U ­ LED modules, converters and systems CONVERTER

Uconverter LCAI 80 W 700 mA I010 one4all 220-240 V uconverterIN-BUILTLCI

Product description ·Dimmablebuilt-incontrolgearforLED ·Constantcurrentcontrolgearwith700mAoutputcurrent ·Outputpower80W ·Nominallifetimeof50,000h(atta45°Cwithafailureratemax. 0.2%per1,000h) ·5-yearguarantee Properties ·Low-profilemetalcasingwithwhitecover ·TypeofprotectionIP20 Interfaces ·DALI(devicetype6) ·DSI ·switchDIM(withmemoryfunction) ·corridorFUNCTION Functions ·Overloadprotection ·Overtemperatureprotection ·Shortcircuitproof ·DimminginDCadjustable ·Suitableforemergencylightingunitsacc.toEN50172 Ordering data

Type LCAI 080/0700 I010 one4all 220-240 V

Packaging:25pieces/carton,700pieces/pallet

Article number 86459394

Data sheet 05/12-LC003-2 Subject to change without notice.

www.tridonic.com

1

U ­ LED modules, converters and systems CONVERTER

Technical data

Ratedsupplyvoltage ACVoltagerange DCVoltagerange Mainsfrequency Typ.ratedcurrent(at230V/50Hz/fullload)1 Mainscurrent(at220V/0Hz/fullload)2 Leakagecurrent(PE) Max.inputpower Typ.efficiency1 Typ.(at230V/50Hz/fullload)1 Typ.powerinputonstandby Switch-ontime(DCmode) 220­240V 198­264V 170­280V 0/50/60Hz 410mA 100mA 0.4mA 92W 92% 0.95 <1W 0.4s

Switch-ontime(at230V/50Hz/fullload/acc.to 0.6s theDALIstandard)1 Switchovertime(AC/DC) Turnofftime(at230V/50Hz/fullload) Holdtime3 PWMfrequency Dimmingrange Operatingtemperaturerangeta Max.casingtemperaturetc Weight DimensionsLxWxH HolespacingD 0.2s 0.1s 4ms 400Hz 3­100% -20...+45°C 75°C 0.22kg 280x30x21mm 270mm

Specific technical data

Type LCAI 080/0700 I010 one4all 220-240 V

1 2 3 4

Outputcurrent1 700mA

Outputcurrenttolerance1 ±5%

Outputvoltagerange 50­120V

Max.outputvoltage4 420V

Typ.outputpower 80W

Validat100%dimminglevel Validat15%dimminglevel Atpowerfailure

Inno-loadoperation

Data sheet 05/12-LC003-2 Subject to change without notice.

www.tridonic.com

2

U ­ LED modules, converters and systems CONVERTER

Standards EN55015 EN61000-3-2 EN61000-3-3 EN61347-1 EN61347-2-13 EN61547 EN62384 IEC62386-101 IEC62386-102 IEC62386-207(DALIDEVICEType6) AccordingtotheEN50172suitableforcentralbatterysystems AccordingtotheEN60598suitableforemergencylightinginstallations

Overload protection / underload protection IftheoutputvoltagerangeisexceededthecontrolgearturnsofftheLEDoutput andtriesarestartevery6seconds.Theoverloadprotectionisdeactivatedin emergencyoperation. Overtemperature protection Thecontrolgearisprotectedagainsttemporarythermaloverheating.Ifthe temperaturelimitisexceededtheoutputcurrentoftheLEDisreduced.The temperatureprotectionisactivatedbetween10°Cand14°Cabovetcmax(see page1).Thisfunctionisdeactivatedinemergencyoperation. Short-circuit behaviour Incaseofashortcircuitonthesecondaryside(LED)theLEDouputisswitchedoff. Every6secondsthecontrolgeartriestorestart. No-load operation Thecontrolgearisnotdamagedintheno-loadoperation.Every6secondsthe controlgeartriestorestart.Themax.outputvoltage(seepage1)canbeobtainedfor ashorttime(50ms)duringno-loadoperation.

Expected lifetime Type LCAI 080/0700 I010 one4all 220-240 V tc Lifetime

ta = 40 °C 70°C 75,000h

ta = 45 °C 75°C 50,000h

Storage conditions Humidity: 5%uptomax.85%, notcondensed (max.56days/yearat85%) Storagetemperature:-40°Cuptomax.+80°C Thedeviceshavetobewithinthespecifiedtemperaturerange(ta)beforethey canbeoperated.

Maximum loading of automatic circuit breakers Automaticcircuitbreakertype InstallationØ LCAI 080/0700 I010 one4all 220-240 V C10 1.5mm2 14 C13 1.5mm2 18 C16 2.5mm2 22 C20 4mm2 26 B10 1.5mm2 7 B13 1.5mm2 9 B16 2.5mm2 11 B20 4mm2 13 Inrushcurrent Imax 40A Duration 200s

Harmonic distortion in the mains supply (at 230 V / 50 Hz and full load) in % THD 3. LCAI 080/0700 I010 one4all 220-240 V 12 11

5. 3

7. 4

9. 4

11. 3

Data sheet 05/12-LC003-2 Subject to change without notice.

www.tridonic.com

3

U ­ LED modules, converters and systems CONVERTER

Dimming Dimmingrange3%to100% Digitalcontrolwith: ·DSIsignal:8bitManchesterCode Speed3%to100%in1.4s ·DALIsignal:16bitManchesterCode Speed3%to100%in0.1s Programmableparameter: Minimumdimminglevel Maximumdimminglevel Defaultminimum=3% Programmablerange3%MIN100% Defaultmaximum=100% Programmablerange100%MAX3% Dimmingcurveisadaptedtotheeyesensitiveness.

Dimming characteristics Digital dimming value 255 225 200 175 150 125 100 75 50 25 0 0 10 20 30 40 50 60 70 80 90 100 Relative lighting level % DALI DSI

Dimming characteristics as seen by the human eye

Control input (DA/D1, DA/D2) DigitalDALIsignalorswitchDIMcanbewiredonthesameterminals (DA/D1andDA/D2). Digital signal DALI/DSI Thecontrolinputisnon-polarandprotectedagainstaccidentalconnectionwith amainsvoltageupto264V.ThecontrolsignalisnotSELV.Controlcablehasto beinstalledinaccordancetotherequirementsoflowvoltageinstallations. Differentfunctionsdependingoneachmodule. switchDIM IntegratedswitchDIMfunctionallowsadirectconnectionofapushtomake switchfordimmingandswitching. Briefpush(<0.6s)switchesconverterONandOFF.Theconvertersswitch-ON atlightlevelsetatswitch-OFF. Whenthepushtomakeswitchisheld,LEDmodulesaredimmed.Afterrepush theLEDmodulesaredimmedintheoppositedirection. Ininstallationswithconverterswithdifferentdimminglevelsoroppositedimming directions(e.g.afterasystemextension),allconverterscanbesynchronizedto 50%dimminglevelbya10spush. Useofpushtomakeswitchwithindicatorlampisnotpermitted.

corridorFUNCTION ThecorridorFUNCTIONcanbeprogrammedintwodifferentways. ToprogramthecorridorFUNCTIONbymeansofsoftwareaDALI-USBinterfaceis neededincombinationwithaDALIPS.Thesoftwarecanbethe masterCONFIGURATOR. ToactivatethecorridorFUNCTIONwithoutusingsoftwareavoltageof230Vsimply hastobeappliedforfiveminutesattheswitchDIMconnection. TheunitwillthenswitchautomaticallytothecorridorFUNCTION. Note: IfthecorridorFUNCTIONiswronglyactivatedinaswitchDIMsystem(forexamplea switchisusedinsteadofpushbutton),thereistheoptionofinstallingapushbutton anddeactivatingthecorridorFUNCTIONmodebyfiveshortpushesofthebutton withinthreeseconds. switchDIMandcorridorFUNCTIONareverysimpletoolsforcontrollingballasts withconventionalmomentary-actionswitchesormotionsensors. Toensurecorrectoperationasinusoidalmainsvoltagewithafrequencyof50Hz or60Hzisrequiredatthecontrolinput. Specialattentionmustbepaidtoachievingclearzerocrossings.Seriousmains faultsmayimpairtheoperationofswitchDIMandcorridorFUNCTION. Light output level in DC operation Programmablefrom3%to100% ProgrammingbyextendedDSIorDALIsignal(16bit). Defaultvalueis15% InDCoperationdimmingmodecanbeactivated. Programming WithappropriatesoftwareandaUSBinterfacedifferentfunctionscanbeactivated andvariousparameterscanbeconfiguredintheuconverterLCAI070/300 I010one4all.AllthatisneededisaDALI-USBandthesoftware (masterCONFIGURATOR). masterCONFIGURATOR ForprogrammingthecorridorFUNCTION,deviceconfiguration(fadetime, ePowerOnLevel,etc.)DClevel,compatibilitysettings,andstartupdateandfor resetting.

Data sheet 05/12-LC003-2 Subject to change without notice.

www.tridonic.com

4

U ­ LED modules, converters and systems CONVERTER

Wiring guidelines ·Thesecondarycablesshouldberunseparately fromthemainsconnectionsandmainscablesto ensuregoodEMCconditions ·TheLEDwiringshouldbekeptasshortas possibletoensuregoodEMC.Therecommended secondarycablelengthismax.2m. ·Theconverterdoesnothavepolarityreversal protectiononthesecondaryside. LEDmodulesthatdonothavepolarityreversal protectionmaybedamagedifpolarityisreversed.

Wiring type and cross section Thewiringcanbeinflexiblecablewithferulesor solidfrom0.5­1.5mm².Forperfectfunctionof thepush-wireterminals(WAGO250)thestriplength shouldbe7.5­8.5mm.

wire preparation: 0.5 ­ 1.5 mm²

Release of the wiring Pressdownthe"pushbutton"andremove thecablefromfront.

7.5 ­ 8.5 mm

ControlgearisnotSELV(outputvoltageupto420V).

Circuit diagrams

1 3 4

+

* * control signal

6 7

DA DA

­

* * digital DSI/DALI signal or switchDIM/corridorFUNCTION

LED'shavetobeconnectedasshownabovetoworkproperly.ItispossibletoconnectadifferentnumberofLED'sontwocircuits(likeon toppicture).Theminimumpowerloadhastobeconnected.Otherwisetheconverterwillswitchoff.

Operation on DC voltage ThecontrolgearisdesignedforoperationwithDC voltageandpulsedDCvoltage.