Read untitled text version

TCAE-THAE 114÷160

Compact Range

Packaged air-cooled reversible water chillers and heat pumps with axial fans. Range with hermetic Scroll compressors and R407C refrigerant gas.

Construction features

Compressor: hermetic, rotary Scroll compressor, complete with thermal protection. Water side heat exchanger: stainless steel plate exchanger closed cell polyurethane foam rubber insulation, complete with antifreeze heater and water flow differential pressure switch. Air side heat exchanger: featuring finned coil with copper pipes and aluminium fins, complete with protection grille. Fan: electric axial fan with external rotor, equipped with internal thermal protection and complete with protection grille. Control: microprocessor electronic control available in 2 versions Standard and iDRHOSS, both compatible with AdaptiveFunction logic. Structure: peraluman, complete with condensation drain pain for THAE.

· U with primary electric pump and electric pump in stand-by (TCAE-THAE 150-160 only, with iDRHOSS compatible control option). Pump assembly complete with: water buffer tank with antifreeze heater, primary circulation pump and stand-by pump that is automatically activated in the event of an alarm, non-return valves, expansion tank with membrane, manual air bleed valve, safety valve, water drain tap and system pressure gauge.

Factory fitted accessories

TCAE-THAE 114÷126 only · Antifreeze heater on the buffer tank. TCAE-THAE 150-160 only · Desuperheater (complete with condensation control). · Thermostat with display for desuperheater. · Soft-start device.

Accessories supplied loose

· Antivibration rubber mountings. · -10°C condensation control. · Remote keyboard with display. Option with Standard control · RS 485 serial interface connection (Supported protocols: proprietary protocol; Modbus RTU). · RS 232 hardware key. Option with control · Clock card · RS 485 serial interface connection (Supported protocols: proprietary protocol; Modbus RTU). · FTT10 serial interface protocol Lonworks® compatible. · RS 485/RS 232 serial converter in the event of centralised unit management. · RS 485/USB serial converter in the event of centralised unit management. · CAN-bus (Controller Area Network) serial interface for the iDRHOSS system.

Models

TCAE: unit designed for cooling only. THAE: heat pump unit. · R22 gas models available on request.

STANDARD version

Without pump assembly and buffer tank.

TANK & PUMP version

· T with standard electric pump. · H with high-pressure electric pump. Pump assembly complete with: water buffer tank with antifreeze heater for models 132÷160, standard or high pressure circulation pump for models 114-117 only, expansion tank with membrane, manual air bleed valve, safety valve, water drain tank and system pressure gauge for models 132÷160.

P.6

Microsystem 14.3÷64.5 kW 15.3÷69.9 kW

TANK & PUMP version

Liquid receiver

Water buffer tank

Circulation pumps

Expansion tank

TCAE-THAE MODEL Nominal cooling capacity Nominal heating capacity Sound pressure Water tank content T - H - U Available static pressure of electric pump T - U Available static pressure of electric pump T Absorbed power Absorbed power Main supply DIMENSIONS AND WEIGHTS L - Width H - Height STANDARD H - Height TANK & PUMP P - Depth

Weight TCAE Weight THAE

114 kW kW dB(A) l kPa kPa kW kW 14,3 15,3 49 55 45 175 4,88 4,84

117 17,1 18,7 50 55 40 151 5,61 5,51

121 21,1 23,2 51 80 152 ­ 7,17 6,94

126 25,1 28,3 52 80 141 ­ 8,91 8,38

132 32,1 37,2 55 80 99 ­ 12,8 11,9

138 39,5 43,4 57 80 80 ­ 14,2 14,6

150 51,3 54,9 58 150 177 ­ 19,5 19,4

160 64,5 69,9 58 150 158 ­ 23,9 23,5

V-ph-Hz 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50

mm mm mm mm kg kg

1.320 1.280 1.575 525 280 290

1.320 1.280 1.575 525 300 310

1.710 1.280 1.575 610 360 380

1.710 1.280 1.575 610 400 410

1.328 1.593 1.593 968 460 470

2.200 1.593 1.593 968 590 600

2.270 1.650 1.650 968 760 775

2.270 1.650 1.650 968 780 790

In the following conditions: Air: 35°C - Water: 7/12°C - Air: 7°C D.B. - 6°C W.B. - Water: 45/40°C. At 5 m from the unit in free field (Q = 2). Weight refers to the most complete version.

WATER CHILLERS - HEAT PUMPS

114

117

121

126

132

138

150

160