WARDFLEX CORRUGATED STAINLESS STEEL TUBING

Mechanical Joint Fittings / Male NPT

Attaches Tubing to Appliance, Regulator, Manifold or Tee NEE # MJ38TX12MP MJ12TX12MP MJ34TX34MP MJ1TX34MP MJ1TX1MP MJ114TX114MP Size 3/8" Tube x 1/2" MNPT 1/2" Tube x 1/2" MNPT 3/4" Tube x 3/4" MNPT 1" tube x 3/4" MNPT 1" tube x 1" MNPT 1 1/4" tube x 1 1/4" MNPT Case Qty 24 20 12 8 8 4

Mechanical Joint Fittings / Female NPT

Attaches Tubing to Appliance, Regulator, Manifold or Tee NEE # MJ12TX38FP MJ12TX12FP MJ34TX34FP MJ1TX34FP MJ1TX1FP Size 1/2" tube x 3/8" FNPT 1/2" tube x 1/2" FNPT 3/4" tube x 3/4" FNPT 1" tube x 3/4" FNPT 1" tube x 1" FNPT 20 12 8 8 Case Qty

Mechanical Joint Gaskets

Non-Asbestos Fiber Gaskets for All Tubing Joints and Terminations NEE # GASK38 GASK12 GASK34 GASK1 Size 3/8" 1/2" 3/4" 1"

Malleable Iron Manifolds

Supply Multiple Appliances in Parallel from Main Distribution Point NEE # MAN1/2-3X1/2 MAN3/4-3X1/2 MAN3/4-4X1/2 MAN1/2-4X1/2 Size 1/2" with three 1/2" outlets 3/4" with three 1/2" outlets 3/4" with four - 1/2" outlets 1/2" with four - 1/2" outlets

HOSE & TUBING

Strip Wound Conduit

Protective Galvanized Steel Sleeve for Tubing NEE # STRWND38-12 STRWND12-12 STRWND34-12 STRWND1-12 STRWND38-600 STRWND12-600 STRWND34-600 STRWND1-600 STRWND114-12 STRWND114-600 Size 3/8" Tubing 1/2" Tubing 3/4" Tubing 1" Tubing 3/8" Tubing 1/2" Tubing 3/4" Tubing 1" Tubing 1 1/4" Tubing 1 1/4" Tubing length 12" 12" 12" 12" 50 ft 50 ft 50 ft 50 ft 12" 50 ft

Striker Plates

Protection Plates for Exposed Tubing NEE # STRPLTFULL STRPLTHALF STRPLTLARGE STRPLTQUARTER description Full Striker Plate Half Striker Plate Large Striker Plate Quarter Striker Plate length 11 1/2" 6 1/2" 17 1/2" 2 3/4" Width 2 3/4" 2 3/4" 3 1/4" 1 1/2"

CANADA'S LEADE R I N E N E RGy PRODUCTS EQU I PM E NT

115

WARDFLEX CORRUGATED STAINLESS STEEL TUBING

Outdoor Termination Outlet / Female NPT

Terminates Gas Piping at Appliance

Outdoor Termination Outlet / Male NPT

Terminates Gas Piping at Appliance

NEE # OUTTERM12T12FP OUTTERM34T34FP OUTTERM1T1FP

dimensions / Size 1/2" tube to 1/2" FNPT 3/4" tube to 3/4" FNPT 1" tube to 1" FNPT

NEE # OUTTERM38T12MP OUTTERM12T12MP OUTTERM34T34MP OUTTERM1T34MP OUTTERM1T1MP

dimensions / Size 3/8" Tubing x 1/2" MNPT 1/2" Tubing x 1/2" MNPT 3/4" Tubing x 3/4" MNPT 1" Tubing x 3/4" MNPT 1" Tubing x 1" MNPT

HOSE & TUBING

Indoor Termination Outlet

Terminates Gas Piping at Appliance

Tubing Cutters

Ensures Proper Clean Cutting of Tubing

NEE # INTERM38T12MP INTERM12T12MP INTERM34T34MP INTERM1T1MP

dimensions / Size 3/8" Tubing x 1/2" MNPT 1/2" Tubing x 1/2" MNPT 3/4" Tubing x 3/4" MNPT 1" Tubing x 1" MNPT

NEE # CUTTER38-34 CUTTERWHEEL38-34 CUTTER34-114

description 3/8" to 1/2" tube cutter Hardened steel replacement cutter wheel 3/4" to 1 1/4" tube cutter

Coating Strippers

Removes PVC Coating Sheath on Wardflex Tubing. NEE # COATSTRIP38-34 COATSTRIP1 description for 3/8" and 1/2" tubing for 3/4" and 1-1/4" tubing

116

NATIONAL TOLL F R E E DI R ECTORY 1-866-574-5100

I

ON TH E WE B w w w.nee.ca

WARDFLEX CORRUGATED STAINLESS STEEL TUBING

NaTural gaS

maximum Capacity of Wardflex Corrugated Stainless Steel Tubing in Cubic Feet of gas per hour for: Gas Pressure: 7-8 Inches Water Column

length of Tubing run 5 feet 10 feet 15 feet 20 feet 25 feet 30 feet 40 feet 50 feet 60 feet 80 feet 100 feet 150 feet 200 feet 300 feet 500 feet 10a (3/8") 15 63 44 36 31 27 25 21 19 17 15 13 10 9 7 5 15a (1/2") 19 134 95 77 67 60 55 47 42 39 33 30 24 21 17 13

Pressure Drop: 0.5 inches Water Column

Tubing & Size End 25a (1") 30 471 330 268 231 206 188 162 144 131 113 101 82 71 57 44 32a (1 1/4") 37 1091 781 642 559 502 460 400 360 329 287 257 212 184 151 118

1 CuFt = 1,000 BTU

38a (1 1/2") 48 2073 1473 1206 1046 937 857 743 666 609 528 473 387 336 275 214 50a (2") 62 3993 2880 2379 2077 1870 1716 1498 1348 1237 1080 972 803 701 579 455

20a (3/4") 25 270 192 157 137 122 112 97 87 80 69 62 51 44 36 28

HOSE & TUBING

Propane

maximum Capacity of Wardflex Corrugated Stainless Steel Tubing in KBTu per hour for: Gas Pressure: 11-13 Inches Water Column

length of Tubing run 5 feet 10 feet 15 feet 20 feet 25 feet 30 feet 40 feet 50 feet 60 feet 80 feet 100 feet 150 feet 200 feet 300 feet 500 feet 10a (3/8") 15 100 70 57 49 43 40 33 30 27 24 21 16 14 11 8 15a (1/2") 19 212 150 122 106 95 87 74 66 62 52 47 38 33 27 21 20a (3/4") 25 427 304 248 217 193 177 153 138 126 109 98 81 70 57 44

Pressure Drop: 0.5 inches Water Column

Tubing & Size End 25a (1") 30 745 522 424 365 326 297 256 228 207 179 160 130 112 90 70 32a (1 1/4") 37 1725 1235 1015 884 794 727 632 569 520 454 406 335 291 239 187 38a (1 1/2") 48 3277 2328 1906 1653 1481 1355 1175 1053 963 835 748 612 531 435 338 50a (2") 62 6312 4553 3761 3283 2956 2713 2368 2131 1955 1707 1536 1269 1108 915 719

Both tables include losses for four 90º bends and 2 end fittings. To compute flow capacity for tubing runs with a larger number of bends and/or fittings, add the appropriate number of feet to the actual run length using the following formula: L = 1.3 (n) L = Numbers of feet to be added to actual run length. n = Number of bends and/or fittings over six. Contact NEE for capacities at other pressures.

CANADA'S LEADE R I N E N E RGy PRODUCTS EQU I PM E NT

117

Information

Book_3rdEdition.indd

3 pages

Find more like this

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

331296


You might also be interested in

BETA
FF214LL/Full LIne Cat WEB
BALUNS PART I
Anaerobic Biogas (Methane) Digester: Construction Instruction___
908459.qxd
Diapositiva 1