DISTRIBUTION ASSEMBLIES

GENERAL DESCRIPTION

The over-view below shows the full range of SCAME's distribution assemblies. With their compact size, robust construction and protection degree from IP44 to IP66, they meet the most varied power distribution requirements in factories, workshops, agriculture, services, construction sites and shipyards, in both normal and heavy duty ambient conditions.

REFERENCE STANDARDS

European Standard EN 60439-1 IEC 439/1

Low voltage switchgear and control gear assemblies Part 1: Type-tested and partially type-tested assemblies

IEC 60670

General requirements for enclosures for accessories for household and similar fixed electrical installations

European Standard EN 60439-4 IEC 439/4

Low voltage switchgear and control gear assemblies Part 4: Particular requirements for assemblies for construction sites (ACS)

OVERVIEW OF SCAME DISTRIBUTION ASSEMBLIES

MEGA Series

IP55

Max. 12 interlocked sockets · Transportable · With SELV safety transformer 220/24V

MASTERBOX Series

IP66 13 or 13+13 DIN Modules

Max. 10 interlocked sockets · Transportable · Surface mounting · Empty units · With SELV safety transformer 220/24V

DOMINO Series

IP44 - IP55 16 DIN Modules

Max. 6 sockets or 4 interlocked sockets · Portable with cable and plug · Surface mounting · Empty units · With SELV safety transformer 220/24V

BLOCK 3 Series

IP44 - IP66 6 DIN Modules

Max. 3 sockets · Portable with cable and plug · Surface mounting · Empty units

BLOCK 4 Series

IP44 - IP66 10 DIN Modules

Max. 4 sockets · Portable with cable and plug · Surface mounting · Empty units · With SELV safety transformer 220/24V

GOMMA Series

IP44 12 DIN Modules

Max. 5 sockets · Portable with cable and plug · Surface mounting · Empty units

GOMMA Series

IP44 8+8 DIN Modules

Max. 8 sockets · Surface mounting · Empty units

from t. 74

from t. 76

from t. 82

from t. 84

from t. 84

from t. 89

from t. 89

EMPTY UNITS

DISTRIBUTION ASSEMBLIES

see also

Enclosures for electrical equipment

Sec. 2.1 - p. 87

t. 66

TECHNICAL DATA

2

VERSIONS

The SCAME range of distribution assemblies includes the following Series: - MEGA - MASTERBOX - DOMINO - BLOCK - GOMMA SCAME's distribution assemblies are available in the following versions: - Fully pre-wired units: standard equipment for industrial and similar applications, construction sites, etc. - Partly pre-wired units: equipment partly factory-wired at SCAME, to be completed by the user. - Empty units with plain front panel: which can house any type of industrial and/or domestic sockets, protective devices and other types of compatible low-voltage electrical equipment (this version is not available for MEGA units). - Empty units with front-panel cut-outs: designed to house industrial 16 A and 32 A IEC309 or EUREKA Series socket outlets, 10 A and 16 A domestic European type socket outlets (to CEI, VDE, UTE and BS) and 16 A and 32 A OMNIA interlocked-switch socket outlets (only for DOMINO units) NOTE: This version is available only in DOMINO and BLOCK Series.

PRE-ASSEMBLIES

Pre-assemblies are ready-made distribution assemblies, fully pre-wired and equipped with industrial and/or domestic sockets, protective devices (modular or moulded-case MCBs and RCDs) and accessories. SCAME also offer a partly wired version (up to the EN50022 rail), equipped with industrial and/or domestic sockets, but without protective devices. The choice, purchase and installation of these articles is left to the customer. Pre-assemblies constructed and wired in-house by SCAME undergo strict quality control to pass all tests required by the standards. This assures the safety, reliability and long life of the equipment, provided the user operates correct installation, practices in accordance with the relevant wiring regulations. The following pages describe many of the standard assemblies produced by SCAME, which differ from each other by version, socket combination, protective devices and protection degree. Together they will meet most of the installation requirements that arise in terminal power distribution.

1

PLUG& SOCKETS IEC309 EUREKA ADAPTORS EASIGO HEAVY DUTY CEEGO

2

COMBINATION UNITS OMNIA ADVANCE QUADRA

Distribution assemblies

CUSTOMISED ASSEMBLIES

Consistent with their strongly customer-oriented marketing policy, SCAME also offer distribution assemblies housing combinations of sockets and protection devices made up to specific customer requirements. SCAME are in a position to design, implement and supply to order, accurately finished distribution assemblies at short notice. For any enquires in connection with customised distribution assemblies, please contact SCAME UK.

MEGA MASTERBOX DOMINO BLOCK GOMMA PDU

3

ENCLOSURES & BOXES EASYBOX DOMINO BLOCK SCABOX ALUBOX ACCESSORIES

COMPLIANCE WITH STANDARDS

All SCAME's empty units are constructed to meet IEC 670 requirements. The assemblies comply with EN 60439-1 (IEC 60439-1) and EN 60439-4 (IEC 60439-4) standards.

ACCESSORIES

SCAME supply a kit containing several standard installation accessories together with every empty unit. Other optional accessories are available on request.

DOUBLE INSULATION

All SCAME's thermoplastic units are provided with double insulation. This ensures safety in use since it prevents live parts from coming in contact with the outside of the enclosure in the event of a malfunction.

4

INSTALLATION ACCESSORIES TRUNKINGS LUMINAIRES CABLE REELS FUSES SWITCHES CONNECTORS

PRACTICAL ADVICE

Read and follow the instructions carefully. All regulations in force governing electrical installations must be observed: Check the assemblies regularly and replace them as soon as they show evident signs of wear and tear. Always employ qualified technical staff. If the product has been subject to impact or knocks, it should be checked at once even if it has suffered no evident damage. Never enclose the assembly in such a way as to hinder inspection and/or maintenance. Always employ qualified technical staff for any work on the switchgear. If any switchgear has been subject to impact, it should be checked at once even if it has suffered no evident damage.

INDEX

t. 67

DISTRIBUTION ASSEMBLIES

COMPLIANCE WITH DISTRIBUTION ASSEMBLIES STANDARDS

Distribution assemblies must comply with the standards listed below:

EUROPEAN STANDARD EN 60439-4 (IEC 439-4)

Distribution assemblies for use on construction sites. In conformity with the requirements of international regulations, distribution assemblies used on construction sites must comply with standard EN 60439-4 "Particular requirements for assemblies for construction sites (ACS)" , which supplement, amend and supersede some articles of standard IEC 439-1. Therefore all assemblies for construction sites (ACS) must take into account both the general standard EN 60439-1 and the specific standard for construction sites EN 60439-4. In particular, standard EN 60439-4 requires that: - the maximum rated voltage does not exceed 1000 V (a.c.) and 1500 V d.c.; - all ACS distribution assemblies bear one or more permanently inscribed data plates which are clearly visible after installation; - the data plates carry the following information: · manufacturer's name or trade-mark · designation of the type and identification number which allow the user to apply to the manufacturer to obtain additional technical information; · reference to standard EN 60439-4; · rated current, type of current and, if a.c, frequency.

European standard EN 60439-1

Distribution assemblies to be used in industrial, agricultural, service industry etc., applications in regular and heavy duty conditions. This standard requires: - that mass-produced distribution assemblies (TTA) are subject to type testing, and - that non-mass produced distribution assemblies (PTTA) are partly subject to type testing. All SCAME distribution assemblies (pre-wired unit fully equipped with sockets, protective devices, etc.) comply with IEC 60439-1. Since they are mass-produced (TTA), they are subject to type testing, an additional assurance for the user.

FINAL DISTRIBUTION ACS

Masterbox Series distribution assembly data plate

Compliance of ACS assemblies to EN 60439-4 is tested by type tests on a sample constructed according to the manufacturer's prescribed production system or without modifications from it such as to affect the performance.

BLOCK 3 Series: distribution assembly.

t. 68

TECHNICAL DATA

2

DOCUMENTATION FOR ACS

The manufacturer must specify in their documentation all conditions of installation, operation and maintenance of the assemblies and of the equipment housed in them. If the wiring diagram is not evident, suitable additional information must be supplied, eg. circuit diagrams or tables of connections. The manufacturer must also issue a conformity declaration certifying that the product has been produced in compliance with the standards.

FLEXIBLE USE

An outstanding feature of SCAME's range of distribution assemblies is their highly flexible use due to: - the considerable number of different possible combinations of industrial and/or domestic socket outlets which can be mounted in the assemblies; - the numerous possibilities of stationary and mobile installation: surface mounting, flush mounting, turret mounting, self-supporting, portable and on a wheeled cable-reel stand.

1

PLUG& SOCKETS IEC309 EUREKA ADAPTORS EASIGO HEAVY DUTY CEEGO

2

COMBINATION UNITS OMNIA ADVANCE QUADRA

Distribution assemblies

MEGA MASTERBOX DOMINO BLOCK GOMMA PDU

3

ENCLOSURES & BOXES EASYBOX DOMINO BLOCK SCABOX ALUBOX ACCESSORIES

ROLLER-BLOCK 450 Series: Assembly-cable reel combination on wheeled stand.

4

INSTALLATION ACCESSORIES TRUNKINGS LUMINAIRES CABLE REELS FUSES SWITCHES CONNECTORS

INDEX

ACS: Assembly for construction site.

t. 69

DISTRIBUTION ASSEMBLIES

DEFINITIONS

DISTRIBUTION ASSEMBLY

A combination of one or more low-voltage protective and operating devices with any possible measuring, indicating, protective and/or regulatory devices, entirely installed under the manufacturer's responsibility, with all internal wiring and mechanical connections, including the structural supporting parts.

Portable (or semi-stationary) ACS

An assembly designed to be used in a place where it is not permanently installed; its may be moved from one area to another on a construction site. Whenever an assembly has to be transported, it must first be disconnected.

- TTA: Mass-produced assembly

EURO P STAN EAN D EN 6 ARD 0439 -1

Mass -pro assem duced blies

TTA

An assembly conforming to a given type or construction system or in any case without modifications from it such as to affect its performance to a decisive extent compared to the type tested assembly as prescribed by the Standard.

- PTTA: Non-mass produced assembly

EURO P STAN EAN D EN 6 ARD 0439 -1

on-m a produ ss assem ced blies

PTTA N

Assemblies containing both configurations tested by type tests and configurations not tested by type tests, provided that the latter are derived (eg. by calculation) from configurations which passed the prescribed tests.

- ACS Mass-produced assembly for construction sites

EURO P STAN EAN D EN 6 ARD 0439 -4

Mobile ACS

An ACS can be moved during progress of work on the building site and does not need to be disconnected.

Asse for co mblies nstru cti sites on

ACS

Combinations of one or more transformers or switches and their associated control, measuring, indicating, protective and setting devices, with all their wiring and mechanical connections as well as their bearing structures, designed and constructed for use indoors and outdoors on construction sites.

ACS assemblies must be mass-produced (TTA).

t. 70

TECHNICAL DATA

2

UNITS

Each ACS may include the following units: - Inlet unit The unit through which power is supplied (from the outside) to the assembly. - Outlet unit The unit through which power is supplied to one or more external circuits. - Transformer unit This unit may be either LV/FELV or LV/SELV. - Measuring unit A unit housing appliances for measuring the electric power.

1

PLUG& SOCKETS IEC309 EUREKA ADAPTORS EASIGO HEAVY DUTY CEEGO

2

COMBINATION UNITS

INLET UNIT

OMNIA ADVANCE QUADRA

Distribution assemblies

ACS

Safety extra-low voltage SELV: SCAME provides 220/24V~ Class F toroidal isolating transformers with power between 150 and 300 VA g.

MEGA MASTERBOX DOMINO BLOCK GOMMA PDU

3

ENCLOSURES & BOXES EASYBOX DOMINO BLOCK SCABOX ALUBOX ACCESSORIES

OUTLET UNIT

4

INSTALLATION ACCESSORIES TRUNKINGS LUMINAIRES CABLE REELS FUSES SWITCHES CONNECTORS

INDEX

BLOCK 4 Series: Wiring diagram of ACS assembly

t. 71

DISTRIBUTION ASSEMBLIES

TYPES OF ACS

The EN 60439-4 Standard classes distribution assemblies into 6 types depending on the specific end uses of the equipment installed in the construction site's electrical distribution system: - Power supply inlet and measuring ACS - Main distribution ACS - Distribution ACS - Transformer ACS - Final distribution ACS - Socket outlets ACS

Power supply inlet ASC di alimentazione and measuring ACS di entrata e di misura Main distribution ASC di distribuzione ACS principale I 630A

ASCDistribution di distribuzione ACS I = 125A ÷ 630A

Distribution ACS ASC di distribuzione I = 125A - 630A ÷ 630A

=

Transformer ACS ASC di I 630A trasformazione I 630A

Final distribution ASC di ACS distribuzione I I 125A finale125A

Distribution ASC di ACS distribuzione I = 125A - 630A ÷ 630A

Final distribution ASC di ACS distribuzione I I 125A finale125A

Final distribution ASC di ACS distribuzione I 125A finale I 125A

= = =

=

6 =ASC di prese a spina I 63A Socket outlets ACS

t. 72

TECHNICAL DATA

2

ACS SCAME

SCAME ACS assemblies are available for the functions listed below. Their specifications comply with those prescribed by the standards: Distribution ACS consisting of one inlet unit and several outlet units. - rated current between 125 A and 630 A - outgoing feeder cables connected to terminals or sockets - isolating device that can be padlocked in OFF position. Final distribution ACS consisting of one or more outgoing feeders - Max. rated current 125 A - isolating device can be padlocked in OFF position - no provision for delaying the tripping time of the protective devices - residual current device (RCD) with I dn < 30mA as additional protection against indirect contacts - max. 6 sockets protected by each RCD. Socket-outlet ACS mobile or portable - Max. rated current 63A - incoming cable connection either to appliance inlet or to connecting device - outgoing cables connected only to socket outlets - each socket outlet to be provided with its own overload protection. In addition, all socket outlets (max. 6) to be protected against indirect contacts by means of RCD with I dn > 30 mA. SCAME's factory-assembled MEGA, MASTERBOX and portable DOMINO and BLOCK Series assemblies have been designed and constructed for use on construction sites. These assemblies therefore comply with EN 60439-1 and EN 60439-4; in particular, they meet Standard requirements for the following uses: - MEGA assemblies: distribution ACS - MASTERBOX assemblies: final distribution ACS - DOMINO and BLOCK portable assemblies: socket outlet ACS NOTE: Two or more functions as described above may be combined in a single ACS assembly, eg. a socket outlet ACS may be combined with a transformer ACS. Compliance with the European Standard 60439-4 for assemblies for construction sites (ACS) will be mandatory in all CENELEC member countries.

1

PLUG& SOCKETS IEC309 EUREKA ADAPTORS EASIGO HEAVY DUTY CEEGO

2

COMBINATION UNITS OMNIA ADVANCE QUADRA

Distribution assemblies

MEGA MASTERBOX DOMINO BLOCK GOMMA PDU

3

CIRCUIT BREAKERS

Time/current tripping curves in conformity to IEC 898.

ENCLOSURES & BOXES EASYBOX DOMINO BLOCK SCABOX ALUBOX ACCESSORIES

C type

120 60 40 20 10 6 4 Minutes 2 1 40 20 Seconds 10 6 4 2 1 0.6 0.4 0.2 0.1 0.06 0.04 0.02 0.01 1

1.45 1.13

D type

120 60 40 20 10 6 4 Minutes 2 1 40 20 Seconds 10 6 4 2 1 0,6 0,4 0,2 0,1 0,06 0,04 0,02 0,01

1.45 1.13

4

INSTALLATION ACCESSORIES TRUNKINGS LUMINAIRES CABLE REELS FUSES SWITCHES CONNECTORS

c.a (a.c.) c.c. (d.c.) ···

~

c.a (a.c.) c.c. (d.c.) ···

~

INDEX

1,5

2

3

4

5 6 5

8 10 10

15 15

20

30

1

1,5

2

3

4

5 6 5

8 10 10

15 15

20 20

30 40 50 30

multiples of rated current

multiples of rated current

Tripping curve The circuit breakers housed in the assemblies comply with IEC 898 (EN 60898) and their tripping characteristic conforms to curve "C" of this standard. For special applications, contact your SCAME Dealer.

t. 73