Read R2.PDF text version

Siemens Series Rating Chart

Switchboards SB1, SB2, SB3 Panelboard S1

Max System Voltage Maximum SCCR 65kA

120/240 Vac 100kA

(See Notes on Page 2) Line Side Max Fuse Load side Fuse Current Rating Circuit Breaker Amps LPJ, LPN-RK 600 15-70 QPH, BQH, BLH JJN (300V) 1200 15-125 KRP-C 6000 15-100 15-70 QP, BQ, BL 15-125 15-100 HQP, HBQ, HBL, QPH, 15-100 BQH, BLH QPF, BQF, BLF, QE, BE, 200 BLE, QEH, BLEH, BLHF, 15-30 JJN QPHF, BQHF (300V) QEH, BLEH, QE, QPHF, 15-60 BLHF, BLE, QPF, BLF QT 600 QPH, BQH, BLH, HQP, HBQ, HBL ED4, HED4 ED4, ED6, HED4, HED6 FD6-A, FXD6-A JD6-A, JXD6-A, JXD2-A, SJD6-A LD6-A SLD6-A LXD6-A ED4, HED4 ED4, ED6, HED4, HED6 FD6-A, FXD6-A JD6-A, JXD6-A, JXD2-A, SJD6-A LD6-A SLD6-A LXD6-A ED4, HED4 ED4, ED6, HED4, HED6 15-50 15-70 15-125 15-100 15-100 15-125 70-250 200-400 200-600 300-600 450-600 15-100 15-125 70-250 200-400 200-600 300-600 450-600 15-100 15-125 70-250 200-400 200-600 300-600 450-600 500-800 500-1200 1200-1600 1600-2000 125-200 125-225 125-225 70-250 70-250 70-250 500-800 500-1200

Poles 1 (120V) 2 3 1 (120V) 2 3 3 1 (120V)

2 1 (120V),2 1 (120V) 2 3 1 (120V) 2,3 2,3 2,3 2,3 3 2,3 1 (120V) 2,3 2,3 2,3 2,3 3 2,3 1 (120V) 2,3 2,3 2,3 2,3 3 2,3 3 3 3 3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3

LPJ, LPN-RK

600

JJN (300V) 100kA

1200

240 Vac

KRP-C

6000

200kA

LPN-RK JJN (300V) LPJ LPJ, LPN-RK JJN (300V)

200 400 600 600 1200

KRP-C

6000

FD6-A, FXD6-A JD6-A, JXD6-A, JXD2-A, SJD6-A LD6-A SLD6-A LXD6-A SMD6 SND6 PD6, PXD6, SPD6 RD6, RXD6 QJH2, QJ2H, QJ2 QJ2 QJH2, QJ2H HFD6, HFXD6 HFD6, HFXD6 HFD6, HFXD6 MD6, MXD6, HMD6, HMXD6 ND6, NXD6, HND6, HNXD6

© 2000 Cooper Bussmann, Inc.

Page1 of 2

10/3/00

Siemens Series Rating Chart

Switchboards SB1, SB2, SB3 Panelboards S2, SE, S3, S4, S5

Max System Voltage Maximum SCCR 50kA Line Side Fuse LPJ LPJ JJS, LPJ LPJ, LPS-RK JJS, LPJ, LPS-RK 480 Vac 100kA JJS, KRP-C 1200 JJS Max Fuse Current Rating 400 400 600 600 600 800 (See Notes Below) Load side Circuit Breaker Amps 60-100 ED4 15-100 ED4 15-50 FD6-A, FXD6-A 70-250 HFD6, HFXD6 70-250 JD6-A, JXD6-A, HJD6-A, 200-400 HJXD6-A LD6-A, HLD6-A 200-600 LXD6-A, HLXD6-A 450-600 HFD6, HFXD6 70-250 JD6-A, JXD6-A, HJD6-A, 200-400 HJXD6-A LD6-A, HLD6-A 200-600 LXD6-A, HLXD6-A 450-600 HFD6, HFXD6 70-250 MD6, MXD6, HMD6, 500-800 HMXD6 ND6, NXD6, HND6, 500-1200 HNXD6 BQD, CQD 15-100 BQD*, CQD * 20-30 BQD, CQD 15-100 BQD*, CQD * 20-30

Poles 1 (277V) 2,3 1 (277V) 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 1 (277V) 2,3 1 (277V) 2,3

KRP-C

6000

LPS-RK 480/277V 200kA JJS, LPJ

100 200

* BQD and CQD breakers are series rated from 15-100A for Series 7A, S2 and S3 panelboard applications only. NOTE (1): The data in these charts was compiled from information in Siemens SpeedFax 2000 Electrical Products publication, catalog reference number GNPC-01000. Cooper Bussmann assumes no responsibility for the accuracy or reliability of the information. The information contained in the tables may change without notice due to equipment design modifications. NOTE (2): The line-side fused switch may be in a separate enclosure or in the same enclosure as the loadside circuit breaker. A line-side fused switch may be integral or remote. NOTE (3): Max fuse current rating denotes the largest amperage fuse that may be used for that series rated combination. A lower amperage fuse may be substituted for the listed fuse.