PUBLIC SAFETY TESTING AND EVALUATION 900 Montclair Road, Suite A; Birmingham, Alabama www.sbccies.org

SERVICES 35213-1206

INC.

Evaluation Reports are the opinion of the Committee on Evaluation, based on the findings, and do not constitute or imply an approval or acceptance by any local community. The Committee, in review of the data submitted, finds that in their opinion the product, material, system, or method of construction specifically identified in this report conforms with or is a suitable alternate to that specified in the Standard and International Codes, SUBJECT TO THE LIMITATIONS IN THIS REPORT.

The Committee on Evaluation has reviewed the data submitted for compliance with the Standard Building [email protected], the Standard Mechanical [email protected], the International Mechanical Code, the Florida Building Code 2001- Building and the Florida Building Code 2001 -Mechanical and submits to the Building Official or other authority having jurisdiction the following report. The Committee on Evaluation, SBCCI PST & ESI and its staff are not responsible for any errors or omissions to any documents, calculations, drawings, specifications, tests or summaries prepared and submitted by the design professional or preparer of record that are listed in the Substantiating Data Section of this report. Portions of this report were previously included in Evaluation Reports #9105, #94117, and #94117 A. Copyrighted @ 2003 SBCCI PST & ESI

REPORT NO.: 941178

MK-6 is used in new construction. Retro-Guard is used for abatemenVre-spray application in existing construction.

4.

4.1

DESCRIPTION General

Monokote MK-6: Spray applied fireproofing is a single component, mill-mixed fire-proofing plaster which requires only the addition of water on the job site to form a pumpable slurry. Monokote MK-6 is available in two formulations, MK-6s and MK-6/[email protected] Spatterkote Type SK-3 must be applied to the flat plate cellular decking prior to application of MK-6/[email protected] and MK65. MK-6 is used in new construction. Retro-Guard: Spray-applied fireproofing is a factory blended cementitious, plaster-based material used as replacement fireproofing. Retro-Guard is mixed with water on the job site to form a pumpable slurry. Spatterkote Type SK-3 must be applied to the flat plate cellular decking prior to application of RG. Retro-Guard is used for abatementlre-spray applications in existing construction. Both Monokote Type MK-6 and Retro-Guard are intended for spray application as part of beam, columns, non-load bearing walls, floor-ceiling, and roof-ceiling Fire-Resistance Rated Assemblies. Retro-Guard is classified for use over UL Classified encapsulant materials which are listed under category CBUI in the ULI Fire Resistant Directory. The hourly rating depends upon the material type, density, and thickness applied as per the designs which are listed in the Underwriters Laboratories Inc. Fire Resistance Directory.

EXPIRES:

See current SBCCI REPORT LISTING

PST & ESI EVALUATION

CATEGORY: SUBMITTED

W. R. GRACE CAMBRIDGE, 617-498-4441

FIRE RESISTIVE CONSTRUCTION BY'

& COMPANY AVENUE MASSACHUSETTS 02140-1692 -CONN.

62 WHITTEMORE

PRODUCT TRADE NAME

w. R. Grace & Co.-Conn. Spray-Applied MK-6/[email protected], Cementitious MK-6s

4.2

Fire Testing

Fireproofing: 1.1 [email protected] Type MK-6; 1.2 [email protected]; RG

2.

SCOPE OF EVALUATION

Monokote Type MK-6 and Retro-Guard Spray-Applied Fireproofing were tested as part of fire resistance rated assemblies for floor-ceiling, roof-ceiling, steel columns, steel beams, and non-bearing walls under ASTM E 119. The assemblies are listed in Section 5. INSTALLATION.

Fire resistance rated assemblies

3.

USES

REPORT NO.941178 PAGE 1 OF 3

Monokote Type MK-6 and [email protected] Spray-Applied Fireproofing are used to provide fire resistance ratings for structural members, floor/ceiling, roof/ceiling, and non-load bearing wall assemblies in buildings of any type construction.

REPORT NO.941178

5.

5.1

PAGE20F3

.Letter report on use of spatter coat Type SK-3 with MK6/HY, R4339, May 7, 1996, signed by Robert S. Lukasz and Daniel J. Kaiser.

INSTALLATION

General

The manufacturer's published application instructions and the U.L. Fire Resistance Rating Design Specifications on the assembly being constructed shall be strictly adhered to and a copy of these instructions shall be available at the job site during installation. 5.2 Fire Resistance Rated Assemblies

6.3

The UL Design Nos. in Table 1 are listed in the Underwriters Laboratories Inc. Fire Resistance Directory. The assemblies shall be installed in accordance with their listing to obtain the desired fire resistance rating. See Limitation No. 9.2 of this report.

TABLE 1 MK-6/HY,

Test report on fire resistance rated assemblies under ASTM E 119 for Retro-Guard RG, Underwriters Laboratories Inc., File R4339, Projects 85NK25882, 86NK13714, 87NK1332, 87NK11974, and 88NK7670, issued April 13, 1988, revised August 19, 1988, signed by Robert S. Lukasz and Nestor G. Sanchez. .Letter report on use of spatter coat Type SK-3 with Type RG, R4339, May 7, 1996, signed by Robert S. Lukasz and Daniel J. Kaiser. Test reports on surface burning characteristics of Monokote Type MK-6 and Retro-Guard under ASTM E 84, Underwriters Laboratories Inc., signed by R.S. Lukasz and Richard N. Walke: .Monokote Types MK-6/ED and MK-6/CBF, File R4339, Project 90NK9891 and File R5483, Project 80NK5333, issued June 16, 1980, revised May 16, 1990. .Retro-Guard Types RG and RG1, File R5483, Project 80NK5333; and File R4339, Project 90NK9891 , issued June 16, 1980, revised May 16, 1990. .Letter report on MK-6s, File R4339, July 29, 1996, signed by Robert S. Lukasz.

Test reports on physical properties, Froehling &

6.4

MONOKOTE

TYPE

MK-65

and

RG

UL DESIGN

NUMBERS1

A702, D711, D728, D746, D758, D917, J705, N706, P701, P733, P923, X701, Y710,

D701, D703, D704, D705, D712, D715, D716, D722, D729, D730, D739, D740, D747, D748, D750, D751, D779, D780, D782, D905, D920, D925, G701, G702, J706, J709, J712, J919, N708, N732, N736, N754, P708, P709, P710, P711, P740, P901, P902, P907, S701, S702, S715, S728, X704, X722, X723, X751, Y715, U413, U475, U703

D706, D723, D742, D752, D907, G703, J957, N756, P714, P908, S734, X752,

D708, D725, D743, D753, D909, G704, J966, N782, P717, P919, S735, X771,

D709, D726, D744, D754, D910, J701, N401, P675, P725, P920, S736, X772,

D710 D72T D745, D756, D916, J704, N404, P676, P732, P921, X527, X791,

6.5

See Limitation No. 9.2 of this report. 5.3 Plenums

Monokote Type MK-6 and Retro-Guard may be installed exposed within a plenum when applied to noncombustible structural members in accordance with this report. 6. 6.1 SUBSTANTIATING DATA

Robertson, Inc., signed by James P. Willis, C.W.I. Copyright 1996. The following tests were performed on Monokote Type MK-6/HY and Type MK-6s and RetroGuard Type RG: .Cohesion/Adhesion under ASTM E 736 .Deflection under ASTM E 759 .Corrosion under ASTM E 937 .Compression under ASTM E 761 .Impact Penetration under ASTM proposed standard .Air Erosion under ASTM E 859 .Bond Impact under ASTM E 760 .Abrasion under ASTM proposed standard

6.6

6.2

Manufacturer's descriptive literature, specifications, and application instructions. Test report on fire resistance rated assemblies under ASTM E 119 for Monokote Type MK-6, Underwriters Laboratories Inc., File R4339, Projects 85NK25882, 86NK13714, 87NK1332, 87NK11974, and 88NK7670, issued March 4, 1988, revised August 19, 1988, signed by Robert S. Lukasz and Nestor G. Sanchez. .Letter report on MK-6s in fire resistance rated assemblies equivalent to MK-6/CBF, File R4339, February 16, 1996, signed by Robert S. Lukasz and Daniel J. Kaiser. .Letter report on MK-6s and MK-6/HY, R4339/96M22611, July 29, 1996, signed by Robert S. Lukasz and Randall K. Laymon. .Letter report on MK-6/HY equivalent to MK-6/CBF , R4339/96N22942, July 31, 1996, signed by Robert S. Lukasz and Daniel J. Kaiser. .Letter report on use of spatter coat Type SK-3 with MK6s, R4339, May 7, 1996, signed by Robert S. Lukasz and Daniel J. Kaiser.

6.7

6.8

6.9

6.10

Test reports on heat and smoke release rates using an oxygen consumption calorimeter under ASTM E 135492, flux of 75 kW/m2 for 600 sec, Southwest Research Institute, SwRI Project No. 01-5218-013a, Revised June 1993, signed by Arthur J. Parker. Summary report letters, dated June 15, 1993, signed by Arthur J. Parker. Test report on heat and smoke release rates using an oxygen consumption calorimeter under ASTM E 1354, flux of 75 kw/m2 for 600 sec, Underwriters Laboratories Inc., File R4339, Project 96NK09594, September 30, 1996, Michelle M. Sluga and Robert Backstrom. Engineering Fire Risk Analysis, review of cone calorimeter testing under ASTM E 1354 comparing Monokote Type MK-6 and Retro-Guard Fireproofing to gypsum wallboard for use in noncombustible construction, prepared by The Code Consortium Inc., June 29, 1994, signed and sealed by Rick Thornberry, P.E. Engineering Fire Risk Analysis, review of cone calorimeter testing under ASTM E 1354 comparing Monokote Type MK-6s to gypsum wallboard for use in noncombustible construction, The Code Consortium Inc., January 14, 1997. signed and sealed by Rick Thornberry, P.E. Underwriters Laboratories Inc., UL Directory, Fire Resistance -Vol. 1, 1997.

CODE REFERENCES

Standard Section Section Section Section Building 103.7 202 601.3 601.4 [email protected] -1999 Edition

Sectio in 603 Sectio in 604 Sectio in 606 Sectio in 609 Table 600 Section 701.2 Section 701.4 Section 701.5 Section 701.6.2 Section 703 Section 704 Table 705.1.2 Section Section Section Section Section Section 705.2.2 705.2.3 707 709.5 803.1.2 1709

Alternate Materials and Methods Noncombustible Building Material Fire Resistance Requirements Materials and Construction Approved for Fire Resistance Type I Construction Type II Construction Type IV Construction Partitions Fire Resistance Ratings Required Fire Resistance in Hours Tests -Fire Resistant Materials and Construction Column Fire Resistance Fire Resistance References Lintel Protection Materials for Fire Protection Fire Resistant Separations Minimum Fire Resistance of Walls, Partitions and Opening Protective Shaft Enclosures Shaft Enclosure Construction Combustible in Concealed Spaces Steel Assemblies Interior Finish Inspection of Spray-Applied Fire Resistance Materials Edition

Section Section Section Section Section

705.2.3 707 709.5 803.1.2 1708

Shaft Enclosure Construction Combustible in Concealed Spaces Steel Assemblies Interior Finish Inspection of Spray-Applied Fire Resistance Materials

Code 2001 -Mechanical

Florida

Building

Chapter 1 Section 202 Section 602

Administration Noncombustible Plenums FINDINGS

Materials

8.

COMMITTEE

The Committee on Evaluation in review of the data submitted finds that, in their opinion, the Monokote Type MK-6 and RetroGuard Spray-Applied Fireproofing as described in this report conform with or are suitable alternates to that specified in the Standard Building [email protected], the Standard Mechanical [email protected], the International Mechanical [email protected], the Florida Building Code 2001 -Building and the Florida Building Code 2001 Mechanical or Supplements thereto.

9.

9. 9.2

LIMITATIONS This Evaluation Report and the installation instructions, when required by the building official, shall be submitted at the time of permit application. Monokote Type MK-6 and Retro-Guard Spray-Applied Fireproofing shall be applied in accordance with the manufacturer's instructions and the Underwriters Laboratories Fire Resistance Directory for the assembly it is used in. The density and thickness shall be inspected after application in accordance with Section 1709 of the Standard Building [email protected] Unless specified under the individual designs and on the UL Classification cards as being suitable for exterior use applications, Monokote Type MK-6 and RetroGuard Spray-Applied Fireproofing are intended for interior use applications only. The scope of this report does not include the engineering design of the structural framing systems. The structural systems shall be designed in accordance with the Standard Building [email protected]

Standard Mechanical [email protected] -1997 Section 103.7 Section 202 Section 609

International Mechanical

Alternate Materials and Methods Noncombustible Material Plenums

[email protected] -1998 Edition

9.3

9.4

Methods

Section 105.2 Section 202 Section 602

Florida Section Section Section Section Building 103.7 202 601.3 601.4 Code

Alterative Materials, Equipment and Appliances Noncombustible Materials Plenums

2001 -Building

9.5

Section 603 Section 604 Section 606 Section 609 Table 600

Section 701.2

Section 701.4 Section 701.5 Section 701.6.2 Section 703 Section 704 Table 705.1.2 Section 705.2.2

Alternate Materials and Methods Noncombustible Building Material Fire Resistance Requirements Materials and Construction Approved for Fire Resistance Type I Construction Type II Construction Type IV Construction Partitions Fire Resistance Ratings Required Fire Resistance in Hours Tests -Fire Resistant Materials and Construction Column Fire Resistance Fire Resistance References Lintel Protection Materials for Fire Protection Fire Resistant Separations Minimum Fire Resistance of Walls, Partitions and Opening Protective Shaft Enclosures

10.

IDENTIFICATION

Each package of Monokote MK-6 and Retro-Guard SprayApplied Fireproofing covered by this report shall be labeled with the manufacturer's name and/or trademark, the SBCCI Public Safety Testing and Evaluation Services Inc. Seal or initials (SBCCI PST & ESI), and the number of this report for field identification.

11

PERIOD OF ISSUANCE

SEE CURRENT SBCCI PST & ESI EVALUATION REPORT LISTING FOR STATUS OF THIS EVALUATION REPORT. For information on this report contact: Michael P. O'Reardon, P.E. 205/599-9800 moreardon @sbccies.ora