Read LV switch-disconnectors 40 to 2500 A type Interpact (ENG) text version

LV switch-disconnectors

Interpact Merlin Gerin 40 to 2500 A

We do more with electr icity

LV switch-disconnectors

The various low-voltage applications

E55274

source coupling switch-disconnector

main power distribution board for commercial applications

main power distribution board for industrial applications

i 1000 A

15 -40 kA

i 1600 A

20 -80 kA

replacement source modular subdistribution board industrial distribution board i 160 A : 15 - 25 kA i 400 A : 20 - 80 kA

automatic control panel

i 160 A

15 - 25 kA

i 400 A

source changeover system

local isolation enclosure

final distribution enclosure for commercial applications i 10 kA i 63 A i 63 A i 10 kA

local isolation enclosure i 25 kA

control panel

local isolation enclosure

i 40 A i 630 A

i 5 kA

5-15 kA

i 125 A

M

M

M

M

N.B. adjacent to or built into the machine

M

building utilities

building final distribution

continuous processes

manufacturing processes and individual machines

Legend

052384 86081 86087

052164

Masterpact

Compact C

086106

Interpact INS

Compact NS

Vario

024262

056385

054361

035050

Compact CM

Interpact IN

Interpact INS

NG125

031107

Multi 9

Schneider Electric

2

Interpact

Source coupling switch-disconnector

c Merlin Gerin Masterpact, Compact CM and Interpact IN switch-disconnectors c current ratings: up to 6300 A c standards: IEC 60947-3, EN 60947-3 c catalogue: Masterpact, Compact CM, Interpact (see following pages).

049575

Main power distribution boards for commercial and industrial applications

c Merlin Gerin Masterpact, Interpact INS/IN and Compact C switch-disconnectors c current ratings: 400 to 1000 A for commercial applications and 400 to 1600 A for industrial applications c standards: IEC 60947-3, EN 60947-3 c catalogue: Masterpact, Compact, Interpact (see following pages).

Industrial switchboards and automatic-control panels

Masterbloc main power distribution board with Masterpact switch-disconnectors

c Merlin Gerin Interpact INS and Compact NS switch-disconnectors c current ratings: up to 400 A c standards: IEC 60947-3, EN 60947-3 c catalogue: Compact, Interpact (see following pages).

E45106

Sub-distribution boards for modular products

c Merlin Gerin Interpact INS and NG 125 switch-disconnectors c current ratings: up to 160 A c standards: IEC 60947-3, EN 60947-3 c catalogue: Multi 9, Interpact (see following pages).

Local isolation enclosures

c Merlin Gerin switch-disconnectors: v Interpact INS and Multi 9 (low ratings) v Interpact INS and Compact NS c Telemecanique switch-disconnectors (12 to 175 A) c current ratings: up to 63 A (low ratings), up to 630 A (industry) c standards: IEC 60947-3, EN 60947-3 c catalogue: Compact, Interpact (see following pages), Telemecanique.

Prisma sub-distribution board with Interpact switch-disconnectors

Small distribution enclosures for commercial applications

c Merlin Gerin Interpact INS and Multi 9 switch-disconnectors c current ratings: up to 63 A c standards: IEC 60947-3, EN 60947-3 or IEC 60669-1 c catalogue: Multi 9, Interpact (see following pages).

052135

Control panels

c Telemecanique Vario switch-disconnectors c current ratings: up to 60/80 A c standards: IEC 60947-3, EN 60947-3 c catalogue: Telemecanique.

Local isolation enclosures (manufacturing processes and individual machines)

c Interpact INS and Telemecanique Vario switch-disconnectors c current ratings: up to 63/80 A (Vario) and > 63/80 A (Interpact INS) c standards: IEC 60947-3, EN 60947-3 c catalogue: Interpact (see following pages), Telemecanique.

Pragma final distribution board with Interpact switch-disconnector

3

Interpact

Schneider Electric

LV switch-disconnectors

Interpact from 40 to 2500 A

c circuit control and isolation c industrial devices with modular profile from 40 to 160 A c industrial devices from 100 to 2500 A for installation in functional and universal switchboards c front or lateral handle are available on the same device (up to INS250)

Interpact INS from 40 to 630 A

055996

055999

Interpact INS switchdisconnector from 40 to 80 A

Interpact INS switch-disconnector from 100 to 160 A

056648

Interpact INS250 switch-disconnector

Interpact IN from 1000 to 2500 A

035053

Interpact IN1600 switch-disconnector

4

Interpact

056385

Interpact INS switch-disconnector from 400 to 630 A

Schneider Electric

Compact from 80 to 1250 A See Compact catalogue

c circuit control and isolation c additional functions for safety, remote control and convenience: v earth-fault protection v MN/MX auxiliary releases v motor mechanism v ammeter v source changeover c homogeneity with respect to Compact circuit breakers in the same switchboard

86087

Compact switch-disconnector

053039

053041

044313

Compact switchdisconnector equipped with Vigi earth fault protection module

Compact switch-disconnector with motor-mechanism

MN/MX voltage release

5

Interpact

Schneider Electric

LV switch-disconnectors

Masterpact from 800 to 6300 A See Masterpact catalogue

c circuit control and isolation c high making capacity and electrodynamic withstand c additional functions for safety and convenience: v MN/MX auxiliary releases v XF closing release v motor mechanism v source changeover

052384

Masterpact switch-disconnector

6

Interpact

Schneider Electric

Presentation

LV switch-disconnectors

1

Interpact 40 to 2500 A Interpact INS range

Simplified installation Enhanced modularity For all fields of activity and all applications Compliance with regulations

Functions and characteristics Installation and connection Technical details Catalogue numbers

8 10

10 11 12 13

15 45 69 75

7

Interpact

Schneider Electric

Presentation

Interpact 40 to 2500 A

Interpact 40 to 2500 A switchdisconnectors are used to control and isolate electrical distribution circuits.

E26803

Interpact switch-disconnectors are used as incomers for: c source coupling switchboards c main power distribution switchboards for commercial and industrial applications c modular distribution switchboards for commercial and industrial applications c control panels c enclosures for local control and isolation of circuits supplying motors, machine-tools, etc. Characteristics: c industrial performance levels as defined by IEC 60947-1 and IEC 60947-3: v rated operational voltage 500 to 690 V v rated operational current AC21A, AC22A, AC23A and B, DC21A, DC22A, DC23A and B v rated impulse-withstand voltage 8 kV v no derating up to 60° C ambient temperature. c front or lateral rotary handle c positive contact indication c visible break.

Interpact INS/INV: a complete range from 40 to 630 A

055999 055996

Switch-disconnector with positive contact indication

Switch-disconnector with visible break

055997

056652

Emergency-off switchdisconnector with positive contact indication

Emergency-off switchdisconnector with visible break

The complete range

c modular profile c mounting on backplate

40 A

INS40

63 A

INS63

80 A

INS80

100 A

INS100 INS250 100 A INV100

125 A

INS125 -

160 A

INS160 INS250 160 A INV160

200 A

INS250 200 A INV200

056654

250 A

INS250 INV250

320 A

INS320 INV320

400 A

INS400 INV400

056398

Interpact INV

055998

056390

Interpact INS

056650

056395

Interpact INV

056648

056385

Interpact INS

500 A

INS500 INV500

630 A

INS630 INV630

Interpact IN: 1000, 1600 and 2500 A

035053

8

Interpact

Schneider Electric

Positive contact indication or visible break...

056389 056397

Positive contact indication A mechanical device ensures that the position of the handle always reflects the position of the main contacts. With positive contact indication, Schneider guarantees users of the Interpact range an optimum level of safety. When the device is locked in the open position, the user can rest assured that the load circuit is totally isolated from the upstream circuit.

Visible break The physical separation of the main contacts is directly visible through a transparent cover. The Interpact INV range thus offers double safety, i.e. both positive contact indication and visible break.

...for a wide range of applications

056387

Coupling

056396 E54452

Distribution

056656

Source changeover

056660

Isolation

9

Interpact

Schneider Electric

Presentation

Interpact INS range Simplified installation

E32409

Mounting on a symmetrical rail (up to INS 160)

Mounting on a symmetrical rail or a backplate

Simplified connections

INS40 to INS80

052167 052170

INS100 to INS160

Connection of bare cables up to 50 mm2

Standard connection of bars or cables with lugs

Connection accessories

c a solution for all installations: v 1-cable connectors for Interpact INS 100 to 160 v distribution connectors for Interpact INS40 to INS80 v distribution connectors for Interpact INS 100 to 160 v distribution block, etc.

Distribloc distribution block

053049

New

E49824

One-piece spreader for Interpact INS and INV and Compact NS

One-piece spreader for Interpact INS and INV and Compact NS Interpact INS and INV and Compact NS devices may be equipped with a spreader corresponding to the pitch of the terminals of the next highest frame size. The one-piece spreader offers improved accessibility and helps conserve the homogeneity of the electrical installation. It may be fitted with all the connection and isolation accessories of the Compact NS device with the next highest frame size.

Schneider Electric

ø5...8

10

Interpact

.4

.2

.1

N

.4

.2

.1

N

Interpact INS switch-disconnectors offer the following features: c mounting on a symmetrical rail (up to INS 160) or a backplate c same volume for three and four-pole versions c 45 mm-standard front (up to INS 160), as for Multi 9 products c all types of connection made easy c standard rotary handle may be installed on front or side (up to INS 250) (extension option available) c locking of the toggle in the OFF position with up to three padlocks (ON position locking also possible) c remote indications via auxiliary contacts c uniformity with Compact NS range of circuit breakers in terms of frame sizes, aesthetics, auxiliaries, etc.

Mounting on a symmetrical rail or a backplate

E32410

Enhanced modularity

Common accessories with Compact NS circuit breakers

055994

One catalogue number for auxiliary contacts

A single catalogue number (identical to Compact NS) for auxiliary contacts: c used on all Interpact INS and INV switchdisconnectors c no increase in overall volume c three different functions: v OF contact (circuits open/closed) v CAF early-make contact v CAO early-break contact.

E32412

Front and lateral rotary handle as standard, up to INS 250

The same handle may be easily installed on the front or side with a single screw up to INS160.

E32411

.4 .2 .1

Interpact INS 80 with adaptable handle

11

Interpact

N

Ø5 5

8

N

or

Schneider Electric

Presentation

Interpact INS range For all fields of activity and all applications

Commercial and industrial applications

E45106

Interpact INS and INV switchdisconnectors integrate perfectly in the Schneider functional system. That guarantees a high level of performance, even under the most severe operating conditions. Whether installed on a symmetrical rail (40 to 160 A) or a back plate (100 to 630 A), Interpact INS and INV switch-disconnectors comply with CNOMO regulations governing machine-tools.

Incomers for distribution switchboards in commercial buildings

056049

Sub-distribution boards with Interpact incomers from 40 to 160 A

Power distribution boards with Interpact incomers from 400 to 2500 A

Local control of machines

052760 052812

Automatic control panels

Enclosures for local isolation with Interpact switch-disconnectors from 40 to 630 A

Control panels with Interpact incomers from 63 to 400 A

Manual source-changeover systems

E49823

New

E45105

N

R

The new range of Interpact INS and INV switch-disconnectors offers a complete range of source-changeover solutions with rotary handles, keylocks and, above all, the new complete source changeover assembly with a fast coupling system. All source-changeover systems now have the same distance between centres for mounting to simplify integration in the various installation systems.

12

Interpact

Schneider Electric

Compliance with regulations

E32413

Recyclable packing

053048

Compliance with all international standards

c The entire range has been fully certified IEC 60947-1, IEC 60947-3 and EN 60947-1, EN 60947-3. Certification was carried out within the framework of the LOVAG agreement by independent certification organizations. c Marine certification is underway. c Certain ratings are UL 1087 listed for the markets requiring such certification.

E49828

C erti

fi

13

Interpact

.4

.2

.1

N

Interpact INS and INV switchdisconnectors comply with the most recent environmental protection regulations. c Interpact INS and INV switchdisconnectors are modular in design c complete disassembly results in single-material parts, most of which are non-polluting and/or recyclable c moulded parts are made of thermoplastics (PBT, PET, etc.). These materials are made of carbon, hydrogen and oxygen, so their elimination, even by incineration, does not produce any polluting substances.

Recyclable materials

ca

te of Co nf

or

m it y

Schneider Electric

Functions and characteristics

LV switch-disconnectors Presentation

1 7

General characteristics Switch-disconnector selection

Interpact INS40 to 160 Interpact INS250 Interpact INS320 to 630 Interpact INV100 to 250 Interpact INV320 to 630 Interpact IN1000 to 2500

16 18

18 20 22 24 26 28

Installation Connection

Interpact INS40 to 160 Interpact INS250 to 630 Interpact INV100 to 630 Interpact IN1000 to 2500

30 31

31 32 32 34

Connection accessories

Distribution blocks One-piece spreader Insulation of live parts

35

35 36 37

Auxiliary contacts Rotary handle Disabling device closing Switching to a replacement source Current measurements Accessories

Installation and connection Technical details Catalogue numbers

38 39 40 41 42 43

45 69 75

15

Interpact

Schneider Electric

Functions and characteristics

General characteristics

E49909

MERLIN GERIN

interpact

Conformity with standards

Interpact switch-disconnectors and auxiliaries comply with the following international recommendations: c IEC 60947-1: general rules c IEC 60947-3: switches, disconnectors, switch-disconnectors, etc. c IEC 60947-5.1 and following: control-circuit devices and switching elements; automatic-control components. In that these recommendations are applied in most countries, Interpact switchdisconnectors and auxiliaries comply with European (EN 60947-1, EN 60947-3, EN 60947-5-1) and the corresponding national standards: c France NF c Germany VDE c United Kingdom BS c Australia AS c Italy CEI. Interpact switch-disconnectors are suitable for the control of machine-tools in that they comply with French standard NF C 79-130 and with the recommendations issued by the CNOMO organisation.

INS 250

Ui 750V Uimp 8kV Ith 250A 60°C

AC22A AC23A

IEC 947.3

CEI UTE UNE VDE BS

DC23A (2/4PS)

Ue(V) 690 Ie (A) 250

500 690 250 250

125(2P) 250(4P) 250 250

Ith : Ui : Uimp : Ue : Ie :

conventional thermal current rated insulation voltage rated impulse-withstand voltage rated operational voltage rated operational current suitable for isolation

Class II front face

This insulation is obtained by: c double insulation for the INS range c respecting the distances and insulation rules defined in standards IEC 60661, IEC 60947-1, IEC 60364... For the INV range.

Tropicalisation

Interpact switch-disconnectors meet the tropicalisation T2 requirements as defined in the following standards: c IEC 68-2-30: 95% relative humidity at 55°C (hot and humid climate conditions) c IEC 68-2-11: salt mist.

Degree of pollution

Interpact switch-disconnectors are certified for operation in pollution-degree III environments as defined by IEC standard 60947 (industrial environments).

Ambient temperature

c Interpact switch-disconnectors can be used at temperatures ranging from -25°C to 70°C. Above 60°C, always take into account the derating coefficients indicated in the documentation c wherever possible, the switch-disconnectors should be put into service at their normal ambient operating temperature, however this can be done at temperatures between -35°C and -25°C as long as this condition does not last for an extended period c in their original packing, Interpact switch-disconnectors may be stored at temperatures ranging from -50°C to +85°C.

Degree of protection (as per standard NF C 20-010)

IP40

E32416 E32415

IP40

E32417

IP55

Bare switch-disconnector with terminal shields

Switch-disconnector in cabinet or enclosure (direct handle)

Switch-disconnector in cabinet or enclosure (extended handle)

16

Interpact

Schneider Electric

056389

Suitable for isolation with positive contact indication

E26803

All Interpact switch-disconnectors are suitable for isolation as defined in IEC standard 60947-3: c the isolation position corresponds to the O (OFF) position c the operating handle cannot indicate the OFF position unless the contacts are actually open c padlocking in the OFF position is not possible unless the contacts are actually open. Installation of an extended handle does not alter the suitability for isolation. The isolation function is certified by tests guaranteeing: c the mechanical reliability of the position-indication system c the absence of leakage currents c overvoltage withstand capacity between upstream and downstream connections.

Suitable for isolation with positive contact indication

056397

Suitable for isolation with visible break

The physical separation of the main contacts is directly visible through a transparent cover. The Interpact INV range offers both positive contact indication and visible break.

Suitable for isolation with visible break

Emergency-off switch disconnector

056652

This switch-disconnector can be used as an emergency-off device. For this application, it must be easily visible, accessible and identifiable (see standards and rules concerning the safety of machines VDE 0660, VDE 0113, CNOMO, etc.). For easy identification, the emergency-off switch-disconnector uses special colours stipulated by the standards and different from those of the standard version: c yellow for the front face of the device c red for the handle. The performance characteristics of Interpact emergency-off switch-disconnector are the same as those of the standard version. The emergency-off switch-disconnectors are available in positive contact indication and visible-break versions.

INS250 emergency-off switch-disconnector

056654

INV250 emergency-off switch-disconnector

17

Interpact

Schneider Electric

Functions and characteristics

Switch-disconnector selection Interpact INS40 to 160

052164

Interpact INS switch-disconnectors

Number of poles

Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Rated operational current (A) Ith Ui Uimp Ue Ie at 60 °C AC 50/60 Hz AC 50/60 Hz DC AC 50/60 Hz 220-240 V 380-415 V 440-480 V (1) 500 V 660-690 V DC 125 V (2P in series) 250 V (4P in series) uninterrupted duty intermittent duty min. (switch-disconnector alone) max. (with upstream protection circuit breaker) 1s 3s 20 s mechanical electrical AC AC22A 500 V AC22A 690 V AC23A 220-240 V AC23A 380-415 V AC23A 440 V AC23A 500 V AC23A 690 V electrical DC DC23A 250 V

Interpact INS80 switch-disconnector

052168

Rated duties Short-circuit making capacity Icm (kA peak)

Short-time withstand current

Icw (A rms)

Interpact INS160 switch-disconnector

Suitability for isolation Endurance (category A) (CO cycles)

052967

Positive contact indication Degree of pollution

Upstream protection

See the "Technical details" section, page 4.0000

Installation and connection

Fixed, front connection

Interpact INS160 emergency-off switch-disconnector

symmetrical rail backplate

Indication and measurement auxiliaries

Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module

Control auxiliaries

Auxiliary releases and motor mechanism Direct and extended front / lateral rotary handle Locking by padlocks Manual source-changeover system

Installation and connection accessories

Bare cable connectors Terminal extensions and spreaders Terminal shields and shrouds Phase barriers Front-panel escutcheon

Dimensions and weights

Overall dimensions H x W x D (mm) Approximate weight (kg) 3/4 poles 3 poles 4 poles

(1) Suitable for 480 V NEMA

18

Interpact

Schneider Electric

INS40

3, 4 40 690 8 500 250 AC 22 A 40 40 40 40 AC 23 A 40 40 40 32 -

INS63

3, 4 63 690 8 500 250 AC 22 A 63 63 63 63 AC 23 A 63 63 63 40 -

INS80

3, 4 80 690 8 500 250 AC 22 A 80 80 80 80 AC 23 A 80 72 63 40 -

INS100

3, 4 100 750 8 690 250 AC 22 A 100 100 100 100 100 AC 23 A 100 100 100 100 63

INS125

3, 4 125 750 8 690 250 AC 22 A 125 125 125 125 125 AC 23 A 125 125 125 125 80

INS160

3, 4 160 750 8 690 250 AC 22 A 160 160 160 160 160 AC 23 A 160 160 160 160 100

DC 22 A DC 23 A 40 40 40 40 c class 120 - 60% 15 75 3000 1730 670 c 20000 1500 1500 1500 1500 1500 1500 yes III

DC 22 A DC 23 A 63 63 63 63 c class 120 - 60% 15 75 3000 1730 670 c 20000 1500 1500 1500 1500 1500 1500 yes III

DC 22 A DC 23 A 80 80 80 80 c class 120 - 60% 15 75 3000 1730 670 c 20000 1500 1500 1500 1500 1500 1500 yes III

DC 22 A DC 23 A 100 100 100 100 c class 120 - 60% 20 154 5500 3175 1230 c 15000 1500 1500 1500 1500 1500 1500 1500 1500 yes III

DC 22 A DC 23 A 125 125 125 125 c class 120 - 60% 20 154 5500 3175 1230 c 15000 1500 1500 1500 1500 1500 1500 1500 1500 yes III

DC 22 A DC 23 A 160 160 160 160 c class 120 - 60% 20 154 5500 3175 1230 c 15000 1500 1500 1500 1500 1500 1500 1500 1500 yes III

c c c c c c c 90 x 81 x 62.5 0.5 0.6

c c c c c c c 90 x 81 x 62.5 0.5 0.6

c c c c c c c 90 x 81 x 62.5 0.5 0.6

c c c c c c c c 135 x 100 x 62.5 0.8 0.9

c c c c c c c c 135 x 100 x 62.5 0.8 0.9

c c c c c c c c 135 x 100 x 62.5 0.8 0.9

19

Interpact

Schneider Electric

Functions and characteristics

Switch-disconnector selection Interpact INS250

056648

Interpact INS switch-disconnectors

Number of poles

Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Rated operational current (A) Ith Ui Uimp Ue Ie at 60 °C AC 50/60 Hz AC 50/60 Hz DC AC 50/60 Hz 220-240 V 380-415 V 440-480 V (1) 500-525 V 660-690 V 125 V (2P in series) 250 V (4P in series) Rated duties Short-circuit making capacity Icm (kA peak) Icw (A rms) uninterrupted duty intermittent duty min. (switch-disconnector alone) max. (with upstream protection circuit breaker) 1s 3s 20 s 30 s mechanical electrical AC

DC

Interpact INS250 switch-disconnector

056652

Short-time withstand current

Suitability for isolation Endurance (category A) (CO cycles)

electrical DC

AC22A 500 V AC22A 690 V AC23A 440 V AC23A 500 V AC23A 690 V DC23A 250 V

Interpact INS250 emergency-off switch-disconnector

Positive contact indication Degree of pollution

Upstream protection

See the "Technical details" section, page 4.0000

Installation and connection

Fixed, front connection Fixed, rear connection

Indication and measurement auxiliaries

Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module

Control auxiliaries

Auxiliary releases and motor mechanism Direct and extended front rotary handle Direct and extended lateral rotary handle Locking by padlocks Manual source-changeover system

Installation and connection accessories

Bare cable connectors Terminal extensions, spreaders and one-piece spreader Terminal shields and shrouds Phase barriers Front-panel escutcheon

Dimensions and weights

Overall dimensions H x W x D (mm) Approximate weight (kg) 3/4 poles 3 poles 4 poles

(1) Suitable for 480 V NEMA (2) Mounted with adaptation kit for direct rotary handle

20

Interpact

Schneider Electric

INS250-100

3, 4 100 750 8 690 250 AC 22 A 100 100 100 100 100 AC 23 A 100 100 100 100 100

INS250-160

3, 4 160 750 8 690 250 AC 22 A 160 160 160 160 160 AC 23 A 160 160 160 160 160

INS250 -200

3, 4 200 750 8 690 250 AC 22 A 200 200 200 200 200 AC 23 A 200 200 200 200 200

INS250

3, 4 250 750 8 690 250 AC 22 A 250 250 250 250 250 AC 23 A 250 250 250 250 250

DC 22 A DC 23 A 100 100 100 100 c class 120 - 60% 30 330 8500 4900 2200 1800 c 15000 1500 1500 1500 1500 1500 1500 yes III

DC 22 A DC 23 A 160 160 160 160 c class 120 - 60% 30 330 8500 4900 2200 1800 c 15000 1500 1500 1500 1500 1500 1500 yes III

DC 22 A DC 23 A 200 200 200 200 c class 120 - 60% 30 330 8500 4900 2200 1800 c 15000 1500 1500 1500 1500 1500 1500 yes III

DC 22 A DC 23 A 250 250 250 250 c class 120 - 60% 30 330 8500 4900 2200 1800 c 15000 1500 1500 1500 1500 1500 1500 yes III

c c c c c c (2) c c c c c c c c c 140 x 136 x 86 2 2.2

c c c c c c (2) c c c c c c c c c 140 x 136 x 86 2 2.2

c c c c c c (2) c c c c c c c c c 140 x 136 x 86 2 2.2

c c c c c c (2) c c c c c c c c c 140 x 136 x 86 2 2.2

21

Interpact

Schneider Electric

Functions and characteristics

Switch-disconnector selection Interpact INS320 to 630

056385

Interpact INS switch-disconnectors

Number of poles

Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Rated operational current (A) Ith Ui Uimp Ue Ie at 60 °C AC 50/60 Hz AC 50/60 Hz DC AC 50/60 Hz 220-240 V 380-415 V 440-480 V (1) 500-525 V 660-690 V 125 V (2P in series) 250 V (4P in series) Rated duties

DC

Interpact INS400 switch-disconnector

Short-circuit making capacity Icm (kA peak) Icw (A rms)

Short-time withstand current

056390

uninterrupted duty intermittent duty min. (switch-disconnector alone) max. (with upstream protection circuit breaker) 1s 3s 20 s 30 s mechanical electrical AC

Suitability for isolation Endurance (category A) (CO cycles)

electrical DC Positive contact indication Degree of pollution

AC22A 500 V AC22A 690 V AC23A 440 V AC23A 500 V AC23A 690 V DC23A 250 V

Upstream protection

See the "Technical details" section, page 4.0000

Installation and connection

Fixed, front connection Fixed, rear connection

Interpact INS400 emergency-off switch-disconnector

Indication and measurement auxiliaries

Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module

Control auxiliaries

Auxiliary releases and motor mechanism Direct and extended front rotary handle Direct and extended lateral rotary handle Locking by padlocks Manual source-changeover system

Installation and connection accessories

Bare cable connectors Terminal extensions, spreaders and one-piece spreader Terminal shields and shrouds Phase barriers Front-panel escutcheon

Dimensions and weights

Overall dimensions H x W x D (mm) Approximate weight (kg) 3/4 poles 3 poles 4 poles

(1) Suitable for 480 V NEMA

22

Interpact

Schneider Electric

INS320

3, 4 320 750 8 690 250 AC 22 A 320 320 320 320 320 AC 23 A 320 320 320 320 320

INS400

3, 4 400 750 8 690 250 AC 22 A 400 400 400 400 400 AC 23 A 400 400 400 400 400

INS500

3, 4 500 750 8 690 250 AC 22 A 500 500 500 500 500 AC 23 A 500 500 500 500 500

INS630

3, 4 630 750 8 690 250 AC 22 A 630 630 630 630 630 AC 23 A 500 500 500 500 500

DC 22 A DC 23 A 320 320 320 320 c class 120 - 60% 50 330 20000 11500 4900 4000 c 10000 1500 1500 1500 1500 1500 1500 yes III

DC 22 A DC 23 A 400 400 400 400 c class 120 - 60% 50 330 20000 11500 4900 4000 c 10000 1500 1500 1500 1500 1500 1500 yes III

DC 22 A DC 23 A 500 500 500 500 c class 120 - 60% 50 330 20000 11500 4900 4000 c 10000 1500 1500 1500 1500 1500 1500 yes III

DC 22 A DC 23 A 630 630 630 630 c class 120 - 60% 50 330 20000 11500 4900 4000 c 10000 1500 1000 1500 1500 1500 1000 yes III

c c c c c c c c c c c c c c 185 x 205 x 120 4.6 4.9

c c c c c c c c c c c c c c 185 x 205 x 120 4.6 4.9

c c c c c c c c c c c c c c 185 x 205 x 120 4.6 4.9

c c c c c c c c c c c c c c 185 x 205 x 120 4.6 4.9

23

Interpact

Schneider Electric

Functions and characteristics

Switch-disconnector selection Interpact INV100 to 250 with visible break

Interpact INV switch-disconnectors

Number of poles

056650

Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Rated operational current (A) Ith Ui Uimp Ue Ie at 60 °C AC 50/60 Hz AC 50/60 Hz DC AC 50/60 Hz 220-240 V 380-415 V 440-480 V (1) 500-525 V 660-690 V 125 V (2P in series) 250 V (4P in series) Rated duties

056654

Interpact INV250 switch-disconnector

DC

Short-circuit making capacity

Icm (kA peak) Icw (A rms)

Short-time withstand current

uninterrupted duty intermittent duty min. (switch-disconnector alone) max. (with upstream protection circuit breaker) 1s 3s 20 s 30 s mechanical electrical AC

Suitability for isolation Endurance (category A) (CO cycles)

Interpact INS250 emergency-off switch-disconnector

electrical DC Positive contact indication Degree of pollution

AC21A 690 V AC22A 500 V AC22A 690 V AC23B 440 V AC23B 500 V AC23B 690 V DC22A 250 V DC23B 250 V

Upstream protection

See the "Technical details" section, page 4.0000

Installation and connection

Fixed, front connection Fixed, rear connection

Indication and measurement auxiliaries

Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module

Control auxiliaries

Auxiliary releases and motor mechanism Direct and extended front rotary handle Direct and extended lateral rotary handle Locking by padlocks Manual source-changeover system

Installation and connection accessories

Bare cable connectors Terminal extensions, spreaders and one-piece spreader Terminal shields and shrouds Phase barriers Front-panel escutcheon

Dimensions and weights

Overall dimensions H x W x D (mm) Approximate weight (kg) 3/4 poles 3 poles 4 poles

(1) Suitable for 480 V NEMA (2) Montage avec kit d'adaptation pour commande rotative directe

24

Interpact

Schneider Electric

INV100

3, 4 100 750 8 690 250 AC21A 100 100 100 100 100 AC22A 100 100 100 100 AC23B 100 100 100 80 -

INV160

3, 4 160 750 8 690 250 AC21A 160 160 160 160 160 AC22A 160 160 160 160 AC23B 160 160 160 80 -

INV200

3, 4 200 750 8 690 250 AC21A 200 200 200 200 200 AC22A 200 200 200 200 AC23B 200 200 200 100 -

INV250

3, 4 250 750 8 690 250 AC21A 250 250 250 250 250 AC22A 250 250 250 250 AC23B 250 250 250 100 -

DC21A DC22A DC23B 100 100 100 100 100 100 c class 120 - 60% 30 330 8500 4900 2200 1800 c 15000 1500 1500 300 300 1500 300 yes III

DC21A DC22A DC23B 160 160 160 160 160 160 c class 120 - 60% 30 330 8500 4900 2200 1800 c 15000 1000 1000 200 200 1000 200 yes III

DC21A DC22A DC23B 200 200 200 200 200 200 c class 120 - 60% 30 330 8500 4900 2200 1800 c 15000 1000 1000 200 200 1000 200 yes III

DC21A DC22A DC23B 250 250 200 250 250 200 c class 120 - 60% 30 330 8500 4900 2200 1800 c 15000 1000 1000 200 200 1000 200 yes III

c c c c c c (2) c c c c c c c c c 140 x 136 x 86 2 2.2

c c c c c c (2) c c c c c c c c c 140 x 136 x 86 2 2.2

c c c c c c (2) c c c c c c c c c 140 x 136 x 86 2 2.2

c c c c c c (2) c c c c c c c c c 140 x 136 x 86 2 2.2

25

Interpact

Schneider Electric

Functions and characteristics

Switch-disconnector selection Interpact INV320 to 630 with visible break

Interpact INV switch-disconnectors

Number of poles

056395

Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Rated operational current (A) Ith Ui Uimp Ue Ie at 60 °C AC 50/60 Hz AC 50/60 Hz DC AC 50/60 Hz 220-240 V 380-415 V 440-480 V (1) 500-525 V 660-690 V 125 V (2P in series) 250 V (4P in series) Rated duties

DC

Interpact INV630 switch-disconnector

Short-circuit making capacity Icm (kA peak) Icw (A rms)

056398

Short-time withstand current

uninterrupted duty intermittent duty min. (switch-disconnector alone) max. (with upstream protection circuit breaker) 1s 3s 20 s 30 s mechanical electrical AC

Suitability for isolation Endurance (category A) (CO cycles)

electrical DC Positive contact indication Degree of pollution

AC21A 690 V AC22A 500 V AC22A 690 V AC23B 440 V AC23B 500 V AC23B 690 V DC22A 250 V DC23B 250 V

Upstream protection

See the "Technical details" section, page 4.0000

Interpact INV630 emergency-off switch-disconnector

Installation and connection

Fixed, front connection Fixed, rear connection

Indication and measurement auxiliaries

Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module

Control auxiliaries

Auxiliary releases and motor mechanism Direct and extended front rotary handle Direct and extended lateral rotary handle Locking by padlocks Manual source-changeover system

Installation and connection accessories

Bare cable connectors Terminal extensions, spreaders and one-piece spreader Terminal shields and shrouds Phase barriers Front-panel escutcheon

Dimensions and weights

Overall dimensions H x W x D (mm) Approximate weight (kg) 3/4 poles 3 poles 4 poles

(1) Suitable for 480 V NEMA

26

Interpact

Schneider Electric

INV320

3, 4 320 750 8 690 250 AC21A 320 320 320 320 320 AC22A 320 320 320 320 AC23B 320 320 320 160 -

INV400

3, 4 400 750 8 690 250 AC21A 400 400 400 400 400 AC22A 400 400 400 400 AC23B 400 400 400 200 -

INV500

3, 4 500 750 8 690 250 AC21A 500 500 500 500 500 AC22A 500 500 500 500 AC23B 500 500 500 220 -

INV630

3, 4 630 750 8 690 250 AC21A 630 630 630 630 630 AC22A 630 630 630 630 AC23B 500 500 500 250 -

DC21A DC22A DC23B 320 320 320 320 320 320 c class 120 - 60% 50 330 20000 11500 4900 4000 c 10000 1000 1000 200 200 1000 200 yes III

DC21A DC22A DC23B 400 400 400 400 400 400 c class 120 - 60% 50 330 20000 11500 4900 4000 c 10000 1000 1000 200 200 1000 200 yes III

DC21A DC22A DC23B 500 500 500 500 500 500 c class 120 - 60% 50 330 20000 11500 4900 4000 c 10000 1000 1000 200 200 1000 200 yes III

DC21A DC22A DC23B 630 630 500 630 630 500 c class 120 - 60% 50 330 20000 11500 4900 4000 c 10000 1000 1000 200 200 1000 200 yes III

c c c c c c c c c c c c c c 185 x 205 x 120 4.6 4.9

c c c c c c c c c c c c c c 185 x 205 x 120 4.6 4.9

c c c c c c c c c c c c c c 185 x 205 x 120 4.6 4.9

c c c c c c c c c c c c c c 185 x 205 x 120 4.6 4.9

27

Interpact

Schneider Electric

Functions and characteristics

Switch-disconnector selection Interpact IN1000 to 2500

Interpact IN switch-disconnectors

035053

Number of poles

Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Rated operational current (A) Ith Ui Uimp Ue Ie at 60 °C AC 50/60 Hz AC 50/60 Hz CC AC 50/60 Hz 220-240 V 380-415 V 440-480 V (1) 500 V 660-690 V DC

Interpact IN1000 switch-disconnector

Short-circuit making capacity

Short-time withstand current

125 V (2P) 250 V (4P) Icm (kA peak) min. (switch-disconnector alone) max. (with upstream protection circuit breaker) Icw (A rms) 1s 3s 20 s mechanical electrical AC

Suitability for isolation Endurance (category A) (CO cycles)

electrical DC Positive contact indication Degree of pollution

AC22A 500 V AC22A 690 V AC23A 440 V AC23A 500 V DC23A 250 V DC23A 500 V

Upstream protection

See the "Technical details" section, page 4.0000

Installation and connection

Fixed, front connection symmetrical rail backplate

Indication and measurement auxiliaries

Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module

Control auxiliaries

Auxiliary releases Motor mechanism Direct and extended front rotary handle Direct and extended lateral rotary handle Locking by padlocks Manual source-changeover system

Installation and connection accessories

Bare cable connectors Terminal extensions and spreaders Terminal shields and phase barriers Front-panel escutcheon

Dimensions and weights

Overall dimensions H x W x D (mm) Approximate weight (kg) 3 poles fixed, front connection 4 poles fixed, front connection 3 poles fixed, front connection 4 poles fixed, front connection

(1) Suitable for 480 V NEMA (2) IN1000: 630 A for AC23A, IN1600: 800 A for AC23A. (3) 1450 A at 60° C

28

Interpact

Schneider Electric

IN1000

3, 4 1000 690 8 690 250 AC 21 A 1000 1000 1000 1000 1000 DC 22 A 1000 1000 75 176 35000 20000 7800 c 3000 500 500 500 yes III AC 22 A 1000 1000 (2) 800 800 DC 23 A 1000 1000

IN1600

3, 4 1600 (at 50° C) (3) 690 8 690 250 AC 21 A 1600 1600 1600 1600 1600 DC 22 A 1600 1600 75 105 35000 20000 7800 c 3000 500 500 500 yes III AC 22 A 1600 1600 (2) 1200 1200 DC 23 A 1600 1600

IN2500

3, 4 2500 690 8 690 250 AC 21 A 2500 2500 2500 2500 2500 DC 21 A 2500 2500 105 105 50000 28500 11000 c 3000 500 500 500 (DC21A) yes III AC 22 A 2500 2500 DC 22 A -

c c c c c c c c 340 x 300 x 118 410 x 300 x 118 12 15

c c c c c c c c 340 x 300 x 118 410 x 300 x 118 15 18

c c c c c c c c 340 x 440 x 200 410 x 440 x 200 35 45

29

Interpact

Schneider Electric

Functions and characteristics

Installation

052760

Interpact INS and INV switch-disconnectors offer a number of rational installation solutions to optimise available space inside enclosures. They may be installed in individual enclosures or as incomers in power distribution or control panels. c Interpact INS40 to 160 switch-disconnectors have a standard 45 mm high front and may be clipped onto a Multifix or symmetrical rail. They may be installed in all Multi 9 modular enclosures, including Pragma, Prisma, etc. c Interpact INS250 to 630 and INV100 to 630 switch-disconnectors may be installed on mounting plates or rails. Installation as incomers in Prisma power distribution cubicles is very flexible: v the mounting plates are the same as those used for Compact NS circuit breakers and are identical for direct and extended handles v installation in 300 mm ducts is possible for ratings up to 630 A. c Interpact IN1000 to 2500 switch-disconnectors may be installed on backplates or rails.

Local isolation enclosure

Individual enclosures

c each individual enclosure includes: v a door with a cut-out v a mounting plate v accessories required for extended front or lateral rotary handle v removable plates (without holes) for cable entry. The Interpact INS switch-disconnector must be order separately.

E56047 E32418

Heavy-duty individual enclosure (sheet metal or plastic)

E54453

Pragma modular enclosures

c the enclosures in the Pragma range are: v made of self-extinguishing insulating material v supplied with all accessories (terminal blocks, blanking plates, etc.) v rated class 2.

Power distribution incomer in a Prisma cubicle

056699

Interpact INS40 on a symmetrical rail

Prisma metal cubicles and enclosures

c the metal cubicles and enclosures in the Prisma range are highly adaptable to the type of installation: v basic cubicle or enclosure v multifix rail v modular front plates v distribution accessories v ducts for running cables or installing terminals v plain or transparent doors.

E54454

Installation in a 300 mm duct

Power distribution incomer in a Prisma GK cubicle

30

Interpact

Schneider Electric

Connection Interpact INS40 to 160

Interpact INS40 to INS80

E54455

Interpact INS40 to INS80 switch-disconnectors are equipped as standard with connectors for bare copper or aluminium cables. Distribution connector This connector screws directly into the switchdisconnector terminals for connection of three cables of the following types: c 1 to 10 mm2 flexible cables c 1.5 to 16 mm2 rigid cables c with crimped or auto-crimping ferrules from 1.5 to 4 mm2.

E38888

Interpact INS100 to INS160

E54456

Connection of bars or cables with lugs

Interpact INS100 to INS160 switch-disconnectors are equipped as standard with terminals comprising nuts with M6 screws for direct connection of insulated bars or cables with lugs. Lugs The special lugs for copper cables may be used for cables with cross-sectional areas up to 95 mm2. Crimping by hexagonal necking or punching. Lugs are supplied with phase barriers and are compatible with the terminal shields.

E38889

.4 .2 .1

E54463

E39432

E30707

c 1-cable connectors for Interpact INS100/125/160 snap directly onto the terminals c distribution connectors are designed for four cables with a cross-section areas of 1.5 to 25 mm2 rigid / 16 mm2 flexible. They screw directly to the terminals. The phase barriers supplied with the distribution connectors may be replaced by long terminal shields.

E54457

E32424

E32423

.4

.2

.1

.4

.2

.1

N

N

N

Lug for copper cable

Connection of bare cables (Cu or Al)

1-cable connector

Distribution connector

31

Interpact

Schneider Electric

Functions and characteristics

Connection Interpact INS250 to 630 Interpact INV100 to 630

Front connection of bars or cables with lugs

Interpact INS250 to INS630 and INV100 to INV630 switch-disconnectors are equipped as standard with terminals receiving snap-in nuts and screws (M8 for INS/INV up to 250, M10 from 320 upwards) for direct connection of insulated bars or cables with lugs. Terminal extensions (right-angle, edgewise, spreaders) are available to solve all connection problems. For Interpact INS/INV630 switchdisconnectors, connection most often requires the 52.5 or 70 mm pitch spreaders. Lugs Lugs are different for copper and aluminium cables. They are supplied with phase barriers and are compatible with the long terminal shields. c the small lugs for copper cables may be used for cables with the following cross-sectional areas: v 120, 150 or 185 mm2 (INS/INV up to 250) v 240 or 300 mm2 (INS/INV up to 630). Crimping by hexagonal necking or punching. c the small lugs for aluminium cables may be used for cables with the following cross-sectional areas: v 150 or 185 mm2 (INS/INV up to 250) v 240 or 300 mm2 (INS/INV up to 630). Crimping by hexagonal necking. Spreaders Spreaders increase the pitch of the terminals. They are not compatible with terminal shields. The onepiece spreader increases the pitch to correspond to that of the upstream device and provides protection against direct contact (see page 2.0060).

E54456

E54459

E18600

Right-angle terminal extensions

ø5...8

E18601

Straight terminal extensions for INS/INV250

E54462

E21276

Edgewise terminal extensions for INS/INV320 to 630

E54463

ø5...8

Lug for copper cables

E54460

ø5...8

E30907

Lug for aluminium cables

E54461

E18599

Spreaders

E54464

ø5...8

One-piece spreader

32

Interpact

Schneider Electric

E54457

Front connection of bare cables

Bare-cable connectors for Interpact INS/INV switchdisconnectors may be used for both copper and aluminium cables. 1-cable connectors for Interpact INS250 and INV100 to 250 The connectors snap directly on to the device terminals or clip onto right-angle and straight terminal extensions as well as spreaders. 1-cable and 2-cable connectors for Interpact INS/INV320 to 630 The connectors are screwed to device terminals or right-angle terminal extensions. Distribution connectors for Interpact INS250 and INV100 to 250 These connectors are screwed directly to device terminals. Phase barriers are supplied with distribution connectors, but may be replaced by long terminal shields. Each connector can receive six cables with cross-sectional areas ranging from 1.5 to 35 mm2 each. Polybloc distribution block for Interpact INS250 and INV100 to 250 The Polybloc connects directly to the device terminals and is used to connect up to six or nine flexible or rigid cables with cross-sectional areas not exceeding 10 mm2, to each pole. Connection is made to spring terminals without screws.

E54468

1-cable connector for INS250 and INV100-250

E54465

ø5...8

E54469

1-cable connector for INS/INV320 to 630

E54466

E54470

2-cable connector for INS/INV320 to 630

ø5...8

E54471

Distribution connector for INS250 and INV100 to 250

E54472

Polybloc distribution block for INS250 and INV100 to 250

E54456 E54473

Rear connection

Rear connections for bars or cables with lugs are available in two lengths. Bars may be positioned flat, on edge or at 45° angles depending on how the rear connections are positioned.The rear connections are simply fitted to the device connection terminals. All combinations of rear connection lengths and positions are possible on a given switch-disconnector. The switch-disconnector is mounted on a backplate.For the connection of cables without lugs, the 1-cable connectors for Interpact INS250 and INV100 to 250 may be simply clipped onto the rear connections.

E54467

Two lengths

ø5...8

E54474

Four positions.

33

Interpact

Schneider Electric

Functions and characteristics

Connection Interpact IN1000 to 2500

E54540

Direct connection

Bars

E24005

IN1000 and IN1600

E24006

IN2500

Connection with accessories

Spreaders

E24013

Edgewise terminal connections

E24015

IN1000 and IN1600

Connectors

E24018

IN2500

34

Interpact

Schneider Electric

Connection accessories Distribution blocks

053997

Distribloc

3 outgoing spring terminals 1 to 6 flexible or rigid

E54477

mounting on backplate

7 outgoing spring terminals 1 to 4 flexible or rigid

Distribloc 125 A

clips onto symmetrical rail 2 outgoing spring terminals 1 to 10 flexible 1 to 16 rigid

E54475

1 ingoing tunnel terminal 35 6 to 35 flexible 10 to 50 rigid

N

1 outgoing tunnel terminal 25 4 to 16 flexible 4 to 25 rigid

modular cover

circuit identification

Distribloc is a four-pole distribution block offering: c 13 outgoing terminals per phase (12 spring terminals and 1 tunnel terminal) c 1 incoming tunnel terminal for 35 mm2 flexible cable (50 mm2 rigid). Distribloc exists in two versions: v Distribloc 125, for switch-disconnectors rated up to 125 A v Distribloc 160, supplied with prefabricated connections, for direct connection to switch-disconnectors INS100 to INS160. Distribloc is supplied with a modular cover that fulfils a number of functions: c circuit identification: a protected label identifies the various circuits c aesthetics: the cover has the same design as the associated Interpact INS switch-disconnector c user information: all required information is indicated on the cover. Distribloc can be installed: c on a symmetrical rail or a backplate c to the left, the right or under the switch-disconnector, depending on the desired layout of the switchboard. Installation to the left is particularly useful when the INS switch-disconnector is equipped with a lateral handle. Electrical characteristics c rated short-time withstand current (Icw) = 4.5 kA rms / 1 second. c rated peak withstand current (Ipk) = 20 kA peak. c rated insulation voltage (Ui) = 690 V AC.

041153

N N

Multi-stage distribution block 125 A (40°C)

c 4 x 10 holes (5 x 10 mm2, 4 x 16 mm2, 1 x 35 mm2). dimensions: width 88 mm, height 92 mm, depth 51 mm, distance between fixing centres 68 mm. c 4 x 17 holes (8 x 10 mm2, 8 x 16 mm2, 1 x 35 mm2). dimensions: width 125 mm, height 92 mm, depth 51 mm, distance between fixing centres 105 mm. v supplied with insulating cover v easy mounting on Multifix or symmetrical rail v mounting on slotted plate using screws. Electrical characteristics c rated short-time withstand current (Icw) = 3.5 kA rms / 1 second c rated peak withstand current (Ipk) = 20 kA peak c rated insulation voltage (Ui) = 500 V AC.

35

Interpact

Schneider Electric

Functions and characteristics

Connection accessories One-piece spreader

One-piece spreader

Connection of large cables may require an increase in the distance between the switch-disconnector terminals. The one-piece spreader is an accessory that can also be fitted on Compact NS circuit breakers. It offers the following features: c increases the pitch of the switch-disconnector terminals to correspond to that of the upstream device c compatible with all the connection and insulation accessories available for the upstream device (connectors, terminal extensions, etc.) c enhances insulation between phases in comparison with standard spreaders. INS250 INS320 to 630 INV100 to 250 INV320 to 630

Pitch without spreaders (mm) Pitch with standard spreaders (mm) Pitch with one-piece spreader (mm) 35 45 45 52.5 or 70

E54200

056384

ø5...8

45

70

Mounting

When equipped with a one-piece spreader, INS and INV switch-disconnectors may be installed either at the back of a switchboard or on the front panel with a front alignment base. c devices with different frame sizes can thus be aligned in the switchboard c the same mounting plate can be used for all devices (including Compact NS circuit breakers).

E54541

Connection and insulation accessories are identical to those for Compact NS

E54548

Mounting at the back of a switchboard

Mounting on the front panel with a front alignment base

36

Interpact

Schneider Electric

Insulation of live parts

Terminal shields for INS and INV switchdisconnectors Lead-sealable insulation accessories used to protect against direct contact with power circuits. c degree of protection IP 40 c supplied with lead-sealing accessories. Phase barriers for INS/INV100 to 630 c safety accessories providing maximum insulation between the phases of the power connection c easy installation by snapping into the case c may be combined with all other connection accessories, except the terminal shields and terminal shrouds. Phase barriers for IN1000 to 2500 These devices may be equipped with phase barriers. Terminal shrouds for INS40 to 160 These insulation accessories are used for protection against direct contact with live connection screws. It is also possible to attach an insulating plate (not supplied) to the shrouds to avoid any contact with the power conductors. Spare viewport for Interpact INV switchdisconnectors Viewports are darkened by the electrical arc. A new viewport may be installed to maintain the visible-break function.

056063 avec loupe

E54476

Terminal shields for Interpact INS and INV

E54542

Phase barriers for Interpact INS and INV

E54543

Terminal shrouds for Interpact INS40 to 160 (with insulating plate to avoid contact with the conductors)

E51003

Spare viewport for Interpact INV

37

Interpact

Schneider Electric

.4

Ø5 5

.2

.1

N

8 8

Functions and characteristics

Auxiliary contacts

044314

Interpact INS and INV

One or four common-point changeover contacts can be used to remote switch-disconnector status information for indications, electrical interlocking, relays, etc. Functions Each contact may be used for the following functions: c OF (open/closed): indicates the position of the switch-disconnector poles c CAM (early-make or early-break function): indicates the position of the handle. Used in particular for: v CAO early-break switch (auxiliary contacts open before the main contacts), used, for example, to automatically open a circuit breaker or a contactor before opening the Interpact INS v CAF early-make switch (auxiliary contacts close before the main contacts). c switching of very small loads. A "low-level" version of the auxiliary switches exists for switching very small loads (for example, to control a PLC or electronic circuits). Standards The auxiliary switches comply with international standard IEC 60947-5.1. Installation They simply snap in under the auxiliaries cover (supplied as standard) of the switch-disconnector.

E54504

CAO or CAF or OF

N

Ø5 5

8

CAO or CAF or OF

Auxiliary contact for Interpact INS and INV

Interpact INS40 to 160

E54499

ø5...8

CAO or CAF or OF

Interpact INS250 and INV100 to 250

E54500

ø5...8

CAO or CAF

OF1 OF2 OF3

Interpact INS/INV 320 to 630

Electrical characteristics of auxiliary contacts for Interpact INS and INV

Rated thermal current (A) Minimum load Utilisation category (IEC 60947-5-1) Operational current (A) 24 V 48 V 110 V 220/240 V 250 V 380/415 V 440 V 660/690 V Standard 6 10 mA at 24 V Low level 5 1 mA at 4 V

AC

DC

AC

DC

AC12 AC15 DC12 DC14 AC12 AC15 DC12 DC14 6 6 6 6 6 6 6 6 6 5 4 3 3 0.1 2.5 2.5 0.8 0.3 1 0.2 0.05 0.03 5 5 1.5 1.5 5 5 5 5 3 3 2.5 2 5 2.5 0.8 0.3 1 0.2 0.05 0.03

Interpact IN1000 to IN2500

Possible combinations Interpact

IN1000, IN1600 IN2500

2 OF block

1 1

CAM block

+1 +1

38

Interpact

Schneider Electric

Rotary handle

INS40 to 160 INS250 INS320 to 630 IN1000 to 2500 INV100 to 250 INV320 to 630 Standard rotary handle

Front direct Lateral direct Front extended Lateral extended Standard Standard Optional Optional (1) (2) Standard Standard Optional Optional (1) (2) Standard With conversion Optional Optional Standard With conversion Optional Optional (1) Standard No Optional No Standard No Optional No Standard No Optional No No No No No

052171

Red and yellow rotary handle for emergency-off switch-disconnectors

Interpact INS160 with lateral direct rotary handle

Front direct Lateral direct Front extended Lateral extended

(1) The basic switch-disconnector must be the emergency-off (red and yellow) version (2) Two models for universal enclosures and for Prisma G enclosures.

056656

Interpact INS250 with lateral extended rotary handle

Direct rotary handle on INS40 to 160

056387

E54502

Direct rotary handle on INS250 and INV100 to 250

E54503

Direct rotary handle on INS/INV320 to 630

Interpact INS630 with front extended rotary handle

056652

Interpact IN1000 to IN2500

Interpact INS250 emergency-off version with front direct rotary handle

Extended rotary handle (IP 55) The extended handle is obtained by adding a set of optional accessories to the standard direct rotary handle (front or lateral). The accessories include: c a front plate c an extension shaft. The extended rotary handle can be optionally fitted with: c a door interlock that prevents door opening when the handle is not in the OFF position.

39

Interpact

E24020

N

Direct rotary handle c degree of protection IP 40 c the switch-disconnector may be locked in the OFF position by one to three padlocks, hasp diameter 5 to 8 mm (not supplied). Models c standard with black handle c emergency-off version with red handle and yellow front for machine-tool control. Extended rotary handle Makes it possible to operate the switch-disconnector, installed inside a switchboard, from the front or side of the switchboard. The extended rotary handle may be installed on the front or the side of the switchdisconnector. Degree of protection IP 55.7. Operation c suitability for isolation is maintained. c door opening is prevented when the switchdisconnector is in ON position (for front handle only). c the switch-disconnector may be locked in the OFF position by one to three padlocks, hasp diameter 5 to 8 mm (not supplied). Locking prevents opening of the switchboard door (for front handle only). Models c standard: with black handle. c emergency-off: with red handle and yellow front for machine-tool control. Installation The extended rotary handle is made up of: c an assembly that replaces the direct rotary handle on the Interpact switch-disconnector (secured by screws); c an assembly (handle and front plate) to be mounted on the door or the side of the switchboard. This assembly is always secured in the same position, whether the switch-disconnector is installed vertically or horizontally; c an adjustable extension shaft (see pages 3.0040).

E54501

Schneider Electric

.4

.2

.1

Interpact INS and INV

or

or

ø5...8

ø5...8

Functions and characteristics

Disabling device closing

056649

Device with padlocks

Keylocking

Interpact INS250 to 630, INV100 to 630 and IN1000 to IN2500 switch-disconnectors may be locked in the OFF position using a keylock (optional) that may be installed in the hole prepared for that purpose on the front of the devices. The key may not be removed when the switch-disconnector is in the ON position. Keylocks can also be fitted on switch-disconnectors equipped with extended rotary handles.

E54544

Padlocked Interpact INS250 switch-disconnector

Device with keylock

Type of locking

Type of rotary handle Front Front direct extended

c (1) c c (1) c c (1) c c (1) c c c (2) c

Lateral direct

c (1) c c (1) c

Locking by 3 padlocks

ON (I) OFF (O) Locking by ON (I) Ronis or Profalux OFF (O) keylock Door locking ON (I) Door lock defeat ON (I) Door locking, OFF (O) device padlocked

(1) By simple modification of the standard rotary handle. (2) Using a special tool.

40

Interpact

N

Interpact INS and INV switch-disconnectors may be locked in the OFF position. The handle is designed for locking by up to three padlocks (not supplied). Locking in the OFF position guarantees isolation as defined by the IEC 60947-3 standard. The handle may also be lead-sealed in the OFF position.

E32426

Lateral extended

c (1) c c (1) c

Schneider Electric

.4

Ø5 5

.2

.1

Padlocking

8 8

ø5...8

Switching to a replacement source

Source-changeover systems are essential for continuity of service and energy management. They switch between: c a normal source N which supplies the installation under normal conditions; c a replacement source R which can be another feeder or an engine-generator set.

A source-changeover system is made up of two switch-disconnectors that are mechanically interlocked. The mechanism prevents the simultaneous connection (even transient) of both sources. Switching from one source to another can be achieved by: c a keylock-type interlocking system c a mechanical interlocking system c a complete source-changeover assembly. Possible positions

Normal source Replacement source 1 0 0 1 0 0

Change-over INS40...160 system

Keylock Mechanical Complete assembly c

INS250 INV100...250

c c c

INS320...630 INV320...630

c c c

IN1000...2500

c

E55460

ø5...8

Interlocking with keylocks

The two Interpact switch-disconnectors are each fitted with a standard keylock, but only one key is supplied for the two devices. This solution enables two distant switch-disconnectors to be interlocked.

E54479

ø5...8

ø5...8

ø5...8

Interlocking with keylocks

Mechanical interlocking

ON I

ø5...8

ON I

ø5...8

ø5...8

ø5...8

O OFF

O OFF

A mechanism connects the handles of two Interpact switch-disconnectors: c INS40 to INS160: equipped with extended handles c INS250 to INS630 : equipped with direct or extended handles. The mechanism prevents both switch-disconnectors from being closed at the same time, but does allow opening of both.

ON

E54480

I ON I

ø5...8

ø5...8

O OFF

O OFF

Mechanical interlocking

Complete source changeover assembly

O

ø5...8

ø5...8

These assemblies provide an easy way to implement source changeover functions with: c a single 3-position rotary handle that controls the two switch-disconnectors (Normal source ON, OFF, Replacement source ON) c a smaller size, taking up less room in the switchboard. A complete source changeover assembly can be ordered with a single catalogue number.

E54481

O

Complete source changeover assembly

Downstream coupling accessory

This accessory is used to couple two switchdisconnectors of the same size. c for Interpact INS250 and INV100 to 250, the pitch between outgoing terminals is 35 mm. c for Interpact INS/INV320 to 630, the pitch between outgoing terminals is 52.5 mm. The coupling accessory can be fitted with the same connection and insulation accessories as the switchdisconnectors.

E55272

Downstream coupling accessory

41

Interpact

Schneider Electric

Functions and characteristics

Current measurements

057355

Ammeter module

For Interpact INS250 to 630 and INV100 to 630. Function Measures and displays the current of each phase (phase selection by a threeposition switch on the front) on a dial-type ammeter. Installation c connects directly to the downstream terminals of the switch-disconnector (except on a INS250 with a direct handle) c the ammeter clips into the module housing in any of four 90° positions, i.e. the switch-disconnector may be installed horizontally or vertically c degree of protection IP40 c class II insulation between front and power circuits. Electrical characteristics Accuracy class 4.5.

Current-transformer module

For Interpact INS250 to 630 and INV100 to 630. Function Measure phase currents for display by an ammeter or a Digipact IM or PM module (not supplied, see the corresponding catalogue). Installation c connects directly to the downstream terminals of the switch-disconnector c degree of protection IP40 c class II insulation between front and power circuits c connection via six built-in terminals for cables with a cross-sectional area of 2.5 mm2. Electrical characteristics c current transformer with 5 A secondary winding c accuracy class 3 for the following values of consumed output power: v 100 A rating - 1.6 VA v 150 A rating - 3 VA v 250 A rating - 5 VA v 400/630 A rating - 8 VA.

Interpact INV250 with ammeter module

42

Interpact

Schneider Electric

Accessories

Front-panel escutcheons

Escutcheons for switch-disconnectors and ammeter modules Mounted on switchboard panel from the front using four screws.

E55275

ø5...8

E55276

A

80 40 0

160/5A

160 120

Escutcheon for switchdisconnectors

Escutcheon for ammeter modules

Identification labels

Interpact INS40 to 160 switch-disconnectors may receive Telemecanique prefabricated labels, catalogue number AB1- (eight characters). Interpact INS250 to 630 and INV100 to 630 switch-disconnectors are supplied as standard with a clip-on label for handwritten indications. These devices also come with a nameplate into which a label can be inserted.

E18595

P D E P. P O M

.P DE P

push to trip

O

052760

Individual enclosures

Interpact INS and INV switch-disconnectors equipped with a front handle may be installed in individual enclosures. All fixed, front connections are possible, except right-angle and edgewise terminal extensions. Spreaders may be installed in the enclosures intended for Interpact INS250 to 630 and INV100 to 630 switch-disconnectors. Heavy-duty metal individual enclosure for Interpact INS (IP557) c metal enclosure c door with keylock and cut-out for switch-disconnector rotary handle c extended rotary front handle c device mounting plate c removable plate (without holes) for cable entry through bottom. Heavy-duty insulating individual enclosure for Interpact INS and INV (IP557) c metal enclosure c transparent cover, screwed, lead sealable, with cut-out for switch-disconnector rotary handle c extended rotary front handle c device mounting plate c removable plates (without holes) for cable entry through bottom and/or top. Dimensions Metal enclosures

Interpact INS40 to 160 Interpact INS250 Interpact INS320 to 630

WxHxD

300 x 200 x 150 300 x 400 x 200 400 x 600 x 200

Insulating enclosures

Interpact INS40 to 160 Interpact INS250 Interpact INV100 to 250 Interpact INS320 to 630 Interpact INV320 to 630

WxHxD

270 x 180 x 185 270 x 360 x 235 360 x 720 x 235

43

Interpact

Schneider Electric

Installation and connection Possible installation positions

and mounting techniques

Possible installation positions

E55416

E55417

ø5...8

E55418

ø5...8

ø5...8

ø5...8

E55419

E55420

Possible mounting techniques

INS40 to 160

E55596

E55597

E55421

Ø5 5

8 8

Ø5 5

8 8

Symmetrical rail

Plain mounting plate

Slotted mounting plate

INS250 to 630 - INV100 to 630 - IN1000 to 2500

E55423

E55416

E55422

ø5...8

ø5...8

Rails

Plain mounting plate

Slotted mounting plate

46

Interpact

Schneider Electric

.4

.2

.1

N

ø5...8

.4 .2 .1

N

.4

.2

.1

N

Ø5 5

8 8

ø5...8

Implementation

Reverse supply

Interpact switch-disconnectors may be supplied indifferently via the top or bottom terminals, without any reduction in performance.

E55424

ø5...8

Neutral pole position

On Merlin Gerin switch-disconnectors, the neutral pole is traditionally located on the left-hand side. On the INS and INV ranges, the four poles are identical and the neutral pole can therefore be located on the right-hand side simply by adding an appropriate label.

Conductor materials and electrodynamic forces

to the busbars

Interpact switch-disconnectors may be connected using either bare copper, tinned copper or tinned aluminium conductors (flexible or rigid bars, cables). In the event of a short-circuit, thermal and electrodynamic forces are exerted on the conductors. The conductors must therefore be adequately sized and suitably supported. Note that the terminals of electrical devices (switch-disconnectors, contactors, circuit breakers, etc.) should not be considered to contribute to the support of the conductors.

E55425

Cables ties and flexible bars

outgoing cables

The table below indicates the maximum distances between cable ties depending on the prospective short-circuit current. Care must be taken not to exceed a distance of 400 mm between ties mechanically secured to the switchboard frame. Type of tie "Panduit" type Width: 4.5 mm Max. load: 22 kg Colour: white

200 10 100 15 50 20

"Sarel" type Width: 9 mm Max. load: 90 kg Colour: black

350 20 200 27 100 35 70 45 50 (double ties) 100

Max. distance between ties (mm) Short-circuit current (kA rms)

Note: for cables u 50 mm2, 9 mm wide ties must be used.

47

Interpact

Schneider Electric

Installation and connection Front connection of bare copper

and aluminium cables

Interpact INS40 to INS80 switch-disconnectors are equipped as standard with connectors for bare copper and aluminium cables. Distribution connectors may be screwed directly to the switch-disconnector terminals and can be used to connect three cables. Standard device

E54545-E55101

E38888

E39432

Interpact INS40 to INS80

.4 .2 .1

If 500 V i U i 690 V, phase barriers or long terminal shields are mandatory

c 1-cable connectors snap directly onto the device terminals. c distribution connectors for 4 flexible cables are screwed directly to the device terminals. These connectors are supplied with phase barriers (mandatory installation) which may be replaced by long terminal shields. c Distribloc distribution block supplied via tunnel terminals. Provides 12 screwless spring type and 1 screw type outgoing terminals. 1-cable connector

E54545

E32423

E32424

1-cable connector

E30707

If 500 V i U i 690 V, phase barriers or long terminal shields are mandatory

4-cable distribution connector

15 1.5 to 25 rigid 1.5 to 16 flexible (1) 3

L

L (mm) S (mm2) Cu / Al Torque (Nm) Torque (Nm)

15 10 to 95 rigid 10 to 95 flexible 10

S

Distribloc see page 35

alimentation 5 Nm distribution 3 Nm

E55598

ø5...8

c 1-cable connectors snap directly on to the device terminals or are clipped on to the right-angle or straight terminal extensions or spreaders. These connectors are supplied with phase barriers. Material: steel I i 160 A and tinned aluminium I i 250 A. c 6-cable distribution connectors are screwed directly to the device terminals. These connectors are supplied with phase barriers (mandatory installation) which may be replaced by long terminal shields. Material: tinned aluminium. c Polybloc distribution blocks, for 6 or 9 rigid or flexible cables, are connected directly to the device terminals. Cable connection is made in spring type terminals and does not require screws. 1-cable connector

L

E54468

E54465

E54471

E54545

If 500 V i U i 690 V, phase barriers or long or short terminal shields are mandatory

Distribution connector, 6 cables Cu or Al

S

L (mm) 15 or 30 S (mm2) Cu / Al 1.5...6 (1) 8...35 Torque (Nm) 4 6

E54472

.4

.2

.1

N

N

With distribution connector

Distribution connector

L

e L

S

Pole pitch e (mm) L (mm) L1 (mm) S (mm2) L1 Cu / Al Torque

18 mm 18 mm i5 i 10 i 10 13 1.5 to 50 rigid 1.5 to 16 rigid (1) 1.5 to 35 flexible 1 to 10 flexible (1) 5 Nm 2 Nm

(1) Connection of 1.5 to 4 mm2 flexible cables requires crimped or auto-crimping ferrules.

Interpact INS100 to INS160

4-cable distribution connector

Distribloc

(1) Connection of 1.5 to 4 mm2 flexible cables requires crimped or auto-crimping ferrules.

Interpact INS250 and INV100 to 250

1-cable connector

Distribution connector

Steel Aluminium i 160A i 250A

20 20 1.5...95(1) 10...16 25...35 50...185 12 15 20 26

L (mm) S (mm2) Cu / Al Torque (Nm)

Polybloc distribution block, 6 or 9 cables

L (mm) 12 S (mm2) Cu / Al 1.5...10

Polybloc distribution block

(1) Connection of 1.5 to 4 mm2 flexible cables requires crimped or auto-crimping ferrules.

48

Interpact

Schneider Electric

Interpact INS250 and INV100 to 250 (cont.)

Dimensions 1-cable connector

E55341 E55450 E55426

ø5...8

Z 19

25,5

44

57,5 X

57,5 Z X

6-cable distribution connector

Y

E55427

Z

X

98,5

166

66,5

1-cable connector

ø5...8

2-cable connector

30 or 60 35 to 240 rigid 35 to 240 flexible 31

L

L (mm) S (mm2) Cu / Al Torque (Nm)

30 35 to 300 rigid 35 to 300 flexible 31

E54545

E54470

1-cable or 2-cable connectors made of tinned aluminium, for copper or aluminium cables, are screwed to the device terminals or to right-angle terminal extensions. These connectors are supplied with phase barriers.

E55428

E54469

Interpact INS/INV320 to 630

1-cable connector

2-cable connector

S

Dimensions 1-cable connector If 500 V i U i 690 V, phase barriers or long or short terminal shields are mandatory.

E55429

E55431

49 Z

44

Z 14

88,5 X

88,5 X

2-cable connector

E55430

Z

46,5

88,5 X

49

Interpact

Schneider Electric

Installation and connection Front connection of insulated

bars and cables with crimped lugs

If 500 V i U i 690 V, phase barriers or long or short terminal shields are mandatory

E50702

Interpact INS100 to INS160 switch-disconnectors are equipped as standard with terminals comprising nuts with M6 screws, for direct connection of insulated bars and cables with crimped lugs. Lugs The small lugs for copper cables may be used for cables with cross-sectional areas up to 95 mm2. Crimping by hexagonal necking or punching. Lugs are supplied with phase barriers and are compatible with the terminal shields. INS100 to 160

Pole pitch d (mm) l (mm) e (mm) L (mm) L1 (mm) Dia. (mm) Torque (Nm) Bars, lugs 30 mm i 10 d + 10 2...6.4 15 i 21 u 6.2 8

E38889

E54463

Interpact INS100 to INS160

.1

Interpact INS250 to 630 and INV100 to 630

Interpact INS250 to INS630 and INV100 to INV630 switch-disconnectors are equipped as standard with terminals receiving snap-in nuts and screws (M8 for INS/INV up to 250, M10 from 320 upwards) for direct connection of insulated bars or cables with lugs. Lugs Lugs are different for copper and aluminium cables. They are supplied with phase barriers and are compatible with the long terminal shields. c the small lugs for copper cables may be used for cables with the following cross-sectional areas: v 120, 150 or 185 mm2 (INS/INV up to 250); v 240 or 300 mm2 (INS/INV up to 630). Crimping by hexagonal necking or punching. c the small lugs for aluminium cables may be used for cables with the following cross-sectional areas: v 150 or 185 mm2 (INS/INV up to 250); v 240 or 300 mm2 (INS/INV up to 630). Crimping by hexagonal necking. INS250 INS320 to 630 INV100 to 250 INV320 to 630

Pole pitch d (mm) I (mm) e (mm) L1 (mm) Dia. (mm) Torque (Nm) 35 mm i 10 d + 10 i6 i 25 u 10 15 45 mm i 15 d + 10 3 i e i 10 i 32 u 10 50

E50702

E54459

E54463

ø5...8

If 500 V i U i 690 V, phase barriers or long or short terminal shields are mandatory

E30907

E55434

E55433

N

Small lugs for copper cables

400 l L e

Ø d L

Small lugs for copper cables

Small lugs for aluminium cables

400 l L e

Ø d L

Dimensions INS250 INV100 to 250

INS320 to 630 INV320 to 630

Z

10,5

14

57,5 Z X

X

88,5

50

Interpact

Schneider Electric

E24007

If 500 V i U i 690 V, phase barriers are mandatory

E24005

Interpact IN1000 to 2500

E24008

2 Ø13 17,5 25 12,5 50

25 25 25 100 17,5

3 Ø13

IN1000/IN1600

IN1000/IN1600

IN2500

51

Interpact

Schneider Electric

Installation and connection Front connection with

accessories

Interpact INS250 and INV100 to 250

Spreader

E54460

Material: tinned copper

E18599 E18601

Straight terminal extensions Material: tinned copper

Right-angle terminal extensions Material: tinned copper Installation on upstream terminals

E18600

ø5...8

E25961

If 500 V i U i 690 V, phase barriers or long or short terminal shields are mandatory

E55599

One-piece spreader

Connection of two cables with lugs

E25969

Connector with clip for bare cables

Pole pitch

Without spreader With spreader 35 mm 45 mm

Dimensions

E50702

with spreader

Bars L (mm) l (mm) d (mm) e (mm) Dia. (mm) L (mm) Dia. (mm) (Nm) i 25 d + 10 i 10 i6 8.5 i 25 8.5 15 (1)

400 l L e

Ø d L

Lugs Torque

(1) Tightening torque for spreader Spreaders, straight terminal extensions and right-angle terminal extensions are supplied with phase barriers.

Dimensions Right-angle terminal extensions

E55436

Spreader and straight terminal extensions

E55440

39,5

4 20,5

45

159 45

45 30

19,5

57,5 Z X

98,5 X

One-piece spreader

E55342

Y

Z

45

180,5 45

Z 45 98

Z 98

43,5 125,5 X

Y 24 Without front alignment With front alignment base base

52

Interpact

Schneider Electric

Interpact INS/INV320 to 630

Spreader Material: tinned copper

E18599 E54462 E21276

Edgewise terminal extensions Material: tinned copper

Right-angle terminal extensions Material: tinned copper Installation on upstream terminals

E18600

E54469

ø5...8

If 500 V i U i 690 V, phase barriers or long or short terminal shields are mandatory

One-piece spreader. 1-cable and 2-cable connectors for bare cables

Pole pitch

Without spreader With spreader 45 mm 52.5 or 70 mm

Dimensions

E50702

with spreader

Bars L (mm) l (mm) d (mm) e (mm) Dia. (mm) L (mm) Dia. (mm) (Nm) i 40 d + 15 i 20 3 i e i 10 12.5 i 40 12.5 50 (1)

with edgewise terminal extensions

i 32 30 i I i 34 i 15 3 i e i 10 > 10.5 i 32 10.5 50 (1)

400 l L e

Ø d L

Lugs Torque

(1) Tightening torque for spreader and extensions. Spreaders, edgewise terminal extensions and right-angle terminal extensions are supplied with phase barriers.

Dimensions Edgewise terminal extensions

E55444

Right-angle terminal extensions

F view F

E55438

58

Z 42 8

61 Z

8 34

88,5 X

X

88,5

Spreader

E55442

K9

K8 K8 K8

26 39 108 X

Y

Z

Type

INS320/630, INV320/630 width in mod. of 52.5 mm width in mod. of 70 mm

K8

52.5 70

E54470

K9

187.5 240

53

Interpact

Schneider Electric

Installation and connection Front connection with

accessories

Interpact NI1000 to 2500

Spreader

E24014

120 120 120 8(1) 15 90 25 25 20 5 Ø12,2

70 100 25 50

12,5

(1) 16 mm for IN1600

Edgewise terminal extensions IN1000 IN1600

E24016 E24017

12,5 40 12,5

50 25

12,5

10

75 25 25

50 12,5

70

16

12,5 40 4 Ø12 12,5 25 50

82,5 12,5 47,5 5 Ø12,2 12,5 25 50

Connector IN2500

E24019

14 Ø11 10 25 25 20 55 25 25 90 70 7,5 25 90 25 20 20 65 25 25 16 16

8

If 500 V i U i 690 V, phase barriers are mandatory.

Phase barriers

c distribution blocks, lugs, right-angle/straight/edgewise terminal extensions and spreaders are supplied with phase barriers. c phase barriers may be positioned horizontally or vertically. c they may be replaced by long terminal shields.

E55445

ø5...8

54

Interpact

Schneider Electric

Rear connection of Interpact INS250 to 630 and INV100 to 630

Interpact INS250 to 630 and INV100 to 630 switchdisconnectors may be equipped with long or short rear connections, or a mix of the two. The connections may be positioned flat, on edge or at 45° angles, or any combination thereof. Material of rear connections: tinned copper.

ø5...8

E55446

E25967

Bars or cables with crimped lugs

INS250 INS320 to 630 INV100 to 250 INV320 to 630

Bars L (mm) i 25 l (mm) d + 10 d (mm) i 10 e (mm) i 6 Dia. (mm) > 8 Lugs L (mm) i 25 Dia. (mm) > 8 Torque (Nm) 5 (1)

E50702

Connection of bars or cables with lugs

If 500 V i U i 690 V, short terminal shields are mandatory

400 l L e

Ø d L

i 32 d + 15 i 15 3 i e i 10 > 10.5 i 32 > 10.5 20 (1)

E54473

Two lengths

E54474

(1) Tightening torque for rear connections.

Four positions

Dimensions INS250 and INV100 to 250

E55447

INS/INV320 to 630

E55449

10 8,6 18 57,5 43 short RC 88 long RC Z 6 X 20 13

15

13

23,2 14

30

50 short RC 115 long RC

88,5 Z X

8

For Interpact INS250 and INV100 to 250 switchdisconnectors, the rear connections may be equipped with 1-cable connectors secured by clips.

E55459

ø5...8

If 500 V i U i 690 V, short terminal shields are mandatory

55

Interpact

E25969/B

Bare cables (copper or aluminium)

Schneider Electric

Installation and connection Installation of Interpact

INS40 to 160

Dimensions

Front handle

E32252 E32250

Y

Y

(a) (b)

E32255

K

H3 P5 X H H2 H4 H1 H5

H7

X

X

H6

120°

P P1 P2 P3 P4 Z

K1 L

K1 K1 K L1 L2

(a) Terminal shields for INS40/63/80 (b) Terminal shields for INS100/125/160

Lateral handle

E32254 E32253

X

X

120° 60°

P6 P7

Z

Y L3

Dimensions (mm) Type

INS40/63/80 INS100/125/160

H

H1

H2

H3

H4

H5

H6

H7

K

1 7.5

K1

18 30

L

L1

L2

90 135

L3

109 154

P

P1

E32256

P2

47 47

P3

P4

P5

5 5

P6

P7

22.5 45 22.5 45

40.5 81 50 100

42.5 85 50 100

73.5 147 110 220

46 73 67.5 119

21.3 43 18.5 45

62.5 79 62.5 79

40 66.1 42.5 69.3

56

Interpact

Schneider Electric

Installation

On a backplate

ØT

E32259

sur rail symétrique On a rail

C2 X C1

E32452

U

X

Y Y

Dimensions (mm)

Y R1 R2

Type

INS40/63/80 INS100/125/160

C1

40 37.5

C2

80 75

R1

10 22.5

R2

36 60

ØT

4.5 4.5

U

35 35

Front panel cutout

E32261

Dimensions (mm) Type

INS40/63/80 INS100/125/160

C

47 47

R

92 137

= X = C

Y = R =

57

Interpact

Schneider Electric

Installation and connection Extended handle

for Interpact INS40 to 160

Front handle

E32609

75

E32610

37,5

60°

e

I

75 X 37,5

X

O

60° Y K

Z

B A

Dimensions (mm) Type

INS40/63/80 INS100/125/160

A (on backplate) B (on rail) mini maxi mini maxi

128 128 519 519 123 123 514 514

e

1...3 1...3

K

1 7.5

Length of shaft

A ­ 69 A ­ 69

Door or front panel cutout for front handle

E32611

45°

Ø50

X

36 72 Y Ø4.2 K

58

Interpact

Schneider Electric

Standard lateral handle

E38890

65 32,5

e

E32613

I

75 120° X

X

O

37,5

Y B

P6 Z

Dimensions (mm) Type With shaft

INS40/63/80 INS100/125/160

B mini

155 200

e maxi

396 441 1...3 1...3

P6

40 42.5

Length of shaft

B ­ 95 B ­ 140

Without shaft

INS40/63/80 INS100/125/160

B

102 147

e

1...3 1...3

P6

40 42.5

Lateral handle for functional enclosure

E38890

65 32,5

e

E38891

I

75 120° X

X

O

37,5

Y B

P6 Z

Dimensions (mm) Type Enclosure

INS40/63/80 INS100/125/160

Length of shaft

550 mm 600 mm 550 mm 600 mm

Type

short long short long

B

149 174 194 219

e

1...3 1...3 1...3 1...3

P6

41.5 41.5 41.5 41.5

Side cutout

E38892

Ø6 Ø50 55°

X

R = 36

Z 23,4 23,4 P6

59

Interpact

Schneider Electric

Installation and connection Installation of Interpact

INS250 to 630 INV100 to 630

Dimensions

Front handle

E51177 E51178

(a) (b)

E51179

H3 X H H2 H1

H5

H7 X H8

H4

H6

120°

P P1 P2 P3 P4

K1

Y K1 K L1

k1 L

(a) Terminal shields (b) Phase barriers

Z

Dimensions (mm) Type H H1

80 123

H2

68

H3

136

H4

148 215

H5

296 430

H6

166 ­

H7

332 ­

H8

115 177

K

17.5 22.5

K1

35 45

L

70 92.5

L1

140 185

P

21.5 26

P1

86 110

P2

96 120

P3

131

P4

138

INS250 40 INV100/250 INS320/630 61.5 INV320/630

102.5 205

160.4 162

Lateral handle for INS250 and INV100/250 Front handle

E56574 E56573

91

120° 60°

X

X 50

100

Z

Y

66,2

203

Direct extended

75

E56576

37,5

E56575

1...3

60°

I

X 37,5

O

75

X

60° Z 66,2 Y 152,5 mini 577 maxi

60

Interpact

Schneider Electric

Extended front handle

E54513

75 37,5

E54514

e

60°

I

X 37,5 60°

O

75

X

Y K

A Z

Dimensions (mm) Type

INS250 INS320/630

A mini

185 204

e maxi

600 600 1...3 1...3

K

17.5 22.5

Length of shaft A

101 124

Installation on a backplate

E51183

Door cutout

E51184

Ø5

H11 X H10

= X = H9

Y L5 L6

Y L3 L4

Dimensions (mm) Type H9 H10

50 75

H11

100 150

L3

65.5 85.5

L4

131 171

L5

35 45

L6

70 90

INS250 82 INS320/630 127

Door or front panel cutout for extended handle

Front

E54508 E56577

Lateral (INS250 and INV100/250)

Ø50

Ø50

25,5 (INS250) 30,8 (INS400/630) 25,5 (INS250) 30,8 (INS400/630)

31,2

X

31,2

X

Ø7,1

Y

43 (INS250) 53 (INS400/630)

Ø4,2 17,5 (INS250) 22,5 (INS400/630) 8 (INS250) 8,3 (INS400/630)

Z 66,2 18 36

Note: Lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

61

Interpact

Schneider Electric

Installation and connection Installation of Interpact

IN1000 to 2500

Dimensions

3 poles

E33429

4 poles

E33430

X

H H1 H3

H2

H4

T

X

T

E33431

X

H5

Z

(a) D3 D2 D1 D C (max.)

T1 W1

Y (b) W2

15

T1 W1

Y (b) W

65

(a) Long terminal shield for front connection (b) Terminals for IN2500

Dimensions (mm) Type

IN1000/1600 IN2500

Cmax. D

223.5 305.5 211.5 311.5

D1

118 200

D2

110 192

D3

104.5 180

H

235 235

H1

117.5 117.5

H2

300 440

H3

150 220

H4

540 540

H5

270 270

T

50 50

T1

105 105

W

410 410

W1

170 170

W2

340 340

Installation

On rails 3 poles

E23066 E23067

4 poles

320 160 390 160

E23068

On a backplate 3 poles

E23069

4 poles

390 Ø10 160

Ø10 32 X

Ø10

Ø10

320 160

180 90 Y

X

180 90

Y

X

X

Y

Y

Door cutout

E33432 E33428

X

X C1

C

Z A

R1 R Y

Dimensions (mm) Type

IN1000/1600 IN2500

A

110 192

C

185 185

C1

92.5 92.5

R

188 188

R1

149 149

62

Interpact

Schneider Electric

Extended front handle

E54506

Ø114

E54507

e

T

X

X 58° Y 105

46,5

A(*) Z

F

Dimensions (mm) Type

IN1000/1600 IN2500

A (*) mini

180 262

e maxi

306 388 1...4 1...4

F

109 127

T

50 50

(*) To compensate the vertical play of the shaft, reduce T by 3 mm when d > 220 mm

Door or front panel cutout for extended handle

E54509

105

Ø35±5

Ø8

T

X

Y

43,5 87

63

Interpact

Schneider Electric

Installation and connection Installation of mechanical

interlocks for direct handles

(INS250 to 630, INV100 to 630)

Direct handle

E54510

F

E54511

P

X

Q

X

D C

Y E

Y B A

G Z

Dimensions (mm) Type

INS250 INV100/250 INS320/630 INV320/630

A

325 416

B

90 115

C

87.5 100

D

175 200

E

70 92.5

F

156 210

G

106 130

P

68 102.5

Q

136 205

Door cutout for direct handle

E54512

Dimensions (mm) Type

N X M

INS250 INV100/250 INS630 INV320/630

F

156 210

H

17.5 22.5

K

295 386

L

75.5 100

M

150 175

N

75 74.5

Y H F K

Y H L

64

Interpact

Schneider Electric

Installation of mechanical interlocks for extended handles

(INS40 to 630, INV100 to 630)

Extended handle

F

E55452 E55451

P

X

Q

X

D C

Y

G Z

Y B A

E

Dimensions (mm) Type

INS40/80 INS100/160 INS250 INV100/250 INS320/630 INV320/630

A

325 325 325 416

B

90 90 90 115

C

87.5 87.5 87.5 100

D

175 175 175 200

E

46 70 70 92.5

F

156 156 156 210

G mini

155 200 185 204

P maxi

396 441 600 600 45 50 68 102.5

Q

90 100 136 205

Door cutout for extended handle

Dimensions (mm)

H H

Type

INS40 to INS160 INS250 INV100/250 INS320/630 INV320/630

F

156 156 210

H

0 17.5 22.5

X

Note: Lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

Y F Y

65

Interpact

Schneider Electric

Installation and connection Installation of downstream

coupling

(INS250 to 630, INV100 to 630)

Dimensions

Y

E55454 E55455

Y

X

X

L38

L37

Coupling dimensions

E55456

Connection

Y L28 Y

E55458

Y L29 L30

Y K4 K3 K1 K1 K1

L35 L36

E55457

X G2

L31

X K8 K9

K1 K1 K1

G29 G52 G30

G3

G28

K16 K2 K2 K2 L32 L39 L33 L34 L40

Dimensions (mm)

Type INS250 INV100/250 INS320/630 INV320/630 Type INS250 INV100/250 INS320/630 INV320/630 G2 105.5 141 L28 320 420 G3 169 240.7 L29 82.2 105.2 G28 225.2 315 L30 300 400 G29 83.5 118.4 L31 72.2 95.2 G30 127.5 163.4 L32 16.4 11.1 G52 143.5 202.5 L33 123 187.5 K1 35 45 L34 139.5 184.7 K2 35 52.5 L35 74.5 96.5 K3 51 75 L36 19.5 24 K4 156 210 L37 70 92.5 K8 57.5 88.5 L38 21.5 26 K9 157.5 225.7 L39 24.9 22.4 K16 25.4 26.1 L40 140 210

66

Interpact

Schneider Electric

Front-panel escutcheon

For switch-disconnector

E56501 E56502

E56500

M6

M7

A2

D1

D2

For ammeter module

E21651 E21652

E21650

93,5

80,5

157

3,5

6,5

Dimensions (mm) Type

INS250 INV100/250 INS320/630 INV320/630

A2

174 215.5

D1

3.5 3.5

D2

6.5 6.5

M6

114 164

M7

101 151

67

Interpact

Schneider Electric

Installation and connection Installation of one-piece

source changeover

Dimensions

E62634

E62635

Y

Y

D

X

X

E

A

F Z

B C

Dimensions (mm) Type

INS250 INS320/630

A

60.4 82.5

B

C

D

E

F

131 155

130.4 296 175 395

68 136 102.5 205

Door cutout

E62636

Dimensions (mm) Type

I X J

G

61.8 87

H

I

J

84 128

K

156 210

INS250 INS320/630

279.3 42 383.7 64

G

Y

K H

Y

68

Interpact

Schneider Electric

Technical details

Protection of switch-disconnectors

E51067

Interpact INS switch-disconnectors Upstream protection

By circuit breaker 380/415 V type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type aM (1) / max. rating (A) Isc max. making capacity type gG (2) / max. rating (A) Isc max. making capacity type gG (1) / max. rating (A) Isc max. making capacity type BS (2) / max. rating (A) Isc max. making capacity type BS (1) / max. rating (A) Isc max. making capacity kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

push to trip

90 %Ir 105 alarm

STR

23 SE

Io

.63

.9 .8 .88 .85 1 .8

Ir .93

.95 .98 1 x Io

4 3 2

Im5

6 8

Ir Im

10 1.5 Ir x

.5 x In

test

ø5...8

By circuit breaker 440/480 V (*)

By circuit breaker 500 V (INS40 to INS80) 500/525 V (INS100 to INS160)

By circuit breaker 690 V

By fuse 500 V

(*) Applicable for 480 V NEMA (1) Mandatory protection by an external thermal relay (2) No external thermal protection

70

Interpact

Schneider Electric

INS40

NS100N / 40 25 52 NS100H-L / 40 36 75 NS160N / 40 25 52 NS160H-L / 40 25 52 NSC100N / 40 18 37 NG125N / 40 25 52 NG125H / 40 36 75 NG125L / 40 50 105 NSA160N / 40 30 63 NS100N / 40 25 52 NS100H-L / 40 35 73 NS160N / 40 25 52 NS160H-L / 40 25 52 NSC100N / 40 18 37 NS100N / 40 18 36 NS100H-L / 40 18-25 36-53 NS160N / 40 15 30 NS160H-L / 40 15 30 NSC100N / 40 10 17 40 80 176 32 100 220 125 100 220 32 80 176 125 and 100M125 80 176

INS63

NS100N / 63 25 52 NS100H-L / 63 36 75 NS160N / 63 25 52 NS160H-L / 63 25 52 NSC100N / 63 18 37 NG125N / 63 25 52 NG125H / 63 36 75 NG125L / 63 50 105 NSA160N / 63 30 63 NS100N / 63 25 52 NS100H-L / 63 35 73 NS160N / 63 25 52 NS160H-L / 63 25 52 NSC100N / 63 18 37 NS100N / 63 18 36 NS100H-L / 63 18-25 36-53 NS160N / 63 15 30 NS160H-L / 63 15 30 NSC100N / 63 10 17 63 80 176 50 100 220 125 100 220 50 and 32M50 80 176 125 and 100M125 80 176

INS80

NS100N / 80 25 52 NS100H-L / 80 36 75 NS160N / 80 25 52 NS160H-L / 80 25 52 NSC100N / 80 18 37 NG125N / 80 25 52 NG125H / 80 36 75 NG125L / 80 50 105 NSA160N / 80 30 63 NS100N / 80 25 52 NS100H-L / 80 35 73 NS160N / 80 25 52 NS160H-L / 80 25 52 NSC100N / 80 18 37 NS100N / 80 18 36 NS100H-L / 80 18-25 36-53 NS160N / 80 15 30 NS160H-L / 80 15 30 NSC100N / 80 10 17 80 80 176 63 100 220 125 100 220 63 and 32M63 80 176 125 and 100M125 80 176

INS100

NS100N / 100 25 52 NS100H-L / 100 70 154 NS160-250N / 100 36 75 NS160-250H-L / 100 70 154 NSC100N / 100 18 37 NG125N / 100 25 52

INS125

INS160

NS160-250N / 125 36 75 NS160-250H-L / 125 70 154

NS160-250N / 160 36 75 NS160-250H-L /160 70 154

NG125N / 125 25 52

NSA160N / 100 30 63 NS100N / 100 25 52 NS100H-L / 100 65 143 NS160-250N / 100 35 73 NS160-250H-L / 100 65 143 NSC100N / 100 18 37 NS100N / 100 18 36 NS100H-L / 100 35-100 73-220 NS160-250N / 100 22 46 NS160-250H-L / 100 22 46 NSC100N / 100 10 17 NS100N / 100 8 14 NS100H-L / 100 10-75 17-165 NS160-250N / 100 8 14 NS160-250H-L / 100 10-20 17-40 100 80 176 80 100 220 160 100 220 80 and 63M80 80 176 160 and 100M160 80 176

NSA160N / 125 30 63

NS160N / 160 30 63

NS160-250N / 125 35 73 NS160-250H-L / 125 65 143

NS160-250N / 160 35 73 NS160-250H-L /160 65 143

NS160-250N / 125 22 46 NS160-250H-L / 125 22 46

NS160-250N / 160 22 46 NS160-250H-L /160 22 46

NS160-250N / 125 8 14 NS160-250H-L / 125 10-20 17-40 125 55 121 100 100 220 160 100 220 100 and 63M100 80 176 160 and 100M160 80 176

NS160-250N / 160 8 14 NS160-250H-L /160 10-20 17-40 160 33 69 125 100 220 160 100 220 125 and 100M125 80 176 160 and 100M160 80 176

71

Interpact

Schneider Electric

Technical details

Protection of switch-disconnectors

E51067

Interpact INS switch-disconnectors Upstream protection

By circuit breaker 380/415 V type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type aM (1) max. rating (A) Isc max. making capacity type gG (2) max. rating (A) Isc max. making capacity type gG (1) max. rating (A) Isc max. making capacity type BS (2) max. rating (A) Isc max. making capacity type BS (1) max. rating (A) Isc max. making capacity kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

push to trip

90 %Ir 105 alarm

STR

23 SE

Io

.63

.9 .8 .88 .85 1 .8

Ir .93

.95 .98 1 x Io

4 3 2

Im5

6 8

Ir Im

10 1.5 Ir x

.5 x In

test

By circuit breaker 440/480 V (*)

ø5...8

By circuit breaker 500 V

By circuit breaker 525 V

By circuit breaker 690 V

By fuse 500 V

(*) Applicable for 480 V NEMA (1) Mandatory protection by an external thermal relay (2) No external thermal protection

72

Interpact

Schneider Electric

INS250-100 INV100

NS100-160-250N/100 25-36-36 53-75-75 NS100-160-250H/100 70 154 NS100-160-250L/100 150 330 NS100-160-250N/100 25-25-35 53-53-73 NS100-160-250H/100 65 143 NS100-160-250L/100 130 286 NS100-160-250N/100 18 36 NS100-160-250H/100 50 105 NS100-160-250L/100 100-70-70 220-154-154 NS100-160-250N/100 18 36 NS100-160-250H/100 35 73 NS100-160-250L/100 100-50-50 220-105-105 NS100-160-250N/100 8 14 NS100-160-250H/100 10 17 NS100-160-250L/100 75-20-20 165-40-40 100 100 220 80 100 220 100 100 220 80 and 63M80 80 176 250 and 200M250 80 176

INS250-160 INV160

NS160-250N/160 36 75 NS160-250H/160 70 154 NS160-250L/160 150 330 NS160-250N/160 35 73 NS160-250H/160 65 143 NS160-250L/160 130 286 NS160-250N/160 30 63 NS160-250H/160 50 105 NS160-250L/160 70 154 NS160-250N/160 22 46 NS160-250H/160 35 73 NS160-250L/160 50 105 NS160-250N/160 8 14 NS160-250H/160 10 17 NS160-250L/160 20 40 160 100 220 125 100 220 160 100 220 125 and 100M125 80 176 250 and 200M250 80 176

INS250-200 INV200

NS250N/200 36 75 NS250H/200 70 154 NS250L/200 150 330 NS250N/200 35 73 NS250H/200 65 143 NS250L/200 130 286 NS250N/200 30 63 NS250H/200 50 105 NS250L/200 70 154 NS250N/200 22 46 NS250H/200 35 73 NS250L/200 50 105 NS250N/200 8 14 NS250H/200 10 17 NS250L/200 20 40 200 100 220 160 100 220 200 100 220 160 and 100M160 80 176 250 and 200M250 80 176

INS250 INV250

NS250N/250 36 75 NS250H/250 70 154 NS250L/250 150 330 NS250N/250 35 73 NS250H/250 65 143 NS250L/250 130 286 NS250N/250 30 63 NS250H/250 50 105 NS250L/250 70 154 NS250N/250 22 46 NS250H/250 35 73 NS250L/250 50 105 NS250N/250 8 14 NS250H/250 10 17 NS250L/250 20 40 250 100 220 200 100 220 250 100 220 200 and 100M200 80 176 250 and 200M250 80 176

INS320 INV320

NS400-630N/320 45 94 NS400-630H/320 70 154 NS400-630L/320 150 330 NS400-630N/320 42 88 NS400-630H/320 65 143 NS400-630L/320 130 286 NS400-630N/320 30 63 NS400-630H/320 50 105 NS400-630L/320 100-70 220-154 NS400-630N/320 22 46 NS400-630H/320 35 73 NS400-630L/320 100-50 220-105 NS400-630N/320 10 17 NS400-630H/320 20 40 NS400-630L/320 75-35 165-73 320 100 220 250 100 220 320 100 220 250 and 200M250 80 176 355 and 315M355 80 176

INS400 INV400

NS400-630N/400 45 94 NS400-630H/400 70 154 NS400-630L/400 150 330 NS400-630N/400 42 88 NS400-630H/400 65 143 NS400-630L/400 130 286 NS400-630N/400 30 63 NS400-630H/400 50 105 NS400-630L/400 100-70 220-154 NS400-630N/400 22 46 NS400-630H/400 35 73 NS400-630L/400 100-50 220-105 NS400-630N/400 10 17 NS400-630H/400 20 40 NS400-630L/400 75-35 165-73 400 100 220 315 100 220 400 100 220 315 and 200M315 80 176 355 and 315M355 80 176

73

Interpact

Schneider Electric

Technical details

Use at high temperatures

Power dissipated and resistance per pole

Interpact INS

Rating Resistance per pole Power dissipated per pole 40 0.3 0.5 250 (100) 0.15 1.5 1000 0.032 32 63 0.3 1.2 250 (160) 0.15 4 1600 0.02 53 80 0.3 1.9 250 (200) 0.15 6 2500 0.01 62.5 100 0.2 2 250 0.15 9.5 125 0.2 3.1 320 0.06 6.1 160 0.2 5.1 400 0.06 9.6 500 0.06 15 630 0.06 24

Interpact INS/INV

Rating Resistance per pole Power dissipated per pole

Interpact IN

Rating Resistance per pole Power dissipated per pole

Resistance per pole in milliohms (m) Power dissipated per pole in watts (W)

Temperature derating

Interpact INS 40 63 Front connection with bare-cable connectors or lugs

Thermal current Ith at 60 °C Thermal current Ith at 65 °C Thermal current Ith at 70 °C 40 40 40 63 63 63

80

80 80 80

100

100 100 100

125

125 125 125

160

160 160 150

Interpact INS 250 (100) Interpact INV 100 Front connection / rear connection

Thermal current Ith at 60 °C Thermal current Ith at 65 °C Thermal current Ith at 70 °C 100 100 100

250 (160) 160

160 160 160

250 (200) 250

200 200 200

250 250

250 250 250

320 320

320 320 320

400 400

400 400 400

500 500

500 500 500

630 630

630 590 550

Interpact INS 250 (100) 250 (160) 250 (200) 250 Interpact INV 100 160 250 250 Front connection with right-angle terminal extension + bare-cable connectors

Thermal current Ith at 55 °C Thermal current Ith at 60 °C Thermal current Ith at 65 °C Thermal current Ith at 70 °C 100 100 100 100 160 160 160 160 200 200 200 200 250 250 250 240

320 320

320 320 320 320

400 400

400 400 400 400

500 500

500 500 500 500

630 630

630 590 550 510

Interpact INS 250 (100) 250 (160) 250 (200) Interpact INV 100 160 250 Front connection / rear connection with ammeter or CT module

Thermal current Ith at 40 °C Thermal current Ith at 50 °C Thermal current Ith at 55 °C Thermal current Ith at 60 °C Thermal current Ith at 65 °C Thermal current Ith at 70 °C 100 100 100 100 100 100 160 160 160 160 160 160 200 200 200 200 200 200

250 250

250 250 250 240 230 210

320 320

320 320 320 320 320 320

400 400

400 400 400 400 400 400

500 500

500 500 500 500 480 450

630 630

600 575 540 505 480 450

Interpact IN

Thermal current Ith at 50 °C Thermal current Ith at 55 °C Thermal current Ith at 60 °C Thermal current Ith at 65 °C Thermal current Ith at 70 °C

1000

1000 1000 1000 1000 850

1600

1600 1520 1450 1360 1270

2500

2500 2500 2500 2450 2400

Thermal current Ith in Amps (QA)

76

Interpact

Schneider Electric

Interpact INV - Compact NS combination assembly

E56637

ø5...8

E56638

ø5...8

Direct combination assembly

Flexible combination assembly

Direct combination assembly

Without Vigi Interpact INV100 INV160 INV200 INV250 Compact NS100 NS160 NS250 NS250 Temp. TM-D STR (1) TM-D STR (1) TM-D STR (1) TM-D/STR (1)

30° C 35° C 40° C 45° C 50° C 55° C 60° C 100 100 100 97.5 95 92.5 90 100 100 100 100 100 100 100 160 160 160 156 152 147 144 160 160 160 160 160 160 150 200 200 200 195 190 185 180 200 200 200 200 200 200 200 240 230 225 210 200 190 180

INV320 INV320 INV400 INV500 INV630 NS250 NS400 NS400 NS630 NS630 TM-D STR (1)

250 250 250 244 238 231 225 250 250 250 250 250 240 230 320 320 320 320 320 320 320 400 400 400 400 400 390 380 475 460 445 430 410 395 380 475 460 445 430 410 395 380

With Vigi Interpact INV100 INV160 INV200 INV250 Compact NS100 NS160 NS250 NS250 Temp. TM-D STR (1) TM-D STR (1) TM-D STR (1) TM-D/STR (1)

30° C 35° C 40° C 45° C 50° C 55° C 60° C 100 100 100 97.5 95 92.5 90 160 160 160 160 160 160 160 160 160 160 156 152 147 144 160 160 160 160 160 160 150 200 200 200 195 190 185 180 200 200 200 200 200 200 200 240 230 225 210 200 190 180

INV320 INV320 INV400 INV500 INV630 NS250 NS400 NS400 NS630 NS630 TM-D STR (1)

250 250 250 244 238 231 225 250 250 250 250 250 240 230 320 320 320 320 320 320 320 400 400 400 400 390 380 360 460 445 430 410 395 380 360 460 445 430 410 395 380 360

Flexible combination assembly

Without Vigi Interpact INV100 INV160 INV200 INV250 INV320 INV320 INV400 INV500 INV630 Compact NS100 NS160 NS250 NS250 NS250 NS400 NS400 NS630 NS630 Temp. TM-D STR (1) TM-D STR (1) TM-D STR (1) TM-D STR (1) TM-D STR (1)

30° C 35° C 40° C 45° C 50° C 55° C 60° C 100 100 100 97.5 95 92.5 90 100 100 100 100 100 100 100 160 160 160 156 152 147 140 160 160 160 160 160 160 160 200 200 200 195 190 185 180 200 200 200 200 200 200 200 250 250 250 244 238 231 225 250 250 250 250 250 240 230 250 250 250 244 238 231 225 250 250 250 250 250 240 230 320 320 320 320 320 320 320 400 400 400 400 400 390 380 500 500 500 500 500 475 450 600 575 550 525 500 475 450

With Vigi Interpact INV100 INV160 INV200 INV250 INV320 INV320 INV400 INV500 INV630 Compact NS100 NS160 NS250 NS250 NS250 NS400 NS400 NS630 NS630 Temp. TM-D STR (1) TM-D STR (1) TM-D STR (1) TM-D STR (1) TM-D STR (1)

30° C 35° C 40° C 45° C 50° C 55° C 60° C 100 100 100 97.5 95 92.5 90 100 100 100 100 100 100 100 160 160 160 156 152 147 140 160 160 160 160 160 160 160 200 200 200 195 190 185 180 200 200 200 200 200 200 200 250 250 250 244 238 231 225 250 250 250 250 250 240 230 250 250 250 244 238 231 225 250 250 250 250 250 240 230 320 320 320 320 320 320 320 400 400 400 400 400 390 380 500 500 500 500 480 455 430 580 555 530 505 480 455 430

(1) STR...SE/GE

77

Interpact

Schneider Electric

Use of switch-disconnectors for motor feeder applications

Interpact INS40 to 630

Rated operational current and power for AC23A motors

AC 50/60 Hz 220 V 230 V (NEMA) 240 V 380 V 415 V 440 V 480 V (NEMA) 500 V 525 V 690 V AC 50/60 Hz 220 V 230 V (NEMA) 240 V 380 V 415 V 440 V 480 V (NEMA) 500 V 525 V 690 V INS40 I (A) 40 40 40 40 40 40 40 32 ­ ­ P(KW) 11 ­ 11 20 22 22 ­ 18.5 ­ ­ P(HP) ­ 10 ­ ­ ­ ­ 30 ­ ­ ­ P(HP) ­ 60 ­ ­ ­ ­ 125 ­ ­ ­ INS63 I (A) 63 63 63 63 63 63 63 40 ­ ­ P(KW) 15 ­ 20 30 30 30 ­ 22 ­ ­ P(HP) ­ 20 ­ ­ ­ ­ 40 ­ ­ ­ P(HP) ­ 75 ­ ­ ­ ­ 150 ­ ­ ­ INS80 I (A) 80 80 80 72 72 63 63 40 ­ ­ P(KW) 22 ­ 25 37 37 37 ­ 22 ­ ­ P(HP) ­ 30 ­ ­ ­ ­ 40 ­ ­ ­ P(HP) ­ 100 ­ ­ ­ ­ 200 ­ ­ ­ INS100 I (A) P(KW) 100 22 100 ­ 100 30 100 45 100 55 100 55 100 ­ 100 55 100 55 63 55 INS320 I (A) P(KW) 320 90 320 ­ 320 90 320 160 320 185 320 200 320 ­ 320 220 320 220 320 250 P(HP) ­ 30 ­ ­ ­ ­ 75 ­ ­ ­ P(HP) ­ 125 ­ ­ ­ ­ 250 ­ ­ ­ INS125 I (A) P(KW) 125 37 125 ­ 125 37 125 55 125 55 125 75 125 ­ 125 75 125 75 80 75 INS400 I (A) P(KW) 400 110 400 ­ 400 132 400 200 400 220 400 250 400 ­ 400 250 400 250 400 400 P(HP) ­ 40 ­ ­ ­ ­ 100 ­ ­ ­ P(HP) ­ 150 ­ ­ ­ ­ 300 ­ ­ ­ INS160 I (A) P(KW) 160 45 160 ­ 160 45 160 75 160 90 160 90 160 ­ 160 110 160 110 160 90 INS500/630 I (A) P(KW) 500 132 500 ­ 500 160 500 250 500 250 500 300 500 ­ 500 355 500 355 500 500 P(HP) ­ 60 ­ ­ ­ ­ 125 ­ ­ ­ P(HP) ­ 200 ­ ­ ­ ­ 350 ­ ­ ­

INS250/160 I (A) P(KW) 160 45 160 ­ 160 45 160 75 160 90 160 90 160 ­ 160 110 160 110 160 90

INS250/200 I (A) P(KW) 200 55 200 ­ 200 55 200 90 200 110 200 110 200 ­ 200 132 200 132 200 160

INS250 I (A) P(KW) 250 75 250 ­ 250 75 250 132 250 150 250 132 250 ­ 250 160 250 160 250 220

78

Interpact

Schneider Electric

Interpact: price list

INS40 to INS160 Complete device fixed/FC and accessories

Unit price (excl.VAT) in french francs

Interpact INS40 to INS160 standard version with black handle

Interpact INS40 Interpact INS63 Interpact INS80 3P 28900 28902 28904 4P 28901 28903 28905

E33365

.4 .2 .2 .1

E33366

Interpact INS40 to INS160 with red handle and yellow front

Interpact INS40 Interpact INS63 Interpact INS80 3P 28916 28918 28920 4P 28917 28919 28921

E33365

.4 .1

E33366

Locks, interlocks and coupling accessories

Handle locking

By 1 to 3 padlocks (OFF position), hasp dia. 5 to 8 mm or by lead seals

Ø5 5

E32426

8 8

Interlock for extended rotary handles

Mechanical for INS40 to INS160

E50997

Spare parts

Handle for rotary control

INS40 to INS160

or

E32411

Individual enclosures

IP55 heavy-duty sheetmetal enclosure

E32418

IP55 insulating enclosure

E32419

BTP308E-50010Interpact.fm/ 108

.4

.4

.2

.2

.1

.1

.4

.4

.2

.2

.1

.1

N

N

N N

N

N

N

Interpact INS100 Interpact INS125 Interpact INS160

3P 28908 28910 28912

4P 28909 28911 28913

Interpact INS100 Interpact INS125 Interpact INS160

3P 28924 28926 28928

4P 28925 28927 28929

Built-in

28953

Front or lateral rotary control

Black handle Red handle

28962 28963

For INS40 to INS160 with standard rotary handle For INS40 to INS160 with red rotary handle on yellow front

28965 28966

For INS40 to INS160 with standard rotary handle For INS40 to INS160 with red rotary handle on yellow front

28967 28968

Schneider Electric

Interpact: price list

INS40 to INS160 (cont.) Accessories

Unit price (excl.VAT) in french francs

Accessories

Distribloc distribution block (for bare cables)

INS40 to INS125

E33404

INS100 to INS160

125 A, 12 outgoing spring terminals (7 x 4 mm2 + 3 x 6 mm2 + 2 x 10 mm2) + 1 outgoing tunnel terminal (25 mm2) 160 A, 12 outgoing spring terminals (7 x 4 mm2 + 3 x 6 mm2 + 2 x 10 mm2) + 1 outgoing tunnel terminal (25 mm2) with prefabricated connections 125 A, 4 X 10 holes (5 x 10 mm2 + 4 x 16 mm2 + 1 x 35 mm2) 125 A, 4 X 17 holes (8 x 10 mm2 + 8 x 16 mm2 + 1 x 35 mm2)

7105 * 7106 *

Multi-stage distribution block (for bare cables)

E26801

INS40 to INS125 INS40 to INS125

13512 * 13514 *

Bare cable connectors

Snap-on

E32424

INS100 to INS160 cables up to 95 mm2 INS40 to INS80

Set of 3 Set of 4 Set of 3 Set of 4

28947 28948 19096 * 19091 *

E39432

Distribution connector for 3 rigid cables up to 16 mm2 or 3 flexible cables up to 10 mm2 Distribution connector for 4 rigid cables up to 25 mm2 or 4 flexible cables up to 16 mm2

INS100 to INS160

E30707

Set of 3 Set of 4

28949 28950

Crimp lugs for copper cables

E27797

For 95 mm2 cables with phase INS100 to INS160 barriers

Set of 3 Set of 4

28951 28952

Terminal shrouds

E24075

INS40 to INS80 INS100 to INS160

3P/4P 3P/4P

1 pair 1 pair

28955 28956

Terminal shields

E32457

INS40 to INS80 INS100 to INS160

3P/4P 3P/4P

1 pair 1 pair

28957 28958

Phase barriers

INS100 to INS160

E18606

3P/4P

Set of 6

28959

push to trip

Electrical auxiliaries

Auxiliary contacts

E18608

1 OF / CAF / CAO (depending on how it is mounted) 1 OF / CAF / CAO (low level)

INS40 to INS160 INS40 to INS160

29450 29452

Rotary handles

Accessories for conversion to extended rotary handles

Front control

E33405

Lateral control Lateral control functional enclosure G-GX-PRAGMA F

With black handle With red handle on yellow front With black handle With red handle on yellow front With black handle With red handle on yellow front

INS40 to INS160 INS40 to INS160 INS40 to INS160 INS40 to INS160 INS40 to INS160 INS40 to INS160

28941 28942 28943 28944 28945 28946

* consult us

Schneider Electric

BTP308E-50010Interpact.fm/

Interpact: price list

INS250 to INS630 Complete device fixed/FC and accessories

Unit price (excl.VAT) in french francs

Interpact INS250 to INS630 standard version with black handle

Interpact INS250-100A Interpact INS250-160A Interpact INS250-200A Interpact INS250 3P 31100 31104 31102 31106 3P 31108 31110 31112 31114 4P 31101 31105 31103 31107 4P 31109 31111 31113 31115

E50995

Interpact INS320 Interpact INS400 Interpact INS500 Interpact INS630

E50996

Interpact INS250 to INS630 with red handle and yellow front

Interpact INS250-100A Interpact INS250-160A Interpact INS250-200A Interpact INS250 3P 31120 31124 31122 31126 3P 31128 31130 31132 31134 4P 31121 31125 31123 31127 4P 31129 31131 31133 31135

E50995

Interpact INS320 Interpact INS400 Interpact INS500 Interpact INS630

E50996

Source changeover systems

Complete assembly

With Interpact INS250-100A With Interpact INS250-160A With Interpact INS250-200A With Interpact INS250 With Interpact INS320 With Interpact INS400 With Interpact INS500 With Interpact INS630 3P 31140 31144 31142 31146 31148 31150 31152 31154 4P 31141 31145 31143 31147 31149 31151 31153 31155 3/4P 31073 31074 41950 42878 2x 31087 2x 31088

E46629

O

Interlocks

Mechanical for INS250 Mechanical for INS320/400/630 Keylock type Ronis (2 keylocks / 1 key) Profalux Locking device for Ronis/Profalux keylocks on INS250 Locking device for Ronis/Profalux keylocks on INS320/400/630 3P 29358 32619

E50997

Downstream coupling accessories

For Interpact INS250 Long terminal shields (1 pair) For Interpact INS320/400/630 Long terminal shields (1 pair) 4P 29359 29324 32620 32565

E50998

Individual enclosures

IP55 heavy-duty sheetmetal enclosure

For INS250 with standard extended rotary handle For INS250 with red extended rotary handle on yellow front For INS320/400/630 with standard extended rotary handle For INS320/400/630 with red extended rotary handle on yellow front 31200 31201 31202 31203

E32418

IP55 insulating enclosure

For INS250 with standard extended rotary handle For INS250 with red extended rotary handle on yellow front For INS320/400/630 with standard extended rotary handle For INS320/400/630 with red extended rotary handle on yellow front 31204 31205 31206 31207

E32419

BTP308E-50010Interpact.fm/ 110

N

Schneider Electric

Interpact: price list

INV100 to INV630 (visible break) Complete device fixed/FC and specific accessories

Unit price (excl.VAT) in french francs

Interpact INV100 to INV630 standard version with black handle

Interpact INV100 Interpact INV160 Interpact INV200 Interpact INV250 3P 31160 31164 31162 31166 4P 31161 31165 31163 31167

E51001

Interpact INV320 Interpact INV400 Interpact INV500 Interpact INV630

3P 31168 31170 31172 31174

4P 31169 31171 31173 31175

E51002

Interpact INV100 to INV630 with red handle and yellow front

Interpact INV100 Interpact INV160 Interpact INV200 Interpact INV250 3P 31180 31184 31182 31186 4P 31181 31185 31183 31187

E51001

Interpact INV320 Interpact INV400 Interpact INV500 Interpact INV630

3P 31188 31190 31192 31194

4P 31189 31191 31193 31195

E51002

Individual enclosures

IP55 insulating enclosure

For INV100/160/250 with standard rotary handle For INV100/160/250 with red rotary handle on yellow front For INV320/400/630 with standard rotary handle For INV320/400/630 with red rotary handle on yellow 31204 31205 31206 31207

E32419

INV specific accessories

Spare viewport

E51003

Combination with Compact NS devices (for "tarif jaune / tarif vert")

INV100/160/250 - NS250 combination assembly INV320/400/630 - NS250 combination assembly Front alignment base for INV320/400/630 - NS250 combination assembly INV320/400/630 - NS400/630 combination assembly 31066 31067 31064 31068

E51004

Schneider Electric

E51005

N

For INV100/160/250 For INV320/400/630

31089 31090

Flexible connection assembly, vertical INV100/160/250 to horizontal NS250 Flexible connection assembly, vertical INV320/400/630 to horizontal NS250 Flexible connection assembly, vertical INV100/160/250 to vertical NS250, side-by-side Flexible connection assembly, vertical INV320/400/630 to vertical NS400/630, side-by-side Flexible connection assembly, vertical INV320/400/630 to vertical NS250, side-by-side

31069 31092 31071 31072 31093

BTP308E-50010Interpact.fm/

Interpact: price list

Accessories INS250 and INV100 to INV250 (visible break)

Unit price (excl.VAT) in french francs

Connection accessories (Cu or Al)

Rear connections

E18579

Short (1 pair) Long (1 pair)

29235 29236

Bare cable connectors

Snap-on, for cables:

E18572

1.5 to 95 mm2 ; < 160 A 10 to 185 mm2 ; < 250 A

Tab connector for voltage tap on 185 mm2 bare cable connector Clip for bare cable connector Distribution connector forsix 1.5 to 35 mm2 cables with phase barriers

Set of 3 Set of 4 Set of 3 Set of 4 Set of 2 Set of 10 Set of 3 Set of 4

29242 29243 29259 29260 29348 29241 29248 29249

E18598

"Polybloc" distribution block (for bare cables)

160 A (40°C), for 6 cables up to 10 mm2 250 A (40°C), for 9 cables up to 10 mm2 * consult us

E24076

7100 * 7101 *

Terminal extensions (supplied with 2 or 3 phase barriers)

E18600

Right-angle terminal extensions Set of 3 Set of 4 Straight terminal extensions Set of 3 Set of 4

29261 29262 29263 29264

E18601

Spreaders (for upstream or downstream connection)

Separate for each pole

E18599

3P 4P 3/4P 3/4P

31563 31564 31061 31064

E51006

One-piece Front alignment base

Crimp lugs for copper cables (supplied with 2 or 3 phase barriers)

For cable 120 mm2

E18602

For cable 150 mm2 For cable 185 mm2

Set of 3 Set of 4 Set of 3 Set of 4 Set of 3 Set of 4 Set of 3 Set of 4 Set of 3 Set of 4

29252 29256 29253 29257 29254 29258 29504 29505 29506 29507

Crimp lugs for aluminium cables (supplied with 2 or 3 phase barriers)

For cable 150 mm2

E30908

For cable 185 mm2

Terminal shields

E51007

Short (1 pair) Long (1 pair)

3/4 P 3/4 P

29322 29324

Phase barriers

Set of 6

E18606

29329

push to trip

BTP308E-50010Interpact.fm/ 112

Schneider Electric

Interpact: price list

Accessories (cont.) INS250 and INV100 to INV250 (visible break) (cont.)

Unit price (excl.VAT) in french francs

Electrical auxiliaries

Auxiliary contacts (changeover type)

E18608

OF or CAM (early make or break) Low-level OF or CAM (early make or break)

29450 29452

Indication and measurement modules

Ammeter module (4P)

A

8 4 0

160/5

16 12

Adaptation kit (necessary for devices with direct front handles) Rating (A) 100 150 250 Rating (A) 100 150 250

31081 29456 30556 31566 29458 30558 31568

E51009

E51008

Current transformer module (4P)

Rotary handles

Extended front handles

For Interpact INS250 with standard handle For Interpact INS250 with red handle on yellow front For complete source changeover assembly INS250 Direct handle conversion accessory (to be combined with extended lateral handle) For INS and INV250 with standard handle For INS and INV250 with red handle on yellow front 31050 31051 31055 31054 31057 31058

E54238

Lateral handles

E51011

Locks, interlocks and coupling accessories

Locks

ø5...8

By 1 to 3 padlocks (OFF position) Locking device for Ronis/Profalux keylocks (without keylocks) Keylock Ronis 1351B.500 Profalux KS5 B24 D4Z Mechanical for INS250 Keylock type (2 keylocks / 1 key)

Built-in 31087 41940 42888 31073 41950 42878 31087 29358 29359 29324

E51012

Interlocks

Ronis 1351B.500 Profalux KS5 B24 D4Z Locking device for Ronis/Profalux keylocks Downstream coupling for Interpact INS250 Downstream coupling for Interpact INS250 Long terminal shields (1 pair) 3P 4P

E50997

2x

Coupling accessories

E50998

Installation accessories

Front panel escutcheons

E185991

For switch-disconnector For ammeter module, IP40

31079 29318

Lead seal accessories

29375

Spare parts

12 snap-in nuts for fixed/FC (M8) 100 identification labels Bag of screws Black handle Red handle Viewport for INV100/160/250 30554 29314 29312 31082 31083 31089

Schneider Electric

BTP308E-50010Interpact.fm/

Interpact: price list

Accessories (cont.) INS320 to INS630 and INV320 to INV630 (visible break)

Unit price (excl.VAT) in french francs

Connection accessories (Cu or Al)

Rear connections

E18579

Short (1 pair) Long (1 pair)

32475 32476

Bare cable connectors

E22040

For 1 cable, 35 mm2 to 300 mm2 For 2 cables, 35 mm2 to 240 mm2 Tab connector for voltage tap on 185 mm2 bare cable connector

Set of 3 Set of 4 Set of 3 Set of 4 Set of 2

32479 32480 32481 32482 29348

E22041

Terminal extensions (supplied with 2 or 3 phase barriers)

E18600

Right-angle terminal extensions Set of 3 Set of 4 Edgewise terminal extensions Set of 3 Set of 4

32484 32485 32486 32487

E21276

Spreaders (for upstream or downstream connection)

Separate for each pole

E18599

52.5 mm 70 mm

E51006

One-piece Front alignment base

3P 4P 3P 4P 3/4P 3/4P

32490 32491 32492 32493 (1) (1)

Crimp lugs for copper cables (supplied with 2 or 3 phase barriers)

For 240 mm2 cables

E18602

For 300 mm2 câbles

Set of 3 Set of 4 Set of 3 Set of 4 Set of 3 Set of 4 Set of 3 Set of 4

32500 32501 32502 32503 32504 32505 32506 32507

Crimp lugs for aluminium cables (supplied with 2 or 3 phase barriers)

For 240 mm2 cables

E30908

For 300 mm2 câbles

Terminal shields

Short (1 pair) Long (1 pair) Longs for spreader (1 pair supplied with insulating plate) Set of 6

E18606

3/4P 3/4P 3/4P

32563 32565 32583 32570

E51007

Phase barriers

(1) Available soon

BTP308E-50010Interpact.fm/ 114

Schneider Electric

Interpact: price list

Accessories (cont.) INS320 to INS630 and INV320 to INV630 (visible break) (cont.)

Unit price (excl.VAT) in french francs

Electrical auxiliaries

Auxiliary contacts (changeover type)

E18608

OF or CAM (early make or break) Low-level OF or CAM (early make or break)

29450 29452

Indication and measurement modules

Ammeter module (4P)

Rating (A)

E51008

A

8 4 0

160/5

16 12

400 600

32656 32856

Current transformer module (4P)

Rating (A)

E51009

400 600

32658 32858

Rotary handles

Extended front handles

For Interpact INS320/400/630 with standard handle For Interpact INS320/400/630 with red handle on yellow front For complete source changeover assembly INS320/630 31052 31053 31056

E54238

Locks, interlocks and coupling accessories

Locks

ø5...8

By 1 to 3 padlocks on handle (open position) Locking device for Ronis / Profalux keylocks (without keylock) Keylock Ronis 1351B.500 Profalux KS5 B24 D4Z Mechanical for INS320/400/630 Keylock type Ronis 1351B.500 (2 keylocks / 1 key) Profalux KS5 B24 D4Z Locking device for Ronis / Profalux keylocks Downstream coupling for Interpact INS320/400/630 Downstream coupling for Interpact INS320/400/630 Long terminal shields with 52.5 mm pitch (1 pair) 4P 3P

Built-in 31088 41940 42888 31074 41950 42878 31088 32619 32620 32583

E50997

E51012

Interlocks

2x

Coupling accessories

E50998

Installation accessories

Front panel escutcheons

E18591

For switch-disconnector For ammeter module, IP40

31080 29318

Lead seal accessories

29375

Spare parts

100 identification labels Bag of screws Black handle Red handle Viewport for INV320/400/630 29314 32552 31084 31085 31090

Schneider Electric

BTP308E-50010Interpact.fm/

Interpact: price list

IN1000 to IN2500 Complete device fixed/FC

Unit price (excl.VAT) in french francs

Interpact IN1000 to IN2500

Interpact IN1000 Interpact IN1600 3P 47775 47776 4P 47751 47851

E24068

Interpact IN2500

E24069

47777

47855

BTP308E-50010Interpact.fm/ 116

Schneider Electric

Interpact: price list

IN1000 to IN2500 (cont.) Accessories

Unit price (excl.VAT) in french francs

Locks and interlocks

Handle locking

I ON

O OFF

By 3 padlocks By keylock (in OFF or ON position) 1 keylock Ronis 135.500 Profalux KS5B24D4Z

Built-in 41940 42888

E24074

ON position door interlock (for devices with extended rotary handles)

47754

Key type interlock

2 keylocks / 1 key

E24024

Ronis 1351.500 Profalux KS5B24D4Z

41950 42878

Spare parts

Black handle for direct rotary control

E24083

IN1000/IN1600 IN2500

47759 47862

Connection accessories (Cu or Al)

Terminal extensions for bars

Edgewise terminal extensions

E24080

IN1000 (per pole) IN1600 (per pole)

47758 47858

Spreaders (for upstream or downstream connection)

IN1000

E24081

IN1600

Set of 3 Set of 4 Set of 3 Set of 4

47760 47761 47760 47761 1 set supplied

IN2500

E24082

Connectors

IN2500 (1 connector)

E24034

55675

Phase barriers

E24026

IN1000/IN1600 IN2500

3P/4P 3P/4P

47756 47860

Electrical auxiliaries

Auxiliary contacts

E24072

1 OF or CAM (depending on how it is mounted) 2 OF contacts

42906 47757

Rotary handles

Accessories for conversion to extended rotary handle (short shaft)

Front handle

E23846

47753

Schneider Electric

BTP308E-50010Interpact.fm/

Information

LV switch-disconnectors 40 to 2500 A type Interpact (ENG)

82 pages

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

616183


You might also be interested in

BETA
untitled
3081050.pdf
LV switch-disconnectors 40 to 2500 A type Interpact (ENG)