PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

TABLE OF CONTENTS

Table of Contents ........................................................................................................... 1 Draft Curtain Information And Specifications ................................................................. 2 Partition Information And Specifications......................................................................... 3 Partition Wall Details ...................................................................................................... 4 IH0010 ­ 8" System Transverse Partition Wall ..................................................... 4 IH0020 ­ Transverse Partition Wall Section Cuts ­ Purlins .................................. 5 IH0030 ­ Transverse Partition Wall Section Cuts ­ Joists .................................... 6 IH0040 ­ Longitudinal Partition Wall ..................................................................... 7 IH0050 ­ Longitudinal Partition Wall Section Cuts ................................................ 8 IH0070 ­ Longitudinal Partition Wall Section Cuts ­ Joists To Strut Conn. .......... 9 Draft Curtain Details ..................................................................................................... 10 IJ0010 ­ Transverse Draft Curtain W/ Purlins ­ Horizontal Bottom Support....... 10 IJ0020 ­ Transverse Draft Curtain W/ Purlins ­ Parallel Supports ..................... 11 IJ0040 ­ Transverse Draft Curtain W/ Joists ­ Horizontal Bottom Support ........ 12 IJ0060 ­ Transverse Draft Curtain W/ Joists ­ Away From Main Frame Rafter . 13 IJ0070 ­ Longitudinal Draft Curtain W/ Joists ..................................................... 14 Recessed Endwall Details ............................................................................................ 15 GA0002 ­ Recessed Endwall Detail ................................................................... 15

7.4.1

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

DRAFT CURTAIN INFORMATION AND SPECIFICATIONS

1. Draft curtains may be "transverse" (parallel with building main frames) or "longitudinal" (perpendicular to building main frames). 2. Standard draft curtains shall be sheeted on one side only. 3. The bottom of the standard "transverse" draft curtain shall run parallel with the building roofline. 4. The bottom of the standard "longitudinal" draft curtain shall run parallel with the roofline. 5. Standard draft curtain framing shall be field assembled with angles and selfdrilling fasteners provided by Nucor. Angles field cut to length. 6. Standard draft curtain sheeting and flashing shall consist of 28 gauge white Nucor "Classic Wall" panels with color matching trim at walls, roof and base of panel. Optional sheeting material (not by Nucor) may be used but must not exceed 3lbs./sq.ft. 7. The standard draft curtain framing will allow 4'-0", 6'-0", & 8'-0" draft curtain heights. Draft curtain heights of greater than 8'-0" will utilize optional framing techniques requiring additional field work. 8. Standard transverse draft curtain location is 1'-4 away from the centerline of the frame. If a different location is required, please specify on the order documents.

LAST REVISION DATE: 01/03/02 BY: CDM CHK: RJF

7.4.2

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

PARTITION INFORMATION AND SPECIFICATIONS

1. Partitions may be "transverse" (parallel with building main frames) or "longitudinal" (perpendicular to building main frames). 2. Standard partitions shall be sheeted on one side only. (Sheeting on both sides is optional. Note on quote & contract documents.) 3. Standard partition sheeting and flashing shall consist of 28 gauge white Nucor "Classic Wall" panels with color matching trim at walls and roof. Base trim is optional. 4. Partitions may be used in conjunction with building wall and/or ceiling liner. These conditions may require additional field work and fit-up. 5. Standard transverse partition location is 1'-4 away from the centerline of the frame. If a different location is required, please specify on the order documents. 6. Partition wall girt spacing may not match the exterior wall girt spacing. Maximum spacing at partition walls is 10'-0. If no framed openings or walkdoors are required in the partition wall, the maximum spacing will be used. If there are walkdoors in the partition wall, a girt will be placed at 7'-6 above finished floor. Please indicate on the order documents if walkdoors exist in the partition wall, even if not supplied by Nucor.

LAST REVISION DATE: 01/03/02 BY: CDM CHK: RJF

7.4.3

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

PARTITION WALL DETAILS IH0010 ­ 8" SYSTEM TRANSVERSE PARTITION WALL

LAST REVISION DATE: 10/21/2009 BY: DLC CHK: AES

DETAIL NAME IF APPLICABLE IH0010.DWG

7.4.4

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

IH0020 ­ TRANSVERSE PARTITION WALL SECTION CUTS ­ PURLINS

LAST REVISION DATE: 10/21/2009 BY: DLC CHK: AES

DETAIL NAME IF APPLICABLE IH0020.DWG

7.4.5

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

IH0030 ­ TRANSVERSE PARTITION WALL SECTION CUTS ­ JOISTS

LAST REVISION DATE: 10/21/2009 BY: DLC CHK: AES

DETAIL NAME IF APPLICABLE IH0030.DWG

7.4.6

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

IH0040 ­ LONGITUDINAL PARTITION WALL

LAST REVISION DATE: 02/23/10 BY: DLC CHK:

DETAIL NAME IF APPLICABLE

AES

IH0040.DWG

7.4.7

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

IH0050 ­ LONGITUDINAL PARTITION WALL SECTION CUTS

LAST REVISION DATE: 02/23/10 BY: DLC CHK:

DETAIL NAME IF APPLICABLE

AES

IH0050.DWG

7.4.8

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

IH0070 ­ LONGITUDINAL PARTITION WALL SECTION CUTS ­ JOISTS TO STRUT CONN.

LAST REVISION DATE: 02/23/10 BY: DLC CHK:

DETAIL NAME IF APPLICABLE

AES

IH0070.DWG

7.4.9

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

DRAFT CURTAIN DETAILS IJ0010 ­ TRANSVERSE DRAFT CURTAIN W/ PURLINS ­ HORIZONTAL BOTTOM SUPPORT

LAST REVISION DATE: 01/03/02 BY: CDM CHK: RJF

DETAIL NAME IF APPLICABLE IJ0010.DWG

7.4.10

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

IJ0020 ­ TRANSVERSE DRAFT CURTAIN W/ PURLINS ­ PARALLEL SUPPORTS

LAST REVISION DATE: 01/03/02 BY: CDM CHK: RJF

DETAIL NAME IF APPLICABLE IJ0020.DWG

7.4.11

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

IJ0040 ­ TRANSVERSE DRAFT CURTAIN W/ JOISTS ­ HORIZONTAL BOTTOM SUPPORT

LAST REVISION DATE: 01/03/02 BY: CDM CHK: RJF

DETAIL NAME IF APPLICABLE IJ0040.DWG

7.4.12

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

IJ0060 ­ TRANSVERSE DRAFT CURTAIN W/ JOISTS ­ AWAY FROM MAIN FRAME RAFTER

LAST REVISION DATE: 01/03/02 BY: CDM CHK: RJF

DETAIL NAME IF APPLICABLE IJ0060.DWG

7.4.13

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

IJ0070 ­ LONGITUDINAL DRAFT CURTAIN W/ JOISTS

LAST REVISION DATE: 01/03/02 BY: CDM CHK: RJF

DETAIL NAME IF APPLICABLE IJ0070.DWG

7.4.14

PRODUCT AND ENGINEERING MANUAL

7.4 PARTITIONS AND DRAFT CURTAINS

RECESSED ENDWALL DETAILS GA0002 ­ RECESSED ENDWALL DETAIL

LAST REVISION DATE: 10/04/2007 BY: RJF CHK: KMC

DETAIL NAME IF APPLICABLE GA0002.DWG

7.4.15