<<Contents>> <<Index>>

General Specifications

GS 04M01J01-11E

Data Collector DC100 Main unit --stand-alone type (style number: S10) --expandable type (style number: S10) Sub units --DS400/DS600 (style number: S10)

Refer to the following cautionary notes before you configure your system.

DARWIN is a system comprising a number of dataacquisition equipment components. In the course of system growth, new models, software, various input/output modules and optional features are added to the family to enhance the systems expandability and flexibility.You can check the versions of your equipment and software by referring to the style number:Sn* shown on the nameplate of the main unit. When configuring a system, you must confirm that the style number of each component unit and software meets the following requirements: * release number in the case of software:Rn (1) The style number of each input/output module must be the same as or lower than that of the main unit or sub-unit to which the module is connected. (2) The release number of a dedicated software package must be the same as or higher than the style number of the main unit or sub-unit where the package is installed and where it performs control. Any equipment/software not meeting these requirements is incompatible with your system configuration. For information on how to upgrade to compatible equipment/software, consult our sales personnel.

expandable type

stand-alone type

DC100 Data Collector Model Features DC100 stand-alone type Integrated type capable of measuring data from up to 40 channels. Can be carried about easily and is suitable for small scale data logging. The number of channels can be increased from 10 to 40 channels in a module steps, and also the kinds of inputs can be changed. Universal, DC V/TC/DI, mA, power monitor, strain, Pulse, DI Input modules, communication module, DI/DO module, alarm output modules, retransmission modules DC100 expandable type Can be expanded up to 300 channels. You can perform multi-channel measurement with the minimum of wiring by connecting sub units to the main unit with dedicated cable. The measurement data can easily be analyzed with DARWIN DAQ32 software. The number of channels can be increased from 10 to 300 channels in a module steps, and also the kinds of inputs can be changed. Universal, DC V/TC/DI, mA, power monitor, strain, Pulse, DI (Input modules and retransmission modules are connected to the sub units.) Communications module, DI/DO module, alarm output modules Up to 6 units, 500 m max (Full extension) Input modules, DI/DO module, alarm output module, retransmission modules All channels/0.5 sec

Increasing number of input channels, changing kinds of inputs Kinds of inputs Input and output modules that can be connected to the main unit Connection of sub units, and remote measurement distance Input and output modules that can be connected to the sub units Max scanning speed

Not applicable

Not applicable

All channels/0.5 sec

GS 04M01J01-11E © Copyright November 1997 (YK) 6th Edition: December 2000 (YK)

<<Contents>> <<Index>>

Outline of the stand-alone type

The DC100 Data Collector (stand-alone model) measures input signals from 10 channels to 40 channels and stores the measured data in internal memory. Since it is very portable, it can also be carried around for data logging.

Main features

(1) Compact: Occupies only 1/3 of the volume of other Yokogawa units. (Comparison between a system consisting of the DC100 main unit + one sub unit and a system consisting of one DA2500E + one remote scanner) (2) High speed: Can measure data from 300 channels at 0.5 second intervals maximum. (3) A wide range of inputs: Universal (DC voltage, thermocouple, RTD, contact), DC voltage, thermocouple, contact dedicated inputs, mA, power monitor, strain, pulse, DI input. (4) Remote measurement: The sub unit is designed to be connected to the main unit with dedicated cable, enabling it to be located up to 500 m away from the main unit.

DC100 stand-alone type main unit

Outline of functions Main features

(1) Compact: Occupies only 1/3 of the space of Yokogawa's remote scanner for the DA2500E. (2) High speed: Can measure data from 40 channels in 0.5 second maximum. (3) A wide range of inputs: Universal (DC voltage, thermocouple, RTD, contact), DC voltage, thermocouple, contact dedicated inputs, mA, power monitor, strain, pulse, DI input. (1) Setting and control of the input/output modules on those subunits connected by dedicated cables. (2) Control of the alarm output modules on the DC100 main unit. (3) Transfer of the measured input module data into the DC100 main unit memory via subunits. (4) Stores the results of input module measurements in the main unit's memory or transfers these results to a personal computer via a GPIB, RS-232-C or RS-422-A/RS-485, and Ethernet communication interfaces.

Outline of sub units

The DS400/DS600 sub unit functions as an interface between the expandable version of the DC100 data acquisition and the various input/ output modules to which it is connected. A maximum of four input and output modules of various kinds (4 slots) can be connected to the DS400, and a maximum of six input and output modules (6 slots) can be connected to the DS600. A maximum of six sub units can be connected to one main unit. Both DS400 and DS600 sub units can be connected to the same main unit. The main unit can be connected to the sub units, or the sub units to each other, with dedicated cable, enabling them to be separated by up to 500 m. The sub units have excellent environmental toughness and can be installed very easily, enabling them to be installed over a wide area without environmental restrictions.

Outline of functions

(1) Setting and control of connected input/output modules (2) Stores the results of input module measurements in the main unit's memory or transfers these results to a personal computer via a GPIB, RS-232-C or RS-422-A/RS-485, and Ethernet communication interfaces.

Outline of expandable type

The DC100 Data Collector (expandable model) can accommodate a data acquisition and recording environment for up to 300 channels by connecting the main unit to DS400 (for 4 slots) and/or DS600 (for 6 slots) subunits, each of which have their own input modules. It can also transfer the data to a personal computer simultaneously saving measured data in internal memory.

Outline of functions

(1) Setting and control of the connected input/output modules (by means of commands from the DC100 main unit.) (2) Measured values output to the DC100 main unit .

DC100 expandable type main unit + sub unit

CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10

b -/B +/A CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10

b -/B +/A CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10

b -/B +/A

2

GS 04M01J01-11E

<<Contents>> <<Index>>

I Configuration

Component units

Available module groups

The DC100 data collector can be freely configured for different functions by selecting modules from the following module groups and connecting them to the main or sub units. Input modules: Universal (DC voltage, thermocouple, RTD, contact), DC voltage, thermocouple, contact dedicated input modules, mA, power monitor, strain, pulse, DI input. Alarm modules: 4 point out put (transfer contact) or 10 point out put (make contact) (The number of alarm channels can be increased in module units.) Communications modules: Select one type from GP-IB, RS-232-C, RS-422-A/RS-485, Ethernet. DI/DO modules: Alarm 2-point output (transfer contact) and fail output modules and remote control signal input. Retransmission modules: Re-output of measured values and computed results. NOTE Refer to "Standard connection modules" in GS 04M01E01-11E, or GS 04M01E01-50E for detailed specifications of the above modules.

DC100 main unit stand-alone type

Package Software

DC100 main unit expandable type · DARWIN DAQ 32 (Standard Package) · DARWIN DAQ 32 Plus (Optional Package) General DAQ 32 and DAQ 32 Plus are software packages developed by YOKOGAWA specially for the DARWIN series. These packages run on a personal computer, achieving highly dependable data acquisition using DARWIN series units (DA100, DC100, DR130, DR230, and DR240) and superb operability. The main differences between the two packages are in the monitoring functions. The DAQ 32 only offers two display formats - waveform trend and digital; has 2 groups of 10 channels/window; and does not support alarm display. If simultaneous multi point monitoring or more flexible display forms of data such as level meter, analog meter, and thermometer faceplates, and alarm indications are required, use the optional DAQ 32 Plus. System Requirements Personal Computer: A personal computer running either a Microsoft Windows 95, Windows 98, Windows NT 4.0, or Windows 2000 operating system. · For DAQ 32 (model code DP120-13), a pentium MMX 133 MHz or higher is required (pentium-II recommended) for the processor. · For DAQ 32 Plus (model code DP320-13), a pentium MMX 166 MHz or higher is required (pentium-II recommended) for the processor. RAM: At least 32 megabytes (MB) (64 MB or larger recommended) Hard Disk: 100 MB of free hard disk space is required for installation. The program size is 10 MB. NOTE Refer to GS 04M01F02-11E or GS 04M01W01-11E for detailed specifications of the above software package.

b CH1

-/B -/A b

-/B -/A

CH2

CH1 b -/B -/A

CH3

CH2

CH1 b -/B -/A

CH4

CH3

CH2

CH1

CH5

CH4

CH3

CH2

CH6

CH5

STATUS

CH4 CH3

CH7

CH6

CH5

CH4

CH8

CH7

CH6

CH5

SUB

CH6

CH9

CH8

UNIT

CH7

CH10

CH9

CH8

CH7

CH10

CH9

CH8

CH10

CH9

POWER

CH10

100-240V AC 50/6 0Hz

70VA

MAX

DS400 sub unit

b CH1

-/B -/A b CH1 b CH2 CH1 b CH3 CH2 CH1 b CH4 CH3 CH2 CH1 -/B -/A -/B -/A -/B -/A -/B -/A

CH2

CH3

CH4

CH5

CH6

CH5

CH4

CH3

CH2

CH7

CH6

CH5

STATUS

CH4 CH3

CH8

CH7

CH6

CH5

CH4

CH9

CH8

CH7

CH6

CH5

SUB

CH6

CH10

CH9

CH8

UNIT

CH7

CH10

CH9

CH8

CH7

CH10

CH9

CH8

CH10

CH9

POWER

CH10

100-240V AC 50/6 0Hz

70VA

MAX

DS600 sub unit

Unit configuration

DC100 stand-alone type: Stand-alone type main unit + various input/output modules + communication interface modules DC100 expandable type: Expandable type main unit + sub units (DS400 or DS600) + various input/output modules + communication interface

GS 04M01J01-11E

3

<<Contents>> <<Index>>

Alarm output module

DI/DO module

1-5 V module

4-20 mA module

Universal DC V/TC/DI module

DI module

Pulse module

Power module

No alarm module or DI/DO module can beconnected to theright side of this input module.

4

DC100 stand-alone type system configuration

Install

Personal computer Set-up and control software

package software DARWIN DAQ 32 DARWIN DAQ 32 Plus InTouch for DARWIN 2000 DAQLOGGER Communication interface cable

DC100 main unit

Module

I/O module

Retransmission module

Input module

Communication interface module

Strain module

mA(current) module

GP-IB module

RS-232-C module

RS-422-A/485 module

Ethernet module

Input

GS 04M01J01-11E

~

DC V TC RTD Contact Status AC

A

current PULSE STRAIN

<<Contents>> <<Index>>

Alarm output module

No alarm module or DI/DO module can beconnected to theright side of this input module.

GS 04M01J01-11E

DC100 expandable type system configuration

Install

Personal computer

Set-up and control software

package software DARWIN DAQ 32 DARWIN DAQ 32 Plus InTouch for DARWIN 2000 DAQLOGGER Communication interface cable

DC100 main unit Sub unit

Sub unit

Dedicated cable (up to 500m)

Module

I/O module

Retransmission module

Remote measurement

Input module

Communication interface module

DI/DO module

1-5 V module

4-20 mA module

Extension module

Universal DC V/TC/DI module

DI module

Power module

mA(current) module

Pulse input module

Strain module

GP-IB module

RS-232-C module

RS-422-A/485 module

Ethernet module

Input

~

DCV TC RTD Contact Status AC

A

current PULSE STRAIN

5

<<Contents>> <<Index>>

I Connecting modules

Connecting modules to the stand-alone type Modules that can be connected

Input modules: Universal (DC voltage, thermocouple, RTD, contact), DC voltage, thermocouple, contact dedicated input modules, mA, pulse, DI. Alarm modules: 4 channels (transfer contact) or 10 channels (make contact) (The number of alarm channels can be increased in module units.) Communications modules: Select one type from GP-IB, RS-232-C, RS-422-A/RS-485, Ethernet. DI/DO modules: Alarm 2-point output (transfer contact) and fail output modules and remote control signal input Retransmission modules: Re-output of measured values and computed results

Definition of number of connections for the expandable type

DC100 main unit: · The number of input modules and retransmission modules is 0. · Number of alarm modules + DI/DO module + communications module 4 Sub unit DS400: · The maximum number of modules per slot that can be connected is 4. · Number of input modules + DI/DO module + alarm modules + retransmission modules 4 Sub unit DS600: · The maximum number of modules per slot that can be connected is 6. · Number of input modules + DI/DO module + alarm modules + retransmission modules 6 Common to all: · One DI/DO module can be connected to one expandable type system · The alarm output module and DI/DO module must be connected on the left side of the input modules. · One extension module can be connected to one sub unit. · The standard operating temperature and humidity are different for each module type. Therefore, always make sure to verify this when connecting the module. · Up to 30 retransmission modules per system can be connected.

Definition of number of connections

· A maximum of 4 modules can be connected to the main unit. · The number of DI/DO modules must be no greater than one. · The alarm output module and DI/DO module must be connected on the left side of the input modules. · Number of input modules 4 · Number of input modules + alarm modules + DI/DO module + retransmission modules + communications module 4 · The standard operating temperature and humidity are different for each module type. Therefore,always make sure to verify this when connecting the module.

Method of connecting modules

The standared operating temperature and humidity are different for each module type. Therefore, always make sure to verify these when connecting the module. Stand-alone type: Connect directly to the main unit. The alarm output modlues and DI/DO module must be connected on the left side of the input modules. Expandable type: Connect the input modules, retransmission modules, or extension module directly to the sub unit. (You cannot connect these modules directly to the main unit.) Connect the alarm modules, communications module and DI/DO module directly to the main unit. The alarm output modlues and DI/DO module must be connected on the left side of the input modules.

Connecting modules to the expandable type Modules that can be connected

Main unit Alarm modules: 4-point output (transfer contact) or 10-point output (make contact) (The number of alarm channels can be increased in module units.) Communications modules: Select one type from GP-IB, RS-232-C, RS-422-A/RS-485, Ethernet. DI/DO modules: Alarm 2-point output (transfer contact) and fail output and remote control signal input. Sub unit DS400/DS600 Input modules: Universal (DC voltage, thermocouple, RTD, contact), DC voltage, thermocouple, contact dedicated input modules, mA, pulse, DI. Alarm modules: 4-point output (transfer contact) or 10-point output (make contact) (The number of alarm channels can be increased in module units.) DI/DO modules: Alarm 2-point output (transfer contact) and fail output modules and remote control signal input Retransmission modules: Re-output of measured values and computed results Extension module: For remote measurment

Connecting sub units

Kinds of sub units (type name): DS400 sub unit: For 4 slots DS600 sub unit: For 6 slots Number of sub units to be connected: Stand-alone type:Cannot be connected. Expandable type: A maximum of six sub units can be connected. (This also applies when 4-slot sub units and 6-slot sub units are connected to the same main unit.) Method of connecting sub units: A sub unit can be connected to either the main unit or another sub unit with dedicated cable. The maximum total extension length is 500 m.

6

GS 04M01J01-11E

<<Contents>> <<Index>>

I Standard specifications

General specifications

Construction

Installation method: Floor mounting: Use the stand at the bottom of each unit. Direct panel mounting: Screw the unit directly to the panel at the specified points.Mount the DC100 using the rack-mounting brackets after removing the knobs. Rack mounting: Use the dedicated mounting brackets. Regardless of which mounting method you use, be sure to install the units in an upright position.) Materials: Steel plate, aluminum castings, plastic moldings Paint color: Base unit: Lamp black (equivalent to Munsell 0.8Y2.5/0.4) Slate gray light (equivalent to Munsell 0.1PB4.6/ 0.2) Modules: Slate gray light (equivalent to Munsell 0.1PB4.6/ 0.2) External dimensions: Stand-alone type main unit: Approx. 338 (W) × 236 (H) × 157 (D) mm Expandable type main unit: Approx. 338 (W) × 236 (H) × 157 (D) mm DS400 sub unit: Approx. 336 (W) × 165 (H) × 100 (D) mm DS600 sub unit: Approx. 422 (W) × 176 (H) × 100 (D) mm Weight: Stand-alone type main unit: Approx. 5.3 kg (with 2 input modules, 1 alarm output module, and 1 communications module installed) Approx. 3.5 kg* Expandable type main unit: Approx. 5.3 kg (with 4 input/output modules installed) Approx. 3.5 kg* DS400 sub unit: Approx. 2.5 kg (with 4 input/output modules installed) Approx. 0.9 kg* DS600 sub unit: Approx. 3.5 kg (with 6 input/output modules installed) Approx. 1.1 kg* *: is the weight of each unit without modules installed.

A/D integration period (dependent on the module): Selectable from 20 ms (50 Hz), 16.7 ms (60 Hz), 100 ms (10 Hz), and auto switching (unavailable for a DC power supply model).

Alarm

Number of settings: Up to four settings can be made for each channel. Kinds of alarms: Selection from higher limit, lower limit, difference higher limit, difference lower limit, higher limit of rate of change, lower limit of rate of change. Rate of change alarm time interval: Can be set to measurement interval × 1 to 15 (common to both rising and falling limits) Output mode: Excitation/non-excitation selection, AND/OR mode selection, and output hold/non-hold specification can be made. (common to all channels) Six reflash alarm output contacts can be specified. Number of alarm output points: Stand-alone type: 2 points (DI/DO module) to 30 points max Expandable type: Up to 30 points can be connected to the DC100 main unit (the number of alarm points can be increased in module units). By connecting sub units, (the number of alarm points can be increased in module units). Number of alarm output modules that can be connected: Stand-alone type: The number of alarm points can be increased in module units. Expandable type: Up to 4 modules can be connected to the DC100 main unit, up to 6 modules can be connected to the DS600 sub unit. The number can be increased by adding sub units. Memory Function Section Buffer memory: SRAM buffer memory (lithium battery backup for approx. 8 years) Measured values are saved in internal memory and then transferred to a floppy disk. Number of Floppy Disk Drive: 3.5-inch floppy disk drive × 1 Floppy Disk Recording Density: 2HD or 2DD Floppy Disk Capacity: 1.2 MB, 1.44 MB or 720 kB Memory Capacity: Selected from 1 MB (standard), 2 MB or 4 MB at time of order Data save: Setting values, measured values and computed values Data save Format: Binary for measured and computed values ASCII for setting values Data Acquisition Method: Division (division into 2, 4, 8, or 16) or Data length Data Acquisition Operations: Single, repeat, or rotary Data Acquisition Triggers: Free or trigger mode (utilizes the event/action function)

Input

Measurement range: NOTE Refer to "Standard modules for the DC100 data collector" in GS 04M01E01-11E for detailed specifications of the measurement range. Measurement interval: Selectable from 0.5, 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, and 60 sec Stand-alone type: Max 40 channels/500 ms (when the software provided is used) Expandable type: Max 300 channels/500 ms (when the software provided is used) The measurement interval depends on the minimum measurement interval (when modules with different minimum intervals are installed together, the measurement interval is determined by whichever module has the maximum interval).

GS 04M01J01-11E

7

<<Contents>> <<Index>>

Sample Rate:

0.5 s, 1 s, 2 s, 3 s, 4 s, 5 s, 6 s, 10 s, 12 s, 15 s, 20 s, 30 s, 1 min., 2 min., 3 min., 4 min., 5 min., 10 min., 30 min., or 60 min. LOGIC (event/action function) Recording Data Length in the Data Length Data Acquisition Method (unit: data item/channel): 10, 20, 30, 40, 50, 100, 200, 300, 400, 500, 1 k, 2 k, 3 k, 4 k, 5 k, 10 k, 20 k, 30 k, 40 k, 50 k, 100 k

DC power supply section

Rated supply voltage: 12 to 28 VDC Usable supply voltage range: 10 to 32 VDC Power consumption: max. approx 30 VA (DC100) max. approx 25 VA (DS400, DS600) Terminal: Dedicated connector Others: DC power supply only. However, when purchasing the DC100 DC power operation model, attached the dedicated AC adapter as standard accessory.

Standard computation functions

Computation functions: Difference between arbitrary channels, linear scaling, moving average, pulse integration (when pulse module is installed) Scaling: Ranges for which scaling can be done: DC voltage, thermocouple, RTD, contact, strain, mA. Scaling range: ­30000 to +30000 Decimal point: Can be set freely. Measurement accuracy for scaling: Measurement accuracy for scaling (digits) = Measurement accuracy (digits) × Scaling span (digits)/Measurement span (digits) + 2 digits (Numbers below the decimal point are discarded.) Moving average: The moving average results for between 2 to 64 (2n: n is nonnegative integer) scans are computed.

AC adapter for DC power model

Rated supply voltage: 100 to 240 VAC (free supply voltage selection) Usable supply voltage: 90 to 250 VAC Rated supply frequency: 50/60 Hz Power consumption: max. approx 90 VA

Others

Clock: With calendar function (Western calendar), Clock accuracy is ±100 ppm System alarm: Contact output (when DI/DO module is connected) Set value backup: Lithium battery backup (approx. 8 years), excluding clock function Insulation resistance: At least 20 M between each terminal and ground (measured with 500 VDC) Withstand voltage: Between AC power supply terminal and case of DC100 main unit: 1500 VAC (50/60 Hz) for one minute Between DC power supply terminal and case of DC100 main unit: 1000 VAC (50/60 Hz) for one minute Between input terminal and case of DA100 main unit:1500 VAC (50/60 Hz) for one minute Between output terminal and case of DA100 main unit:2300 VAC (50/60 Hz) for one minute

Communications functions

Communication modules: GP-IB, RS-232-C, RS-422-A/RS-485, Ethernet communications interface modules.

Output functions

DI/DO module: Internal alarm 2 points, fail, and file end output function Retransmission modules: Re-output of measured values and computed results

AC power supply section

Rated supply voltage: 100 to 240 VAC (free supply voltage selection) Usable supply voltage range: 90 to 250 VAC Rated supply frequency: 50/60 Hz Power consumption:

Stand-alone type main unit (when 4 connectable modules are installed) max approx. 90 VA Expandable type main unit (when 4 connectable modules are installed) max approx. 90 VA DS400 sub unit (when 4 connectable input/output modules are installed) max approx. 55VA DS600 sub unit (When 6 connectable input/output modules are installed) max approx. 70 VA

8

GS 04M01J01-11E

<<Contents>> <<Index>>

Normal operation conditions

Supply voltage: 90 to 250 VAC, 10 to 32 VDC Supply frequency: 50 Hz ± 2%, 60 Hz ± 2% Ambient temperature: Stand-alone type main unit expandable type main unit When floor, Panal, Rack, mounted and Desk top: 5 to 40°C DS400/DS600 sub unit When floor-mounted and Desk top: 0 to 50°C When panel-mounted: ­0 to 60°C When Rack-mounted: 0 to 50°C When DC operation: 0 to 50°C Ambient humidity:

Temperature ­10 to 40°C 40 to 50°C 50 to 60°C * no ice formation Vibration: Shock: Magnetic field: Position: Humidity 20 to 80% RH 10 to 50% RH 5 to 30% RH

10 to 60 Hz 0.2 m/s2 Not allowed 400 A/m max (50/60 Hz) Mount the unit left-right horizontally or vertically, as a general rule. Warm-up time: At least 30 minutes after power switch-on

Signal source resistance: Variation with respect to signal source resistance + 1 k change (1) Voltage 2 V range or below ... Within ±10 µV 6 V range or above ... Within ±0.1% of rdg (2) Thermocouple Within ±10 µV; However, it must be within ±100 µ when burnout is specified. (3) RTD Variation with respect to change of 10 per wire (when all three wires are the same resistance value) Indication ... Within ±(0.1% of rdg + 1 digit) Variation in indication with respect to a difference of 40 m in the resistance between conductors (max difference between 3 wires) ... Approx. 0.1°C Mounting position: Variation when the unit is mounted horizontally on a panel ... Within ±(0.1% of rdg + 1 digit) Vibration: Variation when sinusoidal vibration of acceleration 0.2 m/s2 is applied for 2 hours in each of the 3 axial directions over a frequency range of 10 to 60 Hz ... Within ±(0.1% of rdg + 1 digit)

Transportation and storage conditions

These refer to the environmental conditions existing during transportation and storage from the time of shipment from the factory until commencement of use, and also during transportation and storage in the case of a temporary period of non-use. If the environmental conditions are maintained within the specified range, the unit will not incur permanent damage, and can be returned to a normal working condition (re-adjustment may be required in some cases). Ambient temperature: ­20 to 60°C Humidity: 5 to 95% RH Vibration: 10 to 60 Hz 4.9 m/s2 max Shock: 392 m/s2 max (in packed condition)

Standard performance

Reference operation state: 23 ± 2°C, 55 ± 10% RH, supply voltage: 90 to 250 VAC, supply frequency: 50/60 Hz ± 1%, Warmup: At least 30 minutes; When operating, the system must not adversely affect the operation of other measuring instruments by generating vibration, for example. enerating vibration, for example. NOTE Refer to "Standard connection modules for the DC100 data collector" in GS 04M01E01-11E for detailed specifications of the measurement accuracy.

Effect of Operation Conditions

Ambient temperature: Variation for a temperature change of 10°C within ±(0.1% of rdg + 1 digit) ±(0.2% of span + 1 digit) for Cu 10 Voltage variation: Within ±1 digit over the range of 90 to 132, or 180 to 250 VAC (frequency 50/60 Hz) External magnetic field: Variation with respect to AC (50/60 Hz) and DC magnetic fields of 400 A/m ... Within ±(0.1% of rdg + 10 digits) Radio wave: Within ±(1% of span) at 1m from 150 MHz or 460 MHz field

GS 04M01J01-11E

9

<<Contents>> <<Index>>

/M1: MATH Function

Computation types

Types: Four arithmetical operations, SQR (square root), ABS (absolute value), LOG (common logarithm), LN (natural logarithm), EXP (exponent), statistical computation*, logical computation (AND, OR, NOT, and XOR), relational computation, exponentiation, previously-measured value reference, hold**, and reset *Statistical computation CLOG: Computation process of simultaneously measured values within a group (total, maximum, minimum, average, and maximum minimum) TLOG: Computation process of a specific channel over time axis (total, maximum, minimum, average, and maximum - minimum) Statistical computation interval: Set by the event/action function (effective when /M1 option is selected) **Hold Temporary suspending of computation and temporary hold of the computed result During statistical computation, resume the computation from the hold point after the hold is released. (effective when /M1 option is selected) Number of channels for computing (Number of channels that can be allocated for computational purposes.): Stand-alone type: 30ch maximum Expandable type: 60ch maximum Computation interval: Every measurement interval (except when the computation becomes too difficult to be processed every measured interval, in which case an alarm is generated) Significant digits during computation: ±1038 Significant digits of the computed result: ­9999999 to +99999999 (The decimal point can be set to none or have 1 to 4 digits on the right of the decimal point) Computation start/stop: Can be controlled by personal computer, time specified, remote control signal (DI/DO module), and alarm status Temporary hold of the computed result: Can be controlled by remote control signal (DI/DO module), and alarm status Other functions included in the math function: Remote RJC Input type: Thermocouple (TC) Accuracy: (Twice the measurement accuracy of the standard thermocouple input) + (temperature difference between the terminal of the remote terminal section and thermocouple section for measuring the remote terminal temperature) Thermocouple burnout: not selectable

/C5: External Mass Storage Interface Function

(SCSI*1)

By installing the external mass storage interface (SCSI) option to the DC100, you can connect MO/Zip/Jaz/PD disk drives. MO/Zip/Jaz/PD disk drive connected to the DC100 on powerup is automatically detected and can be used as external medium. The external mass storage interface (SCSI) option is a communication interface for saving files created in the DC100 internal RAM (such as measurement data files, report files, and periodic files) onto the MO/Zip/Jaz/PD disk. It is also used for loading files from the disks. In addition, MO/Zip/Jaz/PD disks allow transferring of files between the DC100 and the PC without physically connecting the two using communication cables. *1: SCSI (Small Computer System Interface) It is an interface standard for connecting the computer to peripheral devices such as hard disks and scanners. It is a communication standard (ANSI X3.131-1986) adopted by ANSI (American National Standards Institute) in July 1986. The external mass storage interface (SCSI) option for the DC100 can connect only to MO/Zip/Jaz/PD disk drives meeting the following specifications. Supported models Data Collector DC100 (DC100-1, DC100-2 with /C5 option) Connection with MO/ZIP disk drive · Automatically detect MO/Zip/Jaz/PD disk drive connected on power up. · Manual detection after power up also possible. SCSI controller WD33C93A made by Western Digital SCSI path SCSI (conforms to ANSI X3.131-1986) Terminating resistance Built-in passive terminator (Terminator ON fixed) Connector on the DC100 D-sub half-pitch connector 50-pins female Connector pin assignment Unbalanced transfer type (Single-ended path) SCSI cable Cable that is 3 m or less between the DC100 and the SCSI device. Media MO/Zip/Jaz/PD Maximum connections Up to 7 devices excluding the DC100 DC100 ID number Fixed to 7 ID numbers for MO/Zip/Jaz/PD disk drives Any ID number NOTE If connecting multiple devices, each device must be assigned with a unique ID number.

/D2: F degree Display /L1: Summer/Winter Time Display

10

GS 04M01J01-11E

<<Contents>> <<Index>>

Contmction between SCSI devices · Follow the manuals that come with the MO/Zip/Jaz/PD drives in connecting the devices. · DC100 can access each of the multiple SCSI devices by specifying the ID number. · Attach a terminator to the device on the end of the SCSI chain. Certain devices have built-in terminators that can be turned on with a switch. · SCAM*2 is not supported. *2: SCAM (SCSI Configured AutoMatically) is a standard created by Adaptec and Microsoft to automatically assign unique SCSI IDs. Not all SCSI devices support this standard. Magneto Optical Disk standard · 128 MB, 230 MB, 540 MB, 640 MB magneto optical disks are standardized*3 media. Media from different manufactures are compatible as long as they conform to the standard. · See the instruction manual for the MO drive to see what types of media are supported.

Data processing with the personal computer · Data file can be displayed, analyzed, or converted (Excel/Lotus/ ASCII) with the DAQ 32 software that is provided with the DC100. · Advanced data analysis on multiple channels can be performed simultaneously with the DAQ 32 Plus software. NOTE For information on the software specification, see "DARWIN Software Package Specification (GS 04M01F02-11E)."

Storage Space of Media (Bytes) Compatible Standard

128 M

230 M

540 M

640 M

ISO10090 ECMA-201 ISO15041 ISO15041 ZCAV 512 1.39 ZCAV 512 1.1 ZCAV 2048 1.1

Rotation Control Method CAV Bytes per sector Track Pitch (µ)

512 1.6

*3: Other Magneto Optical disk formats are HS standard (Medium is 90 mm in diameter and holds 650 MB) which uses magnetic modulation method and PD format (Medium is 120 mm in diameter and holds 650 MB) which is a phase change type. Devices that have tested Product Name MO drive Zip drive Jaz drive PD drive Model

SCSI-2 Compatible model iomega Zip 100, Zip 250 iomega Jaz 1GB Panasonic PD/CD-ROM

Manufacturer

Fujitsu Iomega Co.,Ltd. Iomega Co.,Ltd. Panasonic

NOTE Some of the MO/Zip/Jaz/PD disk drives need terminators. Follow the instruction manual for the particular disk drive. Features of the media (MO/Zip/Jaz/PD disk) · The DC100 recognizes up to 272 files for each MO/Zip/Jaz/PD disk. · Set-up data files can be directly written to the MO/Zip/Jaz/PD disk through the SCSI. · Measurement data file, report computation files, and periodic files are stored once in the DC100 internal RAM, then copied to the MO/Zip/Jaz/PD disk through the SCSI. Cannot copy between SCSI devices. · Deleting data files. · Formatting the MO/Zip/Jaz/PD disk. Directory structure of the external SCSI media · All data are saved/loaded to subdirectory "DIR 0 ." · Subdirectory "DIR 0" is automatically created if it does not exist on the external medium. · No limit on the number of files on the external medium.

GS 04M01J01-11E

11

<<Contents>> <<Index>>

Type name and specification code Data collector DC100

Model DC100 Type Software Memory -1 -2 2 -1 -2 -3 1 -1 -2* D F R S W Optional Features /M1 /M3 /C5 /D2 /L1 /FC Suffix Code Optional Code Data collector Stand-alone type Expandable type main unit DARWIN DAQ 32 (English, French, German) Internal memory 1 Mbyte (standard specification) Internal memory 2 Mbyte Internal memory 4 Mbyte Floppy disk drive 100 VAC to 240 VAC 12 VDC to 28 VDC 3-pin power inlet w/UL, CSA cable 3-pin power inlet w/VDE cable 3-pin power inlet w/SAA cable 3-pin power inlet w/BS cable 3-pin power inlet w/screw terminal Mathematical function Report function External mass storage interface F degree display Summer/winter time DARWIN DAQ 32 is supplied with floppy disks Description

FDD Power Supply voltage Power Inlet & Power Cable

*: DC power operation only. However, when specifying this code, the dedicated AC adapter is attached as standard accessory. Power cable of AC adapter must be specified from the code of power inlet & power cable, however W can not be specified.

Subunit DS400/DS600

Model DS400 DS600 Type Power Supply Suffix Code Optional Code Description 4 slots subunit for inputs and alarm output 6 slots subunit for inputs and alarm output Always-00 100 VAC to 240 VAC 12 VDC to 28 VDC (always specify Y for the power cable) 3-pin power inlet w/UL, CSA cable 3-pin power inlet w/VDE cable 3-pin power inlet w/SAA cable 3-pin power inlet w/BS cable 3-pin power inlet w/screw terminal Dedicated connector for DC power operation w/o power cable

-00 -1 -2 D F R S W Y

Power Inlet & Power Cable

12

GS 04M01J01-11E

<<Contents>> <<Index>>

Input module

Model Code DU100-11 DU100-21 DU100-31 DU100-12 DU100-22 DU100-32 DU200-11 DU200-21 DU200-31 DU200-12 DU200-22 DU200-32 DU300-11 DU300-12 DU400-12 DU400-22 DU500-12 DU500-13 DU500-14 DU600-11 DU700-11 Description 10ch universal input module (DCV/TC/DI & RTD) 20ch universal input module (DCV/TC/DI & RTD) 30ch universal input module (DCV/TC/DI & RTD) 10ch universal input module (DCV/TC/DI & RTD) 20ch universal input module (DCV/TC/DI & RTD) 30ch universal input module (DCV/TC/DI & RTD) 10ch DCV/TC/DI input module 20ch DCV/TC/DI input module 30ch DCV/TC/DI input module 10ch DCV/TC/DI input module 20ch DCV/TC/DI input module 30ch DCV/TC/DI input module 10ch mA input module 10ch mA input module Power monitor module for single phase Power monitor module for 3 phase 10ch strain input module (120 ) 10ch strain input module (350 ) 10ch strain input module (External bridge box) 10ch pulse input module 10ch DI input module Terminal Screw Screw Screw Clamp Clamp Clamp Screw Screw Screw Clamp Clamp Clamp Screw Clamp Clamp Clamp Clamp Clamp NDIS Screw Screw

Other module

Model Code DT100-11 DT200-11 DT200-21 DT300-11 DT300-21 DT300-31 DT300-41 DT500-11 DT500-21 Description 2 alarm, 12 remote, fail/file end Screw terminal 4 alarm relay output (transfer contacts) Screw terminal 10 alarm relay output (make contacts) Screw terminal GP-IB interface module RS-232-C interface module RS-422-A/RS-485 interface module Ethernet interface module 10 channels, 1-5 V output retransmission module 2 channels, 4-20 mA output retransmission module

GS 04M01J01-11E

13

<<Contents>> <<Index>>

Accessories

Model Code DV100-011 DV100-012 DV200-000 DV200-001 DV200-002 DC200-005 DV200-010 DV200-020 DV200-050 DV200-100 DV200-200 DV200-300 DV200-400 DV200-500 DV250-001 DV300-011 DV300-012 DV300-101 DV300-102 DV300-251 DV300-252 DV400-011 DV400-012 DV400-015 DV400-071 DV450-001 DV500-001 DV500-002 DV500-003 DV500-004 Description Extension module Extension base unit Extension cable (0.5 m) Extension cable (1 m) Extension cable (2 m) Extension cable (5 m) Extension cable (10 m) Extension cable (20 m) Extension cable (50 m) Extension cable (100 m) Extension cable (200 m) Extension cable (300 m) Extension cable (400 m) Extension cable (500 m) Cable adapter Shunt resistor 10 for screw input terminal Shunt resistor 10 for clamped input terminal Shunt resistor 100 for screw input terminal Shunt resistor 100 for clamped input terminal Shunt resistor 250 for screw input terminal Shunt resistor 250 for clamped input terminal Rack mount kit (DA100 exp./DS400) for ANSI Rack mount kit (DA100 stand./DS600) for ANSI Rack mount kit (DC100 stand./exp) for ANSI Panel mount fittings for DC100 DIN-NDIS strain conversion cable AC adapter for DC operation model with UL, CSA cable AC adapter for DC operation model with VDE cable AC adapter for DC operation model with SAA cable AC adapter for DC operation model with BS cable

Package software

Model Code DP120-13 DP320-13 DP810- 1E VA510-0 -2 Description DARWIN DAQ 32 software (Windows 95/98/NT 4.0/2000) (comes standard) DARWIN DAQ 32 Plus software (Windows 95/98/NT 4.0/2000) (optional) InTouch for DARWIN 2000 for process monitoring software (Windows NT 4.0) (optional) DAQLOGGER for multi-channel data logging software (Windows 95/98/NT 4.0/2000) (optional)

14

GS 04M01J01-11E

<<Contents>> <<Index>>

Wiring Input Signal Lines (to Universal and DCV/TC/DI input modules)

Terminals

Screw type terminal b B + A

Clamp type terminal *There are no RTD input terminals on the DCV/TC/DI input module. A + B b CH1 CH3

DC voltage · TC · contact RTD*

CH1 CH2

CH2 CH4

CH10

CH10

CH9

Wiring Diagram

DC voltage input/DI input (contact) + + DC voltage input DC input + + DC current input Shunt resistor Note:For 4 to 20 mA input, shunt resistance value should be 250 ± 0.1% A

TC input +

RTD input b B

b B Compensation lead 10 * max./leadwire Three wire resistances should be approx. equal. *10 max. for Pt 100 and Pt 50 , 1 max. for Cu 10 .

A

Wiring Alarm Output SIgnal Lines (to DI/DO and Alarm output modules)

Terminals NO C NC DT100-11 Fail output (transfer contact) File Alarm output Remote control signal input NO C NC DT200-11 NO C DT200-21

Contact capacity: 250 VDC/0.1 A (with a resistor load) 250 VAC/2 A (with a resistor load) 30 VDC/2 A (with a resistor load) Fail output: becomes de-activated when an error is detected in the system.

1 Alarm output 2 (transfer contact)

1 2

Alarm output (make contact) 3 4 Alarm output (transfer contact) 10

1 Alarm output 2 (transfer contact)

GS 04M01J01-11E

15

<<Contents>> <<Index>>

Location and Location Number (Channel Number, Alarm Output Number, DI/DO Number)

The location numbers correspond to channel numbers for locations where the input module is connected, to alarm output numbers for locations where the alarm output module is connected, and to DI/DO numbers for locations where the DI/DO module is connected. In case of the DC100 Stand-alone type The location numbers correspond to the location of each module as shown in the figure below.

Module 3 (Location numbers:I31 to I40) Module 2 (Location numbers:I21 to I30) Module 1 (Location numbers:I11 to I20) Module 0 (Location numbers:I01 to I10)

16

GS 04M01J01-11E

<<Contents>> <<Index>>

I Name and Function of Each Part

DC100 Stand-alone type (DC100-1)

External mass storage interface Power switch Display Operation panel Handle Power connector (W:Screw terminal) (DC operation model: Dedicated connector)

CH1

CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10 b -/B +/A

CH1

CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10

b -/B +/A

FDD

Module slots

DC100 Expandable type (DC100-2)

Power switch Display Operation panel Handle External mass storage interface Dedicated cable connector Power connector (W:Screw terminal) (DC operation model: Dedicated connector)

CH1

CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10

b -/B +/A

CH1

CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10

b -/B +/A

FDD

Module slots

Subunit DS400

Module connector Lid covering the extension cable connector Status indicator Screw holes for module installation Power switch Function grounding terminal (below power switch) Feet Installation holes Power connector (W:Screw terminal) (DC operation model: Dedicated connector) Holes for fastening the feet

Switch to set the unit number

Subunit DS600

Installation holes

Module connector Lid covering the extension cable connector Screw holes for module installation Switch to set the unit number Power switch Function grounding terminal (below power switch) Feet Status indicator

Power connector (W:Screw terminal) (DC operation model: Dedicated connector) Holes for fastening the feet

GS 04M01J01-11E

17

<<Contents>> <<Index>>

I Dimensional Drawings

DC100 maine unit (stand-alone type/expandable type) Unit: mm

290

Back panal

20 115 145

338

Rack mount Fitting

10 480±1: JIS 482.6±1: ANSI/EIA 11.3 32 Front panel

6

9

221

6

101 71

56

50

146.1 39 44.5

JIS ANSI/EIA

44.5

If not specified, the tolerance is ±3%. However, in cases of less than 10 mm, the tolerance is ±0.3 mm.

7 299 150 24.5 37.5 44.5 50 310

18

GS 04M01J01-11E

<<Contents>> <<Index>>

Panel mount fittings for DC100

Panel cutout 363.5 Panel mount 8.75

unit: mm

256.5

2 to 11

18

4- 10 389 32

346 +2 0 Front panel

If not specified, the tolerance is ±3%. However, in cases of less than 10 mm, the tolerance is ±0.3 mm.

GS 04M01J01-11E

271.5

230 +2 0

19

<<Contents>> <<Index>>

DC100 Stand-alone type/Subunit DS600

Unit: mm

115 369 422 55 156 162 20

145 100 22

176 168

DC100 Expandable type/Subunit DS400

20

290

8

336 320

20

115 145

100 22

165

If not specified, the tolerance is ±3%. However, in cases of less than 10 mm, the tolerance is ±0.3 mm.

40

50

50

20

GS 04M01J01-11E

<<Contents>> <<Index>>

I Rack Mount Fitting (ANSI/EIA)

DS400 subunit

14.7 482.6 453.2

177 101.6

DS600 subunit

482.6 453.2

37.7

177 101.6

GS 04M01J01-11E

Subject to change withut notice. Printed in Japan, 012 (YG)

37.7

6.8

6.8

14.7

21