Thermostatic Water Controllers

TempControl®

TempControl

TempControl for the Precise and Accurate Control of Tempered or Hot Water

Applications

A necessity for all general uses and applications where the temperature of generated hot water must be controlled and tempered before distribution. To control the main hot water system in any building... hospitals, schools, apartments, hotels, motels, etc. In animal husbandry for washing livestock. For laundry machines, car washes, and all commercial washing and cleaning. In breweries, tanneries, canneries, or any type of processing. In photo or x-ray development and processing. Wherever generated hot water must be tempered for safe, economic use. Not to be used for emergency eyewash or shower applications.

Constant Temperature

The unique construction of TempControl is such that the water, even on low draw or demand, must completely pass the sensing coil of the thermal motor before discharge. This ensures that the delivery temperature will be maintained. Discharge temperature is adjustable to within 10°F of the hot and cold inlet water temperatures (See installation instructions for setting maximum discharge temperatures).

Operation Range

Standard units designed for field setting between 85°F (29°C) and 120°F (49°C) range. See installation instructions for other available settings.

Automatic

Automatic compensation for supply line temperature and pressure changes. Fails safely on hot or cold supply failure to greatly reduce flow. If complete shut down of flow is required, please consult factory for information on high temperature alarm and solenoid systems.

TempControl

Performance

Valve is certified to ASSE Standard 1017-2003 and CSA Standard B-125.3. Valve will control temperature with reduction in flow to minimum flows (see chart on page 4).

Construction and Design Features

All bronze and stainless steel components. Liquid fill thermal motor consisting of 72" (1829mm) coiled sensing tube and highly responsive bellows. Bellows is mounted out of water and therefore is not subject to corrosion and mineral build-up, ensuring long life. This feature assures that bellows will not become coated with lime and foreign matter that would reduce its sensitivity. Precision ground stainless steel piston. Large positive grip adjustment knob for accurate setting of desired temperature. Can be locked at desired setting to prevent unauthorized use. The entire valve control mechanism is housed in a replaceable cartridge unit which ensures the valve body never needs to be removed from the line. Cartridge Unit can be removed in minutes for cleaning, inspection or replacement.

Balanced stainless steel operating piston

Spring loaded swivel action checks with renewable seats

72" sensing coil (1829mm)

Bellows is mounted out of water

TempControl

TempControl® Flow Rates and Sizing

FLOW RATE - gpm (L/min)

PRESSURE DIFFERENTIAL - psi (kPA) Valve Model Min Flow Rate*

0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min)

Min Flow Rate

0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 5 gpm (18.9 L/min) 0.5 gpm (1.9 L/min) 9 gpm (34.1 L/min) 13 gpm (49.2 L/min) 13 gpm (49.2 L/min) 13 gpm (49.2 L/min) 13 gpm (49.2 L/min)

5 psi (34 kPA)

1 gpm (3.8 L/min) 1 gpm (3.8 L/min) 7 gpm (26.5 L/min) 4 gpm (15.1 L/min) 18 gpm (64.4 L/min) 22 gpm (83.3 L/min) 25 gpm (94.6 L/min) 30 gpm (113.6 L/min) 38 gpm (143.8 L/min)

10 psi (69 kPA)

3 gpm (11.4 L/min) 3 gpm (11.4 L/min) 12 gpm (45.4 L/min) 6 gpm (22.7 L/min) 27 gpm (102.2 L/min) 38 gpm (143.8 L/min) 43 gpm (162.8 L/min)

20 psi (138 kPA)

6 gpm (22.7 L/min) 7 gpm (26.5 L/min) 18 gpm (64.4 L/min) 8 gpm (30.3 L/min) 37 gpm (140.1 L/min)

25 psi (172 kPA)

7 gpm (26.5 L/min) 9 gpm (34.1 L/min) 21 gpm (75.7 L/min) 10 gpm (37.9 L/min) 41 gpm (155.2 L/min)

30 psi (207 kPA)

8 gpm (30.3 L/min) 10 gpm (37.9 L/min) 23 gpm (83.3 L/min) 11 gpm (41.6 L/min)

45 psi (310 kPA)

11 gpm (41.6 L/min) 15 gpm (56.8 L/min) 27 gpm (102.2 L/min) 14 gpm (53 L/min)

5-102 5-102-HC 5-200 5-200-1 5-400 5-500 5-700 5-900 5-1000

44 gpm 53 gpm (166.6 L/min) (200.6 L/min) 70 gpm (265 L/min)

50 gpm 55 gpm 59 gpm (189.3 L/min) (208.2 L/min) (223.3 L/min)

57 gpm 62 gpm 66 gpm 77 gpm (215.8 L/min) (234.7 L/min) (249.8 L/min) (291.5 L/min) 84 gpm (318 L/min) 89 gpm 104 gpm (336.9 L/min) (393.7 L/min)

55 gpm 76 gpm (208.2 L/min) (287.7 L/min)

67 gpm 100 gpm 111 gpm 120 gpm 140 gpm (253.6 L/min) (378.5 L/min) (420.2 L/min) (454.2 L/min) (529.9 L/min)

*Minimum flow rate when valve is installed at or near the hot water source with recirculated tempered water and continuously operating circulating pump.

Note: The U.S. Department of Labor, Occupational Safety and Health Administration (OSHA) Technical Manual, Section II, Chapter 7, Legionnaire's Disease, recommends that due to concerns about the potential for growth of Legionella bacteria in stagnant pipe runs, "Domestic hot water recirculation pumps should run continuously. They should be excluded from energy conservation measures."

Proper Sizing

Thermostatic water controllers should be sized according to the flow capacity required from the valve, NOT the pipe size supplied to the valve. The pressure differential shown above represents the actual pressure drop across the valve to produce a given flow rate. The frictional loss associated with the valve is incorporated into the flow rate figures. For assistance and technical support in sizing and selection of the proper TempControl Thermostatic Water Controller, consult the Symmons TEMPSIZETM computer sizing software, your local representative or Symmons Customer Service Department at 1-800-SYMMONS.

TempControl

TempControl® Valve Only

Specification

5-_________( ) inlets ( ) outlets: TempControl thermostatic controller with swivel action check stops,* removable cartridge with strainer, stainless steel piston and liquid fill thermal motor with bellows mounted out of water. Standard valve finish is rough brass or bronze with rough chrome finish on operating handle and service stops.

Modifications: Suffix 1: Provides greater control at low temperature range between 70°­110°F Suffix NI: Rough Suffix P: Suffix W: Suffix HC: For higher capacity up to 15 gpm (56.8 L/min) at 45 psi (310 kPA) (Model 5-102 only)

Model Shown 5-400-P

(51mm)

(51mm) (32mm) (32mm)

(32mm) (32mm)

(102mm)

(51mm) (51mm) (68mm)

5-102 Model No. Inlets

1/2" (13mm) 3/4" (19mm) 3/4" (19mm) 1" (25mm) 1 1/4" (32mm) 1 1/2" (38mm) 1 1/2" (38mm)

5-200 thru 5-700 Outlets

1/2" (13mm) 3/4" (19mm) 1" (25mm) 1 1/4" (32mm) 1 1/2" (38mm) 1 1/2" (38mm) 2" (51mm)

5-900 thru 5-1000 C

2 1/8" (54mm) 1 7/8" (48mm) 1 7/8" (48mm) 1 5/8" (41mm) 1 5/8" (41mm) 2 9/16" (65mm) 2 9/16" (65mm)

A

3 1/2" (89mm) 6 1/4" (159mm) 6 1/4" (159mm) 8" (203mm) 8" (203mm) 12" (305mm) 12" (305mm)

B

5 3/4" (146mm) 5 3/8" (137mm) 6 3/8" (162mm) 7" (178mm) 7" (178mm) 7 3/4 (197mm) 7 3/4 (197mm)

D

1 15/16" (49mm) 2 5/8" (67mm) 2 7/16" (62mm) 2 7/8" (73mm) 2 7/8" (73mm) ­ ­

E

­ 2" (51mm) 2 5/8" (67mm) 3 1/8" (79mm) 3 1/8" (79mm) 3 3/8" (86mm) 3 3/8" (86mm)

5-102 5-200 5-400 5-500 5-700 5-900 5-1000

*Model 5-102A has union check stops. Models 5-200 thru 5-700 have integral check stops. Models 5-900 and 5-1000 have separate check stops. Valve and piping assembly shown with optional wall mounting bracket.

TempControl

TempControl® Valve and Piping Assembly "A" Series

Specification

5-_________A ( ) inlets ( ) outlets: TempControl thermostatic controller with swivel action check stops, removable cartridge with strainer, stainless steel piston * and liquid fill thermal motor with bellows mounted out of water. Volume control shut off valve, bimetal dial thermometer 3" (76mm) face, range 20°­240°F [-7°­116°C), brass pipe, fittings and unions. Standard valve and piping finish is rough bronze, brass or copper.

Model Shown 5-400-P

Modifications: Suffix 1: Provides greater control at low temperature range 70°­110°F (24°­43°C) for use in Suffix ASB: Factory assembled and tested Suffix STN: Suffix STN/POL: Satin Suffix NI: Rough chrome finish (not Suffix P: Suffix W: Suffix V: Suffix HC: For higher capacity up to 15 gpm (56.8 L/min) at 45 psi (310 kPA) (Model 5-102A only)

70 60 50 40 30 80 90 100 120 140 150

Model No.

Inlets

1/2" (13mm) 3/4" (19mm) 3/4" (19mm) 1" (25mm) 1 1/4" (32mm) 1 1/2" (38mm) 1 1/2" (38mm)

Outlets

1/2" (13mm) 3/4" (19mm) 1" (25mm) 1 1/4" (32mm) 1 1/2" (38mm) 1 1/2" (38mm) 2" (51mm)

A

12 5/8" (321mm) 17 1/8" (435mm) 17 3/8" (441mm) 19 1/8" (486mm) 22 1/2" (572mm) 22 3/4" (578mm) 22 5/8" (575mm)

B

1 1/2" (38mm) 3 9/16" (90mm) 3 9/16" (90mm) 3 15/16" (100mm) 4 11/16" (119mm) 2 11/16" (68mm) 2 11/16" (68mm)

C

3 1/2" (89mm) 8 1/2" (216mm) 8 1/2" (216mm) 11" (279mm) 12" (305mm) 12" (305mm) 12" (305mm)

D

2 1/8" (54mm) 1 7/8" (48mm) 1 7/8" (48mm) 1 5/8" (41mm) 1 5/8" (41mm) 2 9/16" (65mm) 2 9/16" (65mm)

E

2 1/8" (54mm) 2 5/8" (67mm) 2 7/16" (62mm) 2 7/8" (73mm) 2 7/8" (73mm) 2 9/16" (65mm) 2 9/16" (65mm)

F

8" (203mm) 7 1/4" (184mm) 8 1/4" (210mm) 8 5/8" (219mm) 8 5/8" (219mm) 10 5/16" (262mm) 10 5/16" (262mm)

5-102A 5-200A 5-400A 5-500A 5-700A 5-900A 5-1000A

*Model 5-102A has union check stops. Models 5-200A thru 5-700A have integral check stops. Models 5-900A and 5-1000A have separate check stops. Valve and piping assembly shown with optional wall mounting bracket.

TempControl

TempControl® Valve and Piping in Cabinet "B" Series

Specification

5-_________B ( ) inlets ( ) outlets: TempControl thermostatic controller with swivel action check stops, removable cartridge with strainer, stainless steel piston and liquid * fill thermal motor with bellows mounted out of water. Volume control shut off valve, bimetal dial thermometer 3" (76mm) face, range 20°­ 240° F (-7°­116°C), brass pipe, fittings and unions to cabinet limits. Bottom supplies, top outlet. Cabinet to be 16 gauge (1.6mm) body, 12 gauge (2.7mm) door, hinged left hand door with cylinder lock. Standard valve and piping finish is rough bronze, brass or copper. Standard cabinet fully recessed steel with baked white enamel finish (specify cabinet material and style modifications as desired).

Model Shown 5-400B-T-P

(51mm)

Modifications: Suffix 1: Provides greater control at low temperature range 70°­ 110°F (24°­43°C) for use in Suffix ASB: Factory assembled and tested Suffix STN: Satin spray finish (ASB units only) Suffix STN/POL: Suffix NI: Rough Suffix P: Polished chrome highlight finish (not available on ASB Suffix M: Suffix S: Semi-recessed cabinet has 4" (102mm) return flange Suffix T: Suffix TOP Suffix V: Suffix HC: For higher capacity up to 15 gpm (56.8 L/min) at 45 psi (310 kPA) (Model 5-102B only)

(51mm) (102mm) (51mm) (51mm)

Model No.

Inlets

1/2" (13mm) 3/4" (19mm) 3/4" (19mm) 1" (25mm) 1 1/4" (32mm) 1 1/2" (38mm) 1 1/2" (38mm)

Outlets

1/2" (13mm) 3/4" (19mm) 1" (25mm) 1 1/4" (32mm) 1 1/2" (38mm) 1 1/2" (38mm) 2" (51mm)

A

22 3/8" (568mm) 22 3/8" (568mm) 22 3/8" (568mm) 31" (787mm) 31" (787mm) 27" (686mm) 27" (686mm)

B

13 3/4" (349mm) 13 3/4" (349mm) 13 3/4" (349mm) 17" (432mm) 17" (432mm) 19" (483mm) 19" (483mm)

C

10" (254mm) 10" (254mm) 10" (254mm) 10 1/2" (267mm) 10 1/2" (267mm) 11 1/2" (292mm) 11 1/2" (292mm)

D

3 1/2" (89mm) 8 1/2" (216mm) 8 1/2" (216mm) 11" (279mm) 12" (305mm) 12" (305mm) 12" (305mm)

E

7 7/8" (200 mm) 8" (203mm) 8" (203mm) 8" (203mm) 8" (203mm) 6 3/4" (171mm) 6 3/4" (171mm)

F

7 7/8" (200mm) 7 1/4" (184mm) 7 1/4" (184mm) 6 3/4" (171mm) 6 3/4" (171mm) 6 3/4" (171mm) 6 3/4" (171mm)

G

6" (152mm) 4 1/4" (108mm) 4 1/4" (108mm) 4 3/4" (121mm) 7" (178mm) 3 1/2" (89mm) 3 1/2" (89mm)

5-102B 5-200B 5-400B 5-500B 5-700B 5-900B 5-1000B

*Model 5-102B has union check stops. Models 5-200B thru 5-700B have integral check stops. Models 5-900B and 5-1000B have separate check stops. Valve and piping assembly shown with optional wall mounting bracket.

TempControl

TempControl® High Temperature Alarm System

Specification

HTA-100: TempControl High Temperature Alarm System to monitor and provide audible and visible alert in the event of hot water temperatures exceeding set point thresholds. Programmable electronic module features three operational modes: normal valve operation, caution (alert), and alarm (shutdown). Set point range is 40°F - 149°F (4.5°C - 65°C). When specified with ______ (optional) solenoid valve, the system, when in alarm mode will provide complete emergency shutdown of water flow. System to include key access programmable electronic module, stainless steel panel, 4"x 4" electrical mounting box, 120V AC - 12V AC/15VA UL Listed/CSA Certified Class 2 transformer, solid state temperature probe with 25' of cable and (2) system operation keys.

Options

Solenoid Valves - 12V DC N.C. 10 watts max SV-102: 1/2" NPT SV-200: 3/4" NPT SV-400: 1" NPT Tee Fittings TF-102: TF-200: TF-400: TF-500: TF-700/900: TF-1000: Cable TPC-50: TPC-100: 50' pre-coiled length 100' pre-coiled length (Contact factory for additional pre-coiled lengths in 50' increments, 1000' maximum) Water Hammer Arrestor WHA-1: 1" NPT water hammer arrestor 1/2" x 1/2"x 1/4" NPT 3/4" x 3/4" x 1/4" NPT 1" x 1" x 1/4" NPT 1-1/4" x 1-1/4" x 1/4" NPT 1-1/2" x 1-1/2" x 1/4" NPT 2" x 2" x 1/4" NPT SV-500: 1-1/4" NPT SV-700/900: 1-1/2" NPT SV-1000: 2" NPT

TempControl

TempControl® Hi-Low Systems

Fully factory assembled and tested. All bronze and stainless steel components. Thermal motor bellows mounted out of water and therefore not subject to mineral build-up for longer service life. TEMPSIZETM Sizing program and support. Entire valve control mechanism housed in a replaceable cartridge unit, minimizes service downtime when unit is serviced.

The TempControl Hi-Low System is a specialized system designed to address applications where there is a potential for pressure disturbances in the supply lines servicing the thermostatic mixing valve. The system is used when the valve is located outside the mechanical room of a building. Any thermostatic mixing valve, especially larger size valves, when flowing well below its rated capacity, may not maintain temperature within the desired range when the hot and cold supply lines servicing the valve are subjected to pressure disturbances. In a mechanical room it is assumed that the supply pressures are stable and are not subject to pressure disturbances. As a result, we do not recommend Hi-Low systems in this location. Conversely, when a valve's intended location is indicated as being outside the mechanical room, it is assumed that there is a potential for pressure fluctuations in the hot and cold supply

lines, great enough to effect temperature control at low flow. Therefore, a Hi-Low System is recommended. (Consult TEMPSIZETM Sizing Program for proper selection) The TempControl Hi-Low System includes a large and a small TempControl thermostatic mixing valve that are piped in parallel to the hot and cold supply lines and a pressure reducing valve (PRV) on the outlet side of the larger valve. When there is a low demand, or draw on the system, the small valve handles the flow requirements. When the demand increases, a greater pressure differential in the system is created, the PRV to open to assist the smaller valve in meeting the higher flow requirements. NOTE: If the system is designed so that a TempControl valve is not subjected to supply pressure disturbances, even though it is located outside the mechanical room, a single valve will operate properly.

TempControl

TempControl® Hi-Low Systems Valve and Piping Assembly

Specification

5-_________( ) inlets ( ) outlets: TempControl HI-LOW system consists of two (2) thermostatic controllers with swivel action check stops, each controller contains a removable cartridge with strainer, stainless steel piston and liquid fill thermal motor with bellows element mounted out of water, inlet manifold piping, pressure reducing valve (PRV), two (2) pressure gauges, two

Model Shown 5-900-200-PRV

(2) ball valves, bi-metal dial thermometer 3" (76 mm) face, range 20°­ 240°F (-7°­116°C), wall bracket, connecting piping and fittings to cabinet limits. Standard rough bronze and copper finish. Bottom supplies and top outlet. Factory assembled and tested.

Modifications: Suffix TOP: Suffix V: Vacuum breaker

Suffix STN:

Suffix STN/POL: Satin spray with polished chrome

FLOW RATE - gpm (L/min)

PRESSURE DIFFERENTIAL - psi (L/min) Valve Model 5-200-102-PRV 5-400-102-PRV 5-500-102-PRV 5-700-102-PRV 5-900-102-PRV 5-1000-102-PRV 5-900-200-PRV 5-1000-200-PRV Inlets

3/4" (19mm) 3/4" (19mm)

Outlets

3/4" (19mm) 1" (25mm)

Min Flow Rate

0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 5 gpm (18.9 L/min)

5 psi (34 kPA)

8 gpm (30.3 L/min) 19 gpm (71.9 L/min) 23 gpm (87.1 L/min) 26 gpm (98.4 L/min) 31 gpm (117.3 L/min) 39 gpm (147.6 L/min) 37 gpm (140 L/min)

10 psi (69 kPA)

15 gpm (56.8 L/min) 30 gpm (113.6 L/min) 41 gpm (155.2 L/min) 46 gpm (174.1 L/min)

20 psi (138 kPA)

24 gpm (90.8 L/min) 43 gpm (162.8 L/min) 56 gpm (212 L/min)

25 psi (172 kPA)

28 gpm (106.0 L/min) 48 gpm (181.7 L/min) 62 gpm (234.7 L/min

30 psi (207 kPA)

31 gpm (117.3 L/min)

45 psi (310 kPA)

38 gpm (143.8 L/min)

52 gpm 64 gpm (196.8 L/min) (242.2 L/min) 67 gpm 81 gpm (253.6 L/min) (306.6 L/min) 74 gpm 88 gpm (280.1 L/min) (333.1 L/min)

1" 1 1/4" (25mm) (32mm) 1 1/4" 1 1/2" (32mm) (38mm) 1 1/2" 1 1/2" (38mm) (38mm) 1 1/2" (38mm) 2" (51mm)

63 gpm 69 gpm (238.5 L/min) (261.2 L/min)

58 gpm 82 gpm 91 gpm 97 gpm 115 gpm (219.5 L/min) (310.4 L/min) (344.4 L/min) (367.1 L/min) (435.3 L/min) 70 gpm (265 L/min) 106 gpm 118 gpm 128 gpm 151 gpm (401.2 L/min) (446.6 L/min) (484.5 L/min) (571.5 L/min)

1 1/2" 1 1/2" (38mm) (38mm) 1 1/2" (38mm) 2" (51mm)

67 gpm 94 gpm 105 gpm 112 gpm 131 gpm (253.6 L/min) (355.8 L/min) (397.4 L/min) (423.9 L/min) (495.8 L/min)

5 gpm 45 gpm 79 gpm 118 gpm 132 gpm 143 gpm 167 gpm (18.9 L/min) (170.3 L/min) (299.0 L/min) (446.6 L/min) (499.6 L/min) (541.3 L/min) (632.1 L/min)

*Model 5-102 has union check stops. Models 5-200 thru 5-700 have integral check stops. Models 5-900 and 5-1000 have separate check stops.

TempControl

TempControl® Hi-Low Systems Valve and Piping in Cabinet Assembly

Specification

5-_________( ) inlets ( ) outlets: TempControl Hi-Low system consists of two (2) thermostatic controllers with swivel action check stops, each controller contains a removable cartridge with strainer, stainless steel piston and liquid fill thermal motor with bellows element mounted out of water, inlet manifold piping, pressure reducing valve (PRV), two (2) pressure gauges, two (2) ball valves, bi-metal dial thermometer 3" face (76mm), range 20°­ 240°F (-7°­116°), wall bracket, connecting piping and fittings to cabinet limits. Standard rough bronze and copper finish. Bottom supplies and top outlet. Factory assembled and tested. Cabinet to be 16 gauge (1.6mm) body, 12 gauge (2.7mm) left hinged door (or double doors on larger systems) with cylinder lock and key. Standard cabinet fully recessed steel, with baked white enamel finish.

Modifications: Suffix M: (outlet is through right side of cabinet) Suffix S: Suffix STN: Suffix T: Suffix STN/POL: Suffix TOP: Top Suffix V: Vacuum breaker

FLOW RATE - gpm (L/min)

PRESSURE DIFFERENTIAL - psi (L/min) Valve Model 5-200B-102-PRV 5-400B-102-PRV 5-500B-102-PRV 5-700B-102-PRV 5-900B-102-PRV 5-1000B-102-PRV 5-900B-200-PRV 5-1000B-200-PRV Inlets

3/4" (19mm) 3/4" (19mm)

Outlets

3/4" (19mm) 1" (25mm)

Min Flow Rate

0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 0.5 gpm (1.9 L/min) 5 gpm (18.9 L/min)

5 psi (34 kPA)

8 gpm (30.3 L/min) 19 gpm (71.9 L/min) 23 gpm (87.1 L/min) 26 gpm (98.4 L/min) 31 gpm (117.3 L/min) 39 gpm (147.6 L/min) 37 gpm (140 L/min)

10 psi (69 kPA)

15 gpm (56.8 L/min) 30 gpm (113.6 L/min) 41 gpm (155.2 L/min) 46 gpm (174.1 L/min)

20 psi (138 kPA)

24 gpm (90.8 L/min) 43 gpm (162.8 L/min) 56 gpm (212 L/min)

25 psi (172 kPA)

28 gpm (106.0 L/min) 48 gpm (181.7 L/min) 62 gpm (234.7 L/min

30 psi (207 kPA)

31 gpm (117.3 L/min)

45 psi (310 kPA)

38 gpm (143.8 L/min)

52 gpm 64 gpm (196.8 L/min) (242.2 L/min) 67 gpm 81 gpm (253.6 L/min) (306.6 L/min) 74 gpm 88 gpm (280.1 L/min) (333.1 L/min)

1" 1 1/4" (25mm) (32mm) 1 1/4" 1 1/2" (32mm) (38mm) 1 1/2" 1 1/2" (38mm) (38mm) 1 1/2" (38mm) 2" (51mm)

63 gpm 69 gpm (238.5 L/min) (261.2 L/min)

58 gpm 82 gpm 91 gpm 97 gpm 115 gpm (219.5 L/min) (310.4 L/min) (344.4 L/min) (367.1 L/min) (435.3 L/min) 70 gpm (265 L/min) 106 gpm 118 gpm 128 gpm 151 gpm (401.2 L/min) (446.6 L/min) (484.5 L/min) (571.5 L/min)

1 1/2" 1 1/2" (38mm) (38mm) 1 1/2" (38mm) 2" (51mm)

67 gpm 94 gpm 105 gpm 112 gpm 131 gpm (253.6 L/min) (355.8 L/min) (397.4 L/min) (423.9 L/min) (495.8 L/min)

5 gpm 45 gpm 79 gpm 118 gpm 132 gpm 143 gpm 167 gpm (18.9 L/min) (170.3 L/min) (299.0 L/min) (446.6 L/min) (499.6 L/min) (541.3 L/min) (632.1 L/min)

*Model 5-102 has union check stops. Models 5-200B thru 5-700B have integral check stops. Models 5-900B and 5-1000B have separate check stops.

Symmons Industries, Inc., 31 Brooks Drive, Braintree, MA 02184-3804 Symmons Industries, Inc., 31 Brooks Drive, Braintree, MA 02184-3804 www.symmons.com www.symmons.com Copyright © 2008 Symmons Industries, Inc., Braintree, Massachusetts

Copyright © 2008 Symmons Industries, Inc., Braintree, Massachusetts

Information

front

12 pages

Find more like this

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

5101


You might also be interested in

BETA
Front Cover.drw
Carbonating at Home with Improvised Equipment and Soda Fountains
Anaerobic Biogas (Methane) Digester: Construction Instruction___
c-i&o