OPERATING INSTRUCTIONS

R

SAV GB 0418-1 FIGHTER 360P

411483

FIGHTER 360P

General

These operating instructions describe the most important functions and the current maintenance requested by FIGHTER 360 and its ventilation equipment.

Regarding component location and detailed information check "Installation and Maintenance Instructions".

Front panel

Pressure gauge

A

Switch

B

Display

C

AB

I II III

AB

I II

I II

AB

54.1°C Varmvattentemp.

2 1 0

bar

1.0

13.43

3 4

Left keypad

D

E

Heating curve offset

Right F keypad

Explanation

A

Pressure gauge

The radiator circuit pressure is displayed here. Normal pressure is 0.5 1.5 bar.

D

Left keypad

This button is used to set the required operating mode -Winter mode -Summer mode -Spring/Autumn mode The Extra hot water function is activated using this button. - 24 hours - Periodic extra hot water - Not selected/Extra hot water function deactivated. This button is used to change the fan speed. Return to normal speed occurs automatically (Does not apply however in the Off position). - Speed II - Off - Speed I - Normal

B

Switch

with three positions 1 - 0 : 1 Normal mode. All control functions connected. 0 Heat pump off. Standby. This position is used in the event of operating disturbances.

C

Display

Här visas symboler, värden, namn på aktuell meny samt menynummer.

FIGHTER 360P

E

Offset heating curve

This knob is used to change the room temperature. Turning clockwise increases the room temperature. When the knob is turned menu 2.0 is shown on the display screen and the value for the calculated supply temperature changes.

F

Right keypad

Plus button This button is used to scroll through the menu system (forwards) or increase the value of the selected parameter. Minus button This button is used to scroll through the menu system (backwards) or lower the value of the selected parameter. Enter button This button is used to select a lower menu in the menu system, to activate a parameter change as well as confirm a parameter change.

Menu system

Hotwatertemperature 1.0

Supply temperature 2.0

Outdoor temperature 4.0

Other settings 7.0

Interval per. XHW 1.1

Heating curve 2.1

Evaporating temperature 4.1

Fan settings 7.10

Operating mode settings 7.20

Other 7.30

Return 7.4

Temperature compr sensor 1.2

Offset heating curve 2.2

Vented air temperature 4.2

Return-time speed II 7.11

Auto Operating mode 7.21

Show servicemenues 7.31

Temperature el. heat sensor 1.3

Return temperature 2.3

Exhaust air temperature 4.3

Return-time speed I 7.12

Stop circulationspump 7.22

Return 7.32

Return 1.4

Min. supply temperature 2.4

Return 4.4

Return 7.13

Stop electric heater 7.23

Max. supply temperature 2.5

Return 7.24

Compensation 2.6

Return 2.7

FIGHTER 360P

Cleaning the air filter

The heat pump's air filter needs to be cleaned regularly (approximately 4 -- 5 times per year). The interval between cleaning operations varies and depends on the amount of dust in the exhaust air. s Set the switch to "0". s Open the upper front cover by pulling it out by the lower edge, then lifting it up. s Release the filter holder by turning the two black knobs a quarter of a turn anticlockwise. s Pull out the holder, take out the filter and shake off any dirt. If the filter is very dirty, turn it upsidedown and wash it carefully with water. Check that the filter is not damaged. New original filters can be ordered from NIBE.

FILTE R

s Assembly takes place in the reverse order.

FILTER-ALARM

1.0

FILTER-ALARM This information is shown every three months and is a call for the air filter to be cleaned. The information disappears when the filter has been cleaned and the main power switch is set to 1 again.

Cleaning the fan

Clean the fan every other year by taking it out of the heat pump and carefully brushing the vanes clean. s Set the switch to "0". s Open the upper front cover by pulling it out by the lower edge, then lifting it up. s To open the inner cover, unscrew the screws in the outer edges of the cover. s The fan is removed by unscrewing the four screws as illustrated and disconnecting the fan cable connector. s After removing the fan check the condensation tray under the evaporator. At the same time, check that the condensation hose connection is not blocked.

3 4

2 1 0

bar

T G

s Assembly takes place in the reverse order.

LEK

NOTE!

Avoid distorting the fan blades as this causes imbalance. Do not use water or detergents.

FIGHTER 360P

Cleaning the ventilation devices

Extract air temperature

5.0°C

Vented air temp.

4.2

Check that the temperature of the extract air (menu 4.2) is clearly lower than the room temperature when the compressor is operational, also see section Dealing with malfunctions -- High extract air temperature. It is normal that the extract air temperature varies. The building's ventilation devices should be cleaned regularly with a small brush to keep the correct ventilation. The device settings must not be changed. NOTE! If you take down more than one ventilation device for cleaning, do not mix them up. Check that the ventilation opening (84), behind the lower front cover, is not blocked. Clean if necessary.

Alarm

Quite a few alarms in the menu for FIGHTER 360P are reset by first switching off the heat pump, followed by an immediate switch on. s Set the switch on position "0" and wait for at least five seconds. s Reset the switch to position "1". s If repeately indicating alarms check "Installation and Maintenance Instructions" section "Dealing with malfunctions" - " Alarm indications on the display".

Checking the safety valves

AB

I II III

AB

I II

I II

AB

-2

0

+2

52

Efterfyll värmesystemet vid be Se skötselanvisning.

Filling the water heater and the heating system

s Open the filling valve (49). The boiler part of the heat pump and the radiator system are now filled with water. s After a while the pressure gauge will show rising pressure. s Turn the safety valve (52) until the boiler pressure reaches the normal working range (0.5 - 1.5 bar).

47

LE K

FIGHTER 360P has two safety valves, one for the heating system and one for the water heater. The heating system's safety valve (52) must be completely tight, but the hot water safety valve (47) may occasionally release some water after hot water has been used. This is because the cold water, which enters the water heater to replace the hot water, expands when heated causing the pressure to rise and the safety valve to open. Check both the pressure relief valves regularly. Check one valve at a time as follows: s Open the valve. s Check that water flows through the valve. s Close the valve. s The heating system may need to be refilled after checking the safety valve (52), see the section Commissioning and adjustment -- Filling the heating system.

v.v.

k.v.

Återledning radiatorer

Återledning radiatorer

Blaha blaha och annat trams

LEK

Blaha blaha och annat trams

49

NOTE!

The product's serial number should always be stated with all correspondence with NIBE. 089_ _ _ _ _ _ _ _ _ _ _

NIBE AB

R

SWEDEN

Box 14 Järnvägsgatan 40 SE- 285 21 MARKARYD

Tel: +46 -(0)433 - 73 000 Fax: +46 -(0)433 - 73 190 www.nibe.com

Information

4 pages

Find more like this

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

870985


You might also be interested in

BETA
MaxE Centrifugal Chiller (Design Level F) Engineering Guide - 160.73-EG1 (606)
untitled
353mc3_e.p65