Parker Hannifin

User Information

Warning -- Aries Series products are used to control electrical and mechanical components of motion control systems. You should test your motion system for safety under all potential conditions. Failure to do so can result in damage to equipment and/or serious injury to personnel. Aries Series products and the information in this user guide are the proprietary property of Parker Hannifin Corporation or its licensers, and may not be copied, disclosed, or used for any purpose not expressly authorized by the owner thereof. Since Parker Hannifin constantly strives to improve all of its products, we reserve the right to change this user guide and software and hardware mentioned therein at any time without notice. In no event will the provider of the equipment be liable for any incidental, consequential, or special damages of any kind or nature whatsoever, including but not limited to lost profits arising from or in any way connected with the use of the equipment or this user guide. © 2008 Parker Hannifin Corporation All Rights Reserved

Technical Assistance

Contact your local automation technology center (ATC) or distributor. North America and Asia

Parker Hannifin 5500 Business Park Drive Rohnert Park, CA 94928 Telephone: (800) 358-9070 or (707) 584-7558 Fax: (707) 584-3793 Email: [email protected] Internet: http://www.parkermotion.com

Germany, Austria, Switzerland

Parker Hannifin Postfach: 77607-1720 Robert-Bosch-Str. 22 D-77656 Offenburg Telephone: +49 (0) 781 509-0 Fax: +49 (0) 781 509-176 Email: [email protected] Internet: http://www.parker-emd.com

Europe (non-German speaking)

Parker Hannifin plc Electromechanical Automation, Europe Arena Business Centre Holy Rood Close Poole Dorset, UK BH17 7BA Telephone: +44 (0) 1202 606300 Fax: +44 (0) 1202 606301 Email: [email protected] Internet: http://www.parker-emd.com

Italy

Parker Hannifin 20092 Cinisello Balsamo Milan, Italy via Gounod, 1 Telephone: +39 02 6601 2478 Fax: +39 02 6601 2808 Email: [email protected] Internet: http://www.parker-emd.com

Technical Support E-mail [email protected]

2 Aries User Guide

Parker Hannifin

Table of Contents

User Information ............................................................................................................................ 2 Table of Contents .......................................................................................................................... 3 Table of Tables............................................................................................................................... 5 Table of Figures ............................................................................................................................. 7 Important User Information ........................................................................................................ 11 Change Summary .................................................................................................................... 12 Chapter 1 Introduction ................................................................................................................ 16 Aries Products--Overview ....................................................................................................... 17 Compatible Parker Products .................................................................................................... 18 Checking Your Shipment.......................................................................................................... 19 Illustrations in this Installation Guide ........................................................................................ 20 Assumptions of Technical Experience ..................................................................................... 20 Technical Support .................................................................................................................... 20 Chapter 2 Mechanical Installation.............................................................................................. 21 Environment & Drive Cooling ................................................................................................... 22 Dimensions............................................................................................................................... 28 Weight ...................................................................................................................................... 30 Mounting Guidelines................................................................................................................. 31 Chapter 3 Electrical Installation ................................................................................................. 32 Installation Safety Requirements.............................................................................................. 33 System Installation Overview ................................................................................................... 34 Power Supply ........................................................................................................................... 39 Multiple Drive Installations........................................................................................................ 48 Brake Relay (Optional) ............................................................................................................. 50 Regeneration Protection........................................................................................................... 54 LEDsDrive Status Indicators................................................................................................. 56 Connector Descriptions ............................................................................................................ 57 Installation Test ........................................................................................................................ 72 Chapter 4 Communications........................................................................................................ 73 RS-232/485 Communications .................................................................................................. 74 Chapter 5 Tuning ......................................................................................................................... 78 Servo Tuning Overview ............................................................................................................ 79 Position Variable Overview ...................................................................................................... 80 Servo Response Overview....................................................................................................... 81 Servo System Gains................................................................................................................. 83 Servo Tuning Example ............................................................................................................. 86 Auto-Tuning .............................................................................................................................. 90 Chapter 6 Command Reference ................................................................................................. 91 Aries Communications Set-up.................................................................................................. 92 Description of Format ............................................................................................................... 92 Syntax ­ Letters and Symbols.................................................................................................. 93 Syntax ­ General Guidelines.................................................................................................... 94 Command Descriptions ............................................................................................................ 95 Chapter 7 Troubleshooting....................................................................................................... 156 Troubleshooting Guidelines.................................................................................................... 157 LEDsDrive Status Indicators............................................................................................... 158

3

Parker Hannifin RS-232/485 Communication Problems.................................................................................. 159 Error Messages ...................................................................................................................... 160 Smart Encoders...................................................................................................................... 163 Hall Sensor Configuration/Troubleshooting ........................................................................... 164 Appendix A Additional Specifications .................................................................................... 168 Amplifier.................................................................................................................................. 169 Feedback................................................................................................................................ 169 Protective Circuits .................................................................................................................. 170 Cables .................................................................................................................................... 173 Appendix B External Power-Dump Resistor Selection.......................................................... 174 External Power-Dump Resistor Selection .............................................................................. 175 Simplified Resistor Selection.................................................................................................. 175 Calculating Resistance--Rotary Motors ................................................................................ 177 Resistor SpecificationsRotary Motors................................................................................. 181 Calculating Resistance--Linear Motors ................................................................................. 183 Resistor SpecificationsLinear Motors ................................................................................. 187 Appendix C Regulatory Compliance­UL and CE ................................................................... 189 System Installation Overview ................................................................................................. 190 Regulatory Agencies .............................................................................................................. 200 Standards of Compliance ....................................................................................................... 200 Appendix D Servo Tuning Flow Diagram................................................................................ 201 Servo Tuning Flow Diagram................................................................................................... 202 Appendix E VM26 Expansion Module ..................................................................................... 203 Overview................................................................................................................................. 204 Index ........................................................................................................................................... 205

4 Aries User Guide

Parker Hannifin

Table of Tables

Table 1 Output Power Level..................................................................................................... 18 Table 2 Ship Kit Items, AR-01xx through AR-13xx .................................................................. 19 Table 3 Ship Kit Items, AR-20xE and AR-30xE ....................................................................... 19 Table 4 Environmental Specifications, AR-01xx through AR-08xx, AR-20xE and AR-30xE... 23 Table 5 Environmental Specifications, AR-13xx ...................................................................... 23 Table 6 AR-02xx Power Dissipation......................................................................................... 24 Table 7 AR-08xx Power Dissipation......................................................................................... 25 Table 8 AR-13xx Power Dissipation......................................................................................... 26 Table 9 AR-30xE Power Dissipation ........................................................................................ 27 Table 10 AR-01xx and AR-02xx Drive Dimensions ................................................................. 28 Table 11 AR-01xx , AR-02xx, & AR-13xx Drive Dimensions ................................................... 29 Table 12 AR-20xE and AR-30xE Drive Dimensions ................................................................ 30 Table 13 Drive Weight.............................................................................................................. 30 Table 14 Motor Power Fuse Information.................................................................................. 41 Table 15 Fuse Part Numbers ................................................................................................... 42 Table 16 Drive Motor Power Inrush Current ............................................................................ 42 Table 17 Output Power-Continuous and Peak......................................................................... 43 Table 18 Wiring to Motors ........................................................................................................ 44 Table 19 AR-20xE & AR-30xE DC Link Inductors ................................................................... 45 Table 20 Brake Relay Operation .............................................................................................. 53 Table 21 Regeneration Absorption .......................................................................................... 55 Table 22 LED Status Indicator-Normal Operation.................................................................... 56 Table 23 LED Status Indicator-Internal Drive Fault.................................................................. 56 Table 24 MOTOR FEEDBACK Connector Pinout........................................................................... 63 Table 25 Inputs--Encoder Inputs Electrical/Timing Characteristics ........................................ 63 Table 26 MOTOR FEEDBACK Connector Pinout for Resolver Option .......................................... 66 Table 27 Resolver excitation .................................................................................................... 66 Table 28 Fault Output Operation.............................................................................................. 67 Table 29 DRIVE I/O Connector Pinout ........................................................................................ 69 Table 30 Inputs--Enable and Reset Electrical/Timing Characteristics.................................... 70 Table 31 Outputs--Encoder Outputs Electrical/Timing Characteristics................................... 70 Table 32 Outputs-- Fault outputs Electrical/Timing Characteristics........................................ 70 Table 33 Inputs--Step & Direction Electrical/Timing Characteristics ...................................... 71 Table 34 Inputs--Analog Electrical/Timing Characteristics ..................................................... 71 Table 35 Terminal Emulator Configuration for RS-232/485 Communication........................... 74 Table 36 RS-232 Connector Pinout ......................................................................................... 75 Table 37 RS-485 Connector Pinout ......................................................................................... 75 Table 38 Position Response Types ......................................................................................... 82 Table 39 Commands-Description of Format ............................................................................ 92 Table 40 Commands-Syntax.................................................................................................... 93 Table 41 Syntax Guidelines ..................................................................................................... 94 Table 42 Configuration Errors and Warnings......................................................................... 100 Table 43 Current Foldback Ratings ....................................................................................... 102 Table 44 Drive Control Mode ................................................................................................. 104 Table 45 Peak Current Rating for Aries Drives ...................................................................... 109 Table 46 Error StatusText Based Report ........................................................................... 131 Table 47 Error LogEnable/Disable ..................................................................................... 132 Table 48 Terminal Emulator Configuration for RS-232/485 Communication......................... 159 Table 49 Communications Port Errors and Resolutions ........................................................ 160 Table 50 Error Messages ....................................................................................................... 163 Table 51 Configuring Hall Sensors......................................................................................... 167 Table 52 LED Short Circuit Fault............................................................................................ 170

5

Parker Hannifin Table 53 LED Drive Over-Temperature Fault ........................................................................ 170 Table 54 Reset Temperature Values ..................................................................................... 171 Table 55 LED Under-Voltage Fault ........................................................................................ 171 Table 56 LED Over-Voltage Fault .......................................................................................... 172 Table 57 Simplified Selection of External Power-Dump Resistor .......................................... 176 Table 58 Drive Capacitor Absorption ..................................................................................... 179 Table 59 Drive Capacitor Absorption ..................................................................................... 185 Table 60 Control Power Filter Selection................................................................................. 194 Table 61 Mains Motor Power Filter Selection ........................................................................ 194 Table 62 Enclosure Mounting Clamps ................................................................................... 196 Table 63 Regulatory Agencies ............................................................................................... 200

6 Aries User Guide

Parker Hannifin

Table of Figures

Figure 1 Cabinet Losses for AR-02xx when connected to a Parker BE231D motor ............... 24 Figure 2 Cabinet losses for AR-08xx when connected to a Parker BE343J motor ................. 25 Figure 3 Cabinet losses for AR-13xx when connected to a Parker MPM1421CSJ motor....... 26 Figure 4 Cabinet losses for AR-30xE when connected to a Parker MPM1422CSJ motor ...... 27 Figure 5 Drive mounting for the AR-01xx & AR-02xx............................................................... 28 Figure 6 Drive mounting for the AR-04xx, AR-08xx, and AR-13xx .......................................... 29 Figure 7 Drive mounting for the AR-20xE and AR-30xE.......................................................... 30 Figure 8 Panel Layout Dimensions for Aries Drives................................................................. 31 Figure 9 Overview of System Installation for AR-01xx to AR-13xx.......................................... 34 Figure 10 AR-01xx to AR-13xx Factory Installed Jumpers ...................................................... 35 Figure 11 Overview of System Installation for AR-20xE & AR-30xE ....................................... 36 Figure 12 AR-20xE to AR-30xE Factory Installed Jumpers..................................................... 37 Figure 13 Connectors on Aries Models AR-01xx to AR-13xx .................................................. 38 Figure 14 Connectors on Aries Models AR-20xE & AR-30xE ................................................. 38 Figure 15 Input Power Requirements ...................................................................................... 39 Figure 16 Motor and Control Mains Power Supply Connection ............................................... 40 Figure 17 Output Power Connection........................................................................................ 44 Figure 18 External DC Link Inductor Connection..................................................................... 45 Figure 19 Mains Control Input Power....................................................................................... 47 Figure 20 Multiple Drives AR-01xx to AR-13xx: Single Point Safety Earth ............................. 48 Figure 21 Multiple Drives AR-20xE & AR-30xE: Single Point Safety Earth ............................. 49 Figure 22 Typical Brake Relay Connection.............................................................................. 50 Figure 23 Brake Relay Connection for Parker Motors ............................................................. 51 Figure 24 Brake Relay Connection for Non-Parker Motors ..................................................... 52 Figure 25 External Regeneration Connection .......................................................................... 54 Figure 26 Mains/Input Power Connector.................................................................................. 57 Figure 27 Output (MOTOR) Power Connector ........................................................................... 59 Figure 28 AR-20xE & AR30xE Control Connector ................................................................... 61 Figure 29 MOTOR FEEDBACK connector, female drive connector pinout.................................... 62 Figure 30 MOTOR FEEDBACK connector, internal circuit diagram............................................... 62 Figure 31 MOTOR FEEDBACK connector, female drive connector pinout.................................... 65 Figure 32 MOTOR FEEDBACK connector for resolver option, internal circuit diagram................. 65 Figure 33 DRIVE I/O connector, female drive connector pinout ................................................. 67 Figure 34 DRIVE I/O connector, internal circuit diagram ............................................................ 68 Figure 35 RS-232/485 Connections......................................................................................... 74 Figure 36 RS-485 Multi-drop Connections............................................................................... 76 Figure 37 Closed Loop and Open Loop System Comparison ................................................. 79 Figure 38 Commanded Position............................................................................................... 80 Figure 39 Integrator Windup (Without Using SGILIM Command)........................................... 84 Figure 40 Integrator Windup (using the SGILIM Command)................................................... 85 Figure 41 Clockwise/ Counter-clockwise rotation .................................................................... 99 Figure 42 Time until current foldback occurs ......................................................................... 102 Figure 43 Linear motor track .................................................................................................. 103 Figure 44 Notch Filter Topology ............................................................................................. 120 Figure 45 Notch Filter Magnitudes ......................................................................................... 120 Figure 46 Notch Filter A ......................................................................................................... 121 Figure 47 Notch Lead Filter Break Frequency ....................................................................... 123 Figure 48 Clockwise/ Counter-clockwise rotation .................................................................. 154 Figure 49 Hall Connection Diagram ....................................................................................... 165 Figure 50 Motor Terminal Voltages (back EMF) and Hall Sensor Signals............................. 167 Figure 51 Time until current foldback occurs ......................................................................... 173 Figure 52 360° Bonding Techniques...................................................................................... 193

7

Parker Hannifin Figure 53 Typical LVD/EMC Installation, AR-02xx to AR-13xx.............................................. 197 Figure 54 Typical LVD/EMC Installation, AR-20xE & AR-30xE ............................................. 198 Figure 55 Panel Layout Dimensions for the Aries Drive ........................................................ 199 Figure 56 Servo Tuning Flow Diagram .................................................................................. 202 Figure 57 VM26 Breakout Module.......................................................................................... 204

8 Aries User Guide

Parker Hannifin

Product Type........................................... Aries Family AR-01Ax, 02Ax, 04Ax, 08Ax, 13Ax, 20AE, and 30AE ................................................................ Aries Family AR-01Sx, 02Sx, 04Sx, 08Sx, 13Sx, 20SE, and 30SE The above product complies with the requirements of directives: · · · EMC Directive 89/336/EEC Low Voltage Directive 73/23/EEC CE Marking Directive 93/68/EEC

Provided the installation requirements described in this guide are met, and there are no special requirements of the installation and operating environment so that the application may be considered typical. The above equipment conforms with the protection requirements of Council Directive 89/336/EEC as amended by Directive 92/31/EEC on the approximation of the laws of the Member States relating to Electromagnetic Compatibility when installed, operated and maintained as intended. Also: The above equipment conforms with the requirements of Council Directive 73/23/EEC (Low Voltage Directive) as amended by Directive 93/68/EEC (CE Marking Directive), when installed, operated, and maintained as intended. In accordance with IEC 61800-3:1997 (Adjustable speed electrical power drive systems) this product is of the restricted sales distribution class which meets the needs of an industrial environment when installed as directed. However, further measures may need to be taken for use of the product in a domestic environment. The installation requirements are detailed in the Information supplied with the equipment. The equipment is sold only to competent system builders. Compliance is demonstrated by the application of the following standards: · BS EN 61800-3 (1997) including Amendment A11 Adjustable speed electrical Power drive systems Part 3. EMC product standard including specific test methods. BS EN 50081-2 (1994) Electromagnetic compatibility--Generic emission standard Part 2. Industrial Environment. BS EN 61000-6-2 (1999) Electromagnetic compatibility Part 6-2: Generic Standards ­ Immunity for industrial environments. BS EN 61010-1 (1993) including Amendment A2. Safety requirements for electrical equipment for measurement, control, and laboratory use. Part 1 General Requirements.

· · ·

9

Parker Hannifin

Warning -- Risk of damage and/or personal injury The Aries drives described in this guide contain no user-serviceable parts. Attempting to open the case of any unit, or to replace any internal component, may result in damage to the unit and/or personal injury. This may also void the warranty.

Symbols

Description Protective Earth Ground Functional Earth (Ground) Terminal Shield, Frame, or Chassis Terminal Caution Risk of Electrical Shock Caution, Refer to Accompanying Documentation

10 Aries User Guide

Parker Hannifin

Important User Information

It is important that motion control equipment is installed and operated in such a way that all applicable safety requirements are met. It is your responsibility as an installer to ensure that you identify the relevant safety standards and comply with them; failure to do so may result in damage to equipment and personal injury. In particular, you should study the contents of this user guide carefully before installing or operating the equipment. The installation, set up, test, and maintenance procedures given in this User Guide should only be carried out by competent personnel trained in the installation of electronic equipment. Such personnel should be aware of the potential electrical and mechanical hazards associated with mains-powered motion control equipment--please see the safety warnings below. The individual or group having overall responsibility for this equipment must ensure that operators are adequately trained. Under no circumstances will the suppliers of the equipment be liable for any incidental, consequential or special damages of any kind whatsoever, including but not limited to lost profits arising from or in any way connected with the use of the equipment or this guide.

Warning -- High-performance motion control equipment is capable of producing rapid movement and very high forces. Unexpected motion may occur especially during the development of controller programs. KEEP WELL CLEAR of any machinery driven by stepper or servo motors. Never touch any part of the equipment while it is in operation.

This product is sold as a motion control component to be installed in a complete system using good engineering practice. Care must be taken to ensure that the product is installed and used in a safe manner according to local safety laws and regulations. In particular, the product must be positioned such that no part is accessible while power may be applied. This and other information from Parker Hannifin Corporation, its subsidiaries, and authorized distributors provides product or system options for further investigation by users having technical expertise. Before you select or use any product or system, it is important that you analyze all aspects of your application and review the information concerning the product in the current product catalog. The user, through its own analysis and testing, is solely responsible for making the final selection of the system and components and assuring that all performance, safety, and warning requirements of the application are met. If the equipment is used in any manner that does not conform to the instructions given in this user guide, then the protection provided by the equipment may be impaired.

The information in this user guide, including any apparatus, methods, techniques, and concepts described herein, are the proprietary property of Parker Hannifin or its licensors, and may not be copied disclosed, or used for any purpose not expressly authorized by the owner thereof. Since Parker Hannifin constantly strives to improve all of its products, we reserve the right to modify equipment and user guides without prior notice. No part of this user guide may be reproduced in any form without the prior consent of Parker Hannifin.

11

Parker Hannifin

Change Summary

Revision G Changes

This document, 88-021610-01G, supersedes 88-021610-1F. Changes associated with Aries User Guide revisions, and document clarifications and corrections are as follows: Topic Electrical Installation Description Added note to Motor Power Fuse Information table that 40A fuse is recommended regardless of single- or 3-phase input power. Added "Yellow & 5 Green (flashing)" for Encoder Loss to Internal Drive Faults table. Corrected connector p/n from ELFA13210E to OSTTJ075102 for Mains/Input Power Connector and Motor Connector. Removed reference to 120V motor power for single- or three-phase AR-20xE in AC Power Supply Connection. Added "--Encoder" to clarify title to section Motor Feedback Connector--Encoder. Corrected Motor Feedback Connector--Resolver schematic by removing pins 16 and 17. Corrected diode connection across motor cable in drawing in Motors without Full Wave Rectifiers. Command Reference Corrected "perception" to "misperception" in Servo Response Overview section, Stability topic. Added "Warning" to CONFIG errors E10, E11, and E12 because they are not faults. Changed start of range for DMPSCL to include 0, with info on using DRES command with 0 value. Changed range maximum to 400 rps for DMTW, DMVLIM, DMVSCL, and SMVER. Added E28 to ERROR command; corrected E34 link from TOTEMP to TDTEMP. Added DTHERM to list of commands stored with ESTORE. Alphabetized list. Added 3 and 4 to ranges, and additional information regarding OHALL 1 and OHALL 4 to OHALL command. Troubleshooting Added E28 to Error Messages table; corrected E34 link from TOTEMP to TDTEMP. Added "Yellow & 5 Green (flashing)" for Encoder Loss to Internal Drive Faults table.

12 Aries User Guide

Parker Hannifin

Revision F Changes

This document, 88-021610-01F, supersedes 88-021610-1E. Changes associated with Aries User Guide revisions, and document clarifications and corrections are as follows: Topic Command Reference Description Additions to ERES, SFB, and TREV commands for Aries Resolver option. Added TIDAC and TIQAC commands. Corrected DCMDZ syntax. Corrected ranges for DMTIC, DMTIP, DMTKE, DMTRES, and ERES. Aries Names LEDs--Drive Status Indicators Resolver option Error Messages Updated part number descriptions to include Resolver and Powerlink Options Updated to include Autorun mode. Added Motor Feedback Connector pinout, circuit diagram, and resolver excitation frequency. Added E50, E51, and E52 error messages

Revision E Changes

This document, 88-021610-01E, supersedes 88-021610-1D. Changes associated with Aries User Guide revisions, and document clarifications and corrections are as follows: Topic AC Power Supply Connection Drive I/O Connector-- Internal Circuit Diagram Drive I/O Connector Description Clarified jumpering two phases of the motor input power to the control input power allows for a single AC connection. Corrected circuit for Step+ and Step-. Step and Direction is not optically isolated, but is 5V differential compatible (RS-422 logic level compatible). Added appendix describing the VM26 Breakout Module.

VM26 Breakout Module

13

Parker Hannifin

Revision D Changes

This document, 88-021610-01D, supersedes 88-021610-1C. Changes associated with Aries User Guide revisions, and document clarifications and corrections are as follows: Topic Regulatory Compliance Output Power Part Number Description Aries is no longer cUL compliant. Corrected to 14.07A In Appendix C, Table 62 Enclosure Mounting Clamps, corrected part number to read R CLAMP KIT. Removed separate Still Air and Moving Air temperature maximums. Now provides only an Ambient Air temperature.

Environment and Drive Cooling

Revision C Changes

This document, 88-021610-01C, supersedes 88-021610-1B. Changes associated with Aries User Guide revisions, and document clarifications and corrections are as follows: Topic Models Regeneration Protection DC Inductance Link Command Reference Description Enhancement: Added models AR-13xx, AR-20xE, and AR-30xE, and relevant information. Enhancement: Added discussion and connections. Enhancement: Added discussion and connections. Enhancements: Added the following commands: ALIGN , DMTSWT, DRES, ENCOFF, ESTORT, IANI, OHALL, P163 Modified the following commands: DMTTCM--range DMTTCW--range DVMLIM--range and default DPWM--range and corrected mode information ERROR--now includes messages E47 and E48 SFB--In OS 2.10 or higher, SFB also functions to set feedback type TMTEMP--Added new reporting capabilities for OS 2.10 or higher Enhancement: Added error messages E47 and E48. See Chapter 7 Troubleshooting.

Error Messages

14 Aries User Guide

Parker Hannifin

Revision B Changes

This document, 88-021610-01B, supersedes 88-021610-1A. Changes associated with Aries User Guide revisions, and document clarifications and corrections are as follows: Topic Fault Operation

DRIVE I/O

Description Enhancement: Added a discussion about fault operations for the DRIVE I/O connector. Correction: Simplified the circuit diagram for the Enable input. Enhancement: Added specifications detailing electrical and timing characteristics on the DRIVE I/O connector. Enhancement: Added specifications detailing electrical and timing characteristics on the DRIVE I/O connector. Enhancement: Added specifications detailing electrical and timing characteristics on the DRIVE I/O connector. Enhancement: Added specifications detailing electrical and timing characteristics on the DRIVE I/O connector. Correction: Both RS-485 channels are Tx/Rx. Enhancements: Added Chapter 5 Tuning, describing servo tuning. Added Appendix D Servo Tuning Flow Diagram. Enhancements: Added the following commands: DMTD, DMTJ, DNOTAD, DNOTAF, DNOTAQ, DNOTBD, DNOTBF, DNOTBQ, DNOTLD, DNOTLG, SGVF. Modified CONFIG--now includes error messages E13-E18. Enhancement: Added error messages E13-E18. See Chapter 7 Troubleshooting.

connectorinternal circuit diagram Inputs--Enable and Reset

Outputs--Encoder

Inputs--Step & Direction Inputs--Analog

RS-485 Communication Tuning

Command Reference

Error Messages

15

Chapter 1 Introduction

CHAPTER ONE

Introduction

IN THIS CHAPTER

Aries Products--Overview......................................................................... 17 Compatible Parker Products...................................................................... 18 Checking Your Shipment ........................................................................... 19 Illustrations in this Installation Guide ......................................................... 20 Assumptions of Technical Experience....................................................... 20 Technical Support...................................................................................... 20

Parker Hannifin

Aries Products--Overview

The Aries drives are a family of super compact, super efficient digital servo drives. Their maximum continuous shaft power ranges from 100 Watts to 3000 Watts (3kW). Ready for direct panel mounting, you can select the precise power level needed for your application.

Aries Product Descriptions

Aries Servo Drives can control the torque, velocity, and position of servo motors using a digital current loop. Control of Aries Drives is performed using controllers, which have standard ±10V torque command, ±10V velocity command, or 5V TTL step & direction interface. For Aries drives using the analog or step and direction command interface, configure the drives through RS-232/485 using the Aries Support Tool on a personal computer (PC), or other standard communication software. For Aries drives using the Ethernet Powerlink command interface, configure the drives through Ethernet using the ACR-View software on a PC. Many advanced features are standard on the product including "plug and play" capabilities with Aries-compatible motors.

Aries Names

The following diagram explains the Aries part numbers: Drive Type............................................... Aries Maximum Shaft Power............................ 01 = 100W 02 = 200W 04 = 400W 08 = 750W 13 = 1300W 20 = 2000W 30 = 3000W Command Interface ................................ A = Analog S = Step & Direction P = Ethernet Powerlink Motor Feedback ...................................... E = Encoder R = Resolver AR ­ 01 A E

Input Power

Motor Power AR-01xx, AR-02xx AR-04xx, AR-08xx, AR-13xx................... 120/240 VAC single-phase mains motor power AR-20xE.................................................. 240 VAC single-phase or threephase mains motor power AR-30xE.................................................. 240 VAC three-phase mains motor power only Control Power AR-01xx through AR-30xE...................... 120/240 VAC single-phase mains control power

Chapter 1 Introduction 17

Parker Hannifin

Output Power Level

Servo Motor Drives

In Table 1, the maximum current is given at 120/240 VAC input, which equates to a motor bus voltage of 170/340 VDC. Drive Continuous Current (RMS) 1A 1.75A 3A 4.50A 6.3A 10A 16A Peak Current (RMS) 3A 5.25A 9A 13.5A 14.07A 30A 48A Continuous Shaft Output Power 100W, 0.13 hp* 200W, 0.27 hp* 400W, 0.53 hp* 750W, 1.0 hp* 1300W, 1.75 hp* 2000W, 2.7 hp** 3000W, 4.04 hp**

AR-01xx AR-02xx AR-04xx AR-08xx AR-13xx AR-20xE AR-30xE

* Maximum rating at 240 VAC, single-phase ** Maximum rating at 240 VAC, three-phase Table 1 Output Power Level

Options

For the latest additions, see our website at www.parkermotion.com.

Compatible Parker Products

Servo Controller (±10V torque or velocity mode)............... ACR series or other Parker controller Stepper Controller (S&D mode) .............. ACR series or other Parker controller Software .................................................. Aries Support Tool For information about cables, motors, etc., see "Chapter 2 Mechanical Installation".

18 Aries User Guide

Parker Hannifin

Checking Your Shipment

Inspect your shipment carefully. You should have received the corresponding ship kit along with your drive.

Ship Kit Items

The following items ship with the AR-01xx through AR-13xx drives: Part Aries Quick Reference Guide AR-01xx AR-02xx, AR-04xx, AR-08xx, & AR-13xx R-Clamp Screw (8-32 /8 inch) Aries compact disc containing the following: · Aries Hardware Installation Guide · Aries Support Tool

3

Part Number 88-021594-01C 52-019734-01 51-006055-01 88-021610-01 Part number N/A

Table 2 Ship Kit Items, AR-01xx through AR-13xx

The following items ship with the AR-20xE and AR-30xE drives: Part Aries Quick Reference Guide AR-20xE and AR-30xE R-Clamp Screw (8-32 /8 inch) Aries compact disc containing the following: · Aries Hardware Installation Guide · Aries Support Tool

3

Part Number 88-025222-01A 50-018127-01 51-006055-01 88-021610-01 Part number N/A

Table 3 Ship Kit Items, AR-20xE and AR-30xE

Motors

You may have ordered a motor from one of the following families of Parker motors: · · · · · · SE/SM Series BE Series NeoMetric Series J Series MaxPlus Rotary MaxPlus Linear · · · · · LXR Linear Series SL Linear Series ILM Linear Series SME Series SMN Series

Chapter 1 Introduction 19

Parker Hannifin

Illustrations in this Installation Guide

Typically, the illustrations in this guide show the Aries AR-01xx and the AR-30xE. These two models represent other models with similar features. AR-01xx represents models AR-01xx through AR13xE. Model AR-30xE represents the similar features of AR-20xE, as well. If there is a need to illustrate differences between drives, relevant drawings are shown for each drive.

Assumptions of Technical Experience

The Aries Drive is designed for industrial applications. To effectively install and troubleshoot the Aries Drive, you must have a fundamental understanding of the following: · · · · Motion control applications Electromechanical actuators Electrical concepts such as voltage, current, switches, etc. Serial Communication (RS-232 or RS-485) depending on which communications protocol you are using.

Technical Support

For solutions to your questions about implementing the Aries Drive, first refer to this manual. If you cannot find the answer in this documentation, contact your local Automation Technology Center (ATC) or distributor for assistance. If you need to talk to our in-house Application Engineers, please contact us at the telephone numbers listed on page 2.

20 Aries User Guide

Chapter 2 Mechanical Installation

CHAPTER TWO

Mechanical Installation

IN THIS CHAPTER

Environment & Drive Cooling..................................................................... 22 Dimensions ................................................................................................ 28 Weight........................................................................................................ 30 Mounting Guidelines .................................................................................. 31

Parker Hannifin

Environment & Drive Cooling

The Aries drive operates in an ambient temperature range of 0°C (32°F) to 45°C (113°F) ambient air temperature for all models except the AR-13xx. The AR-13xx operates in an ambient temperature range of 0°C (32°F) to 40°C (104°F) ambient air temperature. The drive can tolerate atmospheric pollution degree 2. Only dry, non-conductive pollution is acceptable. Therefore, it is recommended that the drive be mounted in a suitable enclosure. For drive cooling, you must install the drive so that the heatsink fins are vertical. Figure 8 on page 31 shows the mounting orientation, as well as the minimum top, bottom, and side installation clearances. The Aries AR-20xE and AR-30xE models (2 and 3 kWs) employ internal fans for additional cooling capacity. The AR-20xE has one fan and the AR-30xE has two. The fans are located at the bottom of the drives. They draw air in from the bottom, force it up over the heatsink, and out the vents in the top of the drive. Fan speed is temperature-dependent in order to minimize audible noise and extend fan operating life.

Notes

· · Avoid installing heat-producing equipment directly below a drive. Make sure the ambient air temperature entering the drive or rising up to the drive is within acceptable ambient temperature limits. Under normal use, the temperature of air leaving the drive and heatsink may be 25°C (45°F) above ambient temperature. After installation, verify that the ambient air temperature directly below the top-most drive does not exceed the maximum Ambient Air Operating Temperature shown below. In addition, make sure that nothing obstructs the circulating airflow.

·

22 Aries User Guide

Parker Hannifin

Environmental Specifications (AR-01xx, AR-02xx, AR-04xx, AR-08xx, AR-20xE, and AR-30xE) Operating Temperature, Maximum Storage Temperature Humidity Shock Vibration Pollution Degree Installation Category Ambient Air Minimum 45°C (113°F) 0°C (32°F)

­40°C to 85°C (­40°F to 185°F) 0 to 95%, non-condensing 15g, 11 ms half-sine 10 to 2000 Hz at 2g 2 (per IEC 61010) 2 (per IEC 61010)

Table 4 Environmental Specifications, AR-01xx through AR-08xx, AR-20xE and AR-30xE

Environmental Specifications (AR-13xx) Operating Temperature, Maximum Storage Temperature Humidity Shock Vibration Pollution Degree Installation Category Ambient Air Minimum 40°C (104°F) 0°C (32°F)

­40°C to 85°C (­40°F to 185°F) 0 to 95%, non-condensing 15g, 11 ms half-sine 10 to 2000 Hz at 2g 2 (per IEC 61010) 2 (per IEC 61010)

Table 5 Environmental Specifications, AR-13xx

Cabinet Cooling

For cabinet cooling calculations, use Table 6 and Table 7 to determine the power dissipation per drive.

AR-02xx

The power dissipation in Table 6 for the AR-02xx has been measured using the Parker BE231D motor.

Chapter 2 Mechanical Installation 23

Parker Hannifin

Figure 1 Cabinet Losses for AR-02xx when connected to a Parker BE231D motor

Shaft Power

Voltage 120 VAC 240 VAC

0W* 15W 32W

20W 25W 44W

200W 34W 47W

* Drive enabled, zero torque. Table 6 AR-02xx Power Dissipation

AR-08xx

The power dissipation in Table 7 for the AR-08xx has been measured using the Parker BE343J motor.

24 Aries User Guide

Parker Hannifin

Figure 2 Cabinet losses for AR-08xx when connected to a Parker BE343J motor

Shaft Power

Voltage 120 VAC 240 VAC

0W* 13W 24W

200W 42W 60W

700W 60W 73W

* Drive enabled, zero torque. Table 7 AR-08xx Power Dissipation

AR-13xx

The power dissipation in Table 8 for the AR-13xx has been measured using the Parker MPM1421CSJXXXN motor.

Chapter 2 Mechanical Installation 25

Parker Hannifin

Figure 3 Cabinet losses for AR-13xx when connected to a Parker MPM1421CSJ motor

Shaft Power

Voltage 120 VAC 240 VAC

0W* 14W 25W

700W 82W 95W

1300W 130W 146W

* Drive enabled, zero torque. Table 8 AR-13xx Power Dissipation

AR-30xE

The power dissipation in Table 9 for the AR-30xE has been measured using the Parker MPM1422CSJXXXN motor.

26 Aries User Guide

Parker Hannifin

Figure 4 Cabinet losses for AR-30xE when connected to a Parker MPM1422CSJ motor

Shaft Power

Voltage 240 VAC

0W* 35W

1500W 103W

3000W 172W

* Drive enabled, zero torque. Table 9 AR-30xE Power Dissipation

Cabinet Cooling Calculations

Use the motor's speed torque curve to determine the torque when the motor is at running speed for your application. If the torque is not known, use the "knee" (where the peak-torque curve intersects the continuous-torque curve) of the graphed motion--this assumes the worst-case scenario for continuous motion.

PLOSS =

PLOSS = PMOTOR = EMOTOR = EDRIVE =

PMOTOR (1 - EDRIVE) EMOTOR

power dissipated to cabinet (Watts) shaft power of the motor (Watts) efficiency of motor (Percent), approximately 0.85 efficiency of Aries drive (Percent), approximately 0.90

Chapter 2 Mechanical Installation 27

Parker Hannifin

Dimensions

There are three basic housing sizes for the Aries drives. However, the height of the heatsink fins varies with each model, except for the AR-20xE and AR-30xE whose dimensions are identical. This section contains the dimensions for all Aries models.

Drive Dimensions--AR-01xx & AR-02xx

Figure 5 Drive mounting for the AR-01xx & AR-02xx

Drive AR-01xx AR-02xx

Fin Height-- in (mm)

Outside Width (OW)--in (mm)

Overall Depth with Cables--in (mm)

0.01 (0.25) 0.375 (9.5)

2.29 (58.2) 2.65 (67.3)

7.60 (193.0) 7.60 (193.0)

Table 10 AR-01xx and AR-02xx Drive Dimensions

28 Aries User Guide

Parker Hannifin

Drive Dimensions--AR-04xx, AR-08xx, & AR-13xx

Figure 6 Drive mounting for the AR-04xx, AR-08xx, and AR-13xx

Drive AR-04xx AR-08xx AR-13xx

Fin Height-- in (mm)

Overall Width (OW)--in (mm)

Overall Depth with Cables--in (mm)

0.625 (15.9) 1.00 (25.4) 2.00 (50.8)

2.90 (73.7) 3.28 (83.3) 4.28 (108.7)

7.60 (193.0) 7.60 (193.0) 7.60 (193.0)

Table 11 AR-01xx , AR-02xx, & AR-13xx Drive Dimensions

Chapter 2 Mechanical Installation 29

Parker Hannifin

Drive Dimensions--AR-20xE & AR-30xE

Figure 7 Drive mounting for the AR-20xE and AR-30xE

Drive AR-20xE & AR-30xE

Fin Height-- in (mm)

Overall Width (OW)--in (mm)

Overall Depth with Cables--in (mm)

1.48 (37.5)

4.67 (118.5)

9.27 (235.5)

Table 12 AR-20xE and AR-30xE Drive Dimensions

Weight

Use Table 13 to determine the weight of your drive.

Drive Weight pounds (kg) Drive Weight pounds (kg)

AR-01xx AR-02xx AR-04xx AR-08xx

1.68 (0.76) 1.90 (0.86) 2.54 (1.15) 2.82 (1.28)

AR-13xx AR-20xE AR-30xE

3.60 (1.63) 7.35 (3.33) 7.40 (3.36)

Table 13 Drive Weight

30 Aries User Guide

Parker Hannifin

Mounting Guidelines

The Aries drive is a vented product. To prevent material spilling into the drive, mount it under an overhang or in a suitable enclosure. Aries products are made available under "Restricted Distribution" for use in the "Second Environment" as described in EN 61800-3 1996, page 9.

Cable Routing

Route high power cables (motor and mains) at right angles to low power cables (communications and inputs/outputs). Never route high and low power cables parallel to each other.

Panel Mounting

The mounting clearance requirements are the same for all models of the Aries Drive. They are shown in Figure 8.

Figure 8 Panel Layout Dimensions for Aries Drives

Chapter 2 Mechanical Installation 31

Chapter 3 Electrical Installation

CHAPTER THREE

Electrical Installation

IN THIS CHAPTER

Installation Safety Requirements............................................................... 33 System Installation Overview..................................................................... 34 Power Supply............................................................................................. 35 Multiple Drive Installations ......................................................................... 48 Brake Relay (Optional) .............................................................................. 50 Regeneration Protection ............................................................................ 54 LEDsDrive Status Indicators .................................................................. 56 Connector Descriptions ............................................................................. 57 Installation Test.......................................................................................... 72

Parker Hannifin

Installation Safety Requirements

Aries drives meet the requirements of both the European LVD (Low Voltage Directive) and EMC (Electromagnetic Compliance) directives when installed according to the instructions given within "Appendix C Regulatory Compliance­UL and CE". As a rule, it is recommended that you install the drive in an enclosure to protect it from atmospheric contaminants and to prevent operator access while power is applied. Metal equipment cabinets are ideally suited for housing the equipment because they provide operator protection, EMC screening, and can be fitted with interlocks arranged to remove all hazardous motor and drive power when the cabinet door is opened. Do not arrange the interlocks to open circuit the motor phase connections while the system is still powered as this could damage the drive.

Precautions

During installation, take the normal precautions against damage caused by electrostatic discharges. · · Wear earth wrist straps. Include a mains power switch or circuit breaker within easy reach of the machine operator. Label, clearly, the switch or breaker as the disconnecting device.

Auto-Configuration for Encoders

The Aries drive recognizes "smart encoders" attached to Parker motors. You can apply power to the drive, and the drive reads all necessary motor parameters from the motor. The drive and motor are then ready to use. If a drive is swapped out for any reason, you can insert a replacement--the replacement drive automatically reads the motor parameters. Several drive related parameters may need additional configuration: CMDDIR, DCMDZ, and ADDR.

Chapter 3 Electrical Installation 33

Parker Hannifin

System Installation Overview

The figures in this section illustrate the components necessary for electrical installation and configuration of the Aries drive. Figure 9 represents the installation of models AR-01xx through AR-13xx. Figure 11 shows the installation of models AR-20xE and AR-30xE, whose connectors differ from the other five models. The illustration shows the use of the Aries dongle (part number 71-02160901), which connects the Aries drive to both a controller and a personal computer (PC). The dongle is for setup purposes only. Do not use the dongle for permanent installation.

AR-01xx, AR-02xx, AR-04xx, AR-08xx, & AR-13xx Installation

Figure 9 Overview of System Installation for AR-01xx to AR-13xx

Warning -- This product has been developed for industrial environments. Due to exposed high voltage terminals, this product must not be accessible to users while under normal operation.

34 Aries User Guide

Parker Hannifin To operate the Aries drive with separate control and motor AC input, remove the factory installed external jumpers. With the jumpers installed, apply power to the motor power mains only. Figure 10 shows the location of the factory installed jumpers.

Figure 10 AR-01xx to AR-13xx Factory Installed Jumpers

Chapter 3 Electrical Installation 35

Parker Hannifin

AR-20xE and AR-30xE Installation

Figure 11 Overview of System Installation for AR-20xE & AR-30xE

Warning -- This product has been developed for industrial environments. Due to exposed high voltage terminals, this product must not be accessible to users while under normal operation.

36 Aries User Guide

Parker Hannifin To operate the Aries drive with separate control and motor AC input, remove the factory installed external jumpers. With the jumpers installed, apply power to the motor power mains only. Figure 12 shows the location of the factory installed jumpers.

Figure 12 AR-20xE to AR-30xE Factory Installed Jumpers

Connector Locations

All Aries drive models have identical DRIVE I/O and Motor Feedback connectors. However, the connectors for motor and control power, on the AR-20xE and AR-30xE differ from the other models due to their higher power capacity. The two power connectors on models AR-01xx through AR-13xx are removable. The two power connectors on Models AR-20xE and AR-30xE are non-removable. Descriptions of individual connectors and their specifications follow in this chapter. See "Connector Descriptions," and in "Appendix A Additional Specifications." Figure 13 shows the names and location of the connectors on Aries drive models AR-01xx through AR-13xx. Figure 14 shows them on the higherpower models AR-20xE and AR-30xE.

Chapter 3 Electrical Installation 37

Parker Hannifin

Figure 13 Connectors on Aries Models AR-01xx to AR-13xx

Figure 14 Connectors on Aries Models AR-20xE & AR-30xE

38 Aries User Guide

Parker Hannifin

Power Supply

Input Power

The mains motor power supply and control power supply for the Aries Drive must meet the following requirements. Model Motor Input Power AR-01xx, AR-02xx, AR-04xx, AR-08xx, AR-13xx (L1, L2) AR-20xE (L1, L2, L3) AR-30xE (L1, L2, L3) Control Input Power All models (C1, C2)

Figure 15 Input Power Requirements

Requirements

120/240 VAC, 50/60 Hz, single phase

240 VAC, 50/60 Hz, single phase or three phase 240 VAC, 50/60 Hz, three phase only

120/240 VAC, single phase

Mains/Input Power Connector

AR-01xx, AR-02xx,AR-04xx, AR-08xx, AR-13xx Connector Type....................................... Removable screw terminal Terminals ........................................7 Pitch ................... 0.200 in (5.08 mm) Wire Range ....................12-26 AWG .......................................14-27 SWG ................................(0.12-3.30 mm2) Wire Strip length .. 0.31 in (7.87 mm) Torque....7.0 in­lbs nom. (0.79 N-m)

AR-20xE, AR-30xE Connector Type....................................... Non-Removable screw terminal Terminals ......................................10 Pitch ........................ 0.315 in (8 mm) Wire Range ....................10-22 AWG .......................................12-23 SWG ....................................(0.5-4.0 mm2) Wire Strip length .... 0.25 in (6.5 mm) Torque....7.0 in­lbs nom. (0.79 N-m)

Chapter 3 Electrical Installation 39

Parker Hannifin

AC Power Supply Connection

Figure 16 on page 34 shows how to connect the external 120/240 VAC motor power source and control power sources to the drive. · The AR-20xE can accept single-phase or three-phase 240V motor power. For single-phase connections, make no connection to terminal labeled L3. The AR-30xE can only accept three-phase 240V motor power.

·

Use the terminal connector that is supplied with the drive. For the Protective Earth ground, make the connection directly by means of a low-impedance path less than or equal to 0.1 ohm (no fuses, etc.). Under normal operation, no current should flow through the Protective Earth connection. If desired, you can jumper two phases of the motor input power to the control input power for a single AC power connection. Jumpers are installed at the factory for this purpose. Remove the jumpers to apply separate control and motor mains power.

Figure 16 Motor and Control Mains Power Supply Connection

Note: See warnings on next page.

40 Aries User Guide

Parker Hannifin

Warning -- You must connect the drive's protective conductor terminal, marked with the earth symbol , to a reliable system Protective Earth.

Warning -- The drive's connector strip terminals have hazardous voltages when power is applied to the drive, and up to several minutes after power is removed. Lower voltages may still be present for several minutes after power is removed. During normal operation, these high voltage terminals must not be accessible to the user.

Motor Power Fuse Information

Aries drives have no user-serviceable internal fuses. For safety, you must provide a fuse in each of the AC Mains Motor power input lines. To determine the proper fuse type and size for your application, see Table 14. (For fuse recommendations for Control-power input lines, see "Control Power Supply" on page 46.) Drive AR-01xx AR-02xx AR-04xx AR-08xx AR-13xx AR-20xE* AR-30xE* AC Voltage 120 VAC 240 VAC 120 VAC 240 VAC 120 VAC 240 VAC 120 VAC 240 VAC 120 VAC 240 VAC 240 VAC 240 VAC Fuse Style 125 VAC Time Delay 250 VAC Time Delay 125 VAC Time Delay 250 VAC Time Delay 125 VAC Time Delay 250 VAC Time Delay 125 VAC Time Delay 250 VAC Time Delay 125 VAC Time Delay 250 VAC Time Delay 250 VAC Time Delay 250 VAC Time Delay Rating 10A 10A 10A 10A 20A 20A 20A 20A 30A 30A 40A 40A Fuse Type RK5 or better RK5 or better RK5 or better RK5 or better RK5 or better RK5 or better RK5 or better RK5 or better RK5 or better RK5 or better RK5 or better RK5 or better

* The 40A fuse is recommended regardless of whether the input power is

single-phase or 3-phase.

Table 14 Motor Power Fuse Information

Chapter 3 Electrical Installation 41

Parker Hannifin Table 15 lists part numbers (at time of publication) for suitable fuses from several manufacturers. These fuses are type RK5 (time delay fuses).

Ferraz Shawmut (formerly Gould)

Amps

Bussmann

Littelfuse

10 20 30 40

FRN-R-10 FRN-R-20 FRN-R-30 FRN-R-40

TR10R TR20R TR30R TR40R

FLNR10 FLNR20 FLNR30 FLNR40

Table 15 Fuse Part Numbers

Drive Inrush Current

The drive inrush current is limited by an internal thermistor that changes value with the ambient temperature. Drive inrush current is therefore dependent upon the temperature of the surrounding environment (Tamb). To determine the drive inrush current for your drive, see Table 16. Drive Type AR-01xx AR-02xx AR-04xx AR-08xx AR13xE AR-20xE AR-30xE

AC Voltage Drive Inrush (25°C Tamb) Drive Inrush (50°C Tamb)

120 VAC 240 VAC 120 VAC 240 VAC 120 VAC 240 VAC 120 VAC 240 VAC 120 VAC 240 VAC 240 VAC 240 VAC

34A 68A 34A 68A 17A 34A 17A 34A 17A 34A 68A 68A

73A 146A 73A 146A 36A 73A 36A 73A 36A 73A 155A 155A

Table 16 Drive Motor Power Inrush Current

42 Aries User Guide

Parker Hannifin

Output Power

Table 17 contains the continuous and peak output power ratings for all Aries drive models.

Continuous Output Drive Current (Amps, RMS) Shaft Power* (Watts, max) Peak Output Current (Amps, RMS) Shaft Power (Watts, max)

AR-01xx AR-02xx AR-04xx AR-08xx AR-13xx AR-20xE AR-30xE

1.0 1.75 3.0 4.5 6.3 10 16

100 200 400 750 1300 2000 3000

3.0 5.25 9.0 13.5 14.1 30 48

300 600 1200 2250 3900 6000 9000

* Maximum shaft power rating at 240 VAC Table 17 Output Power-Continuous and Peak

Motor Connector

AR-01xx, AR-02xx, AR-04xx, AR-08xx, AR-13xx Connector Type....................................... Removable screw terminal Terminals ........................................6 Pitch ................... 0.200 in (5.08 mm) Wire range .....................12-26 AWG .......................................14-27 SWG ................................(0.12-3.30 mm2) Wire strip length ...... 0.310 in (8 mm) Torque....7.0 in­lbs nom. (0.79 N-m)

AR-20xE, AR-30xE Connector Type....................................... Non-Removable screw terminal Terminals ......................................10 Pitch ........................ 0.315 in (8 mm) Wire range .....................10-22 AWG .......................................12-23 SWG ....................................(0.5-4.0 mm2) Wire strip length ..... 0.25 in (6.5 mm) Torque....7.0 in­lbs nom. (0.79 N-m)

Chapter 3 Electrical Installation 43

Parker Hannifin

Output Power Connection

Figure 17 shows how to connect the motor cable to the drive. Use the screw terminal connector that is installed in the drive. Current Parker motor cables are marked with white numbers to indicate the phases. Connect Motor Phase 1 U, 2 V, and 3 W, and Motor Safety Earth to the Protective Earth ground connector.

Figure 17 Output Power Connection

Table 18 contains information for making connections with Parker Hannifin motors.

Phase Hi-Flex/ PS/ Gemini Legacy Parker Hannifin Legacy MaxPlus

U V W

1 2 3 Green/Yellow

Red/Yellow White/Yellow Black/Yellow Green/Yellow

Red Black Blue Green

Table 18 Wiring to Motors

Note: On models AR-20xE and AR-30xE, the Motor Brake Relay is on a separate connector. See Figure 22 on page 50. Warning -- You must connect the Motor Safety Earth conductor terminal, marked with the earth symbol , to the motor cable's motor-safety-earth wire (green/yellow).

Note: See additional warning on next page.

44 Aries User Guide

Parker Hannifin

Warning -- The drive's connector strip terminals have hazardous voltages when power is applied to the drive, and up to several minutes after power is removed. Lower voltages may still be present for several minutes after power is removed. During normal operation, these high voltage terminals must not be accessible to the user.

External DC Link Inductor (Optional)

The Aries AR-20xE and AR-30xE drives have two extra terminals that allow an external DC link inductor to be added if required. To add the DC link inductor, remove the factory installed shorting link, and connect the inductor as shown in Figure 18.

Figure 18 External DC Link Inductor Connection

If a drive is supplied from a low-impedance source (for example, a transformer that has a kVA rating more than 10 times the drive), the input line currents to the drive can be non-sinusoidal. They may have a peak that is two to three times the rms value, compared to 1.4 times for a sinusoidal waveform. This results in higher currents being drawn from the line at rated power and harmonics that might interfere with other equipment. The addition of a DC link inductor reduces the severity of these problems. Table 19 provides compatible DC link inductors for the Aries AR-20xE and AR-30xE. Drive Type AR-20xE AR-30xE Recommended Inductance 1.0 to 3.0 mH 0.75 to 2.0 mH DC Current Rating 10A 15A

Note: Where within the recommended range, the larger inductance gives a better shape to the input current waveform, but at the expense of larger physical size. Table 19 AR-20xE & AR-30xE DC Link Inductors

Chapter 3 Electrical Installation 45

Parker Hannifin

Control Power Supply

With Mains power applied to the Control power terminals C1 and C2, the drive's internal control board remains powered when the primary motor AC power source (L1, L2 (L3)) is disconnected. When operated in this configuration, the Control power input performs a "keep-alive" function. The keep-alive circuit maintains several important functions, including communications, diagnostics, position feedback, and other logic functions, while removing power from the motor output connection. (See the following section, Fuse Information, for a complete list of Control power functions.) Remove the factory installed jumpers to use the product with separate control and motor mains AC power input.

Fuse Information

Fuse Rating............................................. 1 Amp Fuse Type ............................................... Class CC (Bussmann KTK-R-1 or equivalent UL listed fuse) Input Voltage Range ............................... 120/240 VAC, 50/60 Hz Input Current ........................................... 0.2 Amps RMS Control Power Functions......................... Communications Diagnostics Motor position feedback Fault output in fault mode Brake relay in brake mode Reset input

Control Power Connector

AR-01xx, AR-02xx, AR-04xx, AR-08xx, AR-13xx Connector Type....................................... Removable screw terminal Terminals ........................................7 Pitch ................... 0.200 in (5.08 mm) Wire Range ....................12-26 AWG .......................................14-27 SWG ................................(0.12-3.30 mm2) Wire Strip length .. 0.31 in (7.87 mm) Torque....7.0 in­lbs nom. (0.79 N-m)

46 Aries User Guide

Parker Hannifin

AR-20xE, AR-30xE Connector Type....................................... Non-Removable screw terminal Terminals ........................................8 Pitch ...................... 0.400 in (10 mm) Wire Range ....................12-28 AWG .......................................14-29 SWG ................................(0.12-3.30 mm2) Wire Strip length 0.250 in (6.35 mm)

Control Power Connection

Figure 19 shows how to connect the Control power source to the drive. Use the screw terminal connector that is supplied with the drive.

Figure 19 Mains Control Input Power

Warning -- You must connect the drive's protective conductor terminal, marked with the earth symbol , to a reliable system Protective Earth.

Warning -- The drive's connector strip terminals have hazardous voltages when power is applied to the drive, and up to several minutes after power is removed. Lower voltages may still be present for several minutes after power is removed. During normal operation, these high voltage terminals must not be accessible to the user.

Chapter 3 Electrical Installation 47

Parker Hannifin

Multiple Drive Installations

In a typical cabinet installation, a single mains line connects to a terminal bus inside the cabinet. Then from the terminal bus, make individual connections for Mains and Control power to the corresponding connector(s) on each drive. Be sure to install fuses for each drive between the terminal bus and the drive. conductor terminal directly to the system Tie each drive's Protective Earth safety earth location as shown in Figure 20 (for models AR-01xx through AR13xx) or Figure 21 (for models AR-20xE and AR-30xE). Under normal operation, no current should flow through the Protective Earth ground.

Safety Earth Connections

AR-01xx, AR-02xx, AR-04xx, AR-08xx, and AR-13xx For multiple drive installations, Parker Hannifin recommends a single point or "star" safety earth configuration. Figure 20 represents a typical star safety earth connection for Aries models AR-01xx through AR-13xx.

Figure 20 Multiple Drives AR-01xx to AR-13xx: Single Point Safety Earth

AR-20xE and AR-30xE Figure 21 represents a typical star safety earth connection for Aries models AR-20xE and AR-30xE. Note that the AR-20xE and AR-30xE Motor/Power connector has two Earth ground terminalsone for the motor and one for terminal. input power. Be sure to use the VAC INPUT POWER

48 Aries User Guide

Parker Hannifin

Figure 21 Multiple Drives AR-20xE & AR-30xE: Single Point Safety Earth

Chapter 3 Electrical Installation 49

Parker Hannifin

Brake Relay (Optional)

[The Brake Relay connection provides a safety feature for your motion control system, particularly for vertical applications. The drive acts as a control switch for the motor brake (if a brake is present). When 24V is applied from an outside power supply through the drive's BK terminals, the motor brake is disabled. When the power supply is interrupted, or the drive faults or is disabled, the brake is enabled and stops shaft rotation. Connector and wiring information follow in this section.

Brake Relay Connector

AR-01xx, AR-02xx, AR-04xx, AR-08xx, AR-13xx Connector Type....................................... Removable screw terminal Terminals ........................................6 Pitch ................... 0.200 in (5.08 mm) Wire range .....................12-26 AWG .......................................14-27 SWG ................................(0.12-3.30 mm2) Wire strip length ...... 0.310 in (8 mm) Torque....7.0 in­lbs nom. (0.79 N-m) AR-20xE, AR-30xE Connector Type....................................... Non-Removable screw terminal Terminals ........................................8 Pitch ...................... 0.400 in (10 mm) Wire Range ....................12-28 AWG .......................................14-29 SWG ................................(0.12-3.30 mm2) Wire Strip length 0.250 in (6.35 mm)

Brake Relay Connection

On all models, this set of terminals is optically isolated from the drive's internal logic.

Figure 22 Typical Brake Relay Connection

Important warnings:

50 Aries User Guide

Parker Hannifin

Warning -- You must connect the drive's protective conductor terminal, marked with the earth symbol , to a reliable system Protective Earth.

Warning -- The drive's connector strip terminals have hazardous voltages when power is applied to the drive, and up to several minutes after power is removed. Lower voltages may still be present for several minutes after power is removed. During normal operation, these high voltage terminals must not be accessible to the user.

Motor with Full Wave Rectifiers

Some Parker brake motors (BE, SM, SE, NeoMetric, and J series motors, serial numbers greater than 010904xxxxx) contain full wave rectifiers, so connection polarity is not an issue during installation.

Connecting the Brake Relay

1. Connect one red/blue brake wire (Parker Motor cable or equivalent) to the BK terminal of the Motor connector on Aries models AR-01xx to AR-13xx, or the Control connector on models AR-20xE and AR-30xE. 2. Connect the second red/blue brake wire (Parker Motor cable or equivalent) to the 24V return on your power supply. 3. Connect the +24 VDC power supply to the second BK terminal of the Motor connector on Aries models AR-01xx to AR-13xx, or the Control connector on models AR-20xE and AR-30xE. The following shows a typical application--connecting a motor brake to the relay terminals.

Figure 23 Brake Relay Connection for Parker Motors

Chapter 3 Electrical Installation 51

Parker Hannifin

Motors without Full Wave Rectifiers

When using Parker MaxPlus motors, Parker motors with serial numbers less than 010904xxxxx, or non-Parker motors, you must install a fly-back diode. Consult the specifications or the manufacturer of your motor.

Connecting the Brake Relay

1. Connect one red/blue brake wire (Parker Motor cable or equivalent) to the BK terminal of the Motor connector (Aries drive). 2. Connect the second red/blue brake wire (Parker Motor cable or equivalent) to the 24V return on your power supply. 3. Between the two red/blue wires, connect the fly-back diode. See Figure 24. 4. Connect the +24 VDC power supply to the second BK terminal of the Motor connector (Aries drive). Figure 24 shows a typical installation.

Figure 24 Brake Relay Connection for Non-Parker Motors

52 Aries User Guide

Parker Hannifin

Relay Operation

Drive Condition Enabled Faulted No AC power on L1 and L2*, or drive not enabled Relay State Closed (conducting) Open Open

* Mains Control power on C1 and C2 does not affect the relay. With mains power applied to C1 and C2, the relay remains open if AC power is not applied to the L1 and L2 terminals. Table 20 Brake Relay Operation

Relay Specifications

Relay Type .............................................. Solid State Relay Normally open Relay Maximum Rating........................... 1 Amp at 24 VDC Warning -- Do not exceed the ratings of the brake relay. If required, control a suitable external relay with this relay to meet your power requirements.

Chapter 3 Electrical Installation 53

Parker Hannifin

Regeneration Protection

The Aries drive models AR-20xE and AR-30xE have internal regeneration power dump (dissipation) resistors. Models AR-01xx through AR-13xx do not. However, all models can utilize an external regeneration resistor.

Regeneration Connection

To use a external regeneration (power dump) resistor, connect your external resistor to the R+ and R- terminals as follows: · · For models AR-01x to AR-13xx, use the Mains connector. For models AR-20xE and AR-30xE, use the Control connector.

Figure 25 illustrates the external regeneration resistor connections.

Figure 25 External Regeneration Connection

Important! For models AR-20xE and AR-30xE, you must remove the factory-installed link between RINT and R- when you connect the external regeneration resistor. (Otherwise the internal regeneration resistor will still be in the circuit, and its thermal protection circuit limits the performance). For information on selecting a suitable external regeneration (power dump) resistor, see "Appendix B External Power-Dump Resistor Selection." Warning -- The drive's connector strip terminals are at hazardous voltages when power is applied to the drive, and up to several minutes after power is removed. Lower voltages may still be present for several minutes after power is removed. During normal operation, these high voltage terminals must not be accessible to the user.

54 Aries User Guide

Parker Hannifin

Internal Regeneration Capability

The internal regeneration resistor of the AR-20xE and AR-30xE is capable of dissipating 1kW for 1 second and up to 100 Watts continuously (depending upon heatsink temperature). If the calculated temperature of the internal regeneration resistor exceeds 150°C (302°F), the drive turns off the regeneration circuit and may experience an over-voltage fault. Similarly, models AR-01xx through AR-13xx may experience an over-voltage fault if the regeneration exceeds the absorbent capacity of the drive's internal bus capacitors, as shown in Table 21.

Regeneration Absorption

The available absorption varies based on mains voltage and the drive's internal capacitance. The drives can absorb the following amounts of regenerated energy in their internal capacitors:

Drive Absorb (Joules) 120 VAC Absorb (Joules) 240 VAC

AR-01xx AR-02xx AR-04xx AR-08xx AR-13xx AR-20xE AR-30xE

28 43 57 72 104 N/A N/A

9 14 19 24 35 50 50

Table 21 Regeneration Absorption

For more specifications about energy absorption by the Aries drive's capacitors, see Table 58. For more information about selecting an external power-dump resistor, see "Appendix B External Power-Dump Resistor Selection".

Chapter 3 Electrical Installation 55

Parker Hannifin

LEDsDrive Status Indicators

The drive has two bi-color LEDs. The LED on the left displays yellow or green colors; The LED on the right displays red or green colors. The following tables describe LED illumination states and the conditions they indicate.

Normal Operation

LED­Left Off Yellow Off Yellow Off Yellow (flashing) LED­Right Green Green Red Off Red (flashing) Red (flashing) What it means Power on, enabled Power on, regeneration active Power on, disabled­No Fault Power on, boot process Waiting for OS download OS download in process

Table 22 LED Status Indicator-Normal Operation

Internal Drive Faults

LED­Left Yellows Yellow & 1 Green (flashing) Yellow & 2 Green (flashing) Yellow & 3 Green (flashing) Yellow & 4 Green (flashing) Yellow & 5 Green (flashing) LED­Right Red Red Red Red Red Red What it means Control power mode active Bridge Fault Feedback Fault Thermal Fault Other Fault Encoder Loss

Table 23 LED Status Indicator-Internal Drive Fault

56 Aries User Guide

Parker Hannifin

Connector Descriptions

Motor Mains Power Connector

The drive's Mains screw terminal connector provides a connection for AC Mains power to your drive. (For connection information, see "Input Power" on page 39.) The connector differs between the two largest Aries models and the others. Specifications for the connectors follow in this section. On models AR-01xx through AR-13xx, the Mains connector also serves as a connector for Control power (C1 and C2) and a power dissipation resistor (R+ and R­). For more information on these additional connections, see "Control Power Supply" on page 46 "Regeneration Protection" on page 54.) This connector is removable. On models AR-20xE and AR-30xE, the Motor/Power connector serves as the connector for Motor Mains power (L1, L2, L3, and ), as well as for output power to the motor (U, V, W, and ) and a DC Link Inductor. For more information on these additional connections, see "Output Power" on page 43 and "External DC Link Inductor (Optional)" on page 45. This connector is not removable.

Figure 26 Mains/Input Power Connector

Chapter 3 Electrical Installation 57

Parker Hannifin

Mains/Input Power Connector

AR-01xx, AR-02xx, AR-04xx, AR-08xx, AR-13xx................. Amphenol PCD: OSTTJ075102 Parker Hannifin Part Number.................. 43-021069-01 Connector Type....................................... Removable screw terminal Terminals ........................................7 Pitch ................... 0.200 in (5.08 mm) Wire Range ....................12-26 AWG .......................................14-27 SWG ................................(0.12-3.30 mm2) Wire Strip length .. 0.31 in (7.87 mm) Torque....7.0 in­lbs nom. (0.79 N-m) AR-20xE, AR-30xE ................................ Molex: 39960-0110 Parker Hannifin Part Number.................. N/A Connector Type....................................... Non-Removable screw terminal Terminals ......................................10 Pitch ........................ 0.315 in (8 mm) Wire Range ....................10-22 AWG .......................................12-23 SWG ....................................(0.5-4.0 mm2) Wire Strip length .... 0.25 in (6.5 mm) Torque....7.0 in­lbs nom. (0.79 N-m)

58 Aries User Guide

Parker Hannifin

Output Power Connector

The drive's Motor screw terminal connector provides output power to your motor. (For connection information, see "Output Power" on page 43.) The connector differs between the two largest Aries models and the others. Specifications for the connectors follow in this section. On models AR-01xx through AR-13xx, the Motor connector also serves to connect an external motor brake to the drive's internal solid-state relay (BK). For information on this connection, see "Brake Relay (Optional)" on page 50. This connector is removable. On models AR-20xE and AR-30xE, the MOTOR/POWER connector serves as the connector for output power to the motor, as well as for Mains power (VAC Input Power) and a DC Link Inductor. For information on these additional connections, see "Input Power" on page 39 and "External DC Link Inductor (Optional)" on page 45. This connector is not removable.

Figure 27 Output (MOTOR) Power Connector

Chapter 3 Electrical Installation 59

Parker Hannifin

Motor Connector

AR-01xx, AR-02xx, AR-04xx, AR-08xx, AR-13xx ................................. Amphenol PCD: OSTTJ075102 Parker Hannifin Part Number.................. 43-021068-01 Connector Type....................................... Removable screw terminal Terminals ........................................6 Pitch ................... 0.200 in (5.08 mm) Wire range .....................12-26 AWG .......................................14-27 SWG ................................(0.12-3.30 mm2) Wire strip length ...... 0.310 in (8 mm) Torque....7.0 in­lbs nom. (0.79 N-m) AR-20xE, AR-30xE ................................ Molex: 39960-0110 Parker Hannifin Part Number.................. N/A (not replaceable) Connector Type....................................... Non-Removable screw terminal Terminals ......................................10 Pitch ........................ 0.315 in (8 mm) Wire range .....................10-22 AWG .......................................12-23 SWG ....................................(0.5-4.0 mm2) Wire strip length ..... 0.25 in (6.5 mm) Torque....7.0 in­lbs nom. (0.79 N-m)

60 Aries User Guide

Parker Hannifin

AR-20xE & AR30xE Control Connector

On the AR-20xE & AR 30xE models, the Control connector serves for three connections: an external power dump resistor (EXTERNAL REGEN), a control power circuit (CONTROL INPUT POWER), and a safety brake relay (BRAKE RELAY). The connector is an eight-position non-removable screw terminal. Specifications for the connector follow in this section. The Control connector has a factory-installed link between RINT and R- for an internal regeneration resistor, which provides thermal protection. For more information, see "Regeneration Protection" on page 54. For information on additional connections, see "Control Power Supply" on page 46 and "Brake Relay (Optional)" on page 50.

Figure 28 AR-20xE & AR30xE Control Connector

AR-20xE, AR-30xE ................................ PCD: ELM021100 Parker Hannifin Part Number.................. N/A (not replaceable) Connector Type....................................... Non-Removable screw terminal Terminals ........................................8 Pitch ...................... 0.400 in (10 mm) Wire Range ....................12-28 AWG .......................................14-29 SWG ................................(0.12-3.30 mm2) Wire Strip length 0.250 in (6.35 mm)

Chapter 3 Electrical Installation 61

Parker Hannifin

Motor Feedback Connector--Encoder

Inputs for the resolver feedback, motor thermal switch, and hall effects are located on the 15-pin Motor Feedback connector.

Figure 29 MOTOR FEEDBACK connector, female drive connector pinout

Important -- Encoder inputs use a DS26LV32 differential line receiver. Parker Hannifin recommends 26LS31 (or compatible) differential line driven encoders. Single ended encoders are not compatible.

Figure 30 MOTOR FEEDBACK connector, internal circuit diagram

62 Aries User Guide

Parker Hannifin

Pinout--MOTOR FEEDBACK Connector

Note: A box surrounding pins indicates a requirement for twisted pair wiring. Signal ENC Z+ / Data+ ENC Z­ / Data­ DGND +5 VDC +5 VDC DGND ENC A­ / SIN­ ENC A+ / SIN+ Hall 1 / SCLK+ * Thermal+ Thermal­ ENC B / COS­ ENC B+ / COS+ Hall 2 / SCLK­ * Hall 3

* Pin

Description Encoder Z Channel in Encoder Z Channel in Encoder power return +5 VDC Encoder power +5 VDC Hall power Hall power return Encoder A Channel in Encoder A Channel in Hall 1 input Motor thermal switch/thermistor Motor thermal switch/thermistor Encoder B Channel in Encoder B Channel in Hall 2 input Hall 3 input

1 2 3 4 5 6 7 8 9 10 15 11 12 13 14

When using the SinCos protocol, pins 9 and 13 require twisted pair wiring.

Table 24 MOTOR FEEDBACK Connector Pinout

Inputs--Encoder

Description Common Mode Range Current--Encoder Current--Hall Differential Threshold Voltage Differential Termination Impedance Thermal Switch Current Thermal Switch Voltage Maximum (supplied) Input Frequency (pre-quadrature)

Note: All parameters are at the connector pin. Table 25 Inputs--Encoder Inputs Electrical/Timing Characteristics

Min -7

Typical

Max +7 250 250

Units V mA mA mV ohms

-200 120

+200

2 15 5

mA V MHz

Chapter 3 Electrical Installation 63

Parker Hannifin

Connector Specification--Aries Drive

Manufacturer ........................................... KYCON or equivalent Connector Type....................................... 15-Pin High Density D-Subminiature (female socket) KYCON Part Number.............................. K66-E15S-NR

Connector Specification--Mating Connector

Mating connectors are not provided with Aries drives. Parker cables are available with mating connectors attached. Manufacturer ........................................... AMP or equivalent Connector Type....................................... 15-Pin High Density D-Subminiature (male connector) Cable Kit.................................................. AMP Part Number 748473-1 Includes: 748364-1 connector, shield, enclosure, and two jack screws (does not include contacts or ferrules) Contacts .................................................. Crimp style 30µ" Gold--AMP Part Number 748333-4 Gold Flash--Amp Part Number 748333-7

64 Aries User Guide

Parker Hannifin

Motor Feedback Connector--Resolver

Inputs for the encoder feedback, motor thermal switch, and hall effects are located on the 15-pin Motor Feedback connector.

Figure 31 MOTOR FEEDBACK connector, female drive connector pinout

Figure 32 MOTOR FEEDBACK connector for resolver option, internal circuit diagram

Chapter 3 Electrical Installation 65

Parker Hannifin

Pinout--MOTOR FEEDBACK Connector for Resolver Option

Note: A box surrounding pins indicates a requirement for twisted pair wiring. Signal No connection No connection ThermalReference+ ReferenceNo connection ThermalThermal+ SIN­ SIN+ No connection COS­ COS+ No connection No connection Pin 1 2 3 4 15 5 6 10 7 8 9 11 12 13 14 Description -- -- Motor thermal switch/thermistor Resolver excitation signal Resolver excitation signal -- Motor thermal switch/thermistor Motor thermal switch/thermistor SIN resolver feedback signal SIN resolver feedback signal -- COS resolver feedback signal COS resolver feedback signal -- --

Table 26 MOTOR FEEDBACK Connector Pinout for Resolver Option

Resolver Excitation

Description Excitation Frequency Min -- Typical 10 Max -- Units KHz

Note: All parameters are at the connector pin. Table 27 Resolver excitation

Drive I/O Connector

The inputs and outputs (I/O) located on the 26-pin DRIVE I/O connector are described below. For preparing your own cable, use differential pair wiring with a minimum of three turns-per-inch (3 TPI).

Optical Isolation

The following describes which differential I/O signals are optically isolated: · · Enable input is optically isolated with both Anodes (+) and Cathodes (­) available. Reset input is optically isolated with both Anodes (+) and Cathodes (­) available.

66 Aries User Guide

Parker Hannifin ·

Fault output is optically isolated with both Collector (+) and Emitter (­) available.

No Optical Isolation

The following describes which I/O signals are not optically isolated: · · · · Step and Direction inputs are 5V differential compatible (RS-422 logic level compatible. Encoder output signals are non-isolated RS-422 compatible differential drivers referenced to DGND. RS-485 is non-isolated RS-485 compatible differential signals referenced to DGND. AIN+ Analog input is single-ended non-isolated referenced to AIN­, and common mode referenced to DGND.

Fault Operation

When the Aries Drive is enabled and there are no fault conditions, the Fault circuit is closed (conducting). However, the following circumstances can trip the Fault circuit: a fault condition is present (see "Error Messages" on page 160); the Enable circuit is open (see Figure 34); or, Mains power is removed from the drive. You can use the LED status indicators to help identify internal drive faults. For more information, see Table 23. Drive Condition Enabled Faulted No AC power on L1 and L2*, or drive not enabled Fault Output Closed (conducting) Open Open

* Mains Control power on C1 and C2 does not affect the fault circuitry. With mains power applied to C1 and C2, the fault circuit remains open if AC power is not applied to the L1 and L2 terminals. Table 28 Fault Output Operation

Figure 33 DRIVE I/O connector, female drive connector pinout

Chapter 3 Electrical Installation 67

Parker Hannifin

Figure 34 DRIVE I/O connector, internal circuit diagram

68 Aries User Guide

Parker Hannifin

Pinout--DRIVE I/O Connector

Note: A box surrounding pins indicates a requirement for twisted pair wiring. Signal ENABLE+ ENABLE­ DGND ENC A+ ENC A­ ENC B+ ENC B­ ENC Z+ ENC Z­ FAULT+ * FAULT­ STEP+ 1 21 2 3 4 5 6 7 8 9 16 10

Pin

Description Drive Enable input anode Drive Enable input cathode Digital ground Encoder A Channel out Encoder A Channel out Encoder B Channel out Encoder B Channel out Encoder Z Channel out (Index +) Encoder Z Channel out (Index ­ ) Fault Output collector Fault Output emitter 5V Differential compatible (RS-422 logic level compatible) position command Position command return 5V Differential compatible (RS-422 logic level compatible) direction command Direction command return Analog ±10V current command ±10V return Digital Ground Drive Reset input anode Drive Reset input cathode Digital Ground Digital Ground Digital Ground Digital Ground RS-232Rx/ RS-485+ Half-Duplex RS-232Tx/ RS-485­ Half-Duplex

STEP­ DIRECTION+

11 12

DIRECTION­ AIN+ AIN­ DGND RESET+ RESET­ DGND DGND DGND DGND RS-232Rx/ RS-485+ RS-232Tx/ RS-485­

13 14 15 17 18 23 19 20 22 24 25 26

* Opto is ON and conducting when no fault condition is present. When a fault occurs, the opto turns OFF and the transistor does not conduct current. This simulates a normally open relay. For more information, see Table 20. Table 29 DRIVE I/O Connector Pinout

Chapter 3 Electrical Installation 69

Parker Hannifin

Inputs--Enable, Reset

The drive Enable and Reset inputs are optically isolated inputs. Current is limited internally for input voltage control of 5 to 24 volt logic. The Anode (+) and Cathode (-) are on separate connector pins to allow significant flexibility in wiring to different styles of interface. Description Turn-on time Turn-off time Guaranteed on voltage Guaranteed off voltage Maximum forward voltage Maximum reverse voltage Forward current

Note: All parameters are at the connector pin. Table 30 Inputs--Enable and Reset Electrical/Timing Characteristics

Min ­ ­ 4 ­ ­ -30 3

Max 1 1 ­ 2 30 ­ 12

Units ms ms VDC VDC VDC VDC mA

Outputs--Encoder

Description Output Frequency (pre-quadrature) Input Voltage High * Input Voltage Low *

* Based on 120 differential load impedance. Note: All parameters are at the connector pin. Note: Aries encoder is a hardware pass-through; therefore, you cannot change output resolution. Table 31 Outputs--Encoder Outputs Electrical/Timing Characteristics

Min

Typical

Max 5

Units MHz V

2.4 0.5

V

Outputs--Fault

Description Blocking Voltage Continuous Load Current Output Saturation Voltage (at 1.0 mA)

* Based on 120 differential load impedance. Note: All parameters are at the connector pin. Table 32 Outputs-- Fault outputs Electrical/Timing Characteristics

Min

Typical

Max 30 10 1.0

Units V mA V

70 Aries User Guide

Parker Hannifin

Inputs--Step & Direction

Description Common Mode Range Differential Threshold Voltage Differential Termination Impedance Input Frequency (pre-quadrature)

Note: All parameters are at the connector pin. Table 33 Inputs--Step & Direction Electrical/Timing Characteristics

Min -7 -200

Typical

Max +7 +200

Units V mV ohms

120 5

MHz

Inputs--Analog

Description Function Input Range Resolution Impedance

Note: All parameters are at the connector pin. Table 34 Inputs--Analog Electrical/Timing Characteristics

Min -10

Typical 14

Max +10 >20

Units V bits K ohms

Connector Specification--Aries Drive

Manufacturer ........................................... KYCON or equivalent Connector Type....................................... 26-Pin High Density D-Subminiature (female socket) KYCON Part Number.............................. K66-A26S-NR

Connector Specification--Mating Connector

Mating connectors are not provided with Aries drives. Parker cables are available with mating connectors attached. Manufacturer ........................................... AMP or equivalent Connector Type....................................... 26-Pin High Density D-Subminiature (male connector) Cable Kit.................................................. AMP Part Number 748474-1 Includes: 748365-1 connector, shield, enclosure, and two jack screws (does not include contacts or ferrules) Contacts .................................................. Crimp style 30µ" Gold--AMP Part Number 748333-4 Gold Flash--Amp Part Number 748333-7

Chapter 3 Electrical Installation 71

Parker Hannifin

Installation Test

Once you have made the necessary mechanical and electrical connections, you can test the drive. The Aries Support Tool contains the Auto Run Test Wizard, which exercises basic functions of the Aries drive. You must do the following before testing the drive: · · · · Configure the drive for the motor to which it is connected. Resolve any configuration errors before proceeding with the test. Enable the drive. If the Aries drive is connected to a controller, disable the controller's servo loop. If the motor is connected to a load, disconnect the motor so that it is free to turn unimpeded.

Safety Warning -- High-performance motion control equipment is capable of producing rapid movement and very high forces. Unexpected motion may occur especially during the development of controller programs. KEEP WELL CLEAR of any machinery driven by stepper or servo motors. Never touch any part of the equipment while it is in operation.

Testing the Aries Drive

If the Aries drive has been installed correctly, the motor will spin at one revolution per second. If the motor does not spin, a wiring or configuration error possibly exists. 1. Start the Aries Support Tool. 2. Under Menu, click Operating System Update. 3. Click Auto Run Test Wizard.

72 Aries User Guide

Chapter 4 Communications

CHAPTER FOUR

Communications

IN THIS CHAPTER

Terminal Emulator Configuration............................................................... 74 Establishing Communications ................................................................... 74 RS-232 Communications........................................................................... 75 RS-485 Communications........................................................................... 75 RS-485 Multi-Drop ..................................................................................... 76 RS-232/485 Dongle for Communications Setup ....................................... 77

Parker Hannifin

RS-232/485 Communications

The Aries drive has a single serial port, located on the DRIVE I/O connector on the front of the unit. This chapter refers to it as the COM port. The Aries drive uses ASCII and the RS-232 or RS-485 communication protocols.

Terminal Emulator Configuration

RS-232 Rx, Tx, Gnd 9600 baud 8 data bits 1 stop bit No parity Full-duplex RS-485 * 2-wire plus ground (Talk+, Talk­, Gnd) 9600 baud 8 data bits 1 stop bit No parity Half-duplex

* Twisted pair cabling recommended (e.g. Belden 9842) Table 35 Terminal Emulator Configuration for RS-232/485 Communication

Establishing Communications

The 26-pin DRIVE I/O connector (female D-subminiature) also functions as the COM port. You can use it with RS-232 or two-wire RS-485 communications.

Figure 35 RS-232/485 Connections

For setup purposes, you can connect a personal computer (PC) directly to the Aries drive through its COM port. Before attempting to communicate with the Aries drive, verify your PC's connector pinout--make sure the cable connects the following: · · · The PC's transmit terminal (pin 3 of the 9-pin connector) to the Aries's receive terminal (pin 25). The PC's receive terminal (pin 2 of the 9-pin connector) to the Aries's transmit terminal (pin 26). The PC's ground terminal to the Aries's ground terminal (pin 24).

You can also use the Aries Drive I/O Dongle (sold separately), which allows a PC to simultaneously communicate with the Aries drive while also connected to a controller. For more information, see "RS-232/485 Dongle for Communications Setup" on page 77.

74 Aries User Guide

Parker Hannifin Depending on the communications protocol you are using, Aries can automatically configure itself. · · If using RS-232, Aries will automatically detect and configure itself for that communications protocol. If using RS-485 (two-wire) and the standard bias configuration, Aries will automatically detect and configure itself for that communications protocol.

For automatic detection to work, the RS-485 network must be configured with an up bias on + (Talk) and a down bias on ­ (Talk).

RS-232 Communications

The Aries drive supports RS-232 communication. However, you cannot connect the drive in an RS-232 daisy chain.

Pinout for RS-232 Communication

Pin 25 26 24

Description Rx (receive). Connect to Tx on your computer. Tx (transmit). Connect to Rx on your computer. DGND* (logic ground). Connect to DGND on your computer.

Maximum RS-232 cable length is 50 feet (15.25 meters). * Many PC COM ports connect RS-232 ground to chassis ground. Table 36 RS-232 Connector Pinout

RS-485 Communications

The Aries is designed to use RS-485 half-duplex (two-wire). In addition, you can use it in multi-drop networks. For more information about multi-drop, see "RS-485 Multi-Drop" on page 76.

Pinout for 2-wire RS-485 Communication

Pin 25 26 24

· · ·

Description Connect to Tx/Rx+ on your computer. Connect to Tx/Rx­ on your computer. DGND* (logic ground). Connect to DGND on your computer.

Maximum RS-485 cable length is 1000 feet (305 meters). Keep wires as short as possible. Termination resistors may be required on long cable runs. Connect RS-485 cables before applying power to the drive. (Reconnecting the cables with power applied may cause the drive to interpret intermittent connections as RS-232 hardware handshake signals; this may result in shutdown of the RS-485 interface. If this happens, reset the drive to re-enable the RS-485 interface.) Recommended cable: Belden 9842.

·

* Many PC COM ports connect RS-485 ground to chassis ground. Table 37 RS-485 Connector Pinout

For connection information, see Figure 36.

Chapter 4 Communications 75

Parker Hannifin

Figure 36 RS-485 Multi-drop Connections

RS-485 Multi-Drop

RS-485 multi-drop lets you connect up to 99 Aries drives together (see Figure 36). Every drive is factory configured with a default address--zero (0). Using the ADDR command, you can assign a unique address to each drive. You must address each drive individually before connecting it to the multidrop network. Notes · · For RS-485 to work correctly turn off the echo mode (ECHOØ). Zero (0) is not a valid address for a drive.

Setting up Drives for a Multi-Drop Network

1. Connect the drive you want to configure to a PC that is not part of the multi-drop network. 2. Apply power to the drive. 3. Using terminal emulation software, send the following command-- Ø_ADDRi (where i is the address you want to assign the new unit). 4. Remove power to the drive. The drive can now be installed in the network. 5. After installing and connecting the drives to the multi-drop network, test each drive--use safe methods suitable for your particular application-- to ensure each functions correctly. To test each unit, send the i_TREV command, where i represents the address of a drive.

76 Aries User Guide

Parker Hannifin

Warning -- Risk of damage and/or personal injury When testing the installation of drives, use safe methods suitable for your particular application.

Replacing a Unit in the Network

If you need to replace a drive, do the following: 1. Remove the old unit from the network. 2. Connect the new drive to a PC that is not part of the multi-drop network. 3. Apply power to the drive. 4. Using terminal emulation software, send the following command-- Ø_ADDRi (where i is the address you want to assign the new unit). 5. If you can communicate with the old drive, upload its configuration using the Aries Support Tool. Alternatively, you can create a new configuration file using the Aries Support Tool. Then download the configuration file to the new drive. 6. Remove power to the drive. The drive can now be installed in the multidrop network.

Sending Commands to a Specific Unit

You can send ASCII commands from the master unit (for example a personal computer, PLC, or controller) to a specific unit in the multi-drop network. Prefix the command with the unit address and an underscore (_). For example, 3_ERES4ØØØ sets the encoder resolution to 4000 for unit 3. The master unit can receive data from any unit in the network. Note: Make sure you can access each unit on the network. See "Setting up Drives for a Multi-Drop Network" on page 76.

RS-232/485 Dongle for Communications Setup

The Aries Dongle is a Y-cable (part number 71-021609-01) that breaks out the RS-232/485 portion of the DRIVE I/O cable so that you may simultaneously communicate with the Aries Drive while it is also connected with a motion controller. Note: When using the Aries Dongle, you must use a null-modem (crossover) cable between your PC and the Aries drive Caution -- The dongle is designed for setup and troubleshooting purposes only. Do not use the dongle in a permanent installation; it does not meet EMC requirements.

Chapter 4 Communications 77

Chapter 5 Tuning

CHAPTER FIVE

Tuning

IN THIS CHAPTER

Servo Tuning Overview ............................................................................. 79 Position Variable Overview........................................................................ 80 Servo Response Overview ........................................................................ 81 Servo System Gains .................................................................................. 83 Servo Tuning Example .............................................................................. 86

Parker Hannifin

Servo Tuning Overview

The drive uses a digital control algorithm to control and maintain the position and velocity. The digital control algorithm consists of a set of numerical equations used to periodically (once every servo sampling period) calculate the value of the control output. The numerical terms of the equations consist of the current commanded and actual position values (including a few from the previous sampling period), and a set of control parameters. Each control parameter, commonly called a gain, has a specific function (for more information, see "Servo System Gains" on page 83). In addition, tuning is the process of selecting and adjusting gains to achieve optimal servo performance. When using the control algorithm described above, the whole servo system acts as a closed-loop system (see Figure 37). It is called closed loop because the control algorithm accounts for both the command (position, velocity, tension, etc.) and the feedback data from the encoder. Therefore, it forms a closed loop of information. When all gains are set to zero, the digital control algorithm is disabled.

Figure 37 Closed Loop and Open Loop System Comparison

To command a drive, controllers can provide ±10V analog output or step and direction signals. Once the digital control algorithm has calculated the digital control signal, the resultant digital value is sent out from the DSP (digital signal processor) to the DAC (Digital-to-Analog Converter). The DAC has an analog output range of -10V to +10V. It is possible for the digital control signal, calculated by the control algorithm, to exceed the DACs output range. If this occurs, the resulting analog output becomes saturated--where the analog output signal remains at the limit until the position error changes such that the control algorithm calculates a control signal less than the limit. The phenomenon of reaching the output limit is called controller output saturation. When saturation occurs, increasing the gains does not help improve performance because the DAC is already operating at its maximum level.

Chapter 5 Tuning 79

Parker Hannifin

Position Variable Overview

In a servo system, the controller uses two types of position information: commanded position and actual position. As these positions change with time, you can use the position values to determine if the system is positioning as you expect.

Commanded Position

The commanded position is calculated by the motion profile routine from the controller and it is updated every servo sampling period. Therefore, the commanded position is the intended position at any given point of time. To view the commanded position, use the TPC (Transfer Commanded Position) command; the response represents the commanded position at the instant the command is received.

Figure 38 Commanded Position

Actual Position

The actual position of the motor/load is the drive's response to the commanded position, and is measured with the feedback device. The profile resulting from the actual position across time is the position response (for more information, see "Servo Response Overview" on page 81). To view the actual position, use the TPE (Transfer Position of Encoder) command; the response represents the actual position at the instant the command is received. The difference between commanded and actual positions is called position error. To view the position error, use the TPER (Transfer Position Error) command; the response represents the position error at the instant the command is received. If the motor is not moving, the position error is called a steady-state position error. If a position error occurs when the motor is moving, it is called a position tracking error. Even when the system is properly tuned, the position error can still be quite significant due to a combination of factors such as the desired profile, the motor's limitation, the dynamic characteristics of the system, etc. For example, if the commanded velocity is higher than the maximum velocity the motor can physically achieve, the actual position will always lag behind the

80 Aries User Guide

Parker Hannifin commanded position. Under these circumstances, a position error will accumulate no matter how high the gains are set.

Servo Response Overview

Stability

The first objective of tuning is to stabilize the system. The formal definition of system stability is when a bounded input is introduced to the system, the output of the system is also bounded. What this means to a motion control system is if the system is stable, and the position setpoint is a finite value, the final actual position of the system is also a finite value. In contrast, if the system is unstable, no matter how small the position setpoint or how little a disturbance (motor torque variation, load change, noise from the feedback device, etc.) the system receives, the position error will increase exponentially in almost all cases. In practice, when the system experiences instability, the actual position will oscillate in an exponentially diverging fashion as shown in Table 38. One common misperception is that whenever there is oscillation, the system is unstable. It is important to recognize that a system is considered stable if the oscillation finally diminishes (damps out), even if it takes a long time.

Position Response Types

Table 38 identifies the six basic types of position responses. The primary difference among these responses is due to damping--the suppression (or cancellation) of oscillation. Response Unstable Description Instability causes the position to oscillate in an exponentially diverging fashion. A highly damped, or over-damped, system gives a smooth but slower response. A slightly damped, or under-damped, system gives a slightly oscillatory response. Profile (position/time)

Overdamped

Underdamped

Chapter 5 Tuning 81

Parker Hannifin

Response Critically damped

Description A critically-damped response is the most desirable because it optimizes the trade-off between damping and speed of response. An oscillatory response is characterized by a sustained position oscillation of equal amplitude. Chattering is a highfrequency, lowamplitude oscillation that is usually audible.

Profile (position/time)

Oscillatory

Chattering

Table 38 Position Response Types

Performance Measurements

If you plot of the position response versus time, you can make a few measurements to quantitatively assess the performance of the servo. These three measurements are made before or shortly after the motor stops moving: · Overshoot--The measurement of the maximum magnitude that the actual position exceeds the position setpoint. It is usually measured in terms of the percentage of the setpoint value. Rise Time--The time it takes the actual position to pass the setpoint. Settling Time--The time between when the commanded position reaches the setpoint and the actual position settles within a certain percentage of the position setpoint. (Note the settling time definition here is different from that of a control engineering text book, but the goal of the performance measurement is still intact.).

· ·

82 Aries User Guide

Parker Hannifin

Servo System Gains

Proportional Feedback Control (SGP)

Proportional feedback is the most important feedback for stabilizing a servo system. When the controller uses proportional feedback, the control signal is linearly proportional to the position error (the difference between the commanded position and the actual position--see TPER command). The proportional gain is set by the Servo Gain Proportional (SGP) command. Proportional feedback can be used to make the servo system more responsive (stiff), as well as reduce the steady state position error. Because the control is proportional to the position error, whenever there is any disturbance (such as torque ripple or a spring load) forcing the load away from its commanded position, the proportional control can immediately output a signal to move it back toward the commanded position. This function is called disturbance rejection. If you tune your system using only the proportional feedback, increasing the proportional feedback gain (SGP value) too much will cause the system response to be oscillatory, under-damped, or in some cases unstable. Note: Do not set the proportional feedback gain (SGP) to zero, except when open-loop operation is desired.

Velocity Feedback Control (SGV)

Using velocity feedback control, the control signal is proportional to the feedback device's velocity (rate of change of the actual position). The Servo Gain Velocity (SGV) command sets the gain, which is in turn multiplied by the feedback device's velocity to produce the control signal. Because the velocity feedback acts upon the feedback device's velocity, its control action essentially anticipates the position error and corrects it before it becomes too large. Such control tends to increase damping and improve the stability of the system. A high velocity feedback gain (SGV) can also increase the position tracking error when traveling at constant velocity. In addition, setting the velocity feedback gain too high tends to slow down (over-damp) the response to a commanded position change.

Integral Feedback Control (SGI)

Using integral feedback control, the value of the control signal is integrated at a rate proportional to the feedback device position error. The rate of integration is set by the Servo Gain Integral (SGI) command. The primary function of the integral control is to overcome friction and/or gravity and to reject disturbances so that steady state position error is minimized or eliminated. This control action is important for achieving high system accuracy. However, if you can achieve acceptable position accuracy by using only the proportional feedback (SGP), then there is no need to use the integral feedback control.

Chapter 5 Tuning 83

Parker Hannifin

Controlling Integral Windup

If you are using integral control (SGI) and there is an appreciable position error that persists long enough during the transient period (time taken to reach the setpoint), the control signal generated by the integral action can end up too high; this saturates to the maximum level of the controller's analog control signal output. This phenomenon is called integrator windup (see Figure 39).

Figure 39 Integrator Windup (Without Using SGILIM Command)

After windup occurs, it takes time before the integrator output returns to a level within the limit of the controller's output. Such a delay causes excessive position overshoot and oscillation. The integral windup limit (SGILIM) command allows you to set the absolute limit of the integral. The commanded limit, in essence, turns off the integral action as soon as it reaches the limit; consequently, position overshoot and oscillation can be reduced (see Figure 40).

84 Aries User Guide

Parker Hannifin

Figure 40 Integrator Windup (using the SGILIM Command)

Chapter 5 Tuning 85

Parker Hannifin

Servo Tuning Example

The example below illustrates how to experimentally obtain the highest possible proportional feedback (SGP) and velocity feedback (SGV) gains. For a Servo Tuning flow diagram, see "Appendix A Additional Specifications" on page 168. The motion command used for this example is a step command with a step size of 200. The plots shown are as they appear in the Aries Support Tool (X axis = time, Y axis = position). Note: The steps shown below (steps 1 to 11) represent the major steps of the process; the actual progression between these steps may require several iterations.

Step 1

For a starting trial, we set the proportional feedback gain (SGP) to .5. As you can see by the plot, the response is slow. In the next step, we should increase SGP until the response is slightly under damped.

Step 2

With SGP equal to 2, the response becomes slightly under damped (see plot). Therefore, we should introduce the velocity feedback gain (SGV) to damp out the oscillation.

86 Aries User Guide

Parker Hannifin

Step 3

Step 3 With SGV equal to 2, the response is fairly well damped (see plot). At this point, the SGP should be raised again until oscillation or excessive overshoot appears.

Step 4

As we iteratively increase SGP to 5, overshoot and chattering becomes significant (see plot). This means the SGV gain is too low and/or the SGP is too high. Next, we should try raising the SGV gain to see if it will dampen out the overshoot and chattering.

Step 5

After the SGV gain is raised to 5, the overshoot was reduced but chattering is still quite pronounced. This means either one or both of the gains is too high. The next step should be to lower the SGV gain first.

Chapter 5 Tuning 87

Parker Hannifin

Step 6

Lowering the SGV gain to 3 does not help reduce the chattering by much. Therefore, we should lower the SGP gain until chattering stops.

Step 7

Chattering stops after reducing the SGP gain to 4 However, the overshoot is still a little too high. The next step should be to try raising the SGV to damp out the overshoot.

Step 8

After raising the SGV gain to 4, overshoot is reduced a little, but chattering reappears. This means the gains are still too high. Next, we should lower the SGV gain until chattering stops.

88 Aries User Guide

Parker Hannifin

Step 9

After lowering the SGV gain to 3 (even less than in Step 7--3.5), chattering stops. Next we should lower the SGP gain.

Step 10

Overshoot is reduced very little after lowering the SGP gain to 3.5. (The SGV gain might have been lowered too much in Step 9.) Next, we should try raising the SGV gain again until the overshoot is gone.

Step 11

When we raised the SGV gain to 3.5, the step response became fast and very stable.

Chapter 5 Tuning 89

Parker Hannifin

Auto-Tuning

The Aries drive can automatically determine the inertia of the load attached to the motor. This is performed by applying a specified torque to the motor and measuring the acceleration and deceleration of the motor. From this, the Aries drive can calculate the load inertia and store the value in the LJRAT command. Note: Excess friction can affect the measured inertia, thereby estimating the value higher than the actual inertia. While the drive can compensate for some friction, it may not compensate for all. If the estimated load inertia seems overly high, this may be the cause. Note: Use this method of auto-tuning only with the step and direction versions of the Aries drive. The Auto-Tune process should only last a few seconds, during which time the motor will rotate about one-quarter of a turn in each direction. Following are the two methods to start Auto-Tune mode. In the Aries Support Tool, select the Servo Tuner tab. Then click Auto-Tune. --or-- Put the drive in position mode (DMODE6 or 7). On the drive's ±10V Analog Input, apply a command voltage greater than 3V, then reset the drive. To return to normal operation, remove the command voltage and reset the drive.

90 Aries User Guide

Chapter 6 Command Reference

CHAPTER SIX

Command Reference

IN THIS CHAPTER

Description of Format ................................................................................ 92 Syntax ­ Letters and Symbols................................................................... 92 Syntax ­ General Guidelines..................................................................... 94 Command Descriptions ............................................................................. 95

Parker Hannifin

Aries Communications Set-up

Before you can communicate with the Aries drive, you must configure your terminal emulator. You can use HyperTerminal or an equivalent terminal emulator. For information about setting up communications, see "RS-232/485 Communications" on page 71.

Description of Format

1. 2. Encoder Resolution

Encoder Configuration <a_>ERES<i> Rotary motor: i = counts/revolution Linear motor: i = counts/electrical pitch 2ØØ to 1Ø73741823 4ØØØ ERES: <*>4ØØØ Product Aries Rev 1.0

3.

ERES

4. 5. 6. 7. 8. 9. 10. Type Syntax Units Range Default Response See Also

DMEPIT, DMTR, TPE Number

1. 2. 3.

Description

Mnemonic Code: This field contains the command's mnemonic code. Full Name: This field contains the command's full name. Valid Product & Revision: This field lists the Aries Series products and the revision of each product when this command was incorporated or modified per the description. If the command does not apply to that particular product, the Revision is specified as "N/A". All commands applicable to the standard product versions are applicable to the OEM versions unless otherwise noted (e.g., 6250 commands are applicable to the OEM6250 controller). You can use the TREV command to determine which product revision you are using. For example, if the TREV response is Aries Revision 1.0, The product revision is 1.0

4. 5.

Type: This field contains the command's type. Syntax: The proper syntax for the command is shown here. The specific parameters associated with the command are also shown. Definitions of the parameters are described in the Syntax sections below. Units: This field describes what unit of measurement the parameter (b, d, i, r, or t) in the command syntax represents. Range: The range of valid values that you can specify for an argument (or any other parameter specified). Default: The default setting for the command is shown in this field. A command will perform its function with the default setting if you do not provide a value. Response: Some commands allow you to check the status of the command. In the example above, entering the ERES command by itself, you will receive the response <*>4ØØØ. The <*> only appears for RS-485 communication, and does not appear for RS-232 communication. See Also: Commands related or similar to the command described are listed here.

6. 7. 8. 9.

10.

Table 39 Commands-Description of Format

92 Aries User Guide

Parker Hannifin

Syntax ­ Letters and Symbols

The command descriptions provided within this manual use alphabetic letters and ASCII symbols within the Syntax description (see example below) to represent different parameter requirements.

ERES

Type Syntax Units Range Default Response

Encoder Resolution

Encoder Configuration <a_>ERES<i> Rotary motor: i = counts/revolution Linear motor: i = counts/electrical pitch 2ØØ to 1Ø73741823 4ØØØ ERES: <*>4ØØØ Product Aries Rev 1.0

Symbol

a_

Description

Represents an address specifier, numeric value from Ø to 99. An address specifier is required if multiple Aries drives are connected in a daisy-chain or multi-drop configuration; in fact, leaving off the address specifier will cause parameter assignment commands to affect all units and response/transfer commands to request information from all units at the same time (multiple units transmitting characters at one time will garble the communication). To assign unique unit addresses to multiple drives, refer to the ADDR command. Represents the values 1 or Ø; does not require field separator between values. * Represents a character (A to Z, or a to z) Represents the values 1 or Ø, E or e; does not require field separator between values. E or e enables a specific command field. Represents a numeric value that cannot contain a decimal point (integer values only). The numeric range varies by command. Field separator required. Represents a numeric value that may contain a decimal point, but is not required to have a decimal point. The numeric range varies by command. Field separator required. Represents a string of alphanumeric characters from 1 to 16 characters in length. The string must start with an alpha character. (Comma) Represents a field separator. Commands with the symbol r or i in their Syntax description require field separators. Commands with the symbol b or d in their Syntax description do not require field separators (but they may be included). See Table 41.

b c d i

r

t ,

< >

Indicates that the item contained within the < > is optional, and not required by that command. Note: Do not confuse with <cr>, <sp>, and <lf>, which refer to the ASCII characters corresponding to a carriage return, space, and line feed, respectively.

* The ASCII character b can also be used within a command to precede a binary number. When the b is used in this context, it is not to be replaced with a Ø or 1. For example, comparisons such as ERROR= b1x1. Table 40 Commands-Syntax

Chapter 6 Command Reference 93

Parker Hannifin

Syntax ­ General Guidelines

Guideline Topic Guideline

Command Delimiters (<cr> and <lf>) Neutral Characters (<sp>) Case Sensitivity All commands must be separated by a delimiter. A carriage return is the most commonly used. Using neutral characters anywhere within a command will not affect the command. There is no case sensitivity. Use upper or lower case letters within commands. Set velocity limit to 100 rps: DMVLIM<sp>1ØØ<cr> Initiate motion: GO1 go1

Examples

Comment Delimiter [semi-colon ( ; ) or apostrophe ( ` )] Binary and Hexadecimal Values

All text between a comment Add a comment to the command: delimiter and a command delimiter DMVLIM<sp> ; set is considered program comments. velocity ; limit When making assignments with or comparisons against binary or hexadecimal values, you must precede the binary value with the letter "b" or "B", and the hex value with "h" or "H". In the binary syntax, an "x" simply means the status of that bit is ignored. Binary: ERRORL = bØ1111x11111111111 Hexadecimal: ERRORL = h7FxF

Note: The command line is limited to 32 characters (including spaces). Table 41 Syntax Guidelines

94 Aries User Guide

Parker Hannifin

Command Descriptions

You can use the ASCII commands, provided in this chapter, to configure, check errors, and reset the Aries drive through a terminal emulator. A terminal emulator, however, is not required, Instead, you can use the Aries Supp0ort Tool software to perform the same operations. Note: The Aries Support Tool does not support the CMDDIR and ADDR commands. You must use a terminal emulator to set the commanded direction and address of each drive. Before you can communicate with the Aries Drive, you must configure your terminal emulator. You can use HyperTerminal or an equivalent terminal emulator, For more information about setting up communications, see "RS232/485 Communications" on page 74

ADDR

Type Syntax Units Range Default Response See Also

Multiple Unit Address

Drive Configuration <a_>ADDR<i> i = unit number Ø to 255 Ø ADDR: none <*>Ø Product Aries Rev 1.0

The ADDR command configures the unit address for an RS-485 multi-drop network. The factory default address for an Aries drive is zero (0). The ADDR command allows you to uniquely address up to 255 units (99 unit maximum on a single network). After establishing a unique address for each Aries drive, you can address commands to specific units. To do this, prefix the command with the unit's address followed by an underscore ( _ ). For example, 2_ERES reports the resolution on unit 2. RS-485 Multi-Drop You must address each unit before adding it to the multi-drop network. For example, you want to set up a 4-unit multi-drop network, where the drives are addressed as units 1 through 4. After addressing a drive, you can install it in the multi-drop network. 1. Connect the drive to become unit 1. Through a terminal emulator, send the following command: Ø_ADDR1 2. Connect the drive to become unit 2. Through a terminal emulator, send the following command: Ø_ADDR2 3. Connect the drive to become unit 3. Through a terminal emulator, send the following command: Ø_ADDR3 4. Connect the drive to become unit 4. Through a terminal emulator, send the following command: Ø_ADDR4 If you need to replace a unit in the multi-drop network, connect to the individual device and send the Ø_ADDRi command, where "i"

Chapter 6 Command Reference 95

Parker Hannifin represents the address of the new unit. Then connect the drive to the network. Note: All command responses on an RS-485 network are preceded by <*>.

ALIGN

Type Syntax Units Range Default Response See Also

Align encoder

Drive configuration <a_>ALIGN N/A N/A 0 none Product Aries Rev 1.0

DMODE, DRIVE, ENCOFF, ENCPOL, P163, SHALL The ALIGN command aligns the encoder on the motor so that the drive can commutate the motor correctly. This command is especially useful for configuring a custom motor. To align the motor, use the following procedure: 1. Remove any load from the shaft. The procedure works best with an unloaded motor. 2. Disable the drive by means of the hardware enable or by typing DRIVE0 into the terminal and pressing Enter. 3. Type DMODE3 in the terminal and press Enter to enter alignment mode. 4. Enable the drive by means of either the hardware enable or by typing DRIVE1 into the terminal and press Enter. 5. Type ALIGN into the terminal and press Enter to begin the alignment process. 6. The drive then begins the alignment procedure. This could take up to 20 seconds. Note: The motor turns up to 90 degrees during this procedure. 7. The alignment process may modify the following parameters: ENCOFF, ENCPOL, SHALL, CMDDIR, P163 These parameters are stored in the drive. If you want to store them in a smart encoder, type the ESTORE command into the terminal and press Enter. It takes a couple of seconds to store the motor data in the motor.

96 Aries User Guide

Parker Hannifin

ANICDB

Type Syntax Units Range Default Response See Also

Analog Input Center Deadband

Drive Configuration <a_>ANICDB<r> r = volts Ø.ØØ to 1Ø.ØØ Ø.Ø4 ANICDB: *ANICDBØ.Ø4 Product Aries Rev 2.0

DCMDZ, DMTSCL, TANI The ANICDB allows the user to specify the voltage deadband for the command input. ANICDB is used with DCMDZ to configure the command input for DMODE2 and DMODE4. The commanded torque, Trqcommand, is calculated from the input voltage, Vin, using DMTSCL as follows:

V ) Trq command = ( in - DCMDZ - ANICDB

when

Vin > (DCMDZ+ ANICDB)

DMTSCL 10

Trqcommand = 0 (DCMDZ- ANICDB) Vin (DCMDZ + ANICDB) when

V ) Trq command = ( in - DCMDZ + ANICDB

when

Vin < (DCMDZ- ANICDB)

DMTSCL 10

The commanded velocity, Velcommand, is calculated from the input voltage, Vin, using DMVSCL as follows:

DMVSCL V Velcommand = ( in - DCMDZ - ANICDB) 10 when Vin > (DCMDZ+ ANICDB) Vel command = 0 when (DCMDZ- ANICDB) Vin (DCMDZ + ANICDB)

V Velcommand = ( in - DCMDZ + ANICDB)

when Vin < (DCMDZ- ANICDB)

DMVSCL 10

Chapter 6 Command Reference 97

Parker Hannifin

CERRLG Clear the Error Log

Type Syntax Units Range Default Response See Also Error Handling <a_>CERRLG N/A N/A N/A N/A Product Aries Rev 1.0

CONFIG, ERRORL, ERROR, TANI, TDHRS, TDMIN, TDSEC, TDTEMP, TERRLG, TMTEMP, TVBUS The CERRLG command erases the stored contents of the error log. Clearing the error log is a helpful diagnostic tool; it allows you to start the diagnostic process when the error log is in a known state so that you can check the error log in response to subsequent events. The error log is updated every time an error occurs. The TERRLG command displays the last ten error conditions that the drive has experienced, as recorded in these status registers: · · · · · · · TANI (current command input voltage) CONFIG (text-based status report of configuration errors) ERROR (list of error messages) TDHRS (number of hours since the drive was powered up or RESET) TDTEMP (measured temperature of the drive in centigrade) TMTEMP (estimated temperature of the motor in centigrade) TVBUS (measured bus voltage in volts)

CMDDIR Direction of Rotation

Type Syntax Units Range Default Response See Also Drive Configuration <a_>CMDDIR<b> b = enable bit Ø (CW rotation for positive analog input) or 1 (CCW rotation for positive analog input) Ø CMDDIR <*>Ø Product Aries Rev 1.0

ANICDB, DCMDZ, DMTSCL, DRES, ENCPOL, IANI, TANI The CMDDIR command determines the direction of shaft rotation (or direction of travel for linear motors) for positive analog input. The default is clockwise shaft rotation for a positive command. Sending a CMDDIR1 command changes the direction to counter clockwise. In addition, the encoder counts positive for counter clockwise rotation with CMDDIR1. Note: This command does not take effect until you cycle power to the drive, or send the RESET command.

98 Aries User Guide

Parker Hannifin

Rotary Motors--Positive values represent clockwise motion and negative values represent counter-clockwise motion (assuming CMDDIR = Ø, and that you connected the feedback device according to instructions provided in "Chapter 2 Mechanical Installation" and "Chapter 3 Electrical Installation").

Figure 41 Clockwise/ Counter-clockwise rotation

CONFIG

Type Syntax Units Range Default Response See Also

Configuration Errors and Warnings

Error Handling <a_>CONFIG N/A N/A N/A CONFIG <*>No Errors Product Aries Rev 1.0

DMTIC, DMTIND, DMTIP, DMTW, ERROR The CONFIG command gives a text-based status report of current configuration errors and warnings (EØ through E24). Error

EØ--Motor Configuration Warning E1--Motor Configuration Error

Resolution

The motor rating is too high for the drive, and the drive is using its own limits for safety reasons. One of the motor parameters is set to zero (0). Look at the additional errors to find which parameters are set at zero (0). Refer to your motor specifications for the correct value.

E3--Max Inductance = Ø

This parameter is set to zero (0). To correct the error, you must set a non-zero (0) value. Refer to your motor specifications for the correct value. (DMTIND) This parameter is set to zero (0). To correct the error, you must set a non-zero value. Refer to your motor specifications for the correct value. (DMTW) This parameter is set to zero (0). To correct the error, you must set a non-zero value. Refer to your motor specifications for the correct value. (DPOLE) This parameter is set to zero (0). To correct the error, you must set a non-zero value. Refer to your motor specifications for the correct value. (DMTRES) This parameter is set to zero (0). To correct the error, you must set a non-zero value. Refer to your motor specifications for the correct value. (DMKE) This parameter is set to zero (0). To correct the error, you must set a non-zero value. Refer to your motor specifications for the correct value. (DMTIC)

E4--Rated Speed = Ø

E5--DPOLE = Ø

E6--Resistance = Ø

E7--Ke = Ø

E8--Continuous Current = Ø

Chapter 6 Command Reference 99

Parker Hannifin

Error

E9--Peak Current = Ø

Resolution

This parameter is set to zero (0). To correct the error, you must set a non-zero value. Refer to your motor specifications for the correct value. (DMTIP) The continuous current of the motor is higher than the continuous current rating of the drive. Use the continuous current rating for the drive. The motor's torque rating is too high for the power level of the drive. Use the drive's torque rating. The peak current of the motor is higher than the peak current rating of the drive. Use the drive's value for peak current. This parameter is set to zero (0). The drive will not enable Velocity or Position Modes. To correct the error, you must set to a non-zero value. Refer to your motor specifications for the correct value. (DMTJ) This parameter is set to zero (0). The drive will not enable Velocity or Position Modes. To correct the error, you must set to a non-zero value. Refer to your motor specifications for the correct value. (DMTD) The notch filter settings caused an internal calculation error. The last valid value was used. Try different values for the notch filter parameters. (DNOTAF, DNOTAQ, DNOTBF, DNOTBQ) The lead filter setting (DNOTLD) must be greater than or equal to the lag filter setting. (DNOTLG) The lead filter setting (DNOTLD) must be less than or equal to 4 times the lag filter setting. (DNOTLG) The lag filter setting (DNOTLG) must be greater than or equal to 20 Hz. RESERVED

E1Ø--Use Drive Continuous Current Warning E11--Torque Rating > Peak Power Rating Warning E12-- Use Drive Peak Current Warning E13 - Inertia = Ø

E14 ­ Damping = Ø

E15 ­ Notch filter Calc Error.

E16 ­ Lead < Lag Freq E17 ­ Lead 4* Lag Freq E18 ­ Lag Freq < 2Ø Hz E19­E24

Table 42 Configuration Errors and Warnings

100 Aries User Guide

Parker Hannifin

DCMDZ

Type Syntax Units Range Default Response See Also

Zero the Drive Command Offset

Drive Configuration <a_>DCMDZ=<r> r = volts -1Ø.ØØ to 1Ø.ØØ Ø.ØØ N/A Product Aries Rev 1.0

ANICDB, DMODE, TANI The DCMDZ command sets the zero point for the command input. When in torque/force mode (DMODE2), this will minimize motor drift. Executing the DCMDZ command without an argument sets the zero reference point to the last voltage read at the command input. To execute this command correctly, short the AIN + and AIN ­ pins together on the DRIVE I/O connector, or command zero volts from the servo controller. You can also use DCMDZ to set the zero point to an arbitrary voltage by entering that value. For example, DCMDZ = Ø.5 makes 0.5 volts equal to a commanded velocity of zero (0) rps. Note that this value is the internal level and does not take into account any offsets in the incoming command signal.

DIBW

Type Syntax Units Range Default Response See Also

Current Loop Bandwidth

Tuning <a_>DIBW<i> Hz 250-3000 1200 DIBW: <*>1200 Product Aries Rev 3.0

PGAIN, IGAIN, IAUTO When used in conjunction with IAUTO1, this command sets the current loop bandwidth. Higher values of DIBW will give a faster response to changes in commanded current, at the expense of some overshoot. Lower values of DIBW, will give a slower response, with much less overshoot.

Chapter 6 Command Reference 101

Parker Hannifin

DIFOLD

Type Syntax Units Range Default Response See Also

Current Foldback Enable

Drive Configuration <a_>DIFOLD<b> b = enable bit Ø (disable) or 1 (enable) 1 DIFOLD: none <*>Ø Product Aries Rev 1.0

The DIFOLD command enables (1) or disables (Ø) the drive's current foldback protection feature. The current foldback feature reduces the drive's continuous current output by 20% when sustained current has the potential to overheat the drive. For the AR-20xE and AR-30xE drives, this feature is always enabled. Each drive has the specifications shown in Table 43. Note that current ratings are for the drive, not for the motor.

AR-01xx Drive Continuous Current Rating (100%) Max Current Rating AR-02xx AR-04xx AR-08xx AR-13xx AR-20xE AR-30xE

1.0 Arms 3.0 Arms 3.375 sec

1.75 Arms 5.25 Arms 3.375 sec

3.0 Arms 9.0 Arms 3.375 sec

4.5 Arms 13.5 Arms 3.375 sec

6.3 Arms 14.07 Arms 8.64 sec

10 Arms 30 Arms 3.375 sec

16 Arms 48 Arms 3.375 sec

Max Time at Peak Current Rating

Table 43 Current Foldback Ratings

If your drive is operating above its continuous rating, see Figure 42 to predict the number of seconds until foldback occurs. For example, the graph shows that at the drive's peak current rating (300% of continuous), foldback occurs after 3.375 seconds. Note: For model AR-13xx, foldback occurs after 8.64 seconds at its peak rating (225% of continuous).

Figure 42 Time until current foldback occurs

102 Aries User Guide

Parker Hannifin

DMEPIT

Type Syntax Units Range Default Response See Also

Motor Electrical Pitch

Motor (Linear only) <a_>DMEPIT<r> r = millimeters Ø to 3ØØ.ØØ : ±Ø.Ø1 Ø DMEPIT: <*>4Ø.ØØ Product Aries Rev 1.0

ERES Note: This command does not take effect until you cycle power to the drive, or send the RESET command. The DMEPIT command sets the electrical pitch of the magnets for use with permanent magnet brushless linear motors. The DMEPIT value is required to convert between linear units and rotary units. The electrical pitch can be equated to one revolution in a rotary motor. Mechanically, the definition of the electrical pitch is the linear distance between two magnets comprising a full magnetic cycle. For example, the illustration below shows an electrical pitch of 42 mm (DMEPIT42).

Figure 43 Linear motor track

Important! For rotary motors, set the DMEPIT to zero (0). The Aries drive uses the DMEPIT parameter as the determinant for which type of motor, linear or rotary, is connected.

DMODE

Type Syntax Units Range Default Response See Also

Drive Control Mode

Drive Configuration <a_>DMODE<i> i = control mode setting 1 to 17 (see Table 44) 2 DMODE: none <*>2 Product Aries Rev 1.0

Use the DMODE command to select the drive control mode for your Aries drive. For drive mode descriptions and drive compatibility, see Table 44.

Chapter 6 Command Reference 103

Parker Hannifin

DMODE 1 2 3 4 6

Mode Autorun Torque/Force Control Velocity Control Position Control

Description Rotates the motor at 1 rps/mps. Current is reduced by 10%. Allows direct control of rotary motor torque, or linear motor force. Allows direct control of rotary or linear motor velocity. Uses 5V Differential compatible (RS-422 logic level compatible) step and direction control. Reverses the polarity of the step and direction signal.

Feedback Alignment Auto-configure for feedback setup.

7

Reversed Position Control

Table 44 Drive Control Mode

Note: dmodes 6 and 7 are available only on the step and direction versions of the Aries drive.

DMPSCL Incoming Pulse Scaling

Type Syntax Units Range Default Response See Also Drive Configuration <a_>DMPSCL<i> i = multiplier setting 0 to 127 1 DMPSCL: <*>1 Product Aries Rev 2.0

DMODE, DMTR, DRES Use the DMPSCL command to scale the incoming pulses for the step and direction input. A setting of 10 would move the motor 10 encoder pulses for each input pulse. This command is only valid in DMODE6 (Position Mode). DRES command: Added DRES command for step and direction inputs. Input steps will be scaled to DRES value so DRES steps on the input would translate to 1 revolution of the motor. DRES is set to ERES internally if DMPSCL is non-zero for backward compatibility. DMPSCL should be set to 0 to enable DRES support. NB: DRES change requires a reset to take effect. DMPSCL works immediately so the user could use DMPSCL0 to enable DRES support then enable DMPSCL and have both features working at once.

104 Aries User Guide

Parker Hannifin

DMTAMB Motor Ambient Temperature

Type Syntax Units Range Default Response See Also Motor <a_>DMTAMB<r> r = Degrees Celsius -5Ø.ØØ to 25Ø.ØØ : ±Ø.Ø1 4Ø.Ø DMTAMB: <*>4Ø.Ø Product Aries Rev 1.0

DMTMAX, DMTRWC, DMTTCM, DMTTCW The DMTAMB command sets the motor ambient temperature used by the software motor thermal model. The DMTAMB value, in conjunction with the motor thermal time constant (DMTTCM), the motor winding time constant (DMTTCW), the motor thermal resistance (DMTRWC) and the continuous motor current (DMTIC), is used in a real-time estimation of the motor winding temperature. When the winding temperature exceeds DMTMAX, the drive faults and reports E35­Motor Thermal Fault.

DMTD

Type Syntax Units Range Default Response See Also

Motor Damping

Motor <a_><!>DMTD<r> (does not take effect until RESET or cycle power) Rotary motor: r = uNm/rad/sec Linear motor: r = N/meter/sec Rotary motor: Ø.ØØØØØØ to 1ØØØØ : ±1 Linear motor: DMEPIT (electrical pitch) dependent Ø.ØØØØØØ DMTD: *DMTD2ØØ Product Aries Rev 2.0

DMTR Note: This command does not take effect until you cycle power to the drive, or send the RESET command. Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. For a list of auto-configured commands, see DMTR. The DMTD command specifies the damping of the motor itself. This includes both magnetic losses and bearing losses.

Chapter 6 Command Reference 105

Parker Hannifin

DMTIC

Type Syntax Units Range Default Response See Also

Continuous Current

Motor <a_>DMTIC<r> r = Amps-RMS Ø.ØØ to 2ØØ.ØØ : ±Ø.Ø1 Ø.ØØ (DMTIC of Ø results in motor configuration warning) DMTIC: <*>6.5Ø Product Aries Rev 1.0

DMTICD, DMTIP, DMTR, TCI, TDICNT, TDIMAX

Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. Otherwise, the drive reports the configuration errors EØ­Motor Configuration Error and E8­Continuous Current = Ø. For a list of automatically configured commands, see DMTR. The DMTIC command sets the continuous operating current for a motor. Rotary motors: The internal winding temperature will reach 125°C with a specified heatsink in a 40°C ambient--for Parker motors only. Linear motors: The winding will reach 90°C in a 25°C ambient--for Parker motors only. For heatsink dimensions, see pages 28, 29 and 30. Example

DMTIC5 ; Set the motor current to 5 amps rms (equates to ; 7.Ø7 amps peak)

DMTICD

Type Syntax Units Range Default Response See Also

Continuous Current Derating

Motor <a_>DMTICD<i> I = Percent derating at rated speed Ø.ØØ to 1ØØ.ØØ : ±Ø.Ø1 Ø.ØØ (DMTICD of Ø results in no current derating) DMTICD: <*>5 Product Aries Rev 1.0

DMTIC, DMTIP, DMTIP, DMTR, DMTW, TCI, TDICNT, TDIMAX Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. For a list of auto-configured commands, see DMTR.

106 Aries User Guide

Parker Hannifin

The DMTICD command sets the current derating percentage at rated speed (DMTW). This value sets the extent to which continuous current must be reduced at speed to compensate for velocity-related losses in the motor. For example, DMTICD3 sets the motor's continuous current derating to 3% (or 97% of continuous value DMTIC) at the motor's rated speed (DMTW). At half this speed, it will be reduced 1.5%.

DMTIND

Type Syntax Units Range Default Response See Also

Motor Inductance

Motor <a_>DMTIND<r> r = mH Ø.Ø to 2ØØ.Ø : ±Ø.1 Ø.Ø (DMTIND of Ø results in motor configuration error) DMTIND <*>1Ø Product Aries Rev 1.0

DMTINF, DMTR Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. Otherwise, the drive reports the configuration errors E1­Motor Configuration Error and E3­Maximum Inductance = Ø, and shuts down the drive. For a list of automatically configured commands, see DMTR. The DMTIND command specifies the maximum value of motor inductance. This usually differs from the nominal nameplate value because actual inductance is usually position dependent. If the maximum value of motor inductance is not known, specify the nominal inductance as listed on the motor's nameplate.

Chapter 6 Command Reference 107

Parker Hannifin

DMTINF

Type Syntax Units Range Default Response See Also

Motor Inductance Factor

Motor <a_>DMTINF<r> r = units Ø.ØØ to 1.ØØ 1 DMTINF <*>1.ØØ Product Aries Rev 1.0

CONFIG, DMTIND, DMTR Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. Otherwise, the drive reports the configuration errors E1­Motor Configuration Error and E3­Maximum Inductance = Ø, and shuts down the drive. For a list of automatically configured commands, see DMTR. The DMTINF command specifies the minimum motor inductance divided by the maximum motor inductance. Setting DMTINF to 1.ØØ does not derate the motor. If the minimum value of the motor inductance is not known, use the nominal inductance as listed on the motor's nameplate (or set DMTINF1.ØØ)

DMTIP

Type Syntax Units Range Default Response See Also

Peak Current

Motor <a_>DMTIP<r> r = Amps-RMS Ø.ØØ to 4ØØ.ØØ : ±Ø.Ø1 Ø.ØØ (DMTIP of Ø results in motor configuration warning) DMTIP: <*>7.5Ø Product Aries Rev 1.0

DMTIC, DMTICD, DMTLIM, DMTR, TDIMAX

Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. Otherwise, the drive reports the configuration errors E1­Motor Configuration Error and E9­Peak Current = Ø. For a list of automatically configured commands, see DMTR. The DMTIP command sets a limit that the commanded current cannot exceed. This is typically set to three times the motor's continuous current rating (DMTIC) or less. If DMTIP is set higher than the full-scale value calculated by DMTLIM (torque/force limit) the new DMTIP value will be ignored.

108 Aries User Guide

Parker Hannifin

If the DMTIP value exceeds the drive's maximum output current (TDIMAX), the DMTIP value will be ignored and the maximum allowable value will be used (see Table 45). The drive reports EØ­Motor Configuration Warning and E12­Peak Current Too High. Maximum Current Rating (RMS) AR-01xx AR-02xx AR-04xx AR-08xx AR-13xx AR-20xE AR-30xE 3A 5.25A 9A 13.5A 14.1 30 48

Table 45 Peak Current Rating for Aries Drives

DMTJ

Type Syntax Units Range Default Response See Also

Motor Rotor Inertia / Forcer Mass

Motor <a_><!>DMTJ<r> (does not take effect until RESET or cycle power) Rotary motor: r = kgm2 * 1Ø-6 Linear motor: r = kg Rotary motor: Ø.ØØØ to 1ØØØØØØ.ØØØ : ±Ø.ØØ1 Linear motor: DMEPIT (electrical pitch) dependent Ø.ØØØ (DMTJ of Ø results in motor config. error) DMTJ: *DMTJ2ØØ.6ØØ Product Aries Rev 2.0

DMTR, CONFIG Note: This command does not take effect until you cycle power to the drive, or send the RESET command. Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. If the drive is powered up when this command is set to zero (for instance, if RFS is executed), the drive reports a motor configuration error with E13, and shuts down the drive (DRIVEØ). For a list of auto-configured commands, see DMTR. The DMTJ command sets the motor rotor inertia for rotary motors, or the forcer mass for linear motors.

Chapter 6 Command Reference 109

Parker Hannifin

DMTKE

Type Syntax Units

Motor Ke

Motor <a_>DMTKE<r> Rotary motor: r = volts (Ø-peak)/krpm (measured line-to-line) Linear motor: r = volts (Ø-peak)/meter/second (measured line-to-line) Product Aries Rev 1.0

Range Default Response See Also

Rotary motor: Ø.Ø to 8ØØ.Ø : ±Ø.1 Linear motor: DMEPIT (electrical pitch) dependent Ø.Ø (DMTKE of Ø results in motor configuration error) DMTKE: <*>15.Ø

DMEPIT, DMTLIM, DMTR, DMTSCL Note: This command does not take effect until you cycle power to the drive, or send the RESET command. Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. Otherwise, the drive reports the configuration errors E1­Motor Configuration Error and E7­Bad Hall State, and shuts down the drive. For a list of automatically configured commands, see DMTR. The DMTKE command specifies the motor voltage constant (Ke). This defaults to the nominal Ke of the motor selected with the DMTR command. The motor's torque/force constant (Kt) is derived from the motor's voltage constant (Ke) by the following relationship:

3 3 Ke(Volts / krpm) 200 RMS, 0 - peak value Rotary motors: 3 3 Kt ( N / A ) = Ke(Volts /( meter / sec)) Linear motors: 200 RMS, 0 - peak value Kt ( Nm / A ) =

Note: The Aries requires values in rotary units. The Aries Support Tool automatically performs these conversions when you use the Configuration Wizard. If you do not use the Configuration Wizard, you must convert your linear units to rotary units. For more information about conversion, see the DMEPIT command.

110 Aries User Guide

Parker Hannifin

DMTLIM

Type Syntax Units Range

Torque/Force Limit

System <a_>DMTLIM<r> Rotary motor: r = Nm Linear motor: r = N Rotary motor: Ø.Ø to 5ØØ.Ø (motor/drive dependent): ±Ø.1 Linear motor: DMEPIT (electrical pitch) dependent 4ØØ.Ø DMTLIM: <*>1Ø.5 Product Aries Rev 1.0

Default Response See Also

DMODE, DMTIP, DMTKE, DMTR, DMTSCL, TTRQ, TTRQA Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. For a list of auto-configured commands, see DMTR. The DMTLIM command sets a maximum torque/force limit for the system. Requests for higher torque/force will be clamped to this value. This command will default automatically to a value appropriate to the motor selection (DMTR) and the Aries drive you are using, and no changes are required in many cases. If your mechanical system has torque/force limitations (due, for example, to the limitations of a coupler or belt), you can use this command to limit system torque/force without affecting system scaling or gains. During initial tuning, this command can be used to limit the torque/force produced if the system becomes unstable, reducing the rate of motor heating and allowing more reaction time for the person tuning the system, and reducing the chances of damage to the mechanical system. If DMTLIM is set higher than the value allowed by the motor's peak current times the motor's Kt, or the drive's peak current times the motor's Kt (whichever is lower), the new DMTLIM value will be ignored (but not overwritten). In addition, the drive reports EO ­Motor configuration Warning and E11­Torque Rating Too High for Drive, and the maximum internal value is used. You can clear the warning by sending the RESET command or cycling power to the drive. The motor's torque/force constant (Kt) is derived from the motor's voltage constant (Ke, which is set by the DMTKE command) by the following relationship (Note: Ke is set with the DMTKE command):

Chapter 6 Command Reference 111

Parker Hannifin

Rotary motors:

3 3 Ke(Volts / krpm) 200 RMS, 0 - peak value Kt ( Nm / A ) =

3 3 Ke(Volts /( meter / sec)) 200 RMS, 0 - peak value Kt ( N / A ) =

Linear motors:

DMTMAX Maximum Motor Winding Temperature

Type Syntax Units Range Default Response See Also Motor <a_>DMTMAX<r> r = Degrees Celsius Ø.Ø to 2ØØ.Ø : ±Ø.1 125.Ø DMTMAX: <*>125.Ø Product Aries Rev 1.0

DMTAMB, DMTIC, DMTR, DMTRWC, DMTTCM, DMTTCW Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. For a list of auto-configured commands, see DMTR. The DMTMAX command sets the maximum motor winding temperature allowed. The DMTMAX value, in conjunction with the motor thermal time constant (DMTTCM), the motor winding time constant (DMTTCW), the motor thermal resistance (DMTRWC) and the continuous motor current (DMTIC), is used in a real-time estimation of the motor winding temperature. When the winding temperature exceeds DMTMAX, a drive fault occurs and the drive reports E35­Motor Thermal Model Fault.

DMTR

Type Syntax Units Range Default Response See Also

Identify Motor

Drive Configuration <a_>DMTR<t> this command is only a report back t = Parker motor identification number N/A "Blank" DMTR: <*>SM232AE (Servo Motor Data Parameters below), Product Aries Rev 1.0

STATUS

RESET, RFS,

The purpose of the DMTR command is to record and report the identification number of the Parker motor you selected in the Aries Support Tool.

112 Aries User Guide

Parker Hannifin When you select a specific Parker motor using the Aries Support Tool, the DMTR setting and various motor parameters (see Servo Motor Data Parameters below) are automatically configured for the associated motor. Using the Aries Support Tool, you can save the parameters in a configuration file. For the DMTR and all the motor parameter commands to take effect after downloading the configuration file to the Aries drive, you must cycle drive power or send the RESET command. Note: For a non-Parker motor, the default setting is blank (empty). You must set all relevant motor parameters manually. Avoid using the DMTR command to change the motor name, because the new DMTR value may not represent the actual motor parameters that are currently loaded in the drive.

Servo Motor Data Parameters

MEPIT DMTD DMTIC DMTICD DMTIND DMTINF DMTIP DMTJ DMTKE DMTLIM Motor Electrical Pitch Motor Damping Continuous Current Continuous Current Derating Motor Inductance (max) Motor Inductance (min) Peak Current Motor rotor Inertia/Forcer Mass Motor Ke Torque/Force Limit DMTMAX DMTRES DMTRWC DMTTCM DMTTCW DMTW DMVLIM DMVSCL DPOLE ERES Maximum Motor Winding Temperature Motor Winding Resistance Motor Winding Thermal Resistance Motor Thermal Time Constant Motor Winding Time Constant Motor Rated Speed Velocity Limit Velocity Scaling Number of Motor Pole Pairs Encoder Resolution

Although these command values are auto-configured when you select a Parker motor (using the Aries Support Tool), you may individually set the command values with the respective configuration command.

Motor Configuration Error

Many of the above motor parameters, if not configured (i.e. a command remains at its factory default value, or an RFS command is executed) will report a motor configuration warning or error when powering up the Aries drive--EØ­Motor Configuration Warning or E1­Motor Configuration Error (an error also disables the drive--DRIVEØ). To resolve the error or warning condition, you must select a Parker motor using the Aries Support Tool (or configure each motor parameter command with a value other than zero using a terminal emulator), download the resulting configuration information, and then send the RESET command or cycle power.

Chapter 6 Command Reference 113

Parker Hannifin

DMTRES Motor Winding Resistance

Type Syntax Units Range Default Response See Also Motor <a_>DMTRES<r> r = Ohm (measured line-to-line) Ø.ØØ to 10Ø.ØØ : ±Ø.Ø1 Ø.ØØ (DMTRES of Ø results in motor configuration error) DMTRES: <*>7.5Ø Product Aries Rev 1.0

DMTR

Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. Otherwise, the drive reports the configuration errors E1­Motor Configuration Error and E6­Resistance = Ø, and shuts down the drive. For a list of automatically configured commands, see DMTR. The DMTRES command sets the motor winding resistance. This resistance value is measured at 25°C at the drive end of the motor cable (motor cable included). This resistance is the phase-to-phase resistance measured at terminals U to V, V to W, or W to U. Warning -- Disconnect the motor cable from the drive before attempting to make this measurement. For best accuracy, and to avoid injury, this measurement must be made with the motor cable disconnected from the drive.

DMTRWC Motor Winding Thermal Resistance

Type Syntax Units Range Default Response See Also Motor <a_>DMTRWC<r> r = Degrees Celsius/Watt (°C/W) Ø.ØØ to 16.ØØ : ±Ø.Ø1 Ø.5Ø DMTRWC: <*>23.6Ø Product Aries Rev 1.0

DMTR, DMTTCM, DMTTCW

Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. For a list of auto-configured commands, see DMTR.

114 Aries User Guide

Parker Hannifin

DMTRWC specifies the temperature rise of the motor winding above motor case temperature per watt of winding power dissipation between the winding and case. Motor heatsinking does not affect this value.

DMTSCL Torque/Force Scaling

Type Syntax Units Range Default Response See Also Drive Configuration <a_>DMTSCL<r> Rotary motor: r = Nm Linear motor: r = N Ø.Ø to 5ØØ.Ø (motor/drive dependent): ±Ø.1 Ø DMTSCL: <*>2Ø.Ø Product Aries Rev 1.0

DMEPIT, DMODE, DMTKE, DMTLIM, DMTR, TDIMAX, TTRQ, TTRQA Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. For a list of auto-configured commands, see DMTR. The DMTSCL command scales the torque/force command input. It sets the full-scale torque/force that will be produced from a 10-volt input command. It controls the gain applied to the input. This can be used to scale the input to match application needs. For example, if a torque/force sensor produces 2 volts per Newton-meter, the drive could be scaled to match this by using DMTSCL5 -- this sets 10V = 5 N-m (0.5 N-m/Volt). DMTLIM may limit torque/force to less than this full-scale value. Note: To configure the drive in torque/force mode so that a 10-volt torque/force command produces the rated peak current of the drive (without reference to motor parameters), enter for DMTSCL the result of the following calculation:

3 3 DMTSCL = TDIMAX 200 DMTKE

Rotary Motors: V*/krpm Linear Motors: V*/m/s * peak value

Chapter 6 Command Reference 115

Parker Hannifin

DMTSWT Motor temperature switch type

Type Syntax Units Range Motor configuration <a_>DMTSWT<i> i = motor temp switch type 0 (Normally closed switch) 1 (Positive temperature coefficient thermistor) 2 (Normally open switch) 3 (Negative temperature coefficient thermistor) Default Response See Also DMTSWT0 DMTSWT: <*>0 Product Aries Rev 2.10

DTHERM, TMTEMP DMTSWT sets the type of motor switch used. Values of 0 or 1 behave exactly the same and are interchangeable. DMTSWT3 specifies a negative temperature coefficient thermistor. In this case TMTEMP reports the higher of the motor thermal model value or the calculated thermistor temperature, once the thermistor temperature is above 60 degrees C. The drive faults with a motor temperature fault at a thermistor temp of 105 degrees C or the motor thermal model setpoint (whichever is lower) when DMTSWT is set to 3. The default value for this command is DMTSWT0 and will work with both positive temperature coefficient thermistors or normally closed switches.

DMTTCM Motor Thermal Time Constant

Type Syntax Units Range Default Response See Also Motor <a_>DMTTCM<r> r = minutes Ø.Ø to 12Ø.Ø : ±Ø.1 Ø.Ø DMTTCM: <*>3Ø.4 Product Aries Rev 1.0

DMTR, DMTTCW

Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. For a list of auto-configured commands, see DMTR. The DMTTCM command specifies the thermal time constant of the motor and its mounting. The drive uses this value to help protect the motor from thermal damage. It describes the length of time the motor takes to reach 63% of its final temperature, given constant power. Note that the motor mounting affects this measurement. Continuous current ratings and published time constants for Parker motors are specified when mounted to a 10" x 10" x ¼" aluminum plate in 25°C open air. If your mounting surface provides heat-sinking or thermal mass significantly different from this, a different value may be appropriate to your

116 Aries User Guide

Parker Hannifin application. Note also that the time constant of the motor winding itself (DMTTCW) is much faster than this; therefore, the rise in winding temperature will initially be much faster than DMTTCM would suggest.

DMTTCW Motor Winding Time Constant

Type Syntax Units Range Default Response See Also Motor <a_>DMTTCW<r> r = minutes Ø.ØØ to 6Ø.ØØ : ±Ø.Ø1 Ø.ØØ DMTTCW: <*>28.4Ø Product Aries Rev 1.0

DMTR, DMTRWC, DMTTCM Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. For a list of auto-configured commands, see DMTR. The DMTTCW command specifies the time constant of the motor winding alone. This is the time for the winding to reach 63% of its final temperature rise above the rest of the motor, given constant power. Note that this is not the time constant usually specified in motor data sheets (see DMTTCM); the DMTTCW value is typically much faster.

DMTW

Type Syntax Units Range Default Response See Also

Motor Rated Speed

Motor <a_>DMTW<r> Rotary motor: r = revolutions/second Linear motor: r = meters/second Ø.Ø to 400.Ø : ±Ø.1 Ø.Ø (DMTW of Ø results in motor configuration error) DMTW: <*>15Ø.Ø Product Aries Rev 1.0

DMEPIT, DMTICD, DMTR Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. Otherwise, the drive reports the configuration errors EØ­Motor Configuration Warning and E4­Rated Speed = Ø, and shuts down the drive. For a list of automatically configured commands, see DMTR. The DMTW command specifies the rated speed of the motor. This is the lesser of the following: · (Rotary motor) Motor mechanical limited speed

Chapter 6 Command Reference 117

Parker Hannifin · · ·

(Rotary motor) Encoder limit of 5 MHz (pre-quadrature) Linear motor speed limitations include encoder resolution and track length. The corner of the continuous speed/torque or speed/force curve (the point where the continuous and peak torque/force curves meet).

The DMTW value is used in conjunction with DMTICD to protect the motor from thermal damage.

DMVLIM Velocity Limit

Type Syntax Units Range Default Response See Also System <a_>DMVLIM<r> Rotary motor: r = revolutions/second Linear motor: r = meters/second Ø.ØØ to 40Ø.ØØ : ±Ø.Ø1 125.ØØ DMVLIM: <*>5Ø.ØØ Product Aries Rev 1.0

DMODE, DMTR

Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. For a list of auto-configured commands, see DMTR. The DMVLIM command sets a limit that the commanded velocity cannot exceed without affecting gains or scaling. This is typically used to protect parts of the mechanical system. If the velocity demand from the internal Aries control loops exceeds the limits set by DMVLIM, the Aries invokes the "Override Mode", in which the drive software clamps the maximum velocity to the value set by DMVLIM.

118 Aries User Guide

Parker Hannifin

DMVSCL Velocity Scaling

Type Syntax Units Range Default Response See Also Drive Configuration <a_>DMVSCL<r> Rotary motor: r = revolutions/second Linear motor: r = meters/second Ø.ØØ to 4ØØ.ØØ (motor/drive dependent): ±Ø.Ø1 4.ØØ DMVSCL: <*>1ØØ.Ø Product Aries Rev 2.0

DMODE, DMTR

Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to 4.00--you must manually set this parameter to a non-zero number. For a list of auto-configured commands, see DMTR. The DMVSCL command scales the velocity command input. This command is only valid in Velocity mode (DMODE4). It sets the full-scale velocity that will be produced from a 10-volt input command. It controls the gain applied to the input. This can be used to scale the input to match application needs. For example, if an application requires a maximum speed of 10 Rev/Sec, then the DMVSCL could be set to 10. This would scale the input to 1Rev/Sec for every volt applied to the input.

DNOTAD Notch Filter A Depth

Type Syntax Units Range Default Response See Also Tuning <a_><!>DNOTAD<i> n/a Ø.ØØØØ - 1.ØØØØ Ø.ØØØØ (depth is zero) DNOTAD: *DNOTAD.5 Product Aries Rev 2.0

DMODE, DNOTAF, DNOTAQ, DNOTBD, DNOTBF, DNOTBQ, DNOTLD, DNOTLG The DNOTAD command sets the depth for the commanded torque/force notch filter A. Setting this to zero (0) disables the filter. This command is useful in adjusting the maximum allowable attenuation and phase shift through the filter. The deeper the notch depth, the more attenuation and phase shift. In general, the notch depth is increased until the resonance is diminished. Increasing the depth further, might increase the phase shift to an unacceptable level and decrease the overall system performance. There are two cascaded notch filters labeled "A" and "B". Both filters operate in exactly the same way. The diagram below shows the topology of these filters.

Chapter 6 Command Reference 119

Parker Hannifin

Figure 44 Notch Filter Topology

The graphs below illustrate the transfer function for the magnitude and phase of the notch filter command output torque/force vs. the notch filter command input torque/force. In this example, the notch depths are set to .3, .6, and .9 (DNOTAD.3, DNOTAD.6, DNOTAD.9). The notch center frequency is set to 200 Hz (DNOTAF2ØØ) and the "Q" is set to 1 (DNOTAQ1).

Figure 45 Notch Filter Magnitudes

These filters operate in all DMODE settings except Autorun (DMODE1).

DNOTAF Notch Filter A Frequency

Type Syntax Units Range Default Response See Also Tuning <a_><!>DNOTAF<i> i = Hz Ø (disable), or 6Ø-1ØØØ Ø (filter is disabled) DNOTAF: *DNOTAF2ØØ Product Aries Rev 2.0

DNOTAD, DNOTAQ, DNOTBD, DNOTBF, DNOTBQ, DNOTLD, DNOTLG The DNOTAF command sets the center frequency for the commanded torque/force notch filter A. Setting this to 0 disables the filter. If setting a value results in an internal calculation error, the last valid value is used, and TE15 is set. There are two cascaded notch filters labeled "A" and "B". Both filters operate in exactly the same way. The graphs below illustrate the transfer function (magnitude and phase) of the internal commanded torque/force vs. the user commanded torque/force. In this example, the notch frequency is set to 150 Hz (DNOTAF15Ø) and the "Q" is set to 1 (DNOTAQ1).

120 Aries User Guide

Parker Hannifin

Figure 46 Notch Filter A

These filters operate in all DMODE settings, except Autorun (DMODE1).

DNOTAQ Notch Filter A Quality Factor

Type Syntax Units Range Default Response See Also Tuning <a_><!>DNOTAQ<r> r = quality factor Ø.5 to 2.5 1 DNOTAQ: *DNOTAQ1.5 Product Aries Rev 2.0

DNOTAD, DNOTAF, DNOTBD, DNOTBF, DNOTBQ, DNOTLD, DNOTLG The DNOTAQ command sets the quality factor (Q) for notch filter A. The quality factor, or width of the frequency trough, determines how discrete the filter is. For information about the filter's transfer function characteristics, see DNOTAF.

DNOTBD Notch Filter B Depth

Type Syntax Units Range Default Response See Also Tuning <a_><!>DNOTBD<i> n/a Ø.ØØØØ - 1.ØØØØ .ØØØØ (depth is zero) DNOTBD: *DNOTBD.5 Product Aries Rev 2.0

DNOTAD, DNOTAF, DNOTAQ, DNOTBF, DNOTBQ, DNOTLD, DNOTLG The DNOTBD command sets the depth for the commanded torque/force notch filter B. For information about the notch filter depth, see DNOTAD.

Chapter 6 Command Reference 121

Parker Hannifin

DNOTBF Notch Filter B Frequency

Type Syntax Units Range Default Response See Also Tuning <a_><!>DNOTBF<i> i = Hz Ø (disable), or 6Ø-1ØØØ Ø (filter is disabled) DNOTBF: *DNOTBF2ØØ Product Aries Rev 2.0

DNOTAD, DNOTAF, DNOTAQ, DNOTBD, DNOTBQ, DNOTLD, DNOTLG The DNOTBF command sets the center frequency for notch filter B. Setting this to 0 disables the filter. For a description of the filter's transfer function characteristics, refer to the DNOTAF command description.

DNOTBQ Notch Filter B Quality Factor

Type Syntax Units Range Default Response See Also Tuning <a_><!>DNOTBQ<r> r = quality factor Ø.5 to 2.5 1 DNOTBQ: *DNOTBQ1.5 Product Aries Rev 2.0

DNOTAF, DNOTAQ, DNOTBD, DNOTBF, DNOTLD, DNOTLG The DNOTBQ command sets the quality factor (Q) for notch filter B. The quality factor, or width of the frequency trough, determines how discrete the filter is. For information about the filter's transfer function characteristics, see DNOTAF.

DNOTLD Notch Lead Filter Break Frequency

Type Syntax Units Range Default Response See Also Tuning <a_><!>DNOTLD<i> i = Hz Ø (disable), or 8Ø-1ØØØ Ø (filter is disabled) DNOTLD: *DNOTLD2ØØ Product Aries Rev 2.0

DNOTAD, DNOTAF, DNOTAQ, DNOTBD, DNOTBF, DNOTLG The DNOTLD command sets the break frequency of the lead filter. This filter cannot be used alone, but must be used in conjunction with the DNOTLG lag

122 Aries User Guide

Parker Hannifin

filter. The DNOTLG lag filter must be configured before the DNOTLD lead filter is configured. The DNOTLD value must be less than or equal to 4 times the DNOTLG (notch lag frequency) value; otherwise, the new DNOTLD value will be ignored (but not overwritten), the configuration warning bit (E17) will be set, and the last valid DNOTLD value will be used internally. This warning is cleared with the RESET command or by cycling power to the drive. This filter operates in all DMODE settings, except Autorun (DMODE1). In the graphs below, the transfer function is shown relating the internal commanded torque/force vs. the user commanded torque/force. In this example, the lag frequency was set first to 40 Hz (DNOTLG4Ø) and then the lead filter was set to 160 Hz (DNOTLD).

Figure 47 Notch Lead Filter Break Frequency

DNOTLG Notch Lag Filter Break Frequency

Type Syntax Units Range Default Response See Also Tuning <a_><!>DNOTLG<i> i = Hz Ø (disable), or 2Ø-1ØØØ Ø (filter is disabled) DNOTLG: *DNOTLG4ØØ Product Aries Rev 2.0

DNOTAD, DNOTAF, DNOTAQ, DNOTBD, DNOTBF, DNOTBQ, DNOTLD The DNOTLG command sets the break frequency of the lag filter. This filter can be used alone, or in conjunction with lead filter (DNOTLD) to improve the phase response of the notch filters. In this case, the lag value (DNOTLG) must be greater than or equal to ¼ of the lead value (DNOTLD), but not greater than the DNOTLD value. If DNOTLG is lower than ¼ the value of DNOTLD, the new DNOTLG value is ignored (but not overwritten), the configuration warning bit (E17) is set, and the last valid DNOTLG value is used internally. This warning is cleared with the RESET command or by cycling power to the drive. This filter operates in all DMODE settings, except Autorun (DMODE1).

Chapter 6 Command Reference 123

Parker Hannifin

DPOLE

Type Syntax Units Range Default Response See Also

Number of Motor Pole Pairs

Motor <a_>DPOLE<i> i = pole pairs 1 to 2ØØ Ø (DPOLE of Ø results in motor configuration error) DPOLE: <*>5Ø Product Aries Rev 1.0

DMTR Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. Otherwise, the drive reports the configuration errors E1­Motor Configuration Error and E5­DPOLE = Ø, and shuts down the drive. For a list of automatically configured commands, see DMTR. The DPOLE command sets the number of motor pole pairs. The number of pole pairs is defined as the number of poles (P), divided by 2 (or, P/2). The electrical frequency of the current (e) is related to the mechanical speed (m) of the motor by the pole pairs. The equation (right) shows this relationship.

= e 2 m

P

Note: All linear motors, regardless of the number of stator poles, are considered one pole-pair (DPOLE1) machines.

DPWM

Type Syntax Units Range Default Response See Also

Drive PWM Frequency

Drive Configuration <a_>DPWM <i> i = kHz 16 or 32 (16 only for models AR-20xE and AR-30xE) 16 (use the drive's default frequency) DPWM: <*>16 Product Aries Rev 1.0

STATUS Note: This command does not take effect until you cycle power to the drive, or send the RESET command. Use the DPWM command to select the drive's PWM frequency. This value is the internal PWM frequency as seen at the motor windings; the motor ripple current is twice this frequency. In general, for a given drive power level, the higher the switching frequency, the lower the motor ripple current heating and the lower both the peak and continuous current ratings.

124 Aries User Guide

Parker Hannifin

DRES

Type Syntax Units Range Default Response See Also

Drive Resolution

Drive configuration <a_>DRES<i> i = Input Step Resolution 200 to 10737141823 4000 DRES: <*>0 Product Aries Rev 2.10

CMDDIR, DMPSCL The DRES command is only used in step and direction mode (DMODE6 and 7). Input steps will be scaled to the DRES value so DRES steps on the input would translate to one revolution of the motor. DRES is set to ERES internally if DMPSCL is non-zero for backward compatibility with operating system 2.0. DMPSCL should be set to 0 (a new option in OS 2.10) to enable DRES support. Note: This command requires a reset to take effect. DMPSCL changes are immediate so it is possible to enable DRES support, then enable DMPSCL, and have both features working at once.

DRIVE

Type Syntax Units Range Default Response See Also

Drive Enable

Drive Configuration <a_>DRIVE <b> b = enable bit 1(enable) or Ø(disable) Ø DRIVE: <*>Ø Product Aries Rev 2.0

ERROR The DRIVE command allows you to enable or disable (shut down) the drive. If the hardware enable input is closed on power-up, the drive is automatically enabled (generates a DRIVE1 command). To disable the drive, either issue the DRIVEØ command or open the hardware enable interlock. Conversely, if the hardware enable input is open on power-up, the drive is disabled (DRIVEØ). To enable the drive, close the hardware enable input. To verify the hardware enable input is open, query the ERROR command for E46 ­ Hardware Enable. Note: Issuing a DRIVE1 command from a DRIVEØ condition will set the position error to zero (TPER = Ø). All of these "Fault Conditions" automatically cause a shut down (DRIVEØ), as well as activate the "fault" output and open the dry contact relay ("RELAY N.O."): · Certain axis "fault" conditions ­ refer to the status bits denoted with an asterisk (*) in the ERROR description.

Chapter 6 Command Reference 125

Parker Hannifin ·

If operating in the FLTDSB1 mode and the drive received a DRIVEØ command or the hardware enable input was opened.

DTHERM Thermal Switch Checking

Type Syntax Units Range Default Response See Also motor <a_>DTHERM<b> b = enable bit Ø(enable) or 1(disable) Ø DTHERM: *Ø Product Aries Rev 1.0

DMTSWT The DTHERM command is used to disable drive faults when the motor thermal switch opens. It is useful when no thermal switch is present on the motor. Send the DTHERMØ command to re-enable thermal switch checking.

ECHO

Type Syntax Units Range Default Response See Also

Communication Echo Enable

Communication Interface <a_>ECHO<b> b = enable bit Ø (disable) or 1 (enable) 1 ECHO: <*>1 Product Aries Rev 1.0

ADDR, STATUS The ECHO command enables/disables command echo. If using an RS-485 multi-drop, disable echo. Note: The ECHO command has no obvious effect. You will always see the characters that you type echoed on the screen. Only after you send a command delimiter (carriage return or line feed) is a command line sent to the Aries drive.

ENCFLT Maximum pre-quadrature encoder frequency

Type Syntax Units Range Default Response See Also Drive configuration <a_>ENCFLT<i> None 0 (1.02MHz ), 1 (2.67MHz) or 2(5MHz) 0 ENCFLT: None <*>0 Product Aries Rev 3.0

For increased noise immunity, rotary motors have increased filtering on the encoder input. The maximum input frequency in 1.02 MHz pre-quadrature for

126 Aries User Guide

Parker Hannifin rotary motors by default. If a linear motor is configured, the drive sets a 2.67 MHz pre-quadrature maximum input encoder frequency by default. The ENCFLT command increases the default maximum pre-quadrature encoder frequency from 1.02 MHz to 2.67 MHz or 5 MHz. This allows users to take advantage of the higher input frequency, if necessary, at the expense of some noise immunity. Note: This command does not take effect until you cycle power to the drive or send the RESET command.

ENCOFF Encoder Offset

Type Syntax Units Range Default Response See Also Motor configuration <a_>ENCOFF<i> i = encoder offset -32768 to 32767 0 ENCOFF: <*>0 Product Aries Rev 1.0

ALIGN, ENCPOL, SHALL, IANI, CMDDIR, P163 The ENCOFF command specifies the encoder offset. All standard (non-smart) Parker encoders have an encoder offset of 0 degrees. The smart encoders store the encoder offset in the motor, which the drive reads (and stores in the ENCOFF parameter) upon power-up. The offset can vary from ­180 degrees (corresponding to ENCOFF=-32768) to +180 degrees (corresponding to ENCOFF = 32767). Note: To convert from degrees to counts, just multiply the offset in degrees by 182.044.

ENCPOL Encoder Polarity

Type Syntax Units Range Default Response See Also Drive Configuration <a_>ENCPOL<b> b = polarity bit 0 (normal polarity), 1 (reverse polarity) 0 ENCPOL: <*>0 Product Aries Rev 2.0

ALIGN, CMDDIR, TPE, TPER The ENCPOL command reverses the encoder counting direction. You can reverse the encoder polarity if the encoder input is counting in the wrong direction (for example, using a custom motor). This reverses the encoder counting direction without having to change the actual wiring to the encoder input. Notes · This command does not take effect until you cycle power to the drive or send the RESET command.

Chapter 6 Command Reference 127

Parker Hannifin ·

To reverse the commanded direction of motion, make sure there is a direct correlation between commanded direction and encoder direction. You can then issue the CMDDIR command to reverse both the commanded direction and the encoder direction. The ENCPOL command will not affect the encoder output. If ENCPOL1 is required on the drive for servo stability, the equivalent command will also be required on the controller.

For more information, see CMDDIR. ·

ERES

Type Syntax Units Range Default Response See Also

Encoder Resolution

Encoder Configuration <a_>ERES<i> Rotary motor: i = counts/revolution Linear motor: i = counts/electrical pitch 32 to 1Ø73741823 4ØØØ (4096 for Resolver option) ERES: <*>4ØØØ Product Aries Rev 1.0

DMEPIT, DMTR, TPE Auto-Setup: When using a Parker motor and the Aries Support Tool, this command is automatically set for the selected motor. If you did not use the Aries Support Tool, are using non-Parker motors, or sent an RFS command to the drive, the parameter is set to zero (0)--you must manually set this parameter to a non-zero number. For a list of auto-configured commands, see DMTR. Use the ERES command to establish the encoder resolution (post quadrature) in counts/rev or counts/electrical pitch. (To set a linear motor's electrical pitch, refer to the DMEPIT command). The servo system's resolution is determined by the resolution of the encoder used with the servo motor. The ERES command establishes the number of counts (post quadrature), per unit of travel. For example, Parker's SM and NeoMetric Series motors with the "E" encoder option use 1,000-line encoders, and therefore have a 4,000 count/rev post-quadrature resolution (requires ERES4ØØØ). If the encoder is mounted directly to the motor, the Aries' resolution (ERES value) must match the encoder's resolution to ensure that the motor will move according to the programmed distance and velocity.

Resolutions for Parker Encoders

Servo axes BE Series Servo Motors.......................... BExxxxJ-xxxx: ERES8000 ................................................................ BExxxxL-xxxx: ERES20000 SE, SM, N, or J Series Servo Motors ..... SE/SM/N/JxxxxD-xxxx: ERES2000 ................................................................ SE/SM/N/JxxxxE-xxxx: ERES4000 MPM Series............................................. MPMxxxxxxxxJMxx: ERES4000 ................................................................ MPMxxxxxxxxJNxx: ERES8000

128 Aries User Guide

Parker Hannifin ................................................................ MPMxxxxxxxxJLxx: ERES10000 ................................................................ MPMxxxxxxxxJPxx: ERES12000 ................................................................ MPMxxxxxxxxJQxx: ERES20000 ................................................................ MPMxxxxxxxxJTxx: ERES24000 ................................................................ MPMxxxxxxxxJXxx: ERES4096 ................................................................ MPMxxxxxxxxJYxx: ERES8192 ................................................................ MPMxxxxxxxxJZxx: ERES16384 Note: Motors with the Smart Encoder option set ERES automatically. Changing the ERES value may cause unpredictable motor responses. Note: ERES is fixed at 4096 for Aries drives with Resolver option. Daedal Positioning Tables (encoder options) -E2........................................................... ERES42000 -E3........................................................... ERES84000 -E4........................................................... ERES420000 -E5........................................................... ERES8400 For linear servo motors, use the following equation to determine the proper ERES, based on both the encoder resolution and the motor's electrical (or magnetic) pitch (DMEPIT).

ERES =

DMEPIT (mm) Encoder _ resolution (mm

count )

Example Linear encoder resolution (post quad) is 1 m and the electrical pitch is 42 mm (DMEPIT42). ERES is calculated as:

ERES =

42 (mm) = 42000 1 10 -3 ( mm count )

ERROR

Type Syntax Units Range Default Response See Also

Error-Checking Report-Back

Error Handling <a_>ERROR N/A N/A ERROR: none <*>NO ERRORS Product Aries Rev 1.0

The ERROR command gives a text-based status report of drive errors (E25 through E46) that currently prevent the drive from enabling. To re-enable the drive correct the specified fault, then reset the drive or cycle power to it. Table 46 contains the possible errors appearing in the text-based report and their descriptions.

Chapter 6 Command Reference 129

Parker Hannifin

Error

E25--Excessive Command Voltage at Enable

Description

The command voltage (at the ANI+ terminal) was too high when the drive was enabled. Lower the voltage at the ANI+ terminal. Try using the fault on startup voltage. (FLTSTP) The drive is faulted. Excessive current or short on the H-bridge. Excessive current being commanded: 1. If the application is operating in the peak range, limiting the peak current setting with DMTLIM can limit the current commanded and lower the bridge temperature. Default DMTLIM is 3 x continuous current, perhaps lowering it to 2.5 x continuous current or 2 x continuous current can help. This, however, will limit the motor's available torque, which may increase position error and possibly cause a position error fault. 2. Issue a DIFOLD 1 command. This command enables the "current foldback" feature in the drive. However, a drive in "foldback" mode can limit the motor's available torque, which may increase position error and possibly cause a position error fault. 3. Use a larger Aries amplifier, which would be capable of higher current outputs.

E26--Drive Faulted E27--Bridge Hardware Fault E28-Bridge Temperature Fault

E29--Drive Over-voltage

The bus voltage is too high (>410 VDC). Lower the AC Mains voltage and check for excessive regeneration power. (TVBUS) The bus voltage is too low (<85 VDC) or there is overly aggressive acceleration or deceleration. Raise the AC Mains voltage. (TVBUS) Drive current was limited to prevent overheating (warning only). See DIFOLD. Check the Regeneration resistor for a short. Wait for the drive to cool down. (TDTEMP) The motor thermal model has determined the motor is too hot. Wait for the motor to cool, and then re-enable the drive. (TMTEMP) Motor thermal switch has tripped. Wait for the motor to cool, and then re-enable the drive. (TMTEMP) A problem with the Hall sensors exists. Check the Hall state wiring. (THALL) Feedback not present or the signal level is incorrect. (TPE, THALL) The drive is disabled. (DRIVE) The H-bridge is not switching. The drive regenerated (warning only). Shaft power is limited to the rated output to protect the drive (warning only). The motor was turning too fast when the drive was enabled. Commanded position. Actual Position is greater than the value set by SMPER.

E3Ø--Drive Under-voltage

E31--Bridge Foldback E32--Power Regeneration Fault E34--Drive Temperature Fault E35--Motor Thermal Model Fault E36--Motor Temperature Fault

E37--Bad Hall State E38-Feedback Failure E39--Drive Disabled E4Ø--PWM Not Active E41--Power Regeneration Warning E42-Shaft Power Limited Warning E43-Excessive Speed at Enable E44-Excessive Position Error

130 Aries User Guide

Parker Hannifin

Error

E45-Excessive Velocity Error E46-Hardware Enable E47-Low Voltage Enable E48-Control Power Active E49-Alignment Error E50-Flash Error E51-Resolver Error

Description

Commanded velocity. Actual Velocity is greater than the value set by SMVER. 0 = Hardware Enable (Drive I/O Pin 1 and 21) 1 = No Hardware Enable No motor power was present when the drive was enabled. The drive is in Control power mode. No motor power is present. The ALIGN command did not complete successfully. (TPE, THALL) A problem writing to non-volatile memory exists. (RFS). A problem determining the correct resolver angle exists. Applies to Arxx-xR models only. Check the resolver feedback wiring. The drive determined there was loss of feedback. Check the feedback wiring. (TPE, THALL)

E52-Encoder Loss Fault Table 46 Error StatusText Based Report

ERRORL Error Log Selection

Type Syntax Units Range Default Response Error Handling <a_>ERRORL<b><b>...<b><b> (32 bits) b = enable bit Ø (disable) or 1 (enable) 1111111111111111 ERRORL: <*>ØØØØ_ØØØØ_ØØØØ_ØØØØ bit 15 See Also bit Ø Product Aries Rev 1.0

CERRLG, ERROR, TERRLG Use the ERRORL command to choose the conditions that will be included in the error log. When an error log bit is enabled (ERRORL11...11), the operating system will respond to a specific execution error by making an entry in the error log. Each bit corresponds to a different error condition (see Table 47). To enable or disable a specific bit, the syntax is ERRORL=B.n-b, where "n" is the error bit number and "b" is either one (1) to enable or zero (Ø) to disable. Use the TERRLG command to view the error log. Use the CERRLG command to clear the error log.

Chapter 6 Command Reference 131

Parker Hannifin

Bit

0 1 2 3 4 5 6 7 8 9 10 11 12 13-15

Function

Enable/Disable (Hardware enable input or software DRIVE command) Bridge Fault No PWM output (H-bridge switching) Over Voltage (DC bus) Under Voltage (DC bus) Startup Voltage (analog command voltage) Drive Over Temperature Motor Over Temperature (calculated by thermal model) Motor Thermal Switch Feedback Error Hall Error Motor Configuration Error Regeneration Fault Reserved

Table 47 Error LogEnable/Disable

ESTORE Store smart encoder data

Type Syntax Units Range Default Response See Also Motor configuration <a_>ESTORE N/A N/A 0 <*>Storing <*>Stored Motor configuration commands Product Aries Rev 1.0

The ESTORE command is used to store all relevant motor configuration data to the smart encoder. If changes are made to the motor configuration (for example, if the current loop gains are tuned higher for the application), you can store the changes by typing ESTORE into the terminal and pressing Enter. The drive responds with Storing, and then Stored once the parameters have been stored. After a reset, the new values are read from the encoder. Note: The ESTORE command stores the following parameters in the encoder: DMTD, DMTIC, DMTIND, DMTINF, DMTJ, DMTKE, DMTLIM, DMTR, DMTRES, DMTRWC, DMTSCL, DMTSWT, DMTTCW, DMTTWM, DMTW, DMVLIM, DPOLE, DPWM, DTHERM, ENCOFF, ENCPOL, IGAIN, INTLIM, PGAIN, P163.

132 Aries User Guide

Parker Hannifin

FLTDSB Fault on Drive Disable

Type Syntax Units Range Default Response See Also Drive Configuration <a_>FLTDSB<b> b = enable bit Ø (disable) or 1 (enable) Product Aries Rev 1.0

ERROR, FLTSTP, TOUT Use the FLTDSB command to enable/disable the Fault on Drive Disable mode. If Fault on Drive Disable is enabled (FLTDSB1 ­ default setting), and the drive is disabled via the Enable input, fault output is activated and the brake relay is opened.

FLTSTP

Type Syntax Units Range Default Response See Also

Fault on Excessive Startup Voltage

Drive Configuration <a_>FLTSTP<r> Volts Ø to 1ØV 1ØV FLTSTP: <*>1 Product Aries Rev 1.0

DMODE Use the FLTSTP command to set the threshold for the Fault on excessive startup voltage. The default is 10.00V, so no command input will fault the drive. If the threshold is set lower, a command voltage above this level, when the drive is enabled, will fault the drive. To re-enable the drive without causing a fault, command an input voltage below the set value.

IANI

Type Syntax Units Range Default Response See Also

Invert Analog Input

Drive configuration <a_>IANI<b> b = enable bit 0 (do-not invert analog input) or 1 (invert analog input) 0 IANI <*>0 Product Aries Rev 2.10

ENCPOL, CMDDIR, DCMDZ,TANI Note: This command requires a reset to take effect The IANI command inverts the polarity of the analog input to the drive. This has the effect of reversing any torque or velocity command. It can be useful when using custom wiring during initial setup of the drive.

Chapter 6 Command Reference 133

Parker Hannifin

Sending an IANI1 command inverts the input polarity. In addition, the command TANI reflects this change.

IAUTO

Type Syntax Units Range Default Response See Also

Automatically determine Current Loop Gains

Tuning <a_>IAUTO<b> none 0 (disable) or 1 (enable) 1 IAUTO: <*>1 Product Aries Rev 3.0

PGAIN, IGAIN, DIBW The IAUTO command allows the drive to automatically determine the current loop gains according to the bandwidth set via the DIBW command, and the motor parameters (Resistance and Inductance). This can give improved current loop response compared to using the default gains set by the support tool.

IGAIN

Type Syntax Units Range Default Response See Also

Integral Gain

Tuning <a_>IGAIN none Ø.ØØ to 1ØØ.ØØ 1 IGAIN: <*>1.ØØ Product Aries Rev 1.0

IAUTO, PGAIN, SGI The IGAIN command sets the integral gain of the current loop. High gains can emphasize resonance and system noise, adds to heating of both motor and drive, and increases acoustic noise produced by the motor.

INPOS

Type Syntax Units Range Default Response See Also

Enable In Position Output

Drive Configuration <a_>INPOS<b> b = enable bit Ø (disable) or 1(enable) Ø INPOS: <*>Ø Product Aries Rev 2.0

INPOSDB, INPOSTM Use the INPOS command to replace the Fault output with an In-Position output when using the drive in step & direction modes (DMODES6 and 7). If

134 Aries User Guide

Parker Hannifin the In-Position output is enabled, the output will be active when the motor satisfies the In-Position criteria (as specified by the INPOSDB and INPOSTM commands). To restore the Fault Output functionality, use INPOSØ.

INPOSDB In-Position Deadband

Type Syntax Units Range Default Response See Also Drive Configuration <a_>INPOSDB<i> i = deadband in counts Ø-32767 Ø INPOSDB: <*>Ø Product Aries Rev 2.0

INPOSTM, INPOS, TPER Use the INPOSDB command to specify the deadband in encoder counts for the In-Position command. For the `In-Position' output to be classed active, the position error (as specified by the TPER command) should be less than or equal to this value.

INPOSTM In-Position timeout value

Type Syntax Units Range Default Response See Also Drive Configuration <a_>INPOSTM<i> i = ms 1-1ØØØØ 1 INPOSTM: <*>1 Product Aries Rev 2.0

INPOSDB, INPOS Use the INPOSTM command to specify the time in ms before the In-Position output becomes active when the In-Position deadband criteria is met. The drive must not receive any incoming steps during this time in order for the In-Position output to become active.

LJRAT

Type Syntax Units Range Default Response See Also

System Load-to System Load-to-Rotor/Forcer Inertia/Mass Ratio

Tuning <a_>LJRAT<i> Load to Rotor Inertia Ratio Ø.Ø ­ 1ØØ.Ø Ø.Ø LJRAT: <*>Ø.ØØ Product Aries Rev 2.0

IGAIN, PGAIN

Chapter 6 Command Reference 135

Parker Hannifin

This command is only valid in DMODE4 (velocity mode) and DMODE6 or 7 (position mode). The LJRAT command sets the system's load-to-rotor inertia ratio (rotary motors) or load-to-forcer mass ratio (linear motors). The ratio is expressed in the following equation: · · Rotary Motors-- LJRAT = load inertia / motor rotor inertia (Total system inertia = load inertia + motor rotor inertia) Linear Motors-- LJRAT = load mass / forcer mass (Total system mass = load mass + forcer mass)

OHALL

Type Syntax Units Range

Hall-Only Commutation

Drive configuration <a_>OHALL<i> i = Hall commutation type 0 (sinusoidal commutation) 1 (trapezoidal commutation) 2 (DC Brushed motor commutation) 3 (Z-channel commutation ­ Smart Encoder only) 4 (Hall-less startup) Product Aries Rev 2.10

Default Response See Also

0 OHALL: <*>0

ALIGN, SFB, THALL Note: This command requires a reset to take effect. The OHALL command sets the commutation type. Use OHALL1 to set trapezoidal commutation and OHALL2 for DC brushed motors. DC brushed motors should be wired to motor phases U&W, if they are used. The default is OHALL0 (sinusoidal encoder commutation once the first hall transition has occurred). When using OHALL 1, turn off feedback auto-detection by setting SFB to 2. There are application limitations to observe when using OHALL4 (Hall-less commutation startup). When the Aries drive is enabled with OHALL4 set, the motor is moved slightly in open-loop mode and encoder position is monitored to determine the rotor's position in relation to the stator (or forcer/coil in relation to the magnet track for linear motors). For this reason, OHALL4 will not work in vertical applications or applications with heavy loads and/or high frictional loads. If the motor has trouble turning smoothly with the drive in "auto run" mode (DMODE1), that is a good indication that OHALL4 will be unsuccessful.

136 Aries User Guide

Parker Hannifin

OUTBD

Type Syntax Units Range Default Response See Also

Output Brake Delay

Output <a_>OUTBD<i> milliseconds Ø-1ØØØØ Ø OUTBD: none <*>25Ø Product Aries Rev 1.0

The OUTBD command specifies the amount of time that the brake relay will remain asserted after the current is applied to the motor windings when the drive is enabled. This allows torque to build up in the motor while the fault output is still high. This is important in vertical applications where the motor must be able to support the load before the brake is released.

P163

Type Syntax Units Range Default Response See Also

Hall direction P163

Drive configuration <a_>P163<i> i = hall direction 0 (Halls count 623154623... as encoder counts +ve) 1 (Halls count 326451326... as encoder counts +ve) 0 P163: <*>0 Product Aries Rev 1.0

ENCOFF, SHALL, CMDDIR, ENCPOL, IANI Note: This command does not take effect until you cycle power to the drive, or send the RESET command The P163 command determines the order the Hall sensors count as the encoder counts in a +ve direction. The default, P163=0, specifies that as the encoder counts in a +ve direction that the Hall sensors count 6,2,3,1,5,4,6,... P163=1 specifies that the hall sensors count in the opposite direction as the encoder counts in the +ve direction. This command has the same effect as swapping hall wires A and B to the drive.

Chapter 6 Command Reference 137

Parker Hannifin

PGAIN

Type Syntax Units Range Default Response See Also

Proportional Gain

Tuning <a_>PGAIN<r> None Ø.ØØ to 2ØØ.ØØ 2Ø.ØØ PGAIN: <*>2Ø.ØØ Product Aries Rev 1.0

DIBW, IAUTO, IGAIN The PGAIN command sets the proportional gain of the current loop. High gains can emphasize resonance and system noise, adds to heating of both motor and drive, and increases acoustic noise produced by the motor.

PSET

Type Syntax Units Range Default Response See Also

Establish Absolute Position

Tuning <a_>PSET<r> None -2,147,483,648 to +2,147,483,647 N/A PSET: N/A Product Aries Rev 2.0

TPC, TPE Use the PSET command to offset the current absolute position to establish an absolute position reference. All PSET values entered are in counts. The PSET command will define the present commanded position (TPC) to be the absolute position entered. Example

PSETØ ; Wherever the present actual or commanded position ; happens to be, consider that position to have an ; absolute position of zero.

RESET

Type Syntax Units Range Default Response See Also

Reset

Communication Interface <a_>RESET N/A N/A N/A RESET: (Displays power applied message) Product Aries Rev 1.0

RFS, TREV

138 Aries User Guide

Parker Hannifin

The RESET command affects the Aries drive the same as cycling power, or activating the hardware Reset inputs (pins 18 and 23 on the DRIVE I/O connector). The drive's parameters are retained in non-volatile memory. Note: After sending the RESET command to the Aries, wait until you see the power-applied message before communicating with the Aries.

RFS

Type Syntax Units Range Default Response See Also

Return to Factory Settings

Drive Configuration <a_>RFS N/A N/A N/A N/A Product Aries Rev 1.0

RESET, TDHRS, TREV The RFS command returns all settings to factory default, with the exception of the TDHRS value. A RESET command is automatically sent following this command; therefore, no prompt will be returned. When is the RFS event finished? The RFS process can take several seconds. When RFS is finished, the drive transmits the power-applied message. Recommendation: When finished configuring the drive using the Aries Support Tool, save the configuration file to your personal computer's (PC) hard drive for safekeeping. If, after executing the RFS command, you need to restore the previous configuration, re-download the configuration file and program files to your drive. (Remember to reset the drive to invoke new configuration settings).

SFB

Type Syntax Units Range

Set Feedback Type

Drive configuration <a_>SFB<i> i = feedback source 0 (unknown) 1 (OS 1.0,2.0: Standard Encoder OS2.10 or greater: Auto-Detect) 2 (OS 2.10 or greater: specify Standard Encoder) 3 (OS 3.10 or greater: Resolver option identified) 5 (OS 2.10 or greater: specify Smart Encoder) 6 (OS 2.10 or greater: reserved for absolute encoder) 1 SFB: <*>5 Product Aries Rev 1.0

Default Response See Also

STATUS In operating systems 2.0 or earlier, the SFB value reflected the type of motor that the drive auto-detected. In operating system 2.10 and beyond, you also can set a feedback type with the SFB command.

Chapter 6 Command Reference 139

Parker Hannifin

SFB1 sets auto-detect mode and is the default setting. In auto-detect mode the SFB command reports the detected drive-type upon power-up. If SFB is set to a value other than 1, the drive assumes that type of encoder is attached and does not try to auto-detect the feedback type. In operating system 3.10 and beyond, the Aries Resolver option will report an SFB value of 3. Changing the value will not affect the drive operation and it will return to 3 on power-up.

SGI

Type Syntax Units Range Default Response See Also

Servo Gain Integral

Tuning <a_>SGI<i> i = gain value Ø.ØØ to 1ØØØ.ØØ Ø.ØØ SGI: <*>Ø.ØØ Product Aries Rev 2.0

SGILIM, SGP, SGV, IGAIN This command is only valid in DMODE4 (velocity mode) and DMODE6 or 7 (position mode). Use the Integral Gain (SGI) command to set the gain of the integral term in the control algorithm. The primary function of the integral gain is to reduce or eliminate final position error (e.g., due to friction, gravity, etc.) and improve system accuracy during motion. If a position error exists (commanded position not equal to actual position--see TPER command), this control signal will ramp up until it is high enough to overcome the friction and drive the motor toward its commanded position. If acceptable position accuracy is achieved with proportional gain (SGP), then the integral gain (SGI) need not be used. If the integral gain is set too high relative to the other gains, the system may become oscillatory or unstable. The integral gain can also cause excessive position overshoot and oscillation if an appreciable position error has persisted long enough during the transient period (time taken to reach the position setpoint); this effect can be reduced by using the SGILIM command to limit the integral term windup.

SGILIM

Type Syntax Units Range Default Response See Also

Integral Windup Limit

Tuning <a_>SGILIM<i> i = Limit value Ø to 32767 1 SGILIM: <*>1 Product Aries Rev 2.0

SGI, SGP, SGV This command is only valid in DMODE4 (velocity mode) and DMODE6 or 7 (position mode). If integral control (SGI) is used and an appreciable position

140 Aries User Guide

Parker Hannifin error has persisted long enough during the transient period (time taken to reach the setpoint), the control signal generated by the integral action can end up too high and saturate to the maximum level of the drive's analog control signal output. This phenomenon is called integrator windup After windup occurs, it will take a while before the integrator output returns to a level within the limit of the controller's output. Such a delay causes excessive position overshoot and oscillation. Therefore, the integral windup limit (SGILIM) command is provided for you to set the absolute limit of the integral and, in essence, turn off the integral action as soon as it reaches the limit; thus, position overshoot and oscillation can be reduced.

SGP

Type Syntax Units Range Default Response See Also

Servo Gain Proportional

Tuning <a_>SGP<i> i = gain value Ø.ØØ to 1Ø0Ø.ØØ Ø.6Ø SGP: <*>Ø.6Ø Product Aries Rev 2.0

SGILIM, SGI, SGV, PGAIN This command is only valid in DMODE4 (velocity mode) and DMODE6 or 7 (position mode). SGP allows you to set the gain of the proportional term in the servo control algorithm. The output of the proportional term is proportional to the difference between the commanded position and the actual position read from the feedback device. The primary function of the proportional term is to stabilize the system and speed up the response. It can also be used to reduce the steady state position error. When the proportional gain (SGP) is used alone (i.e., the other gain terms are set to zero), setting this gain too high can cause the system to become oscillatory, under damped, or even unstable.

SGV

Type Syntax Units Range Default Response See Also

Servo Gain Velocity

Tuning <a_>SGV<i> i = gain value Ø.ØØ to 1ØØØ.ØØ 1.4Ø SGV: <*>1.4Ø Product Aries Rev 2.0

SGILIM, SGI, SGP This command is only valid in DMODE4 (velocity mode) and DMODE6 or 7 (position mode). SGV allows you to control the velocity feedback gain in the servo algorithm. Using velocity feedback, the controller's output signal is made proportional to the velocity, or rate of change, of the feedback device position. Since it acts on the rate of change of the position, the action of this

Chapter 6 Command Reference 141

Parker Hannifin term is to anticipate position error and correct it before it becomes too large. This increases damping and tends to make the system more stable. If this term is too large, the response will be slowed to the point that the system is over-damped. Since the feedback device signal has finite resolution, the velocity accuracy has a limit. Therefore, if the velocity feedback gain (SGV) is too high, the errors due to the finite resolution are magnified and a noisy, or chattering, response may be observed.

SGVF

Type Syntax Units Range Default Response See Also

Velocity Feedforward Gain

Tuning <a_><!>SGVF<i> N/A Ø-5ØØ 1ØØ SGVF: *SGVF1ØØ Product Aries Rev 2.0

DMTD, LJRAT Use the SGVF command to set the velocity feedforward gain. Velocity feedforward control improves position tracking performance when the system is commanded to move at constant velocity. The velocity tracking error is mainly attributed to viscous friction. The SGVF value is multiplied by the commanded velocity calculated by the Aries drive's move profile routine to produce an estimated torque command that gets added to the servo control signal. The value is normalized to the current setting of both the motor and load viscous damping terms (DMTD) as shown in the equation below.

Estimated velocity torque =

SGVF value = 100%

DMTD 1 24 velocity command 4 3

Setting SGVF to one (1) theoretically produces zero (0) following errors during the constant velocity portion of a move profile. This assumes that the drive or motor are not being current limited, the values for viscous damping are accurate and the models used for analysis are correct. The value of SGVF can be adjusted from zero to as high as five (5) times (SGVF5) the theoretical value. Example

SGVF2 ; Set velocity feedforward to 200% of theoretical value

142 Aries User Guide

Parker Hannifin

SHALL

Type Syntax Units Range Default Response See Also

Hall Sensor Configuration

Drive Configuration <a_>SHALL<i> i = control option number Ø (do not invert) or 1 (invert) Ø SHALL: <*>Ø Product Aries Rev 1.0

ALIGN, RESET, THALL Note: This command does not take effect until you cycle power to the drive, or send the RESET command. The SHALL command controls the logic sense of the Hall sensors. To invert the sensors, use the SHALL1 command. To check the present value of the Hall sensors, use the THALL command.

SMAV

Type Syntax Units Range Default Response See Also

Maximum Acceleration in Velocity Mode

Tuning <a_>SMAV<i> i = Acceleration in rev/sec2 Ø.ØØ to 1ØØØØ.ØØ 1ØØ.ØØ SMAV: <*>1ØØ.ØØ Product Aries Rev 2.0

DMODE This command is only valid in DMODE4 (velocity mode). SMAV allows you to control the maximum acceleration permitted in velocity mode. Use this command to protect the mechanical systems from overly aggressive velocity changes. This command is scaled by the (ERES) command.

SMPER

Type Syntax Units Range Default Response See Also

Maximum Allowable Position Error

Servo <a_>SMPER<i> i = Feedback device steps Ø to 2,147,483,647 4ØØØ SMPER: <*>4ØØØ Product Aries Rev 2.0

ERES, TPE, TPC, TPER This command is only valid in DMODE6 or 7 (position mode). SMPER allows you to set the maximum position error allowed before an error condition occurs. The position error, monitored once per system update period, is the difference between the commanded position and the actual position as read by the feedback device selected with the last SFB command. When the

Chapter 6 Command Reference 143

Parker Hannifin

position error exceeds the value entered by the SMPER command, an error condition is latched (ERROR bit #44) and the Aries drive issues a shutdown and sets its analog output command to zero volts. The DRIVE1 command reenables the drive, clears ERROR bit #44, and sets the commanded position (TPC) equal to the actual feedback device position (TPE) ­ incremental devices will be zeroed. If the SMPER value is set to zero (SMPERØ), the position error condition is not monitored, allowing the position error to accumulate without causing a fault. When SMPER is set to a non-zero value, the maximum position error acts as the servo system fault monitor; if the system becomes unstable or loses position feedback, the drive detects the resulting position error, shuts down the drive, and sets an error status bit.

SMVER

Type Syntax Units Range Default Response See Also

Maximum Allowable Velocity Error

Servo <a_>SMVER<i> i = Rev/Sec Ø.ØØ to 4ØØ.ØØ Ø.ØØ SMVER: <*>Ø.ØØ Product Aries Rev 2.0

ERES, TPE, TVEL, TVELA, TVER This command is only valid in DMODE4 (velocity mode). SMVER determines the maximum velocity error allowed before an error condition occurs. The velocity error is the difference between the commanded velocity (TVEL) and estimated actual velocity (TVELA). If the error exceeds this value, a fault will result in which the drive is shut down (DRIVEØ) and ERROR bit #45 is set. The DRIVE1 command re-enables the drive, clears ERROR bit #45, and sets TVEL equal to TVELA. You can check the actual velocity error with the TVER command. If the SMVER value is set to zero (SMVERØ), the velocity error condition is not monitored, allowing the velocity error to accumulate without causing a fault.

144 Aries User Guide

Parker Hannifin

STATUS Status (full-text report)

Type Syntax Units Range Default Response Transfer <a_>STATUS N/A N/A N/A STATUS: <*>GENERAL: <*> OS Revision: Aries Revision 1.Ø <*> Power Level: 75ØW <*> Control Power: INACTIVE <*>MOTOR: <*> Motor Name: SM232AE <*> Motor Type: ROTARY <*> Feedback Type: SMART ENCODER <*> Motor Temp: 4ØC <*>DRIVE <*> Drive: DISABLED <*> PWM Frequency: 16 kHz <*> Feedback Resolution: 8ØØØ <*> Drive Temperature: 35C <*> Bus Voltage: 85V Product Aries Rev 1.0

See Also

DMTR, DPWM, ERES, TDTEMP, TMTEMP, TREV, TVBUS The STATUS command provides full-text report of the current drive status. It includes general features such as the OS Revision and Control power mode. Control power mode is active when TVBUS is less than 85 VDC. Additionally, it includes motor parameters and drive status.

TANI

Type Syntax Units Range Default Response See Also

Transfer Analog Input Voltage

Transfer <a_>TANI Volts -1ØV to +1ØV N/A TANI: <*>-4.34 Product Aries Rev 1.0

ANICDB, CMDDIR, DCMDZ, DMTSCL, IANI The TANI command returns the voltage level present at the ANI analog input. The value reported with the TANI command is measured in volts.

Chapter 6 Command Reference 145

Parker Hannifin

TCI

Type Syntax Units Range Default Response See Also

Transfer Commanded Current

Transfer <a_>TCI Amps N/A N/A TCI: <*>5.ØØ Product Aries Rev 1.0

DMTIC, DMTICD, DMTIP, TDICNT, TDIMAX The TCI command reports the commanded motor current in amps (peak of sine).

TDHRS

Type Syntax Units Range Default Response See Also

Transfer Operating Hours

Transfer <a_>TDHRS Lifetime operating hours (resolution is hours) Hour counter rolls over at 536854528 hours N/A TDHRS: <*>16 Product Aries Rev 1.0

RESET, TERRLG The TDHRS command reports the lifetime number of hours that the Aries drive has had power applied (AC mains or Control power).

TDICNT

Type Syntax Units Range Default Response See Also

Transfer Continuous Current Rating

Transfer <a_>TDICNT Amps rms Drive Dependant N/A TDICNT: <*>1Ø Product Aries Rev 1.0

DMTIC, DMTICD, DMTIP, TCI, TDIMAX The TDICNT command reports the continuous current rating of the drive in amps rms.

146 Aries User Guide

Parker Hannifin

TDIMAX

Type Syntax Units Range Default Response See Also

Transfer Maximum Current Rating

Transfer <a_>TDIMAX Amps rms N/A N/A TDIMAX: <*>1Ø Product Aries Rev 1.0

DMTIC, DMTICD, DMTIP, TCI, TDICNT The TDIMAX command reports the maximum current rating of the drive in amps rms.

TDMIN

Type Syntax Units Range Default Response See Also

Transfer Operating Minutes

Transfer <a_>TDMIN Minutes Ø to 59 N/A TDMIN: <*>35 Product Aries Rev 1.0

TDHRS, TDSEC, TERRLG The TDMIN command reports the minutes portion of the lifetime operating hours that the Aries drive has had power applied (AC Mains or Control power).

TDSEC

Type Syntax Units Range Default Response See Also

Transfer Operating Milliseconds

Transfer <a_>TDSEC Milliseconds Ø to 59999 N/A TDSEC: <*>35678 Product Aries Rev 1.0

TDHRS, TDMIN The TDSEC command reports the milliseconds portion of the lifetime operating hours that the Aries drive has had power applied (AC Mains or Control power).

Chapter 6 Command Reference 147

Parker Hannifin

TDTEMP Transfer Drive Temperature

Type Syntax Units Range Default Response See Also Transfer <a_>TDTEMP Degrees Celsius N/A N/A TDTEMP: <*>5Ø Product Aries Rev 1.0

STATUS, TERRLG The TDTEMP reports the measured temperature (internal) of the drive.

TERRLG Transfer Error Log

Type Syntax Units Range Default Response Transfer <a_>TERRLG N/A N/A N/A TERRLG: <*>Operating hours: 1Ø5.25 <*>Power on Time: 5hrs 1Ø min 45.35 s <*>Drive Temp: 35C <*>Motor Temp: 85C <*>Bus voltage: 163V <*>Command Voltage: 5.35V <*>Active Errors: E26-Drive Faulted E27-Bridge Hardware Fault <*>[Power Cycle] Product Aries Rev 1.0

See Also

CERRLG, CONFIG, ERROR, ERRORL, OHALL, TANI, TDHRS, TDMIN, TDSEC, TDTEMP, TMTEMP, TVBUS The error log is updated every time an error occurs or the power is cycled. The TERRLG command displays the last ten error conditions or power cycles. The command displays them in order of earliest to latest, and returns a textbased status report. When each error is logged, the following parameters are saved: · · · · · · · Operating Hours (TDHRS, TDMIN, TDSEC) Power-on Time Drive Temperature (TDTEMP) Motor Temperature (TMTEMP) Bus Voltage (TVBUS) Command Voltage (TANI) Active Errors (ERROR)

The CERRLG command erases the stored contents of the error log. Clearing the error log is a helpful diagnostic tool; it allows you to start the diagnostic process when the error log is in a known state so that you can check the error log in response to subsequent events.

148 Aries User Guide

Parker Hannifin

THALL

Type Syntax Units Range Default Response See Also

Transfer Hall Sensor Values

Transfer <a_>THALL N/A 1 to 6 (Ø or 7 is a fault condition) N/A THALL: <*>6 Product Aries Rev 1.0

ALIGN, SHALL Encoder Motors: The THALL command reports the present Hall sensor value. There are six distinct Hall states, from 1 to 6. Rotating the motor shaft clockwise, the Hall state order should be 6, 2, 3, 1, 5, 4, 6, 2, 3, 1, 5, 4, 6... THALL values Ø and 7 are invalid and will fault the drive, and report E37­Bad Hall State. For a complete description on how to troubleshoot Hall sensors, especially for non-Parker Hannifin motors, see Hall Sensor Configuration/Troubleshooting on page 164. Note: For auto-configured "smart encoders", the THALL only reports the initial hall state of the encoder when power is applied.

TIDAC

Type Syntax Units Range Default Response See Also

Transfer D Quadrature Current

Transfer <a_>TCI Amps N/A N/A TCI: <*>5.ØØ Product Aries Rev 3.10

DMTIC, DMTICD, DMTIP, TDICNT, TDIMAX The TIDAC command reports the actual "d" quadrature motor current in amps (peak of sine).

TIQAC

Type Syntax Units Range Default Response See Also

Transfer Q Quadrature Current

Transfer <a_>TCI Amps N/A N/A TCI: <*>5.ØØ Product Aries Rev 3.10

DMTIC, DMTICD, DMTIP, TDICNT, TDIMAX The TIQAC command reports the actual "q" quadrature motor current in amps (peak of sine).

Chapter 6 Command Reference 149

Parker Hannifin

TMTEMP Transfer Motor Temperature

Type Syntax Units Range Default Response See Also Transfer <a_>TMTEMP Degrees Celsius N/A N/A TMTEMP: <*>45 Product Aries Rev 1.0

DMTRWC, DMTTCM, DMTTCW, STATUS, TERRLG The TMTEMP reports the predicted temperature of the motor winding for Parker motors. The temperature is estimated using the winding and motor time constants, the rated continuous current, and the winding thermal resistance. The motor will fault (and the drive reports E35­Motor Thermal Model Fault) at an estimated winding temperature of 125°C, assuming the ambient temperature is 40°C. In OS 2.10, If DMTSWT equals 3, and the thermal temperature is greater than 60°C, TMTEMP reports the higher of the motor model thermistor temperature or the NTC thermistor temperature. If you are using a non-Parker motor, the TMTEMP value depends on parameters you supply for DMTRWC, DMTTCM and DMTTCW.

TOUT

Type Syntax Units Range Default Response See Also

Transfer Output Status

Transfer <a_>TOUT N/A Ø (inactive) or 1 (active) N/A TOUT: none <*>ØØØØ_ØØØØ_ØØØØ_ØØ11 Product Aries Rev 1.0

The TOUT command returns the present status of the brake relay (bit 1) and fault output (bit 0). Bits 2 through 15 are reserved. The return of one (1) indicates the relevant output is active and a zero (Ø) indicates it is inactive.

150 Aries User Guide

Parker Hannifin

TPC

Type Syntax Units Range Default Response See Also

Transfer Position Commanded

Transfer <a_>TPC Encoder counts -2147483648 to +2147483647 N/A TPC: <*> Ø Product Aries Rev 2.0

ERES, TPE, SMPER This command is only valid in DMODE4 (velocity mode) and DMODE6 or 7 (position mode). This command allows you to display the commanded position. Note: The reported value is measured in commanded counts (AKA: "motor counts").

TPE

Type Syntax Units Range Default Response See Also

Transfer Position of Encoder

Transfer <a_>TPE Encoder counts -2147483648 to +2147483647 N/A TPE: <*> Ø Product Aries Rev 1.0

ERES, TPC, SMPER The TPE command reports the present feedback device position, based on the encoder resolution (ERES).

TPER

Type Syntax Units Range Default Response See Also

Transfer Position Error of Encoder

Transfer <a_>TPER Encoder counts -2147483648 to +2147483647 N/A TPER: <*> Ø Product Aries Rev 2.0

ERES, INPOSDB, TPE, SMPER This command is only valid in DMODE6 or 7 (position mode).The TPER command reports the present position error. The error is reported in feedback device counts and is based on the encoder resolution (ERES). The position error is calculated every 62.5 µs. Note: When the drive is set to DMODE6 or DMODE7, the position error is the difference between the commanded position and the actual position read by

Chapter 6 Command Reference 151

Parker Hannifin

the feedback device. TPER does not apply in DMODE2 (torque/force control mode) and in DMODE4 (velocity control mode); TPER reports zero in these modes.

TREV

Type Syntax Units Range Default Response See Also

Transfer Revision Level

Transfer <a_>TREV N/A N/A N/A TREV: <*>Aries OS Revision 1.Ø Product Aries Rev 1.0

RESET, RFS, STATUS The Transfer Revision Level (TREV) command reports the software revision of the Aries firmware. The Aries Resolver option reflects the Resolver feedback capability by stating `Aries Resolver' in the software revision reportback instead of `Aries'. Updating the drive's operating system: The operating system file is located in the "Support & Downloads" section on the Parker Hannifin Motion Online website (www.parkermotion.com).

TSSPD

Type Syntax Units Range Default Response See Also

Transfer PWM Update Period

Transfer <a_>TSSPD Microseconds N/A N/A TSSPD: <*>62.5Ø Product Aries Rev 1.0

DPWM The TSSPD command reports the current PWM update period in microseconds. This is not the current loop update rate, which is fixed at 62.5 s.

152 Aries User Guide

Parker Hannifin

TTRQ

Type Syntax Units Range Default Response See Also

Transfer Commanded Torque/Force

Transfer <a_>TTRQ Newton Meters (Rotary) or Newtons (Linear) -DMTLIM TO +DMTLIM ± Ø.Ø1 N/A TTRQ: <*>1.2Ø Product Aries Rev 1.0

DMODE, DMTLIM, DMTSCL, TTRQA The TTRQ command reports the commanded motor torque/force.

TTRQA

Type Syntax Units Range

Transfer Actual Torque/Force

Transfer <a_>TTRQA Newton Meters (Rotary) or Newtons (Linear) Rotary motor: Ø.Ø to 5ØØ.Ø (motor/drive dependent): ±Ø.1 Linear motor: DMEPIT (electrical pitch) dependent N/A TTRQA: <*>1.2Ø Product Aries Rev 1.0

Default Response See Also

DMTKE, DMTLIM, DMTSCL, TTRQ The TTRQA command reports the calculated torque/force, based on the motor's current and the motor's Ke. The measured motor's Ke value may vary by ±10%; Therefore, the TTRQA may vary by ±10% of the actual torque at the motor.

TVBUS

Type Syntax Units Range Default Response See Also

Transfer Bus Voltage

Transfer <a_>TVBUS Volts N/A N/A <*>17Ø.45 Product Aries Rev 1.0

ERROR, STATUS The TVBUS command reports the DC bus voltage available from the drive in Volts.

Chapter 6 Command Reference 153

Parker Hannifin

TVEL

Type Syntax Units Range Default Response See Also

Transfer Current Commanded Velocity

Transfer <a_>TVEL Revolutions per second or meters per second N/A N/A TVEL: <*> 1.55 Product Aries Rev 2.0

CMDDIR, DMEPIT, DMVLIM, IANI, TVELA This command is only valid in DMODE4 (velocity mode) and DMODE6 or 7 (position mode). In velocity mode (DMODE4), TVEL reports the commanded ±10V value from the user before any internal limits are checked. In position mode (DMODE6-7), TVEL reports the internal velocity command and is limited by DMVLIM.

TVELA

Type Syntax Units Range Default Response See Also

Transfer Current Actual Velocity

Transfer <a_>TVELA Revolutions per second or meters per second N/A N/A TVELA: <*> 1.55 Product Aries Rev 1.0

CMDDIR, DMEPIT, DMVLIM, IANI The TVELA command reports the velocity as derived from the feedback device. The sign determines the direction of motion. Rotary Motors--Positive values represent clockwise motion and negative values represent counter-clockwise motion (assuming CMDDIR = Ø, and that you connected the feedback device according to instructions provided in "Chapter 2 Mechanical Installation" and "Chapter 3 Electrical Installation").

Figure 48 Clockwise/ Counter-clockwise rotation

154 Aries User Guide

Parker Hannifin

TVER

Type Syntax Units Range Default Response See Also

Transfer Current Commanded Velocity Error

Transfer <a_>TVER Revolutions per second or meters per second N/A N/A TVER: <*> 1.55 Product Aries Rev 2.0

DMEPIT, DMVLIM, TVELA, TVEL This command is only valid in DMODE4 (velocity mode) and DMODE6 or DMODE7 (position mode). In velocity mode (DMODE4), TVEL reports the commanded ±10V value from the user before any internal limits are checked. In position mode (DMODE6-7), TVEL reports the internal velocity command and is limited by DMVLIM.

Chapter 6 Command Reference 155

Chapter 7 Troubleshooting

CHAPTER SEVEN

Troubleshooting

IN THIS CHAPTER

Troubleshooting Guidelines ..................................................................... 157 LEDs ........................................................................................................158 RS-232/485 Communication Problems ................................................... 159 Smart Encoders ....................................................................................... 163 Hall Sensor Configuration/Troubleshooting............................................. 164

Parker Hannifin

Troubleshooting Guidelines

If your system is not functioning properly, try the following steps.

First Troubleshooting Steps (verify LEDs)

· Is the Right LED illuminated? If not, look for problems with AC power. Check the AC power source. Also check connections at the L1, L2, and terminals of the motor mains connector, and at the C1 and C2 terminals of the control mains connector). · Is the Right LED illuminated red? Try to enable the drive by connecting ±5­24 VDC to pin 1 (+), and common (GND) to pin 21 (­) of the DRIVE I/O connector. The right LED should turn green. · Cycle power to the drive (this clears most faults). As the drive powers up, watch the right LED.

Does the LED color change from off to red? Power is reaching the drive, but the drive is not enabling. Does the LED change from off to green? The drive is powered up and enabled--power is not a problem. · Remove all connections to the drive (DRIVE I/O, MOTOR, MOTOR FEEDBACK, and R+/R­), leaving Mains power (L1, L2, and terminals) connected. Apply power to the drive.

Does the Right LED change from off to red? Then a short exists in the disconnected cables. · Check Mains wiring and feedback connections. If these steps do not solve your problem, follow the general troubleshooting procedure outlined below.

General Troubleshooting Procedure

· · · · · Check the LEDs (see "LEDsDrive Status Indicators" on page 158) Launch the Aries Support Tool Verify the RS-232/485 communications are functioning correctly. In the Aries Support Tool, look to the Status Panel to identify problems with the drive. Check for non-Drive problems (problems with other parts of the system)

Detailed procedures for each of these topics are given in the rest of this chapter.

Chapter 7 Troubleshooting 157

Parker Hannifin

LEDsDrive Status Indicators

The drive has two bi-color LEDs. The LED on the left displays yellow or green colors; The LED on the right displays red or green colors. The following tables describe LED illumination states and the conditions they indicate.

Normal Operation

LED­Left Off Yellow Off Yellow Off LED­Right Green Green Red Off Red (flashing) What it means Power on, enabled Power on, regeneration active Power on, disabled­No Fault Power on, boot process Waiting for OS download

Yellow (flashing) Red (flashing) OS download in process Table 22 LED Status Indicator-Normal Operation

Internal Drive Faults

LED­Left Yellows Yellow & 1 Green (flashing) Yellow & 2 Green (flashing) Yellow & 3 Green (flashing) Yellow & 4 Green (flashing) LED­Right Red Red Red Red Red What it means Control power mode active Bridge Fault Feedback Fault Thermal Fault Other Fault Encoder Loss

Yellow & 5 Green (flashing) Red Table 23 LED Status Indicator-Internal Drive Fault

Establish Communications & Verify Drive Configuration

If you cannot enable the drive, and examining LED conditions has not solved your problem, then launch the Aries Support Tool and establish communications with the drive. (For detailed instructions on establishing communications, see "Establishing Communications" on page 74.) If you are unable to establish communications, see "RS-232/485 Communication Problems" on page 159.

Save the Configuration File

Because further troubleshooting steps can change the drive configuration, upload the current drive configuration file, and save it to your personal computer. This ensures you have a backup copy of the drive configuration. To save a backup configuration file, use the Aries Support Tool.

158 Aries User Guide

Parker Hannifin

Reconfigure the Drive

To verify proper configuration, you may wish to reconfigure the drive. Pay particular attention to selecting proper configuration settings for the motor that you have installed, as motor configuration problems can cause a variety of errors. Download the new configuration to the drive; the changes take effect after you send the RESET command or cycle power.

RS-232/485 Communication Problems

If you cannot establish RS-232 or RS-485 communications, the next sections give instructions for procedures to help isolate problems. RS-232 Rx, Tx, Gnd 9600 baud 8 data bits 1 stop bit No parity Full-duplex RS-485 * 2-wire plus ground (Talk+, Talk­, Gnd) 9600 baud 8 data bits 1 stop bit No parity Half-duplex *

Twisted pair cabling recommended (e.g. Belden 9842)

Table 48 Terminal Emulator Configuration for RS-232/485 Communication

Ensure the RS-232 or RS-485 wiring is connected prior to powering up the Aries drive. When applying power, the drive will detect either RS-232 or RS485 and configure accordingly.

Testing the COM Port

Using the Aries Support Tool, you can test COM port connections. Under Communications, select the COM port and then click Test. RS-232 communications might require that you use a null modem cable. For information about connecting to the COM port, see "Establishing Communications" on page 74. Additionally, refer to the pinout diagram for the RS-232/485 connector, also located on page 74.

Chapter 7 Troubleshooting 159

Parker Hannifin

Error Invalid COM port number Unable to open COM port

Resolution Select a different COM port No COM port has been specified, or the COM port is being used by other software. Select a different COM port. Power is not supplied to the drive, the drive is not powered up, the power connection is mis-wired, or the RS-232/485 cable is miswired. Check the drive to verify that the power supply is connected, wired correctly. Then apply power to the drive. Verify the wiring on the RS-232/485 cable.

No response from Aries drive

Incorrect response from Aries drive

A different drive or serial device might be connected to the selected COM port. Verify that an Aries drive is connected to the selected COM port.

OS needs to be downloaded Cycle power and download OS

Download the operating system to the Aries drive. The Aries drive has encountered an error while downloading an operating system. Cycle power to the drive and download the operating system again.

Table 49 Communications Port Errors and Resolutions

Error Messages

If the drive will not enable, you can view full-text reports of the drive configuration (EØ through E24) and drive errors (E25 through E46). In a terminal emulator, type CONFIG or ERROR, depending which information you want to view. You can also view the errors using the Aries Support Tool software. In the Menu, select Status Panel. You can view the errors under Bit Status.

The following is a list of Error messages and a brief corrective action:

160 Aries User Guide

Parker Hannifin

Error

EØ--Motor Configuration Warning E1--Motor Configuration Error

Resolution

The motor rating is too high for the drive, and the drive is using its own limits for safety reasons. One of the motor parameters is set to zero (0). Look at the additional errors to find which parameters are set at zero (0). Refer to your motor specifications for the correct value.

E3--Max Inductance = Ø

This parameter is set to zero (0). To correct the error, you must set a non-zero (0) value. Refer to your motor specifications for the correct value. (DMTIND) This parameter is set to zero (0). To correct the error, you must set a non-zero value. Refer to your motor specifications for the correct value. This parameter is set to zero (0). To correct the error, you must set a non-zero value. Refer to your motor specifications for the correct value. (DPOLE) This parameter is set to zero (0). To correct the error, you must set a non-zero value. Refer to your motor specifications for the correct value. (DMTRES) This parameter is set to zero (0). To correct the error, you must set a non-zero value. Refer to your motor specifications for the correct value. (DMKE) This parameter is set to zero (0). To correct the error, you must set a non-zero value. Refer to your motor specifications for the correct value. (DMTIC) This parameter is set to zero (0). To correct the error, you must set a non-zero value. Refer to your motor specifications for the correct value. (DMTIP) The continuous current of the motor is higher than the continuous current rating of the drive. Use the continuous current rating for the drive. The motor's torque rating is too high for the power level of the drive. Use the drive's torque rating. The peak current of the motor is higher than the peak current rating of the drive. Use the drive's value for peak current. This parameter is set to zero (0). The drive will not enable Velocity or Position Modes. To correct the error, you must set to a non-zero value. Refer to your motor specifications for the correct value. (DMTJ) This parameter is set to zero (0). The drive will not enable Velocity or Position Modes. To correct the error, you must set to a non-zero value. Refer to your motor specifications for the correct value. (DMTD)

E4--Rated Speed = Ø

E5--DPOLE = Ø

E6--Resistance = Ø

E7--Ke = Ø

E8--Continuous Current = Ø

E9--Peak Current = Ø

E1Ø--Continuous Current Too High E11--Torque Rating Too High for Drive E12--Peak Current Too High

E13 - Inertia = Ø

E14 ­ Damping = Ø

Chapter 7 Troubleshooting 161

Parker Hannifin

Error

E15 ­ Notch filter Calc Error.

Resolution

The notch filter settings caused an internal calculation error. The last valid value was used. Try different values for the notch filter parameters. (DNOTAF, DNOTAQ, DNOTBF, DNOTBQ) The lead filter setting (DNOTLD) must be greater than or equal to the lag filter setting. (DNOTLG) The lead filter setting (DNOTLD) must be less than or equal to 4 times the lag filter setting. (DNOTLG) The lag filter setting (DNOTLG) must be greater than or equal to 20 Hz. RESERVED The command voltage (at the ANI+ terminal) was too high when the drive was enabled. Lower the voltage at the ANI+ terminal. Try using the fault on startup voltage. (FLTSTP) The drive is faulted. Excessive current or short on the H-bridge. Excessive current being commanded: 1. If the application is operating in the peak range, limiting the peak current setting with DMTLIM can limit the current commanded and lower the bridge temperature. Default DMTLIM is 3 x continuous current, perhaps lowering it to 2.5 x continuous current or 2 x continuous current can help. This, however, will limit the motor's available torque, which may increase position error and possibly cause a position error fault. 2. Issue a DIFOLD 1 command. This command enables the "current foldback" feature in the drive. However, a drive in "foldback" mode can limit the motor's available torque, which may increase position error and possibly cause a position error fault. 3. Use a larger Aries amplifier, which would be capable of higher current outputs.

E16 ­ Lead < Lag Freq E17 ­ Lead 4* Lag Freq E18 ­ Lag Freq < 2Ø Hz E19­E24 E25--Excessive Command Voltage at Enable

E26--Drive Faulted E27--Bridge Hardware Fault E28-Bridge Temperature Fault

E29--Drive Over-voltage

The bus voltage is too high (>410 VDC). Lower the AC Mains voltage and check for excessive regeneration power. (TVBUS) The bus voltage is too low (<85 VDC) or there is overly aggressive acceleration or deceleration. Raise the AC Mains voltage. (TVBUS) Drive current was limited to prevent overheating (warning only). See DIFOLD. Check the Regeneration resistor for a short. Wait for the drive to cool down. (TDTEMP) The motor thermal model has determined the motor is too hot. Wait for the motor to cool, and then re-enable the drive. (TMTEMP) Motor thermal switch has tripped. Wait for the motor to cool, and then re-enable the drive. (TMTEMP) A problem with the Hall sensors exists. Check the Hall state wiring. (THALL) Feedback not present or the signal level is incorrect. (TPE, THALL)

E3Ø--Drive Under-voltage

E31--Bridge Foldback E32--Power Regeneration Fault E34--Drive Temperature Fault E35--Motor Thermal Model Fault E36--Motor Temperature Fault

E37--Bad Hall State E38-Feedback Failure

162 Aries User Guide

Parker Hannifin

Error

E39--Drive Disabled E4Ø--PWM Not Active E41--Power Regeneration Warning E42-Shaft Power Limited Warning E43-Excessive Speed at Enable E44-Excessive Position Error E45-Excessive Velocity Error E46-Hardware Enable E47-Low Voltage Enable E48-Control Power Active E49-Alignment Error E50-Flash Error E51-Resolver Error

Resolution

The drive is disabled. (DRIVE) The H-bridge is not switching. The drive regenerated (warning only). Shaft power is limited to the rated output to protect the drive (warning only). The motor was turning too fast when the drive was enabled. Commanded position. Actual Position is greater than the value set by SMPER. Commanded velocity. Actual Velocity is greater than the value set by SMVER. 0 = Hardware Enable (Drive I/O Pin 1 and 21) 1 = No Hardware Enable No motor power was present when the drive was enabled. The drive is in Control power mode. No motor power is present. The ALIGN command did not complete successfully. (TPE, THALL) A problem writing to non-volatile memory exists. (RFS). A problem determining the correct resolver angle exists. Applies to Arxx-xR models only. Check the resolver feedback wiring. The drive determined there was loss of feedback. Check the feedback wiring. (TPE, THALL)

E52-Encoder Loss Fault

Table 50 Error Messages

Smart Encoders

Several drive related parameters may need additional configuration: CMDDIR, DCMDZ, and ADDR. If the Aries drive does not initialize correctly when connected to a Smart Encoder (Parker motors only) , check the following: 1. Verify the motor phases are wired correctly. Incorrectly wired motor phases can produce any combination of the following symptoms in the motor: runs backwards; produces low torque, or gets warm. 2. Check that the feedback cables are wired correctly. 3. Apply power to the Aries drive. a. Send the SFB command. It should report 5. If the response is not <*>5, then check the feedback cable (if using a non-Parker cable, check that it is correctly wired). If the cable is correctly wired and connected, the problem might be the encoder. b. Send the THALL command. It should report a number in the range of 1-6, which indicates the phase wires are connected correctly. If the response is Ø or 7, a fault exists. Check the motor phase wiring

Chapter 7 Troubleshooting 163

Parker Hannifin

c. Send the TPE command and turn the motor shaft. Verify the encoder is counting in the correct direction. Turning the shaft clockwise results in positive encoder counts. If not, check the encoder feedback wires and reset the drive. Note: The CMDDIR is fixed for smart encoders. To invert the direction, use IANI1; however, for the ACR9000 do not use IANI1.

Hall Sensor Configuration/Troubleshooting

This section can help resolve a "Bad Hall State" error. Use the Troubleshooting Checklist (below) to determine the cause of the error. This section will assist you in resolving a Hall fault (ERROR bit E37-Bad Hall State). Several problems can cause a Hall fault. The following list will help identify these problems.

Troubleshooting Checklist

1. Does THALL report either 0 or 7? If yes, see Problem 1 or 2, below. 2. Does THALL change if you move the motor by hand? If no, see Problem 2, below. 3. Does THALL have six distinct Hall states from 1 to 6? (No numerical order is necessary.) If no, see Problem 2, below. 4. Does THALL report the six distinct Hall states n times as the rotor turns one revolution, where n is equal to the number of pole-pairs (DPOLE)? (Linear motors: n = pitch) If no, see Problem 2 or 3, below. 5. Does THALL report the Hall state sequence [1, 5, 4, 6, 2, 3, 1...] as the motor turns clockwise? (Clockwise means TPE is increasing when CMDDIR set to zero (0); it is also the direction the motor turns in DMODE1.) If no, see Problem 4, below. 6. Does ERROR report a Hall fault each time the drive is enabled (DRIVE1), even though the Hall state sequence is correct? If yes, see Problem 4, below. 7. Does the Hall fault occur irregularly? If yes, see Problem 5 or 6 below.

Possible Problems

1. No Hall states are seen by the drive. 2. The cable is not connected, or is connected incorrectly (mis-wired). 3. DPOLE or DMEPIT is not set correctly. 4. Either the motor wires or the Hall wires are connected incorrectly. Use Procedure 1 to fix this problem by changing the motor wires. Use Procedure 2 to fix this problem by changing the Hall wires. 5. The Hall wires or the encoder wires may have loose connections, causing intermittent faults.

164 Aries User Guide

Parker Hannifin 6. Noise induced on the Hall signals from routing the motor feedback cable next to high-voltage cables (for example, strapped to motor power cables).

Procedure 1

Use this procedure to connect your motor wires to the Aries. 1. With the motor's feedback cable connected to the Aries drive, randomly connect two motor power wires and slowly apply a positive voltage with respect to the third. Note: A variable low voltage (5 to 24V) current limiting (less than continuous current rating of motor) power supply is preferred. Warning -- This procedure could damage the motor. Slowly increase the voltage until the motor moves. Do not exceed the rated current.

Safety Warning -- High-performance motion control equipment is capable of producing rapid movement and very high forces. Unexpected motion may occur especially during the development of controller programs. KEEP WELL CLEAR of any machinery driven by stepper or servo motors. Never touch any part of the equipment while it is in operation. 2. If THALL reports a 1,, 2, or 4, change SHALL from either 0 to 1 or from 1 to 0. After you change SHALL, reset the drive. 3. Repeat step 1 until THALL reports a value of 6. 4. The wire on the negative voltage or ground is motor wire W. The two wires at the positive voltage are U and V. Now there are two possibilities: a. Connect the motor wires to the terminals. Operate the drive in DMODE1. If the motor does not turn in the clockwise direction, exchange motor wires U and V. Verify that the CMDDIR command is set to zero (0). b. Put positive voltage on motor wire W together with either U or V and put negative voltage or ground on the remaining wire. If THALL reports a value of 3, the wire at the negative voltage is V. If THALL reports a value of 5, the wire at the negative voltage is U.

Figure 49 Hall Connection Diagram

Chapter 7 Troubleshooting 165

Parker Hannifin

Procedure 2

Use this procedure to connect your Hall wires to the Aries. 1. First operate the drive in DMODE1 and verify that the motor turns clockwise. If not, swap any two motor wires. 2. Remove the motor power leads, leaving the feedback cable connected to the Aries drive. Connect motor power wires U and V and slowly apply a positive voltage with respect to W.

Note: A variable low voltage (5-24V) current limiting (less than continuous current rating of motor) power supply is preferred. Warning -- This procedure could damage the motor. Slowly increase the voltage until the motor moves. Do not exceed the rated current.

Safety Warning -- High-performance motion control equipment is capable of producing rapid movement and very high forces. Unexpected motion may occur especially during the development of controller programs. KEEP WELL CLEAR of any machinery driven by stepper or servo motors. Never touch any part of the equipment while it is in operation. 3. If THALL reports a value of 1, 2 or 4, change SHALL from either 0 to 1 or from 1 to 0. After you change SHALL, reset the drive. 4. Change the Hall wires until THALL reports a value of 6. 5. Connect motor wires U and W and slowly apply a positive voltage with respect to V. 6. If THALL does not report a value of 3, change Hall wires B and C. If THALL reports a value of 3, the wires are connected correctly. Table 51 summarizes phase voltages and their corresponding Hall states. Starting with SHALLØ and the phase voltages as shown, the THALL command should report the Hall states that match the "Correct" column. If instead THALL reports Hall states that match the "Use SHALL1" column, enter SHALL1 and reset the drive. The Hall states should now match the "Correct" column. For more information, see Figure 50.

166 Aries User Guide

Parker Hannifin

Phase U V W Correct

Hall State Use SHALL1

­ ­ ­ + + +

­ + + + ­ ­

+ + ­ ­ ­ +

1 5 4 6 2 3

6 2 3 1 5 4

Table 51 Configuring Hall Sensors

Figure 50 illustrates the alignment of phases U, V, and W with Halls 1, 2, and 3 as viewed from the front of the shaft. The illustration assumes the following: · · · · Hall signals that are High equal TRUE signals. Hall 1 is the least significant bit (LSB). Hall 3 is the most significant bit (MSB). There is one hall cycle and one electrical cycle per pole pair on the motor.

Figure 50 Motor Terminal Voltages (back EMF) and Hall Sensor Signals

Chapter 7 Troubleshooting 167

Appendix A Additional Specifications

APPENDIX A

Additional Specifications

IN THIS CHAPTER

Amplifier ................................................................................................... 169 Feedback ................................................................................................. 169 Protective Circuits.................................................................................... 170 Cables...................................................................................................... 173

Parker Hannifin

Amplifier

Control Power: all models.................... 120/240 VAC Single Phase Mains Control Power AR-01xx, AR-02xx, AR-04xx, AR-08xx, and AR-13xx ........................... Single Phase AC Input, 120/240 VAC 16 or 32 kHz switching frequency (motor dependant), pulse-width modulated (PWM) with 3-phase motor output Current Loop Update Rate...................... 62.5 s Velocity and Position Loop...................... 250 s AR-20xE and AR-30xE ........................... Single or Three Phase AC Input (AR-30xE is three phase only) 240 VAC 16 kHz switching frequency, pulse-width modulated (PWM) with 3-phase motor output Current Loop Update Rate...................... 62.5 s Velocity and Position Loop...................... 250 s

Feedback

Encoder................................................... Differential Quadrature Encoder Encoder Accuracy................................... ±1 encoder count; encoder dependent Resolver .................................................. Single Speed Resolver Accuracy .................................. ±11 arc minutes (12-bit A to D) Resolver Excitation ................................. 10 KHz Transformation Ratio .............................. 0.5 Maximum Pulse Input/Output Frequency .......................... 5 MHz (5V TTL Only)

Appendix A Additional Specifications 169

Parker Hannifin

Protective Circuits

Short Circuit Protection

The Aries drive has an internal circuit that protects it from short circuits between one motor terminal to another (phase to phase), or from any motor terminal to earth. Short Circuit Fault--Cause ..................... Phase-to-phase short circuit Phase-to-earth short circuit Results of Fault ....................................... Power to motor is turned off Fault output is activated

LED Left Yellow & 1 Green (blinking) LED Right Red

Table 52 LED Short Circuit Fault

Resetting the fault

To clear the latched fault, choose one of the following methods: Cycle power to the Aries drive. ­or­ Open the Aries Support Tool. Then select Operating System Update from the menu and click Reset Drive.

Drive Over-Temperature Protection

The Aries drive's over-temperature circuit monitors the drive's internal temperature. If the sensors exceed the threshold temperature, the drive issues an over-temperature fault. Threshold Temperature AR-01xx, AR-02xx, AR-04xx, AR-08xx, and AR-13xx ........................... 80°C (176°F) AR-20xE and AR-30xE ........................... 90°C (194°F) Results of Fault ....................................... Power to motor is turned off Fault output is activated

LED Left Yellow & 3 Green (blinking) LED Right Red

Table 53 LED Drive Over-Temperature Fault

170 Aries User Guide

Parker Hannifin

Resetting the fault

After the internal temperature has dropped below the values shown in Table 54, you can clear the latched fault. There are two methods available: Cycle power to the Aries drive. ­or­ Open the Aries Support Tool. Then select Operating System Update from the menu and click Reset Drive.

Model

Reset Temperature 75°C (167°F) 85°C (185°F)

AR-01xx, AR-02xx, AR-04xx, AR-08xx, and AR-13xx AR-20xE and AR-30xE

Table 54 Reset Temperature Values

Under-Voltage Protection

The Aries drive's under voltage protection circuit monitors AC input voltage. If the voltage falls below a specific value while the drive is operating, the drive issues an under-voltage fault and turns off power to the motor output terminals (MOTOR connector). This allows the motor to freewheel to a stop. Warning -- When an under-voltage protection fault occurs, the drive disables power to its motor output terminals on the Motor connector. This cuts all control to the motor and allows the load to freewheel to a stop.

Threshold Voltage AR-01xx, AR-02xx, AR-04xx, AR-08xx, and AR-13xx ........................... Voltage below 70 VAC trips fault AR-20xE and AR-30xE ........................... Voltage below 160 VAC trips fault Results of Fault ....................................... Power to motor is turned off Fault output is activated

LED Left Yellow LED Right Red

Table 55 LED Under-Voltage Fault

Resetting the fault

To clear the latched fault, choose one of the following methods: Cycle power to the Aries drive. ­or­ Open the Aries Support Tool. Then select Operating System Update from the menu and click Reset Drive.

Appendix A Additional Specifications 171

Parker Hannifin

Over-Voltage Protection

The Aries drive's over-voltage circuit protects the drive from excessive regeneration. If the voltage on the motor output terminals rises above the threshold voltage, the drive issues an over-voltage fault and turns off power to the motor output terminals (Motor connector). This allows the motor to freewheel to a stop. Warning -- When an over-voltage protection fault occurs, the drive disables power to its motor output terminals on the Motor connector. This cuts all control to the motor and allows the load to freewheel.

Threshold Voltage All Models................................................ 410 VDC Results of Fault ....................................... Power to motor is turned OFF Fault output is activated

LED Left Yellow & 4 Green (blinking) LED Right Red

Table 56 LED Over-Voltage Fault

Resetting the fault

To clear the latched fault, choose one of the following methods: Cycle power to the Aries drive. ­or­ Open the Aries Support Tool. Then select Operating System Update from the menu and click Reset Drive.

Warning -- Over-voltage protection monitors only the motor output terminals (DC motor bus). It does not protect against an over voltage on the AC input terminals, which can permanently damage the drive.

172 Aries User Guide

Parker Hannifin

Current Foldback

The Aries drive's current foldback circuit helps to protect the drive from damage due to prolonged high currents. If your Drive is operating above its continuous current rating, see Figure 51 to predict the number of seconds until foldback will occur. For example, the figure shows that at the Aries drive's peak current rating (250% of continuous), foldback will occur after six seconds. After operating at the drive's peak current, the drive will reduce the drive current to 80% of the drive's continuous rating for 60 seconds. This is to ensure the drive's average continuous current rating is not exceeded.

Figure 51 Time until current foldback occurs

Cables

EMC Ready Cables

Many Parker cables are EMC installation ready. If installed according to instructions provided under "A Highly-Immune, Low-Emission Installation ­ Meeting the Requirements of the Electromagnetic Compatibility (EMC) Directive" on page 192, these cables are designed to aid the user in gaining European Compliance, and are thus an integral part of a CE system solution. EMC cables add RF screening and bonding to reduce emissions, increase immunity, and provide high integrity safety Earth bonding. They also help to reduce problems in high electrical noise environments.

Non-EMC Cables

Parker also offers non-EMC cables, for applications where CE compliance is not required, and where ambient electrical noise does not cause problems. Because these cables are either unshielded, or contain simple foil shielding terminated by a drain wire, they do not provide significant shielding of electrical noise at high frequencies.

Appendix A Additional Specifications 173

Appendix B External Power-Dump Resistor Selection

APPENDIX B

External Power-Dump Resistor Selection

IN THIS CHAPTER

Simplified Resistor Selection ................................................................... 175 Calculating Resistance--Rotary Motors.................................................. 177 Resistor Specifications ............................................................................ 181 Calculating Resistance--Linear Motors .................................................. 183 Resistor Specifications ............................................................................ 187

Parker Hannifin

External Power-Dump Resistor Selection

Deceleration generates excess kinetic and potential energy. You can remove the energy through regeneration--a process where the motor acts as generator. Regeneration allows you to transfer the excess energy from the motor and load back to the power supply. When the drive and assorted losses cannot remove all the stored kinetic energy, you must connect an external power-dump resistor. Connecting an external power-dump resistor to the Aries drive helps dissipate the excess kinetic and potential energy. While the Aries drive contains circuitry to control an external power dump resistor, resistor selection depends on the requirements of your particular application. There are two methods for selecting the appropriate external power-dump resistor: · · "Simplified Resistor Selection" provides quick recommendations for Parker drive and motor combinations. "Calculating Resistance--Rotary Motors" steps you through the relevant formulas to determine the needs of your particular application.

Note: Both methods assume regeneration occurs during a trapezoidal move. Important -- It is possible to overload an Aries drive or the combination of an Aries drive and power dump resistor. If at the end of the calculations you find the required resistor is less than allowed for your specific Aries model, or requires a watt rating greater than the rated resistors available, do not use the Aries drive in your application. Aries drive models AR-01xx, AR-02xx, AR-04xx, AR-08xx, and AR-13xx, require external resistance values of 22 Ohms or greater. Aries drive models AR-20xE and AR-30xE require external resistance values of 8 Ohms or greater

Simplified Resistor Selection

Many applications do not require a power-dump resistor because the drive can absorb or dissipate the regenerative deceleration energy. However, if a drive faults from over-voltage during a deceleration event, an external power dump resistor is probably required. Table 57 contains recommended power-dump resistors for specific Aries drive and Parker Hannifin motor combinations. The recommendations are based on the calculations presented in the section titled "Calculating Resistance--Rotary Motors". These recommendations assume a worst-case load-to-rotor inertia ratio of 10 to 1, maximum duty cycle and maximum deceleration from maximum velocity for that specific motor/drive pairing. These are recommendations only--while not optimized for your particular application, they will work in most situations.

Appendix B External Power-Dump Resistor Selection 175

Parker Hannifin

Drive

AC Voltage

Motor

Resistor Rating (Resistance --Ohms) 100

Resistor rating (Continuous Power-- Watts) 100

Isotek Part Number

AR-01xx

120 240

SM162Z BE164B SM162Z SM161A

BRK-100R-10-L2, 4 See note1 See note1 See note1 See note1 See note1

120 AR-02xx

SM162A SM230A SM231A SM232A 47 47 200 200

BRM-47R0-10-L2, 4 BRM-47R0-10-L2, 4 See note1 See note1

240

BE230D BE231D SM233A 47 200

BRM-47R0-10-L2, 4 See note1 See note1 See note1 See note1 See note1 See note1 See note1 See note1

AR-04xx

240

BE232D BE233D BE233F BE230F

120

BE231F BE232F

AR-08xx 240

BE341F BE342H NO702F NO703F NO704F BE344L 22 22 22 22 22 22 8 8 8 8 8 8 300 300 300 300 300 300 800 1100 1100 1800 1800 1800

BRQ-22R0-10-L2, 4 BRQ-22R0-10-L2, 4 BRQ-22R0-10-L2, 4 BRQ-22R0-10-L2,3,4 BRQ-22R0-10-L2,3,4 BRQ-22R0-10-L2,3,4 IRP20008R0J2, 4 IRP30008R0J2, 4 IRP30008R0J2, 4 IRP60008R0J2, 4 IRP60008R0J2, 4 IRP60008R0J2, 4

AR-13xx

240

MPM1141ASG SMN1002S2F-KPN 1141BSG

AR-20xE

240

1142BSG 1421BSG 1142ASG

AR-30xE

240

1143ASG 1901BSG

1. External power dump resistor not needed. However, higher operating voltage, higher load to rotor inertia ratio, and higher duty cycles can increase the need. 2. Higher friction loads, lower speeds, lower deceleration rates, lower load to rotor inertia ratio, and lower duty cycles can decrease the need for this resistor. 3. Minimum resistance allowed for AR-13 is 22 Ohms, therefore the maximum deceleration rate and/or duty cycle may need to be reduced. 4. Isotek resistor or equivalent Table 57 Simplified Selection of External Power-Dump Resistor

176 Aries User Guide

Parker Hannifin

Calculating Resistance--Rotary Motors

Because there are different types of motion profiles and application specific conditions, you may need to modify the results to suit your particular application. To keep it simple, the formulas assume a trapezoidal move profile, in which the deceleration event is a single constant deceleration to zero (0) velocity. For other motion profiles, you can modify the basic concepts presented below. Calculating the amount of energy to dissipate requires the motion profile parameters, and the motor, drive, and load information. While significantly more information is required, the calculations help tailor the size of powerdump resistor to your application. This is a multi-step process: 1. Calculate the motor's kinetic energy. 2. Calculate the motor's potential energy--vertical applications only. 3. Calculate the energy that can be absorbed by the drive capacitors 4. Calculate energy dissipated in the motor winding resistance 5. Calculate energy dissipated in load 6. Using the results from the previous four calculations, calculate the amount of energy to dissipate through an external power-dump resistor. With that result, you can then calculate the resistor necessary to dissipate the excess energy.

Total Kinetic Energy

A body in motion produces energy. To stop motion, that energy must be absorbed or dissipated elsewhere. That energy can be defined in terms of inertia and velocity.

EK =

Where EK = JM = JL = =

1 2

(J M

+ J L ) 2

rotational kinetic energy (Joules) rotor inertia in kilogram meter squared (kgm2) load inertia in kilogram meter squared (kgm2) rotational speed in radians per sec (1 revolution/sec = 2radians/sec)

Total Potential Energy

A body at rest stores energy relative to the position of the body. When the body moves, the potential energy is released and translated into kinetic energy. For purely horizontal applications, potential energy is negligible and therefore not necessary for inclusion in your calculations. However, for vertical applications, potential energy can greatly affect the selection of power dump resistor. Regardless whether the incline is gentle or steep, it is important to calculate the potential energy that must be absorbed or dissipated elsewhere.

Appendix B External Power-Dump Resistor Selection 177

Parker Hannifin

Ep = mgh

Where Ep = m= g= h= potential energy (Joules) mass of forcer and load (kg) gravitational constant (9.81 m/s2) vertical height change during deceleration (m)

Energy Absorbed by Drive Capacitors

The Aries drive's capacitors can store energy. With motor deceleration, the drive capacitors absorb some of the kinetic and potential energy. While the capacitors absorb energy, the bus voltage increases. Later, the capacitors release that potential energy in subsequent accelerations, or into typical drive losses. If too much energy is absorbed by the capacitors, the Aries drive faults from over-voltage. Under these circumstances, an external power dump resistor is required. That ability to absorb energy can be defined in terms of capacitance and voltage.

Where EC = C=

1 2 2 EC = C (VTRIP - VNOM ) 2

energy that can be absorbed by the drive capacitors (Joules) drive capacitance (Farads)

VTRIP = power dump trip DC voltage (400 VDC for Aries drives) VNOM = nominal DC motor voltage (typically AC mains voltage at 2 ; for example, 120 VAC * 2 = 170 VDC) Fortunately, for a given drive the capacitance and voltages are fixed. Table 58 provides the needed information and results from the above calculation.

178 Aries User Guide

Parker Hannifin

Drive AR-01xx AR-02xx AR-04xx AR-08xx AR-13xx AR-20xE AR-30xE

Capacitance (uF)

VTRIP (VDC)

EC (120 VAC) Joules

EC (240 VAC) Joules

440 660 880 1100 1590 2240 2240

400 400 400 400 400 400 400

28 43 57 72 104 N/A N/A

9 14 19 24 35 50 50

When the voltage drops below 385 VDC, the Aries drive stops dissipating power through the power dump resistor. Table 58 Drive Capacitor Absorption

Energy Dissipated in Motor Winding Resistance

Some energy is dissipated in the motor windings. Because the energy is converted to wasted heat in the motor, it is referred to as copper losses. The energy during deceleration can be derived from the inertia, deceleration rate, motor resistance, and motor torque constant. If some of the parameters are not known, the energy dissipated in the motor windings (EW) can conservatively be assumed zero (0). This is based on current and motor winding resistance.

1 1 (J + J L ) RM t D EW = I 2 RM t D = M kT t D 2 2

2

Where EW = I= RM = tD = JM = JL = kT = = energy dissipated in the motor windings (Joules) ­ copper losses current through the windings (Ampsrms) line to line motor resistance (Ohms) deceleration time (Seconds) rotor inertia (kgm2) load inertia (kgm2) motor torque constant (Nm/Amprms) rotational speed in radians per sec (1 revolution/sec = 2radians/sec)

Appendix B External Power-Dump Resistor Selection 179

Parker Hannifin

Energy Dissipated in Load

The load dissipates energy through friction losses, viscous damping, and other motor/load related losses. These losses are known as load losses. If some of the parameters are not known, the energy dissipated in the load (EL) can conservatively be assumed zero (0). This can be derived from the torque required during the constant velocity portion of the move profile, either measured or calculated.

Where EL = T= = tD =

1 E L = T t D 2

energy dissipated by the load (Joules) ­ load losses torque at constant velocity (Nm) rotational speed in radians per sec (1 revolution/sec = 2radians/sec) deceleration time (Seconds)

Energy to Dissipate in the External Power-Dump Resistor

To stop a motor, kinetic and potential energy must go somewhere. Through the previous calculations, you have determined the total kinetic and potential energy, and the energy lost to various paths. From the total kinetic and potential energy, subtract the energy dissipated through the drive capacitors, motor windings, and load loss. If the copper losses (EW) or load losses (EL) are not easily determined, you can conservatively assume they are zero (0). The resulting sum represents the power for dissipation in an external power dump resistor.

E R = E K + E P - EC - EW - E L

Where ER = EK = EP = EC = EW = EL = energy to be dissipated in the external resistor (Joules) rotational kinetic energy (Joules) potential energy (Joules) energy that can be absorbed by the drive capacitors (Joules) energy dissipated in the motor windings (Joules) ­ copper losses energy dissipated by the load (Joules) ­ load losses

180 Aries User Guide

Parker Hannifin

Resistor SpecificationsRotary Motors

Having determined the amount of energy to dump (ER), you can then calculate the resistor specifications. · · · Maximum resistance Peak dissipation Average dissipation

Maximum Resistance

This calculation determines the maximum value of resistance needed for the external power-dump resistor. We recommend that you select a lower value resistance, typically in the 22 to 100 ohm range.

Important -- It is possible to overload an Aries drive or the combination of an Aries drive and power dump resistor. If at the end of the calculations you find the required resistor is less than allowed for your specific Aries model, or requires a watt rating greater than the rated resistors available, do not use the Aries drive in your application. Aries drive models AR-01xx, AR-02xx, AR-04xx, AR-08xx, and AR-13xx, require external resistance values of 22 Ohms or greater. Aries drive models AR-20xE and AR-30xE require external resistance values of 8 Ohms or greater

RR =

Where RR = V= I=

V VTRIP kT t D = I (J M + J L )

maximum external power dump resistance (Ohms) voltage across the resistor (VTRIP) current through the resistor (drive current required to decelerate the load)(Ampsrms) motor torque constant (Nm/Amprms) rotor inertia (kgm2) load inertia (kgm2) deceleration time (Seconds) rotational speed in radians per sec (1 revolution/sec = 2radians/sec)

VTRIP = power dump trip DC voltage (400 volts for Aries drives) kT = JM = JL = tD = =

Appendix B External Power-Dump Resistor Selection 181

Parker Hannifin

Peak Dissipation

During a single deceleration, all the calculated power-dump energy (ER) must dissipate in the external resistor. The external power-dump resistor then slowly dissipates that energy as heat. This peak power must not exceed the capabilities of the resistor, which is typically 10 times the average power rating.

PPEAK =

Where

ER tD

PPEAK= peak power into the external power dump resistor (Watts) ER = tD = energy to be dissipated in the external resistor (Joules) deceleration time (Seconds)

Average Dissipation

Repetitive moves need to dump the energy each time the deceleration occurs. The duty cycle of this repetition determines the average power the resistor must dissipate. This average power must not exceed the capabilities of the resistor. Power resistors are rated based on ideal heatsink and airflow conditions, and are therefore often over-rated by the manufacturers. To ensure the average energy dissipation of the resistor exceeds the average power dump for the application, the regenerative power should never exceed 50% of the resistor's average power rating.

PAVG = PPEAK

Where

tD tC

PAVG = average power into the external power dump resistor (Watts) PPEAK = peak power into the external power dump resistor (Watts) tD = tC = deceleration time (Seconds) cycle time or time between each deceleration event (Seconds)

Important -- Under normal operation the external power-dump resistor could operate in excess of 200 °C. Keep the resistor away from thermally sensitive components, such as cables or plastic hardware. Proper installation may require the use of thermal compound and proper thermal connection to a heat absorbing metal surface.

182 Aries User Guide

Parker Hannifin

Calculating Resistance--Linear Motors

Because there are different types of motion profiles and application specific conditions, you may need to modify the results to suit your particular application. To keep it simple, the formulas assume a trapezoidal move profile, in which the deceleration event is a single constant deceleration to zero (0) velocity. For other motion profiles, you can modify the basic concepts presented below. Calculating the amount of energy to dissipate requires the motion profile parameters, and the motor, drive, and load information. While significantly more information is required, the calculations help tailor the size of powerdump resistor to your application. This is a multi-step process: 1. 2. 3. 4. 5. Calculate the motor's kinetic energy. Calculate the motor's potential energy--vertical applications only. Calculate the energy that can be absorbed by the drive capacitors Calculate energy dissipated in the motor winding resistance Calculate energy dissipated in load

6. Using the results from the previous four calculations, calculate the amount of energy to dissipate through an external power-dump resistor. With that result, you can then calculate the resistor necessary to dissipate the excess energy. Total Kinetic Energy A body in motion produces energy. To stop motion, that energy must be absorbed or dissipated elsewhere. That energy can be defined in terms of mass and velocity.

EK =

Where EK = MF = ML = v=

1 2

(M F

+ M L )v 2

rotational kinetic energy (Joules) mass of forcer in kilograms (kg) mass of load in kilograms (kg) velocity in meters per second (m/s)

Total Potential Energy

A body at rest stores energy relative to the position of the body. When the body moves, the potential energy is released and translated into kinetic energy. For purely horizontal applications, potential energy is negligible and therefore not necessary for inclusion in your calculations. However, for vertical applications, potential energy can greatly affect the selection of power dump resistor. Regardless whether the incline is gentle or steep, it is important to calculate the potential energy that must be absorbed or dissipated elsewhere.

Appendix B External Power-Dump Resistor Selection 183

Parker Hannifin

Ep = mgh

Where Ep = m= g= h= potential energy (Joules) mass of forcer and load (kg) gravitational constant (9.81 m/s2) vertical height change during deceleration (m)

Energy Absorbed by Drive Capacitors The Aries drive's capacitors can store energy. With motor deceleration, the drive capacitors absorb some of the kinetic and potential energy. While the capacitors absorb energy, the bus voltage increases. Later, the capacitors release that potential energy in subsequent accelerations, or into typical drive losses. If too much energy is absorbed by the capacitors, the Aries drive faults from over-voltage. Under these circumstances, an external power dump resistor is required. That ability to absorb energy can be defined in terms of capacitance and voltage.

1 2 2 EC = C (VTRIP - VNOM ) 2

Where EC = C= energy that can be absorbed by the drive capacitors (Joules) drive capacitance (Farads) power dump trip DC voltage (400 VDC for Aries drives) nominal DC motor voltage (typically AC mains voltage at 2 ;

VTRIP = VNOM =

for example, 120 VAC * 2 = 170 VDC) Fortunately, for a given drive the capacitance and voltages are fixed. Table 59 on page 185 provides the needed information and results from the above calculation.

184 Aries User Guide

Parker Hannifin

Drive AR-01xx AR-02xx AR-04xx AR-08xx AR-13xx AR-20xE AR-30xE

Capacitance (uF)

VTRIP (VDC)

EC (120 VAC) Joules

EC (240 VAC) Joules

440 660 880 1100 1590 2240 2240

400 400 400 400 400 400 400

28 43 57 72 104 N/A N/A

9 14 19 24 35 50 50

When the voltage drops below 385 VDC, the Aries drive stops dissipating power through the power dump resistor. Table 59 Drive Capacitor Absorption

Energy Dissipated in Motor Winding Resistance

Some energy is dissipated in the motor windings. Because the energy is converted to wasted heat in the motor, it is referred to as copper losses. The energy during deceleration can be derived from the mass, deceleration rate, motor resistance, and motor force constant. If some of the parameters are not known, the energy dissipated in the motor windings (EW) can conservatively be assumed zero (0). This is based on current and motor winding resistance.

EW

Where EW = I= RM = tD = MF = ML = kF =

1 1 (M F + M L ) v RM t D = I 2 RM t D = kF tD 2 2

2

energy dissipated in the motor windings (Joules) ­ copper losses current through the windings (Ampsrms) line to line motor resistance (Ohms) deceleration time (Seconds) mass of forcer in kilograms (kg) mass of load in kilograms (kg) motor force constant (N/Amprms)

Appendix B External Power-Dump Resistor Selection 185

Parker Hannifin

Energy Dissipated in Load

The load dissipates energy through friction losses, viscous damping, and other motor/load related losses. These losses are known as load losses. If some of the parameters are not known, the energy dissipated in the load (EL) can conservatively be assumed zero (0). This can be derived from the force required during the constant velocity portion of the move profile, either measured or calculated.

EL =

Where EL = F= v= tD =

1 F v tD 2

energy dissipated by the load (Joules) ­ load losses force at constant velocity in Newtons (N) velocity in meters per second (m/s) deceleration time (Seconds)

Energy to Dissipate in the External Power-Dump Resistor To stop a motor, kinetic and potential energy must go somewhere. Through the previous calculations, you have determined the total kinetic and potential energy, and the energy lost to various paths. From the total kinetic and potential energy, subtract the energy dissipated through the drive capacitors, motor windings, and load loss. If the copper losses (EW) or load losses (EL) are not easily determined, you can conservatively assume they are zero (0). The resulting sum represents the power for dissipation in an external power dump resistor.

E R = E K + E P - EC - EW - E L

Where ER = EK = EP = EC = EW = EL = energy to be dissipated in the external resistor (Joules) rotational kinetic energy (Joules) potential energy (Joules) energy that can be absorbed by the drive capacitors (Joules) energy dissipated in the motor windings (Joules) ­ copper losses energy dissipated by the load (Joules) ­ load losses

186 Aries User Guide

Parker Hannifin

Resistor SpecificationsLinear Motors

Having determined the amount of energy to dump (ER), you can then calculate the resistor specifications. · Maximum resistance · · Peak dissipation Average dissipation

Maximum Resistance

This calculation determines the maximum value of resistance needed for the external power-dump resistor. We recommend that you select a lower value resistance, typically in the 22 to 100 ohm range. Important -- It is possible to overload an Aries drive or the combination of an Aries drive and power dump resistor. If at the end of the calculations you find the required resistor is less than allowed for your specific Aries model, or requires a watt rating greater than the rated resistors available, do not use the Aries drive in your application. Aries drive models AR-01xx, AR-02xx, AR-04xx, AR-08xx, and AR-13xx, require external resistance values of 22 Ohms or greater. Aries drive models AR-20xE and AR-30xE require external resistance values of 8 Ohms or greater

RR =

Where RR = V= I=

V VTRIP k F t D = I (M F + M L ) v

maximum external power dump resistance (Ohms) voltage across the resistor (VTRIP) current through the resistor (drive current required to decelerate the load)(Ampsrms) motor force constant (N/Amprms) mass of forcer in kilograms (kg) load mass in kilograms (kg) deceleration time (Seconds) velocity in meters per second (m/s)

VTRIP = power dump trip DC voltage (400 volts for Aries drives) kF = MF = ML = tD = v=

Peak Dissipation

During a single deceleration, all the calculated power-dump energy (ER) must dissipate in the external resistor. The external power-dump resistor then slowly dissipates that energy as heat. This peak power must not exceed the capabilities of the resistor, which is typically 10 times the average power rating.

Appendix B External Power-Dump Resistor Selection 187

Parker Hannifin

PPEAK =

Where PPEAK= ER = tD =

ER tD

peak power into the external power dump resistor (Watts)

energy to be dissipated in the external resistor (Joules) deceleration time (Seconds)

Average Dissipation

Repetitive moves need to dump the energy each time the deceleration occurs. The duty cycle of this repetition determines the average power the resistor must dissipate. This average power must not exceed the capabilities of the resistor. Power resistors are rated based on ideal heatsink and airflow conditions, and are therefore often over-rated by the manufacturers. To ensure the average energy dissipation of the resistor exceeds the average power dump for the application, the regenerative power should never exceed 50% of the resistor's average power rating.

PAVG = PPEAK

Where PAVG = PPEAK = tD = tC =

tD tC

average power into the external power dump resistor (Watts) peak power into the external power dump resistor (Watts)

deceleration time (Seconds) cycle time or time between each deceleration event (Seconds)

Important -- Under normal operation the external power-dump resistor could operate in excess of 200 °C. Keep the resistor away from thermally sensitive components, such as cables or plastic hardware. Proper installation may require the use of thermal compound and proper thermal connection to a heat absorbing metal surface.

188 Aries User Guide

Appendix C Regulatory Compliance­UL and CE

APPENDIX C

Regulatory Compliance UL and CE

IN THIS CHAPTER

System Installation Overview................................................................... 190 General Safety Considerations................................................................ 190 General EMC Considerations.................................................................. 190 Installing the Aries Drive .......................................................................... 191 Regulatory Agencies................................................................................ 200 Standards of Compliance ........................................................................ 200

Parker Hannifin

System Installation Overview

This appendix contains information related to installation methods and practices that can be used to aid the systems integrator or machine builder in designing a compliant installation, meeting the needs of global regulatory agencies. The installation overview is divided in to two sections--"Safety" and "Electromagnetic Compatibility (or EMC)". It is recommended that the installer read this entire overview, prior to taking any action, as some of the required installation methods can be leveraged across both Safety and EMC installations. Although Aries drives are technically considered motion control components and are therefore not within the scope of the European union's CE (Conformité Européenne) directives, Parker has taken the initiative to provide its customers with easy to integrate motion control products that meet global requirements. The following constitutes what is typically required to install Aries drives into a CE compliant system. Additional installation measures may be required at some locations. The machine builder has ultimate responsibility for machine compliance.

General Safety Considerations

These products are intended for installation according to the appropriate safety procedures including those laid down by the local supply authority regulations. The recommendations provided are based on the requirements of the Low Voltage Directive and specifically on EN61010. Remember, never compromise safety to achieve EMC compliance. Therefore, in the event of a conflict between safety regulations and the following EMC recommendations, safety regulations always take precedence.

General EMC Considerations

The Aries product is a motion control component and as such will be built in to another machine that will in turn be required to comply with the relevant directives of the marketplace. It is important to remember that for specific installations, the full protection requirements of the EMC directive 89/336/EEC need to be met before the system is taken in to service. This must be verified either by inspection or by testing. The following EMC installation recommendations are intended to assist in ensuring that the requirements of the EMC directive are met. It may be necessary to take additional measures in certain circumstances and at specific locations. It should be stressed that although these recommendations are based on the expertise acquired during the design and development of the Aries products, and on tests carried out on similar products, it is impossible for Parker to guarantee compliance of any particular installation. This will be strongly influenced by the physical and electrical details of the installation and the performance of other system components. Nevertheless, it is important to follow all the installation recommendations if an adequate level of compliance is to be achieved.

190 Aries User Guide

Parker Hannifin

Installing the Aries Drive

Only qualified, skilled electrical technicians familiar with local safety requirements should install this product. For service, the drive must be returned to an authorized service center. There are no user serviceable parts inside the chassis. In certain circumstances, opening the cover may void the product warranty. The Aries drive is a vented product. To prevent material spilling into the drive, mount it under an overhang or in a suitable enclosure. Aries products are made available under "Restricted Distribution" for use in the "Second Environment" as described in EN 61800-3 1996, page 9. This means only those individuals familiar with the EMC requirements of power drive systems should install this product and that this product is designed for connection to mains distribution networks other than low-voltage networks, which may supply domestic premises. The drives can tolerate atmospheric pollution degree 2, which means only dry, non-conductive pollution is acceptable. Aries drives have been shown to meet the requirements of both the European LVD & EMC directives when installed according to the recommendations given within this section. It is recommended the drive be installed in an enclosure to protect it from atmospheric and industrial process contaminants and to prevent operator access while it has power applied. Metal equipment cabinets are ideally suited for housing the equipment since they can provide operator protection, EMC screening, and can be fitted with interlocks arranged to remove all hazardous motor and drive power when the cabinet door is opened. Do not arrange interlocks to open circuit the motor phase connections while the system is still powered, as this could cause damage to the drive.

Precautions

During installation, take the normal precautions against damage caused by electrostatic discharges. Wear earth wrist straps. A switch or circuit breaker must be included in the installation, which must be clearly marked as the disconnecting device and should be within easy reach of the machine operator. The Aries Drive has exposed high voltage terminals. In order to comply with the safety requirements pertaining to European Compliance, and other authorities, the drive must be mounted in such a way as to restrict access to these terminals during normal operation.

A Safe Installation ­ Meeting the Requirements of the Low Voltage Directive (LVD)

In order to comply with the requirements of the European Union's Low Voltage Directive, the following installation measures must be taken. · Mains fuses must be installed on all mains input lines carrying operating current. For more information, see "Motor Power Fuse Information" on page 41 and page 46. Drive Protective Earth Conductor must be connected directly to a reliable system safety Earth point. Total resistance from Drive's Protective Conductor Terminal to a Reliable System Safety Earth

·

Appendix C Regulatory Compliance ­ UL and CE 191

Parker Hannifin must not exceed 0.1 Ohm, and must be capable of carrying 25A of Fault Current. · Motor safety earth conductor (for motor voltages greater than or equal to 75 volts) must be connected to the drive's Motor Earth terminal, marked with . The drive must be installed in a manner that prevents operator access to hazardous live terminals during normal operation.

·

Additional safety measures may be required within your particular market, please consult you local regulatory agency for additional requirements.

A Highly-Immune, Low-Emission Installation ­ Meeting the Requirements of the Electromagnetic Compatibility (EMC) Directive

The following information was compiled to aid the machine builder or systems integrator in gaining EMC compliance. For effective control of Conducted and Radiated Emissions, along with maximizing the Aries Drive's inherent noise immunity, the following recommendations should be followed. A drawing of a typical EMC installation is shown below. · Mount the Drive and all components to a clean (not painted), earthed, metal panel.

Important! To reduce the risk of electrical noise entering your system you must properly earth ground the enclosure, and remove all paint and other non-conductive surface coatings from the panel mounting surface and RF earth bonding locations. If you mount the Aries drive in an equipment cabinet, terminate cable braids (screens) at the entrance of the enclosure. This can be easily accomplished using the "additional EMC installation hardware" shown below. The only exception is for the motor braid, which must return to the drive's R-Clamp (located on the bottom of the Aries drive. Do not return the motor braid to any other location, its function is to return highfrequency chopping current back to the drive. This may require mounting the connector on a sub-panel insulated from the main cabinet, or using a connector having an insulated internal screen from the connector housing. The shields of all other cables that enter or exit the enclosure must be RF bonded to the enclosure entrance point using an R-Clamp, bulkhead clamshell clamp, or other 360° bonding technique. This ensures that no stray noise will enter or exit the enclosure. The following drawing illustrates 360° bonding techniques.

192 Aries User Guide

Parker Hannifin

Figure 52 360° Bonding Techniques

All braid termination connections must remain secure. For small diameter cables, it may be necessary to fold back the braid to increase the effective diameter of the cable so that R-Clamps are secure. Within the cabinet itself, all the motor cables should lie in the same trunking as far as possible. Keep the cables separate from any low-level control signal cables. This applies particularly where the control cables are unscreened and run close to the drive. There must be no break in the 360° coverage that the screen provides around the cable conductors. A steel equipment cabinet will screen radiated emissions provided all panels are bonded to a central earth point. Separate earth circuits are commonly used within equipment cabinets to minimize the interaction between independent circuits. A circuit switching large currents and sharing a common earth return with another low-level signal circuit could conduct electrical noise into the low level circuit, thereby possibly interfering with its operation. For this reason, so called `dirty earth' and `clean earth' circuits may be formed within the same cabinet, but all such circuits will eventually need to be returned to the cabinet's main star earth point. Mount the individual drives and EMC filter on a metal earth plane. The earth plane will have its own individual star point earth that should be hard wired (using an insulated copper conductor) back to the cabinet's `clean earth' connection point. Panel mounting can provide a similar measure of EMC performance if strict attention is paid to cable screen termination and cable layout. Again, the machine builders primary focus should be on ensuring operators are kept safe from all hazards. · Install a Mains filter. Aries drives require an EMC mains supply filter to meet EMC emission requirements. It is recommended that the drive is mounted on a conductive panel which is shared with the EMC filters. If the panel has a paint finish, it will be necessary to

Appendix C Regulatory Compliance ­ UL and CE 193

Parker Hannifin remove the paint in certain areas to ensure filters and drive make a good large-area metal to metal contact between filter case and panel. You must install a filter on both the Motor power mains and Control power mains if both are used. Use Table 60 and Table 61 to determine the correct filter for your specific application.

Control Power

Control power is 1 Amp, maximum. Any of the following filters works with all models of the drive. Filter 6EP1 (160937-5) 10EP1 (160937-7) FN2070-10/06

1. Available from Parker:

1,

Manufacturer Corcom Corcom Schaffner

10 Amp filter--part number 47-016140-01 16 Amp filter--part number 47-017900-01

Table 60 Control Power Filter Selection

Mains Motor Power

Filter Continuous Current (Amps)

1 1, 3

AR01xx × × × ×

AR02xx × × × ×

AR04xx

AR08xx

AR13xx

AR20xE

AR30xE

6EP1 (160937-5)

5 at 240 VAC 8 at 240 VAC 10 at 240 VAC 12 at 240 VAC

10EP1 (160937-7) FN2070-10/06 FN2070-12/06 FN2070-16/06 16FCD10 25FCD10

1 1 2, 3 2

× × × ×

× × × ×

x x x x x x x

16 at 240 VAC 16 at 240 VAC 25 at 240 VAC

Product with applicable mains filter denoted by "×" 1. Corcom (a division of Tyco Electronics) 2. Schaffner 3. Available from Parker: 10 Amp filter--part number 47-016140-01 16 Amp filter--part number 47-017900-01

Table 61 Mains Motor Power Filter Selection

·

Install Transient suppressors.

Single Phase Input You must install varistors or other voltage surge limiting devices in order to meet the requirements of EN61000-4-5. Place a Littelfuse V275LA2ØC, or an equivalent varistor, from line to line and from lines to earth before the mains filter, as shown in the EMC Installation drawings. (Intersil, General Electric, and Littelfuse manufacture equivalent varistors.)

194 Aries User Guide

Parker Hannifin

Three Phase Input Control Power ­ You must install varistors or other voltage surge limiting devices in order to meet the requirements of EN61000-4-5. Level 3 Voltage Surge (1000V line-to-line, 2000V line-to-earth) protection can be achieved by placing a Littelfuse V275LA20C, or an equivalent varistors from line-to-line and from line-to-earth before the mains filter as shown in Figure 54 Typical LVD/EMC Installation, AR-20xE & AR-30xE on page 198. Mains Motor Power ­ The three-phase AC power Aries drives (models AR-20xE and AR-30xE) are designed to meet Level 3 Voltage Surge (1000V line-to-line, 2000V line-to-earth) without the need for external voltage surge limiting devices. If a higher level of mains surge immunity is required, external voltage sure limiting devices, such as varistors, can be installed before the mains filter. Figure 54 Typical LVD/EMC Installation, AR-20xE & AR-30xE on page 198 illustrates this installation. Note: Intersil, General Electric, and Littelfuse manufacture equivalent varistors. · Use an EMC-ready motor or a motor that has demonstrated acceptable EMC performance.

Motors with shielded cabling or pipe thread style cabling options allow the easiest integration into machines required to bear the CE mark for EMC. Note: Motors may bear the CE mark. This mark indicates the motor meets the requirements of construction and safety--not EMC compliance. · Use shielded cabling with braided and bonded headshells. Parker EMC cabling--requires no additional cable preparation. All motor connections must be made using a high quality braided-screen cable. Cables using a metalized plastic bandage for an earth screen are unsuitable and in fact provide very little screening. Care must be taken when terminating the cable screen, the screen itself is comparatively fragile; bending it round a tight radius can seriously affect the screening performance. The selected cable must have a temperature rating which is adequate for the expected operating temperature of the motor case. All cables must maintain high integrity 360 degree shielding. Parker CE cables are fully shielded and provide the required screening. When you install limit switches and other inputs/outputs, you must observe these noise immunity procedures and practices. · Route cables as shown in Figure 53 Typical LVD/EMC Installation, AR-02xx to AR-13xx on page 197 and Figure 54 Typical LVD/EMC Installation, AR-20xE & AR-30xE on page 198.

Route high power cables (motor and mains) at right angles to low power cables (communications and inputs/outputs). Never route high and low power cables parallel to each other. Mount filters close to the drive and keep the supply wiring as short as practical. Attempt to layout the wiring in a way that minimizes cross coupling between filtered and non-filtered conductors. This means avoiding running wires from the output of a filter close to those connected to its input. Where you wish to minimize the cross coupling between wires avoid running them side-by-side one another, if they

Appendix C Regulatory Compliance ­ UL and CE 195

Parker Hannifin must cross, cross them at 90° to each other. Keep wiring supported and close to cabinet metalwork. · Cables may require the use of ferrite core suppressors. Some installations may require that you take additional EMC measures. To further increase product immunity and reduce product emissions, you may add clip-on ferrite absorbers to all cables. Parker recommends ferrites with at least 200 ohm impedance at 100 MHz, such as the following: Steward Ferrite Fair-Rite

Note:

Part number 28A2024 Part number 0443164151

These ferrites are available from Parker Hannifin, part number 47-015956-01. For larger diameter cables (up to 0.722 in O.D.), Fair-Rite part number 0444176451 is recommended.

·

Your Installation may require additional EMC installation hardware (as shown in illustrations).

The following clamp kits are available from Parker: Clamp Type R-Clamp Kit (10 per) for models AR-02xx to AR-13xx R-Clamp Kit (10 per) for models AR-20xE and AR-30xE Clamshell Clamp Kit (2 per) for all models

Table 62 Enclosure Mounting Clamps

Parker Part Number R CLAMP KIT R LARGE CLAMP KIT CLAMSHELL KIT

Note: The Control power input also requires a mains power line filter, varistors, and fuses in order to comply with the relevant CE directives.

196 Aries User Guide

Parker Hannifin

Panel Installation, AR-02xx to AR-13xx

Figure 53 Typical LVD/EMC Installation, AR-02xx to AR-13xx

Warning -- This product has been developed for industrial environments. Due to exposed high voltage terminals, this product must not be accessible to users while under normal operation.

Appendix C Regulatory Compliance ­ UL and CE 197

Parker Hannifin

Panel Installation, AR-20xE & AR-30xE

Aries models AR-20xE and AR-30xE require 240 VAC input power and three-phase wiring.

Figure 54 Typical LVD/EMC Installation, AR-20xE & AR-30xE

Warning -- This product has been developed for industrial environments. Due to exposed high voltage terminals, this product must not be accessible to users while under normal operation.

198 Aries User Guide

Parker Hannifin

Panel Mounting

The mounting clearance requirements are the same for all Aries drive models. They are shown in Figure 55.

Figure 55 Panel Layout Dimensions for the Aries Drive

Appendix C Regulatory Compliance ­ UL and CE 199

Parker Hannifin

Regulatory Agencies

The Aries family of products is designed to meet the requirements of global regulatory agencies. Aries products have shown compliance with the regulatory agencies in the following list. The list also shows additional steps users must take to ensure compliance. Agency UL, CE (LVD) CE (EMC) Additional Steps User Must Take Mains fuses Mains fuses; earth connection for drive and motor (if applicable), proper installation Varistors, mains filter, EMC cabling, EMC ready motor, proper installation

Table 63 Regulatory Agencies

Standards of Compliance

UL CE for LVD 508C 72/23/EEC BS EN 61010-1 (1993) including Amendment A2. CE for EMC 89/336/EEC BS EN 61800-3 (1997) including Amendment A11 BS EN 50081-2 (1994) Electromagnetic compatibility BS EN 61000-6-2 (1999) Electromagnetic compatibility Part 6-2: Generic Standards Adjustable speed electric power drive systems Part 3. EMC product standard including specific test methods. Generic emission standard Part 2. Industrial Environment. Safety requirements for electrical equipment for measurement, control, and laboratory use. Part 1. General Requirements.

Immunity for industrial environments.

200 Aries User Guide

Appendix D Servo Tuning Flow Diagram

APPENDIX D

Servo Tuning Flow Diagram

IN THIS CHAPTER

Servo Tuning Flow Diagram .................................................................... 202

Parker Hannifin

Servo Tuning Flow Diagram

Figure 56 Servo Tuning Flow Diagram

202 Aries User Guide

Appendix E VM26 Expansion Module

APPENDIX E

VM26 Expansion Module

IN THIS CHAPTER

Overview ..................................................................................................204

Parker Hannifin

Overview

The VM26 expansion module provides screw-terminal connections for the Drive I/O connectors on the Aries drive. The VM26 comes with a 2-foot cable (609.6 mm) that provides easy connection between the VM26 module and the drive's 26-pin I/O connectors. The VM26 expansion module is ordered separately (part number "VM26-PM"). Notes · · The VM26 module ships with DIN-rail mounting clips installed. The overall cabinet depth with cable-bend radius is 5 inches (127 mm).

Figure 57 VM26 Breakout Module

204 Aries User Guide

Parker Hannifin

Index

120/240 VAC power input .................................. 39, 47 absolute position, establishing effect on position report (TPE) ...........................151 accuracy ...............................................................169 address multiple units (ADDR) ..........................................95 encoder ..................................................................96 align encoder (ALIGN) .............................................96 amplifier ...............................................................169 analog input ANI ........................................................... See ANI analog input center deadband (ANICDB)...................97 ANI check input voltage (TANI) ................................145 input resolution ........................................... 71, 166 voltage status (TANI) ........................................145 wiring .................................................................69 auto-configure, smart encoder ......................... 33, 163 autorun........................................................... 72, 104 binary value identifier (b).........................................94 brake brake relay .........................................................50 non-Parker motors ..............................................52 output delay (OUTBD) .......................................137 Parker motors .....................................................51 bus voltage, report (TVBUS)...................................153 cables EMC .................................................................173 non-EMC...........................................................173 routing ....................................................... 31, 192 carriage return, command delimiters ........................94 case sensitivity ........................................................94 CE EMC ..................................................... 9, 190, 200 LVD ...................................................... 9, 191, 200 center deadband (ANICDB) ......................................97 change summary....................................12, 13, 14, 15 characters command delimiters ............................................94 comment delimiter ..............................................94 field separators ...................................................94 limit per line........................................................94 neutral (spaces) ..................................................94 COM port ........................................................ 75, 159 command offset (DCMDZ)......................................101 commands command description format................................92 command-to-product compatibility .......................92 default settings ...................................................92 delimiters............................................................94 syntax ................................................................92 comment delimiters .................................................94 communication interface echo enable ......................................................126 communications RS-232/485.........................................................74 configuration errors (CONFIG)..................................................99 warnings (CONFIG) .............................................99 configuration error, motor (DMTR) .........................112 connector brake relay ......................................................... 50 control input power............................................. 47 drive I/O ............................................................ 66 locations of......................................................... 37 mains................................................................. 40 motor................................................................. 44 motor feedback .................................................. 62 motor feedback, resolver..................................... 65 motor output power............................................ 43 output power...................................................... 44 regeneration....................................................... 54 continuous current derating, motor (DMTICD)................................. 106 motor (DMTIC) ................................................. 106 control input power................................................. 40 connection ......................................................... 47 supply ................................................................ 46 cooling cabinet..........................................................23­27 drive .................................................................. 22 current foldback enable/disable (DIFOLD) ............................102, 173 overview .......................................................... 173 damping servo motor .......................................................... 105 DC link inductor ...................................................... 45 deadband (ANICDB)................................................ 97 debugging tools error log (TERRLG) ........................................... 148 default command settings ....................................... 92 restore (RFS).................................................... 139 delimiters command ........................................................... 94 comment............................................................ 94 direction of rotation (CMDDIR) ................................ 98 drive bus voltage, status of (TVBUS) .......................... 153 command offset, zero (DCMDZ)......................... 101 drive enable (DRIVE) ........................................ 125 incoming pulse scaling (DMPSCL)....................... 104 operating modes (DMODE)................................ 103 position error (SMPER) ...................................... 143 temperature, status report (TDTEMP) ................ 148 velocity error (SMVER) ...................................... 144 resolution ............................................................. 125 drive cooling ........................................................... 22 drive dimensions ..........................................28, 29, 30 drive dimensions, panel layout..........................31, 199 Drive Enable (DRIVE) ............................................ 125 drive resolution (DRES) ......................................... 125 echo, communication ............................................ 126 electrical pitch (DMEPIT) ....................................... 103 EMC ................................................................33, 200 EMC installation .............................................197, 198 enable input error checking (ERROR) .................................... 129 wiring ................................................................ 69

Index

205

Parker Hannifin

encoder auto-configure (smart)................................. 33, 163 input resolution (ERES)......................................128 position commanded (TPC) ................................151 position report (TPE) .........................................151 position report error (TPER) ...............................151 resolution (ERES) ..............................................128 encoder offset .......................................................127 environment............................................................22 epitch (DMEPIT)....................................................103 error clear log (CERRLG) ..............................................98 display log contents (TERRLG) ...........................148 error checking enable (ERROR) ..........................129 error log setup (ERRORL) ..................................131 error messages ........................................... 159­63 European Conformance Statement ............................ 9 External DC link inductor..........................................45 factory default settings, restore (RFS).....................139 faults fault on drive disable (FLTDSB) ..........................133 fault on excessive startup voltage (FLTSTP) ........133 motor configuration error (DMTR, CONFIG) .. 98, 112 thermal switch (DTHERM)..................................126 feedback...............................................................169 filters, AC mains ....................................................194 foldback................................................................102 foldback (DIFOLD).................................................173 force actual, status (TTRQA) ......................................153 commanded, status (TTRQ) ...............................153 limit (DMTLIM)..................................................111 scaling (DMTSCL) ..............................................115 forcer mass ................................................................109 fuses ................................................................ 41, 42 gains current loop, auto (IAUTO) ................................134 integral (IGAIN) ................................................134 integral (SGI) ....................................................140 integral (SGILIM) ..............................................140 notch filter A depth (DNOTAD)...........................119 notch filter A frequency (DNOTAF) .....................120 notch filter A quality factor (DNOTAQ) ................121 notch filter B depth (DNOTBD) ...........................121 notch filter B frequency (DNOTBF) .....................122 notch filter B quality factor (DNOTBQ) ................122 notch lag filter break freq (DNOTLG) ..................123 notch lead filter break freq (DNOTLD) ................122 proportional (PGAIN) .........................................138 proportional (SGP).............................................141 set current loop bandwidth (DIBW) ....................101 System Load-to-Rotor Inertia Ratio (LJRAT)........135 torque/force limit (DMTLIM)...............................111 velocity (SGV) ...................................................141 velocity feedforward (SGVF)...............................142 velocity limit (DMVLIM)......................................118 hall sensor check sensor values (THALL) .............................149 configuration/inversion (SHALL) .........................143 troubleshooting .................................................164 hexadecimal value identifier (h)................................94 Incoming Pulse Scaling (DMPSCL) ..........................104 inductance motor max (DMTIND)........................................107 motor min (DMTINF) .........................................108 input resolution, analog .........................................169 inrush current ......................................................... 42 installation LVD/EMC...................................................197, 198 installation category ................................................ 22 installation, overview....................................35, 36, 37 jumper wires, pre-installed ................................ 35, 37 lead/lag filters lag ................................................................... 123 lead ................................................................. 122 LEDs ...............................................................56, 158 line feed, command delimiters ................................. 94 linear motor pitch (DMEPIT) .................................. 103 LVD.............................................................9, 33, 200 LVD installation..............................................197, 198 mass, forcer ......................................................... 109 memory after a reset (RESET) ........................................ 138 return to factory settings (RFS) ......................... 139 motor ambient temperature (DMTAMB) ....................... 105 auto-configure .................................................. 112 brake ................................................................. 50 configuration error (DMTR, CONFIG).................. 112 connector ........................................................... 59 continuous current (DMTIC) .............................. 106 continuous current derating (DMTICD)............... 106 damping........................................................... 105 drift, minimizing (DCMDZ) ................................. 101 full wave rectifiers............................................... 51 fuses, input power ........................................ 41, 42 input power.................................................. 39, 40 linear motor pitch (DMEPIT) .............................. 103 output power...................................................... 43 output power, connection.................................... 44 peak current (DMTIP) ....................................... 108 pole pairs (DPOLE)............................................ 124 rated speed (DMTW)......................................... 117 rotor inertia ...................................................... 109 selection recorded (DMTR) ................................ 112 temperature report (TMTEMP) ........................... 150 thermal time constant (DMTTCM) ...................... 116 voltage constant (Ke) (DMTKE).......................... 110 winding resistance (DMTRES) ............................ 114 winding temperature, max. (DMTMAX)............... 112 winding thermal resistance (DMTRWC) .............. 114 winding time constant (DMTTCW)...................... 117 motor inductance max (DMTIND) ................................................. 107 min (DMTINF) .................................................. 108 motor temperature switch type (DMTSWT)............. 116 multiple drives ........................................................ 48 multiple unit address............................................... 95 multiple unit wiring ................................................. 76 neutral characters ................................................... 94 notch filter A depth ............................................................... 119 frequency......................................................... 120 quality factor .................................................... 121 notch filter B depth ............................................................... 121 frequency......................................................... 122 quality factor .................................................... 122 notch lag filter break frequency ............................. 123 notch lead filter break frequency............................ 122 offset zero command offset (DCMDZ).......................... 101 offset, encoder (ENCOFF) ...................................... 127

206 Aries User Guide

Parker Hannifin

operating hours, report (TDHRS) ............................146 operating hours, report (TDMIN) ............................147 operating hours, report (TDSEC) ............................147 operating modes, drive (DMODE) ...........................103 operating system revision (TREV) ...........................152 output power ..........................................................43 outputs status (TOUT) ...................................................150 override mode.......................................................119 over-temperature limits..........................................170 over-voltage protection..........................................172 peak current, motor (DMTIP) .................................108 performance .........................................................169 pole pairs, motor (DPOLE) .....................................124 pollution degree ......................................................22 position actual (TPE)......................................................151 actual error(TPC)...............................................151 commanded (TPC) ............................................151 encoder (TPE) ...................................................151 encoder error (TPER).........................................151 tracking ............................................................142 power dissipation .............................................. 23­27 power supply connection ..........................................................40 fuses ............................................................ 41, 42 input power ................................. 35, 37, 39, 40, 46 power-dump resistor calculating for linear motor ................................183 calculating for rotary motor................................177 selection ................................................... 175, 176 product revision (command implementation).............92 product revision (TREV) .........................................152 program comments...........................................................94 reset, effect of ..................................................138 protection current foldback (DIFOLD) ......................... 102, 173 drive over-temperature......................................170 over-voltage......................................................172 short circuit.......................................................170 under-voltage ...................................................171 PWM frequency (dpwm) ........................................169 PWM frequency (DPWM)........................................124 PWM update period (TSSPD)..................................152 rated speed, motor (DMTW) ..................................117 regeneration .................................... 54, 172, 175, 176 regulatory agencies ...............................................200 relay brake relay .........................................................50 relay, brake operation ............................................................53 output delay (OUTBD) .......................................137 output status (TOUT) ........................................150 specification........................................................53 reset,drive (RESET) ...............................................138 resistor, power-dump............. See power-dump resistor resolution encoder (ERES) .................................................128 encoder input (ERES) ........................................128 resolver ................................................................169 return to factory settings (RFS) ..............................139 revision level, operating system (TREV) ..................152 revision of this manual............................12, 13, 14, 15 rotor inertia, motor ................................................109 RS-232 communications.................................................. 75 dongle ............................................................... 77 wiring ................................................................ 74 RS-232/485 connector ........................................................... 74 troubleshooting ................................................ 159 wiring .......................................................... 74, 75 RS-485 communications.................................................. 75 dongle ............................................................... 77 multi-drop network ............................................. 76 wiring .......................................................... 74, 75 scaling force command................................................. 115 torque command (DMTSCL) .............................. 115 velocity command ............................................. 119 velocity command (DMVSCL) ............................. 119 servo position tracking ............................................... 142 servo tuning actual position .................................................... 80 auto-tuning ........................................................ 90 closed loop ......................................................... 79 commanded position ........................................... 80 current loop gains, auto .................................... 134 inertia ratio (LJRAT).......................................... 135 integral feedback ................................................ 83 integral gain (IGAIN)......................................... 134 integral gain (SGI) ............................................ 140 integral gain limit (SGILIM) ............................... 140 measuring performance ...................................... 82 notch filter A depth (DNOTAD) .......................... 119 notch filter A frequency (DNOTAF)..................... 120 notch filter A quality factor (DNOTAQ) ............... 121 notch filter B depth (DNOTBD) .......................... 121 notch filter B frequency (DNOTBF)..................... 122 notch filter B quality factor (DNOTBQ) ............... 122 notch lag filter break freq (DNOTLG).................. 123 notch lead filter break freq (DNOTLD) ................ 122 open loop........................................................... 79 overview ............................................................ 79 position error (SMPER) ...................................... 143 position respones................................................ 81 position variables ................................................ 80 proportional feedback ......................................... 83 proportional gain (PGAIN) ................................. 138 proportional gain (SGP)..................................... 141 set current loop bandwidth................................ 101 stability .............................................................. 81 torque/force limit (DMTLIM) .............................. 111 tuning example................................................... 86 velocity error (SMVER) ...................................... 144 velocity feedback ................................................ 83 velocity feedforward gain (SGVF) ....................... 142 velocity gain (SGV) ........................................... 141 velocity limit (DMVLIM) ..................................... 118 windup............................................................... 84 servo update ........................................................ 169 ship kit ................................................................... 19 short circuit protection .......................................... 170 software revision level (TREV) ............................... 152 space (neutral character)......................................... 94

Index

207

Parker Hannifin

specifications additional specifications .....................................169 drive I/O connector .............................................66 input power connector.........................................57 mains connector..................................................57 motor connector..................................................59 motor feedback connector ............................. 62, 66 motor feedback, resolver .....................................65 standards.......................................................... 9, 200 status commanded position (TPC) ................................151 commanded velocity, feedback device (TVEL) .....154 encoder position (TPE) ......................................151 encoder position error (TPC) ..............................151 error log (TERRLG)............................................148 full text report (STATUS) ...................................145 outputs (TOUT).................................................150 software revision level (TREV)............................152 velocity, feedback device (TVELA) ......................154 velocity, feedback device error (TVER)................155 voltage input for ANI (TANI) ..............................145 switch type, motor (DMTSWT) ...............................116 motor ...................................................................116 syntax, command ........................................ 92, 93, 94 technical support ...................................................... 2 temperature ............................................................23 drive status (TDTEMP).......................................148 environment .......................................................22 limits ................................................................170 motor status (TMTEMP) .....................................150 motor winding (DMTMAX)..................................112 motor--ambient (DTAMB) ..................................105 thermal switch (DTHERM) ......................................126 thermal time constant, motor (DMTTCM) ................116 torque actual, status (TTRQA) ......................................153 commanded, status (TTRQ) ...............................153 limit (DMTLIM)..................................................111 scaling (DMTSCL) ..............................................115 tranformation ratio ................................................169 transfer actual torque/force (TTRQA) ..............................153 actual velocity (TVELA) ......................................154 analog input voltage, ANI (TANI) .......................145 bus voltage (TVBUS) .........................................153 commanded current (TCI) .................................146 commanded torque/force (TTRQ).......................153 commanded velocity (TVEL)...............................154 commanded velocity error (TVER) ......................155 continuous current rating (TDICNT)....................146 d quadrature current (TCI) ................................149 drive temperature (TDTEMP) ............................. 148 error log (TERRLG) ........................................... 148 hall sensor values (THALL) ................................ 149 maximum current rating (TDIMAX) .................... 147 motor temperature (TMTEMP) ........................... 150 operating hours (TDHRS) .................................. 146 operating milliseconds (TDSEC) ......................... 147 operating minutes (TDMIN) ............................... 147 output status (TOUT) ........................................ 150 position commanded (TPC) ............................... 151 position of encoder (TPE) .................................. 151 position of encoder error (TPER)........................ 151 PWM update period (TSSPD) ............................. 152 q quadrature current (TCI) ................................ 149 revision level (TREV) ......................................... 152 transient suppressors ............................................ 194 troubleshooting..................................................... 156 configuration (CONFIG)....................................... 99 ERROR command (ERROR) ............................... 129 error log (TERRLG) ........................................... 148 error messages............................................159­63 general ............................................................ 157 hall sensors ...............................................149, 164 LEDs ................................................................ 157 tuning ............................................... See servo tuning UL 200 under-voltage protection ....................................... 171 units of measurement ............................................. 92 linear motors .................................................... 103 varistors ............................................................... 194 velocity actual (feedback device) (TVELA) ...................... 154 actual commanded (feedback device) (TVEL) ..... 154 error (feedback device) (TVER).......................... 155 feedforward gain (SGVF) ................................... 142 limit (DMVLIM) ................................................. 118 scaling (DMVSCL) ............................................. 119 Velocity mode maximum acceleration (SMAV) .......................... 143 voltage AC input ............................................................. 39 ANI input (TANI) .............................................. 145 constant (Ke) of motor (DMTKE)........................ 110 weight.................................................................... 30 winding resistance, motor (DMTRES).............................. 114 temperature, max. (DMTMAX) ........................... 112 thermal resistance, motor (DMTRWC) ................ 114 time constant, motor (DMTTCW) ....................... 117 zero command offset (DCMDZ) .............................. 101

208 Aries User Guide

Information

Aries User Guide

208 pages

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

829946


You might also be interested in

BETA
Aries User Guide
APEX615n Servo Controller/Drive Installation Guide
APEX615n Servo Controller/Drive Installation Guide