FISHER PIERCE

AutoCap with Tw o-Way Radio C o m munications

SERIES

4500

AutoCap

TM

Adaptive Capacitor Controller-Recorder With Two-Way Communications

The Fisher Pierce Series 4500 AutoCap ControllerRecorder combines the intelligence of the AutoCap Adaptive Capacitor Controller with data radios for the cost effective automation of switched capacitors. Combining a capacitor control with two-way communications provides a powerful tool for discrete feeder management, data gathering, trouble shooting, system evaluation and analysis. Integrated two-way communication is achieved by incorporating the data radio and capacitor controller in the same enclosure, eliminating the need for additional communication equipment. Communications management and protocol conversion is performed using a dedicated high speed processor and flash memory. This permits remote protocol changes and upgrade without the need for costly field modifications. The Fisher Pierce Series 4500 allows complete control flexibility using twoway communications. The controller can be configured to operate under SCADA control or as a local control with SCADA override. The AutoCap controller with cellular telephone and modem provides instant trouble free, two-way communications. Using any PC/modem and Fisher Pierce SmartSetTM application software, which is Windowsbased and menu driven, the user can program the controller, monitor real-time line conditions, retrieve and graph load survey data. The controller can be used as an analytical tool moving it from site to site for verification of capacitor bank operation, load study and investigation of troublesome feeders. As a multifunction one-to-four season controller, the AutoCap can operate on the basis of VAr, voltage, current, temperature, time and combinations of these functions. In addition, AutoCap includes complete load data and event recording; reports can be created directly using SmartSet. Capacitor Controller Features · · · · Adaptive VArTM control. Voltage GuardTM (adaptive voltage restraint). PhaseFindTM (adaptive wiring corrections).. Windows-based SmartSet application software.

Communications Features · · · · Separate high speed communications processor. Flash memory allows remote change of protocol. Factory installed radio, modem or cellular telephone. Real-time monitoring and control.

Exclusive AutoCap Advantag Exclusive AutoCapT M Advantages

The Series 4500 AutoCap controller includes many new and innova i local control functions which elimit ve n t t e t d t o a s ruggle associated with setting a e h ra i i n l t optimum VAr setpoints (Fig. 1 ­ Adaptive VA ) f n i g r; i d n t e voltage change caused by bank switching (Fig. 2 ­ h Adaptive Voltage Guard); a d f e d w ri g ( i . 3 ­ n il i n Fg PhaseFind). Rever power verse · Reverse power functions calculate proper VAr setpoints to compensate fo a t r d VAr measurement r lee during this condition. Four other control mode options are also ava l bl for use duri g r ia e n everse pow er condit o s. An LED on the controller panel indicates reverse in pow er condition. Rever verse · Reverse Trip/Close detection automatically senses r everse wiring of the Close and Tr p d ve c r u t t t e i ri i c i s o h capacitor sw t h i h b t a l switching, except manual, and i c ; niis l indicates error by flashing LED on front panel. r · Anti-hunt function automatically compensates fo r apid bank tripping due to cycling loads or interaction from other switched banks on the feeder. Undervoltag · Undervoltage inhibitfeature protects the capacitor bank switch from damage caused by l voltage. ow

() B

Close set point = 2/3 bank size Lag

() A

Ii. sg

() D

Bank Size

() C

Lead Tr set point ip Esig.

Adaptive VAr (Fig. 1 ) I e t f e s ze of the capacitor bank and dniis i sets the VA switching points fo r r maximum loss reduction.

PhaseFind (Fig. 3) Compensates for phase rotation (A), finds current signal phase (B) with respect to voltage phase (C), and compensates fo r r eversed w ri g ( ) i n D.

Close inhibited Line Voltage

oltag Guard Adaptive Voltage Guard (Fig. 2 )

Present voltage, PCC in Close Present voltage, PCC in Trp i

Trp i inhibited

I e t f e voltage change from bank dniis to f switching; inhibits Close opera i n i Voltage Guard plus present line voltage exceeds high vo t g l m t lae ii. Reverse conditions inhibit Trp. i

dditional AutoCap A dditional AutoCap Features

The AutoCap co ntroller builds on more than 30 years of Fisher Pierce experience in the design, manu f acture, and application of electronic capacitor controls. · Standard meter socket mounting, pole or wal l mounting ava l bl i a e. · Single phase line current signal input: Line post sensor or CT input fo VAr and current control and r data recording. · Capacitor bank neutral current signal input: Fisher Pierce split lamination sensor (AT929) or CT/VT neutra c r e t i p t l urn nu. · N u ra c r e t l ckout lamp; r s t by manu l button et l urn o ee a or command through RS-232. · Shielded ambient temperature sensor. · 9 Pin, RS-232 communications port . · Optical communication portava l bl i a e. · 365/366 day time clock includes next century. · Progr ammable momentary output relays. · Nonvolatile memory. · Independent watchdog timer. · Electromechanical operations counter ava l bl i a e. · I t rnal LCD read/wri e d s l ava l bl ne t i p ay i a e. · Operational status LED's. · Manual Close/Tr operation and Auto/Manu l ip a switches.

SmartSet SmartSet Application Software

The Series 4500 AutoCap controller is progr ammed using Windows-based SmartSet software created by Fisher Pierce fo greater progr r amming ease. h li Using SmartSet software, t e AutoCap is a mutfunction microprocessor based controller which can be progr ammed fo u t four seasons. Each season can r p o have i s own primary and ove ride functions as listed in t r the Control Modes tabl b l The PCC is progr e e ow. ammed via a standard RS-232 or optional optical communications port using any Windows-based PC. Control Control Modes

Basic Functions · Adaptive VAr ·VAr ·Voltage · Current ·Time · High Temp · L Temp ow Override Functions · Voltage ·Time · High Temp · L Temp ow oltag Voltag e Bias ·Time · High Temp · L Temp ow Rever verse Reverse P ower · Ignore ·Voltage ·VAr ·Tr p a d I h b t i n nii · Close and Inhibit

View l ows user to rev ew controller setup and site i View Setup Screen ­ a l configuration summary.

The fo l l owing additional functions are also provided: · Real-time monitoring of data readings and controller status through local RS-232 or optical port . · Traditional holiday calendar ­ 10 year predefined, holiday can be user edited. · Individual and block holidays ­ 10 year user bloc holidays lock progr ammabl e. · Daylight Saving Time calendar ­ 10 year preDaylight Saving defined, can be edited. · Daily close count limit - User progr Daily close ammabl e. · Switching time delays/inhibits ­ For automatic and Switching delays/inhibits manual modes with LED indication on controller panel. · Neutral current lockout ­ Tr lock ips bank and prevents frther capacitor operation, and flashes ex e u t rnal lamp i t e event of a capacitor can fa l r Reset by n h i u e. ex e a button or RS-232 command. t rn l

Season Configuration Screen ­ fully prompted for easy controller progr amming.

Recording Extensive Data Recording

The Series 4500 AutoCap PCC provides a full spectrum of user defined load data and controller operations recording capability.Three-phase load data are deri ved from single phase measurements and assume balanced load. All recorded data are easily uploaded via RS-232 or optional optical port Memory of 32K standard; expanded 128K is . ava l bl i a e. Recording Parameter arameters Data Recording Parameters

Recording Load Data Recording

(1 min. to 4 hour ave raging peri d o)

Daily Summay Recording Daily Summay Recording

Date Stamp Time of Max/Min Values Daily Max/Min Voltage Daily Max/Min Current Daily Max/Min (3ø) kVAr Daily Max/Min Temp Daily Close Operations Daily Close Hours Close Ops Running To a tl

Recording Operations Recording

Date/Time Stamp Basic Operations Overide Operations r Manual Operations Pow er up/Pow er down Voltage Before/Delta Voltage kVAr Before and After kW Before and After Reverse Pow er/Normal Pow e r

Date/Time Stamp Voltage (Secondary ) Current (Single phase) kVAr (3ø) kVA (3ø) kW (3ø) Pow er Factor Total Harmonic Distort o in Temperature Tr ip/Close Status

Report Report Generation Capability

The SmartSetTM report genera i n feature provides to spreadsheet fo rmat and visual presentation of recorded data as well as many e i i g features.This capability is dtn i t gr n e ated into SmartSet ­ no additional softwa e i r s required. T e a i i y t gr all load study data, specify h b l t o aph time period, and superimpose Close/Tr opera i n i ip tos s included. Report Load Data Repor t s

· Spread sheet fo a f l rm t i e · D r c gr i e t aphing of load data · D r c e i gr i e t d t aph time peri d o ·Tr ip/Close status · Reportp n i g ri t n

Typical Load Data Graph

Specifications: Specifications

AU TO CONTROLLER SERIES 4500 AU TO C A P CONTROLLER AND RECORDER WO WA COMMUNICATIONS WITH T WO - WAY COMMUNICATIONS

TM

RADIO Maximum Maximum Radio Dimensions: 13.50"h x 7.25"w x 2.25"d Po Supply 3 . A o t nuous, 3 0 .A Radio Power Supply 1 Vdc, 2 0 c n i : r tansmit ELECTRICAL Operating Vo tage l ag Ranges: Ranges:

Range n . VT Ratio Range 1: 1 to 1000 : 1 i 0 1 : 1 increments : Current Resolution: Fisher Pierce 1301 sensor: 0.1A Lindsey line post sensor: 0.1A Current transfo rmer: 0.01A (secondary ) Accuracy : Accuracy ± 1.0% Reading, ± 0.2% Range, ± sensor error. Range e Range Fisher Pierce 1301 sensor ... 4-800A tru rm s : Lindsey line post sensor: 4-800A tru rm s. e Current transfo rmer: 0.1 ­ 20A (secondaryt e rm s )ru Current Tr ansfo rmer Ratio (CTR): 5:5 to 2000:5 in 1:5 increments. Reactive Power (VAr): Resolution: 1kVAr Po (VAr): 1kVAr Range Range ±99,999kVAr : 1 ) Temperature: Resolution: 1o F ( o C Accuracy 2 ) Accuracy ± 4o F ( o C : ) Range 4 Range - 0o C to + 60o C (-40o F to + 140o F : : Clock Time Clock Resolution: 1 second Accuracy Accuracy ± 10 minutes per year : Range Range 24 hour clock : Settings: 1 minute increments . Resolution: 0 1o Phase Angle: Accuracy Accuracy ± 1o,± sensor error : 5 Range Range 0o - 3 9o : Neutral Current Resolution: Fisher Pierce AT929 sensor: 0.1A Current Tr ansfo rmer: 0.01A (secondary ) Potential Dev c : 0.1V (secondary ie ) Accuracy Accuracy ± 2% of reading, ± 1% range, ± sensor error : Range Range Fisher Pierce AT929-400 sensor: 1 to 60A : Current Tr ansfo rmer Ratio Sec: 5:5 to 2000:5 Potential DevSe O R i S 0-60V (secondary c: ) ROLLER PRO C O N T ROLLER PRO C E Memory Size Memory Size 32 kB (standard), 128 kB (option) : Memory Memory Types: E P ROM, NVRAM and battery backed RAM SERIES 1301 LINE POST SENSOR. Accuracy Calibration Accuracy at 120A: ± 1% Erro Linearity Erro : 3-1200A, ± 1% r Erro Angle Erro : 3-600A, ± 0.5o r Erro Temperature Erro : ± 0.02% / oC r 7th Harmonic Response: 8 2 %

*See Fisher Pierce Series 1301 bulletin FP054 fo r complete specifications.

95 ­ 140 V, 60 Hz 190 ­ 280 V, 60 Hz 95 ­ 125 V, 50 Hz 190 ­ 250 V, 50 Hz Surg Surg e Withstand: ANSI C62.41-1987 Electrostatic Dischar harg Electrostatic Discharg e Te t 15kV applied to all s: accessibl p rt IEC 801-2. e a s, Relay Output Relay : Number: Tw o Type: Momentary closure Maximum Continuous Maximum Continuous Load: 10A Maximum Maximum Inrush: 50A, 50% PF, 6 cycles, make only Period: ammable 1 - 1000 Contact Closure Period: Progr seconds, i 1 s c increments n e. Fuse Rating: Switch Output to Capacitor Switch 10A FNM Slo-Blo® load fuse. : Controller Controller Input: 2A controller fuse. Communications Po t RS 232 Communications Port DB9 female connector r: Communicatons Po t Optical Communicatons Port Type 2 r: MECHANICAL Enclosure: u Enclosure: L ran, NEMA 3R r aw l r o e racke t Mounting: 4 o 6 j meter base, wa l o p l b Dimensions: 15.25"h x 9.25"w x 8.50"d ENVIRO TA ENVIRO N M E N TA L 4 Operating Temperature: - 0o C to + 80o C ( 4 o F to +176o F -0 ) : Range Humidity Range 0 to 95% (non-condensing) MEASUREMENT PERFORMANCE oltag Voltage Secondary Secondary Resolution: 0 1 Vac . : Accuracy Accuracy ±0.5% of reading over temperature. Range tn ru Range Same as opera i g range,t e rm s : Primary Primary

Ordering Information Ordering Information

Model Section 45 1 1 2 1 N 3 4 ­ ­ C 5 T 6 S 7 ­ D D A ­ SK 6 1 A Example ­ 8 9 10 ­ 11 12 13 14

Section 1 45 Section 2 1 2 0 Section 3 1 2 3 0 Section 4 F N Section 5 C D E N Section 6 T N Section 7 S E Section 8 F D

Basic Model Number Autocap progr ammable capacitor with two-way c o m munications Line Current Input (Current sensing device ordered separately device ordered separately. Fisher Pierce 1301 line post sensor (60A/V) or Lindsey sensor (100A/V) CT (5A secondary ) None Neutral Current Sensor Fisher Pierce AT929 sensor with 6 foot lead (supplied) CT (not supplied) VT (not supplied) None Optical Communication Port Communication Por ort Supplied None Counter/Display Counter/Display Electro-mechanical (counter 120Vac only) 2-line display only (read only) Electro-mechanical counter and 2-line display (read only) None Temperature Sensor Supplied None Memory Memory Standard 32K Expanded 128K munications Protocol C o m munications Protocol Smart e (no comm. micro or flash memory S t no ) DNP 3.0 (comm. micro and flash memory i s a l d ntle)

Note: For cellular phone or modem communication, select "F"

Circuitr cuitry Support Section 9 & 10 Circuitry To Support Communications Cellular / Modem Communications MB Modem installed - PSTN (publ c s rvice telephone netwo ) i e rk Radio BA BB DA DB NC

Note:

Communications Communications Installed - Metricom model 20043 Radio Ready Installed - MDS model 9310, 9810 Radio Ready C o m munications ready or radio upgr ade

Installed = Radio installation by FP, supplied by customer. C o m munication micro, flash memory and pow er supply included. Radio Ready = Radio installed by customer. Radio b racket, antenna mount and cables included. C o m munication micro, flash memory and pow e r supply included. C o m munications Ready (defined by selecting "D" in section 8) = Radio bracket and cables not included. Pow er supply included. Comm. mcro and memory isald ntle. Radio Upgr ade (defined by selecting code "F" in section 8) = Radio bracket and cables not included. Pow er supply included. Comm. micro and memory not installed (Controller board change out required for communications using a protocol other than Smart e ) St.

Section 11 Section 12 6 Section 13 1 2 3 4 5 Section 14

External Wiring and Mounting Below) Configuration (See Below) Enclosure Enclosure Type Luran l ag e/Frequency Vo tage/Frequency 120 Vac, 60Hz 240 Vac, 60 Hz 120 Vac, 50 Hz 220 Vac, 50 Hz 240 Vac, 50 Hz actory Factory Code

Jaw Socket Section 8 Four Jaw Meter Socket Mounting and Wiring Section 11 FJ GJ 1 L L 2 N/GND N/COM 3 TR TR 4 CL CL 5 ­ ­ 6 ­ ­ External GND Lug NO YES Current Inputs NONE NONE

1 3

2 4

Jaw Socket Section 8 Six Jaw Meter Socket Mounting and Wiring Section 11 SJ TJ SM TM SL TL SK TK 1 2 3 L L CSL CSL NSL NSL NSH NSH 4 TR TR CSH CSH NSH NSH CSH CSH 5 CSH CSH TR TR TR TR TR TR 6 CL CL CL CL CL CL CL CL External GND Lug NO YES NO YES NO YES NO YES Current Inputs LINE ONLY LINE ONLY LINE ONLY LINE ONLY NEUTRAL ONLY NEUTRAL ONLY LINE+NEUT LINE+NEUT View socket View looking into socket

CSL N/GND CSL N L N/GND L N L N/GND L N L N/GND/COM L N/COM

1 3 5

2 4 6

Section 8 Bracket Mounting with Terminal Strip Bracket Section 11 BJ: POLE WIRE TO TERMINAL STRIP WJ: W ALL AS SHOWN BELOW (Aluminum Enclosure Only Terminal Strip (Aluminum Enclosure Only ) External GND Lug YES Current Inputs NONE, LINE, NEUTRAL OR LINE+NEUTRAL GND= RLY= CSH = NSH=

Socke for CT short n switch t ig ava l bl for SJ and TJ wiri g ia e n Refer to Fisher Pierce product bulletin IC172-1293-4M-F fo r 2100 Series Meter Socke t orderi g i fo n n rmation.

System ground N= Neutra l L Ln = ie Output relay a rmatures CL= Close TR= Trp i Line current signal High CSL = Line current signal Low Neutral current signal High NSL= Neutral current signal Low

GND

N

L

RLY

CL T R C S H CSL N S H NSL - Broken lines between terminals indicate removeable jumper

AutoCap Contro e Series 4500 AutoCap Adaptive Capacitor Contro l r l

Mechanical Mechanical Data

Pole Bracket

Bracket W all Bracket

View Rear View Meter Plug Radio Dimensions

Cable

Maximum Conductor Diameter: 1 5/8"

A T929-400-6 Current Sensor SERIES 1301 LINE POST SENSOR

LINE POST SENSOR DIMENSIONS

WHT - Signal LO BLK - Signal HI GRN - System Ground

MODEL 1301-11A & 17A (15KV) 1301-41A & 47A (25KV) 1301-21A & 27A (35KV)

A 3.3(84) 5.0(127) 5.0(127)

B 9.3(236) 12.5(317) 14.5(368)

C 5.6(142) 7.0(178) 7.0(178)

Max.Cond.Dia. 1.5(38) 2.0(38) 2.0(51)

Preferred Installation and Preferred Sensor Location

Notes:

1 4W - grounded WYE circuit shown. . 2 Refer to orderi g i fo . n n rmation fo r w ring of other socket codes or i trminal stri e p. 3 Refe t i s ruction manu l for complete . r o nt a i s a l t o i fo n t l a i n n rmation.

Cap. Bank Switch Box

GRN

View Looking Into SK/Tk Socke t

Specifications are subject to change.

FISHER PIERCE

90 Libbey Parkway, Weymouth, MA 02189 U.S.A. Tel: (781) 340-0700 · Fax: (781) 340-0728 www.fisherpierce.com

© Fisher Pierce, 2001, FP110-12/00-Q-CR Printed in U.S.A.

USA · (800) 621-5875 4000 East 116th Street, Cleveland, Ohio 44105 (216) 271-6600 · Fax: (216) 341-3615 Canada · (800) 363-8110 China · Shanghai (514) 631-6145 · Fax (514) 631-1215 (86-21) 62493707 · Fax (86-21) 62493505