Issued 21-Jun-04 Revised 22-Sep-08 C2021R1

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

C2021

Revision 1 Page 1 of 11

****This Standard Supercedes CE Macros MPR1S, MUR1S, MPR3S & MUR3S and portions of BECo Standards CS2.7-1.1, CS2.7-1.5 & CS2.7-1.7****

PRIMARY URD RISER CONSTRUCTION TABLE OF CONTENTS

Page 1 2 3 4 5 6 Scope............................................................................................ Safety............................................................................................ Bill of Material .............................................................................. Compatible Units........................................................................... 2 2 2-3 3

Construction................................................................................... 4-10 Signatures...................................................................................... 11

Issued 21-Jun-04 Revised 22-Sep-08 1.0 Purpose 1.1

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

C2021

Revision 1 Page 2 of 11

The purpose of this construction standard is to show the installation of a primary URD riser, for voltages 25kV and below. Risers shall be built to the highest standard operating voltage in the service center, but arresters shall be matched to the operating voltage.

2.0

Safety 2.1 Follow all appropriate safety procedures and adhere to all safety requirements for the use of personal protective equipment, headgear, and eye protection. All covered primary taps are to be treated as if bare.

3.0

Bill of Materials CAT ID 650 (15 kV) 9045 (27 kV) 15921 (27kV) 8934 (fiberglass) 15980 (Silicone) (rating) 8842 (3 kV) 8843 (6 kV) 8847 (10 kV) 15093 (12 kV) 8848 (18 kV) 9937 UT-URD 9564 9884 9229, 9009 123 833 753 752 1248 9898 1099 15363 1234 UT-BKT CGNP, NCRS4 UGARD3 UGARD2 Compatible Unit CCOFM CCOFH CCOFHP PBE1 PBE1-SIL CSA3 CSA6 CSA10-R CSA12-R CSA18-R

ITEM DESCRIPTION 1 Fused Cutout Polymer, for seacoast use Single phase equip bracket Si Coated, for seacoast use Surge Arrester System Voltages: 3740GY or 4160GY 4800 delta or 8320GY 13200GY 13800GY 22860GY Cold Shrink Termination for 15 kV (#1sol, #2str) & 25 kV (#2str, 1/0sol) Cable Grip ­ 15/25 kV (1" ­ 1 ¼ ") Cable Support Bracket Ground Rod (5/8") & Connctr Wire, #4 Cu, ground wire Ground Wire Molding 3" Cable U guard molding 2" Cable U guard molding 4" RS Conduit, 10 ft length 4" RS Quarter bend, 36" radius 4" PVC to RS Coupling Ground connector for 4" steel riser pipe and sweep 4" Conduit Strap

2 3

4

17 5 6,7 8 9 10 11 12 13 14 16

NCRS4

Issued 21-Jun-04 Revised 22-Sep-08

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

C2021

Revision 1 Page 3 of 11

ITEM 15 16 17 18 19 20 21 22 23 24 25 26 27 28

DESCRIPTION 4" to 3" PVC riser adapter Listed after #14 Listed after #4 Duct Seal 5 kV, #2 Cu EPR/Hypalon 3 Position Equipment Bracket SI Coated, for seacoast use 15 kV Spacer Anti-sway Bar Small, bronze hot line connctr Line Duc for messenger, 4ft 4" PVC cap, external fit Crossarm, double fir Crossarm braces, flat Slip Coupling, 4" cast iron Ground Bushing connector

CAT ID 9402

Compatible Unit NFP4-A32

9469 (1 lb) 15537 8932 15979 8851 8964 735 9460 8839 (8 pin) 8928 1345 1188

NADUX1 CWT-2 PBE3 PBE3-SIL CSP-MAS CSP-LDUC NFP4-CAP PCD10 NCRS4 NFS4-GNDBUSH

4.0

Compatible Units

Compatible Units (CUs) are materials used together to build to standards. They may include individual or groups of items, sometimes called Compatible Unit Assemblies. Below are key riser CU Assemblies and related items. Components CatID Description CatID Qty All materials detailed in bill of materials to build single riser ­ steel conduit, sweep & ground rod Pole ground w/ 35 ft of #4 Cu Wire, connect to grounding installed with riser pipe Single cold shrink termination for 25/15kV URD cable 1/0sol, #1 sol or #2 str with pin terminal connector and cable grip 15/25 kV Cold Shrink Termination Cable Grips 10' 8pin arms & braces 3" U-guard, 10 ft 9937 9564 8839 753 3 3 2 2

CU Name NCRS4 CGNP UT-URD

Title Riser, 4"x10' steel standpipe w/ sweep #4 Cu Pole Ground Cable Termination 15/25KV, single, #1S-1/0S-#2 Al/Cu URD Termination Assembly, 15/25KV 3 Ph , #1S-1/0S-#2 Al/Cu, w/ crossarms & U-guard

UTUA-3PH

Issued 21-Jun-04 Revised 22-Sep-08

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

C2021

Revision 1 Page 4 of 11 15/25 kV Cold Shrink Termination 9937 Cable Grips Fiberglass Equip Bracket, 18" 2" U-guard, 10 ft URD Termination Assembly, 15/25KV 2 Ph , #1S-1/0S-#2 Al/Cu, w/ fiberglass brackets & U-guard Surge Arrester(s) 15/25 kV Cold Shrink Termination Cable Grips Fiberglass Equip Bracket, 18" 3" U-guard, 10 ft 9564 8934 759 9937 9564 8934 753

UTUA-1PH

URD Termination Assembly, 15/25KV 1 Ph , #1S-1/0S-#2 Al/Cu, w/ fiberglass bracket & U-guard

1 1 1 2 2 2 2 2

UTUA- 2PH

CSA__ 5.0

Match Arrester to operating voltage, specify qty

Construction 5.1 Locate the riser and spare duct according to Figure 1. If it is necessary to install a second riser (single phase only) on a pole, locate as indicated. 5.1a No more than 2-single phase or 1-three phase primary risers shall be allowed on a pole. 5.1b At ground level, the pole's circumference cannot be more than 45% encircled with risers from all utilities.

Figure 1 ­ Location of Riser

Issued 21-Jun-04 Revised 22-Sep-08 5.2

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

C2021

Revision 1 Page 5 of 11 Cables that are not to be immediately terminated shall be left individually coiled, with adequate length to apply a termination & connect to the primaries, and supported above the steel riser pipe. Minimum safe bending radius for the cable is 12X cable diameter. Coils left above the riser shall have a 36" diameter to avoid cable damage. If the cables left coiled above the riser are not of adequate length to connect to the primary, they shall be the contractor's, installer of the cable, responsibility to replace. Surge arrester leads should be kept as short as possible to maximize protection. Riser Grounding (See C5000 for more grounding details) 5.5a Bond all steel riser pipes to pole ground. Note: Grounding bushings may be used as an alternative to the U shaped pipe ground connector. If cast iron slip couplings are used, the steel sweep bellow ground shall have its own ground connector connected to the pole ground and rod. To prevent theft and vandalism the ground wire molding shall be stapled every 6". In NSTAR south locations, a bare 1/0 copper ground wire shall be installed, in the trench, from the riser to the first pad or pull box ground ring. In 4800 Volt delta primary areas, do not connect the arrester grounds to the secondary/system neutral. See C4402 for more details

5.3

5.4

5.5

5.5b

5.5c

5.5d

5.5e

5.6

Seal any gaps between the cable and the riser cap or adapter with duct seal. Any unused ducts shall be capped. Minimum 45' pole size is preferred, however, 40' poles may be utilized where clearances allow.

5.7

Issued 21-Jun-04 Revised 22-Sep-08

LA

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

C2021

Revision 1 Page 6 of 11

TOP VIEW

19 3

24"

2

1

4 5

64"

TAPE GROUND WIRE & CONNECTION TO AT LEAST 12" BELOW TERMINATION TIE-WRAP AT THE BOTTOM J-HOOK SUPPORTS CABLE GRIP

12"

17

6"

DUCT SEAL

10 18 15 8 9

48"

8 14

RISER GROUND CLAMP

16

48"

11

IF USING SLIP COUPLING, A GROUND IS REQUIRED ON THE SWEEP BELOW GRADE.

24

12"

7

30"

6 12 13

FRONT VIEW SIDE VIEW

Figure 2 ­ Single-Phase Riser - Open Wire Main Line

Issued 21-Jun-04 Revised 22-Sep-08

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

C2021

Revision 1 Page 7 of 11

23

40"

21

3

1 2 4 5

TAPE GROUND WIRE & CONNECTION TO AT LEAST 12" BELOW TERMINATION TIE-WRAP AT THE BOTTOM

J-HOOK SUPPORTS CABLE GRIP

12"

17

6"

DUCT SEAL

10 15 8 9

48"

8

18

14

RISER GROUND CLAMP

16

48"

11

IF USING SLIP COUPLING, A GROUND IS REQUIRED ON THE SWEEP BELOW GRADE.

24

12"

7

30"

6 12 13

FRONT VIEW SIDE VIEW

Figure 3 ­ Single-Phase Riser - Spacer Cable Main Line

Issued 21-Jun-04 Revised 22-Sep-08

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

C2021

Revision 1 Page 8 of 11

(Typ) 3

LA LA LA

48"

18"

30"

USE 8' GUY INSUL. IF GUY IS REQ'D OR ELSE ATTACH LOWER

36" MIN.

(Typ) 1 (Typ) 4

5

(Typ)

17

12"

J-HOOK SUPPORTS CABLE GRIPS

TAPE GROUND WIRE & CONNECTION TO AT LEAST 12" BELOW TERMINATION TIE-WRAP AT THE BOTTOM

10 15 18 14 8 11 24 6 7

12" 48"

DUCT SEAL

9

48"

16

30"

IF USING SLIP COUPLING, A GROUND IS REQUIRED ON THE SWEEP BELOW GRADE.

12 13

Figure 4 - Three-Phase Riser - Open Wire Main Line

Issued 21-Jun-04 Revised 22-Sep-08

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

C2021

Revision 1 Page 9 of 11

24"

24"

24"

24"

24"

23

40"

(Typ) 1 (Typ) 4

5

(Typ)

17

12"

J-HOOK SUPPORTS CABLE GRIPS

TAPE GROUND WIRE & CONNECTION TO AT LEAST 12" BELOW TERMINATION TIE-WRAP AT THE BOTTOM

10 15 18 14 8 11 24 6 7

12"

DUCT SEAL

9

48"

16

48"

30"

IF USING SLIP COUPLING, A GROUND IS REQUIRED ON THE SWEEP BELOW GRADE.

12 13

Figure 5 - Three-Phase Riser - Spacer Cable Main Line

Issued 21-Jun-04 Revised 22-Sep-08

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

C2021

Revision 1 Page 10 of 11

LA LA

TOP VIEW

19 (Typ) 3

(Typ)

24"

(Typ)

1 (Typ)

2

4 (Typ) 5 (Typ)

64"

TAPE GROUND WIRE & CONNECTION TO AT LEAST 12" BELOW TERMINATION TIE-WRAP AT THE BOTTOM

J-HOOK SUPPORTS CABLE GRIP

12"

DUCT SEAL

17

6"

10 18 15 8 9

48"

8 14

RISER GROUND CLAMP (TYP)

16

48"

11

IF USING SLIP COUPLING, A GROUND IS REQUIRED ON THE SWEEP BELOW GRADE.

12"

7

30"

6

12 13

FRONT VIEW SIDE VIEW

Figure 6 - Single-Phase Loop Riser

Issued 21-Jun-04 Revised 22-Sep-08 6.0

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

C2021

Revision 1 Page 11 of 11

Approval Signature

Approved by:

Amin Jessa Director, Distribution Engineering