MAKE-UP AIR UNITS

®

Our Philosophy

If you need a piece of air handling equipment and cannot find something "off the shelf" that will work, there is a good chance we have already built something similar for someone else. We at Hydro-Temp will work with you to build a piece of equipment to fit your design. If your requirement is indoor, rooftop, or even squeezing a 50 ton unit through a 3 foot door, we will try our best to accommodate your needs. In most cases the relationship with the manufacturer ends at the time of sale. In the case of Hydro-Temp the relationship begins at the time of sale. It is extremely important to us that we have met your needs and have a continuing relationship with you our customer.

HYDRO-TEMP

Earth Coupled Heat Pumps

®

120 Ton Rooftop Make-up Air Unit

HYDRO-TEMP

Earth Coupled Heat Pumps

®

What can a Make-Up Air unit do for you?

In today's more health conscious society, greater attention is being paid to indoor air quality than ever before. Unlike outdoor air, indoor air is recycled again and again which causes it to trap and build up pollutants. Over the past several decades indoor air pollution has become a greater problem due to the drive for more tightly sealed buildings in an effort to increase heating and cooling efficiency. More and more government entities from federal down to local municipalities are requiring that new and retrofit HVAC installations have some method of introducing fresh air into a space in order to prevent build up of carbon dioxide levels and other unwanted contaminants and V.O.C.'s. One way to increase fresh air circulation is to leave a window open, but this makes it difficult to control the temperature in the room or building. Hydro-Temp's solution is the Make-Up Air unit. This unit draws in fresh air from outside and conditions it before introducing it into the occupied spaces. There are several levels available in this type of equipment. In its simplest form, the make up air unit will pull in air from the outside heat or cool the air before introducing it directly into the occupied spaces. The next step would be to add "reheat" to the unit. Warm air is brought into the unit, dehumidified, and reheated to a comfortable level before introducing it into the occupied space. The ultimate in efficiency for the make up air unit is to collect all that already conditioned exhaust air and use the temperature difference between that exhaust air and the incoming air to precondition the incoming air by passing both streams of air through a heat exchanger. The exhaust air gives up its temperature to the incoming air making the task of conditioning the incoming air that much easier. The incoming air is then passed through the rest of the cycle as needed before being introduced into the conditioned spaces. Hydro-Temp's microprocessor controls can be customized to the customer's needs, sampling temperatures and humidity levels at numerous points in the cycle, adjusting the operation of the unit for the most energy efficient use of the various components in the system. There are several variations on this type of unit, from partial heat exchange where a portion of the return air to the unit is exhausted all or part of the time, to 100% outside air where all air entering the unit from inside space is exhausted and replaced with conditioned outside air.

HYDRO-TEMP

Earth Coupled Heat Pumps

®

How it Works

In the cooling mode air is brought in from outside, cooled and there by dehumidified. If the unit is equipped with reheat, the incoming air is warmed to a neutral temperature (adjustable) and introduced into the space. To accomplish reheat a second air coil is placed in parallel with the water coil. As reheat is required a portion of the hot refrigerant is diverted away from the water coil (condenser is this mode) and sent to the second air coil allow it to warm up the dehumidified air. This modulation of refrigerant is controlled by stepper motor modulating valve which allow the required percentage of refrigerant to be diverted to where it is needed.

Disch arge Air Temperature Sensor Disch arge Hu midity Sensor

Supply Air Outside Air In Outdoor Temperature Sensor Outdoor Hu midity Sensor Ma in Air Coil Mo dulating Valve B

Suction

Compressor (s) Reversing Valve

Temperature Mo dulating Air Coil

Stepper M otor Tx Valve

W ater Coil

Discharge

Mo dulating Valve A

Cooling Mode Refrigeration Circuit By adding a reversing valve to the system, the make-up air unit can heat as well. Fresh air can be warmed before being introduced into the space. With the refrigeration circuit shown the air can be re-cooled (if desired) to continue to introduce "neutral" air into the space. In most cases, however, the air is introduced as warm as possible to help reduce the heating requires of the space conditioning equipment. In the heating mode it is important to maintain the entering air coming to the unit above 45 degrees. This is accomplished by resistance heat or by using the most preferred method of reheat recovery using a plate type air to air heat exchanger or a heat recovery wheel.

Disch arge Air Temperature Sensor Disch arge Hu midity Sensor

Supply Air Outside Air In Outdoor Temperature Sensor Outdoor Hu midity Sensor Ma in Air Coil Mo dulating Valve B

Suction

Compressor (s) Reversing Valve

Temperature Mo dulating Air Coil

Stepper M otor Tx Valve

W ater Coil

Discharge

Mo dulating Valve A

Heating Mode Refrigeration Circuit

HYDRO-TEMP

Earth Coupled Heat Pumps

®

The following illustrations show the use of a plate type air to air heat exchanger in the partial and full make-up air modes. Units can be customized to meet air flow, control strategies, cabinet orientations or any specific needs for the particular installation.

Controls

The programmable controller used in the make-up air equipment is compatible with most building automation systems. The controller can communicate with the following communication protocols; BACnet® · LonWorks · Modbus · N2. Programming is custom written, factory tested and is based on proven algorithms. Each job comes with a hand held plug-in panel to monitor the status of the equipment, change set-points and do unit diagnostics. We will work with you to give you the best control solution.

HYDRO-TEMP

Earth Coupled Heat Pumps

®

General Specifications For Make Up-Air Units

CABINET: Cabinets will be built of quality materials, appropriate for the setting into which the unit will be installed. The cabinet design will be optimized for installation and service. Outdoor cabinets are typically salt spray rated 2" double wall construction with an extruded aluminum frame and indoor units are similar construction with 1" thick multi-density sound absorbing insulation. DRAINPAN: One piece sloped and welded stainless steel. REFRIGERATION CIRCUIT: Typical refrigeration circuits include a reversing valve, electronic stepper motor expansion valve, electronic stepper motor modulating hot gas reheat valves and high/low side access valves. COMPRESSOR: Typical refrigeration circuits include parallel hermetically sealed compressors (scroll, reciprocating or screw). A parallel compressor installation refers to a system of compressors interconnected and working together. Though parallel installation has several benefits, the primary reason is reduced operating cost through greater control of capacity and power consumption. This is achieved by staggering compressor switch-on sequences that allow the parallel system to match its power with the capacity needed. The compressors are equipped with overload protection and are mounted on rubber vibration insulators. HEAT EXCHANGERS: Stainless steel brazed plate with brazed fittings. Includes cabinet mounted 18 mesh strainer. AIR COIL: Heatcraft ARI certified, seamless copper filled tube with aluminum lanced fins and aluminum end plates. BLOWER: Delhi Industries centrifugal blower with forward curved galvanized wheel and enamel finish frame. BLOWER MOTOR: Baldor motors rated for continuous operation. Blower motors controlled by Cutler-Hammer adjustable frequency drive which includes electronic motor overload protection circuits that ar designed to meet the requirements of NEC Article 430-2. CONTROLS: Automated Logic Controls, BACnet compatible custom programmable highspeed 16 bit processor with 1 mb flash memory and 1 mb of battery backed ram. ELECTRICAL: Can be configured with built in disconnect, dual point power connection. All internal components are separately fused. OPTIONS AND ACCESSORIES: Corrosion resistant heat exchanger Cleanable electrostatic filters UVC Antibacterial light CO2 Sensors

SUBMITTAL DATA

PROJECT

CATALOG

10/10/06

UNIT DESIGNATION

MAU-15

PHYSICAL INFORMATION

15 Ton Make Up Air W/Reheat - 3 Stage HHX31C180CTXXK1S FAN WHEEL 11.128 X 8 FAN MOTOR 1 1/2 HP Compressor 1 SCROLL 5 TONS Compressor 2 SCROLL 10 TONS Heat/Cool Air Coil 50X30 6 Rows Reheat Air Coil 50 x 30 2 Rows Water Flow 47.0 GPM Loop Pump/s NONE PRESSURE DROP 8.46 Ft of Hd Water Source HX 15 Tons AISI 316 L SS Refrigerant R-22 Filter Size 24X30 (x2) Weight 1800 LBS

DIMENSIONS AND LAYOUT MAY CHANGE WITH SPECIFIC SITE REQUIREMENTS. UNIT ELECTRICAL DATA

Unit VOLTAGE 60 HZ FLA MCA MOCP RECOMM BREAKER Number of Electrical feeds to unit

208V/3Ø 460V/3Ø

58.4 33.2

67.3 38.4

103.0 59.1

80 50

1 1 Dimensions in Inches

A 96 E 0

B 64 F 0

C 36 G 0

D 0 H 0

SX

SY

RX

RY 30 3 IN 1 IN

11 12 50 WATER SUPPLY AND RETURN LINES CONDENSATE LINE

PERFORMANCE DATA

Cabinet Tonnage 15 HEATING GPM 47 EWT 85°F HC 67,321 COP 4.5 COOLING GPM 47.0 GPM EADB 91°F EWT 85°F EAWB 79°F HR 234,553 LADB 55°F TC 187,703 LAWB 55°F SC 86,690 EER 13.7

External Static Pressure Internal Static Pressure Total Static Pressure

1.5 0.4 1.9

CFM

EXTERNAL STATIC PRESSURE @1339 RPM 1.0" 1.1" 1.2" 1.3" 2,325 2,275 2,200 2,125

1.4" 2,050

1.5" 2,000

1.6" 1,950

SUBMITTAL DATA

PROJECT

CATALOG

10/10/06

UNIT DESIGNATION

MAU-25

PHYSICAL INFORMATION

25 Ton Make Up Air W/Reheat - 3 Stage HHX31C300CTXXK1S FAN WHEEL 12.5 C 12.5 FAN MOTOR 3 HP Compressor 1 DANFOSS 10 TONS Compressor 2 DANFOSS 15 TONS Heat/Cool Air Coil 58X30 6 Rows Reheat Air Coil 58X30 2 Rows Water Flow 82.0 GPM Loop Pump/s NONE PRESSURE DROP 8.7 Ft of Hd Water Source HX (2X) 12.5 Tons AISI 316 L SS Refrigerant R-22 Filter Size TBD Weight 3000 LBS

DIMENSIONS AND LAYOUT MAY CHANGE WITH SPECIFIC SITE REQUIREMENTS. UNIT ELECTRICAL DATA

Unit VOLTAGE 60 HZ FLA MCA MOCP RECOMM BREAKER Number of Electrical feeds to unit

208V/3Ø 460V/3Ø

119.7 61.5

138.5 70.3

213.5 105.3

160 80

1 1

Dimensions in Inches A 106 E 0 B 70 F 0 C 36 G 0 D 0 H 0 SX SY RX RY 30 3 IN 1 IN 16 14 58 WATER SUPPLY AND RETURN LINES CONDENSATE LINE

PERFORMANCE DATA

Cabinet HEATING Tonnage GPM 25 82 EWT 85°F HC 145,200 COP 4.4 COOLING GPM 82.0 GPM EADB 91°F EWT 85°F EAWB 79°F HR 412,785 LADB 55°F TC SC 329,600 152,224 LAWB 55°F EER 13.5

External Static Pressure Internal Static Pressure Total Static Pressure

1.5 0.5 2.0

EXTERNAL STATIC PRESSURE @1175 RPM 1.0" 1.1" 1.2" 1.3" CFM 4,450 4,350 4,250 4,150

1.4" 4,075

1.5" 4,000

1.6" 3,900

SUBMITTAL DATA

PROJECT

CATALOG

10/10/06

UNIT DESIGNATION

MAU-45

PHYSICAL INFORMATION

45 Ton Make Up Air W/Reheat - 3 Stage HHX31C540CTXXK1S FAN WHEEL 15.5 X 15 FAN MOTOR 5 HP Compressor 1 DANFOSS 15 TONS Compressor 2 DANFOSS 25 TONS Heat/Cool Air Coil 70X36 6 Rows Reheat Air Coil 70X36 2 Rows Water Flow 135.0 GPM Loop Pump/s NONE PRESSURE DROP 23.3 Ft of Hd Water Source HX 50 Tons AISI 316 L SS Refrigerant R-22 Filter Size TBD Weight 5400 LBS

DIMENSIONS AND LAYOUT MAY CHANGE WITH SPECIFIC SITE REQUIREMENTS. UNIT ELECTRICAL DATA

Unit VOLTAGE 60 HZ FLA MCA MOCP RECOMM BREAKER Number of Electrical feeds to unit

208V/3Ø 460V/3Ø

177.1 91.9

199.1 104.2

287.0 153.5

240 120

1 1

Dimensions in Inches A 120 E 0 B 72 F 0 C 60 G 0 D 42 H 0 SX SY RX RY 36 4 IN 1 IN 19 16 70 WATER SUPPLY AND RETURN LINES CONDENSATE LINE

PERFORMANCE DATA

Cabinet HEATING Tonnage GPM 45 135 EWT 85°F HC 215,400 COP 4.3 COOLING GPM 135.0 GPM EADB 91°F EWT 85°F EAWB 79°F HR 674,163 LADB 55°F TC SC 538,669 248,781 LAWB 55°F EER 13.6

External Static Pressure Internal Static Pressure Total Static Pressure

1.5 0.7 2.2

EXTERNAL STATIC PRESSURE @1100 RPM 1.0" 1.1" 1.2" 1.3" CFM 6,550 6,450 6,350 6,275

1.4" 6,150

1.5" 6,000

1.6" 5,900

SUBMITTAL DATA

PROJECT

CATALOG

10/10/06

UNIT DESIGNATION

RTU-50

PHYSICAL INFORMATION

50 Ton Make Up Air W/Reheat - 3 Stage HHX41C600CTXXK1S FAN WHEEL 18 X 18 FAN MOTOR 5 HP Compressor 1 DANFOSS 20 TONS Compressor 2 DANFOSS 25 TONS Heat/Cool Air Coil 70 X 36 6 Rows Reheat Air Coil 70 X 36 2 Rows Water Flow 153.0 GPM Loop Pump/s NONE PRESSURE DROP 18.5 Ft of Hd Water Source HX 50 Tons AISI 316 L SS Refrigerant R-22 Filter Size 25X20 (x3) Weight 6000 LBS

DIMENSIONS AND LAYOUT MAY CHANGE WITH SPECIFIC SITE REQUIREMENTS.

28 .6 60

T ie Do wn Eyel ets DO NO T USE FOR L IFT ING

20 .3 75 2.68 8

Sup ply Air

23 .3 75

Blo wer an d Air Coi l Servi ce Side

Co mpresso r a nd El ectrical Servi ce Side

Sup ply W ater In and O u t 3" FPT 13 0.000

78 .0 00

Li ftin g Poin ts in Bo ttom R ail

52 .0 00

Ra in Ho od Hi nge d Fi lter Rack in h oo d. F ilter Ra ck h old s 3 x 20" x 25 " x 2" fil te rs

UNIT ELECTRICAL DATA

Unit VOLTAGE 60 HZ FLA MCA MOCP RECOMM BREAKER Number of Electrical feeds to unit

90 .0 00

208V/3Ø 460V/3Ø

180.0 92.6

202.0 104.9

289.9 154.2

240 120

1 1

Dimensions in Inches A 130 E 0 B 78 F 0 C 52 G 0 D 0 H 0 SX SY RX RY 36 4 IN 1 IN 24 19 70 WATER SUPPLY AND RETURN LINES CONDENSATE LINE

PERFORMANCE DATA

Cabinet Tonnage 50 HEATING GPM 153 EWT 85°F HC 294,772 COP 4.2 COOLING GPM 153.0 GPM EADB 91°F EWT 85°F EAWB 79°F HR 764,589 LADB 55°F TC SC 610,476 281,945 LAWB 55°F EER 13.5

External Static Pressure Internal Static Pressure Total Static Pressure

1.5 0.7 2.2

EXTERNAL STATIC PRESSURE @824 RPM 1.0" 1.1" 1.2" 1.3" CFM 9,400 8,450 7,900 7,600

1.4" 7,300

1.5" 6,930

1.6" 6,700

SUBMITTAL DATA

PROJECT

CATALOG

10/10/06

UNIT DESIGNATION

MAU-55

PHYSICAL INFORMATION

55 Ton Make Up Air W/Reheat - 3 Stage HHX31C660CTXXK1S FAN WHEEL 18 X 18 FAN MOTOR 5 HP Compressor 1 DANFOSS 13 TONS Compressor 2 DANFOSS 13 TONS Compressor 3 DANFOSS 25 TONS Heat/Cool Air Coil 58 X 30 (X2) 6 Rows Reheat Air Coil 58 X 30 (X2) 2 Rows Water Flow 137.5 GPM Loop Pump/s NONE PRESSURE DROP 23.3 Ft of Hd Water Source HX (3X) 20 Tons AISI 316 L SS Refrigerant R-22 Filter Size TBD Weight 5400 LBS

DIMENSIONS AND LAYOUT MAY CHANGE WITH SPECIFIC SITE REQUIREMENTS. UNIT ELECTRICAL DATA

Unit VOLTAGE 60 HZ FLA MCA MOCP RECOMM BREAKER Number of Electrical feeds to unit

208V/3Ø 460V/3Ø

193.5 102.7

215.5 115.0

303.4 164.3

260 130

1 1

Dimensions in Inches A 110 E 0 B 80 F 0 C 66 G 0 D 0 H 0 SX SY RX RY 60 4 IN 1 IN 22 19 58 WATER SUPPLY AND RETURN LINES CONDENSATE LINE

PERFORMANCE DATA

Cabinet Tonnage 55 HEATING GPM 137.5 EWT 85°F HC 145,200 COP 4.4 COOLING GPM 137.5 GPM EADB 91°F EWT 85°F EAWB 79°F HR 412,785 LADB 55°F TC SC 329,600 152,224 LAWB 55°F EER 13.5

External Static Pressure Internal Static Pressure Total Static Pressure

1.5 0.5 2.0

EXTERNAL STATIC PRESSURE @791 RPM 1.0" 1.1" 1.2" 1.3" CFM 8,850 8,600 8,425 8,275

1.4" 8,175

1.5" 8,000

1.6" 7,800

SUBMITTAL DATA

PROJECT

CATALOG

10/10/06

UNIT DESIGNATION

MAU-55

PHYSICAL INFORMATION

55 Ton Make Up Air W/Reheat & Heat Recvry- 3 Stage HHX31C660CTXXK1S SUPPLY FAN WHEEL 18 X 18 SUPPLY FAN MOTOR 10 HP EXHAUST FAN WHEEL 18 X 18 EXHAUST FAN MOTOR 7.5 HP Compressor 1 SCROLL13 TONS Compressor 2 SCROLL 13 TONS Compressor 3 SCROLL 25 TONS Heat/Cool Air Coil 58 X 30 (X2) 6 Rows Reheat Air Coil 58 X 30 (X2) 2 Rows Enthalpy Wheel 54"Ø x 15" Water Flow 137.5 GPM Loop Pump/s NONE PRESSURE DROP 3.7 Ft of Hd Water Source HX (3X) 20 Tons AISI 316 L SS Refrigerant R-22 Filter Size TBD Weight 6875 LBS

DIMENSIONS AND LAYOUT MAY CHANGE WITH SPECIFIC SITE REQUIREMENTS. UNIT ELECTRICAL DATA

Unit VOLTAGE 60 HZ FLA MCA MOCP RECOMM BREAKER Number of Electrical feeds to unit

208V/3Ø 460V/3Ø

243.3 120.6

223.3 118.9

311.2 168.2

310 160

1 1

A 135 E 0

B 108 F 0

C 66 G 0

RETURN 27 W x 27 H H 0

Dimensions in Inches EXHAUST

FRESH AIR IN

SUPPLY

22 W x 19 H 27 W x 27 H 22 W x 19 H 4 IN WATER SUPPLY AND RETURN LINES 1 IN CONDENSATE LINE EADB 91°F COOLING GPM 137.5 GPM 1.5 2.1 3.6 1.5 1.6 3.1 EAWB 79°F EWT 85°F LADB 55°F HR 412,785 LAWB 55°F TC SC 329,600 152,224 EER 13.5

PERFORMANCE DATA

Cabinet Tonnage 55 HEATING GPM 137.5 SUPPLY EWT 85°F HC 145,200 COP 4.4

External Static Pressure Internal Static Pressure Total Static Pressure

EXTERNAL STATIC PRESSURE @1061 RPM 0.0" 0.5" 1.0" 1.5" CFM 10,150 9,500 8,800 8,000 EXTERNAL STATIC PRESSURE @976 RPM 0.0" 0.5" 1.0" 1.5" CFM 10,050 9,400 8,750 8,000

1.6" 7,600

EXHAUST

External Static Pressure Internal Static Pressure Total Static Pressure

1.6" 7,800

SUBMITTAL DATA

PROJECT

CATALOG

10/10/06

UNIT DESIGNATION

MAU-70

PHYSICAL INFORMATION

70 Ton Make Up Air W/Reheat - 3 Stage HHX31C840CTXXK1S FAN WHEEL 22x22 FAN MOTOR 7.5 HP Compressor 1 DANFOSS 15 TONS Compressor 2 DANFOSS 15 TONS Compressor 3 DANFOSS 15 TONS Compressor 4 DANFOSS 25 TONS Heat/Cool Air Coil 63 X 30 (X2) 6 Rows Reheat Air Coil 60 X 30 (X2) 2 Rows Water Flow 214.0 GPM Loop Pump/s NONE PRESSURE DROP 5.1 Ft of Hd Water Source HX (4X) 20 Tons AISI 316 L SS Refrigerant R-22 Filter Size TBD Weight 7070 LBS

DIMENSIONS AND LAYOUT MAY CHANGE WITH SPECIFIC SITE REQUIREMENTS. UNIT ELECTRICAL DATA

Unit VOLTAGE 60 HZ FLA MCA MOCP RECOMM BREAKER Number of Electrical feeds to unit

208V/3Ø 460V/3Ø

334.9 152.2

356.9 161.1

444.8 196.8

420 190

1 1

Dimensions in Inches A 116 E 0 B 86 F 0 C 66 G 0 D 0 H 0 SX SY RX RY 60 4 IN 1 IN 28 28 63 WATER SUPPLY AND RETURN LINES CONDENSATE LINE

PERFORMANCE DATA

Cabinet Tonnage 70 HEATING GPM 214 EWT 85°F HC 215,400 COP 4.3 COOLING GPM 214.0 GPM EADB 91°F EWT 85°F EAWB 79°F HR TC SC 1,074,887 857,007 395,804 LADB LAWB 55°F 55°F EER 13.4

External Static Pressure Internal Static Pressure Total Static Pressure

1.5 0.7 2.2

EXTERNAL STATIC PRESSURE @692 RPM 1.0" 1.1" 1.2" 1.3" CFM 11,550 11,250 10,950 10,650

1.4" 10,400

1.5" 10,000

1.6" 9,675

SUBMITTAL DATA

PROJECT

CATALOG

10/10/06

UNIT DESIGNATION

MAU-90

PHYSICAL INFORMATION

90 Ton Make Up Air W/Reheat - 3 Stage HHX41C1080CTXXK1S FAN WHEEL 22x22 FAN MOTOR 7.5 HP Compressor 1 DANFOSS 20 TONS Compressor 2 DANFOSS 20 TONS Compressor 3 DANFOSS 20 TONS Compressor 4 DANFOSS 20 TONS Heat/Cool Air Coil 70 X 36 (X2) 6 Rows Reheat Air Coil 70 X 36 (X2) 2 Rows Water Flow 268.0 GPM Loop Pump/s NONE PRESSURE DROP 23.1 Ft of Hd Water Source HX (2X) 50 Tons AISI 316 L SS Refrigerant R-22 Filter Size TBD Weight 7920 LBS

DIMENSIONS AND LAYOUT MAY CHANGE WITH SPECIFIC SITE REQUIREMENTS. UNIT ELECTRICAL DATA

Unit VOLTAGE 60 HZ FLA MCA MOCP RECOMM BREAKER Number of Electrical feeds to unit

208V/3Ø 460V/3Ø

323.1 154.3

342.6 163.2

420.5 198.9

420 200

1 1

Dimensions in Inches A 120 E 0 B 86 F 0 C 78 G 0 D 0 H 0 SX SY RX RY 60 4 IN 1 IN 28 28 63 WATER SUPPLY AND RETURN LINES CONDENSATE LINE

PERFORMANCE DATA

Cabinet Tonnage 90 HEATING GPM 268 EWT 85°F HC 294,772 COP 4.2 COOLING GPM 268.0 GPM EADB 91°F EWT 85°F EAWB 79°F HR TC SC 1,346,166 1,072,428 495,295 LADB LAWB 55°F 55°F EER 13.4

External Static Pressure Internal Static Pressure Total Static Pressure

1.5 0.7 2.2

EXTERNAL STATIC PRESSURE @692 RPM 1.0" 1.1" 1.2" 1.3" CFM 13,300 13,050 12,800 12,550

1.4" 12,275

1.5" 12,000

1.6" 11,750

SUBMITTAL DATA

PROJECT

CATALOG

10/10/06

UNIT DESIGNATION

MAU-100

PHYSICAL INFORMATION

100 Ton Make Up Air W/Reheat - 3 Stage HHX41C1200CTXXK1S FAN WHEEL 22x22 FAN MOTOR 10 HP Compressor 1 DANFOSS 25 TONS Compressor 2 DANFOSS 20 TONS Compressor 3 DANFOSS 25 TONS Compressor 4 DANFOSS 20 TONS Heat/Cool Air Coil 70 X 36 (X2) 6 Rows Reheat Air Coil 70 X 36 (X2) 2 Rows Water Flow 305.0 GPM Loop Pump/s NONE PRESSURE DROP 28.2 Ft of Hd Water Source HX (2X) 50 Tons AISI 316 L SS Refrigerant R-22 Filter Size TBD Weight 8100 LBS

DIMENSIONS AND LAYOUT MAY CHANGE WITH SPECIFIC SITE REQUIREMENTS. UNIT ELECTRICAL DATA

Unit VOLTAGE 60 HZ FLA MCA MOCP RECOMM BREAKER Number of Electrical feeds to unit

208V/3Ø 460V/3Ø

384.6 198.6

406.6 210.9

494.5 260.2

480 260

1 1

Dimensions in Inches A 120 E 0 B 88 F 0 C 80 G 0 D 0 H 0 SX SY RX RY 72 4 IN 1 IN 28 28 70 WATER SUPPLY AND RETURN LINES CONDENSATE LINE

PERFORMANCE DATA

Cabinet Tonnage 100 HEATING GPM 305 EWT 85°F HC 376,519 COP 4.3 COOLING GPM 305.0 GPM EADB 91°F EWT 85°F EAWB 79°F HR TC SC 1,529,178 1,220,952 563,890 LADB LAWB 55°F 55°F EER 13.5

External Static Pressure Internal Static Pressure Total Static Pressure

1.5 0.7 2.2

EXTERNAL STATIC PRESSURE @722 RPM 1.0" 1.1" 1.2" 1.3" CFM 15,150 14,875 14,700 14,450

1.4" 14,250

1.5" 14,000

1.6" 13,750

SUBMITTAL DATA

PROJECT

CATALOG

10/10/06

UNIT DESIGNATION

MAU-115

PHYSICAL INFORMATION

115 Ton Make Up Air W/Reheat - 3 Stage HHX41C1380CTXXK1S FAN WHEEL 25X25 FAN MOTOR 10 HP Compressor 1 DANFOSS 25 TONS Compressor 2 DANFOSS 25 TONS Compressor 3 DANFOSS 25 TONS Compressor 4 DANFOSS 25 TONS Heat/Cool Air Coil 63 X 30 (X3) 6 Rows Reheat Air Coil 60 X 30 (X3) 2 Rows Water Flow 342.0 GPM Loop Pump/s NONE PRESSURE DROP 19.7 Ft of Hd Water Source HX (2X) 50 Tons AISI 316 L SS Refrigerant R-22 Filter Size TBD Weight 9315 LBS

DIMENSIONS AND LAYOUT MAY CHANGE WITH SPECIFIC SITE REQUIREMENTS. UNIT ELECTRICAL DATA

Unit VOLTAGE 60 HZ FLA MCA MOCP RECOMM BREAKER Number of Electrical feeds to unit

208V/3Ø 460V/3Ø

394.6 212.2

438.6 236.9

614.4 335.5

500 260

1 1

Dimensions in Inches A 120 E 0 B 90 F 0 C 100 G 0 D 0 H 0 SX SY RX RY 90 4 IN 1 IN 32 32 63 WATER SUPPLY AND RETURN LINES CONDENSATE LINE

PERFORMANCE DATA

Cabinet Tonnage 115 HEATING GPM 342 EWT 85°F HC 376,519 COP 4.3 COOLING GPM 342.0 GPM EADB 91°F EWT 85°F EAWB 79°F HR TC SC 1,712,191 1,369,476 632,780 LADB LAWB 55°F 55°F EER 13.6

External Static Pressure Internal Static Pressure Total Static Pressure

1.5 0.7 2.2

EXTERNAL STATIC PRESSURE @627 RPM 1.0" 1.1" 1.2" 1.3" CFM 18,000 17,500 17,200 16,800

1.4" 16,450

1.5" 16,000

1.6" 15,700

SUBMITTAL DATA

PROJECT

CATALOG

10/10/06

UNIT DESIGNATION

MAU-120

PHYSICAL INFORMATION

120 Ton Make Up Air W/Reheat - 3 Stage HHX41C1440CTXXK1S FAN WHEEL 25X25 FAN MOTOR 15 HP Compressor 1 DANFOSS 25 TONS Compressor 2 DANFOSS 25 TONS Compressor 3 DANFOSS 25 TONS Compressor 4 DANFOSS 25 TONS Heat/Cool Air Coil 70 X 36 (X2) 6 Rows Reheat Air Coil 70 X 36 (X2) 2 Rows Water Flow 342.0 GPM Loop Pump/s NONE PRESSURE DROP 19.7 Ft of Hd Water Source HX (2X) 50 Tons AISI 316 L SS Refrigerant R-22 Filter Size 25 X 20 (X6) Weight 9000 LBS

90 .0 00

Blo wer an d Air Coi l Servi ce Side

Co mpresso r a nd El ectr Servi ce Side

DIMENSIONS AND LAYOUT MAY CHANGE WITH SPECIFIC SITE REQUIREMENTS.

Li fting Poin ts in Bo ttom R ail

Ra in Ho ods Hi nge d Filter Rack in e ach ho od. Each filte r ra ck h old s 3 x 20" x 25 " x 2" fil te rs 92 .0 00

24 .5 63 6.93 8

Tie Do wn Eyel ets DO NO T USE FOR L IFT ING

32 .7 50

Sup ply Air

32 .7 50

10 2.000

UNIT ELECTRICAL DATA

Unit VOLTAGE 60 HZ FLA MCA MOCP RECOMM BREAKER Number of Electrical feeds to unit

460V/3Ø

198.2

222.9

321.5

280

1

Sup ply W at er In and O u t 4" FPT

13 0.000

Dimensions in Inches A 130 E 0 B 90 F 0 C 92 G 0 D 0 H 0 SX SY RX RY 73 4 IN 1 IN 33 32 70 WATER SUPPLY AND RETURN LINES CONDENSATE LINE

PERFORMANCE DATA

Cabinet Tonnage 115 HEATING GPM 342 EWT 85°F HC 376,519 COP 4.3 COOLING GPM 342.0 GPM EADB 91°F EWT 85°F EAWB 79°F HR TC SC 1,712,191 1,369,476 632,780 LADB LAWB 55°F 55°F EER 13.6

External Static Pressure Internal Static Pressure Total Static Pressure

1.5 0.7 2.2

EXTERNAL STATIC PRESSURE @668 RPM 1.0" 1.1" 1.2" 1.3" CFM 22,100 20,600 19,250 18,500

1.4" 17,800

1.5" 17,100

1.6" 16,700

Information

Microsoft Word - mAKEUP AIR HEADER2.doc

17 pages

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

500925


You might also be interested in

BETA
Microsoft Word - mAKEUP AIR HEADER2.doc