Read Release_Notes_SFT2841_v10_4 text version

Schneider Electric Industries S.A.S. Power Monitoring and Control Power Department

Date : March 31, 2009 To : Whom it may concern

Address : Schneider Electric Industries Business Unit : Power Department : Power Monitoring and Control Electropole 38050 Grenoble Cedex 9 France

Telephone : Fax :

+33 (0)4 76.60.65.28 +33 (0)4 76.82 25 60

Subject : Sepam setting software SFT2841 Release Notes

Dear Sir or Madam,

In this document, you will find all the modifications that have been done to the Sepam setting software SFT2841. The corrections and enhancements that have been developed are explained. You will find also the software version from which the problem has been introduced.

Please be sure that UPWARD COMPATIBILTY is always ensured : the latest version of Sepam setting software SFT2841 is compatible with all the Sepam.

Yours Sincerely, J-Baptiste SAMUEL Sepam Product Manager Power Monitoring and Control POWER SCHNEIDER ELECTRIC

Copyright SCHNEIDER ELECTRIC 2009 Sepam setting software SFT2841 release notes ­ March, 2009 [email protected]

Page 1 /7

RELEASE NOTES OF SEPAM SETTING SOFTWARE SFT2841

Software Version Date 1.0 Jan 2000 2.0 Jun 2000 3.0 Oct 2000 New Feature New Feature New Feature New Feature 4.0 Aug 2001 Update (3.0) Update (3.0) 5.0 Feb 2002 5.1 May 2002 Update (4.0) New Feature Update (4.0) New Feature Update (5.2) Update (5.2) 5.2 5.2 4.0 3.0 3.0 4.0 New Features Updates: 1st faulty Version First release of SFT2841 software. Application S20 only SFT2841 capabilities extended to include new Sepam series 20 applications M20, T20 & B20 SFT2841 capabilities extended to include new Sepam series 20 applications B21 & B22 SFT2841 capabilities extended to include both SEPAM series 20 and SEPAM series 40 Corrections on Logic discrimination configuration Corrections on Sepam diagnostics functions Corrections on the Print and Upload functions. Enhancement of the verification of Logic Equations. Corrections on the Print function. Enhancement in the diagnosis window. Launching the on-line help sometimes failed Correction on settings of the 66 protection function (starts per hour) SFT2841 capabilities extended to include new SEPAM series 80, with following applications and their associated protection functions : - Substation S80, S81, S82 - TransformerT81,T82,T87 - Generator G82, G87, G88 ­ Motor M81, M87, M88 SFT2841 Remote connection new capability added for the connection with Sepam series 80 on a multi-point RS485 Modbus network Enhancements of the Graphical User Interface in order to have a more unified interface between Sepam series 20 and series 40 Enhancement in editing Logic Equations SFT2841 installation sometimes failed on some PCs. Some HMI windows in Korean were not properly displayed due to special Korean characters. The 67N protection function (directional earth fault) has been extended with a third protection method compliant with the Italian ENEL DK5600 specification. X X X X X X X X X X X 20 40 80

X

X X X

5.2 Dec 2002

6.0 Jul 2003

New Feature

X

New Feature New Feature New Feature Update (6.0) 6.1 Apr 2004 New Feature 6.0

X

X

X

X

X

Copyright SCHNEIDER ELECTRIC 2009 Sepam setting software SFT2841 release notes ­ March, 2009 [email protected]

Page 2 /7

Software Version Date

New Features /Update

Updates 1st faulty Version New Applications with associated protection functions : - Capacitor C86, - Busbar B80 and B83 - Substation S84 Customized applications Z81, Z82, Z83 Logical control function can be downloaded using Logipam application New configuration capabilities for MSC025 and MIMIC modules Edit/Create functions added for single line diagram and downloading MIMIC module Enhancements on downloading Sepam configuration. Enchantements on 87T protection fonction. SFT2841 Remote connection capability extended for connection with all Sepam units New communication interface for SFT remote connection via phone Modem and Modbus TCP/IP Local Area Network Configuration capability added for new ACE969 multi-protocol communication interface (Modbus, DNP3 and IEC60870-5-103) Complete Sepam documentation included in SFT2841 setup

20

40

80

New Feature

X

7.0 Jan 2006

New Feature New Feature New Feature

X X X X X X X X

7.01 Feb 2005 7.02 May 2005

New Feature New Feature New Feature

8.0 Jul 2005

New Feature New Feature New Feature New Feature

X

X

X

X X

X X

X X

The Helpreader tool is now compatible with Adobe Reader version 7 ModbusDriver installation failed when AutoExec.NT windows system file was missing or corrupted. This file is no more needed by new setup.

X

X

X

Update

8.0 SFT2841 setup was aborted in case of license registration issue. The new setup keeps running installing SFT2841 in trial mode. Sometimes SFT2841 abnormally finished and next it was sometimes not possible to start again SFT2841 application.

X

X

X

8.1 Nov 2005

Update

8.0

On some PCs, when system is overloaded by some applications like MediaPlayer or Web applications Modbus communication failed due to too many reception errors. In that case, SFT2841 was no more able to connect with Sepam. It was not possible to upload the configuration of Sepam series 20 or to print the configuration file when Sepam series 20 software version was lower than V0526 Although downloading logical equations is not allowed in remote connection with Sepam series 40, the HMI didn't lock properly this function. In front face connection mode with Sepam series 40, the download of logical equations and user messages (bitmap) failed on some PCs due to access time issue to the COM port.

X

X

X

Update

8.0

X

Update

8.0

X

Update

8.0

X

Copyright SCHNEIDER ELECTRIC 2009 Sepam setting software SFT2841 release notes ­ March, 2009 [email protected]

Page 3 /7

Software Version Date

New Features/ Update Update (8.0)

Updates 1st faulty Version 8.0 Downloading logical equations and user messages (bitmap) in front face connection mode with Sepam series 40 is possible only using ports COM1 to COM4. A new message error is displayed to indicate the incompatibility when trying to use a COM port greater than COM4. Therefore, to allow downloading when an USB converter is used, the converter must mapped on COM number less or equal to COM4

20

40

80

X

Update 8.1 Nov 2005 New Feature

8.0

The status of outputs O1 to O5 was not properly displayed on HMI windows Outputs status When Sepam series 80 is in major fault due to a missing MES module, communication with SFT2841 was lost. It is now possible to connect Sepam in order to modify the Sepam configuration and to remove the MES. When Sepam series 80 is in major fault due to an incompatibility between base and cartridge firmwares, SFT2841 displays a new message that gives the revision number of base and cartridge firmwares. It is now possible to measure I2 with 2TCs for Sepam. Warning: With 2 TCs, I2 can be measured but this value is not taken into account for the protection functions Communication Protocol DNP3 : It is now possible to set the threshold that starts the event transmission 2 new applications S23 and T23 have been created It is now possible to set the time and the date of the Sepam series 40 and 80 through setting software SFT2841 Directional Earth Fault protection 67N type 3 is available EPATR curves are available on Sepam series 80 : type B and type C for Earth fault protection X X

X

X

New Feature

X

New Feature New Feature 9.0 Jun 2006 New Feature New Feature New Feature New Feature

X

X X

X

X

X

X X X

Copyright SCHNEIDER ELECTRIC 2009 Sepam setting software SFT2841 release notes ­ March, 2009 [email protected]

Page 4 /7

Software Version Date

New Feature/ Update New Feature

Updates/ 1st faulty Version IEC61850 communication interface via ECI850 Sepam Server: The configuration capabilities of Sepam networks based on Ethernet has been extended to provide new functions for the configuration of the ECI850 Sepam server. Enhancement of the management of the Trip Circuit Supervision with protection 50BF: a new input "Breaker closed position" is added in the Logical Equations and Logipam program as input variable of the 50BF protection function. The status of the time delays used by LOGIPAM programs is now displayed by SFT2841. 4.0 9.0 8.1 9.0 The translation of "password" into Spanish has been corrected: replaced by contraseña The translation of "E_LAN/ S_LAN" into US English was not correct. It was not possible to upload or to print the configuration of Sepam series 20 whose firmware version was lower than V01xx When a user had prepared a Sepam settings file with values in Amps or % (threshold currents) out of the normal range, there was no fault message when loading this incorrect file into the Sepam. Using an Chinese Windows Operating System, the word "activity" of 38/49T protection for the application T20 and T23 was not translated When SFT2841 was connected in remote mode to a Sepam series 20, and when the remote setting was inhibited, if a session of SFT2841 was open in parallel in not-connected mode, it was not possible to make a modification in this session. When an incorrect protection setting was entered by the user in remote mode, SFT2841 didn't catch correctly the error and this could cause the closing of the communication with Sepam series 20. Now, the incorrect entry is refused by SFT2841 with no impact on the communication with Sepam. Some compatibility problems with Windows display on some PC have been corrected (some fields displayed with black shading instead of white shading) Decimal values was not accepted for setting the Io threshold of the 67 and 67N protections When SFT2841 was connected in remote mode to a Sepam series 40, if a new session of SFT2841 was launched in parallel in not-connected mode, it was not possible to enter Logical Equations or User messages in this new session although the interdiction should apply only for the remote mode. Although loading of Logical Equations is not possible in remote mode with Sepam series 40, when loading a configuration file into Sepam, SFT2841 let believe that Logical Equations defined in this file were taken into count by Sepam by displaying the equations defined in the file rather than the ones defined in Sepam. The SFT2841 was blocked when using a remote connection via phone modem.

20

40

80

X

X

X

New Feature

X

X

New Feature Update Update Update Update

X X X X X X X X

Update Update 10.0 May 2007 Update

2.0 8.0

X X

8.0

X

Update

1.0

X

Update Update

9.0 8.0

X X

Update

8.0

X

Update

9.0

X

Copyright SCHNEIDER ELECTRIC 2009 Sepam setting software SFT2841 release notes ­ March, 2009 [email protected]r-electric.com

Page 5 /7

Software Version Date

New Features

Updates/ 1st faulty Version 9.0 9.0 In IEC103 communication advanced parameters, the selection of the measurements groups was not saved correctly. When editing logical equations with editing assistance, the syntax was sometimes checked while the equation was not completely entered and a misplaced syntax error could be detected. The graphic representation of the On/Off status of the 3 icons defined in the Mimic Symbol Library for the Test, Local and Remote indications was inverted. The status of the Logipam internal bits (MX, MP, MS) was not correctly displayed after having displayed the window about the assignment of the logical inputs/outputs. For 87M protection, after having modified the setting « De-excitation » it was not possible to click on apply button When entering the value of the base current Ib, the maximum authorized value was not in accordance with the format accepted by SFT2841 for keyboarding the value. The Sepam setting software gets stuck: the debugging windows opens and Sepam setting software automatically shuts down while setting events in DNP3 protocol on an ACE969TP or an ACE969FO communication interface. The Sepam setting software gets stuck: the debugging windows opens and Sepam setting software automatically shuts down while editing label using the SEPAM menu access. When opening a Sepam configuration file, the Tripping curve setting of the 67N Unit 1 protection was not correctly displayed: it was always displayed with a definite time curve. With Sepam series 40 firmware above V5.0, logic equations and customized users messages was not loaded into Sepam when loading a configuration file into Sepam and when setting logic equations or customized users messages. New application Substation S43 with associated protection function. It is now possible to set the communication port between SFT2841 and Sepam from COM1 to COM245 for all types of Sepam. In Sepam configuration printout, the logic equation printout was limited to only one page of 62 lines. The printout is now extended up to 10 pages plus one specific page for printing the time delay values if any.

20

40

80

Update Update

X X

Update 10.0 May 2007

7.0

X

Update

9.0

X

Update Update

6.0 4.0

X X X

Update

10.0

X

Update

10.0

X

10.1 Oct 2007 Update

8.0

X

Update

10.0

X

New Feature 10.2 Dec 2007 New Feature New Feature

X X X

Copyright SCHNEIDER ELECTRIC 2009 Sepam setting software SFT2841 release notes ­ March, 2009 [email protected]

Page 6 /7

Software Version Date

New Features

Updates/ 1st faulty Version Compatibility with Microsoft® Vista Service Pack 1 (or higher) operating system. When configuring a SFT2841 Remote access via phone modem, the modem serial link communication speed setting range is extended to 115 Kbits/s. With SFT2841 Phone Modem Remote access, when configuring the phone number, possibility to use all characters you need in the modem AT dial string (like dial pause "," or "+"). Possibility to run your own waveform fault records viewer instead of the SFT2826 software. 10.2 10.2 New releases of Schneider Modbus Driver for Windows XP/Vista management: Modbus Driver v1.8 on XP® and v2.0 on Vista®. When modifying the advanced parameters of the 87T, the setting page was not correctly updated and some parameters were not displayed or could not be modified (High tripping set point, curve slope change point, H2 & H5 restraint settings). Addition of an integrity check of the Sepam network configuration file (*.NET) before running by SFT2841. Enhancements on Sepam configuration download & upload processing. The field for the analog variable type selection in the MSA module setting window has been enlarged to display correctly the scale and unit of the analog variable.

20

40

80

New Feature New Feature New Feature New Feature 10.3 Aug. 2008 Update Update

X X

X X

X X

X

X

X

X X

X X

X X X

Update Update Update

8.0 8.0 7.0

X

X

X X

X

Software Version Date 10.4 March 2009

New Features

Updates/ 1st faulty Version Over voltage protection (ANSI 59): increase of the accuracy of to 1,5% of Unp by step of 1V on the B83 application. Compliance with CEI 0-16 standard (Italia, 2009)

20

40

80

New Feature New Feature

X X

UPWARD COMPATIBILITY: The latest version of Sepam setting software SFT2841 is compatible with all the Sepam

Copyright SCHNEIDER ELECTRIC 2009 Sepam setting software SFT2841 release notes ­ March, 2009 [email protected]

Page 7 /7

Information

Release_Notes_SFT2841_v10_4

7 pages

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

428318


You might also be interested in

BETA
Release_Notes_SFT2841_v10_4