2000 psi minimum poured concrete wall. Southern Yellow Pine specific gravity = 0.55; allowable load per anchor = 364 lbs. Spruce Pine Fir specific gravity = 0.42; allowable load per anchor = 274 lbs. Anchor: 3/8" dia x 3-1/2" long Simpson Strong-Tie Wedge-All. Washer: 7/8" O.D. / 7/16" I.D. min; must conform to ANSI B18.22.1 type A. 3" minimum anchor edge distance required. 1-3/4" minimum embedment required. Maximum spacing shown in chart. Lesser spacing may be used to avoid interference with door component system. Spring pad connection not included. Maximum load per jamb = 0.5 x door width x max positive pressure x door height

8" 8"

keep each area clear of any back jamb attachment fasteners

header

3"

Maximum Fastener On-Center Spacing Door Width Southern Yellow Pine Spruce Pine Fir 24 24 24 24 24 23 20 18 17 24 24 24 24 24 21 18 16 15 24 24 22 18 15 13 18 15 14 13 24 24 24 22 Zone 5 / 25.9 Zone 6 / 30.0 Zone 7 / 34.4 Zone 8 / 37.1 Zone 9 / 40.9 18 16 14 13 11 11 11 10 24 23 19 16 14 12 10 9 8 24 24 24 24 24 24 24 24 22 24 24 24 24 24 24 24 22 20 24 24 24 24 21 Zone 1 / 12.8 Zone 2 / 15.9 Zone 3 / 19.2 9 Zone 5 / 26.9 Zone 6 / 31.2 Zone 7 / 35.7 Zone 8 / 38.7 Zone 9 / 42.6 Zone 1 / 12.8 Zone 2 / 15.9 Zone 3 / 19.2 10 Zone 4 / 22.9 Zone 5 / 26.9 Zone 6 / 31.2 Zone 7 / 35.7 Zone 8 / 38.7 Zone 9 / 42.6 Zone 1 / 12.4 Zone 2 / 15.3 Zone 3 / 18.5 16 Zone 5 / 25.9 Zone 6 / 30.0 Zone 7 / 34.4 Zone 8 / 37.1 Zone 9 / 40.9 Zone 1 / 12.4 Zone 2 / 15.3 Zone 3 / 18.5 18 Zone 4 / 22.0 Zone 4 / 22.0 Zone 4 / 22.9 Zone / Max Positive Pressure

attach header on max 24" bolt centers

Highest anchor installed at least as high as door opening.

Anchors to be evenly spaced between the header and the floor. Tabulted spacings apply to back jamb anchors only.

2x6 structural grade lumber. May be counterbored up to 3/4" deep at each anchor location to provide a flush mounting surface.

First anchor to start at no more than half the maximum on-center distance.

Alternative design may be approved by a registered professional engineer. Supporting structural elements shall be designed by a registered professional engineer for wind loads in addition to other loads. Calculation reference: DASMA TDS #161C, 2005 AF&PA NDS for Wood Construction and Simpson Strong-Tie data.

none

O V E R H E A D

D O O R S

06-22-2006

Back Jamb Attachment Detail Concrete Expansion Anchor C.H.I. Drawing: BJA-003-02

Information

Q:\Engineering\jamb attachment\expansion anchor_z9.dwg A_Size (1)

1 pages

Report File (DMCA)

Our content is added by our users. We aim to remove reported files within 1 working day. Please use this link to notify us:

Report this file as copyright or inappropriate

165976


Notice: fwrite(): send of 203 bytes failed with errno=104 Connection reset by peer in /home/readbag.com/web/sphinxapi.php on line 531