psi (2070 kPa) working pressure. Flanged per ANSI Class 250 cast iron. Fig. F-607-0. 21/2 through 12 in. NPS. Flanged. Fig. F-607-0I. 65 through 300 mm. Flanged per ISO 2084. 12 bar (175 psi) rated working pressure. Fig. FI-607-RW. 21/2, 3, 4, 6, 8, 10, 12 in. Flanged. Model 607RW. 21/2 in. NPS 12 in. NPS flanged. 250 psi (1725 kPa) working pressure.

Resilient seat.

National Fire Fighting Mfg, FZCO, Box 17014, Jebel Ali Free Zone, Dubai, UAE

Model NF-OSY175U. Metal to Metal Seated Gate Valve. 2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

2, 21/2, 3, 4, 6, 8, 10, 12 Flanged

Model NF-OSY200U. Resilient Seated Gate Valve. 2 1/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged

Model NF-OSY250H. Resilient Seated Gate Valve. 2 1/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged

Model NF-OSY250G. Resilient Seated Gate Valve. 3 through 8 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

2 1/2, 3, 4, 6, 8, 10, 12 Grooved

National Fittings Inc, 295 East Swedesford Road #280, Wayne PA 19087-1462

Model 762U. Metal to Metal Seated Gate Valve. 2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

2, 3, 4, 6, 8, 10, 12 Flanged

Model 722U. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged

Model 722H. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged

Model 722G. Resilient Seated Gate Valve. 3, 4 and 6 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

3, 4, 6 Grooved

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Model RELOSY-200-RW. Resilient Seated Gate Valves. Sizes 21/2 through 12 in. NPS 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI, BS10, BS4505, JIS B2212, JIS B2213)

Model RELOSY-250-RW. Resilient Seated Gate Valves. Sizes 4, 6 and 8 in. NPS 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

4, 6, 8 Flanged × Flanged (ANSI)

Shanghai Karon Valves Machinery Co Ltd, No 815 Deyuan Road Nanxiang, Jiading District Shanghai, PRC

Series RRHX. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS. 232 psi (1600 kPa) rated working pressure. Available with the following end connections:

FM Approvals

1-146

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model No

Size

End Connections

RRHX XXX

XXX Valve size in millimeters.

2, 21/2, 3, 4, 5, 6, 8, 10, 12

Flanged x Flanged (ANSI)

Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY, United Kingdom

Model 762U. Metal to Metal Seated Gate Valve. 2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

2, 21/2, 3, 4, 6, 8, 10, 12 Flanged

Model 722U. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged

Model 722H. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged

Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115

Model 722G. 3, 4 and 6 in. NPS. Grooved ends. Resilient Seated. 200 psi (1380 kPa).

Siam Cast Iron Works Co Ltd, Samutsakorn Industrial Estate, Soi 7, 1/12 Moo 2, Rama II Rd, Tahsai, Muang, Samutsakorn 74000, Thailand

Model 105U. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 Flanged Grooved

Stockham Valves & Fittings, 2129 3rd Ave SE, Cullman AL 35055-5477

No. G-610. 21/2 through 12 in. Flanged, 200 psi (1380 kPa). No. B-133. 1 through 2 in. NPS. No. G-633. 21/2 through 6 in. NPS. Screwed. No. G-634. 21/2 through 14 in. NPS. Flanged. No. F-670. 2 through 10 in. NPS, flanged, 300 psi (2070 kPa) working pressure; 12 in. NPS, flanged, 250 psi (1725 kPa) working pressure.

Tong Kwang Valve Industrial Co Ltd, No. 1-1 Ming Chuan Rd, Ming-Sheng Li Tansui, Taipei Hsien, Taiwan ROC

Model 073U. 2, 21/2, 3, 4, 6, 8, 10 and 12 in. NPS. Flanged.

Tyco Fire Products, 1467 Elmwood Ave, Cranston RI 02910

Model OSY-1U. 21/2 through 12 in. NPS. Flanged only. 200 psi (1380 kPa). Model OSY-1H. 21/2 through 12 in. NPS. Flanged only. 250 psi (1725 kPa). Model OSY-1G. 3, 4 and 6 in. NPS. Grooved ends only. 200 psi (1380 kPa).

Resilient seat.

Tyco Water Valve (Shanghai) Co Ltd, No. 399 Jiu Ye Road, Qing Pu Industrial Zone, Shanghai China 201700

Series TM Resilient Seated Gate Valves. Rated working pressure 232 psi (1600 kPa). Available with the following end connections:

Model No. Size End Connections

TMRX-XXXX TMRG-XXXX TMRT-XXXX XXXX: Valve size in millimeters.

3, 4, 5, 6, 8, 10, 12 2, 50, 65, 80, 100, 125, 150, 200, 250, 300 2, 3, 4, 5, 6, 8, 10, 12 50, 65, 80, 100, 125, 150, 200, 250, 300 2, 3, 4, 5, 6, 8, 10, 12, 50, 65, 80, 100, 125, 150, 200, 250, 300 2 1/ 2, 21/2,

21/2,

Flanged × Flanged (ANSI, ISO, JIS) Grooved × Grooved Flanged × Grooved

United Brass Works Inc, S Main St, Randleman NC 27317

Fig. 18. 1 through 2 in. NPS.

United States Pipe & Foundry Co, 3300 First Ave N, Birmingham AL 35222

Metroseal Series*. 4, 6, 8, 10, 12, 14 and 16 in. NPS. 250 psi (1725 kPa) working pressure. Double flanged, double mechanical joint ends and flanged by mechanical joint ends through 16 in. nominal size, Tyton ends through 12 in. nominal size and TR Flex ends in 16 in. nominal size only.

*Resilient seat.

Figure USP0*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

3, 4, 6, 8 21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 21/2, Compression Ends Flanged Standardized Mechanical Joint

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-147

4, 6, 8, 3, 4, 6, 4, 6, 8 4, 6, 8 4, 6, 8, 4, 6, 8, 21/2, 3

10, 12 8, 10, 12

10, 12 10, 12

Standardized Mechanical Joint by Flanged Standardized Mechanical Joint by Tapping Flange Mechanical Joint (Cut In/D150) Mechanical Joint by Standardized Mechanical Joint (Cut In/D150) Slip ­ On Slip ­ On by Flange Threaded

Figure USP1*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

4, 4, 4, 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 8, 8, 8 10, 10, 10, 10, 10, 10, 10, 12, 12, 12, 12 12, 12, 12 14**, 16** 14**, 16** 14**, 16** 14**, 16** 14**, 16** Flanged Standardized Mechanical Joint Standardized Mechanical Joint by Flanged Standardized Mechanical Joint by Tapping Flange Slip ­ On Slip ­ On by Flange AquaGrip restrained mechanical joint, NPS AquaGrip restrained mechanical joint, IPS

Figure USP2*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

21/2, 3, 4, 6, 8, 10, 12 2 1/ 2, 3 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 Flanged Threaded Standardized Mechanical Joint Standardized Mechanical Joint by Flanged Standardized Mechanical Joint by Tapping Flange Slip ­ On Slip ­ On by Flange

*Bonnet with indicator post flange. **Rated Working Pressure 250 psi (1724 kPa).

AquaGrip end connections FM Approved for use with FM Approved PVC, HDPE and ductile iron pipe. 10 and 12 in. NPS AquaGrip end connections limited to 160 psi (1105 kPa) rated working pressure when used with HDPE pipe.

Victaulic Company, Box 31, Easton PA 18044-0031

Figure 771. Resilient Seated Gate Valve, 3, 4, 6 and 8 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

3, 4, 6, 8 Grooved

Figure 771H. Resilient Seated Gate Valve. Sizes 21/2 through 12 in. NPS and 165.1 mm DN, 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12, (165.1 mm) Grooved

Figure 771F. Resilient Seated Gate Valve. Sizes 21/2 through 12 in. NPS and 165.1 mm DN, 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12, (165.1 mm) Grooved × Flanged

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

FIREKING ­ Fig. No. OF200-####. Resilient Seated Gate Valves. Sizes 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12

#### Valve size in millimeters

Flanged × Flanged (ANSI Class 125, BS10 Table E, BS4505 DIN PN10, JIS B2212, JIS B2213)

FIREKING ­ Fig. No. OF250-####. Resilient Seated Gate Valves. Sizes 4 through 8 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

4, 6, 8

#### Valve size in millimeters

Flanged × Flanged (ANSI Class 125, BS10 Table E, BS4505 DIN PN10 & PN16, JIS B2212, JIS B2213)

Waterous Co, 125 Hardman Ave So, South Saint Paul MN 55075-1191

All Series 2500-1 . All Series 2500-1 valves have a 250 psi (1725 kPa) working pressure. Available in the following end connections:

4, 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 8, 10, 10, 10, 10, 10, 10, 12 12 12 12 12 12 Flanged (ANSI Class 125, 150, 250) Standardized Mechanical Joint Flanged (ANSI Class 125) × Standardized Mechanical Joint Flanged (ANSI Class 125) × Tyton Tyton Tapping Flange (ANSI Class 125) × Standard Mechanical Joint

Series 2500. Resilient Seated Gate Valves. 2 through 3 in. NPS OS&Y valves have a rated working pressure of 250 psi (1725 kPa). Available with the following end connections:

2, 21/2 3 2, 3 Flanged (ANSI Class 125) Flanged (ANSI Class 125, 150, 250) Standardized Mechanical Joint

FM Approvals

1-148

September 2007 -- Approval Guide Automatic Sprinkler Systems

2, 21/2, 3 2, 21/2, 3

Push-on for PVC Pipe NPT Threaded

Watts Regulator Co, 815 Chestnut St, North Andover MA 01845

Model 408RW. Resilient Seated Gate Valves. Sizes 21/2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged × Flanged

Model 409. Resilient Seated Gate Valves. Sizes 2 through 10 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10 21/2, 3, 4, 6, 8, 10 21/2, 3, 4, 6, 8, 10 2 Flanged × Flanged Flanged × Grooved Grooved × Grooved Thread × Thread

INSIDE SCREW GATE VALVES

Inside screw gate valves are used underground with indicator posts attached or as roadway box valves (curb box installation). FM Approved valves are available with a variety of end connections as indicated in the listings. Valves having Ring-Tite, Fluid-Tite or Tyton-Joint connections should be anchored in place during installation. Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.

AVK International A/S, Tech Bizonvej 3, Skovby 8464 Galten, Denmark

Series 25. Resilient seat gate valves, with or without Indicator Post Flange. 200 psi (1380 kPa) working pressure.

21/2, 3, 4, 6, 8, 10, 12 in. 21/2, 3, 4, 6 in. 8, 10, 12 in. 12 in. 4, 6, 8, 10 in. 4, 6, 8, 10 in. 4, 6, 8, 10 in. 4, 6, 8, 10 in. ANSI Flanged Flanged, PN 10/16 Flanged, PN 10 Flanged, PN 16 ANSI Flanged by mechanical joint Mechanical joint ANSI Flanged by Tyton joint Double Tyton joint

AVK Saudi Valves Manufacturing Co Ltd, Phase 4, Street No. LO 404, Jeddah, KSA 21443

Series 45. Resilient seat gate valves, with or without Indicator Post Flange. 250 psi (1725 kPa) working pressure.

3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 4, 6, 8, 10, 12 4, 6, 8, 10, 12 DN65, DN80, DN100, DN150, DN200, DN250, and DN300 3, 4, 6, 8 3, 4, 6, 8 4, 6, 8, 10, 12 21/2, Flanged (ANSI Class 125) Standardized Mechanical Joint Flanged (ANSI Class 125) × Standardized Mechanical Joint Flanged (ANSI Class 125) × Tyton Tyton Flanged (ANSI Class 250) Metric, PN 10/16 Grooved End (AWWA C606) Grooved End (AWWA C606) by Flanged Tapping Flange (ANSI Class 125) × Standardized Mech. Joint

American AVK Co, 5286 East Home Ave, Fresno CA 93727

Series 25 Resilient Seated Gate Valves. 21/2 through 8 in. NPS valves have a rated working Pressure of 250 psi (1725 kPa). 10 and 12 in. NPS valves have a rated working Pressure of 200 psi (1380 kPa). All available with or without Indicator Post Flange.

21/2, 2 1/ 2, 2 1/ 2, 2 1/ 2, 2 1/ 2, 2 1/ 2, 3, 3, 3, 3, 3, 3 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 8, 10, 12 8, 10, 12 8, 10, 12 8 8 Flanged Flanged by Mechanical Joint Standardized Mechanical Joint Flanged by Push-on Joint Push-on Joint Cut Grooved

Series 45 Resilient Seated Gate Valves. 3 through 8 in. NPS valves have a rated working Pressure of 250 psi (1725 kPa). 4, 6 and 8 in. NPS sizes only, available with AISI 304 Stainless Steel stems as an alternate material to bronze stems. 4 through 8 in. available with or without

3, 4, 6, 8 3, 4, 6, 8 Grooved Ends Flanged by Grooved Ends

American Darling Valve, Div American Cast Iron Pipe Co (ACIPCO), Box 2727 Birmingham AL 35202

Series 2500-1. All Series 2500-1 valves have a 250 psi (1725 kPa) working pressure and 4 through 12 in. sizes are available with or without an indicator post flange.

4, 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 8, 10, 10, 10, 10, 10, 10, 12 12 12 12 12 12 Flanged (ANSI Class 125, 150, 250) Standardized Mechanical Joint Flanged (ANSI Class 125) x Standardized Mechanical Joint Flanged (ANSI Class 125) × Tyton Tyton Tapping Flange (ANSI Class 125) x Standard Mechanical Joint

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-149

American Flow Control, Div American Cast Iron Pipe Co (ACIPCO), Box 2727, Birmingham AL 35202

Series 2500. Resilient Seated Gate Valves. 2 through 12 in. NPS valves have a rated working pressure of 250 psi (1725 kPa). 14 and 16 in. NPS valves have a rated working pressure of 200 psi (1380 kPa). Available with the following end connections:

2, 3, 2, 4, 4, 4, 4, 2, 2, 21/2, 14, 16 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12, 14, 16 6, 8, 10, 12, 14, 16 6, 8, 10, 12 6, 8, 10, 12 6, 8, 10, 12, 14, 16 21/2, 3, 14, 16 2 1/ 2, 3 Flanged (ANSI Class 125) Flanged (ANSI Class 125, 150, 250) Standardized Mechanical Joint Flanged (ANSI Class 125) × Standardized Mechanical Joint Flanged (ANSI Class 125) × Tyton Tyton Tapping Flange (ANSI Class 125) × Standard Mechanical Joint Push-on Threaded

Belgicast Internacional SL, B°Zabalondo 31, 48100 Munguia (Vizcaya), Spain

Model BV-05-07 *. Resilient Seated Gate Valves. Sizes 4 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

4, 6, 8, 10, 12 4, 6, 8 4, 6, 8, 10, 12

*Bonnet with indicator post flange. Bonnet without indicator post flange. Resilient seat.

Flanged Tyton Joint Slip-On for PVC Pipe

Clow Valve Co, Div McWane Inc, 902 S 2nd St, Oskaloosa IA 52577

Series F-5700. Metal to Metal Seated Gate Valves. Sizes 21/2 through 14 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

Model No. Size End Connections

F-5702 F-5705 F-5707 F-5710 F-5712 F-5715 Tapping F-5717 Tapping F-5720* F-5722* F-5725* F-5727* F-5730* F-5731 F-5732

3, 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12, 14 1/2, 3, 4, 6, 8, 10, 12, 14 2 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 21/2, 3 2 1/ 2, 3

Hub Flanged Mechanical Joint Ring-Tite Flanged × Mechanical Joint Mechanical Joint Hub Hub Flanged Mechanical Joint Ring-Tite Flanged × Mechanical Joint Push-on for PVC Threaded

Series F-6100. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

Model No. Size End Connections

F-6138 F-6140 F-6144 F-6148 F-6154* F-6156* F-6160* F-6164*

2, 21/2, 3, 4, 6, 8, 10, 12 2, 21/2, 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 2, 21/2, 3, 4, 6, 8 4, 6, 8, 10, 12 4, 6, 8, 10, 12 4, 6, 8, 10, 12 2, 21/2, 3, 4, 6, 8

Flanged Mechanical Joint Flanged × Mechanical Joint Push-on for PVC Flanged Mechanical Joint Flanged × Mechanical Joint Push-on for PVC

Model 2638. Resilient Seated Gate Valves. 4 through 16 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

4, 4, 4, 4, 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 8, 8 8, 8, 10, 10, 10, 10, 10, 10, 12, 12, 12, 12, 12 12, 14, 16 14, 16 16 14, 16 14, 16 Mechanical Joint Flanged Tyton Mechanical Joint × Flanged Tyton × Flanged Mechanical Joint × Tapping Flange PVC Groove Groove × Flange

10, 12 10, 12

Model 2639 Resilient Seated Gate Valves. Sizes 2 through 3 in. NPS. 250 psi (1725 kPa) rated working pressure. Sizes 4 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

2, 21/2, 3, 4, 6, 8, 10, 12 2 1/ 2, 3 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 21/2, 3, 4 2, 3, 4, 6, 8, 10, 12 Flanged Flanged × Groove Flanged × Mechanical Joint Flanged × Tyton Grooved Mechanical Joint

FM Approvals

1-150

September 2007 -- Approval Guide Automatic Sprinkler Systems

3, 2, 2, 4,

4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 2 1/ 2, 3 6, 8, 10, 12

Mechanical Joint × Tapping PVC Threaded Tyton

Model 2640. Resilient Seated Gate Valves. 2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

2, 21/2, 3, 4, 6, 8, 10, 12 2 1/ 2 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 21/2, 3, 4 2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 2, 21/2, 3, 4, 6, 8, 10, 12 2, 21/2, 3 4, 6, 8, 10, 12 Flanged Flanged × Groove Flanged × Mechanical Joint Flanged × Tyton Grooved Mechanical Joint × Mechanical Joint Mechanical Joint × Tapping PVC Threaded Tyton

East Jordan Iron Works Inc, 301 Spring Street, East Jordan MI 49727

4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 10, 10, 10, 10, 10, 12 12 12 12 12 Mechanical Joint × Mechanical Joint Mechanical Joint × Tapping Flange Mechanical Joint × Flat Flange Tyton × Tyton Flange × Flange

Ever Metal Industry Co Ltd, 853 Kwang Fu Rd, Pa Teh City, Tao Yuen Hsien, Taiwan ROC

Model 710U. Metal to Metal Seated Gate Valve. 21/2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model 721U. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model 721H. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model 721G. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. All valves are available with an operating nut or indicator post flange with operating nut. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Grooved

Model 721GF. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. All valves are available with an operating nut or indicator post flange with operating nut. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Grooved × Flanged

Fivalco (Qingdao) Co Ltd, 11 Shuangyuan Road Chengyang, Qingdao Shandong, PRC 266111

Model GVNRS-1161-200PSI. Resilient Seated Gate Valves. Sizes 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged × Flanged ANSI, BS10, BS4505, JIS B2212, JIS B2213)

Available with or without indicator post flange.

Kennedy Valve, Div McWane Inc, 1021 E Water St, Elmira NY 14901

KS-FW. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

2, 2, 3, 4, 2, 2, 4, 4, 21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 6, 8, 10, 12 21/2, 3, 4, 6, 8 2 1/ 2, 3 6, 8, 10, 12 6, 8, 10, 12 Flanged Mechanical Joint Mechanical Joint × Flanged Mechanical Joint × Tapping Flanged Push-On for PVC Threaded Tyton Tyton × Flanged

KS-RW. Resilient Seated Gate Valves. Sizes 4 through 12 in. NPS 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

4, 4, 4, 4, 6, 6, 6, 6, 8, 8, 8, 8, 10, 10, 10, 10, 12 12 12 12 Flanged Mechanical Joint Mechanical Joint x Flanged Mechanical Joint x Tapping Flange

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-151

4, 6, 8, 10, 12 4, 6, 8, 10, 12 4, 6, 8

Push - On Push - On x Flanged Push - On for PVC

Ken-Seal D. Resilient Seated Gate Valves. 4 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

4, 4, 4, 4, 6, 4, 4, 6, 6, 6, 6, 8, 6, 6, 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 10, 12 8, 10, 12 8 Standardized Mechanical Joint Flanged Push ­ On Standardized Mechanical Joint by Flanged Push ­ On by Flanged Standardized Mechanical Joint by Tapping Flange Push ­ On for PVC pipe

Bonnet without indicator post flange.

Ken-Seal II. Resilient Seated Gate Valves. 2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

2, 3, 4, 2, 4, 4, 4, 2, 2, 21/2, 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 6, 8, 10, 12 3, 4, 6, 8, 10, 12 6, 8, 10, 12 6, 8, 10, 12 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 2 1/ 2, 3 Flanged Flanged by Standardized Mechanical Joint Flanged by Push-On Standardized Mechanical Joint Standardized Mechanical Joint by Flanged Standardized Mechanical Joint by Tapping Push-On Push-On for PVC Threaded

Model 2620. 14 in. NPS. Available with standardized mechanical joint and flanged ends.

Bonnet without indicator post flange.

Lichfield Fire & Safety Equipment Co Ltd, 2nd Floor, Suite 4, Saturn Centre, Spring Rd, Ettingshall Rd, Wolverhampton WV4 WTX, United Kingdom

Model 710U. Metal to Metal Seated Gate Valve. 21/2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model 721U. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model 721H. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model 721G. Resilient Seated Gate Valve. 3, 4 and 6 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

3, 4, 6 Grooved

Lien Hwa Iron Works Co Ltd, 112 Sec 2 Kuang Fu Rd, Sanchung Taipei Hsien 24113, Taiwan ROC

Fig. 253RB. 4 through 8 in. NPS. Flanged. Fig. 263RB. 4 through 8 in. NPS. Standardized mechanical joint.

Resilient seat.

Linx Limited, 184 John Clarke Road, Middletown RI 02802

``United'' Model 5200. Resilient Seated Gate Valves. Sizes 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI, BS10, BS4505, JIS B2212, JIS B2213)

Available with or without indicator post flange.

M&H Valve Co, Box 2088, Anniston AL 36202

Model 4067. Resilient Seated Gate Valves. Sizes 4 through 12 in. NPS. 200 psi (1380 kPa) rated working Pressure. All available with or without indicator post flange. Available with the following end connections:

4, 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 8, 10, 10, 10, 10, 10, 10, 12 12 12 12 12 12 Flanged Mechanical Joint Mechanical Joint × Flange Mechanical Joint × Tapping Push-on Joint Push-on × Flange

FM Approvals

1-152

September 2007 -- Approval Guide Automatic Sprinkler Systems

Series 7000. Resilient Seated Gate Valves. Sizes 4 through 12 in. NPS. 200 psi (1380 kPa) rated working Pressure. All available with or without indicator post flange. Available with the following end connections:

4, 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 8, 10, 10, 10, 10, 10, 10, 12 12 12 12 12 12 Flanged Mechanical Joint Mechanical Joint × Flange Mechanical Joint × Tapping Push-on Joint Push-on × Flange

Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel

Quikcoup Style 450. Resilient Seated Gate Valves. Sizes 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI, BS10, BS4504, JIS B2212, JIS B2213)

Available with or without indicator post flange.

Mueller Co, 500 W Eldorado St, Decatur IL 62525

Series 2050. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Available with the following end connections.

Figure No. Size End Connections

A-2050-5 A-2050-6 A-2050-20 A-2050-24 A-2050-26

4, 4, 4, 4, 4,

6, 6, 6, 6, 6,

8, 8, 8, 8, 8,

10, 10, 10, 10, 10,

12, 12, 12, 12, 12,

14 14 14 14 14

Hub Flanged Mechanical Joint Asbestos Cement Hub Flanged by Asbestos Cement Hub

Series 2052*. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Available with the following end connections.

Figure No. Size End Connections

A-2052-5 A-2052-6 A-2052-16 A-2050-20 A-2052-23 A-2050-24 A-2050-26

4, 4, 4, 4, 4, 4, 4,

6, 6, 6, 6, 6, 6, 6,

8, 8, 8, 8, 8, 8, 8,

10, 10, 10, 10, 10, 10, 10,

12, 12, 12, 12, 12, 12, 12,

14 14 14 14 14 14 14

Hub Flanged Flanged by Asbestos Cement Hub Mechanical Joint Mechanical Joint Asbestos Cement Hub Flanged by Asbestos Cement Hub

Series 2074. Resilient Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Available with the following end connections.

Figure No. Size End Connections

A-2074-6 A-2074-16 A-2074-20 A-2074-24 A-2074-26 A-2074-53

4, 4, 4, 4, 4,

6, 6, 6, 6, 6,

8, 8, 8, 8, 8, 4,

10, 10, 10, 10, 10, 6

12 12 12 12 12

Flanged Flanged by Mechanical Joint Mechanical Joint Asbestos Cement Hub Flanged by Asbestos Cement Hub Flanged by Grooved

Series 2075*. Resilient Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Available with the following end connections.

Figure No. Size End Connections

A-2075-6 A-2075-16 A-2075-20 A-2075-24 A-2075-26 A-2075-40

4, 4, 4, 4, 4, 4,

6, 6, 6, 6, 6, 6,

8, 8, 8, 8, 8, 8,

10, 10, 10, 10, 10, 10,

12 12 12 12 12 12

Flanged Flanged by Mechanical Joint Mechanical Joint Asbestos Cement Hub Flanged by Asbestos Cement Hub Slip-On Ends

Series 645*. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Tapping Valve. Available with the following end connections.

Figure No. Size End Connections

A-645

4, 6, 8, 10, 12

Flanged by Asbestos Cement Hub

Series 698*. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Tapping Valve. Available with the following end connections.

Figure No. Size End Connections

A-698

4, 6, 8, 10, 12, 14

Flanged by Hub

Series 699*. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Tapping Valve. Available with the following end connections.

Figure No. Size End Connections

A-699

4, 6, 8, 10, 12, 14

Flanged by Mechanical Joint

Series 876*. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Cut-in valve with duck-tipped rubber gaskets. Available with the following end connections.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-153

Figure No.

Size

End Connections

A-876

4, 6, 8, 10, 12

Mechanical Joint

Series 877*. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Cut-in valve with plain rubber gaskets. Available with the following end connections.

Figure No. Size End Connections

A-877

4, 6, 8, 10, 12

Mechanical Joint

Figure 2360*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

3, 4, 6, 8 21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8 4, 6, 8 4, 6, 8, 10, 12 4, 6, 8, 10, 12 2 1/ 2, 3 21/2, Compression Ends Flanged Standardized Mechanical Joint Standardized Mechanical Joint by Flanged Standardized Mechanical Joint by Tapping Flange Mechanical Joint (Cut In/D150) Mechanical Joint by Standardized Mechanical Joint (Cut In/D150) Slip ­ On Slip ­ On by Flange Screwed

Figure 2361*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

4, 4, 4, 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 8, 8, 8 10, 10, 10, 10, 10, 10, 10, 12, 12, 12, 12 12, 12, 12 14**, 16** 14**, 16** 14**, 16** 14**, 16** 14**, 16** Flanged Standardized Mechanical Joint Standardized Mechanical Joint by Flanged Standardized Mechanical Joint by Tapping Flange Slip ­ On Slip ­ On by Flange AquaGrip restrained mechanical joint, NPS AquaGrip restrained mechanical joint, IPS

Figure 2362*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

21/2, 3, 4, 6, 8, 10, 12 2 1/ 2, 3 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 Flanged Threaded Standardized Mechanical Joint Standardized Mechanical Joint by Flanged Standardized Mechanical Joint by Tapping Flange Slip ­ On Slip ­ On by Flange

Figure 2460. Resilient Seated Gate Valves. 250 psi (1724 kPa) rated working pressure. All valves are available with an operating nut or indicator post flange with operating nut. Available with the following end connections:

21/2, 3, 4, 6, 8 21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8 4, 6, 8, 10, 12 2 1/ 2, 3 Compression Ends Flanged Standardized Mechanical Joint Standardized Mechanical Joint by Tapping Flange Mechanical Joint (Cut In/D150) Slip ­ On Threaded

Figure 2461. Resilient Seated Gate Valves. 250 psi (1724 kPa) rated working pressure. All valves are available with an operating nut or indicator post flange with operating nut. Available with the following end connections:

4, 4, 3, 4, 6, 6, 4, 6, 8, 8, 6, 8, 10, 12 10, 12 8, 10, 12 10, 12 Flanged Standardized Mechanical Joint Standardized Mechanical Joint by Tapping Flange Slip ­ On

Figure 2462. Resilient Seated Gate Valves. 250 psi (1724 kPa) rated working pressure. All valves are available with an operating nut or indicator post flange with operating nut. Available with the following end connections:

21/2, 3, 4, 6, 8 21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8 4, 6, 8, 10, 12 2 1/ 2, 3 Compression Ends Flanged Standardized Mechanical Joint Standardized Mechanical Joint by Tapping Flange Mechanical Joint (Cut In/D150) Slip ­ On Threaded

*Bonnet with indicator post flange. **Rated Working Pressure 250 psi (1724 kPa).

AquaGrip end connections FM Approved for use with FM Approved PVC, HDPE and ductile iron pipe. 10 and 12 in. NPS AquaGrip end connections limited to 160 psi (1105 kPa) rated working pressure when used with HDPE pipe.

NIBCO Inc, 1516 Middlebury St, Elkhart IN 46515

Figure F609. All valves are available with an operating nut or indicator post flange with operating nut. Available with the following end connections:

FM Approvals

1-154

September 2007 -- Approval Guide Automatic Sprinkler Systems

4, 6, 8, 10, 12 4, 6, 8, 10, 12 4, 6, 8, 10, 12

Flanged (ANSI/ISO 2084) Standardized Mechanical Joint Standardized Mechanical Joint by Flange

Figure F609RW. Resilient Seated Gate Valves. 250 psi (1725 kPa) rated working pressure. All valves are available with an operating nut or indicator post flange with operating nut. Available with the following end connections:

4, 6, 8, 10, 12 4, 6, 8, 10, 12 4, 6, 8, 10, 12 Flanged (ANSI) Standardized Mechanical Joint Standardized Mechanical Joint by Flange

National Fire Fighting Mfg, FZCO, Box 17014, Jebel Ali Free Zone, Dubai, UAE

Model NF-NRS175U. Metal to Metal Seated Gate Valve. 21/2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model NF-NRS200U. Resilient Seated Gate Valve. 2 1/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model NF-NRS250H. Resilient Seated Gate Valve. 2 1/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model NF-NRS250G. Resilient Seated Gate Valve. 3 through 8 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

3, 4, 6, 8, Grooved

National Fittings Inc, 295 East Swedesford Road #280, Wayne PA 19087-1462

Model 710U. Metal to Metal Seated Gate Valve. 21/2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model 721U. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model 721H. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model 721G. Resilient Seated Gate Valve. 3, 4 and 6 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

3, 4, 6 Grooved

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Model RELNRS-200-RW. Resilient Seated Gate Valves. Sizes 21/2 through 12 in. NPS 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 Flanged 1 × Flanged (ANSI, BS10, BS4505, JIS B2212, JIS B2213)

Available with or without indicator post flange.

Saint-Gobain PAM, 91 Av de la Liberation, 54076 Nancy, Cedex France

Series Euro 20. Resilient Seated Gate Valves. Sizes 11/2 through 8 in. NPS, 235 psi (1620 kPa) rated working pressure. Sizes 10 and 12 in. NPS, 200 psi (1380 kPa). Available with the following end connections:

Model No. Size End Connections

Type 21* Type 23* Type 24*

11/2, 2, 21/2, 3, 4, 5, 6, 8, 10, 12 11/2, 2, 21/2, 3, 4, 5, 6, 8, 10, 12 2, 21/2, 3, 4, 5, 6, 8

Flanged × Flanged (ANSI, ISO) Flanged × Flanged (ANSI, ISO) Socket

*Sizes 4 in. NPS and larger are available with indicator post flange.

Shanghai Karon Valves Machinery Co Ltd, No. 815 Deyuan Road Nanxiang, Jiading District Shanghai, PRC

Series RVCX. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS. 232 psi (1600 kPa) rated working pressure. Available with the following end connections:

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-155

Model No.

Size

End Connections

RVHX/RVCX XXX

XXX Valve size in millimeters.

2, 21/2, 3, 4, 5, 6, 8, 10, 12

Flanged × Flanged (ANSI)

Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY, United Kingdom

Model 710U. Metal to Metal Seated Gate Valve. 21/2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model 721U. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Model 721H. Resilient Seated Gate Valve. 21/2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 Flanged Mechanical Joint

Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115

Model 721G. Resilient Seated Gate Valve. 3 through 6 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

3, 4, 6 Grooved

Stockham Valves & Fittings, 2129 3rd Ave SE, Cullman AL 35055-5477

G-600. 4 through 12 in. Flanged with indicator post flange. 200 psi (1380 kPa). G-601. 4 through 12 in. Standardized mechanical joint, with indicator post flange. 200 psi (1380 kPa). G-602. 4 through 12 in. NPS. Flanged by mechanical joint end, with indicator post flange. 200 psi (1380 kPa). G-603. 4 through 12 in. Tyton joint, with indicator post flange. 200 psi (1380 kPa). G-604. 4 through 12 in. Flanged by Tyton pipe end, with indicator post flange. 200 psi (1380 kPa). G-605. 4 through 12 in. Flanged. 200 psi (1380 kPa). G-606. 4 through 12 in. Standardized mechanical joint, flanged. 200 psi (1380 kPa). G-607. 4 through 12 in. Tyton ends. 200 psi (1380 kPa). G-616. 4 through 12 in. Flanged by mechanical joint end. 200 psi (1380 kPa). G-617. 4 through 12 in. Flanged by Tyton end. 200 psi (1380 kPa). No. G-632. 4 through 12 in. NPS. Flanged. No. G-635. 4 through 14 in. NPS. Standardized mechanical joint. No. G-638. 4 through 14 in. NPS. Ring-Tite.

Tyco Fire Products, 1467 Elmwood Ave, Cranston RI 02910

Model NRS-1U. 21/2 through 12 in. NPS. Flanged or standardized mechanical joint. 200 psi (1380 kPa). 8, 10 in. NPS. Flanged or standardized mechanical joint. 175 psi (1205 kPa). Model NRS-1H. 21/2 through 12 in. NPS. Flanged or standardized mechanical joint. 250 psi (1725 kPa). Model NRS-1G. 3, 4 and 6 in. NPS. Grooved ends only. 200 psi (1380 kPa).

Resilient seat.

Tyco Water Valve (Shanghai) Co Ltd, No. 399 Jiu Ye Road, Qing Pu Industrial Zone, Shanghai China 201700

Series TM Resilient Seated Gate Valves. Rated working pressure 232 psi (1600 kPa) Available with the following end connections:

Model No. Size End Connections

TMCX-XXXX

2, 21/2, 3, 4, 5, 6, 8, 10, 12 50, 65, 80, 100, 125, 150, 200, 250 and 300 2, 21/2, 3, 4, 5, 6, 8, 10, 12 50, 65, 80, 100, 125, 150, 200, 250 and 300 2, 21/2, 3, 4, 5, 6, 8, 10, 12 50, 65, 80, 100, 125, 150, 200, 250 and 300

Flanged × Flanged (ANSI, ISO, JIS)

TMCG-XXXX

Grooved × Grooved

TMCT-XXXX

Flanged × Grooved

Series TM, Indicator Post Flange. Rated working pressure 232 psi (1600 kPa). Available with the end connections listed below:

Model No. Size End Connections

TMCX-P-XXXX *

4, 5, 6, 8, 10, 12 100, 125, 150, 200, 250 and 300 4, 5, 6, 8, 10, 12 100, 125, 150, 200, 250 and 300 4, 5, 6, 8, 10, 12 100, 125, 150, 200, 250 and 300

Flanged x Flanged (ANSI, ISO, JIS)

TMCG-P-XXXX *

Grooved x Grooved

TMCG-P-XXXX *

Flanged x Grooved

XXXX = Valve size in millimeters. * Bonnet with indicator post flange. Bonnet without indicator post flange.

FM Approvals

1-156

September 2007 -- Approval Guide Automatic Sprinkler Systems

United States Pipe & Foundry Co, 3300 First Ave N, Birmingham AL 35222

Metroseal Series*. 4, 6, 8, 10, 12, 14 and 16 in. NPS. 250 psi (1725 kPa) working pressure. Double flanged, double mechanical joint ends and flanged by mechanical joint ends through 16 in. nominal size, Tyton ends through 12 in. nominal size and TR Flex ends in 16 in. nominal size only. With and without indicator post flange.

*Resilient seat.

Figure USP0*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

21/2, 3, 4, 6, 8 21/2, 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8 4, 6, 8 4, 6, 8, 10, 12 4, 6, 8, 10, 12 2 1/ 2, 3 Compression Ends Flanged Standardized Mechanical Joint Standardized Mechanical Joint by Flanged Standardized Mechanical Joint by Tapping Flange Mechanical Joint (Cut In/D150) Mechanical Joint by Standardized Mechanical Joint (Cut In/D150) Slip ­ On Slip ­ On by Flange Screwed

Figure USP1*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

4, 4, 4, 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 8, 8, 8 10, 10, 10, 10, 10, 10, 10, 12, 12, 12, 12 12, 12, 12 14**, 16** 14**, 16** 14**, 16** 14**, 16** 14**, 16** Flanged Standardized Mechanical Joint Standardized Mechanical Joint by Flanged Standardized Mechanical Joint by Tapping Flange Slip ­ On Slip ­ On by Flange AquaGrip restrained mechanical joint, NPS AquaGrip restrained mechanical joint, IPS

Figure USP2*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.

21/2, 3, 4, 6, 8, 10, 12 2 1/ 2, 3 3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 21/2, 3, 4, 6, 8, 10, 12 4, 6, 8, 10, 12 Flanged Threaded Standardized Mechanical Joint Standardized Mechanical Joint by Flanged Standardized Mechanical Joint by Tapping Flange Slip ­ On Slip ­ On by Flange

*Bonnet with indicator post flange. **Rated Working Pressure 250 psi (1724 kPa).

AquaGrip end connections FM Approved for use with FM Approved PVC, HDPE and ductile iron pipe. 10 and 12 in. NPS AquaGrip end connections limited to 160 psi (1105 kPa) rated working pressure when used with HDPE pipe.

Victaulic Company, Box 31, Easton PA 18044-0031

Figure 772. Resilient Seated Gate Valve. 3, 4, 6 and 8 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:

3, 4, 6, 8 Grooved

Figure 772H. Resilient Seated Gate Valve. Sizes 21/2 through 12 in. NPS and 165.1 mm DN, 250 psi (1725 kPa) rated working pressure. All valves are available with an operating nut or indicator post flange with operating nut. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12, (165.1 mm) Grooved

Figure 772F. Resilient Seated Gate Valve. Sizes 21/2 through 12 in. NPS and 165.1 mm DN, 250 psi (1725 kPa) rated working pressure. All valves are available with an operating nut or indicator post flange with operating nut. Available with the following end connections:

21/2, 3, 4, 6, 8, 10, 12, (165.1 mm) Grooved × Flanged

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

FIREKING ­ Fig. No. NF200-####. Resilient Seated Gate Valves. Sizes 21/2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections: 21/2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI Class 125, BS10 Table E, BS4505 DIN PN10, JIS B2212, JIS B2213)

#### Valve size in millimeters

Available with or without indicator post flange.

Waterous Co, 125 Hardman Ave So, South Saint Paul MN 55075-1191

Series 2500-1 . All Series 2500-1 valves have a 250 psi (1725 kPa) working pressure and 4 through 12 in. sizes are available with or without an indicator post flange. Available in the following end connections:

4, 4, 4, 4, 4, 4, 6, 6, 6, 6, 6, 6, 8, 8, 8, 8, 8, 8, 10, 10, 10, 10, 10, 10, 12 12 12 12 12 12 Flanged (ANSI Class 125, 150, 250) Standardized Mechanical Joint Flanged (ANSI Class 125) × Standardized Mechanical Joint Flanged (ANSI Class 125) × Tyton Tyton Tapping Flange (ANSI Class 125) × Standard Mechanical Joint

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-157

Series 2500. Resilient Seated Gate Valves. 2 through 3 in. NPS NRS valves have a rated working pressure of 250 psi (1725 kPa). 14 and 16 in. NPS valves have a rated working pressure of 200 psi (1380 kPa). Available with the following end connections:

2, 21/2, 14, 16 3 2, 3, 14, 16 2, 21/2, 3 2, 21/2, 3 14, 16 14, 16 14, 16 Flanged (ANSI Class 125) Flanged (ANSI Class 125, 150, 250) Standardized Mechanical Joint Push-on for PVC Pipe NPT Threaded Flanged (ANSI Class 125) × Standardized Mechanical Joint Tapping Flange (ANSI Class 125) x Standard Mechanical Joint Push-on for D. I. Pipe

INDICATING VALVES, Butterfly or Ball Type

Design features provide a dependable visible indication of the open position even at a distance. If excessive force is applied to the handle, weakness-joints will break so as to preserve correct orientation between indicator and valve position. Valve and indicator parts are so designed that they can be assembled only one way, always to give correct indication. All FM Approved indicating valves turn clockwise to shut. They are small, lightweight, and, because of a resilient seat, are easy to operate. They are not subject to sticking or dropped gates. They are not recommended for throttling service. Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.

Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801

Model Number Product Type Nominal Pipe Size in./ mm Rated Working Pressure, psi (kPa) Remarks

AE7722-3A

Remarks:

Butterfly Valve, Grooved Ends

2, 21/2, 3, 4, 5, 6, 8, 10 in. 76.1, 139.7, 165.1 mm

300 (2070)

a, b, c

a. Available with dual supervisory switches. b. FM Approved for indoor and outdoor service. c. FM Approved for aboveground installations only.

AnvilStar LLC, Division of Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801

Model Number Product Type Nominal Pipe Size in. / mm Rated Working Pressure, psi (kPa) Remarks

AE7722-3A

Remarks:

Butterfly Valve, Grooved Ends

2, 21/2, 3, 4, 5, 6, 8, 10 in. 76.1, 139.7, 165.1 mm

300 (2070)

a, b, c

a. Available with dual supervisory switches. b. Approved for indoor and outdoor service. c. Approved for aboveground installations only.

DANFOSS SOCLA S.A.S., 365, rue du Lieutenant Putier, 71530 Virey-Le-Grand, France

Model Number Product Type Nominal Pipe Size, mm Rated Working Pressure, psi (kPa) Remarks

BOMBYX

Butterfly Valve, Wafer Style with, centering lugs, Lugged Body

32, 40, 50, 65, 80, 100, 125, 150, 200, 250, 300

232 (1600)

a, b, c

Remarks: a. Available with dual supervisory switches. b. FM Approved for indoor and outdoor service. c. FM Approved for aboveground installations only.

Fivalco Inc, 2221 E Winston Rd, Unit J, Anaheim CA 92806

Model Number Product Type Nominal Pipe Size Rated Working Pressure, psi (kPa) Remarks

Firefly-BT Firefly-BG Fireriser-DG Fireriser-DW Fireriser-HPG

Butterfly Valve, Threaded Ends Butterfly Valve, Grooved Ends Butterfly Valve, Grooved Ends Butterfly Valve, Wafer Body Butterfly Valve, Grooved Ends

1, 11/4, 11/2, 2, 21/2 2, 21/2 2 1/ 2, 2 1/ 2, 3, 4, 6, 8 3, 4, 6, 8

21/2, 3, 4, 6, 8

175 (1205) 175 (1205) 175 (1205) 175 (1205) 300 (2070)

a, b a, b a, b a, b a, b

FM Approvals

1-158

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model Number

Product Type

Nominal Pipe Size

Rated Working Pressure, psi (kPa)

Remarks

Fireriser-HPW

Remarks:

Butterfly Valve, Wafer Body

21/2, 3, 4, 6, 8

300 (2070)

a, b

a. Available with dual supervisory switches. b. Approved for above ground, indoor and outdoor use only.

Global Safety Products Inc, 970 E Orangethorpe Ave, Unit B, Anaheim CA 92801

Model Number Product Type Nominal Pipe Size, in. (mm) Rated Working Pressure, psi (kPa) Remarks

BV-W

Butterfly Valve, Wafer Body Butterfly Valve, Grooved Ends Butterfly Valve, Threaded Ends Butterfly Valve, Grooved Ends Butterfly Valve, Grooved Ends Butterfly Valve, Wafer Body

21/2, 3, 4, 5, 6, 8 (65), (80), (100), (125), (150), (200) 21/2, 3, 4, 5, 6, 8 (65), (125), (150) 1, 11/4, 11/2, 1, 2, 21/2

175 (1205) 175 (1205) 175 (1205) 175 (1205) 300 (2070) 300 (2070)

a, c, d

BV-G

a, c, d

BB-T

a, c, d

BB-G

2, 21/2

a, c, d

BO-G 300

21/2, 3, 4, 5, 6, 8 (65), (125), (150), (200) 21/2, 3, 4, 5, 6, 8 (65), (80), (100), (125), (150), (200)

a, b, c

BO-W 300

Remarks: a. b. c. d.

a, b, c

Available with dual supervisory switches. FM Approved for indoor and outdoor service. FM Approved for aboveground installations only. FM Approved for indoor service only.

Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658

Model Number Product Type Nominal Pipe Size Rated Working Pressure, psi (kPa) Remarks

GL175T GL175G GLR175G GLR175W GLR300G GLR300W

Remarks:

Butterfly Valve, Threaded Ends Butterfly Valve, Grooved Ends Butterfly Valve, Grooved Ends Butterfly Valve, Wafer Body Butterfly Valve, Grooved Ends Butterfly Valve, Wafer Body

1, 11/4, 11/2, 2, 21/2 2, 21/2 21/2, 3, 4, 6, 8 2 1/ 2, 3, 4, 6, 8

21/2, 3, 4, 6, 8 21/2, 3, 4, 6, 8

175 (1205) 175 (1205) 175 (1205) 175 (1205) 300 (2070) 300 (2070)

a, b a, b a, b a, b a, b a, b

a. Available with dual supervisory switches. b. Approved for above ground, indoor and outdoor use only.

Henry Pratt Co, 401 S Highland Ave, Aurora IL 60506

Type FM-3. 6, 8, 10, 12, 14, 16, 18, 20, 24 in. Available with wafer (for mounting between flanges), mechanical joint or flanged-end connections. Also available in push-on end connections in 4, 6, 8, 10, 12, 14 and 16 in. NPS. Valves available with either hand crank or 2 in. (51 mm) square operating nut. Valves having operating nut limited to underground installations in watertight, frost proof concrete or masonry pits.

Kennedy Valve, Div McWane Inc, 1021 E Water St, Elmira NY 14901

Model Number Product Type Nominal Pipe Size, in. Rated Working Pressure, psi (kPa) Remarks

Figure 82M

Butterfly Valve, Grooved Ends Butterfly Valve, Grooved Ends Butterfly Valve, Grooved Ends

3, 4, 5, 6, 8

175 (1205) 300 (2070) 175 (1205)

c, d

Figure 83M

3, 4, 5, 6, 8

c, d

Figure 93G

21/2, 3, 4, 6, 8

a, c, d

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-159

Model Number

Product Type

Nominal Pipe Size, in.

Rated Working Pressure, psi (kPa)

Remarks

Figure 93W

Butterfly Valve, Wafer Style (ANSI)

21/2, 3, 4, 6, 8

175 (1205)

a, c, d

Figure 01G

Butterfly Valve, Grooved Ends Butterfly Valve, Grooved Ends, Extended Length Butterfly Valve, Wafer Style (ANSI) Butterfly Valve, Grooved Ends Butterfly Valve, Grooved Ends, Extended Length

21/2, 3, 4, 6, 8

300 (2070) 300 (2070)

a, c, d

Figure 02G

8

a, c, d

Figure 01W

21/2, 3, 4, 6, 8

300 (2070) 300 (2070) 300 (2070)

a, c, d

Figure G300

21/2, 3, 4, 6

a, b, c

Figure G300E

21/2, 3, 4, 6

a, b, c

Remarks: a. b. c. d. Available with dual supervisory switches. FM Approved for indoor and outdoor service. FM Approved for aboveground installations only. FM Approved for indoor service only.

Milwaukee Valve Company Inc, 16550 West Stratton Drive, New Berlin WI 53151

Model Number Product Type Nominal Pipe Size, in. Rated Working Pressure, psi (kPa) Remarks

BBSC

Butterfly Valve, Threaded Ends Butterfly Valve, Grooved Ends Butterfly Valve, Threaded Ends Butterfly Valve, Grooved Ends

1, 11/4, 11/2, 2, 21/2 2, 21/2

175 (1205) 175 (1205) 175 (1205) 175 (1205)

b, c, d

BBSC

b, c, d

BBSCS

1, 11/4, 11/2, 2, 21/2 2, 21/2

a, b, c, d

BBSCS

Remarks: a. b. c. d.

a, b, c

Available with dual supervisory switches. FM Approved for indoor and outdoor service. FM Approved for aboveground installations only. FM Approved when supplied with female NPT threaded end connections.

Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel

Model 200 Wafer body (for mounting between bolted flanges). 21/2, 3, 4, 6, 8 in. NPS and 65, 80, 100, 150 and 200 mm NPS. Model 100. Grooved inlet and outlet connections. 21/2, 3, 4, 6, 8 in. NPS and 65 and 150 mm NPS. Model 500-T. Threaded connections. 1, 11/4, 11/2, 2, 21/2 in. NPS. Model 500-G. Grooved inlet and outlet connections. 2, 21/2 in. NPS. Valves are FM Approved for aboveground indoor use only. Valves are available with two supervisory switches.

Mueller Co, 500 W Eldorado St, Decatur IL 62525

Fig No. Product Type Nominal Pipe Size, in. Rated Working Pressure, psi (kPa) Remarks

B3250-00

Butterfly Valve, Wafer Body Butterfly Valve, Wafer or Lug Body Butterfly Valve, Wafer or Lug Body Butterfly Valve, Grooved End Butterfly Valve, Grooved End

2, 21/2, 3, 4, 5, 6, 8

175 (1205) 250 (1725) 250 (1725) 300 (2070) 300 (2070)

c, d

B3253-00

2, 21/2, 3, 4, 5, 6

a, b, c

B3253-00

8, 10, 12

a, c, d

B3254-52

3, 4, 6, 165 mm

a, b, c

B3254-52

Remarks:

8

a, c, d

FM Approvals

1-160

September 2007 -- Approval Guide Automatic Sprinkler Systems

a. b. c. d.

Available with supervisory switches. FM Approved for indoor and outdoor service. FM Approved for aboveground installations only. FM Approved for indoor service only.

NIBCO Inc, 1516 Middlebury St, Elkhart IN 46515

Fig No. Product Type Nominal Pipe Size, in. Rated Working Pressure, psi (kPa) Remarks

WD-3510-4 WD-3510-8 LD-3510-4 LD-3510-8 EW-3510-4 EW-3510-8 EL-3510-4 EL-3510-8 GD-1765-4N GD-1765-8N GD-4765-4N GD-4765-4N KT-505W-4 KT-505W-8 KG-505W-4 KG-505W-8

Remarks:

Butterfly Valve, Wafer Body Butterfly Valve, Lug Body Butterfly Valve, Wafer Body Butterfly Valve, Lug Body Butterfly Valve, Grooved End Butterfly Valve, Grooved End Ball Valve, Threaded Ends Ball Valve, Grooved Ends

2, 21/2, 3, 4, 5, 6, 8, 10, 12

250 (1725) 250 (1725) 250 (1725) 250 (1725) 175 (1205) 300 (2070) 300 (2070) 300 (2070)

a, b, c, d, e

2, 21/2, 3, 4, 6, 8, 10, 12

a, b, c, d

2, 21/2, 3, 4, 6, 8, 10, 12

a, b, c, e

2, 21/2, 3, 4, 6, 8, 10, 12

a, b, c, f

21/2, 3, 4, 5, 6, 8, 10

a, b, c

21/2, 3, 4, 6, 8

a, b, c

1, 11/4, 11/2, 2, 21/2

a, b, c, d

2, 21/2

a, b, c

a. Aboveground, indoor or outdoor. b -4: no supervisory switches. c. -8: with supervisory switches. d. For mounting between ANSI bolted flanges. e. For use with ANSI, ISO NP10 and 16 or ``BS.10'' D & E flanges. f. For use with metric flanges, NP10 and 16. g. With threads available to ANSI/ASME B1.20.1 and BS21 Pipe Thread Standards.

Rapidrop Limited, Manasty Road, Peterborough PE2 6UP, United Kingdom

Model No. Product Type Nominal Pipe Size, in. Rated Working Pressure, psi (kPa) Remarks

BT 175 BG 175 DG 175 DW 175 HPG 300 HPW 300

Butterfly Valve, Threaded Ends Butterfly Valve, Grooved Ends Butterflu Valve, Grooved Ends Butterfly Valve, Wafer Body Butterfly Valve, Grooved Ends Butterfly Valve, Wafer Body

1, 11/4, 11/2, 2, 21/2 2, 21/2 21/2, 3, 4, 6, 8 21/2, 3, 4, 6, 8 21/2, 3, 4, 6, 8 21/2, 3, 4, 6, 8

175 (1205) 175 (1205) 175 (1205) 175 (1205) 300 (2070) 300 (2070)

a, b a, b a, b a, b a, b a, b

SAPAG Industrial Valves, BP2-2 rue du Marais, F-80400 Ham, France

Model JMA-FPS, Figure 81219. Wafer body (for mounting between bolted flanges). 2, 21/2, 3, 4, 5, 6, 8, 10, 12 in. NPS. Model JPL-FPS, Figure 39109. Cut grooved inlet and outlet body connections. 21/2, 3, 4, 5,6, 8, 10, 12 in. NPS. 76.1, 139.7, 165.1 mm OD sizes. All valves are FM Approved for aboveground use only. Valves are available with 2 supervisory switches.

Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY, United Kingdom

Model Number Product Type Nominal Pipe Size, in. Rated Working Pressure, psi (kPa) Remarks

SDBV-W

Butterfly Valve, Wafer Body

21/2, 3, 4, 6, 8 in.

175 (1205)

a, b

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-161

Model Number

Product Type

Nominal Pipe Size, in.

Rated Working Pressure, psi (kPa)

Remarks

SDBV-G

Butterfly Valve, Grooved Ends Butterfly Valve, Threaded Connections Butterfly Valve, Grooved Ends

21/2, 3, 4, 6, 8 in.

175 (1205) 175 (1205) 175 (1205)

a, b

SDBB-T

1, 11/4, 11/2, 2, 21/2 in.

a, b

SDBB-G

Remarks:

2, 21/2 in.

a, b

a. Available with two supervisory switches. b. Approved for aboveground indoor use only.

Stockham Valves & Fittings, 2129 3rd Ave SE, Cullman AL 35055-5477

Fig. LD-52-UF, Fig. LG-52-UF. Wafer body (for mounting between bolted ANSI flanges). 4, 5, 6, 8, 10, 12 in. NPS. Fig. LD-62-UF, Fig. LG-62-UF. Drilled lug body. 4, 5, 6, 8, 10, 12 in. NPS. Fig. LD-72-UF, Fig. LG-72-UF. Drilled and tapped lug body, 4, 5, 6, 8, 10, 12 in. NPS. Fig. LD-82-UF, Fig. LG-82-UF. Cut grooved inlet and outlet body connections. 4, 6, 8 in. NPS. All valves are FM Approved for aboveground use only. Valves are available with one or two supervisory switches.

Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446

Model Number Product Type Nominal Pipe Size, in. Rated Working Pressure, psi (kPa) Remarks

Grinnell BFV-1 TFP BFV-1

Remarks:

Butterfly Valve, Grooved Ends Butterfly Valve, Grooved Ends

21/2, 3, 4, 5, 8, 10 21/2, 3, 4, 5, 8, 10

300 (2070) 300 (2070)

a, b, c

a, b, c

a. Available with dual supervisory switches. b. FM Approved for indoor and outdoor service. c. FM Approved for aboveground installations only.

Tyco Fire and Building Products, 1467 Elmwood Ave, Cranston RI 02910

Fig No. Product Type Nominal Pipe Size, in. Rated Working Pressure, psi (kPa) Remarks

BFV-N

Butterfly Valve, Wafer Body Butterfly Valve, Lug Body

2, 21/2, 3, 4, 5, 6, 8, 10, 12

250 (1725) 250 (1725)

a, b, c, d

BFV-N

2, 21/2, 3, 4, 6, 8, 10, 12

a, b, c

BFV-N

Butterfly Valve, Grooved End Butterfly Valve, Grooved End

10

175 (1205) 300 (2070)

a, b

BFV-N

Remarks: a. b. c. d.

21/2, 3, 4, 6, 8

a, b

Aboveground, indoor or outdoor. Available with or without supervisory switches. For mounting between ANSI bolted flanges. For use with ANSI, ISO NP10 and 16 or ``BS.10'' D & E flanges.

Victaulic Company, Box 31, Easton PA 18044

Model Number Product Type Nominal Pipe Size in. / mm Rated Working Pressure,psi (kPa) Remarks

Series 702

Butterfly Valve, Grooved Ends

21/2, 3, 4, 6, 8, 10

175 (1205)

a, b, c

Series 728

Ball Valve, Threaded and Grooved Ends

1, 11/4, 11/2, 2

350 (2415)

a, b, c

Series 705W

Remarks:

Butterfly Valve, Grooved Ends

21/2, 3, 4, 5, 6, 8, 10, 12 also 76.1mm, 165.1mm

300 (2070)

a, b, c

FM Approvals

1-162

September 2007 -- Approval Guide Automatic Sprinkler Systems

a. Available with dual supervisory switches. b. FM Approved for indoor and outdoor service. c. FM Approved for aboveground installations only.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

Model Number Product Type Nominal Pipe Size, mm Rated Working Pressure, psi (kPa) Remarks

FIREKING-DG FIREKING-DW FIREKING-HPG FIREKING-HPW

Remarks:

Butterfly Valve, Grooved Ends Butterfly Valve, Wafer Body Butterfly Valve, Grooved Ends Butterfly Valve, Wafer Body

21/2, 3, 4, 6, 8 21/2, 3, 4, 6, 8 21/2, 2 1/ 2, 3, 4, 6, 8 3, 4, 6, 8

175 (1205) 175 (1205) 300 (2070) 300 (2070)

a, b a, b a, b a, b

a. Available with dual supervisory switches. b. Approved for above ground, indoor and outdoor use only. Model Number Product Type Nominal Pipe Size, mm Rated Working Pressure, psi (kPa) Remarks

FBV-FP

Ball Valve, Threaded Ends

3/ 4,

1, 11/4, 11/2, 2

175 (1205)

a, b, c

a. Available with dual supervisory switches. b. FM Approved for indoor and outdoor use. c. FM Approved for aboveground installations only.

Wouter Witzel EuroValve BV, De Pol 12, 7581 CZ Losser, Netherlands

Model Number Product Type Nominal Pipe Size, mm. Rated Working Pressure, psi (kPa) Remarks

Type EVS Type EVBS Type EVBLS Type EVML Type EVTLS Type EVTLLS Type EVFS Type EVFL Type EVCS

Remarks:

Butterfly Valve, Wafer Body Butterfly Valve, Semi-Lugged Butterfly Valve, Semi-Lugged Butterfly Valve, Mono-Flanged Butterfly Valve, Lugged Butterfly Valve, Lugged Butterfly Valve, Flanged Ends Butterfly Valve, Flanged Ends Butterfly Valve, Semi-Lugged

50, 65, 80, 100, 125, 150, 200, 250, 300 50, 65, 80, 100, 125, 150, 200, 250, 300 50, 65, 80, 100, 125, 150, 200 80, 100, 125, 150, 200, 250, 300 50, 65, 80, 100, 125, 150, 200, 250, 300 50, 65, 80, 100, 125, 150, 200 50, 65, 80, 100, 125, 150, 200, 250, 300 50, 65, 80, 100, 125, 150, 200, 250, 300 50, 65, 80, 100, 125, 150, 200, 250, 300

175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205)

a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c

a. Available with dual supervisory switches. b. FM Approved for indoor and outdoor service. c. FM Approved for aboveground installations only.

INDICATOR POSTS

Indicator posts are controls, extending aboveground, for operating underground sprinkler system valves. As an important feature of their design, a target or indicator, visible through an opening in the post, shows whether the valve is open or shut. The indicator post generally consists of a cast iron barrel, an extension flange which allows the height of the barrel to be regulated, and a wrought iron or mild steel stem which operates the underground valve and simultaneously moves the target. A telescoping union permits turning the stem from a constant height. Indicator posts are available for installation on non-rising stem gate valves. Unless otherwise specified, indicator posts are Approved for use on 4 through 14 in. NPS non-rising stem gate valves with an indicator post flange. In all new fire protection system installations, buried valves must open in a counterclockwise direction regardless of the direction the valves of the public water system open. An exception to this is when all other buried valves in a plant yard open in a clockwise direction. Then all new valves should open clockwise also.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-163

When some buried valves in a system open one way and some the other, all new valves should open counterclockwise. There may be exceptions to this when most valves in an extensive yard system open clockwise. In such cases, FM Global should be consulted regarding the proper direction of opening.

AVK International A/S, Bizonvej 3, Skovby DK-8464, Denmark

Model 34-00 Vertical Ind. Post, Adjustable. Model 34-80 Wall type.

American Darling Valve, Div American Cast Iron Pipe Co (ACIPCO), Box 2727, Birmingham AL 35202

Model IP-71. Fixed barrel.

American Flow Control, Div American Cast Iron Pipe Co (ACIPCO), Box 2727, Birmingham AL 35202

Model A240. Buried type, two-piece adjustable. Model A278. Floor-mounted type. Models A280, A281, A282. Wall type, various mounting configurations. Model A279. Miter gearing wall-mounted assembly. Model A-193-1, -2, -3. Coupling. For use with FM Approved post indicator valves. Model IP-71. Fixed barrel.

Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446

Figure 800W. Wall type.

Clow Canada, Div Canada Pipe Co Ltd, 245 Industrial Dr, Grandview Industrial Park, Saint John, New Brunswick E2R 1A4 Canada

``McAvity'' Cat. Fig. 2945. Nonadjustable Type. Vertical. ``McAvity'' Cat. Fig. 2945A. Adjustable Type. Vertical.

Clow Valve Co, Div McWane Inc, 902 S 2nd St, Oskaloosa IA 52577

Style 2945. Nonadjustable type. Style 2945A. Adjustable type. Style F5765K. Wall type.

Ever Metal Industry Co Ltd, 853 Kwang Fu Rd, Pa Teh City, Tao Yuen Hsien Taiwan ROC

Fig. 800 Fig. 800 W. Wall type.

Fivalco (Qingdao) Co Ltd, 11 Shuangyuan Road Chengyang, Qingdao Shandong, PRC 266111

Model IP888. Vertical type. Model WP999. Wall Post.

Interfit India Ltd, SF No 112 / 3D, Part Mathapur Road, Kaniyur Village, Coimbatore 641 659, India

Model 800. Adjustable barrel. Vertical. Model 810. Wall type.

Kennedy Valve, Div McWane Inc, 1021 E Water St, Elmira NY 14901

Fig. Fig. Fig. Fig. Fig. 641-S. Wall post. 551. Right angle gear for use with Fig. 641-S. 641-14. Pit style post. Floor mounted. 2945. Vertical nonadjustable type post. 2945A. Vertical adjustable type post.

Lichfield Fire & Safety Equipment Co Ltd, 2nd Floor, Suite 4, Saturn Centre, Spring Rd, Ettingshall Rd, Wolverhampton WV4 WTX, United Kingdom

Fig. 800 Fig. 800 W. Wall Type.

Lien Hwa Iron Works Co Ltd, 112 Sec 2 Kuang Fu Rd, Sanchung Taipei Hsien 24113, Taiwan ROC

Fig. 130. Wall type. Fig. 135.

Linx Limited, 184 John Clarke Road, Middletown RI 02802

``United'' Model 5400. Vertical Type. ``United'' Model 5500. Wall Post.

Mueller Canada Inc, 8069 Lawson Rd, Milton, Ontario L9T 5C4, Canada

Model C20806. Vertical adjustable type. Model C20808. Vertical nonadjustable type. Model C20813. Horizontal wall mounted.

Mueller Co, 500 W Eldorado St, Decatur IL 62525

Cat. Fig. A-20806. Vertical adjustable type. Two piece. Cat. Fig. A-20808. Vertical nonadjustable type. One piece. Cat. Fig. A-20813. Horizontal wall mounted.

National Fire Fighting Mfg, FZCO, Box 17014, Jebel Ali Free Zone, Dubai, UAE

Fig. NF-PI800A. Fig. NF-PI800W. Wall Type.

FM Approvals

1-164

September 2007 -- Approval Guide Automatic Sprinkler Systems

National Fittings Inc, 295 East Swedesford Road #280, Wayne PA 19087-1462

Model 800. Adjustable barrel. Vertical. Model 810. Wall type. Figure 800.

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Model RELPI-WALL. Wall Indicator Post. Model RELPI-UP. Indicator Post, Upright, Adjustable.

Shanghai Karon Valves Machinery Co Ltd, No 815 Deyuan Road Nanxiang, Jiading District Shanghai, PRC

Model RBLX Vertical Indicator Post, Adjustable. Model RWHX Wall type.

Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY, United Kingdom

Fig. 800. Fig. 800 W. Wall Type.

Stockham Valves & Fittings, 2129 3rd Ave SE, Cullman AL 35055-5477

Cat. Figs. G-950, G-950-A. Wall type. Cat. Figs. G-951, G-951-A.

Tyco Fire Products, 1467 Elmwood Ave, Cranston RI 02910

Fig. IP-1. Fig. IP-1W. Wall type.

Victaulic Company, Box 31, Easton PA 18044-0031

Series 774 Series 773 Wall Type

The Viking Corporation, 210 N Industrial Park Rd, Hastings MI 49058

FIREKING ­ Fig. No. IP 888. Vertical Type. FIREKING ­ Fig. No. WP 999. Wall Post.

Waterous Co, 125 Hardman Ave So, South Saint Paul MN 55075-1191

No. A240. Buried type, two-piece adjustable. No. A278. Floor-mounted type. No. A-193-1, -2, -3. Coupling. For use with FM Approved post indicator valves.

POST INDICATOR VALVE ASSEMBLIES, Butterfly Type

Post indicator valve assemblies are used to control waterflow to fire protection systems. The assembly consists of a buried, quarter-turn valve and an above grade indicator operator. It is not necessary for the weekly inspector to ``try'' these valves to make sure they are open, thus saving time. Built-in design features provide a dependable ``open'' signal which can be seen at considerable distance. If excessive force is applied to the handle, weakness-joints will break so as to preserve correct orientation between indicator and valve position. Parts are so designed that they can be assembled only one way, always to give correct indication. In case the post is broken off above grade, fail-safe features will keep the valve intact, and it will automatically remain in place or move into the wide open position. All FM Approved valves turn clockwise to shut. Their rubber seats make them easy to operate. Their compactness and light weight permit quick installation in small space. The valves are not subject to sticking or to dropped gates. This device is available only as a factory-assembled unit with true orientation guaranteed by the manufacturer. By means of standard adapters, the valve can be used with all types of pipe joints. When ordering, it is necessary to specify depth to which it is buried. Unless otherwise noted in the listing, this valve assembly has 175 psi (1205 kPa) rated working pressure.

Henry Pratt Co, 401 S Highland Ave, Aurora IL 60506

Post Indicator Valve Assembly. Types FM-4, FM-4A, FM-4B. 6, 8, 10, 12, 14, 16, 18, 20, 24 in. NPS. Types FM-5, FM-5A, FM-5B. 4, 6, 8, 10, 12, 14, 16, 18 in. NPS. Available with wafer (for mount between ANSI bolted flanges), standardized mechanical joint or flanged-end connections. Also available in push-on end connections in 4, 6, 8, 10, 12, 14 and 16 in. NPS.

QUICK OPENING VALVES

Manually operated ball valves are used to control water to small open-head extinguishing systems or in the trim on waterflow alarm valves, dry pipe valves or automatic water control valves. The friction loss through these valves should be considered when they are used in hydraulically calculated extinguishing systems. Consult the manufacturer for details. Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-165

Bugatti Valvosanitaria, Via Iseo, 3-25045 Castegnato (Brescia), Italy

Product Designation Description Nominal Pipe Size, in.

1/ 2, 3/ 4,

Pressure Rating, psi (kPa)

Remarks

221 222 226 227 553 9241 9242 9246 9247 9276 9277 9551

Remarks: a. b. c. d. e. f. g.

Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valves

1, 11/4, 11/2, 2 1

175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205)

f b, f g b, g f a a, b c b, c d, e b, d, e a

1/ 2, 3/ 4,

1/ 2, 3/ 4,

1, 11/4, 11/2, 2 1

1/ 2, 3/ 4,

1/ 2, 3/ 4,

1, 11/4, 11/2, 2 1, 11/4, 11/2, 2 1

1/ 2, 3/ 4,

1/ 2, 3/ 4,

1/ 2, 3/ 4,

1, 11/4, 11/2, 2 1

1/ 2, 3/ 4,

1/ 2, 3/ 4,

1, 11/4, 11/2, 2 1

1/ 2, 3/ 4,

1/ 2, 3/ 4,

1, 11/4, 11/2, 2

Valve supplied with female NPT pipe thread connections. Valve supplied with butterfly handle. Valve supplied with one male NPT and one female NPT pipe thread connection. Valve supplied with tube end connections. Manufacturer's instructions shall be followed closely during installation to prevent damage to the valve seat. Valve supplied with Female ISO 7/1 thread connections. Valve supplied with one male ISO 7/1 and one female ISO 7/1 thread connection.

Compass Asia Inc, 11FL, No 165, Sec 4, Nanjing E Rd, Taipei 105, Taiwan

Product Designation Description Nominal Pipe Size, in.

1/ 2

Max Working Pressure, psi (kPa)

Remarks

Lansdale Int'l 900-02020 Lansdale Int'l 900-02030 Lansdale Int'l 900-02040 Lansdale Int'l 900-02050 Lansdale Int'l 900-02060 Lansdale Int'l 900-02070 Lansdale Int'l 900-02110 Lansdale Int'l 900-02120 Lansdale Int'l 900-02130 Lansdale Int'l 900-02140 Lansdale Int'l 900-02150 Lansdale Int'l 900-02160

Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve

600 (4135) 600 (4135) 600 (4135) 600 (4135) 600 (4135) 600 (4135) 600 (4135) 600 (4135) 600 (4135) 600 (4135) 600 (4135) 600 (4135)

a a a a a a b b b b b b

3/ 4

1 11/4 11/2 2

1/ 2

3/ 4

1 11/4 11/2 2

a. Valve supplied with female NPT pipe thread connections. b. Valve supplied with solder end connections.

FM Approvals

1-166

September 2007 -- Approval Guide Automatic Sprinkler Systems

Conbraco Industries Inc, Box 247, Matthews NC 28105

Product Designation Description Nominal Pipe Size, in.

1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2, 2

Pressure Rating, psi (kPa)

Remarks

94A

Remarks:

Quick Opening Ball Type Valve

175 (1205)

a, d

a. Valve supplied with female NPT threaded end connections. d. Valve supplied with tube end connections.

Crane Supply, 615 Dixon Rd, Toronto, Ontario M9W 1H9, Canada

Product Designation Description Nominal Pipe Size, in.

1/4, 3/8, 1/2, 3/4,

Pressure Rating, psi (kPa)

Remarks

CSC-9302 CSC-9322

Remarks:

Ball Valve Ball Valve

1, 11/4, 11/2, 2

600 (4135) 600 (4135)

a b

1/ 2, 3/ 4,

1, 11/4, 11/2, 2

a. Valve supplied with female NPT pipe thread connections. b. Valve supplied with solder end connections.

Enolgas Bonomi SpA, Via Europa 227, 25062 Concesio (BS), Italy

Product Designation Description Nominal Pipe Size, in.

1/ 2

Pressure Rating, psi (kPa)

Remarks

Topic S1241 Topic S1241 Topic S1241 Topic S1241 Topic S020 ­ Topic S020 ­ Topic S020 ­

Remarks: a. b. f. g. h. i. j.

Quick Opening Ball Type Valve Quick Opening Ball Type Valve Quick Opening Ball Type Valve Quick Opening Ball Type Valve Quick Opening Ball Type Valve Quick Opening Ball Type Valve Quick Opening Ball Type Valve

580 (4000) 1 435 (3000) 363 (2500) 290 (2000) 1 435 (3000) 363 (2500) 290 (2000)

a a a a a, b, f, g, h, i, j a, b, f, g, h, i, j a, b, f, g, h, i, j

3/ 4,

11/4, 11/2 2

3/ 4,

11/4, 11/2 2

Valve supplied with female NPT pipe thread connections. Valve supplied with butterfly handle. Valve supplied with Aluminum lever handle. Valve supplied with fem/fem ISO 7/1 Rp thread connections. Valve supplied with fem/fem ISO 7/1 Rc thread connections. Valve supplied with male/fem ISO 7/1 Rp thread connections. Valve supplied with male/fem ISO 7/1 Rc thread connections.

Fire Protection Products Inc, 6241 Yarrow Drive, Suite A, Carlsbad CA 92011

Product Designation Description Nominal Pipe Size, in.

1/4, 1/2, 3/4,

Pressure Rating psi (kPa)

Remarks

TrimFit TrimFit

Remarks:

Quick Opening Ball Type Valve Quick Opening Ball Type Valve

1, 11/4, 11/2 2

600 (4140) 300 (2070)

a a

a. Valves supplied with female NPT threaded end connections.

Fortune Manufacturing Company Ltd, 11F No 222 Sec 5, Nanking E Rd, Taipei, Taiwan ROC

Product Designation Description Nominal Pipe Size, in.

1/4, 3/8, 1/2, 3/4,

Pressure Rating, psi (kPa)

Remarks

220-TF

Ball Valve

1, 11/4, 11/2, 2

600 (4135)

a

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-167

Product Designation

Description

Nominal Pipe Size, in.

1/ 2, 3/ 4,

Pressure Rating, psi (kPa)

Remarks

220-CC FBV-3C FBVS-3C

Remarks:

Ball Valve Ball Valve Ball Valve

1, 11/4, 11/2, 2 1, 11/4, 11/2, 2

600 (4135) 600 (4135) 600 (4135)

b a b

1/4, 3/8, 1/2, 3/4,

1/ 2, 3/ 4,

1, 11/4, 11/2, 2

a. Valve supplied with female NPT pipe thread connections b. Valve supplied with solder end connections.

Fratelli Pettinaroli SpA, Via Pianelli 38, 28017 San Maurizio d'Opaglio Novara, Italy

Model T-100N-E. 1/4 through 2 in.; 1/4 through 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working pressure. Female pipe thread end connections, brass valve stem and ball. Model T-100-C; 1/2 through 2 in.; 1/2 through 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working pressure. Female pipe thread end connections. Model T-100-SSN-E. 1/2 through 2 in.; 1/4 through 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working pressure. Female pipe thread end connections, 316 stainless steel valve stem and ball. Model S-100N-E. 1/2 through 2 in.; 1/2, 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working pressure. Tube by tube end connections, brass valve stem and ball. Model S-100-C. 1/2 through 2 in.; 1/2, 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working pressure. Tube by tube end connections, brass valve stem and ball. All above 5 Models are available with: a) steel handle - 90° to open or close. b) aluminum tee handle - 90° to open or close. c) plastic ``top ball'' handle with one full turn to open or close. Model T-100. 1/4 through 1 in.; 1/4 through 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 in., 500 psi (3450 kPa) rated working pressure. Female pipe thread end connections, brass valve stem and ball. Model T-100-C. 1/2 through 2 in.; 1/2 through 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working pressure. Female pipe thread end connections. Model T-100-SS. 1/2 through 1 in.; 1/4 through 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 in., 500 psi (3450 kPa) rated working pressure. Female pipe thread end connections, 316 stainless steel valve stem and ball. Model S-100. 1/2 through 1 in.; 1/2, 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 in., 500 psi (3450 kPa) rated working pressure. Tube by tube end connections, brass valve stem and ball. Model S-100-C. 1/2 through 2 in.; 1/2, 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working pressure. Tube by tube end connections, brass valve stem and ball. All above with aluminum tee handle - 90° to open or close. Model T-100. 1/4 through 2 in.; 1/4 through 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working pressure. Female pipe thread end connections, brass valve stem and ball. Model T-100-C. 1/2 through 2 in.; 1/2 through 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working pressure. Female pipe thread end connections. Model T-100-SS. 1/2 through 2 in.; 1/4 through 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working pressure. Female pipe thread end connections, 316 stainless steel valve stem and ball. Model S-100. 1/2 through 2 in.; 1/2, 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working pressure. Tube by tube end connections, brass valve stem and ball. Model S-100-C. 1/2 through 2 in.; 1/2, 3/4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working pressure. Tube by tube end connections, brass valve stem and ball. All above with plastic ``top ball'' handle with one full turn to open or close.

Fu San Machinery Co Ltd, 22 Lane 89, Sec 4 Chang-Mei Road, Ho-Mei Town Chang-Hua, Taiwan ROC

Fig. F1361FP. Ball type valves. 1/2, 3/4, 1, 11/4, 11/2, 2 in. Rated working pressure 600 psi (4130 kPa).

Fu San Valve (Suzhou) Limited, No. 1, Cheng Hu Zhong Rd, Wuzhong Economic Development Zone, Suzhou City, Jiangsu Province, China

Product Designation Description Nominal Pipe Size in.

1/2, 3/4,

Pressure Rating psi (kPa)

Remarks

Model F1361FP

Remarks:

Quick Opening Ball Type Valve

1, 11/4, 11/2 and 2

600 (4130)

a

a. Valves are available with threads to ANSI/ASME B1.20.1 and BS21 Pipe Thread Standards.

A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d'Opaglio, Italy

Model Model Model Model Model Model Model R250D. 1/2, 3/4 in., 600 psi (4135 kPa) rated working pressure; 1 through 2 in., 500 psi (3445 kPa) rated working pressure. R850. 1/2 through 2 in., 600 psi (4135 kPa) rated working pressure. NPT end connections. R858. 1/2 through 2 in., 600 psi (4135 kPa) rated working pressure. Solder joint end connections. R910. 1/2 through 2 in., 600 psi (4135 kPa) rated working pressure. NPT end connections. R918. 1/2 through 2 in., 600 psi (4135 kPa) rated working pressure. Solder joint end connections. R850PR. 1/2 through 2 in., 600 psi (4135 kPa) rated working pressure. NPT end connections. R858PR. 1/2 through 2 in., 600 psi (4135 kPa) rated working pressure. Solder joint end connections.

Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Series 17*. 1/4 through 2 in. 600 psi (4140 kPa) rated working pressure.

*Available with NPT end threaded or ISO 7/1 end threaded.

FM Approvals

1-168

September 2007 -- Approval Guide Automatic Sprinkler Systems

Hammond Valve, 16550 West Stratton Drive, New Berlin WI 53151

Product Designation Description Nominal Pipe Size in.

1/2, 3/4, 1, 11/4, 11/2, 2

Pressure Rating psi (kPa)

Remarks

Model 8901

Remarks:

Quick Opening Ball Type Valve

600 (4135)

a

a. Valves supplied with female NPT threaded end connections.

IMT Armaturen AG, Sonnenstrasse 8, CH-9434 AU/SG, Switzerland

Figure 592NTP, sizes 1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2 and 2 in. Female pipe thread end connections. 250 psi (1725 kPa) rated working pressure. Figure 592SP, sizes 1/2, 3/4, 1, 11/4, 11/2 and 2 in. Solder joint end connections. 250 psi (1725 kPa) rated working pressure. Figure 593NT, sizes 1/2, 3/4, 1, 11/4, 11/2 and 2 in. Female pipe thread end connections. 250 psi (1725 kPa) rated working pressure. Figure 593S, sizes 1/2, 3/4, 1, 11/4, 11/2 and 2 in. Solder joint end connections. 250 psi (1725 kPa) rated working pressure.

IVR Valvole a sfera spa, Via Brughiera III n°1, Loc. Piano Rosa, 28010 Boca (NO), Italy

Product Designation Description Nominal Pipe Size in.

1/2, 3/4,

Pressure Rating, psi (kPa)

Remarks

Model 45 FBV-3

Remarks:

Quick Opening Ball Type Valve

1, 11/4, 11/2, 2

600 (4140)

a

a. Female pipe thread end connections with Standard Steel Handle ­ 90° to open or close.

Jomar International Ltd, 7243 Miller Drive, Warren MI 48092

Product Designation Description Nominal Pipe Size in.

1/2, 3/4

Pressure Rating, psi (kPa)

Remarks

S-100 S-100 S-100 S-100 S-100 S-100 S-100-C S-100-C S-100-C S-100-C T-100 T-100 T-100-C T-100-C T-100-SS T-100-SS T-100 T-100 T-100-C

Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve

600 (4140) 500 (3450) 6 00 (4140) 500 (3450) 600 (4140) 500 (3450) 600 (4140) 500 (3450) 600 (4140) 500 (3450) 600 (4140) 500 (3450) 600 (4140) 500 (3450) 600 (4140) 500 (3450) 600 (4140) 500 (3450) 600 (4140)

b, e, g b, e, g b, c, e b, c, e b, d, e b, d, e b, c, e b, c, e b, d, e b, d, e b, f, g b, f, g f, g f, g f, g, h f, g, h b, c, f b, c, f c, f

1, 11/4, 11/2, 2

1/ 2,

¾

1

1/2, 3/4

1, 11/2, 11/2, 2

1/2, 3/4

1, 11/4, 11/2, 2

1/2, 3/4

1, 11/4, 11/2, 2 ¼, 3/4 1, 11/4, 11/2, 2

1/2, 3/4

1, 11/4, 11/2, 2 ¼, 1/2, 3/4 1, 11/4, 11/2, 2 ¼, 1/2, 3/4 1

1/2, 3/4

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-169

Product Designation

Description

Nominal Pipe Size in.

Pressure Rating, psi (kPa)

Remarks

T-100-C T-100-SS T-100-SS T-100 T-100 T-100-C T-100-C T-100-SS T-100-SS JF-100T

Remarks: a. b. c. d. e. f. g. h.

Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve Ball Valve

1, 11/4, 11/2, 2 ¼, 1/2, 3/4 1 ¼, 1/2, 3/4 1, 11/4, 11/2, 2

1/2, 3/4

500 (3450) 600 (4140) 500 (3450) 600 (4140) 500 (3450) 600 (4140) 500 (3450) 600 (4140) 500 (3450) 600 (4140)

c, f c, f, h c, f, h b, d, f b, d, f d, f d, f d, f, h d, f, h a

1, 11/4, 11/2, 2 ¼, 1/2, 3/4 1, 11/4, 11/2, 2

1/4, 3/8, 1/2, 3/4,

1, 11/4, 11/2, 2

Valves supplied with female NPT threaded end connections and BS21 Pipe Thread Standards. Brass valve stem and ball. All above with Aluminum Tee Handle ­ 90° to open or close. All above with Plastic ``Slo-Ball'' Handle with one full turn to open or close. Tube by tube end connections. Female pipe thread end connections. All above with Standard Steel Handle ­ 90° to open or close. 316 stainless steel valve stem and ball.

Karl DUNGS Inc, 524 Apollo Dr, Suite 10-30, Lino Lakes MN 55014

Model KH01/6, sizes 1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2 and 2 in. Female pipe thread end connections. 250 psi (1725 kPa) rated working pressure.

Kitz Corporation, 1-10-1 Nakase, Mihama-ku Chiba 261, Japan

Figure AKSZA, Code #58. 1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2, and 2 in., 175 psi (1205 kPa) rated working pressure. Female pipe thread end connections. Figure AKSZAW, Code #58W. 1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2, and 2 in., 175 psi (1205 kPa) rated working pressure. Female pipe thread end connections and wing handle. Figure CSZA, Code #59. 1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2, and 2 in., 175 psi (1205 kPa) rated working pressure. Solder joint end connections. Figure CSZAW, Code #59W. 1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2, and 2 in., 175 psi (1205 kPa) rated working pressure. Solder joint end connections, and wing handle. Figure AKSZAN, Code #58N (Keepalloy). 1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2, and 2 in., 175 psi (1205 kPa) rated working pressure. Female pipe thread end connections. Figure AKSZANW, Code #58NW (Keepalloy). 1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2, and 2 in., 175 psi (1205 kPa) rated working pressure. Female pipe thread end connections, and wing handle. Figure CSZAN, Code #59N (Keepalloy). 1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2, and 2 in., 175 psi (1205 kPa) rated working pressure. Solder joint end connections. Figure CSZANW, Code #59NW (Keepalloy). 1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2, and 2 in., 175 psi (1205 kPa) rated working pressure. Solder joint end connections, and wing handle. Figure No. 68. 1/4, 3/8, 1/2, 3/4, 1 and 11/4 in., 600 psi (4135 kPa) rated working pressure; 11/2 and 2 in., 500 psi (3445 kPa) rated working pressure. Female pipe thread end connections. Figure No. 69. 3/8, 1/2, 3/4, 1 and 11/4 in., 600 psi (4135 kPa) rated working pressure; 11/2 and 2 in., 500 psi (3445 kPa) rated working pressure. Solder joint end connections.

Legend Valve & Fitting, 51245 Filomena Drive, Shelby Township MI 48315

Product Designation Description Nominal Pipe Size in.

1/2, 3/4,

Pressure Rating, psi (kPa)

Remarks

T-1001 T-1004

Ball Valve Ball Valve

1, 11/4, 11/2, 2 1, 11/4, 11/2, 2

600 (4135) 600 (4135)

a a

1/2, 3/4,

a = Valve supplied with female NPT pipe thread connections.

FM Approvals

1-170

September 2007 -- Approval Guide Automatic Sprinkler Systems

Milwaukee Valve Company Inc, 16550 West Stratton Drive, New Berlin WI 53151

Product Designation Nominal Pipe Size, in.

1/2, 3/4, 1, 11/4, 11/2, 2 1/2, 3/4,

Description

Pressure Rating, psi (kPa)

Remarks

Model BB2-FP Model BA-475-B

Quick Opening Butterfly Type Valve Quick Opening Ball Type Valve

175 (1205) 600 (4135)

a a

1, 11/4, 11/2, 2

a = Valves supplied with female NPT threaded end connections.

NIBCO Inc, 1516 Middlebury St, Elkhart IN 46515

Product Designation Description Nominal Pipe Size, in.

1/4, 3/8, 1/2, 3/4 1, 11/4, 11/2, 2 1/4, 3/8, 1/2, 3/4 1, 11/4, 11/2, 2 1/4, 3/8, 1/2, 3/4,

Pressure Rating, psi (kPa)

Remarks

T-FP600 T-FP600N KT-585-70-UL KT-580-70-UL

Remarks:

Quick Opening Ball Type Valve Quick Opening Ball Type Valve Quick Opening Ball Type Valve Quick Opening Ball Type Valve

300 (2070) 300 (2070) 300 (2070) 300 (2070)

a, b a, b a, b a, b

1

11/4, 11/2, 2

a. Valves supplied with female NPT threaded end connections. b. Valves are available with threads to ANSI/ASME B1.20.1 and BS21 Pipe Thread Standards.

NIGO Industrial Co Ltd, No 9 Lane 93, Chang Lu Road, Changhua, Taiwan R.O.C.

Product Designation Description Nominal Pipe Size, in.

1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2, 2 1/4

Pressure Rating, psi (kPa)

Remarks

100SSW 101SSW 102SSW 106SSW

Remarks: a. b. c. d. e.

Ball Valve Ball Valve Ball Valve Ball Valve

300 (2068) 300 (2068) 300 (2068) 300 (2068)

a b c d, e

, 3/8, 1/2, 3/4, 1, 11/4, 11/2, 2 , 3/8, 1/2, 3/4, 1, 11/4, 11/2, 2 , 3/8, 1/2, 3/4, 1, 11/4, 11/2, 2

1/4

1/4

Valve supplied with female NPT pipe thread connections. Valve supplied with one male NPT and one female NPT pipe thread connection. Valve supplied with male NPT pipe thread connections. Valve supplied with tube end connections. Manufacturer's instructions shall be followed closely during installation to prevent damage to the valve seat.

Ningbo Zhiqing Industrial Co Ltd, No. 12 Wai Huan (W.) Road, Yuelong Street, Ninghai County, Ningbo, 315600, China

Product Designation Description Nominal Pipe Size, in.

1/4, 3/8, 1/2, 3/4,

Pressure Rating, psi (kPa)

Remarks

Q11F-600TB Q61F-600TL Q61F-600TL2

Ball Valve Ball Valve Ball Valve

1, 11/4, 11/2, 2

600 (4135) 600 (4135) 600 (4135)

a b b

1/ 2, 3/ 4,

1, 11/4, 11/2, 2 1, 11/4, 11/2, 2

1/ 2, 3/ 4,

a. Valve supplied with female NPT pipe thread connections. b. Valve supplied with solder end connections.

Potter-Roemer Inc, 15125 Proctor Avenue, Box 3527, City of Industry CA 91744-0527

Models 4405; 4407. 1/2, 3/4 in.; 600 psi (4135 kPa) rated working pressure. Models 4410, 4412, 4415, 4420. 1, 11/4, 11/2, 2 in.; 500 psi (3445 kPa) rated working pressure.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-171

Red-White Valve Corp, 20600 Regency Lane, Lake Forest CA 92630

Product Designation Description Nominal Pipe Size, in.

1/ 2, 3/ 4,

Pressure Rating, psi (kPa)

Remarks

5044A 5044F 5544

Ball Valve Ball Valve Ball Valve

1, 11/4, 11/2, 2 1, 11/4, 11/2, 2 1, 11/4, 11/2, 2

600 (4135) 600 (4135) 600 (4135)

a a a

1/ 2, 3/ 4,

1/ 2, 3/ 4,

a. Valve supplied with female NPT pipe thread connections.

Rubinetterie Bresciane Bonomi SpA, Via Industralie 30, Box 31, 25065 Lumezzane SS Brescia, Italy

Product Designation Description Nominal Pipe Size, in.

1/4, 3/8, 1/2, 3/4,

Pressure Rating, psi (kPa)

Remarks

171N 171O 600002 16 17 1970 1972

Remarks:

Ball Valve, Threaded Ends Ball Valve, Threaded Ends Butterfly Valve, Threaded Ends Ball Valve, Threaded Ends Ball Valve, Threaded Ends Ball Valve, Press x Press Ball Valve Press x Thread

1, 11/4, 11/2, 2 1, 11/4, 11/2, 2

600 (4140) 600 (4140) 200 (1380) 400 (2760) 600 (4140) 200 (1380) 200 (1380)

a b a, b a a, b c a, b, c

1/4, 3/8, 1/2, 3/4,

1/ 2, 3/ 4,

1, 11/4, 11/2, 2 1, 11/4, 11/2, 2 1, 11/4, 11/2, 2

1/ 2, 3/ 4,

1/4, 3/8, 1/2, 3/4,

1/ 2, 3/ 4,

1, 11/4, 11/2, 2 1, 11/4, 11/2, 2

1/ 2, 3/ 4,

a. Approved when supplied with female NPT end connections. b. Approved when supplied with ISO 7/1 female threaded ends. c. To be installed using Ridgid pressing tool Model CT-400 only

Rubinetterie Italiane Valvole, Via Dell Acacie 8-ZI, D4 28075 Grignasco NO, Italy

Series 4201. Sizes 1/2, 3/4, 1, 11/4, 11/2 in. NPS. 600 psi (4140 kPa) maximum rated working pressure. Size 2 in. NPS, 400 psi (2760 kPa) maximum rated working pressure. Female NPT end connections.

Rubinetterie Utensilerie Bonomi, Via Padana Superiore 27/29, Ciliverghe Di Mazzano, Brescia 25080, Italy

Model S.92. 1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2 and 2 in. 400 psi (2760 kPa) rated working pressure. Brass and chrome-plated finishes. NPT M×F and F×F end threaded. Model S.95. 1/4, 3/8, 1/2, 3/4, 1, 11/4, 11/2 and 2 in. 400 psi (2760 kPa) rated working pressure. Brass and chrome-plated finishes. NPT F×F end threaded.

Toyo Valve Co Ltd, TT-2 Bldg, 8-1, 3-Chome, Nihonbashi-Ningyocho, Chuo-Ku, Tokyo 103-0013 Japan

Product Designation Description Nominal Pipe Size, in.

1/4, 3/8, 1/2, 3/4,

Pressure Rating, psi (kPa)

Remarks

5044A 5044W 5049A 5049W

Ball Valve Ball Valve Ball Valve Ball Valve

1, 11/4, 11/2, 2 1, 11/4, 11/2, 2 1, 11/4, 11/2, 2 1, 11/4, 11/2, 2

175 (1205) 175 (1205) 175 (1205) 175 (1205)

a a, c b b, c

1/4, 3/8, 1/2, 3/4,

1/4, 3/8, 1/2, 3/4,

1/4, 3/8, 1/2, 3/4,

a. Valve supplied with female NPT pipe thread connections. b. Valve supplied with solder end connections. c. Valve supplied with wing handle.

VIR Valvoindustria Ing Rizzio SpA, Via Circonvallazione 10, 13018 Valduggia, Italy

Product Designation Description Nominal Pipe Size, in.

1/ 2, 3/ 4,

Pressure Rating, psi (kPa)

Remarks

340T 350T

Ball Valve Ball Valve

1, 11/4, 11/2, 2 1, 11/4, 11/2, 2

600 (4135) 600 (4135)

a a

1/4, 3/8, 1/2, 3/4,

FM Approvals

1-172

September 2007 -- Approval Guide Automatic Sprinkler Systems

a. Valve supplied with female NPT pipe thread connections.

Victaulic Company, Box 31, Easton PA 18044

Style 722. 1/2, 3/4 in., 600 psi (4135 kPa) rated working pressure; 1 through 2 in., 500 psi (3445 kPa) rated working pressure.

Watts Regulator Co, 815 Chestnut St, North Andover MA 01845

Product Designation Description Nominal Pipe Size, in.

1/4, 3/8, 1/2, 3/4,

Pressure Rating, psi (kPa)

Remarks

FBV-3C FBVS-3C

Remarks:

Ball Valve Ball Valve

1, 11/4, 11/2, 2

600 (4135) 600 (4135)

a b

1/ 2, 3/ 4,

1, 11/4, 11/2, 2

a. Valve supplied with female NPT pipe thread connections. b. Valve supplied with solder end connections.

SINGLE CHECK VALVES

Single check valves are used in fire protection systems to allow waterflow in one direction only. Typical applications are at connections between public water supplies and private fire service systems, at the discharge from fire pumps, at gravity tank connections and at fire service pumper connections. Valves identified in the listing by a single asterisk (*) have side covers; valves identified by a double asterisk (**) have no removable covers; others have top covers. Clearance must be provided for side-cover valves to permit clapper removal. Valves without covers must be removed from the system for clapper replacement or repair. Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.

Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801

Model No. Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

78FP

Remarks:

Swing Check Valve, Cut Groove

2, 21/2, 3, 4, 5, 6, 8, 10 in. 76.1, 139.7, 165.1 mm

300 (2070)

a, b

a. For use in horizontal and vertical installations. b. Resilient seat.

AnvilStar LLC, Division of Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801

Model No. Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

78FP

Remarks:

Swing Check Valve, Cut Groove

2, 21/2, 3, 4, 5, 6, 8, 10 in. 76.1, 139.7, 165.1 mm

300 (2070)

a, b

a. For use in horizontal and vertical installations. b. Resilient seat.

Ban Chang Hardware Co Ltd, No 168, Lane 432, Sec 3, Lu Ho Road, LuKang ChangHua Hsien 505, Taiwan

Product Designation Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

B120G

a. Supplied with grooved inlet and outlet.

4

250 (1725)

a

Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Model B

a. Resilient seat.

Swing Check Valve, Cut Groove

4

250 (1725)

a

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-173

Clow Valve Co, Div McWane Inc, 902 S 2nd St, Oskaloosa IA 52577

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Figure 126 Figure 126A Figure 426 Figure 706

a. Metal Seat. b. Resilient Seat.

Swing Check Valve, Flanged Ends Swing Check Valve, Flanged Ends Swing Check Valve, Grooved Ends Swing Check Valve, Wafer Type

21/2, 3, 4, 5, 6, 8, 10, 12 21/2, 3, 4, 5, 6, 8, 10, 12 21/2, 3, 4, 6, 8 4, 6, 8

175 (1207) 175 (1207) 250 (1725) 300 (2070)

a b b b

Crane Valves, 1000 No. 12th Ave, Washington IA 52353

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Model 375

a. Metal Seat.

Swing Check Valve, Flanged Ends

3, 4, 6, 8,10

175 (1205)

a

Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

``Automatic'' Model 352 ``Automatic'' Model 202

a. Resilient Seat. b. Available with riser trim package.

Swing Check Valve, Flanged Ends Swing Check Valve, Grooved Ends

4, 6 4

175 (1207) 300 (2070)

a a, b

Ever Metal Industry Co Ltd, 853 Kwang Fu Rd, Pa Teh City, Tao Yuen Hsien, Taiwan ROC

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

763UM 763UR 453UF 453UG

Remarks a. Metal seat. b. Resilient seat. c. No removable covers.

Swing Check Valve Flanged Ends Swing Check Valve Flanged Ends Dual Plate Check Valve Flanged Ends Dual Plate Check Valve Grooved Ends

3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8 3, 4, 6, 8

200 (1380) 200 (1380) 250 (1725) 200 (1380)

a b b, c b, c

Fire Protection Products Inc, 6241 Yarrow Drive, Suite A, Carlsbad CA 92009-1541

Product Designation Description Nominal Pipe Size, in. Pressure Rating, psi (kPa) Remarks

Trim-Fit

Remarks b. Resilient Seat. c. No removable covers.

Swing Check Valve, Grooved Ends

2, 21/2, 3, 4

300 (2070)

b, c

Fivalco Inc, 2221 E Winston Rd, Unit J, Anaheim CA 92806

Product Designation Description Nominal Pipe Size in./ mm Max Working Pressure, psi (kPa) Remarks

Firecheck DG

a. Resilient Seat.

Swing Check Valve, Grooved Ends

2, 21/2, 3, 4, 6, 8 76.1mm, 165.1 mm

300 (2070)

a

FM Approvals

1-174

September 2007 -- Approval Guide Automatic Sprinkler Systems

A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d'Opaglio, Italy

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Model A140G**

Remarks a. Resilient seat.

Swing Check Valve, Grooved Ends

4

250 (1725)

a

Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Model CV-1, CV-1S Model CVA** Model RCV**

Remarks

Swing Check Valve, Grooved Ends Swing Check Valve, Grooved Ends Swing Check Valve, Grooved Ends

4 21/2, 3 2, 21/2, 3, 4, 6

175 (1205) 250 (1725) 300 (2070)

a a a

a. For use in horizontal and vertical installations.

Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Product Designation Description Nominal Pipe Size in./ mm Pressure Rating, psi (kPa) Remarks

Model F517

Swing Check Valve, Grooved Ends Swing Check Valve, Grooved Ends Swing Check Valve, Grooved Ends Swing Check Valve, Grooved Ends Swing Check Valve, Flanged Ends Swing Check Valve, Grooved Ends

2, 21/2, 3, 4, 6, 8

250 (1725) 250 (1725) 250 (1725) 175 (1205) 175 (1205) 175 (1205)

a

Model 7800FP

2, 21/2, 3, 4, 5, 6, 8, 10, 12 76.1, 165.1 mm 2 1/ 2

a

Model F52

a

Model F52

4, 6

a

Model F520

4, 6, 8

a

Model F5201

a. Resilient Seat.

4, 6, 8

a

Jenkins Valve, 1000 N. 12th Ave, Washington IA 52353

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Model 477J

Remarks a. Metal Seat.

Swing Check Valve, Flanged Ends

3, 4, 6, 8, 10

175 (1205)

a

Kennedy Valve, Div McWane Inc, 1021 E Water St, Elmira NY 14901

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Figure 126 Figure 126A Figure 426 Figure 706

a. Metal Seat.

Swing Check Valve, Flanged Ends Swing Check Valve, Flanged Ends Swing Check Valve, Grooved Ends Swing Check Valve, Wafer Type

21/2, 3, 4, 5, 6, 8, 10, 12 2 1/ 2, 3, 4, 5, 6, 8, 10, 12 21/2, 3, 4, 6, 8

4, 6, 8

175 (1207) 175 (1207) 250 (1725) 300 (2070)

a b b b

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-175

b. Resilient seat.

Lichfield Fire & Safety Equipment Co Ltd, 2nd Floor, Suite 4, Saturn Centre, Spring Rd, Ettingshall Rd, Wolverhampton WV4 WTX, United Kingdom

Model Model Model Model 763UM. 3 through 12 in. NPS, flanged swing check with bronze seat. 200 psi (1380 kPa) rated working pressure. 763UR. 3 through 12 in. NPS, flanged swing check with rubber faced clapper. 200 psi (1380 kPa) rated working pressure. 453UF**. 3, 4 and 6 in. NPS, flanged dual plate, rubber seat. 250 psi (1725 kPa) rated working pressure. 453UG**. 3, 4, 6 and 8 in. NPS, grooved end dual plate, rubber seat. 200 psi (1380 kPa) rated working pressure.

**These valves have no removable covers.

Lien Hwa Iron Works Co Ltd, 112 Section 2 Kuang Fu Rd, Sanchung, Taipei Hsien 24113, Taiwan ROC

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Figure 451B

Remarks a. Resilient Seat.

Swing Check Valve, Flanged Ends

2, 21/2, 3, 4, 5, 6, 8, 10, 12

175 (1205)

a

Matco Products Inc, Rte 22, Box 27, Brewster NY 10509

Model 120U. 21/2 through 10 in. NPS Flanged. Rubber-faced. Furnished with single clapper-hinge-pin plug. Clearance must be provided to permit hinge pin removal.

Milwaukee Valve Company Inc, 16550 West Stratton Drive, New Berlin WI 53151

Series 1400. 2 through 10 in. NPS. Wafer style. Series 1800. 21/2 through 12 in. NPS. Globe style-flanged. Series 8800. 2 through 12 in. NPS. Oval disc-wafer style.

Mueller Co, 500 W Eldorado St, Decatur IL 62525

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Figure A-2120-6 Figure A-2122-6

a. Metal Seat b. Resilient Seat

Swing Check Valve, Flanged Ends Swing Check Valve, Flanged Ends

2, 21/2, 3, 4, 5, 6, 8, 10, 12, 14 2, 21/2, 3, 4, 5, 6, 8, 10, 12, 14

175 (1207) 175 (1207)

a b

NIBCO Inc, 1516 Middlebury St, Elkhart IN 46515

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

F-908-W W-910-B F-910-B KG-900-W KW-900-W KW-900-W

Remarks a. Metal Seat b. Resilient Seat.

Swing Check Valve, Flanged Ends Swing Check Valve, Wafer Type Swing Check Valve, Flanged Ends Swing Check Valve Dual Disc-Grooved Ends Swing Check Valve, Dual Disc-Wafer Type Swing Check Valve, Dual Disc-Wafer Type

4, 6, 8, 12 2, 21/2, 3, 4, 5, 6, 8, 10

21/2, 3, 4, 5, 6, 8, 10, 12 21/2, 3, 4, 5, 6, 8, 10, 12 2 1/ 2, 3, 4, 5, 6, 8, 10, 12 14, 16

175 (1205) 200 (1380) 200 (1380) 250 (1725) 250 (1725) 200 (1380)

a a a a a b

National Fire Fighting Mfg, FZCO, Box 17014, Jebel Ali Free Zone, Dubai, UAE

Model Number Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

NF-NRV-250HG NF-NRV-250HG NF-NRV-250H NF-NRV-200UF

Remarks:

Swing Check Valve, Flanged End Connections Swing Check Valve, Flanged End Connections Swing Check Valve, Flanged End Connections Swing Check Valve, Grooved End Connections

3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8 3, 4, 6, 8

200 (1380) 200 (1380) 250 (1725) 200 (1380)

a b b, c, d b, c, d

FM Approvals

1-176

September 2007 -- Approval Guide Automatic Sprinkler Systems

a. b. c. d.

Bronze seat. Rubber seat. Dual Plate. No removable covers.

Rapidrop Limited, Manasty Road, Peterborough PE2 6UP, United Kingdom

Product Designation Nominal Pipe Size, in. Max Working Pressure, psi (kPa)

Description

Remarks

FCG 300

a. Resilient Seat.

Swing Check Valve, Grooved Ends

2, 21/2, 3, 4, 6, 8

300 (2070)

a

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Product Designation Nominal Pipe Size in./ mm Max Working Pressure, psi (kPa)

Description

Remarks

Model CVE Model DW Model G

Remarks

Swing Check Valve Grooved Ends Swing Check Valve Wafer Type Swing Check Valve Grooved Ends

4, 6, 8 (100, 150, 200) 4 21/2, 3, 4, 6

300 (2070) 250 (1725) 250 (1725)

a a, b

a. Resilient O-Ring Seat. No removable cover. b. Available with riser check valve trim package.

Ritepro Corporation, 12200 Albert Hudon, Montreal Quebec, H1G 3K7, Canada

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Model 212 Model 312

a. Resilient Seat.

Swing Check Valve, Wafer Type Swing Check Valve, Wafer Type

2, 21/2, 3, 4, 5, 6, 8, 10, 12 2, 21/2, 3, 4, 5, 6, 8, 10, 12

250 (1724) 250 (1724)

a a

Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY, United Kingdom

Model Number Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

763UM 763UR 453UF 453UG

Remarks: a. b. c. d. Bronze seat. Rubber seat. Dual Plate. No removable covers.

Swing Check Valve, Flanged End Connections Swing Check Valve, Flanged End Connections Swing Check Valve, Flanged End Connections Swing Check Valve, Grooved End Connections

3, 4, 6, 8, 10, 12 3, 4, 6, 8, 10, 12 3, 4, 6, 8 3, 4, 6, 8

200 (1380) 200 (1380) 250 (1725) 200 (1380)

a b b, c, d b, c, d

Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

453U RCV

Remarks a. Resilient Seat. b. No removable covers.

Dual Plate Check Valve Grooved Ends Swing Check Valve Grooved ends

3, 4, 6, 8 21/2, 3, 4, 6

200 (1380) 300 (2070)

a, b a

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-177

Siam Cast Iron Works Co Ltd, Samutsakorn Industrial Estate, Soi 7, 1/12 Moo 2, Rama II Rd, Tahsai, Muang, Samutsakorn 74000, Thailand

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

120U 120U 120U 120U

Remarks

Swing Check Valve Flanged ends Swing Check Valve Flanged ends Swing Check Valve Grooved ends Swing Check Valve Grooved ends

21/2, 3, 4, 6, 8, 10 12 21/2, 3, 4, 6, 8, 10 12

200 (1380) 175 (1205) 200 (1380) 175 (1205)

a, b a, b a, b a, b

c. Resilient Seat. d. Clearance must be provided to permit hinge pin removal.

Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154

Product Designation Description Nominal Pipe Size in./ mm Max Working Pressure, psi (kPa) Remarks

Model S380

Remarks a. Resilient Seat.

Riser Check Valve, Grooved Ends

2, 21/2, 3, 4, 6, 8 76.1, 165.1 mm

250 (1725)

a

Stockham Valve Co, 1000 N. 12th Ave, Washington IA 52353

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Model G-939

Remarks a. Metal Seat.

Swing Check Valve, Flanged Ends

3, 4, 6, 8, 10

175 (1205)

a

Tong Kwang Valve Industrial Co Ltd, No. 1-1 Ming Chuan Rd, Ming-Sheng Li, Tansui, Taipei Hsien, Taiwan ROC

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Model 065U

Remarks a. Resilient Seat.

Swing Check Valve, Flanged Ends

3, 4, 6, 8

175 (1205)

a

Tyco Fire Products, 3 Tyco Park, Exeter NH 03833

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Model CV-2

Model CV-2 Figure CV-1F Figure CV-1FR

Remarks

Swing Check Valve Flanged or Grooved End Connections Swing Check Valve, Grooved Ends Swing Check Valve, Grooved Ends Riser Check Valve, Grooved Ends

4, 6, 8 21/2 2 1/ 2, 3, 4, 5, 6, 8, 10 3, 4, 5, 6, 8

175 (1207) 250 (1725) 300 (2070) 300 (2070)

a

a a, b a, b

2 1/ 2,

a. Resilient Seat. b. For use in horizontal and vertical installations.

Val-Matic Valve & Mfg Corp, 905 Riverside Dr, Elmhurst IL 60126

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Series 1400

Swing Check Valve

2, 21/2, 3, 4, 5, 6, 8, 10

200 (1380)

a, b

FM Approvals

1-178

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Description

Nominal Pipe Size, in.

Max Working Pressure, psi (kPa)

Remarks

Series 1800 Series 8800G Series 8800W Series 8800

Swing Check Valve, Flanged Ends Swing Check Valve, Grooved Ends Swing Check Valve, Wafer Style Swing Check Valve, Wafer Style

21/2, 3, 4, 5, 6, 8, 10, 12 21/2, 3, 4, 5, 6, 8, 10, 12 21/2, 3, 4, 5, 6, 8, 10, 12 14, 16

200 (1380) 250 (1725) 250 (1725) 200 (1380)

a, b b, c b, c b, c

a. Available with resilient or metal seat. b. No removable covers. c. Resilient Seat.

Venus Fire Protection Ltd, 4105 Portland Blvd, Sherbrooke, Quebec J1L 1X9, Canada

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Astra Model CV Astra Model CVB-1 Astra Riser Model CVB-1 Astra Model CVB Astra Riser Model CVB Astra Model CVA Astra Riser Model CVA

a. Resilient Seat.

Swing Check Valve, Wafer Type Swing Check Valve, Grooved Ends Swing Check Valve, Grooved Ends Swing Check Valve, Grooved Ends Swing Check Valve, Grooved Ends Swing Check Valve, Grooved Ends Swing Check Valve, Grooved Ends

4, 6 4 4 6 6 21/2, 3

2 1/ 2, 3

175 (1205) 250 (1725) 250 (1725) 175 (1205) 175 (1205) 250 (1725) 250 (1725)

a a a a a a a

Victaulic Company, Box 31, Easton PA 18044

Product Designation Description Nominal Pipe Size in./ mm Max Working Pressure, psi (kPa) Remarks

Style 717 Style 717R

Remarks

Swing Check Valve, Cut Groove Swing Check Valve, Cut Groove

4, 5, 6, 8, 10, 12 139, 165 mm 4, 5, 6, 8, 10, 12 139, 165 mm

250 (1725) 250 (1725)

a a, b

a. For use in horizontal and vertical installations. b. With trim package.

Victaulic-Europe, Neerhonderd 37, Industriepark Kwatrecht, B-9230 Wetteren, Belgium

Product Designation Description Nominal Pipe Size in./ mm Max Working Pressure, psi (kPa) Remarks

Style 717 Style 717R

Remarks

Swing Check Valve, Cut Groove Swing Check Valve, Cut Groove

4, 5, 6, 8, 10, 12 139, 165 mm 4, 5, 6, 8, 10, 12 139, 165 mm

250 (1725) 250 (1725)

a a, b

a. For use in horizontal and vertical installations. b. With trim package.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Model D-1 Model E-1

Model F-1

Model G-1

Swing Check Valve, Flanged or Grooved Ends Swing Check Valve, Groove by Groove, Flange by Groove, or Flange by Flange ends Swing Check Valve, Groove by Groove, Flange by Groove, or Flange by Flange ends Swing Check Valve, Grooved Ends

21/2 2 1/ 2

250 (1725) 250 (1725)

a a

3, 4, 6, 8

250 (1725)

a

3

250 (1725)

a

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-179

Product Designation

Description

Nominal Pipe Size, in.

Max Working Pressure, psi (kPa)

Remarks

Model G-1 Model L-1 Model M-2

Remarks

Swing Check Valve, Flanged or Grooved Ends Swing Check Valve, Grooved Ends Swing Check Valve, Grooved Ends

4, 6, 8 11/2, 2 4

250 (1725) 250 (1725) 250 (1725)

a a a

a. For use in horizontal and vertical installations.

Watts Regulator Co, 815 Chestnut St, North Andover MA 01845

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Series 411 Series 411M1

Swing Check Valve, Flanged Ends Swing Check Valve, Flanged Ends

2 1/2, 3, 4, 6, 8, 10 2, 2 1/2, 3, 4, 5, 6, 8, 10, 12

175 (1205) 175 (1205)

a, b a

a. Resilient Seat. b. Clearance must be provided to permit hinge pin removal

Wilson & Cousins, 4390 Paletta Court, Burlington, Ontario L7L 5R2, Canada

Product Designation Description Nominal Pipe Size, in. Max Working Pressure, psi (kPa) Remarks

Model IE144G

Remarks

Swing Check Valve, Grooved Ends

4

300 (2070)

a, b

a. For use in horizontal and vertical installations. b. No removable covers.

CHECK VALVES, Anti-Water Hammer

Fire-protective systems in high buildings sometimes experience severe water hammer from backflow of a pressure tank when the automatic control shuts down the fire pump. These special check valves are FM Approved only for use in the discharge of a fire pump where conditions may be expected to cause serious water hammer with the usual swing type valve. However, the friction loss through these valves is generally higher than that of a conventional single check valve. Available friction loss data is tabulated in the listings below. The flow rates shown are the maximum flows anticipated for the corresponding valve sizes. Lower flow rates will result in comparably lower losses. Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.

APCO/Valve & Primer Corp, 1420 S Wright Blvd, Schaumburg IL 60193

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Series 300 304.3, 304.4, 304.5, 304.6 306.3, 306.4, 306.5, 306.6 308.3, 308.4, 308.5, 308.6 310.3, 310.4, 310.5, 310.6

4 6 8 10

750 (2840) 1500 (5680) 3000 (11 355) 5000 (18 925)

9.8 (67.5) 6.5 (45.0) 8.2 (56.5) 9.3 (64.0)

Series 600 604.3, 604.4, 604.5, 604.6 606.3, 606.4, 606.5, 606.6 608.3, 608.4, 608.5, 608.6 610.3, 610.4, 610.5, 610.6 612.3, 612.4, 612.5, 612.6 618.1, 618.2

4 6 8 10 12 18

750 (2840) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500) 13,000 (49 210)

7.4 (51.0) 5.7 (39.5) 7.4 (51.0) 8.5 (58.5) 8.0 (55.0) 4.3 (29.5)

FM Approvals

1-180

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate,gal/min (dm3/min)

Friction Loss, psi (kPa)

Series 9000* 9004.1, 9204.1* 9006.1, 9206.1* 9008.1, 9208.1* 9010.1, 9210.1* 9012.1, 9212.1*

*250 psi (1725 kPa) working pressure.

4 6 8 10 12

750 (2840) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500)

7.8 (53.5) 4.3 (29.5) 4.3 (29.5) 3.9 (27.0) 3.5 (24.0)

Ban Chang Hardware Co Ltd, No 168, Lane 432, Sec 3, Lu Ho Road, LuKang ChangHua Hsien 505, Taiwan

Product Description Nominal Pipe Size, in. Flow Rate, gal/min (L/min) Friction Loss, psi (kPa)

B110*§

Remarks

21/2

250 (945)

6.9 (47.5)

*250 psi (1725 kPa) rated working pressure. This Model is available with a ``FG'' suffix indicating that the valve is supplied with a grooved inlet by female threaded outlet. This Model is available with a ``FM'' suffix indicating that the valve is supplied with a male threaded inlet by female threaded outlet. §This Model is available with a ``G'' suffix indicating that the valve is supplied with grooved inlet and outlet.

Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Model B* Model 80* Model 90*

4 4 2 1/ 2 3 4 6

750 (2840) 750 (2840) 250 (945) 400 (1515) 750 (2840) 1500 (5680)

2.6 (18.0) 3.0 (20.5) 1.8 (12.5) 2.4 (16.5) 2.3 (16.0) 2.2 (15.0)

*250 psi (1725 kPa) working pressure.

Cla-Val Co, Box 1325, Newport Beach CA 92659-0325

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Series 580 Wafer Style* 2 21/2 3 4 5 6 8 10 200 (755) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 21.6 (149) 9.5 (67) 10 (69) 10.8 (75) 8.0 (55) 8.6 (59) 10.3 (71) 12.3 (85)

Series 581 Globe Style* 21/2 3 4 5 6 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3.9 (27) 5.2 (36) 6.1 (42) 3.7 (26) 5.0 (35)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-181

Product Designation

Valve Size, in.

Flow Rate,gal/min (dm3/min)

Friction Loss, psi (kPa)

8 10 12

3000 (11 355) 5000 (18 925) 7000 (26 500)

5.4 (37) 6.5 (45) 6.5 (45)

Series 582 Dual Disc Wafer Style* 2 21/2 3 4 5 6 8 10 12

*200 psi (1380 kPa) reated working pressure.

200 (755) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500)

8.7 (60) 5.6 (39) 5.6 (39) 5.6 (39) 3.5 (24) 3.5 (24) 3.7 (26) 3.7 (26) 3.2 (22)

Clow Valve Co, Div McWane Inc, 902 S 2nd St, Oskaloosa IA 52577

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

329

4 5 6 8

636

4 5 6 8 10 12

750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500)

14.0 (96.5) 15.0 (103.5) 19.0 (131.0) 26.0 (179.5) 4.5 (31.0) 2.9 (20.0) 5.1 (35.0) 9.0 (62.0) 10 (65.5) 8.0 (55.0)

Crane Engineered Valves, 9860 Johnson Rd, Montgomery TX 77356

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Duo-Chek U12HMP

4 6 8 10 12

750 (2840) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500)

1.8 (12.5) 1.3 (9.0) 1.8 (12.5) 2.0 (14.0) 2.0 (14.0)

250 psi (1725 kPa) working pressure.

Crane Stockham Valve Ltd, 6 Alexander Rd, Cregagh, Belfast Northern Ireland BT6 9HJ

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Duo-Chek U12HMP

4 6 8

750 (2840) 1500 (5680) 3000 (11 355)

1.8 (12.5) 1.3 (9.0) 1.8 (12.5)

FM Approvals

1-182

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate,gal/min (dm3/min)

Friction Loss, psi (kPa)

10 12

250 psi (1725 kPa) working pressure.

5000 (18 925) 7000 (26 500)

2.0 (14.0) 2.0 (14.0)

Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

``Powhatan'' Model No. 18-460

4

750 (2840)

4.2 (29.0)

Available with male inlet x female outlet threaded end connections and threaded male inlet x cut groove outlet end connections. 250 psi (1725 kPa) rated working pressure.

Fire Protection Products Inc, 6241 Yarrow Drive, Suite A, Carlsbad CA 92009-1541

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

TrimFit

2 21/2 3 4

210 (795) 250 (945) 450 (1705) 750 (2840)

3.8 (26) 3.2 (22) 4.1 (28) 2.0 (14)

Available with grooved × grooved, male × female threaded and male threaded × grooved end connections. Resilient seat. 300 psi (2070 kPa) rated working pressure.

A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d'Opaglio, Italy

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Model A140G

4

750 (2840)

3.8 (25.0)

Available with male inlet x female outlet threaded end connections and threaded male inlet x cut groove outlet end connections. 250 psi (1725 kPa) rated working pressure.

Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Product Designation Valve Size in./ mm Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Grinnell or Gem F515* 4'' NPT Male Outlet 4'' NPT Female Outlet Grinnell or Gem F520, F5201

4

750 (2840)

2.55 (17.5)

4 6 8

Grinnell or Gem F52* Grinnell or Gem 7800 FP*

2 1/ 2 2 21/2 3 4 5 6 8 10 12 76.1 mm (No in. equivalent)

750 (2840) 1500 (5680) 2700 (10 220) 250 (945) 200 (755) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500) 250 (945)

3.5 (24.0) 1.4 (9.5) 1.1 (7.5) 2.7 (19) 3.72 (26.0) 3.15 (22.5) 2.96 (20.5) 2.55 (17.5) 1.33 (9.0) 2.09 (14.5) 3.03 (21.0) 2.03 (14.0) 1.16 (8.0) 3.15 (22.5)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-183

Product Designation

Valve Size in./ mm

Flow Rate,gal/min (dm3/min)

Friction Loss, psi (kPa)

Grinnell or Gem Model B*

*250 psi (1725 kPa) rated working pressure.

165.1 mm (No in. equivalent) 4

1500 (5680) 750 (2840)

2.09 (14.5) 2.6 (18.0)

Groeniger & Co, 27750 Industrial Blvd, Box 3629, Hayward CA 94545

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Figure 68G Kwik

4

750 (2840)

5.5 (38.0)

Kennedy Valve, Div McWane Inc, 1021 E Water St, Elmira NY 14901

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

706*

4 6 8

750 (2840) 1500 (5680) 3000 (11 355)

3.9 (27.0) 4.1 (28.5) 3.3 (23.0)

*250 psi (1725 kPa) working pressure.

Milwaukee Valve Company Inc, 16550 West Stratton Drive, New Berlin WI 53151

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Series 1400 Wafer Style 1402 1425 1403 1404 1405 1406 1408 1410 Series 1800 Globe Style 1825 1803 1804 1805 1806 1808 1810 1812 Series 8800 Dual Disc 8802 8825 8803 8804 8805 8806 8808 8810

2 21/2 3 4 5 6 8 10

200 (755) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500) 200 (755) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925)

21.6 (149.0) 9.5 (65.5) 10.0 (69.0) 10.8 (74.5) 8.0 (55.0) 8.6 (59.0) 10.3 (71.0) 12.3 (85.0) 3.9 (27.0) 5.2 (36.0) 6.1 (42.0) 3.7 (25.5) 5.0 (34.5) 5.4 (37.0) 6.5 (45.0) 6.5 (45.0) 8.7 (60.0) 5.6 (38.5) 5.6 (38.5) 5.6 (38.5) 3.5 (24.0) 3.5 (24.0) 3.7 (25.5) 3.7 (25.5)

2 1/ 2 3 4 5 6 8 10 12

2 2 1/ 2 3 4 5 6 8 10

FM Approvals

1-184

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate,gal/min (dm3/min)

Friction Loss, psi (kPa)

8812

12

7000 (26 500)

3.2 (22.0)

Mueller Co, 500 W Eldorado St, Decatur IL 62525

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

A-2102, A-2102-52

4 6 8

750 (2840) 1500 (5680) 3000 (11 355)

5.5 (38.0) 2.7 (18.5) 5.2 (36.0)

Fig. A-2103-52. 2 through 12 in. NPS. Cut groove. 250 psi (1725 kPa) rated working pressure.

Mueller Steam Specialty, Div Core Industries Inc, RR2 Box 44 Saint Pauls NC 28384

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

71*

2 21/2 3 4 5 6 8 10 12 14 16

72

2 2 1/ 2 3 4 5 6 8 10 12 14

101-AP

4 5 6 8 10

105-AP

4 5 6 8 10 12

200 (755) 300 (1135) 450 (1705) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500) 9500 (35 960) 13,000 (49 210) 200 (755) 300 (1135) 450 (1750) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500) 9500 (35 960) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500)

11 (76.0) 25 (172.5) 6 (41.5) 4.5 (31.0) 3 (20.5) 3.5 (24.0) 4 (27.5) 4.5 (31.0) 3.5 (24.0) 5 (34.5) 3 (20.5) 11 (76.0) 25 (172.5) 6 (41.5) 4.5 (31.0) 3 (20.5) 3.5 (24.0) 4 (27.5) 4.5 (31.0) 3.5 (24.0) 5 (34.5) 6.2 (42.5) 5.1 (35.0) 5.8 (40.0) 7.8 (54.0) 8.7 (60.0) 5.1 (35.0) 5.1 (35.0) 4.4 (30.5) 4.7 (32.5) 8.7 (60.0) 11.2 (77.0)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-185

Product Designation

Valve Size, in.

Flow Rate,gal/min (dm3/min)

Friction Loss, psi (kPa)

107-AP**

4 6

750 (2840) 1500 (5680)

6.2 (42.5) 5.8 (40.0)

*Rated working pressure 200 psi (1380 kPa) in 12 in. (305 mm) and smaller sizes; 150 psi (1035 kPa) in 14, 16 in. (355, 406 mm ) sizes. **Rated working pressure 400 psi (2760 kPa). Rated working pressure 285 psi (1965 kPa) when supplied with Carbon Steel body. Rated working pressure is 275 psi (1900 kPa) when supplied with stainless steel body. Rated working pressure is 225 psi (1550 kPa) when supplied with Bronze body.

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

G*

21/2 3 4 6

250 (945) 400 (1515) 750 (2840) 1500 (5680)

1.4 (9.4) 1.2 (8.6) 1.5 (10.0) 1.2 (8.2)

*250 psi (1725 kPa) working pressure.

Ritepro Corporation, 12200 Albert Hudon, Montreal, North Quebec H1G 3K7, Canada

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

212*, 312*

2 21/2 3 4 5 6 8 10 12

200 (755) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500)

5.7 (39.5) 3.5 (24.0) 3.2 (22.0) 3.7 (25.5) 2.1 (14.5) 2.4 (16.5) 3.5 (24.0) 3.6 (25.0) 3.2 (22.0)

*250 psi (1725 kPa) working pressure.

Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Model B*

*250 (1725 kPa) rated working pressure.

4

750 (2840)

2.6 (18.0)

Spence Engineering Company Inc, 150 Coldenham Rd, Walden NY 12586-2035

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Model 125WTI

2 21/2 3 4 5 6 8 10

200 (755) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925)

1.3 (9.0) 1.3 (9.0) 2.4 (16.6) 1.0 (6.9) 2.0 (13.8) 2.4 (16.6) 2.6 (17.9) 2.9 (20.1)

200 psi (1380 kPa) rated working pressure.

FM Approvals

1-186

September 2007 -- Approval Guide Automatic Sprinkler Systems

Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Grinnell CV-1F**

21/2 3 4 5 6 8 10

Grinnell CV-1FR**

2 1/ 2 3 4 5 6 8

TFP CV-1F**

21/2 3 4 5 6 8

TFP CV-1FR**

2 1/ 2 3 4 5 6 8

250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11355) 5000 (18 925) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11355) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11355) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11355)

2.6 (18) 4.3 (29) 4.0 (28) 2.7 (19) 2.2 (15) 2.2 (15) 1.3 (10) 2.6 (18) 4.3 (29) 4.0 (28) 2.7 (19) 2.2 (15) 2.2 (15) 2.6 (18) 4.3 (29) 4.0 (28) 2.7 (19) 2.2 (15) 2.2 (15) 2.6 (18) 4.3 (29) 4.0 (28) 2.7 (19) 2.2 (15) 2.2 (15)

**300 psi (2070 kPA) rated working pressure. Supplied trimmed as Riser Check Valve.

United Brass Works Inc, S Main St, Randleman NC 27317

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

90

4 6 8

67*

4

750 (2840) 1500 (5680) 3000 (11 355) 750 (2840) 750 (2840)

4.5 (31.0) 3.8 (26.0) 7.0 (48.5) 5.5 (38.0) 5.5 (38.0)

68TXG***

4

Note: Figure 67-Cut groove end connections. Figure 68-NPT male inlet and NPT female outlet connections. *250 psi (1725 kPa) working pressure. ***4 in. male NPT inlet X grooved outlet end connections.

Val-Matic Valve & Mfg Corp, 905 Riverside Dr, Elmhurst IL 60126

Product Designation Valve Size, in. Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Series 1400 Wafer Style* 1402A

2

200 (755)

21.6 (149.0)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-187

Product Designation

Valve Size, in.

Flow Rate,gal/min (dm3/min)

Friction Loss, psi (kPa)

1425A 1403A 1404A 1405A 1406A 1408A 1410A

21/2 3 4 5 6 8 10

250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925)

9.5 (67.0) 10 (65.5) 10.8 (74.5) 8.0 (55.0) 8.6 (59.0) 10.3 (71.0) 12.3 (85.0)

Series 1800 Globe Style* 18021/2 1803 1804 1805 1806 1808 1810 1812

21/2 3 4 5 6 8 10 12

250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500)

3.9 (27.0) 5.2 (36.0) 6.1 (42.0) 3.7 (25.5) 5.0 (34.5) 5.4 (37.0) 6.5 (45.0) 6.5 (45.0)

Series 8800 Dual Disc Wafer Style* 8802 88021/2 8803 8804 8805 8806 8808 8810 8812

2 21/2 3 4 5 6 8 10 12

200 (755) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500)

8.7 (60.0) 5.6 (38.5) 5.6 (38.5) 5.6 (38.5) 3.5 (24.0) 3.5 (24.0) 3.7 (25.5) 3.7 (25.5) 3.2 (22.0)

Series VM 1400 Wafer Style* VM1402 VM14021/2 VM1403 VM1404 VM1405 VM1406 VM1408 VM1410

2 21/2 3 4 5 6 8 10

200 (755) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925)

21.6 (149.0) 9.5 (67.0) 10 (65.5) 10.8 (74.5) 8.0 (55.0) 8.6 (59.0) 10.3 (71.0) 12.3 (85.0)

Series 8800 BBN SSF Dual Disc Wafer Style* 8802 BBN SSF 88021/2 BBN SSF

2 21/2 3 4 5 6

8803 BBN SSF 8804 BBN SSF 8805 BBN SSF 8806 BBN SSF

200 (755) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680)

8.7 (60.0) 5.6 (38.5) 5.6 (38.5) 5.6 (38.5) 3.5 (24.0) 3.5 (24.0)

FM Approvals

1-188

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate,gal/min (dm3/min)

Friction Loss, psi (kPa)

8808 BBN SSF 8810 BBN SSF 8812 BBN SSF

8 10 12

3000 (11 355) 5000 (18 925) 7000 (26 500)

3.7 (25.5) 3.7 (25.5) 3.2 (22.0)

Series 8800 GBN SSF Dual Disc Wafer Style* 8802 GBN SSF 88021/2GBN SSF 8803 GBN SSF 8804 GBN SSF 8805 GBN SSF 8806 GBN SSF 8808 GBN SSF 8810 GBN SSF 8812 GBN SSF

2 21/2 3 4 5 6 8 10 12

200 (755) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500)

8.7 (60.0) 5.6 (38.5) 5.6 (38.5) 5.6 (38.5) 3.5 (24.0) 3.5 (24.0) 3.7 (25.5) 3.7 (25.5) 3.2 (22.0)

Series 8800 GAN SSF Dual Disc Wafer Style* 8802 GAN SSF 88021/2 GAN SSF

2 21/2 3 4 5 6 8 10 12

8803 GAN SSF 8804 GAN SSF 8805 GAN SSF 8806 GAN SSF 8808 GAN SSF 8810 GAN SSF 8812 GAN SSF

*200 psi (1380 kPa) working pressure.

200 (755) 250 (945) 400 (1515) 750 (2840) 1000 (3785) 1500 (5680) 3000 (11 355) 5000 (18 925) 7000 (26 500)

8.7 (60.0) 5.6 (38.5) 5.6 (38.5) 5.6 (38.5) 3.5 (24.0) 3.5 (24.0) 3.7 (25.5) 3.7 (25.5) 3.2 (22.0)

Victaulic Company, Box 31, Easton PA 18044

Product Designation Valve Size in./ mm Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Style 717*

4 5 6 8 139 mm 165 mm

750 (2840) 1000 (3875) 1500 (5675) 3000 (11 625) 1000 (3875) 1500 (5675)

3.53 (24) 1.97 (14) 2.00 (14) 2.31 (16) 1.97 (14) 2.00 (14)

*250 psi (1725 kPa) working pressure.

Victaulic-Europe, Neerhonderd 37, Industriepark Kwatrecht, B-9230 Wetteren, Belgium

Product Designation Valve Size in./ mm Flow Rate,gal/min (dm3/min) Friction Loss, psi (kPa)

Style 717*

4 5 6 8 139 mm

750 (2840) 1000 (3875) 1500 (5675) 3000 (11 625) 1000 (3875)

3.53 (24) 1.97 (14) 2.00 (14) 2.31 (16) 1.97 (14)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-189

Product Designation

Valve Size in./ mm

Flow Rate,gal/min (dm3/min)

Friction Loss, psi (kPa)

165 mm 10 12

*250 psi (1725 kPa) working pressure.

1500 (5675) 4900 (18 990 7000 (27 125)

2.00 (14) 2.6 (17.9) 2.34 (16.1)

SURGE AND WATERHAMMER ARRESTERS

Surge arresters or dampers are used to moderate the potentially destructive effects of pressure surges or water hammer due to pump starting and stopping and valve opening and closing. They are employed when an anti-waterhammer check valve, alone, proves inadequate to control the problem, but should always be used in conjunction with such a valve. These hydropneumatic devices absorb pressure surges into a precalculated volume of captive gas and return the absorbed water volume to the system in a controlled fashion. Surge arresters are installed on the system side of the fire pump discharge check valve and as close to the valve as possible. Because of the complex effects of system variables on satisfactory performance, each surge arrester installation should be engineered by the manufacturer for best results.

Young Engineering Mfg Inc, 560 W Terrace Dr, San Dimas CA 91773-2914

Model No. 2.5 BSA-27 5.0 BSA-27 10 BSA-27 25 BSA-27 40 BSA-27 80 BSA-27 120 BSA-27 150 BSA-27 2.5 BSA-60 5.0 BSA-60 10 BSA-60 25 BSA-50 40 BSA-50 80 BSA-50 120 BSA-50 250 BST-27 500 BST-27

a. Has a 3 in., 150 lb Class ANSI Flange. b. Has a 3 in., 300 lb Class ANSI Flange. c. Has a 4 in. or 8 in., 150 lb Class ANSI Flange. d. Has a 4 in., 300 lb Class ANSI Flange.

Size, gal (Liters) 2.5 (9.46) 5.0 (18.93) 10 (37.85) 25 (94.6) 40 (151.40) 80 (302.80) 120 (454.20) 150 (568) 2.5 (9.46) 5.0 (18.93) 10 (37.85) 25 (94.6) 40 (151.40) 80 (302.80) 120 (454.20) 250 (950) 500 (1900)

Rated Working Pressure, psi (kPa) 275 (1895) 275 (1895) 275 (1895) 275 (1895) 275 (1895) 275 (1895) 275 (1895) 275 (1895) 600 (4135) 600 (4135) 600 (4135) 500 (3445) 500 (3445) 500 (3445) 500 (3445) 275 (1895) 275 (1895)

Notes a a a c c c c c b b b d d d d c c

BACKFLOW PREVENTERS

Backflow preventers are used in connections between public water supplies and fire protection systems to prevent reverse flow. Where health authorities require the installation of backflow preventers, FM Approved models should be used.

FM Approvals

1-190

September 2007 -- Approval Guide Automatic Sprinkler Systems

These backflow preventers have been evaluated for reliability from a fire protection standpoint. No attempt has been made to determine their suitability to ensure the public health. Unless otherwise noted in the listing, these devices have 175 psi (1205 kPa) rated working pressure and are limited to horizontal installations.

Double Check Type

A double check type backflow preventer is an assembly of two check valves and two FM Approved resilient seated NRS or OS&Y gate valves.

Ames Co Inc, 1485 Tanforan Ave, Woodland CA 95776

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 300 (1135) 4 500 (1895) 750 (2840) 1000 (3785) 6 1300 (4920) 1500 (5680) 2500 (9455) 2000 DC 2000 DCA 8 3000 (11 355) 3100 (11 735) 4000 (15 140) 2000 DC 10 4900 (18 550) 5500 (20 820) 100 (380) 21/2 2000 SE (horizontal and vertical installations) 8 200 (755) 300 (1135) 1500 (5680) 2000 (7570) 2500 (9465) 50 (190) 2000 SS, 2000 SS RS (horizontal and vertical installations) 21/2 150 (570) 250 (945) 100 (380) 2000 SS, 2000 SS RS (horizontal and vertical installations) 3 250 (945) 300 (1135) 250 (945) 2000 SS, 2000 SS RS (horizontal and vertical installations) 4 500 (1895) 700 (2650) Friction Loss, psi (kPa) 7.9 (54) 8.2 (56) 11.5 (79) 9.1 (63) 9.8 (68) 10.2 (70) 10.7 (74) 15.5 (107) 16.1 (111) 25.5 (176) 36.0 (248) 44.0 (303) 7.3 (50) 7.8 (55) 11.8 (80) 8.4 (60) 13.5 (95) 21.5 (150) 6.3 (43.5) 5.9 (40.5) 5.8 (40) 6.6 (45.5) 2.3 (16) 2.7 (18.5) 3.6 (25) 4.1 (28.5) 8.0 (55)

2000 DC 2000 DCA

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-191

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 1000 (3785)

Friction Loss, psi (kPa) 4.3 (29.5) 6.2 (42.5) 6.6 (45.5) 3.5 (24) 3.8 (26) 5.2 (36) 5.6 (39) 9.0 (62) 14.2 (100) 7.4 (51.0) 6.4 (44.1) 5.8 (40.0) 8.6 (59.3) 3.3 (22.7) 2.7 (18.5) 3.6 (25) 4.1 (28.5) 8.0 (55) 5.8 (40.0) 10.7 (74.0) 19.3 (133.0) 7.0 (48.5) 14.1 (97.0) 19.2 (132.5) 5.3 (36.5) 7.2 (49.5) 10.0 (69.0) 5.9 (41.0) 8.6 (59.5) 10.9 (75.0) 4.4 (30.0) 3.1 (21.4) 5.1 (35.1) 3.8 (26.2) 6.2 (42.7) 12.3 (85)

2000 SS, 2000 SS RS (horizontal and vertical installations)

6

1250 (4730) 1300 (4920) 1500 (5680)

2000 SS, 2000 SS RS (horizontal and vertical installations)

8

2000 (7570) 2500 (9465) 3000 (11 355)

2000 SS, 2000 SS RS (horizontal and vertical installations)

10

4000 (15 140) 5000 (18 925) 50 (190)

2000 SSF (horizontal and vertical installations)

21/2

150 (570) 250 (945) 100 (380)

2000 SSF (horizontal and vertical installations)

3

250 (945) 300 (1135) 250 (945)

2000 SSF (horizontal and vertical installations)

4

500 (1895) 700 (2650) 500 (1895)

2000CIV (horizontal and vertical installations)

4

750 (2840) 1000 (3785) 1000 (3785)

2000CIV (horizontal and vertical installations)

6

1500 (5680) 1750 (6625) 1500 (5680)

2000CIV (horizontal and vertical installations)

8

2000 (7570) 2500 (9465) 3000 (11 355)

2000CIV (horizontal and vertical installations)

10

4000 (15 140) 4500 (17 035) 150 (570)

2001 SS, 2001 SS RS (horizontal and vertical installations)

3

250 (945) 400 (1895) 250 (945)

2001 SS, 2001 SS RS (horizontal and vertical installations)

4

500 (1895) 750 (2840)

FM Approvals

1-192

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 1000 (3785)

Friction Loss, psi (kPa) 4.4 (30.3) 8.9 (61.3) 14.9 (102.7) 6.7 (46) 12.1 (83.4) 17.8 (122.7) 3.9 (26.9) 2.9 (20.0) 5.7 (39.3) 3.0 (20.7) 6.7 (46.2) 14.6 (100.7) 4.8 (33.1) 11.0 (75.8) 18.2 (125.5) 7.1 (49) 12.3 (85) 19.4 (134) 4.0 (28) 6.0 (41) 10.8 (75) 3.2 (22) 4.0 (28) 9.3 (65) 3.1 (21) 7.8 (54) 18.1 (125) 3.5 (24) 10.6 (75) 17.8 (125) 3.2 (22) 7.5 (28) 14.6 (100) 3.8 (26) 8.7 (60) 17.0 (115)

2001 SS, 2001 SS RS (horizontal and vertical installations)

6

1500 (5680) 2000 (7570) 1500 (5680)

2001 SS, 2001 SS RS (horizontal and vertical installations)

8

2000 (7570) 2500 (17235)

2001 SS, 2001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

150 (570) 3 250 (945) 400 (1895) 250 (945) 4 500 (1895) 750 (2840) 1000 (3785) 6 1500 (5680) 2000 (7570) 1500 (5680) 8 2000 (7570) 2500 (17235) 150 (570)

2001 SS, 2001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

2001 SS, 2001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

2001 SS, 2001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

Colt 200/200a (horizontal and vertical installations)

21/2

250 (950) 400 (1515) 150 (570)

Colt 200/200a (horizontal and vertical installations)

3

250 (945) 500 (1895) 200 (755)

Colt 200/200a (horizontal and vertical installations)

4

500 (1895) 800 (3030) 750 (2840)

Colt 200/200a (horizontal and vertical installations)

6

1500 (5680) 2000 (7570) 1000 (3785)

Colt 200 (horizontal and vertical installations)

8

2000 (7570) 3000 (11 355) 2000 (7570)

Colt 200 (horizontal and vertical installations)

10

3500 (13 250) 5000 (18 925)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-193

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 150 (570)

Friction Loss, psi (kPa) 4.5 (31) 7.7 (53) 14.8 (100) 3.2 (22) 3.8 (26) 8.1 (56) 3.1 (21) 8.3 (57) 19.8 (135) 3.0 (21) 11.3 (78) 19.2 (130) 3.2 (22) 7.9 (54) 15.2 (105) 4.1 (28) 9.8 (68) 19.8 (135) 4.0 (28) 6.0 (41) 10.8 (75) 3.2 (22) 4.0 (28) 9.3 (65) 2.8 (19) 3.9 (27) 11.0 (76) 2.8 (19) 5.8 (40) 9.0 (62) 2.4 (17) 3.6 (25) 6.4 (44) 3.8 (26) 8.7 (60) 17.0 (115)

Colt 200N/200Na

21/2

250 (950) 400 (1515) 150 (570)

Colt 200N/200Na

3

250 (945) 500 (1135) 200 (755)

Colt 200N/200Na

4

500 (1895) 800 (3030) 750 (2840)

Colt 200N/200Na

6

1500 (5680) 2000 (7570) 1000 (3785)

Colt 200N

8

2000 (7570) 3000 (11 355) 2000 (7570)

Colt 200N

10

3500 (13 250) 5000 (18 925) 150 (570)

Maxim 200/200a (horizontal and vertical installations)

21/2

250 (950) 400 (1515) 150 (570)

Maxim 200/200a (horizontal and vertical installations)

3

250 (945) 500 (1895) 200 (755)

Maxim 200/200a (horizontal and vertical installations)

4

500 (1895) 1000 (3785) 750 (2840)

Maxim 200 (horizontal and vertical installations)

6

1500 (5680) 2000 (7570) 1000 (3785)

Maxim 200 (horizontal and vertical installations)

8

2000 (7570) 3000 (11 355) 2000 (7570)

Maxim 200 (horizontal and vertical installations)

10

3500 (13 250) 5000 (18 925)

FM Approvals

1-194

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 150 (570)

Friction Loss, psi (kPa) 4.5 (31) 7.7 (53) 14.8 (100) 3.2 (22) 3.8 (26) 8.1 (56) 3.1 (21) 5.1 (35) 15.2 (105) 3.0 (21) 6.1 (42) 9.5 (66) 2.7 (19) 4.3 (30) 7.8 (54) 4.1 (28) 9.8 (68) 19.8 (135)

Maxim 200N/200Na

21/2

250 (950) 400 (1515) 150 (570)

Maxim 200N/200Na

3

250 (945) 500 (1135) 200 (755)

Maxim 200N/200Na

4

500 (1895) 1000 (3785) 750 (2840)

Maxim 200N

6

1500 (5680) 2000 (7570) 1000 (3785)

Maxim 200N

8

2000 (7570) 3000 (11 355) 2000 (7570)

Maxim 200N

10

3500 (13 250) 5000 (18 925)

Conbraco Industries Inc, Box 247, Matthews NC 28105

Product Designation 40-109-02 40-109-03 (horizontal and vertical installations) Valve Size, in. Flow Rate, gal/min (dm3/min) 50 (190) 21/2 150 (570) 275 (1040) 100 (380) 3 300 (1135) 500 (1895) 500 (1895) 4 750 (2840) 1000 (3785) 1000 (3785) 6 1500 (5680) 1900 (7190) 1500 (5680) 8 2000 (7570) 2400 (9085) Friction Loss, psi (kPa) 6.3 (45) 6.9 (50) 10.0 (70) 5.9 (40) 8.0 (55) 21.0 (145) 6.9 (45) 11.6 (80) 20.0 (140) 6.5 (45) 14.6 (101) 25.0 (172) 5.6 (39) 7.6 (52) 10.7 (74)

40-100-02 40-100-03 (horizontal and vertical installations)

40-10A-02 40-10A-03 (horizontal and vertical installations)

40-10C-02 40-10C-03 (horizontal and vertical installations)

40-10E-02 40-10E-03 (horizontal and vertical installations)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-195

Product Designation 40-10G-02 40-10G-03 (horizontal and vertical installations)

Valve Size, in.

Flow Rate, gal/min (dm3/min) 2000 (7570)

Friction Loss, psi (kPa) 6.1 (42) 7.1 (49) 7.6 (52) 5.6 (40) 6.9 (50) 7.2 (50) 6.3 (45) 6.7 (45) 6.9 (50) 4.5 (30) 5.2 (35) 7.0 (50) 8.3 (55) 13.2 (90) 20.6 (140) 12.5 (86) 21.1 (145) 29.6 (204) 8.6 (60) 12.2 (85) 16.2 (110) 6.2 (45) 7.5 (50) 9.0 (60) 6.9 (50) 8.4 (60) 11.4 (80) 4.9 (35) 5.8 (40) 7.4 (50) 9.1 (65) 14.6 (100) 23.2 (160) 12.5 (85) 21.1 (145) 29.6 (205)

10

2500 (9465) 2750 (10 410) 100 (380)

Model DC (horizontal installation)

21/2

200 (760) 300 (1135) 200 (760)

Model DC (horizontal installation)

3

300 (1135) 400 (1515) 500 (1895)

Model DC (horizontal installation)

4

750 (2840) 1000 (3785) 1000 (3785)

Model DC (horizontal installation)

6

1500 (5680) 2000 (7570) 1500 (5680)

Model DC (horizontal installation)

8

2000 (7570) 2400 (9085) 2500 (9465)

Model DC (horizontal installation)

10

3000 (11 355) 3500 (13 250) 100 (380)

Model DC (vertical installation)

21/2

200 (760) 300 (1135) 200 (760)

Model DC (vertical installation)

3

300 (1135) 400 (1515) 500 (1895)

Model DC (vertical installation)

4

750 (2840) 1000 (3785) 1000 (3785)

Model DC (vertical installation)

6

1500 (5680) 2000 (7570) 1500 (5680)

Model DC (vertical installation)

8

2000 (7570) 2400 (9085)

FM Approvals

1-196

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 2500 (9465)

Friction Loss, psi (kPa) 9.0 (60) 13.1 (90) 18.0 (125) 5.5 (40) 7.5 (50) 8.6 (60) 6.9 (50) 7.6 (50) 9.1 (65) 7.7 (55) 9.6 (65) 11.1 (75) 9.1 (65) 15.0 (105) 23.6 (165) 6.0 (40) 12.7 (90) 15.3 (105) 8.5 (60) 12.3 (85) 16.8 (115) 5.8 (40) 6.0 (40) 12.2 (85) 4.8 (33) 5.8 (40) 13.2 (90) 5.7 (40) 12.3 (85) 24.2 (165) 6.1 (42) 14.2 (100) 26.2 (180) 2.3 (15) 6.9 (50) 15.7 (110)

Model DC (vertical installation)

10

3000 (11 355) 3500 (13 250) 100 (380)

Model DC-U (n-shaped configuration for horizontal installations)

21/2

200 (760) 300 (1135) 200 (760)

Model DC-U (n-shaped configuration for horizontal installations)

3

300 (1135) 400 (1515) 500 (1895)

Model DC-U (n-shaped configuration for horizontal installations)

4

750 (2840) 1000 (3785) 1000 (3785)

Model DC-U (n-shaped configuration for horizontal installations)

6

1500 (5680) 2000 (7570) 1500 (5680)

Model DC-U (n-shaped configuration for horizontal installations)

8

2000 (7570) 2400 (9085) 2500 (9465)

Model DC-U (n-shaped configuration for horizontal installations)

10

3000 (11 355) 3500 (13 250) 150 (570)

Model 4D-100 (Horizontal and Vertical ``flow-up'' installations)

21/2

250 (950) 400 (1515) 200 (755)

Model 4D-100 (Horizontal and Vertical ``flow-up'' installations)

3

400 (1515) 600 (2270) 500 (1895)

Model 4D-100 (Horizontal and Vertical ``flow-up'' installations)

4

700 (4825) 1000 (3785) 1000 (3785)

Model 4D-100 (Horizontal and Vertical ``flow-up'' installations)

6

1500 (5680) 2000 (7570) 1000 (3785)

Model 4D-100 (Horizontal and Vertical ``flow-up'' installations)

8

2000 (7570) 3000 (11 355)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-197

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 2000 (7570)

Friction Loss, psi (kPa) 6.2 (45) 14.0 (95) 25.3 (175)

Model 4D-100 (Horizontal and Vertical ``flow-up'' installations)

10

3000 (11 355) 4000 (15 140)

FEBCO, 3816 S Willow Ave, Fresno CA 93725

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 300 (1135) Febco Models 805Y 805Y, 805YD 3 400 (1515) 500 (1895) 500 (1895) Febco Models 805Y 805Y, 805YD 4 750 (2840) 1000 (3785) 1000 (3785) Febco Models 805Y 805Y, 805YD 6 1500 (5680) 1750 (6625) 1500 (5680) Febco Models 805Y 805Y, 805YD 8 2000 (7570) 2500 (9465) 3000 (11 355) Febco Models 805Y 805Y, 805YD 10 4000 (15 140) 5000 (18 925) Febco Models 870*, 870v* 870*, 870v* (n-shaped configuration for horizontal installation) 50 (190) 21/2 150 (570) 250 (945) 100 (380) 3 250 (945) 400 (1515) 250 (945) 4 500 (1895) 700 (2650) 1000 (3785) 6 1500 (5680) 2000 (7570) 1500 (5680) 8 2000 (7570) 2500 (9465) Friction Loss, psi (kPa) 7.5 (51.5) 11.7 (81.0) 17.8 (122.5) 5.7 (39.5) 10.6 (73.0) 18.5 (130.0) 6.0 (41.5) 9.7 (67.0) 12.0 (83.0) 5.0 (34.5) 6.8 (47.0) 10.4 (71.0) 8.6 (59.5) 13.9 (96.0) 20.1 (139.0) 5.4 (35) 4.6 (30) 6.2 (45) 3.8 (25) 4.8 (35) 8.8 (60) 3.7 (25) 6.2 (45) 10.5 (75) 4.0 (30) 7.2 (50) 12.5 (85) 3.1 (25) 4.9 (35) 6.6 (45)

Febco Models 870*, 870v* 870*, 870v* (n-shaped configuration for horizontal installation)

Febco Models 870*, 870v* 870*, 870v* (n-shaped configuration for horizontal installation)

Febco Models 870*, 870v* 870*, 870v* (n-shaped configuration for horizontal installation)

Febco Models 870*, 870v* 870*, 870v* (n-shaped configuration for horizontal installation)

FM Approvals

1-198

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation Febco Models 870*, 870v* 870*, 870v* (n-shaped configuration for horizontal installation)

Valve Size, in.

Flow Rate, gal/min (dm3/min) 2000 (7570)

Friction Loss, psi (kPa) 5.6 (40) 5.8 (40) 7.5 (50)

10

3000 (11355) 4000 (15140)

*Model Nos. 870 and 870v (in the n-shaped configuration) are available with optional FLGxFLG (21/2, 3, 4, 6, 8 and 10 in.); MJ×MJ (3, 4, 6, 8 and 10 in.) or FLGxMJ (3, 4, 6, 8 and 10 in.) Valve Setter Elbows. The above friction loss data was obtained by assemblies which employed Valve Setter Elbows.

Product Designation Febco Models 870v, 850 870v (z-shaped configuration for vertical installation)

Valve Size, in.

Flow Rate, gal/min (dm3/min) 50 (190)

Friction Loss, psi (kPa) 5.2 (35) 4.1 (30) 5.7 (40) 4.6 (30) 3.5 (25) 5.3 (35) 2.9 (20) 5.8 (40) 10.2 (70) 3.3 (25) 4.7 (30) 6.7 (45) 4.4 (30) 6.3 (45) 9.2 (65) 5.4 (35) 6.4 (45) 9.0 (60) 4.4 (30) 5.5 (40) 7.5 (50) 5.1 (35) 6.7 (45) 8.5 (60) 4.4 (30) 9.0 (60) 15.0 (105) 3.5 (25) 6.6 (45) 10.5 (70)

21/2

150 (570) 250 (945) 50 (190)

Febco Models 870v, 850 870v (z-shaped configuration for vertical installation)

3

200 (760) 300 (1135) 200 (760)

Febco Models 870v, 850 870v (z-shaped configuration for vertical installation)

4

500 (1895) 750 (2840) 750 (2840)

Febco Models 870v, 850 870v (z-shaped configuration for vertical installation)

6

1000 (3785) 1250 (4730) 1500 (5680)

Febco Models 870v, 850 870v (z-shaped configuration for vertical installation)

8

2000 (7570) 2500 (9465) 2000 (7570)

Febco Models 870v, 850 870v (z-shaped configuration for vertical installation)

10

3000 (11355) 4000 (15140) 100 (380)

850 (horizontal installation)

21/2

200 (755) 300 (1135) 200 (755)

850 (horizontal installation)

3

300 (1135) 400 (1515) 500 (1895)

850 (horizontal installation)

4

750 (2840) 1000 (3785) 1000 (3785)

850 (horizontal installation)

6

1500 (5680) 2000 (7570)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-199

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 1500 (5680)

Friction Loss, psi (kPa) 3.3 (25) 4.2 (30) 6.4 (45) 4.1 (30) 5.1 (35) 6.3 (45) 4.7 (30) 6.2 (45) 7.7 (55) 4.5 (30) 7.2 (50) 15.2 (105) 3.3 (25) 3.8 (25) 4.7 (30) 3.6 (25) 4.5 (30) 6.2 (45)

850 (horizontal installation)

8

2000 (7570) 2500 (9465) 100 (380)

850 (vertical installation)

21/2

200 (755) 300 (1135) 200 (755)

850 (vertical installation)

3

300 (1135) 400 (1515) 500 (1895)

850 (vertical installation)

4

750 (2840) 1000 (3785) 500 (1895)

850 (vertical installation)

6

1000 (3785) 1300 (4920) 1500 (5680)

850 (vertical installation)

8

2000 (7570) 2500 (9465)

Hersey Meters, Division of Mueller Group Inc, Hwy 70 Box 128 Cleveland NC 27013

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 300 (1135) No. 2 3 400 (1515) 500 (1895) 500 (1895) No. 2 4 750 (2840) 1000 (3785) 1000 (3785) No. 2 6 1500 (5680) 1750 (6625) 1500 (5680) No. 2 8 2000 (7570) 2500 (9465) 3000 (11 355) No. 2 10 4000 (15 140) 5000 (18 925) Friction Loss, psi (kPa) 7.9 (55) 11.6 (80) 16.9 (115) 7.0 (50) 9.5 (65) 14.6 (100) 7.2 (50) 12.9 (90) 18.3 (125) 5.4 (40) 6.9 (50) 10.6 (75) 11.3 (80) 16.1 (110) 20.2 (140)

FM Approvals

1-200

September 2007 -- Approval Guide Automatic Sprinkler Systems

Mueller Co, 500 W Eldorado St, Decatur IL 62525

Product Designation H-9505 Valve Size, in. 4 Flow Rate, gal/min (dm3/min) 500 (1895) 750 (2840) 1000 (3785) H-9505 6 1250 (4730) 1500 (5680) 1500 (5680) H-9505 8 2000 (7570) 2500 (9465) 4260 (16 125) H-9505 10 4900 (18 550) 5950 (22 525) Friction Loss, psi (kPa) 7.9 (54.5) 15.6 (107.5) 6.4 (44.0) 10.0 (69.0) 12.7 (87.5) 5.8 (40.0) 8.2 (56.5) 12.7 (87.5) 19.99 (135) 25.85 (180) 39.60 (275)

Watts Regulator Co, 815 Chestnut St, North Andover MA 01845

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 100 (380) 709 21/2 (horizontal only) 200 (760) 300 (1135) 300 (1135) 709 3 (horizontal only) 400 (1515) 500 (1895) 500 (1895) 709 4 (horizontal and vertical installations) 750 (2840) 1000 (3785) 1000 (3785) 709 6 (horizontal and vertical installations) 1500 (5680) 1750 (6625) 1500 (5680) 709 8 (horizontal and vertical installations) 2000 (7570) 2500 (9465) 3000 (11 355) 709 10 (horizontal and vertical installations) 4000 (15 140) 4500 (17 035) 200 (760) 770DC 4 500 (1895) 750 (2840) Friction Loss, psi (kPa) 4.0 (30) 6.0 (40) 10.1 (70) 7.6 (52.5) 11.2 (77.0) 17.4 (120.0) 5.8 (40.0) 10.7 (74.0) 19.3 (133.0) 7.0 (48.5) 14.1 (97.0) 19.2 (132.5) 5.3 (36.5) 7.2 (49.5) 10.0 (69.0) 5.9 (41.0) 8.6 (59.5) 10.9 (75.0) 6.3 (45) 5.2 (35) 9.3 (65)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-201

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 750 (2840)

Friction Loss, psi (kPa) 4.8 (35) 3.3 (25) 6.7 (45) 4.2 (30) 5.4 (35) 7.8 (55) 6.8 (45) 6.0 (40) 10.6 (75) 5.4 (35) 5.7 (40) 11.6 (80) 12.6 (85) 19.5 (135) 23.6 (165) 7.4 (50) 9.6 (65) 12.7 (90) 6.3 (43.5) 5.9 (40.5) 5.8 (40) 6.6 (45.5) 2.3 (16) 2.7 (18.5) 3.6 (25) 4.1 (28.5) 8.0 (55) 4.3 (29.5) 6.2 (42.5) 6.6 (45.5) 3.5 (24) 3.8 (26) 5.2 (36) 5.6 (39) 9.0 (62) 14.2 (100)

770DC

6

1000 (3785) 1500 (5680) 2000 (7570)

770DC

8

2500 (9465) 3000 (11355) 200 (760)

772DDC (horizontal and vertical installations)

4

500 (1895) 750 (2840) 750 (2840)

772DDC (horizontal and vertical installations)

6

1000 (3785) 1500 (5680) 2000 (7570)

772DDC (horizontal and vertical installations)

8

2500 (9465) 2750 (10 410) 3000 (11 355)

772DDC (horizontal and vertical installations)

10

3500 (13 250) 4000 (15 140) 50 (190)

774, 774 SR (horizontal and vertical installations)

21/2

150 (570) 250 (945) 100 (380)

774, 774 SR (horizontal and vertical installations)

3

250 (945) 300 (1135) 250 (945)

774, 774 SR (horizontal and vertical installations)

4

500 (1895) 700 (2650) 1000 (3785)

774, 774 SR (horizontal and vertical installations)

6

1250 (4730) 1300 (4920) 1500 (5680)

774, 774 SR (horizontal and vertical installations)

8

2000 (7570) 2500 (9465) 3000 (11 355)

774, 774 SR (horizontal and vertical installations)

10

4000 (15 140) 5000 (18 925)

FM Approvals

1-202

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 100 (380)

Friction Loss, psi (kPa) 7.3 (50) 7.8 (55) 11.8 (80) 8.4 (60) 13.5 (95) 21.5 (150) 4.4 (30) 3.1 (21) 5.1 (35) 3.8 (26) 6.2 (43) 12.3 (85) 4.4 (30) 8.9 (61) 14.9 (103) 6.7 (47) 12.1 (83) 17.8 (123) 3.9 (27) 2.9 (20) 5.7 (39) 3.0 (21) 6.7 (46) 14.6 (101) 4.8 (33) 11.0 (76) 18.2 (126) 7.1 (49) 12.3 (85) 19.4 (134) 4.0 (28) 6.0 (41) 10.8 (75) 3.2 (22) 4.0 (28) 9.3 (65)

774X (horizontal and vertical installations)

21/2

200 (755) 300 (1135) 1500 (5680)

774X (horizontal and vertical installations)

8

2000 (7570) 2500 (9465) 150 (570)

775, 775 SR (horizontal and vertical installations)

3

250 (945) 400 (1895) 250 (945)

775, 775 SR (horizontal and vertical installations)

4

500 (1895) 750 (2840) 1000 (3785)

775, 775 SR (horizontal and vertical installations)

6

1500 (5680) 2000 (7570) 1500 (5680)

775, 775 SR (horizontal and vertical installations)

8

2000 (7570) 2500 (17235)

775, 775 SR (n-shaped configuration for horizontal installation; z-shaped configuration for vertical installation)

150 (570) 3 250 (945) 400 (1895) 250 (945) 4 500 (1895) 750 (2840) 1000 (3785) 6 1500 (5680) 2000 (7570) 1500 (5680) 8 2000 (7570) 2500 (17235) 150 (570)

775, 775 SR (n-shaped configuration for horizontal installation; z-shaped configuration for vertical installation)

775, 775 SR (n-shaped configuration for horizontal installation; z-shaped configuration for vertical installation)

775, 775 SR (n-shaped configuration for horizontal installation; z-shaped configuration for vertical installation)

Silver Eagle 757 / 757a (horizontal and vertical installations)

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 757 / 757a (horizontal and vertical installations)

3

250 (945) 500 (1895)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-203

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 200 (755)

Friction Loss, psi (kPa) 3.1 (21) 7.8 (54) 18.1 (125) 3.5 (24) 10.6 (75) 17.8 (125) 3.2 (22) 7.5 (28) 14.6 (100) 3.8 (26) 8.7 (60) 17.0 (115) 4.5 (31) 7.7 (53) 14.8 (100) 3.2 (22) 3.8 (26) 8.1 (56) 3.1 (21) 8.3 (57) 19.8 (135) 3.0 (21) 11.3 (78) 19.2 (130) 3.2 (22) 7.9 (54) 15.2 (105) 4.1 (28) 9.8 (68) 19.8 (135) 4.0 (28) 6.0 (41) 10.8 (75) 3.2 (22) 4.0 (28) 9.3 (65)

Silver Eagle 757 / 757a (horizontal and vertical installations)

4

500 (1895) 800 (3030) 750 (2840)

Silver Eagle 757 / 757a (horizontal and vertical installations)

6

1500 (5680) 2000 (7570) 1000 (3785)

Silver Eagle 757 (horizontal and vertical installations)

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 757 (horizontal and vertical installations)

10

3500 (13 250) 5000 (18 925) 150 (570)

Silver Eagle 757N/757Na

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 757N/757Na

3

250 (945) 500 (1135) 200 (755)

Silver Eagle 757N/757Na

4

500 (1895) 800 (3030) 750 (2840)

Silver Eagle 757N/757Na

6

1500 (5680) 2000 (7570) 1000 (3785)

Silver Eagle 757N

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 757N

10

3500 (13 250) 5000 (18 925) 150 (570)

Silver Eagle 767 / 767a (horizontal and vertical installations)

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 767 / 767a (horizontal and vertical installations)

3

250 (945) 500 (1895)

FM Approvals

1-204

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 200 (755)

Friction Loss, psi (kPa) 2.8 (19) 3.9 (27) 11.0 (76) 2.8 (19) 5.8 (40) 9.0 (62) 2.4 (17) 3.6 (25) 6.4 (44) 3.8 (26) 8.7 (60) 17.0 (115) 4.5 (31) 7.7 (53) 14.8 (100) 3.2 (22) 3.8 (26) 8.1 (56) 3.1 (21) 5.1 (35) 15.2 (105) 3.0 (21) 6.1 (42) 9.5 (66) 2.7 (19) 4.3 (30) 7.8 (54) 4.1 (28) 9.8 (68) 19.8 (135)

Silver Eagle 767 / 767a (horizontal and vertical installations)

4

500 (1895) 1000 (3785) 750 (2840)

Silver Eagle 767 (horizontal and vertical installations)

6

1500 (5680) 2000 (7570) 1000 (3785)

Silver Eagle 767 (horizontal and vertical installations)

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 767 (horizontal and vertical installations)

10

3500 (13 250) 5000 (18 925) 150 (570)

Silver Eagle 767N / 767Na

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 767N / 767Na

3

250 (945) 500 (1135) 200 (755)

Silver Eagle 767N / 767Na

4

500 (1895) 1000 (3785) 750 (2840)

Silver Eagle 767N

6

1500 (5680) 2000 (7570) 1000 (3785)

Silver Eagle 767N

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 767N

10

3500 (13 250) 5000 (18 925)

Wilkins Operation, Zurn Industries Inc, 1747 Commerce Way, Paso Robles CA 93446

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 100 (380) 350 (horizontal and vertical installation) 21/2 200 (760) 300 (1135) Friction Loss, psi (kPa) 5.8 (40) 6.6 (45) 8.5 (60)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-205

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 300 (1135)

Friction Loss, psi (kPa) 6.6 (45) 9.4 (65) 14.6 (100) 5.6 (40) 12.3 (85) 21.3 (145) 3.7 (25) 6.7 (45) 9.9 (70) 2.8 (20) 4.1 (30) 6.5 (45) 4.4 (30) 8.3 (57) 13.2 (91) 5.5 (40) 12.2 (85) 21.3 (145) 3.7 (25) 7.2 (50) 10.5 (70) 3.2 (20) 4.6 (30) 6.9 (50) 6.1 (40) 7.6 (50) 10.1 (70) 7.3 (50) 9.0 (60) 13.2 (90) 3.6 (25) 6.5 (45) 12.5 (85) 3.4 (25) 5.1 (35) 11.5 (80)

350 (horizontal and vertical installation)

3

400 (1515) 500 (1895) 500 (1895)

350 (horizontal and vertical installation)

4

750 (2840) 1000 (3785) 750 (2840)

350 (horizontal and vertical installation)

6

1250 (4730) 1500 (5680) 1500 (5680)

350 (horizontal and vertical installation)

8

2000 (7570) 2500 (9465) 2000 (7570)

350 (horizontal and vertical installation)

10

2750 (10 410) 3500 (13 250) 500 (1895)

350A (horizontal and vertical installation)

4

750 (2840) 1000 (3785) 750 (2840)

350A (horizontal and vertical installation)

6

1250 (4730) 1500 (5680) 1500 (5680)

350A (horizontal and vertical installation)

8

2000 (7570) 2500 (9465) 100 (380)

450 (n-shaped configuration for horizontal installation)

21/2

200 (760) 300 (1135) 300 (1135)

450 (n-shaped configuration for horizontal installation)

3

400 (1515) 500 (1895) 250 (945)

450 (n-shaped configuration for horizontal installation)

4

500 (1875) 750 (2840) 750 (2840)

450 (n-shaped configuration for horizontal installation)

6

1000 (3785) 1500 (5680)

FM Approvals

1-206

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 1500 (5680)

Friction Loss, psi (kPa) 3.2 (20) 4.2 (30) 6.1 (40) 4.7 (30) 9.8 (70) 17.4 (120) 6.0 (40) 7.5 (50) 9.7 (65) 8.9 (60) 10.5 (70) 12.3 (85) 5.4 (35) 6.1 (40) 8.0 (55) 4.8 (35) 5.2 (35) 6.1 (40) 5.3 (35) 6.0 (40) 6.9 (50) 5.6 (40) 5.8 (40) 6.5 (45)

450 (n-shaped configuration for horizontal installation)

8

2000 (7570) 2500 (9465) 2000 (7570)

450 (n-shaped configuration for horizontal installation)

10

3000 (11 355) 4000 (15 140) 100 (380)

950

21/2

200 (760) 300 (1135) 300 (1135)

950

3

400 (1515) 500 (1895) 400 (1515)

950

4

500 (1895) 600 (2270) 400 (1515)

950

6

800 (3030) 1200 (4545) 1200 (4545)

950

8

1600 (6055) 2000 (7570) 1200 (4540)

950

10

1600 (6055) 2400 (9085)

Reduced Pressure Principle Type

A reduced-pressure principle type backflow preventer is an assembly of two internally loaded check valves, which are separated by an intermediate chamber equipped with an automatic relief valve for venting to atmosphere, and two FM Approved resilient seated NRS or OS&Y gate valves.

Ames Co Inc, 1485 Tanforan Ave, Woodland CA 95776

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 100 (380) 4000 CIV 21/2 200 (760) 250 (945) Friction Loss, psi (kPa) 14.0 (95) 15.2 (105) 17.0 (115)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-207

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 300 (1135)

Friction Loss, psi (kPa) 14.2 (98) 16.9 (116) 21.7 (150) 13.0 (90) 16.7 (115) 22.8 (157) 12.8 (89) 17.5 (120) 21.0 (145) 11.8 (82) 13.1 (91) 15.0 (104) 11.9 (82) 13.8 (95) 15.4 (106) 12 (83) 9.7 (67) 12.7 (87.5) 10.8 (74.5) 8.9 (61.5) 9.4 (65) 8.2 (56.5) 10 (69) 16.3 (112.5) 8.8 (60.5) 11.7 (80.5) 12.8 (88.5) 12.3 (85) 14.1 (95) 16.0 (110) 17.7 (120) 28.6 (195) 36.8 (255) 6.5 (45) 8.9 (60) 14.8 (100)

4000 CIV

3

400 (1515) 500 (1895) 500 (1895)

4000 CIV

4

750 (2840) 1000 (3785) 1000 (3785)

4000 CIV

6

1500 (5680) 1750 (6625) 1500 (5680)

4000 CIV

8

2000 (7570) 2500 (9465) 3000 (11 355)

4000 CIV

10

4000 (15 140) 4500 (17 035) 50 (190)

4000 SS, 4001 SS RS

21/2

150 (570) 300 (1135) 100 (380)

4000 SS, 4001 SS RS

3

250 (945) 300 (1135) 250 (945)

4000 SS, 4001 SS RS

4

500 (1895) 650 (2460) 1000 (3785)

4000 SS, 4001 SS RS

6

1250 (4730) 1300 (4920) 1500 (5680)

4000 SS, 4001 SS RS

8

2000 (7570) 2500 (9465) 3000 (11 355)

4000 SS, 4001 SS RS

10

4000 (15 140) 4800 (18 170) 100 (380)

4001SS, 4001 SS RS

3

250 (945) 500 (1895)

FM Approvals

1-208

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 250 (945)

Friction Loss, psi (kPa) 8.9 (60) 15.4 (105) 26.0 (180) 8.3 (55) 10.7 (75) 23.0 (160) 8.9 (60) 9.1 (65) 15.5 (105) 8.9 (60) 15.9 (110) 26.4 (180) 9.9 (70) 11.1 (75) 23.5 (160) 9.0 (62) 9.2 (63) 12.6 (87) 8.2 (57) 7.9 (54) 12.3 (85) 7.2 (50) 11.2 (77) 21.0 (145) 7.6 (52) 14.5 (100) 22.8 (155) 7.5 (52) 11.7 (81) 19.7 (135) 7.5 (52) 13.0 (90) 23.1 (160) 9.1 (63) 11.2 (77) 18.3 (125)

4001SS, 4001 SS RS

4

500 (1895) 750 (2840) 750 (2840)

4001SS, 4001 SS RS

6

1000 (3785) 1500 (5680)

4001SS, 4001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

100 (380) 3 250 (945) 500 (1895) 250 (945) 4 500 (1895) 750 (2840) 750 (2840) 6 1000 (3785) 1500 (5680) 150 (570)

4001SS, 4001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

4001SS, 4001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

Colt 400

21/2

250 (950) 400 (1515) 150 (570)

Colt 400

3

250 (945) 500 (1895) 200 (755)

Colt 400

4

500 (1895) 800 (3030) 750 (2840)

Colt 400

6

1500 (5680) 2000 (7570) 1000 (3785)

Colt 400

8

2000 (7570) 3000 (11 355) 2000 (7570)

Colt 400

10

3500 (13 250) 5000 (18 925) 150 (570)

Colt 400N/400Z

21/2

250 (950) 400 (1515)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-209

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 150 (570)

Friction Loss, psi (kPa) 8.2 (56) 8.0 (55) 12.9 (89) 7.8 (54) 12.7 (88) 23.0 (160) 7.8 (54) 12.4 (85) 19.0 (130) 8.0 (55) 12.5 (86) 19.5 (135) 7.8 (54) 12.0 (83) 17.8 (125) 9.0 (62) 9.2 (63) 12.6 (87) 8.2 (56) 7.9 (54) 12.3 (85) 9.0 (62) 7.4 (51) 12.2 (84) 7.7 (53) 9.2 (63) 12.2 (84) 7.4 (51) 7.8 (54) 11.1 (76) 7.5 (52) 13.0 (90) 23.1 (160) 9.1 (63) 11.2 (77) 18.3 (125)

Colt 400N/400Z

3

250 (945) 500 (1135) 200 (755)

Colt 400N/400Z

4

500 (1895) 750 (2840) 750 (2840)

Colt 400N/400Z

6

1250 (4730) 1700 (6435) 1000 (3785)

Colt 400N/400Z

8

2000 (7570) 2750 (10 410) 2000 (7570)

Colt 400N/400Z

10

3000 (11 355) 4000 (15 140) 150 (570)

Maxim 400

21/2

250 (950) 400 (1515) 150 (570)

Maxim 400

3

250 (945) 500 (1895) 200 (755)

Maxim 400

4

500 (1895) 1000 (3785) 750 (2840)

Maxim 400

6

1500 (5680) 2000 (7570) 1000 (3785)

Maxim 400

8

2000 (7570) 3000 (11 355) 2000 (7570)

Maxim 400

10

3500 (13 250) 5000 (18 925) 150 (570)

Maxim 400N/400Z

21/2

250 (950) 400 (1515)

FM Approvals

1-210

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 150 (570)

Friction Loss, psi (kPa) 8.2 (56) 8.0 (55) 12.9 (89) 9.5 (66) 8.8 (61) 19.8 (135) 8.0 (55) 10.4 (72) 14.4 (100) 7.5 (52) 8.8 (61) 14.0 (96) 7.8 (54) 12.0 (83) 17.8 (125)

Maxim 400N/400Z

3

250 (945) 500 (1135) 200 (755)

Maxim 400N/400Z

4

500 (1895) 1000 (3785) 750 (2840)

Maxim 400N/400Z

6

1500 (5680) 2000 (7570) 1000 (3785)

Maxim 400N/400Z

8

2000 (7570) 3000 (11 355) 2000 (7570)

Maxim 400N/400Z

10

3000 (11 355) 4000 (15 140)

Conbraco Industries Inc, Box 247, Matthews NC 28105

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 50 (190) 40-209-02 40-209-03 21/2 150 (570) 275 (1040) 100 (380) 40-200-02 40-200-03 3 300 (1135) 500 (1895) 500 (1895) 40-20A-02 40-20A-03 4 750 (2840) 1000 (3785) 1000 (3785) 40-20C-02 40-20C-03 6 1500 (5680) 1900 (7190) 1250 (4730) 40-20E-02 40-20E-03 8 1750 (6625) 2100 (7950) 1750 (6625) 40-20G-02 40-20G-03 10 2250 (8515) 2750 (10 410) Friction Loss, psi (kPa) 13.6 (95) 14.3 (100) 16.2 (110) 13.4 (95) 14.5 (100) 23.1 (160) 12.0 (85) 16.0 (110) 22.2 (130) 11.9 (80) 17.4 (120) 25.2 (175) 11.3 (78) 12.9 (89) 14.4 (99) 12.3 (85) 13.2 (91) 14.2 (98)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-211

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 1500 (5680)

Friction Loss, psi (kPa) 10.3 (70) 14.4 (100) 20.4 (140) 9.9 (70) 15.2 (105) 21.8 (150) 8.7 (60) 14.3 (100) 19.5 (135) 9.9 (70) 15.2 (105) 21.9 (150) 8.3 (55) 14.0 (95) 19.3 (135) 9.8 (70) 15.1 (105) 22.0 (150) 11.2 (75) 13.1 (90) 18.0 (125) 10.0 (70) 11.7 (80) 15.1 (105) 9.0 (60) 13.7 (95) 24.2 (165) 11.1 (75) 20.2 (140) 32.5 (225) 7.0 (50) 10.2 (70) 17.0 (115) 9.5 (65) 16.0 (110) 27.5 (190)

Model RP

8

2000 (7570) 2400 (9085) 2000 (7570)

Model RP

10

2500 (9465) 3000 (11 355) 1500 (5680)

Model RP-U (n-shaped configuration for horizontal installation)

8

2000 (7570) 2400 (9085) 2000 (7570)

Model RP-U (n-shaped configuration for horizontal installation)

10

2500 (9465) 3000 (11 355) 1500 (5680)

Model RP-Z (z-shaped configuration for vertical installtion)

8

2000 (7570) 2400 (9085) 2000 (7570)

Model RP-Z (z-shaped configuration for vertical installtion)

10

2500 (9465) 3000 (11 355) 150 (570)

Model 4D-700

21/2

250 (950) 400 (1515) 200 (755)

Model 4D-700

3

400 (1515) 600 (2270) 500 (1895)

Model 4D-700

4

700 (4825) 1000 (3785) 1000 (3785)

Model 4D-700

6

1500 (5680) 2000 (7570) 1000 (3785)

Model 4D-700

8

2000 (7570) 3000 (11 355) 2000 (7570)

Model 4D-700

10

3000 (11 355) 4000 (15 140)

FM Approvals

1-212

September 2007 -- Approval Guide Automatic Sprinkler Systems

FEBCO, 3816 S Willow Ave, Fresno CA 93725

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 300 (1135) Febco Models 825, 825D, 825YD, 825, 825D, 825YD 3 400 (1515) 500 (1895) 500 (1895) Febco Models 825, 825D, 825YD, 825, 825D, 825YD 4 750 (2840) 1000 (3785) 1000 (3785) Febco Models 825, 825D, 825YD, 825, 825D, 825YD 6 1500 (5680) 1750 (6625) 1500 (5680) Febco Models 825, 825D, 825YD, 825, 825D, 825YD 8 2000 (7570) 2500 (9465) 3000 (11 355) Febco Models 825, 825D, 825YD, 825, 825D, 825YD 10 4000 (15 140) 5000 (18 925) Febco Models 880*, 880v*, 880*, 880v* (n-shaped configuration for horizontal installation) 50 (190) 21/2 150 (570) 250 (945) 100 (380) 3 250 (945) 400 (1515) 250 (945) 4 500 (1895) 700 (2650) 1000 (3785) 6 1500 (5680) 2000 (7570) 1500 (5680) 8 2000 (7570) 2500 (9465) 2000 (7570) 10 3000 (11355) 4000 (15140) Friction Loss, psi (kPa) 14.6 (101.0) 18.3 (126.0) 23.1 (159.5) 11.6 (80.0) 15.3 (105.5) 20.8 (143.5) 12.8 (88.5) 16.3 (112.5) 18.1 (125.0) 10.6 (73.0) 11.8 (81.5) 14.0 (96.5) 14.7 (101.5) 17.6 (121.5) 20.8 (143.5) 10.2 (70) 10.6 (75) 11.8 (80) 10.4 (70) 10.6 (75) 12.8 (90) 11.1 (75) 12.2 (85) 15.0 (105) 10.7 (75) 13.2 (90) 16.6 (115) 10.8 (75) 11.6 (80) 12.7 (90) 11.9 (80) 12.6 (85) 13.1 (90)

Febco Models 880*, 880v*, 880*, 880v* (n-shaped configuration for horizontal installation)

Febco Models 880*, 880v*, 880*, 880v* (n-shaped configuration for horizontal installation)

Febco Models 880*, 880v*, 880*, 880v* (n-shaped configuration for horizontal installation)

Febco Models 880*, 880v*, 880*, 880v* (n-shaped configuration for horizontal installation)

Febco Models 880*, 880v*, 880*, 880v* (n-shaped configuration for horizontal installation)

*Model Nos. 880 and 880v (in the n-shaped configuration) are available with optional FLGxFLG (21/2, 3, 4, 6, 8 and 10 in.); MJ×MJ (3, 4, 6, 8 and 10 in.) or FLGxMJ (3, 4, 6, 8 and 10 in.) Valve Setter Elbows. The above friction loss data was obtained by assemblies which employed Valve Setter Elbows.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-213

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 50 (190)

Friction Loss, psi (kPa) 10.3 (70) 10.8 (75) 12.1 (85) 10.1 (70) 10.1 (70) 12.8 (90) 10.9 (75) 10.8 (75) 12.3 (85) 7.5 (50) 8.0 (55) 10.5 (75) 11.7 (80) 13.2 (90) 14.9 (105) 11.4 (80 12.6 (85) 14.5 (100) 10.8 (75) 10.9 (75) 12.5 (85) 11.3 (80) 12.3 (85) 14.3 (100) 8.4 (60) 11.5 (80) 16.7 (115) 9.6 (65) 9.7 (65) 10.4 (70) 10.6 (75) 11.5 (80) 12.6 (85)

Febco Models 880v, 860880v (z-shaped configuration for vertical installation)

21/2

200 (755) 300 (1135) 100 (380)

Febco Models 880v, 860880v (z-shaped configuration for vertical installation)

3

250 (945) 400 (1515) 200 (760)

Febco Models 880v, 860880v (z-shaped configuration for vertical installation)

4

500 (1895) 600 (2270) 750 (1895)

Febco Models 880v, 860880v (z-shaped configuration for vertical installation)

6

1000 (2270) 1500 (5680) 1500 (5680)

Febco Models 880v, 860880v (z-shaped configuration for vertical installation)

8

2000 (7570) 2500 (9465) 2000 (7570)

Febco Models 880v, 860880v (z-shaped configuration for vertical installation)

10

3000 (11355) 4000 (15140) 50 (190)

860

21/2

150 (570) 250 (945) 200 (755)

860

3

300 (1135) 400 (1515) 500 (1895)

860

4

750 (2840) 1000 (3785) 1000 (3785)

860

6

1500 (5680) 2000 (7570) 1500 (5680)

860

8

2000 (7570) 2500 (9465)

FM Approvals

1-214

September 2007 -- Approval Guide Automatic Sprinkler Systems

Hersey Meters, Division of Mueller Group Inc, Hwy 70 Box 128, Cleveland NC 27013

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 200 (755) 6CM 21/2 250 (945) 300 (1135) 300 (1135) 6CM 3 400 (1515) 450 (1705) 500 (1895) 6CM 4 750 (2840) 800 (3030) 1000 (3785) 6CM 6 1500 (5680) 1750 (6625) 1500 (5680) 6CM 8 2000 (7570) 2500 (9465) 3000 (11 355) 6CM 10 4000 (15 140) 5000 (18 925) Friction Loss, psi (kPa) 13.8 (95) 15.1 (105) 17.3 (120) 14.6 (100) 16.5 (115) 17.7 (120) 13.6 (95) 15.6 (110) 18.2 (125) 12.9 (90) 17.8 (125) 20.3 (140) 13.9 (95) 15.8 (110) 18.4 (125) 14.2 (100) 18.1 (125) 19.6 (135)

Mueller Co, 500 W Eldorado St, Decatur IL 62525

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 500 (1895) H-9506 4 750 (2840) 1000 (3785) 1000 (3785) H-9506 6 1250 (4730) 1450 (5490) 1500 (5680) H-9506 8 2000 (7570) 2500 (9465) 4345 (16 445) H-9506 10 4900 (18 550) 5990 (22 675) Friction Loss, psi (kPa) 11.9 (82.0) 13.1 (90.5) 25.3 (174.5) 11.6 (80.0) 13.6 (94.0) 15.5 (107.0) 10.6 (73.0) 12.2 (84.0) 15.1 (104.0) 20.10 (140) 25.01 (170) 38.29 (265)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-215

Watts Regulator Co, 815 Chestnut St, North Andover MA 01845

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 100 (380) 909 21/2 200 (760) 250 (945) 300 (1135) 909 3 400 (1515) 500 (1895) 500 (1895) 909 4 750 (2840) 1000 (3785) 1000 (3785) 909 6 1500 (5680) 1750 (6625) 1500 (5680) 909-M1 8 2000 (7570) 2500 (9465) 3000 (11 355) 909-M1 10 4000 (15 140) 4500 (17 035) 200 (760) 990RP 4 500 (1895) 700 (2650) 750 (2840) 990RP 6 1000 (3785) 1500 (5680) 2000 (7570) 990RP 8 2500 (9465) 3000 (11355) 250 (945) 992RP 4 500 (1895) 750 (2840) 750 (2840) 992RP 6 1000 (3785) 1500 (5680) Friction Loss, psi (kPa) 14.0 (95) 15.2 (105) 17.0 (115) 14.2 (98.0) 16.9 (116.5) 21.7 (149.5) 13.0 (89.5) 16.7 (115.0) 22.8 (157.0) 12.8 (88.5) 17.5 (120.0) 21.0 (145.0) 11.8 (81.5) 13.1 (90.5) 15.0 (103.5) 11.9 (82.0) 13.8 (95.0) 15.4 (106.0) 12.3 (85) 9.8 (70) 10.2 (70) 11.6 (80) 11.7 (80) 12.0 (85) 10.6 (75) 9.8 (70) 9.7 (65) 11.6 (80) 10.3 (70) 14.9 (105) 12.1 (85) 13.8 (95) 16.5 (115)

FM Approvals

1-216

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 1500 (5680)

Friction Loss, psi (kPa) 13.3 (90) 17.3 (120) 26.1 (180) 11.1 (75) 17.3 (120) 26.3 (180) 12 (83) 9.7 (67) 12.7 (87.5) 10.8 (74.5) 8.9 (61.5) 9.4 (65) 8.2 (56.5) 10 (69) 16.3 (112.5) 8.8 (60.5) 11.7 (80.5) 12.8 (88.5) 12.3 (85) 14.1 (95) 16.0 (110) 17.7 (120) 28.6 (195) 36.8 (255) 6.5 (45) 8.9 (60) 14.8 (100) 8.9 (60) 15.4 (105) 26.0 (180) 8.3 (55) 10.7 (75) 23.0 (160) 8.9 (60) 9.1 (65) 15.5 (105)

992RP

8

2000 (7570) 2500 (9465) 3000 (11 355)

992RP

10

4000 (15 140) 5000 (18 925) 50 (190)

994, 994 SR

21/2

150 (570) 300 (1135) 100 (380)

994, 994 SR

3

250 (945) 300 (1135) 250 (945)

994, 994 SR

4

500 (1895) 650 (2460) 1000 (3785)

994, 994 SR

6

1250 (4730) 1300 (4920) 1500 (5680)

994, 994 SR

8

2000 (7570) 2500 (9465) 3000 (11 355)

994, 994 SR

10

4000 (15 140) 4800 (18 170) 100 (380)

995, 995 SR

3

250 (945) 500 (1895) 250 (945)

995, 995 SR

4

500 (1895) 750 (2840) 750 (2840)

995, 995 SR

6

1000 (3785) 1500 (5680)

995, 995 SR (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

100 (380) 3 250 (945) 500 (1895)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-217

Product Designation 995, 995 SR (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations) 995, 995 SR (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

Valve Size, in.

Flow Rate, gal/min (dm3/min) 250 (945)

Friction Loss, psi (kPa) 8.9 (60) 15.9 (110) 26.4 (180) 9.9 (70) 11.1 (75) 9.0 (62) 9.2 (63) 12.6 (87) 8.2 (57) 7.9 (54) 12.3 (85) 7.2 (50) 11.2 (77) 21.0 (145) 7.6 (52) 14.5 (100) 22.8 (155) 7.5 (52) 11.7 (81) 19.7 (135) 7.5 (52) 13.0 (90) 23.1 (160) 9.1 (63) 11.2 (77) 18.3 (125) 8.2 (56) 8.0 (55) 12.9 (89) 7.8 (54) 12.7 (88) 23.0 (160) 7.8 (54) 12.4 (85) 19.0 (130)

4

500 (1895) 750 (2840) 750 (2840) 1000 (3785) 150 (570)

6

Silver Eagle 957

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 957

3

250 (945) 500 (1895) 200 (755)

Silver Eagle 957

4

500 (1895) 800 (3030) 750 (2840)

Silver Eagle 957

6

1500 (5680) 2000 (7570) 1000 (3785)

Silver Eagle 957

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 957

10

3500 (13 250) 5000 (18 925) 150 (570)

Silver Eagle 957N/957Z

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 957N/957Z

3

250 (945) 500 (1135) 200 (755)

Silver Eagle 957N/957Z

4

500 (1895) 750 (2840) 750 (2840)

Silver Eagle 957N/957Z

6

1250 (4730) 1700 (6435)

FM Approvals

1-218

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 1000 (3785)

Friction Loss, psi (kPa) 8.0 (55) 12.5 (86) 19.5 (135) 7.8 (54) 12.0 (83) 17.8 (125) 9.0 (62) 9.2 (63) 12.6 (87) 8.2 (56) 7.9 (54) 12.3 (85) 9.0 (62) 7.4 (51) 12.2 (84) 7.7 (53) 9.2 (63) 12.2 (84) 7.4 (51) 7.8 (54) 11.1 (76) 7.5 (52) 13.0 (90) 23.1 (160) 9.1 (63) 11.2 (77) 18.3 (125) 8.2 (56) 8.0 (55) 12.9 (89) 9.5 (66) 8.8 (61) 19.8 (135) 8.0 (55) 10.4 (72) 14.4 (100)

Silver Eagle 957N/957Z

8

2000 (7570) 2750 (10 410) 2000 (7570)

Silver Eagle 957N/957Z

10

3000 (11 355) 4000 (15 140) 150 (570)

Silver Eagle 967

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 967

3

250 (945) 500 (1895) 200 (755)

Silver Eagle 967

4

500 (1895) 1000 (3785) 750 (2840)

Silver Eagle 967

6

1500 (5680) 2000 (7570) 1000 (3785)

Silver Eagle 967

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 967

10

3500 (13 250) 5000 (18 925) 150 (570)

Silver Eagle 967N/967Z

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 967N/967Z

3

250 (945) 500 (1135) 200 (755)

Silver Eagle 967N/967Z

4

500 (1895) 1000 (3785) 750 (2840)

Silver Eagle 967N/967Z

6

1500 (5680) 2000 (7570)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-219

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 1000 (3785)

Friction Loss, psi (kPa) 7.5 (52) 8.8 (61) 14.0 (96) 7.8 (54) 12.0 (83) 17.8 (125)

Silver Eagle 967N/967Z

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 967N/967Z

10

3000 (11 355) 4000 (15 140)

Wilkins Operation, Zurn Industries Inc, 1747 Commerce Way, Paso Robles CA 93446

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 100 (380) 375 21/2 200 (760) 300 (1135) 300 (1135) 375 3 400 (1515) 500 (1895) 500 (1895) 375 4 750 (2840) 1000 (3785) 750 (2840) 375 6 1250 (4730) 1500 (5680) 1500 (1580) 375 8 2000 (7570) 2500 (9465) 2000 (7570) 375 10 2750 (10 410) 3250 (12 300) 500 (1895) 375A 4 750 (2840) 1000 (3785) 750 (2840) 375A 6 1250 (4730) 1500 (5680) 1500 (5680) 375A 8 2000 (7570) 2500 (9465) Friction Loss, psi (kPa) 12.8 (90) 14.3 (100) 16.9 (115) 14.4 (100) 16.1 (110) 19.5 (135) 9.0 (60) 13.1 (90) 20.8 (145) 7.3 (50) 10.2 (70) 12.6 (85) 10.8 (75) 11.9 (80) 13.5 (95) 11.0 (76) 13.6 (94) 18.7 (129) 9.6 (65) 14.5 (10) 22.5 (155) 8.2 (55) 10.0 (70) 14.0 (95) 12.2 (85) 12.4 (85) 13.9 (95)

FM Approvals

1-220

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation 475, 475V (475 is an n-shaped configuration for horizontal installation, 475V is an z-shaped configuration for vertical installation)

Valve Size, in.

Flow Rate, gal/min (dm3/min) 100 (380)

Friction Loss, psi (kPa) 11.6 (80) 14.0 (95) 18.0 (125) 12.2 (85) 12.9 (90) 14.2 (100) 10.5 (70) 10.1 (70) 15.4 (105) 7.4 (50) 9.0 (60) 14.0 (95) 9.9 (70) 11.2 (75) 13.7 (95) 11.3 (80) 16.2 (110) 21.0 (145) 11.2 (75) 13.3 (90) 15.3 (105) 11.1 (75) 12.7 (90) 14.2 (100) 10.1 (70) 11.3 (80) 13.1 (90) 10.6 (75) 12.0 (85) 13.8 (95) 12.0 (85) 12.8 (90) 13.9 (95) 10.5 (70) 10.9 (75) 11.4 (80)

21/2

200 (760) 300 (1135) 200 (760)

475, 475V (475 is an n-shaped configuration for horizontal installation, 475V is an z-shaped configuration for vertical installation)

3

300 (1135) 400 (1515) 250 (945)

475, 475V (475 is an n-shaped configuration for horizontal installation, 475V is an z-shaped configuration for vertical installation)

4

500 (1895) 750 (2840) 750 (2840)

475, 475V (475 is an n-shaped configuration for horizontal installation, 475V is an z-shaped configuration for vertical installation)

6

1000 (3785) 1500 (5680) 1500 (5680)

475, 475V (475 is an n-shaped configuration for horizontal installation, 475V is an z-shaped configuration for vertical installation)

8

2000 (7570) 2500 (9465) 2000 (7570)

475, 475V (475 is an n-shaped configuration for horizontal installation, 475V is an z-shaped configuration for vertical installation)

10

3000 (11 355) 3400 (12 870) 100 (380)

975

21/2

200 (760) 300 (1135) 100 (380)

975

3

200 (760) 300 (1135) 200 (760)

975

4

400 (1515) 600 (2270) 400 (1515)

975

6

800 (3030) 1200 (4540) 1200 (4540)

975

8

1600 (6055) 2000 (7570) 1500 (5680)

975

10

2000 (7570) 2500 (9465)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-221

Double Check -- Detector Check Type

A double check-detector check type backflow preventer is an assembly of two internally loaded check valves, a metered, internally loaded double check by-pass and two FM Approved resilient seated NRS or OS&Y gate valves.

Ames Co Inc, 1485 Tanforan Ave, Woodland CA 95776

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 50 (190) 3000B 2 150 (570) 250 (945) The 2 in. Model No. 3000B is FM Approved for use in the horizontal and vertical ``flow-up'' orientations. 500 (1895) 3000 DCDC 3000 DCDA 4 750 (2840) 1000 (3785) 1000 (3785) 3000 DCDC 3000 DCDA 6 1300 (4920) 1500 (5680) 2000 (7570) 3000 DCDC 3000 DCDA 8 2500 (9465) 3000 (11 355) 4000 (15 140) 3000DCDC 10 4900 (18 550) 5500 (20 820) 100 (380) 3000 SE (horizontal and vertical installations) 21/2 200 (755) 300 (1135) 1500 (5680) 3000 SE (horizontal and vertical installations) 8 2000 (7570) 2500 (9465) 50 (190) 3000 SS, 3000 SS RS (horizontal and vertical installations) 21/2 150 (570) 250 (945) 100 (380) 3000 SS, 3000 SS RS (horizontal and vertical installations) 3 250 (945) 300 (1135) 250 (945) 3000 SS, 3000 SS RS (horizontal and vertical installations) 4 500 (1895) 700 (2650) 11.2 (77.0) 11.9 (82.0) 13.5 (93.0) 9.1 (62.5) 9.8 (67.5) 10.2 (70.5) 7.3 (50.5) 10.7 (73.5) 15.5 (107.0) 25.5 (180.0) 36.0 (248.5) 44.0 (303.5) 7.3 (50) 7.8 (55) 11.8 (80) 8.5 (60) 13.5 (95) 21.5 (150) 6.3 (43.5) 5.9 (40.5) 5.8 (40) 6.6 (45.5) 2.3 (16) 2.7 (18.5) 3.6 (25) 4.1 (28.5) 8.0 (55) Friction Loss, psi (kPa) 7.0 (50) 9.1 (65) 17.1 (120)

FM Approvals

1-222

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 1000 (3785)

Friction Loss, psi (kPa) 4.3 (29.5) 6.2 (42.5) 6.6 (45.5) 3.5 (24) 3.8 (26) 5.2 (36) 5.6 (39) 9.0 (62) 14.2 (100) 7.4 (51.0) 6.4 (44.1) 5.8 (40.0) 8.6 (59.3) 3.3 (22.7) 2.7 (18.5) 3.6 (25) 4.1 (28.5) 8.0 (55) 7.5 (52.0) 11.3 (78.0) 18.7 (129.0) 9.0 (62.0) 14.2 (98.0) 19.2 (132.5) 8.8 (61.0) 10.0 (69.0) 12.2 (84.0) 9.9 (68.5) 11.2 (77.5) 12.7 (87.5) 4.4 (30.0) 3.1 (21.4) 5.1 (35.1) 3.8 (26.2) 6.2 (42.7) 12.3 (85)

3000 SS, 3000 SS RS (horizontal and vertical installations)

6

1250 (4730) 1300 (4920) 1500 (5680)

3000 SS, 3000 SS RS (horizontal and vertical installations)

8

2000 (7570) 2500 (9465) 3000 (11 355)

3000 SS, 3000 SS RS (horizontal and vertical installations)

10

4000 (15 140) 5000 (18 925) 50 (190)

3000 SSF (horizontal and vertical installations)

21/2

150 (570) 250 (945) 100 (380)

3000 SSF (horizontal and vertical installations)

3

250 (945) 300 (1135) 250 (945)

3000 SSF (horizontal and vertical installations)

4

500 (1895) 700 (2650) 500 (1895)

3000CIV (horizontal and vertical installations)

4

750 (2840) 1000 (3785) 1000 (3785)

3000CIV (horizontal and vertical installations)

6

1500 (5680) 1750 (6625) 1500 (5680)

3000CIV (horizontal and vertical installations)

8

2000 (7570) 2500 (9465) 3000 (11 355)

3000CIV (horizontal and vertical installations)

10

4000 (15 140) 4500 (17 035) 150 (570)

3001 SS, 3001 SS RS (horizontal and vertical installations)

3

250 (945) 400 (1895) 250 (945)

3001 SS, 3001 SS RS (horizontal and vertical installations)

4

500 (1895) 750 (2840)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-223

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 1000 (3785)

Friction Loss, psi (kPa) 4.4 (30.3) 8.9 (61.3) 14.9 (102.7) 6.7 (46) 12.1 (83.4) 17.8 (122.7) 3.9 (26.9) 2.9 (20.0) 5.7 (39.3) 3.0 (20.7) 6.7 (46.2) 14.6 (100.7) 4.8 (33.1) 11.0 (75.8) 18.2 (125.5) 7.1 (49) 12.3 (85) 19.4 (134) 4.0 (28) 6.0 (41) 10.8 (75) 3.2 (22) 4.0 (28) 9.3 (65) 3.1 (21) 7.8 (54) 18.1 (125) 3.5 (24) 10.6 (75) 17.8 (125) 3.2 (22) 7.5 (28) 14.6 (100) 3.8 (26) 8.7 (60) 17.0 (115)

3001 SS, 3001 SS RS (horizontal and vertical installations)

6

1500 (5680) 2000 (7570) 1500 (5680)

3001 SS, 3001 SS RS (horizontal and vertical installations)

8

2000 (7570) 2500 (17235)

3001 SS, 3001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

150 (570) 3 250 (945) 400 (1895) 250 (945) 4 500 (1895) 750 (2840) 1000 (3785) 6 1500 (5680) 2000 (7570) 1500 (5680) 8 2000 (7570) 2500 (17235) 150 (570)

3001 SS, 3001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

3001 SS, 3001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

3001 SS, 3001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

Colt 300/300a (horizontal and vertical installations)

21/2

250 (950) 400 (1515) 150 (570)

Colt 300/300a (horizontal and vertical installations)

3

250 (945) 500 (1895) 200 (755)

Colt 300/300a (horizontal and vertical installations)

4

500 (1895) 800 (3030) 750 (2840)

Colt 300/300a (horizontal and vertical installations)

6

1500 (5680) 2000 (7570) 1000 (3785)

Colt 300 (horizontal and vertical installations)

8

2000 (7570) 3000 (11 355) 2000 (7570)

Colt 300 (horizontal and vertical installations)

10

3500 (13 250) 5000 (18 925)

FM Approvals

1-224

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 150 (570)

Friction Loss, psi (kPa) 4.5 (31) 7.7 (53) 14.8 (100) 3.2 (22) 3.8 (26) 8.1 (56) 3.1 (21) 8.3 (57) 19.8 (135) 3.0 (21) 11.3 (78) 19.2 (130) 3.2 (22) 7.9 (54) 15.2 (105) 4.1 (28) 9.8 (68) 19.8 (135) 4.0 (28) 6.0 (41) 10.8 (75) 3.2 (22) 4.0 (28) 9.3 (65) 2.8 (19) 3.9 (27) 11.0 (76) 2.8 (19) 5.8 (40) 9.0 (62) 2.4 (17) 3.6 (25) 6.4 (44) 3.8 (26) 8.7 (60) 17.0 (115)

Colt 300N/300Na

21/2

250 (950) 400 (1515) 150 (570)

Colt 300N/300Na

3

250 (945) 500 (1135) 200 (755)

Colt 300N/300Na

4

500 (1895) 800 (3030) 750 (2840)

Colt 300N/300Na

6

1500 (5680) 2000 (7570) 1000 (3785)

Colt 300N

8

2000 (7570) 3000 (11 355) 2000 (7570)

Colt 300N

10

3500 (13 250) 5000 (18 925) 150 (570)

Maxim 300/300a (horizontal and vertical installations)

21/2

250 (950) 400 (1515) 150 (570)

Maxim 300/300a (horizontal and vertical installations)

3

250 (945) 500 (1895) 200 (755)

Maxim 300/300a (horizontal and vertical installations)

4

500 (1895) 1000 (3785) 750 (2840)

Maxim 300 (horizontal and vertical installations)

6

1500 (5680) 2000 (7570) 1000 (3785)

Maxim 300 (horizontal and vertical installations)

8

2000 (7570) 3000 (11 355) 2000 (7570)

Maxim 300 (horizontal and vertical installations)

10

3500 (13 250) 5000 (18 925)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-225

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 150 (570)

Friction Loss, psi (kPa) 4.5 (31) 7.7 (53) 14.8 (100) 3.2 (22) 3.8 (26) 8.1 (56) 3.1 (21) 5.1 (35) 15.2 (105) 3.0 (21) 6.1 (42) 9.5 (66) 2.7 (19) 4.3 (30) 7.8 (54) 4.1 (28) 9.8 (68) 19.8 (135)

Maxim 300N/300Na

21/2

250 (950) 400 (1515) 150 (570)

Maxim 300N/300Na

3

250 (945) 500 (1135) 200 (755)

Maxim 300N/300Na

4

500 (1895) 1000 (3785) 750 (2840)

Maxim 300N

6

1500 (5680) 2000 (7570) 1000 (3785)

Maxim 300N

8

2000 (7570) 3000 (11 355) 2000 (7570)

Maxim 300N

10

3500 (13 250) 5000 (18 925)

Conbraco Industries Inc, Box 247, Matthews NC 28105

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 100 (380) Model DCDA (horizontal installation) 21/2 200 (760) 300 (1135) 200 (760) Model DCDA (horizontal installation) 3 300 (1135) 400 (1515) 500 (1895) Model DCDA (horizontal installation) 4 750 (2840) 1000 (3785) 1000 (3785) Model DCDA (horizontal installation) 6 1500 (5680) 2000 (7570) 1500 (5680) Model DCDA (horizontal installation) 8 2000 (7570) 2400 (9085) Friction Loss, psi (kPa) 5.6 (40) 6.9 (50) 7.2 (50) 6.3 (45) 6.7 (45) 6.9 (50) 4.5 (30) 5.2 (35) 7.0 (50) 8.3 (55) 13.2 (90) 20.6 (140) 6.0 (40) 12.7 (90) 15.3 (105)

FM Approvals

1-226

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 2500 (9465)

Friction Loss, psi (kPa) 8.5 (60) 12.3 (85) 16.8 (115) 16.2 (110) 12.5 (85) 21.1 (145) 29.6 (205) 5.9 (40) 13.1 (90) 18.0 (125) 6.4 (45) 11.1 (75) 16.0 (110) 8.5 (60) 12.3 (85) 16.8 (115) 9.0 (60) 10.6 (75) 13.9 (95) 8.4 (58) 11.7 (81) 19.2 (132) 8.6 (59) 14.9 (103) 20.7 (143) 8.5 (60) 10.8 (75) 14.1 (95) 8.6 (60) 10.6 (75) 13.9 (95) 5.8 (40) 6.0 (40) 12.2 (85)

Model DCDA (horizontal installation)

10

3000 (11 355) 3500 (13 250) 3500 (13 250) 1500 (5680)

Model DCDA (Vertical Installation)

8

2000 (7570) 2400 (9085) 2500 (9465)

Model DCDA (Vertical Installation)

10

3000 (11 355) 3500 (13 250) 1500 (5680)

Model DCDA-U (n-shaped configuration for horizontal installation)

8

2000 (7570) 2400 (9085) 2500 (9465)

Model DCDA-U (n-shaped configuration for horizontal installation)

10

3000 (11 355) 3500 (13 250)

40-600-02 40-600-03 (horizontal and vertical installations)

300 (1135) 3 400 (1515) 500 (1895) 500 (1895) 4 750 (2840) 1000 (3785) 1000 (3785) 6 1500 (5680) 1750 (6625) 1500 (5680) 8 2000 (7570) 2500 (9465) 2000 (7570) 10 3000 (11 355) 4000 (15 140) 150 (570)

40-60A-02 40-60A-03 (horizontal and vertical installations)

40-60C-02 40-60C-03 (horizontal and vertical installations)

40-60E-02 40-60E-03 (horizontal and vertical installations)

40-60G-02 40-60G-03 (horizontal and vertical installations)

Model 4D-600 (Horizontal and Vertical ``flow-up'' installations)

21/2

250 (950) 400 (1515)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-227

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 200 (755)

Friction Loss, psi (kPa) 4.8 (33) 5.8 (40) 13.2 (90) 5.7 (40) 12.3 (85) 24.2 (165) 6.1 (42) 14.2 (100) 26.2 (180) 2.3 (15) 6.9 (50) 15.7 (110) 6.2 (45) 14.0 (95) 25.3 (175)

Model 4D-600 (Horizontal and Vertical ``flow-up'' installations)

3

400 (1515) 600 (2270) 500 (1895)

Model 4D-600 (Horizontal and Vertical ``flow-up'' installations)

4

700 (4825) 1000 (3785) 1000 (3785)

Model 4D-600 (Horizontal and Vertical ``flow-up'' installations)

6

1500 (5680) 2000 (7570) 1000 (3785)

Model 4D-600 (Horizontal and Vertical ``flow-up'' installations)

8

2000 (7570) 3000 (11 355) 2000 (7570)

Model 4D-600 (Horizontal and Vertical ``flow-up'' installations)

10

3000 (11 355) 4000 (15 140)

FEBCO, 3816 S Willow Ave, Fresno CA 93725

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 500 (1895) Febco Models 806, 806YD, 806, 806YD 4 750 (2840) 1000 (3785) 1000 (3785) Febco Models 806, 806YD, 806, 806YD 6 1500 (5680) 1750 (6625) 1500 (5680) Febco Models 806, 806YD, 806, 806YD 8 2000 (7570) 2500 (9465) 3000 (11 355) Febco Models 806, 806YD, 806, 806YD 10 4000 (15 140) 5000 (18 925) 300 (1135) Febco Models 831H* (horizontal and vertical installation) 4 500 (1895) 800 (3030) Febco Models 876*, 876v* 876*, 876v* (n-shaped configuration for horizontal installation) 50 (190) 21/2 150 (570) 250 (945) Friction Loss, psi (kPa) 8.0 (55.0) 10.8 (74.5) 18.4 (127.0) 10.2 (70.5) 12.4 (85.5) 13.4 (92.5) 9.4 (65.0) 10.4 (72.0) 12.0 (83.0) 11.3 (78.0) 13.5 (93.0) 16.5 (114.0) 6.6 (45) 6.6 (45) 14.6 (100) 9.6 (65) 7.7 (55) 8.2 (55)

FM Approvals

1-228

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation Febco Models 876*, 876v* 876*, 876v* (n-shaped configuration for horizontal installation)

Valve Size, in.

Flow Rate, gal/min (dm3/min) 100 (380)

Friction Loss, psi (kPa) 7.0 (55) 6.5 (45) 10.5 (75) 5.2 (35) 6.8 (45) 11.5 (80) 5.5 (40) 9.0 (60) 13.5 (95) 5.3 (35) 6.0 (40) 7.6 (50) 1.4 (50) 7.1 (50) 6.9 (50)

3

250 (945) 400 (1515) 250 (945)

Febco Models 876*, 876v* 876*, 876v* (n-shaped configuration for horizontal installation)

4

500 (1895) 700 (2650) 1000 (3785)

Febco Models 876*, 876v* 876*, 876v* (n-shaped configuration for horizontal installation)

6

1500 (5680) 2000 (7570) 1500 (5680)

Febco Models 876*, 876v* 876*, 876v* (n-shaped configuration for horizontal installation)

8

2000 (7570) 2500 (9465) 2000 (7570)

Febco Models 876*, 876v* 876*, 876v* (n-shaped configuration for horizontal installation)

10

3000 (11355) 4000 (15140)

*Model Nos. 876 and 876v (in the n-shaped configuration) are available with optional FLGxFLG (21/2, 3, 4, 6, 8 and 10 in.); MJ×MJ (3, 4, 6, 8 and 10 in.) or FLGxMJ (3, 4, 6, 8 and 10 in.) Valve Setter Elbows. The above friction loss data was obtained by assemblies which employed Valve Setter Elbows.

Product Designation Febco Model 876v 876v (z-shaped configuration for vertical installation)

Valve Size, in.

Flow Rate, gal/min (dm3/min) 50 (190)

Friction Loss, psi (kPa) 8.5 (60) 6.8 (45) 7.7 (55) 8.0 (55) 5.9 (40) 6.8 (45) 4.4 (30) 6.2 (45) 8.5 (60) 4.3 (30) 4.6 (30) 7.5 (50) 4.8 (35) 6.5 (45) 9.0 (60) 7.0 (50) 8.0 (55) 9.4 (65)

21/2

150 (570) 250 (945) 50 (190)

Febco Model 876v 876v (z-shaped configuration for vertical installation)

3

150 (570) 300 (1135) 200 (760)

Febco Model 876v 876v (z-shaped configuration for vertical installation)

4

500 (1895) 600 (2270) 750 (1895)

Febco Model 876v 876v (z-shaped configuration for vertical installation)

6

1000 (2270) 1500 (5680) 1500 (5680)

Febco Model 876v 876v (z-shaped configuration for vertical installation)

8

2000 (7570) 2500 (9465) 2000 (7570)

Febco Model 876v 876v (z-shaped configuration for vertical installation)

10

3000 (11355) 4000 (15140)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-229

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 50 (190)

Friction Loss, psi (kPa) 6.8 (45) 7.0 (50) 8.1 (55) 7.1 (50) 8.3 (55) 9.9 (70) 5.5 (40) 9.7 (65) 15.2 (105) 4.5 (30) 7.1 (50) 10.4 (70) 4.4 (30) 4.6 (30) 5.9 (40) 6.4 (45) 6.7 (45) 7.8 (55) 7.0 (50) 8.0 (55) 9.4 (65) 4.1 (30) 4.8 (35) 9.1 (65) 4.5 (30) 4.1 (30) 4.0 (30) 4.2 (30) 4.4 (30) 5.5 (40)

Febco Model 856 856 (horizontal installation)

21/2

150 (570) 250 (945) 200 (755)

Febco Model 856 856 (horizontal installation)

3

300 (1135) 400 (1515) 500 (1895)

Febco Model 856 856 (horizontal installation)

4

750 (2840) 1000 (3785) 1000 (3785)

Febco Model 856 856 (horizontal installation)

6

1500 (5680) 2000 (7570) 1500 (5680)

Febco Model 856 856 (horizontal installation)

8

2000 (7570) 2500 (9465) 50 (190)

Febco Model 856 856 (vertical installation)

21/2

150 (570) 250 (945) 200 (755)

Febco Model 856 856 (vertical installation)

3

300 (1135) 400 (1515) 300 (1135)

Febco Model 856 856 (vertical installation)

4

500 (1895) 750 (2840) 500 (1895)

Febco Model 856 856 (vertical installation)

6

1000 (3785) 1300 (4920) 1500 (5680)

Febco Model 856 856 (vertical installation)

8

2000 (7570) 2500 (9465)

Hersey Meters, Division of Mueller Group Inc, Hwy 70 Box 128 Cleveland NC 27013

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 300 (1135) DDC II 3 400 (1515) 500 (1895) Friction Loss, psi (kPa) 10.0 (70) 12.2 (85) 16.0 (110)

FM Approvals

1-230

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 500 (1895)

Friction Loss, psi (kPa) 9.1 (65) 11.6 (80) 20.3 (140) 9.5 (65) 12.8 (90) 17.5 (120) 8.0 (55) 8.8 (60) 10.6 (75) 10.4 (70) 13.0 (90) 16.7 (115)

DDC II

4

750 (2840) 1080 (4090) 1000 (3785)

DDC II

6

1500 (5680) 1750 (6625) 1500 (5680)

DDC II

8

2000 (7570) 2500 (9465) 3000 (11 355)

DDC II

10

4000 (15 140) 5000 (18 925)

Watts Regulator Co, 815 Chestnut St, North Andover MA 01845

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 300 (1135) 709DCDA 3 (horizontal only) 400 (1515) 500 (1895) 500 (1895) 709DCDA 4 (horizontal and vertical installations) 750 (2840) 1000 (3785) 1000 (3785) 709DCDA 6 (horizontal and vertical installations) 1500 (5680) 1750 (6625) 1500 (5680) 709DCDA 8 (horizontal and vertical installations) 2000 (7570) 2500 (9465) 3000 (11 355) 709DCDA 10 (horizontal and vertical installations) 4000 (15 140) 4500 (17 035) 200 (760) 770DCDC 4 500 (1895) 750 (2840) 750 (2840) 770DCDC 6 1000 (3785) 1500 (5680) Friction Loss, psi (kPa) 9.1 (63.0) 12.3 (85.0) 17.6 (121.0) 7.5 (52.0) 11.3 (78.0) 18.7 (129.0) 9.0 (62.0) 14.2 (98.0) 19.2 (132.5) 8.8 (61.0) 10.0 (69.0) 12.2 (84.0) 9.9 (68.5) 11.2 (77.5) 12.7 (87.5) 6.3 (45) 4.8 (35) 9.8 (70) 7.0 (50) 5.4 (35) 7.2 (50)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-231

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 2000 (7570)

Friction Loss, psi (kPa) 4.5 (30) 6.9 (50) 9.6 (65) 7.0 (50) 6.6 (45) 8.4 (60) 9.1 (65) 8.1 (55) 8.1 (55) 4.6 (30) 7.6 (50) 13.3 (90) 5.3 (35) 5.3 (35) 7.7 (55) 7.0 (50) 9.1 (65) 17.1 (120)

770DCDC

8

2500 (9465) 3000 (11355) 200 (760)

772DCDC (horizontal and vertical installations)

4

500 (1895) 650 (2460) 750 (2840)

772DCDC (horizontal and vertical installations)

6

1000 (3785) 1250 (4730) 1000 (3785)

772DCDC (horizontal and vertical installations)

8

1500 (5680) 2000 (7570) 2000 (7570)

772DCDC (horizontal and vertical installations)

10

2500 (9465) 3000 (11 355) 50 (190)

007DCDA

2

150 (570) 250 (945)

The 2 in. Model No. 007DCDA is FM Approved for use in the horizontal and vertical ``flow-up'' orientations. 50 (190) 774DCDA, 774 DCDA SR (horizontal and vertical installations) 21/2 150 (570) 250 (945) 100 (380) 774DCDA, 774 DCDA SR (horizontal and vertical installations) 3 250 (945) 300 (1135) 250 (945) 774DCDA, 774 DCDA SR (horizontal and vertical installations) 4 500 (1895) 700 (2650) 1000 (3785) 774DCDA, 774 DCDA SR (horizontal and vertical installations) 6 1250 (4730) 1300 (4920) 1500 (5680) 774DCDA, 774 DCDA SR (horizontal and vertical installations) 8 2000 (7570) 2500 (9465) 6.3 (43.5) 5.9 (40.5) 5.8 (40) 6.6 (45.5) 2.3 (16) 2.7 (18.5) 3.6 (25) 4.1 (28.5) 8.0 (55) 4.3 (29.5) 6.2 (42.5) 6.6 (45.5) 3.5 (24) 3.8 (26) 5.2 (36)

FM Approvals

1-232

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 3000 (11 355)

Friction Loss, psi (kPa) 5.6 (39) 9.0 (62) 14.2 (100) 7.3 (50) 7.8 (55) 11.8 (80) 8.5 (60) 13.5 (95) 21.5 (150) 4.4 (30) 3.1 (21) 5.1 (35) 3.8 (26) 6.2 (43) 12.3 (85) 4.4 (30) 8.9 (61) 14.9 (103) 6.7 (47) 12.1 (83) 17.8 (123) 3.9 (27) 2.9 (20) 5.7 (39) 3.0 (21) 6.7 (46) 14.6 (101) 4.8 (33) 11.0 (76) 18.2 (126) 7.1 (49) 12.3 (85) 19.4 (134) 4.0 (28) 6.0 (41) 10.8 (75)

774DCDA, 774 DCDA SR (horizontal and vertical installations)

10

4000 (15 140) 5000 (18 925) 100 (380)

774XDCDA (horizontal and vertical installations)

21/2

200 (755) 300 (1135) 1500 (5680)

774XDCDA (horizontal and vertical installations)

8

2000 (7570) 2500 (9465) 150 (570)

775DCDA, 775 DCDA SR (horizontal and vertical installations)

3

250 (945) 400 (1895) 250 (945)

775DCDA, 775 DCDA SR (horizontal and vertical installations)

4

500 (1895) 750 (2840) 1000 (3785)

775DCDA, 775 DCDA SR (horizontal and vertical installations)

6

1500 (5680) 2000 (7570) 1500 (5680)

775DCDA, 775 DCDA SR (horizontal and vertical installations)

8

2000 (7570) 2500 (17235)

775DCDA, 775 DCDA SR (n-shaped configuration for horizontal installation; z-shaped configuration for vertical installation)

150 (570) 3 250 (945) 400 (1895) 250 (945) 4 500 (1895) 750 (2840) 1000 (3785) 6 1500 (5680) 2000 (7570) 1500 (5680) 8 2000 (7570) 2500 (17235) 150 (570) 21/2 250 (950) 400 (1515)

775DCDA, 775 DCDA SR (n-shaped configuration for horizontal installation; z-shaped configuration for vertical installation)

775DCDA, 775 DCDA SR (n-shaped configuration for horizontal installation; z-shaped configuration for vertical installation)

775DCDA, 775 DCDA SR (n-shaped configuration for horizontal installation; z-shaped configuration for vertical installation)

Silver Eagle 757 DCDA/757a DCDA (horizontal and vertical installations)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-233

Product Designation Silver Eagle 757 DCDA/757a DCDA (horizontal and vertical installations)

Valve Size, in.

Flow Rate, gal/min (dm3/min) 150 (570)

Friction Loss, psi (kPa) 3.2 (22) 4.0 (28) 9.3 (65) 3.1 (21) 7.8 (54) 18.1 (125) 3.5 (24) 10.6 (75) 17.8 (125) 3.2 (22) 7.5 (28) 14.6 (100) 3.8 (26) 8.7 (60) 17.0 (115) 4.5 (31) 7.7 (53) 14.8 (100) 3.2 (22) 3.8 (26) 8.1 (56) 3.1 (21) 8.3 (57) 19.8 (135) 3.0 (21) 11.3 (78) 19.2 (130) 3.2 (22) 7.9 (54) 15.2 (105) 4.1 (28) 9.8 (68) 19.8 (135) 4.0 (28) 6.0 (41) 10.8 (75)

3

250 (945) 500 (1895) 200 (755)

Silver Eagle 757 DCDA/757a DCDA (horizontal and vertical installations)

4

500 (1895) 800 (3030) 750 (2840)

Silver Eagle 757 DCDA/757a DCDA (horizontal and vertical installations)

6

1500 (5680) 2000 (7570) 1000 (3785)

Silver Eagle 757 DCDA (horizontal and vertical installations)

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 757 DCDA (horizontal and vertical installations)

10

3500 (13 250) 5000 (18 925) 150 (570)

Silver Eagle 757N DCDA/757Na DCDA

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 757N DCDA/757Na DCDA

3

250 (945) 500 (1135) 200 (755)

Silver Eagle 757N DCDA/757Na DCDA

4

500 (1895) 800 (3030) 750 (2840)

Silver Eagle 757N DCDA/757Na DCDA

6

1500 (5680) 2000 (7570) 1000 (3785)

Silver Eagle 757N DCDA

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 757N DCDA

10

3500 (13 250) 5000 (18 925)

Silver Eagle 767 DCDA/767a DCDA (horizontal and vertical installations)

150 (570) 21/2 250 (950) 400 (1515)

FM Approvals

1-234

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation Silver Eagle 767 DCDA/767a DCDA (horizontal and vertical installations)

Valve Size, in.

Flow Rate, gal/min (dm3/min) 150 (570)

Friction Loss, psi (kPa) 3.2 (22) 4.0 (28) 9.3 (65) 2.8 (19) 3.9 (27) 11.0 (76) 2.8 (19) 5.8 (40) 9.0 (62) 2.4 (17) 3.6 (25) 6.4 (44) 3.8 (26) 8.7 (60) 17.0 (115) 4.5 (31) 7.7 (53) 14.8 (100) 3.2 (22) 3.8 (26) 8.1 (56) 3.1 (21) 5.1 (35) 15.2 (105) 3.0 (21) 6.1 (42) 9.5 (66) 2.7 (19) 4.3 (30) 7.8 (54) 4.1 (28) 9.8 (68) 19.8 (135)

3

250 (945) 500 (1895) 200 (755)

Silver Eagle 767 DCDA/767a DCDA (horizontal and vertical installations)

4

500 (1895) 1000 (3785) 750 (2840)

Silver Eagle 767 DCDA (horizontal and vertical installations)

6

1500 (5680) 2000 (7570) 1000 (3785)

Silver Eagle 767 DCDA (horizontal and vertical installations)

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 767 DCDA (horizontal and vertical installations)

10

3500 (13 250) 5000 (18 925) 150 (570)

Silver Eagle 767N DCDA/767Na DCDA

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 767N DCDA/767Na DCDA

3

250 (945) 500 (1135) 200 (755)

Silver Eagle 767N DCDA/767Na DCDA

4

500 (1895) 1000 (3785) 750 (2840)

Silver Eagle 767N DCDA

6

1500 (5680) 2000 (7570) 1000 (3785)

Silver Eagle 767N DCDA

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 767N DCDA

10

3500 (13 250) 5000 (18 925)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-235

Wilkins Operation, Zurn Industries Inc, 1747 Commerce Way, Paso Robles CA 93446

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 100 (380) 350DA (horizontal and vertical installation) 21/2 200 (760) 300 (1135) 300 (1135) 350DA (horizontal and vertical installation) 3 400 (1515) 450 (1705) 500 (1895) 350DA (horizontal and vertical installation) 4 750 (2840) 1000 (3785) 750 (2840) 350DA (horizontal and vertical installation) 6 1250 (4730) 1500 (5680) 1500 (5680) 350DA (horizontal and vertical installation) 8 2000 (7570) 2500 (9465) 2000 (7570) 350DA (horizontal and vertical installation) 10 2750 (10 410) 3500 (13 250) 500 (1895) 350ADA (horizontal and vertical installation) 4 750 (2840) 1000 (3785) 750 (2840) 350ADA (horizontal and vertical installation) 6 1250 (4730) 1500 (5680) 1500 (5680) 350ADA (horizontal and vertical installation) 8 2000 (7570) 2500 (9465) 250 (945) 450DA (n-shaped configuration for horizontal installations) 4 500 (1895) 750 (2840) 750 (2840) 450DA (n-shaped configuration for horizontal installations) 6 1000 (3785) 1500 (5680) Friction Loss, psi (kPa) 9.2 (65) 9.4 (65) 13.3 (90) 9.9 (70) 14.0 (95) 17.0 (115) 5.5 (40) 12.3 (85) 21.3 (145) 3.3 (25) 6.8 (45) 10.4 (70) 4.2 (30) 5.8 (40) 8.9 (60) 6.0 (41) 11.2 (77) 18.1 (125) 5.5 (40) 12.2 (85) 21.3 (145) 3.7 (25) 7.4 (50) 11.1 (75) 4.6 (30) 6.3 (45) 9.3 (65) 3.6 (25) 6.5 (45) 12.5 (85) 3.4 (25) 5.1 (35) 11.5 (80)

FM Approvals

1-236

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 1500 (5680)

Friction Loss, psi (kPa) 5.4 (40) 6.9 (50) 10.2 (70) 6.7 (45) 14.6 (100) 19.9 (135) 6.8 (47) 7.6 (52) 9.8 (68) 7.0 (48) 7.9 (54) 9.7 (67) 8.5 (60) 9.5 (65) 10.6 (75) 7.6 (50) 8.8 (60) 10.4 (70) 8.8 (60) 9.9 (70) 12.2 (85) 11.5 (80) 14.8 (100) 17.0 (115)

450DA (n-shaped configuration for horizontal installations)

8

2000 (7570) 2500 (9465) 2000 (7570)

450DA (n-shaped configuration for horizontal installations)

10

3000 (11 355) 3500 (13 250) 50 (190)

950DA

21/2

150 (570) 275 (1040) 100 (380)

950DA

3

200 (760) 325 (1230) 400 (1515)

950DA

4

500 (1895) 600 (2270) 400 (1515)

950DA

6

800 (3030) 1200 (4545) 1500 (5680)

950DA

8

2000 (7570) 2500 (9465) 3000 (11 355)

950DA

10

4000 (15 140) 4500 (17 035)

Reduced Pressure Principle -- Detector Check Type

A reduced-pressure principle ­ detector check type backflow preventer is an assembly of two internally loaded check valves, which are separated by an intermediate chamber equipped with an automatic relief valve for venting to atmosphere in addition to a metered, internally loaded double check by-pass, and two FM Approved resilient seated NRS or OS&Y gate valves.

Ames Co Inc, 1485 Tanforan Ave, Woodland CA 95776

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 50 (190) 5000 CIV 21/2 150 (570) 250 (945) Friction Loss, psi (kPa) 15.7 (110) 15.1 (105) 18.0 (125)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-237

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 100 (380)

Friction Loss, psi (kPa) 15.0 (105) 15.2 (105) 17.3 (120) 13.0 (90) 14.7 (100) 14.9 (105) 13.8 (95) 14.7 (100) 17.3 (120) 14.9 (105) 16.1 (110) 20.0 (140) 14.2 (100) 15.5 (105) 17.2 (120) 12 (83) 9.7 (67) 12.7 (87.5) 10.8 (74.5) 8.9 (61.5) 9.4 (65) 8.2 (56.5) 10 (69) 16.3 (112.5) 8.8 (60.5) 11.7 (80.5) 12.8 (88.5) 6.5 (45) 8.9 (60) 14.8 (100) 8.9 (60) 15.4 (105) 26.0 (180) 8.3 (55) 10.7 (75) 23.0 (160)

5000 CIV

3

200 (760) 360 (1365) 200 (760)

5000 CIV

4

500 (1895) 750 (2840) 500 (1895)

5000 CIV

6

1000 (3785) 1500 (5680) 1500 (5680)

5000 CIV

8

2000 (7570) 3000 (11 355) 2000 (7570)

5000 CIV

10

3000 (11 355) 4000 (15 140) 50 (190)

5000 SS, 5000 SS RS

21/2

150 (570) 300 (1135) 100 (380)

5000 SS, 5000 SS RS

3

250 (945) 300 (1135) 250 (945)

5000 SS, 5000 SS RS

4

500 (1895) 650 (2460) 1000 (3785)

5000 SS, 5000 SS RS

6

1250 (4730) 1300 (4920) 100 (380)

5001SS, 5001 SS RS

3

250 (945) 500 (1895) 250 (945)

5001SS, 5001 SS RS

4

500 (1895) 750 (2840) 750 (2840)

5001SS, 5001 SS RS

6

1000 (3785) 1500 (5680)

FM Approvals

1-238

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation 5001SS, 5001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

Valve Size, in.

Flow Rate, gal/min (dm3/min) 100 (380)

Friction Loss, psi (kPa) 8.9 (60) 9.1 (65) 15.5 (105) 8.9 (60) 15.9 (110) 26.4 (180) 9.9 (70) 11.1 (75) 23.5 (160) 9.0 (62) 9.2 (63) 12.6 (87) 8.2 (57) 7.9 (54) 12.3 (85) 7.2 (50) 11.2 (77) 21.0 (145) 7.6 (52) 14.5 (100) 22.8 (155) 7.5 (52) 11.7 (81) 19.7 (135) 7.5 (52) 13.0 (90) 23.1 (160) 9.1 (63) 11.2 (77) 18.3 (125) 8.2 (56) 8.0 (55) 12.9 (89) 7.8 (54) 12.7 (88) 23.0 (160)

3

250 (945) 500 (1895) 250 (945)

5001SS, 5001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

4

500 (1895) 750 (2840) 750 (2840)

5001SS, 5001 SS RS (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

6

1000 (3785) 1500 (5680) 150 (570)

Colt 500

21/2

250 (950) 400 (1515) 150 (570)

Colt 500

3

250 (945) 500 (1895) 200 (755)

Colt 500

4

500 (1895) 800 (3030) 750 (2840)

Colt 500

6

1500 (5680) 2000 (7570) 1000 (3785)

Colt 500

8

2000 (7570) 3000 (11 355) 2000 (7570)

Colt 500

10

3500 (13 250) 5000 (18 925) 150 (570)

Colt 500N/500Z

21/2

250 (950) 400 (1515) 150 (570)

Colt 500N/500Z

3

250 (945) 500 (1135) 200 (755)

Colt 500N/500Z

4

500 (1895) 750 (2840)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-239

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 750 (2840)

Friction Loss, psi (kPa) 7.8 (54) 12.4 (85) 19.0 (130) 8.0 (55) 12.5 (86) 19.5 (135) 7.8 (54) 12.0 (83) 17.8 (125) 9.0 (62) 9.2 (63) 12.6 (87) 8.2 (56) 7.9 (54) 12.3 (85) 9.0 (62) 7.4 (51) 12.2 (84) 7.7 (53) 9.2 (63) 12.2 (84) 7.4 (51) 7.8 (54) 11.1 (76) 7.5 (52) 13.0 (90) 23.1 (160) 9.1 (63) 11.2 (77) 18.3 (125) 8.2 (56) 8.0 (55) 12.9 (89) 9.5 (66) 8.8 (61) 19.8 (135)

Colt 500N/500Z

6

1250 (4730) 1700 (6435) 1000 (3785)

Colt 500N/500Z

8

2000 (7570) 2750 (10 410) 2000 (7570)

Colt 500N/500Z

10

3000 (11 355) 4000 (15 140) 150 (570)

Maxim 500

21/2

250 (950) 400 (1515) 150 (570)

Maxim 500

3

250 (945) 500 (1895) 200 (755)

Maxim 500

4

500 (1895) 1000 (3785) 750 (2840)

Maxim 500

6

1500 (5680) 2000 (7570) 1000 (3785)

Maxim 500

8

2000 (7570) 3000 (11 355) 2000 (7570)

Maxim 500

10

3500 (13 250) 5000 (18 925) 150 (570)

Maxim 500N/500Z

21/2

250 (950) 400 (1515) 150 (570)

Maxim 500N/500Z

3

250 (945) 500 (1135) 200 (755)

Maxim 500N/500Z

4

500 (1895) 1000 (3785)

FM Approvals

1-240

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 750 (2840)

Friction Loss, psi (kPa) 8.0 (55) 10.4 (72) 14.4 (100) 7.5 (52) 8.8 (61) 14.0 (96) 7.8 (54) 12.0 (83) 17.8 (125)

Maxim 500N/500Z

6

1500 (5680) 2000 (7570) 1000 (3785)

Maxim 500N/500Z

8

2000 (7570) 3000 (11 355) 2000 (7570)

Maxim 500N/500Z

10

3000 (11 355) 4000 (15 140)

Conbraco Industries Inc, Box 247, Matthews NC 28105

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 300 (1135) 40-700-02 40-700-03 3 400 (1515) 500 (1895) 500 (1895) 40-70A-02 40-70A-03 4 750 (2840) 1000 (3785) 500 (1895) 40-70C-02 40-70C-03 6 1000 (3785) 1200 (4540) 1500 (5680) 40-70E-02 40-70E-03 8 2000 (7570) 3000 (11 355) 1500 (5680) 40-70G-02 40-70G-03 10 2000 (7570) 2500 (9465) 150 (570) Model 4D-700 21/2 250 (950) 400 (1515) 200 (755) Model 4D-700 3 400 (1515) 600 (2270) 500 (1895) Model 4D-700 4 700 (4825) 1000 (3785) Friction Loss, psi (kPa) 16.4 (115) 17.5 (120) 19.0 (130) 14.6 (100) 16.5 (115) 19.3 (135) 14.0 (95) 13.9 (95) 14.5 (100) 14.9 (105) 16.1 (110) 20.3 (140) 14.7 (100) 15.3 (105) 16.1 (110) 11.2 (75) 13.1 (90) 18.0 (125) 10.0 (70) 11.7 (80) 15.1 (105) 9.0 (60) 13.7 (95) 24.2 (165)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-241

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 1000 (3785)

Friction Loss, psi (kPa) 11.1 (75) 20.2 (140) 32.5 (225) 7.0 (50) 10.2 (70) 17.0 (115) 8.8 (60) 16.0 (110) 29.0 (200)

Model 4D-700

6

1500 (5680) 2000 (7570) 1000 (3785)

Model 4D-700

8

2000 (7570) 3000 (11 355) 2000 (7570)

Model 4D-700

10

3000 (11 355) 4000 (15 140)

FEBCO, 3816 S Willow Ave, Fresno CA 93725

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 50 (190) Febco Model 826YD 826YD 21/2 150 (570) 300 (1135) 300 (1135) Febco Model 826YD 826YD 3 400 (1515) 450 (1705) 400 (1515) Febco Model 826YD 826YD 4 500 (1895) 600 (2270) 455 (3615) Febco Model 826YD 826YD 6 1250 (4730) 1580 (5980) 1500 (5680) Febco Model 826YD 826YD 8 2000 (7570) 2500 (9465) 3000 (11 355) Febco Model 826YD 826YD 10 4000 (15 140) 5000 (18 925) Friction Loss, psi (kPa) 16.8 (115) 17.5 (120) 20.8 (145) 16.5 (115) 18.8 (130) 20.2 (140) 15.0 (105) 15.9 (110) 16.8 (115) 13.3 (90) 14.5 (100) 16.0 (110) 13.5 (95) 14.8 (100) 16.4 (115) 16.3 (110) 18.8 (130) 21.6 (150)

Watts Regulator Co, 815 Chestnut St, North Andover MA 01845

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 50 (190) 909RPDA 21/2 150 (570) 250 (945) Friction Loss, psi (kPa) 15.7 (110) 15.1 (105) 18.0 (125)

FM Approvals

1-242

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 100 (380)

Friction Loss, psi (kPa) 15.0 (105) 15.2 (105) 17.3 (120) 13.0 (90) 14.7 (100) 14.9 (105) 13.8 (95) 14.7 (100) 17.3 (120) 14.9 (105) 16.1 (110) 20.0 (140) 14.2 (100) 15.5 (105) 17.2 (120) 13.0 (90) 12.7 (90) 12.3 (85) 14.1 (95) 13.2 (90) 14.1 (95) 11.3 (80) 11.8 (80) 13.3 (90) 11.2 (75) 9.8 (70) 9.0 (60) 14.5 (100) 14.4 (100) 15.1 (105) 13.3 (90) 12.3 (85) 16.5 (110) 13.0 (90) 12.1 (85) 12.9 (90)

909RPDA

3

200 (760) 360 (1365) 200 (760)

909RPDA

4

500 (1895) 750 (2840) 500 (1895)

909RPDA

6

1000 (3785) 1500 (5680) 1500 (5680)

909RPDA

8

2000 (7570) 3000 (11 355) 2000 (7570)

909RPDA

10

3000 (11 355) 4000 (15 140) 200 (760)

990RPDA

4

500 (1895) 750 (2840) 750 (2840)

990RPDA

6

1000 (3785) 1250 (4730) 1500 (5680)

990RPDA

8

2000 (7570) 2500 (9465) 200 (760)

992RPDA

4

500 (1895) 600 (2270) 750 (2840)

992RPDA

6

1000 (3785) 1250 (4730) 1000 (3785)

992RPDA

8

1500 (5680) 2000 (7570) 1500 (5680)

992RPDA

10

2000 (7570) 2500 (9465)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-243

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 50 (190)

Friction Loss, psi (kPa) 12 (83) 9.7 (67) 12.7 (87.5) 10.8 (74.5) 8.9 (61.5) 9.4 (65) 8.2 (56.5) 10 (69) 16.3 (112.5) 8.8 (60.5) 11.7 (80.5) 12.8 (88.5) 6.5 (45) 8.9 (60) 14.8 (100) 8.9 (60) 15.4 (105) 26.0 (180) 8.3 (55) 10.7 (75) 23.0 (160) 8.9 (60) 9.1 (65) 15.5 (105) 8.9 (60) 15.9 (110) 26.4 (180) 9.9 (70) 11.1 (75) 9.0 (62) 9.2 (63) 12.6 (87) 8.2 (57) 7.9 (54) 12.3 (85)

994RPDA, 994 RPDA SR

21/2

150 (570) 300 (1135) 100 (380)

994RPDA, 994 RPDA SR

3

250 (945) 300 (1135) 250 (945)

994RPDA, 994 RPDA SR

4

500 (1895) 650 (2460) 1000 (3785)

994RPDA, 994 RPDA SR

6

1250 (4730) 1300 (4920) 100 (380)

995RPDA, 995 RPDA SR

3

250 (945) 500 (1895) 250 (945)

995RPDA, 995 RPDA SR

4

500 (1895) 750 (2840) 750 (2840)

995RPDA, 995 RPDA SR

6

1000 (3785) 1500 (5680)

995RPDA, 995 RPDA SR (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

100 (380) 3 250 (945) 500 (1895) 250 (945) 4 500 (1895) 750 (2840) 750 (2840) 6 1000 (3785) 150 (570)

995RPDA, 995 RPDA SR (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations) 995RPDA, 995 RPDA SR (n-shaped configuration for horizontal installations and z-shaped configuration for vertical installations)

Silver Eagle 957 RPDA

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 957 RPDA

3

250 (945) 500 (1895)

FM Approvals

1-244

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 200 (755)

Friction Loss, psi (kPa) 7.2 (50) 11.2 (77) 21.0 (145) 7.6 (52) 14.5 (100) 22.8 (155) 7.5 (52) 11.7 (81) 19.7 (135) 7.5 (52) 13.0 (90) 23.1 (160) 9.1 (63) 11.2 (77) 18.3 (125) 8.2 (56) 8.0 (55) 12.9 (89) 7.8 (54) 12.7 (88) 23.0 (160) 7.8 (54) 12.4 (85) 19.0 (130) 8.0 (55) 12.5 (86) 19.5 (135) 7.8 (54) 12.0 (83) 17.8 (125) 9.0 (62) 9.2 (63) 12.6 (87) 8.2 (56) 7.9 (54) 12.3 (85)

Silver Eagle 957 RPDA

4

500 (1895) 800 (3030) 750 (2840)

Silver Eagle 957 RPDA

6

1500 (5680) 2000 (7570) 1000 (3785)

Silver Eagle 957 RPDA

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 957 RPDA

10

3500 (13 250) 5000 (18 925) 150 (570)

Silver Eagle 957N RPDA/957Z RPDA

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 957N RPDA/957Z RPDA

3

250 (945) 500 (1135) 200 (755)

Silver Eagle 957N RPDA/957Z RPDA

4

500 (1895) 750 (2840) 750 (2840)

Silver Eagle 957N RPDA/957Z RPDA

6

1250 (4730) 1700 (6435) 1000 (3785)

Silver Eagle 957N RPDA/957Z RPDA

8

2000 (7570) 2750 (10 410) 2000 (7570)

Silver Eagle 957N RPDA/957Z RPDA

10

3000 (11 355) 4000 (15 140) 150 (570)

Silver Eagle 967 RPDA

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 967 RPDA

3

250 (945) 500 (1895)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-245

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 200 (755)

Friction Loss, psi (kPa) 9.0 (62) 7.4 (51) 12.2 (84) 7.7 (53) 9.2 (63) 12.2 (84) 7.4 (51) 7.8 (54) 11.1 (76) 7.5 (52) 13.0 (90) 23.1 (160) 9.1 (63) 11.2 (77) 18.3 (125) 8.2 (56) 8.0 (55) 12.9 (89) 9.5 (66) 8.8 (61) 19.8 (135) 8.0 (55) 10.4 (72) 14.4 (100) 7.5 (52) 8.8 (61) 14.0 (96) 7.8 (54) 12.0 (83) 17.8 (125)

Silver Eagle 967 RPDA

4

500 (1895) 1000 (3785) 750 (2840)

Silver Eagle 967 RPDA

6

1500 (5680) 2000 (7570) 1000 (3785)

Silver Eagle 967 RPDA

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 967 RPDA

10

3500 (13 250) 5000 (18 925) 150 (570)

Silver Eagle 967N RPDA/967Z RPDA

21/2

250 (950) 400 (1515) 150 (570)

Silver Eagle 967N RPDA/967Z RPDA

3

250 (945) 500 (1135) 200 (755)

Silver Eagle 967N RPDA/967Z RPDA

4

500 (1895) 1000 (3785) 750 (2840)

Silver Eagle 967N RPDA/967Z RPDA

6

1500 (5680) 2000 (7570) 1000 (3785)

Silver Eagle 967N RPDA/967Z RPDA

8

2000 (7570) 3000 (11 355) 2000 (7570)

Silver Eagle 967N RPDA/967Z RPDA

10

3000 (11 355) 4000 (15 140)

Wilkins Operation, Zurn Industries Inc, 1747 Commerce Way, Paso Robles CA 93446

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) 100 (380) 375DA 21/2 200 (760) 300 (1135) Friction Loss, psi (kPa) 15.0 (105) 16.8 (115) 18.7 (130)

FM Approvals

1-246

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 300 (1135)

Friction Loss, psi (kPa) 16.5 (115) 21.0 (145) 25.5 (175) 9.0 (60) 13.1 (90) 20.8 (145) 7.3 (50) 10.2 (70) 12.6 (85) 12.0 (80) 13.2 (90) 15.5 (150) 12.7 (88) 16.6 (114) 22.2 (153) 9.0 (60) 13.1 (90) 20.8 (145) 7.3 (50) 10.2 (70) 12.6 (85) 12.0 (80) 13.2 (90) 15.5 (150) 10.5 (95) 10.1 (70) 15.4 (105) 7.4 (50) 9.0 (60) 14.0 (95) 11.7 (80) 13.7 (95) 17.2 (120) 13.2 (90) 14.4 (100) 16.0 (110)

375DA

3

400 (1515) 500 (1895) 500 (1895)

375DA

4

750 (2840) 1000 (3785) 750 (2840)

375DA

6

1200 (4540) 1500 (5680) 1500 (5680)

375DA

8

2000 (7570) 2500 (9465) 2000 (7570)

375DA

10

2750 (10 410) 3250 (12 300) 500 (1895)

375ADA

4

750 (2840) 1000 (3785) 750 (2840)

375ADA

6

1200 (4540) 1500 (5680) 1500 (5680)

375ADA

8

2000 (7570) 2500 (9465)

475DA, 475DAV (475DA is an n-shaped configuration for horizontal installation; 475DAV is an z-shaped configuration for vertical installation) 475DA, 475DAV (475DA is an n-shaped configuration for horizontal installation; 475DAV is an z-shaped configuration for vertical installation) 475DA, 475DAV (475DA is an n-shaped configuration for horizontal installation; 475DAV is an z-shaped configuration for vertical installation)

250 (945) 4 500 (1895) 750 (2840) 750 (2840) 6 1000 (3785) 1500 (5680) 1500 (5680) 8 2000 (7570) 2500 (9465) 50 (190)

975DA

21/2

150 (570) 250 (945)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-247

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min) 100 (380)

Friction Loss, psi (kPa) 12.9 (90) 13.9 (95) 16.4 (115) 13.4 (90) 14.5 (100) 17.5 (120) 13.2 (90) 14.2 (100) 16.0 (110) 14.0 (95) 15.5 (105) 17.1 (120) 14.3 (100) 14.8 (100) 15.3 (105)

975DA

3

200 (755) 350 (1325) 200 (760)

975DA

4

350 (1325) 650 (2460) 500 (1895)

975DA

6

750 (2840) 1200 (4540) 1000 (3785)

975DA

8

1500 (5680) 2000 (7570) 1500 (5680)

975DA

10

2000 (7570) 2500 (9465)

FIRE SERVICE METERS

Where local waterworks authorities require the installation of full registration metering devices on public water connections to private fire protection systems, meters especially designed for fire protection service should be used. Unless otherwise noted in the listing, these meters have 175 psi (1205 kPa) rated working pressure.

ABB Ltd, Oldends Lane, Stonehouse, Gloucestershire GL10 3TA, United Kingdom

Aquamaster FS (Fire Service) Model Code MM/GFabcdefgUh4Aijklmn Full Bore Fire Service Meter Assembly 3, 4, 6 and 8 in. NPS. (80, 100, 150 and 200 mm). 95-240 VAC and/or battery powered display. 225 psi (1550 kPa) rated working pressure.

a = Language code. b = 0080, 0100, 0150 or 0200 bore diameter (mm). c = Display and sensor configuration. d = 0, A, B, C, D or L power supply. e = 2 or C enclosure options. f = Cable length. g = Label type. h = Cable connection type. i = Electrode material. j = Options. k = Communication protocol. l = Data protocol. m = Pressure transducer option. n = Pressure span.

Aquamaster FC (Fire Service Coned) Model Code MM/GAabcdefgUh4Aijklmn Reduced Throat Bore Fire Service Meter Assembly 3, 4, 6, 8 and 10 in. NPS (80, 100, 150, 200, and 250 mm). 95-240 VAC and/or battery powered display. 175 psi (1205 kPa) rated working pressure.

a = Language code. b = 0080, 0100, 0150, 0200, or 0250 bore diameter (mm). c = Display and sensor configuration. d = 0, A, B, C, D, or L power supply. e = 2 or C enclosure options. f = Cable length. g = Label type. h = Cable connection type. I = Electrode material. j = Options. k = Communication protocol. l = Data protocol. m = Pressure transducer option. n = Pressure span.

FM Approvals

1-248

September 2007 -- Approval Guide Automatic Sprinkler Systems

ABB Water Meters Inc, 1100 SW 38th Ave, Ocala FL 34478

Fire Service Compound Turbine Meter Assembly. Consists of Arad Ltd. Dalia Strainer, Model FSM-3 turbine meter with detector check valve and a bypass line. Sizes 4, 6, 8 in. NPS.

AMCO Water Metering Systems, 1100 SW 38th Ave, Ocala FL 34474

Model F4000 Fire Service Compound Turbine Meter Assembly. Sizes 4, 6, 8 and 10 in. NPS. Consists of a Model AFSS strainer, AMCO main turbine meter and register, a Model 1000 DCV detector check valve, and a bypass line which includes an AMCO Model C700 bypass meter and register.

Ames Company Inc, 1485 Tanforan Ave, Woodland CA 95776

Model T 4000 Fire Service Compound Turbine Meter Assembly. Sizes 4, 6, 8 and 10 in. NPS. Consists of a Model AFSS strainer, AMCO main turbine meter and register, a Model 1000 DCV detector check valve, and a bypass line which includes an AMCO Model C700 bypass meter and register.

Arad Ltd Dalia, 19239 Doar Dalia, Kibbutz Dalia, Israel

Fire Service Compound Turbine Meter Assembly. 4 in. NPS. Consists of Model ST-4A Strainer, Model FSM-4A turbine meter with detector check valve and a bypass line. Fire Service Compound Turbine Meter Assembly. 6 in. NPS. Consists of Model ST-6A Strainer, Model FSM-6A turbine meter with detector check valve and a bypass line. Fire Service Compound Turbine Meter Assembly. 8 in. NPS. Consists of Model ST-8A Strainer, Model FSM-8A turbine meter with detector check valve and a bypass line. Fire Service Turbine Meter Assembly. 4 in. NPS. Consists of Model ST-4A Strainer and Model MMT-4A turbine meter. Fire Service Turbine Meter Assembly. 6 in. NPS. Consists of Model ST-6A Strainer and Model MMT-6A turbine meter. Fire Service Turbine Meter Assembly. 8 in. NPS. Consists of Model ST-8A Strainer and Model MMT-8A turbine meter.

Badger Meter Inc, 4545 W Brown Deer Rd, Milwaukee WI 53223

Model FSAA-01 Fire Service Compound Turbine Meter Assembly. 4, 6, 8, 10 and 12 in. NPS. Consists of a Model FSSA-01 Strainer, a Series TSM turbine meter, a Model DCA-01 detector check valve and a bypass line. Model FSMA-01 Fire Service Turbine Meter Assembly. 3, 4, 6, 8 and 10 in. NPS. Consists of a Model FSSA-01 Strainer and a Series TSM turbine meter.

Hersey Meters, Division of Mueller Group Inc, Hwy 70, Box 128, Cleveland NC 27013

Models MFM 11/MCT 11, MFM 11/MHR, MFM 11/MVR. 3, 4, 6, 8, 10 in. (76, 102, 152, 203, 254 mm). Model MFM II/Horizon. 4, 6, 8, 10, 12 in. (102, 152, 203, 254, 305 mm). Horizon Fire Service Turbine Meter Assembly. 4, 6 and 8 in. NPS. Consists of Mueller Steam Model 595 Strainer and a Hersey Horizon turbine meter.

Master Meter, 101 Regency Pkwy, Mansfield TX 76063

Model No. MMFSC Fire Service Compound Turbine Meter Assembly. 4 in. NPS. Consists of Model 908 400 FSS Strainer, Model FSM-4A turbine meter with detector check valve and bypass line. Model No. MMFSC Fire Service Compound Turbine Meter Assembly. 6 in. NPS. Consists of Model 908 600 FSS Strainer, Model FSM-6A turbine meter with detector check valve and bypass line. Model No. MMFSC Fire Service Compound Turbine Meter Assembly. 8 in. NPS. Consists of Model 908 800 FSS Strainer, Model FSM-8A turbine meter with detector check valve and bypass line. Model No. MMFST Fire Service Turbine Meter Assembly. 4 in. NPS. Consists of Model 908 400 FSS Strainer and Model MMT-4A turbine meter. Model No. MMFST Fire Service Turbine Meter Assembly. 6 in. NPS. Consists of Model 908 600 FSS Strainer and Model MMT-6A turbine meter. Model No. MMFST Fire Service Turbine Meter Assembly. 8 in. NPS. Consists of Model 908 800 FSS Strainer and Model MMT-8A turbine meter.

Metron-Farnier LLC, 5665 Airport Blvd, Suite 105, Boulder CO 80301

Enduro Class Fire Service Meter Assembly. 6 and 8 in. The Enduro Class Fire Service Meter Assembly consists of an Ames Company Model AFSS strainer and an Enduro class turbine meter.

Neptune Technology Group Inc, 1600 Alabama Hwy 229 S, Tallassee AL 36078

HP Fire Service Turbine Cold Water Meter. 3, 4, 6, 8, 10 in. These meters must be installed and are supplied with an Approved strainer. HP Protectus III Fire Service and Cold Water Meter. 4, 6, 8, 10 in. Consists of strainer, fire service turbine, detector check valve and bypass loop with gate valve, check valve and trident meter for low flows.

Sensus Metering Systems, 9495 Delegates Drive, Orlando FL 32837

Compact Fireline Meter Assembly. 4 in. Consists of Model FS-4C strainer, Model W-1000 turbine meter, FM Approved detector check valve and by-pass loop. Compact Fireline Meter Assembly. 6 in. Consists of Model FS-6C strainer, Model W-2000 turbine meter, FM Approved detector check valve and by-pass loop. Compact Fireline Meter Assembly. 8 in. Consists of Model FS-8C strainer, Model W-3500 turbine meter, FM Approved detector check valve and by-pass loop. Compact Fireline Meter Assembly. 10 in. Consists of Model FS-10C strainer, Model W-5500 turbine meter, FM Approved detector check valve and by-pass loop. By-pass loop for above assemblies consists of ball valves, check valve and Model W-160 turbine meter for low flows. Compact Fire Service Meter Assembly. 4 in. Consists of Model FS-4C strainer and Model W-1000 turbine meter. Compact Fire Service Meter Assembly. 6 in. Consists of Model FS-6C strainer and Model W-2000 turbine meter. Compact Fire Service Meter Assembly. 8 in. Consists of Model FS-8C strainer and Model W-3500 turbine meter. Compact Fire Service Meter Assembly. 10 in. Consists of Model FS-10C strainer and Model W-5500 turbine meter. Models W-2000, W-3500 and W-5500 turbine meters must be installed with Models FS-6C, FS-8C and FS-10C strainers, respectively.

WATERFLOW DETECTOR CHECK VALVES

Where the waterworks authorities require metering devices on connections used only for fire service, there are instances where the indication of waterflow is considered of greater importance than knowing the actual amount of water used. When acceptable to the authorities, supervision of a fire service connection is best accomplished by means of a FM Approved waterflow detector check valve. Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-249

Ames Co Inc, 1485 Tanforan Ave, Woodland CA 95776

Product Designation Valve Size, in. Flow Rate, gal/min (dm3/min) Friction Loss, psi (kPa)

2000 DC

4

6

8

10

1000 DCV

4

6

8

10

1000 SS DCV

8

10

300 (1135) 500 (1895) 750 (2840) 1000 (3785) 1300 (4920) 1500 (5680) 2500 (9465) 3000 (11 355) 3100 (11 735) 4000 (15 140) 4900 (18 550) 5500 (20 820) 500 (1895) 750 (2840) 1000 (3785) 1000 (3785) 1500 (5680) 1750 (6625) 1500 (5680) 1750 (6625) 2500 (9465) 3000 (11 355) 4000 (15 140) 5000 (18 925) 1500 (5680) 1750 (6625) 2500 (9465) 3000 (11 355) 4000 (15 140) 5000 (18 925)

7.9 (54.5) 8.2 (56.5) 11.5 (78.5) 9.1 (62.5) 9.8 (67.5) 10.2 (70.5) 10.7 (74.0) 15.5 (107.0) 16/1 (111.0) 25.5 (176.0) 36.0 (248.0) 44.0 (303.5) 2.9 (20.0) 3.0 (21.0) 5.1 (35.5) 4.0 (27.5) 3.6 (25.0) 3.0 (21.0) 3.4 (23.5) 3.3 (23.0) 3.2 (22.0) 1.9 (13.0) 1.9 (13.0) 2.5 (17.0) 3.4 (23.5) 3.3 (23.0) 3.2 (22.0) 1.9 (13.0) 1.9 (13.0) 2.5 (17.0)

Badger Meter Inc, 4545 W Brown Deer Rd, Milwaukee WI 53223

DCA-01 4 500 (1895) 750 (2840) 1000 (3785) 1000 (3785) 1500 (5680) 1750 (6625) 1500 (5680) 1750 (6625) 2500 (9465) 2.9 (20.0) 3.0 (21.0) 5.1 (35.5) 4.0 (27.5) 3.6 (25.0) 3.0 (21.0) 3.4 (23.5) 3.3 (23.0) 3.2 (22.0)

6

8

FM Approvals

1-250

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min)

Friction Loss, psi (kPa)

10

3000 (11 355) 4000 (15 140) 5000 (18 925)

1.9 (13.0) 1.9 (13.0) 2.5 (17.0)

Danfoss Flomatic Corporation, 15 Pruyn's Island Drive, Glens Falls NY 12801

SDC 4 500 (1895) 800 (3030) 1200 (4540) 1100 (4165) 1800 (6815) 2200 (8325) 2.8 (19)) 4.0 (28) 9.9 (68) 2.0 (14) 5.0 (34) 8.7 (60)

6

FEBCO, 3816 S Willow Ave, Fresno CA 93725

800* 4 500 (1895) 750 (2840) 1000 (3785) 1000 (3785) 1500 (5680) 1750 (6625) 1595 (6040) 2070 (7835) 2540 (9615) 3060 (11 580) 4210 (15 935) 4880 (18 470) 1.7 (11.7) 3.4 (23.4) 5.8 (40.0) 1.9 (13.1) 3.5 (24.1) 4.6 (31.7) 1.7 (11.7) 2.5 (17.2) 3.2 (22.1) 2.5 (17.2) 3.5 (24.1) 4.5 (31.0)

6

8

10

*250 psi (1725 kPa) working pressure.

Hersey Meters, Division of Mueller Group Inc, Hwy 70, Box 128, Cleveland NC 27013

DC 2 140 (530) 175 (660) 220 (835) 250 (945) 400 (1515) 600 (2270) 500 (1895) 750 (2840) 1000 (3785) 1000 (3785) 1500 (5680) 2000 (7570) 2000 (7570) 3000 (11 355) 1.1 (8.0) 1.4 (10.0) 1.7 (12.0) 1.0 (7.0) 1.9 (13.0) 4.6 (32.0) 1.7 (12.0) 2.5 (17.0) 3.3 (23.0) 1.6 (11.0) 2.2 (15.0) 2.6 (18.0) 1.7 (12.0) 2.4 (16.5)

3

EDC

4

6

8

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-251

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min)

Friction Loss, psi (kPa)

10

EDC II

8

EDC III

4

6

8

10

EDC IV

3

4

6

8

10

4000 (15 140) 2250 (8515) 4500 (17 035) 6750 (25 550) 2000 (7570) 3000 (11 355) 4000 (15 140) 500 (1905) 750 (2840) 1000 (3785) 1000 (3785) 1500 (5700) 2000 (7550) 1500 (5700) 2000 (7550) 2500 (9455) 2250 (8515) 4500 (17 035) 6000 (22 710) 200 (757) 400 (1514) 600 (2270) 800 (3030) 500 (1893) 750 (2839) 1000 (3785) 1000 (3785) 1500 (5678) 2000 (7570) 1500 (5678) 3000 (11 355) 4000 (15 140) 2250 (8516) 4500 (16 843) 6750 (25 550)

3.1 (21.5) 1.6 (11.0) 2.2 (15.0) 2.6 (18.0) 1.7 (12.0) 2.4 (16.5) 3.1 (21.5) 2.5 (17.0) 2.6 (18.0) 2.0 (14.0) 2.5 (17.0) 3.0 (21.0) 4.0 (27.5) 1.8 (12.5) 2.0 (14.0) 2.0 (14.0) 1.6 (11.0) 1.5 (10.5) 1.6 (11.0) 2.6 (18.1) 3.0 (20.9) 2.4 (16.8) 3.0 (20.9) 1.1 (7.9) 2.5 (16.9) 4.1 (28.6) 1.8 (12.2) 1.9 (12.9) 3.2 (22.1) 3.2 (22.1) 2.4 (16.5) 3.9 (26.9) 2.9 (20.0) 2.5 (17.2) 4.9 (33.8)

Sensus Metering Systems, 9495 Delegates Drive, Orlando FL 32837

E 4 500 (1905) 750 (2840) 1000 (3785) 1000 (3785) 3.7 (26) 4.7 (32) 8.1 (56) 2.7 (18)

6

FM Approvals

1-252

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Valve Size, in.

Flow Rate, gal/min (dm3/min)

Friction Loss, psi (kPa)

8

10

1500 (5700) 2000 (7550) 2000 (7570) 2500 (9465) 3000 (11 355) 2250 (8515) 4500 (17 035) 6750 (25 550)

3.2 (22) 4.5 (31) 2.2 (15) 2.4 (17) 2.6 (18) 1.6 (11) 2.4 (16) 2.9 (20)

Watts Regulator Co, 815 Chestnut St, North Andover MA 01845

07-F 4 500 (1895) 750 (2840) 1000 (3785) 1000 (3785) 1500 (5680) 1900 (7190) 1400 (5300) 1800 (6815) 2400 (9085) 3500 (13 250) 4500 (17 035) 5500 (20 820) 500 (1895) 750 (2840) 1000 (3785) 750 (2840) 1000 (3785) 1500 (5680) 1500 (5680) 1750 (6625) 2500 (9465) 3000 (11 355) 4000 (15 140) 5000 (18 925) 3.0 (20) 4.4 (30) 7.6 (50) 1.6 (10) 3.4 (25) 5.6 (40) 2.1 (15) 1.4 (10) 2.3 (15) 2.2 (15) 3.6 (25) 5.4 (35) 1.9 (13.0) 4.4 (30.0) 8.0 (55.0) 1.2 (8.0) 1.8 (12.0) 4.0 (28.0) 3.4 (23.5) 3.3 (23.0) 3.3 (22.0) 1.9 (13.0) 1.9 (13.0) 2.5 (17.0)

6

8

10

SS07F

4

6

8

10

Wilkins Operation, Zurn Industries Inc, 1747 Commerce Way, Paso Robles CA 93446

Model 310 4 300 (1135) 500 (1895) 750 (2840) 1000 (3785) 1500 (5680) 2000 (7570) 1.0 (6.9) 2.3 (16) 4.6 (32) 1.6 (11) 3.2 (22) 5.4 (37)

6

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-253

SUCTION PRESSURE REGULATING VALVES for Booster Pumps

Suction pressure regulating valves are used with booster pumps in fire protection systems when local authorities require that a minimum suction pressure be maintained. The valve is installed in the discharge line of the booster pump. The pump suction pressure is monitored through a pressure line to the controlling mechanism of the regulating valve.

Cla-Val Co, Box 1325, Newport Beach CA 92659

Model 50B-5KG. 3, 4, 6, 8 in. NPS.

Model No. Valve Size, in. Flow Rate, gal/min (dm3/min) Friction Loss, psi (kPa)

50B-5KG 50B-5KG 50B-5KG 50B-5KG

3 4 6 8

400 (1500) 750 (2800) 1500 (5700) 3000 (11 400)

14 (100) 20 (140) 21 (145) 20 (140)

Size 3 in. available with NPT ends rated at 400 psi (2760 kPa). Sizes 3, 4, 6, 8 in. available with 150 lb F.F. flanges rated at 250 psi (1725 kPa). Sizes 3, 4, 6, 8 in. available with 300 lb R.F. flanges rated at 400 psi (2260 kPa). Sizes 80, 100, 150, 200 mm available with ISO PN10, PN16, PN25 flanges rated at 12, 16, 25 bar (175, 232, 363 psi) respectively. All above models available with white epoxy coating on body. Add suffix -KC to model no. Available ANSI flanged body connections are as follows: Class 300 inlet, Class 150 outlet; 250 psi rated working pressure, Class 300 inlet, Class 300 outlet; 400 psi rated working pressure, Class 150 inlet, Class 150 outlet; 250 psi rated working pressure.

OCV Control Valves, 7400 E 42nd Place, Tulsa OK 74145

Model 108 FPS Globe valves and Model 108FPSA Angle valves. Sizes 3, 4, 6, and 8 in. NPS. Hydraulically operated, diaphragm ­ actuated valves. Suction pressure adjustment range is 5 psi (35 kPa) to 30 psi (207 kPa). Available with ANSI flanged body connections as follows: Class 150 inlet by Class 150 outlet, Class 300 inlet by Class 150 outlet, rated working pressure is 250 psi (1725 kPa). Class 300 inlet by Class 300 outlet, rated working pressure is 450 psi (3103 kPa). Friction Loss: Models 108FC and 108FPS Globe Valves

Valve Size, in. Flow Rate, gal/min (dm3/min) Friction Loss, psi (kPa)

3 4 6 8

400 750 1500 3000

16 (110) 13 (90) 11 (76) 16 (110)

Models 108FCA and 108FPSA Angle Valves

Valve Size, in. Flow Rate, gal/min (dm3/min) Friction Loss, psi (kPa)

3 4 6 8

400 750 1500 3000

9 (62) 7 (48) 5 (35) 9 (62)

Watts/ACV, Box 752289, Houston TX 77275

Model No. Valve Size, in. Flow Rate, gal/min (dm3/min) Friction Loss, psi (kPa)

116-1FM

4 6 8

750 (2800) 1500 (5700) 3000 (11 400)

17 (115) 16 (110) 14 (100)

Sizes 4 and 6 in. NPS valves available with ANSI Class 125 and 250 rated flanges. 8 in. NPS valves available with ANSI Class 125 rated flanges only. ANSI Class 125 valves have a rated working pressure of 175 psi (1205 kPa). ANSI Class 250 valves have a rated working pressure of 300 psi (2070 kPa).

FM Approvals

1-254

September 2007 -- Approval Guide Automatic Sprinkler Systems

Model No.

Valve Size, in.

Flow Rate, gal/min (dm3/min)

Friction Loss, psi (kPa)

Watts Regulator Co, 815 Chestnut St, North Andover MA 01845

PV60GFM 4 6 8 750 (2800) 1500 (5700) 3000 (11 400) 17 (115) 16 (110) 14 (100)

Sizes 4 and 6 in. NPS valves available with ANSI Class 125 and 250 rated flanges. 8 in. NPS valves available with ANSI Class 125 rated flanges only. ANSI Class 125 valves have a rated working pressure of 175 psi (1205 kPa). ANSI Class 250 valves have a rated working pressure of 300 psi (2070 kPa).

FIRE SERVICE CONNECTIONS

A fire service pumper connection, located outside buildings, permits the fire service to pump water into a sprinkler system from a nearby public hydrant or reservoir. Water supplied at high pressure will aid automatic sprinklers to control a fire. The connection may also be used to supply building standpipes. FM Approved connections are made of bronze and consist of two inlet couplings threaded for standard fire hose and siamesed into an outlet pipe connection. A check valve is provided in each inlet so that either connection may be used separately. The connections are available in straight, 45° or 90° patterns. Unless otherwise noted in the listing, these connections have 175 psi (1205 kPa) rated working pressure.

A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d'Opaglio, Italy

Fig. No. Component Description Nominal Size, Inlets×Outlet, in.

A101 A102

300 psi (2070 kPa) rated working pressure.

Straightway Siamese 90° Siamese

3×3×4 3×3×4

Ban Chang Hardware Co Ltd, 17 Lane 620, Sec 3 Lu Ho Rd, Lu Kang Chang Hua, Taiwan ROC

Fig. No. Component Description Nominal Size, Inlets×Outlet, in.

86A 86B

Straightway Single Clapper 90° Single Clapper

21/2×21/2×4 21/2×21/2×4

These connections have a 300 psi (2070 kPa) rated working pressure.

Fig. No. Component Description Nominal Size, Inlets×Outlet, in.

B87 B88

90° Double Clapper Straight Double Clapper

21/2×21/2×4 21/2×21/2×4

Model 614. Sprinkler System Alarm Tester. 1 and 11/4 in. NPT female threaded inlet with male threaded outlet. 1/2 in. nominal orifice. 175 psi (1205 kPa) rated working pressure.

Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446

Fig. No. Component Description Nominal Size, Inlets×Outlet, in.

Fig. No. 86A 86B

Component Description Straightway Single Clapper 90° Single Clapper

Nominal Size, Inlets×Outlet, in. 21/2×21/2×4 21/2×21/2×4

These connections have a 300 psi (2070 kPa) rated working pressure.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-255

Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620

Fig. No. Component Description Nominal Size, Inlets×Outlet, in.

Model 21-132 Model 21-203 Model 21-133 Model 21-207 Model 21-201* Model 21-132** Model 21-133**

*250 psi (1725 kPa) rated working pressure.

Double Check, Straightway Siamese Double Check, Straightway Siamese Double Check, 90° Siamese Double Check, 90° Siamese Single Check, Straightway Siamese Straightway Siamese Dual Clapper 90° Siamese Dual Clapper

21/2×21/2×4 21/2×21/2×4 21/2×21/2×4 21/2×21/2×4 21/2×21/2×4 3×3×4 3×3×4

**These connections are FM Approved for hose threads conforming to the standard for hose coupling screw threads, ANSI B2.4 or the Engineering Division, Dept. of Purchase, City of New York, Specification No. 2103b, and outlet conforming to 8 threads per in. per ANSI B2.1. Nominal Size, Inlets×Outlet, in.

Fig. No.

Component Description

``Powhatan'' Model 21-201* ``Powhatan'' Model 21-132 ``Powhatan'' Model 21-203 ``Powhatan'' Model 21-132** ``Powhatan'' Model 21-133 ``Powhatan'' Model 21-207 ``Powhatan'' Model 21-133**

*250 psi (1725 kPa) rated working pressure.

Single Check, Straightway Siamese Double Check, Straightway Siamese Double Check, Straightway Siamese Straightway Siamese Dual Clapper Double Check, 90° Siamese Double Check, 90° Siamese 90° Siamese Dual Clapper

21/2×21/2×4 21/2×21/2×4 21/2×21/2×4 3×3×4 21/2×21/2×4 21/2×21/2×4 3×3×4

**These connections are FM Approved for hose threads conforming to the standard for hose coupling screw threads, ANSI B2.4 or the Engineering Division, Dept. of Purchase, City of New York, Specification No. 2103b, and outlet conforming to 8 threads per in. per ANSI B2.1.

Elkhart Brass Mfg Co Inc, 1302 W Beardsley Ave, Elkhart IN 46514

Fig. No. Component Description Nominal Size, Inlets×Outlet, in.

10 11 12 15 & 16 155 & 156 165 166

90° Sidewalk Siamese Straightway Siamese '' (Female Connections) Sidewalk Siamese (Male Connections) (With Sill Cock) Wall Siamese (Without Sill Cock) (With Sill Cock) Flush Siamese (Without Sill Cock)

21/2×21/2×4, 6 21/2×21/2×4 21/2×21/2×4, 6 21/2×21/2×4, 5, 6 21/2×21/2×4, 5, 6

21/2×21/2×4, 5, 6

21/2×21/2×4, 5, 6

Fire Protection Products Inc, 6241 Yarrow Dr, Suite A, Carlsbad CA 92009-1541

Fig. No. Component Description Nominal Size, Inlets×Outlet, in.

09-501 09-500

90° Single Clapper Straightway Single Clapper

21/2×21/2×4 21/2×21/2×4

FM Approvals

1-256

September 2007 -- Approval Guide Automatic Sprinkler Systems

A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d'Opaglio, Italy

Fig. No. Component Description Nominal Size, Inlets×Outlet, in.

A95 A96 A105 A106

Straightway Siamese 90° Siamese Straightway Siamese 90° Siamese

21/2×21/2×4 21/2×21/2×4 21/2×21/2×4 21/2×21/2×4

Grinnell Corp, 3 Tyco Park, Exeter NH 03833

Fig. No. Component Description Nominal Size, Inlets×Outlet, in.

Grinnell or Gem F-715 F-716 F-717 1682 1683 1684 Straightway 45°Connection 90°Connection Straightway 45°Connection 90°Connection 21/2×21/2×4 21/2×21/2×4 21/2×21/2×4 21/2×21/2×4 3×3×4 21/2×21/2×4 21/2×21/2×4

Potter-Roemer Inc, 15125 Proctor Avenue, Box 3527, City of Industry CA 91744-0527

Fig. No. Component Description Nominal Size, Inlets×Outlet, in.

5710 5715

Straightway Siamese 90° Siamese

21/2×21/2×4 21/2×21/2×4

Shuenn Cherng Industrial Co Ltd, 113 Tsao-Kang Lane, Tsao-Jong Lee Lukang, Chang Hua Hsien 505, Taiwan ROC

Fig. No. Component Description Nominal Size, Inlets×Outlet, in.

22D 21S

90° Single Clapper Straightway Single Clapper

21/2×21/2×4 21/2×21/2×4

Wilson & Cousins Interior Fire Protection, 4390 Paletta Court, Burlington, Ontario L7L 5R2 Canada

Fig. No. Component Description Nominal Size, Inlets×Outlet, in.

IE-33S

Straightway Single Clapper Female Connection 90° Single Clapper Female Connection

21/2×21/2×4

IE-34S

21/2×21/2×4

Zhejiang Slion Brass-Craft Manufacturing Co Ltd, 256 Chuyou South Rd Chumen, Yuhuan, Zhejiang, China 317605

Fig. No. Component Description Nominal Size, Inlets×Outlet, in.

8511030

Straightway Single Clapper Female Connection 90° Single Clapper Female Connection

21/2×21/2×4

8511031

21/2×21/2×4

These connections have a 300 psi (2070 kPa) rated working pressure.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-257

BALL DRIPS

Ball drips are designed to automatically drain off water which may leak into piping that must be kept free of water. A common use is on fire service pumper connections or the trim of dry pipe valves. The ball drip is normally open and closes when the flow of water through is between 4 and 10 gal/min (15 through 40 dm3/min). Unless otherwise noted in the listing, these ball drips have a rated working pressure of 175 psi (1205 psi).

Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620

``Automatic'' Model A. 1/2 in. NPS.

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Model C. 1/2, 3/4 in. NPS.

Tyco Fire Products, 451 N Cannon Ave, Lansdale PA 19446

Model AD-2. 1/2 in. NPS.

WATER MOTOR GONGS

Water motor gongs give a locally audible alarm signal when the automatic sprinkler system operates. They may be used with waterflow alarm, dry pipe, or automatic water control valves.

Angus Fire Sprinklers, Thame Park Rd, Oxfordshire OX9 3RT, United Kingdom

Model D. Model E. Limited to installations where freezing temperatures are not anticipated. Model F. Available with British Standard threads.

Central Sprinkler Co, 451 N Cannon Ave, Lansdale PA 19446

Models F, F-1.

Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620

``Automatic'' Model 168. ``Automatic'' Model 168-200.

GW Sprinkler A/S, Kastanievej 15, DK-5620 Glamsbjerg, Denmark

Model C. Model D. Model E. Limited to installations where freezing temperatures are not anticipated.

Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658

Models C, E, F. Model WM. Single gong. Model WM-2. Double gong.

Jomos Brandschutz AG, Sagmattstrasse 5, CH-4710 Balsthal, Switzerland

Model No. PM 12 3569 93, AG2.

Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840 Bad Oldesloe, Germany

Model No. PM 12 3569 93, AG2.

Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313

Model C.

Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154

Model CD.

Tyco Fire Products, 451 N Cannon Ave, Lansdale PA 19446

Model WMA-1. U.S. and European versions available.

Venus Fire Protection Ltd, 4105 Portland Blvd, Sherbrooke, Quebec J1L 1X9, Canada

Astra Model E.

Victaulic Company, Box 31, Easton PA 18044

Model 168-205. Series 760 Water Motor Alarm.

The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058

Models No. F-1, F-2.

FM Approvals

1-258

September 2007 -- Approval Guide Automatic Sprinkler Systems

HUBLESS PIPE COUPLINGS

Hubless pipe couplings are used with hubless cast iron or steel pipe in drain, waste, vent, sewer, rainwater or storm drain systems. These couplings may be used above ground when the piping system is adequately supported and braced, and below ground when the system is laid on a continuous firm bed, concrete or other adequate supports. Any required clamps, restraints or supports should be installed or framed prior to careful placement of backfill and should conform to the requirements of the authority having jurisdiction.

Clamp-All Products Corp, c/o Torca Products Inc, 2430 E Walton Blvd, Auburn Hills MI 48326

CLAMP-ALL ``Hi-Torq-125.'' Stainless steel band style clamp with neoprene sleeve. 11/2, 2, 3, 4, 5, 6, 8, 10, 12 and 15 in. Nominal sizes. 15 psi (105 kPa) working pressure. CLAMP-ALL ``Hi-Torq-80.'' Stainless steel band style clamp with neoprene sleeve. 11/2, 2, 3, 4, 5, 6, 8, 10 in. Nominal sizes. 15 psi (105 kPa) working pressure. Four largest sizes may require restraint per manufacturer's instructions.

GROOVED COUPLINGS

Grooved couplings are used to join pipe and fittings in both wet and dry sprinkler systems. Unless otherwise noted, these couplings are intended to provide some flexibility in piping systems. Typical applications are in sprinkler risers, in feed mains passing through walls from one building area to another, in locations subject to earthquakes, in the discharge line from aboveground pump suction tanks, in new connections to existing feed mains and in air or water fire service lines subject to excessive vibration or difficult alignment. Unless otherwise noted, these couplings are limited to use with rolled or cut groove-ended pipe, valves and fittings, at a minimum rated working pressure of 175 psi (1205 kPa) and are suitable for aboveground service. Higher rated pressures are noted in the text of the listing. Selection of pipe schedules for use with grooved pipe couplings should be made according to applicable FM Global Property Loss Prevention Data Sheets installation standards. These pipe schedules determine system pressure ratings and may take precedence over the higher rated working pressures listed for some couplings. Installation must be made according to the manufacturer's instructions and requirements. Where couplings are used to join FM Approved pipe, the pipe manufacturer's installation instructions and requirements must also be observed. Grooves should be made according to ANSI/AWWA C606 (latest edition), ``Grooved and Shouldered Joints'', unless otherwise specified. FM Approved grooved pipe couplings joining steel pipe may be used in underground service, subject to the installation restrictions placed upon the pipe and to the coupling manufacturer's recommendations and requirements. Unless otherwise stated in the listing, these couplings have been evaluated for a maximum ambient temperature of 225°F (107°C), suitable for use in normal warehouse protection. For special applications, temperatures, or environments, the manufacturer's recommendations and requirements are to be followed.

Grooved Couplings, Standard -- Flexible

These couplings join pipe, valves or fittings having equal nominal-sized diameters.

ATUSA empresarial SL, Aptd. Correos 8, Poligono Industrial Agurain S/N, 01200 Salvatierra, Álava, Spain

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

EO Model FN/FR EO Model FN/FR

Remarks:

11/4, 11/2, 2, 21/2, 3, 4, 5, 6 76.1, 165 mm

Cut Groove Rolled Groove Cut Groove Rolled Groove

a, b, c a, b, c

300 (2070) 300 (2070)

a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 40; 8 in. NPS and larger ­ Schedule 30. b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall. c. Approved when supplied with EPDM gasket.

Allied Piping Products Inc, 500 Ternes Drive, Monroe MI 48162

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

10

11/4-3 4 5-8

Cut Groove or Rolled Groove '' '' ''

a, b, c a, b, c a, b, c a, b, c

11

11/4-8

500 (3445) 300 (2070) 175 (1205) 500 (3445)

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With EPDM gasket.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-259

Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

Gruvlok 7000

11/4-3 11/4, 11/2, 2'' 11/4-4 1-2 11/4, 11/2, 2, 21/2, 3, 4 11/4-8 11/4-8 21/2-8 76, 108, 133, 139.7, 159, 165 mm

Rolled Groove '' '' '' '' Rolled Groove, Cut Groove Rolled Groove `` ''

c, d, w c, m, w c, e, f, n, r, s, t, u, v, w c, p, w c, n, w a, c, w b, c, k, m, w c, k, w c, h

300 (2070) 300 (2070) 300 (2070) 175 (1205) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070)

Gruvlok 7000T Gruvlok 7001

11/4-8 1-12

Cut Groove, Rolled Groove Cut Groove Rolled Groove Rolled Groove Rolled Groove 2, '' ``

a, b, c, f a, c, w

175 (1205) 500 (3445) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 500 (3445) 400 (2760) 450 (3105) 350 (2415) 500 (3445) 500 (3445) 400 (2760) 175 (1205) 300 (2070) 300 (2070) 175 (1205)

1, 11/4, 11/2, 2 1-3 1, 11/4, 11/2,

c, m, w c, d, w c, n, w c, k, w

21/2, 3, 4 3-8

1-6 8 10 12 76.1 mm 165.1 mm 216 mm, 267 mm 318 mm 7001E 7000E 11/4, 10, 12 11/2, 2, 21/2, 3, 4, 5

`` '' `` '' Cut Groove Rolled Groove Rolled Groove '' Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove

b, c, w b, c, w b, c, w b, c, w c, h c, l c, l a, b, c, w a, b, c, d, i, k, t, w c, h a, b, c, w

76, 165 mm 6, 8

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With EPDM gasket Grade E (green stripe), Grade E Type A (violet stripe), and Grade E Type A Dri-SealTM (violet stripe). Flush gap gasket in 11/2-12 in. nominal sizes are interchangeable with standard gasket. d. Min schedule pipe to be joined: 3 in. or smaller ­ Allied Tube & Conduit FM Approved ``XL'', ``Super-XL'' and ``Super-40'' Thinwall pipe. e. Min schedule pipe to be joined: Allied Tube ``Dyna-Flow'' Lightwall pipe, 11/4-4 in. 300 psi (2070 kPa). f. Min schedule pipe to be joined: Allied Tube & Conduit ``Super-Flo'' Lightwall pipe, 11/4-4 in. 300 psi (2070 kPa). h. Metric Pipe: Equivalent to 76.1, 108, 133, 139.7, 159 and 165.1 mm. British Standard 1387, medium or equal. j. Central Sprinkler ``TL'' threadable Thinwall pipe. k. Tex-Tube Co. ``Tex-Flow'' non-threadable Lightwall pipe. l. JIS Schedule 20 pipe or heavier. m. For use with Northwest ``EZ-Flow'' in 3 through 6 in. sizes. n. Youngstown Tube ``Fire-Flo'' Non-Threadable Lightwall Sprinkler Pipe. p. IDOD Systems Gal-5 and All-Gal, Bull Moose Ultra-Eddy, and Wheatland WST Schedule 5 Pipes. r. IDOD Systems Gal-7 and Gal-flo pipe. s. Western International Fire Line Flow or Fire Line Thread Light pipe. t. Wheatland Mega-Flow, Mega-thread, MLT, GL, and WLS pipe. u. Bull Moose EDDY-flow, EDDY-lite pipe. v. For use with Yieh Phui SPS Flow Pipe in 11/4 through 4 in. NPS. w. EPDM Grade E (green stripe) flush gap gaskets in 1-12 in. nominal sizes are interchangeable with standard EPDM gaskets.

FM Approvals

1-260

September 2007 -- Approval Guide Automatic Sprinkler Systems

AnvilStar LLC, Division of Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

C-1

11/4, 11/2, 2, 21/2, 3, 4, 5 76, 165 mm 10, 12 11/4, 11/2, 6 2, 8

C-3

11/4, 11/2, 2, 21/2, 3, 4, 5 76, 165 mm 6, 8

Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove

a, b, c, d, e, f, g, h, i, k, l, m, n, p, q, s c, r a, b, c, s a, b, c, o, s a, b, c a, b, c, d, e, f, g, h, i, k, l, m, n, p, q, s c, r a, b, c, s

300 (2070) 300 (2070) 300 (2070) 175 (1205) 175 (1205) 300 (2070) 300 (2070) 300 (2070)

Remarks: a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 40; 8 in. NPS and larger ­ Schedule 30. b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 10S, 8 in. NPS and larger, 0.188 in. (5 mm) wall. c. With EPDM gasket using standard gasket lubricant or dry lubricant. d. For use with Allied Tube and Conduit ``Super-Flo'' and ``Dyna-Flow'' Lightwall steel sprinkler pipe in sizes: 11/4, 11/2, 2, 21/2, 3, and 4 in. NPS. e. For use with Northwest Pipe ``EZ-Flow'' Lightwall steel sprinkler pipe in size 4 in. NPS. f. For use with Allied Tube and Conduit ``XL'', ``XL-II'' threadable Thinwall steel sprinkler pipe in sizes: 11/4, 11/2, 2, 21/2, and 3 in. NPS. g. For use with Allied Tube and Conduit ``Super-XL'' threadable Thinwall steel sprinkler pipe in sizes: 11/4, 11/2, 2, 21/2, and 3 in. NPS. h. For use with Allied Tube and Conduit ``Super-40'' threadable Thinwall steel sprinkler pipe in sizes: 11/4, 11/2, 2, 21/2, and 3 in. NPS. i. For use with Allied Tube and Conduit ``BLT'' threadable Thinwall steel sprinkler pipe in sizes: 11/4, 11/2, and 2 in. NPS. k. For use with Wheatland Tube ``WLS'' threadable Thinwall steel sprinkler pipe in sizes: 11/4, 11/2, and 2 in. NPS. l. For use with Western International Forest Products ``Fire-Flow'' Lightwall steel sprinkler pipe in sizes: 11/4, 11/2, 2, 3, and 4 in. NPS. m. Available with flush gap gasket, 11/2-12 in. NPS. n. For use with Tex-Tube ``Tex-Flow'' Lightwall steel sprinkler pipe in sizes: 3 and 4 in. NPS. o. For use with Bull Moose ``Ultra-Eddy'' Schedule 5 steel sprinkler pipe in sizes: 11/4, 11/2, and 2 in. NPS. p. For use with Wheatland Tube ``Mega-Flow'' Lightwall steel sprinkler pipe in sizes: 11/4, 11/2, 2, 3, and 4 in. NPS. q. For use with Welded Tube­Berkeley LLC ``Steady-Flow'' Lightwall steel sprinkler pipe in sizes: 11/2, 2, 21/2, 3, and 4 in. NPS. r. For use with BS 1387 Medium or Heavy steel pipe in sizes: 76 and 165 mm NPS. s. EPDM Grade E (green stripe) flush gap gaskets in 1-12 in. nominal sizes are interchangeable with standard EPDM gaskets.

Beijing Tian Ning Yi He Pipe System Equipment Co Ltd, No. 2, North Road, Ju Yuan, Ma Pa Ju Yuan Industrial Base, Shunyi District, Beijing, P. R. China

Product Designation Pipe Size, mm Pipe Ends Remarks Max Working Pressure, psi (kPa)

GCQT2 GCQT2

76.1, 88.9, 108, 114.3, 159 60.3, 139.7, 165.1, 219

Rolled Groove, Cut Groove Cut Groove

a, b, c a, c

175 (1205) 175 (1205)

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With EPDM gasket.

Corcoran Piping Systems, 500 Ternes Drive, Monroe MI 48162

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

10

11/4-4 5-8

Cut Groove, Rolled Groove '' ''

a, b, c, d a, b, c a, b, c

11

a. b. c. d.

11/4-8

300 (2070) 175 (1205) 500 (3445)

Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. or larger ­ 0.188 in. (5 mm) wall. With EPDM gasket. For use with IDOD Systems Gal-5 pipe at 175 psi (1205 kPa).

Dong Yang Bend Co Ltd, 37-3, Songma-Ri, Daegot-Myeon, Gimpo-Si, Gyeonggi-do, Korea

Product Designation Pipe Actual Size mm/in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

XY02 XY02 XY02

50A/2 65A/21/2 80A/3

Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove

a, b, c a, b, c a, b, c

300 (2070) 300 (2070) 300 (2070)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-261

Product Designation

Pipe Actual Size mm/in.

Pipe Ends

Remarks

Max Working Pressure, psi (kPa)

XY02 XY02 XY02 XY02 XY02 XY02

100A/4 125A/5 150A/6 200A/8 250A/10 300A/12

Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove

a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c

300 (2070) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 175 (1205)

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With EPDM gasket.

Ever Metal Industry Co Ltd, 853 Kwang Fu Rd, Pa Teh City, Tao Yuen Hsien, Taiwan ROC

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

TRUE 5-C, 402 TRUE EM405

11/4-8 11/4-8 2, 21/2, 3, 4

Cut Groove Rolled Groove Cut Groove, Rolled Groove

a, c b, c a, b, c

300 (2070) 300 (2070) 300 (2070)

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 in. ­ 0.188 in. (5 mm) wall. c. With EPDM, EM757A or SBR gaskets.

Gentler Industrial Co Ltd, 178-10A Chung Chang Rd, Chung Chang, Tsun Ta Liau Shiang Kaohsiung Hsien, Taiwan ROC

DUCCO Brand Couplings

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

GT-402

11/4, 11/2, 2, 76, 133, 165 mm 21/2, 3, 4, 5, 6 8 11/4, 11/2 2, 21/2, 3, 4, 5, 6 76, 133, 165 mm 8

Cut Groove

a, c, d

500 (3445) 175 (1205) 500 (3445) 300 (2070) 175 (1205) 500 (3445) 400 (2760) 300 (2070)

'' Rolled Groove ''

a, c b, c b, c

'' Cut Groove, Rolled Groove Cut Groove, Rolled Groove ''

b, c a, b, c a, b, c a, b, c

GT-402H

2, 21/2, 3 4 6, 8

a. b. c. d.

Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 in. ­ 0.188 in. (5 mm) wall. With EPDM gasket. For British Standard 1387, medium steel pipe or equal.

Interfit India Ltd, SF No 112 / 3D, Part Mathapur Road, Kaniyur Village, Coimbatore 641 659, India

FireShield Series 300 Products.

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

Inter-Fit 10

11/4-4 5-12 14-18 11/4-6 76.1, 139.7, 165 mm

Cut Groove Rolled Groove '' '' '' ''

a, b, c a, b, c a, b, c a, b, c, d, e, k, m c, i

500 (3445) 300 (2070) 175 (1205) 300 (2070) 300 (2070)

FM Approvals

1-262

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Nominal Pipe Size, in.

Pipe Ends

Remarks

Max Working Pressure, psi (kPa)

Inter-Fit 11

11/4-8 10, 12 76.1, 165 mm 11/4-4

Cut Groove Rolled Groove '' '' Rolled Groove

a, b, c a, b, c c, i c, e, h, j, k, o, p, r, t

500 (3445) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 175 (1205) 300 (2070) 300 (2070)

Inter-Fit 12

1-2 1-4 1-8 76.1, 139.7, 165 mm

'' '' Cut Groove Rolled Groove ''

c, n c, e, h, j, k, m a, b, c, s c, i

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With EPDM gasket and flush-seal gasket. d. For use with Northwest ``EZ-Flow'' e. Allied ``Dyna-Flow'' h. Bull Moose ``EDDY-Lite'' i. British Standard BS 1387 Pipe, Med. and Heavy. j. Allied ``XL'' k. Allied ``Super-Flo'' m. Central Sprinkler ``TL'' pipe. n. Wheatland Schedule 5 and IDOD Gal-5. o. IDOD Gal-7. p. Tex-Tube Tex-Flow r. Western International Fire-Thread and Fire-Flow s. Northwest EZ-Flow t. Welded Tube ­ Berkeley, LLC Steady-Flow

JFE Pipe Fitting Mfg Co Ltd, 153 Tajime-Cho, Kishiwada Osaka, Japan

Product Designation Nominal Pipe Size, in. Fitting Description Remarks Max Working Pressure, psi (kPa)

7705

1-8

Rolled Groove, Cut Groove

a, b, c, d, e, f, g, h, j, k, l, m, p

300 (2070)

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10. c. Allied ``Super-Flo'', Allied ``Dyna-Flow'', 4 in. or smaller. d. Allied ``Super 40'', Bull Moose ``Ultra-Eddy'', 3 in. or smaller. e. Bull Moose ``EDDY-LITE'', 11/4 through 2 in. f. BS 1387 medium or heavy grade, 11/4, 11/2, 2, 21/2, 3, 4, 6 in. g. Bull Moose Tube EDDY-FLOW pipe, 11/2-4 in. h. American Tube ``BLT'', 11/4 through 2 in. j. American Tube ``Dyna-Thread'' 11/4 through 2 in. k. ``Super-XL'', 11/4 through 3 in. l. Allied Tube ``XL-II'', 11/4 through 3 in. m. Central ``TL'', 11/4 through 2 in. p. Wheatland WST, 11/4 through 2 in.

Jinan Meide Casting Co Ltd, No. 3 Nanmen Road, Pingyin, Jinan, 250400 China

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

1N 1N

Remarks: a. b. c. d.

11/4, 11/2, 2, 21/2, 3, 4, 5, 6, 8 76.1, 139.7, 165 mm

Cut Groove Rolled Groove Cut Groove Rolled Groove

a, b, c, d c, d

300 (2070) 300 (2070)

Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 40; 8 in. NPS and larger ­ Schedule 30. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall. Approved when supplied with EPDM gasket. Approved for use with GB/T3092 regular and extra heavy pipe, ISO 4200, and BS 1387 medium and heavy pipe.

Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

Quikhinge 007

1-6 76 mm 140, 165 mm

Cut Groove, Rolled Groove ''

a, b, c, f, j a, b, c, h, j

175 (1205) 175 (1205)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-263

Product Designation

Nominal Pipe Size, in.

Pipe Ends

Remarks

Max Working Pressure, psi (kPa)

07

2, 21/2, 3 11/2-6 8 8 76, 139.7 mm

'' '' Rolled Groove Cut Groove Cut Groove Rolled Groove Cut Groove, Rolled Groove Rolled Groove

c, d, f, j a, b, c, f, j b, c, j a, c, j c, g, h, j a, b, c, d, f, j c, g, j

75

11/4-8 76.1, 108, 133, 139 159, 165 mm

300 (2070) 500 (3445) 400 (2760) 500 (3445) 500 (3445) 500 (3445) 290 (2000) 175 (1205)

76

a. b. c. d. e. f. g. h. j.

10-12

Cut Groove, Rolled Groove

a, b, c, f, j

Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. or larger ­ 0.188 in. (5 mm) wall. With EPDM gasket (green stripe), -30° to +230°F; with nitrile gasket (orange stripe), -20° to +180°F. For use with Allied Tube & Conduit ``Dyna-Flow'' Lightwall pipe at 175 psi (1205 kPa). For use with all FM Approved Thinwall sprinkler pipe. With EPDM ``EA'' gasket (violet stripe). For use with BS 1387 metric pipe in sizes 76.1, 108, 133, 159, and 165 mm NPS. For use with DIN 2448 and 2458 metric pipe. With EPDM gasket ``EP'', using pre-lubricated material.

NIBCO Inc, 1516 Middlebury St, Elkhart IN 46515

Model F75 Steelok Grooved Pipe.

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

Couplings

1, 11/4, 11/2, 2, 21/2, 3, 4, 5, 6, 8 8 10, 12 1, 11/4

Cut Groove, Rolled Groove Rolled Groove, Cut Groove Cut Groove Rolled Groove Rolled Groove '' ''

a, b, c, j b, c a, c a, b, c c, f c, e, g, d, h c

1-3 11/2-3

300 (2070) 175 (1205) 300 (2070) 175 (1205) 175 (1205) 300 (2070) 175 (1205)

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. ­ 0.188 in. (5 mm) wall. c. With EPDM gasket. d. When joining Allied Tube & Conduit ``XL'' threadable Thinwall pipe. e. FM Approved for use on Allied Tube & Conduit ``Dyna-Flow'' non-threadable Lightwall pipe. f. For Schedule 5 /non-threadable Lightwall pipe as manufactured by Bull Moose Tube Co. g. When joining Allied Tube & Conduit ``Super-Flo'' non-threadable Lightwall pipe. h. For use with Central Sprinkler ``TL'' threadable Thinwall pipe, Allied ``BLT'' and Wheatland ``WLS.'' j. For use with Bull Moose Tube EDDY-Flow pipe.

National Fittings Inc, 295 East Swedesford Road #280, Wayne PA 19087-1462

FireShield Series 300 Products.

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

Style 10

11/4-3 4 5-8 11/4-3 11/4-4 11/4-2 5-12 76.1, 165.1 mm 3-8

Cut Groove, Rolled Groove '' '' '' '' '' '' '' Rolled Groove

a, b, c a, b, c a, b, c, p c, l a, b, c, d, m c, g, o a, b, c c, k c, p

500 (3445) 300 (2070) 175 (1205) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 175 (1205) 300 (2070)

FM Approvals

1-264

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Nominal Pipe Size, in.

Pipe Ends

Remarks

Max Working Pressure, psi (kPa)

2 Style 11 11/4-3 11/4-4 11/4-2 11/4-4 11/4-8 Style 12 11/4-3 11/4-4 11/4-2 11/4-8 11/4-2 3

'' Cut Groove, Rolled Groove '' '' '' '' '' '' '' '' Rolled Groove ''

c, q c, l c, d, m c, g a, b, c a, b, c c, l c, d, m c, g, o a, b, c c, q, r c, r

300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 500 (3445) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205) 175 (1205)

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With standard EPDM gasket, or dry lubricant EPDM gasket. d. Allied ``Dyna-Flow.'' g. Bull Moose ``EDDY-Lite.'' k. British Standard BS 1387 Pipe. l. Allied ``XL.'' m. Allied ``Super-Flo.'' o. With Central Sprinkler ``TL'' threadable Thinwall pipe. p. Tex-Tube Co. ``Tex-Flow'' non-threadable Lightwall pipe. q. Western International Forest Products ``Fire Thread'' threadable Thinwall pipe. r. Western International Forest Products ``Fire Flow'' non-threadable Lightwall pipe.

Qingdao V-Cart Piping Systems Co Ltd, JuiZhao Road, NanGuan Industry Zone, JiaoZhou City, Qingdao, China

Model No. Sizes, in. or mm End Connections Notes Pressure, bar (psi)

11/4-2, 57, 76 mm Figure 10 3, 4 5 through 12 108, 127, 133, 139, 159, 165 mm

a. b. c. d.

Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove

a, b, c, d a, b, c a, b, c, d

34 (495) 27 (390) 20 (290)

Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 or 10 in. ­ 0.188 in. (5 mm) wall. With EPDM gasket. For use with GB/T 3091-93 or GB/T 8163-99 Pipe.

Robor Pipe Systems, Box 1098, Isando, Gauteng 1600, South Africa

Style ``STEELGRO F75'' Grooved.

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

Pipe Couplings

1-6 8, 10, 12 8 10, 12 1, 11/4 1-3 11/2-3 76, 139, 165

Rolled Groove Cut Groove '' '' '' Rolled Groove '' '' Rolled Groove Cut Groove

a, b, c, j b, c a, c a, c c, f c, d, e, g, h c c, k

300 (2070) 175 (1205) 300 (2070) 175 (1205) 175 (1205) 300 (2070) 175 (1205) 300 (2070)

a. b. c. d. e.

Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. ­ 0.188 in. (5 mm) wall. With EPDM gasket. When joining Allied Tube & Conduit ``XL'' threadable Thinwall pipe. FM Approved for use on Allied Tube & Conduit ``Dyna-Flow'' non-threadable Lightwall pipe.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-265

f. g. h. j. k.

For Schedule 5 non-threadable Lightwall pipe as manufactured by Bull Moose Tube Co. When joining Allied Tube & Conduit ``Super-Flo'' non-threadable Lightwall pipe. For use with Central Sprinkler ``TL'' threadable Thinwall pipe, Allied ``BLT'', and Wheatland ``WLS.'' For use with Bull Moose Tube EDDY-Flow pipe. For use with BS 1387 medium and heavy pipe, or equal.

SCE Company Ltd, Unit E&F, 20/F., CDW Building, 388 Castl Peak Road, Tsuen Wan, N.T., Hong Kong

Product Designation Nominal Pipe Size, in. Pipe Ends Max Working Pressure, psi (kPa)

Remarks

AQUILA Model 1G AQUILA Model 1G

Remarks:

2,

21/2,

3, 4, 5, 6

76.1, 165 mm

Cut Groove Rolled Groove Cut Groove Rolled Groove

a, b, c a, b, c

300 (2070) 300 (2070)

a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 40; 8 in. NPS and larger ­ Schedule 30. b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall. c. Approved when supplied with EPDM gasket.

SPT Metal Corp, 19-1 Da Y/eh St, Da Liao Hsiang, Kaohsiung Hsien, Taiwan ROC ´

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

505 505 505 505 505 507 507 507 507 505 Stainless Steel 505 Stainless Steel

1-4 1, 11/4, 11/2, 2, 21/2, 3, 4, 5, 6, 8 76.1, 165.1 mm 11/4 through 4 11/4 through 4 11/2-6 11/2 through 4 11/2 through 14 16 through 24 2, 21/2, 3, 4, 5, 6, 8, 10 12

Rolled Groove Cut Groove Rolled Groove Rolled Groove '' '' '' '' Cut Groove Rolled Groove '' Cut Groove Rolled Groove Cut Groove Rolled Groove

c, e, f, g, h, i, j, n a, b, c, n c, d, n c, m, n c, n c, e, f, g, h, i, j, n c, n a, b, c, n a, b, c, n c, k, p c, k, p

300 (2070) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 300 (2070) 175 (1205) 300 (2070) 175 (1205) 300 (2070) 250 (1720)

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. ­ 0.188 in. (5 mm) wall. c. With EPDM gasket. d. For metric pipe per BS 1387 medium or equal. e. When joining Allied Tube & Conduit ``XL'' threadable Thinwall pipe, 1-2 in. only. f. For use on Allied Tube & Conduit ``Dyna-Flow'' non-threadable Lightwall pipe. g. When joining Allied Tube & Conduit ``Super-Flo'' non-threadable Lightwall pipe. h. For use on Northwest ``EZ-Flow'' non-threadable Lightwall pipe in 4 in. nominal size. i. For use with Central Sprinkler ``TL'' threadable Thinwall pipe. j. For use with Bull Moose Tube EDDY-Flow pipe. k. For use on Schedule 40 Cut Groove and Rolled Groove only. m. For use with Wheatland Mega-Flow non-threadable Thinwall pipe. n. Ductile Iron p. Stainless Steel.

Shanghai Recomb Piping System Co Ltd, No. 270 Yixian Rd, Shanghai 200434, Peoples Republic China

Product Designation Pipe Actual Size mm Pipe Ends Remarks Max Working Pressure, psi (kPa)

XGQT2

33.7, 42, 48, 60, 73, 76, 89, 108, 114, 133, 140, 141.3, 159, 165, 168 and 219 273 and 325 42.4 48.3 60.3

Rolled Groove, Cut Groove

a, b, c

300 (2070)

XGQT2 XGQT2-42.4 XGQT2-48.3 XGQT2-60.3

Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove

a, b, c a, b, c a, b, c a, b, c

175 (1205) 300 (2070) 300 (2070) 300 (2070)

FM Approvals

1-266

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Pipe Actual Size mm

Pipe Ends

Remarks

Max Working Pressure, psi (kPa)

XGQT2-76.1 XGQT2-88.9

76.1 88.9

Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove

a, b, c a, b, c

300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 175 (1205)

XY02 XY02 XY02 XY02 XY02 XY02 XY02 XY02 XY02

50A/2 65A/21/2 80A/3 100A/4 125A/5 150A/6 200A/8 250A/10 300A/12

a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c

a. Min schedule cut groove pipe to be joined: 6 in. or smaller -- Schedule 40; 8 in. or larger -- Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller -- Schedule 10; 8 in. or larger -- 0.188 in. (5 mm) wall. c. With EPDM gasket.

Shanghai Vision Mechanical Joint Co Ltd, Jinlan Road, Loutang Industrial Park, Jiading District, Shanghai 201807 PRC

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

101 101

a. b. c. d.

11/4, 11/2, 2, 21/2, 3, 4, 6, 8 57, 76, 108, 133, 140, 159, 165 mm

Cut Grooved Rolled Groove Cut Groove Rolled Groove

a, b, c, d, e a, b, c, d, e

300 (2070) 300 (2070)

Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 40; 8 in. and larger ­ Schedule 30. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 10S; 8 in. NPS and larger ­ 0.188 in. (5 mm) wall. With EPDM gasket. For use with Chinese Standard GB/T 3091-1993, GB/T 3092-1993 welded steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000, Schedule 40 pipe (8 in. NPS ­ Schedule 30). e. For use with Chinese Standard GB/T 17395-1998 seamless steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000, Schedule 40 pipe (8 in. NPS ­ Schedule 30).

Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115

Product Designation Nominal Pipe Size, in. Fitting Description Remarks Max Working Pressure, psi (kPa)

7705

1 through 8

Rolled Groove, Cut Groove Rolled Groove Rolled Groove, Cut Groove Rolled Groove Cut Groove Rolled Groove Rolled Groove, Cut Groove '' '' '' ''

7705 7705H 7705 7705 7707 7707 7707 7707 7707 7707

1-2 8 10, 12 10, 12 2 through 10 12 11/2 through 10 21/2, 5, 6 14, 16, 18, 20, 22 24

a, b, c, d, e, f, g, h, j, l, m, q, r, s p, s, t a, s b, s a, s b, s a, b, s a, s s, f a, s a, s

300 (2070) 175 (1205) 450 (3100) 175 (1205) 250 (1720) 450 (3098) 300 (2066) 500 (3443) 500 (3443) 175 (1205) 250 (1720)

a. b. c. d. e. f. g.

Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 and 10 in.-0.188 in. wall; 12 in.-0.250 in. wall. Allied ``Super-Flo'', Allied ``Dyna-Flow'', 4 in. or smaller. Allied ``Super 40'' and ``Super-XL'', 1 through 3 in. Bull Moose ``EDDY-Lite'', 1 through 2 in. BS 1387 medium or heavy grade, 11/4, 11/2, 2, 21/2, 3, 4, 6 in. Bull Moose Tube EDDY-Flow pipe, 11/2 through 4 in.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-267

h. American Tube ``BLT'', 1 through 2 in. j. American Tube ``Dyna-Thread'' 1 through 2 in. l. Allied Tube ``XL-II'', 1 through 3 in. m. Central ``TL'', 1 through 2 in. p. Wheatland WST, 1 through 2 in. q. ``Fire-Thread'', 1 through 2 in. r. ``Fire-Flow'', 11/2 and 11/2 in. s. EPDM gasket. t. Bull Moose ``Ultra-EDDY'', 2 in. or smaller.

Taehwa Metal Co Ltd, 577-3 Kajwa-Dong, Seo-ku,Incheon, Korea 404-812

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

AJ320 AJ320 AJ320

a. b. c. d. f.

11/4, 11/2, 2 76 mm ­ 12 14-24

Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove

a, b, c, d a, b, c, f a, b, c, f

300 (2070) 300 (2070) 175 (1205)

Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 or 10 in. ­ 0.188 in. (5 mm) wall. With EPDM gasket (green Stripe). For use with Korean KS D3507 pipe. For use with metric OD pipe.

Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

Grinnell 7000S

11/4-6 8 8 76.1-159 mm 165.1 mm 11/4-4

Rolled Groove, Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove '' '' '' '' '' '' Rolled Groove Cut Groove Rolled Groove

a, b, c b, c a, c c, h c, h c, d, e, f, j a, c c, k b, c b, c b, c a, c c, l c, l a, b, c, d, e, h, j, l, m, q, s, u p, s, t

Grinnell 7001

8-12 8 8 10 12 8-12 216 mm, 267 mm 318 mm

Grinnell Fig 705 Grinnell Fig 705

1 1

500 (3445) 350 (2415) 500 (3445) 500 (3445) 400 (2760) 300 (2070) 500 (3445) 300 (2070) 400 (2760) 450 (3105) 350 (2415) 500 (3445) 500 (3445) 400 (2760) 300 (2070) 175 (1205)

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 and 10 in. ­ 0.188 in. wall; 12 in. ­ 0.250 in. wall. c. Allied ``Super-Flo'', Allied ``Dyna-Flow'', 4 in. or smaller. d. Allied ``Super 40'' and ``Super-XL'', 1 through 3 in. e. Bull Moose ``EDDY-Lite'', 1 through 2 in. h. American Tube ``BLT'', 1 through 2 in. j. American Tube ``Dyna-Thread'' 1 through 2 in. l. Allied Tube ``XL-II'', 1 through 3 in. m. Central ``TL'', 1 through 2 in. p. Wheatland WST, 1 through 2 in. q. ``Fire-Thread'', 1 through 2 in. s. EPDM gasket. t. Bull Moose ``Ultra-EDDY'', 2 in. or smaller. u. For use with Yieh Phui SPS Flow Pipe in 11/4 through 4 in. NPS. Product Designation Nominal Pipe Size, in. Pipe Ends Max Working Pressure, psi (kPa)

Remarks

540

21/2

Cut Groove, Rolled Groove

a, b, c, h, i, j, k, s

300 (2070)

FM Approvals

1-268

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Nominal Pipe Size, in.

Pipe Ends

Remarks

Max Working Pressure, psi (kPa)

575

11/4-8 11/4-2 11/4-2 11/4-3 11/4-4 3, 4 4, 6 6

Cut Groove, Rolled Groove Rolled Groove Rolled Groove Rolled Groove Rolled Groove Rolled Groove Rolled Groove Rolled Groove Rolled Groove Cut Groove Rolled Groove Rolled Groove, Cut Groove Rolled Groove Rolled Groove '' '' Rolled Groove Cut Groove Rolled Groove, Cut Groove '' Rolled Groove '' '' '' '' '' '' Cut Groove

a, b, c c, f, i, j, s, t, w c, d, f, n, p, u c, f, g c, f, h, l, q, v c, o c, o c, f, o a, b, c, f c, f, h, l, n, o, q, u, v, y c, f, i, j, w, x c, f c, o a, b, c, f c, f, p, u c, k, x

705

11/4-10 11/4-4 11/4-2 11/2-4 6 12 11/4-2 108, 133, 159, 216 mm

300 (2070) 300 (2070) 175 (1205) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 175 (1205) 250 (1725) 175 (1205) 300 (2070) 300 (2070) 500 (3445) 450 (3105) 175 (1205) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 200 (1380) 300 (2070)

705 BS 707

76, 139, 165 mm 11/2-12 11/2-12 11/2-2 11/2-2 11/2-4 3-4 6 14 76.1 mm 165.1 mm

c, f, k a, c, f b, c, f c, f, n, u c, f, i, j, s, t, x c, f, h, q c, o c, o a, b, c c, f, k

a. b. c. d. f. g. h. i. j. k. n. o. p. q. s. t. u. v. w. x. y.

Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. or larger ­ 0.188 in. (5 mm) wall. With EPDM gasket using standard gasket lubricant or dry lubricant. For use with Allied Tube & Conduit ``Dyna-Light'' Schedule 5 non-threadable Lightwall pipe. Also available with Tri-Seal EPDM gasket. Recommended by the manufacturer for dry systems. For use with standard gasket lubricant or dry lubricant. For use with Allied Tube & Conduit ``XL'' threadable Thinwall pipe. For use with Allied Tube & Conduit ``Dyna-Flow'' and ``Super-Flo'' non-threadable Lightwall pipe. For use with Allied Tube & Conduit ``BLT'' threadable Thinwall pipe. For use with Allied Tube & Conduit ``Dyna-Thread'' threadable Thinwall pipe. For use with BS1387 medium or heavy pipe. For use with Bullmoose Tube Co. ``Ultra-EDDY'' Schedule 5 non-threadable Lightwall pipe. For use with Northwest ``EZ-Flow'' non-threadable Lightwall pipe. For use with IDOD Systems Schedule 5 non-threadable Lightwall pipe. For use with Wheatland Tube Co. ``Mega-Flow'' non-threadable Lightwall pipe. For use with Allied ``XL'' pipe. For use with Wheatland Tube Co. ``MLT'' threadable Thinwall pipe. For use with Wheatland Tube Co. ``WST'' Schedule 5 non-threadable Lightwall pipe. For use with Youngstown Tube Co. ``Fire-Flo'' non-threadable Lightwall steel sprinkler pipe. For use with Youngstown Tube Co. ``EZ-Thread'' threadable Thinwall steel sprinkler pipe. For use with IDOD's Gal-7 and Gal-Flo pipe. For use with Bullmoose Tube Co. ``EDDY-flow'' non-threadable Lightwall pipe.

Victaulic Company, Box 31, Easton PA 18044

Product Designation Nominal Pipe Size, in. Pipe Ends Max Working Pressure, psi (kPa)

Remarks

75

11/4, 11/2, 2

Rolled Groove

a, e, x, aa

175 (1205)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-269

Product Designation

Nominal Pipe Size, in.

Pipe Ends

Remarks

Max Working Pressure, psi (kPa)

11/4, 11/2, 2 11/2, 2 11/4, 11/2, 2, 21/2, 3, 4 11/4, 2, 3, 4, 6 11/2, 2, 21/2, 3 11/2, 21/2,

'' '' '' '' '' '' '' '' '' '' '' Cut Groove Rolled Groove '' '' '' '' ''

1/2,

e, h, aa t, aa a, e, g, j, k, u, w, z, aa, ab o, q, s, v, y, aa a, e, p, aa a, e, l, aa a, e, aa e, s, aa a, e, z, aa e, s, aa a, e, i, v, y, aa a, c, e, aa b, d, e a, d, e, aa a, d, e, aa b, e, n, aa b, d, e a, e, i, f a, e, o, q, s, zz

11/2, 2, 21/2, 3 11/2, 2, 21/2, 3, 4 6 6 3, 4 3, 4, 6, 8 1-8 3.0 11/2, 2, 21/2, 3, 4, 5, 6, 8 5, 6, 8 108, 133, 139.7 152, 159, 165 mm 76 mm 216 mm 1, 1

1/ 4,

1 2, 2 3, 4, 6

1/ 2,

300 (2070) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 300 (2070) 175 (1205) 175 (1205) 300 (2070) 300 (2070) 300 (2070) 500 (3445) 300 (2070) 500 (3445) 300 (2070) 300 (2070) 175 (1205) 300 (2070) 300 (2070) 175 (1205) 300 (2070) 500 (3445) 300 (2070) 175 (1205) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 300 (2070) 450 (3105) 175 (1205) 300 (2070) 300 (2070) 450 (3105) 175 (1205) 300 (2070) 175 (1205) 300 (2070) 175 (1205)

1, 1 1/4, 1 1/2, 2, 2 1/2, 3

a, e, p

1, 11/4, 11/2, 2, 2 1/2, 3

a, e, l

77

1-12 14 1-4 1, 11/4, 11/2, 2

'' '' '' '' '' '' '' '' '' '' '' '' '' '' '' '' 2 '' '' '' Rolled Groove Cut Groove

a, c, e, aa a, c, e o, aa e, h, aa a, e, g, w, z, aa a, e, j, k, u, aa q, y, aa e, s, aa e, s, aa a, e, z, aa a, d, e, aa a, e, aa a, d, e a, e, i, v, aa b, e, n, aa a, e, p, aa a, e, l, t, y, aa a, b, n, aa a, e, r, aa e, ff

1, 11/2, 2, 21/2, 3, 4 11/4, 11/2, 2, 21/2, 3, 4 1-4 21/2, 3, 4

6 6 1-12 11/2-3 14 3-8 165 mm

3/4-2

1,

11/4,

11/2,

76, 108, 133, 139.7, 159 mm 11/4, 11/2, 2 77 267, 318 mm

FM Approvals

1-270

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Nominal Pipe Size, in.

Pipe Ends

Remarks

Max Working Pressure, psi (kPa)

307

3, 4, 6, 8, 10, 12

Rolled Groove, Cut Groove ''

i, m

175 (1205) 500 (3445) 300 (2070) 350 (2415) 350 (2415) 300 (2070) 250 (1725)

705

11/4, 11/2 (42, 48 mm) 2-4 2, 21/2, 3, 4, 6, 8 2, 21/2, 3, 4 6 8

c, d

791 Boltless

Rolled Groove Cut Groove, Rolled Groove '' '' ''

q, aa a, c, e, aa a, d, e, aa a, d, e, aa a, d, e, aa

a. Also available with Style 77FS gasket. Recommended by manufacturer for use with dry pipe systems. aa. For use with VicMax EPDM Gaskets in 2 through 8 in. and 76 and 165 mm sizes. ab. For use with Yieh Phui SPS Flow Pipe in 11/4 through 4 in. NPS. b. For steel pipe having metric sized outside dia. (ref. DIN 2448 & 2458). c. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. d. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 in. or larger ­ 0.188 in. (5 mm) wall. e. With gasket E (green stripe), H (white stripe) or L (solid red). f. For use with JIS steel pipe. ff. For use with JIS G3452 steel sprinkler pipe. g. For use with Youngstown Tube ``Fire-Flo'' non-threadable Lightwall steel sprinkler pipe. h. For use with Youngstown Tube ``EZ-Thread'' threadable Thinwall steel sprinkler pipe. i. With gasket M. j. For use with Welded Tube Berkeley ``Steady Flow'' Lightwall non-threadable, Lightwall steel sprinkler pipe in sizes 11/4, 11/2, 2, 21/2, 3 and 4 in. NPS. k. For use with Welded Tube Berkeley ``Steady Thread'' threadable Thinwall steel sprinkler pipe in sizes 1, 11/4, 11/2 and 2 in. NPS. l. When joining Allied Tube & Conduit ``XL'' threadable Thinwall pipe. m. Joins rolled or cut groove steel pipe, per note d to cut groove iron pipe per note i. n. For steel pipe having outside dia. sized per British Standard 1387, medium or equal. o. All FM Approved for use on Allied Tube & Conduit ``Dyna-Flow'' non-threadable Lightwall pipe. p. For Schedule 5 non-threadable Lightwall pipe as manufactured by Bull Moose Tube Co. q. When joining Allied Tube & Conduit ``Super-Flo'' non-threadable Lightwall pipe. s. For use on Northwest ``EZ-Flow'' non-threadable Lightwall pipe in 4 and 6 in. nominal size. t. For use with Central Sprinkler ``TL'' threadable Thinwall pipe. u. For use with Bull Moose Tube EDDY-Flow pipe. v. For use with Tex-Tube Co. ``Tex-Flow'' non-threadable Lightwall pipe. w. For use with Central 7 pipe. x. For use with IDOD Systems Gal-5 pipe. y. For use with Western ``Fire-Flow'' and ``Fire-Thread'' pipe. z. For use with Wheatland ``Mega-Flow'' pipe. zz. For use with Wheatland MLT up to 2 in. nominal size.

Victaulic Company of Japan Limited (The), IINO Building 3F, 1-1, Uchisaiwaicho 2-Chome, Chiyoda-Ku, Tokyo 100-0011, Japan

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

Jady 35 G-1

a. b. c. d.

2, 21/2, 3, 31/2, 4, 5, 6, 8 60.5, 76.3, 89.1, 114.3, 139.8, 165.2, 216.3

Cut Groove, Rolled Groove Cut Groove Rolled Groove

a, b, c a, d

175 (1205) 300 (2070)

With EPDM gasket, orange stripe. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 31/2 in. or smaller ­ Schedule 10S; 4 in. or larger ­ 0.188 in. (5 mm) wall. For use with JIS G3454, Schedule 40 steel sprinkler pipe.

Victaulic-Europe, Neerhonderd 37, Industriepark Kwatrecht, B-9230 Wetteren, Belgium

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

75

1, 11/4, 11/2, 2 1, 11/4, 11/2, 1/2, 3, 4, 6 2, 2 1, 11/4, 11/2, 2, 21/2, 3 1, 11/4, 11/2, 2, 21/2, 3 1-8 3.0 1-4 5-8

Rolled Groove '' '' '' Cut Groove Rolled Groove '' ''

a, e, t, v a, e, o, q, s, w a, e, p a, e, l a, c, e a, b, d, e a, d, e a, d, e

300 (2070) 300 (2070) 175 (1205) 300 (2070) 500 (3445) 300 (2070) 500 (3445) 300 (2070)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-271

Product Designation

Nominal Pipe Size, in.

Pipe Ends

Remarks

Max Working Pressure, psi (kPa)

77

108, 133, 139.7 152, 159, 165 mm 3.0 1-12 14 1, 11/4, 11/2, 2 1-4 21/2, 3, 4, 6 1-12 14 1-12 165 mm

3/4-2

'' '' Cut Groove '' Rolled Groove '' '' '' '' '' '' '' '' '' '' Rolled Groove, Cut Groove '' Rolled Groove Cut Groove, Rolled Groove '' '' ''

b, e, n b, d, e a, c, e a, c, e o q, u o, s a, d, e a, d, e a, c, e b, e, n a, e, p a, e a, e, l, t a, b, n i, m c, d q a, c, e a, d, e a, d, e a, d, e

11/2-3 1-2 108, 133, 139.7, 159 mm 3-12 11/4, 11/2 (42, 48 mm) 2-4 2, 3, 4, 6, 8 1/2, 3, 4 2, 2 6 8 21/2,

307 Style 705 791 Boltless

300 (2070) 175 (1205) 500 (3445) 300 (2070) 175 (1205) 300 (2070) 300 (2070) 450 (3105) 300 (2070) 500 (3445) 450 (3105) 175 (1205) 175 (1205) 300 (2070) 175 (1205) 175 (1205) 500 (3445) 300 (2070) 350 (2415) 350 (2415) 300 (2070) 250 (1725)

a. Also available with Style 77FS gasket. Recommended by manufacturer for use with dry pipe systems. b. For steel pipe having metric sized outside dia. (ref. DIN 2448 & 2458). c. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. d. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 in. or larger ­ 0.188 in. (5 mm) wall. e. With gasket E (green stripe), H (white stripe) or L (solid red). i. With gasket M. l. When joining Allied Tube & Conduit ``XL'' threadable Thinwall pipe. m. Joins rolled or cut groove steel pipe, per note d to cut groove iron pipe per note i. n. For steel pipe having outside dia. sized per British Standard 1387, medium or equal. o. All FM Approved for use on Allied Tube & Conduit ``Dyna-Flow'' non-threadable Lightwall pipe. p. For Schedule 5 non-threadable Lightwall pipe as manufactured by Bull Moose Tube Co. q. When joining Allied Tube & Conduit ``Super-Flo'' non-threadable Lightwall pipe. s. For use on Northwest ``EZ-Flow'' non-threadable Lightwall pipe in 4 and 6 in. nominal size. t. For use with Central Sprinkler ``TL'' threadable Thinwall pipe. u. For use with Bull Moose Tube EDDY-Flow pipe. v. For use with Wheatland ``Mega-Flow'' up to 4 in. nominal size. w. For use with Wheatland ``MLT'' up to 2 in. nominal size.

Viking SA, Zone Industrielle Haneboesch, L-4562 Differdange/Niedercorn, Luxembourg

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

``Uniking'' Style 4075

1, 11/4, 11/2, 2, 21/2, 3, 4, 5, 6, 8 76.1, 139.7, 165.1 mm

3/ 4

Cut Groove Rolled Groove '' '' '' ''

a, b, c, e, f, h, j c, d a, b, c, e, f, h, j

``Uniking'' Style 6077

through 6

8 through 12 76, 108, 133, 139, 159, 165 mm

a. b. c. d.

c, d

300 (2070) 300 (2070) 500 (3445) 300 (2070) 300 (2070)

Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. ­ 0.188 in. (5 mm) wall. With EPDM gasket. For metric pipe per BS 1387 medium or heavy.

FM Approvals

1-272

September 2007 -- Approval Guide Automatic Sprinkler Systems

e. f. h. j.

For use on Wheatland ``Mega-Flow'' pipe. All FM Approved for use on Allied Tube & Conduit ``Dyna-Flow'' and ``Super-Flo'' non-threadable Lightwall pipe. For use on Northwest ``EZ-Flow'' non-threadable Lightwall pipe in 4 in. nominal size at 250 psi (1725 kPa). For use with Bull Moose Tube EDDY-Flow pipe.

Weifang 100tong Casting Co Ltd, No. 1919 Jinchang South Road, Weicheng District, Weifang, Shandong, PR China 261052

Product Designation Nominal Pipe Size, mm Pipe Ends Rated Working Pressure, psi (kPa)

Remarks

GCQT2

33, 42, 48, 60, 76, 89, 108, 114, 133, 140, 159, 165, 168, 219

Cut Groove or Rolled Groove

a, b, c, d, e, f

230 (1600)

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With EPDM gasket. d. For use with BS 1387 medium or equal metric pipe. e. For use with Chinese Standard GB/T 3091-1993, GB/T 3092-1993 welded steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000, Schedule 40 pipe (8 in. NPS ­ Schedule 30). f. For use with Chinese Standard GB/T 17395-1998 seamless steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000, Schedule 40 pipe (8 in. NPS ­ Schedule 30).

Grooved Couplings, Standard -- Rigid

These couplings join pipe, valves or fittings having equal diameters.

AJS Co Ltd, 1001 Namsung Plaza #345-30, Gasan-dong, Geumcheon-gu, Seoul 153-782 Korea

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

AJ510 AJ510

Remarks: a. b. c. d.

11/4, 11/2, 2, 3, 4, 5, 8 76, 165 mm

Cut Grooved Rolled Groove Cut Groove Rolled Groove

a, b, c, d, e c, d, e

300 (2070) 300 (2070)

Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 40; 8 in. and larger ­ Schedule 30. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 10S; 8 in. NPS and larger ­ 0.188 in. (5 mm) wall. With EPDM gasket. For use with Chinese Standard GB/T 3091-1993, GB/T 3092-1993 welded steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000, Schedule 40 pipe (8 in. NPS ­ Schedule 30). e. For use with Chinese Standard GB/T 17395-1998 seamless steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000, Schedule 40 pipe (8 in. NPS ­ Schedule 30).

ATUSA empresarial SL, Aptd. Correos 8, Poligono Industrial Agurain S/N, 01200 Salvatierra, Álava, Spain

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

EO Model FN/FR EO Model FN/FR

Remarks:

11/4, 11/2, 2, 21/2, 3, 4, 5, 6 76.1, 165 mm

Cut Groove Rolled Groove Cut Groove Rolled Groove

a, b, c a, b, c

300 (2070) 300 (2070)

a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 40; 8 in. NPS and larger ­ Schedule 30. b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall. c. Approved when supplied with EPDM gasket.

Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801

Product Designation Nominal Pipe Size, in. Fitting Description Remarks Max Working Pressure, psi (kPa)

Gruvlok HPR* 7004

2-8 2-3 2-8

Cut Groove, Rolled Groove '' Rolled Groove Rolled Groove, Cut Groove Rolled Groove ''

a, c c, d b, c, w a, b, c, d, e, f, j, l, p, r, s, t, w c, n, w c, n, w

Rigidlite 7400*

1-8 21/2-4 6

750 (5170) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 175 (1205)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-273

Product Designation

Nominal Pipe Size, in.

Fitting Description

Remarks

Max Working Pressure, psi (kPa)

3-8 76.1, 139.7, 165.1 mm 1-2 Gruvlok 7400 S* Rigidlok 7401* 2-6 11/2-3 11/2-4 11/2-2 11/2-3 11/2-3 3-8 4, 5 6 8, 10, 12 11/2-4 5, 6 8 10 12 76.1, 139.7, 165.1 mm

Rolled Groove Rolled Groove, Cut Groove Rolled Groove '' Rolled Groove '' '' '' '' '' '' '' '' Cut Groove, Rolled Groove '' '' '' '' ''

c, n c, h c, m a, b, c, d, e, f, h, l, m c, e c, f, p c, o, w c, d, w b, c, w c, n, w b, c, w b, c, w b, c, w a, c a, c a, c a, c, w a, c, w c, h

175 (1205) 300 (2070) 175 (1205) 175 (1205) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 500 (3445) 400 (2760) 300 (2070) 750 (5170) 500 (3445) 450 (3105) 300 (2070) 300 (2070) 500 (3445)

7400E*

11/4, 11/2, 2, 21/2, 3, 4, 5, 6, 8, 10 12 76, 165 mm 11/4, 11/2, 2, 21/2, 3, 4

Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Rolled Groove

a, b, c, d, e, f, i, l, m, o, p, t, w a, c, w c, h c, m, w

300 (2070) 300 (2070) 300 (2070) 175 (1205)

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in areas subject to earthquake. a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With EPDM gasket Grade E (green stripe), Grade E Type A (violet stripe), and Grade E Type A DriSealTM (violet stripe). Flush gap gasket in 11/2-12 in. nominal sizes are interchangeable with standard gasket. d. Min schedule pipe to be joined: 3 in. or smaller ­ Allied Tube & Conduit FM Approved ``XL'', ``Super-XL'' and ``Super-40'' Thinwall pipe. e. Min schedule pipe to be joined: Allied Tube & Conduit ``Dyna-Flow'' Lightwall pipe, 1-4 in. f. Min schedule pipe to be joined: Allied Tube & Conduit ``Super-Flo'' Lightwall pipe, 1-4 in. h. Metric Pipe: Equivalent to 76.1, 108, 133, 139.7, 159 and 165.1 mm. British Standard 1387, medium or equal. j. For use with Central Sprinkler ``TL'' threadable Thinwall pipe. l. Min schedule rolled groove pipe to be joined: Bull Moose EDDY-Lite, 2 in. and EDDY-flow, 11/2-4 in.175 psi (1205 kPa). m. Min schedule rolled groove pipe to be joined: Bull Moose Ultra-EDDY, 1-2 in., IDOD Systems Gal-5 and All-Gal, and Wheatland WST Schedule 5 pipes. n. For use with Tex-Tube ``Tex-Flow'' Lightwall pipe 21/2 to 6 in. o. For use with Youngstown Tube ``EZ-Thread'' Threadable Thinwall Sprinkler Pipe. p. For Use with Northwest ``EZ-Flow'' pipe in 3 thru 6 in. sizes. r. IDOD Systems Gal-7 and Gal-flo pipe. s. Western International Fire Line Flow or Fire Line Thread Light. t. Wheatland Mega-Flow, Mega-thread, MLT, GL, and WLS pipe. w. EPDM Grade E (green stripe) flush gap gaskets in 1-12 in. nominal sizes are interchangeable with standard EPDM gaskets.

AnvilStar LLC, Division of Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max. Working Pressure, psi (kPa)

C-4

11/4. 11/2, 2, 21/2, 3, 4, 5, 6, 8, 10, 12 76, 165 mm 11/4. 11/2, 2, 21/2, 3, 4

Cut Groove Rolled Groove Cut Groove Rolled Groove Rolled Groove

a, b, c, d, e, f, g, i, j, l, m, o, s c, p c, k, n, o, s

300 (2070) 300 (2070) 175 (1205)

Remarks: a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 40; 8 in. NPS and larger ­ Schedule 30. b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 10S, 8 in. NPS and larger, 0.188 in. (5 mm) wall.

FM Approvals

1-274

September 2007 -- Approval Guide Automatic Sprinkler Systems

c. With EPDM gasket using standard gasket lubricant or dry lubricant. d. For use with Allied Tube and Conduit ``Super-Flo'' and ``Dyna-Flow'' Lightwall steel sprinkler pipe in sizes: 11/4, 11/2, 2, 21/2, 3, and 4 in. NPS. e. For use with Northwest Pipe ``EZ-Flow'' Lightwall steel sprinkler pipe in size 3, 4 and 6 in. NPS. f. For use with Allied Tube and Conduit ``XL'', ``XL-II'' threadable Thinwall steel sprinkler pipe in sizes: 11/4, 11/2, 2, 21/2, and 3 in. NPS. g. For use with Allied Tube and Conduit ``BLT'' threadable Thinwall steel sprinkler pipe in sizes: 11/4, 11/2, and 2 in. NPS. i. For use with Wheatland Tube ``WLS'' threadable Thinwall steel sprinkler pipe in sizes: 11/4, 11/2, and 2 in. NPS. j. For use with Bull Moose Tube ``EDDY-Lite'' threadable Thinwall steel sprinkler pipe in sizes: 11/4, 11/2, and 2 in. NPS. k. For use with Bull Moose Tube ``EDDY-Flow'' Lightwall steel sprinkler pipe in sizes: 11/2 through 4 in. NPS. l. Available with flush gap gasket, 11/2-12 in. NPS. m. For use with Tex-Tube ``Tex-Flow'' Lightwall steel sprinkler pipe in sizes: 3 and 4 in. NPS. n. For use with Bull Moose ``Ultra-Eddy'' Schedule 5 steel sprinkler pipe in sizes: 11/4, 11/2, and 2 in. NPS. o. For use with Welded Tube­Berkeley LLC ``Steady-Flow'' Lightwall steel sprinkler pipe in sizes: 11/2 and 2 in. NPS, FM Approved for 300 psi rated working pressure, and 4 in. NPS, FM Approved for 175 psi rated working pressure. p. For use with BS 1387 Medium or Heavy steel pipe in sizes: 76 and 165 mm NPS. q. For use with Schedule 40 steel sprinkler pipe only. s. EPDM Grade E (green stripe) flush gap gaskets in 1-12 in. nominal sizes are interchangeable with standard EPDM gaskets.

Beijing Tian Ning Yi He Pipe System Equipment Co Ltd, No. 2, North Road, Ju Yuan, Ma Pa Ju Yuan Industrial Base, Shunyi District, Beijing, P. R. China

Product Designation Pipe Size, mm Pipe Ends Remarks Max Working Pressure, psi (kPa)

GCQT1 GCQT1

76.1, 88.9, 108, 114.3, 159 60.3, 139.7, 165.1, 219

Rolled Groove, Cut Groove Cut Groove

a, b, c a, c

175 (1205) 175 (1205)

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With EPDM gasket.

Corcoran Piping Systems, 500 Ternes Drive, Monroe MI 48162

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

Style 5

1, 11/2, 2, 21/2, 3, 4, 6, 8 1, 11/2, 2, 21/2, 3, 4, 6, 8

Cut Groove, Rolled Groove Rolled Groove

a, c b, c

300 (2070) 300 (2070)

a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With EPDM gasket.

Dong Yang Bend Co Ltd, 37-3, Songma-Ri, Daegot-Myeon, Gimpo-Si, Gyeonggi-do, Korea

Product Designation Pipe Actual Size mm/in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

XD01 XD01 XD01 XD01 XD01 XD01 XD01 XD01

50A/2 65A/21/2 80A/3 100A/4 125A/5 150A/6 200A/8 250A/10

Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove

a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c

300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 175 (1205)

a. Min schedule cut groove pipe to be joined: 6 in. or smaller - Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With EPDM gasket.

Gentler Industrial Co Ltd, 178-10A Chung Chang Rd, Chung Chang Tsun Ta Liau Shiang Kaohsiung Hsien, Taiwan ROC

DUCCO Brand Couplings

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

GT-402R*

11/4, 11/2, 2 21/2, 3, 4, 6 11/4, 11/2, 2 8

Cut Groove Rolled Groove Rolled Groove Cut Groove Rolled Groove

a, b, c, e c, d a, b, c, e

300 (2070) 175 (1205) 200 (1375)

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-275

a. b. c. d. e.

Min schedule cut groove pipe to be joined: 6 in. or smaller -- Schedule 40. Min schedule rolled groove pipe to be joined: 6 in. or smaller -- Schedule 10. With EPDM gasket. For use with Schedule 5 pipe. For use with Allied Super-Flo or Dyna-Flow pipe.

Interfit India Ltd, SF No 112 / 3D, Part Mathapur Road, Kaniyur Village, Coimbatore 641 659, India

FireShield Series 300 Products.

Product Designation Nominal Pipe Size, in. Max Working Pressure, psi (kPa)

Remarks

Style 5*

1-12 76.1, 139.7, 165.1 mm 1-4 14-18 1-2

a, b, c, s c, n c, d, g, l, m, o, p, t a, b, c c, u

300 (2070) 300 (2070) 300 (2070) 175 (1205) 175 (1205)

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake. a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With EPDM gasket, and flush-seal gasket. d. Allied ``Dyna-Flow'' g. Bull Moose ``EDDY-Lite'' l. Allied ``XL'' m. Allied ``Super-Flo'' n. BS 1387 pipe, Med. or Heavy. o. IDOD Gal-7 p. Tex-Tube Tex-flow r. Western International Fire-Thread and Fire-Flow s. Northwest EZ-Flow t. Welded Tube ­ Berkeley, LLC Steady-Flow u. Wheatland Sch. 5 and IDOD Gal-5

JFE Pipe Fitting Mfg Co Ltd, 153 Tajime-Cho, Kishiwada Osaka, Japan

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

K-9

11/4 through 6 8

Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove

a, b, c, d, e, f, g, h, j, k, l, m, p a, b

175 (1205) 175 (1205) 300 (2070) 200 (1375)

7771

2 through 8 10

a, b a, b

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake. a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10. c. Allied ``Super-Flo'', Allied ``Dyna-Flow'', 4 in. or smaller. d. Allied ``Super 40'', Bull Moose ``Ultra-Eddy'', 3 in. or smaller. e. Bull Moose ``EDDY-LITE'', 11/4 through 2 in. f. BS 1387 medium or heavy grade, 11/4, 11/2, 2, 21/2, 3, 4, 6 in. g. Bull Moose Tube EDDY-FLOW pipe, 11/2-4 in. h. American Tube ``BLT'', 11/4 through 2 in. j. American Tube ``Dyna-Thread'' 11/4 through 2 in. k. ``Super-XL'', 11/4 through 3 in. l. Allied Tube ``XL-II'', 11/4 through 3 in. m. Central ``TL'', 11/4 through 2 in. p. Wheatland WST, 11/4 through 2 in.

Jinan Meide Casting Co Ltd, No. 3 Nanmen Road, Pingyin, Jinan, 250400 China

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

1G

11/4, 11/2, 2, 21/2, 3, 4, 5, 6, 8 10, 12 76.1, 139.7, 165 mm

1GS

2,

21/2,

3, 4, 6, 8

76.1, 139.7, 165 mm

Remarks:

Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove

a, b, c, d a, c c, d a, b, c, d c, d

300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070)

a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 40; 8 in. NPS and larger ­ Schedule 30.

FM Approvals

1-276

September 2007 -- Approval Guide Automatic Sprinkler Systems

b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall. c. Approved when supplied with EPDM gasket. d. Approved for use with GB/T3092 regular and extra heavy pipe, ISO 4200, and BS 1387 medium and heavy pipe.

Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

007* 1, 11/4,

76 mm 11/2, 2, 2, 21/2, 3, 4, 6

1 1/ 2,

21/2,

3, 4

Cut Groove, Rolled Groove Cut Groove, Rolled Groove Rolled Groove Cut Groove, Rolled Groove Cut Groove, Rolled Groove Cut Groove, Rolled Groove Cut Groove, Rolled Groove Cut Groove, Rolled Groove Cut Groove, Rolled Groove Cut Groove, Rolled Groove Rolled Groove

c, d, f, g, h a, b, c, f, g, h d, e, f, g, h a, b, c, d, f, g, h a, b, c, d, h a, b, c, d, h a, b, c, d, h a, b, c, d, h a, b, c, f, g, h a, b, c, f, h a, b, c, f, h

140, 165 mm 007RT 11/2, 2, 3, 4, 6 76, 140, 165 mm 75RT 1 1/ 2, 2, 3, 4, 6, 8 76, 140 76R 79* *

Remarks:

10, 12 2-8 2, 21/2, 3

175 (1205) 175 (1205) 175 (1205) 175 (1205) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 500 (3445) 300 (2070)

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in areas subject to earthquake. a. b. c. d. e. f. g. h. Minimum schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Minimum schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. or larger ­ 0.188 Wall (5 mm Wall). With EPDM ``EP'' gasket (green stripe). For use with DIN 2448 and 2458 steel pipe. For use with all FM Approved Thinwall steel sprinkler pipe. With EPDM ``EA'' gasket (violet stripe). For installation with cast rigid insert placed in the bolt pocket, according to the manufacturer's instructions. With EPDM ``EP'' gasket with pre-lubricated material.

NIBCO Inc, 1516 Middlebury St, Elkhart IN 46515

Steelok Style R75 Grooved Couplings.

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

R75* Grooved* Couplings

1-8 1, 11/4 1-4 1-3 11/2-3

Cut Groove Rolled Groove Rolled Groove '' '' ''

a, b, c c, f c, e, g, i, j c, d, h c

300 (2070) 175 (1205) 300 (2070) 300 (2070) 175 (1205)

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake. a. b. c. d. e. f. g. h. i. j. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. or larger ­ 0.188 in. (5 mm) wall. With EPDM gasket. When joining Allied Tube & Conduit ``XL'' threadable Thinwall pipe. FM Approved for use on Allied Tube & Conduit ``Dyna-Flow'' non-threadable Lightwall pipe. For Schedule 5 non-threadable Lightwall pipe as manufactured by Bull Moose Tube Co. When joining Allied Tube & Conduit ``Super-Flo'' non-threadable Lightwall pipe. For use with Central Sprinkler ``TL'' threadable Thinwall pipe, Allied ``BLT'' and Wheatland ``WLS.'' For use on Northwest EZ Flow non-threadable Lightwall pipe in 4 in. nominal size. For use with Bull Moose Tube EDDY-Flow pipe.

National Fittings Inc, 295 East Swedesford Road #280, Wayne PA 19087-1462

FireShield Series 300 Products.

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

Style 5*

2-3 2-4 2

Cut Groove, Rolled Groove '' ''

c, l c, d, m c, g

175 (1205) 175 (1205) 175 (1205)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-277

Product Designation

Nominal Pipe Size, in.

Pipe Ends

Remarks

Max Working Pressure, psi (kPa)

2-8 3-8 2

'' Rolled Groove ''

a, b, c c, n c, o, p

175 (1205) 175 (1205) 175 (1205)

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake. a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With standard EPDM gasket, or dry lubricant EPDM gasket. d. Allied ``Dyna-Flow.'' g. Bull Moose ``EDDY-Lite.'' l. Allied ``XL.'' m. Allied ``Super-Flo.'' n. Tex-Tube ``Tex-Flow'' Lightwall pipe. o. Western International Forest Products ``Fire Thread'' threadable Thinwall pipe. p. Western International Forest Products ``Fire Flow'' non-threadable Lightwall pipe.

Qingdao V-Cart Piping Systems Co Ltd, JuiZhao Road, NanGuan Industry Zone, JiaoZhou City, Qingdao, China

Product Designation Nominal Pipe Size, in. or mm Pipe Ends Max Working Pressure, psi (kPa)

Remarks

11/4-2 57, 76 mm Figure 5* 3 4 through 12 108, 133, 139, 159, 165 mm

a. b. c. d.

Cut Groove Rolled Groove '' ''

a, b, c, d a, b, c, d a, b, c, d

34 (495) 27 (390) 20 (290)

Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 or 10 in. ­ 0.188 in. (5 mm) wall. With EPDM gasket. For use with GB/T 3091-93 or GB/T 8163-99 Pipe.

Robor Pipe Systems, Box 1098 Isando, Gauteng 1600, South Africa

Style ``STEELGRO R75'' Grooved.

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

Pipe Couplings*

1-8 1, 11/4

Cut Groove Rolled Groove Rolled Groove '' '' '' Rolled Groove Cut Groove

a, b, c c, f c, e, g, i, j c, d, h c, d c, k

1-4 1-3 11/2-3 76, 139, 165

300 (2070) 175 (1205) 300 (2070) 300 (2070) 175 (1205) 300 (2070)

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake. a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With EPDM gasket. d. When joining Allied Tube & Conduit ``XL'' threadable Thinwall pipe. e. FM Approved for use on Allied Tube & Conduit ``Dyna-Flow'' non-threadable Lightwall pipe. f. For Schedule 5 non-threadable Lightwall pipe as manufactured by Bull Moose Tube Co. g. When joining Allied Tube & Conduit ``Super-Flo'' non-threadable Lightwall pipe. h. For use with Central Sprinkler ``TL'' threadable Thinwall pipe, Allied ``BLT'' and Wheatland ``WLS.'' i. For use on Northwest EZ Flow non-threadable Lightwall pipe in 4 in. nominal size. j. For use with Bull Moose Tube EDDY-Flow pipe. k. For use with BS 1387 medium and heavy pipe, or equal.

SCE Company Ltd, Unit E&F, 20/F., CDW Building, 388 Castl Peak Road, Tsuen Wan, N.T., Hong Kong

Product Designation Nominal Pipe Size, in. Pipe Ends Max Working Pressure, psi (kPa)

Remarks

AQUILA Model 1G AQUILA Model 1G

Remarks:

2,

21/2,

3, 4, 5, 6

76.1, 165 mm

Cut Groove Rolled Groove Cut Groove Rolled Groove

a, b, c a, b, c

300 (2070) 300 (2070)

a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 40; 8 in. NPS and larger ­ Schedule 30.

FM Approvals

1-278

September 2007 -- Approval Guide Automatic Sprinkler Systems

b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall. c. Approved when supplied with EPDM gasket.

SPT Metal Corp, 19-1 Da Yeh St, Da Liao Hsiang, Kaohsiung Hsien, Taiwan ROC ´

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

501 Standard Rigid * 501 Standard Rigid * 502 L.W. Rigid * 502 L.W. Rigid * 502 L.W. Rigid *

11/4, 11/2, 2, 21/2, 3, 4, 5, 6, 8, 10, 12 21/2 BS, 5 BS, 6 BS 11/2-4 11/2-6 11/4, 8

Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove

c, k c, d c, e, f, g, h, i, j, m a, b, c c, k

300 (2070) 300 (2070) 175 (1205) 175 (1205) 300 (2070)

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake. a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. ­ 0.188 in. (5 mm) wall. c. With EPDM gasket. d. British Standard Pipe e. When joining Allied Tube & Conduit ``XL'' threadable Thinwall pipe, 1-2 in. only. f. For use on Allied Tube & Conduit ``Dyna-Flow'' non-threadable Lightwall pipe. g. When joining Allied Tube & Conduit ``Super-Flo'' non-threadable Lightwall pipe. h. For use on Northwest ``EZ-Flow'' non-threadable Lightwall pipe in 4 in. nominal size. i. For use with Central Sprinkler ``TL'' threadable Thinwall pipe. j. For use with Bull Moose Tube EDDY-Flow pipe. k. For use on Schedule 40 Cut Groove and Rolled Groove only. m. For use with Wheatland ``Mega-Flow'' non-threadable Thinwall pipe.

Shanghai Recomb Piping System Co Ltd, No. 270 Yixian Rd, Shanghai 200434, P.R. China

Product Designation Pipe Actual Size mm Pipe Ends Remarks Max Working Pressure, psi (kPa)

XGQT1 XGQT1

33.7, 42, 48, 60, 73, 76, 89, 108, 114, 133, 140, 141.3, 159, 165, 168 and 219 273 and 325

Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove Rolled Groove, Cut Groove

a, b, c a, b, c

300 (2070) 175 (1205) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 175 (1205)

XGQT1-42.4 XGQT1-48.3 XGQT1-60.3 XGQT1-76.1 XGQT1-88.9

42.4 48.3 60.3 76.1 88.9

a, b, c a, b, c a, b, c a, b, c a, b, c

XD01 XD01 XD01 XD01 XD01 XD01 XD01 XD01

50A/2 65A/21/2 80A/3 100A/4 125A/5 150A/6 200A/8 250A/10

a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c a, b, c

a. Min schedule cut groove pipe to be joined: 6 in. or smaller -- Schedule 40; 8 in. or larger -- Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller -- Schedule 10; 8 in. or larger -- 0.188 in. (5 mm) wall. c. With EPDM gasket.

Shanghai Vision Mechanical Joint Co Ltd, Jinlan Road, Loutang Industrial Park, Jiading District, Shanghai 201807 PRC

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

001

11/4, 11/2, 2, 21/2, 3, 4, 6, 8

Cut Grooved Rolled Groove

a, b, c, d, e

300 (2070)

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-279

Product Designation

Nominal Pipe Size, in.

Pipe Ends

Remarks

Max Working Pressure, psi (kPa)

001

Remarks: a. b. c. d.

45, 57, 76, 108, 133, 159, 165 mm

Cut Groove Rolled Groove

a, b, c, d, e

300 (2070)

Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 40; 8 in. and larger ­ Schedule 30. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller ­ Schedule 10S; 8 in. NPS and larger ­ 0.188 in. (5 mm) wall. With EPDM gasket. For use with Chinese Standard GB/T 3091-1993, GB/T 3092-1993 welded steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000, Schedule 40 pipe (8 in. NPS ­ Schedule 30). e. For use with Chinese Standard GB/T 17395-1998 seamless steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000, Schedule 40 pipe (8 in. NPS ­ Schedule 30).

Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

K-9* K-9* K-9 K-9H 7771* 7771* 7771* 7771 7771 7771 R20 SS-7 C301 Z05 Z05 Z05 Z05 Z05 Z07 Z07 Z07 Z07 Z07 Z07

11/4 through 6 11/4 through 8 21/2, 5, 6 8 1 1/ 2 2 through 8 10 12 14, 16, 18, 20 22, 24 11/4, 1/2, 2, 21/2, 3, 4, 5, 6 11/4, 11/2, 2, 21/2, 3, 5, 6, 8

Rolled Groove Cut Groove '' '' '' '' '' '' '' '' '' '' '' '' '' '' '' '' '' '' '' '' ''

c, d, e, f, h, j, l, m, p, r, s, t, w a, b, g, q, s f, s a, b, s a, b, s a, b, s a, b, s a, b, s a, s a, s, u a, b, c, d, e, f, p, q, s, w a, b, s a, b, i, s a, b, s a, b, s, x a, b, c, s a, b, g, s, y a, b, s a, b, s a, b, s a, b, s a, b, s, x a, b, g, s, y a, b, s

2, 21/2, 3, 4 and 6 11/4, 11/2, 2, 21/2, 3, 4, 5, 6, 8 11/4, 11/2, 2 2, 2 1/ 2, 3, 4

11/4, 11/2, 2, 21/2, 3, 4, 11/2, 2, 21/2, 3 11/4, 11/2, 2, 21/2, 3, 4

5, 6, 8 10, 12 11/4, 11/2, 2 1 1/ 4, 11/2, 2, 21/2, 3, 4

'' ''

11/2,

2,

21/2,

3

175 (1205) 300 (2070) 300 (2070) 300 (2070) 500 (3447) 300 (2070) 200 (1375) 300 (2070) 175 (1205) 175 (1205) 300 (2070) 300 (2070) 200 (1380) 350 (2410) 350 (2410) 300 (2070) 300 (2070) 175 (1205) 500 (3447) 400 (2760) 350 (2410) 350 (2410) 300 (2070) 175 (1205)

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake. a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10. c. Allied ``Super-Flo'', Allied ``Dyna-Flow'', 4 in. or smaller. d. Allied ``Super 40'', ``Super-XL'', 11/4 through 3 in. e. Bull Moose ``EDDY-LITE'', 11/4 through 2 in. f. BS 1387 medium or heavy grade, 11/4, 11/2, 2, 21/2, 3, 4, 5, 6 in. g. Bull Moose Tube EDDY-Flow pipe, 11/4 through 4 in. h. American Tube ``BLT'', 11/4 through 2 in. i. For use with copper tubing in ``K'' type pipe. j. American Tube ``Dyna-Thread'' 11/4 through 2 in. k. ``Super-XL'', 11/4 through 3 in. l. Allied Tube ``XL-II'', 11/4 through 3 in. m. Central ``TL'', 11/2 through 2 in. p. Wheatland WST, 11/4 through 2 in. q. ``Fire-Thread'', 11/2 through 2 in. r. ``Fire-Flow'', 11/4, 11/2, 4 in. s. EPDM gasket.

FM Approvals

1-280

September 2007 -- Approval Guide Automatic Sprinkler Systems

t. IDOD Systems ``Gal-5'', 11/4 through 2 in. u. Schedule 20. v. Schedule 30. w. Bull Moose ``Ultra-EDDY'', 2 in. or smaller. x. Allied Tube ``XL'' y. Wheatland ``Mega-Flow'', 11/4 through 4 in.

Taehwa Metal Co Ltd, 577-3 Kajwa-Dong, Seo-ku,Incheon, Korea 404-812

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

AJ520 AJ520 AJ520

a. b. c. d. f.

11/4, 11/2, 2 76 mm ­ 12 14-24

Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove Cut Groove

a, b, c, d a, b, c, f a, b, c, f

300 (2070) 300 (2070) 175 (1205)

Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 or 10 in. ­ 0.188 in. (5 mm) wall. With EPDM gasket (green Stripe) For use with Korean KS D3507 pipe. For use with metric OD pipe.

Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

Grinnell 7400*

1-8 10-12 3-8 76.1, 139.7, 165.1 mm

Rolled Groove, Cut Groove '' Rolled Groove Rolled Groove, Cut Groove

a, b, c, d, e, f, j a, b, c c, n c, h

300 (2070) 300 (2070) 175 (1205) 300 (2070)

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in areas subject to earthquake. a. b. c. d. e. f. h. j. n. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 in. or larger ­ 0.188 in. (5 mm) wall. With EPDM gasket (green or violet stripe). Min schedule pipe to be joined: 3 in. or smaller ­ Allied Tube & Conduit FM Approved ``XL'', ``Super-XL'' and ``Super-40'' Thinwall pipe. Min schedule pipe to be joined: Allied Tube & Conduit ``Dyna-Flow'' Lightwall pipe, 1-3 in. Min schedule pipe to be joined: Allied Tube & Conduit ``Super-Flo'' Lightwall pipe, 1-4 in. Metric Pipe: Equivalent to 76.1, 108, 133, 139.7, 159 and 165.1 mm. British Standard 1387, medium or equal. For use with Central Sprinkler ``TL'' threadable Thinwall pipe. Tex-Tube ``Tex-Flow'' Lightwall pipe. Nominal Pipe Size, in. Pipe Ends Max Working Pressure, psi (kPa)

Product Designation

Remarks

572

11/4-8

Rolled Groove Cut Groove Rolled Groove '' '' '' Rolled Groove Cut Groove Rolled Groove '' '' '' Rolled Groove Rolled Groove Cut Groove Rolled Groove Rolled Groove Rolled Groove

a, b, c, e, q

300 (2070) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 300 (2070) 300 (2070) 500 (3445) 300 (2070) 300 (2070) 175 (1205)

11/4-6 11/4-2 11/4-4 6 577 1-8 1-6 1-2 1-2, 6 76, 139, 165 mm 772 11/4-2 11/2-4 11/4-6 11/4-4 11/4-21/2

c, e, f, j, u c, e, g, h, p, r, s, t c, e, o, p c, e, l a, b, c, e, n c, e, f, i, c, e, g, h, o, p, r, s, t c, e, j, l, m, u c, e, n, v c, p, v a, b, c, e c, e, f, l, q c, o, e, w c, e, j, m, u

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-281

Product Designation

Nominal Pipe Size, in.

Pipe Ends

Remarks

Max Working Pressure, psi (kPa)

11/4-2 11/4-4 5, 6 8 5 6 8 10, 12 76, 165 mm

'' '' '' '' Cut Groove '' '' Cut Groove Rolled Groove Cut Groove Rolled Groove

c, e, g, h, r, s, t c, p b, c, e b, c, e a, c, e a, c, e a, c, e a, b, c, e c, e, n

300 (2070) 300 (2070) 300 (2070) 400 (2760) 300 (2070) 400 (2760) 450 (3105) 250 (1725) 300 (2070)

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake. a. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. b. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10S; 8 in. or larger ­ 0.188 in. (5 mm) wall. c. With EPDM gasket (green stripe). For use with standard lubricant or dry lubricant. e. Also available with Tri-Seal EPDM gasket. Recommended by the manufacturer for dry systems. For use with standard lubricant or dry lubricant. f. For use with Allied Tube & Conduit ``Dyna-Flow'', Northwest ``EZ-Flow'' and Allied ``Super-Flo'' non-threadable Lightwall pipe, in sizes up to 4 in. NPS. g. For use with Allied Tube & Conduit ``BLT'' threadable Thinwall pipe, in 6 in. NPS size. h. For use with Allied Tube & Conduit ``Dyna-Thread'' threadable Thinwall pipe. i. For use with Wheatland WLS. j. For use with Bull Moose ``Ultra-EDDY'' Schedule 5 pipe. l. For use with Northwest ``EZ-flow'' Pipe in 6 in. NPS size. m. For use with IDOD Systems Sch. 5 Pipe. n. For use with BS 1387 medium and heavy wall pipe. o. For use with Youngstown Tube Co. ``Fire-Flo'' non-threadable Lightwall steel sprinkler pipe. p. For use with Youngstown Tube Co. ``EZ-Thread'' threadable Thinwall steel sprinkler pipe. q. For use with Wheatland Tube Co. ``Mega-Flow'' non-threadable Lightwall pipe. r. For use with Wheatland Tube Co. ``Mega-Thread'' threadable Thinwall pipe. s. For use with Wheatland Tube Co. ``WLS'' threadable Thinwall pipe. t. For use with Wheatland Tube Co. ``MLT'' threadable Thinwall pipe. u. For use with Wheatland Tube Co. ``WST'' Schedule 5 non-threadable Lightwall pipe. v. For use with IDOD's Gal-7 and Gal-Flo pipe. w. For use with Bull Moose ``EDDY-flow'' non-threadable Lightwall pipe.

Victaulic Company, Box 31, Easton PA 18044

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

005*

11/4-4 5-8

Rolled Groove '' '' '' '' '' Cut Groove '' 3, 4 Rolled Groove '' '' '' '' '' '' '' '' ''

a, c, g, k, l, t a, c, g, k i, m, o, q, s, z, aa a, k, p, aa e, i, aa d, e, u, aa a, c, k, aa a, c, k, aa a, k, aa a, b, e, k, n, aa a, e, w, r, aa a, c, g, k, aa a, c, g, k, l, o, p, q , aa a, k, l, p, aa a, *, k, l, o, q, t, aa a, e, f, k a, e, k, y , aa a, e, r, aa

005H*

11/4, 11/2, 2, 21/2, 3, 4, 6 11/4, 11/2, 2, 21/2, 2 3

1 1/ 4,

11/2,

11/2, 2, 21/2, 3, 4 11/4, 11/2, 2, 21/2, 3 4-8 005H* 1 1/ 2, 2, 21/2,

005H*

76, 108, 133, 139.7, 159, 165 mm 11/2, 2, 21/2, 3, 4 11/4-2 11/4-11/2 2-3 11/4, 11/2, 2, 21/2 139, 216 mm 3-8 6

350 (2415) 300 (2070) 300 (2070) 175 (1205) 300 (2070) 300 (2070) 350 (2415) 300 (2070) 175 (1205) 350 (2415) 300 (2070) 300 (2070) 175 (1205) 175 (1205) 175 (1205) 300 (2070) 300 (2070) 300 (2070)

FM Approvals

1-282

September 2007 -- Approval Guide Automatic Sprinkler Systems

Product Designation

Nominal Pipe Size, in.

Pipe Ends

Remarks

Max Working Pressure, psi (kPa)

009*

11/4,-4

Rolled Groove Cut Groove Rolled Groove Cut Groove Rolled Groove '' '' '' 3, 4 '' '' '' '' Cut Groove

07* 07 Zero-Flex

267, 318 mm 1, 2, 3, 4, 6 1/4, 11/2, 2 1, 1 11/4, 11/2, 2 1, 11/4, 11/2, 2 1, 11/4, 11/2, 2, 2 21/2, 11/2, 21/2,

c, d, g, i, j, k, l, m, o p, q, r, s, x, y, z aaa, bb, cc, dd, ee, ff, gg e, k, f o, q, s, z, aa a, e, l, p, aa a, e, j, aa e, j, m, aa i, m, aa a, e, l, aa aa a, d, e, u, w, r, aa a, c, e, aa

300 (2070) 175 (1205) 300 (2070) 175 (1205) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 175 (1205) 300 (2070) 500 (3445) 450 (3105) 300 (2070) 400 (2760) 500 (3445) 400 (2760) 500 (3445) 300 (2070) 175 (1205) 450 (3105) 400 (2760) 350 (2415) 175 (1205) 300 (2070) 300 (2070) 750 (5170) 700 (4825) 500 (3445) 300 (2070) 250 (1725) 250 (1725) 250 (1725) 250 (1725)

11/2,

11/2, 2, 21/2, 3, 4 11/2, 2, 21/2, 3, 4 1, 11/4, 11/2, 2, 21/2, 3, 4, 5, 6 8 1-2 10, 12 1, 1 1/ 4, 11/2, 2, 21/2, 3, 4 5, 6, 8 6 6 6 1/ 2 8 10, 12 10, 12 76, 108, 133, 139.7, 159 mm 216 mm, HP-70 2-4 2-8 10, 12 2-12 HP-70ES 008 Stainless Steel Coupling 2-8 3-8 in.

'' Rolled Groove '' '' '' '' '' '' '' '' '' '' '' '' Cut Groove '' Rolled Groove Special Rolled Groove Cut Groove Rolled Groove

a, c, e, aa t, aa a, c, e, aa a, e, g, aa a, e, g, aa a, c, e, aa a, e, r, aa b, c, e, aa a, c, e, aa a, c, e a, e, g a, b, n, aa a, e, f, k q, z, aa a, c, e, aa a, c, e a, g, aa v* a, e, g c, h, k a, e, g c, h, k

76, 139, 165 mm

Cut Groove Rolled Groove

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake. a. Also available with Style 77FS gasket. Recommended by manufacturer for use with dry pipe systems. b. For steel pipe having metric sized outside dia. (ref. DIN 2448 & 2458). c. Min schedule cut groove pipe to be joined: 6 in. or smaller ­ Schedule 40; 8 in. or larger ­ Schedule 30. d. For use with Youngstown Tube ``Fire-Flo'' non-threadable Lightwall steel sprinkler pipe. e. With gasket E (green stripe), H (white stripe) or L (solid red), using standard gasket lubricant or Vic-Plus dry lubricant. f. For use with JIS steel pipe. g. Min schedule rolled groove pipe to be joined: 6 in. or smaller ­ Schedule 10; 8 in. or larger ­ 0.188 in. (5 mm) wall. h. For use with Schedules 10 and 40 stainless steel pipe. i. For use with Welded Tube­Berkeley LLC ``Steady Flow'' non-threadable Lightwall steel sprinkler pipe in sizes 11/4, 11/2, 2, 21/2, 3, and 4 in. NPS. j. For use with Youngstown Tube ``EZ-Thread'' threadable Thinwall steel sprinkler pipe. k. With gasket E, Grade A (violet stripe) with or without dry lubricant . l. For use with Allied Tube & Conduit ``XL'' and BLT threadable Thinwall pipe. m. For use with Welded Tube­Berkeley LLC ``Steady Thread'' threadable Thinwall steel sprinkler pipe in sizes 1, 11/4, 11/2, and 2 in. NPS. n. For steel pipe having outside dia. sized per British Standard 1387, medium or equal. o. For use on Allied Tube & Conduit ``Dyna-Flow'' and Super-flo non-threadable Lightwall pipe. p. For Schedule 5 non-threadable Lightwall pipe as manufactured by Bull Moose Tube Co.

FM Approvals

September 2007 -- Approval Guide Automatic Sprinkler Systems

1-283

q. For use with IDOD Systems Gal-7 and Gal-flo pipe, 11/4-2 in. sizes. r. For use on Wheatland ``Mega-Flow'' pipe. s. For use on Northwest ``EZ-Flow'' non-threadable Lightwall pipe in 4 and 6 in. nominal size. u. For use with Bull Moose Tube EDDY-Flow pipe. v. For use on Schedules 10 and 40 pipe with end seal grooves only. Not for use with standard rolled or cut grooves. Not for use with hydrocarbon based fluids. x. For use with IDOD Systems Gal-5 and All-Gal pipe, 11/4-2 in. sizes at 175 psi. y. Tex-Tube ``Tex-Flow'' Lightwall pipe. z. For use with Western ``Fire-Flow'' and ``Fire-Thread'' pipe. aa. For use with VicMax EPDM Gaskets in 2 through 8 in. and 76 and 165 mm sizes. aaa. = For use with ``EDDY-lite'' and ``EDDY-thread'' pipe made by Bull Moose Tube. bb. = For use with ``GL'', ``WLS'' and ``MLT'' pipe made by Wheatland Tube. cc. = For use with ``WST'' pipe at 175 psi, as made by Wheatland Tube. dd. = For use with ``Ultra-EDDY'' pipe at 175 psi, as made by Bull Moose Tube. ee. = For use with ``Dyna-light'' pipe at 175 psi, as made by Allied Tube & Conduit. ff. = For use with Allied Tube & Conduit ``Dyna-thread'' threadable Thinwall pipe. gg. = For use with Wheatland Tube ``Mega-thread'' threadable Thinwall pipe.

Victaulic-Europe, Neerhonderd 37, Industriepark Kwatrecht, B-9230 Wetteren, Belgium

Product Designation Nominal Pipe Size, in. Pipe Ends Remarks Max Working Pressure, psi (kPa)

005*

11/4-11/2 2-3 11/4, 11/2, 2 11/4, 11/2, 2, 21/2, 3, 4, 6 11/4, 11/4, 11/2, 2, 2, 21/2, 3

Rolled Groove '' '' '' '' '' Cut Groove Rolled Groove '' '' '' '' 3 21/2, '' Cut Groove '' Rolled Groove '' 2, Rolled Groove '' '' '' '' '' '' '' '' Cut Groove '' Rolled Groove

a, c, g, k, l, o, p, q a, k, l, p a, k, l, t o, q, s l, p a, g a, c, k a, b, n b, c, e, g o, q, s a, e, l, p a, e, l u a, c, e a, c, e t a, c, e a, e, g a, e, g a, c, e b, c, e a, c, e a, c, e a, e, g a, b, n q a, c, e a, c, e a, g

11/2,

21/2,

3, 4, 5, 6

11/4, 11/2, 2, 21/2, 3, 4, 5. 6 76, 108, 133, 139.7, 153, 159 mm