Read Microsoft Word - Plumbing.doc text version

Firestop Submittal

Project Name: Location: Submitted by: Submittal assembled by:

Distributed in Oregon, Washington, Idaho. by:

2628 Pearl Road Medina, Ohio 44256 (866) 209-2404

935 SE 12th Ave Portland, OR 97214 (503) 351-2098

Tremco Fire Protection Systems Group

Submittal for Firestopping of Plumbing Systems

Section 07840

Product Data Sheets TREMstop Acrylic GG TREMstop D TREMstop Fyre-Sil Gun Grade TREMstop IA (Intumescent Acrylic) TREMstop Strap TREMstop WS General Certificate of Conformance Systems System Name C-AJ-1302 Products TREMstop Intumescent Acrylic Penetrant Details 12" Steel, Iron, 6" Conduit, Copper Tube, Copper Pipe, 4" EMT; Optional Sleeve, 4-1/4" or 3-3/4" Mineral Wool, Backer Rod, Caulk Only Optional, Install from Bottom Optional 8" Steel , Iron, 6" Conduit, 4" EMT, Copper Tube, Copper Pipe; 4" Mineral Wool, Multiple Penetrants 3" PVC, CPVC, RNC; Optional Backer Rod, Caulk Only 1-1/2", 2", 3", 4" or 6" PVC, ccPVC, 1-1/2", 2" ,3" or 4" ABS, ccABS, PVDF F Rating 2 & 3 hr.

C-AJ-1448 C-AJ-2184 C-AJ-2233

TREMstop Intumescent Acrylic TREMstop Intumescent Acrylic

3 hr. 2 hr. 2 hr. 2 hr. 2 hr. 2 hr. 2 hr.

TREMstop-D, TREMstop Acrylic Gun Grade, TREMstop Intumescent Acrylic, Fyre-Sil Gun Grade C-AJ-2507 TREMstop Strap, TREMstop Acrylic Gun 3" PVC, RNC, ABS; Optional Sleeve Grade, TREMstop Intumescent Acrylic, Fyre-Sil Gun Grade C-AJ-2508 TREMstop Strap, TREMstop Acrylic Gun 4" ABS; Optional Sleeve Grade, TREMstop Intumescent Acrylic, Fyre-Sil Gun Grade F-B-2027 TREMstop Strap, TREMstop Acrylic Gun 4" PVC, ccPVC, CPVC, RNC, ABS; Grade, TREMstop Intumescent Acrylic, Optional Sleeve Fyre-Sil Gun Grade RQ/PHV 120-02 TREMstop Strap, TREMstop Acrylic Gun 4" PVC Grade, TREMstop Intumescent Acrylic, Fyre-Sil Gun Grade RQ/PHV 120-04 TREMstop Strap, TREMstop Acrylic Gun Grade, TREMstop Intumescent Acrylic, Fyre-Sil Gun Grade RQ/PV 120-01 TREMstop Strap, TREMstop Acrylic Gun Grade, TREMstop Intumescent Acrylic, Fyre-Sil Gun Grade W-L-1158 TREMstop Intumescent Acrylic W-L-1302 TREMstop Acrylic Gun Grade, TREMstop Intumescent Acrylic, Fyre-Sil Gun Grade Continued on Page 2

4" PVC, 3" ccPVC, ABS, ccABS, , 50 Pa 4" PVC, ccPVC, ABS, ccABS, 3" FRPP, 2" CPVC, 50 Pa 12" Steel, Iron, 6" Conduit, 4" EMT, Copper Tube, Copper Pipe; Optional Backer Rod 2" Steel, Iron, Conduit, EMT; 2-1/2" Mineral Wool, Multiple Penetrants

2 hr. 2 hr. 1 & 2 hr. 1 & 2 hr.

www.tremcofirestop.com

Technical Services: 866-209-2404 Tremco Fire Protection Systems Group 2628 Pearl Road Medina, OH 44256

Tremco Fire Protection Systems Group

Submittal for Firestopping of Plumbing Systems

Section 07840

W-L-2083 W-L-2129 W-L-2429

TREMstop-WS, TREMstop-D, TREMstop Acrylic Gun Grade, TREMstop Intumescent Acrylic, Fyre-Sil Gun Grade TREMstop Intumescent Acrylic TREMstop Strap, TREMstop Acrylic Gun Grade, TREMstop Intumescent Acrylic, Fyre-Sil Gun Grade

8" PVC, 1-1/4" CPVC 2" PVC, CPVC; Optional Backer Rod 3" PVC, RNC

1 & 2 hr. 1 & 2 hr. 1 & 2 hr.

MSDS Sheets

TREMstop Acrylic GG TREMstop D TREMstop Fyre-Sil Gun Grade TREMstop IA (Intumescent Acrylic) TREMstop Strap TREMstop WS

www.tremcofirestop.com

Technical Services: 866-209-2404 Tremco Fire Protection Systems Group 2628 Pearl Road Medina, OH 44256

TREMstop Acrylic (GG)

Gun Grade Acrylic Firestopping Sealant

PRODUCT DESCRIPTION:

TREMstop Acrylic (GG) is a single component, water-based, acrylic firestop sealant. TREMstop Acrylic (GG) is a high performance, antifungal sealant capable of plus or minus 25 percent movement in fire-rated joints. TREMstop Acrylic (GG) is an economical choice when used as a cold smoke seal for 2 to 3 hour fire-rated penetrations and up to a 2 hour fire rating for up to 2 inch joints. TREMstop Acrylic is also available in a sprayable grade that is compatible with the gun grade.

ADVANTAGES:

· High performance, elastomeric sealant specially formulated for firestopping applications · Capable of plus or minus 25% movement · Easy gunning · Easy clean up with water · Paintable when fully cured · The most economical and user-friendly firestopping sealant on the market · Listed up to a 2 hour fire rating in joints · Listed up to a 3 hour fire rating in through penetrations

BASIC USES:

Penetrations · Steel, copper, iron, and EMT pipe · PVC and ccPVC pipe · ABS and ccABS pipe · CPVC pipe · Romex cable, jacketed cables and bundles · Insulated pipe · Duct work Building Assemblies · Concrete floor or wall · Gypsum wallboard · Wood floor/ceiling · Metal pan deck · Joints · Hollowcore concrete

PHYSICAL PROPERTIES:

Color: White, limestone, rust red pH: 7.0-9.0 Shore "A" Hardness: 15 ­ 20 (ASTM C-661) VOC (grams/liter): 65 Application Temperature 40°F ­ 110°F (Min./Max.): (5°C ­ 43°C) Flame Spread: 15 (ASTM E-84) Smoke Develop: 0 (ASTM E-84) Cure Time: 3-5 Days Skin Over Time: Overnight Movement Capability: Tested to ±25% (UL 2079; class I, II, III) Sound Transmission (STC Rating): 52 Shelf life: 1 year Freeze Sensitive: yes Accepts Paint: yes

PACKAGING:

10.1 fl. oz. (300 ml, 18 in3) cartridge 30/case 20 fl. oz. (600 ml, 36 in3) sausage 15/case 28.7 fl. oz. (850 ml, 51 in3 ) cartridge 12/case 5 gal. (19 L, 1155 in3) pail

TREMstop Acrylic (GG)

TREMstop Acrylic (GG)

Gun Grade Acrylic Firestopping Sealant

INSTALLATION TECHNIQUES:

Refer to the Tremco Firestop Manual or the UL/ULC Fire Resistance Directory for specific application instructions. The firestop system details will cover the required sealant depth, necessary amount of packing material and the permitted joint size or annular space. TREMstop Acrylic (GG) is a gunnable sealant, typically applied using conventional caulking equipment.

WARRANTY:

Tremco warrants its Firestop Materials to be free of defects, but makes no warranty as to appearance or color. Since methods of application and on-site conditions are beyond our control and can affect performance, Tremco makes no other warranty, expressed or implied, including warranties of MERCHANTABILITY and FITNESS FOR A PARTICULAR PURPOSE with respect to Firestop Materials. Tremco's sole obligation shall be, at its option, to replace or to refund the purchase price of the quantity of the Firestop Materials proved to be defective and Tremco shall not be liable for any loss or damage.

TECHNICAL SERVICES

For more information, contact technical services: Toll free: (866) 209-2404 Fax: (330) 220-7055 E-mail: [email protected]

O R DER PLA CEM ENT:

To place an order, contact customer service: United States: (800) 321-7906 Canada: (800) 363-3213

LIMITATIONS:

· Not recommended for use in passive fire containment systems not listed or approved by Tremco. · Do not apply over damp or contaminated surfaces.

APPLICABLE TEST STANDARDS:

UL 1479 (ASTM E-814) UL 263 (ASTM E-119) UL 723 (ASTM E-84) UL 2079 (ASTM E-1966) ASTM E-1399 CAN4-S115M CAN/ULC-S101M

T H E

T R E M C O

F A M I L Y

O F

P R O D U C T S

I S

R E C O G N I Z E D

B Y

Tremco Incorporated · 2628 Pearl Road · Medina, Ohio 44256 USA Phone: (330) 273-8828 · Fax: (330) 220-7075 · Toll Free: (866) 209-2404 Tremco Canada Division · 215 Wicksteed Ave. · Toronto, Ontario M4H 1G7 Canada Phone: (416) 467-2455 · Fax: (800) 361-3514 · Toll Free: (800) 363-3213 For MSDS or additional Spec Data Sheets, contact customer service at (800) 321-7906 or visit www.tremcofirestop.com

FPSG061 7/04

A Prefabricated Firestopping Collar Device

PRODUCT DESCRIPTION:

TREMstop D

ADVANTAGES:

· Pre-fabricated collar device with one-step installation · Great solution for odd-sized pipes and applications where closing a fixed clamp is impossible · Eliminates labor costs associated with cutting, measuring and installation · Hose clamp sealing system makes securing the device fast and easy · Available to fit a wide variety of pipe sizes · Listed up to a 3 hour fire rating TREMstop D is a pre-fabricated collar device used to firestop nonmetallic pipe penetrations. TREMstop D is a combination of TREMstop MCR and TREMstop WS formed into a specific sized device. Installing TREMstop D will save on labor costs associated with the cutting, measuring and installation of the field fabricated TREMstop WS/MCR system. TREMstop D is available in sizes ranging from 1.5 in. to 12 in. (3.8 cm to 30.5 cm) to fit industry standard pipe diameters. TREMstop D uses a hose clamp sealing system for securing the device around the penetrating items. The hose clamp sealing system is necessary for odd pipe sizes or pipes where it is impossible to close a fixed clamp sealing system. The device is simple to install using a power driver or a screwdriver.

BASIC USES:

Penetrations · PVC and ccPVC pipe · ABS and ccABS pipe · FRPP pipe · PVDF pipe Building Assemblies · Concrete floor or wall · Wood floor/ceiling · Gypsum wallboard · Fluted metal deck · Hollowcore concrete

PHYSICAL PROPERTIES:

· 28-gauge steel collar · Zinc coated · See TREMstop WS data sheet for physical properties of wrap strip TREMstop TREMstop TREMstop TREMstop TREMstop TREMstop TREMstop TREMstop

PACKAGING:

D D D D D D D D 1.5 in. 2 in. 3 in. 4 in. 6 in. 8 in. 10 in. 12 in. (3.8 (5.1 (7.6 (10.2 (15.2 (20.3 (25.4 (30.5 cm) 12/case cm) 10/case cm) 10/case cm) 6/case cm) 2/case cm) 2/case cm) 1/case cm) 1/case

Sizes greater than 12 in. (30.5 cm) available upon request. Half sizes appropriate for hubs also available upon request.

TREMstop D

A Prefabricated Firestopping Collar Device

INSTALLATION TECHNIQUES:

Refer to the Tremco Firestop Manual or the UL/ULC Fire Resistance Directory for specific application instructions. TREMstop D is easily installed by wrapping the device around the penetrating item and securing the hose clamp. Bend the tabs outward and slide the device flush with the wall or floor. Mechanically fasten the TREMstop D with the correct amount of fasteners, symmetrically located, to the building assembly. See Tremco TREMstop D Installation Guide for further detail.

TREMstop D

WARRANTY:

Tremco warrants its Firestop Materials to be free of defects, but makes no warranty as to appearance or color. Since methods of application and on-site conditions are beyond our control and can affect performance, Tremco makes no other warranty, expressed or implied, including warranties of MERCHANTABILITY and FITNESS FOR A PARTICULAR PURPOSE with respect to Firestop Materials. Tremco's sole obligation shall be, at its option, to replace or to refund the purchase price of the quantity of the Firestop Materials proved to be defective and Tremco shall not be liable for any loss or damage.

TECHNICAL SERVICES

For more information, contact technical services: Toll free: (866) 209-2404 Fax: (330) 220-7055 E-mail: [email protected]

O R DER PLA CEM ENT:

To place an order, contact customer service: United States: (800) 321-7906 Canada: (800) 363-3213

LIMITATIONS:

· Not recommended for passive fire containment systems not listed or approved by Tremco.

APPLICABLE TEST STANDARDS:

UL 1479 (ASTM E-814) UL 263 (ASTM E-119) UL 723 (ASTM E-84) CAN4-S115M CAN/ULC-S101M

T H E

T R E M C O

F A M I L Y

O F

P R O D U C T S

I S

R E C O G N I Z E D

B Y

Tremco Incorporated · 2628 Pearl Road · Medina, Ohio 44256 USA Phone: (330) 273-8828 · Fax: (330) 220-7075 · Toll Free: (866) 209-2404 Tremco Canada Division · 215 Wicksteed Ave. · Toronto, Ontario M4H 1G7 Canada Phone: (416) 467-2455 · Fax: (800) 361-3514 · Toll Free: (800) 363-3213 For MSDS or additional Spec Data Sheets, contact customer service at (800) 321-7906 or visit www.tremcofirestop.com

FPSG065 7/04

Single Component, Silicone Firestopping Sealant

PRODUCT DESCRIPTION:

TREMstop Silicone (Fyre-sil) s

ADVANTAGES:

· Single component, neutral cure silicone firestopping sealant · Capable of plus or minus 25% movement in a fire-rated joint · Easy gunning · Approved for both through penetrations and joint applications · Available in self-leveling (SL) or gun grade (GG) · Approved for use in food processing facilities in Canada · Naturally fungal-resistant and water-tight · Listed up to a 4 hour fire rating TREMstop Silicone is a single component, neutral cure, silicone firestopping sealant. This elastomeric, high performance sealant is capable of plus or minus 25 percent movement in a fire-rated joint. TREMstop Silicone is available in selfleveling (SL) or non-sag gun grade (GG) formula for ASTM E-814 through penetrations. TREMstop Silicone is tested for up to a four hour fire rating by independent laboratories and is approved for both through penetrations and joint applications. This high grade sealant is both water-tight and naturally fungalresistant. TREMstop is approved by Agriculture Canada and Health and Welfare Canada for use in food processing plants.

BASIC USES:

Penetrations · Steel, iron, copper and EMT pipe · Fiberglass insulated pipe · Jacketed cables and bundles · Bus ducts · Mixed penetrations Building Assemblies · Concrete wall or floor · Gypsum wallboard · Joints · Curtain wall · Hollowcore concrete · Wood floor/ceiling · Fluted Metal Deck

PHYSICAL PROPERTIES:

Limestone, rust red pH: 7.0 - 9.0 Shore "A" Hardness: 15 (ASTM C-661) VOC (grams/liter): 0 Application Temperature 40°F ­ 110°F (Min./Max.): (5°C ­ 43°C) Flame Spread: 0 (ASTM E-84) Smoke Develop: 15 (ASTM E-84) Cure Time: 7 ­ 14 days (ASTM C-679) Skin Over Time: Overnight Movement Capability: Tested to ±25% (UL 2079; class I, II, III) Sound Transmission (STC Rating): 53 Shelf Life: 1 year Accepts Paint: No Color:

PACKAGING:

For gun grade: 10.1 fl. oz. (300 ml, 18 in3) cartridge 30/case 20 fl. oz. (600 ml, 36 in3) sausage 15/case 28.7 fl. oz. (850 ml, 51 in3) cartridge 12/case 4.5 gallon (17 L, 1040 in3) pail For self-leveling: 20 fl. oz. (600 ml, 36 in3) sausage 15/case 28.7 fl. oz. (850 ml, 51 in3) cartridge 12/case 4.5 gallon (17 L, 1040 in3) pail

TREMstop Silicone (Fyre-Sil)

TREMstop Silicone (Fyre-sil) s

Single Component, Silicone Firestopping Sealant

LIMITATIONS:

· Not recommended for use in passive fire containment systems not listed or approved by Tremco. · Do not apply over damp or contaminated surfaces.

INSTALLATION TECHNIQUES:

Refer to the TREMco Firestop Manual or the UL/ULC Fire Resistance Directory for specific application instructions. The firestop system details will cover the required sealant depth, necessary amount of packing material and the permitted joint size or annular space. TREMstop Silicone is a gunnable sealant, typically applied using conventional caulking equipment. TREMstop self-leveling allows for easy application in hard to reach spaces or configurations.

WARRANTY:

Tremco warrants its Firestop Materials to be free of defects, but makes no warranty as to appearance or color. Since methods of application and on-site conditions are beyond our control and can affect performance, Tremco makes no other warranty, expressed or implied, including warranties of MERCHANTABILITY and FITNESS FOR A PARTICULAR PURPOSE with respect to Firestop Materials. Tremco's sole obligation shall be, at its option, to replace or to refund the purchase price of the quantity of the Firestop Materials proved to be defective and Tremco shall not be liable for any loss or damage.

APPLICABLE TEST STANDARDS:

UL 1479 (ASTM E-814) UL 263 (ASTM E-119) UL 723 (ASTM E-84) UL 2079 (ASTM E-1966) ASTM E-1399 CAN4-S115M CAN/ULC-S101M

TECHNICAL SERVICES

For more information, contact technical services: Toll free: (866) 209-2404 Fax: (330) 220-7055 E-mail: [email protected]

O R DER PLA CEM ENT:

To place an order, contact customer service: United States: (800) 321-7906 Canada: (800) 363-3213

T H E

T R E M C O

F A M I L Y

O F

P R O D U C T S

I S

R E C O G N I Z E D

B Y

Tremco Incorporated · 2628 Pearl Road · Medina, Ohio 44256 USA Phone: (330) 273-8828 · Fax: (330) 220-7075 · Toll Free: (866) 209-2404 Tremco Canada Division · 215 Wicksteed Ave. · Toronto, Ontario M4H 1G7 Canada Phone: (416) 467-2455 · Fax: (800) 361-3514 · Toll Free: (800) 363-3213 For MSDS or additional Spec Data Sheets, contact customer service at (800) 321-7906 or visit www.tremcofirestop.com

FPSG064 7/04

Intumescent Acrylic Firestopping Sealant

PRODUCT DESCRIPTION:

TREMstop IA

ADVANTAGES:

· Single component, water-based, intumescent acrylic · Expands to fill voids left when combustible materials burn away during a fire · Approved for 95% of the applications encountered on a project · Easy gunning · Antifungal properties · Excellent flexibility · Paintable once fully cured · Listed up to a 4 hour fire rating TREMstop IA is a single component, water-based, intumescent acrylic firestop sealant that will expand to fill any void left when combustible materials burn away during a fire. TREMstop IA is a unique, firestopping sealant that has been tested at independent laboratories to treat 95 percent of the applications commonly encountered on a project. TREMstop IA has exceptional sealant qualities, including superb unprimed adhesion, easy gunning, antifungal properties and the ability to be painted once fully cured.

BASIC USES:

Penetrations · Steel, copper and EMT pipe · Plastic pipe (vented and closed) · Romex cables, jacketed cables and bundles · Duct work · PVC and ccPVC pipe · ABS and ccABS pipe · CPVC pipe · Fiberglass insulated pipe · AB/PVC and cellular glass pipe insulation · Mixed penetrations Building Assemblies · Concrete wall or floor · Gypsum wallboard · Wood floor/ceiling · Stairway conditions · Joints · Hollowcore concrete

PHYSICAL PROPERTIES:

Color: pH: Shore "A" Hardness: (ASTM C-661) VOC (grams/liter): Application Temperature (Min./Max.): Flame Spread: (ASTM E-84) Smoke Develop: (ASTM E-84) Cure Time: (ASTM C-679) Skin Over Time: Movement Capability: (UL 2079; class II, III) Sound Transmission (STC Rating): Shelf Life: Freeze Sensitive: Accepts Paint: Rust red 7.0 ­ 10.0 15 ­ 20 0 40ºF ­ 110ºF (5ºC ­ 43ºC) 0 0 3 ­ 5 days Overnight ± 3%

PACKAGING:

10.1 fl. oz. (300 ml, 18 in3) cartridge 30/case 20 fl. oz. (600 ml, 36 in3) sausage 15/case 28.7 fl. oz. (850 ml, 51 in3) cartridge 12/case 5 gal. (19 L, 1155 in3) pail

52 1 year Yes Yes

TREMstop IA

Intumescent Acrylic Firestopping Sealant

INSTALLATION TECHNIQUES:

Refer to the Tremco Firestop Manual or the UL/ULC Directory for specific application instructions.

TREMstop IA

WARRANTY:

Tremco warrants its Firestop Materials to be free of defects, but makes no warranty as to appearance or color. Since methods of application and on-site conditions are beyond our control and can affect performance, Tremco makes no other warranty, expressed or implied, including warranties of MERCHANTABILITY and FITNESS FOR A PARTICULAR PURPOSE with respect to Firestop Materials. Tremco's sole obligation shall be, at its option, to replace or to refund the purchase price of the quantity of the Firestop Materials proved to be defective and Tremco shall not be liable for any loss or damage.

LIMITATIONS:

· Not recommended for use with passive fire containment systems not listed or approved by Tremco.

TECHNICAL SERVICES

For more information, contact technical services: Toll free: (866) 209-2404 Fax: (330) 220-7055 E-mail: [email protected]

O R DER PLA CEM ENT:

To place an order, contact customer service: United States: (800) 321-7906 Canada: (800) 363-3213

APPLICABLE TEST STANDARDS:

UL 1479 (ASTM E-814) UL 263 (ASTM E-119) UL 723 (ASTM E-84) UL 2079 (ASTM E-1966) ASTM E-1399 CAN4-S115M CAN/ULC-S101M

T H E

T R E M C O

F A M I L Y

O F

P R O D U C T S

I S

R E C O G N I Z E D

B Y

Tremco Incorporated · 2628 Pearl Road · Medina, Ohio 44256 USA Phone: (330) 273-8828 · Fax: (330) 220-7075 · Toll Free: (866) 209-2404 Tremco Canada Division· 215 Wicksteed Ave. · Toronto, Ontario M4H 1G7 Canada Phone: (416) 467-2455 · Fax: (800) 361-3514 · Toll Free: (800) 363-3213 For MSDS or additional Spec Data Sheets, contact customer service at (800) 321-7906 or visit www.tremcofirestop.com

FPSG063 7/04

TREMstop Strap

PRODUCT DESCRIPTION:

TREMstop Strap is a state-of-the art system that provides easily installed firestopping for your closed or vented plumbing system. This new intumescent strap can be used in place of a traditional firestopping collar device. It is simple to install by wrapping the strap around the pipe, fastening the ends to each other with the attached tab and sliding it into place within the annular space. This easily installed system does not require fasteners reducing installation time. Available for 11/2 in., 2 in., 3 in. and 4 in. diameter pipes for most nonmetallic penetrations.

A Convenient, One-Piece Flexible Intumescent Strap for Plastic Pipe

ADVANTAGES:

· One-piece flexible intumescent strap is easily applied in seconds around a nonmetallic pipe penetration through a fire-rated floor or wall assembly. · Can be installed during the roughin-stage or as a retrofit. · Available for 11/2 in., 2 in., 3 in. and 4 in. diameter pipes · Does not require special tools or compaction of mineral wool or backer material · Extremely environmentally stable and resistant to humidity and/or immersion in water · Easily installed from the top or bottom of a slab and tucked into the opening. · Listed up to a 2 hour fire rating

BASIC USES:

Penetration · PVC and ccPVC · ABS and ccABS · CPVC · FRPP Building Assemblies · Concrete floors or walls · Hollow core concrete · Fluted metal deck · Gypsum wallboard · Wood floor/ceiling

PHYSICAL PROPERTIES:

Nominal Size 11/2 in. 2 in. 3 in. 4 in. Overall Length -- in. (cm) Approximately 97/8 (25) Approximately 117/8 (30) Approximately 16 (40.6) Approximately 203/4 (52.7)

PACKAGING:

11/2 in. TREMstop Strap 2 in. TREMstop Strap 3 in. TREMstop Strap 4 in. TREMstop Strap 36/case 36/case 24/case 16/case

· Resistant to humidity and/or immersion in water

TREMstop Strap

TREMstop Strap

INSTALLATION TECHNIQUES:

Refer to the Tremco Firestop Manual or the UL/ULC Fire Resistance Directory for specific instructions. Select the proper TREMstop Strap for the pipe application based on the size and type, along with the fire rating and construction of the floor or wall assembly being penetrated. Wrap the TREMstop Strap around the pipe and fasten using the integral adhesive strip. Slide into annular space.

A Convenient, One-Piece Flexible Intumescent Strap for Plastic Pipe

WARRANTY:

Tremco warrants its Firestop Materials to be free of defects, but makes no warranty as to appearance or color. Since methods of application and on-site conditions are beyond our control and can affect performance, Tremco makes no other warranty, expressed or implied, including warranties of MERCHANTABILITY and FITNESS FOR A PARTICULAR PURPOSE with respect to Firestop Materials. Tremco's sole obligation shall be, at its option, to replace or to refund the purchase price of the quantity of the Firestop Materials proved to be defective and Tremco shall not be liable for any loss or damage.

TECHNICAL SERVICES

For more information, contact technical services: Toll free: (866) 209-2404 Fax: (330) 220-7055 E-mail: [email protected]

O R DER PLA CEM ENT:

To place an order, contact customer service: United States: (800) 321-7906 Canada: (800) 363-3213

APPLICABLE TEST STANDARDS:

UL 1479 (ASTM E-814) CAN4-S115M including 50pa Positive Pressure for DWV piping

T H E

T R E M C O

F A M I L Y

O F

P R O D U C T S

I S

R E C O G N I Z E D

B Y

Tremco Incorporated · 2628 Pearl Road · Medina, Ohio 44256 USA Phone: (330) 273-8828 · Fax: (330) 220-7075 · Toll Free: (866) 209-2404 Tremco Canada Division · 215 Wicksteed Ave. · Toronto, Ontario M4H 1G7 Canada Phone: (416) 467-2455 · Fax: (800) 361-3514 · Toll Free: (800) 363-3213 For MSDS or additional Spec Data Sheets, contact customer service at (800) 321-7906 or visit www.tremcofirestop.com

FPSG057 7/04

Graphite-Based Intumescent Firestopping Wrap Strip

PRODUCT DESCRIPTION:

TREMstop WS (Wrap Strip) is a graphite-based intumescent wrap strip used to treat combustible penetrations. Under heat, TREMstop WS creates a hard char to prevent the spread of flame, smoke, toxic fumes and water through voids created when combustible penetrations burn. TREMstop WS is a highly flexible laminate that is easy to work with, handle, cut and fabricate. The amount of wraps necessary is determined by independent testing based upon the type of penetration and the amount of time for which the building assembly is rated. During a fire, TREMstop WS will expand up to 10 times its normal size. TREMstop WS is available in two sizes. TREMstop WS1 (rolls) is primarily used for nonmetallic piping penetrations with a 4 in. (10.2 cm) diameter or less. TREMstop WS2 (strips) is primarily used for nonmetallic piping penetrations ranging from six to 10 inches (15.2 cm to 25.4 cm) in diameter but may also be used within the firestop systems for TREMstop WS1.

TREMstop WS

ADVANTAGES:

· Creates a hard char to prevent the spread of fire, smoke, toxic fumes and water through voids created when combustible penetrations burn · Excellent firestop solution for pipe penetrations with diameters less than 10 inches · Easy-to-handle, cut and fabricate on the jobsite · Available in rolls or pre-cut strips to accommodate virtually any job · Will expand up to 10 times its normal size when exposed to fire · Listed up to a 2 hour fire rating

BASIC USES:

Penetrations · PVC and ccPVC pipe · CPVC pipe · ABS and ccABS pipe · PVDF pipe · FRPP pipe · Metallic pipe with fiberglass or AB/PVC insulation Building Assemblies · Concrete floor or wall · Gypsum wallboard · Wood floor/ceiling · Fluted metal deck · Hollowcore concrete

PHYSICAL PROPERTIES:

Color: Odor: Flame Spread: (ASTM E-84) Smoke Develop: (ASTM E-84) Grey None 0 0

PACKAGING:

TREMstop WS1: 1.4 in. x 0.1 in. x 41.01 ft. (3.6 cm x .3 cm x 12.5 m) rolls 10 rolls/case TREMstop WS2: 2.4 in. x 0.1 in. x 43 in. (6 cm x .3 cm x 109.2 cm) 12 strips/bundle 12 bundles/case

TREMstop WS

TREMstop WS

INSTALLATION TECHNIQUES:

Refer to Tremo Firestop Manual or the UL/ULC Fire Resistance Directory for specific application instructions. The firestop system detail will cover the required amount of TREMstop WS necessary for the permitted pipe size or annular space. TREMstop WS is easily installed by wrapping the penetrations until the necessary amount of wraps are completed.

Graphite-Based Intumescent Firestopping Wrap Strip

WARRANTY:

Tremco warrants its Firestop Materials to be free of defects, but makes no warranty as to appearance or color. Since methods of application and on-site conditions are beyond our control and can affect performance, Tremco makes no other warranty, expressed or implied, including warranties of MERCHANTABILITY and FITNESS FOR A PARTICULAR PURPOSE with respect to Firestop Materials. Tremco's sole obligation shall be, at its option, to replace or to refund the purchase price of the quantity of the Firestop Materials proved to be defective and Tremco shall not be liable for any loss or damage.

TECHNICAL SERVICES

For more information, contact technical services: Toll free: (866) 209-2404 Fax: (330) 220-7055 E-mail: [email protected]

O R DER PLA CEM ENT:

To place an order, contact customer service: United States: (800) 321-7906 Canada: (800) 363-3213

LIMITATIONS:

· Not recommended for use with passive fire containment systems not listed or approved by Tremco.

APPLICABLE TEST STANDARDS:

UL 1479 (ASTM E-814) UL 263 (ASTM E-119) UL 723 (ASTM E-84) CAN4-S115M CAN/ULC-S101M

T H E

T R E M C O

F A M I L Y

O F

P R O D U C T S

I S

R E C O G N I Z E D

B Y

Tremco Incorporated · 2628 Pearl Road · Medina, Ohio 44256 USA Phone: (330) 273-8828 · Fax: (330) 220-7075 · Toll Free: (866) 209-2404 Tremco Canada Division · 215 Wicksteed Ave. · Toronto, Ontario M4H 1G7 Canada Phone: (416) 467-2455 · Fax: (800) 361-3514 · Toll Free: (800) 363-3213 For MSDS or additional Spec Data Sheets, contact customer service at (800) 321-7906 or visit www.tremcofirestop.com

FPSG055 7/04

Tremco Incorporated

2628 Pearl Road ­ Medina, Ohio 44256 Toll Free: 866.209.2404 _______ ____ ________________________

Sealant/Weatherproofing Division Fire Protection Systems Group

GENERAL CERTIFICATE OF CONFORMANCE DESCRIPTION: TREMCO© FIRE STOP PRODUCTS

TREMstop Acrylic TREMstop IA TREMstop PS1 & PS2 TREMstop D TREMstop UniCollar TREMstop Quickstop Coupling TREMstop Quickstop Sleeve TREMstop Strap Fyre-Sil Fyre-Can Device/Fyre-Can TM TREMstop FS Blanket Dymonic FC THC-900 TREMstop Acrylic SP TREMstop WS wrap strips TREMstop Fire Mortar TREMstop MP TREMstop Anchor Solid TREMstop Split Anchor TREMstop Putty

Fyre-Sil S/L Fyre-Can sleeve Blueskin Dymeric 240FC Vulkem 45SSL

THESE PRODUCTS ARE TESTED TO ONE OR MORE OF THE FOLLOWING STANDARDS:

· · · · ASTM E-119 (UL 263) ASTM E-814 (UL 1479) Fire Tests of Building Construction and Materials Time-Temperature Curve Fire Tests of Through-Penetration Fire Stops (under positive furnace pressure of minimum .01 inches of water column - 2.5+ Pascal) Surface Burning Characteristics of Building Materials Test for Fire Resistance of Building Joint Systems

ASTM E-84 (UL 723) UL 2079

No asbestos or PCB's are used or contained in these products.

11/19/2004

Senior Technical Engineer Date:

System No. C-AJ-1302

February 04, 2004 F Ratings - 2 and 3 Hr (See Item 3) T Rating -- 0 Hr

*Reproduced courtesy of Underwriters Laboratories, Inc.®

(UL / cUL)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

1. Floor or Wall Assembly -- Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete floor or min 4-1/2 in. thick reinforced lightweight or normal weight concrete wall. The min thickness of the wall is dependent upon the firestop configuration as shown in Item 3. Wall may also be constructed of any UL Classified Concrete Blocks*. Floor may also be constructed of any min 6 in. thick UL Classified hollow-core Precast Concrete Units*. If the firestop system is installed wit hin a hollow-core precast concrete unit, max diam of opening shall be 7 in. Otherwise, max diam of opening is 15-1/4 in. See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 1A. Metallic Sleeve -- (Optional) --Nom 14 in. diam (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces. The use of the steel sleeve is dependent upon the firestop configuration as shown in Item 3. 2. Through Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space the between pipe, conduit or tubing and periphery of opening is dependent up on the type and max diam of through penetrant and the firestop configuration as shown in Item 3. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe -- Nom 12 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -- Nom 12 in. diam (or smaller) cast or ductile iron pipe. C. Conduit -- Nom 4 in. diam (or smaller) steel electrical metallic tubing or nom 6 in. diam (or smaller) steel conduit. D. Copper Tubing -- Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe -- Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe. 3. Firestop System -- The F Rating of the firestop system is dependent upon the min thickness of the wall, type and max nom diam of the through penetrant, min and max annular space within the firestop system and the firestop configuration as shown in the table below: Min Thickness of Wall, In 4-3/4 4-3/4 4-3/4 4-1/2 4-1/2 4-1/2 5-1/4 5-1/4 Max Nom Diam of Through Penetrant, In. 12 6 4 12 6 4 8 4 Min, Max Annular, In. 0, 2 0, 2 0, 2 0, 2 0, 2 0, 2 0, 2 0, 2

Type of Through Penetrant Steel Pipe & Iron Pipe Steel Conduit, Copper Tube & Copper Pipe Steel EMT Steel Pipe & Iron Pipe Steel Conduit, Copper Tube & Copper Pipe Steel EMT Steel Pipe & Iron Pipe Steel Conduit, Copper Tube, Copper Pipe &

Use of Steel Sleeve Optional Optional Optional Not Applicable Not Applicable Not Applicable Optional Optional

Firestop Configuration A A A B B B C C

F Rating, Hr 3 3 3 2 2 2 3 3 (UL / cUL)

*Reproduced courtesy of Underwriters Laboratories, Inc.®

2

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

Steel EMT 4-1/2 4-1/2 Steel Pipe & Iron Pipe Steel Conduit, Copper Tube, Copper Pipe & Steel EMT 8 4 Not Applicable Not Applicable 0, 7/8 0, 7/8 D D 2 2

The firestop system shall consist of the following: Configuration A A. Packing Material -- Min 4-1/4 in thickness of 4 pcf mineral wool batt insulation firmly packed into opening as a permanent. Packing material to be recessed from top surface of floor or from both surfaces of wall and hollow-core precast concrete units as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* -- Caulk -- Min 1/4 in. of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall and hollow-core precast concret e units. TREMCO INC -- TREMstop Intumescent Acrylic Configuration B A. Packing Material -- Foam backer rod firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or both surfaces of wall and hollow-core precast concrete units as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* -- Caulk -- Min 1 in. thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall and hollow-core precast concrete units. A min 1/4 in. bead of fill material shall be applied at point contact location on top surface of floor and both surfaces of wall or hollow-core precast concrete units. TREMCO INC -- TREMstop Intumescent Acrylic Configuration C A. Packing Material -- Min 3-3/4 in. thickness of 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material shall be recessed 3/4 in. from bottom of floor or both surfaces of wall to accommodate the required thickness of fill material at bottom of floor. B. Fill, Void or Cavity Material* -- Caulk -- Min 3/4 in. of fill material applied within the annulus, flush with bottom surface of floor or with both surfaces of wall. TREMCO INC -- TREMstop Intumescent Acrylic Configuration D A. Packing Material -- Foam backer rod firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or both surfaces of wall and hollow-core precast concrete units as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* -- Caulk -- Min 1/2 in. thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall and hollow-core precast concrete units. A min 1/4 in. bead of fill material shall be applied at point contact location on top surface of floor and both surfaces of wall or hollow-core precast concrete units. TREMCO INC -- TREMstop Intumescent Acrylic *Bearing the UL Classification Mark

*Reproduced courtesy of Underwriters Laboratories, Inc.®

(UL / cUL)

3

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

System No. C-AJ-1448

October 04, 2002 F Rating -- 3 Hr T Rating -- 0 Hr

1. Floor or Wall Assembly -- Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete floor. Wall may also be constructed of any UL Classified Concrete Blocks*. Max area of opening is 192 sq in. with a max dimension of 24 in. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manuf acturers. 2. Through Penetrants -- One or more pipes, conduits or tubing to be installed within the opening. The space between the pipes, conduits or tubes shall be min 1 in. to max 2 in. The annular space between the pipes, conduits or tubing and the periphery of the opening shall be min 0 in. (point contact) to max 3-7/8 in. Pipes, conduits or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pi pe -- Nom 8 in. diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe -- Nom 8 in. diam (or smaller) cast or ductile iron pipe. C. Conduit -- Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT) or nom 6 in. diam (or smaller) rigid conduit. D. Copper Pipe -- Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe. E. Copper Tube -- Nom 4 in. diam (or smaller) Type L (or heavier) copper tube. 3. Firestop System -- The firestop system shall consist of the following: A. Forming Material -- Min 4 in. thickness of 4 pcf mineral wool batt insulation tightly packed into the annular space, recessed ½ in. from top surface of floor or both surfaces of wall to accommodate fill material (Item 3B). The insulation is formed from one piece, cut to the shape of the through opening, and tightly packed with a 50 percent compression in the width direction. Additional pieces of insulation tightly packed in to fill any remaining voids. Packing material recessed from top surface of floor or both surfaces of wall unit as required to accommodate fill material (Item 3B). B. Fill, Void or Cavity Material*- Caulk -- Min 1/2 in. thickness of fill material applied within annulus, flush with top surface of floor assembly or both surfaces of wall assembly. At point contact locations, min 1/4 in. diam bead of fill material applied at metallic pipe/concrete interface on top surface of floor or on both surfaces of wall. TREMCO INC -- TREMstop Intumescent Acrylic *Bearing the UL Classification Mark

*Reproduced courtesy of Underwriters Laboratories, Inc.®

(UL / cUL)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

System No. C-AJ-2184

November 25, 2003 F Rating -- 2 Hr T Ratings -- 1/4 and 1-1/2 Hr (See Item 3)

1. Floor or Wall Assembly -- Min 4-1/2 in. thick reinforced normal weight (140-150 pcf) concrete. Floor may also be constructed of any min 6 in. thick UL Classified hollow-core Precast Concrete Units*. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 5 in. See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 2. Through Penetrants -- One nonmetallic pipe or conduit to be installed either concentrically or eccentrically within the firestop system. The max diam of pipe or conduit, annular space, thickness of caulk, type of system and T Rating shall be as specified in the table below. Pipe or conduit to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of nonmetallic pipes may be used: A. Polyvinyl Chloride (PVC) Pipe -- Nom 3 in. diam (or smaller) Schedule 40 solid core PVC pipe for use in closed (process or supply) or vented (drain waste on vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe -- Nom 3 in. diam (or smaller) SDR13.5 CPVC pip e for use in closed (process or supply) piping systems. C. Rigid Nonmetallic Conduit+ -- Nom 3 in. diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No. 70). 3. Firestop System -- The firestop system shall consist of the following: A. Packing Material (Optional) -- Foam backer rod firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall and hollow-core precast concrete units as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* -- Caulk -- Fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall and hollow-core precast concrete units as shown in the table below. When required, additional fill material to be installed such that a min 1/8 in. crown is formed around the penetrating item. *Reproduced courtesy of Underwriters Laboratories, Inc.® (UL / cUL)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

Max Diam of Pipe, In. 2 2 3

Annular Space, In. 1/4 to 3/8 3/4 to 1 3/4 to 7/8

Min Thkns of Caulk, In. 1/2 2 2

Crown Required Yes No No

Type of System++ C C, V C

T-Rating Hr 1-1/2 1/4 1-1/2

++-C: Closed (process or supply) piping systems only. V: Vented (drain, waste or vent) piping systems. TREMCO INC -- TREMstop Intumescent Acrylic +Bearing the UL Listing Marking *Bearing the UL Classification Mark

*Reproduced courtesy of Underwriters Laboratories, Inc.®

(UL / cUL)

2

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

System No. C-AJ-2233

March 11, 2004 F Rating -- 2 Hr T Ratings -- 1 and 2 Hr (See Item 3C)

1. Floor or Wall Assembly -- Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf (1600-2400 kg/cu meter) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow-core Precast Concrete Units*. Max diam of opening is 7 in. ( 178 mm). See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 2. Through Penetrants -- One nonmetallic pipe to be installed within the firestop system. The annular space shall be min 0 in. (point contact) to max 1/4 in. (6 mm) for 1-1/2, 2 or 3 in. (38, 51, 76 or 102 mm) diam penetrants. For 4 and 6 in. (102 and 152 mm) diam penetrants, the annular space shall be min 0 in. (point contact) to max 1/2 in. (13 mm). Pipe to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of nonmetallic pipe may be used: A. Polyvinyl Chloride (PVC) Pipe -- Nom 1-1/2, 2, 3, 4 or 6 in. (38, 51, 76, 102 or 152 mm) diam Schedule 40 cellular or solid-core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. B. Acrylonitrile Butadiene Styrene (ABS) Pipe -- Nom 1-1/2, 2, 3 or 4 in. (38, 51, 76 or 102 mm) diam Schedule 40 cellular or solid-core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. C. Polyvinylidene Fluoride (PVDF) Pipe -- Nom 1-1/2, 2, 3 or 4 in. (38, 51, 76 or 102 mm) diam Schedule 40 PVDF pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. 3. Firestop System -- The firestop system shall consist of the following: A. Firestop Device* -- Firestop device shall be installed in accordance with the accompanying installation instructions. Device wrapped around the pipe and secured by using the attached hose clamp. In floors, device slid along the pipe until it abuts the bottom of the floor. Device secured to concrete with min 1/4 in. (6 mm) diam by 1-1/4 in. (32 mm) long steel masonry bolts in conjunction with 1-1/4 in. (32 mm) diam steel fender washers at every other anchor tab. As an alternate, device may be secured to concrete using 1-1/2 in. (38 mm) long powder-driven fasteners in conjunction with 1 in. (25 mm) diam steel fender washers through every other anchor tab. A min of two anchor bolts required for nom 1-1/2 and 2 in. (38 and 51 mm) diam pipes. A min of four anchor bolts required for 3 and 4 in. (176 and 102 mm) diam pipes. A min of six anchor tabs required for 6 in. (152 mm) diam pipes. In walls, device installed on each surface of wall. TREMCO INC -- TREMstop D B. Fill, Void or Cavity Materials* -- Caulk -- (Optional)-- Nom 1/2 in. (13 mm) thickness of fill material applied within the annulus, flush with top surface of floor or both surfaces of wall assembly. At point contact location, 1/2 in. (13 mm) diam bead of caulk applied at interface of pipe and periphery of opening at top surface of floor or both surfaces of wall. When nom 6 in. (152 mm) diam PVC pipe is used, caulk is required to be used. T Rating is 1 hr when caulk is not used. T Rating is 2 hr when caulk is used. TREMCO INC -- TREMstop Acrylic, TREMstop Intumescent Acrylic or Fyre-Sil *Bearing the UL Classification Mark *Reproduced courtesy of Underwriters Laboratories, Inc.® (UL / cUL)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

System No. C-AJ-2507

F Rating -- 2 Hr T Rating -- 0 Hr

1. Floor or Wall Assembly - Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf (1600-2400 kg/cu meter)) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 4-1/2 in. (114 mm). See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 1A. Metallic Sleeve - (Optional) - Nom 4-1/2 in. (114 mm) diam (or smaller), cylindrical sleeve fabricated from 0.013 in. (0.3 mm) thick (30 gauge or heavier) galvanized steel and having a min 1 in. (25 mm) overlap along longitudinal seam. Sleeve may be installed flush or recessed with both surfaces of floor or wall. 2. Through Penetrants - One nonmetallic pipe or conduit to be installed concentrically within the firestop system. The annular space between the pipe or conduit and the periphery of the opening shall be as shown below. Pipe or conduit to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Rigid Nonmetallic Conduit++ - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No. 70). C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. Max Hole Diam In. (mm) 2-1/2 (64) 3 (76) 4-1/2 (114) Nom. Pipe Diam In. (mm) Annular Space In. (mm) 11/32 (8) 11/32 (8) 1/2 (13)

1-1/2 (38) 2 (51) 3 (76)

3. Firestop System -- The firestop system shall consist of the following: A. Firestop Device* -- Wrap material enclosed with foil pouch and designated TREMstop Strap 1-1/2", 2" and 3" installed around nom 1-1/2, 2, and 3 in. (38, 51 and 76 mm) diam. pipe/conduit respectively. The device is wrapped around the outer circumference of the pipe/conduit with the ends held together with tape supplied with the product. The wrap material is then slid into the annular space and made flush with the bottom surface of the floor. For wall assemblies the wrap material shall be installed on both sides of the wall and made flush with each surface. TREMCO INC ­ TREMstop Strap 1-1/2", 2", 3" B. Fill, Void or Cavity Material* - Sealant -- (Optional) A ¼ in. (6 mm) thick layer of fill material may be applied within the annulus, at the top surface of floor or, for walls, a ¼ in. (6 mm) thick crown of fill material may be applied over the wrap material and around the penetrant at both surfaces of wall assembly. TREMCO INC - TREMstop Acrylic, TREMstop Intumescent Acrylic or Fyre-Sil Sealant *Bearing the UL Classification Mark ++Bearing the UL Listing Mark *Reproduced courtesy of Underwriters Laboratories, Inc.® (UL)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

System No. C-AJ-2508

F Rating -- 2 Hr T Rating -- 0 Hr

1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf (1600-2400 kg/cu meter)) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 6 in. (152 mm). See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 1A. Metallic Sleeve - (Optional) - Nom 6 in. (152 mm) diam (or smaller), cylindrical sleeve fabricated from 0.013 in. (0.3 mm) thick (30 gauge or heavier) galvanized steel and having a min 1 in. (25 mm) overlap along longitudinal seam. Sleeve may be installed flush or recessed with both surfaces of floor or wall. 2. Through Penetrants - One nonmetallic pipe to be installed concentrically within the firestop system. The annular space between the pipe and the periphery of the opening shall be 3/4 in. (19 mm). Pipe to be rigidly supported on both sides of the floor or wall assembly. The following type and size of nonmetallic pipe may be used: A. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam., Schedule 40 solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. 3. Firestop System -- The firestop system shall consist of the following: A. Firestop Device* -- Wrap material enclosed with foil pouch and designated TREMstop Strap 4" installed around pipe. The device is wrapped around the outer circumference of the pipe with the ends held together with tape supplied with the product. The wrap material is then slid into the annular space and made flush with the bottom surface of the floor. For wall assemblies the wrap material shall be installed on both sides of the wall and made flush with each surface. TREMCO INC ­ TREMstop Strap 4" B. Fill, Void or Cavity Material* - Sealant -- (Optional) A ¼ in. (6 mm) thick layer of fill material may be applied within the annulus, at the top surface of floor or, for walls, a ¼ in. (6 mm) thick crown of fill material may be applied over the wrap material and around the penetrant at both surfaces of wall assembly. TREMCO INC - TREMstop Acrylic, TREMstop Intumescent Acrylic or Fyre-Sil Sealant *Bearing the UL Classification Mark

*Reproduced courtesy of Underwriters Laboratories, Inc.®

(UL)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

System No. F-B-2027

F Rating -- 2 Hr T Rating -- 0 Hr

A

5

1

A

5 3

4

Section A-A

1. Floor Assembly - Min 6 in. (152 mm) thick UL Classified hollow core Precast Concrete Units*. Max diam of opening is 6 in. (152 mm). See Precast Concrete Units (CFTV) category in the Fire Resistance Directory for names of manufacturers. 2. Metallic Sleeve - (Optional, Not shown)- Nom 6 in. (152 mm) diam (or smaller) cylindrical sleeve fabricated from 0.013 in. (0.3 mm) thick (30 gauge) (or heavier) galvanized steel and having a min 1 in. (25 mm) lap along longitudinal seam. Sleeve installed flush with both surfaces of floor. 3. Through Penetrants- One nonmetallic pipe or conduit to be centered within the firestop system. The annular space between the pipe or conduit and the periphery of the opening shall be as shown below. Pipe or conduit to be rigidly supported on both sides of the floor assembly. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe -- Nom 4 in. (102 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems. C. Rigid Nonmetallic Conduit++ - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No. 70). D. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. Max Hole Diam In. (mm) 2-1/2 (64) 3 (76) 4-1/2 (114) 5-1/2 (140) Nom. Pipe Diam In. (mm) 1-1/2 (38) 2 (51) 3 (76) 4 (102) Annular Space In. (mm) 11/32 (8) 11/32 (8) 1/2 (13) 1/2 (13)

4. Firestop Device* -- Wrap material enclosed with foil pouch and designated TREMstop Strap 1-1/2", 2", 3" and 4". Device installed around nom 1-1/2, 2, 3 and 4 in. (38, 51, 76 and 102 mm) diam pipe/conduit, respectively. The wrap material is wrapped around the outer circumference of the pipe/conduit with the ends held together with tape supplied with the product. The wrap material is then slid into the annular space and made flush with the bottom surface of the floor. *Reproduced courtesy of Underwriters Laboratories, Inc.® (UL)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

TREMCO INC ­ TREMstop Strap 1-1/2", 2", 3" 5. Fill, Void or Cavity Material* - Sealant -- Min 1/4 in. (6 mm) thickness of fill material applied within the annulus between the device or penetrant and the periphery of the opening, flush with both floor surfaces. In addition, a min. 1/4 in. (6 mm) bead of fill material applied at the device/penetrant interface. TREMCO INC - TREMstop Acrylic, TREMstop Intumescent Acrylic or Fyre-Sil Sealant *Bearing the UL Classification Mark

*Reproduced courtesy of Underwriters Laboratories, Inc.®

(UL)

2

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

Design No. RQ/PHV 120-02

Horizontal or Vertical (floor or wall ratings: see table below) Hole size: see Item 3 Testing Standards: ASTM-E814 at 0.01" water column Pressure Differential.

Penetrant PVC

Pipe Size 4"

ASTM-E814 F, T 2 hours

1. Floor or Wall Assembly: Code conforming 2 hour rated floor or wall assembly, nominal 2-1/2" thickness (or greater), normal or low density cast concrete. 2. Penetrant: (See table above) PVC Schedule 40, DWV or closed (process or supply) applications. Fittings optional within the piping assembly. Ratings achieved equivalent to that of the fire separation. 3. Firestop System Component: TREMstop Strap installed flush to the underside of the concrete slab, according to manufacturer's installation instructions. TREMstop Acrylic, TREMstop Intumescent Acrylic or Fyre-Sil sealant optional to provide smoke sealing of the firestop system, if desired.

Nominal Pipe Size 4"

Maximum Hole Size 6"

*Reproduced courtesy of Intertek Testing Services NA Inc.® *System listing number is reproduced courtesy of Royal Quickstop Fireprotection Systems Co. (Tremco Inc. system listing number to follow)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

DESIGN NO. RQ/PHV 120-04

Horizontal or Vertical (floor or wall ratings: see table below) Hole size: see Item 3 Testing Standard: ASTM-E814, CAN/ULC-S115 at 50 Pa Pressure Differential.

Penetrant PVC ccPVC ccABS ABS

Pipe Size 1-1/2" to 4" 1-1/2" to 3" 1-1/2" to 3" 1-1/2" to 3"

CAN/ULC-S115 F 2 hour 2 hour 2 hour 2 hour

ASTM-E814 F 2 hour 2 hour 2 hour 2 hour

1. Floor or Wall Assembly: Code conforming 2 hour rated floor or wall assembly, nominal 2-1/2" thickness (or greater), normal or low density cast concrete. 4" PVC is acceptable only in concrete slab 4-1/2" thickness or greater. Minimum wall thickness 6". Wall construction may include masonry units. 2. Penetrant: (See table above) ccABS, ABS, ccPVC, PVC Schedule 40, DWV or closed (process and supply) applications. Fittings optional within the piping assembly. Ratings achieved equivalent to that of the fire separation. 3. Firestop System Component: TREMstop Strap installed within the fire separation, according to manufacturer's installation instructions. Tremco Sealant optional. TREMstop Acrylic, TREMstop Intumescent Acrylic or Fyre-Sil may be installed to improve smoke sealing characteristics of the firestop system if desired.

Nominal Pipe Size 1-1/2" 2" 3" 4"

Maximum Hole Size 2-1/2" Thick Concrete >/= 4-1/2" Thick Concrete 2-1/2" 2-1/2" to 3" 3" 4-1/2" NA 3" to 3-1/2" 4-1/2" to 5" 6"

*Reproduced courtesy of Intertek Testing Services NA Inc.® *System listing number is reproduced courtesy of Royal Quickstop Fireprotection Systems Co. (Tremco Inc. system listing number to follow)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

Design No. RQ/PV 120-01

Vertical (wall ratings: see table below) Hole size: see Item 3 Testing Standards: ASTM-E814, CAN/ULC-S115 at 50 Pa Pressure Differential.

Penetrant ccPVC PVC CPVC ccABS ABS FRPP

Pipe Size 1-1/2" to 4" 1-1/2" to 4" 1-1/2" to 2" 1-1/2" to 4" 1-1/2" to 4" 1-1/2" to 3"

CAN/ULC-S115 F, FH, FT, FTH 2 hour 2 hour 2 hour 2 hour 2 hour 2 hour

ASTM-E814 F, T 2 hour 2 hour 2 hour 2 hour 2 hour 2 hour

1. Wall Assembly: Code conforming 1 or 2 hour rated gypsum wallboard wall, framed with nominal 2" x 4" wood or steel studs. Ratings will equal that of wall assembly. 2. Penetrant: (See table of ratings) ccABS, ABS, ccPVC, PVC, CPVC, FRPP Schedule 40, DWV or closed (process or supply) applications. Fittings optional within the piping assembly. 3. Firestop System Component: TREMstop Strap installed on both sides of wall, with 1/4" of strap exposed from surface of wall. TREMstop Acrylic, TREMstop Intumescent Acrylic or Fyre-Sil sealant may be installed to improve smoke sealing characteristics of the firestop system if desired.

Nominal Pipe Size 1-1/2" 2" 3" 4"

Maximum Hole Size 2-1/2" 3" 4-1/2" 5-3/4"

*Reproduced courtesy of Intertek Testing Services NA Inc.® *System listing number is reproduced courtesy of Royal Quickstop Fireprotection Systems Co. (Tremco Inc. system listing number to follow)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

System No. W-L-1158

December 07, 2001 F Ratings -- 1 and 2 Hr (See Item 1) T Rating -- 1/4 Hr

1. Wall Assembly The 1 or 2 hour fire-rated gypsum board stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide and spaced max 24 in. OC. B. Gypsum Board* One or two layers of nom 1/2 or 5/8 in. thick gypsum board as specified in the individual Wall and Partition Design. Max diam of opening is 13-3/4 in. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants One metallic pipe, tubing or conduit to be installed either concentrically or eccentrically within the firestop system. Pipe, tubing or conduit to be rigidly supported on both sides of wall assembly. The pipe, tubing or conduit may be installed at an angle not greater t han 45 degrees from the perpendicular. The annular space shall be min 0 (point contact) in. to max 1/2 in. The following types and sizes of metallic pipe tubing or conduit may be used: A. Steel Pipe Nom 12 in. diam (or smaller) Schedule 10 (or heavier) st eel pipe. B. Iron Pipe Nom 12 in. diam (or smaller) cast or ductile iron pipe. C. Conduit Nom 4 in. diam (or smaller) steel electrical metallic tubing or nom 6 in. diam (or smaller) steel conduit. D. Copper Tubing Nom 4 in. diam (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe. 3. Firestop System The firestop system shall consist of the following: A. Packing Material (Optional) -- Foam backer rod firmly packed into the opening as a permanent form. Packing material to be recessed from both surfaces of wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* -- (Caulk) Min 1/2 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. Additional fill material to be installed such that a min 3/8 in. crown is formed around the penetrating item and lapping 1/2 in. beyond the periphery of the opening. TREMCO INC -- TREMstop Intumescent Acrylic *Bearing the UL Classification Mark *Reproduced courtesy of Underwriters Laboratories, Inc.® (UL / cUL)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

System No. W-L-1302

March 11, 2004 F Rating -- 1 & 2 Hr (See Item 1) T Rating -- 1/2 Hr

1. Wall Assembly -- The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs -- Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in (610 mm) OC. B. Gypsum Board* -- One or two layers of nom 5/8 in. (16 mm) thick gypsum board, as specified in the individual Wall and Partition Design. Max area of opening is 33 sq in. (213 sq cm) with max dimensions of 11 in. (279 mm). 2. Through Penetrants -- One or more pipes, conduits or tubing to be installed within the opening. The space between pipes, conduits or tubing shall be a nom 1/2 in. (13 mm). The space between pipes, conduits or tubing and periphery of opening shall be min 0 in. (point contact) to max 3/4 in. (19 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of pipes, conduits or tubing may be used: A. Steel Pipe -- Nom 2 in. (51 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -- Nom 2 in. (51 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit -- Nom 2 in. (51 mm) diam (or smaller) steel electrical metallic tubing or rigid steel conduit. 3. Firestop System -- The firestop system shall consist of the following: A. Packing Material -- Min 2-1/2 in. (64 mm) thickness of min 4 pcf (64 kg/cu meter) mineral wool batt insulation compressed and firmly packed into opening as a permanent form. Packing material recessed from both surfaces of wall as required to accommodate the required thickness of fill material. B. Fill Void or Cavity Materials* -- Sealant -- Min 1/2 in. (13 mm) thickness of fill material applied within annulus, flush with both surfaces of wall. TREMCO INC -- TREMstop Acrylic, TREMstop Intumescent Acrylic or Fyre-Sil *Bearing the UL Classification Mark

*Reproduced courtesy of Underwriters Laboratories, Inc.®

(UL / cUL)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

System No. W-L-2083

December 07, 2002 F Ratings -- 1 and 2 Hr (See Item 1) T Ratings -- 0 and 1 Hr (See Item 1)

1. Wall Assembly -- The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs -- Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 3-5/8 in. wide and spaced max 24 in. OC. B. Batts and Blankets* -- (Not Shown) -- When required in the individual wall and partition design, mineral wool batts friction fitted to fill interior of stud cavities. C. Gypsum Board* -- One or two layer of nom 1/2 in. or 5/8 in. thick gypsum board, as specified in the individual Wall and Partition Design. Max diam of opening is 9 in. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall it is installed in. The T ratings are 0 and 1 hr when installed in a 1 and 2 hr. fire rated walls, respectively. 2. Through-Penetrants -- One nonmetallic pipe to be installe deither concentrically or eccentrically within the firestop system. Pipe to be rigidly supported on both sides of wall assembly. The following types and sizes of nonmetallic pipes may be used: A. Polyvinyl Chloride (PVC) Pipe -- Nom 8 in. diam (or smaller) Schedule 40 PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe -- Nom 1-1/4 in. diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems. 3. Firestop System -- The firestop system shall consist of the the following: A.Fill, Void or Cavity Material* -- Wrap Strip -- Nom 0.10 in. thick intumescent wrap strip faced on one side with glass webbing. Width of wrap strip used shall be 1.4 in. for max 4 in. diam pipes and 2-3/8 in. for 6 and 8 in. diam pipes. The wrap strip is continuously wrapped around the outer circumference of the pipe and held in place with pieces of tape. When multiple wrap strips are used to achieve the required number of layers, the ends are to be butted end to end and held in place with tape. Wrap strips are installed on each side of wall. The number of wrap strip layers required and the annular space are dependent upon the pipe size and type, as shown in the table:

*Reproduced courtesy of Underwriters Laboratories, Inc.®

(UL / cUL)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

Nom Pipe Diam In. 1-1/4 1-1/2 2 3 4 4* 6 or 8

Pipe Type CPVC PVC PVC PVC PVC PVC PVC

Max Annular Space In. 3/16 1/16 3/16 1/8 1/8 3/8 0 to 3/8

Min No. of Wrap Strip Layers 3 3 3 4 6 7 10

*Not for use with TREMstop -D Device. TREMCO INC -- TREMstop -- WS B. Steel Collar -- Collar fabricated from coils of precut min 0.016 in. thick (No. 28 gauge) galv steel available from the fill material manufacturer. Collar shall be nom 1-1/2 or 2-1/2 in. deep dependent on wrap strip width with 1 in. wide by 2 in. long anchor tabs on 2-1/4 in. centers for securement to the wall. In addition, the collar contains retainer tabs, 3/8 to 3/4 in. wide, located on both sides of the collar for retaining the wrap strips. The collar shall be wrapped over the wrap strip, overlapped min 1 in. and secured together using a min of 3 No. 6 by 3/8 in. self-drilling, self-tapping steel screws or using one min 1/2 in. wide by 0.028 in. thick stainless steel hose clamp. The retaining tabs adjacent to the anchor tabs are bent toward the pipe at one or more locations to retain the wrap strip. The retaining tabs opposite the anchor tabs are folded 90 degrees towards the pipe to maintain the annular space around the pipe and to retain the wrap strip layers. Wrap strip/collar assembly is slid along the pipe until it butts the surface of the wall. Collar secured to wall surface at anchor tab with 1/4 in. diam by 2-3/4 in. long hollow wall anchors in conjunction with min 1/4 in. diam fender washers. When diam of penetrant is 4 in. or less, nom 1-1/4 in. diam RamsetRedhead Poly-Set expansion anchors may be used in conjunction with No. 8 by 1-1/2 in. long steel screws and 1-1/4 in. diam steel fender washers. Two anchors, symmetrically located, required for nom 1-1/4 in. to nom 2 in. diam pipes. Four anchors, symmetrically located, required for nom 3 in. to nom 4 in. diam pipes. Anchors are to be used in each anchor tab for 6 in. diam and larger pipes. Collars are installed on each side of wall. As an alternate to (Items 3A and B) Wrap Strip/Steel Collar--Firestop Device*-- The firestop device shall be installed in accordance with the accompanying installation instructions. Device wrapped around the pipe and secured by using the attached hose clamp. Device slid along the pipe until it abuts the surface of the gypsum wall. Anchor bolts to be used as described under steel collar (Item 3B). Device secured to gypsum wall with min 1/4 in. diam by 2-3/4 in. long steel hollow wall anchors, in conjunction with 1-1/4 in. diam steel fender washers. TREMCO INC -- TREMstop -D C. Fill, Void or Cavity Material* -- Caulk -- (Optional)-- Min 1/4 in. bead of caulk to be applied at the interface of the wall and steel collar and at the interface of the steel collar and pipe. The caulk shall be installed symmetrically on both sides of the wall assembly. TREMCO INC -- TREMstop Acrylic or Intumescent Acrylic *Bearing the UL Classification Mark

*Reproduced courtesy of Underwriters Laboratories, Inc.®

(UL / cUL)

2

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

System No. W-L-2129

April 14, 2004 F Ratings -- 1 & 2 Hr (See Items 1 and 2) T Ratings -- 0, 1 & 2 Hr (See Items 1 and 2)

1. Wall Assembly -- The 1 or 2 h fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. S tuds -- Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide and spaced max 24 in. OC. B. Gypsum Board* -- 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Max diam of opening is 4 in. The hourly F & T ratings of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed unless noted otherwise. 2. Through Penetrants -- One nonmetallic pipe to be installed either concentrically or eccentrically within the firestop system. Pipe to be rigidly supported on both sides of wall assembly. The following types and sizes of nonmetallic pipes may be used: A. Polyvinyl Chloride (PVC) Pipe -- Nom 2 in. diam (or smaller) Schedule 40 solid core PVC pipe for use in closed (process or supply) or vented (drain, wast e or vent) piping systems. The annular space between pipe and periphery of opening shall be min 0 in. (point contact) to max 7/8 in. For use with 1 hr wall constructions only. When used, F Rating is 1 hr and T Rating is 0 hr. B. Polyvinyl Chloride (PVC) Pi pe -- Nom 2 in. diam (or smaller) Schedule 40 solid core PVC pipe for use in closed (process or supply) piping systems. The annular space between pipe and periphery of opening shall be min 1/4 in. to max 1-3/8 in. C. Chlorinated Polyvinyl Chloride (CPVC) Pipe -- Nom 2 in. diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems. The annular space between pipe and periphery of opening shall be min 1/4 in. to max 1-3/8 in. 3. Firestop System -- The firestop system shall consist of the following: A. Packing Material -- (Optional) In 2 hr wall assemblies, foam backer rod firmly packed into opening as a permanent form. Packing material to be recessed from both surfaces of wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* -- Caulk -- Min 1/2 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. Additional fill material to be installed such that a min 1/4 in. crown is formed around the penetrat ing item. TREMCO INC -- TREMstop Intumescent Acrylic *Bearing the UL Classification Mark

*Reproduced courtesy of Underwriters Laboratories, Inc.®

(UL / cUL)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

System No. W-L-2429

F Ratings -- 1 and 2 Hr (See Item 1) T Rating -- 0 Hr

1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the mat erials and in the manner specified in the individual U300, U400 OR V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 byy 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-5/8 in. (92 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Min 5/8 in. (16 mm) thick, 4 ft (122 cm) wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers and orientation shall be as specified in the individual Wall and Partition Design. Max diam of opening is 4-1/2 in. (114 mm). The hourly F rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants - One nonmetallic pipe or conduit to be centered within the firestop system. The annular space shall be as specified below. Pipe or conduit to be rigidly supported on both sides of wall assembly. The following types and sizes of pipes or conduit may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Rigid Nonmetallic Conduit++ - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No. 70).

Max Hole Diam In. (mm) 2-1/2 (64) 3 (76) 4-1/2 (114)

Nom. Pipe Diam In. (mm)

Annular Space In. (mm)

1-1/2 (38) 2 (51) 3 (76)

11/32 (8) 11/32 (8) 1/2 (13)

3. Firestop System -- The firestop system shall consist of the following: A. Firestop Device* -- Wrap material enclosed with foil pouch and designated TREMstop Strap 1-1/2", 2" and 3" for use around nom 1-1/2, 2 and 3 in. (38, 51 and 76 mm) diam pipes/conduits respectively. The device is wrapped around the outer *Reproduced courtesy of Underwriters Laboratories, Inc.® (UL)

1

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

circumference of the pipe/conduit, with the ends held together with aluminum foil tape, and slid into annular space such that it protrudes ¼ in. (6 mm) beyond each wall surface. The wrap material is installed on both sides of the wall. TREMCO INC ­ TREMstop Strap 1-1/2", 2", 3" B. Fill, Void or Cavity Material* - Sealant ­ (Optional) A ¼ in. (6 mm) thick crown of fill material may be applied over the wrap material and around the penetrant at both surfaces of wall assembly. TREMCO INC - TREMstop Acrylic, TREMstop Intumescent Acrylic or Fyre-Sil Sealant *Bearing the UL Classification Mark ++Bearing the UL Listing Mark

*Reproduced courtesy of Underwriters Laboratories, Inc.®

(UL)

2

Tremco Inc.®, 2628 Pearl Road, Medina, Ohio 44256 www.tremcofirestop.com

3735 GREEN ROAD BEACHWOOD, OHIO 44122-8068

MATERIAL SAFETY DATA SHEET TELEPHONE: (216)292-5000

EMERGENCIES: (216)765-6727 8:30-5:00 EST AFTER HOURS: CHEMTREC (800)424-9300

-----------------------------------------------------------------------------------------------SECTION 1 -----------------------------------------------------------------------------------------------Order Code: 901874 805 Product Name: Chemical Name: Chemical Family: Product Code: MSDS Preparer: TREMSTOP ACRYLIC (RUST RED) Sealant 901-874 R. A. MIKOL Date Prepared: Replaces Date: 30-NOV-01 26-APR-96

-------------------------------------------------------------------------------Section 2 - Molecular Composition -------------------------------------------------------------------------------Common Name and Chemical Name Weight % CAS Number Exposure Limits ACRYLIC POLYMER OSHA:TWA ACGIH:TWA WATER OSHA:TWA ACGIH:TWA 40.0-50.0 Trade Secret STEL STEL STEL STEL STEL STEL 35.0-40.0 5.0-10.0 (mist) 10 mg/M3 (mist) 1.0-5.0 (total nuisance dust) (total nuisance dust) 1.0-5.0 STEL STEL 112945-52-5 8042-47-5 7732-18-5

WHITE MINERAL OIL OSHA:TWA 5 mg/M3 ACGIH:TWA 5 mg/M3

SILICA, AMORPHOUS, FUMED OSHA:TWA 15 mg/M3 STEL ACGIH:TWA 10 mg/M3 STEL TITANIUM DIOXIDE OSHA:TWA 10 mg/M3 ACGIH:TWA 10 mg/M3 1,2-PROPANEDIOL OSHA:TWA ACGIH:TWA IRON OXIDE OSHA:TWA ACGIH:TWA PHTHALO BLUE OSHA:TWA ACGIH:TWA

13463-67-7

(total dust, no asbestos, <1% SiO2) 1.0-5.0 57-55-6

(PROPYLENE GLYCOL) STEL STEL STEL STEL STEL STEL STEL STEL -

10 mg/M3 10 mg/M3 -

1.0-5.0 (dust, fume as iron) (fume as iron) 0.1-0.2

1309-37-1

147-14-8

CHLOROTHALONIL OSHA:TWA ACGIH:TWA -

0.1-0.3 -

1897-45-6

-----------------------------------------------------------------------------Section 3 - Hazards Identification -----------------------------------------------------------------------------****************************************************************************** Emergency Overview: Rust Red paste. If inhaled can cause irritation to respiratory system. Leave area to breathe fresh air. ****************************************************************************** Potential Hlth Effect/Rte of Entry: ----------------------------------Inhalation: 37 44 2 Product 901-874 Page 1 of 5

Order Code: 901874 805

May cause Eyes: May cause Ingestion: May cause lethargy, Skin: May cause

irritation to respiratory system, headache, and nausea. irritation. gastrointestinal discomfort including nausea, vomiting, and diarrhea and may be fatal. slight irritation.

Aggravated Medical Conditions: Pre-existing skin, eye, respiratory disorders may be aggravated by exposure. Acute Health Effects: See effects described above. Chronic Health Effects: Prolonged overexposure to silica dust by inhalation may cause delayed lung injury. Since silica in this product is encapsulated, release is not expected unless it is necessary to abrade, grind or sand surfaces coated with this product. -----------------------------------------------------------------------------Section 4 - First Aid Measures -----------------------------------------------------------------------------Inhalation: Leave area to breathe fresh air. Eyes: Flush immediately with running water for 15 minutes, lifting the upper and lower lids occasionally. Get medical attention immediately. Ingestion: Get medical attention immediately. Skin: Wash with soap and water. Notes to Physician: N/A -----------------------------------------------------------------------------Section 5 - Fire Fighting Measures -----------------------------------------------------------------------------Flash Point: N/A Method: N/A Lower Flammability Limit: N/A Upper Flammability Limit: N/A Autoignition Temperature: N/A Extinguishing Media: Not applicable. Water base compound, not expected to burn. Fire and Explosion Hazards: Not Applicable Special Fire Fighting Procedures: During a fire, personnel at the scene are to prevent exposure to fumes using accepted fire fighting techniques. Fire Fighting Equipment: N/A Other Precautions: Not Applicable -----------------------------------------------------------------------------Section 6 - Accidental Release Measures -----------------------------------------------------------------------------Release Response Overview: Absorb spill in sand, earth or other suitable material.Transfer to appropriate container for disposal. -----------------------------------------------------------------------------Section 7 - Handling and Storage -----------------------------------------------------------------------------Handling and Storage Precautions:

38 44

3

Product 901-874 Page 2 of 5

Order Code: 901874 805

Store under normal warehouse conditions. Handle in compliance with common hygienic practices. -----------------------------------------------------------------------------Section 8 - Exposure Controls/Personal Protection -----------------------------------------------------------------------------Respiratory: Not required. Skin: Protect hands with rubber or other suitable gloves. Eyes: Wear suitable safety eyewear. Face: Not required. Engineering: Use local exhaust when the general ventilation is not adequate. -----------------------------------------------------------------------------Section 9 - Physical and Chemical Properties -----------------------------------------------------------------------------Odor/Appearance: ACRYLIC/RUST RED PASTE Color: RED Physical State: PASTE pH: N/A Vapor Pressure: N/A Vapor Density: N/A Boiling Point: N/A Melting Point: N/A Freezing Point: <32 F Solubility in Water: MISCIBLE Specific Gravity: 1.06 % Volatile Weight: 40.0 -----------------------------------------------------------------------------Section 10 - Reactivity/Stability -----------------------------------------------------------------------------Stability: Stable Incompatible Products: Avoid contact with strong oxidizing agents, acids, bases. Conditions to Avoid Polymerization: Hazardous polymerization will not occur. -----------------------------------------------------------------------------Section 11 - Toxicological Information -----------------------------------------------------------------------------Eyes: SEE SECTION 3 Ingestion: " " " Inhalation: " " " Skin: " " " Subchronic: " " " Chronic: " " " -----------------------------------------------------------------------------Section 12 - Ecological Information -----------------------------------------------------------------------------Ecotoxicological Data: N/A Chemical Fate: N/A -----------------------------------------------------------------------------Section 13 - Disposal Considerations -----------------------------------------------------------------------------RCRA Class: N/A Disposal Method: Not regulated by RCRA. Dispose of in compliance with state and local regulations.

39 44

4

Product 901-874 Page 3 of 5

Order Code: 901874 805

EPA Reportable Quantities ------------------------N/A -----------------------------------------------------------------------------Section 14 - Transportation Data -----------------------------------------------------------------------------DOT Shipping Name: NOT REGULATED DOT Hazard Class: DOT Label: UN/NA Number: Packing Group: Special Provisions: Packaging --------Exceptions: Non-Bulk: Bulk: Quantity Limitations -------------------Passenger Aircraft or Railcar: Cargo Aircraft: Vessel Stowage Requirements --------------------------Vessel Stowage: Other Stowage: Transportation Notes: N/A -----------------------------------------------------------------------------Section 15 - Regulatory Information -----------------------------------------------------------------------------TSCA Status: On the TSCA Inventory OSHA Status: Considered hazardous based on the following criteria: Irritant Target Organs ------------Eye Skin Lung OSHA Hazardous Components ---------------------------------------------SILICA, AMORPHOUS, FUMED TITANIUM DIOXIDE * WHITE MINERAL OIL * - CHEMICAL IS LISTED AS AN IARC, NTP, OSHA, Compliance Quantites -------------------N/A SARA 311 Ratings ---------------Immediate Health Hazard: Delayed Health Hazard: Fire Hazard: Reactivity Hazard: Sudden Release of Pressure Hazard: CAS Number -----------112945-52-5 13463-67-7 8042-47-5 or ACGIH CARCINOGEN

N Y N N N CAS Number ------------

SARA 313 Ingredients ---------------------------------------------No Sara 313 ingredients

Proposition 65 Ingredients -------------------------Chemicals known to the State of California to cause cancer,

40 44

5

Product 901-874 Page 4 of 5

Order Code: 901874 805

birth defects and/or other reproductive harm. --------------------------------------------CHLOROTHALONIL (<0.3%)

CAS Number -----------1897-45-6

-----------------------------------------------------------------------------Section 16 - Other Information -----------------------------------------------------------------------------FOR INDUSTRIAL USE ONLY. KEEP OUT OF REACH OF CHILDREN. THE HAZARD INFORMATION HEREIN IS OFFERED SOLELY FOR THE CONSIDERATION OF THE USER, SUBJECT TO HIS OWN INVESTIGATION OF COMPLIANCE WITH APPLICABLE REGULATIONS, INCLUDING THE SAFE USE OF THE PRODUCT UNDER EVERY FORESEEABLE CONDITION.

41 44

6

Product 901-874 Page 5 of 5

3735 GREEN ROAD BEACHWOOD, OHIO 44122-8068

MATERIAL SAFETY DATA SHEET TELEPHONE: (216)292-5000

EMERGENCIES: (216)765-6727 8:30-5:00 EST AFTER HOURS: CHEMTREC (800)424-9300

-----------------------------------------------------------------------------------------------SECTION 1 -----------------------------------------------------------------------------------------------Order Code: 823707 504 Product Name: Chemical Name: Chemical Family: Product Code: MSDS Preparer: TREMSTOP D ARTICLE 823-7XX R. A. MIKOL Date Prepared: Replaces Date: 06-AUG-99 N/A

A Material Safety Data Sheet is not required on TREMSTOP D due to the fact that this product is an "article" (as defined in 29CFR 1910.1200) and is therefore exempt from OSHA Labeling/MSDS requirements. Please do not hesitate to call (216) 765-6727 for further health and safety information about any Tremco product.

22 34

2

Product 823-7XX Page 1 of 1

3735 GREEN ROAD BEACHWOOD, OHIO 44122-8068

MATERIAL SAFETY DATA SHEET TELEPHONE: (216)292-5000

EMERGENCIES: (216)765-6727 8:30-5:00 EST AFTER HOURS: CHEMTREC (800)424-9300

-----------------------------------------------------------------------------------------------SECTION 1 -----------------------------------------------------------------------------------------------Order Code: 938874 805 Product Name: TREMSTOP FYRE-SIL G.G.(RUST RED) Chemical Name: Chemical Family: Product Code: 938-874 Date Prepared: 02-APR-02 MSDS Preparer: R. A. MIKOL Replaces Date: 25-APR-96 -------------------------------------------------------------------------------Section 2 - Molecular Composition -------------------------------------------------------------------------------Common Name and Chemical Name Weight % CAS Number Exposure Limits CALCIUM CARBONATE (LIMESTONE) OSHA:TWA 15 mg/M3 STEL ACGIH:TWA 10 mg/M3 STEL SILICONE POLYMER OSHA:TWA ACGIH:TWA STEL STEL 10.0-20.0 63148-62-9 35.0-45.0 1317-65-3 (total dust, 5mg/M3 respirable fraction) (total dust, no asbestos, <1% SiO2) 30.0-40.0 Trade Secret

POLYDIMETHYLSILOXANE, TRIMETHYL ENDCAP OSHA:TWA STEL ACGIH:TWA STEL SILICA, AMORPHOUS, FUMED OSHA:TWA 15 mg/M3 STEL ACGIH:TWA 10 mg/M3 STEL OXIMINO SILANE OSHA:TWA ACGIH:TWA IRON OXIDE OSHA:TWA ACGIH:TWA 10 mg/M3 5 mg/M3 STEL STEL STEL STEL -

1.0-10.0 (total nuisance dust) (total nuisance dust) 1.0-5.0

112945-52-5

Trade Secret

1.0-3.0 (dust,fume as Fe) (fume as Fe) 0.5-1.0 (respirable dust) (respirable dust)

1309-37-1

CRYSTALLINE SILICA (QUARTZ) OSHA:TWA 0.10 mg/M3 STEL ACGIH:TWA 0.10 mg/M3 STEL

14808-60-7

METHYL ETHYL KETOXIME 0.0-0.08 96-29-7 OSHA:TWA STEL (See Below) ACGIH:TWA STEL -----------------------------------------------------------------------------Section 3 - Hazards Identification -----------------------------------------------------------------------------****************************************************************************** Emergency Overview: Red paste. If inhaled can cause headache, dizziness, irritation to respiratory system. Leave area to breathe fresh air. Avoid further overexposure. If symptoms persist, get medical attention immediately. As a by product of curing up to 4% Methyl Ethyl Ketoxime (MEKO) may be released within product. Due to extremely low vapor pressure of MEKO (<8mmHg at 20 C) relesae of high airborne concentration is not expected under normal conditions of use. ****************************************************************************** Potential Hlth Effect/Rte of Entry: ----------------------------------Inhalation: May cause nasal and respiratory tract irritation. May cause narcotic effects at high concentrations and coma and respiratory failure at extremely high concentrations. May cause blood effects (methemaglobinemia and anemia). Eyes: May cause severe irritation or corrosive burns. Ingestion: May cause nausea, vomiting, and symptoms similar to those described for 64 50 2 Product 938-874 Page 1 of 5

Order Code: 938874 805

inhalation. Skin: May cause irritation. Can be absorbed through the skin and cause effects similar to those described for inhalation and ingestion. Allergic skin reactions have been observed in animals. Aggravated Medical Conditions: Preexisting eye, skin, respiratory, and liver disorders may be aggravated by exposure. Sympathomimeteric drugs may initiate cardiac arrythmias. Acute Health Effects: See effects described above. Chronic Health Effects: MEKO has caused allergic skin reactions and liver tumors in animals. Overexposure may cause blood effects (methmoglobinemia and anemia.) Inhalation of crystalline silica (quartz) can cause cancer based on animal data, and IARC concludes sufficient evidence in humans. Prolonged and repeated overexposure to free crystalline silica dust above the TLV level may cause scarring of the lungs with cough and shortness of breath. A delayed lung injury, silicosis may result from breathing free silica. Fillers are encapsulated and not expected to be released in product under normal conditions of use. -----------------------------------------------------------------------------Section 4 - First Aid Measures -----------------------------------------------------------------------------Inhalation: Leave area to breathe fresh air. Avoid further overexposure. If symptoms persist, get medical attention immediately. Eyes: Flush immediately with running water for 15 minutes, lifting the upper and lower lids occasionally. Get medical attention immediately. Ingestion: Get medical attention immediately. Skin: Wash area of contact thoroughly with hand cleaner followed by soap and water. If irritation, rash or other disorders develop, get medical attention immediately. Notes to Physician: N/A -----------------------------------------------------------------------------Section 5 - Fire Fighting Measures -----------------------------------------------------------------------------Flash Point: 170 F Method: TCC Lower Flammability Limit: N/A Upper Flammability Limit: N/A Autoignition Temperature: N/A Extinguishing Media: Water fog. Fire and Explosion Hazards: Not Applicable Special Fire Fighting Procedures: During a fire, personnel at the scene are to prevent exposure to fumes using accepted fire fighting techniques. Fire Fighting Equipment: N/A Other Precautions: Not Applicable -----------------------------------------------------------------------------Section 6 - Accidental Release Measures -----------------------------------------------------------------------------Release Response Overview: Absorb spill in sand, earth or other suitable material.Transfer to appropriate container for disposal. -----------------------------------------------------------------------------Section 7 - Handling and Storage -----------------------------------------------------------------------------Handling and Storage Precautions: Store under normal warehouse conditions. Prevent inhalation of vapor,

65 50

3

Product 938-874 Page 2 of 5

Order Code: 938874 805

ingestion, and contact with skin and eyes. Keep container closed when not in use. Precautions also apply to emptied containers. Change soiled workclothes frequently. Clean hands thoroughly after handling. -----------------------------------------------------------------------------Section 8 - Exposure Controls/Personal Protection -----------------------------------------------------------------------------Respiratory: Wear NIOSH/MSHA approved respirator as directed by the manufacturer when the ventilation is not adequate. Skin: Protect hands with impervious rubber gloves and wear typical full cover clothing. Prevent contact with skin. Eyes: Wear suitable safety eyewear. Face: Not required. Engineering: Use local exhaust when the general ventilation is not adequate. -----------------------------------------------------------------------------Section 9 - Physical and Chemical Properties -----------------------------------------------------------------------------Odor/Appearance: OXIME/RED PASTE Color: RUST RED Physical State: PASTE pH: Vapor Pressure: N/A Vapor Density: N/A Boiling Point: N/A Melting Point: N/A Freezing Point: N/A Solubility in Water: NEGLIGIBLE Specific Gravity: 1.37 % Volatile Weight: 0.0 -----------------------------------------------------------------------------Section 10 - Reactivity/Stability -----------------------------------------------------------------------------Stability: Stable Incompatible Products: Avoid contact with strong oxidizing agents. Conditions to Avoid Polymerization: Hazardous polymerization will not occur. Decomposition Products: At temperatures over 300 F formaldehyde is a by product of oxidative thermal decomposition of dimethylpolysiloxane. Formaldehyde is a skin and respiratory sensitizer, eye, and throat irritant, acute toxicant, and potential cancer hazard. -----------------------------------------------------------------------------Section 11 - Toxicological Information -----------------------------------------------------------------------------Eyes: SEE SECTION 3 Ingestion: " " " Inhalation: " " " Skin: " " " Subchronic: " " " Chronic: " " " -----------------------------------------------------------------------------Section 12 - Ecological Information -----------------------------------------------------------------------------Ecotoxicological Data: N/A Chemical Fate: N/A -----------------------------------------------------------------------------Section 13 - Disposal Considerations -----------------------------------------------------------------------------RCRA Class: N/A Disposal Method:

66 50

4

Product 938-874 Page 3 of 5

Order Code: 938874 805

Not regulated by RCRA. Dispose of in compliance with state and local regulations. EPA Reportable Quantities ------------------------N/A -----------------------------------------------------------------------------Section 14 - Transportation Data -----------------------------------------------------------------------------DOT Shipping Name: NOT REGULATED DOT Hazard Class: DOT Label: UN/NA Number: N/A Packing Group: Special Provisions: Packaging --------Exceptions: Non-Bulk: Bulk: Quantity Limitations -------------------Passenger Aircraft or Railcar: Cargo Aircraft: Vessel Stowage Requirements --------------------------Vessel Stowage: Other Stowage: Transportation Notes: N/A -----------------------------------------------------------------------------Section 15 - Regulatory Information -----------------------------------------------------------------------------TSCA Status: On the TSCA Inventory OSHA Status: Considered hazardous based on the following criteria: Irritant Sensitizer Target Organs ------------Central Nervous System Blood Lung Skin Eye OSHA Hazardous Components ---------------------------------------------CALCIUM CARBONATE (LIMESTONE) * CRYSTALLINE SILICA (QUARTZ) SILICA, AMORPHOUS, FUMED IRON OXIDE * - CHEMICAL IS LISTED AS AN IARC, NTP, OSHA, Compliance Quantites -------------------N/A SARA 311 Ratings ---------------Immediate Health Hazard: Delayed Health Hazard: Fire Hazard: Reactivity Hazard: Sudden Release of Pressure Hazard: SARA 313 Ingredients -------------------No SARA 313 Ingredients CAS Number -----------1317-65-3 14808-60-7 112945-52-5 1309-37-1 or ACGIH CARCINOGEN

Y Y N N N

67 50

5

Product 938-874 Page 4 of 5

Order Code: 938874 805

Proposition 65 Ingredients -------------------------Chemicals known to the State of California to cause cancer, birth defects and/or other reproductive harm. CAS Number -------------------------------------------------------CRYSTALLINE SILICA (QUARTZ) 14808-60-7 -----------------------------------------------------------------------------Section 16 - Other Information -----------------------------------------------------------------------------FOR INDUSTRIAL USE ONLY. KEEP OUT OF REACH OF CHILDREN. THE HAZARD INFORMATION HEREIN IS OFFERED SOLELY FOR THE CONSIDERATION OF THE USER, SUBJECT TO HIS OWN INVESTIGATION OF COMPLIANCE WITH APPLICABLE REGULATIONS, INCLUDING THE SAFE USE OF THE PRODUCT UNDER EVERY FORESEEABLE CONDITION.

68 50

6

Product 938-874 Page 5 of 5

3735 GREEN ROAD BEACHWOOD, OHIO 44122-8068

MATERIAL SAFETY DATA SHEET TELEPHONE: (216)292-5000

EMERGENCIES: (216)765-6727 8:30-5:00 EST AFTER HOURS: CHEMTREC (800)424-9300

-----------------------------------------------------------------------------------------------SECTION 1 -----------------------------------------------------------------------------------------------Order Code: 937860 805 Product Name: Chemical Name: Chemical Family: Product Code: MSDS Preparer: TREMSTOP IA RUST RED Sealant 937-860 R.A.MIKOL Date Prepared: Replaces Date: 11-MAY-01 N/A

-------------------------------------------------------------------------------Section 2 - Molecular Composition -------------------------------------------------------------------------------Common Name and Chemical Name Weight % CAS Number Exposure Limits ACRYLIC POLYMER OSHA:TWA ACGIH:TWA WATER OSHA:TWA ACGIH:TWA 25.0-35.0 Trade Secret STEL STEL STEL STEL 25.0-35.0 10.0-20.0 1317-65-3 (total dust, 5mg/M3 respirable fraction) (total dust, no asbestos, <1% SiO2) 5.0-10.0 STEL STEL STEL STEL (mist) 10 mg/M3 (mist) 3.0-7.0 1.0-3.0 STEL STEL STEL STEL (dust) 1.0-3.0 10 mg/M3 5 mg/M3 (dust,fume as Fe) (fume as Fe) 1.0-3.0 68002-20-0 1309-37-1 65997-17-3 1.0-5.0 (total nuisance dust) (total nuisance dust) 1.0-5.0 STEL STEL 112945-52-5 TRADE SECRET 8042-47-5 7732-18-5

CALCIUM CARBONATE (LIMESTONE) OSHA:TWA 15 mg/M3 STEL ACGIH:TWA 10 mg/M3 STEL WHITE MINERAL OIL OSHA:TWA 5 mg/M3 ACGIH:TWA 5 mg/M3 AMINE PHOSPHATE OSHA:TWA ACGIH:TWA -

SILICA, AMORPHOUS, FUMED OSHA:TWA 15 mg/M3 STEL ACGIH:TWA 10 mg/M3 STEL EXPANDABLE GRAPHITE OSHA:TWA ACGIH:TWA FIBROUS GLASS OSHA:TWA ACGIH:TWA 10 mg/M3 IRON OXIDE OSHA:TWA ACGIH:TWA

Trade Secret

MODIFIED MELAMINE FORMALDEHYDE RESIN OSHA:TWA STEL ACGIH:TWA STEL -

1,3-PROPANEDIOL,2,2,BIS(HYDROXYLMETHYL)1.0-3.0 115-77-5 OSHA:TWA 10 ppm STEL (total dust, 5mg/M3 respirable fraction) ACGIH:TWA 10 mg/M3 STEL 1,2-PROPANEDIOL OSHA:TWA ACGIH:TWA (PROPYLENE GLYCOL) STEL STEL (as ammonia) (as ammonia) 0.1-0.5 2 (respirable dust) Product 937-860 Page 1 of 5 14808-60-7 0.5-1.5 57-55-6

AMMONIUM HYDROXIDE ((NH4)(OH)) OSHA:TWA STEL 35 ppm ACGIH:TWA 25 ppm STEL 35 ppm CRYSTALLINE SILICA (QUARTZ) OSHA:TWA 0.10 mg/M3 STEL

0.1-1.0

1336-21-6

55 48

Order Code: 937860 805

ACGIH:TWA 0.10 mg/M3 CHLOROTHALONIL OSHA:TWA ACGIH:TWA -

STEL STEL STEL

-

(respirable dust) 0.1-0.3 1897-45-6

-----------------------------------------------------------------------------Section 3 - Hazards Identification -----------------------------------------------------------------------------****************************************************************************** Emergency Overview: Rust red paste. If inhaled can cause headache, dizziness, nausea, drowsiness, stupor, irritation to respiratory system. Leave area to breathe fresh air. Avoid further exposure. If symptoms persist, get medical attention. ****************************************************************************** Potential Hlth Effect/Rte of Entry: ----------------------------------Inhalation: Can cause headache, dizziness, nausea, drowsiness, stupor, irritation to respiratory system. Eyes: Can cause irritation. Ingestion: Can cause gastrointestinal irritation. Skin: Can cause irritation. Aggravated Medical Conditions: Pre-existing eye, skin and respiratory disorders may be aggravated by exposure. Acute Health Effects: See effects described above. Chronic Health Effects: Inhalation of crystalline silica (quartz) can cause cancer based on animal data, and IARC concludes sufficient evidence in humans (Group 1). Prolonged and repeated overexposure to free crystalline silica dust above the TLV level may cause scarring of the lungs with cough and shortness of breath. A delayed lung injury, silicosis may result from breathing free silica. Fillers are encapsulated and not expected to be released from product under normal conditions of use. -----------------------------------------------------------------------------Section 4 - First Aid Measures -----------------------------------------------------------------------------Inhalation: Leave area to breathe fresh air. Avoid further overexposure. If symptoms persist, get medical attention immediately. Eyes: Flush immediately with running water for 15 minutes, lifting the upper and lower lids occasionally. Get medical attention immediately. Ingestion: Do not induce vomiting. Get medical attention immediately. Skin: Clean area of contact thoroughly using soap and water. If irritation, rash or other disorders develop, get medical attention immediately. Notes to Physician: N/A

-----------------------------------------------------------------------------Section 5 - Fire Fighting Measures -----------------------------------------------------------------------------Flash Point: N/A WATER-BASED Method: N/A

56 48

3

Product 937-860 Page 2 of 5

Order Code: 937860 805

Lower Flammability Limit: N/A Upper Flammability Limit: N/A Autoignition Temperature: APPROX 800F Extinguishing Media: Not applicable. Water base compound, not expected to burn. Fire and Explosion Hazards: Not Applicable Special Fire Fighting Procedures: During a fire, personnel at the scene are to prevent exposure to fumes using accepted fire fighting techniques. Fire Fighting Equipment: N/A Other Precautions: Not Applicable -----------------------------------------------------------------------------Section 6 - Accidental Release Measures -----------------------------------------------------------------------------Release Response Overview: Absorb spill in sand, earth or other suitable material.Transfer to appropriate container for disposal. -----------------------------------------------------------------------------Section 7 - Handling and Storage -----------------------------------------------------------------------------Handling and Storage Precautions: Store under normal warehouse conditions. Prevent inhalation of vapor, ingestion, and contact with skin and eyes. Keep container closed when not in use. Precautions also apply to emptied containers. Change soiled workclothes frequently. Clean hands thoroughly after handling. -----------------------------------------------------------------------------Section 8 - Exposure Controls/Personal Protection -----------------------------------------------------------------------------Respiratory: Wear NIOSH/MSHA approved respirator as directed by the manufacturer when the ventilation is not adequate. Skin: Protect hands with rubber or other suitable gloves. Eyes: Wear suitable safety eyewear. Face: Not required. Engineering: Use local exhaust when the general ventilation is not adequate. -----------------------------------------------------------------------------Section 9 - Physical and Chemical Properties -----------------------------------------------------------------------------Odor/Appearance: MILD/RUST RED VISCOUS PASTE Color: RUST RED Physical State: VISCOUS PASTE pH: 7.0-10.0 Vapor Pressure: SAME AS WATER Vapor Density: SAME AS WATER Boiling Point: 212F (WATER) Melting Point: N/A Freezing Point: 32F (WATER) Solubility in Water: DISPERSIBLE Specific Gravity: 1.45 % Volatile Weight: 27.0 -----------------------------------------------------------------------------Section 10 - Reactivity/Stability -----------------------------------------------------------------------------Stability: Stable

57 48

4

Product 937-860 Page 3 of 5

Order Code: 937860 805

Incompatible Products: Avoid contact with strong oxidizing agents, acids, bases. Conditions to Avoid Polymerization: Hazardous polymerization will not occur. -----------------------------------------------------------------------------Section 11 - Toxicological Information -----------------------------------------------------------------------------Eyes: SEE SECTION 3 Ingestion: " " " Inhalation: " " " Skin: " " " Subchronic: " " " Chronic: " " " -----------------------------------------------------------------------------Section 12 - Ecological Information -----------------------------------------------------------------------------Ecotoxicological Data: N/A Chemical Fate: N/A -----------------------------------------------------------------------------Section 13 - Disposal Considerations -----------------------------------------------------------------------------RCRA Class: N/A Disposal Method: Not regulated by RCRA. Dispose of in compliance with state and local regulations. EPA Reportable Quantities ------------------------N/A -----------------------------------------------------------------------------Section 14 - Transportation Data -----------------------------------------------------------------------------DOT Shipping Name: NOT REGULATED DOT Hazard Class: NOT APPLICABLE DOT Label: UN/NA Number: N/A Packing Group: Special Provisions: Packaging --------Exceptions: Non-Bulk: Bulk: Quantity Limitations -------------------Passenger Aircraft or Railcar: Cargo Aircraft: Vessel Stowage Requirements --------------------------Vessel Stowage: Other Stowage: Transportation Notes: N/A -----------------------------------------------------------------------------Section 15 - Regulatory Information -----------------------------------------------------------------------------TSCA Status: On the TSCA Inventory OSHA Status: Considered hazardous based on the following criteria: Irritant Target Organs ------------Lung

58 48

5

Product 937-860 Page 4 of 5

Order Code: 937860 805

Skin Eye OSHA Hazardous Components ---------------------------------------------CALCIUM CARBONATE (LIMESTONE) * CRYSTALLINE SILICA (QUARTZ) SILICA, AMORPHOUS, FUMED IRON OXIDE * WHITE MINERAL OIL 1,3-PROPANEDIOL,2,2,BIS(HYDROXYLMETHYL)* - CHEMICAL IS LISTED AS AN IARC, NTP, OSHA, Compliance Quantities -------------------N/A SARA 311 Ratings ---------------Immediate Health Hazard: Delayed Health Hazard: Fire Hazard: Reactivity Hazard: Sudden Release of Pressure Hazard: SARA 313 Ingredients -------------------No SARA 313 Ingredients Proposition 65 Ingredients -------------------------Chemicals known to the State of California to cause cancer, birth defects and/or other reproductive harm. CAS Number -------------------------------------------------------CRYSTALLINE SILICA (QUARTZ) 14808-60-7 CHLOROTHALONIL# 1897-45-6 FORMALDEHYDE (<0.004%) 50-00-0 -----------------------------------------------------------------------------Section 16 - Other Information -----------------------------------------------------------------------------FOR INDUSTRIAL USE ONLY. KEEP OUT OF REACH OF CHILDREN. THE HAZARD INFORMATION HEREIN IS OFFERED SOLELY FOR THE CONSIDERATION OF THE USER, SUBJECT TO HIS OWN INVESTIGATION OF COMPLIANCE WITH APPLICABLE REGULATIONS, INCLUDING THE SAFE USE OF THE PRODUCT UNDER EVERY FORESEEABLE CONDITION. CAS Number -----------1317-65-3 14808-60-7 112945-52-5 1309-37-1 8042-47-5 115-77-5 or ACGIH CARCINOGEN

Y Y N N N

59 48

6

Product 937-860 Page 5 of 5

3735 GREEN ROAD BEACHWOOD, OHIO 44122-8068

MATERIAL SAFETY DATA SHEET TELEPHONE: (216)292-5000

EMERGENCIES: (216)765-6727 8:30-5:00 EST AFTER HOURS: CHEMTREC (800)424-9300

-----------------------------------------------------------------------------------------------SECTION 1 -----------------------------------------------------------------------------------------------Order Code: 825115 504 Product Name: Chemical Name: Chemical Family: Product Code: MSDS Preparer: TREMSTOP STRAP 825-1XX R. A. MIKOL Date Prepared: Replaces Date: 19-APR-04 N/A

A Material Safety Data Sheet is not required on TREMSTOP STRAP due to the fact that this product is an "article" (as defined in 29CFR 1910.1200) and is therefore exempt from OSHA Labeling/MSDS requirements. Please do not hesitate to call (216) 765-6727 for further health and safety information about any Tremco product.

28 38

2

Product 825-1XX Page 1 of 1

3735 GREEN ROAD BEACHWOOD, OHIO 44122-8068

MATERIAL SAFETY DATA SHEET TELEPHONE: (216)292-5000

EMERGENCIES: (216)765-6727 8:30-5:00 EST AFTER HOURS: CHEMTREC (800)424-9300

-----------------------------------------------------------------------------------------------SECTION 1 -----------------------------------------------------------------------------------------------Order Code: 821500X502 Product Name: Chemical Name: Chemical Family: Product Code: MSDS Preparer: TREMSTOP WS Fire Retardant Tape/Sealant 821-500 R.A.MIKOL Date Prepared: Replaces Date: 31-OCT-00 09-FEB-93

Other Applications: THIS MATERIAL SAFETY DATA SHEET (MSDS) APPLIES TO 821-500,-500X,-515,-5XX (OTHER SIZES) -------------------------------------------------------------------------------Section 2 - Molecular Composition -------------------------------------------------------------------------------Common Name and Chemical Name Weight % CAS Number Exposure Limits GRAPHITE OSHA:TWA ACGIH:TWA 2.0 mg/M3 ALUMINUM HYDROXIDE OSHA:TWA 15 mg/M3 ACGIH:TWA 10 mg/M3 NEOPRENE LATEX OSHA:TWA ACGIH:TWA RESIN OSHA:TWA ACGIH:TWA 40.0-75.0 STEL STEL STEL STEL STEL STEL STEL STEL STEL STEL 1.0-15.0 1.0-8.0 1.0-5.0 Ceil 2.00 mg/M3 Ceil 2.00 mg/M3 1.0-5.0 STEL STEL STEL STEL 0.1-1.0 (dust) 0.0-1.0 (as ammonia) (as ammonia) 1336-21-6 65997-17-3 Trade Secret 1310-58-3 Trade Secret Trade Secret (except graphite fibers) 15.0-35.0 (total nuisance dust) (total nuisance dust) 1.0-15.0 21645-51-2 7782-42-5

Trade Secret

ACRYLIC COPOLYMER OSHA:TWA ACGIH:TWA POTASSIUM HYDROXIDE OSHA:TWA ACGIH:TWA FOAMING AGENT OSHA:TWA ACGIH:TWA FIBROUS GLASS OSHA:TWA ACGIH:TWA 10 mg/M3

AMMONIUM HYDROXIDE ((NH4)(OH)) OSHA:TWA STEL 35 ppm ACGIH:TWA 25 ppm STEL 35 ppm

-----------------------------------------------------------------------------Section 3 - Hazards Identification -----------------------------------------------------------------------------****************************************************************************** Emergency Overview: Gray solid strip with no odor. Glass fiber backing may cause skin and eye irritation. Avoid contact with skin and eyes. If on skin, wash with soap and water, if irritation persists get medical attention. If in eyes, flush immediately with water for 15 minutes. If irritation develops or persists, get medical attention. No other health hazards known. ****************************************************************************** Potential Hlth Effect/Rte of Entry:

4 8

2

Product 821-500 Page 1 of 5

Order Code: 821500X502

Inhalation: Not Applicable Eyes: Contact with glass fiber backing may cause eye irritation. Contact with the sealant material alone unlikely to have effects. Ingestion: Can cause gastrointestinal irritation. Skin: Contact with glass fiber backing may cause skin irritation. Aggravated Medical Conditions: Pre-existing eye, skin and respiratory disorders may be aggravated by exposure. Acute Health Effects: See effects described above. Chronic Health Effects: Not established. -----------------------------------------------------------------------------Section 4 - First Aid Measures -----------------------------------------------------------------------------Inhalation: Not Applicable Eyes: Flush with running water for 15 minutes. If irritation persists, get medical attention immediately. Ingestion: Get medical attention or contact Poison Control Center immediately. Skin: Clean area of contact thoroughly using soap and water. If irritation, rash or other disorders develop, get medical attention immediately. Notes to Physician: N/A -----------------------------------------------------------------------------Section 5 - Fire Fighting Measures -----------------------------------------------------------------------------Flash Point: N/A Method: N/A Lower Flammability Limit: N/A Upper Flammability Limit: N/A Autoignition Temperature: N/A Extinguishing Media: Carbon dioxide, dry chemical, foam. Fire and Explosion Hazards: Not Applicable Special Fire Fighting Procedures: Not Applicable Fire Fighting Equipment: N/A Other Precautions: N/A -----------------------------------------------------------------------------Section 6 - Accidental Release Measures -----------------------------------------------------------------------------Release Response Overview: Sweep or scrape up and transfer to appropriate container for disposal. -----------------------------------------------------------------------------Section 7 - Handling and Storage -----------------------------------------------------------------------------Handling and Storage Precautions: Store under normal warehouse conditions. Handle in compliance with common hygenic practices. ------------------------------------------------------------------------------

5 8

3

Product 821-500 Page 2 of 5

Order Code: 821500X502

Section 8 - Exposure Controls/Personal Protection -----------------------------------------------------------------------------Respiratory: Not required under normal conditions of use. Skin: Protect hands with rubber or other suitable gloves. Eyes: Wear suitable safety eyewear. Face: Not required. Engineering: Use normal workroom ventilation. -----------------------------------------------------------------------------Section 9 - Physical and Chemical Properties -----------------------------------------------------------------------------Odor/Appearance: ODORLESS/GRAY SOLID STRIP Color: GRAY Physical State: SOLID pH: N/A Vapor Pressure: N/A Vapor Density: N/A Boiling Point: N/A Melting Point: N/A Freezing Point: N/A Solubility in Water: Insoluble Specific Gravity: 1.0 % Volatile Weight: 0.0 -----------------------------------------------------------------------------Section 10 - Reactivity/Stability -----------------------------------------------------------------------------Stability: Stable Incompatible Products: Not known. Conditions to Avoid Polymerization: Hazardous polymerization will not occur. -----------------------------------------------------------------------------Section 11 - Toxicological Information -----------------------------------------------------------------------------Eyes: SEE SECTION 3 Ingestion: " " " Inhalation: " " " Skin: " " " Subchronic: " " " Chronic: " " " -----------------------------------------------------------------------------Section 12 - Ecological Information -----------------------------------------------------------------------------Ecotoxicological Data: N/A Chemical Fate: N/A -----------------------------------------------------------------------------Section 13 - Disposal Considerations -----------------------------------------------------------------------------RCRA Class: N/A Disposal Method: Not regulated by RCRA. Dispose of in compliance with state and local regulations. EPA Reportable Quantities ------------------------N/A

6 8

4

Product 821-500 Page 3 of 5

Order Code: 821500X502

-----------------------------------------------------------------------------Section 14 - Transportation Data -----------------------------------------------------------------------------DOT Shipping Name: NOT REGULATED DOT Hazard Class: DOT Label: UN/NA Number: Packing Group: Special Provisions: Packaging --------Exceptions: Non-Bulk: Bulk: Quantity Limitations -------------------Passenger Aircraft or Railcar: Cargo Aircraft: Vessel Stowage Requirements --------------------------Vessel Stowage: Other Stowage: Transportation Notes: N/A

-----------------------------------------------------------------------------Section 15 - Regulatory Information -----------------------------------------------------------------------------TSCA Status: On the TSCA Inventory OSHA Status: Considered hazardous based on the following criteria: Irritant Target Organs ------------Skin Eye OSHA Hazardous Components ---------------------------------------------POTASSIUM HYDROXIDE Compliance Quantities -------------------No Compliance Quantities SARA 311 Ratings ---------------Immediate Health Hazard: Delayed Health Hazard: Fire Hazard: Reactivity Hazard: Sudden Release of Pressure Hazard: SARA 313 Ingredients -------------------No SARA 313 Ingredients Proposition 65 Ingredients -------------------------No Proposition 65 Ingredients -----------------------------------------------------------------------------Section 16 - Other Information -----------------------------------------------------------------------------CAS Number -----------1310-58-3

N N N N N

7 8

5

Product 821-500 Page 4 of 5

Order Code: 821500X502

FOR INDUSTRIAL USE ONLY. KEEP OUT OF REACH OF CHILDREN. THE HAZARD INFORMATION HEREIN IS OFFERED SOLELY FOR THE CONSIDERATION OF THE USER, SUBJECT TO HIS OWN INVESTIGATION OF COMPLIANCE WITH APPLICABLE REGULATIONS, INCLUDING THE SAFE USE OF THE PRODUCT UNDER EVERY FORESEEABLE CONDITION.

8 8

6

Product 821-500 Page 5 of 5

Information

Microsoft Word - Plumbing.doc