Read LCS01A01.pdf text version

nt rre rs & Cu so rs n to Se oni M

AC Current Indicator LCS10T12 & LPM Go-Glow Indicator

Description

The LCS10T12 connected to the LPM12 or LPMG12 indicator is a low cost, easy to use, go/no go indication system for the remote monitoring of current flow. The LCS10T12 is installed on an adequately insulated wire of the monitored load. Its 12 in. (30.4 cm) leads are connected to the LPM12 or LPMG12 panel mount indicator directly or via customer supplied wires up to 500 feet (152.4 m) long.

Operation

When the monitored current is 5 ampere-turns, the panel mount LPM indicator will glow. The LCS10T12 is designed to maximize the light output of the panel mount indicator. It can be used to monitor current flow of less than 5 A by passing the monitored conductor 2 or more times through the sensor.

Connection

Mechanical View

Inches (Millimeters)

Wire Length: 500 Ft. (152.4 m) Max. (Customer Supplied)

Low Cost Go/No Go Indication May Be Connected To Wires Up To 500 Feet (152.4 m) Long Remote Monitoring of Currents Up To 50 A Green or Red LED Indicator Available Approvals:

CURRENT LIMITING RESISTOR

CAUTION: The LCS10T12 must be connected to the LPM12 or LPMG12 before current flows to prevent damage or a shock hazard. Monitored wires must be properly insulated.

2 24 AWG (0.25 mm) UL1007 STRIPPED 0.25 (6.35) 0.53 12 ± 1 (304.8 ± 25.4) (13.46)

0.28 (7.11 < 0.22 _ (5.59)

Inches (Millimeters)

Panel mount indicator designed to match the output of the LCS10T12. The LPM12 and LPMG12 come with 12 in. (30.4 cm) wires and a one piece mounting clip. Both devices install quickly in a 0.25 in. (6.35 mm) hole in panels from 0.031 ... 0.062 in. (0.79 ... 1.6 mm) thick.

Available Models· LCS10T12 · LPM12 · LPMG12

Don't see what you need? Call us for a minimum quantity and price quote! Ordering Table

Description AC Current Sensor Red LED Indicator Green LED Indicator Part Number LCS10T12 LPM12 LPMG12

Technical Data

Monitored Current Current Range 2 ... 50 A AC Wire Passes Min. Current Max. Current Max. Inrush 1 5A 50 A 120 A 2 2.5 A 25 A 60 A 3 1.7 A 16.6 A 40 A 4 1.3 A 12.5 A 30 A 5 5/X 50/X 120/X Maximum Current 50 ampere-turns continuous Frequency 50 ... 60 Hz DC Resistance of Current Limiter 65 Mechanical Sensor Hole 0.36 in. (9.14 mm) for up to #4 AWG (21.1 mm2) THHN wire Termination 12 in. (30.4 cm) wire leads Environmental Operating/Storage Temperature -40°C ... +60°C/-40°C ... +85°C Weight LCS: 0.8 oz (23 g) LPM: 0.2 oz (6 g) 8.14

· denotes a preferred product

SSAC, LLC. · 800-377-7722 · [email protected] · [email protected] · www.ssac.com

Max. Wire Dia. 0.355 in. (9.0 mm) 0.187 in. (4.7 mm) 0.15 in. (3.8 mm) 0.125 in. (3.2 mm)

LCS01B01