Read D00004FI, 28/2007 text version

D01616/GB0, 30/2008

ASD1 and ASD2 Aspiration Smoke Detectors

The ASD1 (single channel) ASD2 (dual channel) aspiration systems actively draws air from the protected area through a network of 25 mm pipes perforated with sampling holes. The system incorporates up to two conventional or addressable point detectors providing the ability for either redundancy or mixed detection strategies. Each channel can have a pipe run of up to 100 m. Both model options utilise a high performance aspiration and flow monitoring circuitry. The flow level is displayed on a 10 elements bar graph with adjustments for high and low flow thresholds. Flow failure is reported as a device fault.

ASD1

Product features

The ASD provides a number of options as far as detection strategies are concerned. Firstly there are the detectors themselves where the Installer/Consultant can specify the same detector brand and range that is used to protect the rest of building thereby providing the simplest and most cost effective Aspirated Smoke Detector on the market today. The ASD detector is fitted with the most powerful fan in its class. It can be adjusted via programming and is capable of producing 200pa of negative pressure which is stronger than most of its full sized competitors. This fan has been integrated together with the flow sensing system to provide the most sensitive, accurate and useable flow sensor. This is displayed on the 10 segment bargraph that is provided for each pipe.

Technical data

Number of Detectors (not supplied) ASD1: 2 addressable or conventional ASD2: 2 addressable or conventional Nominal 24VDC (18 to 30 VDC) Max 350 mA -10°C to +60°C 0 to 95% RH (non-condensing) 25 mm o/d max 100 m (for VdS approved installations, consult the manual) IP53 Serviceable filter. External filter optional High and Low adjustable VdS, CE

Operating Voltage Current Consumption Operating Temperature Operating Humidity Pipe Length

IP Rating Filtration Flow Monitoring Equipment Approvals

Pipe and pipes accessories

Accessories Plastic pipe 25 mm Bend 45° Bend 90° Socket End cap Bracket Glue Fixings Comments

Local requirement of pipes and pipe installation must be followed

Mechanical installation

Electrical connections

Only in the ASD2

BATTERY BAT +24V 0V FUSE

LOOPLOOP IN OUT

FAULT 1 NO COM NC

FAULT 2 NO COM NC

+- +-

Connections of the ASD1 and ASD2

In the event of a fault condition, one or both of the Fault relays will change state.

Pelco Finland Oy

D01616/GB0, 30/2008

2

ASD1 with single conventional detectors

Detector must be fitted to position 2. Terminating resistor or End of line unit (EOL) may be fitted as shown below if required. FR is a fault relay.

BATTERY +24V BATTERY 0V

-

+

2 1

EOL

LOOP IN (+) LOOP IN (-)

+

FR

ASD1

ASD1 with 2 conventional detectors

Terminating resistor or End of line unit (EOL) may be fitted as shown below if required.

BATTERY +24V BATTERY 0V

-

+

2 1

EOL

LOOP IN (+) LOOP IN (-)

+

FR

LOOP OUT (+) LOOP OUT (-)

ASD1

Pelco Finland Oy

D01616/GB0, 30/2008

3

Series of ASD1 units on a conventional detection circuit

Schematic shows first and last units. Zone circuit wiring returned from last unit to first via Fault 2 relay contacts in each unit and terminating resistor or End of line unit (EOL) fitted to first unit as shown. Flow fault condition in any unit will break the connection to the terminating resistor (or EOL) and indicate a zone fault without affecting the operation of the detectors themselves.

-

+

BATTERY +24V BATTERY 0V

-

+

2 1

FR

+

FAULT 2 NO COM NC

EOL

ASD1

BATTERY +24V BATTERY 0V

-

+

2 1

FR

+

FAULT 2 NO COM NC

ASD1

Pelco Finland Oy

D01616/GB0, 30/2008

4

ASD1 with 2 addressable detectors

Detectors wired directly to loop with Fault 2 relay connected to loop via monitoring unit.

-

+

BATTERY +24V BATTERY 0V

-

+

2 1

FR

+

FAULT 2 NO COM NC

Monitoring unit

ASD1

-

FX addressable loop

+

ASD2 with conventional detectors

A pair of Conventional Point Detectors are mounted on the display/mounting board using the screws provided.

-

BATTERY +24V BATTERY 0V

+

-

+

2 1

FAULT 1 NO COM NC

EOL

-

+

FAULT 2 NO COM NC

ASD2

Pelco Finland Oy

D01616/GB0, 30/2008

5

Series of ASD2 units on conventional detection circuit

-

+

BATTERY +24V BATTERY 0V

-

+

2 1

FAULT 1 NO COM NC

EOL

-

+

FAULT 2 NO COM NC

ASD2

BATTERY +24V BATTERY 0V

-

+

2 1

FAULT 1 NO COM NC

-

+

FAULT 2 NO COM NC

ASD2

Pelco Finland Oy

D01616/GB0, 30/2008

6

ASD2 with addressable detectors

-

+

BATTERY +24V BATTERY 0V

-

+

2 1

FAULT 1 NO COM NC

Monitoring unit

-

+

FAULT 2 NO COM NC

Monitoring unit

LOOP IN (+) LOOP IN (-) LOOP OUT (+) LOOP OUT (-)

ASD2

-

FX addressable loop

+

Pelco Finland Oy

D01616/GB0, 30/2008

7

CEA 4022 certified detectors used in the ASD1

The following detectors have been independently tested and certified for use in the ASD1 unit. The table shows the limits which should not be exceeded if installation is to conform to this requirement. All figures are based on the standard configurations. Pipe lengths are 50 m pipe with a fan speed of 9 unless otherwise stated.

Detector Brand Detector Model S65 Optical XP95 Optical Intellia Optical Intellia Optical 2251EM 3 2251EM 4 7251 Laser 5 7251 Laser 5 Configuration 1 (see below) Sampling Hole Limits 1 x 8 mm End Hole 1 x 8 mm End Hole 1 x 8 mm End Hole 2 x 5 mm Holes 1 x 8 mm End Hole 2 x 5 mm Holes 13 x 3 mm, 6 mm end 75 m Pipe11 x 3 mm, 6 mm end Configuration 2 (see below) Sampling Hole Limits n/a n/a n/a n/a n/a n/a 8 x 3 mm, 6 mm end n/a

Apollo

1 2

System Sensor

6

1) 2) 3) 4) 5) 6)

Using standard sensitivity alarm level of 55 Using pre-alarm sensitivity level of 45 Using standard sensitivity alarm level of 2200 Using high sensitivity alarm level of 1800 Using alarm level 3 Per branch

Standard configuration

Configuration 1

"Tee"

Max 1 m

Configuration 2

Configuration 1: ASD1 with single pipe. Configuration 2: ASD1 with Tee and 2 pipes. Distance from unit to Tee must be max. 1m and pipes should be balanced i.e. equal length and equal number of holes. Significant reductions in pipe length may allow the fan speed to be reduced and/or number of holes increased. Results of such changes must be verified with the PipeTracer software. Other detectors and pipe lengths up to 100 m may be used if CEA 4022 certification is not requirement. Designs should be verified with the PipeTracer software to ensure that the performance is suitable for the intended application.

Pelco Finland Oy D01616/GB0, 30/2008 8

CEA 4022 certified detectors used in the ASD2

The following detectors have been independently tested and certified for use in the ASD2 unit. The table shows the limits which should not be exceeded if installation is to conform to this requirement. All figures are based on the standard configurations with maximum 50 m pipe length per channel and fan speed of 9.

Detector Brand Detector Model S65 Optical XP95 Optical Intellia Optical Intellia Optical 2251EM 3 2251EM 4 7251 Laser 5 Sampling Hole Limits (per pipe) 1 x 8 mm End Hole 1 x 8 mm End Hole 1 x 8 mm End Hole 2 x 5 mm Holes 1 x 8 mm End Hole 2 x 5 mm Holes 8 x 3 mm + 6 mm End Hole

Apollo

1 2

System Sensor

1) 2) 3) 4) 5)

Using Using Using Using Using

standard sensitivity alarm level of 55 pre-alarm sensitivity level of 45 standard sensitivity alarm level of 2200 high sensitivity alarm level of 1800 alarm level 3

Significant reductions in pipe length may allow the fan speed to be reduced and/or number of holes increased. Results of such changes must be verified with the pipe simulation utility. Other detectors and pipe lengths up to 100 m may be used if CEA 4022 certification is not requirement. Designs should be verified with the pipe simulation utility to ensure performance is suitable for application. Standard configuration

ASD2 with 2 pipes: Pipes should be balanced i.e. equal size/number of holes.

Pelco Finland Oy

D01616/GB0, 30/2008

9

Fan speed

The following table shows typical settings for a variety of standard fan speed/hole quantity combinations. Other speed/hole combinations should be verified by testing during commissioning.

Typical flow sensitivity setting Pipe set up (all 50 m lengths unless otherwise stated) 13 x 3 mm Sampling Holes, 1 x 6 End Hole 8 x 3 mm Sampling Holes, 1 x 6 End Hole 4 x 3 mm Sampling Holes, 1 x 6 End Hole 1 x 5 mm Sampling Holes, 1 x 5 End Hole 1 x 8 mm End Hole 1x 8 mm End Hole (10 m Pipe)

Recommended fan speed 9 6-9 6-9 6-9 5-9 3-9

Flow sensitivity 9 9 7 5 2 1

Typical supply current/fan speed

Bargraph 0 1 2 3 4 5 6 7 8 Value Fan Speed 1 2 3 4 5 6 7 8 9 Current (mA) 110 120 130 150 170 190 220 235 265 Typical current consumption figures for different fan speeds. Results are based upon ASD2 installation with 10 m standard, 25 mm aspirating pipe per channel. The unit was powered from 24V supply. 9 10 300 a

Note!

The ASD1 and ASD2 system has been independently tested and certified to CEA 4022 and must be installed in strict compliance with the instructions if certification is to be maintained. The equipment must be installed, maintained and tested by qualified personnel in accordance with all local and national regulations.

Note!

Pelco Finland Oy

D01616/GB0, 30/2008

10

Information

D00004FI, 28/2007

10 pages